Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

6AV21240MC010AX0 Datasheet en PDF

Download as pdf or txt
Download as pdf or txt
You are on page 1of 10

Data sheet 6AV2124-0MC01-0AX0

SIMATIC HMI TP1200 COMFORT, COMFORT PANEL, TOUCH


OPERATION, 12" WIDESCREEN-TFT-DISPLAY, 16 MIL. COLORS,
PROFINET INTERFACE, MPI/PROFIBUS DP INTERFACE, 12 MB
USER MEMORY, WINDOWS CE 6.0, CONFIGURABLE FROM
WINCC COMFORT V11

General information
Product type designation TP1200 Comfort

Display
Design of display TFT
Screen diagonal 12.1in
Display width 261.1mm
Display height 163.2mm
Number of colors 16777216
Resolution (pixels)
Horizontal image resolution 1280Pixel
Vertical image resolution 800Pixel
Backlighting
MTBF backlighting (at 25 C) 80000h
Backlight dimmable Yes; 0-100 %

Control elements
Keyboard fonts
Function keys
Number of function keys 0

6AV2124-0MC01-0AX0 Subject to change without notice


Page 1/10 10/09/2017 Copyright Siemens
Keys with LED No
System keys No
Numeric keyboard Yes; Onscreen keyboard
alphanumeric keyboard Yes; Onscreen keyboard
Touch operation
Design as touch screen Yes
Expansions for operator control of the process
DP direct LEDs (LEDs as S7 output I/O)
F1...Fx 0
Direct keys (keys as S7 input I/O)
F1...Fx 0
Direct keys (touch buttons as S7 input I/O) 40

Installation type/mounting
Mounting position vertical
Mounting in portrait format possible Yes
Mounting in landscape format possible Yes
maximum permissible angle of inclination without 35
external ventilation

Supply voltage
Type of supply voltage DC
Rated value (DC) 24V
permissible range, lower limit (DC) 19.2V
permissible range, upper limit (DC) 28.8V

Input current
Current consumption (rated value) 0.85A
Starting current inrush It 0.5As

Power
Active power input, typ. 20W

Processor
Processor type X86

Memory
Flash Yes
RAM Yes
Memory available for user data 12Mbyte

Type of output
Info LED No
Power LED No
Error LED No
Acoustics
Buzzer No

6AV2124-0MC01-0AX0 Subject to change without notice


Page 2/10 10/09/2017 Copyright Siemens
Speaker Yes

Time of day
Clock
Hardware clock (real-time) Yes
Software clock Yes
retentive Yes; Back-up duration typically 6 weeks
synchronizable Yes

Interfaces
Number of industrial Ethernet interfaces 1; 2 ports (switch)
Number of RS 485 interfaces 1; RS 422/485 combined
Number of RS 422 interfaces 0; together with RS485
Number of RS 232 interfaces 0
Number of USB interfaces 2; USB 2.0
USB Mini B 1; 5-pole
Number of 20 mA interfaces (TTY) 0
Number of parallel interfaces 0
Number of other interfaces 0
Number of SD card slots 2
With software interfaces No
Industrial Ethernet
Industrial Ethernet status LED 2
Number of ports of the integrated switch 2

Protocols
PROFINET Yes
Supports protocol for PROFINET IO Yes
IRT Yes; As of WinCC V12
MRP Yes; As of WinCC V12
PROFIBUS Yes
MPI Yes
Protocols (Ethernet)
TCP/IP Yes
DHCP Yes
SNMP Yes
DCP Yes
LLDP Yes
WEB characteristics
HTTP Yes
HTTPS Yes
HTML Yes
XML Yes
CSS Yes

6AV2124-0MC01-0AX0 Subject to change without notice


Page 3/10 10/09/2017 Copyright Siemens
Active X Yes
JavaScript Yes
Java VM No
Further protocols
CAN No
EtherNet/IP Yes
MODBUS Yes

EMC
Emission of radio interference acc. to EN 55 011
Limit class A, for use in industrial areas Yes
Limit class B, for use in residential areas No

