1 Notes on this manual
1.1 Validity
This manual will provide detailed product information and installation instructions for CAUTION indicates a hazardous situation which, if not avoided,
users of model TL3-X series photovoltaic inverter of Shenzhen Growatt new energy Co., could result in minor or moderate injury.
CAUTION
Ltd. (hereinafter referred to as Growatt new energy). Please read this manual carefully
before using this product. Growatt new energy will not inform users of any changes to
this manual.
MOD 3000TL3-X NOTICE is used to address practices not related to personal injury.
MOD 4000TL3-X NOTICE
MOD 5000TL3-X
MOD 6000TL3-X Information that you must read and know to ensure optimal
MOD 7000TL3-X operation of the system.
MOD 7000TL3-X-AU Information
MOD 8000TL3-X
MOD 8000TL3-X-AU
MOD 9000TL3-X
MOD 9000TL3-X-AU
1.3.2 Markings on this product
MOD 10KTL3-X
MOD 10KTL3-X-AU Symbol Explanation
MOD 11KTL3-X
MOD 11KTL3-X-AU
MOD 12KTL3-X Danger: Electricity!
MOD 13KTL3-X
MOD 15KTL3-X
Danger:Flame!
1.2 Applicable personnel
The inverter must be installed by professional electricians who are certified by relevant
departments. By reading this manual in detail, the installer can install the MOD TL3-X Danger:Hot surface!
series inverter correctly and quickly, and can carry out troubleshooting and
communication system construction.
Operation after 5 minutes
If there are any problems during the installation process, the installer can log on to
www.growatt.com to leave a message on the website or call our 24-hour service
phone: +86 755 2747 1942 . Point of connection for grounding protection
3 4
2.2 Qualification of skilled person 2.3.2 Electrical Connection Warnings
This grid-tied inverter system operates only when properly connected to the AC
distribution network. Before connecting the MOD TL3-X to the power distribution grid,
contact the local power distribution grid company. This connection must be made only Ø The components in the inverter are live. Touching live components
by qualified technical personnel to connect, and only after receiving appropriate can result in serious injury or death.
approvals, as required by the local authority having jurisdiction. Ÿ Do not open the inverter except the wire box by qualified persons.
Ÿ Electrical installation, repairs and conversions may only be carried
2.3 Safety instructions out by electrically qualified persons.
1.Please read this manual carefully before installation.If you fail to install according Ÿ Forbid live line work.
to the instructions in this manual,or ignore the warnings in the manual and the Ø Danger to life due to high voltages in the inverter
equipment is damaged,our company reserves the right not to guarantee the quality; Ÿ There is residual voltage in the inverter after the device shutdown.
2.All operations and wiring should be finished by the professional electrical or mechanic- The inverter need to take 20 minutes to discharge for safety.
al engineers; DANGER
Ø Persons with limited physical or mental abilities may only work
3.During installation,except for the wiring terminals,please do not move other parts with the Growatt inverter following proper instruction and under
inside the chassis; constant supervision. Must keep the Growatt inverter away from
4.All electrical installations must comply with local electrical safety standards; children.
5.If the machine needs maintenance,please contact the local designated system
installation and maintenance personnel;
6.The use of this machine for grid-connected power generation requires permission
from the local power supply department; Ø Make all electrical connections (e.g. conductor termination,
7.When installing photovoltaic modules during the day,use opaque materials to fuses, PE connection, etc.) in accordance with prevailing
cover the photovoltaic modules,otherwise the voltage at the module terminals will regulations. When using the inverter to provide the power,
be high in the sun,which may cause personal danger. adhere to all prevailing safety regulations to minimize risk of
accidents.
2.3.1 Assembly Warnings WARNING Ø Systems with inverters typically require additional control (e.g.,
Ø Before installation, pleae check the unit to ensure that there is no switches, disconnects) or protective devices (e.g., fusing circuit
transportation or handling damage, which may affect the breakers) depending upon the prevailing safety rules.
insulation integrity or safety clearances; otherwise, it may cause
safety hazards.
Ø Follow the instructions in this manual to assemble the inverter.
Note that select the suitable mounting location and comply with
the specified requirements of cooling.
