Multicont Manual
Multicont Manual
Multicont Manual
1. version
HiTECH/NIVELCO
301 Oxford Valley Road, Bldg 505, Yardley, PA 19067-7111
Tel: (215) 321-6012 Fax: (215) 321-6067
Technical Support: 888.NIVELCO (888) 648-3526)
e-mail: info@hitechtech.com www.hitechtech.com
1
2
TABLE OF CONTENT
1. Application ....................................................................................4 6. Errors, Error messages, Error codes......................................... 49
2. Technical data .............................................................................4 7. Protection of settings by hardware ............................................ 51
3. Order code....................................................................................6 8. Fuse replacement...................................................................... 52
3.1. Dimensions...................................................................................7
3.2. Safety regulation of Ex approved units.........................................8
4. Electric connection. ...............................................................9
4.1. Arrangement of the cable terminals .............................................9 Appendix
4.2. Wiring of the transmitters............................................................10
4.2.1. Wiring of the 2-wire transmitters.................................................10 1. The ID identification codes of the manufacturer........................ 53
4.2.2. Wiring 4-wire transmitters ............................11 2. The menu of theMultiCONT PRW-100...................................... 54
4.2.3. Wiring of combined system ........................................................12 3. Programming the relays ............................................................ 55
5. Programming of MultiCONT .......................................................13 4. Programming the current generators......................................... 56
5.1. Steps of programming ................................................................14 5. Measurment mode..................................................................... 57
5.1.1. Stepping between menu tables and scrolling menupoints .........15
5.1.2. Activation of devices, relays and current generators .................16
5.1.3. Assignment of (relays and current ) output ................................17
5.1.4. Editing parameter values............................................................18
5.1.5. Editing staves .............................................................................19
5.2. Putting into operation of network with MultiCONT......................20
5.2.1. Preparing transmitters ................................................................20
5.2.2. Wiring..........................................................................................21
5.2.3. Setting up of MultiCONT.............................................................21
5.3. Main menu..................................................................................27
5.4. MultiCONT configuration ............................................................28
5.5. Programming devices.................................................................35
5.6. Remote programming.................................................................36
5.6.1. Editing the linearisation table......................................................38
5.7. Relay configuration.....................................................................39
5.8. Current generator configuration .................................................45
5.9. Switching on ...............................................................................46
5.10. Measurement mode....................................................................48
3
users1
1. APPLICATION
MultiCONT P-100 series is first of all a controller and display capable to provide powering for 2-wire transmitters and accomplish complex control tasks. Further
it is a MASTER for all NIVELCO made smart transmitters as well as a universal interface between field devices with HART and other components of the
process control system such as PC, PLC, displays and different actuators. MultiCONT P-100 units support communication with a maximum of 15 ordinary or 2
Ex certified HART-capable NIVELCO made 2- or 4-wire transmitters. Should a system contain more transmitters than one MultiCONT can handle further
MultiCONT units can be organized in row by RS485. Remote programming of the transmitters and downloading of the measured data is a routine for the
MultiCONT. Measured values and new values calculated from the measured ones can control different outputs such as 4 20 mA, relays and digital output.
Large DOT matrix LCD panel facilitate a wide variety of display functions including tank content visualization. The output facilities of the basic unit can be
extended with external (relay and/or current generator) modules.
Explosion proof certified versions of the MultiCONT should be accommodated in non-hazardous area.
