Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Quantum-Scalari40i80 I3 UserGuide

Download as pdf or txt
Download as pdf or txt
You are on page 1of 404

Users Guide

Quantum Scalar i40 and Scalar i80

6-66545-06 Rev A
Scalar i40 and Scalar i80 Users Guide, 6-66545-06 Rev A, June 2011, Product of U.S.A.
Quantum Corporation provides this publication as is without warranty of any kind, either express or
implied, including but not limited to the implied warranties of merchantability or fitness for a particular
purpose. Quantum Corporation may revise this publication from time to time without notice.

COPYRIGHT STATEMENT
Copyright 2011 by Quantum Corporation. All rights reserved.
Your right to copy this manual is limited by copyright law. Making copies or adaptations without prior
written authorization of Quantum Corporation is prohibited by law and constitutes a punishable
violation of the law.

TRADEMARK STATEMENT
Quantum, the Quantum logo, and Scalar are registered trademarks of Quantum Corporation, registered
in the U.S.A. and other countries.
Preserving the Worlds Most Important Data. Yours., StorageCare, and Vision are trademarks of
Quantum.
LTO and Ultrium are trademarks of HP, IBM, and Quantum in the U.S.A. and other countries. All other
trademarks are the property of their respective companies.
Specifications are subject to change without notice.

ii Quantum Scalar i40 and Scalar i80 Users Guide


Contents

Preface xxi
Worldwide End-User Product Warranty . . . . . . . . . . . . . . . xxviii

Chapter 1 Description 1
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Library Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Front Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Robotic System and Barcode Scanner . . . . . . . . . . . . . . . . . . . . 3
Magazines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Power Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
System Control Board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Tape Drives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Standard Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
User Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Partitions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Control Path Modification. . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Support for WORM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Licensable Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Capacity on Demand (COD) . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Advanced Reporting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Encryption Key Management . . . . . . . . . . . . . . . . . . . . . . . . . 15

Quantum Scalar i40 and Scalar i80 Users Guide iii


Contents

Chapter 2 Unpacking the Library 17

Chapter 3 Understanding the User Interface 21


Operator Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Operator Panel Layout and Functions . . . . . . . . . . . . . . . . . . . 22
Navigating and Editing on the Operator Panel . . . . . . . . . . . . 27
Web Client. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Tips . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Sorting Information In Tables . . . . . . . . . . . . . . . . . . . . . . . . . 29
Web Client Layout and Functions . . . . . . . . . . . . . . . . . . . . . . 29
Web Client Home Page . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
System Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Subsystem Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Menu Trees . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33

Chapter 4 Configuring the Library 37


Using the Setup Wizard. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Default Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Configuring Network Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Library Host Name . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
DHCP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
IP Addresses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Default Gateway, Subnet Mask, Network Prefix, and DNS
Addresses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Configuring SNMP Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Registering External Management Applications . . . . . . . . . . . 44
Enabling SNMP Versions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Enabling SNMP Authentication Traps . . . . . . . . . . . . . . . . . . . 46
Modifying the SNMP Community String . . . . . . . . . . . . . . . . . 47
Downloading the SNMP MIB. . . . . . . . . . . . . . . . . . . . . . . . . . 47
Setting the Date, Time, and Time Zone . . . . . . . . . . . . . . . . . . . . . . . . 48
Setting the Date and Time Manually. . . . . . . . . . . . . . . . . . . . 49
Setting the Date and Time Using the Network Time Protocol . 49
Setting the Time Zone. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Setting Daylight Saving Time . . . . . . . . . . . . . . . . . . . . . . . . . 51

iv Quantum Scalar i40 and Scalar i80 Users Guide


Contents

Working With Partitions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51


Automatically Creating Partitions . . . . . . . . . . . . . . . . . . . . . . 53
Manually Creating Partitions. . . . . . . . . . . . . . . . . . . . . . . . . . 54
Modifying Partitions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Deleting Partitions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Viewing the Current Partitions . . . . . . . . . . . . . . . . . . . . . . . . 58
Changing Access to Partitions. . . . . . . . . . . . . . . . . . . . . . . . . 59
Taking a Partition Online or Offline. . . . . . . . . . . . . . . . . . . . . 59
Configuring Cleaning Slots . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Configuring I/E Station Slots . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Configuring Tape Drive Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Configuring Control Paths . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Adding or Upgrading Licensable Features . . . . . . . . . . . . . . . . . . . . . . 69
About License Keys . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
Viewing Your License Keys . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
Viewing Installed Licenses. . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
Obtaining a License Key . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
Applying a License Key . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
Working With E-mail Notifications . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
Creating E-mail Notifications . . . . . . . . . . . . . . . . . . . . . . . . . 73
Modifying E-mail Notifications . . . . . . . . . . . . . . . . . . . . . . . . 74
Deleting E-mail Notifications . . . . . . . . . . . . . . . . . . . . . . . . . 75
Configuring the Library E-Mail Account. . . . . . . . . . . . . . . . . . . . . . . . 76
Setting Customer Contact Information . . . . . . . . . . . . . . . . . . . . . . . . 78
Configuring the Service Port . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
Working With Local User Accounts and Passwords . . . . . . . . . . . . . . . 79
Using the Web Client Default Administrator Account . . . . . . . 80
Privilege Levels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
Creating Local User Accounts on the Web Client . . . . . . . . . . 82
Modifying Local User Accounts on the Web Client . . . . . . . . . 83
Deleting Local User Accounts on the Web Client . . . . . . . . . . 84
Enabling and Creating Passwords on the Operator Panel . . . . 84
Disabling Passwords on the Operator Panel . . . . . . . . . . . . . . 87
Modifying Passwords on the Operator Panel . . . . . . . . . . . . . 87
Resetting Passwords on the Operator Panel . . . . . . . . . . . . . . 88
Working With LDAP User Accounts (Remote Authentication) . . . . . . . 88
Local Authentication vs. Remote Authentication . . . . . . . . . . 88
LDAP Server Guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89

Quantum Scalar i40 and Scalar i80 Users Guide v


Contents

Configuring Secure LDAP on the Library . . . . . . . . . . . . . . . . 90


Configuring LDAP on the Library . . . . . . . . . . . . . . . . . . . . . . 90
Testing LDAP Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
Configuring Kerberos . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
Generating the Kerberos Service Keytab File . . . . . . . . . . . . . . 96
Setting the Session Timeout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
Configuring System Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
Unload Assist . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
Logical Serial Number Addressing. . . . . . . . . . . . . . . . . . . . . . 99
Manual Cartridge Assignment . . . . . . . . . . . . . . . . . . . . . . . 100
SNMP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
SMI-S . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
Power Save . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
Configuring Security Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103
Network Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103
SSH Services . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
Internet Control Message Protocol (ICMP) . . . . . . . . . . . . . . 104
Remote Access Via Web Client . . . . . . . . . . . . . . . . . . . . . . . 105
Remote Service Login . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
SNMP V1/V2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
SSL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106
Saving and Restoring the Library Configuration . . . . . . . . . . . . . . . . 107
Saving the Library Configuration . . . . . . . . . . . . . . . . . . . . . 107
Restoring the Library Configuration . . . . . . . . . . . . . . . . . . . 108
Registering the Library. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109
Changing Operator Panel Home Screen View . . . . . . . . . . . . . . . . . . 109
Changing to Alternate Home Screen. . . . . . . . . . . . . . . . . . . 109
Returning to Default Home Screen . . . . . . . . . . . . . . . . . . . . 110

Chapter 5 Advanced Reporting 111


Advanced Reporting Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 112
Required Firmware . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113
Working with Control Path Failover (CPF) . . . . . . . . . . . . . . . . . . . . . 113
Prerequisites . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113
Configuring CPF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 114
Forcing CPF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 116
Using Advanced Reporting Reports . . . . . . . . . . . . . . . . . . . . . . . . . . 118

vi Quantum Scalar i40 and Scalar i80 Users Guide


Contents

Configuring the Drive Resource Utilization Report . . . . . . . . 119


Configuring the Media Integrity Analysis Report. . . . . . . . . . 121
Using Advanced Reporting Templates. . . . . . . . . . . . . . . . . . 123
Loading and Reloading Advanced Reporting Data . . . . . . . . 124
Deleting Advanced Reporting Data . . . . . . . . . . . . . . . . . . . . 125
Saving and E-mailing Advanced Reporting Data Files . . . . . . 125
Working with the Media Security Log . . . . . . . . . . . . . . . . . . . . . . . . 126
Configuring Media Security . . . . . . . . . . . . . . . . . . . . . . . . . 127
Viewing, Saving, and E-mailing Media Security Log . . . . . . . 128
Viewing the Media Usage Log . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 129
Automatically E-mailing Advanced Reporting Reports and Logs . . . . 130
Creating a Recipient . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 131
Modifying a Recipient . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 134
Deleting a Recipient . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 134

Chapter 6 Performing Library Operations 135


Logging In . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 136
Simultaneous Logins . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 136
Logging in for the First Time . . . . . . . . . . . . . . . . . . . . . . . . . 136
Logging in Using the Operator Panel . . . . . . . . . . . . . . . . . . 137
Logging in Via the Web Client . . . . . . . . . . . . . . . . . . . . . . . 137
Logging in When LDAP or Kerberos is Enabled . . . . . . . . . . . 138
Logging Out . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 138
Shutting Down, Restarting, Turning Off, and Removing Power. . . . . 139
Shutting Down the Library . . . . . . . . . . . . . . . . . . . . . . . . . . 140
Restarting the Library . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 142
Turning Off the Library . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 143
Completely Removing Library Power. . . . . . . . . . . . . . . . . . . 144
Emergency Power-off Procedure . . . . . . . . . . . . . . . . . . . . . . 144
Taking the Library Offline . . . . . . . . . . . . . . . . . . . . . . . . . . . 145
Unlocking and Opening the I/E Station . . . . . . . . . . . . . . . . . . . . . . . 145
Releasing Magazines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 148
Releasing Magazines via the User Interface. . . . . . . . . . . . . . 149
Releasing Magazines Manually . . . . . . . . . . . . . . . . . . . . . . . 150
Performing Media Operations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 151
Importing Tape Cartridges . . . . . . . . . . . . . . . . . . . . . . . . . . 152
Bulk Loading Tape Cartridges . . . . . . . . . . . . . . . . . . . . . . . . 155

Quantum Scalar i40 and Scalar i80 Users Guide vii


Contents

Moving Tape Cartridges . . . . . . . . . . . . . . . . . . . . . . . . . . . . 156


Exporting Tape Cartridges. . . . . . . . . . . . . . . . . . . . . . . . . . . 158
Loading Tape Drives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 160
Unloading Tape Drives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 161
Cleaning Tape Drives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 163
Valid Cleaning Cartridges . . . . . . . . . . . . . . . . . . . . . . . . . . . 164
About AutoClean . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 164
Enabling AutoClean . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 165
Importing Cleaning Cartridges . . . . . . . . . . . . . . . . . . . . . . . 165
Exporting Cleaning Cartridges . . . . . . . . . . . . . . . . . . . . . . . 167
Manually Cleaning Tape Drives . . . . . . . . . . . . . . . . . . . . . . . 169
Taking a Tape Drive Online or Offline . . . . . . . . . . . . . . . . . . . . . . . . 172

Chapter 7 Encryption Key Management 175


About the EKM License . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 176
Configuring Scalar Key Manager (SKM) on the Library . . . . . . . . . . . 176
Step 1: Upgrade Firmware . . . . . . . . . . . . . . . . . . . . . . . . . . 176
Step 2: Install the EKM License Key on the Library . . . . . . . . 176
Step 3: Install SKM on a Server or Servers . . . . . . . . . . . . . . . 177
Step 4: Configure Encryption Settings and Key Server Addresses
177
Step 5: Install TLS Communication Certificates on the Library. . .
179
Step 6: Run EKM Path Diagnostics . . . . . . . . . . . . . . . . . . . . 179
Step 7: Configure SKM Partitions and Generate Data Encryption
Keys . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 179
Step 8: Save the Library Configuration . . . . . . . . . . . . . . . . . 182
EKM Path Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 182
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 182
Failure Scenarios . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 183
Running Manual EKM Path Diagnostics . . . . . . . . . . . . . . . . 183
Enabling Automatic EKM Path Diagnostics . . . . . . . . . . . . . . 184
Viewing Tape Drive Encryption Settings . . . . . . . . . . . . . . . . . . . . . . 185
Scalar Key Manager Functions Available on the Library . . . . . . . . . . . 185
Installing TLS Certificates on the Library . . . . . . . . . . . . . . . . 186
Generating Data Encryption Keys . . . . . . . . . . . . . . . . . . . . . 191
Sharing Encrypted Tape Cartridges . . . . . . . . . . . . . . . . . . . . 195
Exporting Encryption Certificates . . . . . . . . . . . . . . . . . . . . . 197

viii Quantum Scalar i40 and Scalar i80 Users Guide


Contents

Importing Encryption Certificates . . . . . . . . . . . . . . . . . . . . . 198


Exporting Data Encryption Keys . . . . . . . . . . . . . . . . . . . . . . 199
Importing Data Encryption Keys . . . . . . . . . . . . . . . . . . . . . . 201
Accessing the SKM Server Logs . . . . . . . . . . . . . . . . . . . . . . . 202
Using the SKM Encryption Key Import Warning Log . . . . . . . 202

Chapter 8 Getting Information About the Library 205


Viewing Library Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 206
Viewing System Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 206
Viewing the Location of the Robot . . . . . . . . . . . . . . . . . . . . . . . . . . 207
Viewing the Library Configuration Report . . . . . . . . . . . . . . . . . . . . . 210
Saving and E-mailing the Library Configuration Record. . . . . . . . . . . 212
Saving the Configuration Record . . . . . . . . . . . . . . . . . . . . . 213
E-mailing the Configuration Record . . . . . . . . . . . . . . . . . . . 213
Viewing the Network Settings Report . . . . . . . . . . . . . . . . . . . . . . . . 214
Viewing the Logged in Users Report . . . . . . . . . . . . . . . . . . . . . . . . . 215
Viewing the All Slots Report . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 215
Viewing, Saving, and E-mailing Library Logs . . . . . . . . . . . . . . . . . . . 217
Cleaning Log. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 217
Diagnostic Tickets Log . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 218
Media Security Log (with Advanced Reporting License) . . . . 219
Media Usage Log (with Advanced Reporting License) . . . . . . 219
SKM Encryption Key Import Warning Log (with EKM License) . .
219
Tape Drive Log . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 220
Viewing Library Information on the Operator Panel . . . . . . . . . . . . . 221
Viewing Partition Information. . . . . . . . . . . . . . . . . . . . . . . . 221
Viewing Tape Drive Information . . . . . . . . . . . . . . . . . . . . . . 222
Viewing Network Settings. . . . . . . . . . . . . . . . . . . . . . . . . . . 222
Viewing the Date, Time, and Time Zone . . . . . . . . . . . . . . . . 223
Viewing Licenses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 223
Using Advanced Reporting Features . . . . . . . . . . . . . . . . . . . . . . . . . 223
Viewing the Open Source License Agreement . . . . . . . . . . . . . . . . . . 223
Viewing the Copyright Statement . . . . . . . . . . . . . . . . . . . . . . . . . . . 224

Quantum Scalar i40 and Scalar i80 Users Guide ix


Contents

Chapter 9 Installing, Removing, and Replacing Components 225


Taking ESD Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 226
Connecting Library Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 227
Installing the Rack Mount Kit (Rail Kit) . . . . . . . . . . . . . . . . . . . . . . . 229
Supported Rack Types. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 229
Space Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 230
Tools Required . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 230
Rack Mount Kit Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . 230
Installing the Rack Mount Shelves. . . . . . . . . . . . . . . . . . . . . 232
Installing the Library In a Rack. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 241
Removing the Library From a Rack . . . . . . . . . . . . . . . . . . . . . . . . . . 243
Installing the Library in a Desktop Kit . . . . . . . . . . . . . . . . . . . . . . . . 244
Kit Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 246
Tools Required . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 246
Space Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 247
Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 247
Removing the Library from a Desktop Kit . . . . . . . . . . . . . . . . . . . . . 252
Removing and Replacing the Front Bezel. . . . . . . . . . . . . . . . . . . . . . 253
Required Tools . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 253
Bezel Replacement Kit Contents . . . . . . . . . . . . . . . . . . . . . . 253
Bezel Replacement Procedure . . . . . . . . . . . . . . . . . . . . . . . . 253
Replacing the Chassis . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 258
Required Tools . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 258
Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 259
Removing and Installing a Filler Plate . . . . . . . . . . . . . . . . . . . . . . . . 269
Removing and Installing a Tape Drive Filler Plate . . . . . . . . . 269
Removing and Installing a Power Supply Filler Plate . . . . . . . 269
Removing and Replacing a Magazine . . . . . . . . . . . . . . . . . . . . . . . . 271
Required Tools . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 271
Magazine Replacement Kit Contents . . . . . . . . . . . . . . . . . . 271
Creating a Backup Map of Cartridge Locations . . . . . . . . . . . 271
Removing the Magazine from the Library . . . . . . . . . . . . . . . 272
Installing the Magazine. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 273
Removing and Installing a Power Supply. . . . . . . . . . . . . . . . . . . . . . 276
Replacing a Power Supply in a Single-Power-Supply System
(Scalar i40 and Scalar i80). . . . . . . . . . . . . . . . . . . . . . . . . . . 277

x Quantum Scalar i40 and Scalar i80 Users Guide


Contents

Adding or Replacing a Redundant Power Supply on the Scalar i80


278
Removing and Replacing the System Control Board . . . . . . . . . . . . . 279
Replacing the System Control Board . . . . . . . . . . . . . . . . . . . 279
Installing Library Firmware . . . . . . . . . . . . . . . . . . . . . . . . . . 281
Restoring the Library Configuration . . . . . . . . . . . . . . . . . . . 283
Manually Reconfiguring the Library . . . . . . . . . . . . . . . . . . . 284
Removing and Replacing a Tape Drive. . . . . . . . . . . . . . . . . . . . . . . . 286
Preparing Partitions and Control Paths . . . . . . . . . . . . . . . . . 287
Removing a Tape Drive from the Library . . . . . . . . . . . . . . . . 288
Installing a Tape Drive. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 288
Packaging the Library for Moving or Shipping. . . . . . . . . . . . . . . . . . 292
Packaging Kit Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 292
Creating a Backup Map of Cartridge Locations . . . . . . . . . . . 292
Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 293
Replacing the Y-tray with Robot . . . . . . . . . . . . . . . . . . . . . . . . . . . . 298

Chapter 10 Updating Firmware 299


Updating Library Firmware . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 299
Updating and Autoleveling Tape Drive Firmware . . . . . . . . . . . . . . . 304
About Tape Drive Firmware Autoleveling . . . . . . . . . . . . . . . 305
Uploading Tape Drive Firmware Used in Autoleveling. . . . . . 306
Deleting Tape Drive Firmware Used in Autoleveling . . . . . . . 308
Initiating Tape Drive Firmware Autoleveling . . . . . . . . . . . . . 310

Chapter 11 Troubleshooting 311


About Diagnostic Tickets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 312
Viewing, Closing, and Resolving Diagnostic Tickets . . . . . . . 313
Closing Diagnostic Tickets Automatically . . . . . . . . . . . . . . . 316
Capturing Snapshots of Library Information . . . . . . . . . . . . . . . . . . . 317
Troubleshooting Library Not Ready Messages . . . . . . . . . . . . . . . . 318
Not Ready Messages on the Operator Panel . . . . . . . . . . . 318
Not Ready Messages on the Web Client . . . . . . . . . . . . . . 318
Retrieving Tape Drive Logs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 320
Interpreting LEDs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 320

Quantum Scalar i40 and Scalar i80 Users Guide xi


Contents

Front Panel LEDs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 321


System Control Board LEDs . . . . . . . . . . . . . . . . . . . . . . . . . . 322
Tape Drive/Sled LEDs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 323
Power Supply LED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 324
Running the Installation and Verification Test (IVT). . . . . . . . . . . . . . 325
Running the IVT Diagnostic Subtests Individually Robotics, Tape Drive,
and Magazine Tests. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 327
Running the Random Move Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . 329
Performing Library Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 330
Resetting a Tape Drive . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 331
Robotics Get/Put Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 332
Resetting Factory Defaults . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 333

Chapter 12 Working With Cartridges and Barcodes 335


Handling Tape Cartridges Properly . . . . . . . . . . . . . . . . . . . . . . . . . . 336
Write-Protecting Tape Cartridges. . . . . . . . . . . . . . . . . . . . . . . . . . . . 337
Barcode Label Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 337
Supported Barcode Formats . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 338
Installing Barcode Labels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 339

Appendix A Specifications 341


Physical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 341
Capacity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 342
Environmental Specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 343
Air Clearance Requirements. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 343
Library Power Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 344
Power Consumption and Heat Output . . . . . . . . . . . . . . . . . . . . . . . 345
Communication Interfaces. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 346
Supported Tape Drives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 346
Supported Media. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 347

xii Quantum Scalar i40 and Scalar i80 Users Guide


Contents

Supported Internet Browsers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 347


Supported Operating Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 348

Appendix B Tape Alert Flag Descriptions 349

Appendix C Disposal of Electrical and Electronic Equipment 359

Glossary 361

Index 371

Quantum Scalar i40 and Scalar i80 Users Guide xiii


Contents

xiv Quantum Scalar i40 and Scalar i80 Users Guide


Figures

Figure 1 Front Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2


Figure 2 Scalar i40 Internal Layout and Magazine Slot Location
Coordinates6
Figure 3 Scalar i80 Internal Layout and Magazine Slot Location
Coordinates7
Figure 4 Scalar i40 Back Panel Components . . . . . . . . . . . . . . . . . . 10
Figure 5 Scalar i80 Back Panel Components . . . . . . . . . . . . . . . . . . 11
Figure 6 Packaging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Figure 7 Removing the Robot Restraint . . . . . . . . . . . . . . . . . . . . . 20
Figure 8 Operator Panel User Interface - Home Screen . . . . . . . . . . 22
Figure 9 Operator Panel User Interface - Alternate Home Screen . . 23
Figure 10 Using the Buttons to Set the Date and Time. . . . . . . . . . . 28
Figure 11 Web Client User Interface - Home Page . . . . . . . . . . . . . . 30
Figure 12 Operator Panel Menus . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Figure 13 Web Client Menus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Figure 14 LDAP Setup Example. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
Figure 15 Setup - Drive Settings Screen . . . . . . . . . . . . . . . . . . . . . 114
Figure 16 Setup - Control Path Screen . . . . . . . . . . . . . . . . . . . . . . 115

Quantum Scalar i40 and Scalar i80 Users Guide xv


Tables

Figure 17 Tools - Drive Operations Screen for CPF . . . . . . . . . . . . . 116


Figure 18 Force CPF Screen. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 117
Figure 19 Template and Report Data Functions . . . . . . . . . . . . . . . 123
Figure 20 Report Data Buttons . . . . . . . . . . . . . . . . . . . . . . . . . . . . 125
Figure 21 Saving and E-mailing the Report Data . . . . . . . . . . . . . . 126
Figure 22 Shutdown in Progress Message . . . . . . . . . . . . . . . . . . . 140
Figure 23 Ready to Power Down Message . . . . . . . . . . . . . . . . . . . 141
Figure 24 Ready to Power Down Message . . . . . . . . . . . . . . . . . . . 141
Figure 25 Series of Restart Messages . . . . . . . . . . . . . . . . . . . . . . . 142
Figure 26 I/E Station Unlocked Message. . . . . . . . . . . . . . . . . . . . . 146
Figure 27 I/E Station Locked Message . . . . . . . . . . . . . . . . . . . . . . 147
Figure 28 Magazine Unlocked Message . . . . . . . . . . . . . . . . . . . . . 149
Figure 29 Magazine Locked Timer Message . . . . . . . . . . . . . . . . . . 149
Figure 30 Magazine Release Latch Access . . . . . . . . . . . . . . . . . . . 151
Figure 31 Configuring Encryption Settings and Key Server Addresses .
178
Figure 32 Configuring Partition Encryption . . . . . . . . . . . . . . . . . . 180
Figure 33 Enabling Automatic EKM Path Diagnostics. . . . . . . . . . . 184
Figure 34 Checking and Installing TLS Certificates . . . . . . . . . . . . . 187
Figure 35 Accessing the Encryption Partition Configuration Screen 193
Figure 36 Changing Encryption Method to Allow Application Managed
194
Figure 37 Changing Encryption Method Back to Enable Library
Managed195
Figure 38 Exporting Encryption Certificates . . . . . . . . . . . . . . . . . . 197
Figure 39 Importing Encryption Certificates . . . . . . . . . . . . . . . . . . 198
Figure 40 Exporting Encryption Keys . . . . . . . . . . . . . . . . . . . . . . . 199
Figure 41 Importing Data Encryption Keys . . . . . . . . . . . . . . . . . . . 201
Figure 42 Connection Locations . . . . . . . . . . . . . . . . . . . . . . . . . . . 228
Figure 43 Rack Mount Shelf Depth Requirements . . . . . . . . . . . . . 233

xvi Quantum Scalar i40 and Scalar i80 Users Guide


Tables

Figure 44 Assembling the Left and Right Rack Mount Shelves . . . . 234
Figure 45 Rail Adapter Types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 235
Figure 46 Assembling the Left-Hand Rack Mount Shelf . . . . . . . . . 236
Figure 47 Installing the Rack Mount Shelves . . . . . . . . . . . . . . . . . 238
Figure 48 Tightening the Rack Mount Shelves . . . . . . . . . . . . . . . . 239
Figure 49 Location for Installing the Clip Nut or Cage Nut . . . . . . . 241
Figure 50 Magazine Release Latch Access Holes . . . . . . . . . . . . . . . 242
Figure 51 Securing the Scalar i40 and Scalar i80 in the Rack . . . . . 243
Figure 52 Desktop Kit, Scalar i40 and Scalar i80. . . . . . . . . . . . . . . 245
Figure 53 Magazine Release Latch Access Holes . . . . . . . . . . . . . . . 248
Figure 54 Location of Rubber Feet on Bottom of Library . . . . . . . . 249
Figure 55 Installing side panels . . . . . . . . . . . . . . . . . . . . . . . . . . . 251
Figure 56 Installing Top Cover . . . . . . . . . . . . . . . . . . . . . . . . . . . . 252
Figure 57 Bezel Screw Locations on Bottom of Library . . . . . . . . . . 255
Figure 58 Bezel Screws . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 256
Figure 59 Scalar i80 Pull/Push Locations . . . . . . . . . . . . . . . . . . . . . 257
Figure 60 Components to Remove . . . . . . . . . . . . . . . . . . . . . . . . . 261
Figure 61 Removing the Y-tray Restraints. . . . . . . . . . . . . . . . . . . . 262
Figure 62 Restraining the Y-tray . . . . . . . . . . . . . . . . . . . . . . . . . . . 264
Figure 63 Reinstalled Components . . . . . . . . . . . . . . . . . . . . . . . . . 267
Figure 64 Filler Plates Installed . . . . . . . . . . . . . . . . . . . . . . . . . . . . 270
Figure 65 Magazine Release Latch Access Holes . . . . . . . . . . . . . . . 273
Figure 66 Proper Orientation (Right-Side Magazine) . . . . . . . . . . . 274
Figure 67 Removing/Installing the Magazine Bezel. . . . . . . . . . . . . 275
Figure 68 Single Power Supply System . . . . . . . . . . . . . . . . . . . . . . 276
Figure 69 Redundant Power Supply System . . . . . . . . . . . . . . . . . . 277
Figure 70 Ethernet Port Locations on the SCB . . . . . . . . . . . . . . . . 281
Figure 71 Acceptable Installation Locations for Full-Height Tape Drives
289

Quantum Scalar i40 and Scalar i80 Users Guide xvii


Tables

Figure 72 Installing a Tape Drive . . . . . . . . . . . . . . . . . . . . . . . . . . 290


Figure 73 Restraining the Y-tray . . . . . . . . . . . . . . . . . . . . . . . . . . . 295
Figure 74 Scalar i40 Packaging . . . . . . . . . . . . . . . . . . . . . . . . . . . . 296
Figure 75 Scalar i80 Packaging . . . . . . . . . . . . . . . . . . . . . . . . . . . . 297
Figure 76 Tools - Update Library Firmware Screen . . . . . . . . . . . . . 301
Figure 77 Front Panel LEDs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 321
Figure 78 System Control Board LEDs. . . . . . . . . . . . . . . . . . . . . . . 322
Figure 79 Fibre Channel Tape Drive LEDs . . . . . . . . . . . . . . . . . . . . 324
Figure 80 Power Supply LED. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 325
Figure 81 Barcode Label Orientation . . . . . . . . . . . . . . . . . . . . . . . 340

xviii Quantum Scalar i40 and Scalar i80 Users Guide


Tables

Table 1 Front Panel Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2


Table 2 Operator Panel Functions . . . . . . . . . . . . . . . . . . . . . . . . . 24
Table 3 Web Client Screen Elements . . . . . . . . . . . . . . . . . . . . . . . 31
Table 4 Scalar i80 I/E Slot Configuration . . . . . . . . . . . . . . . . . . . . 64
Table 5 Fibre Channel Tape Drive Configurable Settings . . . . . . . . 66
Table 6 Encryption Methods . . . . . . . . . . . . . . . . . . . . . . . . . . . . 181
Table 7 Base Library . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 341
Table 8 Library Installed in a Desktop Kit . . . . . . . . . . . . . . . . . . 342
Table 9 Tape Alert Flag Severity Codes . . . . . . . . . . . . . . . . . . . . 349
Table 10 Tape Drive Tape Alert Flag Descriptions . . . . . . . . . . . . . 350

Quantum Scalar i40 and Scalar i80 Users Guide xix


Tables

xx Quantum Scalar i40 and Scalar i80 Users Guide


Preface

This manual introduces the Quantum Scalar i40 and Scalar i80 and
discusses:
System operations
Configuration
Web and operator panel interface
Installation and replacement
Basic troubleshooting

Audience This manual is written for Scalar i40 and Scalar i80 operators, system
administrators, and field service engineers.

Document Organization Following is a brief description of chapter contents.


Chapter 1, Description provides a physical description of the library,
its components, and major features.
Chapter 2, Unpacking the Library describes how to prepare a space
and unpack the library.
Chapter 3, Understanding the User Interface describes the
appearance and function of the operator panel and Web client.

Quantum Scalar i40 and Scalar i80 Users Guide xxi


Preface

Chapter 4, Configuring the Library provides instruction and


description for all the configurable features of the library.
Chapter 5, Advanced Reporting describes the features available with
the Advanced Reporting license.
Chapter 6, Performing Library Operations explains how to run the
library from the operator panel and Web client.
Chapter 7, Encryption Key Management describes the features
available with the Encryption Key Management (EKM) license.
Chapter 8, Getting Information About the Library describes all of
the reporting features on the library.
Chapter 10, Updating Firmware describes how to upgrade library
firmware and install and autolevel tape drive firmware.
Chapter 9, Installing, Removing, and Replacing Components
provides detailed instruction on how to install, remove, and replace
all the physical components of the library.
Chapter 11, Troubleshooting describes the librarys troubleshooting
tools, including diagnostic tickets, LEDs, and tests.
Chapter 12, Working With Cartridges and Barcodes provides basic
information about how to label and care for media used in the
library.
Appendix A, Specifications provides physical, environmental, power,
and other specifications about the library, tape drives, and media.
Appendix B, Tape Alert Flag Descriptions lists all the Tape Alerts you
may encounter in a diagnostic ticket.
Appendix C, Disposal of Electrical and Electronic Equipment
provides information on disposing and recycling.
The document concludes with a glossary and index.

xxii Quantum Scalar i40 and Scalar i80 Users Guide


Preface

Notational Conventions This manual uses the following conventions:

Convention Example

File and directory names, menu /data/upload


commands, button names, and
window names are shown in bold
font.

Menu names separated by arrows Utilities > Firmware


indicate a sequence of menus to be
navigated.

The following formats indicate important information:

Note: Note emphasizes important information related to the main


topic.

Caution: Caution indicates potential hazards to equipment or data.

WARNING: Warning indicates potential hazards to personal safety.

Right side of the system Refers to the right side as you face the
component being described.
Left side of the system Refers to the left side as you face the
component being described.

Product Safety Quantum will not be held liable for damage arising from unauthorized
Statements use of the product. The user assumes all risk in this aspect.
This unit is engineered and manufactured to meet all safety and
regulatory requirements. Be aware that improper use may result in
bodily injury, damage to the equipment, or interference with other
equipment.
The System, Safety, and Regulatory Information Guide is located on the
Scalar i40 and Scalar i80 documentation and training CD.

Quantum Scalar i40 and Scalar i80 Users Guide xxiii


Preface

WARNING: Before operating this product, read all instructions and


warnings in this document and in the System, Safety, and
Regulatory Information Guide.

xxiv Quantum Scalar i40 and Scalar i80 Users Guide


Preface

Related Documents The following Quantum documents are also available for Scalar i40 and
Scalar i80 systems:

Document
No. Document Title

6-66546-xx Scalar i40 and Scalar i80 Quick Start Guide


6-66547-xx Scalar i40 and Scalar i80 Release Notes
6-00618-xx System, Safety, and Regulatory Information
6-66773-xx Scalar i40 and Scalar i80 Basic SNMP Reference
Guide
6-00423-xx Quantum Intelligent Libraries SCSI Reference Guide
6-01317-xx Quantum Intelligent Libraries SMI-S Reference
Guide
6-66531-xx Scalar Key Manager Users Guide

For the most up to date product information and documentation, see:


http://www.quantum.com/ServiceandSupport/Index.aspx

Quantum Scalar i40 and Scalar i80 Users Guide xxv


Preface

SCSI-2 Specification
The SCSI-2 communications specification is the proposed American
National Standard for information systems, dated March 9, 1990.
Copies may be obtained from:
Global Engineering Documents
15 Inverness Way, East
Englewood, CO 80112
(800) 854-7179 or (303) 397-2740

Contacts Quantum company contacts are listed below.

Quantum Corporate Headquarters


To order documentation on the Scalar i40 or Scalar i80 or other
products, contact:
Quantum Corporation (Corporate Headquarters)
1650 Technology Drive, Suite 700
San Jose, CA 95110-1382

Technical Publications
To comment on existing documentation send e-mail to:
doc-comments@quantum.com

Quantum Home Page


Visit the Quantum home page at:
http://www.quantum.com

xxvi Quantum Scalar i40 and Scalar i80 Users Guide


Preface

Getting More StorageCare, Quantums comprehensive service approach, leverages


Information or Help advanced data access and diagnostics technologies with cross-
environment, multi-vendor expertise to resolve backup issues faster and
at lower cost.
Accelerate service issue resolution with these exclusive Quantum
StorageCare services:
Service and Support Web site Register products, license
software, browse Quantum Learning courses, check backup
software and operating system support, and locate manuals, FAQs,
firmware downloads, product updates and more in one convenient
location. Benefit today at:
http://www.quantum.com/ServiceandSupport/Index.aspx
Telephone Support Find contact information for your location at:
http://www.quantum.com/ServiceandSupport/Contacts/
ProductSelect/Index.aspx
eSupport Submit online service requests, update contact
information, add attachments, and receive status updates via
e-mail. Online Service accounts are free from Quantum. That
account can also be used to access Quantums Knowledge Base, a
comprehensive repository of product support information. Sign up
today at:
http://www.quantum.com/osr
StorageCare Guardian Securely links Quantum hardware and the
diagnostic data from the surrounding storage ecosystem to
Quantum's Global Services Team for faster, more precise root cause
diagnosis. StorageCare Guardian is simple to set up through the
internet and provides secure, two-way communications with
Quantums Secure Service Center. More StorageCare Guardian
information can be found at:
http://www.quantum.com/ServiceandSupport/Services/
GuardianInformation/Index.aspx

Quantum Scalar i40 and Scalar i80 Users Guide xxvii


Preface

Quantum Vision Quantum Vision software enables simplified


monitoring and reporting of Quantum DXi disk-based systems and
Scalar tape libraries. Especially powerful for customers with multiple
disk systems or a combination of Quantum disk and tape libraries
working together, Vision puts you in control to make better
decisions that will prevent issues, manage resources efficiently, and
improve uptime. Vision can aggregate data across multiple systems,
provide system status, and display trend information all from a
single console. More quantum Vision information can be found at:
http://www.quantum.com/Products/Software/QuantumVision/
Index.aspx
Latest Library Firmware - You can view a listing of the latest
version of library firmware on the following Web site:
http://www.quantum.com/ServiceandSupport/
SoftwareandDocumentationDownloads/SI40/Index.aspx and click
the Firmware tab.
If your library has an internet connection, you can log into your
library to view the latest firmware version available. Click Tools >
Update Library Firmware. The screen displays the firmware
currently loaded on your library and the latest available firmware.
Follow instructions in Chapter 10, Updating Firmware to upgrade
Firmware. For further assistance, or if training is desired, contact the
Quantum Customer Support Center.

Worldwide End-User For more information on the Quantum Worldwide End-User Standard
Product Warranty Limited Product Warranty:
http://www.quantum.com/pdf/QuantumWarranty.pdf

xxviii Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 1
Description

This chapter covers the layout and basic functionality of the library,
including:
Overview
Library Components
Standard Features
Licensable Features

Overview
The Scalar i40 and i80 tape libraries automate the retrieval, storage, and
management of tape cartridges. Tape cartridges are stored in the library
and mounted and dismounted from tape drives using firmware running
on the library or software running on the host systems.
See Appendix A, Specifications for library capacity and a list of tape
drives and media supported by the Scalar i40 and Scalar i80 libraries.

Quantum Scalar i40 and Scalar i80 Users Guide 1


Chapter 1: Description
Library Components

Library Components

Front Panel Figure 1 illustrates the features of the operator panel. The picture shows
the Scalar i40, but the features are the same on the Scalar i80. These
features are described in Table 1.

Figure 1 Front Panel

Operator panel screen

Navigation/selection buttons

Ticket indicator LED


Power-on LED
Power button

Table 1 Front Panel Features


Feature Description

Operator The operator panel displays library status


panel screen information and allows you to access the library
menus. These menus allow you to view or change
the library settings and run diagnostic tests. For
more information, see Operator Panel on page 21.

2 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 1: Description
Library Components

Feature Description

Four naviga- These buttons, in combination with the operator


tion/selection panel display, are used to scroll through screens and
buttons select options or commands. The functionality of
these buttons changes depending on the currently
displayed operator panel screen.

Ticket indica- Indicates whether a diagnostic ticket exists on the


tor LED library. See Front Panel LEDs on page 321 and About
Diagnostic Tickets on page 312 for more informa-
tion.

Power-on LED Indicates whether library power is on or off. See


Front Panel LEDs on page 321 for more information.

Power button Turns the library on or off.


Turning off the library using the power button turns
off the robot and operator panel, but power still
runs to the power supplies. See Shutting Down,
Restarting, Turning Off, and Removing Power on
page 139 for instructions on how to shut down the
library safely.

Robotic System and The robotic system identifies and moves the cartridges between the
Barcode Scanner storage slots, tape drives, and the I/E station. The robotic arm (picker)
has picker fingers that enable it to grab tape cartridges and move them
into and out of slots and tape drives.
A barcode scanner is attached to the librarys robotic hand. This barcode
scanner automatically identifies the slots and cartridges in the library, if
the cartridges are fitted with acceptable barcode labels.
Each tape cartridge must contain a unique, matching-readable barcode
that the barcode scanner reads during the inventory process. During the
inventory process, the barcode scanner reads the barcode labels on the
tape cartridges and empty slots to identify the types of tape cartridges
that are installed in the library.

Quantum Scalar i40 and Scalar i80 Users Guide 3


Chapter 1: Description
Library Components

Tape cartridges cannot have duplicate barcode labels. This barcode


identifies the cartridge. The library stores the physical location of the
tape cartridge in an inventory database. All library or host requests
typically reference the location of the tape cartridges based on this
barcode number. Barcode labels are mandatory and must adhere to
specific standards. For more information on barcodes, see Chapter 12,
Working With Cartridges and Barcodes.
Robots can only be replaced by a Quantum Support technician.

Magazines Magazines are removable and contain storage and import/export


station slots for cartridges. Each magazine has 20 slots, arranged in four
columns of five slots each. The Scalar i40 contains two magazines; the
Scalar i80 contains four. The right magazines provide up to five slots
each for use as an import/export (I/E) station. For more information on
I/E stations, see Configuring I/E Station Slots on page 63.

Note: Cartridges are gently restrained within the magazine by a


detent found on the left side of each individual magazine bin
slot. To manually remove a cartridge, pull a cartridge from the
front or push on the cartridge from the rear of the magazine
via an access hole. Be gentle to avoid any bending of the top
magazine cover sheet metal.

The library will run if one or more magazines is open or removed;


however, it runs at reduced speed. The library will not move a cartridge
to an open or removed magazine, but it will move a cartridge to any of
the other installed magazines.
You can open the magazines using library software or manually. For
information, see Releasing Magazines on page 148.
For information on removing and replacing magazines, see Removing
and Replacing a Magazine on page 271.

4 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 1: Description
Library Components

Magazine Slot Location Coordinates


Each slot in the installed magazine is numbered with location
coordinates. The library location coordinate contains three digits as
follows: [Magazine],[Column],[Slot]. Figure 2 and Figure 3 show the
magazines and list all of the location coordinates.
Magazine Library magazine level is represented by the first digit
of a library coordinate. In a Scalar i40, there is only one level of
magazine. The coordinate is always zero. In a Scalar i80 library, the
bottom magazines are indicated by a zero; the top magazines are
indicated by the number 1.
Column A storage column is a group of slots arranged vertically
in the library. Columns are represented by the second digit of a
library coordinate. Columns are identified relative to the front left of
the library. The column in the front left of the library is number 1.
The column numbering continues around the library in a clockwise
direction. The I/E station column is always number 8.
Slot Slots (both storage and I/E station) are represented by the
third digit of the library location coordinate. Within each magazine
column, slots are numbered from 1 to 5, starting at the top of the
magazine.

Quantum Scalar i40 and Scalar i80 Users Guide 5


Chapter 1: Description
Library Components

Figure 2 Scalar i40 Internal Tape Drives Robot on Y-tray


Layout and Magazine Slot
Location Coordinates

Right magazine

Left magazine

Left Magazine Right Magazine

0,1,1 0,2,1 0,3,1 0,4,1 0,5,1 0,6,1 0,7,1 0,8,1

0,1,2 0,2,2 0,3,2 0,4,2 0,5,2 0,6,2 0,7,2 0,8,2

0,1,3 0,2,3 0,3,3 0,4,3 0,5,3 0,6,3 0,7,3 0,8,3

0,1,4 0,2,4 0,3,4 0,4,4 0,5,4 0,6,4 0,7,4 0,8,4

0,1,5 0,2,5 0,3,5 0,4,5 0,5,5 0,6,5 0,7,5 0,8,5

6 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 1: Description
Library Components

Figure 3 Scalar i80 Internal


Layout and Magazine Slot Robot on Y-tray
Location Coordinates
Top right
magazine

Top left Bottom right


magazine magazine

Bottom left
magazine

Top Left Magazine Top Right Magazine

1,1,1 1,2,1 1,3,1 1,4,1 1,5,1 1,6,1 1,7,1 1,8,1

1,1,2 1,2,2 1,3,2 1,4,2 1,5,2 1,6,2 1,7,2 1,8,2

1,1,3 1,2,3 1,3,3 1,4,3 1,5,3 1,6,3 1,7,3 1,8,3

1,1,4 1,2,4 1,3,4 1,4,4 1,5,4 1,6,4 1,7,4 1,8,4

1,1,5 1,2,5 1,3,5 1,4,5 1,5,5 1,6,5 1,7,5 1,8,5

Bottom Left Magazine Bottom Right Magazine

0,1,1 0,2,1 0,3,1 0,4,1 0,5,1 0,6,1 0,7,1 0,8,1

0,1,2 0,2,2 0,3,2 0,4,2 0,5,2 0,6,2 0,7,2 0,8,2

0,1,3 0,2,3 0,3,3 0,4,3 0,5,3 0,6,3 0,7,3 0,8,3

0,1,4 0,2,4 0,3,4 0,4,4 0,5,4 0,6,4 0,7,4 0,8,4

0,1,5 0,2,5 0,3,5 0,4,5 0,5,5 0,6,5 0,7,5 0,8,5

Quantum Scalar i40 and Scalar i80 Users Guide 7


Chapter 1: Description
Library Components

Power Supply The Scalar i40 and Scalar i80 libraries support single power
configurations consisting of a single AC line input and single DC power
supply. The Scalar i80 library supports a redundant power configuration
consisting of a dual AC line input and dual DC power supplies.
If you have a Scalar i80 and are only using one power supply, the power
supply should be installed in the upper power supply slot, and a filler
plate must cover the empty power supply slot (see Figure 5 on page 11).
If you are using redundant power, you can hot add or hot swap a power
supply (power to the library remains on while you add or exchange the
hardware).
The Scalar i40 power supply cannot be installed in a Scalar i80. However,
the Scalar i80 power supply works in either the Scalar i40 or the
Scalar i80.

Warning: The power outlet must be available near the library and
must be easily accessible.

The power system consists of the following components:


Power supply
AC power cord
The power supply has one status LED. For more information, see Power
Supply LED on page 324.
For information on removing and replacing power supplies, see
Removing and Installing a Power Supply on page 276.

System Control Board The system control board (SCB) contains the library firmware, all
configurable settings, license keys, and SKM TLS certificates. It manages
the entire library, including the operator panel and robot, and is
responsible for running system tests to ensure that the library is
functioning properly. The SCB has two Ethernet ports:
Left port For remote management (Web client)
Right port For service only. In rare cases, you may need to change
the IP address of the port if it conflicts with your library IP address
(see Configuring the Service Port on page 78).
See Figure 4 on page 10 and Figure 5 on page 11 for port locations.

8 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 1: Description
Library Components

The SCB contains one LED, in addition to two LEDs on each Ethernet
port (for a total of 5 LEDs). For more information, see System Control
Board LEDs on page 322.
For information on removing and replacing the SCB, see Removing and
Replacing the System Control Board on page 279.

Tape Drives Every library configuration must contain at least one tape drive.
See Appendix A, Specifications for a list of tape drives and media
supported by the Scalar i40 and Scalar i80 libraries.
The library supports mixing different tape drive types within the library
and within partitions. For information on how to do this, see Working
With Partitions on page 51.
Tape drives are installed into tape drive slots in the rear of the library. If a
tape drive slot is empty, a filler plate must cover the empty slot (see
Figure 5 on page 11).

Caution: Filler plates are required to maintain proper library cooling.


Do not run the library with uncovered slots.

SAS tape drives have one status LED. Fibre Channel tape drives contain a
status and a link LED. For more information on tape drive LEDs, see Tape
Drive/Sled LEDs on page 323.
All tape drives contain only one cable connector.
For information on removing and replacing tape drives, see Removing
and Replacing a Tape Drive on page 286.

Installed Tape Drive Location Coordinates


Installed tape drives have a two-digit location coordinate. These are the
coordinates shown in the library configuration report. The first digit is
always zero. The second digit indicates the location of the tape drive
relative to the other tape drives. The bottommost tape drive has
location coordinates [0,1], the next-to-bottom has location coordinates
[0,2], and so on.

Quantum Scalar i40 and Scalar i80 Users Guide 9


Chapter 1: Description
Library Components

Figure 4 Scalar i40 Back Panel Full-height tape drives


Components Power supply cord

Unavailable Ethernet Service port


Tape drive cable FC port cable in LEFT do not use
SCB port

Half-height tape drives


Power supply cord

Ethernet Service port


Tape drive cables
cable in LEFT do not use
SCB port

10 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 1: Description
Library Components

Figure 5 Scalar i80 Back Panel


Components
Full-height tape drives
Tape drive filler plate Power supply cord

Power supply
filler plate

Ethernet Service port


Tape drive cables Unavailable
cable in LEFT do not use
FC port
SCB port

Half-height tape drives

Power supply cord

Power supply
filler plate

Ethernet Service port


Tape drive cables cable in LEFT do not use
SCB port

Quantum Scalar i40 and Scalar i80 Users Guide 11


Chapter 1: Description
Standard Features

Standard Features
This section describes several features of Scalar i40 and Scalar i80
libraries.

User Interface The operator panel is located on the front of the library and allows you
to work locally on the library via the user interface. The Web client
allows you to view and perform library functions from remote sites and
is accessible through a browser. The operator panel and Web client each
contain a different user interface and functionality.
See Chapter 3, Understanding the User Interface for more information
about the operator panel and the Web client.

Partitions Partitions are virtual sections within a library that present the
appearance of multiple, separate libraries for purposes of file
management, access by multiple users, or dedication to one or more
host applications.
Organizing the library into partitions divides the resources into virtual
sections. If one of the resources is not available due to a failure or other
cause, the other partitions and their assigned components are still
available. Partitions can also be used to control access to portions of the
library by granting permissions to user accounts to access certain
partitions (see Privilege Levels on page 81 and Creating Local User
Accounts on the Web Client on page 82).
For more information on partitions, see Working With Partitions on
page 51.

Control Path The control path tape drive is used to connect a partition to a host
Modification application. Only one tape drive can be selected as the control path at
one time. By default, the first tape drive assigned to a partition is
designated as the control path. In the event that the control path
connection to the host application fails, you can select a new control
path for the partition. See Configuring Control Paths on page 67.

12 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 1: Description
Licensable Features

Support for WORM Scalar i40 and Scalar i80 tape libraries support WORM (write once, read
many) technology. WORM allows non-rewriteable and non-erasable
data to be written and provides extra data security by prohibiting
accidental data erasure. The WORM feature is supported whenever you
use WORM cartridges.

Licensable Features
In addition to the standard features, the following additional, licensable
features are available:
Capacity on Demand (COD)
Advanced Reporting - includes custom reports and logs and Control
Path Failover functionality.
Encryption Key Management
For information on how to obtain and install a license key, see Adding or
Upgrading Licensable Features on page 69.

Capacity on Demand All Scalar i40 and Scalar i80 library configurations ship with the
(COD) purchased number of slots pre-activated. After the initial purchase of
your library, you can activate any remaining inactive slots in your library
by purchasing a COD license upgrade.
The Scalar i40 base configuration has 25 slots activated (these slots
comprise the first 5 magazine columns starting from the left front
magazine column going clockwise). You can buy a COD license to
activate the remaining 15 slots.
The Scalar i80 base configuration has 50 slots activated (these slots
comprise the first 5 magazine columns starting from the left front
magazine column going clockwise). You can buy a COD license to
activate the remaining 30 slots.
To see your librarys current configuration and slot availability, open the
Library Configuration Report (choose Reports > Library Configuration
from the Web client).

Quantum Scalar i40 and Scalar i80 Users Guide 13


Chapter 1: Description
Licensable Features

Advanced Reporting The Advanced Reporting license applies to your entire library, regardless
of library size. This means you only need to purchase the license once. If
you increase the size of your library, your existing license applies to your
new library configuration.
Advanced Reporting provides the following features and reports that
you can configure for viewing and analysis:
Control Path Failover (CPF) - Provides support for configuring the HP
LTO-5 drive for control path failover. When control path failover is used,
one drive is assigned as the primary control path and another drive as
the control path failover (secondary) drive. The control path failover
drive is used whenever the primary control path drive fails or is
inoperable
Reports - Listed below are report names. You can view, configure, send
via e-mail, and save and reuse report configurations as templates. In
addition, you can automatically e-mail any of the reports to designated
recipients at specified, scheduled times.
Drive Resource Utilization ReportProvides tape drive usage
information, showing you which tape drives are working at
optimum capacity and which are under-utilized. This can help you
allocate your tape drive resources properly.
Media Integrity Analysis ReportProvides Tape Alert count for
various combinations of tape drives, tape cartridges, and Tape Alert
flags. This can help you determine if a problem is due to a specific
tape drive or tape cartridge.
Logs - Listed below are available logs:
Media Security Log - Lists media that has been removed from the
library.
Media Usage Log - Lists information on all media that have ever been
in the library.
For information on how to use the advanced reporting features, see
Advanced Reporting on page 111.

14 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 1: Description
Licensable Features

Encryption Key The Encryption Key Management (EKM) license enables tape drive
Management transparent encryption using library-managed encryption. The EKM
license applies to the entire library, regardless of how many slots are
licensed. If you increase the number of slots in your library, your existing
license applies to your new library configuration. For more information
about EKM, see Chapter 7, Encryption Key Management.

Quantum Scalar i40 and Scalar i80 Users Guide 15


Chapter 1: Description
Licensable Features

16 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 2
Unpacking the Library

Choose a location in which to install the library that is as free from dust
as possible. Dust can damage or degrade performance of library
components and media.
Refer to the following sections of this manual for important information
that you need when installing and setting up your library:
Environmental Specifications on page 343
Taking ESD Precautions on page 226

Note: Unpack the library as close to the installation location as


possible.

1 Inspect the outer library packaging for damage. If there is any


damage evident on the library packaging, do not continue with the
installation and contact Quantum customer support.
2 Open the library packing box and remove the kit tray containing the
accessory kit and the rail kit (see Figure 6). Some configurations
come with tape drives installed in the library, and some come with
tape drives packaged separately. If yours comes with tape drives
packaged separately, remove them and set aside for installation
later.

Quantum Scalar i40 and Scalar i80 Users Guide 17


Chapter 2: Unpacking the Library

Figure 6 Packaging

Accessory kit

Rail kit

Kit tray

Media labels

Top foam

Bottom foam

Shipping carton

Bottom tray (Scalar i80 only)


Scalar i40
Pallet (Scalar i80 only)
Scalar i80

3 Remove the top foam.


4 Scalar i80 only: Remove the shipping carton by lifting it straight up
out of the bottom tray.
5 With the help of a second person, lift the library chassis out of the
shipping carton and place it on a table approximately waist high.

18 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 2: Unpacking the Library

WARNING: Two people are required to safely lift the library out of
its packaging or into a rack.

Caution: Lift the library chassis at the sides. Avoid putting the
weight of the library chassis on the front bezel.

6 Remove the anti-static wrapping from the library. Keep the anti-
static wrapping intact so that you can use it later if needed.
7 Save the packing box, packaging material, and anti-static wrapping
in case you need to move or ship the library in the future.
8 Remove the Y-tray restraint. The Y-tray restraint consists of four (4)
thumbscrews, a plastic sheet, a small metal clip, and underneath
the plastic sheet, an orange restraint tablocated on the top cover
of the library. See Figure 7.
a Unscrew and remove the four thumbscrews from the top cover
(see Figure 7). Save the thumbscrews in case you need to move
or ship the library in the future.
b Remove the plastic sheet and metal clip and discard. You will
not need to use them again.

Quantum Scalar i40 and Scalar i80 Users Guide 19


Chapter 2: Unpacking the Library

Figure 7 Removing the Robot


Restraint

c Remove the orange shipping restraint tab and discard. You will
not need to use it again.

Note: TheY-tray may stay at the top of the library, or it may


move downward toward the floor of the library. If it
moves downward, you will hear the gears turning as it
moves. This is normal.

9 Once you remove the Y-tray restraint, you may cover the holes in the
library top cover with stickers, which are provided in the accessory
kit for this purpose. This step is optional and is intended to prevent
small objects from accidentally falling into the library through the
holes.
10 Remove the protective plastic sheet covering the front panel display.

20 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 3
Understanding the User
Interface

The user interface for the Scalar i40 and Scalar i80 libraries is available in
two formats: the operator panel and the Web client. Operations on the
library can be performed locally on the operator panel or remotely on
your computer using the Web client.
Both the operator panel and the Web client are required to operate the
library. Some functionality is only available through the Web client, and
some functionality is only available through the operator panel.
However, it is recommended that you use the Web client rather than the
operator panel to perform most library operations.
This chapter covers:
Operator Panel
Web Client
Menu Trees

Operator Panel
The operator panel is located on the front panel of the physical library.
The operator panel screen contains a menu bar with operations that
correspond to the four physical buttons below it. The menu operations
and button functions change with each screen.

Quantum Scalar i40 and Scalar i80 Users Guide 21


Chapter 3: Understanding the User Interface
Operator Panel

The operator panel home screen refreshes every 5 seconds to provide


up-to-date information about library performance.

Operator Panel Layout You can choose your desired operator panel home screen that displays
and Functions on the local user interfacethe default home screen or the alternate
home screen that allows easy I/E unlock access. Figure 8 and Figure 9
depict these screen options; Table 2 describes the operator panel
functions.

