T R 1 - Testing Distance Relays
T R 1 - Testing Distance Relays
T R 1 - Testing Distance Relays
1. Introduction
The DVS3 mk2 and 50A-3PH may be used to generate impedances for testing distance relays.
Using these units the relay zone boundaries may be tested and the trip time of each zone
ascertained.
In testing distance relays, the 50A-3PH acts as a simple current source, supplying 3 phase current
to the relay under test and a phase reference to the DVS3. The magnitude and phase angle of the
voltage is controlled on the DVS3 to give the desired impedance. The impedance may either be
varied continuously or in steps.
RX Diagram
100
80
60
40 Mho
X
20
0
-20 0 20 40 60 80 100
-20
R
50.00
40.00
30.00
20.00 Zone 1
Zone 2
10.00
Zone 3
0.00 Zone 4
-100.00 -80.00 -60.00 -40.00 -20.00 0.00 20.00 40.00 60.00 80.00 100.00 PSIA
-10.00
-20.00
-30.00
VT Ratio: 230kV/110V
CT Ratio: 1000/1A
Many older distance relays work in terms of secondary voltages, currents and impedances.
Most numerical distance protection works in terms of primary system voltages, currents and
impedances.
RatioVT
Z sec = Z pri .
RatioCT
RatioCT
Z pri = Z sec .
RatioVT
e.g The line positive sequence above is 48.42 79.41 as a primary system impedance. To
calculate this expressed as an impedance referred to the CT & VT secondary, carry out the
following calculation:
RatioVT
Z sec = Z pri .
RatioCT
230000 / 110
Z sec = 48.42
1000 / 1
Z sec = 101.379.41
The relay is tested by applying a series of impedances to the relay by leaving the current fixed and
altering the voltage magnitude and phase angle using the DVS3. By typing in values for the
voltage, step changes of impedance can be generated which step from outside of the trip zone of
the relay to inside of any of the zones. The trip time of the relay then indicates which zone has
operated. A series of points can be defined which will exercise the relay and verify the position of
the zone boundaries.
60.00
50.00
40.00
30.00
Zone 1
20.00 Zone 2
Zone 3
10.00
Zone 4
0.00 PSIA
-100.00 -80.00 -60.00 -40.00 -20.00 0.00 20.00 40.00 60.00 80.00 100.00 Test vector 1
-10.00
-20.00
-30.00
-40.00
To test a relay exhaustively, test vectors must be set up to verify all boundaries of the relay zones.
This is necessary for commissioning, but may not be required for maintenance testing, where a few
vectors will verify operation of the relay and the position of the boundaries.
60.00
A
50.00
B
40.00 C
D
Zone 1
30.00 E Zone 2
F Zone 3
20.00 G Zone 4
H PSIA
Test vector 1
10.00
0.00
-10.00 10.00 30.00 50.00 70.00 90.00
-10.00
Set the phase angle for the test vector on the DVS3. This remains constant
throughout the test on a particular vector.
Switch on the current on the 50A-3PH, and set each phase to the test current (In or
other suitable value).
Apply an initial impedance to the relay outside all zones (point A on figure 4) by setting
the voltage on the DVS3 to an appropriate value. This point is always on the angle of
the test vector, and placed outside the outermost zone of operation.
Apply the test impedance (for example point B on figure 4) by entering the new
voltage on the test vector using the keypad on the DVS3. The relay will trip in the
time appropriate for the zone, and the trip time will be displayed on the DVS3.
Reset the DVS3 to the initial out of zone impedance ready for the next test point. The
DVS3 timer will show the relay reset time.
After each test point it is important to return the impedance to the out of zone impedance to reset
the relay ready for the next test point. Detailed instructions may be found in section 5 Test
Procedures.
V
Z =
I
For example, if we inject a current of 1A and apply a voltage of 100V at 29, the following
impedance is generated:
100
Z =
1
= 100
V = I .Z
For example, if the impedance to be generated is 10030 (100 at 30) and the test current is
1A, the required voltage may be calculated as follows:
V = I .Z
= 1A.100
= 100V
The phase angle of the voltage will be the same as the phase angle of the impedance, so the
voltage is 10030V.
Z = 86.6 2 + 50 2
= 100
50
= tan 1
86.6
= 30
The voltage and phase angle may then be calculated as in section 4.1.1.1. Alternatively, the
voltage may be calculated in complex notation, and then converted to magnitude and phase values.
5. TEST PROCEDURES
It is advisable to decide on the number of test vectors and test points required to effectively test the
relay before starting to test. These points can then be converted to currents, voltages and phase
angles using the calculation spreadsheet. The calculated test points are then applied to the relay in
turn and the operation of the relay verified. If the relay impedances are given as primary system
values, these will have to be converted to impedances referred to the VT and CT secondary values.
Figure 5. Connections
Before making any connections, ensure that the system under test is dead and earthed.
Connecting to a live system may result in personal injury or equipment damage.
WARNING
Connect the output from the DVS3 to the voltage coil of the relay.
Connect the 50A-3PH to the current coils of the relay, observing polarity of each coil.
Connect the T&R link output from the 50A-3PH to the T&R link input of the DVS3
using T&R Link Lead 1. This locks the phase relationship between the DVS3 and the
50A-3PH.
