Datasheet

Surge arrester
POLIM-K

Document ID CHABB-104 EN 31.03.2010


Protection of
• Transformers
• Motors (case by case)
• Cables (case by case)
• Cable sheaths (case by case)
• other medium voltage equipment

Application
• AC
• Outdoor and Indoor
Technical Data
Metal oxide surge arrester without spark gaps. Direct moulded silicone housing, grey color. Designed and tested according to IEC 60099-4

Nominal discharge current In 8/20 µs 10 kA (pk)


Line discharge class 2
High current operating duty test Ihc 4/10 µs 100 kA (pk)
Long duration current impulse 500 A / 2000 µs
Short circuit rating Is 50 Hz 50 kA (rms) for 0.2 s
Classification according to IEEE (ANSI) C62.11 intermediate

The thermal stability of the MO-surge arrester is proved in the operating duty test according to LD2 which gives an energy input of 5.2 kJ/kV (Uc).

Power frequency voltage versus time characteristic (TOV) with prior energy input.
t = 1 s UTOV = 1.312 x Uc
t = 3 s UTOV = 1.285 x Uc
t =10 s UTOV = 1.258 x Uc

Ambient air temperature -60 to +40 °C (for higher values contact manufacturer)
Altitude up to 1800 m (for higher values contact manufacturer)
Frequency 50/60 Hz

Weather ageing tested according to series A (1000 h salt fog)

Uc Ur
Residual voltage (Ures) in kV (pk) at specified impulse current
Continuous
Rated
operating wave 1/ ... µs wave 8/20 µs wave 30/60 µs
voltage
voltage
kV (rms) kV (rms) 5 kA (pk) 10 kA (pk) 1 kA (pk) 2.5 kA (pk) 5 kA (pk) 10 kA (pk) 20 kA (pk) 125 A (pk) 250 A (pk) 500 A (pk)

4 5.0 13.0 14.7 10.9 11.7 12.4 13.4 14.9 9.7 10.0 10.3
5 6.3 16.2 18.3 13.6 14.5 15.4 16.7 18.6 12.1 12.5 12.9
6 7.5 19.4 21.9 16.3 17.4 18.5 20.0 22.2 14.5 14.9 15.4
7 8.8 22.7 25.7 19.1 20.3 21.6 23.4 26.0 17.0 17.5 18.0
8 10.0 25.9 29.3 21.7 23.2 24.7 26.7 29.7 19.4 19.9 20.6
9 11.3 29.1 32.9 24.4 26.0 27.7 30.0 33.3 21.7 22.4 23.1
10 12.5 32.3 36.5 27.1 28.9 30.8 33.3 37.0 24.1 24.9 25.6
11 13.8 35.6 40.2 29.9 31.8 33.9 36.7 40.8 26.6 27.4 28.2
12 15.0 38.8 43.8 32.5 34.7 36.9 40.0 44.4 29.0 29.8 30.8
13 16.3 42.0 47.4 35.2 37.6 40.0 43.3 48.1 31.4 32.3 33.3
14 17.5 45.3 51.1 38.0 40.5 43.1 46.7 51.9 33.8 34.8 35.9
15 18.8 48.5 54.8 40.7 43.4 46.1 50.0 55.5 36.2 37.3 38.5
16 20.0 51.6 58.4 43.3 46.2 49.2 53.3 59.2 38.6 39.8 41.0
17 21.3 54.9 62.1 46.1 49.2 52.3 56.7 63.0 41.0 42.3 43.6
18 22.5 58.1 65.7 48.8 52.0 55.4 60.0 66.6 43.4 44.7 46.1
19 23.8 61.3 69.3 51.5 54.9 58.4 63.3 70.3 45.8 47.2 48.7
20 25.0 64.5 72.9 54.1 57.7 61.5 66.6 74.0 48.2 49.7 51.2
21 26.3 67.8 76.6 56.9 60.7 64.6 70.0 77.7 50.7 52.2 53.8
22 27.5 71.0 80.2 59.6 63.5 67.6 73.3 81.4 53.0 54.7 56.3
23 28.8 74.2 83.9 62.3 66.4 70.7 76.6 85.1 55.4 57.1 58.9
24 30.0 77.5 87.6 65.0 69.3 73.8 80.0 88.8 57.9 59.6 61.5
25 31.3 80.7 91.2 67.7 72.2 76.9 83.3 92.5 60.3 62.1 64.0
26 32.5 83.9 94.8 70.4 75.1 79.9 86.6 96.2 62.7 64.6 66.6
27 33.8 87.2 98.5 73.2 78.0 83.0 90.0 99.9 65.1 67.1 69.2
28 35.0 90.4 102.1 75.8 80.9 86.1 93.3 103.6 67.5 69.6 71.7
29 36.3 93.6 105.7 78.5 83.7 89.1 96.6 107.3 69.9 72.0 74.2
30 37.5 96.8 109.4 81.2 86.6 92.2 99.9 110.9 72.3 74.5 76.8
31 38.8 100.1 113.1 84.0 89.5 95.3 103.3 114.7 74.7 77.0 79.4
32 40.0 103.2 116.7 86.6 92.4 98.3 106.6 118.4 77.1 79.5 81.9
33 41.3 106.4 120.3 89.3 95.3 101.4 109.9 122.0 79.5 81.9 84.5
34 42.5 109.7 124.0 92.1 98.2 104.5 113.3 125.8 82.0 84.5 87.1
35 43.8 112.9 127.6 94.8 101.1 107.6 116.6 129.5 84.4 86.9 89.6
36 45.0 116.1 131.2 97.4 103.9 110.6 119.9 133.1 86.7 89.4 92.1

