Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Growatt 1000-3000-S User Manual

Download as pdf or txt
Download as pdf or txt
You are on page 1of 29

Growatt 1000-S

Growatt 1500-S
Growatt 2000-S
Growatt 2500-S
Growatt 3000-S

Shenzhen Growatt New Energy Technology CO.,LTD


Building B, Jiayu Industrial Park, #28, GuangHui Road,
Shiyan Street, Baoan District, Shenzhen, P.R.China Installation
T
F
0755-29515888
0755-27472131
& Operation Manual
E service@ginverter.com
W www.ginverter.com

GR - UM - 033 - A - 03
Contents

1 About Manual
1.1 Validity
1.2 Target Group
1.3 Additional information
1.4 Symbols in this document
1.5 Glossary

2 Safety
2.1 Intended Use
2.2 Qualification of skilled person
2.3 Safety instruction
2.4. Assembly Warnings
2.5. Electrical Connection Warnings
2.6. Operation Warnings

3 Product Description

3.1. Overview

3.2. Type label

3.3. Dimensions and Weight

3.4. Transport and Store

3.5. The advantage of Inverter

4 Unpacking
5 Installation
5.1. Safety instructions
10 Trouble Shooting
10.1 Warnings(W)
5.2. Selecting mounting location
10.2 Errors(E)
5.3. Mounting Inverter
5.4. Connect switch
5.5. Grounding
5.6. Connect grid type
11 Decommissioning
11.1. Dismantling the Inverter
5.7. Electrical connection
11.2. Packing the Inverter

11.3. Storing the Inverter


11.4. Disposing of the Inverter
6 Commissioning
6.1. Parameters setting
6.2. Independent function option 12 Technical Data
6.3. LCD display 12.1. Specification

6.4. Communication 12.2. DC connector info

6.5. Commissioning the inverter 12.3. Trip volatge &Trip frequency


6.6. Monitoring tool instructions 12.4. Torque
12.5. Accessories

7 Startup and Shutdown


the Inverter 7.1. Start up the Inverter
13 PV System Installation
7.2. Shutdown the Inverter
13.1. Single inverter
13.2. Multi inverters

8 Operation Modes
8.1. Waiting mode
8.2. Normal mode 14 Compliance Certificates
8.3. Fault mode
14.1. List
8.4. Shutdown mode
14.2. Download address

9 Maintenance and
Cleaning 9.1. Checking heat dissipation
9.2. Checking the DC switch 15 Contact
9.3. Cleaning the Inverter
About Manual 1
Manual Introduce and Copyright

1.1 . Validity
Copyright © 2010 Shenzhen Growatt New Energy Technology Co., Ltd,
All rights reserved.
This installation and user guide describes the assembly, installation,
No part of this document may be reproduced, stored in a retrieval system, commissioning, communication, maintenance, operating and failure search of the
or transmitted, in any form or by any means, electronic, mechanical,
following Growatt inverters:
photographic, magnetic or otherwise, without the prior written permission
of Shenzhen Growatt New Energy Technology Co., Ltd. Growatt 1000-S
Growatt 1500-S
Shenzhen Growatt New Energy Technology Co., Ltd makes no Growatt 2000-S
representations, express or implied, with respect to this documentation Growatt 2500-S*
or any of the equipment and/or software it may describe, including (with
no limitation) any implied warranties of utility, merchantability, or fitness Growatt 3000-S
for any particular purpose. All such warranties are expressly disclaimed.
Neither Shenzhen Growatt New Energy Technology Co., Ltd nor its Note “*”: Growatt 2500-S is designed only for UK.
distributors or dealers shall be liable for any indirect, incidental, or
consequential damages under any circumstances. This manual does not cover any details concerning equipment connected to the
Growatt ( e.g. PV modules). Information concerning the connected equipment is
(The exclusion of implied warranties may not apply in all cases under available from the manufacturer of the equipment
some statutes, and thus the above exclusion may not apply.)

Specifications are subject to change without notice. Every attempt has


been made to make this document complete, accurate and up-to-date. 1.2. Target group
Readers are cautioned, however, that Growatt reserves the right to make
changes without notice and shall not be responsible for any damages,
including indirect, incidental or consequential damages, caused by This manual is for qualified personnel who have received training and have
reliance on the material presented, including, but not limited to, demonstrated skills and knowledge in the construction and operation of this
omissions, typographical errors, arithmetical errors or listing errors in the device. Qualified Personnel are trained to deal with the dangers and hazards
content material. involved in installing electric devices.

All trademarks are recognized even if these are not marked separately.
Missing designations do not mean that a product or brand is not a 1.3. Additional information
registered trademark.

SHENZHEN GROWATT NEW ENERGY TECHNOLOGY CO.,LTD Find further information on special topics in the download area at
Building B, Jiayu Industrial Park, #28, GuangHui Road, Shiyan Street, www.ginverter.com
Baoan District, Shenzhen, P.R.China The manual and other documents must be stored in a convenient place and be
available at all times. We assume no liability for any damage caused by failure to
observe these instructions. For possible changes in this manual, SHENZHEN
GROWATT NEW ENERGY TECHNOLOGY CO.,LTD accepts no responsibilities to
inform the users.

1
1.4. Symbols in this document 1.4.2. Markings on this product

1.4.1. Warnings in this document Symbol Explanation

A warning describes a hazard to equipment or personnel. It calls attention to a Electrical voltage!


procedure or practice, which, if not correctly performed or adhered to, could result
in damage to or destruction of part or all of the Growatt equipment and/or other
equipment connected to the Growatt equipment or personal injury. Risk of fire or explosion!

Symbol description
Risk of burns

DANGER indicates a hazardous situation which, if not Operation after 5 minutes


avoided, will result in death or serious injury.
DANGER
Point of connection for
grounding protection.
WARNING indicates a hazardous situation which, if not
avoided, could result in death or serious injury.
WARNING Direct Current (DC)

CAUTION indicates a hazardous situation which, if not Alternating Current (AC)


avoided, could result in minor or moderate injury.
CAUTION
The inverter has no transformer.
NOTICE is used to address practices not related to personal
injury.
NOTICE Read the manual.

Information that you must read and know to ensure optimal


operation of the system. Bluetooth communication is enabled.
Information

CE mark.
The inverter complies with the
requirements of the applicable
EC guidelines.

The inverter must not be disposed


of with the household waste.

2 3
Safety 2
1.5.Glossary
2.1. Intended Use
AC
Abbreviation for "Alternating Current" The unit converts the DC current generated by the photovoltaic (PV) modules to
grid-compliant alternating current and performs single-phase feed-in into the
DC electricity grid. Growatt 1000-3000-S series inverters are built according to all
required safety rules. Nevertheless, improper use may cause lethal hazards for
Abbreviation for "Direct Current"
the operator or third parties, or may result in damage to the units and other
Energy property.

Energy is measured in Wh (watt hours), kWh (kilowatt hours) or MWh (megawatt


hours). The energy is the power calculated over time. If, for example, your inverter Principle of a PV plant with this Growatt XXXX single-phase inverter
operates at a constant power of 1500W for half an hour and then at a constant
power of 1000 W for another half an hour, it has fed 1250 Wh of energy into the
power distribution grid within that hour.

Power
Power is measured in W (watts), kW (kilowatts) or MW (megawatts). Power is an
instantaneous value. It displays the power your inverter is currently feeding into
the power distribution grid.

Power rate
Power rate is the radio of current power feeding into the power distribution grid The inverter may only be operated with a permanent connection to the public
and the maximum power of the inverter that can feed into the power distribution power grid.
The inverter is not intended for mobile use. Any other or additional use is not
Power Factor considered the intended use. The manufacturer/supplier is not liable for damage
caused by such unintended use. Damage caused by such unintended use is at the
Power factor is the ratio of true power or watts to apparent power or volt amps. sole risk of the operator.
They are identical only when current and voltage are in phase than the power
factor is 1.0. The power in an ac circuit is very seldom equal to the direct product of
the volts and amperes. In order to find the power of a single phase ac circuit the
product of volts and amperes must be multiplied by the power factor. PV modules Capacitive Discharge Currents

PV modules with large capacities relative to earth, such as thin-film PV modules


PV with cells on a metallic substrate, may only be used if their coupling capacity does
Abbreviation for photovoltaic not exceed 470nF. During feed-in operation, a leakage current flows from the cells
to earth, the size of which depends on the manner in which the PV modules are
wireless communication installed (e.g. foil on metal roof) and on the weather (rain, snow). This "normal"
leakage current may not exceed 50mA due to the fact that the inverter would
The external wireless communication technology is a radio technology that allows otherwise automatically disconnect from the electricity grid as a protective
the inverter and other communication products to communicate with each other. measure.
The external wireless communication does not require line of sight between the
devices and it is selective purchasing.

4 5
2.2. Qualification of skilled person Grounding the PV modules: The Growatt inverter is a
transformerless inverter. That is why it has no galvanic
separation. Do not ground the DC circuits of the PV modules
This grid-tied inverter system operates only when properly connected to the AC connected to the inverter. Only ground the mounting frame of
–distribution network. Before connecting the inverter inverter to the power the PV modules. If you connect grounded PV modules to the
distribution grid, contact the local power distribution grid company. This Growatt inverters, the error message "PV ISO Low".
connection must be made only by qualified technical personnel to connect, and Comply with the local requirements for grounding the PV
only after receiving appropriate approvals, as required by the local authority CAUTION modules and the PV generator. GROWATT recommends
having jurisdiction. connecting the generator frame and other electrically
conductive surfaces in a manner which ensures continuous
conduction with ground these in order to have optimal
2.3. Safety instruction protection of the system and personnel.

The GROWATT Inverters are designed and tested according to international


safety requirements; however, certainsafety precautions must be observed when 2.5. Electrical Connection Warnings
installing and operating this inverter. Read and follow all instructions, cautions
and warnings in this installation manual. If questions arise, please contact
Growatt's technical services at +86 (0)755 2951 5888. Symbol description

The components in the inverter are live. Touching live


components can result in serious injury or death.
2.4. Assembly Warnings Do not open the inverter except the wire box by qualified
persons.
Electrical installation, repairs and conversions may only be
carried out by electrically qualified persons.
Symbol description Do not touch damaged inverters.
Danger to life due to high voltages in the inverter
There is residual voltage in the inverter. The inverter takes
Prior to installation, inspect the unit to ensure absence of any 20 minutes to discharge.
DANGER
transport or handling damage, which could affect insulation Wait 20 minutes before you open the wire box.
integrity or safety clearances; failure to do so could result in Persons with limited physical or mental abilities may only work
safety hazards. with the Growatt inverter following proper instruction and under
Assemble the inverter per the instructions in this manual. Use constant supervision. Children are forbidden to play with the
care when choosing installation location and adhere to Growatt inverter. Must keep the Growatt inverter away from
specified cooling requirements. children.
Unauthorized removal of necessary protections, improper
WARNING use, incorrect installation and operation may lead to serious
safety and shock hazards and/or equipment damage.
In order to minimize the potential of a shock hazard due to
hazardous voltage, cover the entire solar array with dark
material prior to connecting the array to any equipment.

6 7
Make all electrical connections (e.g. conductor termination, All operations regarding transport, installation and start-up,
fuses, PE connection, etc.) in accordance with prevailing including maintenance must be operated by qualified, trained
regulations. When working with the inverter powered on, adhere personnel and in compliance with all prevailing codes and
to all prevailing safety regulations to minimize risk of accidents. regulations.
Systems with inverters typically require additional control (e.g., Anytime the inverter has been disconnected from the power
WARNING
switches,disconnects) or protective devices (e.g., fusing circuit network, use extreme caution as some components can retain
breakers) depending upon the prevailing safety rules. charge sufficient to create a shock hazard; to minimize
occurrence of such conditions, comply with all corresponding
safety symbols and markings present on the unit and in this
The Growatt Inverter converts DC Current from PV generator manual.
into AC current. The inverter is suitable for mounting indoors In special cases, there may still be interference for the specified
and outdoors.
CAUTION application area despite maintaining standardized emission
CAUTION You can use the AC current generated as follows: limit values (e.g. when sensitive equipment is located at the
setup location or when the setup location is near radio or
House grid: Energy flows into the house grid. The consumers television receivers).In this case, the operator is obliged to take
connected,for example, household devices or lighting, proper action to rectify the situation.
consume the energy. The energy left over is fed into the Do not stay closer than 20 cm to the inverter for any length of
public grid. When the Growatt is not generated any time.
energy, e.g., at night, the consumers which are
connected are supplied by the public grid. The Growatt
does not have its own energy meter. When energy is fed
into the public grid, the energy meter spins backwards.

Public grid: Energy is fed directly into the public grid. The Growatt is
connected to a separate energy meter. The energy
produced is compensated at a rate depending on the
electric power company .

2.6. Operation Warnings

Symbol description

Ensure all covers and doors are closed and secure during operation.
Although designed to meet all safety requirements, some parts and
surfaces of Inverter are still hot during operation. To reduce the risk
of injury, do not touch the heat sink at the back of the PV-Inverter or
nearby surfaces while Inverter is operating.
Incorrect sizing of the PV plant may result in voltages being present
WARNING which could destroy the inverter. The inverter display will read the
error message“PV Voltage High!”
Turn the rotary switch of the DC Disconnect to the Off position
immediately.
Contact installer.

