Growatt 1000-3000-S User Manual
Growatt 1000-3000-S User Manual
Growatt 1000-3000-S User Manual
Growatt 1500-S
Growatt 2000-S
Growatt 2500-S
Growatt 3000-S
GR - UM - 033 - A - 03
Contents
1 About Manual
1.1 Validity
1.2 Target Group
1.3 Additional information
1.4 Symbols in this document
1.5 Glossary
2 Safety
2.1 Intended Use
2.2 Qualification of skilled person
2.3 Safety instruction
2.4. Assembly Warnings
2.5. Electrical Connection Warnings
2.6. Operation Warnings
3 Product Description
3.1. Overview
4 Unpacking
5 Installation
5.1. Safety instructions
10 Trouble Shooting
10.1 Warnings(W)
5.2. Selecting mounting location
10.2 Errors(E)
5.3. Mounting Inverter
5.4. Connect switch
5.5. Grounding
5.6. Connect grid type
11 Decommissioning
11.1. Dismantling the Inverter
5.7. Electrical connection
11.2. Packing the Inverter
8 Operation Modes
8.1. Waiting mode
8.2. Normal mode 14 Compliance Certificates
8.3. Fault mode
14.1. List
8.4. Shutdown mode
14.2. Download address
9 Maintenance and
Cleaning 9.1. Checking heat dissipation
9.2. Checking the DC switch 15 Contact
9.3. Cleaning the Inverter
About Manual 1
Manual Introduce and Copyright
1.1 . Validity
Copyright © 2010 Shenzhen Growatt New Energy Technology Co., Ltd,
All rights reserved.
This installation and user guide describes the assembly, installation,
No part of this document may be reproduced, stored in a retrieval system, commissioning, communication, maintenance, operating and failure search of the
or transmitted, in any form or by any means, electronic, mechanical,
following Growatt inverters:
photographic, magnetic or otherwise, without the prior written permission
of Shenzhen Growatt New Energy Technology Co., Ltd. Growatt 1000-S
Growatt 1500-S
Shenzhen Growatt New Energy Technology Co., Ltd makes no Growatt 2000-S
representations, express or implied, with respect to this documentation Growatt 2500-S*
or any of the equipment and/or software it may describe, including (with
no limitation) any implied warranties of utility, merchantability, or fitness Growatt 3000-S
for any particular purpose. All such warranties are expressly disclaimed.
Neither Shenzhen Growatt New Energy Technology Co., Ltd nor its Note “*”: Growatt 2500-S is designed only for UK.
distributors or dealers shall be liable for any indirect, incidental, or
consequential damages under any circumstances. This manual does not cover any details concerning equipment connected to the
Growatt ( e.g. PV modules). Information concerning the connected equipment is
(The exclusion of implied warranties may not apply in all cases under available from the manufacturer of the equipment
some statutes, and thus the above exclusion may not apply.)
All trademarks are recognized even if these are not marked separately.
Missing designations do not mean that a product or brand is not a 1.3. Additional information
registered trademark.
SHENZHEN GROWATT NEW ENERGY TECHNOLOGY CO.,LTD Find further information on special topics in the download area at
Building B, Jiayu Industrial Park, #28, GuangHui Road, Shiyan Street, www.ginverter.com
Baoan District, Shenzhen, P.R.China The manual and other documents must be stored in a convenient place and be
available at all times. We assume no liability for any damage caused by failure to
observe these instructions. For possible changes in this manual, SHENZHEN
GROWATT NEW ENERGY TECHNOLOGY CO.,LTD accepts no responsibilities to
inform the users.
1
1.4. Symbols in this document 1.4.2. Markings on this product
Symbol description
Risk of burns
CE mark.
The inverter complies with the
requirements of the applicable
EC guidelines.
