Service: Marine Generator Sets
Service: Marine Generator Sets
Service: Marine Generator Sets
Models:
6EKOD
5EFKOD
9--11EKOZD
7--9EFKOZD
TP-6774 2/14a
Product Identification Information
Engine Identification
Record the product identification information from the
engine nameplate.
Manufacturer
Model Designation
Serial Number
x:in:007:001
2 TP-6774 2/14a
Table of Contents
NOTICE Fire
Notice communicates installation, Exhaust System
operation, or maintenance information WARNING
that is safety related but not hazard WARNING
related.
This manual provides troubleshooting and repair Read this manual and carefully follow all procedures
instructions for 6EKOD, 9-11EKOZD, 5EFKOD and and safety precautions to ensure proper equipment
7-9EFKOZD model generator sets (4-lead and operation and to avoid bodily injury. Read and follow the
12-lead), Advanced Digital Control, and accessories. Safety Precautions and Instructions section at the
beginning of this manual. Keep this manual with the
Refer to the engine service manual for generator set equipment for future reference.
engine service information.
x:in:001:001 The equipment service requirements are very important
Information in this publication represents data available to safe and efficient operation. Inspect the parts often
at the time of print. Kohler Co. reserves the right to and perform required service at the prescribed intervals.
change this publication and the products represented Maintenance work must be performed by appropriately
without notice and without any obligation or liability skilled and suitably-trained maintenance personnel
whatsoever. familiar with generator set operation and service.
x:in:001:003
Service Assistance
D Visit
the Kohler Power Systems website at East China Regional Office, Shanghai
KOHLERPower.com. Phone: (86) 21 6288 0500
Fax: (86) 21 6288 0550
D Look at the labels and stickers on your Kohler product India, Bangladesh, Sri Lanka
or review the appropriate literature or documents India Regional Office
included with the product Bangalore, India
Phone: (91) 80 3366208
D Call toll free in the US and Canada 1-800-544-2444 (91) 80 3366231
Fax: (91) 80 3315972
D Outside the US and Canada, call the nearest regional
office Japan, Korea
North Asia Regional Office
Headquarters Europe, Middle East, Africa Tokyo, Japan
(EMEA) Phone: (813) 3440-4515
Kohler Power Systems Netherlands B.V. Fax: (813) 3440-2727
Kristallaan 1
Latin America
4761 ZC Zevenbergen
Latin America Regional Office
The Netherlands
Lakeland, Florida, USA
Phone: (31) 168 331630
Phone: (863) 619-7568
Fax: (31) 168 331631
Fax: (863) 701-7131
Asia Pacific
Power Systems Asia Pacific Regional Office
Singapore, Republic of Singapore
Phone: (65) 6264-6422
Fax: (65) 6264-6455
9EKOZD/ 11EKOZD/
Component Specification 7EFKOZD 9EFKOZD
Hot exciter field voltage/amperage readings at rated voltage
No load (63 Hz)volts/amps 12/0.8 5/0.9
Full load (60 Hz)volts/amps 33/2.2 14/2.3
Exciter field resistance (cold)ohms @ 20_C (68_F) 4.8 4.8
Exciter armature resistance (cold)ohms (line-to-line) 1.18 1.18
Main field (rotor) resistance (cold)ohms @ 20_C (68_F) 5.7 5.7
Stator output voltages with separately excited generator, using 12-volt battery (60 Hz only)
1--2, 3--4volts 115 184
55--66volts 155 193
Cold stator resistance
1--2, 3--4ohms 0.19 0.28
55--66ohms 1.9 1.3
1 2 3 4 5 6 8 10 11 12
13
7 9
14
15
16
24 23 22 21 20 19 18 17 25 26
29 38
28
39
27
ADV7942-A
WARNING
-- -- -- -- -- -- -- -- + + + + + + + + + +
40 35 30 25 20 15 10 5 0 5 10 15 20 25 30 35 40 45 50
SAE 10W*
1234567890
SAE 20W*
SAE 30*
SAE 40*
SAE 10W--30**
SAE 10W--40**
SAE 10W--60**
SAE 15W--40 **
SAE 15W--40 **
SAE 20W--60 **
SAE 5W--30 ***
SAE 5W--40 ***
SAE 0W--30 ***
* Mineral base
SAE-- Grade ** Semi--synthetic base
*** Synthetic base
1. Push the power button on the Advanced Digital 1. Loosen the fuel filters air vent screw. See
Control IId to the ON position. Figure 4-4.
2. When the run time hours appear on the LCD digital 2. Initiate the auto/start sequence until fuel, free of air
display, rotate the pushbutton/rotary selector dial bubbles, flows from the vent screw at the fuel filter.
until PUSH TO PRIME appears on the LCD digital
3. Tighten the fuel filters air vent screw.
display.
1
2
PUSH TO
PRIME
GM74543-B
GM58225A
1. LCD digital display
2. Pushbutton/rotary selector dial
3. Power button
1 3
1
2 3
I-940
1. Fuel inlet
2. Negative (--) terminal
3. Positive (+) terminal 1. Speed adjusting screw
4. Fuel outlet 2. Locking nut
3. Adjusting arm
Figure 4-5 Fuel Pump
Figure 4-6 Governor Adjustment
5.1 General
Heat exchanger cooling consists of a heat exchanger
with coolant recovery tank, thermostat, rubber impeller
seawater pump, centrifugal-type engine circulating
pump, water-cooled exhaust manifold, and an exhaust
mixer. See Figure 5-1 for cooling system components.
1
8
10
2
12
4 11
Seawater
6
Freshwater (Coolant/Antifreeze)
NOTICE
Saltwater damage. Saltwater quickly deteriorates metals.
Wipe up saltwater on and around the generator set and
remove salt deposits from metal surfaces.
1
2
1. Thermostat assembly
2. Thermostat (located inside thermostat housing)
17. Fit the circlip and flange back into position. See
Figure 5-14.