2. TECHNICAL DATA
TYPE P
- 1
-
Installation Wall mounting
PRC, PRD, PRW -20 C +50 C
Ambient temperature
PRH -30 C +50 C
Transmitter power supply 30 V DC 60 mA, for Ex version 22 mA
Display 120 x 32 Dot-matrix/ 128 x 64
Max. 2 x 4 20 mA, galvanically isolated
Analogue
max load 500 ohm, over-voltage protection (isolation voltage 1000 V)
Output
4
users1
TYPE P
- 1
-
Powering, relays, analogue 4 20 mA 0.5 2.5 mm2 core cross section
RS 485 interface Shielded, twisted cable pair, cross section: 0.5 2.5 mm2
Cables
Below 1500 m Shielded, twisted cable pair, min. cross section 0,5mm
HART cabling Over 1500 m Two shielded, twisted cable, min. cross section 0,8mm
Resistance max. 75 ohm, capacitance max. 225 nF
Number of transmitters to be powered 15 ordinary or maximum 4 Ex transmitters
Power supply / 85 255 V AC 50 60 Hz / 12 VA / 255 Veff
consumption / 10,5 28 V AC 50 60 Hz / 12 VA / 28 Veff
maximum voltage 10,5 40 V DC / 11 W / 40 V DC
Housing material Polycarbonate (PC)
Ingress protection IP65
Ex marking II (1) G [EEx] ia IIB
Uomax = 30 V Imax = 140 mA Pmax= 1 W
Intrinsical safety data
Lmax = 30 mH Cmax = 300 nF
Electric protection Class I/III
Mass 0.9 kg
5
users1
3. ORDER CODE
MultiCONT P 1
EXTENSION CODE ENCLOSURE CODE INPUT CODE OUTPUT CODE POWER SUPPLY CODE
Standard * R IP 65 W 1 tx with HART 1 Display only 0 85 255 V AC 1
Not possible E IP 65 with transparent cover C 4 tx with HART 4 1 relay 1 24 V AC / DC 2
IP 65 with lockable transparent 8 tx with HART 8 2 relays 2 85 255 V AC Ex 5
D
cover 15 tx with HART M 3 relays 3 24 V AC / DC Ex 6
IP 65 with transparent cover and 4 relays 4
H
heating 1 relay + 1x420 mA
5
Analogue output
2 relays + 1x420 mA
6
Analogue output
3 relays+ 1x420 mA
7
Analogue output
4 relays + 1x420 mA
8
Analogue output
4 relays + 2x420 mA
9
Analogue output
RS 485 interface A
Internet communication B
GSM communication C
Order codes of the certified units are followed by Ex tag.
* Standard units can be extended with relay-, current generator- and combined modules.
6
users1
3.1. DIMENSIONS
75.5 75.5
89.5
107
A Pg9 or M16
B Pg11 or M20 A Pg9 or M16 R 2.5
C Pg11, Pg13.5 or M20 B Pg11 or M20
A B B C
166 C Pg11, Pg13.5 or M20
A B B C 10
193
112
160
160
.7
10
R2
P
W P
C, P
D, P
H MOUNTING
ESC OK ESC OK
W
P C, P
P D, P
H
7
users1
8
users1
4. ELECTRIC CONNECTION
Shielding of the interconnecting cable between the transmitter and the controller should be grounded at one end preferably at the MultiCONT.
Intrinsically safe (Ex) transmitters should be connected through the terminals L+, L- to the controller. These points are galvanically isolated from the other parts
of the electronics and the power supply for the Ex transmitter is current, voltage and power limited.
9
users1
4.2. WIRING
Before wiring the units are suggested to be checked for type (all Tx with HART), value of loop current and polling address (transmitters should have
different addresses). See 5.2. Steps of set up
Tx 1
Tx 2
MultiCONT
Tx 3
+Us
I+ L+
255
Tx N I L
SH
HART interface
Shielding grounded
at the MultiCONT
10
users1
Tx 1
Tx 2
MultiCONT
Tx 3
255
I+ L
I SH
HART interface
Tx 15
85...255 VAC
10,5...28 VAC Shielding grounded
10,5...40 VDC at the MultiCONT
11
users1
Tx 1
Shielding grounded
at the MultiCONT
Tx 2
Tx 3 MultiCONT
+Us
I+ L+
255
Tx N I L
I+ SH
I
HART interface
85...255 VAC
10,5...28 VAC
10,5...40 VDC
Tx 1
Tx M
12
users1
5. PROGRAMMING OF MULTICONT
During programming the following can be performed:
Automatic detection of devices (transmitters)
connected to the MultiCONT, their taking up in the list of devices. Devices not being on the list are part of the system but unable to
communicate with the MultiCONT (see 5.2.3 Main menu/MultiCONT config/ DEV detect).
