Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

HTM 02 01 Part A

Download as pdf or txt
Download as pdf or txt
You are on page 1of 201

Medical gases – Health Technical Memorandum 02-01 Medical gas pipeline systems – Part A: Design, installation, validation and

verification
Medical gases
Health Technical Memorandum
02-01: Medical gas pipeline
systems
Part A: Design, installation, validation
and verification

IS B N 0 -1 1 -3 2 2 7 4 2 -6

www.tso.co.uk
9 780113 227426
DH INFORMATION READER BOX

Policy Estates
HR / Workforce Performance
Management IM & T
Planning Finance
Clinical Partnership Working

Document Purpose Best Practice Guidance


ROCR Ref: 0 Gateway Ref: 6543
Title Health Technical Memorandum 02-01 : Medical Gas Pipeline
Systems - Part A Design, Installation, Validation and Verification
Author DH Estates and Facilities Directorate
Publication Date May 2006
Target Audience PCT CEs, NHS Trust CEs, Care Trust CEs, Foundation Trust CEs ,
Medical Directors, Directors of Nursing, PCT PEC Chairs, NHS
Trust Board Chairs, Special HA CEs

Circulation List Department of Health libraries, House of Commons library


Strategic Health Authority, UK Health Departments

Description This document covers piped medical gases, medical and surgical
air, and medical vacuum installations. It applies to all medical gas
pipeline systems installed in healthcares premises. Anaesthetic gas
scavenging and disposal system are included. Specifically, it deals
with issues in the design, installation, validation and verification
(testing and commissioning) of the MGPS.

Cross Ref n/a


0
Superseded Docs HTM 2022 : Design, installation, validation and verification
0
Action Required n/a
0
Timing n/a
Contact Details Ken Holmes
Department of Health
Finance and Investment Directorate
Estates and Facilities Division
Quarry House
Leeds
LS2 7UE
ken.holmes@dh.gsi.gov.uk
For Recipient's Use
Medical gases
Health Technical Memorandum
02-01: Medical gas pipeline systems

Part A: Design, installation, validation and verification

London: The Stationery Office


Medical gases – HTM 02-01 Medical gas pipeline systems – Part A: Design, installation, validation and verification

Published by TSO (The Stationery Office) and available from:


Online
www.tsoshop.co.uk
Mail, Telephone, Fax & E-mail
TSO
PO Box 29, Norwich NR3 1GN
Telephone orders/General enquiries 0870 600 5522
Fax orders 0870 600 5533
E-mail customer.services@tso.co.uk
Textphone 0870 240 3701
TSO Shops
123 Kingsway, London WC2B 6PQ
020 7242 6393 Fax 020 7242 6394
68–69 Bull Street, Birmingham B4 6AD
0121 236 9696 Fax 0121 236 9699
9–21 Princess Street, Manchester M60 8AS
0161 834 7201 Fax 0161 833 0634
16 Arthur Street, Belfast BT1 4GD
028 9023 8451 Fax 028 9023 5401
18–19 High Street, Cardiff CF10 1PT
029 2039 5548 Fax 029 2038 4347
71 Lothian Road, Edinburgh EH3 9AZ
0870 606 5566 Fax 0870 606 5588
TSO Accredited Agents
(see Yellow Pages)
and through good booksellers

© Crown copyright 2006


Published with the permission of the Estates and
Facilities Division of the Department of Health,
The paper used in the printing of this document (Revive Silk)
on behalf of the Controller of Her Majesty’s Stationery Office.
is 75% made from 100% de-inked post-consumer waste, the
This document/publication is not covered by the HMSO remaining 25% being mill broke and virgin fibres. Recycled
Click-Use Licences for core or added-value material. papers used in its production are a combination of Totally
Chlorine Free (TCF) and Elemental Chlorine Free (ECF). It
If you wish to re-use this material, please send your application
is recyclable and biodegradable and is an NAPM and Eugropa
to:
approved recycled grade.
Copyright applications
The Copyright Unit
OPSI
St Clements House
2–16 Colegate
Norwich NR3 1BQ
ISBN 0-11-322742-6
978-0-11-322742-6
First published 2006
Printed in the United Kingdom for The Stationery Office

ii
Preface

About Health Technical Memoranda main source of specific healthcare-related guidance for
estates and facilities professionals.
Engineering Health Technical Memoranda (HTMs) give
comprehensive advice and guidance on the design, The new core suite of nine subject areas provides access to
installation and operation of specialised building and guidance which:
engineering technology used in the delivery of healthcare. • is more streamlined and accessible;
The focus of HTM guidance remains on healthcare- • encapsulates the latest standards and best practice in
specific elements of standards, policies and up-to-date healthcare engineering;
established best practice. They are applicable to new and
existing sites, and are for use at various stages during the • provides a structured reference for healthcare
whole building lifecycle: engineering.
Figure 1 Healthcare building life-cycle

DISPOSAL CONCEPT

RE-USE
DESIGN & IDENTIFY
OPERATIONAL OPERATIONAL
MANAGEMENT REQUIREMENTS

Ongoing SPECIFICATIONS
MAINTENANCE TECHNICAL & OUTPUT
Review

PROCUREMENT
COMMISSIONING

CONSTRUCTION
INSTALLATION

Healthcare providers have a duty of care to ensure that Structure of the Health Technical
appropriate engineering governance arrangements are in
Memorandum suite
place and are managed effectively. The Engineering
Health Technical Memorandum series provides best The new series of engineering-specific guidance contains
practice engineering standards and policy to enable a suite of nine core subjects:
management of this duty of care. Health Technical Memorandum 00
It is not the intention within this suite of documents to Policies and principles (applicable to all Health
unnecessarily repeat international or European standards, Technical Memoranda in this series)
industry standards or UK Government legislation. Where Health Technical Memorandum 01
appropriate, these will be referenced. Disinfection and sterilization
Healthcare-specific technical engineering guidance is a Health Technical Memorandum 02
vital tool in the safe and efficient operation of healthcare Medical gases
facilities. Health Technical Memorandum guidance is the

iii
Medical gases – HTM 02-01 Medical gas pipeline systems – Part A: Design, installation, validation and verification

Health Technical Memorandum 03 In a similar way Health Technical Memorandum 07-02


Ventilation systems will simply represent:
Health Technical Memorandum 04 Environment and Sustainability – EnCO2de.
Water systems
All Health Technical Memoranda are supported by the
Health Technical Memorandum 05 initial document Health Technical Memorandum 00
Fire safety which embraces the management and operational policies
from previous documents and explores risk management
Health Technical Memorandum 06
issues.
Electrical services
Some variation in style and structure is reflected by the
Health Technical Memorandum 07
topic and approach of the different review working
Environment and sustainabilty
groups.
Health Technical Memorandum 08
DH Estates and Facilities Division wishes to acknowledge
Specialist services
the contribution made by professional bodies,
Some subject areas may be further developed into topics engineering consultants, healthcare specialists and
shown as -01, -02 etc and further referenced into Parts A, NHS staff who have contributed to the review.
B etc.
Example: Health Technical Memorandum 06-02 Part A
will represent:
Electrical Services – Safety – Low Voltage
Figure 2 Engineering guidance

iv
Executive summary

Introduction • a liquid source such as a large vacuum-insulated


evaporator (VIE);
A medical gas pipeline system (MGPS) is installed to
provide a safe, convenient and cost-effective system • liquid cylinders or compressed gas cylinders; or
for the provision of medical gases to the clinical and • a combination of these to provide the necessary
nursing staff at the point-of-use. It reduces the problems stand-by/back-up capacity.
associated with the use of gas cylinders such as safety,
porterage, storage and noise. Oxygen can also be supplied from an oxygen
concentrator (pressure-swing adsorber). Such systems are
This Health Technical Memorandum is divided into two usually installed where liquid or cylinders are expensive,
parts. Guidance in this part (Part A) covers piped medical unavailable or impracticable.
gases, medical and surgical air, and medical vacuum
installations: it applies to all medical gas pipeline Medical air
systems installed in healthcare premises and anaesthetic
gas scavenging disposal systems. Specifically, it deals Medical air is usually supplied from a compressed air
with the issues involved in the design, installation, and plant that includes high-quality drying and filtration
validation and verification (testing and commissioning) equipment. Blending oxygen and nitrogen on-site
of an MGPS. Part B covers operational management. to provide a high-quality product with minimum
maintenance can also provide medical air. Where such
The guidance given in this document should be followed systems are installed to provide both oxygen and medical
for all new installations and refurbishment or upgrading air, nitrogen can be used for the power source for surgical
of existing installations. tools.
It is not necessary to apply the guidance retrospectively
unless patient or staff safety would be compromised. In Other gases
this case, the guidance given in this document should be All other gases are supplied from cylinders.
followed.
(On-site blended oxygen/nitrous oxide mixture is a
Existing installations should be assessed for compliance possibility if bulk liquid supplies of nitrous oxide are
with this guidance document. A plan for upgrading the available, although this system is unlikely to be adopted
existing system should be prepared, taking account of the in the UK.)
priority for patient safety. Managers will need to liaise
with medical colleagues and take account of other Basic principles of design
guidance published by the Department of Health in
order to assess the system for technical shortcomings. Patient safety is paramount in the design, installation,
commissioning and operation of medical gas pipeline
Health Technical Memorandum 02 supersedes all systems. The basic principles of safety are achieved by
previous versions of Health Technical Memorandum ensuring quantity of supply, identity of supply, continuity
2022. of supply and quality of supply.

Sources of supply for pipeline Quantity of supply


installations This is achieved by ensuring that the design of the
pipeline installation and capacity of the supply plant is
Oxygen sufficient to provide the required flows of gases and
Oxygen is generally supplied from: vacuum for the intended number of patients to be treated


Medical gases – HTM 02-01 Medical gas pipeline systems – Part A: Design, installation, validation and verification

at any one time. Adequacy of supply is established during


commissioning of the systems. General uses of gas and pipeline
installations
Identity of supply • Oxygen is one of the most extensively used
This is achieved by ensuring that all points to which the gases for respiratory therapy and life-support
user can connect medical equipment (terminal units) and is additionally used in anaesthetic
and user-replaceable components are provided with gas- procedures.
specific connectors. Such connectors are also identified • Medical air is mainly used in respiratory
by symbol and often colour. The gas specificity is therapy as a power source for patient
maintained by comprehensive tests and checks during ventilators, and for blending with oxygen.
installation and commissioning, and during any work or It is also used as the driving gas for nebulised
maintenance on the systems. drugs and chemotherapy agents.
Continuity of supply • Surgical air (of medical air quality) is also
used, at a higher pressure, to power a variety
This is achieved by installing, as a minimum, duplex
of surgical tools and other devices such as
components and providing additional means of supply
tourniquets. (As an alternative, nitrogen can
provision in the event of failure of the primary and
be used for this purpose.).
secondary plant or supply system. Systems are also
connected to the essential electrical supply. • Nitrous oxide is used for anaesthetic and
analgesic purposes, being mixed with air,
Quality of supply oxygen, and nebulised agents.
Quality of supply is ensured by the use of gaseous • Pipeline systems for a 50% mixture of
or liquid sources that are provided to an appropriate oxygen and nitrous oxide are widely
product specification, usually a recognised European installed in the UK for analgesic purposes,
Pharmacopoeia (Ph. Eur.) monogram. In the case of particularly in maternity departments.
compressor-based systems, filtration equipment to a
• Helium/oxygen mixture is used to treat
known and agreed standard is installed. To ensure that
patients with respiratory or airway
the product is not adulterated in the distribution system,
obstruction and to relieve symptoms and
pipeline installations and components are required to
signs of respiratory distress; guidance on
meet agreed specifications. There are strict Ph. Eur.
pipeline systems is now included.
requirements for medical gases.
• Carbon dioxide is used less commonly
now as a respiratory stimulant, and for
insufflation during surgery. Pipeline systems
for respiratory use have not been installed in
the UK but they are now being installed for
this latter purpose.
• Piped vacuum is provided in most clinical
areas by means of centrally sited vacuum
pumps.
• The control of occupational exposure to
waste anaesthetic gas (nitrous oxide) and
nebulised agents is a legal requirement under
the Control of Substances Hazardous to
Health (COSHH) Regulations 2002. Where
nitrous oxide is provided for anaesthetic
purposes, scavenging systems are installed.

vi
Acknowledgements

Mike Arrowsmith Arrowsmith and Associates


Geoffrey Dillow Geoffrey Dillow and Associates
Ian Fraser Department of Health
Mike Ralph Medical Gas Association

vii
Medical gases – HTM 02-01 Medical gas pipeline systems – Part A: Design, installation, validation and verification

Contents

Preface
Executive summary
Acknowledgements
Chapter 1 Scope page 1
Guidance in this document
Other guidance
Chapter 2 General principles page 2
Introduction
Quality requirements for medical gases and air
Sources of supply
Sizing information for gas supply sources
Pipeline distribution system design
Safety
Installation/supply of equipment/maintenance
Modifications
Removal of pipework
Validation and verification
General fire precautions
Electricity supply to medical gas installations
Chapter 3 Provision of terminal units, and the location of AVSUs, local alarm indicator panels
and LVAs page 10
General
Terminal units
Terminal units for helium/oxygen mixture
Nitrogen for surgical tools
AVSUs
Local alarm indicator panels
LVAs
Specific labelling requirements
Chapter 4 Gas flow page 22
General
Terminal unit flows
Pipeline flows
Oxygen
Hyperbaric oxygen chambers
Nitrous oxide
Nitrous oxide/oxygen mixture
Air
Vacuum
Helium/oxygen mixture
Anaesthetic gas scavenging systems

viii
Contents

Chapter 5 Cylinder manifold installations page 36


Primary supply system
Secondary supply system
Chapter 6 Oxygen systems page 41
Liquid oxygen systems
Oxygen concentrator installations (PSA plant)
Chapter 7 Medical compressed air systems page 66
General
Compressor systems
Quality
Siting
Compressor noise
Air intake
Compressor types
Compressor lubrication
After-coolers
Receivers
Air treatment and filtration
Pressure control
Traps, valves and non-return valves
Operating and indicating system
Synthetic air
System description
Storage vessels
Vaporisation
Medical oxygen flow control
Surgical nitrogen flow control
Control panel for the nitrogen and oxygen supplies to the mixing panels
Air mixing panels
Buffer vessels
Alarm signal status unit
Emergency supply provision
Additional use of medical air systems
Chapter 8 Surgical air systems page 82
General
Extension of surgical air systems into dental departments
Chapter 9 Medical vacuum systems page 85
General
Siting
Pump noise
Vacuum plant exhaust
Efficiency
Vacuum pumps
Pressure control
Valves
Pressure regulation of vacuum system
Vacuum indicators
Electrical supply
Pump operating and indicating system

ix
Medical gases – HTM 02-01 Medical gas pipeline systems – Part A: Design, installation, validation and verification

Chapter 10 Anaesthetic gas scavenging disposal systems page 91


Terminology
General
Selecting the number of disposal system pumps
Flow and diversity
Discharge outlet
Plant control indication
Chapter 11 Other medical gas pipeline installations page 94
General
Helium/oxygen mixture
Oxygen/CO2 mixture
Carbon dioxide
Nitric oxide
Chapter 12 Warning and alarm systems page 96
General
Dedicated systems
Panel location
System components
System layout
General requirements
Warning and alarm system faults
Indicator panel requirements for all systems
Central indicator panel requirements
Repeater indicator panel requirements
Area warning and alarm panel
Integrated systems
Chapter 13 Pipeline installation page 104
Pipeline materials
Cleaning
Pipeline jointing
Inspection of joints
Jointing methods (mechanical)
Capping
Pipe supports
Identification of pipelines
Pipeline components
Medical supply units
Flexible pendant fittings
Bed-head trunking/walling systems
LVAs and AVSUs
Specific labelling requirements
Pressure control equipment
Pressure sensors
Pressure gauges
Test points
Emergency inlet port
Line pressure alarms and safety valves
Other systems
Chapter 14 Accommodation page 114
Design and construction of plant and manifold rooms


Contents

Chapter 15 Validation and verification page 117


Summary of tests
General requirements for testing
Modifications, extensions or repairs to existing systems
Requirements for pipeline carcass tests
Labelling and marking
Sleeving and supports
Leakage
Cross-connection
Requirements for pipeline system tests
Leakage from total compressed medical gas systems
Leakage into total vacuum systems
Closure of area valve service units and line valve assemblies
Zoning of AVSUs and terminal unit identification
Cross-connection
Flow and pressure drop at individual terminal units, mechanical function and correct
installation
Performance tests on the pipeline system
Functional tests of supply systems
Pressure safety valves
Warning and alarm systems
Verification of as-fitted drawings
Filling with medical air
Purging and filling with specific gases
Pharmaceutical testing
Quality of medical gas systems
AGS disposal systems
Requirements before a medical gas pipeline system is taken into use
Appendix A Testing, commissioning and filling for use: forms to be completed during testing
and commissioning of piped medical gases systems page 141
Appendix B Gas pressure variation with temperature page 161
General
Calculation
Examples
Appendix C Pressure-drop test device page 162
General
Measurement principle
Functional requirements
Orifices
Flowmeter
Pressure gauge
Appendix D Membrane filter test device page 163
General
Measurement principle
Test equipment
Appendix E Equipment for contaminant testing page 164
General
Measurement principle

xi
Medical gases – HTM 02-01 Medical gas pipeline systems – Part A: Design, installation, validation and verification

Appendix F Equipment for gas identification page 165


General
Specificity
Specification
Appendix G Pressure loss data page 166
Pipeline pressure-drop calculations
Appendix H Checklist for planning/installing/upgrading a cryogenic liquid supply system page 172
Delivery frequency
Calculating consumption
Age of current system
Siting of system and the site survey
Costs
Emergency provision
System shutdown during installation
Paperwork
Health and safety
Preparation
Installation
Follow-up
Appendix J Upgrading surgical air systems page 176
Background
Modifying “old” systems
Appendix K Signage requirements page 178
Appendix L Important notes for use of medical vacuum and anaesthetic gas scavenging page 182
Infectious disease units
Laser/surgical diathermy smoke extraction
Dental vacuum systems
Anaesthetic gas scavenging (AGS)
Appendix M Oxygen usage data page 183
Appendix N Pressure conversion table page 184
References page 185

xii
1 Scope

Guidance in this document for upgrading the existing system should be


prepared, taking account of the priority for patient
1.1 This Health Technical Memorandum is divided safety. Managers will need to liaise with medical
into two parts. Guidance in this part (Part A) colleagues and take account of other guidance
covers piped medical gases, medical and surgical air, published by the Department of Health in order to
and medical vacuum installations; it applies to all assess the system for technical shortcomings.
medical gas pipeline systems installed in healthcare
premises. Anaesthetic gas scavenging disposal 1.5 Throughout this document, “medical gas pipeline
systems are also included. Specifically, it deals system(s)” will be described by the term MGPS.
with the issues involved in the design, installation,
and validation and verification (testing and Other guidance
commissioning) of an MGPS. Part B covers 1.6 Model Engineering Specification C11 –
operational management. ‘Medical gases’ supports this Health Technical
1.2 The guidance given in this document should be Memorandum. It provides details of the extent of
followed for all new installations and refurbishment the works required and is a procurement
or upgrading of existing installations. specification.
1.3 It is not necessary to apply the guidance 1.7 Whenever appropriate, British Standard
retrospectively unless patient or staff safety would specifications should be used.
be compromised. In this case, the guidance given in 1.8 Guidance on the provision of MGPS is given in the
this document should be followed. Health Building Notes and other relevant British,
1.4 Existing installations should be assessed for European, and International standards.
compliance with this guidance document. A plan


Medical gases – HTM 02-01 Medical gas pipeline systems – Part A: Design, installation, validation and verification

2 General principles

Introduction Note
2.1 An MGPS is designed to provide a safe and
Portable suction devices should be used in infectious
effective method of delivering medical gases,
disease units.
medical air and surgical air from the source of
supply to the appropriate terminal unit by means of
a pipeline distribution system. Medical vacuum is
Quality requirements for medical gases
also provided by means of a pipeline system. and air
Anaesthetic gas scavenging disposal systems are 2.8 Medical gases supplied from cylinder or liquid
provided to control occupational exposure to waste sources comply with the appropriate sections of the
anaesthetic gases and agents. current edition of the European Pharmacopoeia
2.2 It is essential to ensure that there is no possibility of (Ph. Eur.). The Ph. Eur. also specifies the approved
a cross-connection between any system and that all testing methods to be adopted for gas identity.
parts of each system to which connections can be 2.9 The quality specification for medical, surgical and
made by users are gas-specific. synthetic air, and oxygen-enriched air produced
2.3 Dental compressed air and vacuum systems have from a pressure swing adsorber (PSA) system, is as
differing requirements, and these are covered given in Table 29. The medical air and synthetic air
in Health Technical Memorandum 2022 should also comply with the appropriate sections of
Supplement 1 – ‘Dental compressed air and the current edition of the current edition of the Ph.
vacuum systems’. Eur. (see Table 30).
2.4 During the installation stage, extensive tests are 2.10 The quality of piped medical compressed air, and
carried out to verify that there is no cross- the particulate content, dryness and concentration
connection. of impurities should comply with the requirements
for maximum concentrations given in Table 30.
2.5 Medical gas systems may be extended to those Information on testing procedures is given in
departments where respiratory equipment or Chapter 15 “Validation and verification”.
surgical tools are serviced, such as in electronic and
biomedical equipment (EBME) workshops and 2.11 Bacteria filters should be included in medical and
sterile services departments (SSDs). Specific surgical compressor systems to reduce the risk of
additional uses of air systems are covered in delivering spores or other infectious material to
Chapters 7 and 8. vulnerable patients.
2.6 MGPS should not be used to supply pathology 2.12 Micro-organisms can penetrate a bacteria filter if
departments, general workshops or mechanical the material is wet. Therefore it is essential that the
services. dryness of the medical air supplied to a bacteria
filter is checked regularly (at least every three
2.7 Separate installations should be provided for months) at the test point, using the test equipment
pathology and general laboratories and workshops, specified in Chapter 15.
although it is recommended that they be
constructed to the same specification as MGPS.
They should not be provided with medical gas
Sources of supply
terminal units. 2.13 Both BS EN 737-3:2000 and ISO 7396-1:2002
propose that all medical gas supplies should
comprise three sources of supply identified as
“primary”, “secondary” and “reserve”, although the


2 General principles

latter is more commonly referred to as a third 2.15 Regardless of these classification differences,
means of supply. The supply system should be the choice of central source will be defined by
designed to achieve continuity of supply to the the ability of the source not only to provide a
terminal units in normal condition and in a single continuous supply of gas over a range of possible
fault condition. A single fault condition is where a flow rates but also to offer security of supply by
single means for protection against a safety hazard virtue of adequate capacity.
in equipment is defective or a single external
2.16 For these reasons, types, capacities and locations of
abnormal condition is present. Loss of supply
primary, secondary and reserve sources of supply
due to maintenance of a supply source (or a
will be based on both system design parameters and
component within it) is not considered a single
the need for supply security, identified by a risk
fault condition.
assessment during the planning stage. Security of
2.14 Comparing this Health Technical Memorandum medical air supplies must be given a high priority.
with the above Standards will reveal a different Total electrical failure must not be allowed to
classification of, for example, individual banks of a jeopardise supplies, and all medical air systems
cylinder manifold. Whereas EN 737-3:2000 refers must be supported by an appropriate fully-
to the separate banks of an automatic manifold as automatic manifold. Tables 1–9 describe the
primary and secondary supplies, this Health various options for gas supply. For each, the
Technical Memorandum classifies such a manifold primary, secondary and reserve sources are
as a primary supply, that is, one single operating identified.
unit.

Table 1 Compressed gas cylinder manifold systems


Primary supply Secondary supply Reserve supply (third source of supply)
Fully automatic manifold. Manual emergency reserve manifold. Automatic/manual manifold supplying
Number of cylinders based on system To come on line automatically via a non- via non-interchangeable screw thread
design return valve. (NIST) connectors
Number of cylinders based on ability to OR
provide 4 hours’ supply at average use Locally-based integral valved cylinders
with regulators/flowmeters attached
Table 2 VIE systems
Primary supply Secondary supply Reserve supply (third source of supply)
Simplex VIE (vacuum-insulated Automatic manifold system. Automatic manifold system.
evaporator) vessel system To come on-line in the event of plant May be sited to support high-
failure dependency areas or whole site
OR
Locally-based integral valved cylinders
with regulators/flowmeters attached
One vessel of a duplex VIE (vacuum- Second vessel of a duplex VIE system Automatic manifold system.
insulated evaporator) vessel system (on May be sited to support high-
same plinth) dependency areas or whole site
One vessel of a duplex VIE vessel system Second vessel of a duplex VIE system (on Type and capacity of supply to be
(on separate plinths) separate plinths). determined by risk assessment.
NB split-site systems are intended May not be required when a ring main
primarily for systems where the risk or other dual supply to a pipeline
assessment has identified that the site distribution system is provided
for the primary supply is limited in size
or presents too high a risk having both
tanks on the same site. These supply
systems should be fitted with appropriate
non-return valved connections to prevent
gas loss in the event of one tank/system
failing


Medical gases – HTM 02-01 Medical gas pipeline systems – Part A: Design, installation, validation and verification

Table 3 Liquid cylinder systems


Primary supply Secondary supply Reserve supply
(Third source of supply)
Liquid cylinder manifold system. Automatic manifold system. Automatic manifold system.
NB: This is NOT a changeover To come on-line in the event of plant May be sited to support high-
manifold. All cylinders are on-line failure. dependency areas or whole site
simultaneously. OR
Locally-based integral valved cylinders
with regulators/flow meters attached.

Table 4 PSA plant


Primary supply Secondary supply Reserve supply
(Third source of supply)
Multiplex compressors and columns Automatic manifold system. Type and capacity of supply to be
(adsorbers). To come on-line in the event of plant determined by risk assessment.
Subject to design. failure.
May be fitted with third party cylinders,
or filled from compressor of main plant.
Number of cylinders based on ability to
provide 4 hours’ supply at average use.
Locally filled cylinders or gas suppliers’
cylinders can be used

Table 5 Compressor-driven medical air systems


Primary supply Secondary supply Reserve supply
(Third source of supply)
Duplex compressor system. Automatic manifold system. Automatic manifold system.
To come on-line automatically in the May be sited to support high-
event of plant failure. dependency areas or whole site
Number of cylinders based on ability to OR
provide 4 hours’ supply at average use. Locally-based integral valved cylinders
with regulators/flow meters attached.
Two compressors of a triplex compressor Third compressor of a triplex system. Automatic manifold system.
system. To support whole site.
Two compressors of a quadruplex system. Other two compressors of a quadruplex Automatic manifold system.
system. To support whole site.

Table 6 Synthetic air plant


Primary supply Secondary supply Reserve supply
(Third source of supply)
Primary oxygen and nitrogen VIE vessels Secondary oxygen and nitrogen VIE Type and capacity of supply to be
and mixer unit. vessels and mixer unit. determined by risk assessment.


2 General principles

Table 7 Combined medical/surgical air plant


Primary supply Secondary supply Reserve supply
(Third source of supply)
Duplex compressor system. Two automatic manifold systems: Automatic manifold system.
• one dedicated to support medical air (MA) system; May be sited to support high-
• one dedicated to support surgical air (SA) system. dependency areas or whole site
OR
All to come on-line in the event of plant failure.
Locally-based integral valved cylinders
Number of cylinders on each based on ability to
with regulators/flow meters attached.
provide 4 hours’ supply at average use
Two compressors of a Third compressor of a triplex system. Automatic manifold system.
triplex compressor system. To support whole site.
Two compressors of a Other two compressors of a quadruplex system. Automatic manifold system.
quadruplex system. To support whole site.

Table 8 Compressor-driven surgical air systems


Primary supply Secondary supply Reserve supply
(Third source of supply)
Simplex compressor unit. Automatic manifold system. Locally based integral valved cylinders
To come on-line in the event of plant failure. with regulators/flow meters attached.
Number of cylinders based on ability to provide
4 hours’ supply at average use.
One compressor of a Second compressor of a duplex compressor system. Automatic manifold system.
duplex compressor system.

Table 9 Central medical vacuum systems


Primary supply Secondary supply Reserve supply
(Third source of supply)
Two compressors of a triplex pump Third pump of a triplex system. Portable suction equipment.
system.
Two pumps of a quadruplex system. Other two pumps of a quadruplex Portable suction equipment.
system.
Notes to Tables 1–9:
General guidance on vacuum systems is contained in Appendix L.
a. Duplex vacuum plant will be classified as a primary source only. A third pump will need to be added to provide a secondary
supply to meet the recommendations of this Health Technical Memorandum.
b. For duplex and triplex compressor systems and triplex vacuum pump systems, each compressor/pump will be sized to provide
the system’s full design flow.
c. For quadruplex systems, each compressor/pump is sized to cope with half the system design flow.
d. For all compressor systems with a design flow greater than 500 L/min, two receivers, each able to be isolated individually,
should be installed.
e. All plant is to be connected to the essential electricity supply.
f. For vacuum provision during total electricity supply failure, cylinder- or medical-gas-system-powered vacuum generators can be
used.
g. The use of venturi-type vacuum generators is recommended only for emergency use, as these units are generally driven from
the medical oxygen system and use large amounts of gas. This can lead to oxygen enrichment and present a potential fire hazard
and may result in the emission of pathological material.
h. The manual/secondary manifolds supporting fully automatic manifolds are usually sited with the manifold system. If a risk
assessment indicates that this is not in the interests of supply security, they may be sited remotely from the manifold.


Medical gases – HTM 02-01 Medical gas pipeline systems – Part A: Design, installation, validation and verification

In these circumstances, care should be taken to ensure that appropriate backflow protection (or non-return valves) are used to
protect the system from failure of either manifold.
j. Manifolds supporting medical air, surgical air and PSA systems should be sited remotely from the compressor systems.
Appropriate backflow protection should be provided, as above.
k. Where practicable, a valved by-pass arrangement around compressor and VIE-plant non-return valves should be installed to
permit valve replacement without plant shutdown.
m. Fitting non-return valves one pipe size larger will reduce flow resistance, if this is shown to be a critical factor in system design.
n. All sources of supply should be fitted with a test point comprising weatherproof terminal unit and lockable isolating valve.
p. Where medical air is provided by multiple, locally-sited regulators fed from a combined surgical and medical air distribution
system, it will be impracticable to connect supporting manifolds at each regulating station. In this situation, extra care should
be taken to ensure that the third means of supply is able to support both systems simultaneously. Consideration should be given
to additional manifolds sited to support medical air supplies to critical care areas.

Sizing information for gas supply sources


2.17 Table 10 provides guidance on suggested maximum sizes for gas sources. Final decisions on plant and manifold
capacities will depend on both available accommodation and risks to supply security.
Table 10 Suggested sizes for gas sources
Source Service Number of cylinders Cylinder size Notes
Oxygen 2 x 10 J Used as a stand-alone manifold or
support for cryogenic system/PSA plant
Medical air 2 x 10 J Used as a stand-alone manifold or
Surgical air 2x6 J support for compressor plant
Automatic Oxygen/nitrous oxide mixture 2x8 G
manifold
Nitrous oxide 2x6 G
Carbon dioxide 2x4 VF
Helium/oxygen 2x4 H
Nitrogen 2x6 W
Oxygen 2x2 J
Medical air 2x2 J
Surgical air 2x1 J
Manual Oxygen/nitrous oxide mixture 2x2 G As secondary supply for an automatic
manifold Nitrous oxide 2x2 G manifold system
Carbon dioxide 2x1 VF
Helium/oxygen 2x1 H
Nitrogen 2x2 W

Source Service Plant size Notes


Duplex compressor system Medical air Each compressor sized at full design flow capacity Receiver water capacity
Triplex compressor system Medical air Each compressor sized at full design flow capacity sized at 50% free air
delivery (FAD) in
Quadruplex compressor Medical air Each compressor sized at half design flow capacity
1 minute
system
Simplex compressor system Surgical air Compressor sized at 1/3 design flow Water capacity of receiver
Duplex compressor system Surgical air Each compressor sized at 1/ design flow sized at 2 x design flow in
3
1 minute
Triplex pump system Medical Each pump sized at full design flow capacity Water capacity of reservoir
vacuum sized at design flow in
Quadruplex pump system Medical Each pump sized at half design flow capacity 1 minute
vacuum


2 General principles

2.18 Sizing of vacuum-insulated evaporator (VIE) Safety


systems, liquid cylinder storage systems, PSA
plant and synthetic air plant should be based on 2.22 The safety of an MGPS is dependent on four basic
historical consumption data and appropriate risk principles:
assessments carried out with the medical gas a. identity;
supplier. Allowance should be made for increases in
the use of medical gases and changes to the gas b. adequacy;
demands caused by local developments and c. continuity;
strategic issues. For a completely new site, the
d. quality of supply.
proposed gas supplier will need to be consulted
so that a review of their historical data can be 2.23 Identity is assured by the use of gas-specific
conducted for similar sites. The graph shown in connections throughout the pipeline system,
Appendix M will give an approximate indication including terminal units, connectors etc, and by
of expected annual consumption, based on the the adherence to strict testing and commissioning
number of hospital beds. It should be noted that procedures of the system.
higher consumption could be expected when,
2.24 Adequacy of supply depends on an accurate
for example, high numbers (>20) of continuous
assessment of demands and the selection of plant
positive airway pressure (CPAP) machines are in
appropriate to the clinical/medical demands on the
frequent use (>40 hours per week).
system.
Notes 2.25 Continuity of supply is achieved by:

a. Automatic manifolds are generally expected to hold • the specification of a system that (with the
a minimum of two days’ supply on each bank. exception of liquid oxygen systems which may
include a secondary vessel) has duplicate
b. Sufficient cylinders for changing one complete components;
bank should be stored in the manifold room for
all gases except nitrous oxide/oxygen mixture, for • the provision of a third means of supply for all
which two complete changes should be stored in systems except vacuum;
the manifold room. • the provision of alarm systems; and
c. Sufficient additional cylinders should be held in the • connection to the emergency power supply
medical gas store to ensure continuous supply for system.
one week.
2.26 Surgical air systems are not considered to be
life-support systems and therefore duplicate
Pipeline distribution system design components are not normally required; an
2.19 The following general information is required to emergency/secondary supply is provided.
design an MGPS:
2.27 Quality of supply is achieved by the use of gases
a. schedule of provision of terminal units; purchased to the appropriate Ph. Eur. requirements
b. design flow rates and pressure requirements at or produced by plant performing to specific
each terminal unit; standards, by the maintenance of cleanliness
throughout the installation of the system, and by
c. diversified flows for each section of the pipeline the implementation of the various testing and
system; commissioning procedures.
d. total flow.
Installation/supply of equipment/
2.20 Guidance on deriving and calculating the above
parameters is given in Chapters 3 and 4 of this maintenance
Part. 2.28 The installation of an MGPS should be carried out
2.21 The definition of “departments”, which may
only by specialist firms registered to BS EN ISO
comprise several wards, treatment rooms etc, 9001:2000/BS EN ISO 13485:2003 with the scope
should be agreed at the project design stage to of registration appropriately defined.
avoid confusion.