19. Replace the thermostat assembly and tighten the 5.4 Check and Fill Coolant
screws. See Figure 5-16.
Note: Do not add coolant to a hot engine. Adding
coolant to a hot engine can cause the cylinder
block or cylinder head to crack. Wait until the
engine has cooled.
1. Remove the water drain pipe plug located at the 2. Remove the seawater pump coverplate. See
heat exchanger and completely drain the system. Figure 5-19.
3
1. Pressure cap
9EKOZD/ <50% of
6.35 (0.25) x 20 (0.78)
7EFKOZD, length/diameter
11EKOZD/
9EFKOZD
2
3
7 8
9
20
6
1
5
18 4
Waterline
19
14 10
17
13
15
11
16
12 TP-5586-3
6.1 Introduction D Blown fuses. See Figure 6-1 for fuse identification.
Always check and replace the fuses before replacing
Corrective action and testing in many cases requires other components. See the operation manual or
knowledge of electrical systems and electronic circuits. parts catalog for fuse part numbers.
Have an authorized distributor/dealer or trained service
technician perform testing and service. Label Amp Fuse
F1 10 Auxiliary winding
Refer to the Engine Service Manual, TP-6776 for engine
F2 20 Controller, fuel pump, and fuel shutoff
service information. solenoid
7.1 Introduction See Figure 7-1 for the locations of the controller and
related components.
This section covers operation, configuration,
adjustment, and replacement of the ADC IId controller.
See Section 6 for troubleshooting procedures.
2
1
3
4
11
12
7
8
10
13
14
Figure 7-1 Advanced Digital Control IId (ADC IId) and Junction Box Detail
1
2
14
5
13 8
10
12
11
GM82832-D
The following items are necessary PC requirements for 1. Push the generator set power button OFF.
using the SiteTecht software.
2. Disconnect power to the battery charger, if
D SiteTecht Software Version 3.0 or higher by
equipped.
accessing TechTools to download on your PC hard 3. Disconnect the generator set engine starting
drive or disk if not already installed on your PC. battery, negative (--) lead first.
D TP-6701 SiteTecht Software Operation Manual
available by accessing TechTools. WARNING
D USB Cable with a male USB-A connector on the PC
side and a male standard B connector on the
controller side.
Accidental starting.
7.4 Controller Service Can cause severe injury or death.
Replacement Kit GM83745 Disconnect the battery cables before
working on the generator set.
If the troubleshooting procedures in Section 6 identify a Remove the negative (--) lead first
faulty controller, use the procedure in this section for when disconnecting the battery.
controller replacement. Always check the controller Reconnect the negative (--) lead last
configuration, fuse, wiring, and connections before when reconnecting the battery.
replacing the controller.
Sound Shield Equipped Models: For access to the
After replacing the controller, verify that the new
generator set to perform regular maintenance, remove
controllers configuration settings match the generator
the sound shield doors and roof.
set system voltage and frequency, battery voltage, and
communications settings. Refer to Section 7.13 for 4. Sound-Shielded Models: Open the service-side
instructions to check the controller configuration and to door.
change the settings, if necessary.
5. Sound-Shielded Models: Release the two wing
After the controller configuration has been checked and nuts located underneath the roof. See Figure 7-3.
set to match the generator set, use a voltmeter to check
the generator set output voltage. If the output voltage or 6. Sound-Shielded Models: Lift up the roof.
frequency needs adjustment, use the voltage
adjustment procedure in Section 7.10.4 and 7.13.8 and 7. Sound-Shielded Models: Slide the roof towards
the governor adjustment instructions in Section 4.4. the service side of the unit for removal.
3 2 1
GM79009-A
1. P1
2. P2
4
Figure 7-5 Controller Connections
6 11. Remove the old controller.
5
1. Sound shield roof 12. Reconnect P1 (35-pin plug) and P2 (8-pin plug) to
2. Wing nut the new controller assembly.
3. Alternator-end door
4. Service-side door
5. Front rail 13. Mount the new controller assembly onto the
6. Engine-end door junction box using the four (4) screws removed in
step 9.
Figure 7-3 Sound Shield Roof Removal
14. Reconnect the engine starting battery, negative (--)
9. Loosen and remove the four controller mounting lead last.
screws securing the controller and carefully lift the
controller. 15. Reconnect power to the battery charger, if
equipped.
Note: Be careful of the leads and harness
connected to the controller. 16. Follow the instructions in Section 7.13 to change
the new controllers configuration settings to match
the generator set system voltage and frequency,
1 battery voltage, and communications settings.
See Section 7.10.5, System Fault Warning Lamp with See Section 7.10.6, System Fault Shutdown Lamp with
Digital Displays, for definitions of the items listed. The Digital Displays, for definitions of the items listed. The
following conditions cause a system warning: following conditions cause a system shutdown:
D AC sensing loss D AC sensing loss
D High battery voltage D Auxiliary input (analog or digital)
D High coolant temperature D Engine over speed
D Low battery voltage D Engine under speed
D Low cranking voltage D High coolant temperature
D Low oil pressure D High exhaust temperature
D Locked rotor (failed to crank)
D Low seawater pressure
D Low oil pressure
D Overcrank
D Overfrequency
D Overvoltage (each phase)
D Underfrequency
D Undervoltage (each phase)
Overview Menu Oil Pressure displays the engine oil pressure. This
value also shows in the Overview Menu.
When a new shutdown or warning fault occurs, the
auto-paging display feature activates. Coolant Temperature displays the engine coolant
temperature. This value also shows in the Overview
Active Shutdowns display if any are present. This Menu.
alerts the user to single or multiple shutdown fault
conditions. See Section 7.10.6, System Shutdown Battery displays the DC voltage of the engine starting
Fault Lamp with Digital Displays for a list of possible battery(ies). This value also shows in the Overview
shutdown faults. Menu.
To enable calibration, start the generator set and select System Frequency displays the programmer-entered
the Volts L1-L2 display. Then push and hold the L1/L2/L3 output voltage frequency for three-phase or
pushbutton/rotary selector dial until the Calibration the L1/L2 output voltage frequency for single-phase.