Activation, inactivation of devices (transmitters)
Theoretically all devices in the system should be working. For this, however devices should be activated, since MultiCONT will query the
activated transmitters only and those, which are inactive not. Devices wishing to be temporarily out of use for any reason can be cut out by
inactivation. (See 5.2.3 Main menu/ Devices)
Activation, inactivation of relays and current generators
Relays and current generators of the MultiCONT should also be activated (see Attachment 3 and 4)
Assignment of the MultiCONT outputs (relays, current generators) to devices (transmitters)
or to functional values composed from the measured values
Setting composition of functional values
Functional values can be composed from measured values such as difference (of e.g. two levels), sum of two measurement values,
average of measurements.
Remote programming of devices
however programming of devices is supposed to perform in the workshop before their installing and wiring.
(P01, P02, etc. parameters of the transmitters will be used in this Manual the same way as described in their Installation and Users Manual)
Programming of MultiCONT
Relay parameters and current generator parameters of the MultiCONT will be identified as RP1, RP2, RP3 and CR1, CR2, CR3 respectively.
For planning, erection and putting into operation of systems involving MultiCONT sound knowledge of the HART standard and devices
applied is required.
During programming full scale of operation such as polling of devices, function of relays and current generators will be maintained. Modifications will
only be effective after clicking OK in Main menu /Save and returning back to measurement. If the MultiCONT is left in Programming Mode by mistake, it
will automatically return to measurement after 5 minutes following the last clicking on any key (modifications will be lost!).
13
users1
Press for entering Programming mode and Menu points and for quitting
Keys are used for editing parameters with numbers or text, choosing local value or position of character to edit and in some menu tables
Keys are used for scrolling numbers and characters when editing parameters with numbers or text.
14
users1
Measurement result
15
users1
Devices on the list may be active ( ) or inactive( ). Only active devices will be queried. Active relays and current generators operate
according to their setting, inactive relays are de-energized output of inactive current generator is 0 mA.
or
Relays 6 18 Relays 6 18
01: R_IN_1 01: R_IN_1
02: R_IN_2 or 02: R_IN_2
03: R_IN_3 03: R_IN_3
Marking/activating of other functions or features (activation of current generator, language, strategy, etc.) will be performed the same way.
16
users1
During configuring relays and current generators should be assigned to field devices
Relays 6 18 Relays 6 18
01: R_IN_1 01: R_IN_1
02: R_IN_2 02: R_IN_2
03: R_IN_3 03: R_IN_3
Relays 6 18 Relays 6 18
01: R_IN_1 01: R_IN_1
02: R_IN_2 02: R_IN_2
03: R_IN_3 03: R_IN_3
17
users1
MultiCONT parameters have mathematics signs and local values. Signs and value can be modified with keys .
The keys and are for reversing the sign or changing a character.
Changing sign
Parameter 23 Parameter 23
RP1 = + 0000.00 RP1 = 0000.00
RP2 = 0.00 RP2 = 0.00
RP3 = 0 RP3 = 0
Parameter 23 Parameter 23
RP1 = + 0000.00 RP1 = + 0000.00
RP2 = 0.00 RP2 = 0.00
RP3 = 0 RP3 = 0
Parameter 23 Parameter 23
RP1 = + 0000.00 RP1 = + 0010.00
RP2 = 0.00 RP2 = 0.00
RP3 = 0 RP3 = 0
18
users1
ST300-12 ST301-12
19
users1
It is suggested to check preferably in the workshop the Polling address (in P19 or P13) and current output of the transmitters. The loop current of
the ordinary MultiCONT is max. 60mA, and max. 22mA with the Ex certified version. If the loop current exceeds this value the voltage will be too low for
the transmitters to start to work. In networks with more than one field device the units should be addressed with numbers 1 15 and the current of the
transmitters will be limited to 4mA. This constraint may be subject to overwriting with programming in some devices (se table below). It is important that
the loop power should not exceed the above limit.
Further precondition of proper operation is the different polling addresses for different devices.