Medical gases – HTM 02-01 Medical gas pipeline systems – Part A: Design, installation, validation and verification

Modifications Validation and verification


2.29 Special precautions are required when existing 2.33 The objective of validation and verification is to
installations are to be modified or extended, to ensure that all the necessary safety and performance
ensure that all sections of the pipeline system requirements of the MGPS will be met. Validation
remaining in use are not contaminated, and that and verification procedures will be required for new
the supply to patients is not compromised. The installations, additions to existing installations and
section to be modified should be physically isolated modifications to existing installations. The scope of
from the section in use. Closure of isolating valves work will dictate the specific programme required.
is insufficient for this purpose. Where area valve This is described in Chapter 15.
service units (AVSUs) and/or line valve assemblies
(LVAs) have been installed, blanking spades should Notes
be used. This isolation procedure is not required The concept of the existing quality assurance BSI
when work is to be carried out on individual scheme schedule QAS 3720. 1/206/A1 is currently
terminal units. under review. Further guidance will be given when
2.30 Modification of existing systems may be appropriate.
detrimental to the overall performance of the
system. In the case of older systems, there may be General fire precautions
insufficient capacity to permit the system to operate
safely with the flows typically encountered in use General
today. 2.34 The siting and general structural principles for the
2.31 Any work involving alteration, extension or design of liquid oxygen storage accommodation
maintenance work on an existing system should be are given in Chapter 6, and the requirements for
subject to the permit-to-work procedure (see plantrooms and gas manifold rooms in Chapter 14.
Part B, Chapter 8). 2.35 Guidance on cylinder storage and handling is given
in Part B.
Removal of pipework
Fire detection system
2.32 Removal and cutting out of redundant medical gas
pipelines and equipment can present as great a 2.36 Smoke or heat detector heads should be installed in
hazard to patient safety as any other modification. the plantrooms, medical gases manifold rooms and
All such removal (including cutting into existing (when internal) medical gases cylinder stores in
pipelines, and capping off and removal of any hospital having a fire detection system in
redundant pipework and equipment) should be accordance with Health Technical Memorandum
carried out by specialist medical gas contractors 05-03, Part B – ‘Firecode: alarm and detection
only. General demolition contractors should not systems’. External stores may also require fire
carry out this work. detection systems.

Note Electricity supply to medical gas


Removal of vacuum systems may present additional installations
microbiological hazards and should be undertaken
in accordance with routine hygiene practices, that is, General
covering of open wounds and immediate cleansing and 2.37 Electrical installations should be carried out in
dressing of cuts/scratches received while carrying out accordance with the current addition of BS 7671
the work. Immunisation against certain diseases may wiring regulations and associated guidance
be required by the hospital’s occupational health documents.
department or the employer of tradespeople; therefore,
all operatives should ensure that this requirement has 2.38 Provision of electrical supply and distribution
been met. should take account of guidance issued in Health
Technical Memorandum 06-01 – ‘Electrical
services’.


2 General principles

Resilience of supply 2.45 Care should be taken when installing both electrical
systems and medical pipeline systems to avoid
2.39 Medical gas pipeline systems, associated equipment
occasional contact between pipework and electrical
and alarms are a critical service within a healthcare
cables, conduit or trunking. When physical
establishment. Due consideration should be given
separation is impractical or contact with extraneous
to ensure the continuity of service under mains
metalwork occurs (for example where the pipeline
power failure conditions.
is carried in metal partitions or where terminal
2.40 Medical gas equipment should be supplied from units are mounted on metal bed-head units),
a dedicated, final sub-circuit which is considered the pipeline should be effectively bonded to the
“essential” within the electrical distribution strategy. metalwork in accordance with BS 7671 wiring
Alternative means of supply should be considered regulations.
in the event that internal sub-distribution is
2.46 The final connection to any equipment (for
compromised.
example alarm panels or control panels) should be
2.41 In the event of power failure or interruption, all made using an unswitched fused connection unit;
systems should continue to function as they did a double-pole switch should be available to permit
before the interruption occurred. For example, work on the equipment.
except for automatic cycling compressors, dryers,
2.47 Where electrical systems and medical gas pipeline
pumps etc, the same compressor and dryer (or
systems are enclosed in a boom, rigid pendant or
vacuum pump) set should be on-line, and for
multi-purpose-type enclosure, care should be taken
manifold systems the same bank should be
to ensure that low voltage (LV), extra-low voltage
running.
(ELV) and communications and data systems are
2.42 All electrical systems, including plant control maintained together but separate from pipeline
systems, alarm interfaces etc, should be designed in systems. There should be no access to unprotected
accordance with electromagnetic compatibility live parts within the pendant except by the use of a
(EMC) directives. For further details, see the tool.
“EMC section” within Health Technical
Memorandum 06-01. Earthing
2.43 It is important that operational managers and 2.48 Medical gas pipelines should be bonded together
designers are fully aware of stand-by electrical and bonded to the local electrical distribution
supply arrangements and availability and that plans board in accordance with BS 7671 wiring
are available to deal with the total loss of electricity regulations. The pipelines should not in themselves
under adverse circumstances. be used for earthing electrical equipment.
2.49 Flexible pipeline connections, wherever used,
Electrical installation
should be bonded across the fixed points to ensure
2.44 Wiring systems for medical gas installations should earth continuity.
be selected in accordance with BS 7671 wiring
2.50 Where a medical gas outlet or pipeline system is
regulations with particular regard to the
present within a group 2 location as defined by IEE
environment and risk from mechanical damage.
Guidance Note 7 – ‘Medical locations’, care must
In this regard, PVC-insulated MICS (mineral-
be taken to ensure the resistance of the bonding
insulated copper-sheathed) cable for external/
connection is in accordance with the required
internal locations and heat-rated singles cable in
value.
galvanised conduit for plantrooms are considered
suitable. For large equipment, fire-rated SWA (steel
wire armoured) cable may be appropriate.


Medical gases – HTM 02-01 Medical gas pipeline systems – Part A: Design, installation, validation and verification

3 Provision of terminal units, and the location


of AVSUs, local alarm indicator panels and
LVAs

General b. vacuum systems in which body or other fluids


are drawn through a fixed pipeline connecting a
3.1 Terminal unit provision, location of AVSUs, local terminal unit or other connector to a remote
alarm indicator panels and LVAs are given in suction jar.
Table 11. Medical treatment policy is evolutionary,
however, and the project team should review 3.5 All terminal units should conform to BS EN
requirements for individual schemes. 737-1:1998. Terminal units intended for wall
mounting where directly connected equipment
Terminal units such as flow meters are to be used must include a
non-swivel device. Terminal units intended for
3.2 Terminal units should be mounted in positions that installation with the socket axis vertical, for
result in the shortest practicable routes for flexible example in certain types of pendant, or where
connecting assemblies, between the terminal unit horizontally mounted but intended for use with
and apparatus. Terminal units may be surface- or indirectly connected equipment by means of a
flush-mounted. They may also be incorporated flexible connecting assembly, should also have a
with electrical services, nurse call systems, non-swivel device because flow meters may be
televisions, radio and audio services, in proprietary attached. Dimensions of probes are given in BS
fittings such as medical supply units, wall panel 5682:2005. It is essential that probes be machined
systems and pendant fittings etc. When they are from stainless steel.
installed within such fittings, it is essential to
maintain the concentricity of the terminal unit 3.6 An anaesthetic gas scavenging (AGS) terminal unit
bezel with the fascia plate aperture; if the should be provided whenever nitrous oxide and
installation is highly eccentric, the bezel will bind anaesthetic agents are available for anaesthetic
on the fascia plate and the terminal unit will not procedures. In recovery areas, where nitrous oxide
function properly. is not provided, there is no primary source of
anaesthetic gas pollution; thus, no anaesthetic gas
3.3 When planning the installation of operating-room scavenging system (AGSS) is required. Guidance
pendant fittings, the location of the operating on operating departments requires such areas to
luminaire and other ceiling-mounted devices be mechanically ventilated. Where nitrous oxide
should be taken into consideration. When the mixed with oxygen is provided for analgesic
operating room is provided with an ultra-clean purposes, scavenging is not generally practicable
ventilation (UCV) system, it may be more and pollution should therefore be controlled by
practicable (and cost-effective) to have the services mechanical ventilation. Details of ventilation
(both medical gas and electrical) incorporated as requirements are given in Health Building Note 26
part of the UCV system partial walls. It is (Volume 1) – ‘Facilities for surgical procedures’.
particularly advantageous in the case of surgical For dental departments, scavenging is possible by
air systems as rigid pipework can be used, thus means of nasal masks, and reference should be
avoiding pressure-loss problems that can occur with made to Heath Technical Memorandum 2022
flexible assemblies used within pendant fittings. (Supplement 1) – ‘Dental compressed air and
3.4 The following are not permitted: vacuum systems’ (see also Chapter 10).

a. floor-mounted terminal units; 3.7 The terminal unit (AGS) is specified in ISO 7396.
AGSS are covered in Chapter 10.

10
3 Provision of terminal units, and the location of AVSUs, local alarm indicator panels and LVAs

Figure 1 Terminal unit mounting order


Note WALL MOUNTED TERMINALS – Horizontal array

Reference should be made to the Department of LEFT RIGHT


Health’s (1996) ‘Advice on the implementation of the
Health & Safety Commission’s occupational exposure
standards for anaesthetic agents’. Further guidance is
O2 N2O O2/N2O MA SA VAC AGS He/O2
given in the Health & Safety Executive’s (1996)
‘Anaesthetic agents: controlling exposure under WALL MOUNTED TERMINALS – Vertical array
COSHH’.
TOP TOP
O2
3.8 Where respiratory equipment or surgical SA
O2
instruments are serviced, such as in EBME N2O
workshops and SSDs, it is normally necessary to N2O VAC
install the full range of medical gas terminal units. O2/N2O OR
O2/N2O AGS
AGS should be provided as a dedicated system.
MA
MA He/O2
3.9 The fixing of terminal units into medical supply
SA
systems or to wall surfaces etc should be such that
the following forces can be applied: VAC

a. a lateral force of 20 N applied at 100 mm from


the surface of the terminal unit without AGS O2
dislodgement or breakage;
He/O2 He/O2 N2O
b. an axial force of 450 N without dislodgement or AGS

breakage. VAC O2/N2O


CIRCULAR (eg pendant) – Viewed from below
3.10 Where an array of terminal units is provided at a
SA MA
location, they should be arranged as follows (see
Figure 1): 3.11 Oxygen/carbon dioxide mixture systems have been
a. for a horizontal array, when viewed from the installed, but are no longer covered by this Health
front, left to right: oxygen, nitrous oxide, Technical Memorandum.
nitrous oxide/oxygen mixture (50% v/v), 3.12 Helium/oxygen mixtures may be required to be
medical air, surgical air, vacuum, anaesthetic supplied by pipeline in some critical care areas.
gas scavenging, helium/oxygen mixture. If this Systems for these are included in Chapter 11.
arrangement is impracticable, a number of rows
can be used. For example: 3.13 Mounting heights for terminal units should be
between 900 mm and 1600 mm above finished
O2, N2O and/or N2O/O2 floor level (FFL) when installed on walls or similar
MA, SA, VAC, AGS, He/O2; vertical surfaces – the optimum height for the
convenience of users of the medical gas system is
b. for a vertical array, with oxygen at the top and 1400 mm (see Figure 2). When terminal units are
in the sequence as for a horizontal array. In incorporated within a horizontal bedhead service
many cases a vertical array is impracticable and trunking system, which also provides integrated
a more convenient arrangement will comprise a linear lighting for general room and/or patient
number of rows (see Figure 1); reading illumination, it should be of a design that
c. for a circular array, for example where terminal does not compromise the convenience of the
units are installed on the under-surface of a medical gas facility.
pendant, with the sequence as for a horizontal 3.14 When installed in pendants or similar, terminal
array, in a clockwise direction when viewed units should be of a type suitable for mounting
from below. The AGS terminal unit may occupy within the specified fitting.
the centre of such an array.
3.15 Pressure losses across terminal units should be in
accordance with BS EN 737-1:1998. (The standard
does not give pressure loss data for surgical air at

11
Medical gases – HTM 02-01 Medical gas pipeline systems – Part A: Design, installation, validation and verification

350 L/min – but this can be up to 100 kPa when b. the distance between the centre of the terminal
connected via a ceiling NIST (non-interchangeable unit and a potential obstruction on either side
screw thread) connector and 5 m of hose.) (for example when installed in a corner) should
be a minimum of 200 mm on either side;
3.16 Terminal units that are wall mounted should be
located as follows (see Figure 2): c. care should be taken to ensure that connected
medical gas equipment and hoses do not foul
a. distance between centres of adjacent horizontal
other nearby equipment and services during use.
terminal units:
Particular attention should be given to terminal
(i) 135 ± 2.5 mm for three or more terminal unit positioning with respect to worktops,
units; electrical sockets, cupboards, equipment rails,
(ii) 150 ± 2.5 mm for two terminal units only; ventilation flaps and door openings. A
minimum radial clearance of at least 200 mm
from these items is suggested, but this may have
Note
to be increased depending on the nature of
To promote a more “domestic” environment, some connected equipment.
in-patient accommodation is provided with terminal
units installed in recesses behind covers/decorative Terminal units for helium/oxygen
panels etc. To accommodate this it is necessary to allow
an additional 100 mm on each side of the outermost
mixture
terminal units and 200 mm from centre to top of 3.17 BS EN 737-1:1998 does not include a terminal
recess and 300 mm from centre to bottom of recess. unit for helium/oxygen mixture. They will be
The depth of the recess should be 150 mm. The included in a new edition of BS 5682:1998.
surface should be clearly marked with suitable legend
denoting medical equipment is installed within.

Figure 2 Terminal unit mounting heights PENDANTS


(For rigid units, distance
is measured in fully
retracted position)

400 mm
TU separation
135 mm ± 2.5 mm
between centres,
Terminal unit mounting for 3 or more TUs
height range
900–1600 mm
above FFL
700 mm TU centreline
(Recommended range
900–1400 mm 200 mm (min)
above FFL) from side walls

TU separation
150 mm ± 2.5 mm
between centres,
for 2 TUs only
900 mm

FINISHED FLOOR LEVEL

12
3 Provision of terminal units, and the location of AVSUs, local alarm indicator panels and LVAs

Nitrogen for surgical tools


Note
3.18 BS EN 739:1998 gives details of connectors for
nitrogen for driving tools. The body of the NIST The minimum height of 1 m is the optimum. In
connector should form the wall outlet. critical care areas where dual circuits are installed, it
may be necessary to reduce this to 800 mm to avoid an
excessive number of columns of AVSUs.
AVSUs
3.19 AVSUs should be mounted at a convenient height
between 1 m and 1.8 m such that they can be Local alarm indicator panels
operated comfortably by staff without their needing
3.20 The placing of local alarm indicators should be
to stoop or overreach (see Figure 3). The order of
such that they are readily visible by staff; notices,
the location of individual valves in an array should
partitioning, screens etc should not obscure them.
follow that for terminal units, for example: O2,
The mounting height should be such that in the
N2O and/or N2O/O2, MA, SA, VAC, He/O2.
event of an audible alarm sounding, staff can
If the array exceeds 1 m in height from top to
activate the “mute” switch without overreaching,
bottom, it may be preferable to arrange them in
and be a maximum 1.8 m above finished floor level
two columns. Care must be taken to ensure that
(see Figure 3).
AVSUs cannot be obscured by opening doors etc.
Details of the design of AVSUs are given in
Chapter 13. LVAs
3.21 LVAs should be installed at branches from risers,
branches from main runs, and where pipelines pass
into or out of a building. Details of the design of
LVAs are given in Chapter 13.

Figure 3 AVSU and local alarm panel mounting heights


AVSU
ALARM

PANEL

800 mm

Mounting height
range for AVSUs Mounting height 1800 mm
1000–1800 mm range for local alarm
(1000 mm is the panel
optimum height: 1000–1800 mm
when multi-circuits
are installed, it may 1000 mm Recommended
be necessary to (800 mm) location –
reduce this to Nurse base
800 mm to avoid
too many columns)

Mounting order as for


vertical TU array

FINISHED FLOOR LEVEL

13
Medical gases – HTM 02-01 Medical gas pipeline systems – Part A: Design, installation, validation and verification

Specific labelling requirements


3.22 All AVSUs should be labelled to identify the
individual rooms, sets of terminal units etc
controlled. They should be provided with flow
direction arrows.
3.23 In critical care areas where dual circuits and/or
subdivision of circuitry occur, terminal units
require to be identified as associated with the
specific AVSU. Correspondingly, AVSUs should be
similarly labelled to identify the terminal units
controlled.

14
Table 11 Provision of terminal units, AVSUs and local alarms
Department O2 N2O N2O/O2 MA4 SA7 VAC AGSS He/O2 AVSU Alarm
Accident and Emergency 1 set (1) 1 set hp/lp (9)
Resuscitation room, per trolley space 2 2 – 2 – 2 2 – 2 sets*
Note: One set either side of the trolley space, if installed in
fixed location, eg trunking; or both sets in an articulated supply
pendant that can be positioned either side of the bed space.

3 Provision of terminal units, and the location of AVSUs, local alarm indicator panels and LVAs
Major treatment/plaster room per trolley space 1 1 1p 1 1p 1 1 – 1 set/8 TUs
Post-anaesthesia recovery per trolley space 2 – – 2 – 2 – – 2 sets*
Note: One set either side of the trolley space, if installed in
fixed location, eg trunking; or both sets in an articulated supply
pendant that can be positioned either side of the bed space.
Treatment room/cubicle 1 – – – – 1 – – 1 set/8 TUs
Operating department 1 set (1)
Anaesthetic rooms (all) 1 1 – 1 – 1 1 –
Operating room, orthopaedic:
For anaesthetist 2 1 – 2 – 2 1 – 1 set per suite 1 set per suite
(2)(3) hp/lp (10)
For surgeon – – – – 4 2 – – –

Note: Orthopaedic surgery is normally performed in operating
rooms provided with ultra-clean systems. Such systems are much
more effective in terms of airflow when provided with partial
walls. These walls may be effectively used to include terminal
units that can be supplied by rigid pipework. Such installations
do not suffer from excessive pressure loss when surgical air is
required at high flows.
Operating room, neurosurgery
Anaesthetist 2 1 – 2 – 2 1 – 1 set per suite 1 set per suite
(2)(3) hp/lp (10)
Surgeon – – – – 2 2 – –
Note: If multi-purpose pendants are used, there may be some
loss of performance of surgical tools because of bore restrictions
and convolution of the flexible connecting assemblies at the
articulated joints.
15
16

Medical gases – HTM 02-01 Medical gas pipeline systems – Part A: Design, installation, validation and verification
Department O2 N2O N2O/O2 MA4 SA7 VAC AGSS He/O2 AVSU Alarm
Operating room, general surgery etc
Anaesthetist/surgeon (see (14) regarding CO2) 2 2 – 2 2p 2 2 – 1 set per suite 1 set per suite
(2)(3) hp/lp (10)
Note: Terminal units installed in separate pendants: p = project
team option where some orthopaedic overspill surgery may be
performed.
Post-anaesthesia recovery, per bed space 2 – – 2 – 2 – – 2 sets* (5) 1 alarm for both
sets of AVSUs (11)
Note: One set either side of the bed space, if installed in fixed
location, eg trunking; or both sets in an articulated supply
pendant that can be positioned either side of the bed space.
Equipment service room per work space 1 1 – 1 1 1 1 – 1 set 1 set hp/lp (12)
Maternity department 1 set (1) 1 set (9)
LDRP room (normal/abnormal) 1 set per 6–8
rooms (5)
Mother 1 – 1 – – 2 – –
Baby (per cot space) (allow for 2 cots only) 1 – – 1 – 1 – –
Operating suite:
Anaesthetist 1 1 – 1 – 1 1 – 1 set 1 set hp/lp (10)
Obstetrician – – – – – 2 – –
Paediatrician (per cot space) (allow for 2 cots only) 1 – – 1 – 1 – –
Post-anaesthesia recovery (per bed space) 1 – – 1 – 1 – – 1 set 1 set (11)
Equipment service room** per work space 1 1 1 1 – 1 1 – 1 set 1 set (12)
Neonatal unit, per cot space 2 – – 2 – 2 – – 2 sets* 1 for both sets of
AVSUs (11)
Note: One set either side of the bed space, if installed in fixed
location, eg trunking; or both sets in an articulated supply
pendant that can be positioned either side of the bed space.
Equipment service room** per work space 1 – – 1 – 1 – – 1 set 1 set (12)
In-patient accommodation:
Single bed room 1 – – – – 1 – – 1 set for ward 1 set (11)
unit
Multi-room, per bed space 1 – – – – 1 – –
Nursery, per cot space 1 – – – – 1 – –
Provision for 2 cots only irrespective of number of cot spaces
Department O2 N2O N2O/O2 MA4 SA7 VAC AGSS He/O2 AVSU Alarm
Diagnostics departments 1 set (1) 1 set (9)

Special procedures room 1 1 – 1 – 1 1 – 1 set 1 set (10)


Anaesthetic room 1 1 – 1 – 1 1 – 1 set
Holding and recovery 1 – – 1p – 1 – – 1 set
Ultrasound 1 – – – – 1 – – 1 set
Fluoroscopy 1 – – – – 1 – – 1 set

3 Provision of terminal units, and the location of AVSUs, local alarm indicator panels and LVAs
Urography 1 – – – – 1 – – 1 set
Tomography 1 – – – – 1 – – 1 set
Magnetic resonance imaging (MRI) suite 1 1 – 1 – 1 1 – 1 set 1 set (10)
CAT room 1 1 – 1 – 1 1 – 1 set 1 set (10)
Angiography 1 1 – 1 – 1 1 – 1 set 1 set (10)
Endoscopy 1 1 – 1 – 1 1 – 1 set 1 set (10)
Lineac bunkers 1 1 – 1 – 1 1 – 1 set 1 set (10)
General purpose rooms 1 – – – – 1 – –
In-patient accommodation 1 set for the
ward unit (1)
Single-bed room 1 – – 1 – 1 – – 1 set (11)
1 – – 1 – 1 – –
Multi-bed room, per bed space 1 – – 1 – 1 – –
Treatment room
(Appropriate for adult acute, children and the elderly) 1 – – 1 – 1 – –
Renal
Per dialysis station 1 – – 1 – 1 – –
Per bed space 1 – – 1 – 1 – –
Critical care area 1 set (1) 1 set (11)
Per bed space 4 2p 2p 4 4 2p 2p 2 sets* (4)
Note: One set either side of the bed space, if installed in fixed
location, eg trunking; or both sets in an articulated supply
pendant that can be positioned either side of the bed space.
Equipment service room, per work space 1 1p 1p 1 1 1p 1 set 1 set (12)
Coronary care unit (CCU)
Per bed space 4 4 4 2 sets* (4)(6)(7) 1 for both sets of
17

AVSUs (11)
18

Medical gases – HTM 02-01 Medical gas pipeline systems – Part A: Design, installation, validation and verification
Department O2 N2O N2O/O2 MA4 SA7 VAC AGSS He/O2 AVSU Alarm
High dependency unit (HDU)
Per bed space 4 4 4 2 sets* (4)(6)(7) 1 for both sets of
AVSUs (11)
Burns unit 2 2p 2p 2 2 2p 2 sets* (4)(6)(7) 1 for both sets of
AVSUs (11)
Adult mental illness accommodation 1 set (1)
Electro-convulsive therapy (ECT) room 1 1 1 1 1 1 set (2) 1 set hp/lp (10)
Post-anaesthesia recovery, per bed space 1 1 1 1 set (1) 1 set (11)
Adult acute day care accommodation 1 set
Treatment room:
Anaesthetist 1 1p 1p 1 1p 1 set 1 set hp/lp
Surgeon 2 if (p) (10)
Post anaesthesia recovery, per bed space 1 1p 1 1 set 1 set (11)
Day patient accommodation 1 set (1)

Single bed room 1 1 1 set (1)(13) 1 set hp/lp (11)


Multi-bed room, per bed space 1 1
Treatment room 1 1p 1
Endoscopy room 1 1p 1p 1 1p 1 set (2)(13) 1 set (10)
Fracture clinic
Plaster room 1 1 1p 1p 1 1 1 set (1) 1 set (9)
Oral surgery, orthodontic department 1 set (1) 1 set hp/lp if (p)
(9)

Consulting/treatment room, type 1 1 1p 1 Dental † 1p 1 set/4–6 rooms


air
Consulting/treatment room, types 2 and 3 1 1 † 1 set/4–6 rooms
will be
required
Recovery room, per recovery position 1 1 1 1 set
Appliance laboratory, per workstation 1 1p 1 1 1 1p 1 set 1 set hp/lp (11)
Out-patient department
Treatment room/cubicles 1 1p 1p 1 1p 1 set (1)(8) 1 set hp/lp if (p)
(9)
Sterile services department
Wash room 1 1
Inspection, assembly and packing (IAP) room 1 1 1 1 1 set (1) 1 set (9)
Other departments (as required by project team) 1 set (1) 1 set located (9–12)
as appropriate
Notes: (8) Additional AVSUs may be required in a large unit: the aim should be to have about
8–12 rooms controlled by a set of valves – discretion is required to arrive at the
* Dual circuits.

3 Provision of terminal units, and the location of AVSUs, local alarm indicator panels and LVAs
logical number.
** Where the delivery and neonatal units are in close proximity, the equipment service
(9) Installed in reception area.
room can be shared.
(10) Installed in the operating room in the “main panel” or within the room, or an
† Dental vacuum only.
ante-room, eg control room of an MRI device.
p = Project team option.
(11) Installed at the main staff base (nurses’ station).
hp/lp = high-pressure and low-pressure alarms for oxygen, medical air and nitrous oxide
(12) Installed in the room space with the AVSUs.
when installed together. All other local alarms, low pressure only.
(13) Separate AVSUs will be required if endoscopy room is included.
(1) Departmental AVSUs installed on the hospital street side of fire compartment
doors. (14) Carbon dioxide is used for insufflation during some surgical procedures. A
pipeline installation is a project team option and is covered in Chapter 11. Two
(2) Installed immediately outside the room.
NIST connector bodies units should be installed.
(3) Where air is used to control movable pendant fittings, it should be taken from the
General:
7 bar surgical air system.
Normally, departmental AVSUs would be installed at the hospital street side of the
(4) In addition to the dual circuits, additional AVSUs will be required to sub-divide the
entrance doors to a department and would reflect the method of horizontal evacuation
number of terminal units controlled. This subdivision should be based on the layout
in the event of an emergency. In some large departments, for example an operating
of the accommodation; for example, if the recovery area is divided into a number of
department, the clean-service corridor is likely to cross one or more fire compartment
separate room/areas, each would have a separate sub-set (see Figures 4 and 5).
walls. Additional AVSUs may therefore be required to reflect the evacuation route.
(5) This is intended to provide some flexibility and the exact number will depend on
If a department includes one or more floors, a set of AVSUs should be provided for
the total number of rooms within the department.
each floor, which will act as emergency overall fire valves.
(6) If a high-dependency unit is included within general in-patient accommodation,
AVSUs for zones within critical care areas should be located where they can be seen by
a separate set of AVSUs should be provided for the unit. In addition to the
staff – not necessarily at the staff base.
departmental valves or the ward as a whole, an additional set will be required to
control the single-bed, multi-bed and treatment rooms. Local alarms within critical care areas should be provided for the individual space; that
is, if a critical care area of, say, 18 beds is sub-divided into three separate six-bed wards,
(7) Department AVSUs may be required if the units are large and separate from, for
there should be one alarm only for each space (not one for each of the dual circuits).
example, the critical care area.
19
Medical gases – HTM 02-01 Medical gas pipeline systems – Part A: Design, installation, validation and verification

Figure 4 Larger critical care area with isolation room and twin four-bed bays

Terminal
units
Bed 1 Bed 2 Bed 3 Bed 4

4 Bed Bay 1

AVSU

AVSU

Pressure
switch

AVSU AVSU

4 Bed Bay 2
Isolation Unit

Bed 9 Bed 8 Bed 7 Bed 6 Bed 5

20
3 Provision of terminal units, and the location of AVSUs, local alarm indicator panels and LVAs

Figure 5 Smaller critical care area with isolation room and five-bed bay

Terminal
units
Bed 1 Bed 2 Bed 3

Pressure
AVSU switch
location (b)

5 Bed Bay
Pressure
switch (a)

Isolation Unit

Bed 6 Bed 5 Bed 4

Note:
Pressure switch location is decided as follows:

(a) upstream of unit AVSUs assumes a departmental AVSU is upstream of


pressure switch;
(b) downstream of unit AVSUs will require two pressure switches connected
in parallel, one for each circuit.

21
Medical gases – HTM 02-01 Medical gas pipeline systems – Part A: Design, installation, validation and verification

4 Gas flow

General 4.5 There is a limited range of pipe sizes, and where


there is any doubt about flow requirements, a larger
4.1 Various layouts of an MGPS are shown throughout pipe size should be selected.
this document, and each will need to be designed
to take into account the anticipated design flow. Note
Appendix N provides a conversion table for various
units of measurement that may be encountered. When calculating diversified flows, it is the number
of bed spaces, treatment spaces or rooms in which the
4.2 There are several aspects of gas flow to consider
clinical procedure is being performed that is used; this
when designing the pipeline distribution system: is not the individual number of terminal units since, in
a. the test flow that is required at each terminal many cases, more than one is installed. For example, a
unit for test purposes (this flow is essentially bed position in a critical care area may have four or
to establish that the terminal unit functions more oxygen terminal units.
correctly and that there are no obstructions; see
Table 12); 4.6 The overall pipeline design should be based on a
5% pressure drop from the plant/source of supply
b. the typical flow required at each terminal (this is
to that measured at the terminal unit outlet at the
the maximum flow likely to be required at any
specified test flows.
time in clinical use; see Table 12);
c. the likely numbers of terminal units in use at Terminal unit flows
any time;
4.7 At the design stage, the project team should
d. the flow required in each sub-branch of the define the individual room/space requirements.
distribution, for example from the terminal unit Departments usually comprise several ward units,
or a number of terminal units (for example four treatment rooms and other spaces. In order to
in a four-bed ward) to the pipeline in the false avoid confusion, the nomenclature for each clinical
ceiling of the ward corridor; space should be clearly defined so that the
e. the total flow to the ward/department, that is, appropriate gas flow requirements can be
the sum of the diversified flows in each sub- established at the commencement of the design
branch; stage.

f. the flow in the main branches/risers, that is, the


Pipeline flows
summation of all diversified flows;
4.8 Precise prediction of pipeline flow is not possible,
g. the flow required at the plant. In most cases this
but there are guidelines that can be used. and these
will be the flow in (f ) above except in the case of
have been shown to be adequate in practice.
vacuum that is not used continuously.
4.9 For vacuum systems, the minimum vacuum should
4.3 The pipeline system should be designed so that the
not fall below 300 mm Hg at the front of each
flows given in Table 12 can be achieved at each
terminal unit at a design flow of 40 L/min.
terminal unit: the flows are expressed in free air.
Diversified flows are used for the purposes of pipe 4.10 The design of the pipework system is based on the
size selection. diversified flows and the permissible pressure loss
from the source of supply to, and including, the
4.4 The designer should always ensure that due
terminal unit pressure loss. The pipe sizes should be
account is taken of the stated use of a particular
selected to ensure that the pressure loss is below 5%
department.

22 22
4 Gas flow

Table 12 Gas flow – flows required at terminal units

Service Location Nominal Design flow Typical flow Test flow


pressure (L/min) required (L/min)
(kPa) (L/min)
Oxygen Operating rooms and rooms in which N2O is 400 100(1) 20 100
provided for anaesthetic purposes
All other areas 400 10 6 40
Nitrous oxide All areas 400 15 6 40
Nitrous oxide/ LDRP (labour, delivery, recovery, post-partum) 310(2) 275 20 275
oxygen mixture rooms
All other areas 400 20 15 40
Medical air Operating rooms 400 40(3) 40 80
400 kPa
Critical care areas, neonatal, high dependency units 400 80(3) 80 80
Other areas 400 20 10(3) 80
Surgical air/ Orthopaedic and neurosurgical operating rooms 700 350(4) 350 350
nitrogen
Vacuum All areas 40 (300 mm 40 40 40
Hg below maximum,
atmospheric further
pressure) diversities
apply
Helium/oxygen Critical care areas 400 100 40 80
mixture
Notes:
1. During oxygen flush in operating and anaesthetic rooms.
2. Minimum pressure at 275 L/min.
3. These flows are for certain types of gas-driven ventilator under specific operating conditions, and nebulisers etc.
4. Surgical air is also used as a power source for tourniquets.