Enabled popup appears. Calibration of each display is
now available. The display will show the following Battery Voltage displays the engine electrical system
values for three-phase generator sets. Single-phase 12 or 24 volts.
generator sets will only display items marked (*).
CAN A displays the remote communications protocol in
D Volts L1-L2 * use (J1939, SmartCraft, or NMEA 2000).
D Volts L2-L3
D Volts L3-L1 Note: After changing the CAN A communication setting,
D Volts L1-N power off and then power on the controller.
D Volts L2-N Measure Units displays the user selected unit of
D Volts L3-N measure as Metric or English.
The user can change individual values or can select Contrast displays user selected resolution values to
Reset Calib?--Yes to reset all values. The Reset Calib? improve digital display clarity.
display will only show if calibration is enabled. Refer to
the requirements shown with Generator Set Calibration
in 7.10.7 Status and Notice Digital Displays. Voltage Regulator Menu
The voltage regulator value is reviewable at all times
To disable calibration, Rotate the pushbutton/rotary
and provides the ability to fine adjust voltage. Changing
selector dial until the <--Return popup appears.
the system voltage or replacing the circuit board
Momentarily press the pushbutton/rotary selector dial.
typically requires a voltage adjustment.
Stop the generator set if not already done.
To enable calibration, start the generator set and select
Generator Set Information Menu the VR Volt Adj, Volt/Hz, Gain, or Stabil display. Then
push and hold the pushbutton/rotary selector dial until
GenSet M/N displays the generator set model number.
the Editing Enabled popup appears. Editing of the
GenSet S/N displays the generator set serial number. Voltage Adjustment, Volts/Hz, Gain, and Stability is now
available.
Controller S/N displays the controller serial number.
The user can change the individual value or can select
Reset VR?--Yes to reset to the default value. The Reset
VR Settings display will only show if editing is enabled.
D 120/240 V 1 Ph (3 wire)
D 139/240 V 3 Ph (Wye)
D 277/480 V 3 Ph (Wye)
D 120/240 V 3 Ph (Delta)
D 115/230 V 1 Ph (3 wire)
D 120 V 1 Ph (2 wire)
D 230 V 1 Ph (2 wire)
D 240 V 1 Ph (2 wire)
D 110/190 V 3 Ph (Wye)
D 127/220 V 3 Ph (Wye)
D 115/230 V 3 Ph (Delta)
D 230/400 V 3 Ph (Wye)
D 240/416 V 3 Ph (Wye)
Note: Before inserting a mass-storage device (USB host D 5-Amp (F3) fuse protects the customer connections.
connector), power off and then power on the
controller.
See Figure 7-8 for tested/approved manufacturers
USB flash drive types that work with the ADC IId
controller.
CustomUSB
(Kohler Power Systems 2-GB spin full size
Part Number KW-A202)
Imation 4-GB full size
Lexar 4-GB full size
PNY 4-GB full size and micro
Verbatim 4-GB full size and micro
Figure 7-8 USB Types Tested/Approved for ADC IId 1. Fuses (qty. 3) 1
1
1. USB port cover
1 2
Figure 7-10 ADC IId USB Identification Figure 7-12 Preheat Relay Specs
GM82844-D
Note: Text shown in italics in this section of the manual The low battery voltage feature monitors the battery and
represents digital display messages. battery charging system in the generator set operating
and off modes. The controller logic inhibits the low
AC Sensing Loss. The fault lamp illuminates green battery voltage warning during the crank cycle.
then red when the controller does not detect the nominal
generator set AC output voltage after crank disconnect. Low Cranking Voltage. The fault lamp illuminates
The controller displays AC Sens Loss Warning. green, then red when the battery voltage drops below
60% of the nominal voltage (12 VDC) for more than
High Battery Voltage. The fault lamp illuminates 6 seconds during the crank cycle. The local display
green, then red, maybe black when the battery voltage shows Lo Crank Vlt Warning.
rises above the preset level for more than 10 seconds.
The local display shows Battery High Warning. Low Oil Pressure. The fault lamp illuminates green
Figure 7-16 shows high battery voltage specifications. then red when the engine oil pressure approaches the
The high battery voltage feature monitors the battery shutdown range. The low oil pressure warning does not
and battery charging system in the generator set function during the first 11 seconds after startup. The
operating and off modes. local display shows Oil Press Low Warning.
Note: Text shown in italics in this section of the manual Low Seawater Pressure. The fault lamp flashes red
represents digital display messages. and the unit shuts down because of low seawater
pressure. Shutdown occurs 5 seconds after low
AC Sensing Loss. The fault lamp flashes red and the seawater pressure is detected. Local display shows
unit shuts down when the controller does not detect the Sea Pressure Low Shutdwn.
nominal generator set AC output voltage for more than 3
seconds after crank disconnect. The controller displays Low Oil Pressure. The fault lamp flashes red and the
AC Sens Loss Low Shutdwn. unit shuts down because of low oil pressure. The
shutdown occurs 10 seconds after the low pressure
Auxiliary Input (Shutdown). The fault lamp flashes condition is detected. The low oil pressure shutdown
red and the unit shuts down when an auxiliary inputs does not function during the first 15 seconds after
signals the controller. Use SiteTecht software to define startup. The local display shows Oil Press Low
inputs as shutdowns. The local display shows Aux Input Shutdwn.
Shutdwn.
Overcrank. The fault lamp flashes red and cranking
Engine Over Speed. The fault lamp flashes red and the stops when the unit does not start within the defined
unit shuts down immediately when the governed cranking period. The local display shows Over Crank
frequency on 50 and 60 Hz models exceeds the over Shutdwn. See Section 7.5.2, Starting the Generator Set
speed setting. The local display shows Eng Speed High and Section 7.10.1, Status Event and Fault
Shutdwn. Specifications for cyclic crank specifications.