Parameters of the Polling address and constant current of NIVELCO made devices
Device series Polling address parameter Constant current parameter
ST300 P19 P08
SC300 P19 P08
SE300 P19 P08
SG300 P19 P08
CT300 P19 P08
MT300 P19 P08
TB P13 N/A
NB P13 N/A
PDT ( 2 ) P13 N/A
PDT ( 4 ) P13 N/A
20
users1
5.2.2. Wiring
Switching on initiates a test process, during which MultiCONT is checking the memory, which is storing settings of the unit. (See 5.9 Switching on)
This process lasting about 50 sec can be accelerated (time period. 25 sec) by pressing key ESC
In case of positive result the process will continue with polling and finally
To change Language take the route Main menu/MultiCONT config/Language go to and mark the Language required with pressing keys and as
well as . To keep this language setting should be saved in Main menu/Save config menu point otherwise with re-powering of the unit default English
will return.
21
users1
M
No HART device
"OK"
Main menu 6 05
Devices
Relays
Current generators
"OK"
22
Message appears
Scanning HART line
N=0...15 "OK"
Device: N
Same address
M
No HART device
1. In this case one of the transmitters is not HART-capable. Confer name plates and 3.1 Order Code
2. There are more devices in the system than the actual MultiCONT can handle (Confer nameplate and 3.1 Order Code). Information is provided
on the route and in menu point Main menu/Local config/Report/Devices (See 5.3.) with numbers 0nn/0mm. Number of devices listed is
represented by nn and numbers of devices that can be handled is represented by mm.
3. Device is out of order. Dismount the unit and check it in the workshop.
Next steps are adding devices to the list, setting devices and activating devices
23
users1
Detected DEV 37 "?" is to signify that the unit has answered to the
? 1: ST300 query but it is non on the list yet.
? 2: SE300 Goto to the unit to be added by
pressing keys and click
? 3: XXXX
"OK"
1: ST300 38
Add
Remove
Set Up
"OK"
"OK"
24
Detected DEV 37
+ 1: ST300 Device No 1 has added to the list
Selecting Remove "+" will be changed to "?" and
? 2: SE300 device removed from the list.
? 3: XXXX
"OK"
1: ST300 38
Add Setting and viewing of features of devices
can only be performed in Set up if they are
Remove on the list (with "+" marking).
Set up
"OK"
Device: ST300 6 07
Remote Short TAG being the order code (e.g ST300)
Short TAG can be changed here.
Polling address
"OK"
Main menu 6 05
Devices
Relays
Current generator
"OK"
Devices 6 06
01: ST300 None of the unit is active.
Goto the unit to activate it with
02: SE300 or and activate it with key
03: STHCL
25
Devices 6 06
01: ST300 Inactive device
02: SE300 Active device
03: STHCL
"ESC"
Main menu 6 05
Devices
Relays
Current generator
"ESC"
1: ST300 LEV M
Returning to the Measurement Mode
2.452 m the result of the measurement
should appear on the screen.
1
users1
It is essential not to mix up Polling address and list-tag of the units. Polling addresses 1 . 15 given to devices during their programming mainly in the
workshop is for the HART detection and query. MultiCONT is identifying devices on the basis of the multi-decimal list-tags 1, 8, 9, A, B, F
assigned to the unit on its detection.
Note:
If the list of DEVices was not empty at the starting of the search than the following can appear on the screen
Detected DEV 37
! 1: SE380-11 "!" included in the list, but failed to answer
"+" included in the list and answered
+ 2 : ST360-1 "?" not included in the list, but answered
? 3 : SC380
The list can be modified on Menu table 38 in menu point Add and Remove or the whole list can be erased in Main menu/Default
26
users1
Main menu 6 05
Devices Setting features of devices (transmitters) (See 5.6.)
Relays Programming relay working mode and parameters (See 5.7.)
Current generator Programming current generator working mode and parameters (See 5.8.)
MultiCONT config Programming features of MultiCONT (See 5.4.)