The relay will also require an auxiliary supply (not shown in figure 5).
An auxiliary supply of 110Vac or 230Vac is available from the 50A-3PH to power the relay, and if
other voltages are required, a range of optional auxiliary supply converters are available.
60.00
A
50.00
40.00
Zone 1
30.00 Effect of reducing voltage
20.00
Relay trip PSIA
Test vector 1
10.00
0.00
-10.00 10.00 30.00 50.00 70.00 90.00
-10.00
Connect contact input 1 of the DVS3 to the contacts relating to the zone under test.
Set the phase angle for the test vector on the DVS3.
Switch on the current on the 50A-3PH, and set each phase to the test current (In or
other suitable value).
Apply an initial impedance to the relay outside all zones (point A on figure 6) by setting
the voltage on the DVS3 to an appropriate value. This point is always on the angle of
the test vector, and placed outside the outermost zone of operation.
Slowly decrease the DVS3 voltage until the relay trips. The result is accurate for a
zone with instantaneous trip time, but dependant on the rate of change of voltage on a
zone with delayed operation. Zones with delays require a much slower approach to
the trip value.
Calculate the impedance at the trip point from the voltage and current (Z=V/I). The
angle of the impedance is the same as the angle of the voltage.
Set the phase angle for the test vector on the DVS3.
Switch on the current on the 50A-3PH, and set each phase to the test current (In or
other suitable value).
Apply an initial impedance to the relay just outside the zone boundary under test
(point A on figure 7) by setting the voltage on the DVS3 to an appropriate value using
the keypad. The relay should trip in the time appropriate to the zone in which the
impedance lies (zone 4 in figure 7).
Type in a new voltage value on the DVS3 that should cause the relay to trip in the
next zone (point B, zone 3 on figure 7). The relay should trip in the zone 3 delay time.
If the relay has tripped as expected, take a point mid-way between the two test points
and enter this voltage. If this trips the relay in the same time as point A, apply the
next point mid-way between point B and C. If it trips the relay in the same time as
point B, apply the next test mid-way between point A and B.
The aim is to reduce the impedance between two tests so that points either side of
the zone boundary but adjacent to it are found.
Calculate the impedance at the zone boundary from the voltage and current (Z=V/I).
The angle of the impedance is the same as the angle of the voltage.
60.00
50.00
A
C
40.00 D
B E
Zone 1
30.00 Zone 2
Zone 3
20.00 Zone 4
PSIA
Test vector 1
10.00
0.00
-10.00 10.00 30.00 50.00 70.00 90.00
-10.00
60.00
A
50.00
B
40.00
C Zone 1
30.00 Zone 2
Zone 3
D
20.00 Zone 4
PSIA
Test vector 1
10.00 E
0.00
-10.00 10.00 30.00 50.00 70.00 90.00
-10.00
Switch on the current on the 50A-3PH, and set each phase to the test current (In or
other suitable value).
Apply an initial impedance to the relay just outside all of the zones of operation (point
A). The relay should not trip.
Type in a new voltage value on the DVS3 that should cause the relay to trip in the
outer zone (point B, zone 4 on figure 8). The DVS3 timer will display the zone 4 trip
time.
Type in the point A voltage to return the relay to its non-tripped state. The DVS3 timer
will display the relay reset time.
Repeat the process for each of the other test points for the other zones.
This spreadsheet is designed for Excel 97 onwards. Please note that Excel must have the Analysis
ToolPak installed for this spreadsheet to function. To check that the analysis toolpak is installed, go
to the Tools menu and select Add-Ins. Check that Analysis TooPak is checked in the dialogue
box that appears. If not, tick the box and click OK.
Values that may be changed on the spreadsheet appear as bold red values in boxes. If other
values are typed over or altered, the calculation functions of the spreadsheet may stop working.
To use these facilities, enter the following parameters into the spreadsheet as shown in figure 9:
Rated current in A
The CT and VT ratio is calculated and displayed along with the primary values.
In addition, the required test current from the 50A-3PH is entered at this point. This may be the
nominal CT secondary current, or another value if this is not acceptable. This value is used
throughout the impedance calculations in the sections below.
A drop-down box is provided in this section to select between primary and secondary impedances.
If the Primary option is selected, impedances are entered and displayed referred to the power
system values. If Secondary is selected impedances are referred to the secondary values of the
CT and VT.
The table displays the current to be injected from the 50A-3PH and the voltage magnitude and
phase angle to be generated by the DVS3. If the Primary impedance option is selected in the first
section of the spreadsheet, the impedance values are taken to be primary values. The table also
displays the system voltages and currents that the impedance relates to.
Values are entered for the relay positive sequence impedance angle and the point at which the
characteristic crosses the R and X axis for each zone. Zone 1 and zone 2 may also have a
directional characteristic selected.
The relay zones are then plotted, and the test vectors from table 1 and table 2 plotted on the graph.
If you have any comments or questions about this procedure or the associated spreadsheet, please
contact Ian Lake, ilake@trtest.com.
T&R Test Equipment Ltd, Keens Lane, Worplesdon, Guildford, Surrey, GU3 3JS, UK
www.trtest.com