Switchgear
Switchgear Catalog HA 41.11
2003
Type 8DH10 up to 24 kV,
SF6-Insulated, Extendable Supersedes:
Catalog HA 41.11 · 2001
Switchgear Type 8DH10 up to 24 kV, SF6-Insulated, Extendable
Page Features
8DH10 switchgear is a factory- Quality and environment
Application, Requirements assembled, type-tested, three- Quality and environmental
Features, typical uses 2 and 3 phase, metal-enclosed, metal-clad management system acc. to
single-busbar switchgear for in- DIN EN ISO 9001 and
Technical Data door installation: DIN EN ISO 14001
Electrical data, filling pressure, • Up to 24 kV
temperature 4 Personal safety
• Feeder currents up to 630 A
Switchgear installation, shipping data 5 and 6 • Safe-to-touch and hermetically
• Busbar currents up to 1250 A
sealed primary enclosure
Product Range
Typical uses • HV HRC fuses and cable sealing
Product range overview 6 to 13
8DH10 switchgear is used – even ends are only accessible when
Design under severe environmental con- the outgoing feeders are earthed
Panel design 14 and 15 ditions – for power distribution in • Operation is only possible when
secondary distribution systems, the enclosure is closed
Components e.g. in • Logical mechanical interlocking
3AH vacuum circuit-breakers 16 and 17 ■ Substations, customer trans- • Capacitive voltage detection sys-
Three-position switch-disconnectors 18 fer substations, distribution sub- tem for verification of safe isola-
stations and switching substa- tion from supply
Busbars 19
tions of power supply and
Transformers 20 to 25 public utilities • Earthing of outgoing feeders by
Cable connection 26 means of make-proof earthing
Low-voltage equipment 27
■ Industrial plants, such as: switches
• Wind power stations
Dimensions • High-rise buildings Security of operation
Individual panels, panel blocks 28 to 32 • Airports • Hermetically sealed primary
Metering panel combinations 31 and 33 enclosure independent of
• Lignite open-cast mines environmental effects (dirt,
Floor openings and fixing points 34 to 37
Cable-connection fittings 38 • Underground railway stations moisture and small animals) –
sealed for life:
• Sewage treatment plants
Standards – Welded switchgear vessel
• Port facilities – Welded-in bushings and operating
Standards, specifications, guidelines 39 mechanism
• Traction power supply systems
Appendix • Automobile industry • Maintenance-free operating
mechanism parts
Notes 39 • Petroleum industry (IEC 60 694/VDE 0670, Part 1000)
Further Information • Chemical industry • Switch operating mechanisms
See Catalog HA 40.1 • Cement industry accessible outside the switchgear
vessel
• Unit-type heating power stations
• Switchgear interlocking by
• Textile, paper and food
means of logical mechanical
industry
interlocking
• Emergency power supply
• Mechanical switch position
installations
indications integrated in the
mimic diagram
Modular design
• Individual panels and panel Cost-efficiency
blocks can be freely combined
Extremely low “life-cycle costs”
and extended – without the need
and extremely high availability
for work involving SF6 gas
throughout the entire product
• Low-voltage compartments can service life as a result of:
be supplied in two overall heights
• Maintenance-free concept
and are wired to the panel by
means of plug-in connections • Climatic independence
• Minimum space requirement
Reliability
• Maximum availability
• Type and routine-tested
• Standardized and manufactured Security of investment
using numerically controlled Innovative developments, such as:
machines
• Modular design
• More than 350,000 8DJ/ 8DH
panels in operation worldwide • Extendability of the switchgear
for many years without gas work on site
• 3AH maintenance-free vacuum
© Siemens AG 2003
circuit-breakers
• SIPROTEC protection relay family
2 Siemens HA 41.11 · 2003
Switchgear Type 8DH10 up to 24 kV, SF6-Insulated, Extendable
Application
Typical uses
Technical features
• Maintenance-free
• Climate-independent
• Three-pole primary enclosure,
metal-enclosed, metal-clad
• Insulating gas SF6
• Gas-tight, welded switchgear
R-HA41-013a eps
vessel made of stainless steel
with welded-in bushings for
electrical connections and
mechanical components
• Three-position switch-discon-
nector with load-break and
make-proof earthing function
• Cable connection for bushings
with outside cone
• Connection by means of cable
plugs
– In ring-main feeders and
circuit-breaker feeders with
bolted contact (M16)
Example
– In transformer feeders with Customer transfer switchgear
plug-in contact
• Option: Connection with conven-
tional cable sealing ends
– For thermoplastic-insulated
cables via elbow adapter
AKE 20/ 630 (make Siemens)
– For paper-insulated mass-
impregnated cables via commer-
cially available adapter systems
• Easy installation
• Option: Pressure absorber
system
– Maintenance-free
– For rated short-time withstand
current Ik £ 20 kA
– For single and multi-panel
combinations of 700 mm to
2000 mm width (for panel type
ME1 with max. 1 adjacent panel)
– With 300 mm high pressure
absorber duct below the
switchgear
– With 115 mm deep pressure
absorber duct for pressure relief
upwards
– Possible for switchgear with
standard cable compartment
cover,
R-HA41-015 eps
Standards
Application
See page 39
Power supply of high-rise buildings
Technical Data
Filling pressure,
Electrical data temperature
Rated frequency fr Hz 50/60 50/60 50/60 50/60 50/60 Minimum operating 1300 hPa
pressure pme (absolute)
Rated normal for busbar (standard) A 630 630 630 630 630 for insulation
current Ir 1)
(not for billing for busbar (option) A 1250 1250 1250 1250 1250
metering panels
type ME1) Ambient temperature T
Panels without – 40 °C
secondary equipment to +70 °C
Ring-main panel type RK, bus sectionalizer panel type LT2, cable connection panel type K Panels with secon- – 5 °C
dary equipment and to +55 °C
Rated normal for feeder (for panel types RK … and K …) A 400, 630 400, 630 400, 630 400, 630 400, 630 circuit-breaker panels
current Ir 1) for bus sectionalizer panel type LT2 A 400, 630 400, 630 400, 630 400, 630 400, 630
Rated short-time for switchgear with tk = 1 s up to kA 20 25 20 25 20 25 20 25 20
withstand current Ik for switchgear with t = 3 s (option) up to kA 20 – 20 – 20 – 20 – 20
k
Rated peak withstand current Ip up to kA 50 63 50 63 50 63 50 63 50
Rated short-circuit making current Ima up to kA 50 63 50 63 50 63 50 63 50
Rated normal for feeder (for panel types LS …) A 400, 630 400, 630 400, 630 400, 630 400, 630
current Ir 1) for bus sectionalizer panel type LT1 A 400, 630 400, 630 400, 630 400, 630 400, 630
Rated short-time for switchgear with tk = 1 s up to kA 20 25 20 25 20 25 20 25 20
withstand current Ik for switchgear with t = 3 s up to kA 20 – 20 – 20 – 20 – 20
k
Rated peak withstand current Ip up to kA 50 63 50 63 50 63 50 63 50
Rated short-circuit making current Ima up to kA 50 63 50 63 50 63 50 63 50
Rated short-circuit breaking current Isc 4) up to kA 20 25 20 25 20 25 20 25 20
Electrical at rated normal current 10 000 operating cycles
service life of
3AH vacuum at rated short-circuit breaking current 50 make-break operations
circuit-breakers
Busbar earthing panel type SE, busbar voltage metering panel type ME3
Switchgear installation
Wall-standing arrangement
– Single row
– Double row (for face-to-face
aaarrangement)
Room dimensions
See opposite dimension
drawings
Door dimensions
The door dimensions depend
on the
– Number of panels in a
transport unit
– Design with or without
low-voltage compartment
Switchgear fastening
• For floor openings and fixing
points of the switchgear,
see pages 34 and 35
• Foundations:
– Steel structure
– Steel-reinforced concrete
Panel dimensions
See pages 28 to 32
Weight
The weight of a panel depends
on the extent to which it is
equipped (e.g. with motor
operating mechanism, voltage
transformer). For details,
please refer to page 6.