Ø Unauthorized removal of necessary protections, improper use,
incorrect installation and operation may lead to serious safety and
WARNING
shock hazards and/or equipment damage.
Ø In order to minimize the possibility of shock hazards due to
dangerous voltages, cover the entire solar array with dark colored
materials before connecting the array to any equipment.
5 6
2.3.3 Operation Warnings
Product overview 3
3.1 Appearance overview
7 8
Unpacking inspection 4
3.2 Dimensions Before opening the inverter package,please check whether the outer package is
damaged.After unpacking,please check whether the appearance of the inverter is
damaged or lack of accessories.If there is damage or missing parts,please contact the
dealer.
A B C D E
F G H I J K L M N O P Q
Fig 3.2
J Expansion screw 3
K Security screw 1
9 10
5 Installation
5.1 Basic installation requirements
Ø The wall on which the inverter is mounted must be sturdy and can withstand the
weight of the inverter for a long time (refer to the specifications in Chapter 17 for the
weight of the inverter);
Ø The installation location must match the size of the inverter;
Ø Do not install the inverter on a building constructed of flammable or heat-resistant
materials;
Ø Install the inverter in an eye-view orientation to facilitate inspection of the OLED
display and maintenance work;
Ø The machine's degree of protection is IP66 and can be installed indoors and outdoors;
Ø It is not recommended to expose the inverter directly to strong sunlight to prevent
overheating and cause power derating;
Ø The humidity of the installation environment should be between 0 and 90%;
Ø The ambient temperature around the inverter should be between -25 ° C ~ 60 ° C;
Ø The inverter can be mounted on a plane that is tilted vertically or backwards.
Please refer to the following figure:
Fig 5.2 Installation dimensions for one inverter
Ø In order to ensure the normal operation of the machine and the convenience of
personnel operation, please pay attention to provide sufficient clearance for the inverter.
Please refer to the figure below:
Above 500
Fig 5.3 Installation dimensions for multiple inverters
Under 500
Ø Do not install the inverter on the TV antenna, other antennas or antenna cables;
Both sides 300
Ø Do not install the inverter in the living area;
Forward 300 Ø Do not install the inverter where children can reach it;
Ø The inverter should be installed in a sheltered and protected location such as cool,
rain-proof;
11 12
5.2 Install the wall mount
5.2.1 Install the wall mount
Fig 5.4 Installation Environment Secure the wall mount as shown, do not let the screws flush with the wall, instead expose
2 to 4 mm.
Ø Make sure that the inverter is installed in a suitable place and is not allowed to be
installed in a closed box;
Ø In order to reduce the inverter load and extend the life of the inverter due to direct
sunlight, we recommend installing a awning. The distance between the awning and the
inverter is as follows:
13 14
Inverter wiring 6
6.1 Security
There may be a high voltage in the conductive part of the inverter,
which may cause electric shock.Therefore, when installing the
inverter,make sure that the AC and DC sides of the inverter are
Danger
powered off.
Fig 5.9 Schematic diagram of inverter wall mounting 6.2 AC side wiring
Before making electrical connections, please make sure that the
DC switch of the inverter is in the "OFF" state and disconnect the
AC side MCB, otherwise the high voltage of the inverter may
Danger
cause death.
15 16
Preparation before wiring: AC connection steps:
Connect the protective ground wire (PE) 1.Pass the 5 wires (A,B,C,N and PE wires) through the AC shield,crimp the O/U terminal
Connect the inverter to the grounding bar through the protective earth (PE) to achieve and connect to the screw terminals on the AC connector.
grounding protection.
Ø Good grounding is good for resisting surge voltage impact
and improving EMI performance.Therefore,you need to ground
the wire before connecting the AC,DC,and communication a
cables.
Ø For a single-machine system,only the PE cable needs to be
grounded;For a multi-machine system,the PE cables of all
inverters need to be connected to the same grounding copper
bar to ensure equipotential connection.
c
Fig 6.1 Grounding diagram Fig 6.2 AC output wiring diagram
Ø Disconnect the inverter DC switch,AC side circuit breaker or switch.
Ø Measure the voltage and frequency of the public grid (voltage:AC 230V;
frequency:50Hz) 2.Lock the AC cable to the corresponding AC terminal.