Figure 6 T
 ypical pressures in medical air/oxygen/nitrous oxide/nitrous oxide-oxygen mixture systems
under design flow conditions
Local alarm pressure switch
setting 360 kPa

5% allowable pressure drop to front


Plant/manifold outlet pressure (dynamic) 420 kPa of most remote terminal unit
Pressure safety valve setting 530 kPa Minimum pressure to be achieved at
front of most remote terminal unit
Pressure switch settings (alarms) 370 kPa with system at design flow
HIGH 500 kPa (including test instrument flow at
LOW 370 kPa terminal unit)

23
Medical gases – HTM 02-01 Medical gas pipeline systems – Part A: Design, installation, validation and verification

Figure 7 Typical pressures in a vacuum system under design flow conditions


Local alarm pressure switch
setting 37 kPa (275 mm Hg)

Plant outlet pressure (dynamic) Minimum pressure to be achieved at front of


60 kPa (450 mm Hg) most remote terminal unit
40 kPa (300 mm Hg) with system at design
flow (including test instrument flow of
Pressure switch setting (Plant alarm) 40 l/min at terminal unit)
LOW 48 kPa (360 mm Hg)

Figure 8 T
 ypical pressures in a single pressure reduction surgical air system under design flow
conditions
Local alarm pressure switch
setting 650 kPa

Plant outlet pressure (dynamic) 850 kPa Maximum static pressure 950 kPa

Pressure safety valve setting 1100 kPa


Minimum pressure to be achieved at front of
Pressure switch settings (alarms) most remote terminal unit
HIGH 1050 kPa 700 kPa with system at design flow (including
LOW 650 kPa test instrument flow of 350 l/min at terminal unit)

Figure 9 T
 ypical pressures in a double pressure reduction surgical air system under design flow
conditions
Local alarm pressure switch
setting 650 kPa

Plant outlet pressure (dynamic) 1100 kPa 5% allowable pressure drop


(Primary regulator) to input of secondary
pressure regulator Minimum pressure to be achieved
Pressure safety valve setting 1300 kPa at front of most remote
NB. Maximum static pressure terminal unit
Pressure switch settings (alarms) from this regulator 900 kPa 700 kPa with system at design
HIGH 1200 kPa flow (including test instrument
LOW 900 kPa flow of 350 l/min at terminal unit)

24
4 Gas flow

of the nominal pipeline pressure (see Figures 6–9, operating room and anaesthetic room should be
and Appendix G). able to pass 100 L/min. It is unlikely that an
oxygen flush will be administered simultaneously in
4.11 Pressure requirements for surgical air are based on
several operating rooms. The diversified flow Q is
the requirement that the minimum pressure should
based on 100 L/min for the first operating room
be 700 kPa at the terminal unit at a flow of 350 L/
and 10 L/min for the remainder. To obtain the
min.
flow to each operating suite, add together the flows
4.12 Details of pressure requirements for all systems are for the operating and anaesthetic room, that is,
described in paragraphs 4.43–4.50. 110 L/min.
4.19 For anaesthetic rooms, each terminal unit should
Oxygen be capable of passing 100 L/min (it may be
necessary to use oxygen “flush”), but the actual flow
In-patient accommodation
likely to be used is 6 L/min or less. As it is unlikely
4.13 Oxygen is used at a typical flow of 5–6 L/min. that a patient would be anaesthetised at the same
Each terminal unit should, however, be capable of time that a patient in the associated operating room
passing 10 L/min (at standard temperature and was continuing to be treated under an anaesthetic
pressure (STP)) at a supply pressure of 400 kPa (and because the duration of induction is short),
(nominal) as shown in Table 12, in case nebulisers no additional flow is included.
or other respiratory equipment are used. Table 13
4.20 In recovery, it is possible that all bed spaces may be
contains the formula for arriving at diversified
in use simultaneously; hence, no diversity is used.
flows.
4.14 For a 28-bed ward unit comprising single and four- Critical care, coronary care and high-dependency
bed rooms and a treatment room, the diversified units
flow is calculated on the assumption that one bed 4.21 The flow for these units assumes that, although all
space requires 10 L/min, and one in four of the bed spaces may be occupied, three-quarters of these
remainder require 6 L/min. For the purpose of pipe will require the use of oxygen. Each terminal unit
size selection, the diversified flow at entry to the should be capable of delivering 10 L/min. The
ward is taken as 50 L/min (strictly 50.5 L/min); it diversified flow is calculated assuming 10 L/min for
is assumed that a patient will use oxygen in a ward the first bed space and 6 L/min for three-quarters
or in the treatment room but not both. of the remainder.
4.15 When selecting the size of a sub-branch serving, for
4.22 Oxygen should not be used as the driving gas for
example, a four-bed ward, the flow would be taken gas-powered ventilators if they are capable of being
to be 28 L/min as all four in-patients could be powered by medical air. The minimum flow that
using oxygen; for larger wards no additional flow is has been shown to be adequate to drive current
added until the formula in Table 13 comes into types of ventilator is 80 L/min at 360 kPa. For test
play. purposes the minimum pressure is 370 kPa.
4.16 A department may comprise several ward units as 4.23 If oxygen has to be used to power ventilators and/
above. The diversified flow for each department Qd or ventilators are operating in CPAP mode, the
is based on Qw for the first ward unit, plus 50% of high flows that may be encountered should be
the flow for the remaining ward units. For the taken into account both when designing the
purposes of this calculation, the first ward unit is pipeline and when sizing the supply vessel. These
taken as the largest within the department. ventilators use exceptional amounts of oxygen,
4.17 If one ward unit is significantly larger than the particularly if adjusted incorrectly. If incorrectly
others, the flows from the ward units should be set, they can use in excess of 120 L/min, but their
averaged to obtain a more realistic value. therapeutic benefit will be effective at lower flows.
To allow for some flexibility, and additional
Operating departments capacity, a diversified flow of 75 L/min for 75% of
beds has been included. If significant numbers of
4.18 The diversified flow for operating departments
beds are required to treat patients using CPAP
is based on 100 L/min required for the oxygen
ventilation, consideration should be given to
flush. Therefore each oxygen terminal unit in the
running a separate pipeline from the source of

25
Medical gases – HTM 02-01 Medical gas pipeline systems – Part A: Design, installation, validation and verification

Table 13 Oxygen: design and diversified flows


Department Design flow Diversified flow Q (L/min)
for each
terminal unit
(L/min)
In-patient accommodation (ward units):
Single 4-bed rooms and treatment room 10 Qw = 10 + [(n – 1)6/4]
Ward block/department 10 Qd = Qw[1 + (nW – 1)/2]
Accident & emergency:
Resuscitation room, per trolley space 100 Q = 100 + [(n – 1)6/4]
Major treatment/plaster room, per trolley space 10 Q = 10 + [(n – 1)6/4]
Post-anaesthesia recovery, per trolley space 10 Q = 10 + [(n – 1)6/8]
Treatment room/cubicle 10 Q = 10 + [(n – 1)6/10]
Operating:
Anaesthetic rooms 100 Q = no addition made
Operating rooms 100 Q = 100 + (nT – 1)10
Post-anaesthesia recovery Q = 10 + (n – 1)6
Maternity:
LDRP rooms:
Mother 10 Q = 10 + [(n – 1)6/4]
Baby 10 Q = 10 + [(n – 1)3/2]
Operating suites:
Anaesthetist 100 Q = 100 + (nS – 1)6
Paediatrician 10 Q = 10 + (n – 1)3
Post-anaesthesia recovery 10 Q = 10 + [(n – 1)3/4]
In-patient accommodation:
Single/multi-bed wards 10 Q = 10 + [(n – 1)6/6]
Nursery, per cot space 10 Q = 10 + [(n – 1)3/2]
Special care baby unit 10 Q = 10 + (n – 1)6
Radiological: 100 Q = 10 + [(n – 1)6/3]
All anaesthetic and procedures rooms
Critical care areas 10 Q = 10 + [(n – 1)6]3/4
Coronary care unit (CCU) 10 Q = 10 + [(n – 1)6]3/4
High-dependency unit (HDU) 10 Q = 10 + [(n – 1)6]3/4
Renal 10 Q = 10 + [(n – 1)6/4]
CPAP ventilation 75 Q = 75n × 75%
Adult mental illness accommodation:
Electro-convulsive therapy (ECT) room 10 Q = 10 + [(n – 1)6/4]
Post-anaesthesia, per bed space 10 Q = 10 + [(n – 1)6/4]
Adult acute day care accommodation:
Treatment rooms 10 Q = 10 + [(n – 1)6/4]
Post-anaesthesia recovery per bed space 10 Q = 10 + [(n – 1)6/4]
Day patient accommodation (as “In-patient accommodation”) As “In-patient accommodation”
Oral surgery/orthodontic:
Consulting rooms, type 1 10 Q = 10 + [(n – 1)6/2]
Consulting rooms, types 2 & 3 10 Q = 10 + [(n – 1)6/3]
Recovery room, per bed space 10 Q = 10 + [(n – 1)6/6]
Out-patient:
Treatment rooms 10 Q = 10 + [(n – 1)6/4]
Equipment service rooms, sterile services etc 100 Residual capacity will be adequate
without an additional allowance

26
4 Gas flow

Legend for Tables 13–21:


Q = diversified flow for the department;
Qw = diversified flow for the ward;
Qd = diversified flow for the department (comprising two or more wards);
n = number of beds, treatment spaces or single rooms in which the clinical procedure is being performed, not the individual
numbers of terminal units where, in some cases, more than one is installed;
nS = number of operating suites within the department (anaesthetic room and operating room).
nW = number of wards
nT = number of theatres

supply. Care should be taken when calculating air 4.25 In the event of multiple births, the additional gas
exchange rates in wards/rooms in which large usage will have negligible overall effect on the total
numbers of CPAP machines may be in use flow.
simultaneously and where failure of mechanical
4.26 Maternity department operating rooms are
ventilation could result in raised ambient oxygen
designed as a suite; that is, it is presumed that
concentrations. Consideration should be given to
oxygen will be provided either in the anaesthetic
installation of systems to warn of ventilation failure
room or in the operating room. In post-anaesthesia
and oxygen concentrations above 23%.
recovery, it is assumed that 75% of beds will
require oxygen to be delivered.
Maternity
4.24 For LDRP (labour, delivery, recovery, post-partum) Hyperbaric oxygen chambers
rooms, the diversified flow is based on 10 L/min
for the first terminal unit and 6 L/min for 25% of 4.27 Hyperbaric oxygen chambers should be supplied
the remainder. Two cot spaces may be provided, from a separate branch from the main riser/
each with a terminal unit. Only one will be distribution pipe: the pipeline system should be
considered to be in use. The diversified flow for cot from a liquid supply source. Typical flows for a
spaces is based on 10 L/min for the first and 50% single patient chamber are as shown in Table 14.
of the remainder at 3 L/min.

Table 14 Gas flow – hyperbaric chambers


Max. time for one complete Total consumption for max. Consumption for each
treatment treatment time (L) additional minute (L/min)
O2 atmosphere and
recirculation:
On open circuit 2 hours 30,000 250
On recirculation 2 hours 7,250 40
O2 only, no recirculation 2 hours 30,000 250
O2 delivery by built-in
breathing mask and overboard 2 hours 1,200 10
pump
O2 delivery by built-in
breathing hood and overboard 2 hours 7,250 60
pump

27
Medical gases – HTM 02-01 Medical gas pipeline systems – Part A: Design, installation, validation and verification

operating rooms. As it is unlikely that a patient


Notes would be anaesthetised in the anaesthetic room
a. T
 he flows for a recirculating unit assume the at the same time that a patient in the associated
standard method of operation is recirculation operating room was continuing to be treated
throughout the treatment. It is recommended that under an anaesthetic (and because the duration of
the pipeline should be designed for open circuit induction is short), no additional flow is included.
operation to ensure adequate flow under all
conditions. Nitrous oxide/oxygen mixture
b. C
 linical practice may require the inclusion of air 4.31 All terminal units should be capable of passing
during the treatment; it may also be necessary to 275 L/min for a very short period (normally of five
switch to air in the unlikely event of an oxygen seconds’ duration) to supply inhalationary “gasps”
convulsion. Therefore consideration should be by the patient, and a continuous flow of 20 L/min.
given to the provision of medical air from a separate The actual flow would not normally exceed 20 L/
dedicated medical air plant in accordance with min.
Chapter 7.
4.32 The diversified flow in delivery rooms is based on
c. S ome hyperbaric chambers use air as a buffer and 275 L/min for the first bed space and 6 L/min for
consequently less oxygen is consumed. The advice each of the remainder, of which only half of the
of the manufacturer should be sought. Where this is women in labour will be using gas for 50% of the
the case, the air should be supplied from a separate time. (The peak inhalationary “gasp” is 275 L/min,
supply system complying with the requirements for whereas the respirable minute volume will be
medical air systems. catered for with a flow of 6 L/min – it should also
be borne in mind that a woman in labour would
Nitrous oxide not continuously breathe the analgesic mixture.)
For larger maternity departments with twelve or
4.28 Nitrous oxide is provided for anaesthetic purposes
more LDRP rooms, two peak inhalationary “gasps”
and occasionally for analgesic purposes. In all cases,
are included.
each terminal unit should be capable of passing
15 L/min, but in practice the flow is unlikely to 4.33 Nitrous oxide/oxygen mixture may be used in other
exceed 6 L/min. areas for analgesic purposes. The diversified flow is
based on 10 L/min for the first treatment space,
4.29 When calculating diversities in a department, 15 L/
and 6 L/min for a quarter of the remainder for
min is allowed for the first and 6 L/min for the
25% of the time.
remainder, subject to the appropriate diversity
factor being applied (see Table 15). 4.34 Design and diversified flows for nitrous oxide/
oxygen mixtures are given in Table 16.
4.30 It is assumed that, for an operating department,
nitrous oxide may be in use simultaneously in all

Table 15 Nitrous oxide: design and diversified flows


Department Design flow for Diversified flow Q (L/min)
each terminal unit
(L/min)
Accident & emergency: resuscitation room, per trolley space 10 Q = 10 + [(n – 1)6/4]
Operating 15 Q = 15 + (nT – 1)6
Maternity: operating suites 15 Q = 15 + (nS – 1)6
Radiological: all anaesthetic and procedures rooms 15 Q = 10 + [(n – 1)6/4]
Critical care areas 15 Q = 10 + [(n – 1)6/4]
Oral surgery/orthodontic: consulting rooms, type 1 10 Q = 10 + [(n – 1)6/4]
Other departments 10 No additional flow included
Equipment service rooms 15 No additional flow included

28
4 Gas flow

Table 16 Nitrous oxide/oxygen mixtures – design and diversified flows


Department Design flow for each terminal unit Diversified flow Q (L/min)
(L/min)
Maternity:
<12 LDRP room(s), mother 275 Q = 275 + [(n – 1)6/2]
>12 LDRP rooms Q = 275 x 2 + [(n – 1)6/2]
Other areas 20 Q = 20 + [(n – 1)10/4]
Equipment service rooms 275 No additional flow included

Air during critical care. Pneumatically-powered


ventilators can use up to 80 L/min free air
4.35 Air is used to provide power for several types of continuously. The exact flow requirements will
equipment including surgical tools, ventilators and depend on the design of the ventilator. The flow
nebulisers. Oxygen should be avoided as a power and pressure requirements for some typical
source because of fire risk and cost, and should not ventilators are given in Table 17.
be used where medical air is available, unless
specifically recommended by the device 4.41 Current models of anaesthetic ventilator are very
manufacturer. similar to critical care models, and may require
peak flows of up to 80 L/min and average flows of
4.36 Air should be provided at two different pressures 20 L/min. Almost all such units are pneumatically
but to the same Ph. Eur. standard: driven and electronically controlled.
a. a pressure of 400 kPa is required for medical air 4.42 Medical air 400 kPa is also used for other
to drive ventilators and for other respiratory equipment such as anaesthetic gas mixers,
applications; humidifiers and nebulisers. The flow rates normally
b. a pressure of 700 kPa or higher is required for required would not exceed 10 L/min, and this flow
surgical air to drive surgical tools. is always in excess of the actual volume respired.

Medical air 400 kPa Pressure requirements


4.43 A minimum pressure required at terminal units for
General respiratory use is 370 kPa.
4.37 The use of medical air, particularly for respiratory
4.44 Medical air should not be used to supply
use and during anaesthesia, has increased markedly mechanical services (see paragraph 7.130).
in recent years. This service is the most critical of
the medical gas services, since air-powered 4.45 Some medical gas pendants use the medical air
ventilators cease to operate in the event of failure of supply for operating the control/retraction system.
the supply. This is permitted, provided that:
4.38 Medical air is also directly inhaled by patients a. a flow limiting device is provided to protect the
during ventilation. It may also be used to dilute medical air system in the event of failure of any
oxygen before administration because of the downstream component;
potentially toxic effects of pure oxygen. b. a non-return valve is incorporated to protect the
4.39 The supply system for medical air 400 kPa may system integrity;
be a manifold system, a compressor system or a c. appropriate AVSU arrangements are in place
proportioning system (synthetic air), and includes (see Chapter 3).
an emergency reserve manifold. A compressor
plant, or synthetic air supply, should always be (The surgical air supply should be used to provide
specified where air-powered ventilators are to be the power source whenever possible.)
used. 4.46 The flow requirements should be ascertained and
4.40 One of the major uses of medical air is for patients’ taken into account prior to the installation of the
ventilators, which fall into two main categories – equipment.
those used during anaesthesia and those used

29
Medical gases – HTM 02-01 Medical gas pipeline systems – Part A: Design, installation, validation and verification

Flow requirements In these areas they should be capable of passing


20 L/min, although typically 10 L/min will be
4.47 Flow requirements for medical air are given
required in in-patient accommodation where air is
Table 18. In ward areas and treatment rooms, the
used for nebulisers.
use of medical air is most likely to be for nebulisers.

Table 17 Typical pressure and flow requirements for ventilators and nebulisers
Ventilator type Pressure (kPa) Flow (L/min)
Anaesthesia, typically gas-driven, Nominally 400. Max 600(1) Pneumatically driven ventilators use up to 80 max.
electronically controlled 20 continuous
Critical care, electrically controlled, Nominally 400. Max 600(1) 180 peak(2)
gas-powered 80 continuous
Neonatal, gas-driven, electronically Nominally 400. Max 600(1) 80 peak(2)
controlled 40 continuous
Nebulisers 400 10
Notes:
1. It is strongly recommended that ventilators are not connected to the 700 kPa system since their blenders only work satisfactorily
with a tolerance of about 10%: with high differential pressures for air and oxygen an incorrect mixture could be obtained.
2. These flows can be achieved under certain clinical conditions. The peak flows are usually of very short duration.

30
4 Gas flow

Table 18 Medical air 400 kPa – design and diversified flows


Department Design flow for Diversified flow Q (L/min)
each terminal
unit (L/min)
In-patient accommodation (ward units):
Single/multi-bed and treatment rooms(1) 20 Qw = 20 + [(n – 1)10/4]
Ward block/department 20 Qd = Qw[1 + (nW – 1)/2]
Accident & emergency:
Resuscitation room, per trolley space 40 Q = 40 + [(n – 1)20/4]
Major treatment/plaster room, per trolley space 40 Q = 40 + [(n – 1)20/4]
Post-anaesthesia recovery, per trolley space 40 Q = 40 + [(n – 1)40/4]
Operating:
Anaesthetic rooms 40 No additional flow included
Operating rooms 40 Q = 40 + [(nT – 1)40/4]
Post-anaesthesia recovery 40 Q = 40 + [(n – 1)10/4]
Maternity:
LDRP rooms: 40 Q = 40 + [(n – 1)40/4]
Baby(2) 40 Q = 40 + [(n – 1)40/4]
Operating suites:
Anaesthetist 40 Q = 40 + [(nS – 1)10/4]
Post-anaesthesia recovery 40 Q = 40 + [(n – 1)40/4]
Neonatal unit (SCBU) 40 Q = 40n
Radiological:
All anaesthetic and procedures rooms 40 Q = 40 + [(n – 1)40/4]
Critical care areas(3) 80 Q = 80 + [(n – 1)80/2]
High-dependency units 80 Q = 80 + [(n – 1)80/2]
Renal 20 Q = 20 + [(n – 1)10/4]
Oral surgery/orthodontic:
Major dental/oral surgery rooms 40 Q = 40 + [(n – 1)40/2]
All other departments 40 No additional flow
allowance to be made
Equipment service rooms 40 No additional flow included
Notes:
1. It is assumed that a patient will use oxygen in a ward or in the treatment room.
2. Where two cot spaces have been provided in an LDRP room, assume only one will require medical air.
3. This diversified flow is also used for helium/oxygen mixture (see paragraph 4.73).

Surgical air 700 kPa possibility of using nitrogen as the power source for
surgical tools.
4.48 The pressure requirements of surgical tools are
between 600 and 700 kPa and flows may vary 4.50 The pipeline systems should be designed to provide
between 200 and 350 L/min (STP; see Table 19). a flow of 350 L/min at 700 kPa at the outlet from
Most surgical tools are designed to operate within the terminal unit. Existing systems may not meet
this pressure range. Higher pressures are likely this requirement (but should be capable of
to cause damage to tools. Inadequate tool delivering 250 L/min at the terminal unit).
performance, however, is likely to result from the
lack of flow at the specified pressure. Note
4.49 The introduction of synthetic air (from on-site Some surgical tools require up to 500 L/min at up to
blending of oxygen and nitrogen) leads to the 1400 kPa. These will require a separate supply,
normally from cylinders.

31
Medical gases – HTM 02-01 Medical gas pipeline systems – Part A: Design, installation, validation and verification

Dual pressure surgical air systems


4.51 There are cases where, because of system size, a
Note
simple single regulation system (that is, directly Health Technical Memorandum 2022, Supplement 1
from a receiver pressure of say, 10 bar, to a line – ‘Dental compresssed air and vacuum systems’
pressure of approximately 8 bar) will not ensure allows for the extension of surgical air into dental
correct flow conditions at the surgical air terminal departments for tool use only. No diversity factor
units. To overcome possible flow problems, a should be applied to the dental service as all dental
double pressure regulating system can be used. clinics can be in use simultaneously: the total design
flow of the dental department should be added.
4.52 Such a system will involve a compressed air plant
receiver operating at a typical pressure of 13 bar,
4.55 Unlike dental departments, the use of surgical tools
followed by first-stage pressure regulation to a line
in an operating procedure takes place for a limited
pressure of 11 bar. Locally-sited pressure regulators
period of time.
(for example for each operating room) are provided
to give the recommended flow and pressure at the
Table 19 T
 ypical pressure and flow requirements
terminal unit outlet(s).
for surgical tools
4.53 If this type of system is installed, for design
purposes the maximum allowable pressure drop of Type of tool Pressure (kPa) Flow (L/min)
5% should be taken from the plantroom wall to Small air drill 600–700 200
the upstream side of the secondary regulator. The Medullary reaming 600–700 350
secondary regulator should be adjusted to give machine
700 kPa at a flow of 350 L/min at the terminal unit Oscillating bone saw 600–700 300
outlets(s) and should not allow the static pressure Universal drill 600–700 300
on the upstream side of the terminal unit to rise
Craniotome 620–750 300
above 9 bar.
System capacity
Diversity
4.56 Unlike respirable equipment, surgical tools are used
4.54 Surgical air 700 kPa is only required where surgical
intermittently, typically for a few seconds, up to a
tools are to be used. This would typically be
maximum of three minutes. The plant, therefore,
orthopaedic and neurosurgery operating rooms,
should have the capacity to provide the design
and possibly plaster rooms. For flexibility, and to
flow of the pipeline for a maximum period of five
allow for possible overspill, surgical air should be
minutes in any 15-minute period. The diversified
extended to two to four adjacent operating rooms.
flow is based on the assumption of 350 L/min for
It is not required in maternity or ophthalmology
the first theatre and a quarter of the remainder –
operating rooms.
see Table 20.

Terminal units intended for equipment testing


4.57 It may be necessary to provide surgical air at
700 kPa in the equipment service workshop for
testing purposes. Unless a surgical air 700 kPa
pipeline is available nearby, it may be cost-effective

Table 20 Surgical air 700 kPa – design and diversified flows


Department Design flow for each Diversified flow Q
terminal unit (L/min)
(L/min)
Operating room (orthopaedic and neurosurgical operating rooms only):
<4 operating rooms 350 Q = 350 + [(n – 1)350/2]
>4 operating rooms 350 Q = 350 + [(n – 1)350/4]
Other departments, eg equipment workshops, fracture clinic 350 Q = 350
Equipment service rooms 350 No additional flow required

32
4 Gas flow

to use portable cylinders, with a two-stage Medical supply units/bedhead trunking systems
regulator.
4.66 When designing vacuum (and medical gas
4.58 If a pipeline supply is to be provided, each terminal systems), it is expected that the greatest pipeline
unit should be capable of delivering 350 L/min. pressure losses will occur near to the terminal units.
Where several terminal units are provided, it is
4.67 Care must be taken when sizing vacuum pipework
unlikely that more than one terminal unit will be in
within medical supply units with two or more bed/
use at any time, and therefore the total design flow
treatment spaces, where availability of space will
for the equipment service workshop will be 350 L/
often limit the size of pipe. The largest size of pipe
min.
that can be accommodated (typically 22 mm)
should be used, as this will ensure that excessive
Vacuum pressure losses do not occur within the units. Such
losses could necessitate the installation of larger
General diameter pipework within the rest of the system in
4.59 In virtually all cases, vacuum is used via a suction order to ensure that the system pressure drops
control device and fluid is collected in suction jars. prescribed in this Health Technical Memorandum
On wards these are typically of approximately 1 L are not exceeded.
capacity. In operating rooms, two or four 2–3 L 4.68 In some instances it may be necessary to provide
capacity vessels are provided for the suction control more than one “feed” from the ceiling distributor
regulator. to the medical supply unit in order to keep pressure
4.60 Once full, suction jars have to be emptied; losses within acceptable limits.
therefore, vacuum cannot be applied continuously.
Operating departments
4.61 The greatest generation of fluid to be aspirated is
likely to arise in the operating room, particularly 4.69 Vacuum is provided for the surgical team and
during orthopaedic surgery, where jet lavage to anaesthetist in the operating room. It is also
irrigate and cleanse the wound may be in use. The provided in the anaesthetic and recovery rooms.
maximum rate of collection is about 4 L/min, but 4.70 Since it is possible for both the surgical team and
it is not continuous. anaesthetist to use vacuum simultaneously, each
4.62 During induction of anaesthesia, a patient may operating room will require 80 L/min and each
vomit. Therefore, it is essential that oral and nasal terminal unit should be capable of passing 40 L/
passages can be cleared as quickly as possible. The min (see Table 21).
highest likely amount of fluid to be aspirated in 4.71 As it is unlikely that a patient would be
this case will be no more than 0.5 L. anaesthetised at the same time that a patient in the
4.63 In order to aspirate fluid, a suction cannula is associated operating room was continuing to be
normally used, and this will aspirate air as well treated under an anaesthetic, the need to clear an
as the fluid to be removed. The flow required, airway is extremely unlikely and no additional flow
however, is higher than would be the case if fluid is included.
only were to be removed. The ratio of air/fluid
aspirated will depend upon the diameter of the Helium/oxygen mixture
cannula.
4.72 Helium/oxygen mixture is used by patients with
respiratory or airway obstruction and to relieve
In-patient accommodation
symptoms and signs associated with respiratory
4.64 For a 28-bed ward unit comprising single rooms, distress. It can be administered by means of face
four-bed rooms and a treatment room, the mask, a demand valve with face mask, a nebuliser,
diversified flow is based on 40 L/min. or a ventilator.
4.65 When selecting the size of a sub-branch serving, for 4.73 Pipeline supply will be primarily limited to critical
example, a four-bed ward, the flow would be taken care areas, where the gas mixture is used for driving
to be 160 L/min as all four terminal units could, in a ventilator. The design and diversified flows should
theory, be in use. be based on the figures given for medical air (see
Table 17).

33
Medical gases – HTM 02-01 Medical gas pipeline systems – Part A: Design, installation, validation and verification

Table 21 Vacuum – design and diversified flows


Department Design flow Diversified flow Q (L/min)
for each
terminal unit
(L/min)
In-patient accommodation:
Ward unit 40 Q = 40
Multiple ward units 40 Qd = 40 + [(n – 1)40/4]
Accident & emergency:
Resuscitation room, per trolley space 40 Q = 40 + [(n – 1)40/4]
Major treatment/plaster room, per trolley space 40 Q = 40 + [(n – 1)40/4]
Post-anaesthesia recovery, per trolley space 40 Q = 40 + [(n – 1)40/4]
Treatment room/cubicle 40 Q = 40 + [(n – 1)40/8]
Operating:
Anaesthetic rooms 40 No additional flow included
Operating rooms:
Anaesthetist 40 Q = 40
Surgeon 40 Q = 40
Operating suites 40 Qs = 80 + [(nS – 1)80/2]
Post-anaesthesia recovery 40 Q = 40 + [(n – 1)40/4]
Maternity:
LDRP rooms:
Mother 40 Q = 40 + [(n – 1)40]/4
Baby 40 No additional flow included
Operating suites:
Anaesthetist 40 Q = 40
Obstetrician 40 Q = 40
Operating suites Qs = 80 + [(nS – 1)80/2]
Post-anaesthesia recovery 40 Q = 40 + [(n – 1)40/4]
In-patient accommodation:
Ward unit comprising single, multi-bed and treatment room 40 Q = 40
Multi-ward units 40 Q = 40 + [(n – 1)40/2]
Nursery, per cot space 40 No additional to be included
SCBU 40 Q = 40 + [(n – 1)40/4]
Radiology/diagnostic departments:
All anaesthetic and procedures rooms 40 Q = 40 + [(n – 1)40/8]
Critical care areas 40 Q = 40 + [(n – 1)40/4]
High-dependency units 40 Q = 40 + [(n – 1)40/4]
Renal 40 Qd = 40 + [(n – 1)40/4]
Adult mental illness accommodation:
ECT room 40 Q = 40 + [(n – 1)40/4]
Post-anaesthesia, per bed space 40 Q = 40 + [(n – 1)40/4]
Adult acute day care accommodation:
Treatment rooms 40 Q = 40 + [(n – 1)40/4]
Post-anaesthesia recovery per bed space 40 Q = 40 + [(n – 1)40/8]
Day patient accommodation (as “In-patient accommodation”) As “In-patient accommodation”
Oral surgery/orthodontic:
Consulting rooms, type 1 40 Dental vacuum only
Consulting rooms, types 2 & 3 40 Dental vacuum only
Recovery room, per bed space 40 Q = 40 + [(n – 1)40/8]
Out-patient:
Treatment rooms 40 Q = 40 + [(n – 1)40/8]
Equipment service rooms, sterile services etc 40 Residual capacity will be adequate
without an additional allowance

34
4 Gas flow

4.74 Helium/oxygen mixtures administered by means of


a face mask and cannula, a demand valve with face
mask and cannula attached, or a nebuliser, are
normally supplied using cylinders fitted with an
integral valve.

Anaesthetic gas scavenging systems


4.75 For anaesthetic gas scavenging systems, it should be
assumed that for each operating suite two terminal
units could be in use simultaneously, for example in
the anaesthetic room and operating room (receiving
systems may be left connected when patients are
transferred from the anaesthetic room to the
operating room). The diversified flows for other
departments are as below:

Department Design flow for each terminal Diversified flow Q (L/min)


unit (L/min)
Accident & emergency resuscitation room (per trolley space) V(1) Q = V + [(n – 1)V/4]
Operating departments V Q = V + (nT– 1)V
Maternity operating suites V Q = V + (nS – 1)V
Radiodiagnostic (all anaesthetic and procedures room) V Q = V + [(n – 1)V/4]
Oral surgery/orthodontic consulting rooms (type 1) V Q = V + [(n – 1)V/4]
Other departments V Q = V + [(n – 1)V/8]

Note:
1. For the purpose of sizing the AGS disposal system pump,
V is taken as either 130 L/min or 80 L/min (see paragraph
10.16).

35
Medical gases – HTM 02-01 Medical gas pipeline systems – Part A: Design, installation, validation and verification

5 Cylinder manifold installations

5.1 A cylinder manifold installation comprises a 5.5 An automatic manifold changeover from duty to
primary and secondary supply system. stand-by should occur at a cylinder pressure that
will ensure the greatest possible utilisation of the
Primary supply system contents of the cylinders in the duty bank. If the
normal operation of the changeover control
5.2 The primary supply is provided by two banks of depends on an electricity supply, the design should
equal numbers of gas cylinders which are connected be such that failure of the electricity supply does
to the pipeline via a control panel. The changeover not disrupt the flow of gas to the distribution
from the “duty” to the “stand-by” bank of cylinders system.
should be automatic. All manifolds should be
capable of passing the full pipeline flow. The
Note
temperature of the gas may fall as low as –30°C as
the gas passes through the regulator at maximum Some systems are designed so that both banks (duty
capacity, and the equipment should be designed and stand-by) supply gas in the event of a power
accordingly. failure.
5.3 A schematic layout for a primary supply system
5.6 In the event of power failure, when the power is
is shown in Figure 10. Total storage is usually
restored, the original “running bank” should be on-
provided on the basis of a risk assessment. Each
line, that is, the same bank that was the “running
bank of the manifold should have sufficient
bank” prior to interruption of the supply.
cylinders for two days. Additional cylinders for one
complete bank change should be held in the
manifold room; for nitrous oxide/oxygen mixture, Note
sufficient cylinders to change two banks should be Some manifolds default to a specific bank following
held. a power failure, regardless of which bank was the
5.4 The nominal and usable capacity of the cylinders
running bank prior to interruption of the supply.
commonly used on manifolds are given in Table 22 NB: Some units may require manual resetting to the
(the figures are the equivalents at STP). original condition.

Table 22 Capacities of medical gas cylinders used on manifolds


Gas Nominal capacity (L) at 137 bar Usable capacity (L)1
Oxygen J-size 6,800 6,540
Nitrous oxide:
J-size 18,000 –
G-size 9,000 8,900
Nitrous oxide/oxygen mixture G-size 5,000 4,740
Medical air J-size 6,400 6,220
5,550
Helium/oxygen mixture K-size – 7000 nominal
Note:
1 T
 he usable figures are for discharge to a gauge pressure of 7 bar. Two sets of figures are provided for air – for 400 kPa systems
and 700 kPa systems. The latter is for discharge to 15 bar.

36
Figure 10 Typical automatic manifold control system and emergency reserve manifold

Terminal Ball
Lockable
unit valve
valve
Distribution
System

Pressure Non-return Pressure


Pressure
Pressure valve Pressure Ball
switch gauge switch
gauge gauge Exhaust valve
(piped to safe position) Terminal
Pressure Pressure Pressure Pressure Lockable
Sintered Sintered unit
regulator regulator regulator regulator valve
Ball Ball
filter filter
valves valve

Non-return
Shut-off Shut-off Pressure valve
valve valve safety
Pressure
valve
switch
Pressure Ball Pressure
safety valve safety Pressure
Pressure
valve valve
safety regulator
valve

Pressure Sintered Pressure


switch filter switch

Isolation Isolation
valve valve
Non-return valve

Exhaust
(piped to safe position)
Tailpipe

Cylinder valve

5 Cylinder manifold installations


Cylinder

Symbols to BS 2971:1993/ISO 1219-1:1991


37
Medical gases – HTM 02-01 Medical gas pipeline systems – Part A: Design, installation, validation and verification

5.7 Manifolds and control panels should be designed 5.11 Separate pressure regulating valves should be
and certificated for use with 230 bar cylinders. The provided for each cylinder bank. The control
manifold headers should incorporate a renewable system should be designed so that the cylinders of
non-return valve to prevent the discharge of a one bank can be changed, or the pressure regulator
complete bank of cylinders in the event of “tail- for one bank can be overhauled, without loss of
pipe” rupture. continuity of the gas supply.
5.8 The tail-pipe cylinder connector must be a pin- 5.12 Pressure safety valves should be of the self-closing
index yoke connector in accordance with BS EN type and be installed on each distribution pipeline
ISO 407:2004 for oxygen, nitrous oxide/oxygen downstream of the manifold line pressure regulator
mixture (50% v/v) and medical air. No non- and upstream of the main isolation valve. A
metallic flexible connectors should be used. The pressure safety valve should also be installed
connector for nitrous oxide should be a side outlet between the secondary source of supply
valve connector in accordance with BS 341-3:2002. (emergency/reserve manifold) and the pipeline
The manifold connectors should be in accordance distribution system. It should have a flow capacity
with the following: at least equal to that of the pressure regulator
immediately upstream of it. The discharge pipe
Thread Medical gas should be at least one size larger than the main
M24 x 2 Medical air pipeline and be separate for each safety valve.
M22 x 2 N2O/O2
5.13 This discharge pipeline should be vented to
M20 x 2 O2 atmosphere, outside the building, in an area where
M18 x 2 N2O the discharge of oxygen, nitrous oxide, or nitrous
Where it is necessary to use non-metallic materials, oxide/oxygen mixture will not present a fire hazard
consideration should be given to the use of non- or cause injury to personnel. Medical and surgical
halogenated polymers in high pressure systems air may be vented internally provided that this is
(>3000 kPa) delivering oxygen or gaseous mixtures done in a safe way. Warning signs should be posted
with oxygen concentrations greater than that in at the discharge positions; access for inspection
ambient air. Consideration should also be given to should be provided.
fitting sintered filters upstream of non-metallic 5.14 It should terminate at least 3 m clear of any door/
materials to minimise the risk of particle collisions window that can be opened or other ventilation/air
and impacts, which are a potential source of intake. The ends of the discharge pipelines should
ignition. In addition, there are tests that should be be turned downwards to prevent the ingress of dirt
conducted to ensure that the risk of ignition is and moisture, and be placed and protected so that
minimised. Attention is drawn to BS EN ISO frost cannot form or be collected upon them.
15001: 2004. Similar safety valve arrangements are required for
installations supplied from liquid oxygen cylinders.
Note
Studies have shown that inadvertent ignition of Note
halogenated polymers can lead to highly toxic High pressure cylinders with integral pressure
by-products being delivered to the gas stream. regulation can be used on manifold systems.

5.9 Pressure indication should be provided to indicate


pressure in each cylinder bank and in the MGPS. Manifold monitoring and indicating system
5.15 The monitoring and indicating system should
Pressure control perform the following functions:
5.10 The pressure control should maintain the nominal a. overall manifold monitoring;
pipeline pressure within the limits given in
Chapter 4. High-pressure regulators should comply b. manifold condition indication;
with BS EN 738-2:1999 and be supplied with c. overall supply plant indication.
auto-ignition test results.