2 3
Safety 2
1.5.Glossary
2.1. Intended Use
AC
Abbreviation for "Alternating Current" The unit converts the DC current generated by the photovoltaic (PV) modules to
grid-compliant alternating current and performs single-phase feed-in into the
DC electricity grid. Growatt 1000-3000-S series inverters are built according to all
required safety rules. Nevertheless, improper use may cause lethal hazards for
Abbreviation for "Direct Current"
the operator or third parties, or may result in damage to the units and other
Energy property.
Power
Power is measured in W (watts), kW (kilowatts) or MW (megawatts). Power is an
instantaneous value. It displays the power your inverter is currently feeding into
the power distribution grid.
Power rate
Power rate is the radio of current power feeding into the power distribution grid The inverter may only be operated with a permanent connection to the public
and the maximum power of the inverter that can feed into the power distribution power grid.
The inverter is not intended for mobile use. Any other or additional use is not
Power Factor considered the intended use. The manufacturer/supplier is not liable for damage
caused by such unintended use. Damage caused by such unintended use is at the
Power factor is the ratio of true power or watts to apparent power or volt amps. sole risk of the operator.
They are identical only when current and voltage are in phase than the power
factor is 1.0. The power in an ac circuit is very seldom equal to the direct product of
the volts and amperes. In order to find the power of a single phase ac circuit the
product of volts and amperes must be multiplied by the power factor. PV modules Capacitive Discharge Currents
4 5
2.2. Qualification of skilled person Grounding the PV modules: The Growatt inverter is a
transformerless inverter. That is why it has no galvanic
separation. Do not ground the DC circuits of the PV modules
This grid-tied inverter system operates only when properly connected to the AC connected to the inverter. Only ground the mounting frame of
–distribution network. Before connecting the inverter inverter to the power the PV modules. If you connect grounded PV modules to the
distribution grid, contact the local power distribution grid company. This Growatt inverters, the error message "PV ISO Low".
connection must be made only by qualified technical personnel to connect, and Comply with the local requirements for grounding the PV
only after receiving appropriate approvals, as required by the local authority CAUTION modules and the PV generator. GROWATT recommends
having jurisdiction. connecting the generator frame and other electrically
conductive surfaces in a manner which ensures continuous
conduction with ground these in order to have optimal
2.3. Safety instruction protection of the system and personnel.
6 7
Make all electrical connections (e.g. conductor termination, All operations regarding transport, installation and start-up,
fuses, PE connection, etc.) in accordance with prevailing including maintenance must be operated by qualified, trained
regulations. When working with the inverter powered on, adhere personnel and in compliance with all prevailing codes and
to all prevailing safety regulations to minimize risk of accidents. regulations.
Systems with inverters typically require additional control (e.g., Anytime the inverter has been disconnected from the power
WARNING
switches,disconnects) or protective devices (e.g., fusing circuit network, use extreme caution as some components can retain
breakers) depending upon the prevailing safety rules. charge sufficient to create a shock hazard; to minimize
occurrence of such conditions, comply with all corresponding
safety symbols and markings present on the unit and in this
The Growatt Inverter converts DC Current from PV generator manual.
into AC current. The inverter is suitable for mounting indoors In special cases, there may still be interference for the specified
and outdoors.
CAUTION application area despite maintaining standardized emission
CAUTION You can use the AC current generated as follows: limit values (e.g. when sensitive equipment is located at the
setup location or when the setup location is near radio or
House grid: Energy flows into the house grid. The consumers television receivers).In this case, the operator is obliged to take
connected,for example, household devices or lighting, proper action to rectify the situation.
consume the energy. The energy left over is fed into the Do not stay closer than 20 cm to the inverter for any length of
public grid. When the Growatt is not generated any time.
energy, e.g., at night, the consumers which are
connected are supplied by the public grid. The Growatt
does not have its own energy meter. When energy is fed
into the public grid, the energy meter spins backwards.
Public grid: Energy is fed directly into the public grid. The Growatt is
connected to a separate energy meter. The energy
produced is compensated at a rate depending on the
electric power company .
Symbol description
Ensure all covers and doors are closed and secure during operation.