Figure 8 Operator Panel User


Interface - Home Screen
Name Status Health status

Title bar

Active display

Menu bar

Navigation/selection
buttons

You can choose to change the view of the home screen for easy I/E
unlock access. Refer to Changing Operator Panel Home Screen View on
page 109.

22 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 3: Understanding the User Interface
Operator Panel

Figure 9 Operator Panel User


Interface - Alternate Home
Screen

Scalar i40

Number of occupied
I /E slots

Number of configured
I /E slots

Unlock I/E Station

Scalar i80

Number of occupied
I /E slots

Number of
configured I/E slots

Unlock bottom Unlock top


I/E Station I/E Station

Quantum Scalar i40 and Scalar i80 Users Guide 23


Chapter 3: Understanding the User Interface
Operator Panel

Table 2 Operator Panel


Functions Operator Panel
Element Description

Title bar The title bar is present on every screen, and


contains three fields: name, status, and health
status.

Name The name field displays a description of the


current view. It changes depending on the menu
selection.
On the home screen, the field displays the
library type (Scalar i40 or Scalar i80).
On active pages, the field displays the name of
the main menu (Setup, Actions, Tools, Reports).
When a message displays, the field displays the
message type (Success, Completed,
Information, FAILURE, NOTICE). Failure
messages will blink.

24 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 3: Understanding the User Interface
Operator Panel

Operator Panel
Element Description

Status The status field displays the current state or


operation being performed by the robot. If the
robot is not idle, the status will blink. status can
be any of the following:
Initializing The is currently in the process of
initializing.
Autoleveling The robotics hardware is being
autoleveled.
Homing The robot is performing a home
operation.
Teaching The robot is performing a teach
operation.
Calibrating The robot is performing a
calibration operation.
Scanning The robot is performing an
inventory operation.
Unlocking The robot is in the process of
unlocking a magazine.
Move Media The robot is moving media
from one location to another.
Loading The robot is in the process of
moving a tape to load into a tape drive.
Unloading The robot is in the process of
unloading a tape drive and returning it to the
source location.
Idle The robot is ready and idle.
Not Ready The robotics system is not ready.

Quantum Scalar i40 and Scalar i80 Users Guide 25


Chapter 3: Understanding the User Interface
Operator Panel

Operator Panel
Element Description

Health status The health status field displays an icon


representing the health of the library.
Heart Library is in good health (no open
or unopened diagnostic tickets are present).
Triangle Library health is degraded
(library contains open or unopened low- or
high-priority diagnostic tickets).
Exclamation point Immediate attention
is required (library contains open or
unopened urgent diagnostic tickets).

Active display The active display provides information or menu


items according to the selected menu item or
operation.
The default home screen displays the number and
state of partitions, tape drives, storage slots, and
I/E slots.
The alternate home screen displays the number
and state of the I/E slots, and provides access to
unlock I/E stations.

Menu bar The menu bar displays the function associated


with each of the navigation/selection buttons.
The button function changes with each menu.
Common functions are navigation (up, down,
left, right, next) and menu selection (select, apply,
exit, yes, no, cancel).

Navigation/ The physical buttons enable you to navigate


Selection menus and start and stop library operations
Buttons according to the functions listed in the button
bar. Not all buttons are functional for every
operation. See Navigating and Editing on the
Operator Panel on page 27 for more information.

26 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 3: Understanding the User Interface
Operator Panel

Navigating and Editing You use the four navigation/selection buttons exclusively to move
on the Operator Panel through the menus and commands on the operator panel.
From the default home screen, the menu bar lists the four main menu
headings. From the alternate home screen, you can select Menu to
return to the default home screen to access the four main menu
headings.
Press the button corresponding to a menu item to bring up the list of
sub-menu items. The item you are currently on is highlighted. Press the
buttons corresponding to Up, Down, Left, or Right to navigate to a
desired menu item. As you move through the items, the highlighting
moves with you so you always know which item you are on. Press the
button corresponding to Select to select a highlighted item or action.
This in turn brings up either another sub-menu, a screen where you can
modify settings or perform operations, or a screen displaying
information.
To edit a modifiable field, such as date, time, licenses, IP address, and so
on, use the Left and Right buttons to move through the field, one
segment at a time (for license keys and passwords, you will move one
digit or letter at a time). Use the Up and Down buttons to change the
value of each segment. When you reach the value you want, press the
Right button. As you press Right, the value fills in and you go to the
next segment. To edit a previous entry, press the Left button until you
reach the entry and edit as before. For multiple fields, continue to press
Right after each entry until you reach the last entry. At this point, the
Right button designation changes to Apply. Press the Apply button.
The new information displays. Press Exit to exit. For an example, see
Figure 10 on page 28.
To scroll through a list of items, or to edit letters and numbers, you can
press the appropriate button repeatedly to scroll one item at a time, or
you can hold the button down for fast scrolling through the available
options.
To exit a screen, press the Exit button.
To cancel an operation without saving any changes, press the Cancel
button. If you are in the middle of making changes, repeatedly press the
Left button until you are back at the first field on the screen, then press
the Cancel button.

Quantum Scalar i40 and Scalar i80 Users Guide 27


Chapter 3: Understanding the User Interface
Web Client

Figure 10 Using the Buttons to


Set the Date and Time

Web Client
The Web client interface is accessible from supported Web browsers (see
Supported Internet Browsers on page 347).
To access the library from a remote location, the library must be
connected to your network via an Ethernet connection. Simply enter the
librarys IP address in your Internet browser bar to access the Web client.
See Configuring Network Settings on page 40 for information on
setting the network configuration settings for remote use.

Tips Keep the following tips in mind when using the Web client:
You must disable Web browser popup blockers to use the Web
client interface and the librarys online Help. Add the Scalar i40 or
Scalar i80s Internet Protocol (IP) address to the list of trusted/
allowed sites on your Scalar i40- or Scalar i80-supported browser, so
the Web client pages will automatically refresh.
Do not use your Internet browser Back button to navigate the Web
client pages. Instead, use the buttons provided within the Web
client.

28 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 3: Understanding the User Interface
Web Client

Optimum screen resolution for viewing using a Windows operating


system is 96 DPI. If your resolution is set higher, certain screen
messages may not display as intended. To change screen resolution,
show the desktop, right click to display the Properties window, and
click Settings > Advanced.
Log out of the library before closing the Internet browser window
when you are using the Web client. If you do not log out, the
session will remain open. Clicking the close button (X) in the upper-
right corner of the Web client closes the browser window but does
not log you out.

Sorting Information in You can sort information displayed in tables if the table column heading
Tables is bold. Click the column heading and the information will sort. Click
again to toggle from ascending to descending.

Web Client Layout and Figure 11 on page 30 shows the Web client interface. Table 3 on
Functions page 31 explains the Web client interface elements.

Quantum Scalar i40 and Scalar i80 Users Guide 29


Chapter 3: Understanding the User Interface
Web Client

Figure 11 Web Client User


Interface - Home Page

Library is not ready Home Online Logout


message area help

Header

Menu bar

Active
display

View diagnostic tickets

30 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 3: Understanding the User Interface
Web Client

Table 3 Web Client Screen


Elements Web Client
Element Description

Header The header is present on all pages and contains


the library type (Scalar i40 or Scalar i80) and three
buttons:
Home Brings you to the home page.

Help Displays the online help.

Logout Logs out of the current session.

A message in the header alerts you when the


robot is not ready to perform library functions.
See Troubleshooting Library Not Ready
Messages on page 318 for more information on
Library Not Ready messages displayed in the
header.

Menu bar Displays the available menu choices. The choices


vary depending on login privileges.
The far right of the menu bar also displays the
name of the logged-in user, with the associated
privilege level indicated in brackets.
If a menu item selected has a sub-menu, then >
is displayed to the right of the item.

Active display The active display provides information or menu


items according to the selected menu item or
operation.

Web Client Home Page The home page displays status and health information in the active
display portion of the window (see Figure 11 on page 30). See System
Summary and Subsystem Status below for more information.

System Summary The system summary is available on the home page of the Web client.

Quantum Scalar i40 and Scalar i80 Users Guide 31


Chapter 3: Understanding the User Interface
Web Client

It provides tabular data on the capacity of the librarys partitions, slots,


and tape drives. It also displays whether partitions are online or offline
(in the Storage Slots section). The current users login privileges
determine which partitions are displayed (see Privilege Levels on
page 81).

Subsystem Status You can quickly gauge the health of the library by observing the color of
the three subsystem status buttons located at the bottom of the home
page. These buttons provide quick access to information about the
health of the library for faster recovery if problems occur. You can
select the buttons to view diagnostic tickets that report problems in the
subsystems.
The three subsystems are:
Library Represents connectivity, control, cooling, power, and
robotics.
Drives Represents tape drive components, such as tape drives,
tape drive firmware, and tape drive sleds.
Media Represents media components, such as cartridges and
barcode labels.
Each button has three states indicated by color. The three states are:
Green (check mark) No diagnostic tickets exist, or, if any tickets
do exist, they have all been closed.
Yellow (exclamation point) The library contains open or
unopened, low- or high-priority diagnostic tickets.
Red (X mark) The library contains open or unopened urgent
diagnostic tickets.
If the color of a subsystem button is red or yellow, you can click the
button to display the corresponding Diagnostic Tickets screen. This
screen lists library, drives, or media tickets, depending on which button
was selected. See About Diagnostic Tickets on page 312 for more
information.

32 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 3: Understanding the User Interface
Menu Trees

Menu Trees
The following menus organize operations and commands into logical
groupings:
The Setup menu consists of commands that users with
administrator privileges can use to set up and configure various
aspects of the library, including partitions, I/E station slots, cleaning
slots, control paths, network settings, drive settings, users,
notifications, date and time, licenses, library registration, and e-
mail.
The Operations/Actions menu consists of commands that enable
users to change the librarys mode of operations, import and export
cartridges, load and unload tape drives, move media, lock or unlock
the I/E station, log out, and shut the library down. The menu is
called Actions on the operator panel and Operations on the Web
client.
The Tools menu consists of commands that you can use to maintain
your library such as viewing diagnostic tickets, generating
diagnostic logs, identifying drives, configuring the internal network,
saving and restoring the library configuration, setting system and
security settings, and updating firmware, and performing library
diagnostics.
The Reports menu provides various kinds of library information.
Administrators have access to all menu commands, but users privileges
are more limited.
Figure 12 lists the operator panel menus. Figure 13 lists the Web client
menus.

Quantum Scalar i40 and Scalar i80 Users Guide 33


Chapter 3: Understanding the User Interface
Menu Trees

Figure 12 Operator Panel


Menus
Operator Panel
Main Menu Bar

Setup Actions Tools Reports

Network Configuration I/E IVT Diagnostic Tickets

Date & Time Unlock I/E Station Diagnostics Library

License Installation Import Tape Robotics Test Tape Drives

Dedicated Slots Import Cleaning Tape Tape Drive Test Media

Cleaning Export Tape Magazine Test Close ALL

I/E Export Cleaning Tape Random Move Test About Library

Tape Drives (FC) Magazine Robotics View Partitions

Configure Partitions Release Service Network Tape Drives


View Current
Tape Drive Modify Subnet Network Settings
Partitions
Auto-Create Partitions Change Mode Reset Factory Defaults Date/Time

Delete Partitions Unload Licenses

Account Settings Manual Cleaning Copyright Statement

Password Settings Reset

Session Timeout Change Partition Mode

Modify Password* Shutdown

System Settings Shutdown Library


ACCESS KEY
Unload Assist Restart Library
NOTE: If passwords are not
enabled on the operator
Logical SN Addr
panel, all users have access
to all menus and functions.
Man Cart Assign
All Users
SNMP

Admin Privileges Only


SMI-S
* Only Available if LUI
Power Save
Passwords are enabled
Alternate Home

Auto DT Close

Security Services

Network IF

SSH Services

ICMP

Web client

Service User

SNMP V1/V2

SSL

34 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 3: Understanding the User Interface
Menu Trees

Figure 13 Web Client Menus

Web Client
Main Menu Bar

Setup Operations Tools Reports

Setup Wizard Media All Diagnostic Tickets System Information

Partitions Move Capture Snapshot Library Configuration

Save/Restore
Cleaning Slots Import Network Settings
Configuration
E-mail Configuration
I/E Station Slots Export Logged In Users
Record

Drive Settings Cleaning Media Save Configuration Record All Slots

Control Path Import Drive Operations Log Viewer

License Export Download SNMP MIB Advanced Reporting

Drive Resource
Notification Partitions EKM Path Diagnostics
Utilization

E-mail Configuration Change Mode EKM Management Media Integrity Analysis

Import Communication
Advanced Reporting Drive About
Certificates
Receiver
Addresses Load Encryption Certificate Scalar i40/i80

Media Security Import


Unload Open Source Licenses

Diagnostic Tickets Export


Change Mode
Receiver
Encryption Key
Addresses
Contact I/E Station Unlock
Import
Information
Release Magazines
Export
Network Management

System Shutdown
Retrieve SKM Logs
Network

Log Out Update Library Firmware


SNMP ACCESS KEY

SNMP Trap Diagnostics


All Users
Registrations
EKM
User Management Admin Privileges Only

Drives
User Accounts

Robotics
Remote Authentication

Reset Operator Panel Exit


Passwords

Encryption

System Configuration

Partition Configuration

Date & Time

Register Library

Quantum Scalar i40 and Scalar i80 Users Guide 35


Chapter 3: Understanding the User Interface
Menu Trees

36 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 4
Configuring the Library

A Setup Wizard is available to assist you with the initial configuration of


the library. The Setup Wizard, however, contains only a subset of
configuration tasks. The operator panel and Web client menus provide
access to all configuration options that are included in the Setup Wizard
and many that are not.
This chapter covers the Setup Wizard and all of the other configuration
options. Paths to open the appropriate screens on both the operator
panel and the Web client are given for each task. (For complete menu
trees, see Menu Trees on page 33.)

Note: These operations should not be performed concurrently by


multiple administrators logged in from different locations. You
can access the screens, but you cannot apply changes while
another administrator is performing the same operation.

Caution: Always save the library configuration after modifying a


configurable item. This will allow you to restore the most
current settings if necessary. See Saving and Restoring the
Library Configuration on page 107.

Note: Power cycling (powering the library on and off) is not necessary
to configure the library.

Quantum Scalar i40 and Scalar i80 Users Guide 37


Chapter 4: Configuring the Library

This chapter covers:


Using the Setup Wizard
Configuring Network Settings
Configuring SNMP Settings
Setting the Date, Time, and Time Zone
Working With Partitions
Configuring Cleaning Slots
Configuring I/E Station Slots
Configuring Tape Drive Parameters
Configuring Control Paths
Adding or Upgrading Licensable Features
Working With E-mail Notifications
Configuring the Library E-Mail Account
Setting Customer Contact Information
Configuring the Service Port
Working With Local User Accounts and Passwords
Working With LDAP User Accounts (Remote Authentication)
Setting the Session Timeout
Configuring System Settings
Configuring Security Settings
Saving and Restoring the Library Configuration
Registering the Library
Changing Operator Panel Home Screen View

38 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 4: Configuring the Library
Using the Setup Wizard

Using the Setup Wizard


When you first power on the library, the operator panel displays the
Setup Wizard, which walks you through the initial configuration of the
librarys basic operational settings.
The Setup Wizard on the operator panel displays when you first install
your library. It displays only once, with the following exceptions: it will
also display after SCB replacement, resetting factory defaults, or
downgrading library firmware.
When the Setup Wizard displays on the operator panel, you must either
complete the Setup Wizard or cancel out of it. If you cancel, you accept
the librarys default configuration (see Default Configuration on
page 40). You can modify the configuration at any time later using the
Setup Wizard on the Web client, or by using the Setup menu options
from the operator panel or Web client.

Operator Panel
The Setup Wizard on the operator panel is covered in detail in the
Scalar i40 and Scalar i80 Quick Start Guide.

Web Client
To access the Setup Wizard, click Setup > Setup Wizard. Work through
several screens that enable you to add licenses; set date, time, and time
zone; configure cleaning slots; configure I/E station slots; and auto-
create partitions.

Quantum Scalar i40 and Scalar i80 Users Guide 39


Chapter 4: Configuring the Library
Default Configuration

Default Configuration
The library comes with a default configuration, which you can modify at
any time. The default configuration is as follows:

Feature Default Configuration

Library host name library

Network settings IPv4, DHCP enabled


IPv6 disabled

Number of partitions Equal to the number of unique tape


drives based on interface type (Fibre
Channel or SAS) and drive generation
(LTO-4, LTO-5) not currently
assigned to a partition.
Storage slots are divided equally
among the partitions.

Number of I/E station slots 5

Number of cleaning slots 0

Configuring Network Settings


The operator panel Setup Wizard allows you to configure network
settings that allow remote access to the library from the Web client. At a
minimum, you must initially configure the network IP address from the
operator panel. After the initial configuration, you can modify the
network settings from either the operator panel or the Web client.

40 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 4: Configuring the Library
Configuring Network Settings

Note: Changing the network settings may interrupt the library


connection and library communication. Your current browser
session may become invalid. If this happens, you must close
your browser and then restart it to reconnect to the library with
your new configuration settings.

Note: Make sure that the library is connected to the network before
modifying network settings. If the Ethernet cable is not
installed properly, you cannot configure the network settings.
Install one end of the Ethernet cable in the left-most Ethernet
port of the system control board (SCB) located on the back of
the library (see Figure 4 or Figure 5 on page 11). Make sure the
other end of the Ethernet cable is installed in the appropriate
LAN port on your LAN.

You can configure the following network settings:


Library Host Name
DHCP
IP Addresses
Default Gateway, Subnet Mask, Network Prefix, and DNS Addresses
Some settings are only available on the Web client; others are only
available on the operator panel, as described below.

Library Host Name The host name is the network name you want to assign to the library.
The host name is limited to 12 lowercase alphanumeric characters and
dashes (-).
You can view, but not modify, the host name on the operator panel. To
modify the host name, you must use the Web client.

Web Client
1 Select Setup > Network Management > Network.
2 Type a name in the Host Name field, and click Apply.

Quantum Scalar i40 and Scalar i80 Users Guide 41


Chapter 4: Configuring the Library
Configuring Network Settings

DHCP DHCP is enabled by default. When DHCP is enabled, the library obtains
an IP address automatically. If DHCP is disabled, you must manually
enter an IP address, default gateway, and subnet mask/net prefix. You
can enable/disable DHCP from the operator panel or Web client.

Operator Panel
Select Setup > Network Configuration.

Web Client
Select Setup > Network Management > Network.

IP Addresses The library can support both IPv4 and IPv6 network settings at the same
time. For more details, see the bullets below.

Caution: If you change the IP address on your library, make sure to


change it on any host applications that access the library.

Note: Be sure to add your librarys IP address to the list of trusted/


allowed sites on your library-supported browser, so the Web
client pages automatically refresh.

IPv4 Addresses The library always supports IPv4 network


settings. The library can support either a DHCP-obtained or a static
IPv4 address.
IPv4 addresses must be entered in dot notation (for example,
192.168.0.1). They are limited to numeric characters and do not
allow values exceeding 255 for dot-separated values.
IPv6 Addresses IPv6 is disabled by default and can only be
enabled/disabled via the operator panel. Once enabled, you must
use the Web client to modify the address. Unlike IPv4, the library
can support both DHCP-obtained and static IPv6 addresses at the
same time.

42 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 4: Configuring the Library
Configuring Network Settings

IPv6 addresses must be entered in the proper notation. IPv6 address


can be entered in the most common notation, as eight groups of
four hexadecimal digits. 2001:0ff8:55cc:033b:1319:8a2e:01de:1374
is an example of a valid IPv6 address. Also, if one or more of the
four-digit groups contains 0000, you can omit the zeros and replace
them with two colons (::), as long as there is only one double colon
used in an address. Using this notation,
2001:0ff8:0000:0000:0000:0000:01de:1374 is the same as
2001:0ff8::01de:1374.
You can configure IPv4 addresses on the operator panel or Web client.
You can set the library to use IPv6 via the operator panel, but you must
use the Web client to configure a static IPv6 address.

Operator Panel
1 Select Setup > Network Configuration.
2 Modify the IP address using the method described in Navigating
and Editing on the Operator Panel on page 27.

Web Client
Select Setup > Network Management > Network.

Default Gateway, These settings have specific configuration requirements, as follows:


Subnet Mask, Network Default Gateway The IP address of the default gateway for your
Prefix, and DNS portion of the Ethernet network. For IPv4, this setting can only be
Addresses changed if DHCP is disabled.
Subnet Mask (IPv4 only) Available only if DHCP is disabled.
Network Prefix (IPv6 only). Can be entered only on the Web client.
Primary DNS Address (optional, Web client only) Must be entered
as an IP address. This text box is available only if DHCP is disabled.
Secondary DNS Address (optional, Web client only) Must be
entered as an IP address. This text box is available only if DHCP is
disabled.

Quantum Scalar i40 and Scalar i80 Users Guide 43


Chapter 4: Configuring the Library
Configuring SNMP Settings

Operator Panel
1 Select Setup > Network Configuration.
2 Modify the fields using the method described in Navigating and
Editing on the Operator Panel on page 27.

Web Client
Select Setup > Network Management > Network.

Configuring SNMP Settings


Simple Network Management Protocol (SNMP) is a light-weight
protocol designed for remote management and monitoring of
infrastructure devices. The library provides SNMP support, so an external
management application can be configured to receive library SNMP
information. The library supports SNMP by publishing a Management
Information Base (MIB) that can be queried to obtain the status of the
library and many of its individual components. SNMP information can
be obtained from the library using SNMP Traps and GET queries.
For more information about SNMP, see the Scalar i40 and Scalar i80
Basic SNMP Reference Guide (6-66773-xx).
For information on integrating MIBs with an SNMP management
application, contact your network management application vendor.

Registering External Administrators can register transport protocols, IP addresses, and port
Management numbers of external management applications to enable them to
Applications receive SNMP traps from the library. (By default, the library ignores all
SNMP SET operations, so external management applications cannot
register themselves to receive SNMP traps from the library.)
After registering the transport protocols, IP addresses, and
corresponding port numbers, you can perform a test to verify that the
library can send the SNMP traps to the addresses.

44 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 4: Configuring the Library
Configuring SNMP Settings

When registering external management applications to receive SNMP


traps, you can set the following parameters:
Transport The transport protocol. This should be the same as the
transport protocol configured on the SNMP trap receiver. Select one
of the following:
UDP User Datagram Protocol for IPv4.
UDP6 User Datagram Protocol for IPv6.
TCP Transmission Control Protocol for IPv4.
TCP6 Transmission Control Protocol for IPv6.
Host Name/IP Address The host name or the IP address of the
external management application you want to register. A host name
may be entered only if DNS is enabled. Otherwise, IP addresses must
entered. For information on DNS, see Default Gateway, Subnet
Mask, Network Prefix, and DNS Addresses on page 43.
Port the port number of the external application you want to
register. The default port number for an external application is 162.
You can only perform these functions from the Web client.

Web Client
1 Select Setup > Network Management > SNMP Trap
Registrations.
2 Click one of the following buttons to perform these actions:
Create Adds the IP address and port number of the external
application to the list of registered addresses that will be sent
SNMP traps.
Delete Deletes a selected IP address and port number.
Test This test simply sends the traps; it does not check to see
if they were received. You must check the external management
applications to verify that the traps were received.

Quantum Scalar i40 and Scalar i80 Users Guide 45


Chapter 4: Configuring the Library
Configuring SNMP Settings

Enabling SNMP The library supports SNMP v1, v2c, and v3.
Versions You can enable or disable support for SNMP v1 and v2c. They are
enabled by default. The recommended practice is to disable SNMP v1
and SNMP v2c in highly secure environments.
SNMP v3 is always enabled and cannot be disabled.
The authentication algorithm is set to MD5, and the encryption is
disabled system-wide.

Operator Panel
1 Select Setup > Security Services > SNMP V1/V2
2 Press Modify.
3 Use the Up and Down buttons to select Enabled or Disabled and
press Apply.
4 Press Exit.

Web Client
1 Select Setup > Network Management > SNMP.
2 Select the SNMP V1 and V2c check box (under New Settings) to
enable SNMP v1 and v2c. Clear the SNMP V1 and V2c check box to
disable SNMP v1 and v2c.

Enabling SNMP The library allows you to enable or disable SNMP authentication traps.
Authentication Traps When the library receives an SNMP message that does not contain the
correct community string or other authentication information, the
library sends an SNMP authentication trap message to the external
management application, indicating the authentication failure. SNMP
authentication traps are disabled by default.

46 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 4: Configuring the Library
Configuring SNMP Settings

Web Client
1 Select Setup > Network Management > SNMP.
2 Select the SNMP Authentication Traps check box (under New
Settings) to enable SNMP authentication traps. Clear the SNMP
Authentication Traps check box to disable SNMP authentication
traps.

Modifying the SNMP Administrators can modify the SNMP community string. The SNMP
Community String community string is a text string that acts as a password to authenticate
GET and GET-NEXT SNMP v1 and SNMP v2c messages exchanged
between the library and an external management application. The
SNMP community string used by the library must match the string used
by the external management application.
The default SNMP community string on the library is: publicCmtyStr.
For security purposes, this string should be modified. When modifying
the community string, adhere to the following guidelines: the
community string is case-sensitive, cannot be empty, and cannot exceed
32 characters.
You can modify the SNMP community string from the Web client only.

Web Client
1 Select Setup > Network Management > SNMP.
2 Enter a new community string in the SNMP Community text box
under New Settings.
3 Click Apply.

Downloading the SNMP The SNMP Management Information Base (MIB) is for library customers,
MIB partners, third-party management software developers, and other
parties interested in integrating the Scalar i40 and Scalar i80 with
commercial management frameworks. The Scalar i40 and Scalar i80
libraries support SNMP by publishing a MIB that can be queried to
obtain the status of the library and many of its individual components.
Administrators can download the SNMP MIB from the library. The MIB
can then be installed on an SNMP external management application.

Quantum Scalar i40 and Scalar i80 Users Guide 47


Chapter 4: Configuring the Library
Setting the Date, Time, and Time Zone

For more information about the library MIB, see the Scalar i40 and
Scalar i80 Basic SNMP Reference Guide (6-66773-xx) or contact
Quantum Support.
For information on integrating MIBs with an SNMP management
application, contact your network management application vendor.

Web Client
1 Select Tools > Download SNMP MIB.
2 Save the file to a known location.

Setting the Date, Time, and Time Zone


You can either set the library date, time, and time zone settings
manually or configure the Network Time Protocol (NTP). NTP allows you
to synchronize the library date and time with other components in your
IT infrastructure.
If you enable NTP, you must also configure the IP address of at least one
NTP server. Contact your network administrator for NTP server IP address
information.
You can configure the date and time on both the operator panel and
the Web client. You can view the time zone on the operator panel, but
must use the Web client to change it. You can only configure NTP
settings on the Web client.

Note: The following operations should not be performed


concurrently by multiple administrators logged in from
different locations. You can access the appropriate screens, but
you cannot apply changes while another administrator is
performing the same operation.

48 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 4: Configuring the Library
Setting the Date, Time, and Time Zone

Setting the Date and Date and time settings are used to log the date and time events take
Time Manually place and to set the time for automatic backup and restore functions. At
a minimum, you should set the librarys date and time as part of the
initial library configuration.
The time is set to a 24 hour clock. For example, four oclock in the
afternoon is entered as 16:00.

Operator Panel
1 Select Setup > Date & Time.
2 Modify the date and time using the method described in Navigating
and Editing on the Operator Panel on page 27.

Web Client
1 Select Setup > Date & Time.
2 Refer to the library Web client online help for detailed instructions.
To view the help, click the Help icon in the upper right corner of the
screen.

Setting the Date and The library supports the Network Time Protocol (NTP). NTP allows you to
Time Using the Network synchronize the library date and time with other components in your IT
Time Protocol infrastructure. Administrators can either modify the date and time zone
settings manually or configure NTP.
If NTP is enabled, the time zone and IP addresses (or host names, if DNS
is configured) of at least one NTP server must be configured on the
library. Contact your network administrator for NTP server IP address
information.

Caution: Using two NTP servers can cause incorrect time


calculations. You should use either one NTP server, or more
than two, but not exactly two.

Quantum Scalar i40 and Scalar i80 Users Guide 49


Chapter 4: Configuring the Library
Setting the Date, Time, and Time Zone

Details on NTP settings include:


At least one NTP server must be configured and available.
NTP is enabled on the Date & Time screen. When NTP is enabled,
you cannot manually configure date and time. For more information
on setting date and time manually, see Setting the Date and Time
Manually on page 49.
You can enter an IP address (or host name, if DNS is configured) for
the NTP servers.
NTP server IP addresses must be entered in the proper format. See
Configuring Network Settings on page 40 for the proper format of
IPv4 and IPv6 addresses.
After you apply NTP settings, system clock synchronization may take
several minutes.
You can only enable and configure NTP on the Web client.

Web Client
1 Select Setup > Date & Time.
2 Refer to the library Web client online help for detailed instructions.
To view the help, click the Help icon in the upper right corner of the
screen.

Setting the Time Zone To select your time zone from a list, disable Use Custom Time Zone
setting and select your time zone from the list.
If your time zone does not appear on the list, or if you want more
control over your time settings, enable Use Custom Time Zone and set
a Universal Coordinated Time (UTC) offset.
You can only set the time zone via the Web client.

50 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 4: Configuring the Library
Working With Partitions

Web Client
1 Select Setup > Date & Time.
2 Refer to the library Web client online help for detailed instructions.
To view the help, click the Help icon in the upper right corner of the
screen.

Setting Daylight Saving If you selected your time zone from the drop-down list (see Setting the
Time Time Zone on page 50), the library automatically adjusts for daylight
saving time. There is no need to manually reset the clock for time
changes.
However, if you set a custom time zone, the library will not
automatically adjust for daylight saving time. You must enable the Use
Custom Daylight Saving Time setting. Once enabled, you can set start
and stop times to an accuracy of one minute.
You can only set daylight saving time on the Web client.

Web Client
1 Select Setup > Date & Time.
2 Refer to the library Web client online help for detailed instructions.
To view the help, click the Help icon in the upper right corner of the
screen.

Working With Partitions


Partitions are virtual sections within a library that present the
appearance of multiple, separate libraries for purposes of file
management, access by multiple users, or dedication to one or more
host applications. The library must contain at least one unassigned tape
drive and slot to create a partition.

Quantum Scalar i40 and Scalar i80 Users Guide 51


Chapter 4: Configuring the Library
Working With Partitions

There are two ways to create partitions:


Automatically Library resources are assigned proportionately
among the partitions. Tape drives are grouped according to their
interface type (Fibre Channel or SAS) and media generation (LTO-4,
LTO-5). When you automatically create partitions, you add to the
number of existing partitions. You can create partitions
automatically on either the operator panel or the Web client. For
more information, see Automatically Creating Partitions on page 53.
Manually An administrator can create partitions one at a time.
Creating partitions manually gives you more control over resource
allocation. When you manually create partitions, you add to the
number of existing partitions. You can only create partitions
manually on the Web client. For more information, see Manually
Creating Partitions on page 54.
You can modify a partition if you need to change its settings. For
example, the partition name, emulation type, media barcode format (to
report to host), and number of assigned tape drives and slots can be
modified. For information on modifying partitions, see Modifying
Partitions on page 56.
When a partition is no longer needed, it can be deleted. For information
on deleting partitions, see Deleting Partitions on page 57.
Administrators can create, delete, and control access to all library
partitions. Users can be given access to only certain partitions and
denied access to others. For information on changing partition access
for users, see Changing Access to Partitions on page 59.
Details on partitions include:
A partition consists of one tape drive and one slot at a minimum.
The tape drive or slot cannot be shared with another partition.
The default configuration for the library is one partition per unique
tape drive installed in the library, based on interface type (Fibre
Channel or SAS) and media generation (LTO-4, LTO-5).
Partition names are limited to 12 lower-case alphanumeric
characters and underscores (_).
The maximum number of partitions that can be created is equal to
the number of tape drives in the library.
The minimum number of partitions is one (the minimum may be
higher when automatically creating partitions; see Automatically
Creating Partitions on page 53 for details).

52 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 4: Configuring the Library
Working With Partitions

Import/export (I/E) station slots are shared between all partitions.


Partitions take temporary ownership of I/E station slots performing
certain operations, such as importing and exporting cartridges.

Automatically Creating Automatic partitioning assigns available library resources


Partitions proportionately among the partitions, grouping tape drives according
to their interface type (Fibre Channel or SAS) and media generation
(LTO-4, LTO-5).
The library must contain at least one unassigned tape drive and one
unassigned slot to automatically create a partition. If no unassigned
tape drives or slots exist, you must modify or delete one or more
partitions to free up resources. For more information, see Modifying
Partitions on page 56 and Deleting Partitions on page 57.
You can select the number of partitions to create. The maximum
number of partitions that you can create is equal to the number of tape
drives in the library that are not currently assigned to a partition. The
minimum number of partitions you can create automatically is the
number of unique tape drives based on interface type (Fibre Channel
or SAS) and media generation (LTO-4, LTO-5) not currently assigned
to a partition. For example, if your library contains two tape drives, a
Fibre Channel HP LTO-4 and a Fibre Channel HP LTO-5, two partitions is
the minimum because the tape drive generations are different.
You cannot mix tape drive interface types or media generations within a
partition when creating partitions automatically. If you wish to do so,
you must create the partition manually (see Manually Creating Partitions
on page 54).
When the library automatically creates partitions, it assigns the first tape
drive in the partition as the control path. You can change the control
path at any time. See Configuring Control Paths on page 67 more
information.
Before automatically creating partitions, verify that all tape drives are
unloaded and that all cartridges are in their appropriate storage slots.
For information on unloading tape drives, see Unloading Tape Drives on
page 161.

Quantum Scalar i40 and Scalar i80 Users Guide 53


Chapter 4: Configuring the Library
Working With Partitions

Operator Panel
1 Select Setup > Configure Partitions > Auto-Create Partitions.
2 Use the Up and Down buttons to select the number of partitions
you want to create. (If the Up and Down buttons are not available,
you do not have available resources. Modify or delete partitions to
create resources.)
3 Press Apply.
4 Save the library configuration (see Saving the Library Configuration
on page 107).

Web Client
1 Select Setup > Partitions.
2 Click Automatic. (If the Automatic button is not visible, you do not
have available resources. Modify or delete partitions to create
resources.)
The Automatically Create Partitions screen displays.
By default, the library applies the Scalar i40-i80 library emulation
type and Standard media barcode format to each partition. You can
change these settings by modifying the partition after it has been
created (see Modifying Partitions on page 56).
3 Using the Partitions drop-down list, select the number of partitions
to create.
4 Click Apply.
5 Save the library configuration (see Saving the Library Configuration
on page 107).

Manually Creating You can manually create partitions any time after the initial
Partitions configuration of the library. The maximum number of partitions that can
be created is equal to the number of tape drives in the library.
The library must contain at least one unallocated tape drive and one
unallocated slot to manually create a partition. If no unallocated tape
drives or slots exist, you must modify or delete partitions to free
resources. For more information, see Modifying Partitions on page 56
and Deleting Partitions on page 57.

54 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 4: Configuring the Library
Working With Partitions

When the library creates partitions, it assigns the first tape drive in the
partition as the control path. You can change the control paths at any
time. See Configuring Control Paths on page 67 more information.
Before creating partitions, verify that all tape drives are unloaded and
that all cartridges are in their appropriate storage slots. For information
on unloading tape drives, see Unloading Tape Drives on page 161.
You can create partitions manually only on the Web client.

Web Client
1 Select Setup > Partitions.
2 Click Manual.
3 Type a name to describe the new partition into the Enter Name text
box.
4 Select one of the following emulation types from the Emulation
Type drop-down list:
Scalar i40-i80 (default)
ADIC Scalar i500
Quantum Scalar i500
Quantum Scalar i2000
ADIC Scalar i2000
5 Select one of the following media barcode formats (for reporting to
host) from the Set Media Barcode Format drop-down list:
Standard Six Six character barcode number with or without
a one or two-character media ID; for example, XXXXXX
orXXXXXXL4. Only the six character barcode is reported to the
host.
Plus Six Six character barcode number followed by a media
ID; for example, XXXXXXL3. Six character barcode and media
ID are reported to the host.

Quantum Scalar i40 and Scalar i80 Users Guide 55


Chapter 4: Configuring the Library
Working With Partitions

Extended Five to 15 characters total, including a barcode


number and optional media ID. All characters are reported to
the host, regardless of having a media ID or not. If a media ID is
included, the label must have a five to 13 character barcode
followed by a media ID; for example, XXXXXL2 or
XXXXXXXXXXXXXL2. If a media ID is not included, the label
must have a five to 15 character barcode; for example, XXXXX
or XXXXXXXXXXXXXXX.
Media ID Last Five to 13 character barcode number followed
by media ID; for example, XXXXXXXXXXXXXL4. The media ID
is reported to the host last.
Media ID First Five to 13 character barcode number followed
by a two-character media ID, for example;
XXXXXXXXXXXXXL4. The media ID is reported to the host
first, as in L4XXXXXXXXXXXXX.
Standard (default) Five to 15 characters total, including a
barcode number and optional media ID. The media ID is not
reported to the host. If a media ID is included, the label must
have a five to 13 character barcode followed by a media ID; for
example, XXXXXL3 or XXXXXXXXXXXXXL3. If a media ID is
not included, the label must have a five to 15 character barcode;
for example, XXXXX or XXXXXXXXXXXXXXX.
6 Type the number of slots to assign to the new partition into the
Enter Number of Slots text box.
7 Under the Select Drives section, assign one or more available tape
drives to the partition by selecting the check box located to the left
of the tape drive.
8 Click Apply.
9 Save the library configuration (see Saving the Library Configuration
on page 107).

Modifying Partitions You can modify partition settings any time after a partition is created.
For example, you can modify the name, emulation type, media barcode
format, and number of assigned tape drives and slots.
The library automatically takes the partition offline before modifying it
and places it back online after it has been modified.

56 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 4: Configuring the Library
Working With Partitions

The tape drive set as the control path for a particular partition cannot be
deleted from that partition. The check box associated with the control
path is grayed out. For more information on setting the control path,
see Configuring Control Paths on page 67.
Before modifying partitions, verify that all tape drives are unloaded and
that all cartridges are in their appropriate storage slot location. For
information on unloading tape drives, see Unloading Tape Drives on
page 161.
You can modify partitions only on the Web client.

Web Client
1 Select Setup > Partitions.
2 Select a partition and click Modify.
3 Modify any of the settings. For a description of what each setting
means, see Manually Creating Partitions on page 54.
4 Save the library configuration (see Saving the Library Configuration
on page 107).

Deleting Partitions A partition can be deleted when it is no longer needed. After a partition
is deleted, its resources (tape drives and slots) become unassigned and
can be used to create new partitions or added to existing partitions.
Before deleting a partition, unload cartridges from the tape drives
within the partition and then export all cartridges from the partition.
Remove the cartridges from the I/E station after exporting them. For
information on unloading tape drives, see Unloading Tape Drives on
page 161. For information on exporting cartridges, see Exporting Tape
Cartridges on page 158s. You can also remove cartridges by releasing
the magazine and removing them by hand (see Releasing Magazines on
page 148). If you do this, be sure to only remove cartridges assigned to
that partition (see Viewing the Library Configuration Report on
page 210).
After a partition is deleted, its resources (for example, tape drives and
slots) become available and can be reassigned to new or existing
partitions.

Quantum Scalar i40 and Scalar i80 Users Guide 57


Chapter 4: Configuring the Library
Working With Partitions

Deleting a partition does not delete users assigned to that partition.


However, if these users are not assigned to other partitions, they will not
be able to perform any library operations. For information on how to
assign a user to another partition, see Changing Access to Partitions on
page 59.

Note: You may need to modify settings in your host application as a


result of deleting a partition. See your host application
documentation.

You can delete partitions on both the operator panel and the Web
client.

Operator Panel
1 Select Setup > Configure Partitions > Delete Partition.
2 If more than one partition is configured on the library, use the Up
and Down buttons to select a partition from the list.
3 Press Delete.
4 Save the library configuration (see Saving the Library Configuration
on page 107).

Web Client
1 Select Setup > Partitions.
2 Select a partition and click Delete.
3 Save the library configuration (see Saving the Library Configuration
on page 107).

Viewing the Current You can view basic details about all of your partitions, including online/
Partitions offline status, control path tape drive, number of tape drives in the
partition, number of storage slots, and number of I/E station slots
available to the partition.

58 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 4: Configuring the Library
Working With Partitions

Operator Panel
1 Select Reports > Partitions (alternatively, select Setup >
Configure Partitions > View Current Partitions).
2 If more than one partition is configured on the library, select a
partition and press Select.

Web Client
You can view partition information in several places:
Library home page (see Web Client Home Page on page 31)
Library configuration report (see Viewing the Library Configuration
Report on page 210).
Partition modification screen (select Setup > Configure Partitions,
select a partition, and click Modify).

Changing Access to An administrator can control which partitions a specified user can
Partitions access by modifying the users account on the Web client. For more
information, see Working With Local User Accounts and Passwords on
page 79.

Web Client
Select Setup > User Management > User Accounts.

Taking a Partition There are two partition modes: online and offline.
Online or Offline Online SCSI hosts control the partition. In this mode, all host
application SCSI commands are processed.
Offline SCSI hosts cannot control the partition. In this mode,
library operations can be performed via the local or remote user
interface.

Quantum Scalar i40 and Scalar i80 Users Guide 59


Chapter 4: Configuring the Library
Working With Partitions

Changing the partition mode changes whether or not the specified


partition is online or offline to the host application. Changing a
partition mode using the library interface may affect your host
application. See your host application documentation for more
information.

Note: The library automatically turns partitions offline when


performing certain operations, and turns them back online
again when the operation successfully completes. If the
operation fails, the partitions will remain offline until you
manually turn them back online again.

Note: Some maintenance activities require that the entire library be


taken offline. To take the library offline, change the mode of all
partitions from online to offline.

When you are changing the partition mode, be aware of the following:
When you access the Change Partition Mode screen, you will see
only partitions to which you have been given access.
When changing the partition mode from online to offline, all host
application commands in progress at the start of the mode change
are completed.
You can change partition modes from the operator panel or the Web
client.

Operator Panel
1 Select Actions > Change Partition Mode.
The partitions are displayed, along with their online/offline status.
2 If more than one partition is configured on the library, use the Up
and Down buttons to select a partition.
3 Press Modify.
4 Uses the Up and Down buttons to change the mode.
5 Press Apply.

60 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 4: Configuring the Library
Configuring Cleaning Slots

Web Client
1 Select Operations > Partitions > Change Mode.
In the partition table under Mode, the Current column indicates
the current mode of the partition. The New column contains an
Online/Offline button. The button toggles between modes.

Note: If a partition is in use, the Online/Offline button is grayed


out.

2 In the partition table, identify the partition that requires a mode


change.
3 Click the Online/Offline button to toggle to the desired mode.
4 Click Apply.
5 Save the library configuration (see Saving the Library Configuration
on page 107).

Configuring Cleaning Slots


Cleaning slots are used exclusively to store cleaning cartridges.
Configuring one or more cleaning slots enables the librarys AutoClean
feature for all partitions in the library. When AutoClean is enabled, the
library is notified by a tape drive when cleaning is required, and the
library automatically cleans the tape drive using a cleaning cartridge.
You can configure cleaning slots during the initial library configuration
or at any time in the future as long as there are licensed slots available
in the library.
If no licensed slots are available, you must purchase additional slots or
modify or delete a partition to free existing slots (see Working With
Partitions on page 51). Cleaning slots are not assigned to specific
partitions. They are shared by all partitions within a library.
A maximum of four cleaning slots can be configured. Zero cleaning slots
are configured by default.

Quantum Scalar i40 and Scalar i80 Users Guide 61


Chapter 4: Configuring the Library
Configuring Cleaning Slots

Cleaning slots do not need to be configured if you clean tape drives


manually. For more information about manual tape drive cleaning, see
Manually Cleaning Tape Drives on page 169. In addition, you do not
need to configure cleaning slots if you use host-based cleaning.
Cleaning slots are not visible to the host application. To use host-based
cleaning, configure zero cleaning slots in the library and set up your
host application to manage the cleaning process. See your host
application documentation for more information.

Note: If you decrease the number of cleaning slots from what is


currently configured, the extra slots become unassigned and
available to use as storage slots in new or existing partitions.
For information on how to assign available storage slots, see
Manually Creating Partitions on page 54, and Modifying
Partitions on page 56.

Note: If the library contains zero import/export (I/E) station slots, you
will not be able to import or export cleaning cartridges. See
Configuring I/E Station Slots on page 63 for more information.

Note: This operation should not be performed concurrently by


multiple administrators logged in from different locations. You
can access the screen, but you cannot apply changes while
another administrator is performing the same operation.

Operator Panel
1 Select Setup > Dedicated Slots > Cleaning.
2 Press Modify.
3 Use the Up and Down buttons to select a value from zero to 4.
4 Press Apply.
5 Press Exit.
6 Save the library configuration (see Saving the Library Configuration
on page 107).

62 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 4: Configuring the Library
Configuring I/E Station Slots

Web Client
1 Select Setup > Cleaning Slots.
2 Under the New Settings column, select the number of cleaning
slots to configure.
3 Click Apply.
4 Save the library configuration (see Saving the Library Configuration
on page 107).

Configuring I/E Station Slots


I/E station slots are used to import and export tape cartridges into and
out of the library without disrupting normal library operations.
I/E station slots can be configured as either I/E station slots or storage
slots. I/E station slots are used to import and export cartridges and are
shared by all partitions. Storage slots are used to store data cartridges
and cleaning cartridges and are assigned to a single partition.
An I/E station that has been configured for storage may contain
cleaning slots. These cleaning slots must be deleted before you can
reconfigure the storage slots as I/E station slots. You can view the Library
Configuration Report to determine how I/E slots are configured. For
more information, see Viewing the Library Configuration Report on
page 210. For instructions on deleting cleaning slots, see Configuring
Cleaning Slots on page 61.
You cannot configure I/E station slots if cartridges are currently loaded
in the I/E station(s). Remove all cartridges from the I/E station(s) before
attempting the following procedure.
Each I/E station is configured as a complete unit. When configuring an
I/E station, all the slots in the I/E station are configured the same way.
The Scalar i40 and Scalar i80 are configured with 5 I/E station slots by
default.

Quantum Scalar i40 and Scalar i80 Users Guide 63


Chapter 4: Configuring the Library
Configuring I/E Station Slots

On the Scalar i40, you can configure 0, 5, or 20 I/E station slots.


Configured I/E station slots are located in the right magazinefor 5, the
right front 5 are configured. On the Scalar i80, you can configure 0, 5,
10, 20, 25, or 40 I/E station slots. The table below lists slots that will be
configured based on setting selected.

Table 4 Scalar i80 I/E Slot


Configuration
Setting Selected Slots Configured

5 Right top front 5

10 Right top front 5


Right bottom front 5

20 Right top 20

25 Right top 20
Right bottom front 5

40 Right top 20
Right bottom 20

You can configure zero I/E station slots. However, configuring zero I/E
station slots has the following consequences:
You cannot import and export data or cleaning cartridges using I/E
stations.
You cannot manually clean tape drives with a cleaning cartridge
using the operator panel.
You will need to bulk load and bulk unload cartridges, disrupting
library operations (see Bulk Loading Tape Cartridges on page 155).

Note: Before using the I/E station to load and unload cartridges, you
need to unlock the I/E station, which allows you to slide the
magazine out just far enough to access the I/E station slots (see
Unlocking and Opening the I/E Station on page 145).

Caution: Empty I/E station slots before changing the I/E


configuration to avoid tape cartridge ownership confusion.

64 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 4: Configuring the Library
Configuring Tape Drive Parameters

Operator Panel
1 Select Setup > Dedicated Slots > I/E.
2 Press Modify.
3 Use the Up and Down buttons to select a value.
4 Press Apply.
5 Press Exit.
6 Save the library configuration (see Saving the Library Configuration
on page 107).

Web Client
1 Select Setup > I/E Station Slots.
The I/E Station Configuration screen displays. The Current
Settings column lists the number of I/E station slots that are
currently configured.
2 Under the New Settings column, select the number of I/E station
slots to configure.
3 Click Apply.
4 Save the library configuration (see Saving the Library Configuration
on page 107).

Configuring Tape Drive Parameters


You can configure Fibre Channel tape drive loop ID, topology, and speed
using the operator panel or the Web client. On the Web client, you can
also view the actual topology and speed, plus the tape drives world-
wide node name (WWNN) and other information about the tape drives.
You cannot configure SAS tape drive settings. A SAS tape drives SAS
address is automatically and uniquely generated based on a unique
World Wide Name (WWN) that the drive receives when it is configured.
You can view SAS tape drive settings (but not change them) on the Web
client.

Quantum Scalar i40 and Scalar i80 Users Guide 65


Chapter 4: Configuring the Library
Configuring Tape Drive Parameters

Note: If the affected partition is online, it will be taken offline before


the parameters are set, and brought back online after they are
set.

Table 5 Fibre Channel Tape


Drive Configurable Settings Setting Description

Loop ID A unique loop ID is selected by default for all FC tape


drives installed in the library. For example, the tape
drive installed in the top drive bay is assigned a
default loop ID of 61. The tape drive installed in the
bottom drive bay is assigned a default loop ID of 63.
If you change the default loop IDs, make sure each FC
tape drive with a topology setting of Auto (LN), Loop
(L), or Auto (NL) has a unique loop ID.

Requested The requested topology connection mode can be set


Topology* to one of the following:
Auto (LN) Auto-configure trying L-Port first
Loop (L) Force L-Port
Point to Point Force N-Port
Auto (NL) Auto-configure trying N-Port first
(default)

Requested The requested interface speed can be set to Auto


Speed* (default), 1 Gb/s, 2 Gb/s, 4 Gb/s, or 8 Gb/s, depending
on the tape drive.
When you set the speed to 4 Gb/s or 8 Gb/s on the
Web client, a caution message displays informing you
that the speed selection may not be applicable to all
FC tape drives installed in the library. Acknowledge
the message by clicking OK.
* If the requested FC topology and speed settings are not supported, the next
appropriate settings are negotiated. On the Web client, the Setup - Drive
Settings screen displays both the requested and the actual FC topology
connection mode and interface speed. If FC drives are not connected to the
host, the negotiated actual settings appear on the screen as unknown.

66 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 4: Configuring the Library
Configuring Control Paths

Operator Panel
1 Select Setup > Tape Drives (FC).
2 If more than one Fibre Channel tape drive is installed, use the Up
and Down buttons to select a tape drive and press Select.
3 Use the Up and Down buttons to select the item to configure
(Speed, Topology, or Loop ID) and press Modify.
4 Use the Up and Down buttons to scroll through the list of options
until you reach the one you want, then press Apply.
5 Continue to modify as above. When finished, press Exit.
6 Save the library configuration (see Saving the Library Configuration
on page 107).

Web Client
1 Select Setup > Drive Settings.
2 View the SAS tape drive settings, if desired.
3 Make changes to any of the Fibre Channel tape drive settings by
using the drop-down lists to select new values.
4 Click Apply.
5 Save the library configuration (see Saving the Library Configuration
on page 107).

Configuring Control Paths


A control path is the connection between a partition and host
application. The control path connection is made through a designated
tape drive.
When you create a partition, the library automatically assigns the first
tape drive in the partition as the control path. You can modify the
control path at any time.

Quantum Scalar i40 and Scalar i80 Users Guide 67


Chapter 4: Configuring the Library
Configuring Control Paths

Only one tape drive can be selected as the control path per partition. In
the event that the tape drive control path connection to the host
application fails, you can manually select a different control path tape
drive for the partition.

Note: You might need to modify settings in your host application as a


result of modifying the control path. See your host application
documentation for more information.

You can only configure control paths via the Web client.

Web Client
1 Select Setup > Control Path.
2 If more than one partition exists, select a partition and click Next.
3 To select a new control path for the partition, select a tape drive
from the list of tape drives.
4 To delete the control path for the partition, locate the tape drive
that is currently selected as the control path and clear the selection.
5 Click Apply.
6 Save the library configuration (see Saving the Library Configuration
on page 107).

Note: You can configure a control path failover drive if you have an
Advanced Reporting license and HP LTO5 tape drives. See
Working with Control Path Failover (CPF) on page 113

68 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 4: Configuring the Library
Adding or Upgrading Licensable Features

Adding or Upgrading Licensable Features


You can increase the functionality of your library by purchasing licenses
for the following upgrades:
Capacity on Demand (COD)
Advanced Reporting - includes custom reports and logs and Control
Path Failover (CPF) functionality.
Encryption Key Management (EKM)
For more information about these features, see Licensable Features on
page 13.
A license key can be applied to only one library and is tied to the library's
serial number. If the license is not installed when you receive your
library, you will receive a License Key Certificate that contains an
authorization code and instructions on how to obtain your license key
from the Quantum Web site. Once you install the license key on the
library, the feature becomes available.

About License Keys Details about license keys include:


An authorization code to obtain a license key can be used one time
only.
A license key consists of 5 characters randomly selected from the
following allowable characters: a-h, j-n, p-t, v-z, 2-9, and the
ampersand character (@). Alpha characters are always lower case.
A given license key can only be used on the library to which it is
assigned and cannot be transferred to another library. The key is
verified when it is applied to the library to make sure it is the proper
key associated with the library serial number.
License keys do not expire.
Once installed on the library, license keys cannot be removed (unless you
replace the library chassis or system control board (SCB).
If you replace the library chassis: The license key is associated with
the serial number of the library. If you replace your library chassis,
you must replace all your installed license keys. Request replacement
license keys from Quantum.

Quantum Scalar i40 and Scalar i80 Users Guide 69


Chapter 4: Configuring the Library
Adding or Upgrading Licensable Features

If you replace the SCB: The SCB contains information about your
library configuration. If you replace your SCB, you must reinstall your
license key(s) onto the library. You may be able to reinstall them yourself
if you have saved the license keys or can retrieve them from the Web
sites listed above. In some cases, factory installed license keys will not be
listed on the Web site and you will need to contact Quantum Support
for a replacement. If you cannot retrieve your license keys or need
assistance, contact Quantum Support.

Viewing Your License To see the licenses you have purchased and obtained, go to the
Keys following Web site: http://www.quantum.com/licensekeys. The license
history for each feature is listed (feature licensed, authorization code,
and date license key was obtained).

Viewing Installed To see which licenses are installed on your library, go to the following
Licenses screens:

Operator Panel
Select either of the following
Reports > Licenses
Setup > License Installation

Web Client
Select Setup > License.

Obtaining a License Key To obtain your license key for a new feature or upgrade:
1 Contact your Quantum technical sales representative to submit your
order for the feature or upgrade.
2 Upon receipt of your order, Quantum will mail you a license key
certificate containing your authorization code.

70 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 4: Configuring the Library
Adding or Upgrading Licensable Features

3 On your library, locate the serial number. You will need the serial
number to retrieve your license key from the Web site. To locate the
serial number:
On the operator panel, select Reports > About Library.
On the Web client, select Reports > About > Scalar i40/i80.
4 Access the License Key Management Web site: http://
www.quantum.com/licensekeys.
5 Enter the information requested on the screen to obtain your license
key.
You are now ready to apply the license key to the library. See Applying a
License Key on page 71.

Applying a License Key Once purchased, you can apply a license key to the library.

Caution: While you are installing a license key, backup operations


may be interrupted.

Operator Panel

Note: Entering a license key on the operator panel is difficult. It is


recommended that you use the Web client, if possible.

1 Select Setup > License Installation and press Select.


The Current Licenses screen is displayed.
2 Select Add.
The Enter License Key screen is displayed. Five blank digits appear on
the screen. The first digit is highlighted.
3 Use the Up and Down buttons to scroll through the list of letters
and numbers until you reach the letter or number you want. Press
the Right button to advance to the next digit. Repeat for the
remaining digits.
4 When all the digits are entered correctly, press Apply.
5 Press OK.

Quantum Scalar i40 and Scalar i80 Users Guide 71


Chapter 4: Configuring the Library
Working With E-mail Notifications

6 Save the library configuration (see Saving the Library Configuration


on page 107).

