Switchgear
Page Features
8DJ10 secondary distribution Personal safety
Application, Requirements switchgear is a factory-assem- Safe-to-touch and hermetically
Features 2 bled, type-tested, metal-enclosed sealed primary enclosure
Designs, typical use 3 switchgear for indoor installation.
HV HRC fuses and cable sealing
Typical uses ends are only accessible when
Technical Data, Shipping
feeders are earthed
Electrical data, temperature, filling pressure 4 8DJ10 secondary distribution
switchgear is used for power dis- Operation is only possible
Switchgear installation, shipping data 4 when the enclosure is closed
tribution in substations even
Product Range under severe environmental con- Logical mechanical interlocking
ditions, such as:
Product range overview, schemes 5 Capacitive voltage detection
Industrial environments system for verification of safe
Equipment features 5
Damp, sandy or dusty areas isolation from supply
Design Simple outdoor substations Feeder earthing by means of
Panel design 6 make-proof earthing switches
Main uses
Components Operating safety
Compact substations
Three-position switch-disconnector 7 Hermetically sealed primary en-
Compact transformer substations, closure independent of environ-
Operating mechanisms 7 e. g. for wind power stations
HV HRC fuse assembly 8 mental effects (dirt, moisture &
Secondary equipment 8 Garage and vault substations small animals) sealed for life:
Cable connection 9 Underground and underfloor Welded switchgear vessel
substations Welded-in bushings and
Dimensions operating mechanism
Substations by pavements,
e. g. in systems with extremely Maintenance-free operating
Switchgear,
small construction widths, in mechanism parts (IEC 60 694/
floor openings, fixing points 10
particular the basic versions of VDE 0670-1000)
Cable connection fittings 11
schemes 10 and 71 in conurba- Switch operating mechanisms
Notes tions accessible outside the switch-
Substations with control aisle gear vessel
11
Switchgear interlocking with
Further Information Technical features logical mechanical interlocking
See Catalog HA 40.1 Secondary distribution switch-
gear design with up to 6 feeders Cost-efficiency
Application
R-HA45-121b eps
R-HA45-119b eps
R-HA45-120b eps
Ring-main feeders
Transformer feeders with
HV HRC fuse assemblies
Basic design
2 ring-main feeders 3 ring-main feeders 4 ring-main feeders
Transformer cable connection 1 transformer feeder 1 transformer feeder 2 transformer feeders
above Scheme 10 Scheme 71 Scheme 62
With logical mechanical inter-
Ring-main/transformer blocks
locks
With ready-for-service indicator
With a capacitive voltage
detection system at the
ring-main feeders
Options
Capacitive voltage detection
system at the transformer
feeders
Motor operating mechanisms
for the three-position switch-
disconnectors of the ring-
main and transformer feeders
Auxiliary switch for three-
position switch-disconnector
and make-proof earthing switch
R-HA45-122c eps
8DJ10 switchgear
with walk-in access
Electrical data
Rated voltage Ur
Rated frequency fr
Rated normal current Ir
for ring-main feeders
for transformer feeders
depending on the
HV HRC fuse link
Rated short-time
withstand current Ik, 1 s
Rated short-time
withstand current Ik, 3 s (option)
Pressure values at 20 C
for the insulation:
Rated
filling pressure pre
Minimum
operating pressure pme
kV
kV
kV
kA
kA
kA
kA
kA
kA
kA
kA
kA
kA
kA
7.2
20
60
25
20
50
63
25
50
63
12
28 1)
75 1)
50/60 Hz
400 A or 630 A
200 A
20
20
25
20
50
63
25
50
63
40 to +70 C
36
95
20
25
20
50
63
25
50
63
38
95
16
20
25
20
40
50
63
25
40
50
63
24
50
125
16
20
20
40
50
25
40
50
63
No.
71
62
62
Switchgear installation,
shipping data
Switchgear installation
HA45-2383 eps
700 700
1 Switchgear
2 Floor opening
into cable duct
3 Cooling sheets made
of expanded metal
4 Direction of pressure relief
5 Cable
6 Sheet-metal
partition (not included
in the scope of supply)
Shipping data
Scheme Version
(abbrevi-
ations)
3RK+1T
4RK+2T
3RK+1T
4RK+2T
Switch-
gear
height
mm
1360
1650
1360
1650
1360
1650
1
4
5
6
Abbreviations:
RK = Ring-main feeder
T = Transformer feeder
Wall-standing arrangement
Direction of
pressure relief
Transport dimensions
Width
71
2RK+1T 1360
1650
1.10
1.10
1.45
1.45
1.80
1.80
Height Depth
1.56
1.85
1.56
1.85
1.56
1.85
2.0
2.0
2.0
2.0
2.0
2.0
m
1.10
1.10
1.10
1.10
1.10
1.10
1.15
1.15
1.15
1.15
1.15
1.15
Vol-
ume
m3
1.89
2.24
2.49
2.95
3.09
3.66
2.53
2.53
3.34
3.34
4.14
4.14
Gross
weight
2)
approx.