27
users1
Main menu 05
Relays
Current generator
MultiCONT config MultiCONT bell. 6 35
DEV keres
EXT keres
Strategy
User display
Display mode
Secret code
Language
Address
Backlight
HART test
Report
Fresh FLASH
28
users1
Detect DEV: MultiCONT will detect transmitters (max 15) in the HART network and compile a list with
Multi decimal marking 1, ,8,9,A,B,,F (See also 5.2.3 Setting up MultiCONT)
Detect EXT: Detection of extension modules such as Relay-, Current Generator- or Combined Modules
Strategy 42
P by P One after the order
Manual Query selected device only
29
users1
Users image: Beyond the Measurement image M (as shown at the end of section 5.2.3) the following Users images U can be compiled in the Users
Image below (table 51) and displayed in the measurement mode for better information.
Difference U
+ ShortTAG1 ShortTag2
1 2 3 4 5 6 U
100% 1.054 m
0%
Average LEV U
124
List number of devices involved.
Blinking list number represents failure of the unit.
12.24 m
30
users1
Display mode 6 48
Being back in Measurement mode
Manual Device can be selected with
Automatic steps of 5s
Automatic stepping with 2 different space
Automatic steps 10s
Asked Result of the queried transmitter will be displayed.
Secret code: Reading or modification of the configuration of the MultiCONT can be protected with eight-digit secret code other than zero. Key next to the
menu table number represents presence of secret code. If the key is blinking access is enabled.
Secret code 44
Unlock
Change
Avert
"OK"
Avert 46
All Avert all
Modification Modification will be averted (parameters can be viewed)
31
users1
Language 6 43
English Selection with
German pressing key
French
Hungarian
MultiCONT address: Address (1254) for systems with several MultiCONT units connected together over RS485 interface
MultiCONT address 54
nnn
32
users1
HART test 45
Drive
Watch
Drive 49
No signal Continuous HART signal can be given to the system
1200 Hz (1) Selection with keys
2200 Hz (0)
Watch 50
RxD = 2200 Hz (0) Watching the line continuously result detection
CD = No (0) of trouble will be indicated
RxD= pickup
Watch 50
CD = Carrier detect, if the line is noisy 1 will prevail
RxD = 2200 Hz (0)
or waggling device may not answer.
CD = Present (1)
(See: HART test function of the transmitters)
33
users1
Report: Report provides information on the network such as number of devices (transmitters), relays, current outputs, extension modules
involved and capable to handle. Assignment of a relay or current generator to a device will be called route.
Report 6 53
Devices: 002/015 2 devices in the network out of the possible 15
Extension: 000/032 Number of extension modules (presently 0)
Relays: 004/064 4 relays from the possible 64 (external+internal=64)
Current gen.: 002/016 2 current generators (external+internal=14)
Routes: 008/100 8 routes from the possible 100
Type: PRW115 MultiCONT type (e.g. PRW115)
SW type: 01 MultiCONT software type
SW version: 00.01 MultiCONT software version
Serie: 123456 Serial number of the Main PCB
Date: 2004/01/23 Date and
Time: 0/1/50 time of loading MultiCONT software
Fresh FLASH: For trouble-free operation of the program-memory this program should be run once a year
34
users1
5.5. PROGRAMMING DEVICES (TRANSMITTERS)
Main menu 6 05
Devices
Relays
Current generator
"OK"
Devices 6 06
Go to the required devices with keys and and click
01: ST300
to enter its file in order to view and/or change parameters
02: SE300
Table of the inactive device will not appear!!
03: SG300
"OK"
35
thus it is not recommended!
Message 32 character field offered to the user to edit
any message relating to the technology or operation
Descriptor 16 character field offered to the user to
identify the process medium
Date Date to be assigned to the unit
Final ass. number n.a.
Factory ID Assigned to NIVELCO by HART Communication Foundation (fixed 151)
Device type ID NIVELCO code
1=ST300 EchoTREK (4 wire) 6=MT300 NIVOTRACK
2=SC300 EasyTREK 20=TB THERMOCONT
3=SE300 EchoTREK (2 wire) 21=NB NIVOPRESS
4=SG300 22=PDT (2) univ. controller
5=CT300 THERMOCONT 23=PDT (4) univ. controller
SW version Software version of the unit (transmitter) (See relevant Manual)
HW version Hardware version of the unit (transmitter) (See relevant Manual)
Device ID Electronic serial number of device assigned by the factory.