Degree and class of protection


IP (at the front) IP65
Enclosure Type 4 at the front Yes
Enclosure Type 4x at the front Yes
IP (rear) IP20

Standards, approvals, certificates


CE mark Yes
cULus Yes
RCM (formerly C-TICK) Yes
KC approval Yes
Marine approval
Germanischer Lloyd (GL) Yes; As of product version: 10
American Bureau of Shipping (ABS) Yes; As of product version: 10
Bureau Veritas (BV) Yes; As of product version: 10
Det Norske Veritas (DNV) Yes; As of product version: 10
Lloyds Register of Shipping (LRS) Yes; As of product version: 10
Nippon Kaiji Kyokai (Class NK) Yes; As of product version: 10
Polski Rejestr Statkow (PRS) No
Use in hazardous areas
ATEX Zone 2 Yes
ATEX Zone 22 Yes
IECEx Zone 2 Yes
IECEx Zone 22 Yes
cULus Class I Zone 1 No
cULus Class I Zone 2, Division 2 Yes
FM Class I Division 2 Yes

Ambient conditions
Ambient temperature during operation
Operation (vertical installation)

6AV2124-0MC01-0AX0 Subject to change without notice


Page 4/10 10/09/2017 Copyright Siemens
For vertical installation, min. 0C
For vertical installation, max. 50C; (55 C, see entry ID: 64847814)
Operation (max. tilt angle)
At maximum tilt angle, min. 0C
At maximum tilt angle, min. 40C
Operation (vertical installation, portrait format)
For vertical installation, min. 0C
For vertical installation, max. 40C
Operation (max. tilt angle, portrait format)
At maximum tilt angle, min. 0C
At maximum tilt angle, min. 35C
Ambient temperature during storage/transportation
min. -20C
max. 60C
Relative humidity
Operation, max. 90%; no condensation

Operating systems
proprietary No
pre-installed operating system
Windows CE Yes

Configuration
Message indicator Yes
Alarm system (incl. buffer and acknowledgment) Yes
Process value display (output) Yes
Process value default (input) possible Yes
Recipe management Yes
Configuration software
STEP 7 Basic (TIA Portal) No
STEP 7 Professional (TIA Portal) No
WinCC flexible Compact No
WinCC flexible Standard No
WinCC flexible Advanced No
WinCC Basic (TIA Portal) No
WinCC Comfort (TIA Portal) Yes; from V11
WinCC Advanced (TIA Portal) Yes; from V11
WinCC Professional (TIA Portal) Yes; from V11

Languages
Online languages
Number of online/runtime languages 32
Project languages
Languages per project 32

6AV2124-0MC01-0AX0 Subject to change without notice


Page 5/10 10/09/2017 Copyright Siemens
Functionality under WinCC (TIA Portal)
Libraries Yes
Applications/options
Web browser Yes
Pocket Word Yes
Pocket Excel Yes
PDF Viewer Yes
Media Player Yes
SIMATIC WinCC Sm@rtServer Yes
SIMATIC WinCC Audit Yes
Number of Visual Basic Scripts Yes
Task planner
time-controlled Yes
task-controlled Yes
Help system
Number of characters per info text 70
Message system
Number of alarm classes 32
Bit messages
Number of bit messages 4000
Analog messages
Number of analog messages 200
S7 alarm number procedure Yes
System messages HMI Yes
System messages, other (SIMATIC S7, Yes
Sinumerik, Simotion, etc.)
Number of characters per message 80
Number of process values per message 8
Acknowledgment groups Yes
Message indicator Yes
Message buffer
Number of entries 1024
Circulating buffer Yes
retentive Yes
maintenance-free Yes
Recipe management
Number of recipes 300
Data records per recipe 500
Entries per data record 1000
Size of internal recipe memory 2Mbyte
Recipe memory expandable Yes

