Installation Procedure
1. Go to http://www.anybus.com/products/abxss.shtml and select File/Document Downloads.
2. Download and install the IPconfig package.
Changing IP settings
To change the IP settings on a detected device, double-click the device in the list of devices. This will open up a dialog in SP1668 3.1
which you can enter the desired IP configuration. The default password for authentication of the new settings is admin.
Click Set to restart the Anybus device with the new settings applied.
Test the new settings by opening a web browser and entering the assigned IP address. To discover the assigned IP address
when using DHCP, simply perform a new scan with the IPconfig utility and locate the device in the list.
Technical data
Power Supply: 924 V AC/DC (2W)
Temperature range: Operating: -40 to +65 C
Storage: -40 to +85 C E214107
Humidity range: 595 % RH, non-condensing
Mounting option: DIN rail (EN 50022)
HMS Industrial Networks
CE certification: According to EN 55011:2007 and EN 61000-6-2:2005 Mailing address: Box 4126, 300 04 Halmstad, Sweden E-mail: info@hms-networks.com
Visiting address: Stationsgatan 37, Halmstad, Sweden Web: www.anybus.com
SP1668, rev. 3.1, Apr 2016 AB7702-B
DIN Rail Mounting Connections
1
3
2
2 Power + RS-485 Serial (Terminal Block)
1 Pin
24
Description
Vin +
23 Vin - ! Field wiring terminals must be connected
with minimum wire size 24 AWG.
22 Digital Input 2 + (1024 VDC)
LED Indicators 21
20
Digital Input 1 + (1024 VDC)
Digital Input Common -
1819 Not used
17 RS-232 Receive
16 RS-232 Transmit
15 Common
14 RS-485 Line A
13 RS-485 Line B