Major version n.a.
Device version n.a.
"OK"
"OK"
36
by 4 digit secret code
(See Installation and Programming Manual of the relevant device)
Unlock Making access lock inactive. After unlocking key will be blinking.
Change code To delete or change secret code
as part of the programming can only be performed
after unlocking (entering old code)*
Parameters To view and modify** parameter values.
If the access code is active
only viewing is possible*.
Save in P+C TMP Complete set of parameters will be downloaded
from the unit and saved in a temporary table (TMP)
Send TMP to DEV Complete set of parameters saved in the temporary table (TMP)
will be uploaded to the unit (to ease programming of
silos with the same shape and task).
Linear. table Editing the linearisation table (see 5.6.1.)
Echo map Displays Echo Map of ultrasound transmitters (ST300,
SE300, SG300) ***. With other devices where this feature
is not applicable Unknown DEV/comm error will be indicated
Delete TOT1 Deleting of TOT1 in devices with flow measurement
Delete TOT2 Deleting of TOT2 in devices with flow measurement
(Access with the Factory code only!)
users1
Unlock lease
Click OK-t After entering secret code and clicking OK access is free for programming.
** Parameters entered during remote programming via MultiCONT will be sent immediately to and checked in the field device only. If the
parameter value is incorrect or not applicable the following message appears:
37
Warning!
5.6.1.
users1
Editing the linearisation table
Remote program 08
Save in P+C to TMP
"OK"
"OK"
Lin. 01
01.00 m
0.00 m3/s
38
"OK"
Lin. 01
01.00 m
000000.00 m3/s
"OK"
Linear. table 6 12
Lin. 01 Disappearing of the brackets
(Lin. 02) shows that a line of the table is deleted.
(Lin. 03)
users1
ALARM low
RP1
Default: Inversion=OFF
Below RP1 relay will be de- energized
t RP1
Inversion of the operation (below RP1 relay will be energized
with selection of Inversion=ON Energised
Switching difference = 2.5% of RP1 Relay
De-energised
39
users1
ALARM high
RP1
Default: Inversion=OFF
over RP1 relay will be de- energized
Inversion of the operation (over RP1 relay will be energized t RP1
with selection of Inversion=ON
Switching difference = 2.5% of RP1 Energised
Relay
De-energised
Energised
Relay K K K Delay
De-energised
Window comparator
RP1
Default: Inversion=OFF
Within the range of RP1..RP2 relay will be energised RP2 RP1, RP2
Inversion of the operation (within the range of RP1..RP2 relay t
will be de-energised) with selection of Inversion=ON
Energised
Relay
De-energised
40
users1
Error
Default: Inversion=OFF RP3
In case of error relay will be de-energised. RP3=0 with any error RP3=n with error of n code
Inversion of the operation (in case of error relay will be energised ) with selection of Inversion=ON
Temperature Temp
RP1
Default: Inversion=OFF
RP1 over temperature of relay will be de-energised
Inversion of the operation (over temperature of RP1relay will be t RP1
energised ) with selection of Inversion=ON
Switching difference = 2.5% of RP1 Energised
Relay
De-energised
41
users1
Impulse C Energised
Default: Inversion=OFF Relay 200 ms
relay will be energised for appr. 200ms in 0 intervals De-energised RP3
Inversion of the operation with selection of Inversion=ON RP3 [sec]
Interval can be set under RP3 in sec
TOT1 RP3=10
Impulse F
Default: Inversion=OFF 20
relay will be energised for appr. 200ms with each amount of flow 10 RP3
set under RP3 (default=0) t
Inversion of the operation with selection of Inversion=ON
Energised
Relay
De-energised
TOT1 RP1=20
TOT1
Default: Inversion=OFF 20
relay will be de-energised when TOT1 reaches value of RP1 RP1
Inversion of the operation (relay will be energised) with selection of t
Inversion=ON
Energised
Relay
De-energised
42
users1
43
users1
Notes:
1. Parameter are to program in the Main menu/Relays/Relay/Program/Parameter menu table by going to the relevant
Parameter 23 parameter with entering value in between pointers and clicking OK. Programming parameters can only be completed
RP1 = 0001.25 with clicking OK after setting RP3 (even if it is zero or not applicable in the given function!)