Web Client
1 From the Web client, select Setup > License.
2 Type the new license key in the Enter New License Key text box.
3 Click Apply.
4 Refresh your Internet browser. Adding a license can sometimes
affect menu display. Refreshing the browser updates all the menus.
5 Save the library configuration (see Saving the Library Configuration
on page 107).

Working With E-mail Notifications


The library can be configured to automatically send e-mail notifications
to specified e-mail addresses whenever an issue of a particular severity
level occurs with one of its components. The information in the e-mail
notification provides details about the issue and the library conditions at
the time of the error.
Before you can configure e-mail notifications, you must configure the
librarys e-mail account so that the library can send notifications to the
designated recipients. See Configuring the Library E-Mail Account on
page 76 for information on how to configure the e-mail account.
The library supports a maximum of 20 e-mail notification recipients,
including the default Quantum Support e-mail notification. See Creating
E-mail Notifications on page 73 for information on setting up additional
e-mail notifications.
If an e-mail notification is no longer needed, you can delete it. For
information on how to delete an e-mail notification, see Deleting E-mail
Notifications on page 75.

72 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 4: Configuring the Library
Working With E-mail Notifications

There are three e-mail notification filter levels:


All Tickets Notifies e-mail recipients of all tickets.
High and Urgent tickets only Notifies e-mail recipients of high-
severity and urgent tickets.
Urgent tickets only Notifies e-mail recipients of urgent tickets
only.
The library comes with one default e-mail notification recipient, for
Quantum Support. The filter level and e-mail address of the default
technical support notification cannot be modified, but the notification
can be enabled or disabled. It is disabled by default.
Users with administrator privileges can configure the library e-mail
account and e-mail notifications. Users with user privileges can receive
e-mail notifications, but they cannot configure the library e-mail
account or e-mail notifications.
You can view and configure e-mail notifications from the Web client
only.

Creating E-mail Administrators can create e-mail notifications. The library supports a
Notifications maximum of 20 e-mail notification recipients, including the default
support e-mail notification. Each e-mail notification recipient must have
a unique e-mail address.
To set e-mail notifications, you need to provide the e-mail address and
filter level setting for the recipient. For more information on filter levels,
see Working With E-mail Notifications on page 72.
Each e-mail notification includes an optional Comments text box you
can use to enter important system configuration details, such as the
network environment or third-party software applications that interface
with the library. Such information can help technical support personnel
to troubleshoot the library.
You can create e-mail notifications on the Web client only.

Quantum Scalar i40 and Scalar i80 Users Guide 73


Chapter 4: Configuring the Library
Working With E-mail Notifications

Web Client
1 Select Setup > Notification > Setup.
The Setup - System E-mail Notifications screen displays. The
screen lists all e-mail notifications that have been created.
2 Click Create.
The Create System E-mail Notification screen displays.
3 In the Select Filter Level drop-down list, select the filter level to
assign to the e-mail notification. For more information on filter
levels, see Working With E-mail Notifications on page 72.
4 In the Enter E-mail Address text box, type the e-mail address that
you want to receive e-mail notifications.

Note: Do not enter more than one e-mail address in the Enter
E-mail Address text box. If you need to send e-mail
notifications to multiple e-mail addresses, create an e-mail
notification for each e-mail address.

5 In the Enter E-mail Comment text box, type a comment (optional).

Note: Only letters, numbers, spaces, and hyphens are allowed in


this fields. Do not use any special characterslike commas,
apostrophes to name a few.

6 Click Apply.
7 Save the library configuration (see Saving the Library Configuration
on page 107).

Modifying E-mail Administrators can modify existing e-mail notification settings at any
Notifications time after the e-mail notification is created.

Note: The e-mail address of the default technical support notification


(techsup@quantum) cannot be changed, but the notification
can be enabled or disabled.

You can modify e-mail notifications on the Web client only.

74 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 4: Configuring the Library
Working With E-mail Notifications

Web Client
1 Select Setup > Notification > Setup.
The Setup - System E-mail Notifications screen displays. The
screen lists all the e-mail notifications that have been created.
2 Select an address to modify, and click Modify.
The Modify System E-mail Notification screen displays.
3 Modify any of the following settings:
Under the New Settings column, select the Enabled check box
to enable e-mail notification. Clear the Enabled check box to
disable e-mail notification.
Under the New Settings column, select a new filter level from
the Filter Level drop-down list. For more information on filter
levels, see Working With E-mail Notifications on page 72.
In the E-mail Address text box, type a new e-mail address.
In the E-mail Comment text box, type a new comment.

Note: Only letters, numbers, spaces, and hyphens are allowed in


this fields. Do not use any special characterslike commas,
apostrophes to name a few.

4 Click Apply.
5 Save the library configuration (see Saving the Library Configuration
on page 107).

Deleting E-mail Administrators can delete an e-mail notification when it is no longer


Notifications needed.

Note: The default techsup@quantum.com e-mail notification


cannot be deleted, but the notification can be enabled or
disabled. It is disabled by default.

You can delete e-mail notifications on the Web client only.

Quantum Scalar i40 and Scalar i80 Users Guide 75


Chapter 4: Configuring the Library
Configuring the Library E-Mail Account

Web Client
1 Select Setup > Notification > Setup.
2 Select an e-mail notification and click Delete.
A confirmation dialog box displays.
3 Click OK.
4 Save the library configuration (see Saving the Library Configuration
on page 107).

Configuring the Library E-Mail Account


The library uses the library e-mail account whenever library e-mail
services are used, such as when the library automatically sends e-mail
notifications about library issues.
Before configuring the e-mail account, ask your network administrator
for the IP address, valid login account (optional), and valid password
(optional) of your SMTP server. E-mail account settings are not case-
sensitive.

Note: You may use a host name for the SMTP server instead of an IP
address only if the library is set up to use Domain Name System
(DNS) servers. See Default Gateway, Subnet Mask, Network
Prefix, and DNS Addresses on page 43 for more information.

After configuring the e-mail account, you can send a test message to an
e-mail address to verify that the account is configured properly.
You must have administrator privileges to configure the e-mail account.
You can configure the library e-mail account from the Web client only.

Web Client
1 Select Setup > Notification > E-mail Account.
The Setup - E-mail Account screen displays.

76 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 4: Configuring the Library
Configuring the Library E-Mail Account

2 In the SMTP server text box, type the IP address or host name of the
SMTP server.

Note: IP addresses may be entered using the IPv4 dot notation or


using the IPv6 format. IPv4 addresses must be entered in
dot notation (for example, 192.168.0.1). IPv4 address text
boxes do not allow values exceeding 255 for dot-separated
values.

3 In the Sender e-mail address text box, type an e-mail address for
the SMTP server (for example, scalar_i40@mycompany.com). The
sender address indicates the originator of the e-mail message.
4 For Send snapshot with e-mail notifications, do one of the
following:
To attach a library snapshot file to e-mail notifications, select the
check box.
To not attach a library snapshot file to e-mail notifications, clear
the check box.

Note: Send snapshot with e-mail notifications instructs the


library to automatically attach a library snapshot file (ASCII
format) to most e-mail notifications. This feature is turned
off by default. Library snapshot files can also be sent to
specified e-mail addresses using the capture snapshot
operation. The capture snapshot operation allows you to
create the snapshot in ASCII format. See Capturing
Snapshots of Library Information on page 317.

5 For Authentication, do one of the following:


If you do not need to configure login account and password
authentication settings, clear the Authentication check box.
Continue with Step 6.
If you need to configure login account and password
authentication settings, select the Authentication check box.
The Login Account, Password, and Confirm Password text
boxes display. Do the following:
a In the Login Account text box, type the name of a valid
account on the SMTP server (for example, john.user).

Quantum Scalar i40 and Scalar i80 Users Guide 77


Chapter 4: Configuring the Library
Setting Customer Contact Information

b In the Password text box, type the password for the


account that you specified in the Login Account text box.
c In the Confirm Password text box, retype the password to
confirm it.
6 Click Apply.
7 To test the e-mail account, type an e-mail address into the Send a
test e-mail to text box and click Send e-mail. Check the e-mail
account to verify that an e-mail message was sent from the library.
8 Save the library configuration (see Saving the Library Configuration
on page 107).

Setting Customer Contact Information


Administrators can enter contact information into the library for the
person who is the primary customer contact for the library. Keep this
information current to expedite the service process.
When a problem occurs with the library, the contact information is
mailed to techsup@quantum.com along with diagnostic ticket
information, assuming that the default e-mail notification has been
configured (see Creating E-mail Notifications on page 73).
You can set customer contact information from the Web client only.

Web Client
1 Select Setup > Notification > Contact Information.
2 Enter or modify any of the information in the following text boxes:
First Name
Last Name
Company Name
Phone Number
E-mail Address
System Description

78 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 4: Configuring the Library
Configuring the Service Port

3 Click Apply.
4 Save the library configuration (see Saving the Library Configuration
on page 107).

Configuring the Service Port


There are two Ethernet ports on the SCB. The left port is for customer
use for remote access via the Web client, and the right port is for service
use only. The default service port IP address is 192.168.177.1.
You should never change the service port subnet unless it happens to
conflict with the subnet configured for the customer port. Incorrectly
setting the service port subnet could impact connectivity of the
customer port and network traffic attached to the customer port, even
when the service port is disconnected. If there is a subnet conflict you
must change the service port subnet to avoid ambiguity between the
two interfaces.
The instructions below explain how to change the IP address on the
service port. You can only change the subnet (third octet) of the IP
address: 192.168.xxx.1. The other sections must remain as they are. You
may choose a number from 1 to 255.
You can only configure the service network from the operator panel.

Operator Panel
1 Select Tools > Service Network.
Under Modify Subnet the three-digit octet of the IP address is
highlighted.
2 Use the Up and Down buttons to scroll to the desired subnet, and
press Apply.
For more information on scrolling, see Navigating and Editing on
the Operator Panel on page 27).

Note:

3 Press OK.

Quantum Scalar i40 and Scalar i80 Users Guide 79


Chapter 4: Configuring the Library
Working With Local User Accounts and Passwords

4 Save the library configuration (see Saving the Library Configuration


on page 107).

Working With Local User Accounts and Passwords


Administrators can create and modify two types of local user accounts:
user and administrator. These users have different library privilege levels
and can access different things. The Web client requires user accounts
and user logins; the operator panel does not. You can configure the
operator panel to run with logins required. You can also configure the
library to use Lightweight Directory Access Protocol (LDAP) accounts.
This section covers:
Using the Web Client Default Administrator Account on page 80
Privilege Levels on page 81
Creating Local User Accounts on the Web Client on page 82
Modifying Local User Accounts on the Web Client on page 83
Deleting Local User Accounts on the Web Client on page 84
Enabling and Creating Passwords on the Operator Panel on page 84
Disabling Passwords on the Operator Panel on page 87
Resetting Passwords on the Operator Panel on page 88
You must have administrator privileges to create, modify, and delete
local user accounts.

Using the Web Client The library ships with a default administrator account for use on the
Default Administrator Web client. The default administrator account has the following
Account settings:
User name: admin
Password: password.

80 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 4: Configuring the Library
Working With Local User Accounts and Passwords

The first time you access the library via the Web client, when you see the
Login screen, type admin in the User name text box and type password in
the Password text box. As soon as you complete the initial library setup,
you should change the password on the default administrator account.
For information on changing passwords, see Modifying Local User
Accounts on the Web Client on page 83.

Note: You cannot delete the default administrator account or modify


the user name. You can, however, change the password.

Note: If you misplace the password for the default administrator


account, contact Quantum Support (see Getting More
Information or Help on page xxvii).

Privilege Levels Privilege levels are manually assigned to user accounts created within
the library. Controlling access to screens and operations within the
library preserves the integrity of the library and the data that is stored in
it.

Note: If passwords are not enabled on the operator panel, all users
have access to all privileges. See Enabling and Creating
Passwords on the Operator Panel on page 84.

Three types of users are defined in Scalar i40 and Scalar i80 libraries:
Administrators have access to the entire physical library and all of
its partitions. The library ships with a default administrator account.
The user name for the default administrator account is admin and
the password is password. You cannot modify or delete the user
name for the default administrator account, but you can modify the
password. If you misplace the password for the default
administrator account, contact Quantum Support.
For security purposes, an administrator can prevent a service user
from logging on to the library remotely, from either the Web client
or over the Ethernet service port. The service user will still be able to
log in to the library from the operator panel interface. For more
information, see Remote Service Login on page 105.

Quantum Scalar i40 and Scalar i80 Users Guide 81


Chapter 4: Configuring the Library
Working With Local User Accounts and Passwords

Users have access to portions of the Actions, Operations, and


Reports menus. Users cannot access the Setup and Tools menus.
Users can perform functions within a partition (such as performing
cartridge and tape drive operations), but cannot perform operations
that affect the physical library (such as creating or deleting
partitions).
On the Web client, users can only perform operations and view
reports within partitions to which they have been granted
access.
On the operator panel, users can perform actions and view
reports for all partitions.
Service users have access to the entire physical library and all of its
partitions as well as to service-only functions. Each library has only
one service user account. When a service user logs in, all other active
users are automatically logged out.

Creating Local User During or after the initial configuration, you can use the default
Accounts on the Web administrator account to create additional local user accounts, including
Client other accounts with administrator privileges. These administrators can
themselves create other local administrator and user accounts. Users
without administrator privileges cannot create user accounts. The library
can contain a total of eighteen user/administrator accounts, including
the default administrator account.

Web Client
1 Select Setup > User Management > User Accounts.
2 Click Create.
The Create User Account screen displays.
3 Enter User Name - Type a name for the local user account. User
names are limited to 112 lower-case letters, numbers, and
underscores (_). For example: john_usa.
4 Enter Password - Type a password for the local user account.
Passwords are limited to 616 lower-case alphanumeric characters
and can also include underscores (_), periods (.), hyphens (-),
asterisks (*), and the at symbol (@). For example: pass_19.
5 Confirm Password - Retype the password.

82 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 4: Configuring the Library
Working With Local User Accounts and Passwords

6 Select Privilege - Select a local user account privilege level by


selecting either Admin or User. For more information on users and
administrators, see Privilege Levels on page 81.
7 If the new local user account was given user privileges, click Next.
The Create User Account - User Name screen displays, where User
Name is the name of the user account. This screen lists all library
partitions.
8 Select the library partitions that you want the user to access.
9 Click Apply.
10 Save the library configuration (see Saving the Library Configuration
on page 107).

Modifying Local User After a local user account has been created, administrators can modify
Accounts on the Web the account settings, such as the password, privilege level, and partition
Client access. You cannot modify the user name. Instead, you will need to
delete the user account and create a new one (see Deleting Local User
Accounts on the Web Client on page 84).

Web Client
1 Select Setup > User Management > User Accounts.
The Setup - Users screen displays.
2 Select a user account and click Modify.
The Modify User Account screen displays, where User Name is the
name of the local user account.
3 Enter your Admin password to verify you have privileges to modify
the account.
4 Enter new password for selected user name: - Optionally, type a
new password. Passwords are limited to 616 lower-case
alphanumeric characters and can include also include underscores
(_), periods (.), hyphens (-), asterisks (*), and the at symbol (@).
For example: pass_19.
5 Confirm new password for selected user name:- Retype the
password.
6 Select Privilege:- Optionally, change privilege level.

Quantum Scalar i40 and Scalar i80 Users Guide 83


Chapter 4: Configuring the Library
Working With Local User Accounts and Passwords

7 If the user account has user privileges and you want to modify
partition access, click Next.
The Modify User Account - User Name screen displays, where User
Name is the name of the user account. This screen lists all library
partitions, with the users assigned partitions checked.
8 Modify any of the partition selections.
9 Click Apply.
10 Save the library configuration (see Saving the Library Configuration
on page 107).

Deleting Local User Administrators can delete other local administrator and user accounts
Accounts on the Web when they are no longer needed.
Client
Note: You cannot delete the default administrator account.

Web Client
1 Select Setup > User Management > User Accounts.
The Setup - Users screen displays.
2 Select a user account and click Delete.
A confirmation dialog box displays.
3 Click OK.
4 Save the library configuration (see Saving the Library Configuration
on page 107).

Enabling and Creating If you do not set passwords on the operator panel, all users will have
Passwords on the access to all functions, including administrator and service functions. If
Operator Panel you want to restrict access to some users, you must set passwords on
the operator panel.

84 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 4: Configuring the Library
Working With Local User Accounts and Passwords

Passwords on the operator panel are disabled by default. Once you


enable and configure passwords on the operator panel, all users must
enter a password on the operator panel to log in. In addition, the
service login is automatically enabled and users with user or admin
privileges cannot access service functions. The service password is only
available to Quantum Support personnel.
Passwords on the operator panel are completely different and separate
from passwords on the Web client. On the Web client, you can create
and set up to 18 unique user accounts with different user names,
passwords, privileges, and partition access. On the operator panel, only
three unique accounts names are allowed, and the user names and
privileges cannot be changed (the only things you can change are the
passwords on the user and admin accounts). The accounts and
corresponding privilege levels are:

Account Privilege Level

admin Administrator

user User

service Service Only service users may use this


account. You cannot change the password for
this account.

See Privilege Levels on page 81 for a description of administrator and


user privileges.
In order to use logins and passwords, you must set the passwords for at
least the admin account. You can only do this via the operator panel.
You can enable just the admin password (and NOT the user password).
However, you cannot enable just the user password.

Operator Panel
You start out by creating the admin account password. Once created,
you are logged out and need to log back in using the admin password.
Then you can create the user account password.
1 Select Setup > Account Settings > Password Settings.
Admin Password is highlighted.

Quantum Scalar i40 and Scalar i80 Users Guide 85


Chapter 4: Configuring the Library
Working With Local User Accounts and Passwords

2 Press Modify.
Disabled is now highlighted.
3 Press the Up button to change the setting to Enabled.
4 Press Apply.
5 You are prompted to create the password. The password is a 4-digit
code (no letters or other characters). The first digit of the code is
highlighted. Use the Up and Down buttons to select a number for
the first digit, then press Right to go to the second digit. As you
move off the digit you created, it displays as a # symbol so that only
the digit you are working on displays actual numbers. If you need to
view or change a digit, press the Left button.
6 When you are finished creating the admin password, press Right
until the Validate Password prompt appears. Re-enter the
password the same way you created it. When finished, press Apply.
A confirmation screen displays.
7 Press OK.
The library logs the session out and the operator panel displays the
login screen, with the User ID of admin highlighted.
8 Press Apply to go to the password line.
9 Using the directional buttons, enter the admin password you
created and press Apply.
10 Select Setup > Account Settings > Password Settings.
11 Press the Down button to highlight User Password and press
Modify.
Disabled is highlighted.
12 Press the Up button to change the setting to Enabled.
13 Press Apply.
14 Create and validate the user password the same way you created
the admin password above.
15 Save the library configuration (see Saving the Library Configuration
on page 107).

86 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 4: Configuring the Library
Working With Local User Accounts and Passwords

Disabling Passwords on If you no longer want to use passwords on the operator panel, you can
the Operator Panel disable them. Once you disable the admin password, the user password
is also automatically disabled. You can only do this on the operator
panel.

Operator Panel
1 Select Setup > Account Settings > Password Settings.
Admin Password is highlighted.
2 Press Modify to modify the Admin password.
Enabled is now highlighted.
3 Press the Down button to change the setting to Disabled.
4 Press Apply.
5 Save the library configuration (see Saving the Library Configuration
on page 107).

Modifying Passwords Once passwords are created, you can modify them.
on the Operator Panel
Operator Panel
1 Select Setup > Account Settings > Modify Password.
2 Use the Up and Down buttons to select admin or user.
3 Press Apply.
4 Enter the current password and press Apply.
5 Enter a new password and press Apply.
6 Re-enter the new password to validate it and press Apply.
7 Save the library configuration (see Saving the Library Configuration
on page 107).

Quantum Scalar i40 and Scalar i80 Users Guide 87


Chapter 4: Configuring the Library
Working With LDAP User Accounts (Remote Authentication)

Resetting Passwords on If you forget your operator panel passwords and cannot log in, you
the Operator Panel must reset the passwords. Resetting the passwords disables them and
deletes both the admin and user passwords. This means that no login is
required to access the operator panel. You can re-create the passwords
again as needed.
You can only reset operator panel passwords via the Web client.

Web Client
1 Select Setup > User Management > Reset Operator Panel
Passwords.
2 Click Apply.

Working With LDAP User Accounts (Remote


Authentication)

Local Authentication vs. Local authentication control is managed on the library. An administrator
Remote Authentication sets up accounts and privileges on the library. To use local
authentication, a user must enter a local user name and password.
Remote authentication is managed by a Lightweight Directory Access
Protocol (LDAP) server. Enabling LDAP allows existing user accounts
residing on an LDAP server to be integrated into the librarys current
user account management subsystem. User account information is
centralized and shared by different applications, simplifying user
account management tasks.
To use remote authentication, you must enable LDAP on the library.
Once LDAP is enabled, users can log into the library using either LDAP or
local authentication. To use LDAP authentication, a user must enter a
directory service user name and password. The Web client Login screen
displays the Remote Authentication login option only when LDAP is
enabled. See Logging in When LDAP or Kerberos is Enabled on
page 138.
LDAP logins are only available on the library Web client.

88 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 4: Configuring the Library
Working With LDAP User Accounts (Remote Authentication)

LDAP Server Guidelines The following groups must be created on the LDAP server to enable
remote login on the library:
Library User Group Assign users to this group who need user-
privilege access to the library. Enter the name of this group in the
Library User Group field on the Setup - Remote Authentication
screen on the library Web client (see Configuring LDAP on the
Library on page 90).
Partition Groups For LDAP users with user privileges, access to
library partitions is determined by group assignment on the LDAP
server. Groups must be created on the LDAP server with names that
match the library partitions names (names must match but are not
case sensitive). Users with user privileges must be assigned to these
groups on the LDAP server to have access to the corresponding
partitions on the library.
Library Admin Group Assign users to this group who need
administrator-privilege access to the library. LDAP users with
administrator privileges have access to all partitions and
administrator functions and do not need to be assigned to
partition-related groups on the LDAP server. Enter the name of this
group in the Library Admin Group field on the Setup - Remote
Authentication screen on the library Web client (see Configuring
LDAP on the Library on page 90).
You will need to have at least one user assigned to both the Library User
Group and the Library Admin Group on the LDAP server in order to test
the LDAP settings on the library (see Testing LDAP Settings on page 94).
Since most normal users will not be members of both these groups, you
may need to create a special or temporary user specifically for this
purpose.

Quantum Scalar i40 and Scalar i80 Users Guide 89


Chapter 4: Configuring the Library
Working With LDAP User Accounts (Remote Authentication)

Configuring Secure You can configure Secure LDAP using one of two methods (do not use
LDAP on the Library both).
LDAPS Uses Secure Sockets Layer (SSL) over a specific port for
LDAP (636). You may enable LDAP over SSL (LDAPS) by entering a
URI in the form of ldaps://hostname in the Server URI field. This
will use SSL to send secure communication via port 636. If the LDAP
server does not support LDAPS or does not have LDAPS enabled,
then login operations will fail. LDAPS has been deprecated in favor
of using StartTLS (see option below). Do not use LDAPS if you are
using StartTLS. Once you apply LDAPS, StartTLS will not be available.
StartTLS Uses Transport Layer Security (TLS) over the same port as
regular LDAP (389). Select the StartTLS check box to configure
secure LDAP communication using TLS. If TLS mode is not
supported on your LDAP server, then login operations will fail. Do
not use StartTLS if you are using LDAPS.
Additionally, if you are using one of these Secure LDAP methods listed
above, you can also Install a TLS CA certificate for additional verification
that the LDAP server has not been compromised. The certificate must be
the same certificate that is installed on your LDAP server and must be in
.pem format. The library will only perform the verification if you have
configured Secure LDAP (using either LDAPS or StartTLS). Place a copy of
the certificate file in an accessible location on your computer and use
the Browse button to locate and install it.
Once a certificate is installed, you can remove it by checking the
Remove TLS CA Certificate check box. This check box only becomes
available once a certificate is installed. The presence of this check box
lets you know that a certificate is installed. Refer to Figure 14 LDAP
Setup Example on page 93.

Configuring LDAP on Administrators can enable and configure Lightweight Directory Access
the Library Protocol (LDAP). LDAP is the industry standard Internet protocol that
provides centralized user account management.
Administrators can add, delete, and modify only local user account
information. The library Web client does not allow you to create,
modify, or delete user account information on an LDAP server. This must
be done by the directory service provider. For more information on
working with local user accounts, see Working With Local User Accounts
and Passwords on page 79.

90 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 4: Configuring the Library
Working With LDAP User Accounts (Remote Authentication)

The library supports all LDAP servers. You can also use Kerberos for
added security. For specific instructions on configuring Kerberos, see
Configuring Kerberos on page 94.

Web Client
1 Select Setup > User Management > Remote Authentication.
The Setup - Remote Authentication screen displays.
2 Under Authentication Type, do one of the following:
To enable LDAP, select LDAP and continue with Step 3.
To disable LDAP, select Local Only and continue with Step 4.
To modify LDAP configuration settings, continue with Step 3.
3 Obtain the following LDAP parameters from your network
administrator and enter them in the fields provided:
Server URI The Uniform Resource Identifier (URI) of the LDAP
server where user account information is stored. The URI
includes the LDAP server host name or IP address and can
include the LDAP server network port. Port 389 is the default.
Examples:
ldap://hostname:389
ldap://10.50.91.103
ldap://mycompany.com
LDAPS - Optional. See Configuring Secure LDAP on the Library
on page 90.
StartTLS - Optional. See Configuring Secure LDAP on the Library
on page 90.
Install TLS CA Certificate Optional. See Configuring Secure
LDAP on the Library on page 90.
Principal An LDAP user login ID with permissions to search
the LDAP directory. The library logs into LDAP using this ID.
For an example, see Figure 14 on page 93.
Password The password for the principal authorization login
ID.

Quantum Scalar i40 and Scalar i80 Users Guide 91


Chapter 4: Configuring the Library
Working With LDAP User Accounts (Remote Authentication)

User DN The Fully Qualified Distinguished Name that contains


the users.
For an example, see Figure 14 on page 93
Group DN The Fully Qualified Distinguished Name that
contains the groups.
For an example, see Figure 14 on page 93
Library User Group The name of the group on the LDAP server
associated with library users who have user-level privileges (see
Privilege Levels on page 81 for more information on user
privilege levels). This group must exist on your LDAP server (see
LDAP Server Guidelines on page 89).
For an example, see Figure 14 on page 93
Library Admin Group The name of the group on the LDAP
server associated with library users who have administrator-level
privileges (see Privilege Levels on page 81 for more information
on user privilege levels). This group must exist on your LDAP
server (see LDAP Server Guidelines on page 89).
For an example, see Figure 14 on page 93
A sample of a completed dialog box is depicted below:

92 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 4: Configuring the Library
Working With LDAP User Accounts (Remote Authentication)

Figure 14 LDAP Setup Example

4 Click Apply to apply any changes.


If you enabled LDAP or modified LDAP settings, the Test Settings
button is activated.
5 Click the Test Settings button to test all the new or changed LDAP
settings. See Testing LDAP Settings on page 94 for more
information.
6 Save the library configuration (see Saving the Library Configuration
on page 107).

Quantum Scalar i40 and Scalar i80 Users Guide 93


Chapter 4: Configuring the Library
Working With LDAP User Accounts (Remote Authentication)

Testing LDAP Settings The Test Settings button tests communication between the library and
the LDAP server, and tests the currently applied LDAP settings. If there
are any problems, an error message identifies the problem area.
If you change the LDAP settings, click Apply before using this button.
Otherwise, any changes you made will be lost and will not be tested.
To test the settings, you must enter a user name and password, then
click the button. The user you use for the test must be a member of both
the Library User Group and the Library Admin Group on the LDAP server.
Since most normal users will not be members of both these groups, you
may need to create a special or temporary user specifically for this
purpose.
After configuring LDAP settings, save the library configuration.

Configuring Kerberos Use Kerberos if you want extra security with remote authentication.
You can configure the Kerberos settings any time after the initial
library configuration. Before you can configure Kerberos, you need to
generate the service keytab file on your Kerberos (AD) server. For
instructions, see Generating the Kerberos Service Keytab File on
page 96.
You must have administrator privileges to configure Kerberos.
You can only configure Kerberos on the Web client.

Web Client
1 Make sure that both the library and the Kerberos/Active Directory
server are set to the same time (within 5 minutes). Otherwise, the
authentication will fail. It is recommended that you use Network
Time Protocol (NTP) to synchronize the time between the library and
the Kerberos server. See Setting the Date and Time Using the
Network Time Protocol on page 49.
2 Select Setup > User Management > Remote Authentication.
The Setup - Remote Authentication screen displays.

94 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 4: Configuring the Library
Working With LDAP User Accounts (Remote Authentication)

3 Under Authentication Type, do one of the following:


To enable Kerberos, select LDAP with Kerberos and continue
with Step 4.
To disable Kerberos, select LDAP or Local Only and continue
with Step 6.
To modify Kerberos configuration settings, continue with
Step 4.
4 Fill the following Kerberos fields:
Realm The Kerberos realm name, typed in all uppercase
letters. Usually the realm name is the DNS domain name.
Example: MYCOMPANY.COM
KDC (AD Server) The key distribution center (in other words,
the server on which Kerberos/Active Directory is installed).
Example: mycompany.com:88
Domain Mapping The domain portion of the librarys fully
qualified domain name.
Example: mycompany.com
Service Keytab Click the Browse button to select the service
keytab file. The service keytab file is a file you generate on your
Kerberos/Active Directory server. If you have not already
generated this file, do so now. For instructions, see Generating
the Kerberos Service Keytab File on page 96. Then click the
Browse button to upload the file.
5 Configure the LDAP settings as described in Configuring LDAP on
the Library on page 90.
6 Click Apply to apply any changes.
7 If you enabled LDAP or Kerberos, or modified LDAP or Kerberos
settings, click the Test Settings button to test all the new or
changed LDAP settings. See Testing LDAP Settings on page 94 for
more information.
8 Save the library configuration (see Saving the Library Configuration
on page 107).

Quantum Scalar i40 and Scalar i80 Users Guide 95


Chapter 4: Configuring the Library
Working With LDAP User Accounts (Remote Authentication)

Generating the These instructions are for generating the service keytab file for use with
Kerberos Service Keytab Microsoft Active Directory. If you not using Active Directory, refer to
File your Kerberos vendor for instructions on generating this file.
1 Set up an Active Directory domain on the Windows 2003 server.
2 If Active Directory is not already configured, run dcpromo.
3 Windows 2003 servers only: Install Windows Support Tools on the
Windows 2003 server as follows:
a Go to www.microsoft.com and search for windows server
2003 support tools sp2 or click on the following link:
http://www.microsoft.com/downloads/
details.aspx?FamilyID=96a35011-fd83-419d-939b-
9a772ea2df90&DisplayLang=en
b Download both support.cab and suptools.msi.
c Run suptools.msi to begin installation.
4 Create a computer account in Active Directory.
Do not select any of the check boxes during creation.
The account name will be used for <computer account> fields
shown in the following steps.
5 At the command prompt, map SPN to the computer account. Use
the following format:
setspnAlibrary/<fqdnoflibrary><computer
account>
For example:
setspnAlibrary/delos.dvt.mycompany.comkerbtest
6 At the command prompt, create the keytab file for the SPN. Use one
of the following formats:
For Windows 2003:
ktpassoutlibrary.keytabprinc
library/<fqdnoflibrary>@<realm>
+rndPassptypeKRB5_NT_SRV_HSTcryptoRC4
HMACNTmapUser<realm>/computers/<computer
account>

96 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 4: Configuring the Library
Setting the Session Timeout

For example:
ktpassoutlibrary.keytabprinclibrary/
delos.dvt.mycompany.com@OURREALM.LOCAL
+rndPassptypeKRB5_NT_SRV_HSTcryptoRC4
HMACNTmapUserourrealm.local/computers/
kerbtest
For Windows 2008:
ktpassoutlibrary.keytabprinclibrary/
<fqdnoflibrary>@<realm>
+rndPassptypeKRB5_NT_SRV_HSTcryptoAES256
SHA1
mapUser<realm>/computers/<computeraccount>
For example:
ktpassoutlibrary.keytabprinclibrary/
delos.dvt.mycompany.com@OURREALM.LOCAL
+rndPassptypeKRB5_NT_SRV_HSTcryptoAES256
SHA1
mapUserourrealm.local/computers/kerbtest

Setting the Session Timeout


The library automatically logs out a user or administrator when the
library has detected no activity for a specified length of time. This
always occurs on the Web client, and will occur on the operator panel if
passwords are enabled (see Enabling and Creating Passwords on the
Operator Panel on page 84). The default session timeout is 15 minutes.
You can change that to 30, 45, or 60 minutes. You can only change this
setting on the operator panel.

Quantum Scalar i40 and Scalar i80 Users Guide 97


Chapter 4: Configuring the Library
Configuring System Settings

Operator Panel
1 Select Setup > Account Settings > Session Timeout.
The current timeout setting is highlighted.
2 Use the Up and Down buttons to select the desired timeout.
3 Press Apply.
4 Save the library configuration (see Saving the Library Configuration
on page 107).

Configuring System Settings


You can enable/disable the following system settings on the operator
panel:
Unload Assist
Logical Serial Number Addressing
Manual Cartridge Assignment
SNMP
SMI-S
Power Save

Unload Assist When Unload Assist is enabled, the library will unload tape drives when
a move command from the tape drive is received. When Unload Assist is
disabled, the tape drive must be unloaded prior to a move command, or
the move command will fail. This setting is enabled by default.

Operator Panel
1 Select Setup > System Settings > Unload Assist.
2 Press Modify.
3 Use the Up and Down buttons to select Enabled or Disabled and
press Apply.

98 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 4: Configuring the Library
Configuring System Settings

4 Make another selection or press Exit.


5 Save the library configuration (see Saving the Library Configuration
on page 107).

Logical Serial Number The library uses the actual tape drive serial numbers by default (logical
Addressing SN addressing is disabled). Enabling logical SN addressing enables the
library to assign logical serial numbers to all tape drives in the library.
Specifically, the library assigns a logical serial number to a tape drive in a
specific location, not the serial number of the particular tape drive. If
the tape drive is then replaced by another tape drive in the same library
location, the logical serial number remains the same. From the host
applications perspective, the replacement tape drive is the same as the
original. This setting is disabled by default.

Caution: If you change the logical serial number addressing setting,


you must power cycle the library (perform a shutdown and
press the power button) or remove and replace each tape
drive in the library in order for the change to take effect.

Operator Panel
1 Select Setup > System Settings > Logical SN Addr.
2 Press Modify.
3 Use the Up and Down buttons to select Enabled or Disabled and
press Apply.
4 Make another selection or press Exit.
5 Power cycle the library.
6 Save the library configuration (see Saving the Library Configuration
on page 107).

Quantum Scalar i40 and Scalar i80 Users Guide 99


Chapter 4: Configuring the Library
Configuring System Settings

Manual Cartridge Administrators can disable or enable (default setting) manual cartridge
Assignment assignment. When manual cartridge assignment is enabled, the I/E
Assign screen automatically displays on the operator panel once
cartridges are placed into the I/E station. The I/E Assign screen prompts
you to assign the cartridges to a specific partition. The cartridges can
then be used only by the assigned partition.
When manual cartridge assignment is disabled, the I/E Assign screen
does not display on the operator panel, and the cartridges in the I/E
station are visible to all partitions, as well as the System partition, and
can be used by any partition.
The manual cartridge setting is enabled by default. You can only change
this setting on the operator panel.

Understanding Host Application Notification


When manual cartridge assignment is enabled, SCSI Unit Attention 6/
2801 notifies the host application when the I/E station has been
accessed, allowing the host to automatically detect the presence of
media in the I/E station and update its I/E station status information.
When manual cartridge assignment is disabled, host notification via
SCSI Unit Attention 6/2801 depends on the number of configured
partitions:
If multiple partitions are defined, the host application is not notified
when the I/E station has been accessed. Media presence in the I/E
station is reported to any partition requesting it.
If a single partition is defined, the host application is notified when the
I/E station has been accessed. Media presence is reported to the sole
defined partition, as well as to the System partition, when either of
these partitions checks for changes in the status of the I/E station.
For information about using the host to perform tape operations, see
your host application documentation.

Operator Panel
1 Select Setup > System Settings > Man Cart Assign.
2 Press Modify.
3 Use the Up and Down buttons to select Enabled or Disabled and
press Apply.

100 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 4: Configuring the Library
Configuring System Settings

4 Make another selection or press Exit.


5 Save the library configuration (see Saving the Library Configuration
on page 107).

SNMP Enables or disables SNMP traffic to the library. This setting is enabled by
default.

Operator Panel
1 Select Setup > System Settings >SNMP.
2 Select the setting you want to modify and press Modify.
3 Use the Up and Down buttons to select Enabled or Disabled and
press Apply.
4 When finished making all changes, press Exit.
5 Save the library configuration (see Saving the Library Configuration
on page 107).

SMI-S Allows you to enable or disable SMI-S running on the library. This
setting is disabled by default.

Operator Panel
1 Select Setup > System Settings > SMI-S.
2 Press Modify.
3 Use the Up and Down buttons to select Enabled or Disabled and
press Apply.
4 Make another selection or press Exit.
5 Save the library configuration (see Saving the Library Configuration
on page 107).

Quantum Scalar i40 and Scalar i80 Users Guide 101


Chapter 4: Configuring the Library
Configuring System Settings

Power Save To help save power, the operator panel goes dark after a period of
inactivity on the operator panel (meaning, no buttons have been
pressed). The default period is 30 minutes. You can set this period to 15
minutes, 30 minutes, 45 minutes, 60 minutes, or never.
To immediately restore the operator panel screen once it has gone dark,
press any of the four navigation buttons on the library.
The operator panel will restore when any of the following happens:
Any navigation button is pressed.
The Assign I/E screen displays (see Manual Cartridge Assignment on
page 100).
Tape drives start to autolevel.
The library receives a signal to shut down.
Library health (diagnostic ticket) status changes.
Library ready status changes.
The operator panel will NOT go dark when:
The library is initializing.
Tape drives are autoleveling.
The Assign I/E screen is displayed (see Manual Cartridge Assignment
on page 100).
An operator panel-initiated operation is in progress (such as IVT).
The Setup Wizard is displayed.
Passwords are enabled on the operator panel and a user is logged
in.
The power save timeout value is set to NEVER.

Operator Panel
1 Select Setup > System Settings > Power Save.
2 Press Modify.
3 Use the Up and Down buttons to select the desired setting and
press Apply.

102 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 4: Configuring the Library
Configuring Security Settings

Configuring Security Settings


You can enable/disable the following security settings on the operator
panel:
Network Interface
SSH Services
Internet Control Message Protocol (ICMP)
Remote Access Via Web Client
Remote Service Login
SNMP V1/V2
SSL

Network Interface Enables or disables all external access to the library. This setting is
enabled by default to allow external access.

Operator Panel
1 Select Setup > Security Services > Network IF.
2 Press Modify.
3 Use the Up and Down buttons to select Enabled or Disabled and
press Apply.
4 Make another selection or press Exit.
5 Save the library configuration (see Saving the Library Configuration
on page 107).

Quantum Scalar i40 and Scalar i80 Users Guide 103


Chapter 4: Configuring the Library
Configuring Security Settings

SSH Services Enables or disables Secure Shell (SSH) services, such as SSH, from
accessing the library. This setting is enabled by default.

Operator Panel
1 Select Setup > Security Services > SSH Services.
2 Press Modify.
3 Use the Up and Down buttons to select Enabled or Disabled and
press Apply.
4 Make another selection or press Exit.
5 Save the library configuration (see Saving the Library Configuration
on page 107).

Internet Control Enables or disables external attempts to discover the library by pinging
Message Protocol it (by means of the ICMP Echo packets. This setting is enabled by
(ICMP) default.
You may disable this feature if you are using IPv4, but you should NOT
do so if you are using IPv6. Disabling this feature disables all IPv6
communication on the Scalar i40 and Scalar i80. There will be no error
messages, and the library will appear to be working, but it will not be
communicating.

Caution: Do NOT disable ICMP if you are using IPv6!

Operator Panel
1 Select Setup > Security Services > ICMP.
2 Press Modify.
3 Use the Up and Down buttons to select Enabled or Disabled and
press Apply.
4 Make another selection or press Exit.
5 Save the library configuration (see Saving the Library Configuration
on page 107).

104 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 4: Configuring the Library
Configuring Security Settings

Remote Access Via Web Enables or disables remote access to the library via the Web client. This
Client setting is enabled by default (meaning remote access is allowed).

Operator Panel
1 Select Setup > Security Services > Web client.
2 Press Modify.
3 Use the Up and Down buttons to select Enabled or Disabled and
press Apply.
4 Make another selection or press Exit.
5 Save the library configuration (see Saving the Library Configuration
on page 107).

Remote Service Login Enables or disables remote service user login (from the Web client or
over the Ethernet service port). The service user will still be able to log in
to the library from the operator panel. This setting is enabled by default
(meaning remote service login is allowed).

Operator Panel
1 Select Setup > Security Services > Service User
2 Press Modify.
3 Use the Up and Down buttons to select Enabled or Disabled and
press Apply.
4 Make another selection or press Exit.
5 Save the library configuration (see Saving the Library Configuration
on page 107).

SNMP V1/V2 This topic is discussed in Enabling SNMP Versions on page 46.

Quantum Scalar i40 and Scalar i80 Users Guide 105


Chapter 4: Configuring the Library
Configuring Security Settings

SSL Allows you to enable Secure Socket Layer (SSL) for secure data
transmission between the library and remote clients. This setting is
disabled by default.
Enabling SSL encrypts all Web browser connections to the Web client,
and it enables SSL-based authentication for SMI-S. SMI-S is the newest
standard of SNMP, which makes sets of data continuously available. For
more information about SMI-S on the library, see SMI-S on page 101.
Disabling SSL creates an unencrypted connection from a Web browser
to the Web client.
See the Quantum Intelligent Libraries SMI-S Reference Guide
(6-01317-xx) for further configuration and access details.

Note: Before enabling SSL, make sure you enter a name for the library
in the Host Name text box when configuring network settings
(Setup > Network Management > Network on the Web
client; see Library Host Name on page 41). After enabling SSL,
use that host name to access the library. If you do not use that
name, you will receive a security alert. In addition, make sure to
complete all the text boxes listed on the Web client Contact
Information screen (Setup > Notification > Contact
Information) before enabling SSL. This information is used to
identify company information in the SSL certificate.

Operator Panel
1 Select Setup > Security Services > SSL.
2 Press Modify.
3 Use the Up and Down buttons to select Enabled or Disabled and
press Apply.
4 Make another selection or press Exit.
5 Save the library configuration (see Saving the Library Configuration
on page 107).

106 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 4: Configuring the Library
Saving and Restoring the Library Configuration

Saving and Restoring the Library Configuration


The library has many configurable items, such as tape drive IDs,
partitions, user accounts, import/export (I/E) stations, and cleaning slots.
In the event of a hardware failure or firmware upgrade, the save and
restore operations can be used to restore the librarys configurable
items to a previous state. The save/restore operation also saves and
restores library firmware and license keys installed on the library.

Note: The save/restore operations should not be performed


concurrently by multiple administrators logged in from
different locations. You can access the screens, but you cannot
apply changes while another administrator is performing the
same operation.

Saving the Library This operation saves your current library configuration and library
Configuration firmware.
It is recommended that you save the library configuration after
modifying a configurable item and before upgrading firmware. This
allows you to restore the most current settings if necessary.
Save your library configuration when it is in a known working state. In
the event of a hardware failure, the saved configuration can be used to
restore the configuration after hardware repairs are made.
Before initiating a firmware upgrade, you should save the library
configuration. You then have the option to restore the configuration
after either a successful or an unsuccessful upgrade.
You can only save the configuration from the Web client.

Web Client
1 Select Tools > Save/Restore Configuration.
2 Select Save System Configuration.

Quantum Scalar i40 and Scalar i80 Users Guide 107


Chapter 4: Configuring the Library
Saving and Restoring the Library Configuration

3 Click Apply.
4 When the operation completes successfully, complete the next
screens to save the file to a known location.

Restoring the Library You can restore the librarys configurable items to a previous state using
Configuration a saved configuration file. If you updated the library firmware since last
saving the configuration, the library automatically restores the library
firmware to the version that was saved with the configuration.

Caution: After you restore the librarys configuration, verify that


your drive firmware version reflects the desired firmware
level.

Note: You can also downgrade library firmware to an earlier version


using the Tools > Update Library Firmware command (see
Updating Library Firmware on page 299). Note that you will
lose all your current library configuration information except
for network settings, date and time, and license keys. You can
restore the other configurable items using a configuration file
that was saved when the earlier version of library firmware was
installed on the library, or you can reconfigure your librarys
settings.

You can only restore the library configuration via the Web client.

Web Client
1 Select Tools > Save/Restore Configuration.
2 Select Restore System Configuration.
3 Click Apply.
4 Use the next screens to browse to the saved configuration file and
upload it to the library.
This operation saves your current library configuration and library
firmware.
5 Verify the drive firmware level, and if necessary, manually upgrade
to the desired firmware level.

108 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 4: Configuring the Library
Registering the Library

Registering the Library


Registering the library activates the warranty. After completing the
initial setup of the library, choose Setup > Register Library on the Web
client to access the online product registration form.
You cannot register the library from the operator panel.

Web Client
Select Setup > Register Library.

Changing Operator Panel Home Screen View


From the operator panel, you may choose to change the default home
screen to an alternate home screen that facilitates easy I/E unlock
access, displays the number of I/E slots and the number of I/E slots that
are full.
Changes to the home screen can be made only from the operator panel.
Refer to Figure 9 on page 23.

Changing to Alternate 1 Select Setup > System Settings and press Select.
Home Screen 2 Select Alternate Home and press Modify.
3 Select Up to choose Unlock I/E, and press Apply.
4 Select Exit twice to return to the alternate home screen.

Note: From the alternate home screen, selecting Menu returns you to
the default home screen. To return to the alternate home
screen, select Actions > Alternate Home, and press Select.

The Alternate Home Screen as shown in Figure 9 displays.

Quantum Scalar i40 and Scalar i80 Users Guide 109


Chapter 4: Configuring the Library
Changing Operator Panel Home Screen View

Unlocking the I/E is described in Unlocking and Opening the I/E Station
on page 145.

Returning to Default 1 From the alternate home screen, select Menu to return to the
Home Screen default home screen.
The default home screen is displayed temporarily, however upon
power cycle will display the alternate home screen until reset
permanently.
2 To reset to view the default home screen permanently, select
Setup > System Settings and press Select.
3 Select Alternate Home and press Modify.
4 Select Down and press Apply.
Select Exit twice to return to the default home screen.

110 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 5
Advanced Reporting

Advanced Reporting is a licensable feature. You must have an Advanced


Reporting license installed on your library in order to use the features
described in this chapter. For more information on licensing, see Adding
or Upgrading Licensable Features on page 69.
The Advanced Reporting license applies to your entire library, regardless
of library size. This means you only need to purchase the license once. If
you increase the size of your library, your existing license applies to your
new library configuration.

Note: You can work with Advanced Reporting Data using only the
Web client.

This chapter covers:


Advanced Reporting Features
Working with Control Path Failover (CPF)
Using Advanced Reporting Reports
Configuring the Drive Resource Utilization Report
Configuring the Media Integrity Analysis Report
Using Advanced Reporting Templates
Loading and Reloading Advanced Reporting Data
Deleting Advanced Reporting Data

Quantum Scalar i40 and Scalar i80 Users Guide 111


Chapter 5: Advanced Reporting
Advanced Reporting Features

Saving and E-mailing Advanced Reporting Data Filess


Working with the Media Security Log
Viewing the Media Usage Log
Automatically E-mailing Advanced Reporting Reports and Logs

Advanced Reporting Features


The Advanced Reporting license provides the following library features:
Control Path Failover (CPF) - Provides support for configuring the HP
LTO-5 Fibre Channel (FC) drive for control path failover. To configure a
control path failover drive, you must also have an Advanced Reporting
license. When control path failover is used, one drive is assigned as the
primary control path and another drive as the control path failover
(secondary) drive. The control path failover drive is used whenever the
primary control path drive fails or is inoperable.
Reports - Listed below are Advanced Reporting report names. You can
view, configure, send via e-mail, and save and reuse report
configurations as templates. In addition, you can automatically e-mail
any of the reports to designated recipients at specified, scheduled times.
Drive Resource Utilization Report - Provides tape drive usage
information, showing you which tape drives are working at
optimum capacity and which are under-utilized. This report can help
you allocate your tape drive resources properly.
Media Integrity Analysis Report - Provides TapeAlert count for various
combinations of tape drives, tape cartridges, and TapeAlert flags.
This report can help you determine if a problem is due to a specific
tape drive or tape cartridge.
Logs - Listed below are available logs:
Media Security Log - Lists media that has been removed from the
library.
Media Usage Log - Lists media usage information regarding capacity,
and read and write errors for media ever mounted in a drive.-

112 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 5: Advanced Reporting
Working with Control Path Failover (CPF)

Required Firmware To use all the features of Advanced Reporting, you should install the
latest released version of library firmware on your library. For
information on installing library firmware, see Updating Library
Firmware on page 299.

Working with Control Path Failover (CPF)


If an HP LTO-5 FC tape drive is the control path for a partition, you can
select another HP LTO-5 FC tape drive in that partition for control path
failover. This means that if the control path tape drive fails, the failover
tape drive becomes the control path for the partition. The failed-over
tape drive remains the control path for the partition unless it fails or the
library is restarted. When either of these events occurs, the library starts
over and attempts to use the original control path tape drive as the
control path, and the original failover tape drive for failover.
The control path and failover tape drives are assigned by location in the
library, so even if you replace a tape drive with another HP LTO-5 FC tape
drive, the library will still fail over or revert to the specified location.

Prerequisites To configure control path failover, you must have the following setup on
your library:
Advanced Reporting License. Refer to Adding or Upgrading
Licensable Features on page 69.
The control path and failover tape drives must both be HP LTO-5 FC
tape drives, and you must have a minimum of two drives in a single
partition.
The control path and failover tape drives must have their topology
configured as Point to Point. Refer to Configuring Tape Drive
Parameters on page 65.
The control path and failover tape drives must be connected to an
NPIV-enabled switch on the same fabric. They must not be
connected to an FC I/O blade.

Quantum Scalar i40 and Scalar i80 Users Guide 113


Chapter 5: Advanced Reporting
Working with Control Path Failover (CPF)

When control path failover is configured for a partition, the partition


uses a virtual port as the control path communication port. The World
Wide Port Name (WWPN) for this virtual port is listed in the librarys
System Information Report in the Library Partitions section under
Control Path (see Viewing System Information on page 206).

Configuring CPF You can configure control path failover from the Web client only.

Web Client
1 Setup the drive topology.
Set the topology for the control path and control path failover tape
drives to Point to Point. For more information, refer to Configuring
Tape Drive Parameters on page 65.
a Select Setup > Drive Settings.
The Setup - Drive Settings screen displays.

Figure 15 Setup - Drive


Settings Screen

b For the appropriate partition, select the Requested Topology of


Point to Point from the drop down menu.
c Click Apply.

114 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 5: Advanced Reporting
Working with Control Path Failover (CPF)

2 Select Setup > Control Path.


The Control Path screen displays for that partition.

Figure 16 Setup - Control Path


Screen

3 Select the Failover drive by clicking the Failover option.


4 Click Apply.
You can also manually force a failover (see Forcing CPF on page 116).

Quantum Scalar i40 and Scalar i80 Users Guide 115


Chapter 5: Advanced Reporting
Working with Control Path Failover (CPF)

Forcing CPF Web Client


You can manually force a control path failover. You might want to force
a failover to check that the control path on the non-active tape drive is
operational, or to switch back to the original control path tape drive
once the issue that originally caused the failover has been fixed.
1 Click Tools > Drive Operations.
The Tools - Drive Operations screen displays.

Figure 17 Tools - Drive


Operations Screen for CPF

2 Select Force Control Path Failover and click Next.


The Force Control Path Failover screen displays (see Figure 18
below). All of the partitions that have control path failover enabled
are listed. The location and status of the tape drive that is currently
serving as the control path are listed in the Active columns. The
location and status of the tape drive that is currently serving as the
standby control path are listed in the Standby columns. For each
partition, the following information is listed:

Column Indicates

Active Drive Location of the current control path tape


drive.

Active Status Ready status of the current control path


tape drive.

116 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 5: Advanced Reporting
Working with Control Path Failover (CPF)

Column Indicates

Active Connected Whether the current control path tape drive


is connected and has a working link.

Standby Drive Location of the standby tape drive.

Standby Status Ready status of the standby tape drive.

Standby Whether the standby tape drive is


Connected connected and has a working link.

Figure 18 Force CPF Screen

3 Select the partition on which you want to force the failover, and
click Apply.

Note: The standby tape drive must be ready and connected


in order to force a failover.

4 Click Apply.
The new active tape drive location displays in the Active Drive
column. The new standby tape drive location displays in the
Standby Drive column.

Note: If the new tape drive locations do not display, refresh the
browser.

Quantum Scalar i40 and Scalar i80 Users Guide 117


Chapter 5: Advanced Reporting
Using Advanced Reporting Reports

Using Advanced Reporting Reports


The following notes will help you interpret the data listed on the
reports.
The data for the reports is collected in log files. When the log files
reach their maximum size, the oldest information is deleted as new
information is added. This may affect how much historical data you
can access.
The on-screen reports contain a chart and a data table. When the
log files are large, it would take an excessively long time to load all
the historical data into the data table. For this reason, the table
displays a maximum of 1000 rows of data, beginning with the most
recent, even if more data is available. (The chart displays
information for the entire range.) To view all of the data, you need
to save or e-mail the data file. See Saving and E-mailing Advanced
Reporting Data Files on page 125.
The reports are built according to data in the log files, not your
current library configuration. For this reason, your library may
contain tape drives or cartridges that do not show up in the report.
Similarly, the report may contain tape drives and cartridges that no
longer reside in the library.
Information about a tape drive, cartridge, or operation is not
recorded in the Drive Resource Utilization log file until after a tape
cartridge has been mounted (loaded) and unmounted (unloaded)
from the tape drive.
To see the exact values of each item in the displayed chart, move
your mouse so that it hovers over the item you wish to see. An
information bubble displays with the values listed in it. If you click
on a bar, point, or slice, the information bubble locks in place and
the hovering feature turns off until you reload the chart. The
hovering feature does not work when the value equals zero.
Values of zero do not appear in Pie charts.

118 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 5: Advanced Reporting
Using Advanced Reporting Reports

Configuring the Drive This report identifies how tape drive resources are utilized in your
Resource Utilization library. You can use this report to help you determine the proper work
Report load distribution between the tape drives in your library.
The following information is collected for each tape drive installed in the
library:
Drive location (module, row)
Drive serial number
Partition
Megabytes read
Megabytes written
Time and date of mount (UTC)
Time and date of dismount (UTC)
Media motion time (in seconds)
Tape cartridge barcode
You can only access this report from the Web client.
Web Client
1 From the library menu bar, select Reports > Advanced Reporting >
Drive Resource Utilization.

The Drive Resource Utilization Report configuration page opens.


This may take several minutes.
2 Configure the report by specifying the following:
Date Range Specifies the range of time covered by the report.
Choose Last 7 days; Last 4 weeks (default); Last 3 months; or All
History (as far back as there is data in the log file).
Attribute Specifies which value is included in the report.
Select one of the following:
Data Written/Read (default) The amount of data written
to and read from each tape drive, shown separately in the
chart.
Total Read and Write The combined total amount of data
written to and read from each tape drive.