Although designed to meet all safety requirements, some parts and
surfaces of Inverter are still hot during operation. To reduce the risk
of injury, do not touch the heat sink at the back of the PV-Inverter or
nearby surfaces while Inverter is operating.
Incorrect sizing of the PV plant may result in voltages being present
WARNING which could destroy the inverter. The inverter display will read the
error message“PV Voltage High!”
Turn the rotary switch of the DC Disconnect to the Off position
immediately.
Contact installer.
8 9
3 Product Description
Inverter status symbol Indicates inverter operation
status
The Growatt inverters are grid-tied inverters which convert DC current generated
by PV modules into AC current and feed it into the public grid.
C
Model Name xxxxxx
U DC max xxxV
I DC max xxxA
U DC range xxxV~xxxV
D E H G F
V AC norm xxxV
f AC norm xxxHz
Position Description P AC norm xxxxW
A The front enclosure lid I AC norm xxxA
B LCD PF xxxx
C State LED Protection Degree xxxx
D DC switch Operation Ambient
Temperature xxx°C~ xxx°C
E PV input terminals
F AC Output IEC62109 G83 VDE0126-1-1
10 11
More details about the type label as the chart below: 3.4. Transport and Store
Model Name Growatt 1000-S Growatt 1500-S Growatt 2000-S Growatt 2500-S Growatt 3000-S
3.4.1. Transportation
Max input DC voltage 450V 450V 450V 500V 550V
The inverter is thoroughly tested and inspected strictly before delivery. Our
Max input DC current 10A 10A 11A 12A 13A inverters leave our factory in proper electrical and mechanical condition. Special
packaging ensures safe and careful transportation. However, transport damage
PV voltage range 70V-450V 70V-450V 70V-450V 70V-500V 70V-550V may still occur. The shipping company is responsible in such cases. Thoroughly
inspect the inverter upon delivery. Immediately notify the responsible shipping
AC nominal voltage 230V 230V 230V 230V 230V company if you discover any damage to the packaging which indicates that the
inverter may have been damaged or if you discover any visible damage to the
AC grid frequency 50Hz/60Hz 50Hz/60Hz 50Hz/60Hz 50Hz/60Hz 50Hz/60Hz inverter. We will be glad to assist you, if required. When transporting the inverter,
the original or equivalent packaging should be used, and the maximum layers for
Nominal AC output power 1000W 1600W 2000W 2500W 3000W
original carton is seven as this ensures safe transport.
AC normal output current 4.3A 6.9A 8.7A 10.8A 13.0A
The unit must be stored in original package and desiccant must be left in the
3.3. Dimensions and Weight package.
The storage temperature should be always between -25℃ and +60℃ . And
the storage relative humidity can achieve to 100%.
Types H eig ht (H ) W idth (W ) Depth (D) Weig ht If there are a batch of inverters needs to be stored, the maximum layers for
Gro wa tt 1 000-S 26 7mm 2 71 mm 142 mm 6.1k g original carton as follow.
The maximum layers is 11 for Growatt 1000-S-3000-S
Gro wa tt 1 500-S 26 7 m m 2 71 mm 142 m m 6.1k g
After long term storage, local installer or service department of GROWATT
Gro wa tt 2 000-S 26 7 m m 2 71 mm 142 m m 6.1k g
should perform a comprehensive test before installation.
Gro wa tt 2 500-S 32 0 mm 2 71 mm 142 m m 8.8k g
Gro wa tt 3 000-S 32 0 mm 2 71 mm 142 m m 8.8k g
12 13
4 Unpacking Installation 5
Thoroughly inspect the packaging upon received. If any damage to the carton is 5.1. Safety instructions
visible, or if you find that the inverter unit is damaged after unpacking, please
notify the shipping company and SHENZHEN GROWATT NEW ENERGY
TECHNOLOGY CO.,LTD immediately. Danger to life due to fire or explosion
Meanwhile please check the delivery for completeness and for visible external Despite careful construction, electrical devices can cause fires.
damages of the inverter. If there are anything damaged or missing, please contact Do not install the inverter on easily flammable materials and where
your dealer. Don't dispose its original package. If you want to transport the flammable materials are stored.
inverter, it is better to store the inverter into the original package.
After opening the package, please check the contents of the box. It should contain
the following, Please check all of the accessories carefully in the carton. If Risk of burns due to hot enclosure parts
anything missing, contact your dealer at once.
Mount the inverter in such a way that it cannot be touched inadvertently.
A B C D
and personal safety.
The inverter must only be operated with PV generator. Do not connect any
other source of energy to it.
Both AC and DC voltage sources are terminated inside the PV Inverter.
Please disconnect these circuits before servicing.
This unit is designed to feed power to the public power grid (utility) only. Do
not connect this unit to an AC source or generator. Connecting Inverter to
external devices could result in serious damage to your equipment.
When a photovoltaic panel is exposed to light, it generates a DC voltage.
When connected to this equipment, a photovoltaic panel will charge the DC
link capacitors.
Energy stored in this equipment's DC link capacitors presents a risk of
electric shock. Even after the unit is disconnected from the grid and
photovoltaic panels, high voltages may still exist inside the PV-Inverter. Do
Item Number Description Remarks not remove the casing until at least 5 minutes after disconnecting all power
sources.
A 1 Although designed to meet all safety requirements, some parts and surfaces
Growatt inverter
of Inverter are still hot during operation. To reduce the risk of injury, do not
B 1 AC connection plug touch the heat sink at the back of the PV-Inverter or nearby surfaces while
C 2 Mounting screws Inverter is operating.
14 15
5.2. Selecting mounting location Do not install the inverter near television antenna or any other antennas and
antenna cables.
Do not install the inverter in living area, the noise caused by the machine
This is guidance for installer to choose a suitable installation location, to avoid may affect on daily life.
For security reasons, don’t install the inverter in place where the children
potential damages to device and operators.
can reach.
Don't put any things on the inverter.Do not cover the inverter.
The installation location must be suitable for the inverter's weight and Inverter requires adequate cooling space. Providing better ventilation for
dimensions for a long period time. (Refer to section 3.3) the inverter to ensure the heat escape adequately.
Do not install the inverter on structures constructed of flammable or Do not expose the inverter to direct sunlight, as this can cause excessive
heating and thus power reduction.
thermolabile materials. Observe the minimum clearances to walls, other inverters or objects as
Never install the inverter in environment of little or no air flow, nor dust
shown in the diagram below in order to guarantee sufficient heat dissipation.
environment. That may derate the efficiency of the cooling fan of the inverter.
The Ingress Protection rate is IP65 which means the inverter can be installed
outdoors and indoors.
Do not expose the inverter to direct sunlight, in order to avoid the power and
efficiency derating caused by excessive heating.
The humidity of the installation location should be 0~100% without
condensation.
The ambient temperature should be below 40℃ to ensure optimal operation.
The installation location must be freely and safely to get at all times.
Vertically installation and make sure the connection of inverter must be
downwards. Never install horizontal and avoids forward and sideways
tilt.(Refer to drawings below)
16 17
Please make sure the inverter is installed at the right place。The inverter
can’t install close to trunk
There must be sufficient clearance between the individual inverters to In order to avoid electrical shock or other injury, inspect existing
ensure that the cooling air of the adjacent inverter is not taken in. electronic or plumbing installations before drilling holes.
If necessary, increase the clearance spaces and make sure there is enough
fresh air supply to ensure sufficient cooling of the inverters.
DANGER
The inverter can’t install to solarization,drench,firn location. We suggest
that the inverters should be installed at the location with some cover or 1.According to the following distance to drill two holes on the wall;
protection
2.Install the explosion screw into the wall;
18 19
5.3.2. Mounting Inverter 5.4. Connect switch
Separate the Growatt inverter securely from the grid and the PV generators using
Referring to the following figure, make the inverter and explosion screw
DC and AC Switch. You must provide an AC circuit breaker. If Growatt DC Switch
matching,
Hang the inverter on the explosion screw is included in the delivery of the Growatt inverter, it must be used for operating the
inverter.
