Enve 4003
Enve 4003
Enve 4003
Please find attached our ENVE 4003 (Air Pollution & Emissions control) lab report on
Stationary combustion and Emissions Control (Experiment 2). The experiment, performed on
Friday, November 4th 2016, was carried out to determine the composition of NOx emissions
from the Carleton university heating plant, with the use of basic material and energy balance
methods. This report includes our data, calculations, and the discussion of results.
If you have any questions regarding the report, please do not hesitate to contact any member of
our team.
Sincerely,
2
3. Figures, Tables and Equations must be centered and numbered
4. Captions also justified
5. Page numbered
6. Reference list must be prepared according to APA standards
7. Section titles bold and numbered and double-spaced
8. Do not allow the word processor to split a table or a caption
9. Indicate each section written by whom
Fossil fuels are important for electricity generation, as they can be burned to yield large
amounts of energy. The combustion process of electricity generation entails the burning of fuels
in oxygen to produce CO2 and water [2]. Sources of fossil fuels may include coal, petroleum, and
natural gas in form of methane. Depending on the working fluid and the capacity of electricity
generation, the type of boiler used may differ from one application to another. Incomplete
combustion results in the generation of unburned hydrocarbons, the formation of CO, and the
generation of NOx compounds (NO and NO2). On the other hand, complete combustion results
[3]. The amount of air required for complete combustion to take place is referred to as the
theoretical air, and any amount of air above this threshold is considered excess air [6].
The experiment was carried out at the Carleton University maintenance building, where data on
the inlet and exit steam characteristics were obtained for the D-type watertube boilers at the
universitys central heating plant. The plant operates by emitting flames upwards into a cavity
comprising of a water tube layer, in order to allow hot gases to flow through the vertical tubes.
The heat generated from the flame, and the combustion gases are then transferred to the water
tubes through radiation and the water leg (convection) with both processes occurring
simultaneously. The transferred heat then converts the water to steam in the water tubes which is
3
then used to generate heat for the University [4]. Figure 4 shows a schematic representation of
4
Figure 3: Parameters obtained for the D-type boilers
Using the value obtained for the oxygen concentration, with the assumption that natural gas
consists only of methane, the excess air ratio for the plant was calculated to be 16.76%. The
values from table 1 for october were also used to determine the daily CO2 production in the plant
to be roughly 32,874.19 kg/day. Material and energy balance methods were used to calculate the
5
1. (Saptak) Using the measured oxygen concentration and assuming natural gas only
consists of methane, calculate the excess air ratio the plant is operating at
2. (Saptak) Using the values from table 1 of october, find the daily CO2 production in the
plant
3. (Jordan) Calculate the efficiency of the boiler with basic material and energy balance
methods. Also find the rate of energy lost via stack (as exhaust gases)
All heat was assumed to exit the boiler through exhaust air and steam.
The efficiency of the boiler was determined by:
The energy of each assumed component of the boiler process was determined by:
6
Therefore, the efficiency of the boiler is 91.4%.
4. (Hirlatu) Utilizing the emission factors from reference 3, estimate the total emissions of
NOx and CO from natural gas combustion at the universitys heating plant, compare the
number with those reported by Carleton University to NPRI for 2003
The total volume of Natural gas consumption in 2001/2002 fiscal year = 8291586 m3/yr
Total emission of NOx = Emission factor total volume of Natural gas consumption
= 2.243 10-3 kg/m3 8291586 m3/yr = 18598.03 kg/yr
Total emission of CO = 1.346 10-3 kg/m3 8291586 m3/yr = 11160.47 kg/yr
The value that was reported to NPRI by Carleton University for 2003 = 43 tonnes of NOx =
43000 kg of NOx. The value for total emission of NOx calculated above is lower than the value
of NOx reported to NPRI by Carleton University for 2003. In addition, there is no value for CO
found in the NPRI but it is reasonable to assume that the value will be higher than the calculated
value too.
5. (Hirlatu) What would be the concentration of NOx and CO in the stack gas, based on the
emission factor mentioned above?
Concentration = Mass/Volume
Based on the emission factor above, the emission factor of NOx is slightly higher than the
emission factor of CO. In addition, the concentration of NOx was found to be 2.243 ppm is
slightly higher than the concentration of CO, which was found to be 1.346 ppm. Therefore, this
can be concluded that the the higher the emission factor, the higher the concentration.
6. (Rosalia) What are your suggestions for reduction of CO2 production and emission of
NOx and CO?
In comparison with coal fired plants, natural gas plants are considered more beneficial to climate
change, owing to the fact that they tend to produce roughly 34 to 50 percent less emissions than
7
the former [2]. Considering that less CO2 emissions is beneficial for the environment, a few
suggestions can be considered to further reduce the production of CO2 and NOx. Through a
process known as carbon capture sequestration, carbon can be collected and returned to the earth
crust to prevent it from getting into the atmosphere [3]. The technology entails a three-step
process beginning with capturing CO2, transporting it, and then storing it securely in
underground formations such as deep aquifers, and depleted oil fields [1]. Experiments have
proven that from this process, a natural gas plant is capable of emitting CO2 of roughly 5 percent
of the amount that would be emitted from a coal plant without the technology [5]. Another
approach to curb the amount of GHG emissions (particularly NOx) would be to install a selective
catalytic reduction system (SCR). It is essentially a technology that works through the injection
of a reactant such as ammonia, alongside a catalyst, to treat and remove the exhaust gases from
REFERENCES
[1]"What is CCS? The Carbon Capture & Storage Association (CCSA)", Ccsassociation.org,
2016. [Online]. Available: http://www.ccsassociation.org/what-is-ccs/. [Accessed: 18- Nov-
2016].
[4] ENVE 4003 Lab 2 Instructions. (Carleton University, Ottawa) Fall 2016
8
[5] "Natural Gas with CCS - Fossil Transition Project", Fossiltransition.org, 2016. [Online].
Available: http://www.fossiltransition.org/pages/_copy_of__natural_gas_w_ccs/182.php.
[Accessed: 18- Nov- 2016].
[6] "How is excess air calculated? | Kane International Ltd", Kane International Ltd, 2016.
[Online]. Available: https://www.kane.co.uk/knowledge-centre/how-is-excess-air-calculated.
[Accessed: 16- Nov- 2016].
[7] Boiler NOx emissions and Energy Efficiency, Enovity Inc., 2010. [Online]. Available:
http://www.boilerenergyefficiency.com/forms/Boiler_NOx_and_Energy_Efficiency_2010.pdf
[Accessed: 15 - Nove-2016].
Assumptions made:
Feed water temp = 106.8 oC
All heat generated through combustion exits through exhaust and steam
Complete combustion present as per:
CH4 + O2 CO2 + H2O + heat
1 mol of CH4
Hrxn of methane = -802.3 kJ/mol
Stack temperature = 209.44 oC
Cp,steam = average Cp between 5 oC and 209.44 oC = 1.8845 kJ/kg K
Cp,CO2 = 0.844 kJ/kg K (Engineering Toolbox, 2016)
Cp,air = 1.01 kJ/kg K
Heat in exhaust gas (including exhaust air (16.7%) and N2 that did not react:
Efficiency: