Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Model CBLE 125-800 HP Boilers: Table A1-14. Steam Boiler Safety Valve Openings

Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

Model CBLE 125-800 HP Boilers

Table A1-14. Steam Boiler Safety Valve Openings

VALVE
15 PSIG STEAM 100 PSIG STEAM 125 PSIG STEAM 150 PSIG STEAM 200 PSIG STEAM 250 PSIG STEAM 300 PSIG STEAM
SETTING
NO. OF OUTLET NO. OF OUTLET NO. OF OUTLET NO. OF OUTLET NO. OF OUTLET NO. OF OUTLET NO. OF OUTLET
BOILER VALVES- SIZE VALVES- SIZE VALVES SIZE VALVES- SIZE VALVES- SIZE VALVES SIZE VALVES SIZE
HP REQ'D (IN.) REQ'D (IN.) REQ'D (IN.) REQ'D (IN.) REQ'D (IN.) REQ'D (IN.) REQ'D (IN.)
(1) 1-1/2 (1) 1-1/2 (1) 1-1/4
125 1 3 2 1-1/2 2 2 2 2 1 2 1
(1) 1-1/4 (1) 1-1/4 (1) 1
(1) 2 (1) 1-1/2 (1) 1
150 1 3 2 2 1-1/2 2 2 2 1 2 1
(1) 1-1/2 (1) 1-1/4 (1) 1-1/4
(1) 2 (1) 1-1/2 (1) 1
200 2 2-1/2 2 2 2 2 1-1/2 2 2 1-1/4 2
(1) 1-1/2 (1) 1-1/4 (1) 1-1/4
(1) 2-1/2 (1) 2-1/2 (1) 2 (1) 1-1/2
250 2 2 2 2 2 2 1-1/2 2 2 1-1/4
(1) 3 (1) 2 (1) 1-1/2 (1) 1-1/4
(1) 2-1/2 (1) 2-1/2 (1) 2 (1) 1-1/2
300 2 3 2 2 2 2 1-1/2 2 1-1/2 2
(1) 2 (1) 2 (1) 1-1/2 (1) 1-1/4
(1) 2 (1) 2-1/2 (1) 1-1/2 (1) 1-1/2
350 3 3 2 2-1/2 2 2 2 2 1-1/2 2
(2) 3 (2) 2 (1) 2 (1) 1-1/4
(2) 3 (1) 2 (1) 2-1/2 (1) 1-1/2 (1) 2
400 3 3 2 2-1/2 2 2 2 2 1-1/2
(1) 2-1/2 (2) 2-1/2 (1) 2 (1) 2 (1) 1-1/2

500 3 (3) 3 3 (2) 2-1/2 (1) 2 (1) 1-1/2


2-1/2 3 2 2-1/2 2 2 (2) 2 2
(1) 2 (1) 2-1/2 (1) 2
(3) 2-1/2 (1) 2 (1) 1-1/2
600 4 3 4 3 2-1/2 2 2-1/2 2 2 2 2
(1) 2 (1) 2-1/2 (1) 2
(3) 3 (3) 2-1/2 (3) 2-1/2 (2) 2-1/2 (1) 2
700 5 5 4 3 2 2-1/2 2 2 2
(2) 2-1/2 (2) 2 (1) 2 (1) 2 (1) 2-1/2
(3) 3 (3) 2-1/2 (3) 2-1/2 (2) 2-1/2 (1) 2 (1) 2
800 5 5 4 3 2 2-1/2 2 2
(2) 2-1/2 (2) 2 (1) 2 (1) 2 (1) 2-1/2 (1) 2-1/2

NOTES: Valve manufacturers are Kunkle, Consolidated or Conbraco, depending on availability.