Ø
The recommended specifications of the AC output switch are as follows:
6mm² 30m
8 mm² 40m
19 20
Moisture and dust penetration can damage the inverter. Connect DC terminal
Ø Make sure that the waterproof cable gland is firmly tightened.
Ø If the cable connector is not installed correctly,the inverter may be Positive connector
Cables Positive metal terminal
Note damaged due to the penetration of moisture and dust.All warranty claims
are void. 4~6mm²
4~6mm²
The MOD series inverter has two independent inputs, as shown in the figure below:
Cables
Negative metal terminal
Negative connector
Fig 6.9
3 4
1 2
21 22
2.Push the threaded sleeve into the socket and tighten the waterproof gland. 6.5 Grounding the inverter
Inverter side The inverter must be connected to the AC grounding conductor of the power distribution
grid via the ground terminal (PE) .
Click!
Fig 6.13
Remove the signal connector
1.Press down the fastener and pull it out of the inverter.
Fig 6.16
the inverter side
Fig 6.15
23 24
Lightning
6.6 Active power control with smart meter , CT or ripple control
protection device signal receiver
Distribution
Photovoltaic panel Inverter Cabinet
Lightning down the line
Safety
The position of export limitation CT or Meter must between the
interval S 4 1 2 3 Power grid Inverter & Load and gird.
SPD
Information
Grounding bar This series inverter has integrated export limitation functionality. To use this function,
you can connect the Growatt smart meter. For the detailed information, please contact
with Growatt.
Fig 6.17
Fig 6.18
1)It is generally recommended to install lightning protection devices (such as lightning
rods / lightning protection belts and down conductors) to prevent lightning from hitting Active power control with a Radio Ripple Control Receiver(RRCR).
the PV array. Radio ripple Public Grid
2) Lightning protection devices and down-conductors and related equipment in control receiver
photovoltaic systems (including photovoltaic panels, inverters, cables, power
distribution equipment) should maintain a safe separation distance S.
Suggested value of S: According to the general 5 storey height (about 15m) building
roof, S takes 2.5m enough, the distance S have relationship with the building height.
A. When the safety distance S is satisfied:
The position ①③ of the figure should be equipped with a lightning protection module. In Monitor
general, it is recommended to install Type II in position ① and Type I in position ③. Internet
25 26
6.8 Inverter demand response modes (DRMS) 6.8.3 Using the Power Control Interface for EU
This series inverter has the function of demand response modes, We use 16-Pin socket as RRCR
inverter DRMS connection.
6.8.2 Method of asserting demand response modes 6.8.3.2The inverter is preconfigured to the following RRCR power levels:
Socket asserted DRM Socket DRM Socket DRM Socket DRM Socket
Mode Function Active power Cos(φ)
by shorting pins Pin 9 Pin 10 Pin 11 Pin 12
DRM 0 14 13 Operate the disconnection device. Short circuit
0% 1
with Pin 13
DRM 5 9 13 Do not generate power.
Short circuit
30% 1
DRM 6 10 13 Do not generate at more than 50% of rated power. with Pin 13
Do not generate at more than 75% of rated power and Short circuit 1
DRM 7 11 13 60%
reduce the reactive power as far as possible. with Pin 13
Increase power generation (subject to constraints from Short circuit
DRM 8 12 13 100% 1
other active DRMs). with Pin 13
Active power control and reactive power control are enabled separately.
27 28
Debugging 7
6.9 AFCI(Optional) 1.Close the DC switch on the inverter.As long as the input DC voltage is greater
6.9.1 Arc-Fault Circuit Interrupter (AFCI) than 140V,the inverter display will show the following information:No mains
In accordance with the National Electrical Code R, Article 690.11, the inverter has a connection error,the inverter LED will turn red.
If other information is displayed,please refer to Chapter 13.If you encounter any
system for the recognition of electric arc detection and interruption. An electric arc
problems during the debugging process and cannot solve it,please contact customer
with a power of 300 W or greater must be interrupted by the AFCI within the time service.
specified by UL 1699B. A tripped AFCI can only be reset manually. You can deactivate 2.Close the circuit breaker or switch between the inverter and the grid, the inverter
the automatic arc fault detection and interruption (AFCI) via a communication product will start a countdown to the self-check,and after the self-check is normal,it will be
connected to the grid.
in "Installer" mode if you do not require the function. The 2011 edition of the National 3.In normal operation,the leaves of the inverter indicator window will turn green.