8 9
3 Product Description
Inverter status symbol Indicates inverter operation
status
The Growatt inverters are grid-tied inverters which convert DC current generated
by PV modules into AC current and feed it into the public grid.

3.2. Type label


3.1. Overview
The type labels provide a unique identification of the inverter (The type of product,
Device-specific characteristics, Certificates and approvals). The type labels are
A on the left-hand side of the enclosure.

C
Model Name xxxxxx
U DC max xxxV
I DC max xxxA
U DC range xxxV~xxxV
D E H G F
V AC norm xxxV
f AC norm xxxHz
Position Description P AC norm xxxxW
A The front enclosure lid I AC norm xxxA
B LCD PF xxxx
C State LED Protection Degree xxxx
D DC switch Operation Ambient
Temperature xxx°C~ xxx°C
E PV input terminals
F AC Output IEC62109 G83 VDE0126-1-1

G Waterproof breathable valve


H RJ 45 Port

Symbol on the inverter

As the grid standards of many countries are in the process


Symbol Description Explanation of improving or upgrading, please refer to the label on the
Information machine for reference of the newest certificate.

Tap symbol Setting the display operation


by tapping the LCD

10 11
More details about the type label as the chart below: 3.4. Transport and Store
Model Name Growatt 1000-S Growatt 1500-S Growatt 2000-S Growatt 2500-S Growatt 3000-S
3.4.1. Transportation
Max input DC voltage 450V 450V 450V 500V 550V
The inverter is thoroughly tested and inspected strictly before delivery. Our
Max input DC current 10A 10A 11A 12A 13A inverters leave our factory in proper electrical and mechanical condition. Special
packaging ensures safe and careful transportation. However, transport damage
PV voltage range 70V-450V 70V-450V 70V-450V 70V-500V 70V-550V may still occur. The shipping company is responsible in such cases. Thoroughly
inspect the inverter upon delivery. Immediately notify the responsible shipping
AC nominal voltage 230V 230V 230V 230V 230V company if you discover any damage to the packaging which indicates that the
inverter may have been damaged or if you discover any visible damage to the
AC grid frequency 50Hz/60Hz 50Hz/60Hz 50Hz/60Hz 50Hz/60Hz 50Hz/60Hz inverter. We will be glad to assist you, if required. When transporting the inverter,
the original or equivalent packaging should be used, and the maximum layers for
Nominal AC output power 1000W 1600W 2000W 2500W 3000W
original carton is seven as this ensures safe transport.
AC normal output current 4.3A 6.9A 8.7A 10.8A 13.0A

Power factor >0.99 >0.99 >0.99 >0.99 >0. 99


3.4.2. Storage of Inverter
Environmental Protection Ip65 Ip65 Ip65 Ip65 Ip65
Rating If you want to storage the inverter in your warehouse, you should choose an
OperationAmbient -25...+60℃ -25...+60℃ -25...+60℃ -25...+60℃ -25...+60℃ appropriate location to store the inverter.
temperature

The unit must be stored in original package and desiccant must be left in the
3.3. Dimensions and Weight package.
The storage temperature should be always between -25℃ and +60℃ . And
the storage relative humidity can achieve to 100%.
Types H eig ht (H ) W idth (W ) Depth (D) Weig ht If there are a batch of inverters needs to be stored, the maximum layers for
Gro wa tt 1 000-S 26 7mm 2 71 mm 142 mm 6.1k g original carton as follow.
The maximum layers is 11 for Growatt 1000-S-3000-S
Gro wa tt 1 500-S 26 7 m m 2 71 mm 142 m m 6.1k g
After long term storage, local installer or service department of GROWATT
Gro wa tt 2 000-S 26 7 m m 2 71 mm 142 m m 6.1k g
should perform a comprehensive test before installation.
Gro wa tt 2 500-S 32 0 mm 2 71 mm 142 m m 8.8k g
Gro wa tt 3 000-S 32 0 mm 2 71 mm 142 m m 8.8k g

3.5. The advantage of Inverter

Maximum efficiency of 97.6%.


Wide input voltage range from 70-550Vdc.
Integrated DC switch.
Sound control.
Multi communication pattern.
Easy installation.

12 13
4 Unpacking Installation 5
Thoroughly inspect the packaging upon received. If any damage to the carton is 5.1. Safety instructions
visible, or if you find that the inverter unit is damaged after unpacking, please
notify the shipping company and SHENZHEN GROWATT NEW ENERGY
TECHNOLOGY CO.,LTD immediately. Danger to life due to fire or explosion

Meanwhile please check the delivery for completeness and for visible external Despite careful construction, electrical devices can cause fires.
damages of the inverter. If there are anything damaged or missing, please contact Do not install the inverter on easily flammable materials and where
your dealer. Don't dispose its original package. If you want to transport the flammable materials are stored.
inverter, it is better to store the inverter into the original package.
After opening the package, please check the contents of the box. It should contain
the following, Please check all of the accessories carefully in the carton. If Risk of burns due to hot enclosure parts
anything missing, contact your dealer at once.
Mount the inverter in such a way that it cannot be touched inadvertently.

Though the packaging box of Growatt inverter is durable, please


treat the packing box gently and avoid dispose the packing box. All electrical installations shall be done in accordance with the local and
In this package, there are inverter, cystosepiment and carton national electrical codes. Do not remove the casing. Inverter contains no user
from inside to outside. serviceable parts. Refer servicing to qualified service personnel. all wiring
Information For the accessories, there are two kinds of configuration, and electrical Installation should be conducted by a qualified service
please refer to the inverter you receive. personnel .
Carefully remove the unit from its packaging and inspect for external damage.
If you find any imperfections, please contact your local dealer.
Be sure that the inverters connect to the ground in order to protect property

A B C D
and personal safety.
The inverter must only be operated with PV generator. Do not connect any
other source of energy to it.
Both AC and DC voltage sources are terminated inside the PV Inverter.
Please disconnect these circuits before servicing.
This unit is designed to feed power to the public power grid (utility) only. Do
not connect this unit to an AC source or generator. Connecting Inverter to
external devices could result in serious damage to your equipment.
When a photovoltaic panel is exposed to light, it generates a DC voltage.
When connected to this equipment, a photovoltaic panel will charge the DC
link capacitors.
Energy stored in this equipment's DC link capacitors presents a risk of
electric shock. Even after the unit is disconnected from the grid and
photovoltaic panels, high voltages may still exist inside the PV-Inverter. Do
Item Number Description Remarks not remove the casing until at least 5 minutes after disconnecting all power
sources.
A 1 Although designed to meet all safety requirements, some parts and surfaces
Growatt inverter
of Inverter are still hot during operation. To reduce the risk of injury, do not
B 1 AC connection plug touch the heat sink at the back of the PV-Inverter or nearby surfaces while
C 2 Mounting screws Inverter is operating.