1
aa Room planning
HA41-2286e eps
Switchgear room
Cable
basement
Side view
Top view
³15
775
1070
10
10
1 Relief opening
2 Room height
³1000
³1000
³1000
³ 50
³ 50
5
6
7
8
9
10
11
12
16
17
18
2300*
19
19
Top view
115
Side view
³15
*
890
828
834
Cable basement
Technical Data
300
basement corresponding to
the cable bending radius
11 Cable
12 Direction of pressure relief
13 Option:
Pressure absorber duct
14 Base height of the pressure
absorber duct beneath the
panel
15 Depth of the pressure absorber
duct behind the panel
16 Wall distance
17 End wall
18 Panel width
HA41-2287e eps
12
13
14
15
13
5
Switchgear Type 8DH10 up to 24 kV, SF6-Insulated, Extendable
Technical Data
Transport of combinations of different individual panels or panel blocks Busbar voltage metering panel
Comprising Overall width B3 B2 T2
– a number of individual panels or Billing metering panel
£ 850 mm 1.08 1.60 / 2.20 1.10 1.90 / 2.61 2) + 60 ***
– 1 panel block or
– a number of panel blocks or £ 1200 mm 1.40 1.60 / 2.20 1.10 2.46 / 3.39 2) + 70 ***
2) + 85 *** Billing metering busbar connection
– individual panels with panel blocks £ 1800 mm 2.03 1.60 / 2.20 1.10 3.57 / 4.91
2) + 100 ***
panel for cable connection
£ 2350 mm 2.55 1.60 / 2.20 1.10 4.49 / 6.17
Billing metering panel
Transport units for shipping (plan view) with combined transformers
1) The net weight depends on 2) Sum of the * Low-voltage compart- ** The weights depend on the Cable connection/transformer panel block
the extent to which it is equipped net weights ment, 600 mm high, weights of the mounted (cable panel with make-proof
(e.g. with current transformers, of individual weight approx. 60 kg transformers earthing switch)
motor operating mechanism, deep panels and / depending on the panel
cable compartment cover) and or panel blocks type and on the extent *** Packing weight
is therefore given as mean value to which it is equipped
Product Range
Equipment features
Panel Type r
to h
width • Basic equipment r m n ec itc
to is n r or sw
Additional equipment c n o f g or
° e ha isc to
(option), further additional onn ec -d n ec NO thin ect
h 2 r nn
equipment on request isc m itc on d ea
h -d tin
g
s w isc an of isco on r ker
d ” o
– Not available itc on er
a nt n h- D pr h-d iti to
sw ed op ism tme itio itc HE ke- itc -pos r itch n ec brea
s
n ew e n r po sw R T a sw e e sw on uit-
s itio s cr e
th ha pa
c m ee- al ion /EA d m ion thre reak ng isc circ
o / v e r c t n t i d
-p r e o co h ri si ED . a si en it-b rth h h-
ee lac ab g m al r t ct o c o c itc um
hr ove in p p. atin in r fo ele e-p LOS -dis e-p twe ircu f ea wit sw acu ase
t m e re
to t h “C itch thr l b m e e c o s r
r
fo ent ked
c om er er ro to n v le
l c op s t ica mo r t r r e u -p tion ica itio for re
ism rtm r lo
c
ina he e a ind r re n fo C fo n sw fo pan acu ake osi ind pos m ted t
n rm t h e fo io N io ism r v m -p lt e- is ra n
ha mpa ove t te ls in nic vic O) icat +1 osit an ake and for ree fau hre han ope tme
ec c s er h e - c ps
m e co ent cke e a ina tag
e -r s (1N ind 2NO e-p ec t-br tor out r th rth or t me er par r lam
g l a
r ic h m l fo e ( e m i c - o a f m e c
tin ab tm b er vo y- tch ic h hr g cu ne lock ce f or e out ting for com cov le
ra r c ar le e n e t w- se ad wi erv itc r t tin cir on i t - a s e e b
ope fo mp cab tag tag e lo lea . re g s r-s sw ) fo era in isc ing dev cui lock per tran tag tag d ca ry ent
l ck o s l l t re an llin y-fo iary N” rop ock h-d rth ng -cir ng r o nt- vol vol te nda pm
ua lo le c il a -vo -vo ara nt h a il E o l c a i rt i o e - - n i
an nter ab -ra ow ow ep hu ec ign read ux OP ot nter wit e-e ock ho los ot urr ow ow ou ecoequ