38
5 Cylinder manifold installations

5.16 All functions should be appropriately identified. c. for the pipeline distribution system, a red “low
Indicators should have a design life of at least five pressure” and a red “high pressure” indicator to
years. The system should be capable of automatic be illuminated when the respective conditions
reinstatement after restoration of the power supply. occur.
5.17 Manifold monitoring, indicating and alarm systems
Alarm signal status unit
should be on the essential electrical supply.
5.21 The following indication of manifold conditions
Manifold control unit should be provided:
5.18 The control unit should include a green “mains a. green “normal”: normal;
supply on” indicator.
b. yellow “duty bank empty, stand-by running”:
change cylinders;
Manifold monitoring
c. yellow “duty bank empty, stand-by low”: change
5.19 Each automatic manifold should be provided with
cylinders immediately;
monitoring to detect:
d. yellow “emergency reserve bank low”: reserve
a. duty bank operating;
low;
b. duty bank empty and stand-by bank operating;
e. red “pipeline pressure fault”: pressure fault.
c. stand-by bank below 10% capacity, when the
5.22 Conditions (b) to (e) should be transmitted to the
duty bank is empty;
central alarm system. Where relays are used, they
d. each secondary supply (emergency reserve) should be normally energised relays, which de-
manifold bank below nominal 14 bar (for energise under fault conditions, with contacts
nitrous oxide) and below 68/100 bar pressure having a minimum rating of 50 V dc and 50 mA.
for other gases; Volt-free, normally closed contacts rated at 50 V dc
e. pipeline pressure faults outside the normal and 50 mA should be provided for transmission of
range. conditions (b) to (e) to the alarm system.
5.23 The panel can be incorporated into the manifold
Manifold indicator unit control unit or be a separate unit within the
5.20 There should be indicators to show the following plantroom. If mounted separately, the cabling
conditions: should be monitored for open/short circuit. In the
event of such a cable fault, a red “system fault”
a. for each automatic manifold: lamp should be illuminated on the alarm signal
(i) a green “running” indicator for each bank. status unit, together with the appropriate alarm
This should display when the bank is condition.
supplying gas, irrespective of the pressure;
Manifold management
(ii) a yellow “empty” indicator for each bank
when the running bank is empty and 5.24 Connections should be provided that allow
changeover has occurred; monitoring of manifold alarm conditions (b) to (e)
and manifold running for each “bank”. These
(iii) a yellow “low pressure” indicator for each connections should be volt-free contacts normally
bank to be illuminated after changeover, closed for each condition having a minimum rating
when the pressure in the bank now of 50 V dc and 50 mA. The building management
running falls to the low pressure setting; system should not be used to control the manifold.
b. for each secondary supply (emergency reserve)
bank, a yellow indicator to be illuminated when Secondary supply system
the pressure in the bank falls below 14 bar for 5.25 An emergency reserve manifold system should be
nitrous oxide or below 68 bar for other gases provided to form a secondary source of supply, for
(this will require the use of separate pressure emergency use, or to permit servicing or repair.
sensors – one for each bank);
5.26 The supply should be designed to provide the
design flow of the primary system and have

39
Medical gases – HTM 02-01 Medical gas pipeline systems – Part A: Design, installation, validation and verification

sufficient connected capacity to supply the pipeline Figure 11 Typical emergency reserve manifold
for at least four hours. When such provision would From Automatic Distribution
result in more than ten cylinders on each bank, the Manifold System
additional cylinders should be held in the manifold
rooms. A non-return valve and isolating valve Ball
Exhaust valve
should be installed immediately upstream of the Terminal
(piped to safe position) Lockable
reserve manifold connection to the pipeline valve
unit
distribution system.
5.27 The requirements for the emergency reserve supply
Non-return
capacity should be set out in the operational policy valve
document; this should take into account the Pressure
safety
arrangements for the supply of cylinders and the valve
flow that the system is required to provide. The gas
supplier should be consulted.
Pressure
5.28 The specific requirements will depend on the regulator
method of primary supply. Where this results in an
unrealistic number of cylinders being kept on site, Pressure Sintered Pressure
the operational policy should be set out, giving switch filter switch
details of procedures to be followed in an
emergency to ensure continuity of supply.
Isolation Isolation
5.29 For large installations, it may be impractical to rely valve valve
on a cylinder manifold system; thus, consideration
should be given to either a bulk liquid or liquid
cylinder emergency/reserve supply.
5.30 The operational policy document should set out
the location of emergency manifolds, cylinders etc
and the action to be taken in the event of loss of
the primary source of supply.

Location of secondary sources of supply for


manifold installations
5.31 The secondary supply system for cylinder manifold
systems should normally be located in the manifold
room of the primary supply. A two-cylinder
emergency reserve supply would normally be
considered adequate for a cylinder manifold Secondary sources of supply for air compressors/
supply system (but see note (h) to Tables 1–9 liquid oxygen/oxygen concentrators (PSA)
in Chapter 2). All cylinder valves should be 5.33 The supply should comprise a two-bank fully-
permanently open so that gas is immediately automatic manifold system as described in
available, but one of the isolating valves should be paragraphs 5.1–5.23 (except for (d) and (e) in
closed. A typical system is shown in Figure 11. paragraph 5.19; (b) and (c) in paragraph 5.20; and
5.32 The supply system should go into operation
(d) and (e) in paragraph 5.21, which do not apply).
automatically via a non-return valve, and the A typical number of cylinders in each bank would
emergency reserve manifold (ERM) isolating valve be a minimum of ten depending on size and
should remain open. location (see also Chapter 2). The manifold
system(s) should be installed in an appropriate
manifold room(s) separate from the plant.

40
6 Oxygen systems

Liquid oxygen systems Risk assessment


6.6 Risk assessment is used to assist in the development
General of the medical oxygen installation to produce a safe
6.1 Over the last ten years, there has been a significant and practical design and ensure that a safe supply of
increase in the use of medical oxygen for treating oxygen is available for patient use at all times. It is
patients in healthcare facilities, with some hospitals used for all aspects of the process; from the initial
seeing annual increases well in excess of 10%. concept designs through installation and operation
Introduction of the new European Standard on to the routine assessment of the installation, once
medical gas pipeline systems (BS EN 737) also has in service.
implications. 6.7 Advice is given on setting up risk assessment teams
6.2 The scope of the advice provided by this chapter and choosing the correct mix of personnel to ensure
covers the supply of liquid oxygen to healthcare that all aspects of the associated risks are
facilities from delivery into bulk storage vessels for considered.
the larger hospitals to supply of liquid oxygen in 6.8 Throughout this chapter, non-exclusive risk criteria
liquid cylinders to hospitals with lower demands. lists are provided to assist these teams in identifying
The guidance given is intended to cover all the the unacceptable risks and suggesting how they
aspects of a bulk cryogenic liquid system (VIE). might be addressed. It recommends that annual
6.3 This chapter also covers the supply of medical risk assessments are carried out throughout the life
oxygen from on-site generation using PSA plant, or of the system to ensure that a safe system of supply
in medical cylinders, other than (in the case of the is maintained and any new risks are identified.
latter) as a means of backup to the main supply 6.9 The prime responsibility to ensure that adequate
system. stocks of medical oxygen are available for patient
6.4 It does not specifically cover bulk liquid nitrogen use should remain firmly with the hospital’s
installations, but its principles may be applied to management team. However, the hospital may
hospitals where these gases are used in sufficient agree with its gas supplier or facilities management
quantities to make the use of a VIE cost-effective. supplier that they should manage the supplies of
medical oxygen and maintain adequate stocks in
6.5 Significant changes since publication of Health
the vessel. These arrangements should be clearly
Technical Memorandum 2022 (1997) include:
documented within the MGPS operational policy
• the use of risk assessment as a tool to assist in and procedures document. The effectiveness of
the development of the medical oxygen these arrangements will need to be assessed as part
installation; of the risk assessment review and be validated to
ensure that they can be met.
• adoption of the principles outlined in BS EN
737-3:2000; 6.10 Consideration should be given to the operational
management consequences of using different
• new methods of sizing the medical oxygen
suppliers to supply medical oxygen to different
vessels and back-up manifolds;
supply systems on the same pipeline system.
• designation of vessel contents as “operational”
6.11 Any contracts involving different suppliers should
or “reserve” stock.
clearly state the obligations and limitations of
A checklist for planning and upgrading an oxygen liabilities; and any facilities management agreement
system is given in Appendix H. between the hospital and the medical gas supplier
must define the responsibilities of each party.

41
Medical gases – HTM 02-01 Medical gas pipeline systems – Part A: Design, installation, validation and verification

6.12 There must be no modification to the design or Figure 13 Primary supply (liquid cylinder)
any part of the medical liquid oxygen system
without written authorisation from the gas supplier.

BS EN 737-3:2000 Full

6.13 This guidance adopts the principles outlined in BS


Operational
EN 737-3:2000 ‘Medical gas pipeline systems: stock

pipelines for compressed medical gases and


vacuum’, which introduces to the UK the concept Operating alarm signal
Liquid level of operational

of having three independent sources of supply for stock has fallen below
minimum
Risk assessed
stock
medical gas systems. This is covered in Chapter 2. Operating alarm signal
Pressure in primary
vessel has fallen below
Unusable stock
minimum

New methods of sizing Primary supply

6.14 New methods of sizing the medical oxygen vessels


and back-up manifolds are covered, together with Figure 14 Secondary supply (VIE)
advice on appropriate location of vessels on site
using principles of risk assessment. This ensures the
provision of a secure source of supply that reflects
Full
the degree of risk associated with the hospital’s
location and its level of dependency on medical Operational
stock
oxygen. Operating alarm signal
Liquid level of secondary
stock has fallen to
Designation of vessel contents as “operational” or 24 hours’ usage
Risk assessed
stock
“reserve” stock Emergency alarm signal
Pressure from secondary
supply has fallen below
6.15 The operational stock is the volume of product that minimum and emergency
Unusable stock
supply may need to be
the gas supplier uses to manage deliveries to the activated

hospital; when this stock is exhausted, the vessel


should be refilled under normal conditions. Secondary supply

6.16 The reserve stock is the volume of product that is Figure 15 Secondary supply (liquid cylinder)
used to provide additional stock to take account of
fluctuations in demand or when the supplier fails
to make a scheduled delivery.
6.17 Both operational and reserve stock levels are Full

calculated using the risk assessment principles Operational


embodied within this document (see Figures 12– Operating alarm signal
stock

17). Liquid level of secondary


stock has fallen to
24 hours’ usage
Risk assessed
stock
Figure 12 Primary supply (VIE) Emergency alarm signal
Pressure from secondary
supply has fallen below
Unusable stock
minimum and emergency
supply may need to be
activated

Full

Secondary supply

Operational
stock

Operating alarm signal


Liquid level of operational
stock has fallen below
minimum
Risk assessed
stock
Operating alarm signal
Pressure in primary
vessel has fallen below
Unusable stock
minimum

Primary supply

42
6 Oxygen systems

Figure 16 Secondary supply cylinder manifold 6.21 The maximum potential daily demand should be
based on the peak flow conditions measured
between 8.00 am and 6.00 pm, with all operating
rooms in use and with maximum demand being
AUTOMATIC
MANIFOLD provided to pipeline outlets. It should not be based
on the theoretical pipeline design flow conditions.
Full
Where actual flow monitoring is impracticable,
daily cylinder or liquid consumption figures should
Lead bank Emergency
alarm signal
be used.
Operating Pressure from

Note
alarm signal Standby bank secondary supply
Changeover from has fallen below
lead bank to minimum and
standby bank emergency
Secondary supply supply may need
to be activated
Control panels should be capable of passing the
maximum design flow of the oxygen system’s pipeline
distribution system. This may necessitate installing two
Figure 17 Secondary supply liquid manifold control panels in parallel.

6.22 Additionally, historic consumption records should


be reviewed to assess the current usage and the
natural growth of the medical oxygen demand. The
Full growth predictions should take into account any
planned extensions to the hospital’s facilities or
pipeline systems and changes in clinical practices in
the hospital that could affect the medical oxygen
Emergency alarm signal demand. Natural growth in usage of medical
Emergency supply system
pressure low oxygen, due to changes in clinical practice, is about
8% to 10% per annum, but individual hospitals
Emergency alarm signal
Pipeline pressure low
will need to establish this growth figure during the
Emergency supply risk assessment process.

Choosing an oxygen supply system 6.23 For new hospitals, where no historic information is
available, the estimated demand should be based on
6.18 When designing or reviewing an installation to the proposed size and type of the hospital and the
supply medical oxygen to a hospital, the most usage figures of the facilities being replaced.
appropriate method of supplying the gas will be
determined by the potential size and variability of 6.24 It is essential to periodically review the average
the hospital’s medical oxygen demand. daily demand with the gas supplier and agree either
to revise delivery frequencies to maintain the
6.19 To determine the most suitable and cost-effective operational stock levels or increase the size of the
method of supplying medical oxygen and the storage system on site. Any planned increase in
appropriate size of the installation, comprehensive demand due to hospital site developments, pipeline
demand figures should be provided to the designer. extensions or changes in clinical practice should be
6.20 These demand figures (prepared as a part of the risk notified to the gas supplier to ensure that the
assessment) should be based on: changes do not jeopardise security of supply.
• the current average daily gas usage based on the 6.25 The medical liquid oxygen demand should be
past twelve months’ supplies; reviewed with the gas supplier at least annually (or
after a significant extension to the pipeline causing
• the maximum potential daily demand volumes increase in demand) to re-assess the size of the
based on peak flow conditions, as below; installation.
• any planned extensions to the hospital/pipeline 6.26 As the agreed stocks used for the supply of liquid
that may affect the demand; oxygen are all based on an average daily demand,
• the expected natural annual growth in the use of as the demand grows so the storage volume
medical oxygen. requirements will increase. With the increased

43
Medical gases – HTM 02-01 Medical gas pipeline systems – Part A: Design, installation, validation and verification

volume requirements for the reserve stock, the Its provision is determined by factors such as the
volume available for operational stock will reduce. size of the hospital, the availability of space for both
Having reviewed the average daily demand with the the installation and the delivery vehicle, the
gas supplier, it is necessary to agree either revised proximity of the gas supplier and the size of the
delivery frequencies to maintain the operational demand for medical oxygen.
stock levels or to increase the size of the storage
6.34 There are a number of operational benefits in using
system on site.
a medical liquid oxygen system over compressed gas
6.27 The review of the medical liquid oxygen cylinders, including:
installation should also include a review of the risk
• greater volume of medical oxygen stored on site;
assessment to ensure that no other conditions on
site have been changed that jeopardise the security • improved security of supply;
of the gas supply. • reduced storage area for the medical gas
6.28 For smaller hospitals, where the demand is typically cylinders;
below 3000 m3 per annum, the most cost-effective • reduced manual handling requirements for
method of supplying medical oxygen is from a cylinder handling.
compressed gas cylinder manifold.
6.35 When determining the cost-effectiveness of specific
6.29 As the demand increases, it becomes less practicable proposals from suppliers, the total supply costs
to use compressed gas cylinders and more cost- should be assessed, including costs for the site
effective to use medical liquid oxygen. A cylinder preparation and vessel installation, vessel rental and
manifold larger than 2 x 10 J cylinders is likely liquid supply over the total period of the contract.
to prove impracticable because of the manual
handling difficulties with the number of cylinders System configurations
involved. Liquid cylinders, which are ideally suited
to an annual consumption of between 3000 m3 6.36 In order to comply with the requirements of BS
and 40,000 m3, can be connected together by a EN 737-3:2000, it is necessary for all medical
manifold to provide adequate storage capacity and oxygen installations to have three independent
flow rate. supply sources capable of feeding medical oxygen
to the pipeline.
6.30 For hospitals with larger demands, a bulk medical
oxygen VIE will generally be used. There is a 6.37 These three sources are referred to as:
nominal overlap of annual consumption between • the primary supply – the main source of
27,500 m3 and 40,000 m3, where either a bulk medical oxygen on site, providing gas to the
VIE or a liquid cylinder installation could be pipeline;
considered, either to satisfy a particular
requirement, or to accommodate possible site • the secondary supply – the secondary source of
restrictions. medical oxygen on site, providing gas to the
pipeline and capable of providing the total
6.31 The main benefit of using gas cylinders is oxygen flow requirement in the event of a
that installation costs of manifold systems are primary supply failure;
significantly lower than those of a liquid oxygen
system. However, the cost of the medical oxygen in • the reserve supply – the final source of supply
compressed gas cylinders is higher than the cost of to specific sections of the pipeline, capable of
medical liquid oxygen (supplied either into liquid meeting the required demand in the event of
cylinders or into a VIE). As the demand grows, so failure of the primary and secondary supplies, or
the lower unit cost of the liquid oxygen offsets the failure of the upstream distribution pipework.
higher installation costs of the liquid oxygen 6.38 For smaller hospitals, the primary supply can be fed
systems. from compressed gas cylinders but as the demand
6.32 Cryogenic liquid systems are normally used where grows, the most practicable supply source will be
the demand is high enough to make bulk supplies either liquid cylinders or a VIE system.
cost-effective and where the demand makes 6.39 A fully automatic gas cylinder manifold will
cylinder supplies impracticable. normally be used as the secondary supply system
6.33 Liquid oxygen provides a flexible approach to for smaller VIEs and liquid cylinder systems.
both the size and the choice of installation design. Where it is impracticable to maintain supplies to

44
6 Oxygen systems

the hospital using a cylinder manifold, a secondary 6.47 The cryogenic storage vessel is normally
liquid oxygen system will be necessary. constructed from a stainless steel inner pressure
vessel that is supported in a mild steel outer shell.
6.40 Emergency supplies will not normally be fed from
The space between the vessels is filled with a high-
a liquid oxygen supply system, as it is not possible
performance insulating material, maintained under
to prevent the boil-off of the liquid oxygen over
a vacuum, to minimise heat transfer to the inner
extended periods when the emergency system is not
vessel, which reduces the rate of evaporation of the
in use.
liquid oxygen.
6.41 All attempts should be made to locate the primary
6.48 A pressure-raising regulator that permits the flow of
and secondary supply systems on separate sites.
liquid to the pressure-raising vaporiser, as required,
They should have independent control systems and
automatically controls the pressure in the liquid
supply routes into the hospital pipeline system and
oxygen system. The vaporised liquid is fed back to
be valved accordingly to ensure that the systems
the top of the vessel or liquid cylinder to maintain
remain independent.
the pressure in the system.
6.42 Where it is not feasible to utilise two sites, the risk
6.49 Under normal operating conditions for a VIE
assessment should evaluate the greater level of risk
system, the gas supply to the hospital will be
associated with using a single site and define the
maintained by feeding liquid oxygen to the main
appropriate actions that should be established to
vaporiser system where it is converted to a gas and
obviate the higher risks, such as using twin or ring-
warmed towards ambient temperature. There is
main pipeline systems, siting of the emergency
a tendency for the vaporiser system to “ice up”
supply manifold or installing suitable protection for
where hospital demands are high or continuous, or
the installation.
airflow to the vaporisers is restricted. Under these
6.43 The overall system should be designed so that the circumstances the options to be considered should
primary supply is used first, with the secondary include:
supply automatically switching in when the
• installation of additional vaporisers;
primary supply is either empty or fails to supply.
• an auto-changeover system between vaporisers;
Primary supply systems
Note
Cryogenic liquid systems (VIE)
In the event of power failure, control valves on all
6.44 These systems, commonly referred to as vacuum- vaporisers should fail “open”.
insulated evaporators (VIEs), are used to store the
medical gas as a liquid at cryogenic temperatures • hot water/electrically heated vaporisers;
and to vaporise it into a gas at ambient temperature
for distribution through the hospital pipeline. • increasing size of vaporiser;

Plant • repositioning.

6.45 The VIE system consists of: 6.50 Where hospital demands are low or very erratic,
the natural heat transfer into the vessel causes the
• a vacuum-insulated cryogenic storage vessel to liquid oxygen to boil and the vessel pressure to rise.
store the bulk liquid; When the vessel pressure rises to a set point, the
• one or more ambient-heated vaporisers to hospital pipeline is fed from the top gas to prevent
convert the cryogenic liquid into a gas for the vessel pressure rising above the safety-valve
supply to patients via a pipeline; setting. On safety-valve operation, oxygen must be
able to vent safely to atmosphere.
• control equipment to control the pressure and
flow of gas to the pipeline. 6.51 In all cases, the pipeline pressure is controlled
using a system of duplex pressure regulators and
6.46 The liquid oxygen is stored at cryogenic valves. It is essential that all materials used in the
temperatures (down to minus 183°C) and construction of the vessels, control equipment
converted to a gas at ambient temperature by and pipeline are compatible with oxygen at the
passing it through an air-heated vaporiser. operating temperatures that could be encountered
under normal operation with single fault condition.

45
Medical gases – HTM 02-01 Medical gas pipeline systems – Part A: Design, installation, validation and verification

The risk assessment will determine the exact 6.59 Only under extreme conditions should the safety
configuration. distances specified in BCGA CP19 be reduced.
Any relaxation of these safety distances needs
6.52 The control panel design should comply with the
to be agreed with the supply company’s safety
design requirements specified in BS EN 737-3 and
representative and the Authorised Person (MGPS).
be sized to provide the system design flow.
Both parties must ensure that an equivalent level of
Telemetry safety is achieved, and this should be approved and
documented.
6.53 The use of telemetry on the liquid storage system is
recommended because it permits both the hospital 6.60 The layout of the liquid oxygen installation should
and the gas supplier to monitor relevant supply provide adequate access to all of the relevant
conditions continuously, including storage vessel components of the system and permit adequate
levels and pressure. In addition, it can be used to airflow for the ambient vaporisers.
transmit other operational data from the storage
6.61 The plinth should be of concrete construction. The
vessel, pipeline and associated equipment for
area in front of the vessel(s) (tanker apron) should
monitoring purposes. It may be beneficial to make
be non-porous concrete. Under no circumstances
this information available to the relevant person(s)
should tarmac be used in the vicinity of the liquid
in the trust. By having continuous monitoring of
oxygen filling point, or areas where liquid oxygen
stock available through the telemetry system, an
spillage may occur.
existing vessel could be retained. This solution is
only acceptable provided that an appropriate risk 6.62 The location of the liquid oxygen compound
assessment, following the guidance given in this should permit the supplier to gain safe access with
chapter, supports the decision. the appropriately sized tanker. It is the supplier’s
responsibility to assess the space requirements for
Siting
vehicular access.
6.54 The Authorised Person (MGPS) will be responsible
6.63 The design of the liquid oxygen installation should
for agreeing the final location of the liquid oxygen
take into account the gas supplier’s requirements
compound(s), taking into consideration any issues
for discharging the liquid oxygen from the
raised in the initial risk assessment.
cryogenic tanker. The area directly in front of the
6.55 When considering the space requirements for vessel should be kept clear to provide access for
the liquid oxygen compound(s), there may be the delivery vehicle at any time. Under no
operational advantages in having two compounds circumstances should cars be permitted to park in
in different areas on the hospital site, rather than front of the compound.
one larger site utilising either a single large vessel or
6.64 The compound should not be used for the storage
multiple tanks. This arrangement may also have
of other equipment.
benefits with respect to both planning permission
and meeting the safety distances specified in the 6.65 Where the secondary or emergency supply system
British Compressed Gases Association’s (BCGA) is fed from a cylinder manifold, it should be in a
Code of Practice 19 (CP19): ‘Bulk liquid oxygen separate enclosure/manifold room and have
storage at users’ premises’ (henceforth known as adequate space to permit safe cylinder changeover.
BCGA CP19; see Table 23). Spare cylinders should not be held in the VIE
compound or liquid cylinder compound but stored
6.56 Each supply system should be located in a secure
in the nearest medical cylinder store.
fenced compound, which should be sized to allow
adequate access to all of the control equipment. 6.66 A pipework and installation diagram (P&ID) of
the plant should be displayed clearly to indicate the
6.57 The site should essentially be level but designed to
appropriate valves that are necessary to operate the
have adequate falls to prevent water accumulating
plant safely. The medical gases supplier should
beneath equipment.
make the Authorised Person (MGPS), and others
6.58 The location of drains in the vicinity of the site in the hospital that may operate the system, aware
should comply with the requirements specified in of its general operating principles. (Typical plant
BCGA CP19 (see Table 23). installations are shown in Figures 18–20.)

46
6 Oxygen systems

Table 23 Safety distances to comply with BCGA CP19


Safety distances from exposure to vessel/point where oxygen leakage or spillage can Up to 20 tonnes Over 20 tonnes
occur (metres) (metres)
Areas where open flames/smoking permitted 5 8
Places of public assembly 10 15
Offices, canteens and areas of occupancy 5 8
Pits, ducts, surface water drains (untrapped) 5 8
Openings to underground systems 5 8
Property boundaries 5 8
Public roads 5 8
Railways 10 15
Vehicle parking areas (other than authorised) 5 8
Large wooden structures 15 15
Small stocks of combustible materials, site huts etc 5 8
Process equipment (not part of installation) 5 8
Continuous sections of flammable gas pipelines 3 3
Flanges in flammable gas pipelines (over 50 mm) 15 15
Fuel gas vent pipes 5 8
Compressor/ventilator air intakes 5 8
Fuel gas cylinders (up to 70 m3) 5 5
LPG storage vessels (up to 4 tonnes) 7.5 7.5
LPG storage vessels (up to 60 tonnes) 15 15
Bulk flammable liquid storage vessels (up to 7.8 m3) 7.5 7.5
Bulk flammable liquid storage vessels (up to 117 m3) 15 15
MV or HV electrical sub-stations 5 8

47
Figure 18 Primary supply VIE system with compressed gas cylinder manifold
48

Medical gases – HTM 02-01 Medical gas pipeline systems – Part A: Design, installation, validation and verification
PI PS PAL LAL
14A
V6
PSH PAL
PI
V4 V20
PSL PAH

V5 Alarm panel
V15
PI To hospital
33 PSV Pressure pipeline
21
V8

VIE raising
10.5 V9 vaporiser
Bar
LSL LIT
V13 V12
V19

14 14

PCV
28
Main vaporiser Pressure control panel
V10

V11 S36
PSV
22 Third
source of
supply
V7

Storage vessel

Auto-change
manifold

Reserve manifold
Figure 19 Primary and secondary VIE system on single plinth

PI PS PAL LAL LAL


14A 14B
V6
PSH PAL
PI
V4 V20
PSL PAH

V5 Alarm panel
V15
PI To hospital
VIE PSV pipeline
33
21
Pressure
10.5
V8

raising
Bar V9 vaporiser

LSL LIT
V13 V12
V19

14 14

PCV
28
V10

Main vaporiser
V11 S36
PSV Pressure control panel
22 Third
source of
supply
V7

Main storage vessel

V6

V4 V20

V5
V15 Economiser vaporiser
PI
33 VIE PSV Pressure
21 raising
10.5
vaporiser
Bar V9

LSL LIT
V19

V13 V12

14 14

PCV
28
V10

Back-up vaporiser

6 Oxygen systems
V11 S36
PSV
22

V7
49

Back-up storage vessel


Figure 20 Primary and secondary VIE system on separate plinth
50

Medical gases – HTM 02-01 Medical gas pipeline systems – Part A: Design, installation, validation and verification
PI PS PAL LAL
14A
V6
PSH PAL
PI
V4 V20
PSL PAH

V5 Alarm panel
V15
PI To hospital
33 VIE PSV
Pressure pipeline
21
V8

10.5 raising
Bar V9 vaporiser Pressure control panel
LSL LIT
V19

V13 V12
14 14

PCV
28
Main vaporiser
V10

V11 S36
PSV
22 Third
source of
supply
V7

Main storage vessel

V6

V4 V20 PI PS PAL LAL


14A

PSH PAL
V5 PI
V15 Economiser vaporiser
PI
33 VIE PSV
Pressure
PSL PAH
21
V8

10.5 raising
Bar V9 vaporiser
Alarm panel
LSL LIT To hospital
V19

V13 V12

14 14 pipeline
PCV Pressure control panel
28
Back-up vaporiser
V10

V11 S36
PSV
22

V7

Back-up storage vessel (remote)


6 Oxygen systems

Liquid cylinder systems cylinder relief-valve setting, thus ensuring that any
excess pressure is safely vented.
Plant
6.75 Where installed in buildings, generous ventilation
6.67 Liquid cylinder systems can also be used to store
should be provided by means of fully-louvred access
the medical gas as a liquid at cryogenic
doors to the outside. The appropriate calculation
temperatures and to vaporise it into a gas for
must be made to ensure adequate ventilation,
patient use. These systems are used where the
especially during the filling of the vessels, when
demand is too high for compressed gas cylinders
they may be venting freely to atmosphere inside the
to be a practicable option but where it is neither
manifold room.
economic nor possible to supply bulk medical
liquid oxygen in a VIE system. 6.76 A P&ID of the plant should be displayed clearly to
indicate the appropriate valves necessary to operate
6.68 Liquid cylinders are constructed in a similar way to
the plant safely. The Authorised Person (MGPS)
vacuum-insulated cryogenic storage units, that is,
and others in the hospital who may work with the
as double-walled vessels. However, unlike the VIE,
VIE system should be made aware of its general
the liquid cylinder has an internal vaporiser coil to
operating principles by the medical gas supplier.
convert the liquid into a gas.
(Figure 21 shows a typical liquid cylinder manifold
6.69 The size of the liquid cylinder can vary between installation with cylinder backup.)
200 L and 1000 L water capacity. To obtain
sufficient storage capacity and to meet the hospital’s Compressed gas cylinder manifolds
flow requirements, a number of liquid cylinders can
6.77 The simplest supply system to provide medical
be connected together via a manifold.
oxygen to a hospital pipeline system utilises
6.70 The liquid cylinder system consists of: compressed gas cylinders, connected together on
an auto-changeover manifold. As the demand
• a number of vacuum-insulated liquid cylinders;
increases, the number of cylinders fitted to the
• a system to manifold the liquid cylinders manifold can be increased to meet the hospital’s
together to store sufficient liquid on site to meet requirements. The secondary supply for this system
the hospital’s demand; will usually be a manual changeover compressed
• control equipment to regulate the pressure and gas cylinder manifold, which comes on line
flow of gas to the pipeline. automatically (via a non-return valve) in the event
of primary manifold failure.
6.71 Although liquid cylinders are suitable for
6.78 For a full description of manifold supply systems,
transportation when full, they are normally
installed as a fixed installation and remotely filled see Chapter 5.
whilst in situ.
Secondary supply systems
6.72 Liquid cylinders are designed and supplied with
6.79 Where the primary supply system is a VIE, the
gas-specific liquid-fill and gas-use connections
secondary supply system can be either:
(including the connection on the remote liquid-fill
connection where the liquid cylinders are filled in • another VIE; or
situ).
• a liquid cylinder manifold; or
6.73 The connections used are:
• a fully-automatic compressed gas cylinder
• liquid fill: CGA 440; manifold.
• gas use: ISO 5145. 6.80 Where the primary supply system is a liquid
cylinder system, the secondary supply system
Siting
should be a fully automatic changeover gas cylinder
6.74 Where there is no alternative, a liquid cylinder manifold that comes into operation automatically.
manifold may be installed in a building or confined
6.81 There should be a system of backflow prevention to
area, but only if the vent header (to which all liquid
protect either system venting through the other in
cylinder vents will be connected) is piped to a safe
the event of a single fault in either system.
area via a back-pressure control valve. This valve
should be set at a pressure below that of the liquid

51
Figure 21 Typical liquid cylinder manifold installation with cylinder backup
52

Medical gases – HTM 02-01 Medical gas pipeline systems – Part A: Design, installation, validation and verification
PI PS PAL LAL
14A

PSH PAL
PI

PSL PAH

Alarm panel
To hospital
pipeline

Level
monitor
Pressure control panel

Third
source of
Vent supply

Liquid
fill
Remote fill

PI PI
33 33

PCV PCV
28 28

V2 LIT V3 V2 LIT V3 Auto-change


14 14 manifold
V5 V5
V1

V1

Reserve manifold

Liquid cylinder manifold


6 Oxygen systems

6.82 Where the secondary supply is fed from 6.90 Under most conditions, compressed gas cylinders
compressed gas cylinders, the size of the changeover are the appropriate method of providing an
manifold and the number of cylinders stored on emergency supply source.
site should be based on the gas supplier’s ability to
6.91 The size and design of the emergency supply
guarantee a delivery service within a defined period.
system should allow for cylinders to be changed
6.83 Where a liquid oxygen system is used for the whilst in operation.
secondary supply, the system design should allow
6.92 Consideration should also be given to the set point
any liquid oxygen that has boiled off to be fed to
of the regulator of any emergency supply system, to
the pipeline system to utilise product.
ensure that the pipeline pressure remains above the
6.84 Where the feed from the VIE compound to the minimum level of 3.8 bar.
hospital extends a long distance, or is exposed
to potential mechanical damage, particular Emergency inlet ports
importance should be given to siting the secondary 6.93 Emergency inlet ports are covered in Chapter 13.
supply system remotely from the main VIE In some instances, installation of a fixed manifold
compound with a separate supply to the hospital system will obviate the need for fitting an
pipeline system. emergency inlet port.
6.85 Where the secondary supply is sited remotely, 6.94 In smaller installations, fitting an emergency inlet
consideration should also be given to the set point port may be dispensed with if the risk analysis
of the secondary supply output regulator to ensure indicates that adequate supplies can be maintained
that the pipeline pressure is maintained at a via the NIST connectors of AVSUs supplying
minimum level of 4.1 bar. critical care areas.
6.86 When the vessels are located on separate sites, 6.95 When planning emergency provision for a
a backflow prevention device must be fitted on complete system, vulnerability of the primary
each leg feeding into the pipeline system. This will and secondary supplies will be a critical factor in
prevent loss of product, either from the other vessel determining both the type and the means of supply.
or from the hospital pipeline, in the event of failure
of or damage to a VIE unit or its feed into the Fixed automatic/manual manifold systems
hospital pipeline. The backflow protection should
be sited in a secure location where it is not liable to 6.96 Where two VIE units on the same plinth are in use,
mechanical damage and be as close to the hospital the emergency supply system should comprise a
curtilage as possible. fully automatic cylinder manifold permanently
connected to (one of ) the main oxygen riser(s) in
Emergency supply provision the hospital, or directly into a ring-main system. It
must be able to feed a riser automatically (without
6.87 In the event of total plant and/or main pipeline back-feeding to any damaged upstream section) on
failure, an emergency supply of oxygen should be failure of both primary and secondary plant, or the
available for patient use. MGPS upstream of the entry into the hospital.
6.88 The emergency supply system should be activated Such an arrangement is particularly suited to
automatically when the primary and secondary situations in which the main feed from the VIE
system is empty or fails to supply or when the installation to the hospital pipeline is vulnerable to
hospital pipeline pressure falls below 3.8 bar. It mechanical damage, for example when buried
must have the provision to automatically prevent under a roadway. The location and size of the
the backflow of medical oxygen into the remainder manifold should be determined by the risk
of the pipeline system should the pipeline fail assessment and according to the dependency of the
upstream of the connection. patients.
6.89 A variety of sources are available for the provision 6.97 When two separately sited VIE units are used to
of emergency oxygen, and these are detailed in provide the hospital supply, the need for emergency
paragraphs 6.96–6.105. manifold provision should be assessed against the
likelihood of failure of both VIE systems and their
respective feeds into the hospital pipeline.