D 1 Installation & Operation Manual

14 15
5.2. Selecting mounting location Do not install the inverter near television antenna or any other antennas and
antenna cables.
Do not install the inverter in living area, the noise caused by the machine
This is guidance for installer to choose a suitable installation location, to avoid may affect on daily life.
For security reasons, don’t install the inverter in place where the children
potential damages to device and operators.
can reach.
Don't put any things on the inverter.Do not cover the inverter.
The installation location must be suitable for the inverter's weight and Inverter requires adequate cooling space. Providing better ventilation for
dimensions for a long period time. (Refer to section 3.3) the inverter to ensure the heat escape adequately.
Do not install the inverter on structures constructed of flammable or Do not expose the inverter to direct sunlight, as this can cause excessive
heating and thus power reduction.
thermolabile materials. Observe the minimum clearances to walls, other inverters or objects as
Never install the inverter in environment of little or no air flow, nor dust
shown in the diagram below in order to guarantee sufficient heat dissipation.
environment. That may derate the efficiency of the cooling fan of the inverter.
The Ingress Protection rate is IP65 which means the inverter can be installed
outdoors and indoors.
Do not expose the inverter to direct sunlight, in order to avoid the power and
efficiency derating caused by excessive heating.
The humidity of the installation location should be 0~100% without
condensation.
The ambient temperature should be below 40℃ to ensure optimal operation.
The installation location must be freely and safely to get at all times.
Vertically installation and make sure the connection of inverter must be
downwards. Never install horizontal and avoids forward and sideways
tilt.(Refer to drawings below)

Ambient dimensions of one inverter

16 17
Please make sure the inverter is installed at the right place。The inverter
can’t install close to trunk

5.3. Mounting Inverter

Ambient dimensions of series inverters 5.3.1. Mounting bracket

There must be sufficient clearance between the individual inverters to In order to avoid electrical shock or other injury, inspect existing
ensure that the cooling air of the adjacent inverter is not taken in. electronic or plumbing installations before drilling holes.
If necessary, increase the clearance spaces and make sure there is enough
fresh air supply to ensure sufficient cooling of the inverters.
DANGER
The inverter can’t install to solarization,drench,firn location. We suggest
that the inverters should be installed at the location with some cover or 1.According to the following distance to drill two holes on the wall;
protection
2.Install the explosion screw into the wall;

Falling equipment can cause serious or even fatal injury, never


mount the inverter on the bracket unless you are sure that the
mounting frame is really firmly mounted on the wall after
WARNING carefully checking.

18 19
5.3.2. Mounting Inverter 5.4. Connect switch

Separate the Growatt inverter securely from the grid and the PV generators using
Referring to the following figure, make the inverter and explosion screw
DC and AC Switch. You must provide an AC circuit breaker. If Growatt DC Switch
matching,
Hang the inverter on the explosion screw is included in the delivery of the Growatt inverter, it must be used for operating the
inverter.

5.5. Grounding

The Growatt 1000-S-3000-S series are transformerless inverters. That is why it


has no galvanic separation. Do not ground the DC circuits of the PV modules
connected to the inverter. Only ground the mounting frame of the PV modules. If
you connect grounded modules to the inverter, the error message "PV ISO Low".

The inverter must be connected to the AC grounding conductor of the power


distribution grid via the ground terminal (PE)

Because of the transformerless design, the DC positive pole and


DC negative pole of PV arrays are not permitted to be grounded.
WARNING

Connecting the Second Protective Conductor


5.6. Connect grid type
If the installation requires, the earth terminal can be used to connect a second
TN-C grid suitable
protective conductor or as equipotential bonding. This prevents touch current
if the original protective conductor fails. TN-S grid suitable

Cable requirement: TN-C-S grid suitable


Earthing cable cross-section: 3.332 mm² at maximum
TT grid suitable

20 21
5.7. Electrical connection 3.Remove the parts of the AC connection plug from the accessory bag.Guide the
pressure screw, sealing ring, threaded sleeve over the AC cable
5.7.1. Safety

Danger to life due to lethal voltages!


High voltages which may cause electric shocks are present in the
conductive parts of the inverter. Prior to performing any work on
DANGER the inverter, disconnect the inverter on the AC and DC sides.
socket element threaded sleeve sealing ring pressure screw

Danger of damage to electronic components due to electrostatic


discharge.
Take appropriate ESD precautions when replacing and installing 4.Insert the stripped and bared conductors L,N,PE into the screw terminals with
WARNING the inverter. sign L,N,PE on the socket element and tighten the screws firmly.

5.7.2. Connection to the grid(AC)


You must install a separate single-phase circuit-breaker or other
load disconnection unit for each inverter in order to ensure that the
inverter can be safely disconnected under load.

NOTE: The inverter is equipped with integrated RCM(Residual


WARNING current operated monitor)and RCD(Residual current and protective
device) which are used for preventing from being electric shock. An
external built RCD in fact is not necessary . Connect the connector
If the network operator stipulate an external built RCD,you must
choose a residual-current protective device that triggers in the
5.Push the threaded sleeve into the socket element; screw the pressure screw
event of residual current more than 300mA.
tightly onto the threaded sleeve;
Please connect AC cable obey the following procedures:

1.Switch off AC breaker and secure against being inadvertently switched back on.
About the AC breaker,please refer to the below form .
Types Max current output Suggested AC switch spec
Growatt 1000-S 4.7A 400Vac/10A
Growatt 1500-S 7.8A 400Vac/16A
Growatt 2000-S 9.5A 400Vac/16A
Growatt 2500-S 11.9A 400Vac/16A
Growatt 3000-S 14.3A 400Vac/16A
Close the connector
2. The grid connection is made using 3 conductors (L, N, and PE),We recommend
the following requirements for Growatt 1000-S/ Growatt 1500-S/Growatt 2000- 6.Finally, insert the AC connection plug into the AC connection receptacle on the
S/Growatt 2500-S/Growatt 3000-S. inverter.
Model _(mm) Area(mm2) AWG no. MAX.cable length(m)
Growatt 1000-S _ 2.05 3.332 12 63
Growatt 1500-S _ 2.05 3.332 12 45
Growatt 2000-S _ 2.05 3.332 12 47
Growatt 2500-S _ 2.05 3.332 12 34
Lock the housing Unlock the housing
Growatt 3000-S _ 2.05 3.332 12 32
22 23
5.7.3. Connecting the PV array 5.7.3.2. Connecting the PV array (DC)

Danger to life due to lethal voltages!