5.5. Grounding
20 21
5.7. Electrical connection 3.Remove the parts of the AC connection plug from the accessory bag.Guide the
pressure screw, sealing ring, threaded sleeve over the AC cable
5.7.1. Safety
1.Switch off AC breaker and secure against being inadvertently switched back on.
About the AC breaker,please refer to the below form .
Types Max current output Suggested AC switch spec
Growatt 1000-S 4.7A 400Vac/10A
Growatt 1500-S 7.8A 400Vac/16A
Growatt 2000-S 9.5A 400Vac/16A
Growatt 2500-S 11.9A 400Vac/16A
Growatt 3000-S 14.3A 400Vac/16A
Close the connector
2. The grid connection is made using 3 conductors (L, N, and PE),We recommend
the following requirements for Growatt 1000-S/ Growatt 1500-S/Growatt 2000- 6.Finally, insert the AC connection plug into the AC connection receptacle on the
S/Growatt 2500-S/Growatt 3000-S. inverter.
Model _(mm) Area(mm2) AWG no. MAX.cable length(m)
Growatt 1000-S _ 2.05 3.332 12 63
Growatt 1500-S _ 2.05 3.332 12 45
Growatt 2000-S _ 2.05 3.332 12 47
Growatt 2500-S _ 2.05 3.332 12 34
Lock the housing Unlock the housing
Growatt 3000-S _ 2.05 3.332 12 32
22 23
5.7.3. Connecting the PV array 5.7.3.2. Connecting the PV array (DC)
Check the connection cables of the PV modules for correct polarity and make sure that the
maximum input voltage of the inverter is not exceeded. At an ambient temperature over 10
℃, the open circuit voltage of the PV modules should not exceed 90% of the maximum input
voltage of the inverter. Otherwise, the maximum inverter input voltage may be exceeded at
low ambient temperatures.
COM Address:xx
Setting…
3. Single knock to “COM Address: xx” →Double knock change the address to set
model →Single knock to set address. After selecting, you need to wait a few
INPUT 123:XXX seconds until the display becomes dark, then the change is saved.
26 27
If the country you want to select is not in the above list, please
6.2. Independent function option
directly select VDE0126-1-1.
Netherlands select VDE0126-1-1.
NOTICE
6.2.1. Country selecting
When the PV panels are connected and their output voltage is greater than 70Vdc Please finish the country selecting according to the following steps
but the AC grid is not yet connected, inverter will start up automatically. If it is the
first time to power on the inverter after installation, you may need to select a A The LCD will quickly switch to and stay at the 'Please select' interface after
specific country.Otherwise, the interface will stay at the ‘Please Select’ interface power on, as below:
all the time. There are eleven options to select, as the list below.
If you have ordered the inverter with specific country settings, the
parameters have been preset in factory and you don't need to B Single knock on the LCD, countries will vary from one to another along the
operate this step any more. above list order. below acts as an example, and Germany is the second
Information selection.
This series inverter in Hungary market has not country settings.
Germany //1
UK_G83 //2
Italy //3 D When the country arrives at Italy, Double knock to enter the two options 'YES'
and 'NO', and the cursor stays at 'NO' in default, as below:
France //4
Denmark //5
Belgium //6
E Single knock to select 'YES', as below:
Spain //7
Greece //8
Turkey //9
F Double knock to confirm your selection, LCD will display 'Select OK' with the
country name in the below, as below:
28 29
if you still single knock at the interface as E, the cursor will go to
'NO' again as D, then if you double knock, the display will switch to
Information the interface as C.