53
Medical gases – HTM 02-01 Medical gas pipeline systems – Part A: Design, installation, validation and verification

6.98 Where it can be shown that one or both units are Discrete cylinder supplies
fed into the hospital pipeline in a manner such that
6.105 For non-critical care areas where there are no high-
the probability of disruption of one or both of the
dependency patients, it may be appropriate to use
feeds is negligible, the option to waive the fitting of
individual cylinders as the reserve source of supply.
further (manifold) supplies can be considered.
Cylinders fitted with integral valves and having a
product-specific terminal unit outlet are suitable
Local manifold provision (critical care areas)
for this purpose. The difficulties associated with
6.99 To offer additional protection against the storing, testing, maintaining, distributing and
possibility of a pipeline failure within the hospital, connecting large numbers of such equipment must
further (manual or automatic) manifolds can be not be underestimated. (Such protocols should be
permanently connected, via non-return valves, referenced in the MGPS operational policy.)
downstream of AVSUs controlling high-
dependency areas. Such units should come on line Alarm systems
automatically on failure of the main supply to an
6.106 Installations of the following type should be fitted
AVSU. A further non-return valve must also be
with alarm systems to provide visual and audible
added upstream of the AVSU to prevent back-
warnings for the following conditions. For:
feeding into a failed main supply system.
a. dual VIE vessels feeding into a single control
6.100 The positioning of these manifolds is very
panel; or
important to ensure that the critical supply/high-
dependency areas defined in the risk assessment b. a single VIE vessel supported by a liquid
process have adequate stocks of medical oxygen cylinder secondary supply; or
available in the event of a system failure. However, c. a single VIE vessel supported by a fully
the risk analysis for the complete system may automatic compressed gas cylinder manifold,
indicate that the probability of use of such a
manifold system is negligible, or that the the following displays should be presented at the
circumstances causing the system failure would in plant and in a 24-hour-staffed position.
any event require the evacuation of the area.
Status/fault condition Indication Legend
6.101 Availability of accommodation, staff and manual Normal operation
handling issues would also need to be considered Green Normal
System available for use
during the risk assessment process. Where space Primary supply system’s
limitations prevent the installation of such operational stock empty
manifolds, the implications of providing discrete Yellow Refill liquid
Primary supply system’s reserve
cylinder/regulator combinations must be stock in use
considered. Primary supply system’s reserve
Refill liquid
stock empty Yellow
Gas feed via an AVSU (or terminal unit) immediately
Secondary supply system in use
6.102 Oxygen supply to the downstream side of an Secondary supply system empty Emergency
Yellow
AVSU (with the valve closed) may be achieved Emergency system in use supply in use
using an “emergency supply kit” consisting of two Pipeline pressure high or low Red Pressure fault
cylinder regulators and associated supply hoses
6.107 For:
with gas-specific connectors.
a. two discrete VIE vessels feeding into separate
6.103 Such an arrangement may be used to support
parts of the pipeline system; or
high-dependency departments, albeit the unit will
usually be of limited capacity by comparison to a b. a single VIE vessel supported by a liquid
fixed automatic manifold system. cylinder secondary supply that feeds separate
parts of the pipeline system; or
6.104 Storage, maintenance, testing, security and
deployment arrangements for the emergency c. a single VIE vessel supported by a fully-
supply kits must be documented in the MGPS automatic compressed gas cylinder manifold
operational policy. secondary supply that feeds separate parts of
the pipeline system,

54
6 Oxygen systems

the following displays should be presented at the


plant and in a 24-hour-staffed position. At the secondary vessel/liquid cylinder supply/cylinder
manifold and a 24-hour-staffed position
At the primary vessel and a 24-hour-manned position Status/fault condition Indication Legend
Status/fault condition Indication Legend Normal operation
Green Normal
Normal operation System available for use
Green Normal
System available for use Secondary supply system’s
Primary supply system’s operational stock empty Refill liquid/
Yellow
operational stock empty Secondary supply system’s change cylinders
Yellow Refill liquid reserve stock in use
Primary supply system reserve
stock in use Secondary supply system’s
Primary supply system’s reserve reserve stock empty Emergency
Refill liquid Yellow
stock empty Yellow Emergency supply system supply in use
immediately in use
Secondary supply system in use
Secondary supply system low Secondary Pipeline pressure high or low Red Pressure fault
Yellow
stock low 6.113 When the secondary system operational stock has
Pipeline pressure high or low Pressure been exhausted and the vessel contents reach the
Red
fault secondary reserve stock level, the first alarm
6.108 When the primary system operational stock has condition will be indicated by a yellow alarm and
been exhausted and the vessel contents reach the the legend “refill liquid” illuminated. This alarm
reserve stock level, the first alarm condition will be condition continues until the secondary supply
indicated by a yellow alarm and the legend “refill system is refilled.
liquid” illuminated. 6.114 When the secondary supply system is empty, the
6.109 When the primary system reserve stock is empty second alarm condition will be indicated by a
and the secondary supply system is in operation, yellow alarm and the legend “emergency supply in
the second alarm condition will be indicated by use” illuminated. This alarm condition continues
a yellow alarm and the legend “refill liquid until the secondary supply system is refilled or the
immediately” illuminated. This alarm condition secondary supply manifold cylinders are replaced.
continues until the primary supply system is 6.115 Should the secondary supply of medical oxygen to
refilled. the hospital pipeline fail due to lack of contents or
6.110 When the secondary supply system is low, the mechanical failure of any of the components or
third alarm condition will be indicated by a should a serious leak occur, the pipeline pressure
yellow alarm and the legend “secondary stock low” will fall. When the plant output pipeline pressure
illuminated. This alarm condition continues until falls below 3.75 bar, the condition will be
the secondary supply system is refilled or the indicated by the “pressure fault” alarm.
cylinders are replaced. 6.116 With a correctly installed and commissioned
6.111 Should the primary supply of medical oxygen to emergency system, the hospital pipeline pressure
the hospital pipeline fail due to lack of contents or will be maintained downstream of the primary and
mechanical failure of any of the components, or secondary supply connections (non-return valves)
should a serious leak occur, the pipeline pressure at a minimum pressure of 3.9 bar. Pressure on the
will fall. When the plant output pipeline pressure plant side of the non-return valves will, however,
falls below 3.75 bar, the condition will be remain below 3.75 bar until the plant is refilled,
indicated by the “pressure fault” alarm. or any fault remedied. Therefore, the plant and
24-hour-monitored alarms will continue to
6.112 If the regulator controlling the pipeline pressure indicate both “pressure fault” and “emergency
should fail “open”, the pipeline pressure will rise. supply system in use” until the vessel is refilled or
This condition will be indicated by the “pressure any fault rectified.
fault” alarm when the pressure rises above 4.9 bar.
6.117 If the regulator controlling the pipeline pressure
should fail in the “open” position, the pipeline
pressure will rise. This condition will be indicated

55
Medical gases – HTM 02-01 Medical gas pipeline systems – Part A: Design, installation, validation and verification

by the “pressure fault” alarm when the pressure record of the risk assessment will also act as a
rises above 4.9 bar. reference document when the system is reviewed.
6.118 Where the emergency supply is installed on 6.126 Additional local factors and requirements
individual zones of the pipeline system, the identified by the project team will also need to be
“emergency supply in use” alarm must be displayed considered when carrying out the risk assessment
within the pipeline zone area. A separate to take account of site-specific issues concerning
“emergency supply low” alarm should also be how the product is stored, distributed and used.
installed on each zone.
6.127 Any risk control procedures identified by the risk
6.119 Where more than one VIE is used and the assessment process which are designed to minimise
operational and reserve stock is distributed any identified risks must be recorded and
between multiple vessels, a lit “normal” display incorporated into the relevant hospital standard
indicates that the vessel is available for use. operating procedures (SOP) or work instructions
(WI).
6.120 In the event that the primary (or secondary) vessel
should become empty (or suffer from any other 6.128 When sizing the vessels and cylinder manifolds to
fault condition), the “normal” display should be provide adequate storage of medical oxygen on
extinguished, indicating that the vessel is not site, the stock should be distributed between the
available for use. three sources of supply as defined in BS EN 737-3:
2000; that is, the medical oxygen supply system
6.121 Alarm conditions should be transmitted to the
should normally consist of:
central alarm system.
• a primary supply;
6.122 Where relays are used, they should be energised
relays that de-energise under fault conditions, with • a secondary supply;
contacts having a minimum rating of 50 V dc and
• a emergency supply.
50 mA. Alternatively, volt-free, normally closed
contacts rated at 50 V dc and 50 mA should be 6.129 The capacity of the primary and secondary supply
provided for transmission of the conditions to the system will consist of:
alarm system. • operational stock;
6.123 Typical alarm trigger points are shown in • reserve stock.
Figures 12–17.
6.130 The operational stock is the volume of product
Determining system size through risk assessment that the gas supplier uses to manage deliveries to
the hospital, and its exhaustion signals the point at
Introduction which the vessel should be refilled under normal
conditions.
6.124 The 1997 edition of Health Technical
Memorandum 2022 defined a (fixed) VIE primary 6.131 The reserve stock is the volume of product that is
vessel capacity of 14 days’ oxygen supply but did used to provide additional stock, to take account
not define capacity of a liquid cylinder system. of fluctuations in demand, or when the supplier
This section addresses the risk factors associated fails to make a scheduled delivery.
with the supply of oxygen on a hospital site and,
6.132 The system should be designed so that the primary
with the aid of defined risk criteria, offers guidance
and secondary supply system stocks are kept
on the sizing of VIE, liquid cylinder and
separate from each other. Under no circumstances
compressed gas cylinder manifold installations for
can the primary supply system operational stock be
any specified location.
stored in the secondary supply system vessel.
6.125 The risk assessment should take into account all
6.133 However, where it is not possible to install a single
issues concerning the safety and continuity of
large VIE vessel for the primary supply (such as
the medical oxygen supply. It is suggested that
where planning permission restrictions prevent the
identified risk factors and criteria be evaluated
use of a single large vessel), it may be appropriate
using both qualitative and quantitative measures,
to hold all or some of the primary supply system
and that all results be recorded in a logical manner
reserve stock in the secondary supply vessel. Under
that will support the decisions being made. The
these circumstances the primary supply vessel

56
6 Oxygen systems

should retain a minimum level when changing 6.139 When determining the number and size of
over to the secondary supply system. The volume liquid cylinders required for either a primary or a
retained in the primary supply vessel should equate secondary supply to a VIE, an allowance has to be
to the secondary supply system reserve stock. This made for the unusable capacity of each cylinder
should provide adequate stock on site to enable the when connected to the manifold system.
gas supplier to resupply product to the primary Compressed gas cylinder manifold systems
vessel in the event of failure of the secondary
supply. This level should be determined by the risk 6.140 For auto-changeover cylinder manifolds, one
assessment process but should be at least one day’s bank of cylinders should be considered as the
usable stock. operational stock and the other bank as the reserve
stock. The size of each source of supply should be
Review of risk assessment determined by considering the operational and
reserve stock requirements for each source.
6.134 The documented risk assessment should be
reviewed after the installation is complete, prior to 6.141 The secondary supply will normally comprise a
commissioning, to assess whether any parameters manually operated manifold system, connected
or circumstances have changed since the initial such that it will come on line automatically (via a
assessment. The risk assessment must also be non-return valve) in the event of primary supply
reviewed at least annually (or when there is any failure.
significant change to the medical oxygen supply 6.142 For sizing compressed gas cylinder systems, the size
system or usage pattern) to ensure that the details of the manifold will normally be determined by
are current. At this review, all changes should be the ability of the hospital to provide adequately
considered that might have an effect on the safety trained staff to change over cylinders quickly
of the system or the security of supply. enough to meet the demand.
Sizing plant – general 6.143 The number of cylinders required to support
the manifold can be determined by dividing the
VIE installations
relevant stock figure by the usable volume of each
6.135 The operational and reserve stock for each supply cylinder (that is, the volume at full cylinder
system should normally be held in the same vessel. pressure less the volume at the pressure of the
Where planning restrictions prevent the use of a cylinder when the manifold changes over).
single large vessel on site, it may be appropriate to
utilise multiple vessels to provide adequate stocks The risk assessment process
on site. Risk assessment for management responsibilities
6.136 When sizing VIE systems for the primary or
6.144 The risk assessment criteria, when considering
secondary supply, the vessel size will be determined management responsibilities for the medical liquid
by adding the operational and reserve stock oxygen system, need to include the following:
together and allowing for the level of unusable
stock left in the vessel when the designed flow rate • the need to document and agree responsibilities
cannot be maintained. for the monitoring of the medical liquid
oxygen VIE, and the need to establish a back-
Liquid cylinder installations up procedure with the gas supplier to ensure
6.137 For liquid cylinder installations, the primary that adequate stocks will be maintained in the
system should be made up of a number of liquid event of a failure of the fitted telemetry system;
cylinders connected together by a manifold. The • the hospital should set up procedures to ensure
secondary system will comprise an automatic or that the VIE system is monitored at regular
manual compressed gas cylinder manifold system. intervals for any deviation from normal
6.138 Each liquid cylinder will have a maximum design operation (such as safety valves lifting, major
flow rate for continuous use. The number of liquid leaks, or failure of either the telemetry or alarm
cylinders required for an installation may be system);
governed by either the maximum storage capacity • the implications of any decisions to not fit
required on site or the flow rate required to meet telemetry or to utilise a vessel, or vessels,
the hospital’s maximum demand. that do not provide adequate operational and

57
Medical gases – HTM 02-01 Medical gas pipeline systems – Part A: Design, installation, validation and verification

reserve stocks. These decisions should be taken • the need to site the reserve sources of supply
at an appropriate level of management, should local to the point of use to protect against
be documented, and their implications should pipeline failure where high-dependency
be considered as part of the risk assessment; patients are located;
• consideration of the resources needed to • safety requirements for the storage of oxygen
maintain adequate supplies of medical oxygen on site, including compliance with the safety
either under normal, or emergency, conditions. distances specified in BCGA CP19;
When evaluating these requirements,
• the location and extent of the medical oxygen
consideration should be given to the risks that
pipeline system;
the trust would face in the event of supply
failure causing disruption of clinical services; • the vulnerability of the hospital pipeline to
mechanical damage and whether underground
• consideration of the operational management
sections of the pipeline system comply with
consequences of using different suppliers to
the requirements of this Health Technical
supply medical oxygen to different supply
Memorandum; and whether the pipeline is
systems supporting the same pipeline
capable of being inspected throughout its entire
installation. Any contracts involving different
length or pressure tested (whilst maintaining
suppliers should clearly state the obligations
the supply), or otherwise can be tested;
and limitations of liabilities.
• the space available for the liquid oxygen
6.145 Where manifolds are used as either the secondary
installation, or cylinder manifold, and the
or emergency supply, adequately trained staff
available access for the delivery vehicle;
should be available, whenever required, to ensure
continuity of supply. Consideration also needs to • the vulnerability of the site to external damage;
be given to the manual handling issues concerned • the possibility of interference with the supply
with changing cylinders on the manifold and system or other security issues.
arrangements to store adequate stocks to meet
demands. Risk assessment for sizing of operational stock
6.146 Consideration needs to be given to the type of 6.149 The risk assessment criteria for the sizing of the
clinical activities carried out in each area of the operational stock should include:
hospital and the ability to provide emergency • the average daily demand at the end of the
back-up to individual areas used for critical care, contract period. Any changes to the predicted
or within high-dependency units. growth of demand will need to be considered,
Initial risk assessment for siting of plant and changes made to the vessel size or delivery
frequency at the appropriate time within the
6.147 The initial risk assessment should consider the contract period. It may be beneficial to set a
requirements to ensure a continuous supply of daily demand rate at which changes to vessel
medical gas to the patient. size or delivery frequency will be considered;
6.148 The initial risk assessment criteria related to the • a review of vehicular access to the VIE, timing
complete installation should include: of the deliveries, any restrictions due to local
• the size and location of each source of supply planning requirements, and the effect of these
(for example the volume held as operational factors on the delivery frequency;
and reserve stock for each source of supply, • an environmental impact assessment.
located on one site or two independent sites);
Risk assessment for sizing of reserve stock
• the associated risks with siting tanks at either
the same or separate locations (for example 6.150 The risk assessment criteria for the sizing of the
physical space availability, accessibility for reserve stock should include:
delivery and maintenance requirements, • the average daily demand at the end of the
accessibility to the pipeline system [to tie-in contract period. Any changes to the predicted
points etc], alarm systems and cabling, pipeline growth of demand will need to be considered,
routing and protection); and changes made to the vessel size or delivery
frequency at the appropriate time within the

58
6 Oxygen systems

contract period. It may be beneficial to set a 6.153 The current average daily demand can be
daily demand rate at which changes to vessel calculated by dividing the current annual
size or delivery frequency will be considered; consumption by 365 days.
• the delivery frequency guaranteed by the gas 6.154 The operational stock should be based on an
supplier that can be provided at short notice average daily demand predicted for the end of the
should the primary supply system fail; contract period calculated by:
• the minimum response time from when Average daily demand = Current daily demand
the primary supply system fails to when the + Planned growth + Natural growth.
delivery vehicle could be on site to refill
6.155 The operational stock is calculated as:
the secondary supply VIE, or to provide
replacement compressed gas cylinders for the Operational stock = Average daily demand x
manifold. Agreed delivery period.
Risk assessment for the provision of emergency supply systems 6.156 If there is significant growth in average daily
demand within the contract period, either the
6.151 The risk assessment criteria concerning emergency
vessel should be resized or the agreed delivery
supply systems should include:
frequency should be reviewed to reduce the
• the need for installation of independent delivery period and maintain the operational stock
emergency supplies to zones on the medical gas level.
pipeline supplying critical care areas or wards or
6.157 The delivery period for the primary supply will
departments that are remote or vulnerable to
be based on the gas supplier’s normal delivery
interruption;
frequency.
• the positioning of the manifold to ensure ease
6.158 The delivery period for the secondary supply
of changeover of cylinders with respect to
will be based on emergency conditions when
access and manual handling issues;
the primary supply is not available. Under these
• the storage of cylinders associated with the circumstances, special delivery response times must
emergency manifold to ensure compliance with be agreed with the gas supplier.
the appropriate codes of practice and local
6.159 The supply agreement should commit the supplier
hospital requirements;
to manage the operational stock, based on an
• training requirements for both the relevant agreed delivery frequency and the minimum stock
clinical and operational staff to ensure correct level to be maintained in the vessel.
operation of the emergency supply system.
Calculation of primary reserve stock
Stock calculations 6.160 The table below provides a matrix for the
calculation of primary reserve stock based upon
Calculation of operational stock for primary and secondary
distance from gas supplier and fitting of telemetry.
supplies
6.152 The capacity of the operational stock of primary Kilometres from No telemetry Telemetry fitted
and secondary supply systems should be agreed gas supply depot (no of days’ stock) (no of days’ stock)
with the gas supplier and based on the following Up to 75 5 3
parameters: 75–150 6 4
• the current average medical oxygen daily 150–300 7 5
demand, plus any natural growth over the Over 300 8 6
contract period; Calculation of secondary reserve stock
• any additional planned growth (above any 6.161 The minimum level for reserve stock for the
natural growth) in the usage pattern within the secondary supply should allow for circumstances
contract period; in which the primary supply system is not available
• the agreed delivery frequency. for use.

59
Medical gases – HTM 02-01 Medical gas pipeline systems – Part A: Design, installation, validation and verification

6.162 This secondary supply system reserve stock level only be installed when an investment appraisal
will be dependent on: shows them to be economical.
• the proximity of the supplier’s distribution 6.167 When installed, a PSA system will deliver product
depot; gas via the “oxygen” pipeline system.
• the response time that the gas supplier needs to 6.168 Oxygen concentrators operate by adsorbing,
make a delivery under these conditions; under pressure, other gases in the atmosphere onto
materials which have specific physico-chemical
• the delivery frequency that can be sustained
properties, thus freeing the oxygen which is stored
under the conditions when the primary supply
and transmitting it for use. The adsorbents are
is unavailable for use.
known as artificial zeolites, more commonly
Calculation of capacity of emergency supply systems (cylinder referred to as molecular sieves. The sieve units
manifolds) are arranged in pairs, one adsorbing whilst the
6.163 The number of cylinders stored locally to the other regenerates. The waste product, essentially
emergency supply system manifold and the nitrogen, is discharged to atmosphere during
number of connections on the manifold(s) should regeneration of the adsorbents. In some systems,
be determined by risk assessment. the use of vacuum to remove the nitrogen increases
the efficiency of the regeneration/adsorption
6.164 When determining these requirements, the risk process. Regeneration requires the use of a small
assessment needs to consider: proportion of the product gas.
• the maximum demand from the high- 6.169 The PSA process has reached a high level
dependency patients who may be supplied of technical sophistication and is capable of
from the pipeline zone that the emergency producing oxygen with a concentration of about
supply system protects; 95%. (For the UK the minimum level, below
• the maximum duration for which the which the emergency/reserve manifold will
emergency state is likely to last; come into operation, is 94%.) The remainder is
mainly argon with some nitrogen. The highest
• the proximity of the supplier of the compressed concentration is not likely to exceed 97/98%,
cylinders to the hospital; except when the emergency/reserve manifold is in
• the ability of the hospital to connect cylinders use, when it will be 100% if these are from a gas
to the manifold. supplier.

6.165 Consideration needs to be given to the logistics 6.170 The major components of a PSA system and their
of storing and handling the number of cylinders layout are shown in Figure 22. The typical major
needed to provide adequate supplies until the components of the system are the compressors,
primary/secondary supply systems or the hospital receiver(s), dryers, molecular sieves, vacuum
pipeline can be re-established. pumps, filters and regulators. Other components
are identical to those used for medical air and
Oxygen concentrator installations (PSA vacuum plant, which are described fully in the
appropriate sections. A suitable operating and
plant) indicating system is also required, as specified
below. Package supply systems, which should be
General
specified to meet the requirements given in this
6.166 Oxygen concentrators or pressure swing adsorber memorandum, are available from manufacturers.
(PSA) systems may be an alternative to the more
traditional supply systems (the terms oxygen Siting
concentrator and PSA are interchangeable). 6.171 The plant should have all-round access for
Typical installations where PSA systems should maintenance purposes, and allowance should be
be considered are those sites having no access to made for changing major components.
reliable liquid supplies, such as remote or off-shore
locations, or where the safety criteria for a bulk 6.172 The siting of the plant should allow for adequate
liquid vessel cannot be met (for example, very flows of air for three different purposes:
restricted sites). Otherwise, PSA systems should a. air intake to the compressors;

60
Figure 22 Schematic diagram of a typical PSA installation
Primary supply air system PRV Primary supply molecular sieve device PRV Optional pipework
Non-return valve PRV PRV Pressure relief valve
After-cooler
(optional) PRV P Pressure gauge
P P

Flexible
Filter connector Booster Filter Reserve supply
Receiver Molecular Receiver
compressor filling system
(optional) sieve device (optional)
(optional) (if included)
Inlet
Drain
Oxygen
Compressor monitor

Shut-off valve

Interconnection Control system Oxygen monitor


with oxygen
analyser
PRV PRV
After-cooler Non-return valve Oxygen Line press regulator
(optional) PRV monitor
P P Pressure
P
Flexible safety
Filter connector Booster Filter valve
Receiver Molecular Receiver
compressor
(optional) sieve device (optional)
(optional)
Line press regulator
Inlet
P Pressure
Drain safety
Independent valve
oxygen analyser
Compressor and shut-off
valve
Shut-off valve
Pressure control
Secondary supply air system Secondary supply molecular sieve device equipment

Reserve supply PRV


(comprising: primary and secondary supplies with automatic changeover)

Manifold Manifold Non-return valve (shut-off valve


Non-return valve (shut-off valve
if cylinder filling required)
if cylinder filling required)

6 Oxygen systems
P PS PS P
Changeover
Press Press Safety relief device
Safety relief device
switch switch
Pipeline distribution system
Primary reserve Primary reserve
vessel(s) (Automatic) vessel(s)
61
Medical gases – HTM 02-01 Medical gas pipeline systems – Part A: Design, installation, validation and verification

b. cooling of the compressed air by the after- Compressor and vacuum pump noise
coolers;
6.178 The noise level produced by the compressors will
c. cooling of the compressors. increase with the capacity of the supply system.
The maximum free-field noise level for unsilenced
6.173 Each compressor may require ducting to ensure
compressed air plant, at 1 m from the plant, varies
an adequate flow of cool air. The manufacturer
with the type and power of the plant but should
should be consulted over the range of operating
not normally exceed the following values:
temperature for which the system is designed. In
extreme circumstances, refrigeration of the cooling Reciprocating Screw Vane Power
air may need to be provided. 85 dBA 76 dBA 76 dBA 7.5 kW
6.174 Air-inlet filters should be fitted either to the 89 dBA 78 dBA 76 dBA 7.6–15 kW
compressor inlet or at a suitable point in any 93 dBA 80 dBA 79 dBA 15.1–22 kW
ductwork. The filters should comply with BS ISO
97 dBA 92 dBA 90 dBA 22.1–60 kW
5011:2000 and be either dry medium filters or
grade CA paper element filters. 6.179 In noise-sensitive areas, an acoustic enclosure
should be included in the purchase specification
Plant configuration for all compressors. Such an enclosure should
produce a reduction of at least 10 dBA in the free-
6.175 The plant should comprise:
field noise level at 1 m.
a. a duplex compressor – if more than two
compressors are installed, the plant should Molecular sieves
provide the design flow with one compressor
6.180 Duplex molecular sieves should be provided in
out of service;
pairs to permit continuous generation of oxygen.
b. duplexed air treatment/molecular sieve One of the pairs of duplex sieves will be in the
devices, that is, two sets of filters and a pair adsorbing stage, whilst the other regenerates.
of molecular sieves (one adsorbing whilst the
other regenerates) and one vacuum pump (if Dryers
required by the manufacturer). 6.181 Air dryers of the desiccant type are usually
integrated within the molecular sieves and
Note therefore do not regenerate independently.
All duplexed components should be capable of Refrigerant dryers may also be included.
independent operation.
Oxygen monitoring system
Compressors and vacuum pumps 6.182 The plant should include a calibrated
paramagnetic oxygen monitoring system
6.176 The compressors for the PSA systems may be
comprising oxygen analyser, oxygen concentration
any of the type recommended for compressed air indicator, oxygen flow monitor and oxygen
systems. It is also possible to provide a combined concentration/flow recorder. Connections for
medical air PSA plant. Generally, the compressed calibration cylinders should also be provided. In
air requirement per litre of product gas is of the the event of the concentration falling below 94%,
order 4:1; as a result the compressor plant will be the monitoring system should isolate the PSA
on longer than that typically seen in hospitals. system from the pipeline distribution system so
6.177 A vacuum pump may be required as part of the that the emergency/reserve manifold operates.
system. The vacuum pump, if provided, is utilised Additionally, an independent monitoring system
during the adsorption/regeneration process. should be provided to isolate the plant when the
Vacuum pumps may be of any type as for the concentration falls below 94%. The second system
piped medical vacuum system. It will not generally need not be provided with a flow indicator or
be practicable to use water-sealed pumps or the recorder.
medical vacuum plant.

62
6 Oxygen systems

Operating and indicating system 6.189 A warning notice that complies with BS 5499-5:
2002 should be affixed which indicates the
6.183 The operating and indicating system should
presence of low voltage.
perform the following functions, as appropriate:
6.190 A further warning notice indicating that the plant
a. overall plant control and indication;
starts automatically should also be affixed near or
b. individual compressor starting; on the plant.
c. individual vacuum pump starting (where 6.191 Each compressor should have a selector switch
fitted); which, when turned to the “on” position, allows
d. control of dryers (where installed as separate the maximum and minimum pressure switches on
component); the receiver to control the “on” and “off ” loading
of that compressor. An alternative “auto” position
e. control of molecular sieves; of the selector switch may allow automatic
f. plant status monitoring and indication; selection of the compressors.

g. optional indication of the plant alarm status Plant control indication


(this function may be considered to be part of
6.192 There should be indicators for each compressor as
the alarm system).
follows:
6.184 Provided that the individual compressor starters
are housed in a separate compartment, these a. green “mains supply on”;
functions may be carried out by separate units or b. green “compressor called for”, which indicates
may be installed in a common panel and located that the compressor motor is electrically
on the plant or on the plantroom wall. energised;
6.185 Control panels containing pneumatic components c. an indicator of the pressure produced by the
should have vents to permit release of pressure in compressor.
the event of component failure. All functions and
indicators should be appropriately identified and Compressor and vacuum starter units
should have a design life of at least five years.
6.193 There should be individual starter units for each
The operating system should be capable of
compressor and vacuum pump, which should
automatically restarting after reinstatement of the
include the features recommended for medical air
power supply.
compressor plants and vacuum plants respectively.
6.186 All components of the PSA supply system should
be connected to the essential electrical supply. The Molecular sieve control unit
control system should ensure that compressors 6.194 The molecular sieve control unit may be mounted
restart in sequence to avoid overloading the on the molecular sieve columns or may be located
essential power supply. with the plant control unit. There should be
separate power supplies for the “duty” and “stand-
Plant control unit
by” sieve assemblies, taken from the same phase.
6.187 The plant control unit should have a separate
6.195 The vacuum pump, if provided, forms part of the
power supply for each compressor and vacuum
molecular sieve system.
pump, controlled by a separate sub-circuit. The
design should be such that no single component 6.196 The molecular sieve control unit should contain
failure in the control unit will result in loss of the following:
plant output. a. a duty selector switch;
6.188 The unit should allow either manual selection of b. an on/auto selector switch;
duty/stand-by for each of the compressors or have
an automatic sequence selection with a means for c. individually-fused, separate cycling systems for
manual override. The unit should ensure that two each sieve pair;
or more compressors do not start simultaneously d. a system to control regeneration of the sieves in
when power is applied. relation to pipeline demand;

63
Medical gases – HTM 02-01 Medical gas pipeline systems – Part A: Design, installation, validation and verification

e. oxygen concentration, dryness and pressure (iii) overload tripped;


sensors;
(iv) activation of any of the safety devices
f. an automatic changeover to the stand-by supplied by the manufacturer;
molecular sieve system, in the event of failure
(v) oxygen concentration failure;
of the duty unit by oxygen concentration,
dryness or pressure. This requires: (vi) pressure fault;
(i) electrical and pneumatic isolation of the c. plant emergency:
“duty” sub-assembly so that it is taken off- (i) oxygen concentration failed at below 94%
stream; concentration;
(ii) electrical and pneumatic energisation of (ii) receiver pressure 0.5 bar (gauge pressure)
the “stand-by” sub-assembly so that it is below the stand-by cut in pressure;
brought on-stream;
(iii) dryness above 67 ppm (–46°C at
(iii) activation of the appropriate fault atmospheric pressure);
indicator and associated volt-free contacts;
d. pressure fault (cylinder reserve):
(iv) the sub-assembly to remain in this mode
of operation until the fault has been (i) pressure in either bank below 50% (of
rectified; normal cylinder pressure);
g. green function indicators for each dryer sub- e. pressure fault (pipeline):
assembly to indicate: (i) low pipeline pressure;
(i) molecular sieve 1 selected; (ii) high pipeline pressure.
(ii) molecular sieve 2 selected;
Plant status indicator unit
(iii) selected molecular sieve – “normal”;
6.198 In addition to the plant control indication, there
(iv) selected molecular sieve – “failed” should be a plant status indicator panel, which
(this fault indicator should remain until may be mounted on the plantroom wall or
manually reset by means of a reset button); adjacent to either the compressor starter unit or
h. a fail-safe system that, on failure of the power the plant control unit. It should have a warning
supply, causes the closure of all inlet, outlet, notice that complies with BS 5499-5:2002 to
exhaust and purge valves. indicate the presence of low voltage.
6.199 There should be indicators for each compressor to
Plant status monitoring show the following conditions:
6.197 A monitoring system must be provided to detect a. green “mains supply on”;
the following faults in the air compressor system:
b. yellow “control circuit failed”;
a. plant faults (for each compressor):
c. yellow “overload tripped”;
(i) control circuit failed;
d. yellow “after-cooler temperature high”;
(ii) overload tripped;
e. yellow “compressor temperature high”;
(iii) after-cooler temperature high;
f. yellow for each individual safety device
(iv) compressor temperature high; provided by the manufacturers;
(v) compressor run-up time too long; g. yellow “compressor failure”.
(vi) activation of other safety devices supplied 6.200 There should be indicators for each molecular
by the manufacturers; sieve dryer system to show the following:
b. plant faults (for each molecular sieve unit): a. green “mains supply on”;
(i) control circuit failed; b. yellow “oxygen concentration fault”;
(ii) “vacuum pump called for”; c. yellow “pressure fault”;

64
6 Oxygen systems

d. yellow “dryness fault”. 6.203 Alternatively, volt-free, normally closed contacts


rated at 5 V dc and 50 mA should be provided for
(When the stand-by dryer is in operation,
transmission of conditions (b) to (e) to the alarm
conditions (b) and (c) in paragraph 6.199 should
system.
be transmitted as a plant emergency either to the
alarm system or to the plant alarm signal status 6.204 The panel can be incorporated into the plant
unit.) indicator unit, or be a separate unit within the
plantroom. If mounted separately, the cabling
Alarm signal status unit should be monitored for open/short circuit. In the
6.201 An alarm signal status unit should be provided as event of such a cabling fault, a red “system fault”
part of the control system. It should display the lamp should be illuminated on the alarm signal
following conditions: status unit, together with the appropriate alarm
condition.
Indication Legends
6.205 The alarm signal status unit should be supplied
a. Green “normal” Normal conditions from all individual plant control units, or from a
b. Yellow “plant fault” Conditions (b)–(f ) separate common supply.
(see paragraph 6.199)
c. Yellow “plant emergency” Conditions (b) or (c), or Plant management
condition (g)
6.206 Connections should be provided that allow
(see paragraph 6.199)
monitoring (but not control) of the plant
d. Yellow “emergency supply Emergency supply bank(s) operation. For example:
low” low (<50%)
e. Red “pipeline pressure fault” Pressure fault • compressor – “on”, “off ”, “on-load”,
“unloaded”;
f. Red “pipeline concentration Oxygen concentration
below 94% O2 fault • molecular sieves – “on” or “off ”.
Conditions (b) to (e) should be transmitted to the central 6.207 These connections should be used to provide input
alarm system.
to the hospital energy management and building
6.202 Where relays are used, they should be normally management systems.
energised relays, which de-energise under fault
conditions, with contacts having a minimum
rating of 50 V dc and 50 mA.

