Equipment Schedule - Ventilation Basement and 2Nd Floor A/C Ground Floor
Equipment Schedule - Ventilation Basement and 2Nd Floor A/C Ground Floor
Equipment Schedule - Ventilation Basement and 2Nd Floor A/C Ground Floor
EACH UNIT SHALL BE SUITABLE FOR CEILING SUSPENDED INSTALLATION AND SHALL BE
6 BASEMENT 3 COMPLETE WITH ALUMINUM CONSTRUCTED UNIVERSAL/SINGLE NOZZLE, SLIM TYPE
BASEMENT SUPPLY AND EXHAUST FANS SCHEDULE-BASEMENT 2 2,585 22 60 0.75 400 3 60
CENTRIFUGAL FAN, DIRECT DRIVE, STEEL CONSTRUCTED INTAKE SCREEN, G.I. STEEL CASING
AND STEEL HANGERS. MINIMUM THROW OF EACH UNIT SHALL BE 20M.
FAN DATA
UNIT ELECTRICAL EACH UNIT SHALL BE SUITABLE FOR CEILING SUSPENDED INSTALLATION AND SHALL BE
QTY. LOCATION DESCRIPTION POWER CHARACTERISTICS AREA SERVED MATCH LINE
DESIGNATION AIR FLOW E.S.P. REMARKS 6 BASEMENT 2 COMPLETE WITH ALUMINUM CONSTRUCTED UNIVERSAL/SINGLE NOZZLE, SLIM TYPE
TYPE DRIVE (V / PH / HZ) 2,585 22 60 0.75 400 3 60
(CFM) (in W.G.) CENTRIFUGAL FAN, DIRECT DRIVE, STEEL CONSTRUCTED INTAKE SCREEN, G.I. STEEL CASING
AND STEEL HANGERS. MINIMUM THROW OF EACH UNIT SHALL BE 20M.
EACH UNIT SHALL BE COMPLETE WITH WALL COLLAR, DYNAMICALLY BALANCED EACH UNIT SHALL BE SUITABLE FOR CEILING SUSPENDED INSTALLATION AND SHALL BE
EXHAUST WALL MOUNTED BASEMENT 1 COMPLETE WITH ALUMINUM CONSTRUCTED UNIVERSAL/SINGLE NOZZLE, SLIM TYPE
1 BASEMENT 2 16,442 0.26 DIRECT 2,980 WATTS 380 / 3 / 60 CARPARK BASEMENT 2 PROPELLER FAN, PILLOW BLOCK BEARING, WITH GREASING FACILITIES,TEFC 6 2,585 22 60 0.75 400 3 60
FAN PROPELLER TYPE DRIVE MOTOR, INLET GUARD, AND GRAVITY SHUTTER. CENTRIFUGAL FAN, DIRECT DRIVE, STEEL CONSTRUCTED INTAKE SCREEN, G.I. STEEL CASING
AND STEEL HANGERS. MINIMUM THROW OF EACH UNIT SHALL BE 20M.
TOILET 100
4 CEILING CASSETTE 0.18 DIRECT 73.8 W 230 / 1 / 60 WEIGHT=3.9 kg.
EXHAUST FAN
TOILET 100
4 CEILING CASSETTE 0.18 DIRECT 73.8 W 230 / 1 / 60 WEIGHT=3.9 kg.
EXHAUST FAN
TOILET 100
1 CEILING CASSETTE 0.18 DIRECT 73.8 W 230 / 1 / 60 WEIGHT=3.9 kg.
EXHAUST FAN
CYBERPARK TOWER 2
1 EQUIPMENT SCHEDULE - VENTILATION BASEMENT AND 2ND FLOOR; A/C GROUND FLOOR DRAWING PHASE:
M-01 SCALE: NTS
SEAL DESIGNER PROJECT TITLE LAND OWNER & DEVELOPER SHEET NO.
REPUBLIC ACT 9266
ALBERT S. YU
ARCHITECT
ROLANDO B. SANCHEZ
STRUCTURAL ENGINEER
FERDINAND L. FIGUEROA
PROFESSIONAL MECHANICAL ENGINEER
DIO ANTHONY C. FIGUEROA
SANITARY ENGINEER
JESUS M. MISSION
PROFESSIONAL ELECTRICAL ENGINEER
ROSENDO B. SANCHEZ
MECHANICAL ENGINEER
CYBERPARK
TOWER 2
ARANETA CENTER M 01
INCORPORATED TOTAL SHEETS
34