Before connecting the PV array, ensure that the DC switch and AC breaker
5.7.3.1. Conditions for DC connection are disconnect from the inverter.Never connect or disconnect the DC
DANGER connectors under load.

The inverter has 1 independent string input.


Improper operation during the wiring process can cause fatal injury to
The diagram drawing of DC side is shown as below, notice that the connectors are
operator or unrecoverable damage to the inverter. Only qualified personnel
in paired (male and female connectors). The connectors for PV arrays and
can perform the wiring work.
inverters are H4 connectors; WARNING

Risk of damage to the inverter.


If the voltage of the PV modules exceeds the maximum input voltage of the
inverter, it can be destroyed by the overvoltage. This will void all warranty
claims.Do not connect strings to the inverter that have an open-circuit
WARNING
voltage greater than the maximum input voltage of the inverter.

Check the connection cables of the PV modules for correct polarity and make sure that the
maximum input voltage of the inverter is not exceeded. At an ambient temperature over 10
℃, the open circuit voltage of the PV modules should not exceed 90% of the maximum input
voltage of the inverter. Otherwise, the maximum inverter input voltage may be exceeded at
low ambient temperatures.

5.7.4 Inverter demand response modes (DRMs,only for Australia)


Requirements for the PV modules of the connected strings:
Same type This series inverter has the function of demand response modes,moreover, We
Same quantity of PV modules connected in series use RJ45 socket as inverter DRED connection.

5.7.4.1 RJ45 socket pin assignment


Assignment for inverterscapable of
PIN Pin Assignments Front View
both charging and discharging
If the inverter is not equipped with a DC switch but this is mandatory 1 DRM5
12345678
in the country of installation, install an external DC switch. 2 DRM6
1 → 8
The following limit values at the DC input of the inverter must not be 3 DRM7
CAUTION 4 DRM8
exceeded:
5 RefGen
Typ es M ax current input
6 COM/DRM0
G row att 1000 -S 1 0A
7 /
G row att 1500 -S 1 0A RJ45 Socket RJ45 Plug
8 /
G row att 2000 -S 11A
G row att 2500 -S 1 2A
G row att 3000 -S 1 3A 5.7.4.2 Method of asserting demand response modes
Rj45 socket
MODE Asserted by shorting pins Requirement

DRM0 5 6 Operate the disconnection device


DRM5 1 5 Do not generate power
DRM6 2 5 Do not generate at more than 50% of rated power
DRM7 3 5 Do not generate at more than 75% of rated power
AND Sink reactive power if capabie
DRM8 4 5 Increase power generation (subject to constraints
from other active DRMs)
24 25
6 Commissioning
3. Single knock to “set LCD contrast” →Double knock to enter “LCD contrast 2”
6.1. Parameters setting →Single knock to select the luminance. You also need to wait a few seconds
after selecting. When the display becomes dark, the change is saved.
Users can use sound control function to change the display language and
luminance of the display, enable auto-test function and choose utility model.
6.1.3. Set communication address
6.1 .1. Language setting 1. If you want to set communication address, repeat the steps as described in
section 6.1.1.
Before entering the ‘Set Language’ interface, you need to enter a password as 2. When LCD displays ‘INPUT 123:123’, triple knock to enter the setting interface.
below:

COM Address:xx
Setting…
3. Single knock to “COM Address: xx” →Double knock change the address to set
model →Single knock to set address. After selecting, you need to wait a few
INPUT 123:XXX seconds until the display becomes dark, then the change is saved.

6.1.4. Set Queensland grid voltage range


According to the LCD display,you need to input three numbers: 123.You should
finish several steps as below:
1. If you want to set Queensland grid voltage range , repeat the steps as
1. When the LCD stays bright, single knock to ‘Setting…’,and then double knock to described in section 6.1.1.
enter ‘INPUT 123:xxx’interface. 2. When LCD displays ‘INPUT 123:123’, triple knock to enter the setting interface.
2. Double knock to make the first number flash, single knock to change the
number, and the first number you need to input is ‘1’. Double knock to enter the
second number while the first number was ‘1’. Model: GTXXXXXX
3. When the second number is flashing ,single knock to change the number,and
the second number you need to input is ‘2’. Double knock to enter the last number
while the first number was ‘2’.
4. When LCD displays ‘INPUT 123:123’, triple knock to enter the setting interface. 3. Single knock to item “Model: GTXXXXXX” -> Double knock to enter “Normal
Volt range” -> Single knock to change it to “Qld Vmax 255V” -> wait until the
display become dark, then the inverter saved change.
Set Language
This function is only for Ergon Energy area, Queensland, Australia.
5. Single knock to “set language” →Double knock enter “language: English” NOTICE
→Single knock to select the language. After setting, you need to wait a few
seconds until the display becomes dark, then the setting will be saved.
6.1.5. Run auto test function(only for Italy)
6.1.2. Set luminance of LCD display
1. If you want to set luminance of LCD display, repeat the steps as described in Enable Auto test
section 6.1.1.
2. When LCD displays ‘INPUT 123:123’, triple knock to enter the setting interface.
Single knock to make the display become bright → Single knock to “Enable Auto
test” →Double knock to enter “Waiting to start” →Single knock to start auto test. and
Set LCD contrast then waiting several minutes for the test result.

26 27
If the country you want to select is not in the above list, please
6.2. Independent function option
directly select VDE0126-1-1.
Netherlands select VDE0126-1-1.
NOTICE
6.2.1. Country selecting

When the PV panels are connected and their output voltage is greater than 70Vdc Please finish the country selecting according to the following steps
but the AC grid is not yet connected, inverter will start up automatically. If it is the
first time to power on the inverter after installation, you may need to select a A The LCD will quickly switch to and stay at the 'Please select' interface after
specific country.Otherwise, the interface will stay at the ‘Please Select’ interface power on, as below:
all the time. There are eleven options to select, as the list below.

If you have ordered the inverter with specific country settings, the
parameters have been preset in factory and you don't need to B Single knock on the LCD, countries will vary from one to another along the
operate this step any more. above list order. below acts as an example, and Germany is the second
Information selection.
This series inverter in Hungary market has not country settings.

Country/Regulation Name options


C When you need to select any of these countries, you can Double knock to
VDE0126-1-1 // 0 enter the next interface. Here we select Italy as an example, as below:

Germany //1

UK_G83 //2

Italy //3 D When the country arrives at Italy, Double knock to enter the two options 'YES'
and 'NO', and the cursor stays at 'NO' in default, as below:
France //4

Denmark //5

Belgium //6
E Single knock to select 'YES', as below:
Spain //7

Greece //8

Turkey //9
F Double knock to confirm your selection, LCD will display 'Select OK' with the
country name in the below, as below:

28 29
if you still single knock at the interface as E, the cursor will go to
'NO' again as D, then if you double knock, the display will switch to
Information the interface as C.

