2.0 RESPONSIBLITIES
- Anyone working in testing location during commission stage must follow the safety
requirements as per SEC rules and CSD employees are responsible for applying
safety rules in all places which they working in.
- Project site engineer is responsible for committing the contractor to prepare testing
and commissioning places to be done in proper climate conditions as per Company
policies, procedures and accepted temperatures the relays, devices and test
equipment can be tested or operated within it.
- Any of CSD staff is responsible for testing activities according to approved
specification and design and he shall not start any test for any Transformer
Differential Protection relay (87T) until providing the following:
Reference / Criteria
Item Description
Limit
1. General Visual Inspection WI-NG-6460-002-056
CT ratios, and matching CT selection is correct for TX type
2.
(Star or Delta) and for Vector Group
Reference /
Item Description
Criteria Limit
As per WI-NG-
6460-002-057&
1. General Electrical Tests
WI-NG-6460-002-
058
Check Measurements:
2.
Secondary & primary current values for all phases.
Test through current restrain/stability for all phases and all
3.
types of faults
Test pick-up\drop off differential current Id> (without zero
4. sequence elimination and with it). For all phases and all types
of faults and transformer sides.
Test Pick-up\drop off differential current Id>>. For all phases
5.
and all types of faults and transformer sides.
6. Test Bias Characteristic for all phases and all types of faults
Test 2nd & 5th Harmonic restraint. For all phases and all types of
7.
faults
Test Cross Blocking Function. For all phases and all types of
8.
faults
Test negative sequence Relay Operating Angle ( if it is
9.
applicable)
Test sensitive negative sequence ( turn-to-turn fault ) ( if it is
10.
applicable)
Archiving System Website: http://AMAS TP-NG-6250-001-007
NATIONAL GRID
4.0 REFERENCES
Index Number /
Title
Reference Number
PR-NG-6460-002 Project Commissioning Procedure
WI-NG-6460-002-056 Protection Relays general mechanical checks & visual inspection
WI-NG-6460-002-057 Protection Relays general electrical tests
WI-NG-6460-002-058 Guidelines for Testing Digital& Numerical Protection & Control
Relays and IEDs
CL-NG-6460-002-074 Checklist for Transformer Differential Protection Relay (87T)
This document shall comply in accordance with the existing Companys Rules and Regulations.
Any modifications therein found not conformance with the document shall be declared invalid.
For clarification and verification on this document, contact the following:
Substation
Bay/Panel
Equipment Serial No