Electrical Code R, Section 690.11 stipulates that newly installed PV systems attached to 4.Finish debugging.
a building must be fitted with a means of detecting and disconnecting serial electric
arcs (AFCI) on the PV side.
If an "Error 200" message is displayed, the buzzer alarms, an electric arc occurred in
the PV system. The AFCI has tripped and the inverter is in permanent shutdown.
The inverter has large electrical potential differences between its conductors. Arc
flashes can occur through air when high-voltage current flows. Do not work on the
product during operation.
When the inverter error 200, please follow the steps:
Fig 6.21
Wait for the screen be off.
6.9.3.2 Perform troubleshooting on the PV system:
Check the PV strings' open circuit voltage is normal or not.
6.9.3.3 After the fault is rectified, restart the inverter:
Turn the DC & AC Switch to position "ON".
Fig 6.22
29 30
8 Working Mode OLED display and touch button 9
8.1 Normal mode The OLED display can display the running status of the inverter, as well as various
In this mode, the inverter works normally. parameters information, and the display interface of the inverter can be switched and
Ø When the DC voltage is greater than 250V, the energy is sufficient, and the grid the inverter parameters can be set by touching the button.
voltage frequency meets the grid-connected requirements, the inverter will convert
the energy of the solar panels into AC power and export to the grid, and the green Mark Describe Explain
LED will light up.
Switch the display interface or
Ø When the DC voltage is lower than 140V, the inverter will automatically disconnect Single touch
the current number plus 1
from the grid and exit the normal operation mode. When the input voltage reaches
Enter the setting state or
the requirement again and the grid voltage and frequency return to normal, the Double touch
confirm
inverter will automatically connect to the grid. Touch mark
Return to the previous display
Triple touch
interface
8.2 Failure mode The current data returns to the
The inverter controls the chip monitors and adjusts the state of the system in real time. Long press for 5s
default value
When the inverter monitors any unexpected conditions,such as system failure and
inverter failure,the display will show the fault information.In the failure mode,the 9.1 Boot display
inverter will indicate The leaves of the window will turn red and the inverter output will
be disconnected from the grid. When the inverter is turned on, the OLED display interface is as follows:
FW Ver:AK1.0
8.3 Shutdown mode
When the sunlight is weak or there is no sunlight,the inverter will automatically stop
Model:S03B00D
running.When in shutdown mode,the inverter basically does not consume energy from Growatt
00T00P00U00M0
the grid or solar panels,and at the same time,the inverter's display screen and LED lights PV inverter
000
will be turned off.
Connect in
More Info
30S
Power PV1
XXXXw XXXvXXXXw
Etoday PV2
XXXkWh XXXvXXXXw
Etotal Grid
XXXXw XXXvXXXHz
Fig 9.1
31 32
9.3 Function setting Tips and disclaimers
The inverter can support multiple touch modes: single touch, two When the inverter leaves the factory, the grid-connected voltage and frequency are set in
consecutive touches, three consecutive touches, long press for 5S. accordance with the latest domestic standard;
Different types of taps have different functions. Advanced setting If the grid voltage is lower or higher than the domestic legal requirements, the inverter
password: 123 cannot be connected to the grid. After obtaining the permission of the local power
operator, the user can choose other voltage levels according to the voltage situation of
the grid connection point.
All setting interfaces are as follows:
Excessive grid voltage may affect the normal use and service life of home
appliances on the grid-connected side,or cause loss of power generation.
Password General General Our company does not accept any responsibility for the related impacts and
123 Advanced Advanced
consequences caused by enabling the automatic control function of output
voltage to connect to the grid.
Set Country Set Country Set Language Set Language
Set OK Set OK
VDE0126 xxxxxxx English XXXXXXX
9.3.3 Set language
Enable NLine
Disable
Set OK AUTO TEST Waiting to start PASS
The default language is English,touch twice in a row to enter the setting mode,a single
Enable
touch to switch the language, and touch twice to confirm the setting.