6AV2124-0MC01-0AX0 Subject to change without notice


Page 6/10 10/09/2017 Copyright Siemens
Variables
Number of variables per device 2048
Number of variables per screen 400
Limit values Yes
Multiplexing Yes
Structures Yes
Arrays Yes
Images
Number of configurable images 500
Permanent window/default Yes
Global image Yes
Pop-up images Yes
Slide-in images Yes
Image selection by PLC Yes
Image number in the PLC Yes
Image objects
Number of objects per image 400
Text fields Yes
I/O fields Yes
Graphic I/O fields (graphics list) Yes
Symbolic I/O fields (text list) Yes
Date/time fields Yes
Switches Yes
Buttons Yes
Graphic display Yes
Icons Yes
Geometric objects Yes
Complex image objects
Number of complex objects per screen 20
Alarm view Yes
Trend view Yes
User view Yes
Status/control Yes
Sm@rtClient view Yes
Recipe view Yes
f(x) trend view Yes
System diagnostics view Yes
Media Player Yes
HTML browser Yes
PDF display Yes
IP camera display Yes

6AV2124-0MC01-0AX0 Subject to change without notice


Page 7/10 10/09/2017 Copyright Siemens
Bar graphs Yes
Sliders Yes
Pointer instruments Yes
Analog/digital clock Yes
Lists
Number of text lists per project 500
Number of entries per text list 500
Number of graphics lists per project 500
Number of entries per graphics list 500
Archiving
Number of archives per device 50
Number of entries per archive 20000
Message archive Yes
Process value archive Yes
Archiving methods
Sequential archive Yes
Short-term archive Yes
Memory location
Memory card Yes
USB memory Yes
Ethernet Yes
Data storage format
CSV Yes
TXT Yes
RDB Yes
Security
Number of user groups 50
Number of user rights 32
Number of users 50
Password export/import Yes
SIMATIC Logon Yes
Logging through printer
Alarms Yes
Report (shift log) Yes
Hardcopy Yes
Electronic print to file Yes; PDF, HTML
Character sets
Keyboard fonts
US English Yes
Transfer (upload/download)
MPI/PROFIBUS DP Yes

6AV2124-0MC01-0AX0 Subject to change without notice


Page 8/10 10/09/2017 Copyright Siemens
USB Yes
Ethernet Yes
using external storage medium Yes
Process coupling
S7-1200 Yes
S7-1500 Yes
S7-200 Yes
S7-300/400 Yes
LOGO! Yes
WinAC Yes
SINUMERIK Yes; with SINUMERIK option package
SIMOTION Yes
Allen Bradley (EtherNet/IP) Yes
Allen Bradley (DF1) Yes
Mitsubishi (MC TCP/IP) Yes
Mitsubishi (FX) Yes
OMRON (FINS TCP) No
OMRON (LINK/Multilink) Yes
Modicon (Modbus TCP/IP) Yes
Modicon (Modbus) Yes
OPC UA Client Yes
OPC UA Server Yes
Service tools/configuration aids
Backup/Restore manually Yes
Backup/Restore automatically Yes
Simulation Yes
Device switchover Yes

Peripherals/Options
Peripherals
Printer Yes
SIMATIC HMI MM memory card: Multi Media Yes; Up to 128 MB
Card
SIMATIC HMI SD memory card: Secure Digital Yes; Up to 2 GB
memory card
SIMATIC HMI CF memory card Compact Flash No
Card
USB memory Yes
SIMATIC IPC USB Flashdrive (USB stick) Yes; Up to 16 GB
SIMATIC HMI USB stick Yes; Up to 8 GB
Network camera Yes

Mechanics/material

6AV2124-0MC01-0AX0 Subject to change without notice


Page 9/10 10/09/2017 Copyright Siemens
Enclosure material (front)
Plastic No
Aluminum Yes
Stainless steel No

Dimensions
Width of the housing front 330mm
Height of housing front 241mm
Mounting cutout, width 310mm
Mounting cutout, height 221mm
Overall depth 65mm

Weights
Weight without packaging 2.8kg
Weight incl. packaging 3.5kg

last modified: 10/05/2017

6AV2124-0MC01-0AX0 Subject to change without notice


Page 10/10 10/09/2017 Copyright Siemens

You might also like