M I C C L L S S M S A “ M I s D L S C M C L L M S
Column No. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23
• • – • • – – – • – – – –
350 RK-. . ., RK1
• • – – • – – – •
° ° ° – –
° °– ° – –
° ° °– °
350 RK-U
– – • • • – – – •
° °– °– – –
°– °– – –
° ° °
350 K
– – • – • – – – •
° – – – –
°
– – – – –
° ° °– °
350 K-U
– – – –
° – – –
° ° °
350 K •
•
•
• –
•
–
•
• – – –
•
•
° ° – – –
° °– –– –
–
–
–
° ° °– °
350 K-U
– – –
° ° –
° ° ° °
500 TR •
•
•
• –
•
– –
•
• –
° •
•
° ° ° –
° ° –– –– –
–
–
–
° ° °– °
500 TR-U
• • – • – • –
° •
° ° ° –
° ° – – – –
° ° °
500 TR-V
• • – – – • –
° •
° ° ° –
° ° – – – –
° ° °– °
500 TR/V
• • – • – – –
° •
° ° ° °– ° °• °– °
500 LS1-. . .
• • – – – – –
° •
° ° ° ° –
° °– ° ° ° • –
°– °
500 LS1-U
• • – • – – –
° •
° ° ° ° –
° ° ° ° • –
°
500 LS2-. . .
• • – – – – –
° •
° ° ° ° –
° °– ° ° ° • –
°– °
500 LS2-U
• – • – – – –
° •
° ° ° ° –
°• – °– ° ° • – –
°
500 LT1
• – • – – – –
° •
° ° ° ° – • – –
° ° • – –
°
500 LT1-V
• – • – • – –
°– •
° ° ° °– –
° °
• – – – – –
°
500 LT2
° ° ° ° ° °
• • – – • – – – • – – – • – – – – –
350 SE1
• • – – • – – – •
° ° – – – • – – – –
° ° –
°
500 SE2
• – • – • – – – •
° ° – – – – – –
° ° –
°
500 ME3
° ° ° ° ° ° °
– – – – – – – – – – – – – – – – –
850 ME1
– –
•
• • – –
•
• – – – – – – – – – – – –
° ° – °
850 ME1-K
– – • – – – • – – – – – – – – – – – –
° ° °– °
850 ME1-S
– – • • – – • – – – – – – – – – – – –
° ° °
850 ME1-KS
– – • – – – – – – – – – – – – – – – –
° ° °– °
600 ME2
° ° °
Column No. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23
– – – – •1) 1) – – – – –
• • • •
700 R-B2
• • – • • – – – •1)
°) 1
° ° – –
° ° – – –
° ° ° °
1050 R-B3
• • – • – – – •1)
°) 1
° ° –
° °– – – –
° ° ° °
1000 T-B2
• • – • – – –
° •1)
°) 1
° ° –
° ° – – – –
° ° ° °
1500 T-B3
• • – • • – –
°– •1)
°) 1
° ° –
°– ° – –
° ° ° °
700 RT-B2
RK
• • – • 2) – – 1)
°)
1
° ° –
° °– °– – –
° ° ° °
T
• • – • • – –
°– •1) 1
° ° –
°– ° – –
° ° ° °
1050 2RT-B3
RK
• • – • 2) – – 1)
°)
1)
° ° –
° °– °– – –
° ° ° °
T
• • – • • – –
°– •)1 1)
° ° –
°– ° – –
° ° ° °
1400 3RT-B4
RK
• • – • 2) – – 1)
°
1)
° ° –
° °– °– – –
° ° ° °
T
– – • • • – –
°– • 1) 1)
°– °– –
°– °– – – –
° ° ° °
700 KT-B2
K
• – – • 2) – – 1)
°
1) –
°– – – –
° ° ° °
T
• • – • • – –
°– •1) 1
°– °– –
°– °– – – –
° ° ° °
700 KT-B2
K
• • – • 2) – – 1)
°)
1) –
°– – – –
° ° ° °
T
° ° ° ° ° ° ° ° °
1) The equipment applies to the entire panel block, 2) Low-voltage terminals arranged in the low-voltage niche
but it is located in the first feeder panel from the left of the ring-main or cable feeder
Product Range
HA41-2218_1c eps
HA41-2223_1c eps
Type RK1
500 mm wide
HV HRC fuse
option option option
Capacitive
voltage detection
system
**
option Type RK-K * option Type K-K * option Type TR-V *
350 mm wide 350 mm wide 500 mm wide
HA41-2219_1d eps
HA41-2214_1d eps
HA41-2224_1c eps
Cable-type current
for 2nd cable for 2nd cable with plug-in transformer
voltage trans-
formers
4MT8 plug-in
voltage transformer
option Type RK-A * option Type K-A * option Type TR-V * at the connection
350 mm wide 350 mm wide 500 mm wide
HA41-2220_1c eps
HA41-2215_1c eps
HA41-2225_1c eps
HA41-2226_1c eps
surge arrester
for transfer option for transfer for transfer
HA41-2278e eps
Make-proof
earthing switch
cover required
** Cable-type
current
transformer
on the
2nd cable:
For 300 mm
deeper
cable
compartment
cover
8 Siemens HA 41.11 · 2003
Switchgear Type 8DH10 up to 24 kV, SF6-Insulated, Extendable
Product Range
HA41-2232_1c eps
switch-disconnector
700 mm wide 700 mm wide
consisting of consisting of
2 ring-main panels 1 ring-main panel and
1 transformer panel
HV HRC fuse
Capacitive
voltage detection
system
RK RK RK RK RK TR *
HA41-2278e eps
Type R-B3 Type 2RT-B3
HA41-2233_1c eps
HA41-2229_1c eps
RK RK RK TR *
Type 3RT-B4
HA41-2234_1c eps
1 transformer
1000 mm wide panel
consisting of
2 transformer panels
Designs Designs
• Busbar connection system for connection of individual • Busbar connection system for connection of individual
panels or panel blocks: Arranged in the left-hand panel of the panels or panel blocks: Arranged in the left-hand panel of the
panel block (therefore extendable at a later date) panel block (therefore extendable at a later date)
• Only either the left-hand or the right-hand panel of the panel block • Only either the left-hand or the right-hand panel of the panel block
can be designed as a transfer panel with busbar connection can be designed as a transfer panel with busbar connection
• Panel blocks are also available without a busbar connection • Panel blocks are also available without a busbar connection
system (extendable at a later date only via the cable feeder) system (extendable at a later date only via the cable feeder)
Product Range
HA41-2244_1d eps
HA41-2236_1d eps
HA41-2242_1d eps
Three-position
switch-disconnector
option option option option
** **
Capacitive
voltage detection
system
Type LS1 Type LS1-K * Type LS2 Type LS2-K *
500 mm wide 500 mm wide 500 mm wide 500 mm wide **
Basic panel for 2nd cable Basic panel for 2nd cable
Three-phase current
transformer on the
bushing or cable-type
current transformer
option on the cable
option option option
HA41-2239_1c eps
HA41-2245_1c eps
4MT8 plug-in voltage
transformer at the
cable connection
option option option option
4MT3 plug-in
voltage
transformer
Type LS1-A * Type LS1-V * Type LS2-A * Type LS2-V * at the busbar
500 mm wide 500 mm wide 500 mm wide 500 mm wide
with plug-in with plug-in with plug-in with plug-in
surge arresters voltage trans- surge arresters voltage trans-
or limiters formers or limiters formers
Cable (not
included in the
scope of supply)
HA41-2246_1c eps
scope of supply)