Engine Under Speed. The fault lamp flashes red, the Note: The controller is equipped with an automatic
alarm horn sounds, and the unit shuts down immediately restart function. When speed drops below 25 Hz
when the governed frequency on 50 and 60 Hz models (750 rpm) while the engine is running, the unit
drop below the underspeed setting. The local display attempts to recrank. The unit then follows the
shows Eng Speed Low Shutdwn. cyclic cranking cycle and, when the engine fails to
start, will shut down on an overcrank fault
High Coolant Temperature. The fault lamp flashes red condition.
and the unit shuts down because of high engine coolant
temperature. The high coolant temperature shutdown Overfrequency. The fault lamp flashes red and the unit
does not function during the preset inhibit time delay shuts down when the frequency is above the
period after startup. The local display shows Coolnt overfrequency setting. The local display shows Freq
Temp High Shutdwn. High Shutdwn. See Figure 7-18.
Remote Start. This status indicates that the generator Section 7.13, Reviewing the Menu Displays, provides a
set start circuit was closed from a remote location digital display menu overview and explains the
allowing the engine to crank and run. The remote navigation using the pushbutton/rotary selector dial.
location is typically a set of contacts on a transfer switch
or remote start switch. The local display shows Remote
Start Status.
* User-Defined (Changeable) Menu Displays. NOTE: Some changes require activating the calibration or adjustment mode. Some displays may
only appear when in the calibration or adjustment mode. Refer to Section 7.13 Reviewing Menu Displays to activate the calibration or adjustment
mode.
Engine Metering
Genset State ###### Engine ----> Eng Speed:
Metering # R/min
Oil Pressure:
# PSI
Battery:
##.# V
Eng Runtime:
##.# h
Next maint:
##.# h
SW Version:
1.02
7.13.6 GenSet Run Time 3. Scroll through the parameters and press the
selector dial at the parameter that requires
Displays the generator sets operating record including changing. The parameter blinks to indicate that it is
total run time loaded and unloaded, number of starts, editable.
and total energy kW hours.
4. Press the selector dial to change the parameter.
System Freq:
7.13.7 GenSet System User Selectable --> 60 Hz or 50 Hz
Voltage Regulator
Voltage ----> VR Volt Adj:
Regulator xxx.x
VR Volt/Hz:
xxx.x
VR Gain:
xxx.x
VR Stabil:
xxx.x
OR
Reset VR?
Yes
OR 139/240 V 3 Ph
Confirm?
Prime? No
277/480 V 3 Ph
115/230 V 1 Ph
Note: The generator set output leads require voltage
reconnection. See Section 8.11 for voltage
reconnection.
120 V 1 Ph
110/190 V 3 Ph
127/220 V 3 Ph
115/230 V 3 Ph
230/400 V 3 Ph
240/416 V 3 Ph
Rotate Knob
Rotate Knob
TP563274
2. Connect a DC ammeter, 10-amp fuse, and a
8 7 6
12-volt automotive battery to the positive (FP) and
1. FN lead (disconnected in step 1)
negative (FN) exciter leads (or brush leads) as
2. FP lead (disconnected in step 1)
shown in Figure 8-3. Note and record the ammeter 3. 10-amp fuse
reading. 4. DC ammeter
5. 12V battery
Note: The approximate ammeter reading should be the 6. Exciter (or brushes/slip rings)
7. Rectifier module
battery voltage divided by the specified rotor
8. Main field (rotor)
resistance. See Section 1, Specifications, for the
specified rotor resistance values.
Figure 8-3 Separate Excitation Connections
2
1
FN FP 3
4
5
TP-5983-7
1. ADC IId
2. Ohmmeter
3. Exciter field
4. Exciter armature
5. Main field (rotor)
armature frame. Follow the megohmmeter 1. Main field rotor 5. Shaft connection
manufacturers instructions for using the 2. Stator windings 6. Armature
3. Rectifier module 7. Exciter field
megohmmeter. See Figure 8-7. A reading of
4. Megohmmeter
approximately 1.5 MOhms and higher indicates the
exciter armature is functional. A reading of less Figure 8-7 Megohmmeter Connections on
than approximately 1.5 MOhms indicates Exciter Armature
deterioration of the winding insulation and possible
current flow to ground; if so, replace the exciter
armature.
The brushes transfer current from the ADC IId to the slip
rings. The brushes should last the life of the generator.
Abrasive dust on the slip rings, however, shortens the
life of the brushes. Excessive arcing at the brushes
7 5
could damage the ADC IId controller. Weak springs,
Side View
damaged slip rings, sticking brushes, a loose brush 6
holder, or poor brush contact causes arcing. 8 9
3
The brushes must be free to move within the holder and New 1.9 cm (0.75 in.)
be held in contact with the slip rings by the springs.
2 2
When correctly positioned, spring pressure on the brush
surface causes the brush to wear evenly. The entire
3
brush must ride on the ring or arcing occurs and causes
TP5867
burned rings or voltage regulator failure. Figure 8-8
1. Brush holders (2) 7. Brush holder
shows the correct positioning of the brushes. Add or 2. Slip ring 8. Correctly positioned
remove shims as necessary to center the brushes on the 3. Brush brush
slip rings. Replace the brushes if they show uneven 4. Retainer wire 9. Incorrectly positioned
5. Shim brush
wear or are worn to one half their original length. 6. Spring
Check the resistance through the brushes. Resistance Figure 8-8 Brush Assembly
through the brushes should be low, 0.1--0.2 ohms
without meter lead resistance.
Rectifier Module Test Procedure: Generator Main Field (Rotor) Test Procedure:
1. Disconnect the exciter armature and the main field 1. With the generator disassembled, disconnect the
leads from the rectifier module. generator main field windings at the rectifier
module terminals F+ and F--.