G When the selection is successful, the inverter will reboot automatically

If you have selected and confirmed an unwanted country neglectful,


please contact Growatt for specific software to clear and reset
Information again.
Wait the test finish, there are 8 levels testing;

6.2.2.Auto test

6.2.2.1.Spec of the CEI 0-21 SPI

SPI function:the integrated SPI consists of 4 voltage level protection and 2


frequency range protection. The protection logic is as follows:

The test result data is saved in the “Auto test report of xxxxxx .txt” under the
Software install direction;

6.2.2.2.Autotest

Connect the Inverter and the PC by RS232;


Power on the inverter, check the inverter com address, and wait the inverter to
connect to grid;
Open the PC software ShineBus, and select page “5 Auto Test”; set the PC com
port(COM) and the inverter com address(Inv Add);
Click button “Test” to test the SPI function;

30 31
Test fail condition:
6.3. LCD display
In the lower center of inverter there is the LCD display. We can check inverter
running status, etc. on the LCD screen. Items displayed can be changed by knock;
Condition Reason Suggestion
you can also change some inverter parameters by knock.
Test Stop Communication lose or inverter Check the communication or
occur other fault when testing check the inverter state

Test fail The trip value of the test result is Check the grid state, make sure 6.3.1. General LCD display
not in the limit of the spec the grid is stable, and retest
Starting-up display sequence , once the PV power is sufficient , inverter displays
information as shown in the flow chart as follow:
6.2.3. GFCI function

GFCI is short for Ground-Fault Circuit Interrupter which is used for preventing
from being electric shock. The inverter is equipped with integrated RCD (Residual
Current Protective Device) and RCM (Residual Current Operated Monitor). The
current sensor will detect the volume of the leakage current and compare it with
the pre-set value. If the leakage current is above the permitted range, the RCD will
disconnect the inverter from the AC load.

6.2.4. PV isolation detection


Power on LCD display
The ISO function a protection mechanism. The inverter measures the resistances
between both the positive pole and negative pole of PV panel and earth. 6.3.1.1. The first line of LCD
Either of the measured value is lower than the limit, the PV inverter will not
connect to grid, the output relay will stay open, and show 'PV isolation low'. The
limited value is determined by the standards. The firmware setting of our PV STATUS DISPLAY CONTENT REMARK
inverters is 500Kohm. Waiting Waiting When the input voltage is between 70V and
The simplified principle of the isolation resistance measurement is described as 80V during start up, inverter will display
below: ‘waiting’
Standby When the input voltage falls to 70V,inverter
will display standby.The inverter will shut
down when input voltage is lower than 60V.
Connect in xxS System checking

Reconnect in xxS System checking

Normal Connect OK Connecting to the grid


Power: xxxx.xW Inverter output power in normal mode.

Fault Error: xxx System fault


Auto Test Auto Testing Protecting function

Programming Programming Firmware update

32 33
In fault mode, there can be different error messages displayed
in the LCD due to different faults. Please refer to Chapter 10 for
4 Setting status
reference.The first line of LCD display can be changed by knock Setting...
Information on the LCD screen. The second line automatically changes in
the interval of 2 or 4 seconds as above Table.

6.3.2. LCD control


6.3.1.2. The second line of LCD
CYCLE DISPLAY DISPLAY TIME/S REMARK To save power, the LCD display's background light will turn off automatically in
10 seconds. Single knock will turn on the background light. The display on the
inverter can be controlled by knocking the sound control panel in front of it.
2 Model number of the inverter

2 Firmware version of the inverter

2 Serial number, which is also shown on

Energy generated today.For accurate


4 energy to get the FIT payment, please 6.4. Communication
refer to your meter

A detailed wiring diagram and installation description can be found in the


Total generated energy since installation. communication module manual.
4 For accurate energy to get the FIT
payment, please refer to your meter

6.4.1. RS232 (standard)


Power : 2015.0W PV voltage (PV) and Bus voltage (B)
4
PV : 250V B: 360V
RS 232 is used for single point communication. Use a RS 232 cable to
connect from inverter's RS 232 port to computer's RS 232 port, or to connect
to a RS232-to-USB converter, then connect to computer's USB port. And then
4 Grid voltage (AC) and frequency (F) run ShineNet to monitor the inverter.

4 Enable auto test function 6.4.2. WIFI (Optional)

WiFi module (It is available from Growatt.)can be used as an optional monitoring


scheme. The ways to install the WIFI modules and to monitor your inverters
refer to the WIFI module manual.
4 Communication address of the inverter

34 35
6.5. Commissioning the inverter Features:
Monitor and record current data and of inverters.
Record historical data.
1. If the inverter connects with PV panel arrays and the input voltage is higher than Monitor and record event information of inverter
70Vdc, while the AC grid is not connected yet, LCD will display messages in order Connect computer and inverter via RS232 and RS485 port (wire connection)
as below: or Bluetooth module (wireless connection).
‘Ser NO: xxx'->'xxxxx'->'FW version'->'Waiting'->'No AC connection', the display Remote access available for local area network.
repeats 'NO Utility' and LED will be red.

2. Turn on the AC breaker or close the fuse between inverter and grid, the system Users are able to monitor the inverter after the setting of
will operate normally. software. Detailed information about setting and functions refer
to the ShineNET Manual.
3. Under normal operating conditions, the LCD displays 'Power: xxx.x W' at State
Yo u c a n d o w n l o a d t h e S h i n e N e t Y N 2 . 0 f r o m :
info, this is the power fed into grid. LED turns green.
Information ftp://113.106.58.169, the user name is ftpguest and Password is
4. Finish commissioning. ftpguest.
ShineNet may be upgraded for better function or user
experience, please refer to the actual software version.

6.6. Monitoring tool instructions 6.6.2. ShineVision

ShineVision is a wireless monitoring device, which consists of a power monitor


6.6.1. ShineNet
and a number of transmitters, and one shinevision can monitoring 1 to 6
inverters. The transmitters transmit the running data collected from photovoltaic
ShineNet is a monitoring software applied to monitor Growatt inverters via RS232 inverters to the monitor and display the data onto the monitor screen, including
port or Bluetooth module. With the special designed functions and friendly data of generated energy, the gross generated energy and the generation income
compact UI, it can comprehensively meet users' requirements for system obtained from the above-mentioned data through some simple calculations,
monitoring and bring unprecedented user experience. indoor temperature, date and time, as well as CO2 emissions.