for transfer for transfer
to the right to the right
HA41-2278e eps
Product Range
Bus sectionalizer panels, busbar earthing panels and busbar voltage metering panel as individual panels
HA41-2252_1a eps
option
HA41-2254_1c eps
HA41-2248_1b eps
Three-position
switch-disconnector
option
Capacitive
voltage detection
system
Type LT1 Type SE1 Type ME3
500 mm wide 350 mm wide 500 mm wide
Cable-type
with vacuum current trans-
circuit-breaker former on the
screened busbar
option
HA41-2249_1d eps
Make-proof
earthing switch
option
4MT3 plug-in
voltage
transformer
at the connection
HA41-2278e eps
Type LT1-V
500 mm wide 4MT3 plug-in
with vacuum voltage
circuit-breaker and transformer
plug-in voltage at the busbar
transformers
HA41-2253_1c eps
option
HA41-2250_1b eps
option
Product Range
Billing metering panels Billing metering panels as end Billing metering panels for
(standard) panels, for cable connection busbar connection
low structure low structure low structure Current trans-
option option former, cast-resin
option P1 P2 insulated
HA41-2258_1b eps
HA41-2262_1a eps
HA41-2266_1b eps
P2 P2
Voltage transformer,
1) cast-resin insulated
P1 P1
or on request:
Voltage transformer,
cast-resin insulated,
with HV HRC fuses
Scheme 1 Scheme 1 Scheme 1
Type ME1, 850 mm wide Type ME1-K, 850 mm wide Type ME1-S, 850 mm wide
for transfer to the right for transfer to the right for busbar metering Voltage trans-
former, cast-resin
insulated
option option option P1 P2
HA41-2263_1a eps
HA41-2267_1b eps
HA41-2259_1b eps
Fixed points
1) for busbar
earthing
P2 P2
HA41-2278d eps
P1 P1
Cable (not
included in the
Scheme 2 Scheme 2 Scheme 2 scope of supply)
Type ME1, 850 mm wide Type ME1-K, 850 mm wide Type ME1-S, 850 mm wide P1 and P2
for transfer to the right, for transfer to the right, for busbar metering, are terminal
transformer terminals transformer terminals transformer terminals designations
interchanged interchanged interchanged of the current
transformer
option option option P2 P1
HA41-2264_1a eps
HA41-2436_1 eps
HA41-2260_1b eps
1)
P1 P1
P2 P2
Type ME1, 850 mm wide Type ME1-K, 850 mm wide Type ME1-S, 850 mm wide
for transfer to the right for transfer to the right for busbar metering,
transformer terminals
interchanged
option option option P2 P1
HA41-2265_1a eps
HA41-2437_1 eps
HA41-2261_1b eps
P1 P1
1)
P2 P2
Type ME1, 850 mm wide Type ME1-K, 850 mm wide Type ME1-S, 850 mm wide
for transfer to the right, for transfer to the right, for busbar metering,
transformer terminals transformer terminals transformer terminals
interchanged interchanged interchanged
Note Note
Schemes 1 to 4 also feasible Schemes 1 to 4 also feasible
for transfer to the left for transfer to the left
Product Range
Billing metering panels as end Billing metering panels Billing metering panels *
panels, for cable connection as individual panels, for cable with metal-enclosed
low structure connection, low structure combined transformers Current trans-
former, cast-resin
HA41-2276_1d eps
option option P1 P2 insulated
HA41-2268_1d eps
HA41-2473 eps
2)
P2 P2 Voltage transformer,
3)
cast-resin insulated
P1 P1 or on request:
1) 1)
Voltage transformer,
cast-resin insulated,
with HV HRC fuses
Scheme 1 Scheme 1 Scheme 1
Type ME1-KS, 850 mm wide Type ME1-KK, 850 mm wide Type ME2, 600 mm wide
4MK plug-in
for transfer to the right for cable connection for transfer to the right combined current
transformer,
metal-enclosed
HA41-2277_1d eps
option option P1 P2 3)
HA41-2269_1d eps
HA41-2474 eps
2)
1) 1) 4MK plug-in
3)
combined voltage
P2 P2 transformer,
metal-enclosed
P1 P1
Fixed points
Scheme 2 Scheme 2 Scheme 2 for busbar
earthing
Type ME1-KS, 850 mm wide Type ME1-KK, 850 mm wide Type ME2, 600 mm wide
HA41-2278e eps
for transfer to the right, for cable connection, for transfer to the right,
transformer terminals transformer terminals transformer terminals
interchanged interchanged interchanged
Cable (not
HA41-2438_1b eps
HA41-2475 eps
scope of supply)
1) 2)
1) P1 and P2
are terminal
P1 3)
P1 designations
of the current
P2 P2 transformer
Type ME1-KS, 850 mm wide Type ME1-KK, 850 mm wide Type ME2, 600 mm wide
for transfer to the right for cable connection for transfer to the left
HA41-2439_1b eps
option option P2 P1
HA41-2271_1d eps
HA41-2476 eps
2)
P1 P1
3)
P2 P2
1) 1)
Type ME1-KS, 850 mm wide Type ME1-KK, 850 mm wide Type ME2, 600 mm wide
for transfer to the right, for cable connection, for transfer to the left,
transformer terminals transformer terminals transformer terminals
interchanged interchanged interchanged
Design
HA41-2280c eps
HA41-2279d eps
61 1 61
1
2 31
32 34
33
3 23 3
11 11
4 38 23
12 12
5 24 5 35
13 13
6 6
14 7 14
7 15 15
15 15
8
9 25 9 36
16 16
17 17 37
26
18 18
10 27 10 27
19 28 19 28
20 20
29 29
21 21
22 22
Type RK Type TR
40 7 Mimic diagram
11 8 Option: Short-circuit / earth-fault indicator
9 Sockets for voltage detection system
39
39
10 Arrangement of the busbars
6 11 Feeder designation label
12 Option: Locking device for three-position
41 switch-disconnector
7 42 13 Manual operation for the mechanism of
62 the earthing function
14 Manual operation for the mechanism of
the load-break function
15 Interlock of the cable compartment cover
16 Arrangement of the cable connections
17 Busbar system
22
18 Switchgear vessel filled with SF6-gas
30
19 Busbar connection
Type ME1 20 Pressure relief device
Design
Vacuum circuit-breaker:
45 Opening for the hand crank
– for closing with manual operating mechanism
– for emergency operation with motor operating
mechanism
46 Operating mechanism box
47 Mechanical “ON” pushbutton (not supplied with
61 spring-operated mechanism)
48 Mechanical “OFF” pushbutton