65
Medical gases – HTM 02-01 Medical gas pipeline systems – Part A: Design, installation, validation and verification

7 Medical compressed air systems

General third means of supply, an automatic


manifold(s), will supply the distribution system
7.0 Medical compressed air can be derived from at some point close to or within the building;
compressor systems or by mixing gaseous oxygen
and nitrogen from cryogenic liquid supply sources; • Figure 26 shows a combined medical and
air produced by this latter method is referred to as surgical air system with automatic emergency
synthetic air. reserve manifolds (located in separate
accommodation).
Compressor systems 7.4 Other plant layouts are possible depending upon
7.1 Medical and surgical air can be provided from a the specific design requirements.
single combined system or from separate plants.
The choice ultimately depends on the relative Quality
consumption. 7.5 The European Pharmacopoeia (Ph. Eur.) specifies
7.2 In the case of surgical air, consumption is at a high maximum impurity levels for carbon monoxide. It
flow at a high pressure (up to 350 L/min) but for may be necessary to make provision to control the
relatively short periods of time (minutes); also, levels of contaminants and to monitor the supply
very small numbers of terminal units are in to ensure conformance with the specification.
simultaneous use, typically fewer than five. Air European Commission directive 2001/83/EC
for respirable purposes, however, is used at much specifies that medicinal products should be
lower flows (typically less than 80 L/min) but, manufactured to the approved standard.
particularly in the case of patient ventilation,
use can be continuous. Moreover, in the case of Siting
medical air there are considerably greater numbers 7.6 The plant should have all-round access for
of terminal units in use simultaneously. The maintenance purposes, and allowance should be
installation of separate plants therefore can result in made for changing major components.
lower running costs. Requirements for separate
surgical air systems are given in Chapter 8. 7.7 The siting of the plant should allow for adequate
flows of air for three different purposes:
7.3 Some plant configurations are shown in
Figures 23–26: a. air intake to the compressors;
• Figure 23 shows a duplex system with fully b. cooling of the compressed air by the after-
automatic emergency reserve manifold (the coolers;
manifold is located in separate accommodation); c. cooling of the compressors.
• Figure 24 shows a triplex system, each of the
compressors to be capable of supplying the total Compressor noise
design flow. It should be assumed that the third
7.8 The noise level produced by the compressors will
means of supply, an automatic manifold(s), will
increase with the capacity of the supply system.
supply the distribution system at some point
The maximum free-field noise level for unsilenced
close to or within the building;
compressed air plant, at 1 m from the plant, varies
• Figure 25 shows a quadruplex system, each with the type and power of the plant but should
compressor being capable of supplying 50% of not normally exceed the following values:
the design flow. It should be assumed that the

66
7 Medical compressed air systems

Figure 23 T
 ypical duplex medical air 400 kPa plant and energy reserve manifold (reproduced by kind
permission of MEDÆS)
Pressure
safety
Inlet filter Pressure valve
Air Pressure gauge
Temperature
intake switch Fusible
switch

receiver 1
plug
Compressor 1 Non-return Ball
Aftercooler

Air
valve valves
Ball valve
Ball valve
Pressure Flexible
safety Ball connection Ball
valve valves valves
Automatic Automatic
drain drain
*1 *1
Inlet filter
Air Pressure
Pressure Temperature
intake switch safety
switch valve
Compressor 2 Non-return Pressure Fusible
Aftercooler
valve gauge plug

receiver 2
Ball valve
Pressure Flexible Ball

Air
safety Ball connection valves
valve valves Ball valve
Automatic
drain Ball
*1
valves
Automatic
Silencer drain
Notes: *1
1. Drains marked *1 should be fed to an oil/water separator
2. Filters marked *2 are activated carbon to remove hydrocarbon vapours Shut-off
valve Ball valve
3. Dryer control systems may incorporate shuttle valves as shown, or
may use other suitable arrangements of directional control valves Dryer 2 column 2
4. Symbols to BS 2971:1993/ISO 1219-1:1991
Bacteria Dust/Carbon Shut-off Oil Water
Pressure filter filter valve filter separator
safety *2
valve
Non-return *1 *1
Pressure valve
Pressure regulator
gauge Ball Ball valve
valve Ball Dryer 2 column 1
valve
Distribution Supply Ball Shut-off
valve Pressure valve Ball
System System switch valve
Silencer
Ball valve Pressure Flow
Flow Dewpoint transducer restrictor
Non-return restrictor transducer P
Lockable valve
valve D Silencer
Ball
Terminal Ball Shut-off valve
unit valve valve
Ball
Ball valve Dryer 1 column 2
valve
Pressure
gauge Bacteria Dust/Carbon Shut-off Oil Water
filter filter valve filter separator
*2
Pressure
safety
valve Non-return *1 *1
Pressure valve
regulator
Ball valve
Dryer 1 column 1
Shut-off
valve
Ball Terminal
Emergency Lockable unit
Supply valve valve Silencer

Pressure Non-return Pressure


Pressure
Pressure switch valve gauge switch Pressure
gauge gauge
Pressure Pressure Pressure Pressure
Sintered regulator regulator Ball regulator regulator Sintered
Ball
filter valves valve filter

Shut-off Shut-off
valve valve
Pressure
switch
Pressure Ball Pressure
safety valve Pressure safety
valve safety valve
valve

Non-return valve
Exhaust
(piped to safe position)
Tailpipe

Cylinder valve

Cylinder

67
Medical gases – HTM 02-01 Medical gas pipeline systems – Part A: Design, installation, validation and verification

Figure 24 Typical triplex medical air 400 kPa system (reproduced by kind permission of MEDÆS)
Inlet filter
Air Pressure
intake Temperature
switch switch Pressure
Non-return safety
Compressor 1 Aftercooler valve
valve Pressure
gauge
Ball valve Fusible
Pressure Flexible plug

receiver 1
safety Ball connection Ball

Air
valve valves valves
Ball valve
Automatic
drain
*1
Ball
Inlet filter valves
Air Pressure Automatic
intake Temperature
switch switch drain
*1
Compressor 2 Aftercooler Non-return
valve
Pressure
safety
Ball valve valve
Pressure Flexible
safety Ball connection Pressure
valve Fusible
valves gauge plug
Automatic

receiver 2
drain Ball

Air
*1 valves
Inlet filter Ball valve
Air Pressure
intake Temperature
switch switch
Ball
Compressor 3 Aftercooler Non-return valves
valve Automatic
drain
Ball valve *1
Pressure Flexible
safety Ball connection
valve valves

Automatic Ball valve


drain
*1

Silencer
Notes:
1. Drains marked *1 should be fed to an oil/water separator
Shut-off
2. Filters marked *2 are activated carbon to remove hydrocarbon vapours valve
3. Dryer control systems may incorporate shuttle valves as shown, or
may use other suitable arrangements of directional control valves
Dryer 2 column 2
4. Symbols to BS 2971:1993/ISO 1219-1:1991

Bacteria Dust/Carbon Shut-off Oil Water


Pressure filter filter valve filter separator
*2
safety
valve
Non-return *1 *1
Pressure valve
Pressure regulator
gauge Ball valve
Ball Dryer 2 column 1
valve Ball
valve
Ball Shut-off
Distribution Supply valve Pressure valve Ball
System System valve
switch

Non-return Silencer
Ball valve valve Pressure Flow
transducer restrictor
Flow Dewpoint
restrictor transducer P
Lockable
valve D Silencer
Ball
Terminal Ball Shut-off valve
unit valve valve
Ball
Ball valve Dryer 1 column 2
valve
Pressure
gauge
Bacteria Dust/Carbon Shut-off Oil Water
filter filter valve filter separator
*2
Pressure
safety
valve Non-return *1 *1
Pressure valve
regulator
Fully Automatic
Emergency Reserve Ball valve
Dryer 1 column 1
Manifold
(see duplex schematic Shut-off
for detail) valve

Silencer

68
7 Medical compressed air systems

Figure 25 Typical quadruplex medical air 400 kPa plant (reproduced by kind permission of MEDÆS)
Inlet filter
Air Pressure
intake Temperature
switch switch
Compressor 1 Aftercooler Non-return
valve

Ball valve
Pressure Flexible
safety Ball connection
valve valves

Automatic
drain
*1
Inlet filter
Air Pressure
intake Temperature
switch switch Pressure
Non-return safety
Compressor 2 Aftercooler valve
valve Pressure
gauge
Ball valve Fusible
Pressure Flexible plug

receiver 1
safety Ball connection Ball

Air
valve valves valves
Ball valve
Automatic
drain
*1
Ball
Inlet filter valves
Air Pressure Automatic
intake Temperature
switch switch drain
*1
Compressor 3 Aftercooler Non-return
valve
Pressure
safety
Ball valve valve
Pressure Flexible
safety Ball connection Pressure
valve Fusible
valves gauge plug
Automatic

receiver 2
drain Ball

Air
*1 valves
Inlet filter Ball valve
Air Pressure
intake Temperature
switch switch
Ball
Compressor 4 Aftercooler Non-return valves
valve Automatic
drain
Ball valve *1
Pressure Flexible
safety Ball connection
valve valves

Automatic Ball valve


drain
*1

Silencer
Notes:
1. Drains marked *1 should be fed to an oil/water separator
Shut-off
2. Filters marked *2 are activated carbon to remove hydrocarbon vapours valve
3. Dryer control systems may incorporate shuttle valves as shown, or
may use other suitable arrangements of directional control valves
Dryer 2 column 2
4. Symbols to BS 2971:1993/ISO 1219-1:1991

Bacteria Dust/Carbon Shut-off Oil Water


Pressure filter filter valve filter separator
*2
safety
valve
Non-return *1 *1
Pressure valve
Pressure regulator
gauge Ball valve
Ball Dryer 2 column 1
valve Ball
valve
Ball Shut-off
Distribution Supply valve Pressure valve Ball
System System valve
switch

Non-return Silencer
Ball valve valve Pressure Flow
transducer restrictor
Flow Dewpoint
restrictor transducer P
Lockable
valve D Silencer
Ball
Terminal Ball Shut-off valve
unit valve valve
Ball
Ball valve Dryer 1 column 2
valve
Pressure
gauge
Bacteria Dust/Carbon Shut-off Oil Water
filter filter valve filter separator
Pressure *2
safety
valve Non-return *1 *1
Pressure valve
regulator
Fully Automatic
Emergency Reserve Ball valve
Dryer 1 column 1
Manifold
(see duplex schematic Shut-off
for detail) valve

Silencer

69
Figure 26 Typical duplex combined medical and surgical plant with emergency reserve manifolds (reproduced by kind permission of MEDÆS)
70

Medical gases – HTM 02-01 Medical gas pipeline systems – Part A: Design, installation, validation and verification
Notes:
1. Drains marked *1 should be fed to an oil/water separator
2. Filters marked *2 are activated carbon to remove hydrocarbon vapours
Pressure Silencer
3. Dryer control systems may incorporate shuttle valves as shown, or
safety
Inlet filter Pressure valve may use other suitable arrangements of directional control valves
Shut-off
Air Pressure gauge 4. Symbols to BS 2971:1993/ISO 1219-1:1991 valve
intake Temperature
switch switch Fusible

receiver 1
plug Dryer 2 column 2
Compressor 1 Aftercooler Non-return Ball

Air
valve valves
Ball valve Bacteria Dust/Carbon Shut-off Oil Water
Ball valve filter filter valve filter separator
Pressure Flexible Pressure *2
safety Ball connection Ball safety
valve valves valves valve Non-return *1 *1
Pressure valve
Automatic Automatic Pressure regulator
drain drain
*1 gauge Ball Ball valve
*1 Dryer 2 column 1
valve Ball
Inlet filter valve
Air Pressure Ball Shut-off
Pressure Temperature safety
intake switch valve Pressure valve Ball
switch valve switch valve
Compressor 2 Aftercooler Non-return Pressure Fusible Silencer
valve gauge plug Ball valve Pressure Flow
transducer restrictor

receiver 2
Ball valve Flow Dewpoint
Pressure Flexible Ball Non-return restrictor transducer P

Air
safety connection valves Non-return valve
Ball valve D Silencer
valve valves Ball valve
Ball
Automatic Ball Shut-off valve
Pressure
drain valve valve
*1 safety Ball Ball
valve valves Ball valve Dryer 1 column 2
Exhaust Pressure Automatic valve
regulator drain Pressure
*1 gauge Bacteria Dust/Carbon Shut-off Oil Water
Surgical Air filter filter valve filter separator
Ball valve Distribution System Pressure *2
Non-return Pressure Ball Ball safety
valve gauge valves valves valve Non-return *1 *1
Medical Air Pressure valve
Distribution System regulator
Ball valve
Exhaust Pressure Dryer 1 column 1
safety Shut-off
valve
valve
Emergency Ball Ball Terminal Emergency Ball Lockable Terminal
Medical Air Supply valve valve unit Surgical Air Supply valve valve unit
Silencer

Pressure Non-return Pressure Pressure Pressure Non-return Pressure Pressure


Pressure switch valve gauge switch Pressure Pressure switch valve gauge switch Pressure
gauge gauge gauge gauge
Pressure Pressure Pressure Pressure Pressure Pressure Pressure Pressure
Sintered regulator regulator regulator regulator Sintered Sintered regulator regulator Ball Ball regulator regulator Sintered
filter Ball Ball filter filter filter
valves valve valves valve

Shut-off Shut-off Shut-off Shut-off


valve valve valve valve
Pressure Pressure
switch switch
Pressure Pressure Pressure Pressure
safety Ball safety safety Ball safety
valve Pressure valve Pressure
valve valve valve valve
safety safety
valve valve

Non-return valve Non-return valve


Exhaust Exhaust
(piped to safe position) (piped to safe position)
Tailpipe Tailpipe

Cylinder valve Cylinder valve

Cylinder Cylinder
7 Medical compressed air systems

Reciprocating Screw Vane Power 7.12 Air-inlet filters should be fitted immediately
upstream of the compressor. In exceptional
85 dBA 76 dBA 76 dBA 0–7.5 kW
circumstances, additional screens, filters and
89 dBA 78 dBA 76 dBA 7.6–15 kW silencers may be required. The filters should
93 dBA 80 dBA 79 dBA 15.1–22 kW comply with BS ISO 5011:2000 and be either dry
97 dBA 92 dBA 90 dBA 22.1–60 kW medium filters or grade CA paper element filters.
7.9 In noise-sensitive areas, an acoustic enclosure
should be included in the purchase specification for Compressor types
all compressors. Such an enclosure should produce 7.13 There are many different types of compressor
a reduction of at least 10 dBA in the free-field noise currently available, the most common types being:
level at 1 m.
a. reciprocating piston compressors;
Air intake b. rotary vane compressors;
7.10 The position of an air intake can have a c. rotary screw compressors.
considerable effect on delivered air quality, 7.14 The compressors may be of any type, provided they
particularly with respect to levels of carbon are suitable for continuous running on load and
monoxide. The air intake for a compressor should for high frequency start/stop operation. When
be located to minimise contamination from selecting compressors, the opportunity should
internal combustion engine exhausts and the be taken to maximise energy efficiency. If
discharge from vacuum systems, AGSS and reciprocating compressors are used, they may be
ventilation systems or other sources of either of the single- or of the two-stage type,
contaminants. Air intakes should be ducted where although for a 400 kPa system a single-stage
necessary to avoid contamination; a minimum compressor is usually satisfactory.
height of 5 m above ground level should ensure a
reasonable quality of intake air. Where this cannot
be achieved, additional filtration and/or air
Compressor lubrication
treatment may be necessary. If the siting of the 7.15 Compressors may be oil-lubricated, provided that
compressor, regardless of the air intake location, is suitable arrangements are made to ensure that the
considered subject to a risk of aspirating toxic air quality specification given in Table 29 is
fumes and smoke as a result of a fire, an automatic fulfilled.
shutdown system, linked to local smoke detectors,
7.16 Rotary compressors are sealed and cooled by oil
can be installed. If such a system is planned, it is
or water. Oil control is therefore essential and is
essential that an automatic emergency supply
usually provided as an integral part of the
manifold system is sited well away from the fire-risk
compressor. Reciprocating compressors may be oil-
area and is arranged to come on-line automatically
lubricated, carbon ring, PTFE ring or diaphragm-
in the event of plant shutdown.
sealed type.
7.11 Care is needed when extending compressor air
7.17 Oil-free compressors may be beneficial in reducing
intakes. Manufacturers’ data should be consulted
filtration requirements.
to ensure that intake flow, and hence compressor
performance, are not adversely affected by excessive 7.18 Water should not be used as a sealant because of
lengths of intake ducting. Choice of intake material risk of microbial contamination and potential
is also important. Often, intakes are constructed problems with water treatment.
from solvent-welded PVC. In a fire, toxic materials 7.19 There is a danger that PTFE rings and lubricating
from the burning intake could be drawn into the oils could decompose at high temperatures to form
air compressor and distributed throughout the toxic products. This may be countered by fitting a
system. In addition, there is a risk that inadequate temperature sensor to the cylinder head or output
solvent drying time before use of the intake will of the compressor with suitable controls to cut off
result in toxic solvent fumes being drawn into the the power supply to the compressors if excessive
system. Corrosion-resistant ducting (for example temperatures are sensed. BS EN ISO 15001
stainless-steel flue liner) is a suitable material. specifies the requirements for selecting materials
used in medical supply equipment.

71
Medical gases – HTM 02-01 Medical gas pipeline systems – Part A: Design, installation, validation and verification

7.20 On start-up, when oil is used as the sealant, After-coolers


moisture condensing at high pressure forms an
emulsion with the oil. Once operating temperature 7.23 After-coolers (and inter-coolers) usually form part
is reached, water is readily separated. Because it is of the compressor sub-assembly. After-coolers
impossible to match the varying demand with plant should be fitted to oil-lubricated medical air
capacity, it may be necessary to include oil heaters compressor systems. These will normally be
to avoid emulsification. If it is intended to omit oil air-cooled, and may need ducting with forced
heaters, manufacturers should be asked to confirm ventilation to ensure an adequate supply of cooling
the suitability of the compressor for intermittent air.
operation. Oil-lubricated compressors, however,
are considered to be satisfactory. Receivers
7.21 Where oil-lubricated compressors are used, suitable 7.24 Air receivers should comply with BS EN 286-1:
means of separating oil from condensate is 1998 for all vessels up to 10,000 bar litres, and
essential. should be supplied with test certificates. The
minimum water capacity of the receivers should be
7.22 Once a compressor installation has been selected: 50% of the compressor output in 1 minute, stated
a. the plant should include at least two in terms of free air delivered at normal working
compressors, but additional compressors may pressure. Receivers should also be fitted with an
be included provided that in all cases the total automatic drain. Electrically operated automatic
capacity will provide 100% of system design drains have been found to be more reliable.
flow with one compressor not running; 7.25 To facilitate the statutory inspection, there should
b. the individual compressors should be arranged be either two suitably valved air receivers or a by-
so that they will supply the system pass arrangement (for use in manual operating
simultaneously if necessary; mode only) in order to avoid interruption to the
supply. Alternatively the tertiary supply manifold
c. the relative magnitude of the capital and
can be used.
running costs should be evaluated at the time of
purchase. Too much emphasis has been placed 7.26 For systems that have a design flow in excess of
on low capital cost at the expense of reliability 500 L/min, two receivers should be provided with
and high power costs. The running costs should valve arrangements to permit isolation of one or the
be calculated at realistic levels of usage; other for inspection purposes.
d. the control system for the compressor plant
should include an “hours-run” counter and Air treatment and filtration
should be constructed in accordance with the
General
guidelines given below;
7.27 Contaminants can enter the compressed air system
e. the efficiency of plant, expressed as the volume
from three sources: the atmosphere, the compressor
of air delivered to the pipeline distribution
and the pipeline distribution system. Each potential
system (after losses in the drying system and
source must be taken into account when specifying
filtration system) per kilowatt-hour (kWh),
the type and location of air treatment equipment.
should be stated by the supplier of the system.
Filtration equipment may include pre-filters,
The testing procedure should evaluate this
coalescing filters, adsorption equipment, carbon
efficiency by testing the power consumption
filters, particulate filters and any other additional
over a suitable period of time at 100%, 10%
filtration equipment necessary to ensure the quality
and 0% of the system design flow. A minimum
of the product.
efficiency of 5 m3/kWh at 100% and 10% is
required. The power consumption at zero flow
Solid contaminants
should be less than 1% of that at 100% design
flow. 7.28 Particles in the environment cover a wide range of
sizes, but approximately 80% are less than 0.2 µm
and are therefore not removed by the intake filter
to the compressor.

72
7 Medical compressed air systems

7.29 Although particles smaller than 40 µm are unlikely well-maintained oil-lubricated compressors, it is
to cause mechanical damage, a 5 µm intake filter unlikely to exceed 5 mg/m3 due to the high-
is preferred to avoid blockage of internal air/oil efficiency oil/air separator.
separators.
7.36 Oil-contaminated compressor condensate is
7.30 Filters are specified in terms of performance classified as a trade effluent by virtue of Chapter 14
tests – a sodium flame test, a DOP (dispersed oil of the Public Health (Drainage of Trade Premises)
particulate) test etc. Act 1937. An oil condensate separator should
therefore be installed.
Water
7.37 Under Chapter 85 of the Water Resources Act
7.31 Water is always a contaminant in a compressed air 1991, it is illegal to make a discharge of trade
system, regardless of the type and location of the effluent to “controlled waters” via a surface water
compressor plant, since the air drawn into the drain without the consent of the Environment
compressor intake is never completely free of water Agency.
vapour. The amount can vary from 2.5 g/m3 to
7.38 Similarly, under the Water Industry Act 1991, local
over 40 g/m3 depending on the climatic
water companies enforce the limit of oil condensate
conditions. The after-cooler and receiver remove
discharged into the public foul sewer. Prior consent
some of this, but about 20 g/m3 is likely to remain
to discharge is mandatory.
in the compressed air unless removed by dryers.
7.39 Condensate from oil-free compressors may be
7.32 A water content not exceeding 67 vpm (volume
discharged to drain.
parts per million – equivalent to dew-point –46°C
at atmospheric pressure) is specified for medical air 7.40 Any condensate produced from the compressor/
pipeline systems. Only desiccant dryers can usually dryer system must be regarded as trade effluent and
achieve this. A variety of desiccant types are is therefore not suitable for discharge to any surface
available. Activated alumina and silica gel are water system draining to any surface water sewer,
commonly employed. Molecular sieve desiccants water-course or soak away; this may not apply if a
employing zeolites can also be used, but on suitable separator is installed. Maximum oil content
occasions it has been found that this material has limits range from region to region, from 25 mg/L
produced air with an increased oxygen content, in up to 500 mg/L; the local water company should
the order of 24%. Refrigerant dryers can perform be consulted.
satisfactorily down to a pressure dew-point of +3°C
(atmospheric dew-point –20°C) and are therefore Dryer controls
not recommended as the sole form of drying. 7.41 The dryer control system should ensure that
regeneration is operated in proportion to the
Oil
compressed air usage. The effectiveness of the
7.33 With oil-lubricated compressors, it is inevitable control system will become apparent when the
that the compressed air will contain oil. Even with efficiency of the compressor system is tested at
oil-free compressors (non-lubricated), complete 10% and 0% of the system design flow. Evidence
freedom from oil and oil vapour cannot be of the reliability and performance of a dryer system
positively guaranteed, as hydrocarbon vapours may should be sought from manufacturers, since these
be drawn into the compressor. Oil levels in the air items are critical to the overall performance of the
supply must be controlled to 0.1 mg/m3 with compressor system. The dryer control system
means of monitoring on a routine basis. should include a dew-point hygrometer and display
with a minimum accuracy of ±3°C in a range from
7.34 Oil will exist in the system in three forms: bulk
–20°C to –60°C atmospheric dew-point, with a set
liquid, oil aerosol and oil vapour. Provided that the
point of –46°C. It should be arranged that in the
oil lubricant is appropriate and the after-cooler
event of open circuit, a “plant emergency” alarm be
properly designed, the amount of oil present as
initiated.
vapour should be small and is unlikely to exceed
0.5 mg/m3.
Dust filters
7.35 The amount of oil that is present as bulk liquid and
7.42 There should be a dust filter downstream of the
aerosol is more difficult to predict. With modern,
dryers to remove particles down to 1 µm, with a

73
Medical gases – HTM 02-01 Medical gas pipeline systems – Part A: Design, installation, validation and verification

DOP penetration of less than 0.03%, when tested 7.48 All safety valves should be of the closed-bonnet
in accordance with BS EN ISO 3549:2002. type and connected to suitably sized pipework to
allow safe discharge, not necessarily to the outside.
7.43 Each dryer and filter assembly should be rated for
continuous use at the system demand flow, with air
at 100% relative humidity at 35°C. Traps, valves and non-return valves

Activated carbon filter Automatic drainage traps

7.44 Duplex activated carbon filters should be installed 7.49 Electrically- or mechanically-operated automatic
upstream of the final bacteria filter for odour drainage traps should be provided on the after-
removal. coolers, receiver, separators and coalescing filters.
The discharge from these drainage traps should
Bacteria filters be piped to a suitable gully via an oil separator.
Co-ordination with building work is required for
7.45 Duplex bacteria filters should be fitted upstream this provision. Electrically-operated automatic
of the final pressure regulator with appropriate drains have been found to be more reliable.
isolating valves. The filters should provide particle
removal to 0.01 mg/m3 and a DOP penetration of 7.50 Drainage and tundishes are usually provided
less than 0.0001%. under the building contract. Separators should
be provided under the air compressor contract.
Pressure control Provision of interceptor tanks may be made under
either the building contract or the air compressor
7.46 The pressure control should maintain the nominal contract, as appropriate.
pipeline pressure within limits given in Chapter 4.
7.51 Non-return valves are required to prevent backflow
Duplex line pressure regulators should be provided
with suitable isolating valves. The regulators should of the air supply in certain situations. These valves
be of the non-relieving type. should be located as follows:
a. between the compressor and the receiver, but
Safety valves downstream of any flexible connector;
7.47 Safety valves should be provided in accordance with b. downstream of the dust filter on the dryer;
the requirements given in (a)–(c) below. All safety
valves should conform to BS EN ISO 4126- c. upstream of the emergency cylinder reserve
1:2004. A safety valve of the certified discharge connection in the pipeline connecting the plant
capacity stated should be fitted in each of the to the pipeline distribution system, to prevent
following positions: back-feeding this plant;

a. on the delivery pipe of each compressor and d. upstream of any inlet point that may be used to
upstream of any isolating valve, non-return feed the system in an emergency;
valve or after-cooler, capable of discharging the e. downstream of the emergency cylinder manifold
total throughput of the compressor; regulators.
b. on each air receiver and dryer tower, capable of
Isolating valves
discharging the sum of the throughput of all the
compressors. It is not necessary to provide safety 7.52 Isolating valves should be provided downstream of
valves on the dryer columns where the system non-return valves and upstream of, for example,
is already protected by a safety valve on the the connection of the emergency reserve manifold.
receiver and the downstream equipment, that is, Isolating valves should be provided in order to
if the dryer column is already sufficiently facilitate maintenance or replacement of plant
protected; items.
c. immediately downstream of each pressure 7.53 Manually-operated ball isolation valves should be
regulator, capable of discharging the system located in the positions shown in Figures 23–26 to
demand flow. allow isolation of components such as receivers,
dryers, automatic drains, pressure regulators and
filters. There should also be a valve on the

74
7 Medical compressed air systems

compressed air plant, downstream of the plant non- plant or on the plantroom wall. Control panels
return valve and the connection of the cylinder containing pneumatic components should have
manifold supply. vents to permit release of pressure in the event
of component failure. All indicators should be
Pressure indicators appropriately identified and should have a design
7.54 Pressure indicators should comply with BS EN life of at least five years.
837-1:1998 or have an equivalent performance 7.60 The operating system should be capable of
if electronic indicators are used. Calibration automatically restarting after reinstatement of the
should be in bar or kPa. All gauges should have a power supply.
minimum scale length of 90 mm, and the working
7.61 All components of the medical air supply system
range should not exceed 65% of the full-scale range
should be connected to the essential electrical
except on differential pressure gauges. Pressure
supply. The control system should ensure that
indicators should be connected by means of gauge
compressors restart in sequence to avoid
cocks.
overloading the power supply.
7.55 Pressure indicators should be located:
Plant control unit
a. on the plant control unit indicating receiver
pressure; 7.62 The plant control unit should have a separate
power supply for each compressor, controlled by a
b. on each receiver;
separate sub-circuit.
c. downstream of each pressure regulator;
7.63 The unit should allow either manual selection of
d. on each dryer tower; duty/stand-by for each of the compressors or have
e. on the plant pipework, upstream of the plant an automatic sequence selection with a means for
isolating valve. manual override. The unit should ensure that two
or more compressors do not start simultaneously
7.56 Differential pressure indicators should be located when power is applied.
on:
7.64 A warning notice that complies with BS 5499-5:
a. each coalescing filter; 2002 should be affixed which indicates the
b. each dust filter; presence of low voltage.

c. each bacteria filter; Plant control indication


or any combination, as appropriate. 7.65 There should be indicators for each compressor as
7.57 Except for pressure gauges, all control and follows:
measuring devices should be connected directly to a. green “mains supply on”;
the pipework via a minimum leak device (to allow
removal for servicing) and not isolated by valves. b. green “compressor called for”, which indicates
that the compressor motor is electrically
energised;
Operating and indicating system
c. an indicator of the pressure produced by the
7.58 The operating and indicating system should
compressor.
perform the following functions:
a. overall plant control and indication; Compressor starter units
b. individual compressor starting; 7.66 There should be individual starter units for each
compressor which operate a single designated
c. control of dryers;
compressor. The starters should be provided with
d. plant status monitoring. safety interlocks, as specified by the compressor
manufacturers, which should inhibit plant
7.59 Provided that the individual compressor starters are
operation until manually reset by means of a
housed in a separate compartment, these functions
button. The starters should allow automatic restart
may be carried out by separate units or may be
after an interruption to the power supply. Each
installed in a common panel and located on the
starter unit should contain the following:

75
Medical gases – HTM 02-01 Medical gas pipeline systems – Part A: Design, installation, validation and verification

a. an isolator interlocked with the covers; (iv) the sub-assembly to remain in this mode
of operation until the fault has been
b. either HRC (high rupturing capacity) fuses to
rectified;
BS 88 or suitable circuit breakers to BS EN
60947-2:2003 and/or BS EN 60898-1:2003;
Note
c. an industrial grade ammeter to BS EN 60051-
1:1999, IEC 60051-1:1997 (digital ammeters of In the event of power supply failure, all drain and vent
similar accuracy to those compliant with BS EN valves should fail “closed”, and all inlet and outlet
60051-1:1999, IEC 60051-1:1997 may be valves should fail “open”.
used);
g. green function indicators for each dryer sub-
d. a “total hours” counter if not included in the assembly to indicate:
plant control unit;
(i) dryer 1 selected;
e. a green “mains supply on” indicator if mounted
separately from the plant control unit. (ii) dryer 2 selected;
(iii) selected dryer – “normal”;
Dryer control unit
(iv) selected dryer – “failed” (this fault
7.67 The dryer control unit may be mounted on the indicator should remain until manually
dryers or may be located with the plant control reset by means of a reset button);
unit. There should be separate power supplies for
the duty and stand-by dryer assemblies taken from h. a fail-safe system which on failure of the power
the same phase. supply causes the following:

7.68 The dryer control unit should contain the (i) closure of the exhaust and purge valves;
following: (ii) opening of the inlet and outlet valves.
a. a duty dryer selector switch;
Plant status monitoring
b. a service function – to enable selection of
7.69 A monitoring system should be provided to detect
continuous/normal running;
the following faults in the air compressor system:
c. individually fused, separate cycling systems for
a. plant faults (for each compressor):
each dryer;
(i) control circuit failed;
d. a system to control regeneration of the dryers in
relation to pipeline demand; (ii) motor tripped;
e. a hygrometer and display with a minimum (iii) after-cooler temperature high;
accuracy of ±3°C in a range from –20°C to
(iv) compressor temperature high;
–60°C (set to –46°C atmospheric dew-point)
and a pressure sensor; (v) compressor failed to go on load;
f. an automatic changeover to the stand-by dryer (vi) activation of other safety devices supplied
system in the event of failure of the duty unit by by the manufacturers;
either dryness or pressure. This requires: b. plant faults (for each dryer unit):
(i) electrical and pneumatic isolation of the (i) dryer failure;
duty sub-assembly so that it is taken off-
stream; (ii) pressure fault;
(ii) electrical and pneumatic energisation of c. plant emergency:
the stand-by sub-assembly so that it is (i) receiver pressure 0.5 bar below the stand-
brought on-stream; by cut-in pressure;
(iii) activation of the appropriate fault (ii) receiver pressure 0.5 bar above cut-out
indicator and associated volt-free contacts; pressure;
(iii) dryness above –46°C at atmospheric
pressure;

76
7 Medical compressed air systems

d. pressure fault (cylinder reserve): e. red “pipeline pressure fault” (pressure fault).
(i) pressure in duty bank below 50% (of 7.74 Conditions (b) to (e) should be transmitted to the
normal cylinder pressure); central alarm system. Where relays are used, they
should be normally energised relays that de-energise
e. pressure fault (pipeline):
under fault conditions, with contacts having a
(i) low pipeline pressure; minimum rating of 50 V dc and 50 mA.
(ii) high pipeline pressure. 7.75 Volt-free, normally closed contacts rated at 50 V dc
and 50 mA should be provided for transmission of
Plant status indicator unit conditions (b) to (e) to the alarm system.
7.70 In addition to the plant control indication, there 7.76 The panel can be incorporated into the plant
should be a plant status indicator panel that may indicator unit or be a separate unit within the
be mounted on the plantroom wall or adjacent to plantroom. If mounted separately, the cabling
either the compressor starter unit or the plant should be monitored for open/short circuit. In the
control unit. It should have a warning notice that event of such a cabling fault, a red “system fault”
complies with BS 5499-5:2002 to indicate the lamp should be illuminated on the alarm signal
presence of low voltage. status unit together with the appropriate alarm
7.71 There should be indicators for each compressor to condition.
show the following conditions: 7.77 The alarm signal status unit should be supplied
a. green “mains supply on”; from all individual plant control units or from a
separate common supply.
b. yellow “control circuit failed”;
c. yellow “overload tripped”; Plant management

d. yellow “after-cooler temperature high”; 7.78 Connections should be provided which allow
monitoring of plant alarm conditions (b) to (e)
e. yellow “compressor temperature high”; and pump running for each “compressor”. These
f. yellow for each individual safety device provided connections should be volt-free contacts normally
by the manufacturers; closed for each condition having a minimum rating
of 50 V dc and 50 mA. The building management
g. yellow “compressor failure”. system should not be used to control the plant.
7.72 There should be indicators for each dryer system to
show the following: Synthetic air
a. green “mains supply on”; 7.79 This section provides technical details of the
process and systems required to generate medical
b. yellow “dryness fault”;
air from mixing gaseous oxygen and nitrogen,
c. yellow “pressure fault”. derived from cryogenic supplies.
7.80 For the purposes of the Medicines Act 1968, it is
Alarm signal status unit
considered that the synthetic air is manufactured
7.73 An alarm signal status unit should be provided as on-site, for use on that site only, in exactly the same
part of the control system. It should display the way as for medical air derived from compressor
following conditions: plant. The production of synthetic air implies a
a. green “normal” (normal); manufacturing process, and as such, the process
should be subjected to the same safety requirements
b. yellow “plant fault” conditions ((b)–(g) in of any pharmaceutical process. This should include,
paragraph 7.71); for example, a HAZOP (HAZard and OPerability)
c. yellow “plant emergency” (low reservoir analysis and other safety analyses that may be
pressure/high moisture: that is, condition (b) in necessary.
paragraph 7.71); 7.81 Synthetic air is generated by mixing gaseous oxygen
d. yellow “reserve low” (emergency/reserve banks and nitrogen in a blender or mixing panel at pre-set
low (<50%)); pressures to ensure that the resultant mixture is

77
Medical gases – HTM 02-01 Medical gas pipeline systems – Part A: Design, installation, validation and verification

always correct. Continuous on-line monitoring 7.91 Since four VIEs will be required, the space
of oxygen concentration is provided to check the requirements will need special consideration when
mixture; the system shuts down automatically if the planning the installation of a synthetic air system.
oxygen concentration varies from the specified
7.92 The system comprises:
value.
a. storage vessels – one main vessel and one
7.82 If one mixing system shuts down, the pipeline is
secondary supply vessel for both oxygen and
supplied from the secondary mixing system to
nitrogen;
ensure continuity of supply.
b. vaporisers for both oxygen and nitrogen;
7.83 The feasibility study should provide more
information on the details of the monitoring and c. medical oxygen flow control – where used to
alarm systems required, as well as operational supply medical oxygen systems;
information. d. surgical nitrogen flow control – where required;
7.84 The VIE system supplying the medical oxygen e. a control panel for the nitrogen and oxygen
may be used to supply the synthetic air system, supplies to the mixing panels;
depending on the system demands.
f. duplicate air mixing panels;
7.85 Nitrogen supplied to the synthetic air system
may also be used to provide the power source for g. buffer vessels – each mixer has a buffer vessel to
surgical tools instead of surgical air at 700 kPa. smooth fluctuations in demand;
7.86 An electrical power supply is required in order, for h. a warning and alarm system;
example to operate solenoid valves and monitoring j. duplicate oxygen analysers on each mixer.
instrumentation. Therefore the system should be
connected to the essential power supply and via an 7.93 The system is shown in Figure 27.
uninterruptible power supply (UPS) with at least
four hours’ capacity; this should ensure continuity Storage vessels
of supply in the event of power failure.
Vessel summary
System description 7.94 The following vessels are required:
7.87 The gaseous oxygen and nitrogen are derived a. one main oxygen vessel;
from bulk liquid supplies contained in a VIE – as
described in the “Liquid oxygen systems” section of b. one secondary oxygen vessel with at least
Chapter 6. 24 hours’ capacity;

7.88 The oxygen for synthetic air may be taken from the
c. one main nitrogen vessel;
VIE supplying the medical oxygen system or it may d. one secondary nitrogen vessel with at least
be from a dedicated VIE. It would normally be 24 hours’ capacity.
more cost-effective for the oxygen to be taken from
the main VIE, although this would obviously Vessel operating pressure
depend on the existing VIE capacity, the demand,
7.95 The following operating pressures are required:
space constraints etc. The feasibility study should
provide more detailed information on whether it is a. main vessels: 12.5 bar;
likely to be more cost-effective to provide a totally b. back-up vessels: 12.5–14 bar.
separate VIE system or to use the existing medical
oxygen VIE. Main vessel capacity
7.89 For both the oxygen and nitrogen it is necessary 7.96 The main vessel should normally be sized on
to have a secondary supply system to ensure the basis of two weeks’ supply. This should be
continuity of supply; the system demands are calculated as 14 x the average daily usage. This
such that this should be derived from a second – should provide adequate storage and a cost-effective
normally smaller – VIE. vessel-filling regime. The gas supplier should,
7.90 This secondary oxygen supply can also serve the however, be consulted as there may be other factors,
hospital’s medical oxygen system. such as geographical location, space etc, which need

78
Figure 27 Synthetic air plant

PAL LAL LAL


PI PS
14A 14B

PSH PAL

PI

PSL PAH

Alarm panel
Main storage vessel To hospital
O2 pipeline

Main vaporiser

VIE
O2
Economiser vaporiser Pressure control panel
Third
source of
supply

Back-up storage vessel


Back-up vaporiser

To surgical
N2 supply

VIE O2
N2

Main mixer

7 Medical compressed air systems


To hospital
Main storage vessel med air pipeline

Main vaporiser

N2

VIE
N2
Back-up mixer
Gas control panel
Third
source of
supply

Back-up storage vessel


79

Back-up vaporiser
Medical gases – HTM 02-01 Medical gas pipeline systems – Part A: Design, installation, validation and verification

to be taken into account when sizing the main Medical oxygen flow control
vessels.
7.108 A control panel (similar in principle to a C11
Back-up vessel capacity panel) should be provided – the only difference is
that the secondary supply is taken from a low-
7.97 The stand-by vessel should have 24 hours’ capacity pressure liquid source.
at any time; that is, it should be sized on the basis
of twice the average daily usage. This will ensure
Surgical nitrogen flow control
that there is always 24 hours’ supply available.
7.109 A control panel to regulate the gaseous nitrogen to
7.98 In addition to the normal instrumentation as set
between 7.5 and 9.5 bar, depending on the system
out in the “Liquid oxygen systems” section of
design, should be provided.
Chapter 6, the vessels should be fitted with a
telemetry system to continuously monitor the 7.110 The pipeline distribution system should be
vessel contents. designed in exactly the same way as for surgical air
700 kPa systems, as described in Chapter 8.
7.99 This information should be transmitted direct to
the gas supplier and also the hospital. The exact
details of how much information, and where it Control panel for the nitrogen and
should be received, will depend on each hospital oxygen supplies to the mixing panels
site. 7.111 The control panel should be sized to provide
7.100 The main vessel low level alarm is activated at 25% pressure-regulated flows as appropriate for the
full; the back-up low level alarm is activated at mixing system; this would typically be up to
50% full. 200 Nm3/hr (normal cubic metres per hour).
7.101 The safety relief valves and bursting discs should 7.112 The stand-by supply regulation cuts in when the
be sized in accordance with BCGA CP19. main line pressure falls to 11 bar; there is no
regulation on the main supply line.
7.102 The liquid from the vessels should be supplied to
the process at a nominal pressure of 12.5 bar. 7.113 A non-return valve should be installed in both the
nitrogen and oxygen supply lines within the mixer
Vaporisation to prevent cross-contamination.