Features:
Monitor and transmitter communicate via wireless communication technology.
External transmitter, with IP65 waterproof and dustproof.
A monitor can simultaneously communicate with six transmitters.
Communication distance between monitor and transmitter : 30 meter.
Power supply option: built-in battery slot, an external DC power supply.
Easy installation, and convenient to use it.

The Monitor should be kept indoor. For detailed information,


please refer to ShineVision Manual.
Information

36 37
Startup and Shutdown the Inverter 7
6.6.3. ShineWebBox

It is a cost-effective and compact monitoring device, specially designed for solar


7.1. Start up the Inverter
power plant. Using stable Linux operating system with high-speed CPU, it can
smartly record your system features. ShineWebBox Provides local storage, easy 1. Connect the line circuit breaker from single phase.
2. Turn on the DC switch, and the inverter will start automatically when the input
wireless and TCP/IP configuration, and presents plant data over Internet.
voltage is higher than 70V.

7.2. Shutdown the Inverter

1. Disconnect the line circuit breaker from single phase and prevent it from being
reactivated.
2. Turn off the dc switch.
Features:
3. Check the inverter operating status.
A multi-functional and high-performance communication data logger; Keep user 4. Waiting until LED, display have gone out, the inverter is shut down.
informed of the system’s status at any time.
Massive storage with flexible parameters setting, system information
management, error prompt and record.
Collects data and uploads information over the internet in near real-time to
Growatt Shine Server platform.

38 39
8 Operation Modes Maintenance and Cleaning 9
8.1. Waiting mode
9.1. Checking heat dissipation
When the PV voltage is higher than 70V, Inverter will be powered up, and enters
“waiting” mode.
In this mode, inverter will check the system parameters. If the system is normal,
and PV voltage is higher than 80Vdc, the inverter will attempt to connect to grid. If the inverter regularly reduces its output power due to high temperature, please
improve the heat dissipation condition. Maybe you need to clean the heat sink.

8.2. Normal mode

In this mode, the inverter works normally and LED turns green. 9.2. Checking the DC switch
Whenever the DC voltage is higher than 80Vdc, inverter converts power to grid
as generated by the PV panels;
Whenever the DC voltage is lower than 70Vdc, the inverter will work in standby Checking externally visible damage and discoloration of the DC switch. If there is
state and attempt to connect the grid. In waiting state the inverter consumes any visible damage to the DC Disconnect, or visible discoloration, contact the
just enough power generated by the PV panel to monitor the internal system installer.
status; Once a year, turn the rotary switch from the On position to the Off position 5 times
in succession. This cleans the contacts of the rotary switch and prolongs the
The inverter starts up automatically when the DC power from the electrical endurance of the DC Disconnect
PV panel is sufficient.
Information

8.3. Fault mode

The internal intelligent controller can continuously monitor and adjust the system
status. If inverter finds any unexpected conditions such as system fault and
inverter fault, the fault information will be displayed on the LCD. In fault mode the
LED turns red.

Detailed fault information refers to chapter 10 Troubleshooting.


Information
9.3. Cleaning the Inverter

8.4. Shutdown mode


If the inverter is dirty, clean the enclosure lid, the display, and the LEDs using only
Inverters automatically stop running during periods of little or no sunlight. In
clean water and a cloth. Do not use any cleaning agents (e.g. solvents or
shutdown mode the inverters take no power from the grid and panel, and the LCD
abrasives).
and LED turns off.

If the PV string DC voltage is too low (≤ 60 Vdc) or DC switch


open, the inverter will also turn to shutdown Mode
Information

40 41
10 Trouble Shooting
Sometimes, the PV inverter does not work normally, we recommend the following If the suggestions do not work, please connect to the Growatt.
solutions for common troubleshooting. The following table can help the technician Information
to understand the problem and take action.

10.1 Warnings(W)
10.2 Errors(E)
Warnings(W) identify the current status of the Growatt inverter. Warnings do not
relate to a fault. When a (W) with a number after it appears in the display, it Errors(E) codes identify a possible equipment failure, fault or incorrect inverter
indicates a Warning Code and is usually cleared through an orderly shutdown/re- setting or configuration. Any and all attempts to correct or clear a fault must be
set or a self corrective action performed by the inverter. See the (W) codes in the performed by qualified personnel. Typically, the (E) code can be cleared once the
following table. cause or fault is removed. Some of the (E) codes, Error as indicated in the table
below, may indicate a fatal error and require you to contact the supplier or the
Error message Description Suggestion Growatt to replace a new one.

No utility grid 1.Check AC wiring.


No AC Connection connected or utility 2.Contact Growatt. Error code Description Suggestion
grid power failure.

Utility grid voltage is 1.Check grid voltage. Error: 101 Communication fault Slave 1.Restart inverter
AC V Outrange out of permissible 2.If the error message still exists processor can't receive data 2.If error message still exists,
range. despite the grid voltage being within from Master processor. contact Growatt.
the tolerable range, contact Growatt.
Utility grid frequency 1.Check grid frequency. Error: 102 Consistent fault. Data 1.Restart inverter.
AC F Outrange out of permissible 2.If the error message is displayed received by Master and Slave 2.If error message appears
range. despite the grid frequency being within processor are different. The frequently or error message
the tolerable range, contact Growatt. reason can be utility grid still exists after replacement,
voltage or frequency change check utility grid. If you require
1.check the inverter operation state frequently. . help, contact Growatt.
Over Temperature Temperature outrange 2.If the error message is displayed still, 3.If error message still exists,
please contact Growatt. contact Growatt.

1.Check if panel enclosure ground


Error: 116 EEPROM fault Contact Growatt.
properly.
2.Check if inverter ground properly.
PV Isolation Low Insulation problem 3.Check if the DC breaker gets wet. Error: 117 Relay fault Contact Growatt.
4.If the error message is displayed
despite the above checking passed,
Error: 118 Init model fault Contact Growatt.
contact Growatt.