Quantum Scalar i40 and Scalar i80 Users Guide 119


Chapter 5: Advanced Reporting
Using Advanced Reporting Reports

Media Mount Count The number of tape cartridge


mounts.
Media Mount Time The total amount of time media
spent in the selected drive(s).
Media Motion Time The total amount of time media
spent in motion while in the tape drive (writing, reading,
rewinding, etc.).
Chart How the data is displayed in the chart. Choose Area,
Bar (default), Line, or Pie.
Type The chart type. Select one of the following:
Rollup (default) Displays the Grouping on the x-axis and
the Attribute amount on the y-axis.
Trend Shows how the Attribute amount changes over
time for the selected Grouping.
Grouping Specifies which tape drive(s) or partition(s) to
include in the report. Select one of the following:
All Drives by Coordinate (default) Presents the sum total
of the selected attribute for all tape drives according to their
location in the library. If more than one tape drive resided in
that location during the selected range, then the attribute
values for all the tape drives that resided in that location are
combined in the chart.
All Drives by Physical SN Presents the sum total of the
selected attribute for all drives according to the physical
tape drive serial number.
All Partitions Presents a comparison of all drives grouped
by partition in the physical library.
Selected Drive by Coordinate The report chart is based on
an individual tape drive location in the library. If more than
one tape drive resided in that location during the selected
range, then the attribute values for all the tape drives that
resided in that location are combined in the chart.
Selected Drive by Physical SN The report chart is based on
an individual tape drive identified by its physical drive serial
number.
Selected Partition The report chart is based on an
individual partition in the physical library.

120 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 5: Advanced Reporting
Using Advanced Reporting Reports

Note: See Installed Tape Drive Location Coordinates on


page 9 for an explanation of the location coordinates.

3 Click Next.
The report is generated and displays on the screen.

Configuring the Media This report provides TapeAlert counts for various combinations of tape
Integrity Analysis drives, tape cartridges, and TapeAlert flags. You can use this report to
Report help determine if a problem is due to a specific tape drive or tape
cartridge.
The Media Integrity Analysis report collects the following information
for each TapeAlert:
Date/Time
Tape drive physical serial number
Cartridge barcode
TapeAlert value
TapeAlert Description
You can only access this report from the Web client.

Web Client
1 From the library menu bar, select Reports > Advanced Reporting >
Media Integrity Analysis.

The Media Integrity Analysis Report configuration page opens. This


may take several minutes.
2 Configure the report by specifying the following:
Date Range Specifies the range of time covered by the report.
Choose Last 7 days; Last 4 weeks (default); Last 3 months; or All
History (as far back as there is data in the log file).
AttributesSpecifies which values are included in the report,
and how they are combined. Select in any combination,
including all (default) and none. If you select no attributes, the
chart displays the TapeAlert count for the selected Grouping.

Quantum Scalar i40 and Scalar i80 Users Guide 121


Chapter 5: Advanced Reporting
Using Advanced Reporting Reports

Cartridge Barcode All relevant tape cartridges.


Drive Physical SN All relevant tape drives.
TapeAlert The TapeAlert flags that were issued. For a
description of all TapeAlert flags, see Appendix B, Tape Alert
Flag Descriptions.
Chart How the data is displayed in the chart. Choose Area,
Bar (default), Line, or Pie.
Type The chart type. Select one of the following:
Rollup (default) Displays the number of TapeAlerts for the
combination of Grouping and Attributes you selected
(default).
Trend Shows the occurrence of TapeAlerts over time.
GroupingSpecifies which drive(s) or tape cartridge(s) on
which to base the report. Choose one of the following:
All (default) All tape drives and tape cartridges for which
a TapeAlert was issued during the specified range.
Selected Drive by Physical SN An individual tape drive.
Only tape drives which issued a TapeAlert during the
specified range appear in the report.
Selected Cartridge by Barcode An individual tape
cartridge. Only tape cartridges that were associated with a
TapeAlert during the specified range appear in the report.
Sorting Specifies how the data will be sorted. Choose from
the following:
Alphabetical
Count (ascending)
Last Occurrence (default)
3 Click Next.
The report is generated and displays on the screen.

122 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 5: Advanced Reporting
Using Advanced Reporting Reports

Using Advanced If you want to use the same configuration repeatedly, you can save it as
Reporting Templates a template. You can save up to 20 templates for each type of advanced
report.
You can only work with templates from the Web client.

Web Client

Creating or Accessing a Template


1 From the menu bar, select Reports > Advanced Reporting, and
then select the desired report.
The configuration screen for that report appears.
2
3 For a new template, in the Report Templates box at the bottom of
the screen, type a name for the template in the empty field next to
the Save button. The name can have a maximum of 15 characters.
You can use only lowercase letters, numbers, and the underscore
character (_) in template names.

Figure 19 Template and Report


Data Functions

1 Loads the selected template.

2 Template drop-down list.

3 Deletes the selected template.

4 Saves a report configuration as a template.

5 Type name of new report here.

6 Reloads the data from the library log file to the Internet browser.

Quantum Scalar i40 and Scalar i80 Users Guide 123


Chapter 5: Advanced Reporting
Using Advanced Reporting Reports

7 Lists the number of records currently loaded in the Internet browser for this report.

8 Deletes all the Advanced Reporting data.

4 Click Save.
The report appears in the drop-down list next to the Load button.

Using a Saved Template


To use a saved template, select the template from the drop-down list
and click Load.

Deleting a Template
To delete a template, select the template from the drop-down list and
click Delete.

Loading and Reloading When you first open an Advanced Report configuration screen, the
Advanced Reporting system loads all the data from the library log file for that report to the
Data Internet browser in preparation for creating your reports. If there is a lot
of information in the log files, this may take several minutes.
The data that is loaded in the Internet browser remains unchanged until
you log out of your library session or reload the data. If new data is
added to the library log file during your session (for example, a
TapeAlert occurs), it will not appear in the on-screen report until you
either log out of the library and log on again, or reload the data.
To reload the data without logging out, click the Reload button on the
reports configuration page. This action reloads the entire data for that
report, which may again take several minutes.
You can see how many records were loaded from the log files for this
report by looking at the Report Data section of the Report Configuration
page. A note says XX records read, where XX is the number of records
(see Figure 20 on page 125).

124 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 5: Advanced Reporting
Using Advanced Reporting Reports

Deleting Advanced In some circumstances, you may wish to delete the information
Reporting Data contained in the log files used to build the advanced reports. To do this,
click the Delete button in the Report Data section of either report
configuration pagesee Figure 20 on page 125. This action deletes the
data for both the Drive Resource Utilization report and the Media
Integrity Analysis report.

Caution: Once you delete the data in the log files, you cannot get it
back. The Reload button does NOT retrieve deleted data! It
is recommended that you save all the data for both the
Drive Resource Utilization report and the Media Integrity
Analysis report before deleting the data (see Saving and E-
mailing Advanced Reporting Data Files on page 125).

Figure 20 Report Data Buttons

Saving and E-mailing You cannot save the report as it appears on the screen, but you can save
Advanced Reporting or e-mail the report data as a comma-separated values (.csv) file. You
Data Files can then import the .csv data into a spreadsheet program and
manipulate it to create your own reports for analysis. The .csv file
contains all of the data in the log file that falls within the date range
you specify.
You can only access this report from the Web client.

Web Client
1 Generate a report.
2 Scroll down to the bottom of the report viewing screen to a box
titled Retrieve the Report Data File. See Figure 21 on page 126.
3 To save the report data as a.csv file, click Save.

Quantum Scalar i40 and Scalar i80 Users Guide 125


Chapter 5: Advanced Reporting
Working with the Media Security Log

4 To e-mail the report data as a .csv file, type the name of a recipient
in the empty field next to the E-mail button, then click E-mail.

Figure 21 Saving and E-


mailing the Report Data

Working with the Media Security Log

Note: You must have an Advanced Reporting license to use this


feature.

Media removal is detected by the library when it performs an inventory


(at boot up, for example). The media security log lists media that have
been removed from the library. You can configure the library to collect
any or all of the following media removal events for the log.
Unexpected Removal Detection After Power-up and Reboot Only
Unexpected Removal Detection During Library Operation
Expected Removal Detection From I/E Slots During Library Operation
Unexpected removal refers to tape cartridges that were removed from
the library without being exported properly via the I/E station.
Expected removal refers to tape cartridges that were exported properly
via the I/E station.
By default, all the options are disabled and the library collects nothing.
You must enable at least one of the options for the library to begin
collecting data. The log only lists media that is completely removed
from the library. It does not list media that moves from one location to
another within the library.

126 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 5: Advanced Reporting
Working with the Media Security Log

The log file contains the following information:


Date and time of media removal
Tape cartridge barcode
Type of removal (expected or unexpected)
Slot location coordinates (of the slot the cartridge is missing from)
Slot type (I/E, storage, or cleaning)
When the log file reaches its maximum size, the oldest information is
replaced as new information is added.
You can access and configure this log from only the Web client.

Configuring Media You can choose to collect data in a log to list the following conditions
Security that occur in your library:
Unexpected removal of media after a power-up and reboot
Unexpected removal of media during library operation
Expected removal of media from I/E Slots during library operation
Once configured, the library issues diagnostic tickets for the selected
conditions, and collects the media removal conditions in the logs. To
configure the Media Security, do the following:
You can only access this report from the Web client.

Web Client
1 Select Setup > Notifications > Advanced Reporting > Media Security.
The Setup - Advanced Reporting Media Security screen displays.
2 Click to enable any or all of the options.
Unexpected Removal Detection After Power-Up and Reboot
Only
Unexpected Removal Detection During Library Operation
Expected Removal Detection From I/E Slots During Library
Operation

Note: These options are disabled by default.

Quantum Scalar i40 and Scalar i80 Users Guide 127


Chapter 5: Advanced Reporting
Working with the Media Security Log

3 Click Apply.
The Progress Window displays. The Progress Window contains
information on the action, elapsed time, and status of the
requested operation.
If Success appears in the Progress Window, the operation
completed successfully. Click Close to close the Progress
Window.
If Failure appears in the Progress Window, the operation did
not successfully complete.
4 To view the Media Security Log, select Reports > Log Viewer and
then select Media Security Log.

Viewing, Saving, and E- Using the Web client, you can view, save, or e-mail the Media Security
mailing Media Security Log.
Log You can only access this report from the Web client.

Web Client
1 Select Reports > Log Viewer.
2 Select Media Security Log from the list of logs and click Next.
The report displays in a new window for viewing.
3 You can save or e-mail the report following the on-screen
instructions.

Note: If you want to e-mail the log file to a recipient, type the
recipients name in the text box next to the E-mail button,
and then click the E-mail button. You must have your e-
mail notification configured in order to e-mail a log file.
See Configuring the Library E-Mail Account on page 76 for
more information.

128 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 5: Advanced Reporting
Viewing the Media Usage Log

Viewing the Media Usage Log


The Media Usage Log lists information regarding data written and read
on the media and lists statistics pertaining to soft and hard read and
write errors. The media usage log collects information on all media that
have ever been in the library, including media that are no longer in the
library. Lifetime media usage metrics are associated with the cartridge
and are kept on the embedded cartridge memory.
The log reflects what the drive reports from the embedded cartridge
memory whenever the media is unloaded. If the tape cartridge was
never mounted and unloaded, it will not appear in the log. When the
log file reaches its maximum size, old information is deleted as new
information is added. This may affect the amount of available historical
data.
The log provides the following information:
Volser Media cartridge barcode label
SN Media cartridge serial number
Mfr Media cartridge manufacturer
Date Media cartridge manufacturing date (format: YYYYMMDD)
Type Media type
Mounts Cartridge mount count
RRE Recovered read errors
URE Unrecovered read errors
RWE Recovered write errors
UWE Unrecovered write errors
LW Cartridge lifetime MB written
LR Cartridge lifetime MB read
Enc Cartridge encryption status (U=Unknown, E=Encrypted,
N=Not Encrypted)
You can access and configure this log from only the Web client.

Quantum Scalar i40 and Scalar i80 Users Guide 129


Chapter 5: Advanced Reporting
Automatically E-mailing Advanced Reporting Reports and Logs

Web Client
1 To view, save, or e-mail the report, select Reports > Log Viewer.
2 Select Media Usage Log from the list of logs and click Next.

Automatically E-mailing Advanced Reporting Reports


and Logs
You can configure the library to automatically e-mail Advanced
Reporting logs and reports to specified recipients on a daily or weekly
basis.

Note: Before the library can send e-mail notifications, you must
configure the library e-mail account. For information on how to
configure the e-mail account, see Configuring the Library E-
Mail Account on page 76.

You can create up to 20 e-mail recipients. If you want to send the same
recipient a different set of reports, you can enter the same e-mail
address more than once, with different reports selected for each. Each
entry counts as a unique recipient toward the 20 total.

130 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 5: Advanced Reporting
Automatically E-mailing Advanced Reporting Reports and Logs

Note: Duplicate entries are not allowed. A duplicate entry means the
same recipient is set to receive the exact same reports in two
different entries, regardless of the day or time. If you have
duplicate recipients, make sure that the reports selected in
each entry are not an exact match.

For example, if you have one entry in which Recipient A receives


the Drive Utilization and Media Integrity reports on Monday,
you cannot create another entry to send Recipient A the Drive
Utilization and Media Integrity reports on Thursday. Instead,
you can create one entry for Recipient A and send the reports
every day (select Daily as the day to send the report), or you can
change the reports you are sending so that they are not the
same as the first entry. You could create three entries for
Recipient A as follows: 1) send both reports out on Monday; 2)
send Drive Utilization out on Thursday; and 3) send Media
Integrity out on Thursday (in a different entry). The recipient is
the same, but the reports sent in each entry are different.

Each e-mail notification includes an optional comment text box you can
use to enter information about the library or the reports and logs that
you want the recipient to know. This information appears in the body of
the e-mail.
You can modify the settings of an existing e-mail notification at any time
after it is created. If an e-mail notification is no longer needed, you can
delete it.
Administrators can configure the library e-mail account and e-mail
notifications. Users with user privileges can receive e-mail notifications,
but they cannot configure the library e-mail account or e-mail
notifications.

Creating a Recipient Web Client


1 Select Setup > Notifications > Advanced Reporting > Receiver
Addresses.

The Setup - Advanced Reporting Receiver Addresses screen displays.

Quantum Scalar i40 and Scalar i80 Users Guide 131


Chapter 5: Advanced Reporting
Automatically E-mailing Advanced Reporting Reports and Logs

2 Click Create.
The Setup - Advanced Reporting Receiver Address Configuration
screen displays. The screen lists all Advanced Reporting e-mail
notifications that have been created, along with the day/time the e-
mail is scheduled to be sent, and which reports and logs will be
sent.

132 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 5: Advanced Reporting
Automatically E-mailing Advanced Reporting Reports and Logs

3 Under Select Reports, select the check box of the report(s) and
log(s) you want to send.
4 Under Notification Day & Time, there are two drop-down lists.
From the first drop-down list, select the day of the week you want
to send the e-mail, or select Daily to send every day. From the
second drop-down list, select the time of day to send the e-mail
(hourly, using a 24-hour clock).
5 In the E-mail Address field, enter the recipient's e-mail address.
6 In the E-mail Comment field, enter a comment that will be sent in
the body of the e-mail (optional).

Note: Only letters, numbers, spaces and hyphens are allowed in


this fields. Do not use any special characterslike commas,
apostrophes to name a few.

7 Click Apply.
8 On the Success window, click Close.

Quantum Scalar i40 and Scalar i80 Users Guide 133


Chapter 5: Advanced Reporting
Automatically E-mailing Advanced Reporting Reports and Logs

9 Save the library configuration. For instructions on how to save the


library configuration, see Saving the Library Configuration on
page 107.

Modifying a Recipient Web Client


1 Select Setup > Notifications > Advanced Reporting > Receiver
Addresses.

The Setup - Advanced Reporting Receiver Addresses screen displays.


2 Click Modify.
3 Change any of the settings and click Apply.
4 On the Success window, click Close.
5 Save the library configuration. For instructions on how to save the
library configuration, see Saving the Library Configuration on
page 107.

Deleting a Recipient Web Client


1 Select Setup > Notifications > Advanced Reporting > Receiver
Addresses.

The Setup - Advanced Reporting Receiver Addresses screen displays.


2 Select a recipient and click Delete.
3 On the Confirmation window, click OK.
Save the library configuration. For instructions on how to save the
library configuration, see Saving the Library Configuration on
page 107.

134 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 6
Performing Library
Operations

This chapter explains how to access and operate your library. Most of
the library functions described here can be found on the Operations
menu of the Web client, or the Actions menu of the operator panel.
This chapter covers:
Logging In
Logging Out
Shutting Down, Restarting, Turning Off, and Removing Power
Emergency Power-off Procedure
Unlocking and Opening the I/E Station
Releasing Magazines
Performing Media Operations
Cleaning Tape Drives
Taking a Tape Drive Online or Offline

Quantum Scalar i40 and Scalar i80 Users Guide 135


Chapter 6: Performing Library Operations
Logging In

Logging In
All users, service users, and administrators must log in to the library to
perform library functions or view library operations. (Exception: If
passwords are not configured on the operator panel, login to the
operator panel is not required.)

Simultaneous Logins Multiple users can be logged in to the library at the same time. The
same user can be logged from multiple locations. Note that multiple
users logged in from different locations cannot make changes to
configuration settings or perform certain library functions
simultaneously. The screens are visible, but access is denied. Whichever
one is logged in first has access to the screen until they exit the screens.

Logging in for the First When you first boot up the library, the operator panel does not require
Time you to log in. (In fact, if you do not configure passwords for the
operator panel, you never need to log in to the operator panel; see
Enabling and Creating Passwords on the Operator Panel on page 84 for
more information.)
To log in to the Web client for the first time:
1 Make note of your librarys IP address. From the operator panel,
select Reports > Network Settings to display the IP address.
2 Enter the IP address in your Internet browser to bring up the Web
client login screen.
3 Enter the default user name and password:
Default user name: admin
Default password: password
4 Click OK.
After you log in for the first time, change the password for the default
admin account. See Modifying Local User Accounts on the Web Client
on page 83.

136 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 6: Performing Library Operations
Logging In

Note: If you misplace the password for the default admin account,
contact Quantum Support. For contact information, see
Getting More Information or Help on page xxvii.

Logging in Using the If passwords have not been set on the operator panel, you do not need
Operator Panel to log in, and all operations are allowed to all users. It is recommended
that you set passwords on the operator panel (see Enabling and
Creating Passwords on the Operator Panel on page 84).
If passwords have been set on the operator panel, there are three
possible user IDs: admin, user, and service. Log in as follows:
1 At the login screen, use the Up and Down buttons to select admin,
user, or service.
2 Press Apply.
3 Enter the first digit of the password using the Up and Down
buttons to scroll to the correct number, then press Right to go to
the next digit. Enter the rest of the digits in the same way.

Note: Only the digit you are currently modifying displays an


actual number. When you finish one digit and move to the
next, the completed digit displays as a cross-hatch symbol
(#).

4 When finished entering all digits, press Apply.

Note: If you misplace the password for the operator panel logins, you
can clear operator panel passwords via the Web client (see
Resetting Passwords on the Operator Panel on page 88).

Logging in Via the Web 1 Establish an Internet connection to the library by typing the librarys
Client IP address into your Internet browser.
If you do not know your librarys IP address, you can find it on the
operator panel by selecting Reports > Network Settings.
2 At the login screen, enter a user name and its associated password
and click OK.

Quantum Scalar i40 and Scalar i80 Users Guide 137


Chapter 6: Performing Library Operations
Logging Out

Logging in When LDAP When LDAP or Kerberos is enabled, the Web client Login screen displays
or Kerberos is Enabled a Remote Authentication check box. Log in as follows:
Select the Remote Authentication check box to log in using a
directory service user name and password.
Clear the Remote Authentication check box to log in using a local
user name and password.
For more information on LDAP, see Configuring LDAP on the Library on
page 90.
For more information on Kerberos, see Configuring Kerberos on
page 94.

Logging Out
Logging out secures the library from being accessed by unauthorized
users. Log out whenever you have finished accessing the library.

Note: You will only be able to log out of the operator panel if
passwords have been configured (see Enabling and Creating
Passwords on the Operator Panel on page 84).

Note: Clicking the close button (X) in the upper-right corner of the
Web client closes the browser window but does not log you
out.

Note: All users are logged out automatically after a configurable


period of inactivity. The default timeout period is 15 minutes,
but you can change this (see Setting the Session Timeout on
page 97).

Operator Panel
1 Select Actions > Logout.
2 Press Yes to confirm.

138 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 6: Performing Library Operations
Shutting Down, Restarting, Turning Off, and Removing Power

Web Client

1 Click the Logout button in the upper right corner of the screen,
or select Operations > Log Out.
2 Click OK to confirm.

Shutting Down, Restarting, Turning Off, and


Removing Power
It is important to shut down the library properly before turning off the
library or completely removing library power.

Caution: You should always perform a shutdown before turning off


the library or completely removing power. Otherwise, the
following could occur:
The library may not complete closing all data and log
files.
If you turn off power or unplug the power cord while
writing to tape, the data on the tape could become
corrupted.
If you unplug the power cord, the robot may
become frozen in the middle of an operation and unable
to move once library power is restored, possibly
requiring a service call.

The steps for shutting down, turning off, and completely removing
library power are:
1 Make sure the connected host applications are not sending
commands to the library and that all library operations have
stopped.
2 Shut down the library using the operator panel or Web client (see
Shutting Down the Library on page 140).
3 Turn OFF the library by pressing the power button on the front
panel (see Turning Off the Library on page 143).

Quantum Scalar i40 and Scalar i80 Users Guide 139


Chapter 6: Performing Library Operations
Shutting Down, Restarting, Turning Off, and Removing Power

4 Remove library power by disconnecting the power supply cord from


the power supply on the back of the library. If there are two power
supplies, remove the cords to both. See Completely Removing
Library Power on page 144.

Shutting Down the Shutdown shuts down the librarys operating system and firmware,
Library closes data and log files, and retracts the picker so that a tape cartridge
or the picker fingers are not stuck part way into a tape drive or
magazine slot. If the robot was in the middle of a get or put operation,
it will attempt to complete the operation before shutting down, by
either pushing the cartridge into the destination slot, or removing it
completely from the slot and stopping in a safe location from which it
can move again once power is restored.
Once the shutdown is complete, you can safely turn off the library by
pressing the power button on the front panel (see Turning Off the
Library on page 143).

Operator Panel
1 Make sure the connected host applications are not sending
commands to the library and that all library operations have
stopped.
2 Press Actions > Shutdown > Shutdown Library.
3 Press Yes to confirm.
A shutdown in progress message displays on the operator panel
(see Figure 22).

Figure 22 Shutdown in
Progress Message

140 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 6: Performing Library Operations
Shutting Down, Restarting, Turning Off, and Removing Power

4 Wait until the ready to power down message displays (see


Figure 23).

Figure 23 Ready to Power


Down Message

5 Turn OFF the library by pressing the power button on the front
panel.

Web Client
1 Press Operations > System Shutdown.
2 Select Shutdown and click Apply.
3 Click OK to confirm.
4 Wait until the ready to power down message displays on the
operator panel (see Figure 24).

Figure 24 Ready to Power


Down Message

5 Turn OFF the library by pressing the power button on the front
panel.

Quantum Scalar i40 and Scalar i80 Users Guide 141


Chapter 6: Performing Library Operations
Shutting Down, Restarting, Turning Off, and Removing Power

Restarting the Library Restart shuts down and then reboots the library's operating system and
firmware. During the reboot, the library performs an inventory of the
tape drives and magazine slots. If any tape drives or partitions were
previously taken offline, restarting the library brings them back online.
The reboot takes approximately 5 minutes.

Operator Panel
1 Make sure the connected host applications are not sending
commands to the library and that all library operations have
stopped.
2 Press Actions > Shutdown > Restart Library.
3 Press Yes to confirm.
4 Several messages appear on the screen, in the order shown in
Figure 25. Do not do anything in response to these messages. The
library will restart and initialize on its own.

Figure 25 Series of Restart


Messages

142 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 6: Performing Library Operations
Shutting Down, Restarting, Turning Off, and Removing Power

Web Client
1 Make sure the connected host applications are not sending
commands to the library and that all library operations have
stopped.
2 Press Operations > System Shutdown.
3 Select Restart and click Apply.
4 Press OK to confirm.
5 Several messages appear on the operator, in the order shown in
Figure 25 on page 142. Do not do anything in response to these
messages. The library will restart and initialize on its own.

Turning Off the Library Turning OFF the library means pressing the power button on the front
panel.
It is recommended that you perform a shutdown via the Web client or
operator panel before turning off the library. If you do not perform a
shutdown, the library attempts to complete all shutdown operations
before turning off the library. However, it may not have enough time to
shut down completely, and operations could be stopped mid-process.

Caution: You should always perform a shutdown before turning off


the library or completely removing power. Otherwise, the
following could occur:
The library may not complete closing all data and log
files.
If you turn off power while writing to tape, the data on
the tape could become corrupted.

1 Make sure the connected host applications are not sending


commands to the library and that all library operations have
stopped.
2 Shut down the library (see Shutting Down the Library on page 140).
3 Turn OFF the library by physically pressing the power button on the
librarys front panel. It can take up to 12 seconds for the power to
completely turn off.

Quantum Scalar i40 and Scalar i80 Users Guide 143


Chapter 6: Performing Library Operations
Shutting Down, Restarting, Turning Off, and Removing Power

Note: Turning off the library does not completely remove library
power (see Completely Removing Library Power on page 144).

Completely Removing Completely removing library power means disconnecting the power
Library Power cord from each power supply on the library.

Caution: You should always perform a shutdown and then turn off
library power before completely removing power.
Otherwise, the following could occur:
The library may not complete closing all data and log
files.
If you turn off power or unplug the power cord while
writing to tape, the data on the tape could become
corrupted.
The robot may become frozen in the middle of an
operation and unable to move once library power is
restored, possibly requiring a service call.

1 Make sure the connected host applications are not sending


commands to the library and that all library operations have
stopped.
2 Shut down the library (see Shutting Down the Library on page 140).
3 Turn OFF the library by physically pressing the power button on the
librarys front panel (see Turning Off the Library on page 143). Make
sure the operator panel turns off or the LED on the SCB turns off.
4 Disconnect the power cord(s) from all power supplies on the back of
the library. If there are two power supplies, disconnect both cords.
Power is completely removed from the library when the LED on each
power supply is off.

Emergency Power-off In an emergency, you may need to turn off power immediately to stop
Procedure robot motion, bypassing the normal shutdown process.
In an emergency, you can turn off power in one of two ways:
Press the power button on the front of the library to turn the library
OFF. It may take up to 4 seconds for all motion to completely stop.

144 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 6: Performing Library Operations
Unlocking and Opening the I/E Station

Note that this does not completely remove library power (you need
to disconnect the power cords to do that).
Disconnect the power cord from each power supply on the back of
the library. It may take 1 to 2 seconds for motion to completely
stop.

Caution: These methods are not recommended except in case of


emergency where it is vital that library operations be
stopped immediately. If you do not first perform a
shutdown as described in the sections above, the following
could occur:
The library may not complete closing all data and log
files.
If you turn off power or unplug the power cord while
writing to tape, the data on the tape could become
corrupted.
If you unplug the power cord, the robot may become
frozen in the middle of an operation and unable to move
once library power is restored, possibly requiring a
service call.

Taking the Library Some maintenance activities require that the entire library be taken
Offline offline. To take the library offline, change the mode of all partitions from
online to offline. See Taking a Partition Online or Offline on page 59 for
instructions.

Unlocking and Opening the I/E Station


The I/E station is locked during normal library operation. To access the
I/E station you must first unlock it. When you give the command to
unlock the I/E station, the robot physically moves to the unlock
mechanism and unlocks it. This takes a few seconds. Once unlocked,
you have 30 seconds to open the I/E station before it locks again.

Quantum Scalar i40 and Scalar i80 Users Guide 145


Chapter 6: Performing Library Operations
Unlocking and Opening the I/E Station

Opening the I/E station consists of pulling outward on the magazine


bezel handle until the magazine stops moving. The magazine will
automatically stop when the entire I/E station is exposed.

Note: Because the I/E station is part of the magazine, all storage slots
contained in that magazine are unavailable to applications
during the time that the I/E station is open.

Note: On the Scalar i80, if you want to open more than one I/E
station, such as when importing multiple tape cartridges,
unlock and open both I/E stations before you close either of
them. Otherwise, if you open and close one at a time, you must
wait for the robot to complete inventory on the one being
closed before it can open the other one.

For more information about the physical location and capacity of the I/E
station, see Configuring I/E Station Slots on page 63.

Operator Panel
1 If viewing from the default home screen, select Actions >
I/E > Unlock I/E Station. If viewing from the alternate home
screen, select Unlock.
2 If more than one I/E station is configured on the library, select which
I/E station to unlock, and press Unlock for the desired selection.

Note: Only closed I/E stations are listed.

3 Wait until the robot unlocks the I/E station and the screen displays
the I/E Station is Unlocked message (see Figure 26).

Figure 26 I/E Station Unlocked


Message

146 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 6: Performing Library Operations
Unlocking and Opening the I/E Station

4 Within 30 seconds, open the I/E station by pulling outward on the


magazine bezel handle until the magazine stops moving.
If you do not open the magazine within 30 seconds, it locks and you
receive the following failure message.

Figure 27 I/E Station Locked


Message

5 When finished, push the magazine in completely.


The I/E station is now locked.

Web Client
1 Select Operations > I/E Station Unlock.
2 Select an I/E station to unlock and click Apply.

Note: Only closed I/E stations are listed.

3 Click Apply to confirm, and click OK.


The Progress Window displays. The Progress Window contains
information on the action, elapsed time, and status of the
requested operation. Do one of the following:
If Success appears in the Progress Window, the I/E station was
unlocked. Click Close to close the Progress Window. The
operator panel displays the status Unlocking and then Idle.
If Failure appears in the Progress Window, the I/E station did
not unlock.
4 Within 30 seconds, pull outward on the magazine bezel handle to
open the I/E station.
If you do not open the magazine within 30 seconds, it locks.

Quantum Scalar i40 and Scalar i80 Users Guide 147


Chapter 6: Performing Library Operations
Releasing Magazines

5 When finished, push the magazine in completely.


The I/E station is now locked.

Releasing Magazines
Magazines are locked during normal operation. Before you open or
completely remove a magazine, you must release it, either via the user
interface or manually, as described in:
Releasing Magazines via the User Interface on page 149
Releasing Magazines Manually on page 150
When you give the command to release a magazine via the operator
panel or Web client, the robot physically moves to the unlock
mechanism and unlocks it. This takes a few seconds. Once unlocked,
you have 30 seconds to open the magazine before it locks again.

Note: All storage slots contained in an open or removed magazine


are unavailable to applications.

Note: If you want to remove more than one magazine, such as when
bulk loading tape cartridges, release and remove all the
magazines you want to remove before you close any of them.
Otherwise, if you remove and replace them one at a time, you
must wait for the robot to complete inventory on the one
being replaced before it can release another one.

Caution: If the library is turned ON, always release the magazines via
the user interface. It is easier and will not result in a
diagnostic ticket (see About Diagnostic Tickets on
page 312). Additionally, the library makes sure nothing is
physically blocking the magazine that could cause damage
to library components before allowing you to release it.

148 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 6: Performing Library Operations
Releasing Magazines

Releasing Magazines Use this method when the library is turned ON.
via the User Interface
Operator Panel
1 Select Actions > Magazine.
2 Select a magazine and press Release.

Note: Only closed magazines are listed.

3 Wait until the robot unlocks the magazine and the screen displays
the Magazine is now unlocked message (see Figure 28).

Figure 28 Magazine Unlocked


Message

4 Pull outward on the magazine bezel handle to slide the magazine


out as far as you wish, or remove it completely. Once you slide the
magazine back into the slot all the way, it locks again automatically
If you do not open the magazine within 30 seconds, it locks and you
receive the following failure message.

Figure 29 Magazine Locked


Timer Message

Quantum Scalar i40 and Scalar i80 Users Guide 149


Chapter 6: Performing Library Operations
Releasing Magazines

Web Client
1 Select Operations > Release Magazine.
2 Select a magazine and press Apply.

Note: Only closed magazines are listed.

3 Click OK to confirm.
The Progress Window displays. The Progress Window contains
information on the action, elapsed time, and status of the
requested operation. Do one of the following:
If Success appears in the Progress Window, the magazine was
unlocked. Click Close to close the Progress Window. The
operator panel displays the status Unlocking and then Idle.
If Failure appears in the Progress Window, the magazine did
not unlock.
4 Within 30 seconds, pull outward on the magazine bezel handle to
slide the magazine out as far as you wish, or remove it completely.
Once you slide the magazine back into the slot all the way, it locks
again automatically.
If you do not open the magazine within 30 seconds, it locks.

Releasing Magazines Use this method when the library is turned OFF. If you use this method
Manually when the library is turned ON, you will receive a diagnostic ticket.

Caution: If you use the manual method to remove magazine(s)


when the library is turned ON you risk a mechanical
collision between the magazine and the robotics that could
seriously damage components.

1 Insert an opened paperclip, small screwdriver, or other object


(3.5 mm or less in diameter that will not break off) into the access
hole in the bottom of the magazine bezel (see Figure 30).
2 Use the tool to depress the release latch (push straight in) while
gently pulling the magazine bezel handle to slide the magazine out.
3 If the magazine is on the right side, it will only slide out as far as the
I/E station. To release the magazine fully:

150 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 6: Performing Library Operations
Performing Media Operations

On the Scalar i40 and the bottom right magazine of the Scalar
i80, reach under the open magazine and insert the tool directly
into the access hole in the library chassis to depress the release
latch, while pulling outward on the magazine bezel handle.
On the top right magazine of the Scalar i80, reach under the
open magazine and press the release latch directly with your
finger, while pulling outward on the magazine bezel handle.

Figure 30 Magazine Release


Latch Access

Magazine release latch access holes

Performing Media Operations


This section describes how to import, export, load, unload, and move
data cartridges in the library. The following section, Cleaning Tape Drives
on page 163, describes how to perform similar operations with cleaning
cartridges.

Note: The information and procedures in this users guide apply


specifically to the library Web client and the operator panel
user interface, not to the host application. Performing media
operations through the library user interface may affect your
host application. See your host application documentation for
information.

Quantum Scalar i40 and Scalar i80 Users Guide 151


Chapter 6: Performing Library Operations
Performing Media Operations

Importing Tape You can use the I/E station to import data cartridges into the library. The
Cartridges librarys scanner automatically reads the barcode on new cartridges
imported into the library.
Tape cartridges must be present in the I/E station and assigned to a
partition before you can import them. You will select a partition into
which to import the cartridges. If the selected partition is online, it will
be taken offline before the import operation is performed, and brought
back online after the operation is complete. If the library contains
multiple partitions, the import operation will not affect operations in
other partitions.
You must have access to the librarys I/E station and the operator panel
to import cartridges.

Note: All tape cartridges must have a unique, external barcode label
that is machine readable. See Supported Barcode Formats on
page 338 and Installing Barcode Labels on page 339 for more
information.

Note: If your library has zero I/E station slots, you cannot import or
export media using the I/E station. See Configuring I/E Station
Slots on page 63.

Note: Importing cartridges using the library interface may necessitate


performing an inventory on your host application. You can also
import cartridges using your host application. See your host
application documentation for more information.

152 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 6: Performing Library Operations
Performing Media Operations

Note: Note on importing unassigned tape cartridges: When the


manual cartridge assignment setting is enabled (the default
setting), the I/E Assign screen automatically displays on the
operator panel after you have loaded the cartridges into the I/E
station and closed the I/E station. The screen prompts you to
assign the cartridges to a specific partition or to the System
partition. The cartridges can then be used only by the assigned
partition. If you do not wish to assign cartridges to a partition
immediately, or you wish to assign them to different partitions
via the Web client, you can cancel out of this screen and the
cartridges are considered unassigned. Alternatively, you can
disable manual cartridge assignment (operator panel, Setup >
System Settings > Man Cart Assign; see Manual Cartridge
Assignment on page 100). In this case, the I/E Assign screen
does not appear on the operator panel and the cartridges are
considered unassigned. Unassigned cartridges in the I/E
station are available for use by any partition, including the
System partition. However, you can only import or move
unassigned cartridges into the library when manual cartridge
assignment is disabled. Once imported or moved into a
partition, the cartridges are considered assigned to that
partition and can only be used by that partition.

Caution: Some host applications may fail import/export operations


when the I/E station contains cartridges that are assigned
to another partition. Move cartridges from the I/E station
as soon as possible to avoid possible conflicts with the
other partitions.

The process for importing cartridges includes the following steps:

Inserting and Assigning Cartridges


1 Verify that all tape drives are unloaded and that all cartridges are in
their appropriate storage slot locations. Doing this will avoid over-
loading the library with cartridges.
2 Go to the front of the library and insert cartridges into the I/E
station.

Quantum Scalar i40 and Scalar i80 Users Guide 153


Chapter 6: Performing Library Operations
Performing Media Operations

3 Close the I/E station.


The I/E Assign screen displays on the operator panel if Manual
Cartridge Assignment is enabled on the operator panel (Setup >
System Settings).
4 If the I/E Assign screen displays, do the following:
a Using the operator panel, select the partition to which you want
to assign the cartridges. All unassigned cartridges in the I/E
station will be assigned to the same partition.
b Press Apply. (Alternatively, you may press Cancel to bypass this
step if you wish to assign cartridges to different partitions using
the Web client. Note that you must disable manual cartridge
assignment from the operator panel before you can import
unassigned cartridges, as described in the Note above.)
5 Continue using one of these options:
Importing Cartridges via the Operator Panel on page 154
Importing Cartridges via Web Client on page 155

Importing Cartridges via the Operator Panel


You can import one cartridge at a time, or all cartridges at once, using
the operator panel.
1 Select Actions > I/E > Import Tape.
2 If the cartridges in the I/E station are assigned to multiple partitions,
select the partition into which you want to import.
3 If there is more than one cartridge in the I/E station, use the Up and
Down buttons to select a cartridge to import, or select ALL to
import all cartridges. The ALL option is only available if there are
enough empty slots in the selected partition to accommodate all the
cartridges.
4 Press Import.
The library imports the tape cartridge(s) into the first empty slot(s)
in the partition.

154 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 6: Performing Library Operations
Performing Media Operations

Importing Cartridges via Web Client


1 Select Operations > Media > Import.
2 If more than one partition exists, select the partition into which you
want to import cartridges and click Next.
3 The Import Media - Partition (Mode) screen displays, where
Partition is the name of the partition and Mode is the current mode
of the partition. This screen contains a list of cartridges in the I/E
station that are ready for import.
4 Identify the number of empty storage slots that appear in the
Empty Partition Slots field. The number of cartridges you can
import is limited to the number of empty slots that exist in the
partition.
5 Select the cartridges to import into the partition.

Note: You can select all cartridges by selecting the top check box.
You can use the Filter by Barcode text box to filter the
available cartridge barcodes. Click the Help button next to
the Find button for more information about filtering
barcodes. In addition, if not all cartridges appear on the
screen, use the Page 1 of x arrows to view the additional
cartridges.

Note: Bold column headings in the table can be sorted. For


example, selecting the Location column heading will sort
by location coordinates.

6 Click Apply.
7 Click OK to confirm it is OK to take the partition offline.
The library imports the tape cartridge(s) into the first empty slot(s)
in the partition.

Bulk Loading Tape Bulk loading is another way to load media into the library. If zero I/E
Cartridges station slots are configured, you will always need to bulk load cartridges
into the library. If I/E station slots have been configured, you may want
to perform an initial bulk load when you first start using your library.
The library will perform an inventory after the bulk load is complete.

Quantum Scalar i40 and Scalar i80 Users Guide 155


Chapter 6: Performing Library Operations
Performing Media Operations

Before bulk loading, print out the Library Configuration report from the
Web client to see how the physical slots of the library are configured.
The report shows what slots are unavailable or configured as cleaning
slots or as I/E station slots. For information on accessing the report, see
Viewing the Library Configuration Report on page 210.
Place cartridges in their appropriately configured slot location; for
example, cleaning cartridges should not be placed in slots configured
for storage.
To perform an initial bulk load, remove the magazine and manually
insert tape cartridges directly into storage slots (see Releasing
Magazines on page 148). When finished loading the cartridges, reinstall
the magazine and push it in until it is completely closed.
After the initial bulk load, you can use the Import Media screen to add
cartridges without interrupting library operations, as long as I/E station
slots have been configured. For more information, see Importing Tape
Cartridges on page 152.

Moving Tape Cartridges Once a cartridge has been imported into a library and assigned to a
partition, it can be moved to a tape drive for data access, to a storage
slot for storage, or back to the I/E station for removal from the library.
Details on using the library to move media include:
If your library has zero I/E station slots, you cannot move cartridges
to and from the I/E station. See Configuring I/E Station Slots on
page 63.
You can move a cartridge from one location to another within a
partition. You can also move unassigned cartridges from the I/E
station to available locations in the library. If you move an
unassigned tape cartridge into a slot in a partition, it will become
assigned to that partition and will only be available for use by that
partition.

Note: If you move an unassigned tape cartridge directly from the


I/E station to a tape drive, you will not be able to perform
an unload operation on that tape drive later. The tape
drive can only unload a cartridge if that cartridge came
from a storage slot in the partition. You will need to
perform a move operation to move the tape drive to a
storage slot or back to the I/E station.

156 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 6: Performing Library Operations
Performing Media Operations

Moving cartridges using the library Web client may necessitate


performing an inventory on your host system. You can also move
cartridges using your host application. See your host application
documentation for more information.
If the partition is online, it will be taken offline before the move is
performed and brought back online after the move is complete. You
will be asked to confirm that you want to take the partition offline.
You can select only the partitions to which you have been given
access.
You cannot move media directly from one partition to another.
You can only perform move commands from the Web client.

Web Client
1 Select Operations > Media > Move.
2 If more than one partition exists, select the partition that contains
the cartridge you want to move and click Next.
The Move Media - Partition (Mode) screen displays, where
Partition is the name of the partition and Mode is the current mode
of the partition.
3 In the Select Media section, select the source cartridge you want to
move.

Note: You can use the Filter by Barcode text box to filter the
available cartridge barcodes. Click the Help button next to
the Find button for more information about filtering
barcodes. In addition, if not all cartridges appear on the
screen, use the Page 1 of x arrows to view the additional
cartridges.

Note: Bold column headings in the table can be sorted. For


example, selecting the Location column heading will sort
by location coordinates.

4 In the Select Destination section, select a destination location for


the source cartridge.
5 Click Apply.

Quantum Scalar i40 and Scalar i80 Users Guide 157


Chapter 6: Performing Library Operations
Performing Media Operations

6 Click OK to confirm it is OK to take the partition offline.


The robot moves the cartridge to the destination. A success
message displays when the move completes.

Exporting Tape The Export Media operation enables you to export data cartridges from
Cartridges storage slots to empty I/E station slots for removal from the library.
Details on exporting cartridges include:
Exporting cartridges using the library Web client may necessitate
performing an inventory on your host application. If the host
application has issued a prevent media removal command to the
library, you will not be able to use the library Web client to export
cartridges. In addition, you can export cartridges using your host
application. For more information, see your host application
documentation.
If the partition is online, it will be taken offline before the export is
performed, and brought back online after the export is complete.
You will be asked to confirm that you want to take the partition
offline.
If your library has zero I/E station slots, you cannot export
cartridges. See Configuring I/E Station Slots on page 63.
If you have AutoClean enabled, you can also export cleaning
cartridges. For information, see Exporting Cleaning Cartridges on
page 167.
You can select only the partitions to which you have been given
access.
You can only export cartridges if empty I/E station slots are available.
You must have access to the librarys I/E station and the operator
panel to export cleaning cartridges.

Caution: Some host applications may fail import/export operations


when the I/E station contains cartridges that are assigned
to another partition. Move cartridges from the I/E station
as soon as possible to avoid possible conflicts with the
other partitions.

158 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 6: Performing Library Operations
Performing Media Operations

You can export cartridges using either the operator panel or the Web
client.

Operator Panel
1 Select Actions > I/E > Export Tape.
2 If more than one partition exists, use the Up and Down buttons
select the partition that contains the source cartridge you want to
export, then press Select.
3 A list of all the tape cartridges in storage slots in the selected
partition displays. Use the Up and Down buttons to select a tape
cartridge for export. You may also select ALL to export all cartridges;
however, the ALL option is only available if there are enough empty
slots in the I/E station to accommodate all the cartridges in the
selected partition.
4 Press Export.
5 When the screen displays confirmation that the export completed,
press OK.
6 Once the operation completes, you may open the I/E station and
remove the cartridges (see Unlocking and Opening the I/E Station
on page 145).

Web Client
1 Select Operations > Media > Export.
2 If more than one partition exists, select the partition that contains
the source cartridge you want to export.
3 Click Next.
The Export Media - Partition (Mode) screen displays, where
Partition is the name of the partition and Mode is the current mode
(online or offline) of the partition.
4 Note the number of empty I/E station slots that appear in the
Empty I/E Station Slots field. The number of cartridges you can
export is limited to the number of empty I/E station slots. You
cannot export cartridges if all I/E station slots are full.

Quantum Scalar i40 and Scalar i80 Users Guide 159


Chapter 6: Performing Library Operations
Performing Media Operations

5 Select one or more cartridges for export.

Note: You can use the Filter by Barcode text box to filter the
available cartridge barcodes. Click the Help button next to
the Find button for more information about filtering
barcodes. In addition, if not all cartridges appear on the
screen, use the Page 1 of x arrows to view the additional
cartridges.

Note: Bold column headings in the table can be sorted. For


example, selecting the Location column heading will sort
by location coordinates.

6 Click Apply.
7 Click OK to confirm it is OK to take the partition offline.
The robot moves the cartridge to the I/E station. A success
message displays when the export completes.
8 Once the operation completes, you may open the I/E station and
remove the cartridges (see Unlocking and Opening the I/E Station
on page 145).

Loading Tape Drives The Load Drive operation enables you to load a cartridge from a storage
slot into a tape drive. The storage slot and tape drive must be assigned
to the same partition.
This topic focuses on using the library user interface, not the host
application, to load tape drives. Using the library to load tape drives
may necessitate performing an inventory with the host application. See
your host application documentation for more information.
Details on loading tape drives include:
The storage slot and tape drive must be assigned to the same
partition.
The tape cartridge must be compatible with the tape drive.
If the partition is online, it will be taken offline before the load
operation is performed and brought back online after the operation
is complete. You will be asked to confirm that you want to take the
partition offline.

160 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 6: Performing Library Operations
Performing Media Operations

You can select only partitions to which you have been given access.
Default tape drive locations are highlighted if the barcode field is
empty or the field is cleared.

You can only load tape drives from the Web client.

Web Client
1 Select Operations > Drive > Load.
2 If more than one partition exists, select the partition that contains
the tape drive you want to unload, and click Next.
3 The Load Drive - Partition (Mode) screen displays, where Partition
is the name of the partition and Mode is the current mode of the
partition (online or offline).
4 In the Select Media section, select the cartridge you want to load
into a tape drive.

Note: You can use the Filter by Barcode text box to filter the
available cartridge barcodes. Click the Help button next to
the Find button for more information about filtering
barcodes. In addition, if not all cartridges appear on the
screen, use the Page 1 of x arrows to view the additional
cartridges.

Note: Bold column headings in the table can be sorted. For


example, selecting the Location column heading will sort
by location coordinates.

5 In the Select Destination section, select the destination tape drive.


6 Click Apply.
7 Click OK to confirm it is OK to take the partition offline.

Unloading Tape Drives The Unload Drive operation allows you to unload a cartridge from a
tape drive to a storage slot. The storage slot and tape drive must be
assigned to the same partition.

Quantum Scalar i40 and Scalar i80 Users Guide 161


Chapter 6: Performing Library Operations
Performing Media Operations

This topic focuses on using the library user interface, not the host
application, to unload tape drives. Using the library to unload tape
drives may necessitate performing an inventory with the host
application. See your host application documentation for more
information.
Details about unloading tape drives include:
The tape drive and storage slot must be assigned to the same
partition.
Only drives with media loaded appear on the screen.
You can select only partitions to which you have been given access.
If the affected partition is online, it will be taken offline before the
unload operation is performed, and brought back online after it is
complete.
You can unload media from the operator panel or the Web client.

Operator Panel
1 Select Actions > Tape Drive > Unload.
2 If more than one tape drive is installed in the library, use the Up and
Down buttons to select a tape drive to unload.
3 Press Unload.

Web Client
1 Select Operations > Drive > Unload.
2 If more than one partition exists, select the partition that contains
the tape drive you want to unload.
3 Click Next.
The Unload Drive - Partition (Mode) screen displays, where
Partition is the name of the partition and Mode is the current
mode of the partition. The screen contains a list of all tape drives in
the partition that are loaded with a cartridge.
4 Select the tape drive you want to unload.

Note: If not all drives appear on the screen, use the Page 1 of x
arrows to view the additional cartridges.

162 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 6: Performing Library Operations
Cleaning Tape Drives

Note: Bold column headings in the table can be sorted. For


example, selecting the Location column heading will sort
by location coordinates.

5 Click Apply.
6 Click OK to confirm it is OK to take the partition offline.
The library attempts to unload the tape cartridge and move it into
the storage slot it was in when it was originally loaded into the tape
drive. If that storage slot is full, the library will attempt to move it
into another empty slot in the partition. If no empty slots exist, the
unload operation will fail. If this happens, you can try to perform a
move operation to move the cartridge from the tape drive to an I/E
station instead (see Moving Tape Cartridges on page 156), or free
up a storage slot and try the unload operation again.

Cleaning Tape Drives


Tape drives require occasional cleaning. Cleaning cartridges are used to
remove accumulated residue from each tape drives read/write head.
Cleaning slots are used exclusively to store cleaning cartridges.
Configuring one or more cleaning slots enables the librarys AutoClean
feature for all partitions in the library. When AutoClean is enabled, the
library is notified by a tape drive when cleaning is required, and the
library automatically cleans the tape drive using a cleaning cartridge. For
more information about the AutoClean feature, see About AutoClean
on page 164.
You can configure cleaning slots during the initial library configuration
or at any time in the future as long as there are licensed slots available
in the library. For instructions on how to configure cleaning slots, see
Configuring Cleaning Slots on page 61.
A maximum of four cleaning slots can be configured. Zero cleaning slots
are configured by default.

Quantum Scalar i40 and Scalar i80 Users Guide 163


Chapter 6: Performing Library Operations
Cleaning Tape Drives

If no licensed slots are available, you must purchase additional slots or


modify or delete a partition to free existing slots. For information on
how to modify partitions, see Modifying Partitions on page 56. For
information on how to delete partitions, see Deleting Partitions on
page 57. Cleaning slots are not assigned to specific partitions. They are
shared by all partitions within a library.
You do not need to configure cleaning slots if you clean tape drives
manually. For more information about manual tape drive cleaning, see
Manually Cleaning Tape Drives on page 169.
You do not need to configure cleaning slots if you use host-based
cleaning. Cleaning slots are not visible to the host application. To use
host-based cleaning, configure zero cleaning slots in the library and set
up your host application to manage the cleaning process. See your host
application documentation for more information.

Valid Cleaning Use universal cleaning cartridges to clean tape drives. If you attempt to
Cartridges clean a tape drive using a non-cleaning cartridge, the library may show
that the operation completed, but the tape drive will not be cleaned,
and the library will issue a diagnostic ticket.
Universal cleaning cartridges are designated by labels that begin with
CLN or CLNU or end with C1, C2, C3, C4, or CU. Examples: CLN123,
CLNU123L1, CLN123C1, 123CU, 123C1.
Cleaning cartridges, like all other cartridges imported into the library,
must have a unique, external barcode label that is machine readable.
See Supported Barcode Formats on page 338 and Installing Barcode
Labels on page 339 for more information.

About AutoClean Configuring one or more dedicated cleaning slots automatically enables
AutoClean see Configuring Cleaning Slots on page 61). Cleaning
cartridges are stored in designated cleaning slots. When a tape drive
needs cleaning, it notifies the library, and the library automatically
cleans the tape drive using a cleaning cartridge loaded in a cleaning
slot. Automatic cleaning is integrated into routine library operations. For
example, if the host application requests the library to move a tape
cartridge, and the tape drive performing the operation needs cleaning,
the library will perform the move operation and then automatically
clean the tape drive with a cleaning cartridge before informing the host
application that the move operation is complete.

164 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 6: Performing Library Operations
Cleaning Tape Drives

When a cleaning cartridge has expired, the library issues a diagnostic


ticket that tells you to export the expired tape from the library. If more
cleaning cartridges are present, the next cleaning cartridge will be used
for the next cleaning request. If no more cleaning cartridges are
available, the library issues a diagnostic ticket informing you that the
tape drive needs cleaning and that a cleaning cartridge needs to be
imported (see Importing Cleaning Cartridges on page 165 and
Exporting Cleaning Cartridges on page 167).

Enabling AutoClean To enable AutoClean, all you need to do is configure at least one
cleaning slot in the library. For information on configuring cleaning
slots, see Configuring Cleaning Slots on page 61.

Importing Cleaning When AutoClean is enabled (at least one cleaning slot has been
Cartridges configured), you can import cleaning cartridges from the I/E station to
designated cleaning slots. For information on configuring cleaning slots,
see Configuring Cleaning Slots on page 61.
When manual cartridge assignment is enabled (the default setting), you
cannot import cartridges until you have assigned them to a specific
partition or to the System partition. Cleaning cartridges should always
be assigned to the System partition. Assigning cleaning cartridges to the
System partition makes them available to all partitions in the library. For
more information about manual cartridge assignment, see Manual
Cartridge Assignment on page 100.
You must have access to the librarys I/E station and the operator panel
to import cleaning cartridges.

Caution: Some host applications may fail import/export operations


when the I/E station contains cartridges that are assigned
to another partition. Move cartridges from the I/E station
as soon as possible to avoid possible conflicts with the
other partitions.

Note: If your library has zero I/E station slots, you cannot import or
export cleaning media. See Configuring I/E Station Slots on
page 63.

Quantum Scalar i40 and Scalar i80 Users Guide 165


Chapter 6: Performing Library Operations
Cleaning Tape Drives

Note: Cleaning cartridges, like all other cartridges used in the library,
must have a valid, readable barcode label properly installed
(see Supported Barcode Formats on page 338 and Installing
Barcode Labels on page 339).

The process for importing cleaning cartridges includes the following


steps:

Inserting and Assigning Cartridges


1 Verify that there is an available, empty slot that is not assigned to a
partition. If needed, free up access by modifying a partition (see
Modifying Partitions on page 56).
2 Go to the front of the library and insert the cleaning cartridge(s)
into the I/E station.
3 Close the I/E station.
4 If manual cartridge assignment is enabled, the I/E Assign screen
displays on the operator panel. If manual cartridge assignment is
enabled, select the System partition.
5 Press Apply.
6 Continue using one of these options:
Importing Cleaning Cartridges via the Operator Panel on
page 166
Importing Cleaning Cartridges via the Web Client on page 167

Importing Cleaning Cartridges via the Operator Panel


1 Select Actions > I/E > Import Cleaning Tape.
A list of all the cleaning cartridges present in the I/E station displays.
2 If more than one cleaning cartridge is present in the I/E station, use
the Up and Down buttons to select a cleaning cartridge to import,
or select ALL to import all cleaning cartridges. The ALL option is
only available if there are enough empty cleaning slots in the library
to accommodate all the cleaning cartridges.

166 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 6: Performing Library Operations
Cleaning Tape Drives

3 Press Import.
The library moves the cleaning cartridge to a previously configured
cleaning slot.

Importing Cleaning Cartridges via the Web Client


1 Select Operations > Cleaning Media > Import.
The Operations - Import Cleaning Media screen displays. This
screen contains a list of the cleaning cartridges in the I/E station. If
no cleaning slots are configured, a message displays stating that the
library cannot import cleaning cartridges.
2 Note the number of empty cleaning slots that appear in the Total
Empty Cleaning Slots field on the right side of the screen. The
number of cleaning cartridges you can import is limited to the
number of empty cleaning slots.
3 Select one or more cleaning cartridges to import. An error displays if
the number of selected cleaning cartridges is more than the number
of empty cleaning slots.

Note: If not all cartridges appear on the screen, use the Page 1 of
x arrows to view the additional cartridges.

Note: Bold column headings in the table can be sorted. For


example, selecting the Location column heading will sort
by location coordinates.

Exporting Cleaning When AutoClean is enabled (at least one cleaning slot has been
Cartridges configured), you can export one or more cleaning cartridges from
dedicated cleaning slots to the I/E station for removal from the library.
You may need to export expired cleaning cartridges or free up cleaning
slots for data storage.
After exporting cleaning cartridges, you can reduce the number of
configured cleaning slots. The extra slots become available for use as
storage slots. For information on configuring cleaning slots, see
Configuring Cleaning Slots on page 61. For a description of AutoClean,
see About AutoClean on page 164.

