Model CBLE 125-800 HP Boilers: Table A1-14. Steam Boiler Safety Valve Openings
Model CBLE 125-800 HP Boilers: Table A1-14. Steam Boiler Safety Valve Openings
Model CBLE 125-800 HP Boilers: Table A1-14. Steam Boiler Safety Valve Openings
VALVE
15 PSIG STEAM 100 PSIG STEAM 125 PSIG STEAM 150 PSIG STEAM 200 PSIG STEAM 250 PSIG STEAM 300 PSIG STEAM
SETTING
NO. OF OUTLET NO. OF OUTLET NO. OF OUTLET NO. OF OUTLET NO. OF OUTLET NO. OF OUTLET NO. OF OUTLET
BOILER VALVES- SIZE VALVES- SIZE VALVES SIZE VALVES- SIZE VALVES- SIZE VALVES SIZE VALVES SIZE
HP REQ'D (IN.) REQ'D (IN.) REQ'D (IN.) REQ'D (IN.) REQ'D (IN.) REQ'D (IN.) REQ'D (IN.)
(1) 1-1/2 (1) 1-1/2 (1) 1-1/4
125 1 3 2 1-1/2 2 2 2 2 1 2 1
(1) 1-1/4 (1) 1-1/4 (1) 1
(1) 2 (1) 1-1/2 (1) 1
150 1 3 2 2 1-1/2 2 2 2 1 2 1
(1) 1-1/2 (1) 1-1/4 (1) 1-1/4
(1) 2 (1) 1-1/2 (1) 1
200 2 2-1/2 2 2 2 2 1-1/2 2 2 1-1/4 2
(1) 1-1/2 (1) 1-1/4 (1) 1-1/4
(1) 2-1/2 (1) 2-1/2 (1) 2 (1) 1-1/2
250 2 2 2 2 2 2 1-1/2 2 2 1-1/4
(1) 3 (1) 2 (1) 1-1/2 (1) 1-1/4
(1) 2-1/2 (1) 2-1/2 (1) 2 (1) 1-1/2
300 2 3 2 2 2 2 1-1/2 2 1-1/2 2
(1) 2 (1) 2 (1) 1-1/2 (1) 1-1/4
(1) 2 (1) 2-1/2 (1) 1-1/2 (1) 1-1/2
350 3 3 2 2-1/2 2 2 2 2 1-1/2 2
(2) 3 (2) 2 (1) 2 (1) 1-1/4
(2) 3 (1) 2 (1) 2-1/2 (1) 1-1/2 (1) 2
400 3 3 2 2-1/2 2 2 2 2 1-1/2
(1) 2-1/2 (2) 2-1/2 (1) 2 (1) 2 (1) 1-1/2
SectionA1-20 Rev. 09 09
Model CBLE 100-800 HP Boilers
DIMENSION (INCHES)
BOILER HP
A B C D E
CB-125 THRU CB-200 33 55 45 68 32
CB-250 THRU CB-350 42 69 58 86 43
CB-400 THRU CB-800 51 88 71 109 53
Figure A1-7. Space Required to Open Rear Head on Model CB-LE Boilers Equipped with Davits
BOILER HP A B C D E F G X1 X2 X3
125 6 9 112 39-1/2 57-1/2 4 44-1/2 10 9-3/4 22-1/2
150 6 9 136 39-1/2 57-1/2 4 44-1/2 10 9-3/4 22-1/2
200 6 9 167 39-1/2 57-1/2 4 44-1/2 10 9-3/4 22-1/2
250 6 12 131 46 70 4 56 10 22 22-1/2
300 6 12 158 46 70 4 56 10 22 22-1/2
350 6 12 188 46 70 4 56 10 22 22-1/2
NOTE:
All numbers in table are in inches.
6-inch high mounting piers recommended for use beneath the boiler base frame. The use of these piers provides increased
inspection accessibility to the piping beneath the boiler and added height for washing down the area beneath the boiler.
Figure A1-8. Model CB-LE Boiler Mounting Piers (60" and 78")
BOILER HP A B C D E F G
400 6 14 134 50 78 6-1/2 58-7/8
500 6 14 155 50 78 6-1/2 58-7/8
600 6 14 187 50 78 6-1/2 58-7/8
700-750-800 6 14 220 50 78 6-1/2 58-7/8
NOTE:
1. All numbers in table are in inches.
2. 6-inch high mounting piers recommended for use beneath the boiler base frame. The use of these piers provides
increased inspection accessibility to the piping beneath the boiler and added height for washing down the area
beneath the boiler.