kg
300
330
380
430
580
660
350
380
460
510
680
760
Secondary Distribution Switchgear Type 8DJ10 up to 24 kV, Gas-Insulated
Product Range
(Abbreviations 2RK+1T)
710 775 1360 270 Motor operating mechanism for
three-position switch-disconnector
1650 300
Interlock of cable compartment
cover for ring-main feeders x
Shunt release
Scheme 62
6) 5) 4 ring-main feeders and Auxiliary switch for
2 transformer feeders Switch-disconnector CLOSED/OPEN:
T T 1 NO + 1 NC
HA45-2336b eps
(Abbreviations 4RK+2T)
EARTHING CLOSED/OPEN:
1 NO + 1 NC
1410 775 1360
1650
500
580
Locking device for
three-position switch-disconnector
Short-circuit or earth-fault indicator
Wiring at the indicator (standard)
Wiring on the terminal (option)
RK RK RK RK
Closing lock-out for
three-position switch-disconnector
Double cable connection for
Overall switchgear height 1360 mm x
Overall switchgear height 1650 mm x
Surge arrester for
Overall switchgear height 1360 mm 4) x
1) Weight depending on the relevant equipment,
Overall switchgear height 1650 mm x
e.g. motor operating mechanism
5) Cable routing optionally: Mounted cable clamps x
To the rear (standard)
Upwards (option)
To the right (option) 2) For overall switchgear 3) For scheme 62 only possible
6) Cable routing optionally: height 1360 mm: for the right-hand feeder
To the rear (standard) Cable bracket below the feeder 4) Only possible for
Upwards (option) 105 mm deeper
Abbreviations: Abbreviations: cable compartment cover
and
RK = Ring-main feeder RK = Ring-main feeder 300 mm deeper
T = Transformer feeder T = Transformer feeder cable compartment cover
Design
1
24
2 12 18
3
13 19
25
4
5 14 20
6
30
15
7
20
8
10
9 L1 L2 L3 19
2 26
10 21
16 21 26
31
28
32
22 22
27 29
HA45-2350b eps
HA45-2349b eps
HA45-2348c eps
Components
R-HA45-123 eps
Three-position switch-disconnector
switching device. Rear view of the switchgear vessel of a
ring-main/transformer block, scheme 10
Functions 1 Three-position switch-disconnector
Load-break function in the transformer feeder
2 Three-position switch-disconnector
Earthing function with short- 1 in the ring-main feeders
circuit making capacity
3 Pressure relief device
Switch positions 2
CLOSED OPEN EARTHED
Operating mechanisms
The three-position switch-
disconnector is operated from
the switchgear front via
Spring-operated mechanism
With spring-operated 3
CLOSED and
spring-operated OPEN
for use in ring-main feeders
Spring-operated/stored-
energy mechanism
With spring-operated Operating mechanisms
CLOSEDand
R-HA45-124a eps
Control board
spring-operated OPEN for detachable lever mechanisms
for use in transformer feeders (standard)
With an additional energy Example
store device for the function Ring-main/transformer block,
scheme 10
stored-energy OPEN
after being tripped by the 4 Locking device (option)
for the detachable lever mechanism
HV HRC fuse (striker pin
tripping) or by the shunt 5 Detachable lever mechanism
4 for the earthing function
release
6 Detachable lever mechanism
5 for the load-break function
Options
6
Motor operating mechanism
for switch-disconnector
Locking devices
Auxiliary switch for three-
position switch-disconnector 7 Detachable lever mechanism
R-HA45-104 eps
R-HA45-105 eps
R-HA45-107 eps
switch
Control board
for rotary operating mechanisms
Example
1) According to VDN */ VDEW ** Ring-main feeder
recommendation 9 11
9 Symbols for the actuating direction
* Association of German Network of the rotary operating mechanism
Operators VDN e.V. at the VDEW
10 10 Locking device for the
in Germany (as of 2003)
rotary operating mechanism
** Association of German Power 11 Rotary operating mechanism
Stations VDEW e.V.