RP2 = 12.45
RP3 = 0
44
users1
Menue:
Program :
1. Programming error will be indicated if in analogue output operation mode CP1=CP2 and output current will not change
2. Value of the output current will not change if the unit assigned does not answer!
3. If the current output is not activated the output will be 0 mA.
4. If Error function selected no (source) assignment is required since errors of all devices will be monitored
5. The programmed parameters can only be saved at C3 by pressing OK.
45
users1
5.9. SWITCHING ON
MultiCONT
displayed. The procedure takes about 50s and it can be accelerated by click on ESC (time approximately 25 s).
On powering a test program checking the hardware of MultiCONT will be run that can be followed on the screen by the (English) messages
System check In case of error CODE ERROR
message provided
Testing CODE and restart
RESTARTING
System check
CODE OK
In case of no FLASH
System check NONE FLASH
message provided
Testing FLASH and restart RESTARTING
46
In case of corrigible FLASH ERROR
FLASH error, repair PAGE: nnnn
System check
FLASH OK
Since parameters necessary for the trouble free operation are stored in the FLASH in case of FLASH error the unit
should be sent to the service.
After the successfully completed test polling and query will be performed on the basis of the previous configuration
and the MultiCONT will enter Measurement Mode and it will work in accordance with setting of 5.4 Main
menu/MultiCONT config (See 5.10 Measurement Mode)
1: - - - - - - - - DIST M
There is no response from device no. 1. (there is no result to display)
Error Response can be red in the error list.
2 Errors: 1
2: SE300-11 DIST M
The result of the device no. 2. is on the display.
3.125 m Device no. 1. Is under asking.
1
47
users1
Beyond the Measurement Image, User Images, relaydevice, current generator-device m Errors: 2 CLOSED
assignment and error list can be viewed in this operation mode (See Attachment 5). List tag of Protection switch
Beyond the Measurement Image, User Images (Range, Dual, Difference and queried device of settings closed
Average) can also be selected here. (See 5.4 Main menu/MultiCONT config/Users
image.) During programming full scale of operation such as polling of devices, function Error messages can be erased with key
of relays and current generators will be maintained. If the MultiCONT is left in
Programming Mode by mistake, it will automatically return to measurement after 5
minutes following the last clicking on any key.
The relay-device and current generator devise coupling can be seen in this measurement mode.
See Appendix 5.
Even if a possible error does not exists any more, it will be displayed at the given instrument until it is confirmed (ESC). Beside the standard display mode, other
ones can also chosen (Bargraph, Double, Difference, Average) s. 5.4. Main Menu/MultiCONT config/User display.
Measuring, asking the devices and controlling the relays and the current generators are carried on also during programming . If the instrument remains
accidentally in programming mode, it returns automatically after 5 sec to measurement mode. The MultiCONT saves the number of switches and the working
hours.
48
users1
* Device, being on the list and activated does not reply after switching-on. Possible reasons:
- network has been modified before re-powering (device was disconnected, wiring changed, etc.)
- device failed to reach operation conditions (not able to provide measurement results) e.g. STD-300 can not measure until amplification reaches
operation conditions..
49
users1
*** Special indication belongs to the failure of the sensors. This information appears on breaking down of the transducer in the ultrasound transmitter
or cracking of the magnet disc, break of the magnetostrictive wire in the magnetostrictive transmitter. On the other hand this is the message
displayed when echo loss condition occurs with the ultrasonic measurement.
1: SE300-12 DIST M
SENSERR The device answers but there is no valid result because of sensor error.
2 Errors: 1
50
users1
51
users1
8. REPLACING FUSE
Loosen four nuts, which are fastening the front panel. Tilt forward the
PRW10A02-A
+
front panel carefully, in order not to span cable band and replace the
fuse.