56 49 Operating cycle counter
50 “Spring charged” indicator
57
51 Vacuum interrupter
52 Switch position indication
Components
Components
Components
Three-position switch-disconnectors
Features
• Switch positions: CLOSED –
OPEN – EARTHED
• Switching functions as
general-purpose switch-
R-HA41-012 eps
disconnector (class E3)
according to
– IEC 60 265-1
– VDE 0670 Part 301
– IEC 62 271-102
– VDE 0670 Part 2/EN 60 129
(Standards see page 39)
• Designed as a multi-chamber
switch incorporating the
functions
– Switch-disconnector and
– Make-proof earthing switch
• Operation via a gas-tight
welded bushing at the front
of the switchgear vessel
Three-position switch-disconnector
EARTHED
HA41-2288a eps
OPEN
SF6-insulation
1 2 3 4 5 6 CLOSED
Components
Busbars
Features
• Safe-to-touch as a result of
use of metal covers
R-HA41-017a eps
• Plug-in type
• Consisting of round-bar
copper, insulated by means
of silicone rubber
• Busbar joints with cross and
end adapters, insulated by 2 8
means of silicone rubber
• Insensitive to pollution and 3
condensation
• Switchgear extension or
panel replacement is possi- 7
ble without SF6-gas work
• Special busbar connections
to metering panels type ME1
are possible. Connection to
the
– Cable connection bushings
of the adjacent panel Busbar compartments over 2 panels
with busbar connections, busbar covers removed
or to the
– Busbar bushings
• Busbar arrangement in panel
blocks within the switchgear 7
vessel filled with SF6-gas
HA41-2289b eps
8
• Option: Screened busbar:
– Field control by means of 9
electrically conductive layers
on the silicone-rubber
insulation (both internally 1 10
and externally); 2
– Installation of 4MC70 32
current transformers is thus 3
possible 4
• Option: Capacitive voltage 5
detection system for the
busbar, refer also to the
Top view
product range, pages 8 6
to 13
Busbar system
1 End adapter
2 Cross adapter
3 Busbar insulation of silicone rubber
4 Threaded bolt M12 / M16
5 Busbar, Cu, diameter 32 mm
6 Stopper
Switchgear vessel
7 Primary enclosure panel 1
8 Primary enclosure panel 2
9 Bushing
10 Capacitive tap at the bushings,
earthed (standard)
Components
4MT3 * and 4MT8 * plug-in voltage transformers for panel types LS, TR, SE and ME3
Panel section
type LS2-V
HA41-2290b eps
R-HA41-019 eps
R-HA41-018a eps
4MT3 plug-in
voltage
1
transformer
(for the busbar)
R-HA41-020 eps
4MT8 plug-in
voltage
transformer
(at the cable
1 4MT3 * for the busbar 4MT8 plug-in voltage transformer connection)
2 4MT8 * at the cable connection mounted on cable T-plug (in panel type LS1-V)
Components
R-HA41-021b eps
HA41-2291b eps
R-HA41-022 eps
4MC63 three-phase
current transformer
1 4MC63 three-phase 4MC63 three-phase current transformer
current transformer on the bushings of the cable connection
Components
4MC70 33 and 4MC70 31 cable-type current transformers for panel types LS, RK and TR
R-HA41-025 eps
R-HA41-023a eps
HA41-2292b eps
H
4MC70 31 cable-type
current transformer
R-HA41-024 eps
H
4MC70 33 cable-type
current transformers,
4 different overall heights
2 2
1 1
*
• Secondary connection by
Rated continuous max. 1.2 x IN Rated continuous max. 1.2 x IN
means of a terminal strip thermal current ID thermal current ID
inside the panel
• Only for shielded cables Transient overload 1.5 x ID / 1 h or Transient overload 1.5 x ID / 1 h or
current 2 x ID / 0.5 h current 2 x ID / 0.5 h
Installation Rated peak withstand unlimited Rated peak withstand unlimited
current Idyn current Idyn
• 4MC70 33 cable-type current
transformer for panel type LS Secondary data Secondary data
• 4MC70 31 cable-type current Rated current 1 A (option: 5 A) Rated current 1 A (option: 5 A)
transformer for panel types Meas- Class 0.2 0.5 1 Meas- Class 1
RK and TR uring Overcurrent factor FS10 (option: FS5) uring Overcurrent factor FS5 (option: FS10)
core core
• Arranged outside the switch- Rating 2.5 VA to 10 VA Rating 2.5 VA to 10 VA
gear vessel around the cable Pro- Class 10 P 5P Option: Secondary tap 1:2
at the panel connection tection Overcurrent factor 10 10
core
• Transformers mounted on a Rating 2.5 VA to 10 VA
supporting plate at the fac-
Option: Secondary tap 1:2
tory; final assembly around (e.g. 150 A – 300 A)
the cables on site
Dimensions Dimensions
• For double cable: 300 mm
deeper cable compartment Overall height H, mm 50 100 170 285 Overall height H 89 mm
dependent on the
cover core data
* Max. 230 mm, depending on Outside diameter 145 mm Width x Depth 85 mm x 114 mm
the core data of the 4MC70 33 Inside diameter 55 mm Inside diameter 40 mm
cable-type current transformer,
overall heights 170 and 285 mm For cable diameter 50 mm For cable diameter 36 mm
(observe floor openings on page 34)
Other values on request Other values on request
Components
4MC70 32 bus-type current transformers for panel type LT (for screened busbars only)
Panel section
type LT1
HA41-2293b eps
R-HA41-026a eps
R-HA41-027 eps
1
4MC70 32 bus-type
1 4MC70 32 bus-type current transformer
current transformer 4MC70 32 bus-type current transformer,
mounted on screened busbars, in some cases
between the panels
Components
4MA7 current transformers and 4MR voltage transformers
for air-insulated billing metering panels type ME1
R-HA41-028 eps
R-HA41-029a eps
Panel section type ME1
HA41-2294c eps
4MR14 voltage
1 transformer
R-HA41-030a eps
2
4MA7 current
transformer
1 4MR voltage transformer 4MR voltage transformers and
2 4MA7 current transformer 4MA7 current transformers installed in
billing metering panel type ME1
Components
4MK * metal-enclosed combined transformers
for billing metering panels type ME2
R-HA41-032 eps
R-HA41-031a eps
1
1 4MK3
Panel section type ME2 combined
