10 1109@pesc 1997 616727 PDF
10 1109@pesc 1997 616727 PDF
10 1109@pesc 1997 616727 PDF
4"
llxt
I. INTRODUCTION
CONV WIT
Note that sirice the output cunent is the sum of the two
A full bridge PWM DC-to-DC converter with a two output filter cun-enes, the current rating of transformer
inductor rectifier was first proposed by the author in [ l ] and secondary winding is one half the load current. This
is shown in Fig. 1. The two inductor rectifier circuit was effectively reduces the ac winding losses in the transformer
first reported in [2]. and output fileer inductors.
The two inductor rectifier can be modeled as two parallel
connected buck converters. However the analysis differs
from parallel connected modules in that the output inductors
share the same output filter capacitor. This results in cross
coupling between the two output inductor currents and care
sec.
must be taken when designing the control loops.
(a)
111. Average Current Mode Control Implementation
vfpyq prim.
I l fLs+ + Ls
(b)
v o
sec.
Average current mode control is preferred for accurate
control of the average output current and offers higher noise
immunity compared with peak current control. This is
advantageous in current limited power supplies where the
supply current is limited. For this mode of control, current
q=lIl/ppp
sensing can be performed either on the input side or the
output side of the isolation transformer. However, with input
current sensing, the negative slope of the output current
in' + needs to be synthesized which can result in an error if the
Ls Ls output filter inductors are designed using swinging cores.
prim. sec.
On the other hand, output current sensing offers accurate
measurement of the average output current but does not
(C)
guarantee flux balancing in the isolation transformer. As a
Fig. 2: Equivalent circuit modes of the convertex result, a dc bloclung capacitor is needed to prevent flux
imbalance. Figure 4 shows a converter schematic with
average current control and output current sensing. In this
i Mode-I :Mode-111 Mode-III! configuration, a dc blocking capacitor (C,) is utilized to
prevent flux imbalance.
. . . .. .. I I&
:" Lf I ,I
.. .. ..
.
,
.. ..
.. .. +
t
.. .. .. .. ..
... . . I I I I -1'5
.. ..
..
..
.
...
.
... . ..
._ . .
... . .
... ...
_ . .
. .
i i 'Ds2
i. -DTs
2
2 04
output filter inductor currents are not individually regulated,
the small signal model of the system can be reduced to that i
k : . I+- s ,
of a single buck converter with average current mode control (7)
where the resultant filter inductor is the parallel combination
of the two output inductors. Although each inductor current
is not separately regulated, any difference between the
average currents will be corrected by the input dc blocking
capacitor which maintains zero net dc flux within the: This transfer function represents an integrator followed by a
transformer. This guarantees that the two inductor currents, 1ea.d-lag network. T o ensure stability, the zero should be
remain equal. Note that the effective switching frequency of placed before the power stage filter frequency of the current
the resultant system is twice the switching frequency for the loop where the phase shift of the integrator is canceled by the
two filter inductor currents are out of phase which results in zero at half the switching frequency. The pole is normally
frequency doubling at the output. placed above half the switching frequency to roll off the gain
Using the PWM switch model and assuming the and thereby eliminate high frequency noise. Furthermore,
transformer is ideal, the equivalent small signal model of the this pole placement minimizes interaction with the current
converter is shown in Fig. 6. loop.
L. By straightforward analysis, the control to output current
L =-+.
loop transfer function is given by
+ q (s)= R, . H , ( s ) . G,(s).F, . F, (s) (1 1)
where
"0
It is clear from the above figure that the current loop can
be stabilized with proper compensator design and without
slope compensation. In fact, the compensator gain can be
adjusted in a similar fashion to adding slope compensation in
In average current mode control, a possible current peak current mode systems. The gain margin of the current
compensation transfer function is given by loop is 13.5dB and the phase margin is 67.7" while the
current loop bandwidth is 1OkHz.
205
The corresponding closed loop transfer function of the
system is shown in Fig. 8 and the output current step
response is shown in Fig. 9.
Frequency In Hr
102 103 I OH 105 Fig 10 Loop transfer funcbon with average current control
Frequency ( Hz )
c 80.00
40.00
Frequency ( Hz ) 0
206
In contrast to average current mode control small signal , =: F12and Fzz= F,,.
Note that for L I = L ~F,,
model, the peak current small signal model is more involved To guarantee stability, each loop of the system must be
in that the two converters are coupl~sclvia the common output stablc. Two current loops can be identified, a direct loop
filter capacitor. As a result, the sjstem can no longer be associated with each current with its corresponding duty
reduced to that of a single buck converter with peak current cycle and a cross coupled loop with the ~ o ~ ~ l e r ~ e iduty
~tary
control. The equivalent control block diagram of the systern cycle. These loops are given by,
under peak current mode is shown i n Fig. 13.
P' iJ E k e , the negative sign of T12 and T, implies that the phase
lag at the cross over frequency should be less than 360" as
opposed to the conventional 180".
The control to output transfer function may be evaluated
as
Fig. 13: Block diagram of the peak current control model H; = Rb7* H e (23)
Tlhe condition for instability of the control to output transfer
The transfer functions are computed using the average function (21) i s
PWM switch model as shown in Fig. 14.
where
Frequency ( Hz )
Fij = i i / d j (14)
The cross coupled transfer function is given by
207
be one half the down slope of the output filter inductor 80
currents, Sf or 60
,.-.
5 40
L LL
. , E:
d 20
Again, note that the cross coupled loop phase margin is
computed in reference to 360". 0
The stability condition of (24) was evaluated and the
10' 102 103 104 105
results are shown in Fig. 16. The loop transfer function for a
Frequency ( H z )
single converter case is overlaid for reference.
1-1
,""
101 102 101 10a 105
Frequency ( H z )
10' 102 103 104 105
Frequency ( Hz )
Fig. 16: Loop gains with peak current control, Se = -0.5 St
t I I I I
io0 1K 10K
Frequency in Hz
Fig. 19: SPICE loop gains with peak current control, Se = -St
208
[7] R.B. Ridley, B.H. Cho, F.C. Lee, "Analysis and Interpretation of Loop
Gains of Multiloop-Controlled Switching Regulators," EEE Trens. on
Power Electronics, vol. 3, No. 4, pp. 489-498, Oct. 1988.
[8] K. Sin, C.Q. Lee, T.E. Wu, "Current Distribution Control of Para-llel
Converters: P a t I," E E E Trans. on Aerospace and Electronic Systems,
vol. 28, No. 3, pp. 829-840, July 1992.
[SI R.B. Ridley, "A New Continuous Time Model for Current Mode
C,ontrol," IEEE Trans. on Power Electronics, vol. 6, pp. 271-280, April
1991.
[IO] 3. Rajagopalan, K. Xing, Y. Guo, F.C. Lee, B. Manners, "Modeling
and Dynamic Analysis o f Paralleled DClDC Converters with Master-
Slave Current Sharing Control," IEEE APEC Conf. Rec., ppl578-684,
-
111
1-- 1996.
2000u 6OOOU 101loIlU 14oou 18OOU
TIME in Secs
209