01 VESDA HLI Access Protocol VHX-0320 A4 TDS Lores
01 VESDA HLI Access Protocol VHX-0320 A4 TDS Lores
01 VESDA HLI Access Protocol VHX-0320 A4 TDS Lores
VHX-1320 Wall-Mounted
Features
Direct access and monitoring of your
entire VESDAnet network
Seamless data transfer
Easily configured using Xtralis
configuring and monitoring software
packages
Listings/Approvals
VESDA HLIs are recommended for
monitoring only. They are not approved by
VESDA Access High Level Interface Xtralis for use as a primary reporting device.
The VESDA Access High Level Interface (HLI) integrates VESDAnet1 networks with
Protocol Supports
host monitoring platforms such as Building Management Systems (BMSs) and Fire
Alarm Control Panels (FACPs). VESDA VLP, VLS, VLC, VLF, VLI
The Access HLI acts as a proxy for all VESDA devices on the VESDAnet network, and VFT-15 range of Detectors
providing access to the rich status information available from VESDA detectors as well Alarm Status
as the ability to control and configure these devices. The Access HLI is able to report
Fault Status
alarms to the host within a few seconds of a detector reaching an alarm condition.
Exact performance is dependent on the polling strategy and size of the monitored Smoke Level
network. The Access HLI is able to support up to 100 VESDA detectors on a single Detailed Fault Information
VESDAnet network.
Alarm Thresholds
In its simplest configuration, the Access HLI provides a simple Master/Slave interface
Detector Control including Reset,
which allows the host to monitor and control the VESDA devices on a VESDAnet
Disable, Silence, Alarm Test and
network.
Normalise
The Access HLI also supports a subscription mechanism allowing the host to be
Operational Status for processes
asynchronously notified of changes in the status of the monitored VESDA devices on
such as Normalisation and
a VESDAnet network. The host will be notified whenever the state of a device changes
AutoLearn
such as an alarm or fault condition being raised.
Asynchronous notification of the
VHX-1320 Wall-Mounted Access HLI device state including alarm level,
The wall-mounted version is housed in a metal enclosure allowing for permanent detailed faults and current thresholds
mounting on a flat surface. With a built-in VESDAnet interface you dont need a
remote VESDAnet socket module making the wall-mounted HLI a cost effective
solution to your interface requirements.
VHX-0320 Access HLI
A standard unit used to provide a flexible solution where permanent mounting is not
required. In this case a VESDAnet socket interface is required to connect the HLI onto
the VESDAnet network.
1
VESDAnet is a propriety communications protocol allowing your VESDA range of smoke detectors, displays, programmers and remote units (collectively
known as devices) to communicate with each other on the one network. VESDAnet is a fault tolerant bi-directional protocol. This means that if one direction
of communication fails, then your VESDAnet messages are transmitted in the opposite direction.
VESDA Access HLI VHX-0320 Standard
VHX-1320 Wall-Mounted
Dimensions Specifications
Power Consumption:
1.68 W (Quiescent)
Supply Voltage:
(H)
24 VDC
(H)
Current Consumption:
70 mA (Quiescent)
Number of Detectors Supported:
Up to 100 detectors
(W) (W)
Standard:
Standard Wall Mounted Dimensions (WHD):
188 mm x 98 mm x 40 mm
(7.4 in. x 3.9 in. x 1.6 in. approx.)
Example VESDAnet system with Access Protocol HLI
Weight:
0.4 kg (0.9 lbs)
Remote Display VESDA VLF VESDA VLS VESDA VLP
Wall Mounted:
Dimensions (WHD):
280 mm x 185 mm x 55 mm
RS-485
VESDAnet Socket (11 in. x 7.3 in. x 2.2 in. approx.)
(VRT-300)
Weight:
2 kg (4.4 lbs)
Access HLI Supplied With:
(VHX-0320) VESDAlink RS-232 9-way serial cable
RS-232
(malefemale).
VESDAnet
VESDA Subrack
RS-232
Wall-Mounted
Access HLI HOST
(VHX-1320)
Ordering Information
Product Part number
VESDA Access HLI Standard VHX-0320
VESDA Access HLI Metal Box Wall-mounted VHX-1320
VESDAlink RS-232 9-way serial cable VSP-509 (Spare part)
VESDAnet RS-485 15-way cable VSP-511 (Spare part)
www.xtralis.com
The Americas +1 781 740 2223 Asia +852 2916 8876 Australia and New Zealand +61 3 9936 7000
UK and Europe +44 1442 242 330 Middle East +962 6 588 5622
The contents of this document are provided on an as is basis. No representation or warranty (either express or implied) is made as to the
completeness, accuracy or reliability of the contents of this document. The manufacturer reserves the right to change designs or specifications
without obligation and without further notice. Except as otherwise provided, all warranties, express or implied, including without limitation any
implied warranties of merchantability and fitness for a particular purpose are expressly excluded.
This document includes registered and unregistered trademarks. All trademarks displayed are the trademarks of their respective owners.
Your use of this document does not constitute or create a licence or any other right to use the name and/or trademark and/or label.
This document is subject to copyright owned by Xtralis AG (Xtralis). You agree not to copy, communicate to the public, adapt, distribute, transfer,
sell, modify or publish any contents of this document without the express prior written consent of Xtralis.