voltage
HA41-2295b eps
transformer
2 4MK1
combined
1 current
transformer
2
4MK combined
transformer
1 4MK3 combined voltage 4MK combined transformers installed in
transformer billing metering panel type ME2
2 4MK1 combined current
transformer
Technical data
4MK1 combined current transformer 4MK3 combined voltage transformer
Features
Primary data Primary data
• 4MK * combined
Max. equipment operating 12 kV 24 kV Max. equipment operating 12 kV
transformer, comprising voltage Um voltage Um (= 1.2 x UN)
– 4MK1 combined current
transformer Rated short-duration 28 kV 50 kV Rated voltage UN at max. 3.3/ 3 kV at 10 kV
power-frequency rated short-duration 3.6/ 3 kV at 10 kV
– 4MK3 combined voltage withstand voltage power-frequency
transformer 4.8/ 3 kV at 20 kV
withstand voltage
Rated lightning impulse 75 kV 125 kV 5.0/ 3 kV at 20 kV
• According to IEC 60 044-3/ withstand voltage 6.0/ 3 kV at 20 kV
VDE 0414 Part 5 6.6/ 3 kV at 20 kV
Rated current IN 50 A to 600 A
7.2/ 3 kV at 20 kV
• Designed as single-pole, Rated thermal short-time up to 25 kA
10.0/ 3 kV at 28 kV
combined indoor trans- withstand current Ith
11.0/ 3 kV at 28 kV
formers
Rated lightning impulse 75 kV
Rated continuous up to 1.2 x IN
• Metal-enclosed withstand voltage
thermal current ID
• Insulation class E Rated voltage 1.9 x UN
factor (8 h)
• Inductive type Rated peak withstand max. 2.5 x Ith
current Idyn Max. equipment operating 24 kV
• Secondary connection by voltage Um (= 1.2 x UN)
means of screw-type Secondary data
Rated voltage UN at max. 13.8/ 3 kV at 38 kV
terminals Rated current 1 A or 5 A rated short-duration 15.0/ 3 kV at 38 kV
Meas- Class 0.2 0.5 1 power-frequency
17.5/ 3 kV at 50 kV
Panel type ME2 uring Overcurrent factor FS5 or FS10
withstand voltage
20.0/ 3 kV at 50 kV
core 22.0/ 3 kV at 50 kV
• For combination with Rating 10 VA to 15 VA
left-hand panels Pro- Class 10 P Rated lightning impulse 125 kV
– As individual panels or tection Overcurrent factor 10 withstand voltage
– As panel blocks (on request) core Rated voltage 1.9 x UN
Rating 5 VA or 15 VA factor (8 h)
• For combination with
Secondary multi-ratio option
right-hand panels as end function Secondary data
panels or panel blocks
Rated voltage 100/ 3 V
110/ 3 V
Rated voltage for auxiliary 100/3 V
winding (option) 110/3 V
Rating 30 VA 75 VA 150 VA
Class 0.2 0.5 1
Components
Cable connection
Features
Cable connection · Examples
• Bushings with outside cone
• Uniform cable connection L1 L2 L3 L1 L2 L3
Cable connections in
height 575 mm ring-main panels
• With cable bracket, e.g. 1 Prepared for cable
type C40 according to plugs with bolted
contact (M16)
DIN EN 50 024 1 2
3 2 Phase L1:
• Access to the cable con- Make: Euromold,
nection compartment only if 4 type K400 LB as
the feeder has been isolated cable elbow plug
and earthed 3 Phase L2:
Make: Euromold,
Special features type K400 TB as
cable T-plug
– In ring-main panels
4 Phase L3:
– In circuit-breaker panels
R-HA41-034 eps
R-HA41-033 eps
Make: Euromold,
– In cable panels: type AGT 20/630 as
• With bolted contact (M16) cable T-plug
as interface type “C” Cable connection compartment, Cable plugs with For options A, B, C
according to EN 50181/ supplied without cable clamps bolted contact (M16) and E, see below
DIN EN 50181
• For thermoplastic- L1 L2 L3 L1 L2 L3 Cable connections in
insulated cables circuit-breaker panels
• For paper-insulated 5 Prepared for cable
mass-impregnated cables plugs with bolted
with adapter systems contact (M16)
5 6
• For conventional cable 6 Phase L1:
7
Elbow adapter,
sealing ends via elbow make: Siemens,
8
adapter AKE 20/630 type AKE 20/630
(make Siemens)
7 Phase L2:
• For cable T-plugs or cable Make: Euromold,
elbow plugs with bolted type K400 TB as
cable T-plug
contact
8 Phase L3:
• For connection cross-
R-HA41-035 eps
R-HA41-036 eps
Make: Euromold,
sections up to 300 mm² type AGT 20/630 as
(standard) cable T-plug
• Cable routing downwards, Cable connection compartment, Cable plugs with For options A, B, C,
cable connection at front supplied without cable clamps bolted contact (M16) E and F, see below
R-HA41-038 eps
Components
Low-voltage equipment
Low-voltage compartment
Low-voltage compartment
• Height
– Standard 600 mm
– Option 900 mm
• Safe-to-touch
compartmentalization from 1
the high-voltage part of the
panel
2 3
• Installation on the panel:
– Standard for circuit-breaker
panels type LS and bus
sectionalizer panel type LT1
– Option for all other panel 4
types, depending on the
R-HA41-041a eps
R-HA41-039a eps
R-HA41-040 eps
7SJ63 1 LEDs
Low-voltage cables
• Control cables of the panel to
the low-voltage compartment
R-HA41-042 eps
aa
28
2000 (2300)*
2000 (2300)*
2000 (2300)*
350
350
Cable panel
type K
500
1400
Ring-main panel
type RK
1400
Transformer panel
type TR
1
3
1400
³15
HA41-2299d eps
³15
HA41-2300c eps
³15
aa
Switchgear Type 8DH10 up to 24 kV, SF6-Insulated, Extendable
312
312
553
515
~560**
600 (900)*
312
553
~560**
600 (900)*
~520**
747
775
747
775
747
775
60
40
60
40
60
~565
40
575
575
2000 (2300****)
2000 (2300****)
500
500
1400
Circuit-breaker panel
type LS1
1400
Circuit-breaker panel
type LS2
HA41-2302b eps
³15
312
215 110 110
* Option:
With low-voltage compartment
** Dependent on the type of
cable plug
*** Available mounting depth
for low-voltage equipment
**** Option: With high
low-voltage compartment 900 mm
600 (900****)
553
~560**
600 (900****)
553
~560**
747
775
747
775
426***
426***
~565
40
~565
40
Switchgear Type 8DH10 up to 24 kV, SF6-Insulated, Extendable
Dimensions
HA41-2304b eps
HA41-2303b eps
HA41-2305b eps
2000 (2300)*
2000 (2300)*
2000 (2300)*
1400
1400
1400
RK RK RK RK RK TR TR
HA41-2307b eps
HA41-2308b eps