Exporlimit Meter
Set OK Set Comaddr Set Comaddr Language Language Set
OFF ON CT 1 Set OK
2 English XXXX successfully
Reset factory
NO
Set OK
Set Date Set Date Set Date
Set OK
Fig 9.4
YES 2018-12-14 2018-12-14 2018-12-14
7 RS485A3 1 2
Meter communication port
8 RS485B3
Set Language
Reset factory Relay contact Relay contact 1 input/DRM5
English 9
1 /DRM 5 command Fig 10.2 just for Vietnam models
Relay contact Relay contact 2 input/DRM6
10 Description Remarks
2 /DRM 6 command No.
Set Date Set Time Relay contact Relay contact 3 input/DRM7
2018-12-14 12:30:00 11 1 RS485A1 RS485
3 /DRM 7 command
communication
Relay contact Relay contact 4 input/DRM8
12 2 RS485B1 port
4 /DRM 8 command
Set Date 13 REF/GEN Relay&DRM signal reference 3 RS485A2 Meter
Set Time
2018-12-14 communication
12:30:00
14 DRM0/COM DRM0 common node 4 RS485B2 port
10.2 USB-A
Set Date Set Time USB-A port is mainly used to connect monitoring module or firmware update:
2018-12-14 12:30:00 We can connect the external optional monitoring modules,such as Shine WIFI-X, Shine
Shine 4G-X, Shine LAN-X, etc. to the USB interface for monitoring.
Steps for installing the monitoring module: Make sure △ is on the front side, then insert
the datalogger and tighten the screws.
Set OK Set OK
Install Unistall
The inverter side
The inverter side
Fig 9.5 ▲up
9.3.6 Power derating for voltage variation (Volt-Watt mode)
The inverter power output will vary in response to the AC grid voltage. This is switched
on by default.This function belongs to advanced function, if you need to change, please
contact the after-sales operation and maintenance to make adjustments. The inverter side
The inverter side
39 40
13.3 System error Error code Description Suggest
Error code Description Suggest
1.Restart inverter
Error 400 DCI bias abnormal
1.After shutdown,Check the panel terminal. 2.If error message still exists, contact manufacturer.
Error 200 AFCI Fault 2.Restart inverter.
3.If error message still exists,contact manufacturer.
DC Voltage High 1.Restart inverter.
Error 401
Fault 2.If error message still exists,contact manufacturer.
L e a k a g e c u r re n t 1.Restart inverter.
Error 201
too high. 2.If error message still exists,contact manufacturer.
41 42
Manufacturer warranty 14
Error code Description Suggest Please refer to the warranty card.
1.Restart inverter.
Error 413 IGBT drive fault
2.If error message still exists,contact manufacturer.
1.Restart inverter
Error 414 EEPROM fault
2.If error message still exists, contact manufacturer. Decommissioning 15
Internal power
1.Restart inverter.
15.1 Dismantling the Inverter
Error 415 test fail(PV Power
2.If error message still exists,contact manufacturer. 1. Disconnect the inverter as described in section8.
low)
2. Remove all connection cables from the inverter.
Over current
1.Restart inverter.
Error 416 p r o t e c t e d b y
2.If error message still exists,contact manufacturer. Danger of burn injuries due to hot enclosure parts!
software
Wait 20 minutes before disassembling until the housing has cooled down.
The grid voltage 1.Restart the machine;
Error 417 sampling is 2.If the fault information still exists,contact the CAUTION
inconsistent manufacturer.
3. Screw off all projecting cable glands.
4. Lift the inverter off the bracket and unscrew the bracket screws.
1.Restart inverter
Error 425 AFCI self-test fault
2.If error message still exists, contact manufacturer.
