GENERAL Fans
Fan coil units are an integral part of an Quiet low line, centrifugal type, double
overall air conditioning system where width, statically and dynamically
the energy transfer medium (i.e. chilled balanced, multi-bladed impellers are
or hot water) is circulated by a central used. The position and shape of the
plant facility. fan blades and housing has been
developed after extensive testing to ACCESSORIES
temperzone offers an extensive achieve minimum noise levels while 1. Filter Box
range of ducted fan coil units. A maintaining a smooth pressure vs air integrated with return air spigot
variety of options and accessories are flow curve. filter is 13 mm thick, washable
available to meet most air conditioning and rated EU2.
requirements. Coils 2. Spring Mounting Kit.
Coils are manufactured in rifled copper
Low operating cost, energy efficient tubing. All coils are thoroughly tested to 3. Supply and return air plenums
fan motors are used in all units. Easy 2100 kPa. (IMD 95280).
installation and maintenance add to 4. Control switches (IMD 95280)
the cost effectiveness of temperzone Coil rows are staggered for maximum
heat exchange. Different coil on/off and 3 speed rotary
IMD Series fan coil units. switches mounted in a standard
configurations are available refer
All temperzone IMD fan coil units table below. or architrave type flush plate.
are right handed, i.e. when facing the The coil fins are manufactured as a
discharge side of the unit, the water WIRING
continuous plate, die formed from
and electrical connections are on the The electrical supply required
aluminium with a smooth corrugated
right hand side. (including voltage fluctuation limits) is:
surface, specially designed to
1 phase 200252 V a.c. 50 Hz with
overcome and prevent lint build up.
TYPICAL APPLICATIONS neutral and earth. Each IMD unit is
The coil fins are mechanically bonded
Office Buildings fully wired ready to accept the main
to the copper tubing which results
IMD units are ideally suited to office power supply.
in a rigid assembly and provides a
building applications where false permanent metallic contact between Note: When installed with electric heat
ceiling space is available and medium fins and tube for maximum heat the IMD 135550 units require a three
static pressure and ductwork is a transfer. phase power supply of 342436 V a.c.
consideration. 50 Hz.
Casing
Airport Terminal Buildings The casing is manufactured from high
temperzone fan coil units are gaining quality galvanised steel and internally ORDER DETAIL
worldwide popularity in airport insulated. Series
terminals. These complexes generally Size
consist of a number of areas with Insulation Coil Option
very diverse occupancy and capacity Closed cell foam insulation has been
requirements. used in the unit's cabinet to ensure
IMD -
no particles are introduced into the air
Hospitals stream. The insulation is foil faced and Coil Options:
The majority of hospital rooms must meets fire test standards 1 - One row coil for heating
have a separate and independent AS 1530.3 (1989) and BS 476 parts 6 4 - Four row coil for cooling
air conditioning system. This is to and 7. 4/1 - Four row cooling / one row heating
avoid bacterial cross contamination.
Mounting 4/E - Four row cooling + electric heat
temperzone fan coil units have
The IMD unit can be mounted rigid, E - Electric heat only
been used successfully in these
applications. or using the optional spring mounting Note: Please specify on your order the
brackets which minimise transfer of size and coil option using the above
STANDARD FEATURES vibration. codes.
Drain Tray
The drain tray on models IMD 95280 ELECTRICAL BOX Examples:
are made of plastic for complete Wiring from the motors terminate in a IMD 135-4/1
corrosion protection. IMD 420, 550 are terminal block in a sheetmetal enclosed IMD 210-4E
powder coated galvanised steel. electrical box within the unit.
SUMMARY OF CHOICES
Drain trays are removable for ease of
ELECTRIC HEAT Size : 95/135/170/210/280/420/550
cleaning and have a built-in slope to
ensure condensate water drains freely Electric Heat is available with some coil Coil : 1 row Heating
without ponding. configurations (refer table right). 4 rows Cooling
Elements are factory mounted within
the unit. A fan run-on timer (for heat 4 rows Cooling + 1 row Heating
Motors
Permanent split capacitor (PSC) ball dissipation) is included. These units are 4 rows Cooling + Electric Heat
bearing motors are fitted as standard supplied complete with safety cutouts No Coil - Electric Heat Only
on all units. These multi-speed motors required to meet
Filter Box: Yes / No
are resiliently mounted, self aligning AS/NZS 3350.2.40 1997.
and oiled for life. Spring Mounts: Yes / No
Plenums: Yes / No
Control Switch: Yes / No
NOTE: Specifications are subject to change without notice due to the manufacturers ongoing research and development programme.
temperzone limited 2006
SPECIFICATIONS
IMD Series
Model IMD 95 IMD 135 IMD 170 IMD 210 IMD 280 IMD 420 IMD 550
Nominal Air Flow l/s 450 600 750 900 1250 1800 2340
Fan Type forward curved centrifugal - double inlet double width
No. of scrolls 1 1 1 2 2 2 2
Fan Motor Type 4 speed 3 speed, direct drive, permanent split capacitor
Power Source * 1 phase 230 V a.c. 50 Hz
No. Motors 1 1 1 1 2 2 2
Motor Poles 4 4 4 4 4 4 4
Motor Rating W 316 373 550 550 550 746 746
Full Load Amps A 12.6
Heat Exchange Type aluminium corrugated plate fins to expanded rifled copper tube
Source chilled water or hot water
Coil Rows [1 row heat] or [4 rows cooling] or [4 rows cooling + 1 row heating] or [4 rows cooling + elec. heat] or [elec. heat only]
Finish zinc galvanised steel
Test Pressure 2100 kPa
Connection Sizes (mm): Cooling coil 25 BSPM (1") 25 BSPM (1") 25 BSPM (1") 25 BSPM (1") 32 BSPM (11/4") 32 BSPM (11/4") 32 BSPM (11/4")
Heating Coil 15 BSP male ( 1/2") 25 BSPM (1") 32 BSP male (11/4")
Optional Air Filter ** Type washable rated EU 2
No. 1 1 1 1 2 2 2
Thickness (mm) 13 13 13 13 13 13 13
Size (mm) 593 x 275 767 x 275 914 x 275 1064 x 275 593 x 345 685 x 415 712 x 542
Optional Electric Heating * kW 4 6 6 9 9 12 18
Weight (4/1 row unit, incl. water) kg 49 50 64 66 94 133 162
Net Weight (4/1 row unit, excl. water) kg 45 45 59 60 86 120 145
Shipping Weight (approx.) kg 48 48 62 63 96 145 175
Notes:
* Voltage fluctuation limits 200252 V. IMD 135550 electric heat models require a 3 phase power supply, 342436 V a.c 50 Hz.
** Supplied within optional filter box.
NOTE: Specifications are subject to change without notice due to the manufacturers ongoing research and development programme.