2. Use an ohmmeter on the R x 100 scale to check the
resistance between all the rectifier diodes as 2. Check the main field resistance by connecting an
shown in Figure 8-9. The ohmmeter should show a ohmmeter across the main field F+ and F-- leads.
low resistance in one direction and, upon reversing See Figure 8-10. See Section 1, Specifications for
the ohmmeter leads, a high resistance in the other the resistance reading. A low reading indicates an
direction. Replace the rectifier module if any of the internal short and a high reading indicates an open
diodes tests differently than described. winding. Repair or replace the main field if the
ohmmeter readings indicate the main field is
inoperative. If the resistance test is inconclusive,
perform a megohmmeter test on the main field as
A described in the next step.
1 B
--
+ 1
6
AC F+
AC
AC F--
3 C
5 3
2
2
(AC) 4
(AC)
B TP-5983-7
B1
-- + 1. Main field (rotor) 4. Ohmmeter
A1 C1 2. Stator windings 5. Armature
3. Rectifier module 6. Exciter field
C (AC) Figure 8-10 Ohmmeter Connections on
TP-5983-7
1. Diode terminal Main Field
2. Diode terminal
3. Ohmmeter 3. Check the main field for a short-to-ground
Figure 8-9 Rectifier Module Test condition by using a megohmmeter. Apply
500 volts DC to either field lead and the main field
frame. Follow the megohmmeter manufacturers
instructions for using the megohmmeter. See
Figure 8-11. A reading of 1.5 MOhms and higher
indicates the main field is functional. A reading of
less than 1.5 MOhms indicates deterioration of the
winding insulation and possible current flow to
ground; if so, replace the main field.
66
7 5
2 55
3
2
6
4 1 11
6196
Voltage Regulator
Voltage ----> VR Volt Adj:
Regulator xxx.x
VR Volt/Hz:
xxx.x
VR Gain:
xxx.x
VR Stabil:
xxx.x
OR
Reset VR?
Yes
Accidental starting.
Can cause severe injury or death.
Disconnect the battery cables before
working on the generator set.
Remove the negative (--) lead first
when disconnecting the battery.
Reconnect the negative (--) lead last
when reconnecting the battery.
120/240 V 3 Ph
127/220 V 3 Ph
139/240 V 3 Ph
277/480 V 3 Ph
110/190 V 3 Ph
230/400 V 3 Ph
240/416 V 3 Ph
L0 (Neutral)
L0
GRD.
Ground 4 3 2 1
L1
Stator Leads
L2
Load 60 Hz 50 Hz
Side L0--L1 100--120 Volt 100--120 Volt
Two-Pole L0--L2 100--120 Volt 100--120 Volt
Line Circuit
Side Breaker Figure 8-19 100--120-Volt, 2-Wire Configuration
L0 (Neutral)
L0
100--120/200--240-Volt,
4 3 2 1 3-Wire
Stator Leads
60 Hz 50 Hz
L0--L1 100--120 Volt 100--120 Volt
L0--L2 100--120 Volt 100--120 Volt
L1--L2 200--240 Volt 200--240 Volt
115/230
115/230
230
EM-250000
Note: Current Transformers (CTs) are not used on all sets. CT dot or HI toward generator.
Verify the operation of the generator set overspeed, The overspeed setting is programmed into the ADC IId
overcrank, high engine temperature, and low oil controller and is not adjustable. Verify that the following
pressure shutdowns by performing the following tests. If controller configuration is set correctly for your unit.
these tests are inconclusive, test individual shutdown
Open the generator set output circuit breaker before
circuit components (wiring harness, switch, etc.) as
beginning the test. (See 1, Service Views for the circuit
described elsewhere in this section.
breaker location.)
Overcrank Shutdown
WARNING
Disconnect the fuel supply line. Press the power button
to turn the controller on. Press the start/stop button to
start the generator set. Observe that the generator set
simulates cranking for 15 seconds and then rests for
Hot engine and exhaust system. 15 seconds. Check that the generator set shuts down
Can cause severe injury or death. after the third crank/rest cycle.
Do not work on the generator set until High Engine Temperature Shutdown
it cools.
Connect a jumper wire across coolant temperature
Servicing the exhaust system. Hot parts can cause sensor (CTS) connections P8-1 and P8-2. Start the
severe injury or death. Do not touch hot engine parts. The generator set. Verify that the generator set shuts down
engine and exhaust system components become extremely approximately 5 seconds after the generator set comes
hot during operation. up to speed. Remove the jumper wire. Start the
generator set and run it for at least 30 seconds to verify
8.14.1 Controller Fault Shutdown that the generator set does not shut down.
Functions
Check the operation of the fault functions programmed in
the ADC IId by performing the following tests. If the
ADC IId does not operate as described, check the
ADC IId configuration settings; see Section 7.13. Also
check the ADC IId wiring and connections; see
Section 10.
WARNING
ADV7941B-A 1
1. Oil pressure sender
8.15 Fuses
Fuses are located on the side of the junction box. See
Figure 8-29. Always identify and correct the cause of a
blown fuse before restarting the generator set. Refer to
Section 6, Troubleshooting, for conditions that may
indicate a blown fuse. Replace blown fuses with
identical replacement parts.
1
D 10-Amp (F1) fuse protects the auxiliary winding.
1. Coolant temperature sensor
D 20-Amp (F2) fuse protects the controller circuits, fuel
Figure 8-26 Coolant Temperature Sensor Location pump, and fuel shutoff solenoid.
Temperature, _C (_F) Resistance, Ohms D 5-Amp (F3) fuse protects the customer connections.
30 (86) 2106--2392
100 (212) 182--198
Short circuits. Hazardous voltage/current can cause Note: Disconnect the generator set battery before
severe injury or death. Short circuits can cause bodily injury performing continuity checks to prevent damage
and/or equipment damage. Do not contact electrical to the ohmmeter.
connections with tools or jewelry while making adjustments or
repairs. Remove all jewelry before servicing the equipment.
Generator Set
Ohmmeter Ohmmeter Master Switch Ohmmeter Readings for Operative
Component Connections Scale Position Components*
P1 wiring harness P1-3 and ground Rx1 OFF Zero ohms (continuity)
Any other reading indicates a poor ground
connection.