7.103 The main and stand-by vessels should have 7.114 A non-return valve should also be installed on
dedicated vaporisers designed for continuous both the main oxygen supply and the stand-by
capacity and 24-hour capacity respectively at 1.5 x oxygen supply to the mixer to prevent the medical
the required flows to ensure that the vaporisers are oxygen line becoming contaminated with
not overdrawn. nitrogen.

7.104 This may be achieved in each case by either a Air mixing panels
single set of vaporisers or by vaporisers operated on
timed or manual changeover. 7.115 A range of sizes of mixing panels is available
with, typically, nominal capacities of 50, 100 and
7.105 It is preferable for the vaporisers to operate on 200 Nm3/hr.
a timed changeover as this avoids the need for
hospital staff to manually operate the changeover 7.116 A regulated supply of nitrogen and oxygen is
valves. blended in a mixing valve. The differential pressure
at the inlet to the mixing panel is critical and
7.106 The timed changeover will require a 110 V or should not exceed 0.5 bar. A pressure-switch-
240 V supply; this should be on the emergency operated solenoid valve opens and shuts on a
supply and a UPS should also be provided, with at 0.5 bar differential.
least 4 hours’ capacity.
7.117 The main mixer solenoid valve opens when the
7.107 Each vaporiser or set of vaporisers must have a line pressure falls to 4.2 bar; the stand-by mixer
safety relief valve. solenoid valve will open if the line pressure
continues to fall to 4.0 bar.

80
7 Medical compressed air systems

7.118 Two independent paramagnetic oxygen analysers 7.124 Conditions (b) to (e) should be transmitted to the
are provided on each mixer to give continuous on- central alarm system. Where relays are used, they
line measurements. should be normally energised relays that de-
energise under fault conditions, with contacts
7.119 If the oxygen concentration falls outside 20–22%
having a minimum rating of 50 V dc and 50 mA.
as measured by either analyser, the mixer solenoid
valve is held closed and the mixer is shut down. In 7.125 Volt-free, normally closed contacts rated at 50 V
addition, a signal is relayed downstream to close dc and 50 mA should be provided for transmission
the solenoid valve on the buffer vessel associated of conditions (b) to (e) to the alarm system.
with that mixer.
7.126 The panel can be incorporated into the mixing
panel control unit or be a separate unit within the
Buffer vessels plantroom. If mounted separately, the cabling
7.120 Each mixer has associated with it a buffer vessel to should be monitored for open/short circuit. If such
smooth fluctuations in demand. a cabling fault occurs, a red “system fault” lamp
should be illuminated on the alarm signal status
7.121 In the event that the oxygen concentration differs unit together with the appropriate alarm
from the specification (that is, 20–22%), the condition.
solenoid valve downstream of the buffer vessel will
also close, preventing air from the buffer vessel
from entering the distribution system.
Emergency supply provision
7.127 A risk assessment should be carried out to establish
7.122 The buffer vessel, together with appropriate means
the vulnerability of the main supply system of both
of safety relief, should be sized to match each
oxygen and nitrogen. Further information is given
mixing panel to provide stable operation.
in Chapter 2 on sources of supply and in
Chapter 6.
Alarm signal status unit
7.123 The same alarm conditions for liquid oxygen Additional use of medical air systems
should also be transmitted and displayed for the
7.128 It is possible to use medical/surgical air as a power
liquid nitrogen system. The following conditions
source for pendant control and braking systems.
should be displayed for the mixing panels:
7.129 These additions must not compromise either
a. green “normal” (normal);
the medical air system or operation of connected
b. yellow “plant fault” (low gas pressure to any equipment. They must be connected via a non-
mixer); return valve and flow-limiting device, and be
c. yellow “plant emergency” (analysis out of capable of isolation by means of an AVSU labelled
specification on any mixer); to identify the equipment controlled.

d. yellow “reserve low” (operating on final mixing 7.130 Medical air systems must not be used to provide
panel/buffer vessel only); air for sterilizer chamber or door-seal use.

e. red “pressure fault” (pressure fault).

81
Medical gases – HTM 02-01 Medical gas pipeline systems – Part A: Design, installation, validation and verification

8 Surgical air systems

General Note
8.1 Surgical air at 700 kPa is only used as the power Systems designed to meet requirements of earlier
source for surgical tools. These tools typically editions of Health Technical Memorandum 2022 may
require high flows – up to 350 L/min – at 700 kPa not provide 350 L/min at 700 kPa. Information on
at the point of use. Where nitrogen is available on upgrading surgical air systems in given in Appendix J.
site, it may be used as an alternative source of
supply. 8.7 The maximum pressure at the terminal unit under
8.2 Supply systems for surgical compressed air may be “static flow” conditions should not exceed 900 kPa.
a cylinder manifold system, a dedicated 700 kPa 8.8 Cylinders of medical air or nitrogen stored locally
compressor system or a compressor system capable should always be available for use in an emergency.
of supplying both the 700 kPa and the 400 kPa
supplies. In practice, the decision about which 8.9 Vessels should be selected as follows:
compressor system to install needs careful
Design flow Vessel size Compressor
consideration because of the flow rates required and
(L/min) output (L/min)
total usage (see Chapter 7).
>500 1 × 200% design flow 0.33 × design flow
8.3 A compressor system will be required for large 500–2000 2 × 66.6% design flow 0.66 × design flow
operating department complexes specialising in
2000–3500 2 × 200% design flow 0.66 × design flow
orthopaedic and/or neurosurgery that require the
use of pneumatically-powered surgical tools. An 3500–7000 3 × 33.3% design flow 0.5 × design flow
automatic reserve manifold located in separate
accommodation should be provided. A typical Extension of surgical air systems into
system is shown in Figure 28. dental departments
8.4 It is possible to use nitrogen instead of air as the 8.10 Some surgical air systems have been extended
power source for surgical tools. This may be derived into dental departments; such an extension offers
from either a liquid source or cylinders. In either obvious economic and air quality advantages in
case, the terminal units must be different from the comparison with separate provision. When such
existing medical air 700 kPa terminal units. A extensions are made, a non-return valve or back-
NIST connector is already specified for nitrogen feed protection device, with upstream and
and should be used. downstream isolating valves, should be installed in
8.5 The pressure control equipment should comprise the supply line to the dental department. Before
duplex regulating valves with upstream and extending a surgical air system into a dental
downstream isolating valves, pressure gauges and department, the following must be taken into
pressure relief valves. account:

8.6 Whatever supply system is installed, the overall a. the extra demand on the existing system must
system should be designed to provide a minimum not compromise patient safety or operation of
of 700 kPa at the front of each terminal unit at a either the existing system or its extension. In
flow of 350 L/min. particular, the ability of an existing emergency
supply system to cope with potentially very high
demands must be carefully assessed;
b. the Authorised Person (MGPS) with
responsibility for the existing surgical air system

82
8 Surgical air systems

Figure 28 Typical simplex surgical air plant and automatic emergency reserve manifold
Pressure
safety
valve
Pressure
gauge
Fusible
plug
Ball
valve Air
receiver Ball valve
Ball valve

Inlet filter
Air Pressure
intake Temperature
switch switch
Compressor 1 Aftercooler Non-return Ball
valve valves

Ball valve Automatic


Pressure Flexible drain
safety Ball connection *1
valve valves
Ball
Automatic valve
drain
*1

Silencer
Notes:
1. Drains marked *1 should be fed to an oil/water separator
Shut-off
2. Filters marked *2 are activated carbon to remove hydrocarbon vapours valve
3. Dryer control systems may incorporate shuttle valves as shown, or
may use other suitable arrangements of directional control valves
Dryer 2 column 2
4. Symbols to BS 2971:1993/ISO 1219-1:1991

Bacteria Dust/Carbon Shut-off Oil Water


filter filter valve filter separator
Pressure *2
safety
valve *1 *1
Pressure Flow
regulator restrictor
Pressure
gauge Ball valve
Ball Dryer 2 column 1
valve

Ball Shut-off P
Distribution Supply valve valve Pressure
Pressure
System System transducer
switch
Terminal Silencer
Ball valve unit
Flow Dewpoint
Non-return Lockable restrictor transducer
valve valve
D

Ball Non-return Terminal


Emergency Lockable unit
Supply valve valve valve

Pressure Pressure Pressure


Pressure switch gauge switch Pressure
gauge gauge
Pressure Pressure Pressure Pressure
Sintered regulator regulator regulator regulator Sintered
filter Ball Ball filter
valves valve

Shut-off Shut-off
valve valve
Pressure
Pressure switch
Pressure
safety Ball safety
valve Pressure
valve valve
safety
valve

Non-return valve

Exhaust
(piped to safe position)
Tailpipe

Cylinder valve

Cylinder

83
Medical gases – HTM 02-01 Medical gas pipeline systems – Part A: Design, installation, validation and verification

will automatically assume responsibility for the source, the associated medical air system. If
whole of the dental compressed air and vacuum the system is further extended into a dental
system. Both the Authorised Person (MGPS) laboratory, surgical air could be used to support
and Quality Controller (MGPS) must the operation of such devices as natural gas/air
appreciate that extending a surgical air system burners. Cross-connection of these systems is
into a dental unit for dental instrument use unlikely, but the risk must be assessed;
will introduce “non-standard” pipework
c. if the surgical air is derived from a plant that
terminations, for example crimped or
supplies medical air, the medical air supply
compression-fitted connectors, in addition to
should have a separate manifold reserve supply
non-degreased components. Failure of these
when space and system design makes this
“non-standard” components could lead to a
practicable.
serious depressurisation of the existing surgical
air system and, if provided from the same

84
9 Medical vacuum systems

General indicating system, an exhaust system and a flow test


connection. For capacities in excess of 500 L/min,
9.1 The medical vacuum pipeline system provides two vessels that can be independently isolated
immediate and reliable suction for medical needs, should be installed.
particularly in surgical accommodation.
9.2 The medical vacuum pipeline system consists of the Note
vacuum supply system, the distribution pipework The third means of supply for a vacuum installation
and terminal units. The performance of the will comprise portable suction units.
pipeline system is dependent on the correct
specification and installation of its component
parts. This chapter describes the requirements of Siting
the vacuum supply system.
9.9 The plant should have all-round access for
9.3 The medical vacuum pipeline system should be maintenance purposes, and allowance should be
designed to maintain a vacuum of at least 300 mm made for changing major components.
Hg (40 kPa) at each terminal unit during the
system design flow tests. 9.10 The siting of the plant should allow for adequate
flows of air to cool the pumps. The manufacturers
9.4 To ensure continuity of supply, the vacuum plant should be consulted over the range of operating
should be connected to the essential electrical temperatures for which the supply system is
power supply. designed. In extreme cases, refrigerator cooling may
9.5 The capacity of the vacuum supply system should be required.
be appropriate to the estimated demand.
9.6 With the exception of the vacuum discharge to
Pump noise
atmosphere, the pipeline distribution system for 9.11 The noise level produced by the pumps will
vacuum has traditionally been constructed of increase with the capacity of the supply system. For
copper. PVC pipework can be considered where larger systems this can result in an unacceptable
cost-effective. Pressure testing of PVC and copper noise level at the pump. The maximum free-field
pipework should be carried out at 100 kPa. noise level at 1 m from the unsilenced pump
should not exceed the following values for
9.7 The major components of a medical vacuum
individual pumps:
system and their layout are shown in Figure 29.
A suitable operating and indicating system with Power (kW) Noise level (dBA)
alarms is also required. The location of the 5 75
components should allow adequate space for access
5.1–15 82
for maintenance. Packaged supply systems are
available from manufacturers that should be 15 89
specified to meet the requirements given in this 9.12 A suitable acoustic enclosure may be required in
memorandum. the purchase specification for all pumps with a
9.8 The plant should consist of at least three identical free-field noise level at 1 m of 80 dBA or over. An
pumps, a vacuum reservoir with by-pass facilities, enclosure should produce a reduction of at least
duplex bacteria filters with drainage traps, 10 dBA in the free-field noise level at 1 m.
appropriate non-return valves, isolating valves,
gauges and pressure switches, an operating and

85
Medical gases – HTM 02-01 Medical gas pipeline systems – Part A: Design, installation, validation and verification

Figure 29 Triplex vacuum system


Pipeline
system
Ward
Area Line valve
AVSU assembly

Pressure
switch

To other
ward(s)
Terminal Terminal Terminal Terminal
unit unit unit unit
Riser
Pipework

Notes:
1. Non-return valves marked * are only required if exhausts from other
vacuum pumps share a common exhaust pipe
2. Symbols to BS 2971:1993/ISO 1219-1:1991

Pressure Pressure
gauge gauge

Vacuum Ball valve Vacuum Ball valve


vessel vessel
Pressure Bacteria
gauge filter

Ball
Ball valve
Ball Pressure
Ball Ball valve
valve valve valve transducer
P

Ball valve

Flexible Flexible Flexible Ball Bacteria


valve filter Ball
connection connection connection
valve Ball
valve

Ball valve Ball valve Ball valve


Exhaust Exhaust Exhaust Ball
valve
Ball
Non-return Non-return Non-return valve
valve valve valve Drain
flask
Drain
Pump 1 Pump 2 Pump 3 flask

*Non-return Ball *Non-return Ball *Non-return Ball


valve valve valve valve valve valve
Drain Drain Drain
flask flask flask

Vacuum plant exhaust 9.14 Noise from the exhaust should be considered and a
silencer fitted if necessary.
9.13 The position of the termination point should be
carefully chosen to be clear of windows, ventilation 9.15 The construction should conform to the following
intakes and the intake of air compressors and other criteria:
equipment, since for oil-lubricated pumps the a. the exhaust should be sized to give a back
vacuum exhaust is likely to be polluted with oil pressure at system design flow which is matched
fumes. to the pump performance;

86
9 Medical vacuum systems

b. the termination point should be turned down equipment’ with the addition of Class F insulation
and provided with protection to reduce the and Class B temperature rise.
effect of wind pressure and prevent the ingress
9.23 A vacuum reservoir should be provided so that the
of rain, snow, insects or animals;
duty pump does not run continuously for low
c. weatherproof notices should be fixed at the loads. The reservoir should be manufactured in
discharge point(s) with the legend “medical accordance with BS EN 286-1:1998, with test
vacuum discharge point – do not obstruct”; certificates provided to the user. The minimum test
pressure should be 4 bar.
d. the exhaust pipe should be provided with a
drainage valve at its lowest point; 9.24 The water capacity of the reservoir should be equal
to the plant design flow at 450 mm Hg (60 kPa) in
e. a silencer should be fitted in the exhaust pipe
terms of free air aspirated in one minute with the
from each pump. This may be integral with the
pump operating at 475 mm Hg (60 kPa).
pump unit.
9.25 Provision should be made for draining the reservoir
Efficiency under vacuum conditions. By-pass facilities should
be provided so that the reservoir can be drained
9.16 The pump should be capable of producing a higher and inspected without interruption to the vacuum
vacuum than that required in the pipeline, so that supply. The reservoir should be fitted with suitable
the resistance of the bacteria filter and back lifting lugs and feet.
pressure in the exhaust system can be overcome.
9.26 If multiple reservoirs are provided, they should be
9.17 The capacity of the vacuum pump should be arranged in parallel.
specified in terms of the free air aspirated (FAA) in
L/min when the pump is operating at a vacuum of 9.27 The bacteria filters and drainage trap should
475 mm Hg (63 kPa) and at 450 mm Hg (60 kPa) comprise two identical sub-assemblies with
at the plant pipeline connection. manually-operated isolating valves, arranged to
allow either sub-assembly to be on stream. Each
Vacuum pumps sub-assembly should contain a bacteria filter rated
at the plant capacity.
9.18 Any type of pump apart from water-sealed pumps
can be used. 9.28 The bacteria filter should be marked with the
legend “bio-hazard”, together with a description of
9.19 Pumps should normally be oil-lubricated. Vapours a safe procedure for changing and disposing of the
from the lubricating oil are unlikely to be a filters and emptying the drainage trap.
significant component of the exhaust gases if
correctly maintained. “Dry running” rotary vane 9.29 The bacteria filters should have a filter efficiency,
pumps are available at increased capital cost and when tested by the sodium flame test in accordance
with lower efficiency than oil-lubricated pumps of with BS 3928:1969, of greater than 99.995% at
comparable performance. the system design flow.

9.20 At least three pumps should be provided. The 9.30 The pressure drop across a clean filter at the system
actual number is at the discretion of the plant design flow should not exceed 25 mm Hg (3 kPa)
manufacturer to ensure optimum cost benefit of at a vacuum of 475 mm Hg (63 kPa).
the system. All pumps should be designed for high 9.31 The drainage trap may be integral with the bacteria
frequency stop/start or continuous operation. The filter and should be fitted with a transparent bowl
opportunity to maximise energy conservation to collect liquid. The bowl should be suitable for
should be taken into consideration. steam sterilization at 134°C.
9.21 All systems should comprise pumps and motors 9.32 Although there is no firm evidence that has
of identical type that are suitable for continuous demonstrated the need for bacteria filters, it is
running and stop/start operation. recommended that such devices are included as
9.22 Pump motors should comply with the National precautionary measures.
Health Service Model Engineering Specification
C51 – ‘Electrical requirements for specified

87
Medical gases – HTM 02-01 Medical gas pipeline systems – Part A: Design, installation, validation and verification

Pressure control 9.41 Vacuum indicators should be located on:

9.33 The cut-in setting for the vacuum pumps should be a. the plant control unit indicating the vacuum in
adjusted to allow for the pressure drop across the the pipeline (that is, on the pipeline side of the
pipeline distribution system and the bacteria filters. bacteria filter);
The cut-in may be expected at about 500 mm Hg b. each reservoir.
(67 kPa).
9.42 A differential vacuum indicator (to indicate filter
9.34 The cut-out setting should be at an appropriate blockage rather than quantitative pressure drop)
point on the performance curve of the pump, should be located across the bacteria filter and have
which minimises stop/start operation but is at a a service isolation valve.
vacuum which is economically attained by the
pump. This cut-out setting may be expected at Electrical supply
about 650 mm Hg (87 kPa).
9.43 The electrical supply to the medical vacuum plant
Valves should be connected to the essential electrical
supply. A time-delay system should be provided to
9.35 Non-return valves should be fitted, when necessary, avoid overloading the power supply on changeover.
at the inlet and outlet of each pump to prevent
backflow when a common discharge pipe is used. Pump operating and indicating system
(Some vacuum pumps include integral non-return
valves.) General description
9.36 Manually operated valves should be arranged in the 9.44 The operating and indicating system should
positions shown in Figure 29 to allow isolation of perform the following functions:
components such as pumps, reservoirs, by-pass
pipework, drainage taps and bacteria filters. a. overall plant control and indication;
b. individual pump starting;
Pressure regulation of vacuum system c. plant status monitoring and indication;
9.37 A vacuum of 300 mm Hg is required at the
d. alarm signal status unit.
connection point of each terminal unit with a flow
of 40 L/min whilst the system is operating at 9.45 Provided that the individual pump starters are
system design flow. housed in a separate compartment, the operating
and indicating system may be housed in separate
9.38 This performance is tested by the procedures
units or may be installed in a common panel and
carried out in accordance with Chapter 15.
located on the plant or on the plantroom wall.
9.39 A pressure drop of 13 kPa (100 mm Hg) is allowed
9.46 Pneumatic components should have ventilation.
across the terminal unit at a flow of 40 L/min (BS
All functions should be appropriately identified.
5682:1998). The minimum pressure at the front
Indicators should have a design life of at least five
of the most distal terminal unit should be 40 kPa
years. The operating system should be capable of
(300 mm Hg) at a flow of 40 L/min. The
automatically restarting after reinstatement of the
minimum pressure (dynamic) at the plant should
power supply.
be 60 kPa (450 mm Hg).
9.47 The vacuum supply system should be connected to
Note the stand-by electrical supply. The control system
should ensure that pumps restart in sequence to
Precautions for changing filters are included in Part B.
avoid overloading the power supply.

Vacuum indicators
9.40 Vacuum indicators should comply with BS EN
837-1:1998 or have an equivalent performance if
electronic indicators are used. Calibration should
be 0–760 mm Hg (0–101 kPa). All gauges should
be a minimum scale length of 90 mm.

88
9 Medical vacuum systems

Plant control unit d. an industrial grade ammeter to BS EN 60051-1:


1999, IEC 60051-1:1997 or an electronic
9.48 The control unit should have a separate power
digital instrument of comparable, or higher,
supply for each pump controlled by a separate sub-
standard;
circuit. It should be manufactured and installed in
accordance with IEE regulations, and the design e. a total hours counter, if not included in the
should be such that no single component failure in plant control unit;
the control unit will result in loss of plant output.
f. a green “mains supply on” indicator, if mounted
9.49 The unit should allow either manual selection of separately from the plant control unit.
duty/stand-by for each of the pumps or have an
automatic sequence selection with a means for Plant status monitoring
manual override. The control unit should ensure 9.54 A monitoring system must be provided to detect
that two or more pumps do not start the following faults in the vacuum supply system:
simultaneously when power is applied.
a. plant faults for each pump:
9.50 A warning notice which complies with BS 5499-1:
2002 should be affixed which indicates the (i) control circuit failed;
presence of low voltage. (ii) motor tripped;
9.51 For testing purposes, each pump should have a (iii) pump failed to go on load;
selector switch which when turned to the “on”
position allows the pump to run continuously. (iv) activation of other safety devices supplied
by the manufacturers;
Plant control indication b. plant emergency – receiver vacuum has fallen,
9.52 There should be indicators for each pump as for example, by 50 mm Hg below the cut-in
follows: setting for the pump;
a. green “mains supply on”; c. pressure fault (pipeline) – pipeline vacuum less
than 360 mm Hg.
b. green “pump operating”, which indicates that
the pump motor is electrically energised; Plant status indicator unit
c. green “pump operating”, which indicates that 9.55 In addition to the plant control indication, there
the pump is drawing vacuum; should be a plant status indicator panel that may
d. an indicator of the vacuum produced in the be mounted on the plantroom wall or adjacent to
pipeline. either the pump starter unit or the plant control
unit. It should have a warning notice that complies
Pump starter units with BS 5499-1:2002 to indicate the presence of
low voltage.
9.53 There should be individual starter units, each one
operating a single designated pump. The starters 9.56 There should be indicators for each pump to show
should be provided with safety interlocks as the following conditions:
specified by the pump manufacturers, which a. green “mains supply on”;
should inhibit plant operation until manually reset
by means of a button. The starters should allow b. yellow “control circuit failed”;
automatic restart after an interruption to the power c. yellow “motor tripped”;
supply. Each starter unit should contain the
following: d. yellow for each individual safety device provided
by the manufacturers;
a. an isolator interlocked with the covers;
e. yellow “pump failure”.
b. either HRC fuses to BS 88 or suitable circuit
breakers to BS EN 60947-2:2003 and/or BS Alarm signal status unit
EN 60898-1:2003;
9.57 The following indication of plant conditions
c. starter; should be provided:
a. green “normal” (indicator normal);

89
Medical gases – HTM 02-01 Medical gas pipeline systems – Part A: Design, installation, validation and verification

b. yellow “plant fault” conditions (b)–(d); see should be monitored for open/short circuit. In the
paragraph 9.56; event of such a cabling fault, a red “system fault”
lamp should be illuminated on the alarm system
c. yellow “plant emergency” condition (e); see
status unit together with the appropriate alarm
paragraph 9.56;
condition.
d. red “pipeline pressure fault” (pressure fault).
Plant management
9.58 Conditions (b) to (d) should be transmitted to the
central alarm system. Where relays are used, they 9.61 Connections should be provided which allow
should be normally energised relays, which de- monitoring (but not control) of plant alarm
energise under fault conditions, with contacts conditions (b) to (e) and pump running for each
having a minimum rating of 50 V dc and 50 mA. vacuum pump. These connections should be volt-
free contacts normally closed for each condition
9.59 Volt-free, normally closed contacts rated at 50 V dc
having a minimum rating of 50 V dc and 50 mA.
and 50 mA should be provided for transmission of
conditions (b) to (e) to the alarm system. 9.62 Plant should be operated in accordance with the
manufacturer’s instructions and be covered by a
9.60 The panel can be incorporated into the plant status
sound, effective planned preventative maintenance
indicator unit or be a separate unit within a
(PPM) policy.
plantroom. If mounted separately, the cabling

90
10 Anaesthetic gas scavenging disposal
systems

Terminology administered to a patient in the course of medical


treatment.
10.1 An active system, as specified in either BS 6834:
1987 or BS EN 737-2:1998, is one in which a high 10.7 Detailed guidance on compliance with COSHH is
air flow generated by an electrically driven pump given in the Department of Health’s (1996) ‘Advice
is used to exhaust air through the system’s fixed on the implementation of the Health & Safety
pipework. This in turn entrains waste gases from Commission’s occupational exposure standards for
the patient, or patient ventilator, via a transfer hose anaesthetic agents’. Further guidance is given in by
and receiving system. the Health & Safety Executive’s (1996) ‘Anaesthetic
agents: controlling exposure under COSHH’.
10.2 The transfer and receiving system form part of the
anaesthetic/breathing system. 10.8 The COSHH regulations set out very specific
duties that apply to anaesthetic gases, and
10.3 The receiving system is designed to match the employers have a legal obligation to ensure that
variable flow in the breathing system to the these duties are discharged. It is therefore the
constant flow of the disposal system and ensure responsibility of the general manager or chief
that very low induced flows are imposed (0.5 L/ executive to implement the requirements of the
min in the case of BS 6834:1987 and 0.05 L/min COSHH regulations with respect to anaesthetic
in the case of BS EN 737-2:1998 systems). gases. This subject is covered in Part B.
10.4 As a passive system essentially comprises a pipe 10.9 For new installations, an assessment should be
through a hole in a wall through which waste gases made of the transfer and receiving equipment
are driven by the patient or ventilator expiratory currently in use and intended for use with the
effort, there is no pump involved in such a system. new installation. Where the transfer and receiving
In the UK, only systems complying with the BS or equipment has been designed to BS 6834:1987, the
EN Standards above are considered appropriate disposal system design should be to BS 6834:1987.
for scavenging waste anaesthetic gases from Where the transfer and receiving equipment in use
accommodation in which general anaesthesia is has been designed to BS EN 740:1999, the disposal
taking place. system should be designed to BS EN 737-2:1998.
10.5 Active scavenging for dental installations is an Where a mixture of equipment is in use, the system
entirely different concept. An active system is one should be designed to BS 6834:1987. Where both
in which there is a flow generated through the types of equipment are required to be used on the
patient’s nasal mask and this carries away the waste same disposal system, a restrictor should be
gases exhaled by the patient. This flow is in the provided for the BS EN 740:1999 equipment to
order of 45 L/min and is achieved by connection of restrict the flow to its design flow rate. The system
the mask (via a suitable flow-limiting adaptor) to should be installed in all operating departments
either a dental vacuum system or directly to an and other areas, as required, in accordance with the
active scavenging system (BS/EN) wall terminal levels of provision given in Table 11.
unit.
Note
General BS 6834:1987 covered all aspects of the anaesthetic gas
10.6 Anaesthetic gases are considered to be substances scavenging systems and has now been superseded by
hazardous to health for the purposes of the Control BS EN 737-2:1998 and BS EN 737-4:1998. ISO
of Substances Hazardous to Health Regulations 7396 (in preparation) will replace BS EN 737 Parts 2
2002 (COSHH), except where they are and 4.

91
92
Figure 30 Schematic diagram of an AGS disposal system
Flexible hose

Apparatus
incorporating
integral transfer/
receiving system
Permanent
connection

Terminal unit
probe and socket
10.10 A typical system schematic is illustrated in

Flexible hose Permanent connection


Figure 30 and shows the terminology used.

disposal systems are in contact with a patient’s


10.11 The internal components and pipework of AGS

30 mm conical Receiving
connections Discharge
system Flexible
Means of boom or pendant
positive
pressure relief Permanent connection
Breathing
system Receiving
system

Transfer tubing
Probe/terminal
unit socket interface

Limits of Limits of
breathing transfer
system system Limits of receiving system Limits of disposal system
Medical gases – HTM 02-01 Medical gas pipeline systems – Part A: Design, installation, validation and verification

is, however, potential for bacteriological


dilution by virtue of the receiving system that
forms part of the anaesthetic equipment, there
expired breath. Even though there is considerable
10 Anaesthetic gas scavenging disposal systems

contamination. The materials should be reasonably below with the number of terminal units for which
resistant to corrosion and should withstand it has been designed for use.
cleaning, disinfection or sterilization as
appropriate. Disposal system standard
Pressure drop Flow rate
10.12 The fixed pipework may be of copper or other
BS 6834: ISO DIS BS 6834: ISO DIS
suitable material such as PVC. Where copper
1987 7396-2: 1987 7396-2:
pipework is installed at the same time as the 2005 2005
MGPS, it is desirable to use degreased pipework to
Maximum 1 kPa 1 kPa 130 L/min 80 L/min
the same specification as that used for the MGPS
(see Chapter 13) in order to avoid confusion. Minimum 4 kPa 2 kPa 80 L/min 50 L/min
Maximum 20 kPa 15 kPa
10.13 Where PVC pipes larger than 38 mm diameter
static (–ve) (–ve)
pass through a fire compartment, they should be pressure
protected with metal sleeves extending for 1 m
either side of the compartment in accordance Notes
with the Building Regulations 2000. The
recommendations of Firecode and Health Since the preparation of BS 6834:1987, developments
Technical Memorandum 81 should be followed. in anaesthesiology have resulted in reduced flows being
used. Depending on local circumstances, it may be
possible to commission systems for different flows in
Selecting the number of disposal accordance with ISO DIS 7396-2:2005. Details of the
system pumps test flows should be recorded in the commissioning
10.14 For operating departments, the number of disposal documentation.
system pumps should be selected in accordance The pump inlet should include a vacuum indicator for
with the number of air-handling units that are to commissioning purposes.
be installed for each operating suite. For example,
if a separate air-handling unit is supplied for each
suite, a separate AGS disposal system pump should Discharge outlet
be installed. Where an air-handling unit supplies
two or more operating suites, the AGS disposal 10.17 Careful consideration should be given to the
system should serve the same number and in siting of the discharge from the disposal system. It
this case be a duplex system with automatic should preferably be sited at roof level, well away
changeover. (Where a single pump is provided for from ventilation inlets, opening windows and
an individual operating suite, a spare pump for up other apertures, to prevent pollution re-entering
to six units should be provided for immediate the building.
connection into the system in the event of failure.)
Plant control indication
Flow and diversity 10.18 There should be indicators to show the following
10.15 Although more than one AGS terminal unit may conditions:
be installed in an operating room or anaesthetic a. green “mains on”;
room for convenience, it may be assumed that
b. green “air flow” normal;
only one terminal unit in each room will be in use
at any given time. The AGS terminal unit in the c. yellow “duty pump failed” (plant fault);
anaesthetic room and operating room, however,
d. red “system failed” (plant emergency).
may on rare occasions be in use simultaneously;
therefore, the plant is sized for two AGS terminal 10.19 Indicator panels should be installed in operating
units for each operating suite. rooms.
10.16 The performance criteria for the disposal system 10.20 The “air flow normal” indication should be
are specified in the relevant British, European and initiated by either a pressure switch or air flow
International Standards in terms of the extract detection device at the pump.
flows at specified resistance. The disposal system
should meet the requirements set out in the table

93
Medical gases – HTM 02-01 Medical gas pipeline systems – Part A: Design, installation, validation and verification

11 Other medical gas pipeline installations

General Compressed gas cylinder manifold systems


11.1 It is possible to extend medical gas system design Primary supply Secondary supply Tertiary supply
concepts to other gases used from cylinders and still (third means of
maintain the elements of gas specificity that are supply)
essential requirements together with all other Fully automatic Manual emergency Locally based
relevant safety considerations. manifold reserve cylinders with
Manifold to integral regulator/
Number of
Helium/oxygen mixture cylinders based on
come on-line flowmeter and
automatically via a terminal unit
11.2 Helium/oxygen mixture is used by patients with system design
non-return valve. outlet
respiratory or airway obstruction and to relieve
Number of
symptoms and signs associated with respiratory
cylinders based on
distress. It can be administered by means of face ability to provide
mask and cannula, a demand valve with face 4 hours’ supply at
mask with cannula attached, a nebuliser, or by a average use
ventilator.
11.3 Its main use will be in Accident & Emergency Oxygen/CO2 mixture
(A&E), supplied from portable cylinders with 11.9 Oxygen/CO2 mixture has been supplied by
integral control valve and regulator, and in critical pipeline in at least one installation in the UK for
care areas. anaesthetic purposes in cardiothoracic procedures.
11.4 When provided by means of a pipeline installation, 11.10 There has been little interest shown in installing
all the elements of a manifold supply system for others and, therefore, this medical gas is no longer
other medical gases should be installed. included within the scope of this Health Technical
11.5 The manifolds will be designed to operate at Memorandum.
low pressure (10 bar), and connection to K-size
cylinders will be made by means of a low-pressure Carbon dioxide
flexible assembly to a terminal unit integral with
11.11 Carbon dioxide is now not generally used as a
the cylinder regulating valve. The connection to the
respiratory stimulant post-operatively. Pipelines
manifold will be by means of a NIST connector.
have not been installed in the UK for respiratory
11.6 The individual cylinders will include pressure applications. Its main use today is for insufflation
transducers to monitor the pressure upstream of the during surgery, and to date there have been some
integral control valve. (Cylinders do not necessarily installations in the UK.
discharge simultaneously.)
11.12 When pipeline systems are installed for such
11.7 In the case of helium/oxygen mixture pipelines, purposes, the general requirements for other
the tertiary source of supply is a portable cylinder. medical gas pipelines should be followed. The
11.8 The manifold should be located close to the facility
terminal unit should comprise a NIST connector
that it supplies. with integral check valve contained in the surgeon’s
pendant. The level of provision of AVSUs should
be provided as for other medical gas pipelines.
11.13 A semi-automatic manifold will normally be
satisfactory and it should be installed “locally”.