ABB 2
Dimensions and Clearances
Dimensions (in mm)

Mechanical loads:
Torque moment 50 Nm
Tensile strength 1000 N
Bending moment MPSL 200 Nm
(Moment resulting from the force applied in the type test on the longest housing of the surge arrester

Housing 02 04 06 08
Uc
Creepage distance 395 mm 770 mm 1135 mm 1460 mm
4 04-02
5 05-02
6 06-02
7 07-02
8 08-02
9 09-02
10 10-02 10-04
11 11-02 11-04
12 12-02 12-04
13 13-04
14 14-04
15 15-04
16 16-04
17 17-04
18 18-04 18-06
19 19-04 19-06
20 20-04 20-06
21 21-04 21-06
22 22-04 22-06
23 23-04 23-06
24 24-04 24-06 24-08
25 25-06 25-08
26 26-06 26-08
27 27-06 27-08
28 28-06 28-08
29 29-06 29-08
30 30-06 30-08
31 31-06 31-08
32 32-06 32-08
33 33-06 33-08
34 34-06 34-08
35 35-06 35-08
36 36-06 36-08

Housing Creepage Flashover Recommended clearances Height H Weight Insulation withstand voltage
distance distance E min F min of empty housing
1.2/50 µs 50 Hz, 60 s wet
mm mm mm mm mm kg kV (pk) kV (rms)
02 395 198 151 173 199 < 2.0 120 35
04 770 318 277 297 319 < 3.4 200 54
06 1135 431 403 422 429 < 4.6 273 70
08 1460 551 403 422 549 < 5.6 320 92

3 ABB
For further information please contact: Note:
ABB Switzerland Ltd. We reserve the right to make technical changes
High Voltage Products or modify the contents of this document without
Surge Arresters prior notice. With regard to purchase orders,
Jurastrasse 45 the agreed particulars shall prevail. ABB AG
CH-5430 Wettingen/Switzerland does not accept any responsibility whatsoever
for potential errors or possible lack of informa-
Tel. +41 58 585 29 11 tion in this document. We reserve all rights in
Fax +41 58 585 55 70 this document and in the subject matter and
illustrations contained therein. Any reproduc-
Email: sales.sa@ch.abb.com tion, disclosure to third parties or utilization of
www.abb.com/arrestersonline its contents – in whole or in parts – is forbidden
without prior written consent of ABB AG.

Copyright© 2010 ABB


All rights reserved

Detailed information for dimensioning of our products see


following ABB documents:

Application Guidelines Overvoltage Protection in medium voltage systems


Application Guidelines Overvoltage Protection in railway facilities