Model 4WI 100 - 800 HP Boilers: Oil-Fired Burners
Model 4WI 100 - 800 HP Boilers: Oil-Fired Burners
Model 4WI 100 - 800 HP Boilers: Oil-Fired Burners
Oil-Fired Burners
Fuel oil consumption information is shown on the boiler rating sheets in the Dimensions
and Rating Section.
Table A2-23 shows the oil connection sizes and locations for Model CB Boilers firing
No. 2 oil.
Figures Figure A2-5 through Figure A2-8 show typical oil systems and layouts.
Figure A2-8 show the detail of an oil transfer tank (day tank) typically utilized to provide a
storage reservoir between the oil system supply pump and the boiler oil pump.
Table A2-19. Minimum Required Gas Pressure Table A2-20. Maximum Gas Consumption (CFH)
Altitude Conversion for Natural Gas and Propane Vapor
ALTITUDE CORRECTION ALTITUDE CORRECTION BOILER TYPE OF GAS AND HEAT CONTENT
(FT) FACTOR (FT) FACTOR HP NATURAL GAS PROPANE GAS
1000 1.04 6000 1.25 1000 (Btu/cu-ft) 2550 (Btu/cu-ft)
2000 1.07 7000 1.30 125 5103 2000
3000 1.11 8000 1.35 150 6124 2402
4000 1.16 9000 1.40 200 8165 3202
5000 1.21 - - 250 10206 4002
To obtain minimum required gas pressure at altitudes above 700 300 12247 4802
feet, multiply the pressure by the listed factors: 350 14280 5600
Inches WC x 0.577 = oz/sq-in.
Oz/sq-in x 1.732 = Inches WC
400 16329 6404
Inches WC x 0.0361= psig. 500 20415 8006
Oz/sq-in x 0.0625 = psig. 600 24494 9605
Psig x 27.71 = Inches WC
Psig x 16.0 = Oz/sq-in. 700 28576 11206
750 30618 12007
800 32659 12807
A
MODEL 4WI
BOILER CONNECTION LOCATION
HP SIZE DIMENSION A
(IN.) (NPT) (IN.)
100-125 1-1/2 52 BOILER
FRONT
150-200 1-1/2 47-1/2
250-400 2 50
500 2-1/2 60
600 2-1/2 - 3 71 PLAIN VIEW
700-800 3 65
This figure illustrates the basic gas valve arrangement on Cleaver-Brooks Model 4WI
boiler and shows the contractors connection point. The valves and controls between the
contractor connection point and the gas main in the street are representative of a typical
installation. Actual requirements may vary depending on local codes or local gas
company requirements which should be investigated prior to preparation of specifications
and prior to construction.
UL FM CSD-1 NFPA-85
ITEM DESCRIPTION 125 hp - 350 hp - 125 hp - 350 hp - 125 hp - 350 hp -
300 hp 800 hp 300 hp 800 hp 300 hp 800 hp
1 Pilot Shut Off Cock X X X X X X
2 Pilot Pressure Regulator X X X X X X
3 Pilot Pressure Gauge X X X X X X
4 Gas Pilot Valve X X X X X X
5 Pilot Vent Valve X
6 Gas Pilot Valve X
7 Manual Shut Off Valve X X X X X X
8 Low Gas Pressure Switch X X X X X X
9 Main Gas Valve w/o POC X X X X
10 Main Gas Valve w/ POC X X
11 Vent Valve or Valve Proving Switch X X X
12 Regulating Gas Valve w/ POC X X X X X X
13 High Gas Pressure Switch X X X X X X
14 Manual Shut Off Valve X X X X X X
15 Butterfly Valve X X X X X X
MODEL 4WI
RECOMMENDED OIL LINEA
SUPPLY
SIZES
AND
BOILER RETURN (STANDARD PIPE) (IN. - IPS)
HP CONN A (IN.) STORAGE
SIZES TANK TO PUMP RETURN
(IN.) BOILER TO LINE TO
(NPT) OR PUMP BOILER TANK
CONNECT
100
150 3/4 12-1/2 1 1 1
200
250
300 3/4 34 1 1 1
350
400
500 3/4 11-3/4 1 1 1
600
700
750 1 11-3/4 1 1 1
800
NOTE: See No. 2 Oil Line Sizing Instruction for systems with
other conditions.
A. For suction line condition with a maximum of 10 Feet of lift
and a total of 100 feet of suction line.
Table A2-23. No. 2 Oil Connection Size, Location and Recommended Line Sizes
Figure A2-5. No. 2 Oil Piping, Single Boiler Installation, Remote Oil Pump
Figure A2-6. No. 2 Oil Piping, Multiple Boiler Installation, Remote Oil Pumps