Quantum Scalar i40 and Scalar i80 Users Guide 167


Chapter 6: Performing Library Operations
Cleaning Tape Drives

Note: If your library has zero I/E station slots, you cannot import or
export cleaning media. See Configuring I/E Station Slots on
page 63.

Caution: Some host applications may fail import/export operations


when the I/E station contains cartridges that are assigned
to another partition. Move cartridges from the I/E station
as soon as possible to avoid possible conflicts with the
other partitions.

The number of cleaning cartridges you can export is limited to the


number of empty I/E station slots.
You can export cleaning cartridges from either the operator panel or the
Web client.

Operator Panel
1 Select Actions > I/E > Export Cleaning Tape.
2 Use the Up and Down buttons to select a cleaning cartridge to
export. You may also select ALL to export all cleaning cartridges;
however, the ALL option is only available if there are enough empty
slots in the I/E station to accommodate all the cleaning cartridges.
3 Press Export.
The library moves the selected cleaning cartridge to an I/E station
slot.

Web Client
1 Select Operations > Cleaning Media > Export.
The Operations - Export Cleaning Media screen displays. This
screen contains a list of the cleaning cartridges in the library. The
media barcode, location coordinates, media type, and cleaning
status (usable/expired) are displayed for each cartridge.
2 Note the number of empty I/E station slots that appear in the
Empty I/E Station Slots field on the right side of the screen. The
number of cleaning cartridges you can export is limited to the
number of empty I/E station slots.

168 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 6: Performing Library Operations
Cleaning Tape Drives

3 Select one or more cleaning cartridges to export. An error displays if


the number of selected cleaning cartridges is more than the number
of empty cleaning slots.

Note: If not all cartridges appear on the screen, use the Page 1 of
x arrows to view the additional cartridges.

Note: Bold column headings in the table can be sorted. For


example, selecting the Location column heading will sort
by location coordinates.

4 Click Apply.
The library moves the selected cleaning cartridge to an I/E station
slot.

Manually Cleaning Tape When a tape drive needs cleaning, it notifies the library. If the librarys
Drives AutoClean feature is not enabled (meaning, no cleaning slots have been
configured), the library generates a diagnostic ticket informing you that
the tape drive needs cleaning.
Details about manually cleaning tape drives include:
Be sure to unload the tape drive before attempting to clean it. If the
tape drive is loaded with a cartridge, it will not be available for this
operation.
Be sure to use a valid cleaning cartridge. If you use a data cartridge,
for example, the operation may complete but the tape drive will not
have been cleaned, and the library will issue a diagnostic ticket. See
Valid Cleaning Cartridges on page 164.
If you have at least one cleaning slot configured (see Configuring
Cleaning Slots on page 61), the library uses a cleaning cartridge
from either the topmost I/E station slot, or a configured cleaning
slot. If the cleaning cartridge is in the top I/E station slot and manual
cartridge assignment is enabled, assign the cleaning cartridge to the
System partition.
On the Web client, you can choose to use a configured cleaning
slot or the topmost I/E station slot. If two or more cleaning slots
are configured and have cleaning cartridges in them, the library
chooses which cleaning cartridge to use.

Quantum Scalar i40 and Scalar i80 Users Guide 169


Chapter 6: Performing Library Operations
Cleaning Tape Drives

On the operator panel, the library chooses which cleaning


cartridge to use, in this order: 1) topmost I/E station slot, and
2) one of the configured cleaning slots.
If you have zero cleaning slots configured, you must use a cleaning
cartridge in the topmost I/E station slot. If manual cartridge
assignment is enabled, assign the cleaning cartridge to the System
partition.
The associated partition is taken offline during the operation and
brought back online when the operation completes. You will be
asked to confirm that you want to take the partition offline.
When the operation is complete, the library moves the cleaning
cartridge back to the I/E station slot or cleaning slot.
You can clean tape drives manually at any time using commands on the
operator panel or the Web client.

Operator Panel
1 Select Actions > Tape Drive > Manual Cleaning.
2 If more than one tape drive is in the library, use the Up and Down
buttons to select a tape drive to clean, then press Clean.
3 When the operation completes, press OK.

Web Client
1 Select Tools > Drive Operations.
2 Select Clean a tape drive and click Next.
3 If more than one partition exists, select the partition that contains
the tape drive you want to clean, and click Next.
The Clean Drive - Partition (Mode) screen displays, where Partition
is the name of the partition and Mode is the current mode (online/
offline) of the partition. This screen contains a list of tape drives
assigned to the partition.

170 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 6: Performing Library Operations
Cleaning Tape Drives

4 If you have no cleaning slots configured, skip this step (you will use
the top I/E station slot as the source for your cleaning cartridge). If
you have at least one cleaning slot configured, you are asked to
Select Cleaning Source. Select which location to take the cleaning
cartridge from:
Use the top I/E slot Allows you to use a cleaning cartridge
from the topmost I/E station slot. Make sure to install a cleaning
cartridge in the topmost I/E station slot. If manual cartridge
assignment is enabled, assign the cleaning cartridge to the
System partition.
Use configured cleaning tapes Allows you to use a cleaning
cartridge from a configured cleaning slot. If two or more
cleaning slots are configured and have cleaning cartridges in
them, the library chooses which cleaning cartridge to use.
5 Select one or more tape drives to clean.

Note: If not all tape drives appear on the screen, use the Page 1
of x arrows to view the additional tape drives.

Note: Bold column headings in the table can be sorted. For


example, selecting the Location column heading will sort
by location coordinates.

6 Click Apply.
7 Click OK to confirm it is OK to take the partition offline.
The library moves the cleaning cartridge to the tape drive and cleans
it. When finished, it moves the cartridge back to the cleaning slot or
I/E station.

Quantum Scalar i40 and Scalar i80 Users Guide 171


Chapter 6: Performing Library Operations
Taking a Tape Drive Online or Offline

Taking a Tape Drive Online or Offline


There are two tape drive modes: online and offline.
Online Tape drive is available for use. This is the normal operating
mode for the tape drive.
Offline Tape drive is offline to the host application and is not
available for cartridge load and unload (move) operations initiated
by the host application, but it remains available for Web client or
operator panel initiated move commands.

Note: If a cartridge is already in the tape drive when you take the
tape drive offline, then the host can still read and write
data on the tape.

Some operations require that the tape drive be offline. You can take a
tape drive offline rather than the entire library or partition so as to
minimize disruption of library operations. A drive taken offline will
remain offline until you bring it back online, or until the library is
rebooted.This topic focuses on using the library user interface, not the
host application, to change the tape drive mode. Using the library to
change tape drive mode may affect the host application. See your host
application documentation for more information.
Details on changing the tape drive mode include:
The online/offline state follows the tape drive slot, not the particular
tape drive (if the tape drive were to be moved to a different slot in
the library).
You can select only tape drives in partitions to which you have been
given access.
If you change the mode of a control path tape drive to offline, a
caution dialog displays asking you to confirm the mode change. For
information on control path tape drives, see Configuring Control
Paths on page 67.
You can change the tape drive mode from both the operator panel and
the Web client.

172 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 6: Performing Library Operations
Taking a Tape Drive Online or Offline

Operator Panel
1 Select Actions > Tape Drive > Change Mode.
2 If more than one tape drive is in the library, use the Up and Down
buttons to select a tape drive.
3 Press Modify.
4 Use the Up and Down buttons to select Online or Offline.
5 Press Apply.
The new mode is displayed.
6 Press Exit.

Web Client
1 Select Operations > Drive > Change Mode.
The Change Drive Mode screen displays. This screen lists each tape
drives partition, location, state, current mode, activity, and version.

Note: If more than four tape drives are installed in the library, use
the Page 1 of x arrows to view the additional tape drives.

2 Locate the tape drive that you want to take offline or bring online.
In the tape drive table under Mode, the Current column indicates
the current mode of the partition. The New column contains an
Online/Offline button. The button toggles between modes.
3 Toggle the Online/Offline button to the desired mode.

Note: If you change the mode of a control path tape drive to


offline, a caution dialog displays asking you to confirm the
mode change. For information on control path tape drives,
see Configuring Control Paths on page 67.

4 Click Apply.

Quantum Scalar i40 and Scalar i80 Users Guide 173


Chapter 6: Performing Library Operations
Taking a Tape Drive Online or Offline

174 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 7
Encryption Key
Management

Encryption Key Management (EKM) is a licensable feature. You must


have an EKM license installed on your library in order to use the
encryption key management features described in this chapter. For more
information on licensing, see Adding or Upgrading Licensable Features
on page 69.
The Scalar i40 and Scalar i80 libraries support Scalar Key Manager
(SKM), an encryption solution using HP LTO-4 and HP LTO-5 Fibre
Channel and SAS tape drives and LTO-4 and LTO-5 tape cartridges only.
The encryption key management solutions generate, protect, store, and
manage encryption keys. These keys are used by their respective tape
drives to encrypt information being written to, and decrypt information
being read from, tape media. SKM is installed on a server or servers. The
library is configured to communicate with these server(s). The
encryption keys pass through the library, so that encryption is
transparent to the applications.
If you purchase SKM, you will receive the software application, two
servers (optional beginning with SKM 1.1), and installation and
configuration instructions. This chapter describes how to configure SKM
on the library. This chapter also describes all of the EKM functions
available on the library.
Refer to your Scalar Key Manager Users Guide for information on how
to manage SKM outside of the library.

Quantum Scalar i40 and Scalar i80 Users Guide 175


Chapter 7: Encryption Key Management
About the EKM License

This chapter covers:


About the EKM License
Configuring Scalar Key Manager (SKM) on the Library
EKM Path Diagnostics
Viewing Tape Drive Encryption Settings
Scalar Key Manager Functions Available on the Library

About the EKM License


If you purchase an EKM license after you purchased your library, you
must install the license key on your library to enable the EKM
functionality. See Adding or Upgrading Licensable Features on page 69
for instructions.
The EKM license applies to the entire library, regardless of how many
slots are licensed. If you increase the number of slots in your library,
your existing license applies to your new library configuration.

Configuring Scalar Key Manager (SKM) on the Library


Follow these steps to configure SKM on the library.

Step 1: Upgrade Upgrade your library and tape drive firmware to the latest released
Firmware versions.

Step 2: Install the EKM If your EKM license key is not already installed on the library, install it
License Key on the now (see Adding or Upgrading Licensable Features on page 69).
Library

176 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 7: Encryption Key Management
Configuring Scalar Key Manager (SKM) on the Library

Step 3: Install SKM on a You must use two key servers with SKM. You can purchase the two
Server or Servers servers from Quantum or provide your own. Follow the instructions that
came with your SKM system for installing SKM software on the servers.

Note: Make sure ports 80, 6000, and 6001 on the SKM servers are
opened up in a bi-directional mode. If they are not, the library
will not be able to communicate with the SKM servers.

Step 4: Configure Make sure to complete the above steps before proceeding.
Encryption Settings and
Key Server Addresses Note: You cannot edit the encryption system configuration settings
when any partition is enabled for library managed encryption.
If this happens, go to Setup > Encryption > Partition
Configuration, change all EKM partition settings from Enable
Library Managed to Allow Application Managed. Then make
your changes to the system configuration settings. Finally, go
back and change all the EKM partition settings to Enable
Library Managed.

1 Unload tape cartridges from all encryption-capable tape drives in


the library.
2 From the Web client, select Setup > Encryption > System
Configuration (see Figure 31).

Quantum Scalar i40 and Scalar i80 Users Guide 177


Chapter 7: Encryption Key Management
Configuring Scalar Key Manager (SKM) on the Library

Figure 31 Configuring
Encryption Settings and Key
Server Addresses

3 Automatic EKM Path Diagnostics: Enable or disable this feature


and set the test interval as desired. For more information, see
Enabling Automatic EKM Path Diagnostics on page 184).
4 Secure Sockets Layer (SSL): SSL is always enabled. The SSL port
number is always 6000.

Note: While the setting is called SSL, the library actually uses
Transport Layer Security (TLS), a more secure successor to
SSL, to communicate with the encryption servers.

5 In the Primary Key Server IP Address or Host text box, enter either:
The IP address of the primary key server (if DNS is not enabled),
or
The host name of the primary key server (if DNS is enabled).
6 Port Number: The port number is always 6000. You cannot change
SKM port numbers.
7 Enter the IP address or host name of the secondary key server into
the Secondary Key Server IP Address or Host text box.
8 Click Apply.

178 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 7: Encryption Key Management
Configuring Scalar Key Manager (SKM) on the Library

Step 5: Install TLS Depending on when your library was manufactured, TLS certificates may
Communication already be installed. If they are not installed, you must install them. See
Certificates on the Installing TLS Certificates on the Library on page 186 for instructions on
Library how to verify whether they are installed, and how to install them.

Step 6: Run EKM Path Run the Manual EKM Path Diagnostics to be sure the library is
Diagnostics connected properly to both SKM servers. See Running Manual EKM Path
Diagnostics on page 183 for instructions.

Step 7: Configure SKM Encryption on the library is enabled by partition only. You cannot select
Partitions and Generate individual tape drives for encryption; you must select an entire partition
Data Encryption Keys to be encrypted.
Data written to encryption-supported and encryption-capable media in
EKM-supported tape drives will be encrypted unless data was previously
written to the media in a non-encrypted format. For data to be
encrypted, the media must be blank or have been written to using
library managed encryption at the first write operation at the beginning
of tape (BOT).
Configure the partition(s) as follows:
1 From the Web client, select Setup > Encryption > Partition
Configuration.
A list of all your partitions displays, along with a drop-down list
displaying the Encryption Method for each partition (see Figure 32).

Note: The default Encryption Method for a partition containing


encryption-capable tape drives is Allow Application
Managed. To enable SKM encryption on a partition, you
must set the Encryption Method to Enable Library
Managed. This is explained in the following steps.

Quantum Scalar i40 and Scalar i80 Users Guide 179


Chapter 7: Encryption Key Management
Configuring Scalar Key Manager (SKM) on the Library

Figure 32 Configuring
Partition Encryption

2 If you want to change the encryption method for a partition, make


sure that no tape drives in that partition have cartridges loaded in
them. If tape drives have cartridges loaded, you cannot change the
encryption method.
3 Select an encryption method from the drop-down list for each
partition. See Table 6 on page 181 for a description of the
encryption methods. (For tape drives that support encryption, the
default is Allow Application Managed.) The encryption method
applies to all encryption-capable tape drives and media in that
partition.

Note: When you change the encryption method on a partition,


the partition is taken offline. When the change completes,
the partition comes back online automatically.

180 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 7: Encryption Key Management
Configuring Scalar Key Manager (SKM) on the Library

Table 6 Encryption Methods


Encryption
Method Description

Enable Library For use with EKM. Enables encryption


Managed support via a connected EKM key server for
all encryption-capable tape drives and media
assigned to the partition.

Allow Not for use with EKM. Allows an external


Application backup application to provide encryption
Managed support to all encryption-capable tape drives
and media within the partition. The library
will NOT communicate with the EKM key
server on this partition.
This is the default setting if you have
encryption-capable tape drives in the
partition. This option should remain selected
unless you are connecting the library to an
external EKM key server.
Note: If you want an external application to
manage encryption, you must specifically
configure the application to do so. The
library will not participate in performing this
type of encryption.

Unsupported Means that no tape drives in the partition


support encryption.
If Unsupported is shown, it will be greyed
out and you will not be able to change the
setting.

4 Click Apply.
Data encryption keys are generated. When you set the Encryption
Method to Enable Library Managed on a partition for the first
time, the library automatically triggers each SKM server to generate
a set of unique data encryption keys. This may take 15 minutes to
an hour or longer, depending on network performance. The library
notifies you when the process is complete.
5 Wait for the process to complete before resuming library
operations.

Quantum Scalar i40 and Scalar i80 Users Guide 181


Chapter 7: Encryption Key Management
EKM Path Diagnostics

6 Back up both SKM servers following the instructions in the Scalar


Key Manager Users Guide.

Caution: You must back up both SKM servers every time you
generate new data encryption keys to protect against
catastrophic server failure.

Step 8: Save the Library See Saving the Library Configuration on page 107 for instructions.
Configuration

EKM Path Diagnostics


The EKM Path Diagnostics consists of a series of short tests to validate
whether the key servers are running, connected, and able to serve keys
as required.
There are two ways to run EKM Path Diagnostics:
Manually Run the Manual EKM Path Diagnostics any time you
change the key server settings or library encryption settings. See
Running Manual EKM Path Diagnostics on page 183 for details.
Automatically This feature runs automatically in the background
and generates diagnostic tickets if there are problems. You can turn
this feature off but it is recommended that you leave it on. See
Enabling Automatic EKM Path Diagnostics on page 184 for details.

Description The EKM Path Diagnostics consists of the following tests:


Ping Verifies the Ethernet communication link between the
library and the key servers.
Path Verifies that EKM services are running on the key servers.
Config Verifies that the key servers are capable of serving
encryption keys.

182 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 7: Encryption Key Management
EKM Path Diagnostics

Failure Scenarios If any of the tests fail, try the following resolutions and run the test
again to make sure it passes:
Ping Test Failure Verify that the key server host is running and
accessible from the network to which the library is connected.
Path Test Failure Verify that the key server is actually running
and that the IP address configured on the library is correct.
Check to see if there is a network configuration issue, such as a
firewall, preventing communication with the server.
Config Test Failure A database inconsistency has been
detected. Contact Quantum Support.

Running Manual EKM 1 Access the EKM Path Diagnostics screen in one of two ways:
Path Diagnostics Select Setup > Encryption > System Configuration or Setup
> Encryption > Partition Configuration and click the link that
says Click here to run EKM Path Diagnostics.
Enter library Diagnostics (from the Web client select Tools >
Diagnostics) and then select EKM > EKM Path Diagnostics.
Note that entering Diagnostics will log off all other users of the
same or lower privileges and take your partitions offline. When
you exit Diagnostics, the partitions automatically come back
online. See Performing Library Diagnostics on page 330 for
more information.
2 Click Apply.
3 The library performs the diagnostics and displays pass/fail results on
each of the tests in the Progress Window. This may take several
minutes. If a test fails, try the solutions listed under Failure Scenarios
on page 183.
4 Do one of the following:
If Completed appears in the Progress Window, the diagnostics
were performed (this does not mean that the diagnostics
passed, just that the diagnostics were performed). Click Close
to close the Progress Window.
If Failure appears in the Progress Window, the diagnostics were
not able to be performed.

Quantum Scalar i40 and Scalar i80 Users Guide 183


Chapter 7: Encryption Key Management
EKM Path Diagnostics

Enabling Automatic You can enable the library to automatically perform EKM Path
EKM Path Diagnostics Diagnostics at selected intervals. During each interval, the library tests
every configured key server. The default test interval is 10 minutes. The
library generates a diagnostic ticket if there are problems.
Automatic EKM Path Diagnostics is enabled by default and should
always be left enabled. You should not need to disable it unless
Quantum Support directs you to do so.
For a list of tests performed, see EKM Path Diagnostics on page 182.
To enable Automatic EKM Path Diagnostics:
1 From the Web client, select Setup > Encryption > System
Configuration (see Figure 33).
2 Select the Automatic EKM Path Diagnostics check box.
3 Select a test interval from the Interval drop-down list.

Figure 33 Enabling Automatic


EKM Path Diagnostics

184 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 7: Encryption Key Management
Viewing Tape Drive Encryption Settings

Viewing Tape Drive Encryption Settings


You can view the encryption settings in the following ways:
System Information Report To view encryption information on
all key servers, partitions, and tape drives, select Reports > System
Information from the Web client. For more information, see
Viewing System Information on page 206.
Library Configuration Report To view the encryption status of a
selected tape drive or tape cartridge, select Reports > Library
Configuration from the Web client and click a tape drive or slot.
The encryption status is displayed in a pop-up status window. For
more information, see Viewing the Library Configuration Report on
page 210.
Partition Encryption From the Web client, select Setup >
Encryption > Partition Configuration to view and change the
encryption settings of partitions. See Step 7: Configure SKM
Partitions and Generate Data Encryption Keys on page 179 for more
details.

Scalar Key Manager Functions Available on the Library


Once the SKM servers are set up, most SKM functions occur
automatically without user action required. SKM provides some key
management capability through the library Web client.
For a complete description and instructions for using these features, see
the library Web client online help or the Scalar Key Manager Users
Guide.
These functions are:
Installing TLS Certificates on the Library
Generating Data Encryption Keys
Sharing Encrypted Tape Cartridges
Exporting Encryption Certificates

Quantum Scalar i40 and Scalar i80 Users Guide 185


Chapter 7: Encryption Key Management
Scalar Key Manager Functions Available on the Library

Importing Encryption Certificates


Exporting Data Encryption Keys
Importing Data Encryption Keys
Accessing the SKM Server Logs
Using the SKM Encryption Key Import Warning Log

Installing TLS Transport Layer Security (TLS) certificates are unique certificates that
Certificates on the must be installed on the library in order for the library to communicate
Library with Scalar Key Manager (SKM) servers.
If TLS certificates are not installed, you must install them. You can install
either Quantum-provided TLS certificates, or your own TLS certificates.
At any time, you may install a new set of TLS certificates to overwrite the
existing set. The new TLS certificates must all be valid or the overwrite
will not occur and the existing certificates will remain in place.

Checking Whether TLS Certificates are Installed on Library


Your library may have come with TLS certificates pre-installed. You can
check the Web client to see if certificates are installed (Tools > EKM
Management > Import Communication Certificates). At the bottom
of the page, a message tells you whether TLS certificates are currently
installed. If certificates are installed, a table appears below the message
containing information about the installed certificates. See Figure 34 on
page 187.

186 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 7: Encryption Key Management
Scalar Key Manager Functions Available on the Library

Figure 34 Checking and


Installing TLS Certificates

Fill out this


section if
installing
user-supplied
TLS
certificates

Fill out this


section if
installing
Quantum-
supplied TLS
certificates

Tells you
whether TLS
certificates
are currently
installed on
the library

Quantum Scalar i40 and Scalar i80 Users Guide 187


Chapter 7: Encryption Key Management
Scalar Key Manager Functions Available on the Library

Installing Quantum-Supplied TLS Certificates


The Quantum-supplied certificates come on a CD which you received.
The TLS certificates are bundled in a single file.
1 Ensure that the date on both SKM servers and the library are set to
the current date. Incorrect date settings may interfere with the TLS
certificates and cause the library to stop communicating with the
SKM servers.
2 Insert the CD into the CD ROM drive of your computer. Either copy
the file to a known location on your computer or use the CD as the
location from which you will retrieve the file.
3 From the Tools menu, select EKM Management > Import
Communication Certificates.
The Tools - EKM Communication Certificate Import screen opens
(see Figure 34 on page 187). At the top of the page, the primary
and secondary key server status is displayed. If the status is Not
Available, it means there is no communication with the server. The
most likely causes are that the server is down, not connected, or not
configured correctly on the library; or that no TLS certificates are
installed or the TLS certificates are invalid or expired. At the bottom
of the page, a message tells you whether TLS certificates are
currently installed. If certificates are installed, a table appears below
the message containing information about the installed certificates.
4 Select the Use the Quantum Certificate Bundle checkbox.
5 Click the Browse button next to the Quantum Communication
Certificate Bundle File field and locate the TLS certificate file.
6 Click Open.
7 Click Apply.
8 Verify that the TLS certificates are now installed in the library. At the
bottom of the page is a statement letting you know whether the
certificates are currently installed. In addition, the three rows of the
table at the bottom of the screen should be filled in with the correct
information.

188 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 7: Encryption Key Management
Scalar Key Manager Functions Available on the Library

Installing Your Own TLS Certificates


When providing your own certificates, it is assumed you understand the
concepts of PKI (Public Key Infrastructure) and can access the tools or
third-party resources needed to generate or obtain certificates.

Note: You must be running SKM 1.1 or higher on your SKM servers in
order to install your own TLS certificates.

Note: If you install your own TLS certificates on the SKM server, you
must also install your own certificates on the library. Similarly, if
you use the Quantum-provided TLS certificates on the SKM
server, you must also use the Quantum provided TLS certificates
on the library. Newer libraries come with Quantum-provided
TLS certificates pre-installed. To verify whether TLS certificates
are already installed on the library, refer to Checking Whether
TLS Certificates are Installed on Library on page 186.

You need to provide the following certificates:


Root certificate (also called the CA certificate, or Certificate
Authority certificate)
Client certificate
Admin certificate
These files must be in the proper format, as follows. If any of the
following requirements is not met, none of the certificates will be
imported.
The Root Certificate must be 2048 bits.
The Root Certificate must be in PEM format.
Admin and Client certificates must be in pkcs12 (.p12) format, with
a separate certificate and private key contained in each.
Admin and Client certificates must be 1024 bits.
Admin and Client certificates must be signed by the Root Certificate.
Certificates must have the Organization name (O) set in the Issuer
and Subject information.
The Admin certificate must have its Organizational Unit name (OU)
set as akm_admin in its Subject Information.

Quantum Scalar i40 and Scalar i80 Users Guide 189


Chapter 7: Encryption Key Management
Scalar Key Manager Functions Available on the Library

The same Root certificate must be installed on the SKM servers and
the library.
All the certificates have a valid validity period, according to the
librarys date and time settings.

To install your own certificates:


1 Ensure that the date on both SKM servers and the library are set to
the current date. Incorrect date settings may interfere with the TLS
certificates and cause the library to stop communicating with the
SKM servers.
2 Place the TLS certificate files in a known location on your computer.
3 From the Tools menu, select EKM Management > Import
Communication Certificates.
The Tools - EKM Communication Certificate Import screen opens
(see Figure 34 on page 187). At the top of the page, the primary
and secondary key server status is displayed. If the status is Not
Available, it means there is no communication with the server. The
most likely causes are that the server is down, not connected, or not
configured correctly on the library; or that no TLS certificates are
installed or the TLS certificates are invalid or expired. At the bottom
of the page, a message indicates whether TLS certificates are
currently installed. If certificates are installed, a table appears below
the message containing information about the installed certificates.
4 Make sure the Use the Quantum Certificate Bundle checkbox is
deselected.
5 Click the Browse button next to the Root Certificate File. Locate
the file and click Open.
6 Click the Browse button next to the Admin Certificate File. Locate
the file and click Open.
7 Enter an Admin Certificate Password. This is the password you
created when you created the Admin Certificate file. The password
allows the library to read the file.
8 Click the Browse button next to the Client Certificate File. Locate
the file and click Open.

190 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 7: Encryption Key Management
Scalar Key Manager Functions Available on the Library

9 Enter a Client Certificate Password. This is the password you created


when you created the Client Certificate file. The password allows the
library to read the file. If you want to use the same password as the
Admin Certificate password, then just select the Use Admin's
Password checkbox.
10 Click Apply to import the files onto the library.
11 Verify that the TLS certificates are now installed in the library. At the
bottom of the page is a statement indicating whether the
certificates are currently installed. In addition, the three rows of the
table at the bottom of the screen should be filled in with the correct
information.

Generating Data Caution: Every time you generate new data encryption keys, you
Encryption Keys must back up both SKM servers before you begin using the
keys to encrypt data. Refer to the SKM Users Guide for
instructions.

Data encryption keys are generated in sets of a specified quantity (see


the Scalar Key Manager Users Guide for more information).
The library tracks data encryption key usage and reminds you to
generate more keys when needed. If you try to generate data encryption
keys on an SKM server that already has sufficient unused data
encryption keys, then it will not create more. You will receive a message
to that effect on the library remote Web client.

Note: Each library that you connect to an SKM server requires its own
set of data encryption keys. Each library only pulls data
encryption keys from the set that belongs to it. This means
that an SKM server may contain several distinct sets of data
encryption keys. When the data encryption keys for one library
have all been used, then more keys must be generated.

You can generate data encryption keys in the following ways:


Generating Data Encryption Keys at Initial Setup
Generating Data Encryption Keys When 80% Depleted
Generating Data Encryption Keys When 100% Depleted
Manually Generating Data Encryption Keys

Quantum Scalar i40 and Scalar i80 Users Guide 191


Chapter 7: Encryption Key Management
Scalar Key Manager Functions Available on the Library

Generating Data Encryption Keys at Initial Setup


At initial setup, the library triggers each SKM server to generate a set of
data encryption keys. The process is described in Step 7: Configure SKM
Partitions and Generate Data Encryption Keys on page 179.

Generating Data Encryption Keys When 80% Depleted


When an SKM server has used 80 percent of the data encryption keys
assigned to a particular library, that library generates a diagnostic ticket
to let you know. Once you receive the diagnostic ticket, you should
schedule a time to manually generate more data encryption keys as
described in Manually Generating Data Encryption Keys on page 192
and back up both SKM server keystores.

Generating Data Encryption Keys When 100% Depleted


If an SKM server completely runs out of data encryption keys for a
particular library, that library generates a diagnostic ticket, which states
that you have run out of data encryption keys and that the library
attempted to fail over to the other SKM server. If this happens, it is
imperative that you manually generate a new set of data encryption
keys on the depleted server immediately and then back up both SKM
server keystores. See Manually Generating Data Encryption Keys on
page 192.

Manually Generating Data Encryption Keys


To manually generate data encryption keys, you need to temporarily
disable library managed encryption on a partition, and then enable it
again. Enabling library managed encryption on a partition triggers the
library to check both SKM servers to see if new data encryption keys are
needed. If so, it creates the keys.

192 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 7: Encryption Key Management
Scalar Key Manager Functions Available on the Library

Note: The key generation process takes 15 minutes to an hour,


depending on network performance and quantity of keys
already used. The library notifies you when the process
completes. During key generation and backup, the SKM server
will not be able to process any library requests for data
encryption keys. You should not run any library or host-initiated
operations on SKM partitions during key generation and
backup.

Caution: Avoid manually generating keys on more than five libraries


simultaneously as the key generation process is resource-
intensive on the server. Generating keys manually on more
than five libraries at once could result in a failure to
complete the key generation operation, or interfere with
key retrieval operations.
If a failure does occur during key generation, wait 10
minutes, then try to start it again. The key generation
process will resume from where the error was encountered.

To manually generate data encryption keys:


1 Make sure that both SKM servers are running and operational.
2 From the librarys Web client, access the encryption partition
configuration screen (Setup > Encryption > Partition
Configuration). See Figure 35 on page 193.

Figure 35 Accessing the


Encryption Partition
Configuration Screen

Quantum Scalar i40 and Scalar i80 Users Guide 193


Chapter 7: Encryption Key Management
Scalar Key Manager Functions Available on the Library

3 Select an SKM partition configured for library managed encryption,


and temporarily disable library managed encryption by changing
the Encryption Method from Enable Library Managed to Allow
Application Managed (see Figure 36 on page 194). Remember
which partition it is, because you will be changing it back in a few
minutes.
4 Click Apply.

Caution: When you change the partitions encryption method to


Allow Application Managed, the data that was
written to the tapes while the partition was configured
for Enable Library Managed can no longer be read,
until you change the partition back to Enable Library
Managed. You will only be disabling for a short time,
and then changing back to Enable Library Managed
(just to trigger the key generation process) so this
should have little effect, unless you forget to turn it
back to Enable Library Managed.

Figure 36 Changing
Encryption Method to Allow
Application Managed

5 Wait 3 minutes to allow the changes to complete.


6 Go back to the encryption partition configuration screen and
change the Encryption Method back to Enable Library Managed
(see Figure 37).
7 Click Apply.

194 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 7: Encryption Key Management
Scalar Key Manager Functions Available on the Library

Data encryption keys are generated. The library triggers the SKM
server to generate a set of unique data encryption keys. This takes
15 minutes to an hour or longer, depending on network
performance. The library notifies you when the process is complete.

Figure 37 Changing
Encryption Method Back to
Enable Library Managed

8 Wait for the process to complete before resuming library


operations.
9 Back up both SKM server keystores. See the Scalar Key Manager
Users Guide for instructions on backing up the keystores.

Caution: You must back up the keystores every time you


generate new data encryption keys to protect against
catastrophic server failure.

Sharing Encrypted Tape If you are using SKM, you can share encrypted tapes with other
Cartridges companies and individuals who also use SKM for managing encryption
keys.

Quantum Scalar i40 and Scalar i80 Users Guide 195


Chapter 7: Encryption Key Management
Scalar Key Manager Functions Available on the Library

Each SKM server provides a unique encryption key for each tape
cartridge that is encrypted. To read an encrypted tape in a library that is
attached to an SKM server that is different than the server that originally
provided the encryption key, the encryption key from the originating
(i.e., source) SKM server needs to be shared with the receiving (i.e.,
destination) SKM server. The key (or list of keys, if there is more than one
tape), is exported from the source SKM server to a file, which is sent to
the destination recipient. Each key contained in the file is encrypted
using the public key of the destination SKM server. The destination SKM
server provides its public key to the source SKM server as part of an
Encryption Certificate, which the source SKM server uses to wrap
(encrypt) the encryption keys for transport. Upon arrival, the file
containing the wrapped encryption keys can only be unwrapped by the
corresponding private key, which resides on the destination SKM server
and is never shared.
The process is as follows:
1 The destination administrator exports the Encryption Certificate that
belongs to the destination SKM server. The Encryption Certificate is
saved as a file to a location specified by the administrator on a
computer (see Exporting Encryption Certificates on page 197).
2 The destination administrator e-mails the Encryption Certificate file
to the source administrator.
3 The source administrator saves the Encryption Certificate file to a
location on a computer, and then imports the Encryption Certificate
onto the source SKM server (see Importing Encryption Certificates
on page 198).
4 The source administrator exports the Encryption Keys, assigning the
same Encryption Certificate noted above to wrap (encrypt) the keys.
The file containing the wrapped encryption keys is saved to a
location on a computer specified by the source administrator. See
Exporting Data Encryption Keys on page 199.
5 The source administrator e-mails the file containing the wrapped
encryption keys to the destination administrator.
6 The destination administrator saves the file containing the wrapped
encryption keys to a location on a computer, and then imports the
keys onto the destination SKM server (see Importing Data
Encryption Keys on page 201).
7 The destination library can now read the encrypted tapes.

196 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 7: Encryption Key Management
Scalar Key Manager Functions Available on the Library

For more information about the key servers and library managed
encryption best practices, please refer to the Scalar Key Manager Users
Guide.

Exporting Encryption To receive encryption keys from another SKM server, you must first send
Certificates your native encryption certificate to that server. The public key
contained in the certificate will be used to wrap (encrypt) the encryption
keys to protect them during transport to you.
This function is available to administrators and only applies to SKM
servers. Both SKM servers must be connected and operational in order
to import encryption keys.
To export an encryption certificate:
1 Before starting this process, read and follow the sequence of steps
outlined in Sharing Encrypted Tape Cartridges on page 195.
2 From the Tools menu, select EKM Management > Encryption
Certificate > Export. See Figure 38.

Figure 38 Exporting
Encryption Certificates

3 Click Apply to export your SKM servers native encryption


certificate.
4 Click Close to close the Progress Window.
5 In the File Download dialog box that appears, click Save.
6 In the Save As dialog box that opens, choose a location in which to
save the file, then click Save.

Quantum Scalar i40 and Scalar i80 Users Guide 197


Chapter 7: Encryption Key Management
Scalar Key Manager Functions Available on the Library

Importing Encryption The encryption certificate contains a public key that is used to wrap
Certificates (encrypt) encryption keys prior to transporting them to another SKM
server. When sharing tape cartridges, you need to import the encryption
certificate of the destination SKM server.

Note: This function is available to administrators and only applies to


SKM servers. Both SKM servers must be connected and
operational in order to import encryption keys.

To import encryption certificates:


1 Before starting this process, read and follow the sequence of steps
outlined in Sharing Encrypted Tape Cartridges on page 195.
2 Receive the encryption certificate file from the destination SKM
server administrator and save it to a known location on your
computer.
3 From the Tools menu, select EKM Management > Encryption
Certificate > Import.

Figure 39 Importing
Encryption Certificates

4 Click Browse to locate the saved encryption certificate file.


5 Click Open.
6 Click Apply to import the certificate onto your SKM server.
7 Back up both SKM servers to protect against catastrophic server
failure.

198 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 7: Encryption Key Management
Scalar Key Manager Functions Available on the Library

Exporting Data SKM servers provide a unique encryption key for each tape cartridge
Encryption Keys that is encrypted. For another (i.e., destination) SKM server to read
tapes encrypted by your SKM server (i.e., source), you need to export the
encryption keys used to encrypt those tapes and send them to the
destination server.

Note: This function is available to administrators and only applies to


SKM servers. Both SKM servers must be connected and
operational in order to import encryption keys.

To export encryption keys:


1 Before starting this process, read and follow the sequence of steps
outlined in Sharing Encrypted Tape Cartridges on page 195.
2 From the Tools menu, select EKM Management > Encryption Key
> Export.

Figure 40 Exporting
Encryption Keys

3 Assign the encryption certificate with which you will wrap


(encrypt) the keys by selecting it from the Certificate Name Used
For Export drop-down list. Choose the certificate that belongs to
the server to which the keys will be imported.

Quantum Scalar i40 and Scalar i80 Users Guide 199


Chapter 7: Encryption Key Management
Scalar Key Manager Functions Available on the Library

Note: The owner of that server should have sent you the
certificate and you should have imported it (see Sharing
Encrypted Tape Cartridges on page 195 and Importing
Encryption Certificates on page 198). The drop-down list
contains all of the encryption certificates that you have
ever imported onto your SKM server (indicated by the word
imported in the list), as well as the certificate belonging
to your SKM server pair (indicated by the word native in
the list).

4 Select which SKM encryption keys to export from the following


options:
Export Used Exports all the keys that have ever been used to
encrypt tape cartridges on the library performing this export.
Also exports all keys that were imported onto the key server, via
a key import operation, from any library.
Export Current Exports all the keys that were used to
encrypt the tape cartridges that are currently in the library
performing this export. This includes storage slots, I/E stations,
and tape drives. If a tape cartridge is no longer in the library, the
key used to encrypt it will not be exported. If a tape cartridge is
missing its label, the key used to encrypt it will not be exported.
Export Selective Exports only the key(s) associated with a
string of characters that you type into the text box. Each key is
associated with its encrypted tape cartridge, identified by the
tape cartridge barcode. You can type in all or part of a tape
cartridge barcode, and any keys that are associated with that
string will be exported. This is helpful if you only want to export
a single key associated with a particular tape cartridge.
5 Click Apply.
All the exported keys are saved to a single encryption key file.
6 A Save As dialog box opens allowing you to save the encryption key
file to a location on your computer. Choose a location and click
Save.

200 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 7: Encryption Key Management
Scalar Key Manager Functions Available on the Library

Importing Data SKM servers provide a unique encryption key for each tape cartridge
Encryption Keys that is encrypted. In order to read tapes encrypted by a different (i.e.,
source) SKM server, you need to import the encryption keys used to
encrypt those tapes onto your SKM server (i.e., destination).

Note: This function is available to administrators and only applies to


SKM servers. Both SKM servers must be connected and
operational in order to import encryption keys.

To import encryption keys:


1 Before starting this process, read and follow the sequence of steps
outlined in Sharing Encrypted Tape Cartridges on page 195.
2 Receive the file of encryption keys from the source SKM server and
save it in a known location on your computer.
3 From the Tools menu, select EKM Management > Encryption Key
> Import.

Figure 41 Importing Data


Encryption Keys

4 Click Browse to locate the saved file of encryption keys.


5 Click Open.
6 Click Apply to import the keys onto your SKM server.
7 Back up both SKM servers following the instructions in the Scalar
Key Manager Users Guide.

Quantum Scalar i40 and Scalar i80 Users Guide 201


Chapter 7: Encryption Key Management
Scalar Key Manager Functions Available on the Library

Caution: You must back up both SKM servers every time you
import data encryption keys to protect against
catastrophic server failure.

In case of an incomplete import, the library displays a message and


generates a diagnostic ticket. For instructions on what to do if this
happens, see Using the SKM Encryption Key Import Warning Log on
page 202.

Accessing the SKM The SKM server logs contain information about all activities performed
Server Logs by the SKM servers. You should not need to retrieve these logs unless
Quantum Support directs you to do so. You can download the logs to
your computer or e-mail them to a recipient. In order to e-mail the logs,
the library e-mail account must be configured (see Configuring the
Library E-Mail Account on page 76).
The path to open the appropriate screen is as follows:
From the Web client, select Tools > EKM Management > Retrieve
SKM Logs.

Using the SKM This log lists the tape cartridges for which encryption keys failed the
Encryption Key Import most recent encryption key import operation. If you have only partial
Warning Log success when importing a file of encryption keys (meaning, some keys
import successfully but some keys do not), the library displays an
import warning message and generates a diagnostic ticket that
directs you to view this log to see which keys did not get imported.
For each key that failed the import, the log provides a message type that
is either:
Error The key could not be imported.
Warning The key was imported, but the metadata update failed.
For each key that failed the import, the log provides one of the
following message descriptions:
CRC Data Missing Error. Metadata is missing for the key. This
means that the export file is corrupt. Suggested Solution: Export
the key(s) for the listed tape cartridge(s) again, and then perform
the import operation again.

202 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 7: Encryption Key Management
Scalar Key Manager Functions Available on the Library

CRC Check Failed Error. The CRC data does not match the key or
key metadata. The export file is corrupt. Suggested solution: Try to
import the same file again. If this fails, export the key(s) for the
listed tape cartridge(s) again, and then perform the import
operation again.
Import To Primary/Secondary Server Failed Error. The key
import to the stated server failed (probably due to a network or
other connection issue). If the key failed to import to the secondary
server, it may have been imported successfully to the primary server.
Suggested solution: Check network connections and perform the
import operation again.
Key Metadata Update Failed (but key data was imported
successfully) Warning. The key was imported, but the metadata
update failed. You can access the key, but you cannot export it until
it is actually used in an encryption operation on the library.
Suggested solution: Use the key to read (decrypt) a tape. This
marks the key as used and updates the metadata, which will allow
you to export the key.
This log is only available if you are running SKM and have encryption key
management licensed on the library (see Adding or Upgrading
Licensable Features on page 69).
The log file is cleared and created new for each import operation so that
it shows only the key corruptions and import failures that occurred
during the latest encryption key import attempt.
For more information about library logs, see SKM Encryption Key Import
Warning Log (with EKM License) on page 219.
The path to open the appropriate screen is as follows:
From the Web client, select Reports > Log Viewer.

Quantum Scalar i40 and Scalar i80 Users Guide 203


Chapter 7: Encryption Key Management
Scalar Key Manager Functions Available on the Library

204 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 8
Getting Information About
the Library

There are a number of informational screens and reports you can use to
get information about the library.
This chapter covers:
Viewing Library InformationViewing System Information
Viewing the Location of the Robot
Viewing the Library Configuration Report
Saving and E-mailing the Library Configuration Record
Viewing the Network Settings Report
Viewing the Logged in Users Report
Viewing the All Slots Report
Viewing, Saving, and E-mailing Library Logs
Viewing Library Information on the Operator Panel
Using Advanced Reporting Features
Viewing the Open Source License Agreement
Viewing the Copyright Statement

Quantum Scalar i40 and Scalar i80 Users Guide 205


Chapter 8: Getting Information About the Library
Viewing Library Information

Viewing Library Information


The About screen gives you a quick glance at the following library
settings:
Library type (Scalar i40 or Scalar i80)
Library serial number
Copyright date
Library firmware version

Web Client
Select Reports > About > Scalar i40/i80.

Viewing System Information


The System Information report contains information about the library.
On the operator panel, the report provides:
Physical library information serial number, system control board
(SCB) revision, firmware version, board support package (BSP)
version, date and time of last firmware update
Tape drives online/offline mode, firmware version, model,
physical serial number, logical serial number
Robot firmware versions XY control, picker, camera
On the Web client, the report provides:
Date & Time Current date, time, and time zone settings.
Physical Library Host name, IPv4 address, serial number, firmware
version of the physical library, IPv6 addresses if IPv6 support is
enabled, board support package (BSP) level, and the date the
firmware was last updated.

206 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 8: Getting Information About the Library
Viewing the Location of the Robot

Encryption (this section displays only if encryption key management


is licensed and configured on the library) Key server type;
encryption software version; SSL connection (enabled/disabled);
primary host (primary key server IP address or host name), primary
key server port number; primary key server serial number; secondary
host (secondary key server IP address or host name); secondary key
server port number; secondary key server serial number.
Library Partitions Name, serial number, control path, online/
offline status, encryption method, encryption type, number of
storage slots, number of media, and number of tape drives
configured for each partition.
Drives Location coordinates, vendor, model, type, serial number,
physical serial number (P-SN), logical serial number (L-SN), firmware
level, and encryption method.

Operator Panel
1 Select Reports > About Library.
2 Press Next to scroll through all the screens. Press Exit to exit at any
time.

Web Client
Select Reports > System Information.

Viewing the Location of the Robot


You can set the operator panel to view the robot position as library
operations are performed. This view is helpful in diagnosing any library
problems because you can see where the robot is, whether it contains a
tape, and the finger position.
If you perform an operation from the remote interface, the operator
panel displays the operation as it is performed. If you perform an
operation from the operator panel, once complete, you can return to
the Robot View to view the completed operation status.

Quantum Scalar i40 and Scalar i80 Users Guide 207


Chapter 8: Getting Information About the Library
Viewing the Location of the Robot

Note: The operator panel does not update the left side graphical
display until the motion is complete (success or failed)

On the operator panel, do the following:

Note: If you are viewing the alternate home screen, select Menu to
return to default home screen.

1 Select Tools > Robotic View.

The left graphical section depicts the top-down current location of


the robot on the X axis.
The numbers indicate the storage column.
The 'D' designates the tape drive column.

208 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 8: Getting Information About the Library
Viewing the Location of the Robot

The triangle represents the robot. If it is filled in, then the robot
contains the media, otherwise the robot is empty. The direction
the triangle points to indicates its location.
The right information section provides the following:
Describes the current or last operation performed. If the
operation performed affects a device location, the description
will be numericfor example Move Media: [1,2,5] to [1,5,1]. If
the operation affects a slot location, such as unlocking a
magazine, the description will be textual for example, Unlock:
Left Magazine.
Provides the status of the operationActive, Completed, or
Failed.
2 For additional information about the status, select Details.

This screen provides details for the library status:


Last Operation - Status of last completed operation
Succeeded or Failed.
Robot - The Robot location refers to where the robot was at the
end of the operation. For example, if the robot is between two
slots, it will display the robot location as Robot: At [0,1,4] -
[0,1,5]. If it is directly in front of a slot, it would then read, for
example At [0,4,4].
Picker - Extended or Retracted.

Quantum Scalar i40 and Scalar i80 Users Guide 209


Chapter 8: Getting Information About the Library
Viewing the Library Configuration Report

Picker Fingers - Engaged or Released.


3 Select Exit to return to the View.

Viewing the Library Configuration Report


The Library Configuration Report is a dynamic representation of the
various library resources, including tape drives, slots, partitions, and
library chassis. The report shows which slots are assigned to partitions,
I/E stations, configured as cleaning slots, or unassigned; whether the
slot contains a tape drive; and whether a tape drive is the control path
for its partition. You can view all slot location coordinates or media
barcodes at the click of a button, and get detailed information about a
specific resource by clicking on it.
You can view the report on the Web client.

Web Client
1 Select Reports > Library Configuration. The Library Configuration
Report displays in a new window.
2 Do any of the following:
In the Legend, click a partition name to view information about
the partition.

Note: Each partition is assigned a number and color. All slots


and tape drives that are assigned to a partition are
represented in the library map by the partition number
and color.

In the library map, click a specific slot to view information about


the slot.
In the library map, click a specific tape drive to view information
about the tape drive.
In the library map, click the chassis number (0) below the tape
drives to view information about the chassis.

210 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 8: Getting Information About the Library
Viewing the Library Configuration Report

Click Show Barcodes to display the barcodes for all imported


cartridges.
By default, the Library Configuration Report displays the
coordinates for all licensed slots that are assigned to a partition.
To view all library slot coordinates, click Show ALL coordinates.
To print the report, click the Print icon in the upper right of the
screen.

Clicking on a resource (tape drive, slot, partition, or chassis) brings up a


detailed window containing the following information:
Tape Drives The following information is provided for each
installed tape drive:
Fibre Channel tape drive interface type, tape drive type,
state (ready/not ready), status (online/offline), assigned partition
name, location coordinates, media barcode (if media is in slot;
No_Label means unreadable barcode), media type (if media is
in the slot), element address, vendor, model, form factor (half
height or full height), physical SN, logical SN, world wide node
name (WWNN), world wide port name (WWPN), loop ID,
requested topology, requested speed, actual topology, actual
speed, maximum speed, tape drive firmware level, whether the
tape drive is the control path for its partition, and encryption
method.
Serial Attached SCSI (SAS) tape drive interface type, tape
drive type, state (ready/not ready), mode (online/offline),
assigned partition name, location coordinates, media barcode
(if media is in slot; No_Label means unreadable barcode),
media type (if media is in slot), element address, vendor, model,
form factor (half height or full height), physical SN, logical SN,
SAS Address, tape drive firmware level, whether the tape drive is
the control path for its partition, and encryption method.
Slots The following information is provided for each slot: type,
assigned partition name (storage and I/E station slots only), location
coordinates, cartridge barcode (storage and I/E station slots only;
No_Label means unreadable barcode), media type, element
address, encryption method, get count, get retries, put count, and
put retries. If the slot is a cleaning slot, the cleaning status (usable/
expired) and cleaning count (the number of times the cartridge was
used to clean a tape drive) are also displayed.

Quantum Scalar i40 and Scalar i80 Users Guide 211


Chapter 8: Getting Information About the Library
Saving and E-mailing the Library Configuration Record

Partitions The following information is provided for each


partition: name, status (online/offline), emulation type, barcode
policy, total number of tape drives, number of active tape drives,
total media, mounted media, total slots, full slots, total I/E station
slots, full (occupied) I/E station slots, and encryption method.
Chassis The following information is provided for each chassis:
manufacturer, model, and serial number.

Saving and E-mailing the Library Configuration Record


The library configuration record is a text file that contains details about
the librarys configuration. The configuration record can be saved or
e-mailed to a specified e-mail address.Information in the library. The
configuration record includes:
Product information Vendor, model, product ID, product version
(library firmware version), and serial number
License information License keys installed and descriptions,
installation date, and expiration date
Primary Network Information Host Name, DHCP enabled/disabled,
IP address, netmask, gateway, Ethernet MAC, Ethernet link speed
(Mbits/s), and Ethernet link present
Chassis information Manufacturer, model, serial number, and
location
Tape drive information:
Fibre Channel (FC) tape drives Partition name, number of
tape drives in partition, drive location, SCSI element address,
online status, active status, ready state, vendor, model, form
factor, serial number, firmware version, drive type, logical serial
number, interface type, World Wide (WWN), loop ID, topology,
actual topology, speed, and actual speed

212 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 8: Getting Information About the Library
Saving and E-mailing the Library Configuration Record

Serial Attached SCSI (SAS) tape drives partition name,


number of tape drives in partition, drive location, SCSI element
address, interface type, drive type, ready state, online status,
barcode, media type, element address, vendor, model, physical
serial number, logical serial number, SAS Address, firmware
level, control path status

Note: The library configuration report lists the native device


identifier as reported by the tape drive. HP tape drives
always report SCSI as the native device identifier, even
if they are Fibre Channel or SAS. For example, if you
have HP L TO-4 Fibre Channel or SAS drives, they will be
listed in the report as HP LTO-4 SCSI drives.

Partition information:
Library information Number of partitions, number of
cleaning slots, number of unassigned slots, number of import/
export (I/E) slots, I/E manual assignment setting
Partition details Partition name, number of slots, number of
tape drives, and number of cartridges

Saving the Administrators can use the Tools - Save Configuration Record screen on
Configuration Record the Web client to e-mail the library configuration record.
You can only save the library configuration record from the Web client.

Web Client
1 Select Tools > Save Configuration Record.
2 Save the file to a known location on your computer.

E-mailing the Administrators can use the Tools - E-mail Configuration Record screen on
Configuration Record the Web client to e-mail the library configuration record.

Quantum Scalar i40 and Scalar i80 Users Guide 213


Chapter 8: Getting Information About the Library
Viewing the Network Settings Report

Note: Do not enter more than one e-mail address in the E-mail
Address text box on the Tools - E-mail Configuration Record
screen. If you need to send the configuration record to multiple
e-mail addresses, repeat the procedure for each e-mail address.

Before you can e-mail the configuration record, the library e-mail
account must be configured. For information on setting up the e-mail
account, see Configuring the Library E-Mail Account on page 76.
You can only e-mail the library configuration record from the Web
client.

Web Client
1 Select Tools > E-mail Configuration Record.
2 Type an e-mail address into the E-mail Address text box.
3 Click Apply.

Viewing the Network Settings Report


The Network Settings report provides information on the following
library settings:
Network Host name, primary DNS, and alternate DNS
IPv4 Settings DHCP enabled/disabled, IP address, gateway, and
netmask
IPv6 Settings (if IPv6 is enabled) DHCP enabled/disabled,
stateless configuration enabled/disabled, static configuration
enabled/disabled, net prefix, gateway, and all IPv6 addresses
SSL SSL, port, and cipher
SMI-S Access (enabled/disabled) and state (enabled/disabled)
SNMP Enabled/disabled status for Access, V1, V2, V3, and
encryption; algorithm; and port
SNMP-Traps IP addresses and ports

214 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 8: Getting Information About the Library
Viewing the Logged in Users Report

Web Client
Select Reports > Network Settings.

Viewing the Logged in Users Report


The Logged In Users report contains information about the users that
are currently logged in to the library.
The report contains the following information about each user:
User Name User name of logged in user
Privilege Privilege level of the logged in user (Admin for
administrator, User for user)
Login Date/Time Date and time the user logged into the library
Last Activity Date/Time Date and time when the user last logged
into the library
Login Location IP address or host name of the system used to
access the library
User Interface User interface used to access the system (Web
Client or Operator Panel)

Web Client
Select Reports > Logged in Users. The report displays in a new
window.

Viewing the All Slots Report


The All Slots report contains information on all storage, import/export (I/
E) station, and tape drive slots that are currently assigned to one or
more partitions.

Quantum Scalar i40 and Scalar i80 Users Guide 215


Chapter 8: Getting Information About the Library
Viewing the All Slots Report

The report contains the following information about each slot:


Slot Type I/E station, storage, cleaning, or tape drive slot.
Barcode Barcode number of the cartridge installed in the slot. No
barcode number means the slot is empty. No_Label means the
barcode is unreadable.
Partition Partition that owns the slot (I/E station slots are shared
by all partitions).
Location Location coordinates of the slot.
Element Address Element address of the slot.
Encryption The encryption state of the media in the slot. In order
for the library to know the encryption state, the tape must have
been placed into an encryption-capable tape drive in the library. The
encryption-capable tape drive reads and records the encryption
state of the tape, and the encryption state displays as Encrypted
or Not Encrypted. If the tape was not placed into an encryption-
capable tape drive in the library, or if the slot is empty, the
encryption state displays as Unknown.
Get Count The number of times the picker successfully removed
a tape from the slot.
Get Retries The number of times the picker had to perform a
recovery operation to remove a tape from the slot.
Put Count The number of times the picker successfully placed a
tape into the slot.
Put Retries The number of times the picker had to perform a
recovery operation to place a tape into the slot.

Web Client
Select Reports > All Slots.

216 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 8: Getting Information About the Library
Viewing, Saving, and E-mailing Library Logs

Viewing, Saving, and E-mailing Library Logs


You can view, save, and e-mail several logs containing information
about the library:
Cleaning Log
Diagnostic Tickets Log
Media Security Log (available only with Advanced Reporting license)
Media Usage Log (available only with Advanced Reporting license)
SKM Encryption Key Import Warning Log (with EKM License)
Tape Drive Log

Cleaning Log The Cleaning Log shows all cleanings that have been performed in the
library. When the log reaches its maximum size, the oldest information
is replaced as new information is added.
The log provides the following information: Date Time (date and time);
Barcode (barcode of the cleaning cartridge); Tape (location coordinates
of the cleaning cartridge); Drive (location coordinates of the tape drive
that was cleaned); Status (pass/fail); Return Code (service use only),
Cleaning Type (Manual, Auto, MoveMedium), Expired (Invalid if the
tape is expired or a data tape was improperly used to clean; - if not
applicable); Usage Count (N/A if the cleaning did not complete);
Reserved.

Web Client
1 Select Reports > Log Viewer.
2 Select Cleaning Log and press Next.
The report displays in a new window for viewing.
3 You can save or e-mail the report following the on-screen
instructions.