Table A1-15. Hot Water Boiler Relief Valve Openings


VALVE
30 PSIG HW 60 PSIG HW 100 PSIG HW 125 PSIG HW
SETTING
NO. OF OUTLET NO. OF OUTLET NO. OF OUTLET NO. OF OUTLET
BOILER HP VALVES SIZE VALVES SIZE VALVES SIZE VALVES SIZE
REQ'D (IN.) REQ'D (IN.) REQ'D (IN.) REQ'D (IN.)
125 1 2-1/2 1 2 1 2 1 1-1/4
150 1 2-1/2 1 2-1/2 1 2 1 2
(1) 2-1/2
200 2 1 2-1/2 1 2 1 2
(1) 1-1/4
(1) 2
250 2 1 2-1/2 1 2-1/2 1 2
(1) 2-1/2
(1) 1
300 2 2-1/2 2 1 2-1/2 1 2-1/2
(1) 2-1/2
(2) 2-1/2 (1) 2-1/2
350 3 2 1 2-1/2 1 2-1/2
(1) 1 (1) 2
(1) 2 (1) 2 (1) 1
400 3 2 2 1 2-1/2
(2) 2-1/2 (2) 2-1/2 (1) 2-1/2
(1) 1 (1) 2-1/2 (1) 1
500 4 2 2-1/2 2 2
(3) 2-1/2 (1) 1-1/4 (1) 2-1/2
(3) 2-1/2 (1) 1-1 (1) 2 (1) 2-1/2
600 4 3 2 2
(1) 2 (2) 2-1/2 (1) 2-1/2 (1) 1-1/4
700, 750 & (1) 1 (1) 2 (1) 2-1/2
5 3 2 2-1/2 2
800 (4) 2-1/2 (2) 2-1/2 (1) 2

NOTES: Hot water relief valves are Kunkle #537.

SectionA1-20 Rev. 09 09
Model CBLE 100-800 HP Boilers

DIMENSION (INCHES)
BOILER HP
A B C D E
CB-125 THRU CB-200 33 55 45 68 32
CB-250 THRU CB-350 42 69 58 86 43
CB-400 THRU CB-800 51 88 71 109 53

Figure A1-7. Space Required to Open Rear Head on Model CB-LE Boilers Equipped with Davits

BOILER HP A B C D E F G X1 X2 X3
125 6 9 112 39-1/2 57-1/2 4 44-1/2 10 9-3/4 22-1/2
150 6 9 136 39-1/2 57-1/2 4 44-1/2 10 9-3/4 22-1/2
200 6 9 167 39-1/2 57-1/2 4 44-1/2 10 9-3/4 22-1/2
250 6 12 131 46 70 4 56 10 22 22-1/2
300 6 12 158 46 70 4 56 10 22 22-1/2
350 6 12 188 46 70 4 56 10 22 22-1/2
NOTE:
All numbers in table are in inches.
6-inch high mounting piers recommended for use beneath the boiler base frame. The use of these piers provides increased
inspection accessibility to the piping beneath the boiler and added height for washing down the area beneath the boiler.

Figure A1-8. Model CB-LE Boiler Mounting Piers (60" and 78")

Section A1-21 Rev. 09-09


Model CBLE 100-800 HP Boilers

BOILER HP A B C D E F G
400 6 14 134 50 78 6-1/2 58-7/8
500 6 14 155 50 78 6-1/2 58-7/8
600 6 14 187 50 78 6-1/2 58-7/8
700-750-800 6 14 220 50 78 6-1/2 58-7/8
NOTE:
1. All numbers in table are in inches.
2. 6-inch high mounting piers recommended for use beneath the boiler base frame. The use of these piers provides
increased inspection accessibility to the piping beneath the boiler and added height for washing down the area
beneath the boiler.

Figure A1-9. Model CB-LE Boiler Mounting Piers (96")

Section A1-22 Rev. 09-09


Model CBLE 100-800 HP Boilers

ALL DIMENSIONS IN INCHES


BOILER HP VIEW
A B C D E
125 All B 80-1/4 29-3/4 70-1/2 10 3
150 All B 80-1/4 29-3/4 83-1/2 10 3
200 All B 80-1/4 29-3/4 114-1/2 10 3
Steam B 99 36 72 10 3
250
Hot Water B 99 36 81 10 3
Steam B 99 36 99 10 3
300
Hot Water B 99 36 108 10 3
Steam B 99 36 129 10 3
350
Hot Water B 99 36 138 10 3
Steam B 119 35-3/4 78 11 3
400
Hot Water B 119 35-3/4 78 11 3
Steam B 119 35-3/4 99 11 3
500
Hot Water B 119 35-3/4 99 11 3
Steam B 119 35-3/4 131 11 3
600
Hot Water B 119 35-3/4 131 11 3
700, 750 & Steam B 119 35-3/4 164 11 3
800 Hot Water B 119 35-3/4 164 11 3
NOTE: A, B and C dimensions may vary by 1/2 inch.

Figure A1-10. Lifting Lug Location, Model CB-LE Boilers

Section A1-23 Rev. 09-09

You might also like