12V 200AH
Deep Cycle
Specifications
Normal Voltage 12V
Normal Capacity (20HR) 200.0AH
Terminal Type Standard Terminal F11
Optional Terminal -
Container Material Standard Option ABS
Flame Retardant Option (FR) ABS(UL94:VO)
Rated Capacity 214.4 AH/10.7A (20hr, 1.80V/cell, 25C / 77F)
200.0 AH/20.0A (10hr, 1.80V/cell, 25C / 77F)
175.4 AH/35.1A (5hr, 1.75V/cell, 25C / 77F)
159.0 AH/53.0A (3hr, 1.75V/cell, 25C / 77F)
129.2 AH/129.2A (1hr, 1.60V/cell, 25C / 77F)
Max Discharge Current 2000A (5s)
Internal Resistance Approx 2.7m
Discharge Characteristics Operating Temp. Range Discharge: -15 ~ 50C (5 ~ 122F)
Charge: 0 ~ 40C (32 ~ 104F)
Storage: -15 ~ 40C (5 ~ 104F)
Nominal Operating Temp. Range 25 3C (77 5F)
Cycle Use Initial Charging Current less than 60.0A.Voltage
14.4V ~ 15.0V at 25C (77F) Temp. Coefficient -30mV/C
Standby Use No limit on Initial Charging Current Voltage
13.5V ~ 13.8V at 25C (77F) Temp. Coefficient -20mV/C
Capacity affected by Temperature 40C (104F) 103%
25C (77F) 100%
0C (32F) 86%
Design Floating Life at 20C 12 Years
Self Discharge Ultracell batteries may be stored for up to 6 months at 25C(77F) and then a refresh charge is required. For
higher temperatures the time interval will be shorter.
Dimensions
F11 Terminal
20 [0.787] 57 2
M8 [0.315]
6 [0.236]
240 2
224 2
218 2
140 2
_
_
_
_
522 2
1
Ultracell (UK) Ltd | Vesty Business Park | Vesty Road | Liverpool | L30 1NY | United Kingdom
Tel: +44 (0) 151 523 2777 Fax: +44 (0) 151 523 0855 Email: info@ultracell.co.uk ISO9001
www.ultracell.co.uk
Constant Current Discharge (Amperes) at 25C (77F)
F.V/Time 10 min 15 min 20 min 30 min 45 min 1h 2h 3h 4h 5h 6h 8h 10h 20h
1.85V/cell 292.8 246.4 215.3 154.9 123.0 99.9 62.0 48.4 39.2 31.8 27.8 22.7 18.9 10.62
1.80V/cell 374.2 297.7 254.5 182.8 143.1 111.9 67.7 52.0 41.8 34.2 29.8 24.0 20.0 10.72
1.75V/cell 411.1 352.2 273.8 189.8 148.5 117.0 70.2 53.0 42.8 35.1 30.6 24.5 20.2 10.82
1.70V/cell 448.1 347.2 287.7 197.5 154.4 120.7 73.0 54.5 43.9 36.0 31.2 24.8 20.4 11.02
1.65V/cell 483.6 369.2 305.7 208.4 158.3 124.8 75.0 56.8 45.4 37.0 31.9 25.2 20.8 11.16
1.60V/cell \ 394.8 325.6 220.0 165.0 129.2 77.6 58.5 46.8 38.2 32.6 25.4 21.0 11.22
1.80V/cell 688.8 552.9 477.6 347.1 274.6 215.8 131.1 101.2 81.5 66.9 58.6 47.5 39.6 21.4
1.75V/cell 747.5 598.1 509.6 358.5 283.6 224.9 135.6 102.8 83.2 68.6 60.1 48.3 40.0 21.6
1.70V/cell 803.4 663.9 532.5 371.7 294.1 231.5 140.7 105.4 85.2 70.1 61.3 48.9 40.3 22.0
1.65V/cell 860.8 669.7 563.0 390.3 300.3 238.5 144.2 109.6 87.9 72.0 62.6 49.6 41.1 22.2
1.60V/cell \ 707.6 593.6 408.1 310.2 244.9 148.1 112.4 90.3 74.0 63.8 50.0 41.5 22.3
120
6.0 12.0
Terminal Voltage(V)
Charged Volume
100 0.1C 2.5
5.5 11.0
0.1C 0.054C 2.4 Charge Voltage
80 0.08C (Constant 2.45v/cell)
0.214C
5.0 10.0
0.365C
60 0.06C 2.3
3.8C 2.6C 1.1C 0.646C
After 50% Discharge
4.5 9.0
0.04C 2.2
40 After 100% Discharge
1 2 4 6 8 10 20 40 60 2 4 6 8 10 20 0C
min H 0 4 8 12 16 20 24 28
Temperature Effects in Relation to Battery Capacity Cycle Life in Relation to Depth of Discharge
Testing condition
120 Discharging:current 0.17C (FV 1.7V/cell);
Charging:current 2.45V/cell,max. 0.25CA;
0.1CA Charging volume:125% of discharged capacity.
100 0.12CA
0.21CA 120
80 1CA 100
Capacity (%)
2CA
60 3CA
80
Capcity(%)
60
40 100% 50% 30%
DOD DOD DOD
40
20
20
0
-20 -10 0 10 20 30 40 50 0
0 200 400 600 800 1000 1200 1400 1600 1800
Storage Time(Months)
2
Ultracell (UK) Ltd | Vesty Business Park | Vesty Road | Liverpool | L30 1NY | United Kingdom
Tel: +44 (0) 151 523 2777 Fax: +44 (0) 151 523 0855 Email: info@ultracell.co.uk ISO9001
www.ultracell.co.uk