Quantum Scalar i40 and Scalar i80 Users Guide 217


Chapter 8: Getting Information About the Library
Viewing, Saving, and E-mailing Library Logs

Note: If you want to e-mail the log file to a recipient, type the
recipients name in the text box next to the E-mail button,
and then click the E-mail button. You must have your e-
mail notification configured in order to e-mail a log file.
See Configuring the Library E-Mail Account on page 76 for
more information.

Diagnostic Tickets Log The Diagnostic Tickets Log records all diagnostic tickets issued by the
library.
The log provides the following information: Num (ticket number to
provide a consecutive listing of tickets in the order issued; the first ticket
issued is assigned number 1, the second ticket 2, and so on); State
(open, unopened, closed); Priority (low, high, urgent); Created (date the
ticket was first issued); Last Updated (date the ticket was last issued);
Cause Code (the number assigned to the fault and which displays in the
full ticket name; for example, DT031- I/E Unlock Warning has cause code
31); Description; and Details.

Web Client
1 Select Reports > Log Viewer.
2 Select Diagnostic Tickets Log and press Next.
The report displays in a new window for viewing.
3 You can save or e-mail the report following the on-screen
instructions.

Note: If you want to e-mail the log file to a recipient, type the
recipients name in the text box next to the E-mail button,
and then click the E-mail button. You must have your e-
-mail account configured in order to e-mail a log file. See
Configuring the Library E-Mail Account on page 76 for
more information.

218 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 8: Getting Information About the Library
Viewing, Saving, and E-mailing Library Logs

Media Security Log Note: To access the Media Security log, your library must have an
(with Advanced Advanced Reporting license. To learn more about the Advanced
Reporting License) Reporting license, refer to Advanced Reporting on page 14.

Media removal is detected by the library when it performs an inventory


(at boot up; after an open door is closed, etc.). The media security log
lists media that have been removed from the library. By default, the
library collects nothing and the log is empty. You can configure the
library to collect information about media removal, and then view, save,
and/or e-mail the log. Refer to Working with the Media Security Log on
page 126.

Media Usage Log (with Note: To access the Media Usage log, your library must have an
Advanced Reporting Advanced Reporting license. To learn more about the Advanced
License) Reporting license, refer to Advanced Reporting on page 14.

The media usage log lists media usage information regarding capacity
and read and write errors for media ever mounted in a drive., including
media that are no longer in the library. Refer to Viewing the Media
Usage Log on page 129.

SKM Encryption Key Note: To access the SKM Encryption Key Import Warning log, your
Import Warning Log library must have an Encryption Key Management (EKM)
(with EKM License) license. To learn more about the EKM license, refer to
Encryption Key Management on page 15.

Lists keys that failed the most recent data key import operation. This log
is only available if you are running Scalar Key Manager (SKM). For
detailed information about this log, see Using the SKM Encryption Key
Import Warning Log on page 202.

Web Client
1 Select Reports > Log Viewer.
2 Select SKM Encryption Key Import Warning Log and press Next.
3 The report displays in a new window for viewing.

Quantum Scalar i40 and Scalar i80 Users Guide 219


Chapter 8: Getting Information About the Library
Viewing, Saving, and E-mailing Library Logs

4 You can save or e-mail the report following the on-screen


instructions.

Note: If you want to e-mail the log file to a recipient, type the
recipients name in the text box next to the E-mail button,
and then click the E-mail button. You must have your
e-mail account configured in order to e-mail a log file. See
Configuring the Library E-Mail Account on page 76 for
more information.

Tape Drive Log The library allows you to retrieve tape drive logs using the Web client.
Tape drive log information can be used to help troubleshoot the library,
the tape drive sled, and tape drive issues.
Since the log retrieval process can take up to 30 minutes, the tape drive
and associated partition are automatically taken offline during the
operation and brought back online when the operation completes. You
will be asked to confirm that you want to take the tape drive and
partition offline.
Tape drive log files adhere to the following naming convention:
UDS_ID_SN.DMP, where ID identifies the tape drive coordinate location
within the library and SN identifies the tape drive serial number.

Web Client
1 Select Tools > Drive Operations.
2 Select Retrieve tape drive log and click Next.
3 If your library contains multiple tape drive interface types, select the
interface type of the tape drive from which you want to retrieve logs
and click Next.
4 The Retrieve Drive Log screen displays. This screen lists the available
tape drives.
5 Select a tape drive from which you want to retrieve logs and click
Next.

Note: If there is more than one page of tape drives, use the Page
1 of x arrows to view the additional tape drives.

220 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 8: Getting Information About the Library
Viewing Library Information on the Operator Panel

Note: Bold column headings in the table can be sorted. For


example, selecting the Location column heading will sort
by location coordinates.

6 Click Apply.
A dialog displays asking you to confirm you want to take the
partition offline.
7 Click OK.
The Progress Window displays, displaying information on the
action, elapsed time, and status of the operation.
8 If the Progress Window displays a completed message, you can
close the window and save the file to your computer.
9 If the screen displays a failure message, the tape drive log was not
successfully retrieved. Follow the instructions listed in the Progress
Window to resolve any issues that occurred during the operation. If
a complete tape drive log could not be retrieved, you may still be
able to access a partial log. If so, a note will appear stating, A
complete tape drive log could not be retrieved, but a partial log is
available and may be saved for further analysis once the progress
window is closed.

Viewing Library Information on the Operator Panel


The operator panel provides several brief reports about the library.

Viewing Partition The operator panel provides an overview of partition information. For
Information each partition, you can see the following information:
Online/offline mode
Control path tape drive location coordinates
Number of tape drives
Number of storage slots

Quantum Scalar i40 and Scalar i80 Users Guide 221


Chapter 8: Getting Information About the Library
Viewing Library Information on the Operator Panel

Number of I/E station slots containing a tape cartridge assigned to


the partition

Operator Panel
1 Select Reports > Partitions.
2 If the library contains more than one partition, use the Up and
Down buttons to select a partition and press Select.

Viewing Tape Drive The operator panel provides an overview of tape drive information. For
Information each installed tape drive, you can see the following information:
Online/offline mode
Partition to which the tape drive is assigned
Whether the tape drive is the control path for the partition
State (ready/active/mounted)
WWNN (if Fibre Channel) or SAS address (if SAS)

Operator Panel
1 Select Reports > Tape Drives.
2 If the library contains more than one tape drive, use the Up and
Down buttons to select a tape drive and press Select.

Viewing Network A short report on the operator panel displays the librarys network
Settings settings: host name, IP address, and network configuration.

Operator Panel
1 Select Reports > Network Settings.
2 If IPv6 is enabled, the IPv4 information is shown on the first screen.
Press Next to see the IPv6 address information on the next two or
more screens. Although the library can have unlimited IPv6 address,
a maximum of three are shown in this report.

222 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 8: Getting Information About the Library
Using Advanced Reporting Features

Viewing the Date, Time, The operator panel displays the current date, time and time zone
and Time Zone configured on the library.

Operator Panel
Select Reports > Date/Time.

Viewing Licenses The operator panel displays a list of all the licenses currently installed on
the library: number of COD slots licensed, number of unlicensed slots,
and whether Advanced Reporting is licensed.

Operator Panel
Select Reports > Licenses.

Using Advanced Reporting Features


Advanced Reporting features are only available if you have Advanced
Reporting licensed on the library. See Chapter 5, Advanced Reporting
for more information.

Viewing the Open Source License Agreement


A number of open source packages were used to create the library
firmware. You can view the open source license agreement on the Web
client.

Web Client
Select Reports > About > Open Source Licenses.

Quantum Scalar i40 and Scalar i80 Users Guide 223


Chapter 8: Getting Information About the Library
Viewing the Copyright Statement

Viewing the Copyright Statement

Operator Panel
Select Reports > Copyright Statement.

Web Client
Available in the Web client online help. To view the help, click the Help
icon in the upper right corner of the screen.

224 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 9
Installing, Removing, and
Replacing Components

This chapter describes how to add, remove, and replace hardware


components within your library.

WARNING: Two people are required to lift and install the library.

WARNING: Under no circumstances should a rack be moved while a


library is installed.

This chapter covers:


Taking ESD Precautions
Connecting Library Cables
Installing the Rack Mount Kit (Rail Kit)
Installing the Library In a Rack
Removing the Library From a Rack
Installing the Library in a Desktop Kit
Removing the Library from a Desktop Kit
Removing and Replacing the Front Bezel
Replacing the Chassis
Removing and Installing a Filler Plate

Quantum Scalar i40 and Scalar i80 Users Guide 225


Chapter 9: Installing, Removing, and Replacing Components
Taking ESD Precautions

Removing and Replacing a Magazine


Removing and Installing a Power Supply
Removing and Replacing the System Control Board
Removing and Replacing a Tape Drive
Packaging the Library for Moving or Shipping
Replacing the Y-tray with Robot

Taking ESD Precautions


Some components within the Scalar i40 and Scalar i80 libraries contain
static-sensitive parts. To avoid damaging these parts while performing
installation procedures, always observe the following precautions:
Use an antistatic wrist strap. If you do not have one, touch the
outside of the library on the sheet metal before touching any
components to discharge static from your body.
Keep static-sensitive parts in their original shipping containers until
ready for installation. Look for the ESD sticker to identify static
sensitive parts.

Avoid touching connectors and other components.

Note: Dry climates and cold-weather heating environments have


lower relative humidity and are more likely to produce static
electricity.

226 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 9: Installing, Removing, and Replacing Components
Connecting Library Cables

Connecting Library Cables


Connect the cords and cables as follows (see Figure 42 on page 228). It
is recommended that you leave some slack in the cables to allow you to
perform certain replacement procedures in the future.
1 Connect the tape drive cables from the tape drives to the host.

Caution: Use care when handling the fibre optic cables. Do not
crimp or bend the cables. Do not exceed the bend
radius specified by the manufacturer.

2 Connect an Ethernet cable (not supplied with your library) into the
LEFT port on the system control board (SCB). The right SCB port is
for service use only; do not use. Connect the other end of the
Ethernet cable into a live Ethernet jack connected to your network.
3 Connect the power supply cord into the power supply connector.
Plug the other end of the cord into a grounded AC outlet.

Quantum Scalar i40 and Scalar i80 Users Guide 227


Chapter 9: Installing, Removing, and Replacing Components
Connecting Library Cables

Figure 42 Connection
Locations

Full-height tape drives


Filler plate Power supply cord

Filler plate

Tape drive cables Ethernet cable in Service port do not use


LEFT SCB port

Half-height tape drives


Power supply cord

Filler plate

Tape drive cables Ethernet cable in Service port


LEFT SCB port do not use

228 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 9: Installing, Removing, and Replacing Components
Installing the Rack Mount Kit (Rail Kit)

Installing the Rack Mount Kit (Rail Kit)

The instructions for installing the rails are the same for both the Scalar
i40 and the Scalar i80.

WARNING: If the rack is empty at the time of installation, do NOT


install the library too high in the rack. The weight of the
library may cause the rack to become top heavy and
unstable if installed in the top of an empty rack.

WARNING: Do not stack objects on top of the library such as cables


or other computer equipment. The additional weight
could exceed the amount supported by the rack shelves.

Caution: Make sure the rack mounting rails are level, both left to
right and front to back. If the library is not level in the rack,
it will not work properly.

Supported Rack Types The Scalar i40 and Scalar i80 libraries are designed to fit in most
standard 19-inch equipment cabinets, including:
Dell, 08P157 (US-08P157910-3AU-0900),square, 2.48 - 2.72 mm
thick
SUN, 38U, NGR900R, M6
Emcor, 10 Series, round hole
IBM, Machine Type 9306, Model 900, square, 28.25-inch deep, 2.0-
2.25 mm thick
HP, 10K, PN 245169-001, Asm 10642U GR Metallic, square, 2.0-
2.2 mm thick
EMC CX500
Rittal Cable Tester Rack Frame, square
Rack depth of 34 in. (86.3 cm) minimum is recommended; however,
rack depths of 24 to 36 in. (60.9 to 91.4 cm) are supported.

Quantum Scalar i40 and Scalar i80 Users Guide 229


Chapter 9: Installing, Removing, and Replacing Components
Installing the Rack Mount Kit (Rail Kit)

Space Requirements See the following:


Physical Specifications on page 341 and
Air Clearance Requirements on page 343

Tools Required Phillips screwdriver


Magazine lock override tool an opened paperclip, small
screwdriver, or other object (3.5 mm or less in diameter that will not
break off)

Rack Mount Kit The following items are included in the rack mount kit:
Contents

Qty Figure Description

2 Shelf

2 Shelf Extender

16 Phillips head screw, countersunk (M5 x 10) for


shelf assembly

230 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 9: Installing, Removing, and Replacing Components
Installing the Rack Mount Kit (Rail Kit)

Qty Figure Description

8 T- nut (M5) for shelf assembly

8 total Rail adapter 4 each of two types are included. You


need 4 for installation; choose the type appropriate
for your rack (for more information, see Figure 45
on page 235)

8 Phillips head screw, countersunk (M4 x 12) for


mounting shelves to rack

8 Washer, countersunk for mounting shelves to rack

4 Clip nut (M5 x 0.8) for securing library in rack

4 Cage nut (M5) to secure library to rack. Used in


racks with square or round non-threaded holes.

Quantum Scalar i40 and Scalar i80 Users Guide 231


Chapter 9: Installing, Removing, and Replacing Components
Installing the Rack Mount Kit (Rail Kit)

Installing the Rack Before installing the rack mount shelves, you must collect the following
Mount Shelves information:
Type of rack mount rails (square hole, through hole, or threaded
hole)
Depth of rack
1 Assemble the rack mount shelves included in the accessory kit (left
and right):
a The holes used to attach the two halves of the rack mount
shelves differ depending on the depth of the rack (see Figure 43
on page 233). It is recommended that you use the ones that are
exposed and have the widest spacing.

232 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 9: Installing, Removing, and Replacing Components
Installing the Rack Mount Kit (Rail Kit)

Figure 43 Rack Mount Shelf


Use these holes for rack
Depth Requirements

Rear of rack
depths of 24 in (60.9
cm) to 28 in (71.1 cm)

Use these holes for rack


Front of rack

depths of 27 in (68.5
cm) to 36 in (91.4 cm)
Rear of rack

Use these holes for rack


depths of 24 in (60.9
cm) to 28 in (71.1 cm)

Use these holes for rack


depths of 27 in (68.5
cm) to 36 in (91.4 cm)

b Loosely attach the rack mount shelves to the extenders with 4


M5 x 10 screws and T-nuts (see Figure 44).

Quantum Scalar i40 and Scalar i80 Users Guide 233


Chapter 9: Installing, Removing, and Replacing Components
Installing the Rack Mount Kit (Rail Kit)

Figure 44 Assembling the Left The metal fold T-nuts must be oriented as
and Right Rack Mount Shelves must be toward shown to properly fit in the
the outside of shelf adjustment slot
the shelf as r
de

Back of rack
shown
ten
Ex
T-nuts

elf
t sh
un
Front of rack

k mo M5 x 10 screws
rac
ide
f t -s
Le

T-nuts must be
oriented as shown
to properly fit in
the shelf
The metal
adjustment slot
fold must
Ex be toward
te n
de the
r
Back of rack

outside of
the shelf
as shown

T-nuts

Rig
ht
M5 x 10 screws -si
d er
ac
k mo
un
ts
he
lf

234 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 9: Installing, Removing, and Replacing Components
Installing the Rack Mount Kit (Rail Kit)

c Determine the type of rail adapter required for your rack. Each
rail adapter is marked with the specific hole type supported (see
Figure 45).

Figure 45 Rail Adapter Types

Use the rail adapters with


blocks on rails with square
hole patterns

Use the rail adapters with


circle pegs (opposite blocks)
on rails with non-threaded
circle hole patterns

Use the rail adapters with small


circle pegs on rails with threaded
circle hole patterns (M6 on one side
and M5 on the other side)

Quantum Scalar i40 and Scalar i80 Users Guide 235


Chapter 9: Installing, Removing, and Replacing Components
Installing the Rack Mount Kit (Rail Kit)

d Attach the appropriate rail adapter to the front and back of the
rack mount shelves (right and left) with 2 M5 x 10 screws per
adapter (see Figure 46).

Figure 46 Assembling the Left-


Hand Rack Mount Shelf Rail adapter
Arrow must
point up

M5 x 10
elf screws
sh
ft
Le

Rail adapter M5 x 10
screws Arrow must
point up

Rail adapters

M5 x 10
screws
Rig
ht
sh
elf

M5 x 10
screws

236 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 9: Installing, Removing, and Replacing Components
Installing the Rack Mount Kit (Rail Kit)

2 Install the left and right rack mount shelves into the rack (the rack
mount shelves adjust 24 to 36 in.) and secure with the following
parts in four locations (see Figure 47 on page 238):
2 washers
2 M4 x 12 screws

Note: The rack mount shelves must be installed on the inside rack
rails.

Quantum Scalar i40 and Scalar i80 Users Guide 237


Chapter 9: Installing, Removing, and Replacing Components
Installing the Rack Mount Kit (Rail Kit)

Figure 47 Installing the Rack


Mount Shelves

Washers

M4 x 12
screws

Left shelf

Right shelf

238 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 9: Installing, Removing, and Replacing Components
Installing the Rack Mount Kit (Rail Kit)

3 Once the rack mount shelves are secured to the rack, tighten the
screws securing the adjustable shelves (right and left) together (see
Figure 48).

Figure 48 Tightening the Rack


Mount Shelves

Tighten screws to secure


both rack mounting rails

Quantum Scalar i40 and Scalar i80 Users Guide 239


Chapter 9: Installing, Removing, and Replacing Components
Installing the Rack Mount Kit (Rail Kit)

4 If the rack does not have threaded holes, install a clip nut or a cage
nut in the back side of the rail, in the first empty hole below the rail
adapter. This is what you will screw the library thumbscrews into to
secure the library in the rack. See table below for type of nut, and
Figure 49 on page 241 for installation location.

Type of Rail/Type of Nut Description

Square rack holes are the most


common type of rack holes. They can
accept either cage nuts which mount
Cage nut from the back of the rail or clip nuts
which clip on from the side of the
rack rail.

Clip nut

Round, unthreaded holes require clip


Clip nut nuts to accept mounting hardware.

Threaded holes require neither cage


or clip nuts to accept mounting
hardware.

240 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 9: Installing, Removing, and Replacing Components
Installing the Library In a Rack

Figure 49 Location for


Installing the Clip Nut or Cage
Nut

Rail adapter

Clip nut or cage nut installed in the first


empty hole below rail adapter

Installing the Library In a Rack

Caution: Make sure the rack mounting rails are level, both left to
right and front to back. If the library is not level in the rack,
it will not work properly.

WARNING: At least two people are required to lift and install the
library.

1 If tape drives are installed in the library, you may wish to remove
them to reduce weight. To remove tape drives, unscrew the captive
thumbscrews securing them to the back of the library and slide
them out of the library. Set them down gently on a stable surface.

Quantum Scalar i40 and Scalar i80 Users Guide 241


Chapter 9: Installing, Removing, and Replacing Components
Installing the Library In a Rack

2 Lift the library, place it on the rack shelves, and slide it into the rack
as far as it will go.
3 Open one of the magazines slightly to access the captive
thumbscrew that is attached to the library chassis. You will use this
thumbscrew to secure the library to the rack. To open the magazine,
insert the magazine lock override tool into the access hole in the
bottom of the magazine bezel (see Figure 50 on page 242). Use the
tool to depress the release latch while gently pulling outward on the
magazine bezel handle.

Right-side magazines will only slide out as far as the I/E station (one
column of slots). To release the right-side magazines fully:
On the Scalar i40 and the bottom right magazine of the Scalar
i80, reach under the open magazine and insert the tool directly
into the access hole in the library chassis to depress the release
latch, while pulling out on the magazine bezel handle.
On the top right magazine of the Scalar i80, reach under the
open magazine and press the release latch directly with your
finger, while pulling out on the magazine bezel handle.

Figure 50 Magazine Release


Latch Access Holes

Magazine release latch access holes

4 Screw the captive thumbscrew finger-tight into the rack (and


through the clip nut or cage nut, if installed). See Figure 51 on
page 243.
5 Repeat Step 3 and Step 4 for the remaining thumbscrews.
6 Close all the magazines by pushing them in until they click shut.

242 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 9: Installing, Removing, and Replacing Components
Removing the Library From a Rack

Figure 51 Securing the


Scalar i40 and Scalar i80 in the
Rack

Removing the Library From a Rack

WARNING: At least two people are required to lift the library and
remove it from a rack.

1 Shut down the library by selecting Actions > Shutdown from the
operator panel.
2 Turn OFF the library by pressing the power button on the front
panel.
3 Disconnect the power supply cord, the Ethernet cable, and all tape
drive cables from the back of the library. If you have multiple tape
drives, label the cables so you can reconnect them to the correct
tape drives later.

Quantum Scalar i40 and Scalar i80 Users Guide 243


Chapter 9: Installing, Removing, and Replacing Components
Installing the Library in a Desktop Kit

4 Remove all the tape drives from the library (for details, see
Removing and Replacing a Tape Drive on page 286).
5 Remove all the magazines from the library (for details, see Removing
and Replacing a Magazine on page 271).
6 Unscrew the captive thumbscrews in the rack ears that secure the
library to the rack (see Figure 51 on page 243).
7 Slide the library out of the rack. Keep the library level as you slide it
out of the rack.
8 Place the library on a flat, stable surface.

Installing the Library in a Desktop Kit


The instructions for installing the Scalar i40 and the Scalar i80 in a
desktop are the same. The only difference is that the Scalar i40 has two
side panels, and the Scalar i80 has four.

244 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 9: Installing, Removing, and Replacing Components
Installing the Library in a Desktop Kit

Figure 52 Desktop Kit,


Scalar i40 and Scalar i80

Scalar i40

Scalar i80

Quantum Scalar i40 and Scalar i80 Users Guide 245


Chapter 9: Installing, Removing, and Replacing Components
Installing the Library in a Desktop Kit

Kit Contents
Item Quantity

Top cover 1

Side panel 2 for the Scalar i40; 4


for the Scalar i80

Top cover screws 2

Rubber feet 8

Tools Required Phillips screwdriver


Magazine lock override tool an opened paperclip, small
screwdriver, or other object (3.5 mm or less in diameter that will not
break off)

246 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 9: Installing, Removing, and Replacing Components
Installing the Library in a Desktop Kit

Space Requirements See the following:


Physical Specifications on page 341 and
Air Clearance Requirements on page 343

Procedure WARNING: Two people are required to safely lift the library.

1 If your library is currently installed in a rack, remove the magazines


and tape drives, and then remove the library from the rack. See
Removing the Library From a Rack on page 243.
2 Set the library on the desk or table in your chosen location.
3 Remove all the magazines from the library (if you have not already
done so), as follows:
a Insert the magazine lock override tool into the access hole in the
bottom of the magazine bezel (see Figure 53).
b Use the tool to depress the release latch while gently pulling
outward on the magazine bezel handle. If the magazine is on
the right side, it will only slide out as far as the I/E station. To
release the magazine fully:
On the Scalar i40 and the bottom right magazine of the
Scalar i80, reach under the open magazine and insert the
tool directly into the access hole in the library chassis to
depress the release latch, while pulling out on the magazine
bezel handle.
On the top right magazine of the Scalar i80, reach under the
open magazine and press the release latch directly with
your finger, while pulling out on the magazine bezel handle.

Quantum Scalar i40 and Scalar i80 Users Guide 247


Chapter 9: Installing, Removing, and Replacing Components
Installing the Library in a Desktop Kit

Figure 53 Magazine Release


Latch Access Holes

Magazine release latch access holes

4 Look through the magazine slot openings to be sure the Y-tray is


resting on the floor of the library. If not, reach inside and gently
press down on one of the Y-trays side metal rods until the Y-tray
starts moving. It should drift down to rest on the floor of the library.
5 Turn the library carefully on its side (either the left or right side).
Make sure the front end of the library (the rack ear) overhangs the
edge of the table so that the library lies flat.
6 Install the eight rubber feet on the bottom of the library, as follows:
a There are eight holes in the bottom of the library into which you
will press the rubber feet. Four holes are located along the right
edge and four along the left edge. Figure 54 shows the
locations of these holes.
b Use your fingers to press the feet into the holes. Twisting the
feet as you push them may make it easier to get them in. See
Figure 54 on page 249.
c Carefully turn the library back to an upright position so that it is
resting on its rubber feet.

248 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 9: Installing, Removing, and Replacing Components
Installing the Library in a Desktop Kit

Figure 54 Location of Rubber


Feet on Bottom of Library

7 Install the side panels one at a time (in any order) as follows (see
Figure 55 on page 251):
a Orient the side panel correctly. They are all the same but can
only be installed one way. Line up the eight posts on the inside
of the side panel with the holes in the side wall of the library.
Line up the screw hole in the bottom front of the side panel
with the captive thumbscrew behind the magazine on the
library chassis.
b Press the side panel against the wall so that the posts go into
the holes.

Quantum Scalar i40 and Scalar i80 Users Guide 249


Chapter 9: Installing, Removing, and Replacing Components
Installing the Library in a Desktop Kit

c Slide the side panel toward the front of the library about half an
inch until it stops and the posts are engaged in the holes. The
side panel should be flush with the side of the library chassis.
d Tighten the thumbscrew at the front of the library to secure the
side panel to the library.

250 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 9: Installing, Removing, and Replacing Components
Installing the Library in a Desktop Kit

Figure 55 Installing side panels

Holes for side


panel posts

Magazine release Captive Hole for captive


access holes thumbscrew thumbscrew

Inset showing captive thumbscrew behind open magazine

Quantum Scalar i40 and Scalar i80 Users Guide 251


Chapter 9: Installing, Removing, and Replacing Components
Removing the Library from a Desktop Kit

8 Install the top cover as follows (see Figure 56):


a Slide the top cover onto the library, from back to front. The back
of the top cover has two screw holes and overhangs the back of
the library.
b Install the two top cover screws through the top cover and into
the screw holes in the top of the side panels.

Figure 56 Installing Top Cover

9 Re-install the magazines and push them in until they close.


10 Re-install tape drives if you removed them previously.
11 Connect the tape drive cables, Ethernet cable, and power cord (see
Connecting Library Cables on page 227).

Removing the Library from a Desktop Kit


To remove the library from a desktop kit, reverse the steps in Installing
the Library in a Desktop Kit on page 244.

252 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 9: Installing, Removing, and Replacing Components
Removing and Replacing the Front Bezel

Removing and Replacing the Front Bezel

The procedure is similar for the Scalar i40 and the Scalar i80. Pictures
of the Scalar i40 also apply to the Scalar i80.
You may perform this procedure with library power ON. If you do, be
careful not to accidentally press the power button and turn the library
off when installing the bezel.
Read these instructions completely before beginning.

Required Tools Phillips #1 screwdriver

Bezel Replacement Kit 1 Bezel


Contents 4 screws

Bezel Replacement 1 Stop all library operations.


Procedure 2 Open all the magazines in the library a few inches or remove them
completely from the library.

Note: There is less chance of scratching or damaging the new


bezel when you install it if you completely remove the
magazines. On the Scalar i80, it is easier to perform this
procedure with at least the bottom two magazines
completely removed. You need room to maneuver your
fingers on the sides of the bezel. If you remove all the
magazines from a Scalar i80, label them so that you can
reinstall them in the same locations later.

a On the operator panel, select Actions > Magazine.


b Select a magazine and press Release.
c When prompted, pull open the magazine a few inches or
remove the magazine completely.

Quantum Scalar i40 and Scalar i80 Users Guide 253


Chapter 9: Installing, Removing, and Replacing Components
Removing and Replacing the Front Bezel

d Repeat for all magazines in the library.


3 Prepare to gain access to the bezel screws (see Figure 57 on
page 255 and Figure 58 on page 256 for locations). The method
depends upon how your library is installed. Follow the instructions
in the table below that correspond to your library installation.

If your library is... Follow these steps...

Installed in a rack high enough Unscrew all the thumbscrews that secure the library to
to access to the bottom bezel the rack (the Scalar i40 has two thumbscrews; the
screws Scalar i80 has four). See Figure 58 on page 256.

Installed in a desktop kit Release the desktop cover by removing two screws at
rear of the desktop cover, then slide the desktop cover
toward the back of the library two or three inches.

Installed very low in a rack so Remove the library from the rack (see Removing the
that you cannot access the Library From a Rack on page 243).
bottom bezel screws unless you
remove the library from the
rack

4 Slide the library one-to-two inches forward out of the rack or over
the edge of the table or desk in order to access the two bottom
bezel screws.

WARNING: Only slide the library out far enough out to access the
two screws on the bottom of the library. The library is
not secured in the rack or on the desk. Pulling it out
too far could cause the library to slide out of the rack
or off the desk.

Caution: Ensure there is enough slack in the power cords and


cables connected in the rear of the library so that you
do not dislodge them when you slide the library
forward.

Caution: Do not tip the library or tilt it on its side.

254 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 9: Installing, Removing, and Replacing Components
Removing and Replacing the Front Bezel

5 Make sure all the magazines are pulled out a few inches (or
removed) to allow you to remove and install the bezel without
damaging it.
6 Remove and set aside the two screws securing the bezel to the
bottom of the chassis (see Figure 57 on page 255).
7 Remove and set aside the two screws securing the bezel to the top
of the chassis (see Figure 58 on page 256).

Figure 57 Bezel Screw


Locations on Bottom of Library

Bottom
bezel
screws

Quantum Scalar i40 and Scalar i80 Users Guide 255


Chapter 9: Installing, Removing, and Replacing Components
Removing and Replacing the Front Bezel

Figure 58 Bezel Screws

Thumbscrew
securing library
to rack

8 Remove the bezel as follows:


Scalar i40: Grasp the bezel gently at the top and bottom and
pull the bezel straight out and off of the library. Do not tip or
twist the bezel as you pull it off.
Scalar i80: Use your fingers to grasp the bezel near the center
on both sides and pull outward to disengage the bezel (see
Figure 59 for location). There are plastic tabs on the inside of
the bezel that help secure the bezel to the library and pulling
outward from this location helps disengage them. You may
need to move the bezel slightly back and forth to remove it.

256 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 9: Installing, Removing, and Replacing Components
Removing and Replacing the Front Bezel

Figure 59 Scalar i80 Pull/Push


Locations

Pull in this area Pull in this area


when removing when removing
bezel. Push in bezel. Push in
this area when this area when
installing bezel. installing bezel.

9 Install the new bezel straight onto the library. Do not tip or twist the
bezel. If magazines are still in the library, be careful not to scratch or
damage the bezel as you install it. Slide the top and bottom edges
of the bezel to the inside of the top and bottom layers of the chassis
sheet metal. On the Scalar i80, press in near the center on both
sides of the bezel until you hear it snap into place (see Figure 59
for locations).

Caution: Make sure the power button and all four operator
panel control buttons appear through the holes in the
bezel and are not trapped beneath the bezel.

Caution: Be careful not to accidentally hit the power button and


turn the library off while you are installing the bezel.

10 Install the two top screws, then the two bottom screws.
11 Reinstall the library in the rack or desktop kit.
12 Close all the magazines.
13 If you turned the library off to perform this procedure, turn it ON
now by pressing the power button on the front panel. Wait until the
library initializes before resuming library operations.

Quantum Scalar i40 and Scalar i80 Users Guide 257


Chapter 9: Installing, Removing, and Replacing Components
Replacing the Chassis

14 If you removed the library from the rack to perform this procedure,
run the Installation and Verification Test (IVT) to ensure the Y-tray,
tape drives, and magazines are all functioning properly. From the
operator panel, select Tools > IVT and follow the instructions on
the screen. The IVT takes about 30 minutes. See Running the
Installation and Verification Test (IVT) on page 325 for more
information about the IVT.

Replacing the Chassis


DISCLAIMER: Tests have been conducted on the finished product and
have passed Safety Regulatory requirements at time of test.

WARNING: For field/customer replaceable sub-assemblies, all


instructions pertaining to further integration and
operation verification such as those in this document
must be fully complied with. Do not attempt to operate
the product before the product is fully assembled and self
diagnostics show that the product passes, otherwise
serious physical injury may occur to the user. The
manufacturer(s) will not be held liable/responsible if such
precautions are not adhered to.

WARNING: Two people are required to safely lift the library into and
out of its packaging, a rack, or a desktop kit.

When you replace a library chassis, you will remove all the components
from your existing library and install them in the new library.

Required Tools Phillips #1 screwdriver


Magazine lock override tool an opened paperclip, small
screwdriver, or other object (3.5 mm or less in diameter that will not
break off)

258 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 9: Installing, Removing, and Replacing Components
Replacing the Chassis

Procedure When you replace a library chassis, you will remove all the components
from your existing library and install them in the new library.
1 Unpack the new library chassis and place it on a flat, level surface.
See the instructions in Chapter 2, Unpacking the Library for specific
unpacking instructions, particularly about removing the Y-tray
restraints.

2 Verify that the new chassis is the same type (Scalar i40 or Scalar
i80) as the unit you are replacing.
3 If you had license keys installed on your library, you will need to
install new ones on the replacement library. Contact Quantum
Support to request new license keys.
4 If the library you are replacing is still turned on and operational,
shut down the library by selecting Actions > Shutdown from the
operator panel.
5 Turn OFF the library by pressing the power button on the front
panel.
6 Disconnect the power supply cord, the Ethernet cable, and all tape
drive cables from the back of the library. If you have multiple tape
drives, label the cables so you can reconnect them to the correct
tape drives later.
7 Remove all of the following components from the library (see
Figure 60 on page 261).

Component to
Remove Instructions

Power Supplies
Caution: Make sure the power supply is unplugged and disconnected
from live power before you remove it.

1 Disconnect the power cord from the back of the power supply.
2 Unscrew the captive thumbscrews.
3 Pull outward on the power supply handle to remove it from the library.

System Control 1 Loosen the two captive thumbscrews on the SCB.


Board (SCB) 2 Grip the thumbscrews and pull outward to slide the SCB out of the library.
3 Place the SCB on an anti-static surface or in an anti-static bag.

Quantum Scalar i40 and Scalar i80 Users Guide 259


Chapter 9: Installing, Removing, and Replacing Components
Replacing the Chassis

Component to
Remove Instructions

Tape Drives 1 Label each tape drive with its location in the library slots. It is
recommended that you reinstall the tape drives in the same location in the
new chassis.
2 Unscrew the captive thumbscrews securing the tape drive sled to the back
of the library. Half-height tape drives have two thumbscrews. Full-height
tape drives have four thumbscrews.
3 Using the handle, pull the drive sled out of the library. It should slide out
smoothly and easily.

Filler Plates Remove all filler plates (tape drive and power supply).
1 Unscrew the two captive thumbscrews.
2 Pull the filler plate out.

Magazines 1 If your library is a Scalar i80, label the magazines so you can reinstall them
in the same slots.
2 Insert the magazine lock override tool into the access hole in the bottom of
the magazine bezel.
3 Use the tool to depress the release latch while gently pulling outward on
the magazine bezel handle. If the magazine is on the right side, it will only
slide out as far as the I/E station. To release the magazine fully:
On the Scalar i40 and the bottom right magazine of the Scalar i80, reach
under the open magazine and insert the tool directly into the access
hole in the library chassis to depress the release latch, while pulling out
on the magazine bezel handle.
On the top right magazine of the Scalar i80, reach under the open
magazine and press the release latch directly with your finger, while
pulling out on the magazine bezel handle.

260 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 9: Installing, Removing, and Replacing Components
Replacing the Chassis

Figure 60 Components to
Remove

Remove Magazine release Remove


access holes

8 If the library is in a desktop kit or rack, remove it.


To remove the library from a rack, unscrew the captive
thumbscrews on the front of the library that secure the library
to the rack, then slide the library out of the rack. Place the
library on a flat, stable surface.

WARNING: Two people are required to safely lift the library


out of a rack.

To remove the library from a desktop kit, remove the two top
cover screws at the rear of the top cover. Loosen the captive
thumbscrews on the library chassis that are attached to the side
panels of the desktop kit. Slide the side panels one-half inch
toward the rear of the library to disengage the side-panel posts
from the library wall, then pull the side panels off.

Quantum Scalar i40 and Scalar i80 Users Guide 261


Chapter 9: Installing, Removing, and Replacing Components
Replacing the Chassis

Do NOT remove the eight rubber feet installed on the bottom


of the library (you will remove them later, in Step c, Sub-Step c
on page 263, once the library is set on its side).
9 Remove the Y-tray restraint from the replacement chassis. The
restraint consists of four (4) thumbscrews, a plastic sheet, a small
metal clip, and underneath the plastic sheet, an orange restraint tab
(see Figure 61) located on the top cover of the library.
a Unscrew and remove the four thumbscrews from the top cover.
Save the thumbscrews for use in restraining the Y-tray in the
chassis you are returning.
b Remove the plastic sheet and metal clip and discard. You will
not need to use them again.

Figure 61 Removing the Y-tray


Restraints

c Remove the orange shipping restraint tab and discard. You will
not need to use it again.

262 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 9: Installing, Removing, and Replacing Components
Replacing the Chassis

Note: The robot may stay at the top of the library, or it may
move downward toward the floor of the library. If it
moves downward, you will hear the gears turning as it
moves. This is normal.

10 Restrain the Y-tray in the chassis being returned as follows (see


Figure 62 on page 264):
a Look through the magazine slot openings to be sure the Y-tray
is resting on the floor of the library. If not, reach inside and
gently press down on one of the Y-trays side metal rods until
the Y-tray starts moving. It should drift down to rest on the
floor of the library.
b Turn the library carefully on its side (either the left or right side).
Make sure the front end of the library (the rack ear)
overhangs the edge of the table so that the library lies flat.

Caution: Do not turn the library upside down. Do not turn


the library more than 90 degrees from upright.

c If your library was installed in a desktop kit, remove the eight


rubber feet installed on the bottom of the library. You can
remove them by twisting them as you pull them out. Save them
to use on the replacement chassis.
d Take the four thumbscrews you just removed from the
replacement chassis and install them into the floor of the
chassis you are returning in the locations shown in Figure 73.
They will screw through the Y-tray and secure it in place on the
floor of the chassis.
e Do NOT turn the library back to an upright position at this
point. Leave it on its side until you place it in the box.

Caution: If you place the library upright with the Y-tray


restraint thumbscrews installed, you could damage
the chassis or the Y-tray.

Quantum Scalar i40 and Scalar i80 Users Guide 263


Chapter 9: Installing, Removing, and Replacing Components
Replacing the Chassis

Figure 62 Restraining the Y-


tray

Rack ear overhangs Four Y-tray restraint


edge of desk or table thumbscrews

11 If desired, you may cover the holes in the replacement library top
cover with stickers, which are provided in the accessory kit for this
purpose. This step is optional and is intended to prevent small
objects from accidentally falling into the library through the holes.
12 Install the new chassis in a rack or desktop kit. For instructions, see
Installing the Rack Mount Kit (Rail Kit) on page 229 or Installing the
Library in a Desktop Kit on page 244.

WARNING: Two people are required to safely lift the library.

264 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 9: Installing, Removing, and Replacing Components
Replacing the Chassis

13 Install the components you removed from the old chassis into the
new chassis.

Component to
Install Instructions

System Control Install the SCB before you install the power supply.
Board (SCB) 1 Position the SCB for installation: The board components face up. The flat
part of the board faces down. The thumbscrews are on the upper side of
the SCB back plate.
2 Install the new SCB by pushing the SCB into the slot until it stops. It should
slide smoothly and easily. When it reaches the end of its travel, press firmly
on the back panel of the SCB to snap it into place.
3 Tighten the two thumbscrews finger tight.
4 Connect the Ethernet cable to the LEFT Ethernet port (as viewed from the
back of the library; see Figure 63 on page 267).

Power Supplies If your library is a Scalar i80 and you have only one power supply, install it in
the top slot. If you have two power supplies, install them both.

Caution: Make sure the power supply is unplugged and disconnected from
live power before you install it.

1 Push the power supply straight into the slot. You may need to press firmly
on the power supply sheet metal at the very end to plug in the power
supply to the connector on the library. You will feel it snap into place.
The power supply only goes in one way, and should slide in easily. If you
cannot slide it in, you may be trying to install it upside down.
2 Tighten the two thumbscrews finger tight.
3 Connect the power cord to the power supply.
4 Plug the power cord into a grounded AC outlet.

Quantum Scalar i40 and Scalar i80 Users Guide 265


Chapter 9: Installing, Removing, and Replacing Components
Replacing the Chassis

Component to
Install Instructions

Tape Drives 1 Insert the tape drives into the same drive slots they were in the old chassis.
The shelf on the bottom of the drive sled fits into the notch in the library
chassis and slides on the plastic guide rails. The tape drive must be level to
slide in smoothly. At the very end of the slide, you will feel a slight click as
the tape drive sled connector connects into its mating connector in the
library chassis.

2 Tighten the tape drives captive thumbscrews finger tight to secure the tape
drive to the library chassis.
3 Connect all tape drive cables as they were in the old unit. Make sure they
are connected to the host or switch as they were before. For full-height
Fibre Channel tape drives, the cable must go in the LEFT connector (as
viewed from the back of the library; see Figure 63 on page 267).

Filler Plates Make sure every empty power supply slot and tape drive slot is covered with a
filler plate.
1 Slide the filler plate into the slot.
2 Tighten the thumbscrews.

Magazine Slide each magazine into its slot and push it in all the way until it stops.

266 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 9: Installing, Removing, and Replacing Components
Replacing the Chassis

Figure 63 Reinstalled
Components

Half-height tape drives

Power
supply cord

Tape drive cables Ethernet cable in LEFT


SCB port

Full-height tape drives

Power
supply cord

Fibre Channel cables in LEFT Ethernet cable in LEFT


port of full-height tape drives SCB port

Quantum Scalar i40 and Scalar i80 Users Guide 267


Chapter 9: Installing, Removing, and Replacing Components
Replacing the Chassis

14 Turn ON the library by pressing the power button on the front


panel.
15 Wait for the library to initialize. This can take up to 5 to 17 minutes,
depending on library size.
16 You will notice the library has a new diagnostic ticket (DT042)
stating the librarys vital product data (VPD) has changed.
17 Since the VPD change is caused by the intentional library chassis
replacement, follow the Diagnostic Ticket resolution steps to
reconfigure the host application accordingly.
18 If you had license keys installed on the old library, install the new
license keys. From the operator panel, select Setup > License
Installation; or from the Web client, select Setup > License. For
further directions, see Applying a License Key on page 71.
19 Run the Installation and Verification Test (IVT) to ensure the Y-tray,
tape drives, and magazines are all functioning properly. From the
operator panel, select Tools > IVT and follow the instructions on
the screen. The IVT takes about 30 minutes.
20 Save the library configuration (from the Web client, select Tools >
Save/Restore Configuration and save the configuration to a known
location).
21 Wrap the removed chassis in the antistatic wrapping that contained
the replacement chassis. Package the removed chassis using the
packaging that contained the replacement chassis. Use the enclosed
RMA information to send the chassis back to Quantum.
22 If your library is running SKM, you must you run a special script on
the SKM server after you replace the chassis. The script will correct
the library serial number associations in the key server database and
allow you to export used SKM encryption keys via the Web client
correctly. For instructions, refer to the chapter titled Updating the
SKM Keystore After Replacing a Library Control Module in the
Scalar Key Manager 2.0 Users Guide.

268 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 9: Installing, Removing, and Replacing Components
Removing and Installing a Filler Plate

Removing and Installing a Filler Plate


A filler plate is required to cover every empty tape drive and power
supply slot on the rear of the library, in order to maintain proper library
cooling. If you remove a tape drive or power supply from the library, you
must cover the opening with a filler plate.
There are two types of filler plates:
Tape drive
Power supply

Removing and The filler plate is half-height in size. If you remove a full-height tape
Installing a Tape Drive drive, you must install two filler plates to cover the opening.
Filler Plate
Removing a tape drive filler plate
1 Unscrew the two captive thumbscrews and pull the filler plate out.
2 Save the filler plate in case you need to use it again.

Installing a tape drive filler plate


The tape drive filler plate has no top or bottom orientation it
can go in either way (see Figure 64 on page 270).
Slide the filler plate into the slot and tighten the thumbscrews.

Removing and The power supply filler plate is used only on the Scalar i80 when only
Installing a Power one power supply is present.
Supply Filler Plate
Removing a power supply filler plate
1 Unscrew the two captive thumbscrews.
2 Pull out on the thumbscrews so the filler plate is at a slight angle
and the bottom of the filler plate is still attached in the slot.

Quantum Scalar i40 and Scalar i80 Users Guide 269


Chapter 9: Installing, Removing, and Replacing Components
Removing and Installing a Filler Plate

3 Lift the filler plate up to disengage the catch at the bottom and pull
the filler plate out of the slot.

Installing a power supply filler plate:


On the Scalar i80, if you are using only one power supply, you
should install the power supply in the upper slot, and cover the
lower slot with a filler plate (see Figure 64 on page 270).
1 Hold the filler plate with the thumbscrews at the top.
2 Insert the bottom edge of the filler plate into the slot, engaging the
bottom edge of the filler plate into the bottom of the slot.
3 Pivot the filler plate up to fit securely in the hole.
4 Tighten the thumbscrews.

Figure 64 Filler Plates Installed


Tape drive filler plate

Single
power
supply
installed
in top
slot

Power
supply
filler
plate

270 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 9: Installing, Removing, and Replacing Components
Removing and Replacing a Magazine

Removing and Replacing a Magazine

The procedure for replacing magazines is the same on the Scalar i40
and the Scalar i80.

Note: The library can operate with one or more magazines


uninstalled. However, it will operate at reduced speed.

Required Tools Phillips #1 screwdriver

Magazine Replacement (1) magazine


Kit Contents (1) left-side magazine bezel
(1) right-side magazine bezel
(4) M3 x 6 Phillips head screws
(4) washers

Creating a Backup Map When you transfer tape cartridges from the removed magazine into the
of Cartridge Locations replacement magazine, each cartridge needs to go in the same slot
position it was in previously. One way to do this is to transfer the
cartridges one by one from one magazine to the other. However, if the
cartridges get mixed up or dropped, you need a backup method to
know where to place your cartridges. The library configuration report
provides a convenient backup map.
1 On the Web client, select Reports > Library Configuration.
2 Click the Show Barcodes button.
The screen displays a map of the library showing the location of
each cartridge, by barcode.

Quantum Scalar i40 and Scalar i80 Users Guide 271


Chapter 9: Installing, Removing, and Replacing Components
Removing and Replacing a Magazine

3 Click the print icon in the upper right corner to print the report.

Alternatively, take a screen capture of the report and save or print it,
or copy the map by hand.

Removing the You can perform this procedure with library power on.
Magazine from the 1 From the operator panel, select Actions > Magazine.
Library
2 Use the Up and Down buttons to select the magazine you want to
remove and press Release.
3 Wait for the operator panel to display the message: Magazine is
now unlocked. Waiting for the magazine to be moved to the
expected position.
4 Pull out on the magazine bezel handle and remove the magazine
from the library. If you do not remove the magazine within 30
seconds, the magazine locks again.

Note: If the library is turned off, you can release the magazine
manually by inserting an opened paperclip, small screwdriver,
or other object (3.5 mm or less in diameter that will not break
off) into the access hole in the bottom of the magazine bezel
(see Figure 65). Use the tool to depress the release latch while
gently pulling outward on the magazine bezel handle.

Right-side magazines will only slide out as far as the I/E station.
To release right-side magazines fully:
On the Scalar i40 and the bottom right magazine of the
Scalar i80, reach under the open magazine and insert the tool
directly into the access hole in the library chassis to depress the
release latch, while pulling out on the magazine bezel handle.
On the top right magazine of the Scalar i80, reach under the
open magazine and press the release latch directly with your
finger, while pulling out on the magazine bezel handle.

272 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 9: Installing, Removing, and Replacing Components
Removing and Replacing a Magazine

Figure 65 Magazine Release


Latch Access Holes

Magazine release latch access holes

Installing the Magazine The replacement magazine can be used on either the left or right side of
the library, depending on how it is oriented. Once it is oriented correctly,
the left or right bezel can be attached.
You can perform this procedure with the library powered on.
1 Place the removed magazine in the orientation it would be if it were
installed in the library.
2 Place the replacement magazine next to the removed magazine in
the same orientation. Make sure they look the same from all angles.
The storage slots face inward.
On the outer wall of the magazine, the silver rollers sit below
the springs (see Figure 66).

Quantum Scalar i40 and Scalar i80 Users Guide 273


Chapter 9: Installing, Removing, and Replacing Components
Removing and Replacing a Magazine

Figure 66 Proper Orientation


Springs
(Right-Side Magazine)

Silver rollers

3 Choose the correct bezel (left or right) from the magazine


replacement kit.

Note: If you try to install the wrong bezel, it will not fit and you
will not be able to install it.

4 Push up on the top bezel tabs and fit them over the posts on the
top of the magazine. Turn the magazine over and repeat on the
bottom (see Figure 67 on page 275).
5 Install the two washers and two M3 screws securing the top of the
bezel to the magazine. Install them in the outer hole in each tab
(see Figure 67 on page 275).
6 Turn the magazine over and install the two washers and two M3
screws securing the bottom of the bezel to the magazine. Install
them in the outer hole in each tab (see Figure 67).

274 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 9: Installing, Removing, and Replacing Components
Removing and Replacing a Magazine

Figure 67 Removing/Installing
the Magazine Bezel
Bezel
Tab

7 Remove the tape cartridges from the removed magazine and


carefully install them in the exact same slots in the replacement
magazine. Use the map you created if necessary.
8 Slide the magazine into the magazine slot all the way until it stops.
The library performs an inventory on the replaced magazine.
9 Wait for the library to finish its inventory.
10 Run the magazine diagnostics test on the replaced magazine to be
sure it is functioning correctly.
a Place a scratch tape in the top I/E station slot.
b If manual cartridge assignment is enabled, assign the scratch
tape to the System partition.

Quantum Scalar i40 and Scalar i80 Users Guide 275


Chapter 9: Installing, Removing, and Replacing Components
Removing and Installing a Power Supply

c From the operator panel, select Tools > Diagnostics.


d Continue through the next few screens to run the magazine test
on the replaced magazine.
If a problem is found during testing, you receive a diagnostic ticket.
See Running the IVT Diagnostic Subtests Individually Robotics,
Tape Drive, and Magazine Tests on page 327 more information.

Removing and Installing a Power Supply

The Scalar i40 contains one power supply. The Scalar i80 can have up
to two power supplies for redundancy purposes.
An unused power supply slot must be covered by a filler plate.
This document covers:
Replacing a Power Supply in a Single-Power-Supply System (Scalar
i40 and Scalar i80)
Adding or Replacing a Redundant Power Supply on the Scalar i80

Figure 68 Single Power Supply


System Scalar i40, single
power supply

Scalar i80, single


power supply
installed in top slot

Filler plate covers


empty power supply
slot

276 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 9: Installing, Removing, and Replacing Components
Removing and Installing a Power Supply

Figure 69 Redundant Power


Supply System

Scalar i80, dual power


supplies for redundancy

Replacing a Power Note: If you have a single power supply in a Scalar i80, it is
Supply in a Single- recommended that you install it in the upper slot, to provide
Power-Supply System better temperature control (see Figure 68).
(Scalar i40 and Scalar
i80) 1 Shut down the library (from the operator panel, select Actions >
Shutdown > Shutdown Library). Wait for the screen to prompt
you to turn off library power.
2 Turn OFF library power by pressing the power button on the front
panel. Wait for the operator panel screen to turn off.
3 Disconnect the power cord from the power supply.

Caution: Make sure you disconnect live power from the power
supply before you remove or install it. Otherwise,
damage to the power supply could occur.

4 Unscrew the two captive thumbscrews on the power supply.


5 Using the handle, slowly pull the power supply straight out of the
library.
6 Install the new power supply by pushing it straight in to the slot.
You may need to press firmly on the power supply sheet metal at
the very end to plug in the power supply to the connector on the
library. You will feel it snap into place.
The power supply only goes in one way, and should slide in easily. If
you cannot slide it in, you may be trying to install it upside down.
7 Tighten the two thumbscrews finger tight.

Quantum Scalar i40 and Scalar i80 Users Guide 277


Chapter 9: Installing, Removing, and Replacing Components
Removing and Installing a Power Supply

8 Connect the power cord to the power supply.


9 Make sure the power cord is plugged in to a grounded, AC outlet.
10 The power supply LED should turn amber to indicate it is plugged in
but the library is not turned on.
11 Turn ON library power by pressing the power button on the front
panel.
The power supply LED should turn green immediately to indicate
the library is turned on.
If the power supply LED is red, the power supply is not working.
Contact Quantum Support.

Adding or Replacing a You do not need to turn off library power to perform this procedure.
Redundant Power 1 If you are adding a new power supply to a Scalar i80, remove the
Supply on the filler plate and start at Step 6 below.
Scalar i80
2 If you have two power supplies, determine which one to remove.

Caution: Make sure you remove the power supply whose LED is
red or off. Do not remove the power supply whose LED
is green.

3 Disconnect the power cord from the power supply you want to
remove.

Caution: Make sure you disconnect live power from the power
supply before you remove or install it. Otherwise,
damage to the power supply could occur.

4 Unscrew the two captive thumbscrews on the power supply.


5 Using the handle, slowly pull the power supply straight out of the
library.
6 Install the new power supply by pushing it straight in to the space.
You may need to press firmly on the power supply sheet metal at
the very end to plug in the power supply to the connector on the
library. You will feel it snap into place.

278 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 9: Installing, Removing, and Replacing Components
Removing and Replacing the System Control Board

The power supply only goes in one way, and should slide in easily. If
you cannot slide it in, you may be trying to install it upside down.
7 Tighten the two thumbscrews finger tight.
8 Connect the power cord to the power supply.
9 Make sure the power cord is plugged in to a grounded, AC outlet.
The power supply LED should turn green immediately to indicate
the library is turned on.
If the power supply LED is red, the power supply is not working.
Contact Quantum Support.

Removing and Replacing the System Control Board


These instructions explain how to remove a system control board (SCB)
and replace it with a new one.
The SCB contains library firmware, tape drive firmware, all configurable
settings, license keys, and SKM TLS certificates. After you replace the
SCB, you must either restore a previously saved configuration, or
reinstall the license keys and manually reconfigure the settings.

Note: When you replace the SCB you will permanently lose all data
previously collected for logs and reports.

The process steps are:


1 Replacing the System Control Board
2 Installing Library Firmware
3 Restoring the Library Configuration or Manually Reconfiguring the
Library

Replacing the System Caution: You must completely remove power from the library before
Control Board removing and replacing the system control board.

Quantum Scalar i40 and Scalar i80 Users Guide 279


Chapter 9: Installing, Removing, and Replacing Components
Removing and Replacing the System Control Board

1 If the library is still operational, save the library configuration. From


the Web client, select Tools > Save/Restore Configuration. Select
Save Configuration and click Apply. Save the configuration to a
known location.
2 If the library is still operational, and you want to save log and report
information for historical purposes, access the logs and reports you
want using the Web client and save them to a known location.
3 If possible, save a library snapshot for future troubleshooting. From
the Web client, select Tools > Capture Snapshot and follow the
instructions.
4 If the library is still operational, shut down the library by selecting
Actions > Shutdown > Shutdown Library from the operator
panel.
5 When prompted, turn OFF the library by pressing the power button
on the front panel. Wait for all the LEDs on the SCB to turn off.
6 Disconnect the power cords from the power supplies on the back of
the library. The Scalar i40 has one power supply. The Scalar i80 may
have one or two power supplies. Make sure you disconnect all
power cords from the power supplies.
7 Remove the Ethernet cable from the SCB (see Figure 70 on
page 281).
8 Loosen the two captive thumbscrews on the SCB.
9 Grip the thumbscrews and pull outward to slide the SCB out of the
library.
10 Remove the new SCB from its packaging. Wrap the old SCB in the
antistatic bag that the replacement SCB was wrapped in.
11 Position the new SCB for installation as follows: The board
components face up. The flat part of the board faces down. The
thumbscrews are on the upper side of the SCB back plate (see
Figure 70 on page 281).
12 Install the new SCB by pushing the SCB into the slot until it stops. It
should slide smoothly and easily. When it reaches the end of its
travel, press firmly on the back panel of the SCB to snap it into
place.
13 Tighten the two thumbscrews finger tight.
14 Connect the Ethernet cable to the LEFT Ethernet port on the SCB (as
viewed from the back of the library; see Figure 70 on page 281).