Components
R-HA45-129a eps
HV HRC fuse compartment with
above the transformer feeder cable compartment cover removed
outside the switchgear vessel. Phase L1:
HV HRC fuse box with
Standards HV HRC fuse slide removed
HV HRC fuse links with striker Phase L2:
HV HRC fuse box closed
pin in medium version
according to Phase L3:
Replacement of HV HRC fuses
IEC 60 282-1 *
VDE 0670 Parts 4 and 402
DIN 43 625
main dimensions
Features
Access to the HV HRC fuse
compartment and replace-
ment of HV HRC fuses is
only possible if the transfor-
mer feeder has been iso-
lated and earthed
Requirements fulfilled as HV
alternating current switch
fuse combination * Secondary equipment (option)
Selection of HV HRC fuses
R-HA45-112 eps
Secondary equipment
(option)
Examples:
Auxiliary contacts
Motor operating mechanisms
Shunt releases
Wiring
Auxiliary contacts, motor
operating mechanisms or shunt
releases are wired to a terminal
strip, itself located next to the
operating mechanism assembly
of the relevant feeder.
Wiring is led in by the custo-
mer from the side or rear and
connected to the terminal strip
allotted to the operating mecha-
nism assembly.
Components
Cable connection
Bushings according to
EN 50 181/ DIN EN 50 181 1) Cable connection (examples)
with outside cone
L1 L2 L3 L1 L2 L3
Access to the cable con- Cable connections
nection compartment only if in ring-main feeder
the feeder has been isolated 1 Prepared for cable plugs
1 2
and earthed with bolted contact (M16)
3 2 Phase L1:
Ring-main connection Make: Euromold,
4 type K400 LB
With bolted contact (M16) as as cable elbow plug
interface type C according
3 Phase L2:
to EN 50 181/ DIN EN 50 181 Make: Euromold,
Cable connection at one level type K400 TB
as cable T-plug
For thermoplastic-insulated
4 Phase L3:
cables Make: Euromold,
R-HA45-111 eps
R-HA45-128 eps
For paper-insulated mass- type AGT 20/630
as cable T-plug
impregnated cables with
adapter systems Option:
Cable connection compart- Cable plugs with Mounted cable clamps
For conventional cable sealing ment, as delivered bolted contact (M16)
ends via elbow adapters (front view)
AKE 20/630 (make Siemens)
For cable T-plugs or cable
elbow plugs with bolted
contact
For connection cross-sections
up to 300 mm2 (standard)
L3 L2 L1 L3 L2 L1
Cable routing downwards, Cable connections
cable connection at front in transformer feeder
6
For rated normal currents 5 Prepared for cable plugs
of 400 A or 630 A with plug-in contact
7 6 Phase L1:
5 Make: Euromold,
Options
type K158 LR
Suitable for the connection 8
7 Phase L2:
of surge arresters Make: nkt cables,
Short-circuit/earth-fault type EASW 20/250
indicator 8 Phase L3:
Make: Cooper,
Mounted cable clamps type DE 250-R-C
R-HA45-130 eps
R-HA45-131 eps
10
15
1
31
147 44
233
47 197
3
35
19
40
65
HA45-2358d eps
Block types, consisting of ring-main feeders and transformer feeders optionally in 2 overall heights
HA45-2355c eps
175
106
RK
350
110 110
Sections
Section A-A
553
710
700
350
350
100
350
620
~560*
750
B
TR
RK
A
350
110 110
A
775
Ring-main feeder RK
1360 /1650
55
35
623
40
713
610
28 x 14
14 x 28
285/575**
63
2
1165/1455***
60
60
40
HA45-2356c eps
HA45-2359d eps
RK
350
see scheme 10
1060
RK
A
B
TR
350
1050
970
A
350
Section B-B
Transformer feeder T
40
60
M12
1360/1650
Plan view
HA45-2357c eps
40
RK
350
RK
A
350
B
TR
1400
1320
RK
350
1 Wall distance
2 Fixing points
3 Position of the incoming cables
in the ring-main feeder
4 Position of the incoming cables
RK
TR
350
1360/1650
713
63
Cable connection fittings in ring-main feeders
Examples for an overall height of 1650 mm
HA45-2380a eps
553
~560
610**
553
~560
Standard
~560
750
775
a**
750
775
553
635**
750
775
290,5*
101
1
575
3
575
9
575
~560
610**
750
775
610**
~560
750
775
Standard
cable compartment cover
715**
852
880
~190
2
575
10
575
Dimensions
~560
5
575
~560
610**
897
925
150 mm deeper
cable compartment cover
Dimension a
610 mm up to type RDA21
635 mm for type RDA24