6.2.2.Auto test
The test result data is saved in the “Auto test report of xxxxxx .txt” under the
Software install direction;
6.2.2.2.Autotest
30 31
Test fail condition:
6.3. LCD display
In the lower center of inverter there is the LCD display. We can check inverter
running status, etc. on the LCD screen. Items displayed can be changed by knock;
Condition Reason Suggestion
you can also change some inverter parameters by knock.
Test Stop Communication lose or inverter Check the communication or
occur other fault when testing check the inverter state
Test fail The trip value of the test result is Check the grid state, make sure 6.3.1. General LCD display
not in the limit of the spec the grid is stable, and retest
Starting-up display sequence , once the PV power is sufficient , inverter displays
information as shown in the flow chart as follow:
6.2.3. GFCI function
GFCI is short for Ground-Fault Circuit Interrupter which is used for preventing
from being electric shock. The inverter is equipped with integrated RCD (Residual
Current Protective Device) and RCM (Residual Current Operated Monitor). The
current sensor will detect the volume of the leakage current and compare it with
the pre-set value. If the leakage current is above the permitted range, the RCD will
disconnect the inverter from the AC load.
32 33
In fault mode, there can be different error messages displayed
in the LCD due to different faults. Please refer to Chapter 10 for
4 Setting status
reference.The first line of LCD display can be changed by knock Setting...
Information on the LCD screen. The second line automatically changes in
the interval of 2 or 4 seconds as above Table.
34 35
6.5. Commissioning the inverter Features:
Monitor and record current data and of inverters.
Record historical data.
1. If the inverter connects with PV panel arrays and the input voltage is higher than Monitor and record event information of inverter
70Vdc, while the AC grid is not connected yet, LCD will display messages in order Connect computer and inverter via RS232 and RS485 port (wire connection)
as below: or Bluetooth module (wireless connection).
‘Ser NO: xxx'->'xxxxx'->'FW version'->'Waiting'->'No AC connection', the display Remote access available for local area network.
repeats 'NO Utility' and LED will be red.
2. Turn on the AC breaker or close the fuse between inverter and grid, the system Users are able to monitor the inverter after the setting of
will operate normally. software. Detailed information about setting and functions refer
to the ShineNET Manual.
3. Under normal operating conditions, the LCD displays 'Power: xxx.x W' at State
Yo u c a n d o w n l o a d t h e S h i n e N e t Y N 2 . 0 f r o m :
info, this is the power fed into grid. LED turns green.
Information ftp://113.106.58.169, the user name is ftpguest and Password is
4. Finish commissioning. ftpguest.
ShineNet may be upgraded for better function or user
experience, please refer to the actual software version.
Features:
Monitor and transmitter communicate via wireless communication technology.
External transmitter, with IP65 waterproof and dustproof.
A monitor can simultaneously communicate with six transmitters.
Communication distance between monitor and transmitter : 30 meter.
Power supply option: built-in battery slot, an external DC power supply.
Easy installation, and convenient to use it.
36 37
Startup and Shutdown the Inverter 7
6.6.3. ShineWebBox
1. Disconnect the line circuit breaker from single phase and prevent it from being
reactivated.
2. Turn off the dc switch.
Features:
3. Check the inverter operating status.
A multi-functional and high-performance communication data logger; Keep user 4. Waiting until LED, display have gone out, the inverter is shut down.
informed of the system’s status at any time.
Massive storage with flexible parameters setting, system information
management, error prompt and record.
Collects data and uploads information over the internet in near real-time to
Growatt Shine Server platform.
38 39
8 Operation Modes Maintenance and Cleaning 9
8.1. Waiting mode
9.1. Checking heat dissipation
When the PV voltage is higher than 70V, Inverter will be powered up, and enters
“waiting” mode.
In this mode, inverter will check the system parameters. If the system is normal,
and PV voltage is higher than 80Vdc, the inverter will attempt to connect to grid. If the inverter regularly reduces its output power due to high temperature, please
improve the heat dissipation condition. Maybe you need to clean the heat sink.