CURRENTG1
power supply
CURRENTG2
PRWTAP
RS485
POWER SUPPLY FUSE
Fuse B1 85255 V AC 5060Hz T400mA
10,528 V AC 5060Hz
10,540 V DC T1A
Warning!
Only fuses as per the table above can be used
for replacement.
52
users1
53
users1
APPENDIX 2.
Measurement value User display Relay coupling 4-20 mA coupling Error report
1: ST300 LEV M 123456789ABDC DEF R 123456789A BDCDE F C Error report 6E Device: SE300 607 Remote program 6 08 Parameters 6 11
Switching ON
R1 C1 01: SE300-11: Vlasz Remote program Secret unlock
Test (can be accelerated
with "ESC")
1.23 m See 5.5 section
R2 C2 02: ST300 : Program Short TAG Secret mod. Device programming
R3 Polling address Parameters
HW revision
Device ID Program 20 Source 21
Major revision Source 1: SE300
Devices 06
Device revision Mode 2: SC380
or if no key is pressed within 5 min. 01: SE300
Parameter :
the instrument returns automatically 02: ST300
Invert n: ST300-1
to measurement mode. :
Test
15: SC300
n: ST300 LEV M
Cycle 25 Mode 22
12.45 ft Hyst
002568 Alarm low
Relay 19 Alarm low, K
Program Alarm high
Cycle count Alarm high, K
Relays 18 Working
: hour Working hour 25
Window
01: R1 Short TAG Window, D
02: R12 ID 001856
Error
54
:
Temp
12: R12n
Password 200 Entering the service menu: Temp, W
Press the keys at the Main menu Short TAG 25 Pulse, C
05
0000000 same time by switching ON and Pulse, F
Devices
R132-HCL TOT1
enter the password. Relays
Current generator Alt..S
MultiCONT config
Service 6 201 Save config ID 25 Parameter 23
Default Load config RP1 = 0003.45
Default config Current generator 27
PSW CLR 402568 RP2 = 12.45
Reset 01: I1
Stime CLR RP3 = 0
02: I2
Power CLR
:
Device NUM
12: I2n Current gen.: I2 28 Program 29 Source 30
Relay NUM Keys:
Relay (I) NUM Program Source 1: SE300
Keys for changes menu: Short TAG Mode 2: SC380
Current NUM
Current (I) NUM Keys for menu navigation: ID Parameter
: :
U485 (I) NUM Activating: Test n: ST300-1
EXT num MultiCONT config 6 35
Current CAL DEV detect Strategy 42
Legend: P by P
Relay test EXT detect Short TAG 34 Mode 31
Not active Strategy Higher 1st
Current test Primary
Button test Active, relay is energised by assignment User display Fixed R132-HCL Error 3.6 mA
Display test Assignes with positive sign as source Display mode Error 22 mA
SW test Assignes with negative sign as source Password
N485 test Assignes to average calculation as source Language User display 51
U485 test MultiCONT addr. None
F232 test Back light Bargraph ID 34 Parameter 32
HART test HART debug Double CP1 = 0003.45
HOST mode Report Difference 402568 CP2 = 12.45
Save+Reset Flash fresh Average CP3:= 0
users1
APPENDIX 3.
Main menu 05 Relays 18 Relay 19 Programming 20 Source 21 Not assigned with sign
Devices 01: R1 Programming Source 1: SE300 Assigned with "+" sign
Relays 02: R12 Cycle Function 2: SC380 Assigned with "" sign
Current generator : Working
: hours Parameter
: : Assigned, averaged
Local config 12: R12n Short TAG Invert n: ST300-1 Modify with
Save config ID Test
Escape with
Alt..S
Validate with
ID 34 Test 33
Change with
402568 18.565 Changed immediatelly
Figyelem!
A bellts csak abba a memriba kerl be, amelyik a mkdst
befolysolhatja. Ennek tartalma kikapcsolskor elvsz.
Ments "Main menu" / "Ments" menpontban -val
users1
APPENDIX 5.
Switching ON
Test (can be accelerated
with "ESC")
MEASUREMENT MODE
Number
of the device
Measurement value User's image Relay assignment 4-20 mA assignment Error report