P2-6 and P2-7 Rx1 OFF Zero ohms (continuity). If no continuity,
(stator leads 11 and 44 for check wiring.
1-phase models)
or
P2-6, P2-7, and P2-8
(stator leads 7, 8, and 9 for
3-phase models)
P2-3 and P2-4 (stator leads Rx1 OFF Zero ohms (continuity). If no continuity,
55 and 66) check fuse F1 and wiring.
Controller fuse and P1-2 and battery positive R x 100 OFF Zero ohms (continuity). If no continuity is
wiring (+) found, check fuse F2 and wiring.
Auxiliary winding fuse P2-3 and stator lead 55 R x 100 OFF Zero ohms (continuity). If no continuity is
10 amp fuse found, check for an open circuit and/or a
blown fuse.
Low oil pressure (LOP) Lead 7 and ground (engine R x 100 OFF Zero ohms (continuity). No continuity
sender * block) indicates a bad switch and/or wiring.
Temperature sensor P8-1 and P8-2 R x 1000 OFF 180--2500 ohms, depending on engine
(CTS) * temperature. Zero ohms or an open circuit
indicates bad wiring or a bad switch.
Preheat relay Terminals 85 and 86 Rx1 OFF 12-volt relay: 90 10 ohms coil resistance
(PH1 and PH2) Lower resistance indicates a shorted relay
coil and/or wiring. High resistance indicates
an open relay coil and/or wiring.
* See Section 8.14.2, Fault Shutdown Senders
1
Disassembly Procedure:
1. Press the start/stop button to stop the generator
set.
2
2. Press the power button to turn the controller off.
3 2
3. Disconnect power to the battery charger, if
equipped.
WARNING
4
Accidental starting.
Can cause severe injury or death. 6
5
Disconnect the battery cables before
1. Sound shield roof
working on the generator set. 2. Wing nut
Remove the negative (--) lead first 3. Alternator-end door
when disconnecting the battery. 4. Service-side door
Reconnect the negative (--) lead last 5. Front rail
when reconnecting the battery. 6. Engine-end door
GM79009-A
1. P1
2. P2
11
12
7
8
10
13
14
GM76137
Figure 9-4 Advanced Digital Control IId (ADC IId) and Junction Box Detail
12 17
10 16
15
11
5 9
4
2
1 8
7
6
3
GM73473-A
24 25
4 23 28
3 6 27
21 26
5
2
22
1
20
16
19
12
11
17 18 Note: Use cable ties to restrain loose harness
15 leads from entangling in rotor.
14
13
10
GM73474-A
1. Screws and washers 16. Lock washer
2. End bracket panel 17. Washer
3. Overbolts. Torque to 23 Nm (17 ft. lbs.) 18. Exciter armature. Note: Apply a thin coat of anti-seize
4. Washers compound to shaft surface before attaching exciter armature.
5. Screws 19. Rotor assembly
6. Exciter field assembly 20. Stator assembly
7. O-ring. Assemble O-ring into groove in bearing insert. 21. Alternator air outlet guard and screw
8. End bracket 22. Lead, screw, lock washer, and plain washer
9. End bracket air inlet guard and screw 23. Alternator fan
10. Screws 24. Drive disk
11. Screws and lock washers 25. Washers
12. Terminals 26. Screws. Torque to 45 Nm (34 ft. lbs.)
13. Rotating diode board 27. Nuts
14. Spacers 28. Studs. Torque to 23 Nm (17 ft. lbs.)
15. Bolt. Torque to 38 Nm (28 ft. lbs.)
3
4 2 558866
3
1. Lifting eye
2. Backplate
3. Wood block
4. Vibromounts
4
1. Armature
2. Armature retaining bolt 558865
3. Rotor leads
4. Rectifier board
GM73473-A
1. Bolts (6) 2
2. Rotor assembly
558867
1. Sling
2. Fan guard
3. Two-jaw puller
7. Solder the leads onto the collector ring terminals. Figure 9-15 Drive Disc Installation
Bend over terminal and insulate with heat shrink
tubing. Terminal and insulator not to extend more 2. Install the rotor/drive disc assembly on the engine
than 6.4 mm (0.25 in.) beyond collector ring. See flywheel using six studs and nuts torqued to 23 Nm
Figure 9-14. (17 ft. lbs.).
8. Test to ensure continuity at the collector rings. 3. Align the fan to the rotor/drive disc assembly using
the mark created in the disassembly procedure.
Max. finish 32 micro inches Note: Install the fan with the flange side facing
Max. eccentricity mm (in.) 0.08 (0.003) away from the flywheel.
Max. out-of-round mm (in.) 0.01 (0.0002)
4. Replace the O-ring in the end bracket bearing bore.
Figure 9-13 Collector Ring Dimensions Use a sling to support the stator assembly while
installing the stator over the rotor. Do not damage
the rotor. See Figure 9-16.
1
GM71834-A
1. Collector ring
1. O-ring 5588612
6. Use the hoist to raise the alternator end. Remove 15. Reconnect the connectors to the preheat relays.
the wood block from under the locator plate. Lower
the generator set and install a bolt and washer on 16. Reconnect the leads to the fuses.
each vibromount.
17. Reconnect the LO and GRD lead connections.
7. Apply anti-seize compound to the keyed end of the
18. Reconnect the generator output leads to the circuit
rotor shaft. Bring the rotor leads through the bores
breakers.
in the armature while installing the armature on the
shaft. Check the keyway of the shaft and key of the Note: Check the generator set nameplate to verify
armature for damage. Install the armature the original voltage configuration.
retaining bolt and washer.
19. Replace the junction box controller panel.
8. 6EKOD/5EFKOD Model: Feed the brush leads
inside the stator housing up through the opening. 20. Reconnect the P1 (35 pin) and P2 (8 pin)
Secure the brush holder using the original screws. connectors to the ADC IId controller.
9. 6EKOD/5EFKOD Model: Remove the brush 21. Reinstall the ADC IId controller.
retainer and check alignment. See Section 8.6.
