Model CB 15-100 HP Boilers: Table A6-22. Maximum Gas Consumption (CFH) For Natural Gas and Propane Vapor
Model CB 15-100 HP Boilers: Table A6-22. Maximum Gas Consumption (CFH) For Natural Gas and Propane Vapor
Model CB 15-100 HP Boilers: Table A6-22. Maximum Gas Consumption (CFH) For Natural Gas and Propane Vapor
Table A6-22. Maximum Gas Consumption (CFH) for Natural Gas and Propane Vapor
TYPE OF GAS AND HEAT CONTENT
BOILER
HP NATURAL GAS PROPANE GAS
1000 (Btu/cu-ft) 2550 (Btu/cu-ft)
15 625 245
20 835 330
25 1045 410
30 1255 490
40 1675 655
50 2095 820
60 2510 985
70 2930 1150
80 3350 1315
100 4185 1640
NOTES:
BHP followed by “A” designates hot water boilers
furnished in a smaller vessel size with additional tubes in
upper portion of vessel.
30 1-1/2 68
40, 50A 1-1/2 68
50 2 74
PLAN VIEW
60, 70, 80 2 74
100A, 100 2 74
NOTE: BHP followed by “A” designates hot water
boiler furnished in a smaller vessel size with
additional tubes in upper portion of vessel.
This figure illustrates the basic gas valve arrangement on Cleaver-Brooks Model CB
Boiler and shows the contractor’s connection point. The valves and controls between the
contractor connection point and the gas main in the street are representative of a typical
installation. Actual requirements may vary depending on local codes or local gas
company requirements which should be investigated prior to preparation of specifications
and prior to construction.
4 5 6
1
FLOW
8 9
10
2 7
3 11
Gas To
Supply Burner
MAIN GAS LINE
INS UL FM CSD-1
ITEM DESCRIPTION
BOILER HP 15-20 30-50 60-100 15-20 30-100 15-20 30-50 60-100
1 Pilot Shut Off Cock x x x x x x x x
2 Manual Shut Off Valve x x x x x x x x
3 Manual Shut Off Valve x x x x x x x x
4 Pilot Pressure Regulator x x x x x x x x
5 Pilot Pressure Gauge x x x x x x x x
6 Gas Pilot Valve x x x x x x x x
7 High Gas Pressure Switch x x x x
8 Low Gas Pressure Switch x x x x
9 Main Gas Valve with POC x x x x x x x x
10 Main Gas Regulator x x x x x x x x
11 Butterfly Valve x x x x x
CONTRACTOR
BOILER CONNECTIONS
FRONT
BOILER BASE FRAME
MODEL CB
RECOMMENDED OIL LINEA SIZES
SUPPLY AND (STANDARD PIPE)
BOILER HP RETURN CONN DIM. A (IN.)
SIZES (IN.) (IN.)
(NPT) STORAGE TANK TO BOILER PUMP TO RETURN LINE
OR PUMP CONNECT BOILER TO TANK
15, 20 3/4 8-1/4 3/4 NONE 3/4
30, 40 3/4 8-1/4 3/4 NONE 3/4
50, 60 3/4 11-1/2 3/4 1 3/4
70, 80 3/4 11-1/2 3/4 1 3/4
100 3/4 11-1/2 1 1 1
NOTE: See No. 2 Oil Line Sizing Instruction for systems with other conditions.
A. For suction line condition with a maximum of 10 Feet of lift and a total of 100 equivalent feet of suction line.
B. This table is based on a single boiler installation.
Figure A6-10. No. 2 Oil Connection Size, Location and Recommended Line Sizes
BOILER
FRONT
B
PLAN VIEW
A
Figure A6-11. No. 6 Oil Connection Size, Location and Recommended Line Sizes, Model CB Boiler
Figure A6-12. No. 2 Oil Piping, Single Boiler Installation, Remote Oil Pump
Figure A6-13. No. 2 Oil Piping, Multiple Boiler Installation, Remote Oil Pumps