2000 (2300)*
2000 (2300)*
2000 (2300)*
1400
1400
1400
TR TR TR RK TR RK RK TR
HA41-2310b eps
2000 (2300)*
2000 (2300)*
1
Cable panel type K:
2 1 Option: Earthing function
1400
1400
aa
2000 (2300****)
2000 (2300)*
30
500
Bus sectionalizer
panel type LT1
500
500
1400
1400
Bus sectionalizer
panel type LT1-V
1400
Bus sectionalizer
panel type LT2
1
HA41-2311b eps
³15
HA41-2312b eps
³15
HA41-2313c eps
³15
aa
Switchgear Type 8DH10 up to 24 kV, SF6-Insulated, Extendable
312
215 110 110
312
215 110 110
215 110 110
600 (900****)
600 (900****)
600 (900)*
312
747
775
747
775
747
775
426***
426***
40
40
60
40
2000 (2300)*
500
Voltage metering
panel type ME3
1400
1
600 (900)*
312
747
775
60
40
Busbar earthing panels
as individual panels
a 2000 (2300)*
2000 (2300)*
350
Earthing
500
Earthing
1400
* Option:
1400
HA41-2316c eps
³15
HA41-2317c eps
³15
600 (900)*
312
600 (900)*
312
747
775
747
775
60
40
60
40
2000 (2300)*
Only individual
panel or panel block 1)
on the left
HA41-2477 eps
Connection
at the busbar
* Option:
Switchgear Type 8DH10 up to 24 kV, SF6-Insulated, Extendable
600
Billing metering
panel type ME2
1400
Metering panel combination
1
Billing metering
panel
type ME2
600
HA41-2323d eps
³15
1 Cover screwed on
600 (900)*
312
Individual panel
or panel block
on the right
Connection
at the busbar
747
775
339***
31
Dimensions
aa
32
2000 (2300)*
255
850
Billing metering
panel type ME1
1 Cover screwed on
* Option:
255
1400
³15
a
Switchgear Type 8DH10 up to 24 kV, SF6-Insulated, Extendable
747
775
60
675
40
1135
2000 (2300)*
2000 (2300)*
2000 (2300)*
255
255
255
850
Billing metering
panel type ME1-K
850
Billing metering
panel type ME1-S
850
Billing metering
panel type ME1-KS
255
255
255
1400
1400
1400
1
HA41-2320d eps
³15
1
HA41-2321d eps
³15
1
HA41-2322e eps
³15
312
215 110 110
312
600 (900)*
~145**
600 (900)*
600 (900)*
215 110 110
~600
747
775
747
775
747
775
60
675
40
60
675
40
60
675
40
1135
1135
1135
Switchgear Type 8DH10 up to 24 kV, SF6-Insulated, Extendable
Dimensions
1400
or KT-B2 (in TR-U panel)
• Types attached on the right
with connection at the busbar
HA41-2441a eps
Possibility 2
• Types attached on the left
Possiblity 2 with connection at the busbar
Only Billing metering Individual panel – Individual panel type
individual panel, panel or panel block, RK, K, TR, LS1, LS2, SE1, SE2, ME3 or LT
on the left type ME1 on the right
– Panel blocks cannot be attached
• Types attached on the right
with connection at the feeder
– Individual panel type
RK-U, K-U, TR-U, LS1-U or LS2-U
– Panel block type
R-B2 or R-B3 (in RK-U panel),
1400
Possibility 3
• Types attached on the left
with connection at the busbar
850 – Individual panel type
Connection Connection
at the busbar at the feeder ** RK, K, TR, LS1, LS2, SE1, SE2, ME3 or LT
– Panel blocks cannot be attached
Possiblity 3 • Types attached on the right
with connection at the busbar
Only Billing metering Individual panel
– Individual panel type
individual panel, panel or panel block, RK, K, TR, LS1, LS2, SE1, SE2, ME3 or LT
on the left type ME1-S on the right – Panel block type
R-B2, R-B3, T-B2, T-B3, RT-B2, 2RT-B3, 3RT-B4
or KT-B2
1400
HA41-2443a eps
1
aa
³15
1
³15
34
Dimensions
480
150480
150
HA41-2325d eps
HA41-2326d eps
³15 480
150
HA41-2327c eps
HA41-2328c eps
31
233 122 69
47 197
31
233 122 69
47 197
31
233 122 69
47 197
31
233 122 69
47 197
35
10
19
40
35
10
19
40
35
10
19
40
15
35
19
40
a
a
a
Switchgear Type 8DH10 up to 24 kV, SF6-Insulated, Extendable
175
350
110 110
106 100
270
150 150
250
131
420
55
623
500
150 150
600
300
520
28 x 14
250
500
55
623
55
63
623
14 x 28
713
610
28 x 14
14 x 28
713
425
28 x 14
55
623
4
2
4
63
63
50 135
14 x 28
713
610
28 x 14
4
2
4
2
4
5
63
4
2
4
• For ring-main panels
type RK
• For cable panels
type K
• For busbar earthing
panel
type SE1
• For circuit-breaker
panel types LS1 and LS2
each without cable-type
current transformer
• For transformer
panels type TR
• For bus sectionalizer
panels type LT
• For busbar earthing
panel type SE2
• For busbar voltage
metering panel type ME3
• For circuit-breaker
panel types LS1 and LS2
each with cable-type
current transformers
1
³15
1
³15
1
HA41-2329c eps
480
150
HA41-2330d eps
480
150
HA41-2331d eps
31
233 122 69
47 197
31
233 122 69
47 197
31
233 122 69
47 197
35
19
40
35
10
19
40
35
10
19
40
275
256
175
110 110
106 100
40
350
150 150
1 Wall distance
500
255
620
For panel blocks
250
40
850
300
770
700
40
350
19
312
1000
500
920
255
110 110
500
19
40
150 150
55
623
462
55
623
713
610
28 x 14
14 x 28
713
610
14 x 28
63
623
4
2
14 x 28
713
28 x 14
63
610
4
2
4
• For billing metering
–
–
–
–
panels
Type ME1
Type ME1-K
Type ME1-S
Type ME1-KS
• For ring-main
panel block
type R-B2
• For ring-main/
transformer
panel block
type RT-B2
• For cable connection/
transformer
panel block
type KT-B2
• For transformer
panel block
type T-B2
aa
³15
1
³15
1
³15
1
480
150
HA41-2332d eps
480
150480
150
HA41-2333d eps
HA41-2334d eps
31
233 122 69
47 197
31
233 122 69
47 197
31
233 122 69
47 197
35
10
19
40
35
10
19
40
35
10
19
40
a
Floor openings (dimensions in red) and fixing points
175
106 100
40
110 110
350
110 110
106 100
350
350
175
40
250
150 150
500
1 Wall distance
4 Fixing points
350
40
1050
40 40
350
110 110
19
350
970
40 40
350
110 110
19
500
350
500
19
1400
1320
40
150 150
350
500
19
350
40
110 110
312
40 40
110 110
1500
1420
19
40
350
55
623
350
110 110
40
500
19
150 150
462
14 x 28
713
610
28 x 14
40
63
4
55
623
55
14 x 28
713
610
28 x 14
623
63
14 x 28
713
610
28 x 14
63
4
2
4
2
4
• For ring-main
panel block
type R-B3
• For ring-main/
transformer
panel block
type 2RT-B3
• For ring-main/
transformer
panel block
type 3RT-B4