22. Reconnect all of the external connectionsthe
10. 6EKOD/5EFKOD Model: Replace the brush exhaust line to the mixing elbow, the fuel line to the
cover gasket and install the brush holder cover. fuel pump filter inlet, the water line to the seawater
pump, the remote interface connector, the AC
11. 9--11EKOZD and 7--9EFKOZD Models: Use output leads, and the battery cables to the battery
screws and lock washers to install the rotor leads to (negative (--) lead last).
the rectifier board at the positive (+) and negative
(--) terminals. 23. Verify that the generator set is stopped and the
power button is off.
Note: Position the lock washers against the
rectifier board. 24. Reconnect the engine starting battery, negative (--)
lead last.
12. 9--11EKOZD and 7--9EFKOZD Models: Position
the field leads at the top. Install the exciter field 25. Reconnect power to the battery charger, if
using four bolts and washers. See Figure 9-17. equipped.
Note: Use cable tie(s) to restrain loose harness leads 26. Replace the sound shield roof and door(s), if
from entangling in rotor. equipped.
2 GM73474-A
1. Screws (4)
2. Exciter field
WARNING WARNING
Electro Switch
L1 L1
To Generator 2 1 3 4 2 1 3 4
To Shore
Set Power
L2 L2
6 5 7 8 6 5 7 8 To Shore
To Generator
Set Power
L0
10 9 11 12
To Load
To Load
L1 L1
1 2 6 5
To Generator 1 2 6 5 To Shore
Set Power
L2 L2
3 4 8 7 To Generator 3 4 8 7 To Shore
Set Power
L0
9 10 14 13
To Load
To Load
L1 L1
3 2 4 1 To Shore 3 2 4 1
To Generator
Set Power
L2 L2
7 6 8 5 To Generator 7 6 8 5 To Shore
Set Power
L0
11 10 12 9
To Load
To Load
TP-5399-5
L1 L1
3 2 4 1
L2 L2
To Generator 7 6 8 5 To Shore
Set Power
L3 L3
11 10 12 9
L0 L0
15 14 16 13
L1 L2 L3 L0
To Load
I-940
Use the information below and on the following pages to Steps for common hardware application:
identify proper fastening techniques when no specific
reference for reassembly is made. 1. Determine entry hole type: round or slotted.
Bolt/Screw Length: When bolt/screw length is not given, 2. Determine exit hole type: fixed female thread
use Figure 1 as a guide. As a general rule, a minimum (weld nut), round, or slotted.
length of one thread beyond the nut and a maximum
length of 1/2 the bolt/screw diameter beyond the nut is For round and slotted exit holes, determine if
the preferred method. hardware is greater than 1/2 inch in diameter, or
1/2 inch in diameter or less. Hardware that is
Washers and Nuts: Use split lock washers as a bolt greater than 1/2 inch in diameter takes a standard
locking device where specified. Use SAE flat washers nut and SAE washer. Hardware 1/2 inch or less in
with whiz nuts, spiralock nuts, or standard nuts and diameter can take a properly torqued whiz nut or
preloading (torque) of the bolt in all other applications. spiralock nut. See Figure 2.
2
3 1
G-585
G-585
1. Cap screw
2. Entry hole types
3. Standard nut and SAE washer
4. Whiz nut or spiralock: up to 1/2 in. dia. hardware
5. Weld nuts: above 1/2 in. dia. hardware
6. Exit hole types
Notes:
1. The torque values above are general guidelines. Always use the torque values specified in the service manuals and/or assembly drawings
when they differ from the above torque values.
2. The torque values above are based on new plated threads. Increase torque values by 15% if non-plated threads are used.
3. Hardware threaded into aluminum must have either two diameters of thread engagement or a 30% or more reduction in the torque to
prevent stripped threads.
4. Torque values are calculated as equivalent stress loading on American hardware with an approximate preload of 90% of the yield strength
and a friction coefficient of 0.125.
Drive Styles
External Tooth Lock
Hex
Internal Tooth Lock
Hex and Slotted
Internal-External Tooth Lock
Phillipsr
Slotted
Hex Socket
Sample Dimensions
American Standard (Screws, Bolts, Studs, and Nuts) Plain Washers
1/4-20 x 1 9/32 x 5/8 x 1/16
Length In Inches (Screws and Bolts) Thickness
Threads Per Inch External Dimension
Major Thread Diameter In Fractional Inches Or Screw Number Size Internal Dimension
Metric (Screws, Bolts, Studs, and Nuts)
M8-1.25 x 20 Lock Washers
Length In Millimeters (Screws and Bolts) 5/8
Distance Between Threads In Millimeters Internal Dimension
Major Thread Diameter In Millimeters
The Common Hardware List lists part numbers and dimensions for common hardware items.