280 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 9: Installing, Removing, and Replacing Components
Removing and Replacing the System Control Board

Figure 70 Ethernet Port


Locations on the SCB

Thumbscrews

Scalar i40 Ethernet port

Thumbscrews

Ethernet port
Scalar i80

15 Continue to Installing Library Firmware on page 281.

Installing Library 1 Connect the power cords to the power supplies on the back of the
Firmware library. Make sure that each power supply is plugged in to a
grounded, AC outlet.
2 Turn ON the library by pressing the power button on the front
panel.
The LED on the SCB should illuminate green.
The green power LED on the library front panel above the power
button illuminates, and the operator panel screen turns on. The
library goes through a connection and initialization sequence that
takes up to 60 seconds.

Quantum Scalar i40 and Scalar i80 Users Guide 281


Chapter 9: Installing, Removing, and Replacing Components
Removing and Replacing the System Control Board

3 When initialization is complete, the Library Installation screen


displays on the operator panel, displaying the text, The library
needs to have its IP Address configured. The purpose of this screen
is to set the IP address so you can access the library via the Web
client and download firmware. (After you have loaded firmware,
you can change or reconfigure IP addresses if needed.)
4 Press Next.
The screen displays the text, Current protocol: IPv4. Set protocol to
IPv6?
5 Select Yes or No.
If you select Yes, the library supplies a stateless IPv6 address and
displays it, along with other network settings, on two screens.
Use the Next and Back buttons to view the screens. You can
only change these settings via the Web client.
If you select No, you are asked if you want to use DHCP.
If you select Yes, the library assigns IPv4 address and
displays the information on the screen.
If you select No, use the Up and Down buttons to enter the
IP address, mask, and gateway. Set the numeric value for
each segment of the address, then press the Right button
to go to the next segment. See Navigating and Editing on
the Operator Panel on page 27 for more information on
editing the IP address. When finished, press Apply.
6 Take note of the IP address.
7 Download the latest library firmware to a known location on your
computer. Library firmware is available at http://
www.quantum.com. Navigate to the appropriate firmware version
and download the firmware image file.
8 Open an Internet session and enter the library IP address listed on
the operator panel into the Web browser.
The Web client displays a screen instructing you to select the
firmware image you want to load on the library.
9 Click Browse and select the firmware image you downloaded to
install on the library.

282 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 9: Installing, Removing, and Replacing Components
Removing and Replacing the System Control Board

10 Click OK, then click OK again to agree to restart the library.


The Web client displays the following message:
Decoding installation bundle...done.
Validating bundle...good.
Installing firmware...library will reboot when complete.
11 Go to the operator panel and wait until the Setup Wizard displays
on the screen. The Setup Wizard screen may take up to 20 minutes
to appear.
12 Continue as follows:
If you have saved a library configuration that you want to
restore on the library, go to: Restoring the Library Configuration
on page 283.
If you do NOT have a saved library configuration to restore on
the library, go to: Manually Reconfiguring the Library on
page 284.

Restoring the Library Follow the instructions in this section if you have a saved library
Configuration configuration that you want to reinstall on the library.
1 On the operator panel, press Cancel to exit the Setup Wizard.
2 Take note of the librarys IP address (on the operator panel, select
Reports > Network Settings).
3 Access the Web client using the IP address and log in using the
default user name and password:
User name: admin
Password: password

Note: Once you restore the configuration, all your former user
names and passwords are restored.

4 Restore the configuration using the Web client as follows:


a Select Tools > Save/Restore Configuration.
b Select Restore System Configuration.
c Click Browse. Navigate to the saved configuration and click
Open.

Quantum Scalar i40 and Scalar i80 Users Guide 283


Chapter 9: Installing, Removing, and Replacing Components
Removing and Replacing the System Control Board

d Click Apply
e Click OK.

Note: Restoring the configuration does NOT restore your network


settings.

5 Check the librarys date, time, and time zone settings and
reconfigure if necessary. From the Web client, select Setup > Date
& Time.
6 If you changed the IP address from what it was originally, update
host and other applications that access the library.
7 Save the library configuration. From the Web client, select Tools >
Save/Restore Configuration. Select Save Configuration and click
Apply. Save the configuration to a known location.
8 It is recommended that you run the Installation and Verification Test
(IVT). From the operator panel, select Tools > IVT and follow the
instructions. The IVT takes about 30 minutes. If any problems are
detected, the library issues a diagnostic ticket.
9 Package the old SCB in the packaging that shipped with the new
SCB and send the old SCB back to Quantum using the included
return shipping label.

Manually Reconfiguring Follow the instructions in this section if you do not have a saved library
the Library configuration.
1 If you had licenses installed on your library, have the license keys
handy so you can install them on the library. If you no longer have
them, you can obtain them at http://www.quantum.com/
licensekeys, or from Quantum Support.
2 When the firmware update is complete, the Setup Wizard displays
on the operator panel screen. The Setup Wizard helps you configure
the date, time, IP address, IPv6 enable/disable, licenses, partitions,
I/E slots, and cleaning slots.

284 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 9: Installing, Removing, and Replacing Components
Removing and Replacing the System Control Board

3 Complete the Setup Wizard on the operator panel. If you make a


mistake or do not complete all the screens, you can change the
configuration later using the operator panel or Web client Setup
menus.

Note: You cannot update the host name or time zone on the
operator panel. If the displayed host name or time zone is
incorrect, change it later using the Web client (see Step 8
on page 285).

4 Take note of the librarys IP address (on the operator panel, select
Reports > Network Settings).
5 Access the Web client using the IP address and log in using the
default user name and password.

6 Optionally, install tape drive firmware for autoleveling. The library
firmware contains baseline tape drive firmware for autoleveling.
Verify your tape drive firmware is at the level you expect. If not:
a Upload the tape drive firmware you want to use. From the Web
client, select Tools > Drive Operations > Upload/remove tape
drive firmware for autoleveling.
b Unload all tape cartridges from the tape drives on which you
want to autolevel firmware.
c Initiate autoleveling by doing one of the following:
Restart the library (from the operator panel, select Actions
> Shutdown > Restart Library.
Restart all the tape drives you want to autolevel, as follows:
From the Web client, select Tools > Diagnostics. Confirm
you want to take the partitions offline. Select Drives >
Drive Tests > Drive Reset. Select the applicable partitions
and tape drives, then click Apply, then click OK.
7 If you changed the IP address from what it was originally, update
host and other applications that access the library.
8 Update the library name, time zone, and any other configuration
settings, if required, using the Web client Setup menus.

Quantum Scalar i40 and Scalar i80 Users Guide 285


Chapter 9: Installing, Removing, and Replacing Components
Removing and Replacing a Tape Drive

9 If you are connecting to a Scalar Key Manager (SKM), take note that
TLS certificates will need to be loaded onto the library. See
Installing TLS Certificates on the Library on page 186 for
instructions.
10 Save the library configuration. From the Web client, select Tools >
Save/Restore Configuration. Select Save Configuration and click
Apply. Save the configuration to a known location.
11 To ensure the library is fully functional with the new SCB installation
and configuration selections, we recommend you run the
Installation and Verification Test (IVT). From the operator panel,
select Tools > IVT and follow the instructions. The IVT takes about
30 minutes. If any problems are detected, the library issues a
diagnostic ticket.
12 Package the old SCB in the packaging that shipped with the new
SCB and send the old SCB back to Quantum using the included
return shipping label.

Removing and Replacing a Tape Drive


It is recommended that you remove and install tape drives with library
power ON it is faster and keeps non-affected tape drives and
partitions active.
The tape drive always resides in a drive sled, and together they are
effectively one unit. If you order a new or replacement tape drive, it will
already be installed in a sled.

Caution: Do not remove the tape drive from the drive sled.

Note: For multiple tape drive installs in which you are changing
control paths, install and verify the tape drives one at a time,
rather than all at once.

286 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 9: Installing, Removing, and Replacing Components
Removing and Replacing a Tape Drive

Preparing Partitions Depending on the types of tape drives you are removing and installing,
and Control Paths you may need to reconfigure library partitions or change the control
path before you remove and replace the tape drive. There are four
different types of installation, described in the table below. Follow the
instructions in the table before proceeding to the remove/install
procedures.

Type of Installation Instructions

Adding a new tape drive No special instructions.

Replacing a tape drive that is No special instructions.


not assigned to a partition

Replacing tape drive that is Install the replacement tape drive in the same slot as the removed
assigned to a partition with tape drive.
a tape drive that has the There are no special instructions unless the tape drive you are
same: replacing is the control path in a partition with multiple tape drives,
interface type (Fibre and you want the partition to remain online during the replacement
Channel or SAS), and procedure. In this case, select another tape drive as the control path.
form factor (half-height or From the Web client, use the Setup > Control Path menu path.
full-height), and
vendor

Replacing a tape drive that is If the partition contains only one tape drive, delete the partition
assigned to a partition with before removing the tape drive and then re-create the partition
a tape drive that has a once you install the replacement tape drive.
different: If the partition contains multiple tape drives and the tape drive you
interface type (Fibre want to replace is not the control path, delete the tape drive from
Channel or SAS), or the partition.
form factor (half-height or If the partition contains multiple tape drives and the tape drive you
full-height), or want to replace is the control path, select another tape drive as
vendor the control path. Then delete the tape drive you want to replace
from the partition.
To delete tape drives from partitions, select Setup > Partitions from
the Web client.
To modify the control path, select Setup > Control Path from the
Web client.

Quantum Scalar i40 and Scalar i80 Users Guide 287


Chapter 9: Installing, Removing, and Replacing Components
Removing and Replacing a Tape Drive

Removing a Tape Drive Caution: Do not remove a tape drive that is currently performing an
from the Library operation.

1 Make sure the tape drive you want to remove is empty of media.
From the operator panel, select Actions > Tape Drive > Unload.
2 Take the tape drive you want to remove offline. From the operator
panel, select Actions > Tape Drive > Change Mode. Select the
tape drive and press Modify. Press the Down button to select
Offline, then press Apply.
3 Disconnect the cable from the back of the tape drive.
4 Unscrew the captive thumbscrews securing the drive sled to the
back of the library. Half-height tape drives have two thumbscrews.
Full-height tape drives have four thumbscrews.
5 Using the handle, pull the drive sled out of the library. It should slide
out smoothly and easily.
6 Wait at least 10 seconds before installing a replacement tape drive
to allow the library to recognize that the tape drive has been
removed.
7 Install a replacement tape drive following the instructions below. If
any empty slots remain, install a filler plate in the empty slot.
8 If you are returning the tape drive to Quantum, wrap it in the
antistatic bag in which the replacement tape drive is wrapped, then
finish packing it in the same packaging materials from the
replacement tape drive. Ship the tape drive to Quantum using the
RMA materials included in the packaging.

Installing a Tape Drive Tape Drive Slot Location Considerations


Tape drives can only fit in certain slots, as described below and
illustrated in Figure 71. Slots are numbered starting from the bottom
and moving up.
Scalar i40: Half-height tape drives can be installed in slots 1 and 2.
A full-height tape drive can be installed in slot 1.

288 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 9: Installing, Removing, and Replacing Components
Removing and Replacing a Tape Drive

Scalar i80: Half-height tape drives can be installed in slots 1, 2, 3, 4,


and 5. Full-height tape drives can be installed in slots 1, 3, and 5.
The extra space where slot 6 would be cannot hold a half-height
tape drive, but will accommodate a full-height tape drive installed in
slot 5.
If possible, it is recommended to start installing the tape drives at the
bottom slot and work up, without leaving spaces between.
If you are replacing an existing tape drive with a tape drive of the same
interface type, form factor, and vendor, place the replacement tape
drive in the same slot as the removed tape drive.

Figure 71 Acceptable
Installation Locations for Full-
Height Tape Drives

Scalar i40 Scalar i80

Installation Procedure
1 If you need to remove one or more filler plates, unscrew the two
thumbscrews securing the filler plate to the back of the library.
Holding the thumbscrews, pull the filler plate gently out of the
library. Save the filler plate in case you need to use it in the future.
2 Insert the tape drive into the drive slot. The shelf on the bottom of
the drive sled fits into the notch in the library chassis and slides on
the plastic guide rails (see Figure 72 on page 290). The tape drive
must be level to slide in smoothly. At the very end of the slide, you
will feel a slight click as the tape drive sled connector connects
into its mating connector in the library chassis.

Quantum Scalar i40 and Scalar i80 Users Guide 289


Chapter 9: Installing, Removing, and Replacing Components
Removing and Replacing a Tape Drive

Figure 72 Installing a Tape


Drive

Notch in library
chassis

Drive sled shelf


slides in notch

3 Tighten the tape drives captive thumbscrews finger tight to secure


the tape drive to the library chassis.
The tape drive LED illuminates red for up to 30 seconds. Then the
tape drive fan starts and the LED turns amber, indicating the tape
drive is offline. If this is a new installation (not a replacement), the
tape drive will come online automatically.
4 Connect the tape drive cable from the tape drive to the host.
5 If the firmware on the newly installed tape drive is different from
the standard configured on the library, the library will automatically
autolevel the new tape drives firmware upon installation (for more
information, see Updating and Autoleveling Tape Drive Firmware on
page 303).
Autoleveling takes about 7 minutes. A message displays on the
operator panel indicating autoleveling is taking place.
If autoleveling is not required, the tape drive takes about 2 minutes
to come ready.

290 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 9: Installing, Removing, and Replacing Components
Removing and Replacing a Tape Drive

6 If needed, add the new tape drive to an existing partition or create a


new partition for it. From the Web client, select Setup > Partitions
and complete the necessary screens.
7 Bring the tape drive online, if it is not online already. From the
operator panel, select Actions > Tape Drive > Change Mode.
Select the tape drive you want to bring online and press Modify.
Use the Up and Down buttons to change the mode to Online, then
press Apply.
The tape drive LED turns green.
8 Verify the installation by reviewing the library configuration report
on the Web client (Reports > Library Configuration). Make sure
that the new drive is online, in the correct partition, and has the
control path status that you want. You may need to refresh your
Internet browser.
9 Verify that the host computer and backup applications can see the
new tape drive configuration correctly.
10 If any empty slots remain, install a filler plate in the empty slot.

Caution: Filler plates are required to maintain proper library


cooling. Do not run the library with uncovered slots.

11 Run the tape drive diagnostic test on the newly installed tape drive
to be sure it is functioning correctly.
a Install a scratch tape in the top I/E station slot.
b If manual cartridge assignment is enabled, assign the scratch
tape to the System partition.
c From the operator panel, select Tools > Diagnostics.
d Continue through the next few screens to run the tape drive test
on the replaced tape drive.
If a problem is found during testing, you receive a diagnostic ticket.
See Running the IVT Diagnostic Subtests Individually Robotics,
Tape Drive, and Magazine Tests on page 327 for more information.
12 Save the library configuration (see Saving the Library Configuration
on page 107).

Quantum Scalar i40 and Scalar i80 Users Guide 291


Chapter 9: Installing, Removing, and Replacing Components
Packaging the Library for Moving or Shipping

Packaging the Library for Moving or Shipping

Packaging Kit Contents Shipping carton


Top foam
Bottom foam
Anti-static wrapping
(4) M5 Thumbscrews to restrain Y-tray
Bottom tray (Scalar i80 only)
Pallet (Scalar i80 only)
(2) Cardboard corner boards (Scalar i80 only)
(2) Straps and buckles for securing packaging to pallet (Scalar i80
only)

Creating a Backup Map You must remove all the tape cartridges before shipping the library. If
of Cartridge Locations you want to maintain the same partitions and magazine slot
assignments in your new location as you are using currently, you will
want to reinstall your tape cartridges in the same slots they are in now.
The library configuration report provides a convenient map of your
slot assignments. If you print or copy this map, you will be able to easily
install your cartridges later.
1 On the Web client, select Reports > Library Configuration.
2 Click the Show Barcodes button.
The screen displays a map of the library showing the partitions and
the location of each cartridge, by barcode.
3 Click the print icon in the upper right corner to print the report.

Alternatively, take a screen capture of the report and save or print it,
or copy the map by hand.

292 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 9: Installing, Removing, and Replacing Components
Packaging the Library for Moving or Shipping

Procedure 1 As a precautionary measure, save the library configuration: From the


Web client, select Tools > Save/Restore Configuration. Select Save
System Configuration and click Apply. When prompted, save the
file to a known location on your computer.
2 Stop all library and host operations.
3 Remove the magazines from the library:
a From the operator panel, select Actions > Magazine.
b Use the Up and Down buttons to select the magazine you want
to remove and press Release.
c Wait for the operator panel to display the message: Magazine
is now unlocked. Waiting for the magazine to be moved to the
expected position.
d Pull the magazine bezel out and remove the magazine from the
library. If you do not remove the magazine within 30 seconds,
the magazine locks again.
e Repeat for all magazines in the library.

Caution: Do not put your hands or any other objects into the
magazine openings while library power is on.

4 Remove all the tape cartridges from the magazines.


5 Shut down the library by selecting Actions > Shutdown from the
operator panel. Wait for the operator panel to prompt you to turn
off library power.
6 Turn OFF the library by pressing the power button on the front
panel. Wait for the LED on the SCB to turn off.
7 Disconnect the power supply cord, the Ethernet cable, and all tape
drive cables from the back of the library. If you have multiple tape
drives, label the cables so you can reconnect them to the correct
ones later.

Quantum Scalar i40 and Scalar i80 Users Guide 293


Chapter 9: Installing, Removing, and Replacing Components
Packaging the Library for Moving or Shipping

8 If the library is in a rack or desktop kit, remove it.


To remove the library from a rack:
a Remove all the tape drives from the library. Label tape drives
so you know what order to reinstall them later. They must
be reinstalled in the same slots as they were previously.
Unscrew the thumbscrews and pull the tape drive handle to
remove the drive from the library.
b Unscrew the captive thumbscrews on the front of the library
that secure the library to the rack, then slide the library out
of the rack. Place the library on a flat, stable surface.

WARNING: Two people are required to safely remove the


library from the rack.

To remove the library from a desktop kit, remove the two


screws in the decorative top cover. Remove the decorative top
cover by sliding it toward the back. Loosen the captive
thumbscrews on the library chassis that are attached to the side
panels of the desktop kit. Slide the side panels one inch toward
the rear of the library, then pull the side panels off.
9 Make sure the Y-tray is sitting on the floor of the library as follows:
Look inside the library through one of the magazine openings. If the
Y-tray is not sitting on the floor of the library, reach inside and
gently press down on one of the Y-trays metal side rods until the Y-
tray starts moving. It should drift down to rest on the floor of the
library.
10 Reinstall the empty magazines in the library by pushing them in
until they stop.
11 If you removed the tape drives earlier, reinstall them in their proper
slots. Push them carefully into their slots and tighten the captive
thumbscrews.
12 Restrain the Y-tray as follows (see Figure 73 on page 295):
a Turn the library carefully on its side (either the left or right side).
Make sure the front end of the library (the rack ear)
overhangs the edge of the table so that the library lies flat.

Caution: Do not turn the library upside down. Do not turn


the library more than 90 degrees from upright.

294 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 9: Installing, Removing, and Replacing Components
Packaging the Library for Moving or Shipping

b Install four thumbscrews into the floor of the library in the


locations shown in Figure 73 on page 295. They will screw
through the Y-tray and hold it in place on the floor of the
library.

Figure 73 Restraining the Y-


tray

Rack ear overhangs Four Y-tray restraint


edge of desk or table thumbscrews

c Do NOT turn the library back to an upright position at this


point. Leave it on its side until you place it in the box.

Caution: If you place the library upright with the Y-tray


restraint thumbscrews installed, you could damage
the chassis or the Y-tray.

Quantum Scalar i40 and Scalar i80 Users Guide 295


Chapter 9: Installing, Removing, and Replacing Components
Packaging the Library for Moving or Shipping

13 Wrap the library in the anti-static wrapping provided in the


packaging kit.

WARNING: Two people are required to safely lift the library.

14 Place the library in the packaging as shown in Figure 74 and


Figure 75.

Figure 74 Scalar i40 Packaging

Top foam

Library (anti-static
wrap not shown
for clarity)

Bottom foam

Shipping carton

296 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 9: Installing, Removing, and Replacing Components
Packaging the Library for Moving or Shipping

Figure 75 Scalar i80 Packaging

Top foam

Library (anti-static
wrap not shown
for clarity)

Bottom foam

Shipping carton

Bottom tray

Pallet

Scalar i80 only: Place two corner boards on the long edges on top of
the shipping carton. Strap the box to the pallet, then wrap the entire
assembly in stretch-film prior to shipping.

Caution: When unpacking the library in its new location, lift it out of
the packaging and immediately place it on its side to
remove the four thumbscrews securing the Y-tray to the
floor of the library. Do not place it upright until you have
removed the four thumbscrews, or you could damage the
chassis or the Y-tray. When placing the library on its side,
do not set it on the rack ear or the magazine handle, or
you could damage them.

Quantum Scalar i40 and Scalar i80 Users Guide 297


Chapter 9: Installing, Removing, and Replacing Components
Replacing the Y-tray with Robot

Replacing the Y-tray with Robot


Y-tray with Robot replacement is a service-only procedure. If the Y-tray
fails, you will need to call Quantum Support for a replacement.

298 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 10
Updating Firmware

This chapter covers updating library and tape drive firmware, including:
Updating Library Firmware
Updating and Autoleveling Tape Drive Firmware
About Tape Drive Firmware Autoleveling
Uploading Tape Drive Firmware Used in Autoleveling
Deleting Tape Drive Firmware Used in Autoleveling
Initiating Tape Drive Firmware Autoleveling

Updating Library Firmware


The library firmware update operation allows you to update library
firmware using the Web client. With the library firmware update
operation, you can upgrade firmware to a later version or downgrade
firmware to an earlier version. Upgrading library firmware can take up
to 30 minutes.

Quantum Scalar i40 and Scalar i80 Users Guide 299


Chapter 10: Updating Firmware
Updating Library Firmware

Before updating library firmware, it is recommended that you capture


the library snapshot. The library snapshot file saves status information
and trace logs for library components. This information helps technical
support troubleshoot issues that might occur with the firmware
upgrade. For more information, see Capturing Snapshots of Library
Information on page 317.
In addition, it is recommended that you save the library configuration
before upgrading the library (in case the upgrade fails) and again after
the upgrade successfully completes. For more information, see Saving
the Library Configuration on page 107.
When you upgrade or downgrade library firmware, the library also
autolevels tape drive firmware, if needed. Autoleveling will not occur if
a tape drive has a cartridge loaded in it. Make sure to unload all tape
drives before updating library firmware. See Updating and Autoleveling
Tape Drive Firmware on page 303.
The library automatically restarts after the firmware update is complete.
Before logging into the library, clear the Web browser cache. See your
Web browser's documentation for instructions on how to clear the
cache.

Caution: After the update process starts, you must wait until it
completes. Do not attempt to interrupt the process in any
way, and do not power cycle the library. Loss of data or
library operability could occur.

Note: If you downgrade library firmware to an earlier version using


the firmware upgrade process, library configuration settings
will be reset to the factory defaults (see Resetting Factory
Defaults on page 333). You must manually reconfigure your
librarys settings. You can also downgrade library firmware by
restoring a configuration file that contains the version of
firmware to which you want to downgrade (see Restoring the
Library Configuration on page 108).

After downgrading, network settings are not reset, and


licenses remainas long as the downgraded firmware version
supports that licensed feature

You can only update firmware from the Web client.

300 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 10: Updating Firmware
Updating Library Firmware

Web Client
1 Log into your library to view the latest firmware version available.
Click Tools > Update Library Firmware.
If you are connected to the Internet, the screen displays the
firmware currently loaded on your library and the latest available
firmware.

Figure 76 Tools - Update


Library Firmware Screen

Note: You can also view a listing of the latest version of library
firmware on the following Web site:
http://www.quantum.com/ServiceandSupport/
SoftwareandDocumentationDownloads/SI40/Index.aspx
and click the Firmware tab.

View your librarys current firmware version by selecting


Reports > About Library from the operator panel, or
Reports > About >
Scalar i40/i80 from the Web client.

2 Unload tape cartridges from all tape drives installed in the library.

Quantum Scalar i40 and Scalar i80 Users Guide 301


Chapter 10: Updating Firmware
Updating Library Firmware

3 Capture a library snapshot (see Capturing Snapshots of Library


Information on page 317).
4 Save the library configuration (see Saving the Library Configuration
on page 107).
5 If the library has an internet connection, use the Web client to
update the library to the latest firmware. If the library does not have
an internet connection, use a Web browser to browse for a specific
file.

Update using the Web Client


a From the Web client, return to Tools > Update Library
Firmware.
The Tools - Update Library Firmware screen displays.
b Click Read EULA to read and click Accept to accept the End
User License Agreement.
c Click the check box next to Update library firmware with the
version from the Quantum Support Web site.

Note: If a newer version is already installed on your library,


you will receive a warning message.

d Go to Step 6.

Browse for a Specific FIle


a Using a Web browser connected to the internet go to http://
www.quantum.com/ServiceandSupport/
SoftwareandDocumentationDownloads/SI40/Index.aspx and
click the Firmware tab.
b Download the library firmware to a known location on your
computer.
c From the Web client, return to Tools > Update Library
Firmware.
The Tools - Update Library Firmware screen displays.
d Click Browse.
e Locate the library firmware file and click Open.

302 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 10: Updating Firmware
Updating Library Firmware

f Go to Step 6.
6 Click Apply.
A confirmation dialog box displays asking you to confirm that you
want to update the library firmware and reboot the library.
7 Click OK to continue with the library firmware update operation.
The Progress Window displays. The Progress Window contains
information on the action, elapsed time, and status of the
requested operation. The Progress Window closes automatically and
the library shuts down and then reboots. You will need to log back
into the library once it has finished rebooting. Wait for the library to
completely reboot before logging back in to the library. The reboot
takes several minutes.
If Failure appears in the Progress Window, the operation failed. The
library will automatically reload the previous version of library
firmware.
8 Clear the Web browser cache before logging in to the library. See
your Web browsers documentation for instructions on how to clear
the cache.
9 Log in to the library.

Note: If the library is still in the process of restarting, the Web


browser may display an error page or message when you
try to access or log in to the Web client.

10 Verify the library firmware installed successfully. Go to Tools >


Update Library Firmware or view the About Scalar i40/i80 report
(on the Web client) by selecting Reports > About > Scalar i40/
i80).
11 Save the library configuration again (see Saving the Library
Configuration on page 107).

Quantum Scalar i40 and Scalar i80 Users Guide 303


Chapter 10: Updating Firmware
Updating and Autoleveling Tape Drive Firmware

Updating and Autoleveling Tape Drive Firmware


The library firmware bundle file contains baseline tape drive firmware
image that Quantum has validated. Tape drive firmware is installed at
the same time as library firmware. (You can also install upgrades or
patches separately, which is described in the sections below.)
In addition, the library is equipped with a tape drive autoleveling
feature, that automatically updates firmware on all installed tape drives,
keeping all tape drives of the same type at the same firmware level.

About Tape Drive Autoleveling occurs only at specific times:


Firmware Autoleveling Tape drive firmware is verified whenever a tape drive is added,
replaced, or power cycled, or when the library is rebooted. If the
firmware installed on the tape drive does not match the tape drive
firmware installed on the library, the tape drive firmware is
autoleveled.
Tape drive firmware is autoleveled when library firmware is updated
(see Updating Library Firmware on page 299).
Details about Autoleveling include:
The autoleveling feature is always enabled.
The library firmware contains baseline tape drive firmware image
that Quantum has validated. You cannot delete any of the baseline
tape drive firmware images. You may, however, upload separate
tape drive firmware images to use instead (such as a patch or
upgrade provided by Quantum; see Uploading Tape Drive Firmware
Used in Autoleveling on page 306). If you upload a patch, the patch
will display instead of the baseline image, although the baseline
image will remain, hidden. Tape drives will be autoleveled to the
patch. If you delete the patch, then baseline image will reappear on
the screen and the tape drives will autolevel to the baseline image
(see Deleting Tape Drive Firmware Used in Autoleveling on
page 308).

304 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 10: Updating Firmware
Updating and Autoleveling Tape Drive Firmware

If you upgrade library firmware, the baseline tape drive firmware for
that version of library firmware will overwrite the existing baseline
tape drive firmware images. If you did not previously upload a
patch, all the tape drives will be autoleveled to the new baseline. If
you previously uploaded a patch, the patch remains and tape drive
firmware will remain autoleveled to the patch. You will need to
delete the patch in order to have the tape drives autoleveled to the
new baseline (see Deleting Tape Drive Firmware Used in Autoleveling
on page 308).
If you downgrade library firmware, the baseline tape drive firmware
for that version of library firmware will overwrite the existing
baseline tape drive firmware images as well as any patches you may
have uploaded prior to the downgrade, and all tape drives will be
autoleveled to the new baseline. If you want to continue to use the
patch or a different version of tape drive firmware, you will need to
upload it again. Contact Quantum Support if you need help
obtaining firmware (see Getting More Information or Help on
page xxvii).
Autoleveling will not occur if a tape drive has a cartridge loaded in
it. Make sure to unload tape cartridges from all tape drives before
loading new firmware for autoleveling, or before upgrading library
firmware.
Autoleveling occurs after the completes its initialization. This means
it is possible for a host to see the medium changer initially, but
when the autoleveling starts on the drives it is likely the medium
changer will disappear again. Wait until autoleveling completes
before starting backup applications. (The operator panel displays a
message indicating autoleveling is taking place. Wait until this
message disappears before starting backup applications.)
If you reset factory defaults, any tape drive firmware images you
manually uploaded will be deleted (see Resetting Factory Defaults
on page 333).

Quantum Scalar i40 and Scalar i80 Users Guide 305


Chapter 10: Updating Firmware
Updating and Autoleveling Tape Drive Firmware

Uploading Tape Drive Tape drive firmware is bundled with the library firmware and is
Firmware Used in automatically installed and autoleveled on your tape drives when you
Autoleveling install library firmware.
In some cases, a tape drive firmware upgrade or patch may be available
from Quantum Support outside of the normal library firmware release
cycle. The instructions in this section explain how to install such an
upgrade or patch.
You can also use these instructions to install down-rev tape drive
firmware. If you wish to do this, contact Quantum Support for the
firmware image files.

Caution: Only install tape drive firmware image files that have been
tested and qualified by Quantum.

It is not necessary to delete an existing version of firmware before


uploading a new version. The new version overwrites the existing
version.

Note: Uploading tape drive firmware for autoleveling only uploads


the firmware to the library in preparation for autoleveling. It
does not initiate autoleveling or install firmware on the tape
drive. To initiate autoleveling, see Initiating Tape Drive Firmware
Autoleveling on page 310.

You can only upload tape drive firmware on the Web client.

Web Client
1 Check the Quantum Web site to see if you are running the current
level of firmware (go to http://www.quantum.com/
ServiceandSupport/SoftwareandDocumentationDownloads/SI40/
Index.aspx and click the Firmware tab).
2 If needed, obtain the firmware download file from Quantum
Support and place it in a known location on your computer.
3 Verify with the release notes or Quantum Support that you are
installing the correct version of tape drive firmware for your library.
For support contact information, see Getting More Information or
Help on page xxvii.

306 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 10: Updating Firmware
Updating and Autoleveling Tape Drive Firmware

4 Select Tools > Drive Operations.


The Tools - Drive Operations screen displays.
5 Select Upload/remove tape drive firmware for autoleveling and
click Next.
The Tape Drive Firmware Autolevel screen displays. The screen lists
the vendor, type, interface type, form factor, and firmware revision
number for all tape drives that the library supports, whether or not
they are installed in the library.
6 Click Upload.
The Upload Tape Drive Images screen displays. The screen lists the
vendor, type, form factor, and interface type of all tape drives
installed in the library. You can only upload tape drive images for
the listed tape drives.
7 Click Browse.
8 Locate the tape drive firmware image file and click Open.
9 Click Apply. The Progress Window displays. The Progress Window
contains information on the action, elapsed time, and status of the
requested operation. Do one of the following:
If Complete appears in the Progress Window, the tape drive
firmware upload completed. Check to see if a diagnostic ticket
was generated for this operation. For information on diagnostic
tickets, see About Diagnostic Tickets on page 312. If no
diagnostic ticket(s) exists, continue to next step.
If Failure appears in the Progress Window, the tape drive
firmware update was not successful.
10 To initiate autoleveling, see Initiating Tape Drive Firmware
Autoleveling on page 310.

Deleting Tape Drive If you installed a tape drive firmware image to override the library's
Firmware Used in baseline image used for autoleveling, you can delete it. You cannot
Autoleveling delete the library's baseline tape drive firmware images. For more
information, see About Tape Drive Firmware Autoleveling on page 305.

Quantum Scalar i40 and Scalar i80 Users Guide 307


Chapter 10: Updating Firmware
Updating and Autoleveling Tape Drive Firmware

Note: Deleting tape drive firmware for autoleveling only deletes the
firmware and makes the library's baseline tape drive firmware
available for autoleveling. It does not initiate autoleveling or
install firmware on the tape drives. To initiate autoleveling, see
Initiating Tape Drive Firmware Autoleveling on page 310.

You can only delete tape drive firmware on the Web client.

Web Client
1 Select Tools > Drive Operations.
The Tools - Drive Operations screen displays.
2 Select Upload/remove tape drive firmware for autoleveling and
click Next.
The Tape Drive Firmware Autolevel screen displays. The screen lists
the vendor, type, interface type, form factor, and firmware revision
number for all tape drives that the library supports, whether or not
they are installed in the library.
3 Select the tape drive firmware you want to delete.
4 Click Delete.
The Progress Window displays. The Progress Window contains
information on the action, elapsed time, and status of the
requested operation. Do one of the following:
If Success appears in the Progress Window, the tape drive
firmware was successfully deleted. The librarys default baseline
tape drive firmware will now be used for autoleveling.
If Failure appears in the Progress Window, the tape drive
firmware update was not successfully deleted.
5 To initiate autoleveling, see Initiating Tape Drive Firmware
Autoleveling on page 310.

308 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 10: Updating Firmware
Updating and Autoleveling Tape Drive Firmware

Initiating Tape Drive Autoleveling occurs automatically at specific times (whenever a tape
Firmware Autoleveling drive is added, replaced, or power cycled; when the library is rebooted;
or when you update library firmware). If you upload or remove tape
drive firmware separately from library firmware (such as a Quantum-
provided upgrade or patch) and want to autolevel the tape drives
immediately, follow these steps:
1 Unload tape cartridges from all tape drives you want to autolevel.
2 Stop all host commands to the tape drives you want to autolevel.
3 Initiate autoleveling by performing one of the following actions:
Reset (power cycle) the tape drives on which you want to
install firmware. This autolevels only the tape drives you reset. If
you reset all tape drives at once, each tape drive is reset
sequentially, causing the autoleveling to occur one tape drive at
a time. If you reset each tape drive individually, you must wait
for the autolevel to occur before proceeding to the next tape
drive. It takes about 7 minutes to autolevel each tape drive. For
instructions, see Resetting a Tape Drive on page 331.
Restart the library. This verifies and autolevels all tape drives
simultaneously. This process takes about 7 minutes for the
autolevel, plus the time it normally takes the library to reboot.
From the Web client, select Operations > System Shutdown.
Select Restart and click Apply. See Restarting the Library on
page 142 for more information.
The operator panel displays a message indicating autoleveling is
taking place. If the install or autolevel fails, you receive a diagnostic
ticket.
4 Wait until autoleveling is complete before resuming host
commands. To make sure autoleveling is complete, check the system
information report to see if the tape drive firmware is installed on all
intended tape drives. From the Web client, select Reports > System
Information.

Quantum Scalar i40 and Scalar i80 Users Guide 309


Chapter 10: Updating Firmware
Updating and Autoleveling Tape Drive Firmware

310 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 11
Troubleshooting

The Scalar i40 and Scalar i80 libraries include advanced system monitoring
and alerting mechanisms that inform you of library status and issues.
The library provides you with status information about various library
subsystems and components. It also notifies you of issues it detects and
guides you through diagnosing and correcting issues before problems
interfere with backups.
This chapter covers:
About Diagnostic Tickets
Capturing Snapshots of Library Information
Troubleshooting Library Not Ready Messages
Retrieving Tape Drive Logs
Interpreting LEDs
Running the Installation and Verification Test (IVT)
Running the IVT Diagnostic Subtests Individually Robotics, Tape
Drive, and Magazine Tests
Running the Random Move Test
Performing Library Diagnostics
Resetting Factory Defaults

Quantum Scalar i40 and Scalar i80 Users Guide 311


Chapter 11: Troubleshooting
About Diagnostic Tickets

About Diagnostic Tickets


The library uses advanced problem detection, reporting, and
notification technology to alert you of problems as soon as they occur.
The library performs numerous self-tests to monitor the librarys
temperature, voltage and currents, and standard library operations. It
performs these self-tests each time the library is powered on and during
normal operation when the library is idle.
If the self-test detects a problem, the library generates a diagnostic
ticket that identifies the component that is likely causing the problem. If
the problem is not severe, the library continues to provide full
functionality to all unaffected partitions.
The tickets are assigned one of three priority levels:
Urgent The highest level of priority. A ticket with urgent priority
indicates that a failure has occurred or a serious condition exists
within the library that requires immediate corrective action. In most
cases, a hardware component is no longer functioning at an
acceptable level or has failed. Typical library operations required for
backup or restore operations are either not possible or highly
unreliable. This level of priority is conveying a critical issue.
High The middle level of priority. A ticket with high priority
indicates that a condition exists within the library that impacts
system performance, redundancy, or just a specific host application.
Typical library operations can continue without immediate
corrective action, although an application may have failed and may
need to be restarted. A user should investigate the condition and
correct the problem soon. This level of priority is conveying a
warning message.
Low The lowest level of priority. A ticket with low priority
indicates that an abnormal condition existed within the library that
warrants investigation and correction but the nature of the
condition may have little or no effect on operations. This level of
priority is conveying an informational message.

312 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 11: Troubleshooting
About Diagnostic Tickets

The library has a number of visual cues to alert you that one or more
diagnostic tickets exist:
The librarys ticket indicator LED turns on to indicate that at least
one ticket exists (see Front Panel LEDs on page 321).
The operator panel displays a health status icon (see Health status
on page 26 for description).
The Web client displays a subsystem status icon (see Subsystem
Status on page 32).
You can frequently resolve a simple problem yourself, but if the problem
is complex or involves a field replaceable unit (FRU), you will be directed
to contact Quantum Support. Only qualified service technicians can
service FRUs.

Viewing, Closing, and The initial status of all diagnostic tickets is Unopened. Once you select
Resolving Diagnostic the Resolve button, the ticket status changes to Opened. When you
Tickets close the ticket, its status changes to Closed. You can view Opened and
Unopened tickets on both the operator panel and the Web client, but
you can view Closed tickets only on the Web client.
You can view and close diagnostic tickets on both the operator panel
and the Web client, but only the Web client provides a complete
description of the event and guides you through a series of steps to
resolve the issue. It is recommended that you use the Web client to view
and resolve all your diagnostic tickets.
You can close all tickets at once but this is not recommended. It is
recommended that each diagnostic ticket be viewed, analyzed, and
closed individually.
Only one person at a time can resolve a ticket. Multiple users can,
however, view ticket details simultaneously.
If your Web client session goes down while resolving a diagnostic ticket,
you must wait 3 minutes before you can continue resolving the
diagnostic ticket.

Quantum Scalar i40 and Scalar i80 Users Guide 313


Chapter 11: Troubleshooting
About Diagnostic Tickets

If you do not close a diagnostic ticket and the issue recurs, the only
thing that gets updated in the ticket is the date and time the issue
recurred (listed under Last Occurrence on the Web client and Updated
on the operator panel). Ticket details are not updated because the
original issue is often the root cause. If the location of the error in the
library changed since the ticket was first issued, the ticket details will
continue to reflect the original error location.

Note: A diagnostic ticket can have a status of Cancelled. As discussed


below in Closing Diagnostic Tickets Automatically on page 316,
after a reboot or power request, the system may elect to close
a ticket. This cancelled state does not indicate that a problem
has been corrected. The system would re-open the ticket if the
issue is encountered again.

Operator Panel
1 Select Reports > Diagnostic Tickets.
2 Select Library, Tape Drives, or Media to view tickets related to the
selected subsystem. Only the subsystems that contain tickets are
listed.
3 You can also close all tickets at once by selecting Close ALL.

Caution: Be careful when choosing Close ALL. This closes all


diagnostic tickets even if they are not resolved. It is
recommended that each diagnostic ticket be viewed,
analyzed, and closed individually.

4 Press Select.
All of the tickets posted for the selected subsystem are displayed.
5 Scroll through the tickets and select the one you want to view. Press
View.
Basic details about the ticket are displayed, such as ticket ID
number, short description, priority, and when the ticket was created
and updated.
6 You can either press Close to close the ticket, or press Exit to exit
without closing the ticket.

314 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 11: Troubleshooting
About Diagnostic Tickets

Web Client
1 You can view all diagnostic tickets by selecting Tools > All
Diagnostic Tickets. Alternatively, you can view library, tape drive,
and media tickets separately via the Home Page Subsystem Status
buttons (see Subsystem Status on page 32).
Whichever method you choose, the tickets are displayed in order of
last occurrence of each event, beginning with the most recent.

Note: Last Occurrence indicates the last time a ticket event


occurred. This information updates any time the event
recurs. Last Occurrence does NOT update if you open,
close, or resolve the diagnostic ticket. Ticket details are not
updated when a ticket recurs.

2 Identify the diagnostic ticket you want to resolve.

Note: You can use the Go to Diagnostic Ticket text box at the
bottom of the screen to locate a specific ticket number. In
addition, if there is more than one page of tickets, use the
Page 1 of x arrows to view the additional tickets.

3 To view more details about the ticket, including the location


coordinates of resources that may be involved, click the Details
button.
4 To resolve the ticket, click the Resolve button. A series of screens
guides you through steps to resolve the issue on your own. If the
situation cannot be resolved, you are instructed to contact technical
support. When you have finished reading all of the Resolution
screens, do one of the following:
To close the ticket now, click Close. The Tools - All Diagnostic
Tickets window displays, with the ticket no longer in the list.

To leave the ticket open for future troubleshooting, click Exit.


The ticket remains on the list.

Quantum Scalar i40 and Scalar i80 Users Guide 315


Chapter 11: Troubleshooting
About Diagnostic Tickets

5 You can also close all tickets at once by clicking the Close All Tickets
button.

Caution: Be careful when pressing the Close All Tickets button.


This closes all diagnostic tickets even if they are not
resolved. It is recommended that each diagnostic ticket
be viewed, analyzed, and closed individually.

Note: To display all closed tickets, select the Include Closed Tickets
check box at the bottom of the screen. The Tools - All
Diagnostic Tickets screen refreshes, with the Resolve button
unavailable for all closed diagnostic tickets.

Closing Diagnostic When you reboot the library, all currently open diagnostic tickets are
Tickets Automatically closed automatically. If any errors occur during the reboot, the library
issues new tickets.
Automatic ticket closure occurs only when you intentionally initiate a
reboot, by either restarting the library, shutting down the library, or
upgrading library firmware. Automatic ticket closure will not occur if
the library shuts down unexpectedly or if the power cord is unplugged.

Disabling or Enabling this Feature


Automatic ticket closure is enabled by default. You can enable or disable
this feature from the operator panel.
1 Select Setup> System Settings.
2 Press Modify.
3 Press Up to change setting as desired,
4 Press Apply.

Viewing Closed Diagnostic Tickets


You can view closed diagnostic tickets from the Web client.
1 Select Tools > All Diagnostic Tickets.
2 Click the Include Closed Tickets check box.

316 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 11: Troubleshooting
Capturing Snapshots of Library Information

Note: Tickets that were auto-closed are designated as


Canceled.

Capturing Snapshots of Library Information


Technical support personnel may ask you to capture a snapshot of the
library so they can better diagnose issues. The Capture Snapshot
operation captures detailed information about the entire library in a
single ASCII file that can be e-mailed to technical support personnel.
The logged information consists of configuration data, status
information, and trace logs for library components. Trace logs collect
problem data and provide support personnel with vital library
information for troubleshooting and solving problems.
You can e-mail the snapshot file from the Web client. You can also
download the Capture Snapshot file to a computer, however, you
cannot print Capture Snapshot files directly from the Web client.
Depending on the library configuration and your connection speed,
saving the snapshot file takes approximately 30 minutes. The resulting
file size can be large. Your firewall file-size limitations could prohibit you
from e-mailing the file.
On the Web client, ensure that the library e-mail account is
appropriately configured before you attempt to e-mail the snapshot
from the library. If the library e-mail account address is not configured,
an error appears. For information on setting up the e-mail account, see
Configuring the Library E-Mail Account on page 76.
You can set up the library to automatically capture and attach a
snapshot to specific diagnostic ticket e-mail notifications (see
Configuring the Library E-Mail Account on page 76). If the library is in
the process of capturing an automatic snapshot, you will not be able to
manually capture a snapshot via the Web client until the automatic
snapshot is complete. If this happens, an error message will display.
Wait about 10 minutes and try again.You can only capture a snapshot
via the Web client.

Quantum Scalar i40 and Scalar i80 Users Guide 317


Chapter 11: Troubleshooting
Troubleshooting Library Not Ready Messages

Web Client
1 Select Tools > Capture Snapshot.
2 Select whether to download the file or e-mail it to a recipient, and
click Apply.

Troubleshooting Library Not Ready Messages

Not Ready Messages If a not ready message displays on the operator panel at startup, it
on the Operator Panel means the robot cannot move. The library may display a message
stating that it did not initialize. Try the following steps to resolve the
issue:
If the not ready message occurs upon initial installation (first time
out of the box or after a chassis replacement), make sure you
removed the Y-tray restraint as described in Chapter 2, Unpacking
the Library.
Press the Tickets button on the operator panel to view any
diagnostic tickets that occurred as a result of the error.
Log in to the Web client using the IP address that is displayed on the
operator panel screen to view ticket details and resolution steps that
may help resolve the issue.
If none of the above steps works, contact Quantum Support.

Not Ready Messages The Web client includes a header that contains the company logo,
on the Web Client product name, and the three main navigation buttons (Home, Help, and
Logout). In addition, a message in the header alerts you when the
library is not ready. (No message displays in the header when the library
is in a ready state.) For more information on Web client user interface
elements, see Web Client Layout and Functions on page 29.
Library not ready messages continue to display in the header until the
issue has been resolved, and the robot has completed its calibration.

318 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 11: Troubleshooting
Troubleshooting Library Not Ready Messages

If the library displays a not ready message, you may be able to tell
from the message how to remedy the situation. If not, the library
generates a diagnostic ticket whenever the library encounters a
problem. The diagnostic ticket may provide information that can help
you troubleshoot the problem. For more information, see About
Diagnostic Tickets on page 312. The library not ready messages
include the following, with possible solutions listed:

Message Resolution

Library is not ready The library is initializing and becoming


ready. Wait for the library to finish
initialization.

Library is becoming ready Wait for the library to finish


initialization.

Library is not initialized Most likely a problem with the robot.


Try the following:
Check the diagnostic ticket and
follow the resolution steps listed (see
About Diagnostic Tickets on
page 312).
Power cycle the library to clear the
error. If that fails, contact Quantum
Support.

Library needs manual Most likely a problem with the robot or


attention other component. Try the following:
Check the diagnostic ticket and
follow the resolution steps listed (see
About Diagnostic Tickets on
page 312).
Power cycle the library to clear the
error. If that fails, contact Quantum
Support.

Note: You may not see the not ready message in the Web client
until the browser refreshes. Similarly, even if the problem has
been resolved, the not ready message will not disappear
from the Web client until the browser refreshes.

Quantum Scalar i40 and Scalar i80 Users Guide 319


Chapter 11: Troubleshooting
Retrieving Tape Drive Logs

Retrieving Tape Drive Logs


The library allows you to retrieve tape drive logs using the Web client.
Tape drive log information can be used to help troubleshoot the library,
the tape drive sled, and tape drive issues.
Since the log retrieval process can take up to 30 minutes, the tape drive
and associated partition are automatically taken offline during the
operation and brought back online when the operation completes. You
will be asked to confirm that you want to take the tape drive and
partition offline.
Tape drive log files adhere to the following naming convention:
UDS_ID_SN.DMP, where ID identifies the tape drive coordinate location
within the library and SN identifies the tape drive serial number.
You can only retrieve tape drive logs via the Web client.

Web Client
1 Select Tools > Drive Operations.
2 Select Retrieve Tape Drive Log.
3 Click Apply.
4 When the Success message displays, complete the next screens to
save the log file to your computer.

Interpreting LEDs
LEDs provide a visual indication about the status of certain library
components. LEDs can sometimes communicate that a problem exists
when diagnostic tickets cannot.
The following components of the library have LEDs:
Front panel
System control board (SCB)

320 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 11: Troubleshooting
Interpreting LEDs

Tape drives
Power supplies

Front Panel LEDs There are two LEDs on the front panel, above the power button. They
function as follows:

LED Location Color Indicates

Power-on LED Green Library power is ON.


(closest to power
button)

Ticket indicator Amber The LED is illuminated when at least


LED. (farthest from one open or unopened diagnostic
power button) ticket exists.

Figure 77 Front Panel LEDs

Ticket indicator LED


Power-on LED

Quantum Scalar i40 and Scalar i80 Users Guide 321


Chapter 11: Troubleshooting
Interpreting LEDs

System Control Board The SCB has one health status LED. In addition, each Ethernet port
LEDs contains two LEDs, a green activity indicator and an amber link
indicator. The Ethernet port closest to the center of the library is for
customer use. The Ethernet port farthest from the center of the library is
for service use only.

LED Color Indicates

SCB Health Green Healthy and operational.


Status LED
Red Failure. Replacement required.

Ethernet Green This LED illuminates when actual


Port Green traffic is being sent over the Ethernet
LED (Activity cable. The LED may be blinking or on
Indicator) solid; it blinks more rapidly the more
traffic is being sent over the
connection. When the LED is lit,
communications are in process and
when the LED is off no communication
is occurring.

Ethernet Amber This LED illuminates solidly when a


Port Amber link is established, and will be off
LED (Link when no link is present. Link
Indicator) means an Ethernet cable is connected
and the other end of the cable is also
connected to another powered-up and
operational Ethernet device.

Figure 78 System Control


Board LEDs

Customer Ethernet Service Ethernet Health status LED


port LEDs port LEDs

322 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 11: Troubleshooting
Interpreting LEDs

Tape Drive/Sled LEDs The library supports SAS and Fibre Channel tape drives. The drive sled
LEDs for each are described below.

SAS
SAS Tape Drive Sleds have one LED that indicates the following:

Color Indicates

Green Healthy and operational.

Amber Tape drive is offline.

Red Failure. Replacement required.

Fibre Channel
Fibre Channel tape drive sleds have two LEDs on their rear panel,
indicated on the drive sled as STATUS and LINK (see Figure 79).

LED Color Indicates

Status Green Healthy and operational.

Amber Tape drive is offline.

Red Failure. Replacement required.

Link Green On solid Fibre Channel link is


present
Flashing Fibre Channel link is
present and communications are in
process

Off No Fibre Channel link is currently


present.

Quantum Scalar i40 and Scalar i80 Users Guide 323


Chapter 11: Troubleshooting
Interpreting LEDs

Figure 79 Fibre Channel Tape Link LED Status LED


Drive LEDs

Half-height
FC tape
drive

Full-height
FC tape
drive

Link LED Status LED

Power Supply LED Diagnostic tickets typically report all problems related to power
supplies. You can also observe the power supply LED to see if the power
supply is functioning appropriately (see Figure 80). The power supply
LED indicates the following:

LED Color Indicates

Green AC power is present and the library front panel


power switch is turned ON.

Amber AC power is present but the library front panel


switch is turned OFF.

Red Power supply failure.

Off No power. Ensure the power supply is correctly


plugged into a wall outlet.

324 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 11: Troubleshooting
Running the Installation and Verification Test (IVT)

Figure 80 Power Supply LED

Power supply LED

Running the Installation and Verification Test (IVT)


The Installation and Verification Test (IVT) is used to evaluate a newly
installed library or one that has been moved. The test calibrates the
robot to the library, verifies that the robot is functioning properly, and
verifies that the magazines and tape drives are installed correctly and
reachable by the robot. The test also verifies that barcode labels can be
read by the robot scanning operation.
You should run the full IVT upon installation of a new library, and at any
other time you remove, replace, or service components that require you
to move the library into or out of a rack or desktop kit. You must run the
robotics test after a Y-tray replacement.
The full IVT consists of three subtests. You may run the subtests
separately (see Performing Library Diagnostics on page 330). The full IVT
takes up to 30 minutes to complete.
Robotics Test A series of tests that evaluates the basic
functionality of the robotics assembly, including picker travel,
Y-carriage assembly travel, barcode scanning, calibration sensors,
and several moves of a scratch tape. It also calibrates the robot to
the library. The test takes up to 11 minutes to complete.

Quantum Scalar i40 and Scalar i80 Users Guide 325


Chapter 11: Troubleshooting
Running the Installation and Verification Test (IVT)

Tape Drive Test For each installed tape drive, the robot moves a
scratch tape into the tape drive, inventories the scratch tape, and
moves the scratch tape out of the tape drive. The test takes 12
minutes per tape drive.
Magazine Test Moves a scratch tape through all storage slots in
the library. These tests verify the robotics can reach all the slots in
the magazine for both get and put operations. The test takes up to
5 minutes per magazine.
Details about running the IVT include:
Running the IVT takes partitions offline and logs all users off of the
Web client.
The operator panel displays progress of all three subtests. Before a
test begins, its progress is Scheduled. When a test begins, its
progress changes to Running. Once a test completes, its progress
changes to either Passed or Failed.
You can stop the IVT by pressing the Stop button. The progress of
the currently running test changes to Stopping. Once stopped,
the current test and all other scheduled tests display Stopped.
You can only perform the IVT from the operator panel.

Prerequisites for Running IVT


Certain prerequisites must be met in order to run the IVT. Prior to
running the IVT, the library checks to make sure all the prerequisites are
met. If any is not, the operator panel displays a message telling you how
to resolve the issue. Prerequisites include:
All diagnostic tickets must be closed.
I/E station slots must be allocated (minimum of five).
All magazines must be installed in the library (two in the Scalar i40;
four in the Scalar i80).
At least one tape drive must be installed in the library.
All installed tape drives must be in the ready state. (You can check
the Web client Setup > Drive Settings for listing of which drives
are in the ready state.)

326 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 11: Troubleshooting
Running the IVT Diagnostic Subtests Individually Robotics, Tape Drive, and Magazine Tests

A scratch tape must be in the top I/E station slot. The scratch tape
must be assigned to the System partition. The scratch tape must be
compatible with all unloaded tape drives installed in the library. For
a list of supported media, see Supported Media on page 347.

Operator Panel
1 Make sure the prerequisites listed in Prerequisites for Running IVT
on page 326 are met.
2 Select Tools > IVT.
A message displays, telling you that partitions will be turned offline
and all Web client users will be logged out.
3 Press Yes to set partitions offline, log users off the Web client, and
continue with the test.
The library conducts a series of prerequisite checks to be sure
everything is in order. Each prerequisite is listed as the library checks
it. If something is not set up correctly to run the IVT, the operator
panel displays a message letting you know how to fix it. Once you
fix the issue, again select Tools > IVT. If all is in order, the test
begins.
4 When the test completes, if any of the three subtests fails, check the
library diagnostic tickets to help determine and resolve the problem.

Running the IVT Diagnostic Subtests Individually


Robotics, Tape Drive, and Magazine Tests
If you do not need to run the full IVT, you can run the robotics, tape
drive, or magazine test separately to check an individual component.
You should do this when you remove, replace, or service a component
that does not require you to remove the library into or out of a rack or
desktop kit.
For a description of the diagnostic subtests, see Running the Installation
and Verification Test (IVT) on page 325.