43 44
16 EU Declaration of conformity Specification 17
With the scope of EU directives: 17.1 Parameter
•2014/35/EU Low Voltage Directive (LVD)
MOD MOD MOD MOD MOD MOD
•2014/30/EU Electromagnetic Compatibility Directive (EMC) Model
3000TL3- 4000TL3- 5000TL3- 6000TL3- 7000TL3- 8000TL3-
•2011/65/EU RoHS Directive and its amendment (EU)2015/863 Specifications
X X X X X X
Shenzhen Growatt New Energy Technology Co. Ltd confirms that the Growatt inverters
and accessories described in this document are in compliance with the above mentioned Input data(DC)
EU directives. The entire EU Declaration of Conformity can be found at www.ginverter.com. Max. recommended PV
4500W 6000W 7500W 9000W 10500W 12000W
power(for module STC)
Max. DC voltage 1100V
Start voltage 200V
Nominal voltage 580V
MPP voltage range 140-1000V
No. of MPP trackers 2
No. of PV strings per MPP
1/1 1/1 1/1 1/1 1/1 1/1
trackers
Max. input current per
13/13A 13/13A 13/13A 13/13A 13/13A 13/13A
MPP trackers
Max. short-circuit current
16/16A
per MPP trackers
Backfeed current to PV
0A
array
Output data(AC)
AC nominal power 3000W 4000W 5000W 6000W 7000W 8000W
Max. AC apparent 3300VA 4400VA 5500VA 6600VA 7700VA 8800W
Nominal AC voltage/range 230/400V
50/60 Hz
AC grid frequency/range
45~55Hz/55-65 Hz
Max. output current 5.0A 6.7A 8.3A 10.0A 11.7A 13.3A
AC inrush current 30A
Max. output fault current 24.6A 44.5A
Max. output overcurrent
24.6A 44.5A
Protection
Power factor(@nominal
>0.99
power)
Adjustable power factor 0.8Leading ...0.8Lagging
THDi <3%
AC grid connection type 3W+PE /3W+N+PE
Efficiency
Max. efficiency 98.3% 98.6%
Euro-eta 97%
45 46
MOD MOD MOD MOD MOD MOD
Model Model MOD MOD MOD MOD MOD MOD
3000TL3- 4000TL3- 5000TL3- 6000TL3- 7000TL3- 8000TL3-
Specifications Specifications 9000TL3-X 10TL3-X 11TL3-X 12TL3-X 13TL3-X 15TL3-X
X X X X X X
Protection devices Input data(DC)
DC reverse-polarity
YES Max. recommended PV
protection 13500W 15000W 16500W 18000W 19500W 22500W
power(for module STC)
DC switch YES
Max. DC voltage 1100V
DC Surge protection typeII OPT
Start voltage 200V
Insulation resistance
YES Nominal voltage 580V
monitoring
MPP voltage range 140-1000V
AC surge protection typeII OPT
No. of MPP trackers 2
AC short-circuit
YES No. of PV strings per MPP
protection 1/1 1/1 1/1 1/2 1/2 1/2
trackers
Grid monitoring YES
Max. input current per
13/13A 13/13A 13/13A 13/26A 13/26A 13/26A
Anti-islanding protection YES MPP trackers
Max. short-circuit current
Residual-current 16/16A 16/16A 16/16A 16/32A 16/32A 16/32A
YES per MPP trackers
monitoring unit
Backfeed current to PV
String Fuse protection NO 0A
array
String monitoring OPT Output data(AC)
AFCI protection OPT AC nominal power 9000W 10000W 11000W 12000W 13000W 15000W
Max. AC apparent 9900VA 11000VA 12100VA 13200VA 14300VA 165000VA
General data
Nominal AC voltage/range 230/400V
Dimensions (W / H / D) in
425*387*147mm 425*387* 178mm
mm 50/60 Hz
AC grid frequency/range
Weight 12.5kg 14kg 45~55Hz/55-65 Hz
Operating temperature -25°C ... +60°C Max. output current 15A 16.7A 18.3A 20.0A 21.7A 25A
range (>45°CDerating) AC inrush current 30A
Noise emission (typical) ≤35dB(A) Max. output fault current 44.5A 58.4A
Altitude 4000m Max. output overcurrent
44.5A 58.4A
Protection
Internal consumption at
1W Power factor(@nominal
night >0.99
power)
Topology Transformerless
Adjustable power factor 0.8Leading ...0.8Lagging
Cooling Natural heat dissipation THDi <3%
Electronics protection AC grid connection type 3W+PE /3W+N+PE