American Standard
Part No. Dimensions Part No. Dimensions Part No. Dimensions Type
Hex Head Bolts (Grade 5) Hex Head Bolts, cont. Hex Nuts
X-465-17 1/4-20 x .38 X-6238-14 3/8-24 x .75 X-6009-1 1-8 Standard
X-465-6 1/4-20 x .50 X-6238-16 3/8-24 x 1.25
X-465-2 1/4-20 x .62 X-6238-21 3/8-24 x 4.00 X-6210-3 6-32 Whiz
X-465-16 1/4-20 x .75 X-6238-22 3/8-24 x 4.50 X-6210-4 8-32 Whiz
X-465-18 1/4-20 x .88 X-6210-5 10-24 Whiz
X-465-7 1/4-20 x 1.00 X-6024-5 7/16-14 x .75
X-6024-2 7/16-14 x 1.00 X-6210-1 10-32 Whiz
X-465-8 1/4-20 x 1.25
X-465-9 1/4-20 x 1.50 X-6024-8 7/16-14 x 1.25 X-6210-2 1/4-20 Spiralock
X-465-10 1/4-20 x 1.75 X-6024-3 7/16-14 x 1.50 X-6210-6 1/4-28 Spiralock
X-465-11 1/4-20 x 2.00 X-6024-4 7/16-14 x 2.00 X-6210-7 5/16-18 Spiralock
X-465-12 1/4-20 x 2.25 X-6024-11 7/16-14 x 2.75 X-6210-8 5/16-24 Spiralock
X-465-14 1/4-20 x 2.75 X-6024-12 7/16-14 x 6.50
X-6210-9 3/8-16 Spiralock
X-465-21 1/4-20 x 5.00 X-129-15 1/2-13 x .75 X-6210-10 3/8-24 Spiralock
X-465-25 1/4-28 x .38 X-129-17 1/2-13 x 1.00 X-6210-11 7/16-14 Spiralock
X-465-20 1/4-28 x 1.00 X-129-18 1/2-13 x 1.25 X-6210-12 1/2-13 Spiralock
X-125-33 5/16-18 x .50 X-129-19 1/2-13 x 1.50 X-6210-15 7/16-20 Spiralock
X-125-23 5/16-18 x .62 X-129-20 1/2-13 x 1.75 X-6210-14 1/2-20 Spiralock
X-125-3 5/16-18 x .75 X-129-21 1/2-13 x 2.00
X-129-22 1/2-13 x 2.25 X-85-3 5/8-11 Standard
X-125-31 5/16-18 x .88 X-88-12 3/4-10 Standard
X-125-5 5/16-18 x 1.00 X-129-23 1/2-13 x 2.50
X-129-24 1/2-13 x 2.75 X-89-2 1/2-20 Standard
X-125-24 5/16-18 x 1.25
X-125-34 5/16-18 x 1.50 X-129-25 1/2-13 x 3.00
X-125-25 5/16-18 x 1.75 X-129-27 1/2-13 x 3.50
X-125-26 5/16-18 x 2.00 X-129-29 1/2-13 x 4.00 Washers
230578 5/16-18 x 2.25 X-129-30 1/2-13 x 4.50 Bolt/
X-125-29 5/16-18 x 2.50 X-463-9 1/2-13 x 5.50
X-129-44 1/2-13 x 6.00 Part No. ID OD Thick. Screw
X-125-27 5/16-18 x 2.75
X-125-28 5/16-18 x 3.00 X-129-51 1/2-20 x .75 X-25-46 .125 .250 .022 #4
X-125-22 5/16-18 x 4.50 X-129-45 1/2-20 x 1.25 X-25-9 .156 .375 .049 #6
X-125-32 5/16-18 x 5.00 X-129-52 1/2-20 x 1.50 X-25-48 .188 .438 .049 #8
X-125-35 5/16-18 x 5.50 X-25-36 .219 .500 .049 #10
X-125-36 5/16-18 x 6.00 X-6021-3 5/8-11 x 1.00 X-25-40 .281 .625 .065 1/4
X-125-40 5/16-18 x 6.50 X-6021-4 5/8-11 x 1.25 X-25-85 .344 .687 .065 5/16
X-6021-2 5/8-11 x 1.50 X-25-37 .406 .812 .065 3/8
X-125-43 5/16-24 x 1.75 X-6021-1 5/8-11 x 1.75 X-25-34 .469 .922 .065 7/16
X-125-44 5/16-24 x 2.50 273049 5/8-11 x 2.00
X-125-30 5/16-24 x .75 X-25-26 .531 1.062 .095 1/2
X-6021-5 5/8-11 x 2.25 X-25-15 .656 1.312 .095 5/8
X-125-39 5/16-24 x 2.00 X-6021-6 5/8-11 x 2.50
X-125-38 5/16-24 x 2.75 X-25-29 .812 1.469 .134 3/4
X-6021-7 5/8-11 x 2.75
X-25-127 1.062 2.000 .134 1
X-6238-2 3/8-16 x .62 X-6021-12 5/8-11 x 3.75
X-6238-10 3/8-16 x .75 X-6021-11 5/8-11 x 4.50
X-6238-3 3/8-16 x .88 X-6021-10 5/8-11 x 6.00
X-6238-11 3/8-16 x 1.00 X-6021-9 5/8-18 x 2.50
X-6238-4 3/8-16 x 1.25
X-6238-5 3/8-16 x 1.50 X-6239-1 3/4-10 x 1.00
X-6238-1 3/8-16 x 1.75 X-6239-8 3/4-10 x 1.25
X-6238-6 3/8-16 x 2.00 X-6239-2 3/4-10 x 1.50
X-6238-17 3/8-16 x 2.25 X-6239-3 3/4-10 x 2.00
X-6238-7 3/8-16 x 2.50 X-6239-4 3/4-10 x 2.50
X-6238-8 3/8-16 x 2.75 X-6239-5 3/4-10 x 3.00
X-6238-9 3/8-16 x 3.00 X-6239-6 3/4-10 x 3.50
X-6238-19 3/8-16 x 3.25 X-792-1 1-8 x 2.25
X-6238-12 3/8-16 x 3.50 X-792-5 1-8 x 3.00
X-6238-20 3/8-16 x 3.75 X-792-8 1-8 x 5.00
X-6238-13 3/8-16 x 4.50
X-6238-18 3/8-16 x 5.50
X-6238-25 3/8-16 x 6.50
Washers
Bolt/
Part No. ID OD Thick. Screw
M125A-03-80 3.2 7.0 0.5 M3
M125A-04-80 4.3 9.0 0.8 M4
M125A-05-80 5.3 10.0 1.0 M5
M125A-06-80 6.4 12.0 1.6 M6
M125A-08-80 8.4 16.0 1.6 M8
M125A-10-80 10.5 20.0 2.0 M10
M125A-12-80 13.0 24.0 2.5 M12
M125A-14-80 15.0 28.0 2.5 M14
M125A-16-80 17.0 30.0 3.0 M16
M125A-18-80 19.0 34.0 3.0 M18
M125A-20-80 21.0 37.0 3.0 M20
M125A-24-80 25.0 44.0 4.0 M24