• For trans-
former
panel block
type T-B3
Switchgear Type 8DH10 up to 24 kV, SF6-Insulated, Extendable
Dimensions
36
Dimensions
1
HA41-2479a eps
1
HA41-2480a eps
³15
1
HA41-2481a eps
31
233 122 69
47 197
480
150
480
150
480
150
31
35
10
19
40
15
233 122 69
197
31
233 122 69
110 197
42
31
233 122 69
aa
Switchgear Type 8DH10 up to 24 kV, SF6-Insulated, Extendable
35
10
19
40
35
10
19
40
35
10
19
40
175
106 100
350
110 110
270
320
175
110 110
270
110 110
106 100
175
350
270
110 110
106 100
~245*
270
55
623
~101*
4
14 x 28
713
28 x 14
55
648
8, 9
55
~190*
728
55
923
63
425
50 135
14 x 28
713
635
28 x 14
818
715
28 x 14
14 x 28
1013
28 x 14
63
63634
2
4
9, 10
900
4
8
4
• For ring-main panels
type RK
• For cable panels
type K
350
4
2
• For ring-main panels
type RK
• For cable panels
type K
175
350
14 x 28 4
2
• For ring-main panels
type RK
• For cable panels
type K
1
1
HA41-2482a eps
³15
420
HA41-2483a eps
³15
1
HA41-2484a eps
480
150
480
150
480
150
31
233 122 69
197
28 x 14 4
31
8, 9
For individual panels with double cable connection or surge arresters make Tyco Electronics Raychem, type RDA 24
233 122 69
110 197
42
For individual panels with double cable connection (panel depth 880 mm), 105 mm deeper cable compartment cover
4
2
31
233 122 69
65 150 130 197
For individual panels with double cable connection (panel depth 1075 mm), 300 mm deeper cable compartment cover
Legends and footnotes see page 37
35
10
35
10
19
40
35
10
19
40
250
500
150 150
250
500
150 150
250
420
500
150 150
~245*
713
635
14 x 28
818
715
28 x 14
14 x 28
1013
28 x 14
63
63
63
900
4
2
4
2
4
8
4
2
4
• For ring-main panels
type RK1
• For circuit-breaker panels
type LS1 and LS2
215
122
233
47 197
215
122
233
47 197
215
122
233
197
65 150 130
19
40
19
40
19
40
aa
Floor openings (dimensions in red) and fixing points
b
~675***
~101*
~675**
~245*
c
b
c
b
115
713
28 x 14
115
719
115
1013
12
13
4
28 x 14
1128
28 x 14
550
200
834
550
514
1 Wall distance
of an individual panel or
panel block
3 Floor opening for high-
voltage cables and, if
applicable, control cables
4 Fixing points
834
a 11
12
4
2
8
11
7
2
a 11
2
12
3
4
For individual panels with double cable connection
• For ring-main panels
type RK and RK1
• For cable panels
type K
• For circuit-breaker panels
type LS1 and LS2
• For transformer panels
type TR
19
40
Switchgear Type 8DH10 up to 24 kV, SF6-Insulated, Extendable
~675***
~190*
Dimensions
a
c
b
115
824
a = Panel width
b = Width of
550
343
28 x 14
floor opening
c = Fixing
(values see
pages 34 and 35)
939
11
2
12
4
Dimensions
63
HA41-2489 eps
63
aaa
HA41-2339c eps
Switchgear Type 8DH10 up to 24 kV, SF6-Insulated, Extendable
Cable connection in
ring-main panel
553***
~560**
610
747
~560**
610
775
Standard cable compartment cover
HA41-2340c eps
553***
747
775
38
63
553***
~560**
150 mm deeper
715
852
880
553***
~560**
900
1047
1075
~190**
~245**
2
575
3
4
18
19
18
575
575
HA41-2342c eps
63
HA41-2343c eps
63
HA41-2344e eps
63
HA41-2345c eps
63
Cable connection with
surge arresters
553***
~560**
610
747
775
Standard cable compartment cover
553***
~560**
610
747
~560**
775
Standard cable compartment cover
553***
610
25 mm deeper
772
800
300****
553***
~560**
610
150 mm deeper
897
925
575
7
575
8
575
10
9
575
11
12
HA41-2346c eps
63
HA41-2490 eps
63
HA41-2347c eps
63
Connection in
circuit-breaker panel
560
610
~560
747
775
13
575
Standard cable compartment cover
553***
635
747
775
290*
101
14
15
575
553***
~560**
610
150 mm deeper
897
925
17
1 Elbow adapter, make: Siemens,
type AKE 20/630 with
conventional cable sealing end,
make: Corning Cables, type IAE 20
7 Cable plug,
make: Tyco Electronics Raychem,
type RICS 5139
8 Surge arrester,
make: Tyco Electronics Raychem,
type RDA 21 (for type RDA 24,
a floor opening of 635 mm
instead of 610 mm is required)
9 Cable T-plug,
make: ABB Energiekabel,
type SET (12/24)
and
10 Surge arrester
make: ABB Energiekabel,
type MUT (13/23)
or:
9 Cable connector, make: nkt cables,
type AB 24-630
and
10 Surge arrester
make: nkt cables, type ASA 24-5
13 Busbar system
for billing metering panel
type ME1
14 Cable T-plug,
make: nkt cables, type CB 24-630
15 Coupling connector,
make: nkt cables, type CC 24-630
16 Cable T-plug,
make: Euromold, type K400 TB
17 4MT8 plug-in voltage transformer
18 Cable T-plug,
make: ABB Energiekabel,
type SET 24
19 Coupling insert,
make: ABB Energiekabel,
type KU 23.2
Switchgear Type 8DH10 up to 24 kV, SF6-Insulated, Extendable
Standards
Standards
The 8DH10 switchgear
complies with the relevant
standards and specifications
applicable at the time of
type tests.
In accordance with the
harmonization agreement
reached by the countries of the
European Community, their
national specifications
conform to the IEC standard.
Responsible for
Technical contents:
1) Circuit-breaker
Christoph Maul
2) Disconnector and earthing switch Siemens AG,
3) Switch-disconnector Dept. PTD M2 S2
4) Switch-disconnector / Erlangen
fuse combination
General editing:
5) Voltage detection systems Gabriele Pollok
6) HV HRC fuses Siemens AG,
Dept. PTD CC T
Erlangen
* In future, these standards
will be summarized in IEC 62 271 Printed in Germany
(switching devices and switchgear) KGK 06.03 11.0 VO/- 36 En
100637 6101/D6269
** Standard withdrawn
Siemens HA 41.11 · 2003 39
If you have any questions about
Power Transmission and Distribution,
our Customer Support Center
is available around the clock
Tel: +49 180 / 524 70 00 (Subject to changes,
Fax: +49 180 / 524 24 71 e.g.: 12 ct/min.)
E-Mail: support@ptd.siemens.de
www.siemens.com/ptd-support
Published by
Siemens AG
Power Transmission and Distribution
Medium Voltage Division
Postfach 32 20
91050 Erlangen
Germany