In this mode, the inverter works normally and LED turns green. 9.2. Checking the DC switch
Whenever the DC voltage is higher than 80Vdc, inverter converts power to grid
as generated by the PV panels;
Whenever the DC voltage is lower than 70Vdc, the inverter will work in standby Checking externally visible damage and discoloration of the DC switch. If there is
state and attempt to connect the grid. In waiting state the inverter consumes any visible damage to the DC Disconnect, or visible discoloration, contact the
just enough power generated by the PV panel to monitor the internal system installer.
status; Once a year, turn the rotary switch from the On position to the Off position 5 times
in succession. This cleans the contacts of the rotary switch and prolongs the
The inverter starts up automatically when the DC power from the electrical endurance of the DC Disconnect
PV panel is sufficient.
Information
The internal intelligent controller can continuously monitor and adjust the system
status. If inverter finds any unexpected conditions such as system fault and
inverter fault, the fault information will be displayed on the LCD. In fault mode the
LED turns red.
40 41
10 Trouble Shooting
Sometimes, the PV inverter does not work normally, we recommend the following If the suggestions do not work, please connect to the Growatt.
solutions for common troubleshooting. The following table can help the technician Information
to understand the problem and take action.
10.1 Warnings(W)
10.2 Errors(E)
Warnings(W) identify the current status of the Growatt inverter. Warnings do not
relate to a fault. When a (W) with a number after it appears in the display, it Errors(E) codes identify a possible equipment failure, fault or incorrect inverter
indicates a Warning Code and is usually cleared through an orderly shutdown/re- setting or configuration. Any and all attempts to correct or clear a fault must be
set or a self corrective action performed by the inverter. See the (W) codes in the performed by qualified personnel. Typically, the (E) code can be cleared once the
following table. cause or fault is removed. Some of the (E) codes, Error as indicated in the table
below, may indicate a fatal error and require you to contact the supplier or the
Error message Description Suggestion Growatt to replace a new one.
Utility grid voltage is 1.Check grid voltage. Error: 101 Communication fault Slave 1.Restart inverter
AC V Outrange out of permissible 2.If the error message still exists processor can't receive data 2.If error message still exists,
range. despite the grid voltage being within from Master processor. contact Growatt.
the tolerable range, contact Growatt.
Utility grid frequency 1.Check grid frequency. Error: 102 Consistent fault. Data 1.Restart inverter.
AC F Outrange out of permissible 2.If the error message is displayed received by Master and Slave 2.If error message appears
range. despite the grid frequency being within processor are different. The frequently or error message
the tolerable range, contact Growatt. reason can be utility grid still exists after replacement,
voltage or frequency change check utility grid. If you require
1.check the inverter operation state frequently. . help, contact Growatt.
Over Temperature Temperature outrange 2.If the error message is displayed still, 3.If error message still exists,
please contact Growatt. contact Growatt.
Output current DC 1.Restart inverter. Error: 119 GFCI Device Damage Contact Growatt.
Output High DCI offset too high 2.If error message still exists,
contact Growatt.
Error: 120 HCT fault Contact Growatt.
Leakage current 1.Restart inverter.
Residual I High
too high 2.If error message still exists,
contact Growatt. Error: 121 Communication fault. 1.Restart the inverter
Master processor can't 2.If error message still exists,
The DC input receive data from Slave contact Growatt..
voltage is exceeding Disconnect the DC switch
PV Voltage High processor.
the maximum tolerable immediately.
value.
Error: 122 Bus voltage fault Contact Growatt.