IP66
degree
Efficiency
Relative humidity 0~100%
Max. efficiency 98.6%
DC connection H4/MC4(OPT)
Euro-eta 97%
AC connection Waterproof PG head+OT terminal or quick connect terminal
Interfaces
Display OLED+LED
USB/RS485 YES
WIFI/GPRS/4G/RF/LAN OPT
47 48
Model MOD MOD MOD MOD MOD MOD
Australian models
Specifications 9000TL3-X 10KTL3-X 11KTL3-X 12KTL3-X 13KTL3-X 15KTL3-X MOD MOD MOD MOD MOD MOD
Model
3000TL3- 4000TL3- 5000TL3- 6000TL3- 7000TL3- 8000TL3-
Specifications
Protection devices X X X X X-AU X-AU
DC reverse-polarity Input data(DC)
YES
protection
Max. recommended PV
DC switch YES 4500W 6000W 7500W 9000W 10500W 12000W
power(for module STC)
DC Surge protection typeII OPT Max. DC voltage 1100V
Insulation resistance Start voltage 200V
YES
monitoring
Nominal voltage 580V
AC surge protection typeII OPT
MPP voltage range 140-1000V
AC short-circuit
YES No. of MPP trackers 2
protection
Grid monitoring YES No. of PV strings per MPP
1/1 1/1 1/1 1/1 1/2 1/2
trackers
Anti-islanding protection YES Max. input current per
13/13A 13/13A 13/13A 13/13A 13/26A 13/26A
MPP trackers
Residual-current
YES Max. short-circuit current
monitoring unit 16/16A 16/32A
per MPP trackers
String Fuse protection NO Backfeed current to PV
0A
String monitoring OPT array
Output data(AC)
AFCI protection OPT
AC nominal power 3000W 4000W 5000W 6000W 7000W 8000W
General data
Max. AC apparent 3000VA 4000VA 5000VA 6000VA 7000VA 8000W
Dimensions (W / H / D) in
425*387* 178mm Nominal AC voltage/range 230/400V
mm
Weight 14kg 16.0kg 50/60 Hz
AC grid frequency/range
45~55Hz/55-65 Hz
Operating temperature -25°C ... +60°C
range (>45°CDerating) Max. output current 4.5A 6.0A 7.6A 9.1A 10.6A 12.1A
Noise emission (typical) ≤35dB(A) AC inrush current 30A
Max. output fault current 24.6A 44.5A
Altitude 4000m
Max. output overcurrent
Internal consumption at 24.6A 44.5A
1W Protection
night
Power factor(@nominal
Topology Transformerless >0.99
power)
Cooling Natural heat dissipation Adjustable power factor 0.8Leading ...0.8Lagging
Electronics protection THDi <3%
IP66
degree AC grid connection type 3W+PE /3W+N+PE
Relative humidity 0~100% Efficiency
DC connection H4/MC4(OPT) Max. efficiency 98.3% 98.6%
AC connection Waterproof PG head+OT terminal or quick connect terminal Euro-eta 97%
Interfaces
Display OLED+LED
USB/RS485 YES
WIFI/GPRS/4G/RF/LAN OPT
49 50
MOD MOD MOD MOD MOD MOD MOD MOD MOD
Model Model MOD MOD MOD
3000TL3- 4000TL3- 5000TL3- 6000TL3- 7000TL3- 8000TL3- 9000TL3- 10TL3-X- 11TL3-X-
Specifications Specifications 12TL3-X 13TL3-X 15TL3-X
X X X X X-AU X-AU X-AU AU AU
Protection devices Input data(DC)
DC reverse-polarity
YES Max. recommended PV
protection 13500W 15000W 16500W 18000W 19500W 22500W
power(for module STC)
DC switch YES
Max. DC voltage 1100V
DC Surge protection typeII OPT Start voltage 200V
Insulation resistance Nominal voltage 580V
YES
monitoring
MPP voltage range 140-1000V
AC surge protection typeII OPT
Full-load voltage range 320-850V 400-850V 480-850V 520-850V
AC short-circuit
YES
protection No. of MPP trackers 2
Grid monitoring YES No. of PV strings per MPP
1/2 1/2 1/2 1/2 1/2 1/2
trackers
Anti-islanding protection YES Max. input current per
13/26A 13/26A 13/26A 13/26A 13/26A 13/26A
Residual-current MPP trackers
YES Max. short-circuit current
monitoring unit 16/32A 16/32A 16/32A 16/32A 16/32A 16/32A
per MPP trackers
String Fuse protection NO
Backfeed current to PV
0A
String monitoring OPT array
55 56