Quantum Scalar i40 and Scalar i80 Users Guide 327


Chapter 11: Troubleshooting
Running the IVT Diagnostic Subtests Individually Robotics, Tape Drive, and Magazine Tests

Details about running the diagnostic subtests include:


Running a diagnostic takes partitions offline and logs all users off of
the Web client.
The operator panel displays progress of the diagnostic. When a test
begins, its progress displays as Running. Once a test completes,
its progress changes to either Passed or Failed.
Once a diagnostic test starts, you cannot stop it. You must let it run
to completion.
For the tape drive and magazine diagnostics, you may choose
just one device to test, or you can choose to test all. The magazine
diagnostic tests all the slots in the selected magazine(s).
You can only perform the subtests from the operator panel.

Prerequisites for Running Diagnostic Subtests


Certain prerequisites must be met in order to run the diagnostics. Prior
to running a diagnostic, the library checks to make sure all the
prerequisites are met. If any is not, the operator panel displays a
message telling you how to resolve the issue. Prerequisites include:
All diagnostic tickets must be closed.
I/E station slots must be allocated (minimum of five).
All magazines must be installed in the library (two in the Scalar i40;
four in the Scalar i80).
A scratch tape must be in the top I/E station slot. The scratch tape
must be assigned to the System partition. The scratch tape must be
compatible with all unloaded tape drives installed in the library. For
a list of supported media, see Supported Media on page 347.
For the tape drive diagnostics only, at least one tape drive must
be installed in the library. All installed tape drives must be in the
ready state. (You can check the Web client Setup > Drive Settings
for listing of which drives are in the ready state.)

328 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 11: Troubleshooting
Running the Random Move Test

Operator Panel
1 Make sure the prerequisites listed in Prerequisites for Running
Diagnostic Subtests on page 328 are met.
2 Select Tools > Diagnostics.
3 Select Robotics Test, Tape Drive Test, or Magazine Test and press
Select.
4 For the tape drive or magazine test, select which tape drive or
magazine you want to test, or select ALL, then press Select.
5 Press Yes to set partitions offline, log users off the Web client, and
continue with the test.
The library conducts a series of prerequisite checks to be sure
everything is in order. Each prerequisite is listed as the library checks
it. If something is not set up correctly, the operator panel displays a
message letting you know how to fix it. Once you fix the issue, start
over from Step 1. If all is in order, the test begins.
6 Once complete, if the test fails, check the library diagnostic tickets
to help determine and resolve the problem.

Running the Random Move Test


The random move test is a demonstration that consists of moving a
scratch tape into random slots around the library. Partitions are set
offline and the test runs continuously until you stop it. You can only run
this test from the operator panel.

Operator Panel
1 Install a scratch tape in the top I/E station slot.
2 Assign the scratch tape to the System partition.
3 Select Tools > Random Move Test.
4 Press Run.
5 Press Yes to set partitions offline, log users off the Web client, and
continue with the test.

Quantum Scalar i40 and Scalar i80 Users Guide 329


Chapter 11: Troubleshooting
Performing Library Diagnostics

6 When you are ready to stop the test, press Stop.


7 When the operator panel displays the message that the test has
stopped, press OK.

Performing Library Diagnostics


The Diagnostics menu on the Web client contains tests you can run to
determine if tape drives and robotics, are working as they should.
Notes about Diagnostics include:
Entering Diagnostics takes all your library partitions offline. Be sure
any crucial operations have stopped before you enter Diagnostics.
When you exit Diagnostics, your partitions return to the online/
offline status they were in previously.
Only users with Admin level privileges can access Diagnostics.
Only one user can be logged into Diagnostics at a time. Entering
Diagnostics disconnects all other Web client users with the same or
lower privileges (the operator panel user is not logged out, but any
attempted operation using partitions will fail). Users will be unable
to log in to the Web client and will get an error message stating that
Diagnostics is in progress.
You can only enter Diagnostics from the Web client.

Web Client
1 Select Tools > Diagnostics.
A confirmation dialog displays, alerting you that all other users will
be logged out and library partitions will be taken offline.
2 Click OK.
You are now in a page that looks much like the regular Home page,
but with different choices in the menu bars. Also, you will notice
that all your partitions are offline.

330 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 11: Troubleshooting
Performing Library Diagnostics

3 Select the test you want to run from the menus. Your choices
include:
Tape Drive Reset (see Resetting a Tape Drive on page 331 for
more information)
Robotics Get/Put Test (see Robotics Get/Put Test on page 332 for
more information)
4 To exit Diagnostics, select Exit.

Resetting a Tape Drive The Drive Reset operation power cycles the tape drive while the tape
drive remains in the drive sled in the library. You may want to perform a
reset if a tape drive does not come ready or it is not behaving properly
(for example, if a tape is stuck in the drive and will not unload).
The reset may take several minutes. After the reset operation completes,
the tape drive is rebooted and reconfigured. This takes about 60
seconds. Wait 60 seconds before performing further drive operations.
You may perform a tape drive reset from either the operator panel or
the Web client. If you use the Web client, you must enter Diagnostics,
which logs out all users of the same or lower privilege level (see
Performing Library Diagnostics on page 330).

Operator Panel
1 Select Actions > Tape Drive > Reset.
2 If more than one tape drive is installed in the library, select the tape
drive you want to reset and press Reset, or select ALL.
3 Once the operation completes, the operator panel displays a
message stating that the operation completed, and there will be
diagnostic tickets if it failed.
4 Press OK.
5 Check to see if the library generated diagnostic tickets.

Quantum Scalar i40 and Scalar i80 Users Guide 331


Chapter 11: Troubleshooting
Performing Library Diagnostics

Web Client
1 Enter Diagnostics (Tools > Diagnostics, then click OK to take
partitions offline and log out all other users of the same or lower
privileges).
2 Select Drives > Drive Tests > Drive Reset.
3 If the tape drives are assigned to more than one partition, select the
partition in which the tape drive(s) you want to reset are located.
Select Unassigned if the tape drive(s) you want to reset are not
assigned to a partition. Click Next.
4 Select the tape drive(s) you want to reset.
5 Click Apply.
6 The test runs. When complete, a success or failure message
displays.

Robotics Get/Put Test The Get/Put Test requires the robot to remove one tape cartridge from
the top I/E station slot, and then put the tape cartridge back into the
same slot. To run this test, you must insert a tape into the librarys top
(uppermost) I/E station slot.
You can only perform this test from the Web client, by entering
Diagnostics (see Performing Library Diagnostics on page 330).

Web Client
1 Install a scratch tape in the top I/E station slot.
2 If manual cartridge assignment is enabled, assign the scratch tape
to the System partition.
3 Enter Diagnostics (Tools > Diagnostics, then click OK to take
partitions offline and log out all other users of the same or lower
privileges).
4 Select Robotics > Robotics Get/Put Test.
5 Click Apply.
6 The test runs. When complete, a success or failure message
displays.

332 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 11: Troubleshooting
Resetting Factory Defaults

Resetting Factory Defaults


Resetting factory defaults restores the librarys default configuration
(see Default Configuration on page 40).

Resetting factory defaults clears:


Most of the librarys configurable items, such as partitions, user
accounts, import/export (I/E) station slots, cleaning slots.
All diagnostic tickets and log information.
Any tape drive firmware images uploaded manually.

Resetting factory defaults does NOT clear:


Date and time, network configuration, or license key settings, nor does
it change the library firmware version.

You may want to reset factory defaults if you are completely reinstalling
or reconfiguring the library.
If you downgrade your librarys firmware version to an earlier released
version, library configuration settings will be reset to the factory
defaults for the newly installed firmware.
If you upgrade firmware, your library configuration settings remain as
you have set them.

Web Client
On the Web client, this feature is only available to service users using the
service login and password.

Operator Panel
On the operator panel, if logins are disabled (default), this operation is
available to all users. If logins are enabled, this operation is only
available to service users using the service login and password.
1 Select Tools > Reset Factory Defaults.
A message displays stating that configuration data will be cleared
and library rebooted.
2 Press Yes to continue.

Quantum Scalar i40 and Scalar i80 Users Guide 333


Chapter 11: Troubleshooting
Resetting Factory Defaults

334 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 12
Working With Cartridges
and Barcodes

This chapter describes how to work with cartridges and barcodes. When
working with tape cartridges, certain considerations should be taken
into account. For example, all tape cartridges in the library must have a
barcode label. In addition, when loading your library, you should be
aware of whether or not your cartridges are write-protected.
This section discusses these types of items in general terms. See
Supported Media on page 347 for information on what type of tape
cartridges are supported for each drive type.
This chapter covers:
Handling Tape Cartridges Properly
Write-Protecting Tape Cartridges
Supported Barcode Formats
Barcode Label Requirements
Installing Barcode Labels

Quantum Scalar i40 and Scalar i80 Users Guide 335


Chapter 12: Working With Cartridges and Barcodes
Handling Tape Cartridges Properly

Handling Tape Cartridges Properly


To ensure the longest possible life for your cartridges, follow these
guidelines:
Select a visible location to post procedures that describe proper
media handling.
Ensure that anyone who handles cartridges has been properly
trained on all procedures.
Do not drop or strike cartridges. Excessive shock could damage the
internal contents of cartridges or the casings themselves, rendering
the cartridges unusable.
Do not expose cartridges to direct sunlight or sources of heat,
including portable heaters and heating ducts.
Store cartridges in a location that is as free from dust as possible.
Dust can damage or degrade performance of tape media.
Store cartridges in a vertical orientation, not horizontally. Vertical
orientation is particularly important for long-term or archival
storage.
If cartridges must be stacked horizontally for moving and handling,
do not stack cartridges more than five high.
The operating temperature range for Linear Tape Open (LTO)
cartridges is 50F to 113F (10C to 45C). The operating relative
humidity range is 10% to 80% (non-condensing).
If cartridges have been exposed to temperatures outside the range
specified above, stabilize the cartridges at normal operating room
temperature for the same amount of time they were exposed to
extreme temperatures or 24 hours, whichever is less. Temperatures
above 125F (52C) can cause permanent damage.
Do not place cartridges near sources of electromagnetic energy or
strong magnetic fields, such as computer monitors, electric motors,
speakers, or x-ray equipment. Exposure to electromagnetic energy
or magnetic fields can destroy data and the embedded servo code
written on the media by the cartridge manufacturer, rendering the
cartridges unusable.
Place barcode labels only in the designated slots on the cartridges.

336 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 12: Working With Cartridges and Barcodes
Write-Protecting Tape Cartridges

If you ship cartridges, ship them in their original packaging or


something stronger.
Do not insert damaged cartridges into tape drives.
Do not touch the tape or tape leader.

Caution: Do not degauss cartridges that you intend to reuse.

Write-Protecting Tape Cartridges


All tape cartridges have a write-protect (write-inhibit) switch to prevent
accidental erasure or overwriting of data. Before loading a tape
cartridge into the library, make sure that the write-protect switch is
positioned correctly (either on or off).
Slide the red or orange write-protect switch to the right so that the
padlock shows in the closed position. The switch is located on the left
side of the cartridge front.

Barcode Label Requirements


Cartridges must have an external barcode label that is machine
readable. Quantum-supplied barcode labels provide the best results.
Barcode labels from other sources can be used, but they must meet the
following requirements:
ANSI MH10.8M-1983 Standard.
Type font: Code 39 (3 of 9).
Characters: only uppercase letters A to Z and/or numeric values
0 to 9.

Quantum Scalar i40 and Scalar i80 Users Guide 337


Chapter 12: Working With Cartridges and Barcodes
Supported Barcode Formats

Number of digits: 5 to 15 (default for LTO is 6 + 2).

Note: A maximum of 12 characters is recommended. A barcode


label with more than 12 characters may not be printable
according to the Code 39 label specifications for the tape
cartridge area to which the label is attached. The effective
tape cartridge barcode label length, including any media
ID, may be limited to a maximum of 12 characters.

Background reflection: greater than 25 percent.


Print contrast: greater than 75 percent.
Ratio: greater than 2.2.
Module: minimum .254 mm (10 mil).
Print tolerance: 57 mm.
Length of the rest zones: 5.25 mm 0.25 mm.
No black marks should be present in the intermediate spaces or rest
zones.
No white areas should be present on the bars.

Supported Barcode Formats


Quantum supplies industry standard LTO barcode labels with a length of
6 + 2 corresponding to the Standard Six and Plus Six formats listed
below. For advanced uses, your Quantum library supports label lengths
of up to 15 characters allowing you to create custom labels. Refer to
Barcode Label Requirements on page 337 for label details.
The library supports the following tape cartridge barcode formats.
Standard Six Six character barcode number with or without a
one or two-character media ID; for example, XXXXXX
orXXXXXXL4. Only the six character barcode is reported to the
host.
Plus Six Six character barcode number followed by a media ID;
for example, XXXXXXL3. Six character barcode and media ID are
reported to the host.

338 Quantum Scalar i40 and Scalar i80 Users Guide


Chapter 12: Working With Cartridges and Barcodes
Installing Barcode Labels

Extended Five to 15 characters total, including a barcode


number and optional media ID. All characters are reported to the
host, regardless of having a media ID or not. If a media ID is
included, the label must have a five to 13 character barcode
followed by a media ID; for example, XXXXXL2 or
XXXXXXXXXXXXXL2. If a media ID is not included, the label must
have a five to 15 character barcode; for example, XXXXX or
XXXXXXXXXXXXXXX.
Media ID Last Five to 13 character barcode number followed by
media ID; for example, XXXXXXXXXXXXXL4. The media ID is
reported to the host last.
Media ID First Five to 13 character barcode number followed by
a two-character media ID, for example; XXXXXXXXXXXXXL4. The
media ID is reported to the host first, as in L4XXXXXXXXXXXXX.
Standard (default) Five to 15 characters total, including a
barcode number and optional media ID. The media ID is not
reported to the host. If a media ID is included, the label must have a
five to 13 character barcode followed by a media ID; for example,
XXXXXL3 or XXXXXXXXXXXXXL3. If a media ID is not included,
the label must have a five to 15 character barcode; for example,
XXXXX or XXXXXXXXXXXXXXX.

Installing Barcode Labels


Each cartridge in the library must have an external label that is machine
readable to identify the barcode. Most manufacturers offer cartridges
with the labels already applied or with the labels included that you can
attach.
All barcode labels must be applied to the front of a cartridge. Peel off
the label and place it on the cartridge. The label must be placed entirely
within the recessed area on the cartridge. Verify that the label is
oriented so that the numbers appear above the barcode (see Figure 81
on page 340).
Place the barcode label as level as possible in the provided space for the
label. If the label is not placed horizontally level, barcode label scan/read
operations may encounter difficulties reading the label.

Quantum Scalar i40 and Scalar i80 Users Guide 339


Chapter 12: Working With Cartridges and Barcodes
Installing Barcode Labels

The cartridge cannot have any stickers or labels attached to the top or
bottom because if the labels come loose, they can get caught in the
tape drives or become unreadable by the scanner.

Caution: Do not place a barcode label or any labels on the top or


bottom of a cartridge. Doing so can cause the tape
cartridge and tape drive operations to fail.

Figure 81 Barcode Label


Orientation

340 Quantum Scalar i40 and Scalar i80 Users Guide


Appendix A
Specifications

Physical Specifications

Table 7 Base Library

Scalar i40 Scalar i80

Height 5.2 in. (132 mm) 10.4 in. (264 mm)

Width (excluding rack ears) 17.5 in. (445 mm) 17.5 (445 mm)

Depth (from library front bezel to back 31.2 in. (793 mm) 31.2 in. (793 mm)
of library; excluding drive sleds)*

Weight (one power supply, no tape 34.9 lbs. (15.8kg) 52.4 lbs. (23.8 kg)
drives, and no tape cartridges installed)

Weight (one power supply, two tape With 2 half-height SAS tape With 2 full-height SAS tape
drives, and no tape cartridges installed) drives: 44.2 lbs. (20 kg) drives: 65.7 lbs. (29.8 kg)
* Depths listed above exclude drive sleds. Drive sleds will add up to 50 mm to the overall length of the library
depending on tape drive type (half-height, full-height, Fibre Channel, SAS). Additionally, when planning space
requirements, take into account installed cables (particularly fibre-optic cable radius on Fibre Channel tape drives).

Quantum Scalar i40 and Scalar i80 Users Guide 341


Appendix A: Specifications
Capacity

Table 8 Library Installed in a


Desktop Kit

Scalar i40 Scalar i80

Height (with desktop 5.3 in. (135.6 mm) 10.6 in. (268.8 mm)
feet installed)

Width 18.9 in. (480 mm) 18.9 in. (480 mm)

Depth (from library front 31.2 in. (793 mm) 31.2 in. (793 mm)
bezel to back of library;
excludes drive sleds)*
* Depths listed above exclude drive sleds. Drive sleds will add up to 50 mm to the overall length of
the library depending on tape drive type (half-height, full-height, Fibre Channel, SAS). Additionally,
when planning space requirements, take into account installed cables (particularly fibre-optic cable
radius on Fibre Channel tape drives).

Capacity

Scalar i40 Scalar i80

Form Factor 3U 6U

Maximum number of 1 full-height or 2 half- 3 full-height or 5 half-


tape drives height tape drives height tape drives

Number of magazines 2 magazines (20 slots 4 magazines (20 slots


each each)

Number of cartridge Base unit: 25 Base unit: 50


slots Fully licensed: 40 Fully licensed: 80

Maximum native 25 slots: 20 TB 50 slots: 40 TB


capacity 40 slots: 32 TB 80 slots: 64 TB

Number of I/E station 0 or 5 0, 5, or 10


slots

342 Quantum Scalar i40 and Scalar i80 Users Guide


Appendix A: Specifications
Environmental Specifications

Environmental Specifications
The environmental specifications of the library are listed below.

Note: Temperature ranges apply to product inlet temperatures, not


necessarily to ambient room temperatures. Airflow restrictions
or other heat-generating equipment within the rack enclosure
may cause a rise over ambient room temperatures.

Operating Non-Operating Shipping and Storage

Altitude 500 to 10,000 ft 500 to 10,000 ft 500 to 10,000 ft


(152 to 3,048 m) (152 to 3,048 m) (152 to 3,048 m)

Temperature 50 to 95 F 50 to 113 F 40 to 140 F


(10 to 35 C) (10 to 45 C) (40 to 60 C)

Relative Humidity 20 to 80%, 10 to 90%, 0 to 95%,


non-condensing non-condensing non-condensing

Air Clearance Requirements


There must be at least 4 in. (10 cm) of open space in front of and behind
the library for proper air flow

Quantum Scalar i40 and Scalar i80 Users Guide 343


Appendix A: Specifications
Library Power Specifications

Library Power Specifications

Scalar i40 Scalar i80

Line voltage 100 240 VAC 100 240 VAC*

Line frequency 50 60 Hz 50 60 Hz*

Rated AC Input Current 100 Volt 2.8 Amps 100 Volt 5.0 Amps
240 Volt 1.4 Amps 240 Volt 2.5 Amps

Typical Power Consump- 100 watts 200 watts


tion
* A Scalar i80 library with dual power supplies will have these requirement on both AC inputs to the library but
will load share the current draw equally between each supply and from each AC connection.

344 Quantum Scalar i40 and Scalar i80 Users Guide


Appendix A: Specifications
Power Consumption and Heat Output

Power Consumption and Heat Output


Typical library power consumption (watts/hour) and heat output (BTU/
hour) are listed below. The values listed below are average (not peak or
maximum) values.

Typical Power Typical Heat


Consumption Output (BTU/
Component (Watts/Hour) Hour)

Scalar i40 library minimum configuration: 18 61


no tape drives installed; random robot movement

Scalar i40 library maximum configuration: 70 239


two (2) tape drives*, writing

Scalar i80 library minimum configuration: 18 61


no tape drives installed; one power supply, random
robot movement

Scalar i80 library maximum configuration: 159 544


five (5) tape drives*, writing, two power supplies

HP LTO-4 tape drive*, writing, one power supply, 24 82


no robot movement

HP LTO-5 tape drive*, writing, one power supply, 27 92


no robot movement

Second power supply, Scalar i80 7 24


* The difference in power consumption and heat output between full-height and half height tape drives, and
between Fibre Channel and SAS tape drives, is negligible.

Quantum Scalar i40 and Scalar i80 Users Guide 345


Appendix A: Specifications
Communication Interfaces

Communication Interfaces

Library Control Logical Unit Number (LUN)

Connectivity Native drive interface (FC, SAS

Library Management Operator panel


Web client
SNMP protocol
SMI-S protocol

Supported Tape Drives

Media
Vendor Generation Interface Type Speed Connector

HP LTO-4 Fibre Channel 4 Gb/s LC

SAS 3 Gb/s SFF-8088

HP LTO-5 Fibre Channel 8 Gb/s LC

SAS 6 Gb/s SFF-8088

346 Quantum Scalar i40 and Scalar i80 Users Guide


Appendix A: Specifications
Supported Media

Supported Media

Cartridge Type Access

LTO-5 Read/write in LTO-5 tape drives;


supports WORM functionality

LTO-4 Read/write in LTO-4 and LTO-5 tape drives;


supports WORM functionality

LTO-3 Read/write in LTO-4 tape drives;


read-only in LTO-5 tape drives;
supports WORM functionality

LTO-2 Read-only in LTO-4 tape drives

Supported Internet Browsers


The Internet browser software is not supplied with the Scalar i40 and
Scalar i80 systems; you must obtain and install it independently. The
Scalar i40 and Scalar i80 systems support the following Internet
browsers:

Note: For correct operation of the software, disable any pop-up


blockers.

Microsoft Windows
Internet Explorer (IE) 6.0, 7.0, and 8.0
Mozilla Firefox 1.0.6 or later

Linux
Firefox 1.0.6 or later

Quantum Scalar i40 and Scalar i80 Users Guide 347


Appendix A: Specifications
Supported Operating Systems

Solaris
Firefox 1.0.6 or later

Supported Operating Systems


The Scalar i40 and Scalar i80 systems support the following operating
systems:
Microsoft Windows Enterprise Server
Sun Solaris
HP-UX
IBM AIX
Red Hat Enterprise Linux

348 Quantum Scalar i40 and Scalar i80 Users Guide


Appendix B
Tape Alert Flag Descriptions

Tape Alert is an open industry standard that flags errors and provides
possible solutions for storage devices and their media. This section
provides information about Tape Alert flags issued by tape drives,
including the identifying number, severity, recommended message, and
probable cause. Table 9 explains the severity codes, and Table 10 lists all
the existing Tape Alert flags and their descriptions.
Support for specific Tape Alert flags may vary based on tape drive type
and firmware revision. Not all tape drives support every Tape Alert.
Consult your tape drive SCSI manual for more information.
For more information on Tape Alert, see http://www.t10.org/index.html
for INCITS SCSI Stream Commands - 3 (SSC-3).

Table 9 Tape Alert Flag Severity


Codes
I Informational.

W Warning The system may not be operating optimally.


Continued operation without corrective action may cause a
failure or raise critical Tape Alert flags.

C Critical Either a failure has already occurred or a failure is


imminent. Corrective action is required.

Quantum Scalar i40 and Scalar i80 Users Guide 349


Appendix B: Tape Alert Flag Descriptions

Table 10 Tape Drive Tape Alert


Flag Descriptions

Recommended Application Client


No. Flag Severity Message Probable Cause

1 Read warning W The tape drive is having problems The drive is having
reading data. No data has been lost, severe trouble
but there has been a reduction in the reading.
performance of the tape.

2 Write warning W The tape drive is having problems The drive is having
writing data. No data has been lost, but severe trouble
there has been a reduction in the writing.
capacity of the tape.

3 Hard error W The operation has stopped because an The drive had a hard
error has occurred while reading or read or write error.
writing data which the drive cannot
correct.

4 Media C Your data is at risk: Media can no longer


1 Copy any data you require from this be written/read, or
tape. performance is
severely degraded.
2 Do not use this tape again.
3 Restart the operation with a different
tape.

5 Read failure C The tape is damaged or the drive is The drive can no
faulty. Call the tape drive supplier help longer read data
line. from the tape.

6 Write failure C The tape is from a faulty batch or the The drive can no
tape drive is faulty: longer write data to
1 Use a good tape to test the drive. the tape.
2 If the problem persists, call the tape
drive supplier help line.

350 Quantum Scalar i40 and Scalar i80 Users Guide


Appendix B: Tape Alert Flag Descriptions

Recommended Application Client


No. Flag Severity Message Probable Cause

7 Media life W The tape cartridge has reached the end The media has
of its calculated useful life: exceeded its
1 Copy any data you need to another specified life.
tape.
2 Discard the old tape.

8 Not data grade W The tape cartridge is not data-grade. The drive has not
Any data you write to the tape is at risk. been able to read the
Replace the cartridge with a data-grade MRS* stripes.
tape.

9 Write protect C You are trying to write to a write- Write command is


protected cartridge. Remove the write- attempted to a
protection or use another tape. write- protected
tape.

10 Media removal I You cannot eject the cartridge because Manual or software
prevented the tape drive is in use. Wait until the unload attempted
operation is complete before ejecting when prevent media
the cartridge. removal on.

11 Cleaning media I The tape in the drive is a cleaning Cleaning cartridge


cartridge. loaded into drive.

12 Unsupported I You have tried to load a cartridge of a Attempted load of


format type which is not supported by this unsupported tape
drive. format.

13 Recoverable C The operation has failed because the Tape snapped/cut or


mechanical tape in the drive has experienced a other cartridge
cartridge mechanical failure: mechanical failure in
failure 1 Discard the old tape. the drive where
medium can be
2 Restart the operation with a different
demounted.
tape.

Quantum Scalar i40 and Scalar i80 Users Guide 351


Appendix B: Tape Alert Flag Descriptions

Recommended Application Client


No. Flag Severity Message Probable Cause

14 Unrecoverable C The operation has failed because the Tape snapped/cut or


mechanical tape in the drive has experienced a other cartridge
cartridge mechanical failure: mechanical failure in
failure 1 Do not attempt to extract the tape the drive where
cartridge. medium cannot be
demounted.
2 Call the tape drive supplier help line.

15 Memory chip in W The memory in the tape cartridge has Memory chip failed
cartridge failed, which reduces performance. Do in cartridge.
failure not use the cartridge for further write
operations.

16 Forced eject C The operation has failed because the Manual or forced
tape cartridge was manually eject while drive
demounted while the tape drive was actively writing or
actively writing or reading. reading.

17 Read-only W You have loaded a cartridge of a type Media loaded that is


format that is read-only in this drive. The read-only format.
cartridge will appear as write protected.

18 Tape directory W The directory on the tape cartridge has Tape drive powered
corrupted on been corrupted. File search down with tape
load performance will be degraded. The tape loaded, or
directory can be rebuilt by reading all permanent error
the data on the cartridge. prevented the tape
directory being
updated.

19 Nearing media I The tape cartridge is nearing the end of Media may have
life its calculated life. It is recommended exceeded its
that you: specified number of
1 Use another tape cartridge for your passes.
next backup.
2 Store this tape cartridge in a safe
place in case you need to restore data
from it.

352 Quantum Scalar i40 and Scalar i80 Users Guide


Appendix B: Tape Alert Flag Descriptions

Recommended Application Client


No. Flag Severity Message Probable Cause

20 Cleaning C The tape drive needs cleaning: The drive thinks it


required 1 If the operation has stopped, eject has a head clog or
the tape and clean the drive. needs cleaning.
2 If the operation has not stopped,
wait for it to finish and then clean
the drive.
Check the tape drive users manual for
device-specific cleaning instructions.

21 Cleaning W The tape drive is due for routine The drive is ready for
requested cleaning: a periodic cleaning.
1 Wait for the current operation to
finish.
2 Then use a cleaning cartridge.
Check the tape drive users manual for
device-specific cleaning instructions.

22 Expired C The last cleaning cartridge used in the The cleaning


cleaning media tape drive has worn out: cartridge has
1 Discard the worn-out cleaning expired.
cartridge.
2 Wait for the current operation to
finish.
3 Then use a new cleaning cartridge.

23 Invalid cleaning C The last cleaning cartridge used in the Invalid cleaning
tape tape drive was an invalid type: cartridge type used.
1 Do not use this cleaning cartridge in
this drive.
2 Wait for the current operation to
finish.
3 Then use a valid cleaning cartridge.

Quantum Scalar i40 and Scalar i80 Users Guide 353


Appendix B: Tape Alert Flag Descriptions

Recommended Application Client


No. Flag Severity Message Probable Cause

24 Retension W The tape drive has requested a The drive is having


requested retension operation. severe trouble
reading or writing,
which will be
resolved by a
retension cycle.

25 Multi-port W A redundant interface port on the tape Failure of one


interface error drive has failed. interface port in a
on a primary dual-port
port configuration (for
example, Fibre
Channel).

26 Cooling fan W A tape drive cooling fan has failed. Fan failure inside
failure tape drive
mechanism or tape
drive enclosure.

27 Power supply W A redundant power supply has failed Redundant power


failure inside the tape drive enclosure. Check supply unit failure
the enclosure users manual for inside the tape drive
instructions on replacing the failed enclosure or rack
power supply. subsystem.

28 Power W The tape drive power consumption is Power consumption


consumption outside the specified range. of the tape drive is
outside specified
range.

29 Drive W Preventive maintenance of the tape The drive requires


preventive drive is required. Check the tape drive preventative
maintenance users manual for device-specific maintenance (not
required preventive maintenance tasks or call the cleaning).
tape drive supplier help line.

30 Hardware A C The tape drive has a hardware fault: The drive has a
1 Eject the tape or magazine. hardware fault that
requires reset to
2 Reset the drive.
recover.
3 Restart the operation.

354 Quantum Scalar i40 and Scalar i80 Users Guide


Appendix B: Tape Alert Flag Descriptions

Recommended Application Client


No. Flag Severity Message Probable Cause

31 Hardware B C The tape drive has a hardware fault: The drive has a
1 Turn the tape drive off and then on hardware fault that
again. is not read/write
related or requires a
2 Restart the operation.
power cycle to
3 If the problem persists, call the tape recover.
drive supplier help line.

32 Primary W The tape drive has a problem with the The drive has
interface host interface: identified an
1 Check the cables and cable interface fault.
connections.
2 Restart the operation.

33 Eject media C The operation has failed: Error recovery action.


1 Eject the tape or magazine.
2 Insert the tape or magazine again.
3 Restart the operation.

34 Microcode W The microcode update has failed Microcode update


update fail because you have tried to use the failed.
incorrect microcode for this tape drive.
Obtain the correct microcode and try
again.

35 Drive humidity W Environmental conditions inside the Drive humidity limits


tape drive are outside the specified exceeded.
humidity range.

36 Drive W Environmental conditions inside the Cooling problem.


temperature tape drive are outside the specified
temperature range.

37 Drive voltage W The voltage supply to the tape drive is Drive voltage limits
outside the specified range. exceeded.

38 Predictive C A hardware failure of the tape drive is Predictive failure of


failure predicted. Call the tape drive supplier drive hardware.
help line.

Quantum Scalar i40 and Scalar i80 Users Guide 355


Appendix B: Tape Alert Flag Descriptions

Recommended Application Client


No. Flag Severity Message Probable Cause

39 Diagnostics W The tape drive may have a hardware The drive may have a
required fault. Run extended diagnostics to hardware fault that
verify and diagnose the problem. Check may be identified by
the tape drive users manual for device- extended diagnostics
specific instructions on running (i.e., SEND
extended diagnostic tests. DIAGNOSTIC
command).

40 Obsolete

46

47 Reserved

49

50 Lost statistics W Media statistics have been lost at some Drive or library
time in the past. powered down with
tape loaded.

51 Tape directory W The tape directory on the tape cartridge Error prevented the
invalid at just unloaded has been corrupted. File tape directory being
unload search performance will be degraded. updated on unload.
The tape directory can be rebuilt by
reading all the data.

52 Tape system C The tape just unloaded could not write Write errors while
area write its system area successfully: writing the system
failure 1 Copy data to another tape cartridge. area on unload.
2 Discard the old cartridge.

53 Tape system C The tape system area could not be read Read errors while
area read successfully at load time: reading the system
failure 1 Copy data to another tape cartridge. area on load.

356 Quantum Scalar i40 and Scalar i80 Users Guide


Appendix B: Tape Alert Flag Descriptions

Recommended Application Client


No. Flag Severity Message Probable Cause

54 No start of data C The start of data could not be found on Tape damaged, bulk
the tape: erased, or incorrect
1 Check that you are using the correct format.
format tape.
2 Discard the tape or return the tape to
your supplier.

55 Loading or C The operation has failed because the The drive is unable to
threading media cannot be loaded and threaded: load the media and
failure 1 Remove the cartridge, inspect it as thread the tape.
specified in the product manual, and
retry the operation.
2 If the problem persists, call the tape
drive supplier help line.

56 Unrecoverable C The operation has failed because the The drive is unable to
unload failure medium cannot be unloaded: unload the medium.
1 Do not attempt to extract the tape
cartridge.
2 Call the tape driver supplier help line.

57 Automation C The tape drive has a problem with the The drive has
interface failure automation interface: identified an
1 Check the power to the automation interface fault.
system.
2 Check the cables and cable
connections.
3 Call the supplier help line if problem
persists.

58 Microcode W The tape drive has reset itself due to a Microcode bug.
failure detected microcode fault. If problem
persists, call the supplier help line.

59 WORM W The tape drive has detected an Someone has


medium inconsistency during the WORM tampered with the
integrity check medium integrity checks. Someone may WORM medium.
failed have tampered with the cartridge.

Quantum Scalar i40 and Scalar i80 Users Guide 357


Appendix B: Tape Alert Flag Descriptions

Recommended Application Client


No. Flag Severity Message Probable Cause

60 WORM W An attempt had been made to The application


medium overwrite user data on a WORM software does not
overwrite medium: recognize the
attempted 1 If a WORM medium was used medium as WORM.
inadvertently, replace it with a
normal data medium.
2 If a WORM medium was used
intentionally:
a) Check that the software
application is compatible with the
WORM medium format you are
using.
b) Check that the medium is bar-
coded correctly for WORM.

61 Reserved

64
* Media Recognition System (MRS) is a method where pre-defined stripes are placed at the beginning of the media
to identify the media. The MRS stripes are read to determine if the media is of data-grade. Data-grade media
should be used in SCSI streaming devices since it is of the required quality and consistency to be used to store data
(i.e., audio/video grade media should not be used).

358 Quantum Scalar i40 and Scalar i80 Users Guide


Appendix C
Disposal of Electrical and
Electronic Equipment

This symbol on the product or on its packaging


indicates that this product should not be disposed of
with your other waste. Instead, it should be handed
over to a designated collection point for the recycling
of electrical and electronic equipment. The separate
collection and recycling of your waste equipment at
the time of disposal will help to conserve natural
resources and ensure that it is recycled in a manner
that protects human health and the environment. For more information
about where you can drop off your waste equipment for recycling,
please visit our website at: http://qcare.quantum.com or contact your
local government authority, your household waste disposal service or
the business from which you purchased the product.

Quantum Scalar i40 and Scalar i80 Users Guide 359


Appendix C: Disposal of Electrical and Electronic Equipment

360 Quantum Scalar i40 and Scalar i80 Users Guide


Glossary

Numerals 1U, 2U, 3U, etc. Racks manufactured for mounting computer
hardware often define vertical space as units. The
components that are mounted in the racks are defined by how
many units of rack space they require. For example, the height
of a unit in a rack is 1.75 inches. If a component is 5.25 inches in
thickness, the component is said to be a 3U component.

A Arbitrated loop A Fibre Channel configuration that attaches multiple


communicating ports in a loop. Two or more ports can
interconnect, but only two ports can communicate
simultaneously.
Arbitration The submission of a request to gain access to an
arbitrated loop by a device, so that it can transmit data in the
loop.

B Barcode A printed array of varied rectangular bars and spaces that can
be scanned and read for object identification.
Bus A transmission channel through which electrical signals are
carried from one device to another device.

Quantum Scalar i40 and Scalar i80 Users Guide 361


Glossary

C Cartridge A container that is a protective housing for storage media,


such as cartridges for tapes or optical disks.
Cleaning tape / cleaning cartridge A tape used to clean recording
heads and reading heads on a tape drive.
Cleaning slot The physical home where a cleaning tape or cartridge
resides.
COD (Capacity on Demand) A library feature that allows users to
have a large physical library, but only be licensed to use a subset
of its total capacity. Users pay only for what they are currently
using. License upgrades enable more capacity without causing a
system interruption.
Connectivity The method by which hardware devices or software
communicate with other hardware or software.
Control path The connection between a partition and host
application. The control path connection is made through a
designated tape drive. Only one tape drive can be selected as
the control path per partition.
Controller The PCB or system that translates computer data and
commands into a form suitable for use by the storage disks.
CRU (Customer Replaceable Unit) The smallest hardware component
that can be replaced at a customer installation by a customer.

D Default A value or setting that is selected by the hardware or software


unless specified otherwise by the user.
DHCP (Dynamic Host Configuration Protocol) A protocol for
assigning dynamic IP addresses to devices on a network. DHCP
supports a mix of static and dynamic IP addresses.
Diagnostic ticket A ticket that alerts service personnel and customers
of an issue with the library. Diagnostic tickets identify which
library components are most likely causing the issue. When
possible, a diagnostic ticket provides instructions for resolving
the issue.
Directory A file that contains a list of other files. Directory is short for
directory file.

362 Quantum Scalar i40 and Scalar i80 Users Guide


Glossary

Drivers Software programs that enable a computer to communicate


with hard drives, CD ROM drives, printers, and other
peripherals. Drivers are stored on a hard disk and loaded into
memory at boot up.

E Element ID - Logical An address used by a library to locate and track


library component. The address is specified in programming
logic rather than on the physical location of a component
within a library. When a logical library is used, the logical
element ID masks the physical element ID.
Element ID - Physical An address used by a library to locate and track
library component. The address is based on the physical location
of a component within a library. Applications expect to see
resources at specific IDs.
Ethernet A type of local area network designed to transport data at
rates up to 100 million bits per second. Other software, such as
TCP/IP runs on top of Ethernet to provide high-level networking
services to applications.
Event A condition that matches a numbered, predefined set of
circumstances.
Event log A list of all predefined events logged by library and software
management tools.

F FC (Fibre Channel) A high speed data transfer architecture. Using


optical fibre to connect devices, Fibre Channel communications
are serial communications that occur at full duplex and achieve
data transfer rates of 200 MBps.
FC-AL (Fibre Channel Arbitrated Loop) A form of Fibre Channel
network in which up to 126 nodes are connected in a loop
topology. See also Arbitrated loop.
FC-AL Device A device that employs Fibre Channel-Arbitrated Loop
and consists of one or more NL_Ports.
Fiber A thin filament of glass. An optical waveguide consisting of a
core and a cladding which is capable of carrying information in
the form of light. Fiber is also a general term used to cover all

Quantum Scalar i40 and Scalar i80 Users Guide 363


Glossary

physical media types supported by Fibre Channel, such as


optical fiber, twisted pair, and coaxial cable.
Firewall A set of security tools designed to separate an internal
network from the public Internet in order to keep unauthorized
users out of a restricted network. Firewalls are the primary line
of security defense for businesses.
FL_Port Fabric Loop Port. An F_Port that is capable of supporting an
attached Fibre Channel Arbitrated Loop. An FL_Port on a loop
will have the AL_PA hex00 giving the fabric the highest priority
access to the loop. N_Ports or NL_Ports can attach to it in an
Arbitrated Loop topology and are capable of communicating
with FC-AL protocol.
FRU (Field Replaceable Unit) The smallest hardware component that
can be replaced at a customer installation by a certified field
service representative.

G GUI (Graphical User Interface) A computer environment that


provides a visual view of a system by incorporating windows,
icons, menus, and a pointing device. Also referred to as a
Windows, Icons, Mouse, and Pointers (WIMP) interface.

H HDD (High Density Drive) A drive that contains increased storage


capacity of bits and/or tracks per square inch.
Home position Accessor axes positioned at 0 vertical and 0 horizontal,
that serve as the point of reference for the position of other
library components. Home position is used as a basis for
calibration.
Host In general, a host is a computer or program that contains data
and provides services to other computers or devices. In Fibre
Channel terms, a host is a computer that initiates contact with
storage devices.
Hot swappable The ability to replace a defective component while the
system continues to function normally.
HTTP (Hypertext Transfer Protocol) The communication rules by
which a Web browser (client) and a server delivering Web pages
exchange information.

364 Quantum Scalar i40 and Scalar i80 Users Guide


Glossary

I I/E Import/Export. The movement of data or hardware in and out of


processing and storage systems.
I/E slot A bin that contains a single piece of media in the station.
I/E station A door on the front of the library that contains tape
magazines, into which cartridges to be imported are placed
manually or cartridges to be exported are placed by the picker.
Interoperability The capability of two or more hardware devices or
two or more software routines to work together.
IP (Internet Protocol) A protocol that specifies the formats of packets
and addresses. Addresses are formulated as four groups of 2 or
3 digit numbers separated by periods, such as 255.255.255.255.

K Kernel The heart of the UNIX operating system. The kernel is the part
of the operating system that allocates resources and controls
processes. The design strategy has been to keep the kernel as
small as possible and to put the rest of the UNIX functionality
into separately compiled and executed programs.

L L_Port Loop Port. It only has the capability to communicate over FC-AL
hubs and through FL_Ports.
LED (Light Emitting Diode) The mode of data transmission for
multimode cables with short wave optical transceivers. Single-
mode cables, by comparison, use high powered, long wave
lasers.
Library A large-scale tape device with robotics that can house multiple
tape drives and a significant amount of tape cartridges.
Library Control Module See Control module.
License key An absolute value that can only increase a licensed
feature. For example, a license key can be applied to the library
to enable unlicensed slots.
Logical library See Partition.
Loop With this Fibre Channel option, the port operates with attached
loop-capable devices. If a point-to-point device is attached, the
appliance is not able to communicate with it.

Quantum Scalar i40 and Scalar i80 Users Guide 365


Glossary

Loop ID A unique 7-bit value from 0 to 126 that represents the 127
valid AL_PAs (physical addresses) on a loop.
LTO (Linear Tape Open) A family of magnetic tape media that are
open in the sense of not being owned by a single proprietor.
LTO comes in two formats, Accelis and Ultrium. Accelis is the
fast access implementation, while Ultrium is the high capacity
implementation.
LUN (Logical Unit Number) A unique identifier used on a SCSI bus to
distinguish between devices that share the same bus. A LUN can
be an end user, a file, or an application. In storage technology, a
single large storage device might be divided into smaller pieces,
either to make the vast storage space more manageable or
because the storage space is dedicated to different servers,
drives, or applications. When the storage space is divided into
smaller parts, each part is configured with its own SCSI unique
identifier, or LUN.

M Magazine A container for removable media storage used in tape


libraries.
Media A material that stores data, such as tapes in cartridges or
optical disks.
Media ID A barcode number attached to a specific piece of media.
Media type A format/size of media, for example, LTO.
Medium See Media.
Mixed media The ability of a library to simultaneously support
multiple types of storage media.

N N_Port Node Port. It only has the capability to communicate through


an F-Port. It is a port on a computer, disk drive, and so on,
through which the device does its Fibre Channel communication
as a direct fabric-attached port for use with the point-to-point
or fabric topology. It is identified by a world wide name.
NL_Port Node Loop Port. It has the capability to communicate over
both FC-AL hubs and through F_Ports.

366 Quantum Scalar i40 and Scalar i80 Users Guide


Glossary

O Online A status for a component that indicates it is active and


available for use.
OS (Operating System) A control program for a computer that
allocates computer resources, schedules tasks, and provides the
user with a way to access the resources.

P Partition An abstraction of an underlying physical library that may


present a different personality, capacity, or both to a host. It is a
representation of real physical elements, combined to create a
grouping that is different from the physical library. Also a logical
portion of the physical library that is viewed by the host as if it is
a complete library. Partitions present the appearance of
multiple, separate libraries for purposes of file management,
access by multiple users, or dedication to one or more host
application.
Pathname A list of directories separated by slashes (/) and ending with
the name of a directory or nondirectory file. A pathname is used
to trace a path through the file structure to locate or identify a
file.
Picker The robotic hand that handles cartridges.
Point to Point A Fibre Channel topology that consists of a dedicated
connection between two devices: a sending device and a
receiving device.

R Rack Mount An industry standard communication and computer


equipment rack cabinet.

S SAN (Storage Area Network) A dedicated network that connects


storage devices and servers in a pool, providing consolidated
storage and storage management. Storage interconnects
between many initiators and target devices. The SAN allows for
sharing resources (target devices) among multiple servers
(initiators).
SCSI (Small Computer System Interface) A set of standards for a
high-speed, parallel interface that connects processing devices

Quantum Scalar i40 and Scalar i80 Users Guide 367


Glossary

to peripheral devices, such as storage subsystems. The acronym


is pronounced scuzzy.
Server A powerful, centralized computer (or program) designed to
provide information to clients (smaller computers or programs)
upon request.
Setup wizard A tool for initially configuring the library. It appears the
first time the user starts the library. However, it can be used to
modify configurable items anytime after the initial
configuration.
Sled The hardware that houses tape drives in the library.
SMI-S (Storage Management Initiative Specification) An industry
standard SMI-S application programming interface (API)
developed by SNIA that facilitates the management of multi-
vendor devices in a storage area networks (SANs) environment.
Snapshot A rapid, point-in-time image of a volume created initially on
the same disk as the original by duplicating metadata rather
than copying the full data set. Snapshots are often used to
protect against data corruption (viruses, etc.) or to create test or
pre-production environments. Snapshots are also often used as
a first step for creating non-disruptive point-in-time backups,
and for copying datasets to a second disk to create a full
duplicate copy of the volume. Snapshots are created on disk,
and in the same format as the original data. Snapshots are also
referred to as point-in-time copies and as shadow copies.
SNMP (Simple Network Management Protocol) The protocol
governing network management and the monitoring of
network devices and their functions. Similar in function to SAM,
except SNMP governs LAN, whereas SAM governs SAN.
SSL (Secure Sockets Layer) A protocol that provides encrypted
communications on the Internet. SSL is layered beneath
application protocols such as HTTP, SMTP, Telnet, FTP, Gopher,
and NNTP and is layered above the connection protocol TCP/IP.
Storage device An appliance containing data that can be accessed,
added to, changed, or deleted by the user. The storage media
types include tapes and optical disks. A storage device can be a
single disk drive, or constitute thousands of tapes in a large
tape library.
Storage slot The physical home where a data cartridge resides.

368 Quantum Scalar i40 and Scalar i80 Users Guide


Glossary

Subsystem status A feature that provides predictive alerts, warning of


any loss of connectivity or device failure using local or remote
alerts. Subsystem status allows administrators to correct faults
before they affect backup or other data transfer operations.

T Tape drive A device that spins disks and tapes while it reads and writes
data in storage.
TCP/IP (Transmission Control Protocol/Internet Protocol) The
communications protocol used by the Internet. It runs on top of
Ethernet to provide high-level networking services to
applications.
Topology The logical and/or physical arrangement of stations on a
network.
Trap An SNMP alert that is sent when predefined conditions are met.
For example, an error trap tests for an error condition and
provides a recovery routine.

U
User ID An alphanumeric value that the password database associates
with a login name. Also, UID.
UTC (Coordinated Universal Time) The world-wide standard for time,
commonly considered to be the equivalent of Greenwich Mean
Time and Zulu time. For all of these time standards, zero (0)
hours is midnight in Greenwich England, which lies on the zero
longitudinal meridian. The sequence of the letters in the
acronym is a compromise between the English and French terms
(Temps Universel Coordonn).

W WORM (Write Once, Read Many) A common type of data storage


medium, in which data can be read and reread, but not altered,
after it has been recorded.
WWNN (World Wide Node Name) A unique number assigned by a
recognized naming authority. The world wide name is integral
to Fibre Channel operations.

Quantum Scalar i40 and Scalar i80 Users Guide 369


Glossary

WWPN (World Wide Port Name) The WWPN is a 64-bit, hard-coded


address for each port on an FC-connected device. It is used to
identify available SAN devices at end points.

X X-axis, X-position The horizontal position of the librarys robotic arm.

Y Y-axis, Y-position The vertical position of the librarys robotic arm.

370 Quantum Scalar i40 and Scalar i80 Users Guide


Index

browsers, supported 347 cleaning tape drives 163


A bulk loading cartridges 155 automatic 164
aborting an operation 27 manually 169
buttons
About Library 206 back, browser 28 COD, see Capacity on Demand 13

administrator privileges 81 navigation 3 community string 47


navigation/selection 26 configuration
advanced reporting 14, 223 operator panel 27 default 40
all slots report 215 power 3 record 212
authentication traps 46 report 210
authorization code 69 restoring 108
saving 107
AutoClean 164 C
contact information
autoleveling 304
cabling the library 227 customer 78
automatic EKM path diagnostics Quantum xxvi
canceling an operation 27
184
Capacity on Demand 13 control path 67
cartridges, see tape cartridges 336 copyright 224
certificates, see encryption customer contact information 78
B certificates
back button, browser 28 chassis, removing and replacing
barcode 258 D
label requirements 337 cleaning cartridges
labels, installing 339 exporting 167 data encryption keys
scanner 3 importing 165 depletion of 192
supported formats 55, 338 valid 164 exporting 196, 199
generating 181, 191, 195
bezel, library, replacing 253 cleaning log 217
at initial setup 192
browser back button 28 cleaning slots, configuring 61 manually 193

Quantum Scalar i40 and Scalar i80 Users Guide 371


Index

when 100% depleted 192 e-mail notifications


when 80% depleted 192 about 72 G
importing 196, 201 creating 73 gateway 43
date, setting 49 deleting 75
modifying 74 generating data encryption keys
daylight saving time, setting 51 181, 191, 195
send snapshot 77
default administrator account 80 get/put test 332
emergency power-off procedure
default configuration 40 144
default gateway 43 encryption certificates
default password 81, 136 exporting 196, 197 H
default user name 81, 136 importing 196, 198
encryption key management, see health status icons 26
defaults, resetting factory 333
EKM home page 30, 31
desktop kit
encryption keys, see data host name 41
installing library in 244
removing library from 252 encryption keys

DHCP 42 encryption, see EKM and SKM

diagnostic tickets ESD precautions 226 I


about 312 exiting an operation 27
log 218 I/E station
exporting
viewing, closing, and resolving opening 145
cleaning cartridges 167
312, 313 unlocking 145
data encryption keys 196, 199
diagnostics 330 encryption certificates 196, I/E station slots, configuring 63
EKM path 179, 182 197 I/E station, unlocking more than
resetting a tape drive 331 tape cartridges 158 one 146
robotics get/put 332 external management applications ICMP 104
disabling library managed 44 importing
encryption 194 cleaning cartridges 165
disposal information 359 data encryption keys 196, 201
DNS addresses 43 encryption certificates 196,
F 198
downgrading library firmware 108 tape cartridges 152
factory defaults, resetting 333
dust 17 tape cartridges, unassigned
fast scrolling 27 153
filler plate installation and verification test 325
power supply, removing and
E installing 269 Internet browsers, supported 347
tape drive, removing and internet control message protocol
EKM installing 269 104
about 175
firmware IP address
license 15
library, downgrading 108 configuring 42
path diagnostics 179
library, updating 299 IPv4 42
about 182
tape drive, autoleveling 304 IPv6 42
automatic 184
tape drive, updating 304 library 137
manual 183
front panel 2 IVT 325
e-mail account, library 76

372 Quantum Scalar i40 and Scalar i80 Users Guide


Index

loading tape drives 160 moving tape cartridges 156


K local user accounts moving the library 292
Kerberos 94 about 79
Kerberos service keytab file 96 creating 82
deleting 84
key, public 196 modifying 83 N
keys, see data encryption keys location coordinates navigation buttons 3
slot 5
network interface 103
tape drive 9
network prefix 43
L logged in users report 215
network settings
logging off 138
LDAP changing 40
automatically 138
accounts 88 configuring 40
configuring 90 logging on report 214, 222
server guidelines 89 first time 136
network time protocol 49
Kerberos enabled 138
LEDs 320 LDAP enabled 138 NTP 49
front panel 321 operator panel 137
power supply 324 simultaneous 136
power-on 3 Web client 137
system control board 322
logical serial number addressing 99
O
tape drive/sled 323
ticket indicator 3 logs online/offline
cleaning 217 library 145
library configuration
diagnostic tickets 218 partitions 59
record 212
SKM encryption key import tape drives 172
report 210
saving 107 warning log 202, 219 open source license agreement 223
SKM server 202 opening the I/E station 145
library managed encryption tape drive 220, 320
disabling 194 operator panel
library name 41 buttons 27
changing home screen view
library not ready messages 318
M 109
licensable features 69 description 2
license key certificate 69 magazines functions 24
description 4 layout 22
license keys
releasing 148 passwords 84
about 69
removing and replacing 271 power save 101
applying 71
test 327
chassis replacement and 69
obtaining 70 manual cartridge assignment 100
SCB replacement and 70 manual EKM path diagnostics 183
viewing 70
P
mask, subnet 43
licenses packaging the library 292
media barcode formats 55
encryption key management partitions
(EKM) 15 menu trees 33
about 51
report 223 MIB, SNMP 47 access 59
viewing 70 move test 329 automatic creation 53

Quantum Scalar i40 and Scalar i80 Users Guide 373


Index

deleting 57 releasing magazines 148 security settings 103


description 12 remote access, enabling/disabling service port 78
manual creation 54 105 session timeout 97
modifying 56
remote authentication 88 setup wizard 39
reports 221
taking online/offline 59 remote service login 105 sharing encrypted tapes 195
viewing 58 removing power 139, 144 shipping the library 292
passwords, operator panel reports shut down 139, 140
creating 84 about 206
disabling 87 SKM
advanced reporting 223
misplaced 88 about 175
all slots 215
modifying 87 configuring 176
date/time 223
resetting 88 encryption key import warning
library configuration 210
log 202, 219
passwords, Web client licenses 223
installing on servers 177
creating 82 logged in users 215
logs 202, 219
default 81, 136 network settings 214, 222
partition configuration 179
misplaced 137 operator panel 221
server configuration 177
modifying 83 partition 221
server log 202
system information 206
path diagnostics, EKM 179, 182 TLS certificates 179
tape drives 222
automatic 184 slots, location coordinates 5
manual 183 resetting factory defaults 333
SMI-S, enabling/disabling 101
popup blockers 28 resetting tape drive 331
SNMP
power button 3 restart 139, 142
authentication traps 46
power save 101 restoring the library configuration community string 47
108 configuring 44
power supply
description 8 restraint, robot 19 enabling/disabling 101
removing and installing 276 robot 3 MIB, downloading 47
get/put test 332 versions 46
power-off, emergency 144
releasing 19 specifications 341
power-on LED 3
restraint 19 SSH services, enabling/disabling
privilege levels 81 test 327 104
public key 196 running out of keys 192 SSL, enabling/disabling 106
subnet mask 43
subsystem status 32
R S system control board
rack description 8
saving the library configuration 107
installing library in 241 removing and replacing 279
Scalar Key Manager, see SKM
removing library from 243 system information report 206
scanner, barcode 3
rack mount kit, installing 229 system settings 98
SCB, see system control board 8
rail kit, see rack mount kit 229 system summary 31
scrolling, fast 27
random move test 329
secure socket layer, enabling/
registering the library 109
disabling 106

374 Quantum Scalar i40 and Scalar i80 Users Guide


Index

installing 179
T Quantum-supplied 188
Tape Alerts 349 user-supplied 189

tape cartridges traps 46


bulk loading 155 troubleshooting 311
exporting 158 turning off 139, 143
importing 152
map, creating 271
moving 156
proper handling 336 U
storing 336
unassigned 153 UDP 45
write protecting 337 unassigned tape cartridges,
tape drives importing 153
autoleveling 304 unload assist 98
cleaning, about 163 unloading tape drives 161
cleaning, automatically 164
unlocking the I/E station 145
cleaning, manual 169
description 9 unpacking the library 17
loading 160 updating library firmware 299
location coordinates 9 user name, default 81, 136
log 220
online/offline 172 user privileges 81
paramaters, configuring 65
removing and replacing 286
reports 222
resetting 331
W
test 327 Web client
unloading 161 description 28
TCP 45 display 31
test LDAP 94 home page 30, 31
tests WORM 13
installation and verification write protecting cartridges 337
(IVT) 325
magazine 327
random move 329
robotics 327
robotics get/put 332
tape drive 327
ticket indicator LED 3
time zone, setting 50
time, setting 49
timeout 97
TLS certificates

Quantum Scalar i40 and Scalar i80 Users Guide 375


Index

376 Quantum Scalar i40 and Scalar i80 Users Guide

You might also like