Auto Test Failed Auto test didn't passed. Restart inverter
42 43
11 Decommissioning Technical Data 12
11.1. Dismantling the Inverter 12.1. Specification
3. Screw off all projecting cable glands. PV voltage range 70V-450V 70V-450V 70V-450V 70V-500V 70V-550V
4. Lift the inverter off the bracket and unscrew the bracket screws.
MPP work voltage 70V-450V 70V-450V 70V-450V 70V-500V 70V-550V
range/ nominal /180V /250V /360V /360V /360V
voltage
11.2. Packing the Inverter Full load dc voltage 110V-400V 175V-400V 200V-400V 220V-450V 250V-500V
range
If possible, always pack the inverter in its original carton and secure it with tension Max. input current 10A 10A 11A 12A 13A
belts. If it is no longer available, you can also use an equivalent carton. The box
must be capable of being closed completely and made to support both the weight Max. input current
10A 10A 11A 12A 13A
per string
and the size of the inverter.
Number of independent 1/1 1/1 1/1 1/1 1/1
MPP trackers / strings per
MPP tracker
11.3. Storing the Inverter
Output (AC)
Store the inverter in a dry place where ambient temperatures are always between -
25°C and +60°C. Rated AC output
1000W 1600W 2000W 2500W 3000W
power
11.4. Disposing of the Inverter Max. AC power 1000W 1650W 2000W 2500W 3000W
Power factor 1 1 1 1 1
AC connection Single phase Single phase Single phase Single phase Single phase
44 45
Efficiency Features
MPPT efficiency 99.5% 99.5% 99.5% 99.5% 99.5% Interfaces: RS232/Wifi yes/opt yes/opt yes/opt yes/opt yes/opt
Warranty: 5 years yes /opt yes /opt yes /opt yes /opt yes /opt
Protection devices / 10 years
DC reverse polarity yes yes yes yes yes
Certificates and approvals CE, VDE 0126-1-1, VDE-AR-N-4105,IEC 62109, G83,
protection AS4777, NBT32004-2013, EN50438, CEI 0-21,INMETRO
Integrated all - pole sensitive yes yes yes yes yes Country Undervoltage Overvoltage Underfrequncy Overfrequncy
leakage current monitoring unit
Dimensions (W / H / D) 271/267/142 271/267/142 271/267/142 271/320/142 271/320/142 Greece 184V 264V 47.5Hz 51.0Hz
in mm
Germany 184V 252V 47.53Hz 51.47Hz
Weight 6.1KG 6.1KG 6.1KG 8.8KG 8.8KG
Operating temperature –25°C ... +60°C (-13...+140℉) with derating above 45°C /113℉ UK 201V 251V 47.5Hz 51.5Hz
range
Ireland 207V 253V 48Hz 50.5Hz
Noise emission (typical) ≤ 25 dB(A) ≤ 25 dB(A) ≤ 25 dB(A) ≤ 25 dB(A) ≤ 25 dB(A)
China 195.5V 253V 49.5Hz 50.2Hz
Altitude 2000m(6560ft) without derating
Denmark 207V 253V 47.5Hz 52.0Hz
Self-Consumption < 0.5 W < 0.5 W < 0.5 W < 0.5 W < 0.5 W
night Hungary 195.5V 253V 49.0Hz 51.0Hz
Topology transformerless
Italy 195.5V 264.5V 47.5Hz 51.5Hz
Cooling concept Natural Natural Natural Natural Natural
Belgium 195.5V 253V 47.5Hz 50.5Hz
Environmental Protection Ip65 Ip65 Ip65 Ip65 Ip65
Rating
46 47
PV System Installation 13
12.4. Torque
AC terminal 6kg.cm
12.5. Accessories
13.2. Multi inverters
In the following table you will find the optional accessories for your product. If
required, you can order these from SHENZHEN GROWATT NEW ENERGY
TECHNOLOGY CO.,LTD or your dealer.
WIFI
48 49
14 Compliance Certificates
14.1. List
Growatt1000-S-3000-S
15 Contact
If you have technical problems about our products, contact the GROWATT
Serviceline. We need the following information in order to provide you with the
necessary assistance:
Inverter type
Serial number of the inverter
Event number or display message of the inverter
Type and number of PV modules connected
Optional equipment
T 0755-2951 5888
F 0755-2747 2131
E service@ginverter.com
W www.ginverter.com
50