Output current DC 1.Restart inverter. Error: 119 GFCI Device Damage Contact Growatt.
Output High DCI offset too high 2.If error message still exists,
contact Growatt.
Error: 120 HCT fault Contact Growatt.
Leakage current 1.Restart inverter.
Residual I High
too high 2.If error message still exists,
contact Growatt. Error: 121 Communication fault. 1.Restart the inverter
Master processor can't 2.If error message still exists,
The DC input receive data from Slave contact Growatt..
voltage is exceeding Disconnect the DC switch
PV Voltage High processor.
the maximum tolerable immediately.
value.
Error: 122 Bus voltage fault Contact Growatt.
Auto Test Failed Auto test didn't passed. Restart inverter

42 43
11 Decommissioning Technical Data 12
11.1. Dismantling the Inverter 12.1. Specification

1. Disconnect the inverter as described in section 7.


2. Remove all connection cables from the inverter.
Model Growatt Growatt Growatt Growatt Growatt
1000-S 1500-S 2000-S 2500-S 3000-S
Input data(DC)
Danger of burn injuries due to hot enclosure parts!
Wait 20 minutes before disassembling until the housing Max. DC power 1300W 1800W 2300W 2900W 3400W
has cooled down.
CAUTION Max. DC voltage 450V 450V 450V 500V 550V

Start voltage 80V 80V 80V 80V 80V

3. Screw off all projecting cable glands. PV voltage range 70V-450V 70V-450V 70V-450V 70V-500V 70V-550V
4. Lift the inverter off the bracket and unscrew the bracket screws.
MPP work voltage 70V-450V 70V-450V 70V-450V 70V-500V 70V-550V
range/ nominal /180V /250V /360V /360V /360V
voltage
11.2. Packing the Inverter Full load dc voltage 110V-400V 175V-400V 200V-400V 220V-450V 250V-500V
range
If possible, always pack the inverter in its original carton and secure it with tension Max. input current 10A 10A 11A 12A 13A
belts. If it is no longer available, you can also use an equivalent carton. The box
must be capable of being closed completely and made to support both the weight Max. input current
10A 10A 11A 12A 13A
per string
and the size of the inverter.
Number of independent 1/1 1/1 1/1 1/1 1/1
MPP trackers / strings per
MPP tracker
11.3. Storing the Inverter
Output (AC)
Store the inverter in a dry place where ambient temperatures are always between -
25°C and +60°C. Rated AC output
1000W 1600W 2000W 2500W 3000W
power

11.4. Disposing of the Inverter Max. AC power 1000W 1650W 2000W 2500W 3000W

Max. output 4.7A 7.8A 9.5A 11.9A 14.3A


Do not dispose of faulty inverters or accessories together with current
household waste. Please accordance with the disposal regulations for
AC nominal
electronic waste which apply at the installation site at that time. Ensure 220V/230V/240V; 180Vac-280Vac
voltage; range
that the old unit and, where applicable, any accessories are disposed of
in a proper manner. AC grid
50,60H z ;±5 Hz
frequency; range

Power factor 1 1 1 1 1

THDI <3% <3% <3% <3% <3%

AC connection Single phase Single phase Single phase Single phase Single phase

44 45
Efficiency Features

Max. efficiency 97.4% 97.4% 97.4% 97.6% 97.6%


DC connection H4 H4 H4 H4 H4

Euro weighted AC connection connector connector connector connector connector


96.5% 97% 97% 97.1% 97.3%
efficiency Display LCD LCD LCD LCD LCD

MPPT efficiency 99.5% 99.5% 99.5% 99.5% 99.5% Interfaces: RS232/Wifi yes/opt yes/opt yes/opt yes/opt yes/opt

Warranty: 5 years yes /opt yes /opt yes /opt yes /opt yes /opt
Protection devices / 10 years
DC reverse polarity yes yes yes yes yes
Certificates and approvals CE, VDE 0126-1-1, VDE-AR-N-4105,IEC 62109, G83,
protection AS4777, NBT32004-2013, EN50438, CEI 0-21,INMETRO

DC switch rating for


each MPPT
yes yes yes yes yes
12.2. DC connector info
Output over current yes yes yes yes yes
protection
DC connection H4
Output over voltage yes yes yes yes yes
protection-varistor

Ground fault yes yes yes yes yes


monitoring
12.3. Trip volatge &Trip frequency
Grid monitoring yes yes yes yes yes

Integrated all - pole sensitive yes yes yes yes yes Country Undervoltage Overvoltage Underfrequncy Overfrequncy
leakage current monitoring unit

Australia 207V 263V 46.0Hz 54.0Hz


General Data Spain 196V 252V 48.0Hz 50.5Hz

Dimensions (W / H / D) 271/267/142 271/267/142 271/267/142 271/320/142 271/320/142 Greece 184V 264V 47.5Hz 51.0Hz
in mm
Germany 184V 252V 47.53Hz 51.47Hz
Weight 6.1KG 6.1KG 6.1KG 8.8KG 8.8KG

Operating temperature –25°C ... +60°C (-13...+140℉) with derating above 45°C /113℉ UK 201V 251V 47.5Hz 51.5Hz
range
Ireland 207V 253V 48Hz 50.5Hz
Noise emission (typical) ≤ 25 dB(A) ≤ 25 dB(A) ≤ 25 dB(A) ≤ 25 dB(A) ≤ 25 dB(A)
China 195.5V 253V 49.5Hz 50.2Hz
Altitude 2000m(6560ft) without derating
Denmark 207V 253V 47.5Hz 52.0Hz
Self-Consumption < 0.5 W < 0.5 W < 0.5 W < 0.5 W < 0.5 W
night Hungary 195.5V 253V 49.0Hz 51.0Hz
Topology transformerless
Italy 195.5V 264.5V 47.5Hz 51.5Hz
Cooling concept Natural Natural Natural Natural Natural
Belgium 195.5V 253V 47.5Hz 50.5Hz
Environmental Protection Ip65 Ip65 Ip65 Ip65 Ip65
Rating

Relative humidity 100% 100% 100% 100% 100%

46 47
PV System Installation 13
12.4. Torque

Enclosure lid screws 7kg.cm


13.1. Single inverter
Shell and RS232 screws 7kg.cm

AC terminal 6kg.cm

Additional ground screws 20kg.cm

12.5. Accessories
13.2. Multi inverters
In the following table you will find the optional accessories for your product. If
required, you can order these from SHENZHEN GROWATT NEW ENERGY
TECHNOLOGY CO.,LTD or your dealer.

Name Brief description

WIFI

48 49
14 Compliance Certificates

14.1. List

Growatt1000-S-3000-S

Certificates CE, VDE 0126-1-1, VDE-AR-N-4105,IEC 62109, AS4777, NBT32004-2013,


EN50438, CEI 0-21,INMETRO
Declaration G83

14.2. Download address


www.ginverter.com/Download.aspx

15 Contact
If you have technical problems about our products, contact the GROWATT
Serviceline. We need the following information in order to provide you with the
necessary assistance:
Inverter type
Serial number of the inverter
Event number or display message of the inverter
Type and number of PV modules connected
Optional equipment

Shenzhen Growatt New Energy Technology CO.,LTD


Building B, Jiayu Industrial Park, #28, GuangHui Road,
Shiyan Street, Baoan District, Shenzhen, P.R.China

T 0755-2951 5888
F 0755-2747 2131
E service@ginverter.com
W www.ginverter.com

50

You might also like