94
11 Other medical gas pipeline installations

A 2 x 4 VF-size manifold will provide adequate Nitric oxide


capacity. The safety valve discharge should be
taken outside the department. The warning and 11.14 Treatment using nitric oxide is subject to specific
alarm system indicator will normally be installed Ph. Eur. requirements. Distribution of the gas by
in the operating room control panel. pipeline systems is not considered appropriate.

95
Medical gases – HTM 02-01 Medical gas pipeline systems – Part A: Design, installation, validation and verification

12 Warning and alarm systems

General located where information is required to ensure the


necessary action is taken. Area alarms should be
12.1 The provision of a warning and alarm system is provided to give warning to users downstream
essential to monitor the safe and efficient operation of the designated departmental AVSU (see
of an MGPS. There are three reasons for this Chapter 3).
monitoring:
12.5 Pressure sensors should be connected to the
a. to indicate normal function of the pipeline pipeline by means of minimum leak devices.
system by means of visual indicators;
12.6 All MGPS warning and alarm indicating panels
b. to warn by visual and audible indication that should comply with the requirements of this
routine replacement of cylinders or other Health Technical Memorandum, including all
engineering action is required; operating room panels.
c. to inform the user by visual and audible
emergency alarms that abnormal conditions Panel location
have occurred which may require urgent action
by the user. This alarm condition will require a Central indicator panel
rapid response by the various departmental staff. 12.7 Warning and alarm conditions for all medical gas
12.2 To date, practice has been to have a “dedicated” supply systems should be displayed on a central
medical gas warning and alarm system and this panel located in a position where there is
approach will remain in many situations. With the continuous 24-hour occupation, such as the
development of computer-based integrated patient/ telephone switchboard room or the porter’s lodge.
management systems, nurse call and other alarm
systems, however, there is considerable scope for Repeater indicator panel location
including medical gas system information including 12.8 Repeater panels should be provided in other
text action prompts etc. Additionally, building locations to display all or some of the information
management IT-based systems will play an on the central alarm so that appropriate action can
increasing role in the operation and management of be taken to ensure the continuing operation of the
an MGPS. system. Some warning system information may be
appropriate for display in specific departments, for
Dedicated systems example cylinder manifold status information in a
12.3 The requirements of “dedicated” warning and porters’ room, and oxygen concentration in the
alarm systems are covered in paragraphs 12.3 to pharmacy department when a PSA plant supplies
12.62 and a schematic diagram of a typical system the hospital pipeline installation.
layout is shown in Figures 31 and 32. Warning and
alarm systems are required for all medical gas and Area warning and alarm panel location
vacuum systems. A simplified system is required 12.9 Local panels to display “high” and “low” gas
for surgical air systems and for the AGSS, with the pressure should be installed in the locations given
warning/indication panel located in the operating in Chapter 3. The sensors for these panels should
room. be located downstream of the designated AVSUs,
12.4 Warning and alarm systems comprise pressure normally the departmental AVSUs. It should not
sensors, a central system providing information on be possible to isolate the sensor with a separate
all monitored functions, with repeater panels shut-off valve and they should be connected to the
pipeline by means of a minimum leak device.

96
Figure 31 Typical warning and alarm system layout (reproduced by kind permission of Shire Controls)
CENTRAL ALARM PANEL
IN TELEPHONE ROOM REPEATER ALARM REPEATER ALARM
OR PORTERS LODGE IN PORTERS LODGE IN ENGINEERS OFFICE

MULTICORE COMMUNICATION CABLE

TRANSMITTER
PLANT TO ALARM
INTERFACE

END OF LINE
COMPONENTS TRANSMITTER TRANSMITTER

END OF LINE
COMPONENTS END OF LINE
COMPONENTS

12 Warning and alarm systems


OXYGEN V.I.E. MANIFOLD WITH EMERGENCY RESERVE PLANT WITH EMERGENCY RESERVE
97
Medical gases – HTM 02-01 Medical gas pipeline systems – Part A: Design, installation, validation and verification

Figure 32 Typical area alarm panel (reproduced by kind permission of Shire Controls)

SUPPLY
PIPEWORK

PIPEWORK TO
DEPARTMENT

PRESSURE
SENSORS

END OF LINE
COMPONENTS

AVSU
INTER-
CONNECTING
WIRING

AREA ALARM
PANEL

98
12 Warning and alarm systems

System components General requirements


12.10 Warning and alarm systems include the following
Labelling
functional elements:
12.13 All visual signal panels should be permanently
a. interfaces/transmitters that convert the signal
labelled according to their function, including
from the plant or manifold volt-free alarm
clear identification of the areas, rooms or
contacts into a form which can be transmitted
departments served.
via multiplexed cable (for example using pulse-
width modulation). The transmitter may be a Visual signals
separate unit or may be incorporated:
12.14 Flashing visual signals should have alternate “on”
(i) in plant or into a manifold control panel; and “off ” periods, each of equal duration between
(ii) into an indicator panel. 0.25 and 0.50 seconds.
Cases (i) and (ii) should include line-fault 12.15 There should be two separately energised light
monitoring devices; sources for each signal, arranged so that the failure
of one source does not affect the other.
b. indicator panels which display the transmitted
signals; 12.16 The light sources should have a design life of at
least five years of continuous operation.
c. interconnecting multiplex wiring which
connects all interfaces/transmitters to all Audible signals
indicator panels.
12.17 All audible signal tones should be modulated
System layout equally at a rate of 4 Hz ±10% between two tones
of 440 Hz ±10% and 880 Hz ±10%.
Central system
Automatic resetting
12.11 A typical system layout is shown in Figure 31,
which shows initiating devices at remote locations 12.18 When a warning or alarm signal occurs and the
such as the VIE compound, medical air and system condition subsequently reverts to normal,
vacuum plantrooms, nitrous oxide manifold room the corresponding visual and audible signals
and emergency/reserve manifold rooms. The should automatically reset to normal.
transmitters are normally located close to the
initiating devices. Indicator panels are typically Temporary muting
located at the telephone exchange, the porter’s 12.19 Means must be provided on each panel for the user
room and the engineer’s office to provide to mute the audible signal. The signal must re-
information requiring action by engineering and sound after a nominal 15-minute period if the
other support staff. fault condition still exists. The process of muting
and reinstatement of the signal should be repeated
Area warning and alarm systems until the fault condition has been rectified.
12.12 A typical layout of an area warning and alarm Operation of the mute on the central panel should
system is shown in Figure 32. For each gas service be accompanied by change from flashing to steady
there should be local pressure switches for low illumination of the corresponding visual indicator
pressure; high pressure switches are also required on the central and any repeater panels. Operation
when oxygen, nitrous oxide and medical air are of the mute on area alarm or repeater panels
installed together. These conditions should be should not be accompanied by a change from
indicated on a locally-mounted indicator panel, flashing to steady illumination.
with facility to provide a common alarm condition
for connection to other alarm panels. Area panels Continuous muting
carry no indication of the warnings for cylinder 12.20 An internally-mounted switch should be provided
replacement and plant functions that are given on to allow continuous muting during periods of
central indicator panels. maintenance. When the system condition returns
to normal, the continuous muting should
automatically reset to normal operation. When the

99
Medical gases – HTM 02-01 Medical gas pipeline systems – Part A: Design, installation, validation and verification

continuous muting is in operation on any alarm Test facility


condition, it should not prevent the operation of
12.30 Each panel should be provided with a means to
the audible signal on other alarm conditions when
test all visual and audible signals on that panel.
a fault condition arises.
The power supply should be capable of sustaining
all indicators and audible signals.
Electrical wiring
12.21 All electrical wiring should be in accordance with Warning and alarm system faults
IEE regulations.
General
System integrity
12.31 A flashing red visual indicator and an audible
12.22 If extra low voltage (ELV), maximum 50 V, is signal should operate on all panels when any of the
superimposed on the signal or communication following conditions occur:
circuit (for example by cross-connection), the
system design should ensure that any damage a. line fault from the initiating device;
to the system is limited to replaceable panel b. communication fault or other wiring fault;
components and that such damage is indicated as a
system fault. c. mains power failure.

12.23 The performance of the system should not be Line fault


compromised by the use of multi-core cabling that
12.32 The system should monitor the integrity of the
carries ELV and communication signals in adjacent
lines between the initiating devices and the panel
cores.
or transmitter units. The “alarm system fault”
12.24 The system should be designed to reject spurious condition should be indicated on loss of integrity,
radio frequency (RF) or mains noise typically for example open or short circuits, together with
arising in hospitals, examples being diathermy the visual alarm indicator(s) associated with the
equipment and current spikes caused by plant faulty wiring.
start-up etc.
Communication/wiring fault
Relay conditions
12.33 The system should indicate an alarm system fault
12.25 If relays are used to transmit alarm signals, the in the event of loss of data transmission between
relays should be energised in their normal closed panels and transmitters.
condition.
Mains power failure
Mains power supply
12.34 Failure of mains power should be shown by
12.26 The mains electricity supply should be derived a flashing red indicator and an audible signal,
from the essential power supply (that is, must be which should be powered from an internal battery.
on the emergency system). The audible signal may be muted and not
automatically reinstate as required under normal
Safety extra low voltage/functional extra low power supply (see paragraph 12.19), but the visual
voltage power supply indicator should continue to flash until either the
12.27 The panel power may be designed either as a safety fault has been rectified or the battery has
extra low voltage (SELV) system or as a functional discharged.
extra low voltage (FELV) system, as defined in
Part 4 of the IEE Wiring Regulations. Stand-by battery

12.28 The ELV power supply may be housed either in 12.35 A battery should be provided with sufficient
the alarm panels or in a separate metal enclosure. capacity to power the visual and audible “alarm
system fault” signal for a minimum period of
12.29 The power supply should be rated for the full load four hours. The battery should be sealed and
of the panel, with visual and auditory signals on all exchangeable, and should automatically recharge
normal and alarm conditions. within 72 hours.

100
12 Warning and alarm systems

Legend 12.44 Panels should have electrical sections with


protection at least equal to BS EN 60529:1992.
12.36 The legend on this indicator should be “alarm
system fault”. 12.45 Panels and their housings should be of adequate
strength for their purposes and be manufactured
Indicator panel requirements for all from corrosion-resistant materials.
systems 12.46 If gas services are brought into the panel,
they should be housed in separate, enclosed
Indicators compartments, which are vented to the outside.
12.37 Panels should be provided with all indicators for 12.47 There should be gas-tight seals where electrical
the gas services in local use. services pass through any gas compartment.
12.38 The visual indicators should be arranged vertically
in priority order, with the normal indicators at the Remote audible sounder
top. The sequence of gas services should be, from 12.48 All panels should have provision for connection to
left to right: a remote audible sounder.
a. medical oxygen (cryogenic and cylinders/
pressure swing adsorber (PSA) systems); Central indicator panel requirements
b. nitrous oxide; Displays
c. nitrous oxide/oxygen mixture; 12.49 The central panel should display all signals for all
d. medical air 400 kPa (compressor plant, MGPS which are generated by the warning and
cylinders and synthetic air); alarm system, as described in paragraphs 12.50–
12.53.
e. surgical air 700 kPa;
f. medical vacuum (pumps); Normal

g. helium/oxygen mixture. 12.50 The normal condition for all piped MGPS should
be displayed as a steady green visual signal. The
12.39 In addition to the gas service signal indicators, “normal” indicator should extinguish in warning
each panel must include: and alarm conditions.
a. a green “power on” indicator without an
audible signal; Warnings

b. a red “alarm system fault” indicator with an 12.51 Warning conditions appropriate to each MGPS
audible signal. should be displayed as a flashing yellow visual
signal that may be accompanied by a mutable
Labelling audible signal (see Table 24).
12.40 Panels should be labelled as follows: Emergency alarms
a. medical gas alarm; 12.52 Emergency alarms are generated by loss of pipeline
b. with the identification of the medical gas pressure or vacuum and are indicated by flashing
services indicated, and the areas and red visual signals accompanied by mutable audible
departments served. signals.

Construction Alarm system fault


12.41 The fascia panel should be removable to allow 12.53 The “alarm system fault” condition should
access to the rear of the fascia or to the panel for be displayed as a flashing red visual signal
maintenance purposes. accompanied by a mutable audible signal.
12.42 Access to the interior of the panel should be Mute functions
tamper-proof.
12.54 The temporary mute should cancel the audible
12.43 It should be possible to replace the source of signal for about 15 minutes and change the visual
illumination without removing the legend. indicators from flashing to continuous on all
central and repeater panels.
101
Medical gases – HTM 02-01 Medical gas pipeline systems – Part A: Design, installation, validation and verification

12.55 Operation of the continuous mute should inhibit 12.65 Operation of the mute should not inhibit the
the 15-minute reinstatement of the audible alarm. visual or audible indication of any subsequent
alarm conditions.
12.56 Operation of the mute should not inhibit the
visual or audible indication of any subsequent
alarm conditions. Integrated systems
12.66 The introduction of computer-based systems for
Panel legend and display a range of functions such as patient information,
12.57 Panel legend and display should be as shown in nurse call and other alarm conditions provides an
Table 24. opportunity to further include certain provisions
of medical gas pipeline warning and alarm
Repeater indicator panel requirements conditions. This concept is totally new and, at this
stage, the applications have not been thoroughly
Displays evaluated or analysed. One of the advantages of
the concept is that text prompts can be displayed
12.58 The repeater indicator panel should always display on the computer display when changes in the
“normal”, “emergency alarm” and “alarm system status of the pipeline occur, and these prompts can
fault” conditions as given above. The repeater advise staff of the need to take specific action.
panel should display some or all of the warning
conditions that are displayed on the central 12.67 The advantage of a computer-based system is that
indicator panel. The extent of the display of the advice given in the text message can be varied
warnings should be varied to suit local clinical to take account of specific circumstances, changes
requirements. in operating procedures and functional changes
within individual departments. Such systems
Mute functions are likely to be of most use in in-patient ward
accommodation; it may not be appropriate for
12.59 The temporary mute should cancel the audible central warning and alarm conditions or in
signal for about 15 minutes whilst the visual individual operating rooms and other
indicator continues to flash. Operation of the accommodation in which anaesthetic procedures
temporary mute (on the central panel) should are taking place.
change the visual indicator to continuous
illumination on the central and any repeater 12.68 It will be necessary to change the perception of
panels. users in that with this approach the “normal”
conditions of the pipeline systems that are
12.60 Operation of the continuous mute must inhibit continuously displayed on alarm indicator panels
the 15-minute reinstatement of the audible alarm. will not exist – audible emissions and displayed
12.61 Operation of the mute should not inhibit the messages generated by the computer-based system
visual or audible indication of any subsequent will be in response to changes from the “normal”
alarm conditions. situation. To ensure the long-term viability of the
system, any supplier or installer of such a system
Panel legend and display must supply sufficient information about the
system to allow modification, expansion or
12.62 The panel legend and display should be as shown
replacement of sections of the system by a third
in Table 24.
party. This must include source code for any
software, passwords and details of any other
Area warning and alarm panel security device, and details of any communication
protocols. This information must be handed to the
Panel displays and legend end-user before the system is accepted by the end-
12.63 Area panels should display the conditions listed in user.
Table 25.
Note
Mute functions
No further information can be given at this stage until
12.64 The temporary mute should cancel the audible further development and consultation takes place.
signal for about 15 minutes whilst the visual
indicator continues to flash.

102
12 Warning and alarm systems

Table 24 Signals and displays for central alarm panels and repeater panels
Supply system(1) Alarm conditions Legend Colour Audible Location(2)
system
Automatic manifolds 1. Duty bank empty: stand-by Change cylinders Yellow Yes AB
bank running
2. Stand-by bank below 10% Change cylinders Yellow Yes AB
capacity immediately
Compressed cylinders on automatic Changeover of manifold. Pressure Reserve low Yellow Yes AB
manifold serving a single vessel in each bank is not monitored.
cryogenic oxygen system or liquid
cylinder installation
Compressed cylinders on reserve Changeover of manifold. Pressure Reserve low Yellow Yes AB
manifold serving a compressor plant in each bank is not monitored.
Compressed cylinders on reserve Reserve pressure below 68 bar Reserve low Yellow Optional AB
manifold serving an automatic (<14 bar for N2O)
manifold
Medical air compressor and surgical 1. Plant fault Plant fault Yellow Yes AB
air compressor
2. Plant emergency Plant emergency Yellow Yes AB
Medical vacuum plant 1. Plant fault Plant fault Yellow Yes AB
2. Plant emergency Plant emergency Yellow Yes AB
Oxygen concentrator 1. Plant fault Plant fault Yellow Yes AB
2. Plant emergency Plant emergency Yellow Yes AB
Pressure fault (pipeline) high or low For each gas service to indicate Pressure fault Red Yes AB
and oxygen concentration fault for that the pressure in the
PSA plant distribution system has risen/
fallen from the “normal” working
pressure given in Chapter 4
and, for PSA plant, that O2
concentration <94%
Vacuum pressure (pipeline) To indicate that vacuum in the Pressure fault Red Yes AB
pipeline distribution system has
risen above the normal working
pressure given in Chapter 4
Notes:
1. For liquid supply systems, see Chapter 6.
2. A = Central indicator panel – telephone room and/or porters’ room, ie 24-hour occupancy.
B = Facilities management office reception.

Table 25 Area panel legend and display


Alarm function Legend Colour Auditory
signal
For oxygen, nitrous oxide and medical air(1) to indicate that the pressure in the pipeline
High pressure Red Yes
serving the department has risen above the normal value given in Chapter 4
For each gas service to indicate that the pressure in the pipeline serving the department
Low pressure Red Yes
has fallen below the normal value given in Chapter 4
For vacuum to indicate that the pressure in the pipeline serving the department has
Vacuum fault Red Yes
risen above the normal value given in Chapter 4
Notes:
1. A high pressure alarm is only required when oxygen, nitrous oxide and medical air are installed together.
For location of area panels, see Table 11.

103
Medical gases – HTM 02-01 Medical gas pipeline systems – Part A: Design, installation, validation and verification

13 Pipeline installation

13.1 Generally, MGPS should be kept away from areas damage (for example vehicular movement):
where they may be subject to any of the following: by means of galvanised, profile-section steel
of sufficient thickness to afford adequate
a. mechanical damage;
protection. The protection should cover the
b. chemical damage; entire space taken up by the pipeline(s), but
c. excessive heat; stand off the surface such that the pipes can be
inspected visually (The armour should be
d. splashing, dripping or permanent contact with readily detachable to permit more detailed
oil, grease or bituminous compounds, electrical inspection.);
sparks etc.
b. when crossing horizontal surfaces, roofs etc:
13.2 Service ducts or voids containing pipelines that similar protection to (a) above should be
include valves etc should have adequate ventilation provided to withstand “stepping” damage
to prevent gas build-up in the event of any leakage. using profiled section, as above.
Elsewhere, where pipelines are brazed throughout
13.6 Pipework should be protected from lightning
their entire length (and where they will have been
subjected to a pressure test), no ventilation is strikes by ensuring that they are run within a
required. 60‑degree cone beneath the lightning conductor,
for example when run along parapet walls, or when
13.3 Exposed pipelines should not be installed in lift penetrating parapet walls. When run across roof
shafts, kitchens, laundries, boilerhouses, generator surfaces, a copper lightning conductor should be
rooms, incinerator rooms, storage rooms designed run on the top surface of the pipework cover
to house combustible materials, or in any other providing physical protection, and should be
fire-risk areas. Where pipelines in hazardous areas bonded to it.
are unavoidable, they should be enclosed in non-
13.7 Internal pipelines should be suitably protected
combustible, non-corrosive materials that have no
electrolytic reaction with copper in order to prevent where there is a possibility of physical damage,
the possibility of the liberation of gases into the for example from the passage of trolleys, tugs etc.
room in the event of pipeline failure. Medical gas 13.8 Wherever practicable, a clearance of at least 25 mm
pipelines should be routed away from natural gas should be maintained between each service and
pipelines where there is a potential for a flammable 150 mm should be the separation distance between
gas mixture to accumulate in the case of a leak. the medical gas pipeline and heating pipes, hot
13.4 Where pipelines are run in enclosed ducts with water service and steam pipelines. Where pipelines
other services such as steam mains and water supply cross over other services and a clearance of 25 mm
systems, they should be inspected regularly as cannot be maintained, they should be electrically
corrosion can occur as a result of chloride deposits bonded and wrap-insulated, in accordance with
following leakage. They should not be run in IEE regulations. They should be bonded to main
enclosed ducts with other services where they earth at building entry and exit. Care is required
cannot be inspected. when selecting pipeline routes to prevent the pipes
coming into contact with electric cables and wiring,
13.5 External pipe runs should be avoided when and to minimise the risk of electric shock in the
possible. Where external runs, however, are event of a fault on adjacent cables (see Chapter 2).
necessary, they should be protected as follows:
13.9 Underground pipelines should be run in properly
a. on external vertical surfaces up to the drained ducts not less than 450 mm x 450 mm
maximum height of exposure to possible which have removable covers. Where it is not

104
13 Pipeline installation

possible to provide removable covers, two pipes Figure 34 Typical ring-main arrangement
should be run in separate trenches with valves
Primary
provided in a convenient location at either end. Primary
VIE
& Secondary
VIE
The valves should comprise LVAs with NIST
connectors for the purposes of pressure and other Non-return Non-return
tests. The separation distance between the two valve valve

trenches should be not less than 2 m (see Ball Ball


valve valve
Figure 33). The two pipes should each be sized for
the design flow. One or more different gas pipelines
can be run in each trench. The route of the pipeline
should be identified on the surface and should be
clearly shown on site layout drawings. The
possibility of installing a “ring-main” (see Riser to
Figure 34) or double-end supply should also be department

considered for both air and oxygen within the


curtilage of the building. N.B. Diameter of ring pipework is
determined by maximum flow to be
13.10 Pipelines concealed within walls should have carried (ie total flow of all departments
connected to the ring)
their route clearly shown on “as-fitted” drawings.
Pipelines should not be encapsulated in floors,
and any joints should be kept to the minimum
practicable. Pipelines in stud or plasterboard walls
or partitions are acceptable, but the pipeline
should be protected from corrosion. If the
Ball Ball
enclosure of pipelines within plaster wall finishes is valve valve
unavoidable, they should be wrapped in protective Non-return Non-return
grease-free tape. valve valve

13.11 Pipelines need further protection in certain Secondary


Fully
Automatic
circumstances as follows: VIE
Manifold

a. where pipes pass through walls, partitions or


This diagram shows a single feed from each source to the ring main. However,
floors, they should be provided with sleeves of attention is drawn to paragraph 13.9, which details the provision of double feeds to
copper pipe (with fire stopping) and, where reduce the risk of supply failure arising from mechanical damage to vulnerable
pipework.
exposed to general view, be provided with Note: NIST connectors should be fitted either side of each valve. Where three valves
appropriate wall or ceiling plates; are installed close together, only one needs to be installed between the set of three.

Figure 33 Typical twin pipeline supply arrangement

Pipes in separate
ducts/trenches.
Minimum separation 2 m

Interior of building
LEGEND

Line valve with blanking spades


VIE compound with
primary and secondary Non-return valve
vessel
NIST test point
Dotted denotes part of VIE installation

105
Medical gases – HTM 02-01 Medical gas pipeline systems – Part A: Design, installation, validation and verification

b. in radiodiagnostic procedure rooms etc, radio


frequency (RF) screening wave guides may be
Note
required (the advice of the equipment For straight couplings, expanded joints may be used.
manufacturer should be sought);
c. corrosion of pipes can occur where they are in Other fittings
contact with timber that has been treated with
fire-resistant or flame-retardant compounds, for 13.18 Other fittings for connection to copper pipes (for
example some timber used for roof trusses and example valve and control panel fittings) may be of
floor joists. copper, brass, gun-metal, bronze or stainless steel.

13.12 This contact should be avoided by the use of


Cleaning
impermeable non-metallic materials in the area
where contact may occur. PVC spacers or adhesive Pipes
PVC tape may be used for this purpose. If spacers
are used they should not be liable to drop out due 13.19 All pipes must be cleaned and degreased for
to shrinkage or subsequent movement of the pipe oxygen service and be free of particulate matter
or timber. and toxic residues in accordance with BS EN
13348:2001. They must be individually capped
13.13 Such precautions are not required where untreated at both ends and delivered to site identified as
timber is used or where the treated timber is medical gas pipes.
effectively sealed with paint or varnish before the
pipes are fixed to it. Pipe jointing fittings
13.20 All pipe jointing fittings and sub-assemblies of
Pipeline materials
fittings for connection to pipes must be cleaned
Quality and degreased for oxygen service and be free of
particulate matter and toxic residues. They must
13.14 The manufacturer should comply with BS EN be individually sealed in bags or boxes and
ISO 9001:2000 for pipes and for all materials delivered to site identified as medical gas fittings.
including fittings, terminal units etc. A complete
specification is given in Model Engineering 13.21 Although it is not essential to degrease vacuum
Specification C11 – ‘Medical gases’. installations, these are frequently installed by the
contractor simultaneously with the medical gas
13.15 Where materials are obtained from suppliers from pipelines. Degreased pipe and fittings should
other countries, the suppliers should be registered therefore be used for the vacuum installations to
in accordance with BS EN ISO 9001:2000. avoid confusion. PVC pipework may also be used
for vacuum and AGSS but is unlikely to be of
Pipes benefit other than for exhaust discharges.
13.16 Material for pipes should be manufactured from
phosphorus deoxidised, non-arsenical copper to Note
BS EN 1412:1996 grade CW024A (Cu-DHP) Pipes should only be cut with wheel pipe cutters, not
in metric outside diameters and to: hacksaws, to prevent the ingress of copper particles.
• BS EN 13348:2001 – R250 (half hard) for
sizes up to 54 mm; or
Pipeline jointing
• BS EN 13348:2001 – R220 (annealed) for
larger sizes. General
Stainless steel is a suitable material for medical gas 13.22 Except for mechanical joints, only copper-to-
pipeline installations, but is not currently used by copper joints will be permitted on site, made with
installers, and Standards have yet to be established. brazing filler rods that can be used without flux.

Pipe jointing fittings


13.17 In addition to the above, pipe jointing fittings
should be end-feed capillary fittings to BS EN
1254-1:1998.
106
13 Pipeline installation

Use of N2 internal inert gas shield


Note
13.29 Brazing should be carried out using oxygen-free
Brazing is performed at a higher temperature than in
nitrogen as an internal inert gas shield to prevent
the case of silver soldering with capillary fittings; the
the formation of oxides on the inside of the pipes
exterior of the pipe will therefore have considerably
and fittings. This method leaves a bright, clean
darker oxide deposits.
bore. Some slight burnishing may occasionally
13.23 Copper joints to brass or gun-metal fittings will be observed on sectioned joints. Purging is still
require the use of flux, with subsequent cleaning required to remove the internal shield gas and the
to remove the flux residues and oxide deposits. other particulate matter not associated with the
brazing operation.
13.24 Heating of the joint for brazing should be carried
out with oxygen/acetylene or acetylene, liquid 13.30 Oxygen-free nitrogen should be supplied to the
petroleum gas/oxygen torches. Additional heating inside of the pre-assembled, unbrazed pipework
may be required for some fittings, for example, through a pressure regulator and flow controller or
by means of a second torch. flow-regulating device.
13.25 The techniques recommended cover all copper-to- Application
copper joints and all copper-to-brass/gun-metal/
bronze joints in an MGPS, and are explained in 13.31 Oxygen-free nitrogen as an internal inert gas shield
more detail below. should be used for all positive pressure gases and
for vacuum pipelines – up to and including
13.26 The brazing technique should be used on all 22 mm – that are run in medical gas supply units
medical gas pipeline services. and to individual terminal-unit drops. Once the
route of the vacuum service has been clearly
Pipe preparation established (that is, above the ceiling level),
13.27 Pipe ends should be cut square with the pipe axis, nitrogen purging may be discontinued. Nitrogen
using sharp wheel cutters whenever possible, and purging is not required for AGS disposal systems.
be cleaned to get rid of any cuttings or burrs.
Expanded joints should be made using the Note
appropriate tools and dies. Only where the cut During the first-fix stage of pipeline installation,
pipe has either deformation or a burr which particularly when installing in confined locations such
significantly restricts the flow of gas will de- as medical supply units or running pipework within
burring be necessary. Only oil- and grease-free partitions etc to individual terminal unit drops, it is
tools and dies should be used. possible to inadvertently crossover a pipeline. This is
13.28 When brazing copper-to-copper joints: usually discovered at an early stage and, so that the
pipe section can be re-assigned and the fault can be
a. the brazed joints should be made using a silver-
corrected, it is essential to use the shield gas to
copper-phosphorus brazing alloy CP104 to
maintain the cleanliness of the internal bore.
BS EN 1044:1999. No flux should be used;
b. ensure adequate protection of adjacent pipe 13.32 By agreement between the health facility
runs and other services. management and the pipeline contractor, the use
of a purge gas may be waived on joints such as
Note break-ins to old pipeline systems, where pipe joints
will not have been made in accordance with this
Brazing copper to brass/gun-metal/bronze is not
technique.
performed on site. Manufacturers use copper-silver-
zinc brazing alloy AG203 to BS EN 1044:1999 with 13.33 It is recommended that the pipeline to be brazed
an appropriate flux. The flux residues created by the should first be flushed to remove the air. This may
process are chemically removed and, if necessary, the be followed during the brazing operating by a
complete assembly is cleaned and degreased for oxygen continuous or intermittent flow as necessary to
service. Where brass/gun-metal/bronze fittings are prevent the ingress of air. Pipe ends may be capped
required to be installed they should be supplied if desired to direct the flow of nitrogen into
complete with copper “tails” of adequate length to sections of the pipe or pipes to be brazed.
ensure that the brazing process does not damage the Particular attention should be given to the gas
components.

107
Medical gases – HTM 02-01 Medical gas pipeline systems – Part A: Design, installation, validation and verification

shielding of T-joint fittings. Care should also Penetration


be taken to ensure that other pipelines in close
13.38 Penetration of brazing alloy:
proximity to the one being brazed do not oxidise
due to heat transfer. It is essential that there is a a. due to tolerances of the capillary space on these
leak-free connection between the pipework to be pipes and fittings, full penetration of the
brazed and the nitrogen supply. brazing alloy may not occur and is not
necessary;
Safety
b. the minimum penetration at any point on the
13.34 If working for prolonged periods in very confined joint must be three times the wall thickness of
spaces, precautions must be taken to avoid the tube or 3 mm, whichever is greater;
excessive build-up of nitrogen by ventilating the
c. the pipe should be fully inserted up to the
space or by piping the shield gas safely out of the
shoulder of the fitting.
space. The oxygen content of the ambient air
should be monitored when brazing in a confined
space.
Note
These tests can be carried out on a sectional basis.
Control of cylinders
13.35 The contractor and the site engineer must keep Jointing methods (mechanical)
a record of nitrogen cylinders held on a site.
Nitrogen cylinders should be accounted for and 13.39 In addition to mechanical connections to plant
removed from the site at the end of the contract, and valve assemblies, mechanical connections
and must not become mixed up with medical gas can be used for connecting pre-piped bed-head
cylinders. trunking/wall units to the pipeline distribution
system. They may also be used in situations where
Inspection of joints brazing may present a fire risk and in other
situations when patients cannot be transferred to
13.36 Inspection of joints should be carried as a “rolling” alternative accommodation (in which case they
procedure on a monthly basis as work progresses should be of the permanently swaged type).
for each team performing the installation in Mechanical connections should have comparable
accordance with the following procedure: structural integrity to brazed fittings in normal
a. the site engineer should identify a number of operation and in the event of fire. Any lubricant
fittings to be cut out for examination in order required for swaging should be oxygen-compatible.
to establish the quality of the finished joint. The fittings should not contain elastomeric
The exact number to be cut out will vary with materials.
the size of the installation: as a guide, a ratio 13.40 Mechanical joints can also be used in an
of one fitting per 200 should be cut out; a emergency. Fittings that are non-permanent should
minimum of ten for all systems should be cut be number-tagged and marked on the record
out for examination (it is preferable to perform drawings.
these checks before pressure-testing sections of
pipeline); Note
b. the fittings cut out should be cut open Open ends of the remaining pipework should be
(quartered longitudinally) and examined. If capped off. The installation should be made good as
unacceptable joints are found, adjacent fittings soon as possible in accordance with paragraphs 13.29–
should be cut out until the extent of any faulty 13.35.
workmanship has been established. This may
require extensive removal of sections of the 13.41 PTFE tape is not an acceptable sealing material on
installation. oxygen systems or elsewhere downstream of final
filters on supply plants.
Internal cleanliness
13.37 The tube and fitting should be internally clean and
free from oxides and particulate matter. Some heat
burnishing may be apparent and is acceptable.

108
13 Pipeline installation

13.46 The connection of individual, or a number of,


Note vacuum terminal units into branches should be
taken into the top of the pipeline to avoid flooding
PTFE tape, if applied, can enter the gas system and
other vertical pipe drops, should liquid carry-over
fragments can block terminal units and present a fire
occur. Each vacuum main riser should be provided
hazard with high-pressure oxygen. Also, when applied
with a double (15 mm) valve arrangement at the
by hand, traces of oil and grease can contaminate the
base, with an intervening full bore pipe section,
inside of the pipeline.
preferably transparent, to permit drainage when
13.42 Liquid or gel-sealing media should be used only the system is under vacuum; one of the valves
if they have been tested and proven safe when should be lockable in the closed position. Within
subjected to the tests specified in BS EN ISO trunking systems and medical supply units etc,
15001:2004. vacuum pipes should connect into the underside
of terminal units.
Capping
Identification of pipelines
13.43 Sections of pipeline should be capped as soon as
they are completed so as to prevent the ingress of 13.47 Pipelines should be identified in accordance
debris. with BS 1710:1984, and colour banding for
the pipelines should be used. Colour band
identification (see Figure 35) should be applied
Pipe supports near to valves, junctions, walls etc. A label applied
13.44 The pipeline should be adequately supported at every 3 m and bearing 6 mm size letters should
sufficient intervals in accordance with Table 26 to identify each gas. Self-adhesive plastic labels of
prevent sagging or distortion. Supports for surface-
mounted pipework should provide clearance to Figure 35 Pipeline identification colours
permit painting of the surface. Where it is essential
for pipes to cross electric cables or conduit, they O2 OXYGEN
should be supported at intervals on either side of
the crossing to prevent them from touching the N2O NITROUS OXIDE
cables or conduit. Supports should be of suitable
material or suitably treated to minimise corrosion OXYGEN/NITROUS OXIDE
O2/N2O 50/50
and prevent electrolytic reaction between pipes and MIXTURE
50%/50%
supports.
MEDICAL AIR
MA
Table 26 Intervals between copper pipe supports
(horizontal and vertical)
SA SURGICAL AIR

Outside diameter (mm) Maximum interval between


supports (m)
MEDICAL VACUUM
VAC
Up to 15 1.5
22–28 2.0
AGS AGS SYSTEM
35–54 2.5
>54 3.0
HELIUM/OXYGEN MIXTURE
Note: Consideration should be given to additional supports He/O2 79/21 79%/21%
near LVAs, elbows etc where the potential effects of
inadvertently applied torque can result in severe pipeline
distortion or fracture. SN SURGICAL NITROGEN
(Alternative label N2)
13.45 Pipelines need not be laid with falls. In the case of
vacuum, the sub-atmospheric pressure will result
in the evaporation of any moisture entering the EXHAUST EXHAUST FROM PSVs ETC

system.

CO 2 CARBON DIOXIDE

109
Medical gases – HTM 02-01 Medical gas pipeline systems – Part A: Design, installation, validation and verification

approved manufacture may be used for this


purpose. A band 150 mm wide is usually adequate.
Note
All colour-coded tapes applied by the pipe In cases where medical or surgical air terminal units
manufacturers should be removed before the are not required to be included in these pendants, an
systems are identified, in accordance with this AVSU will still be required “locally” for emergency
paragraph. isolation and servicing of the air-braking mechanisms
of some units.
13.48 Care should be taken to maintain pipeline
identification when periodical re-painting is
undertaken. The direction of flow should be Flexible pendant fittings
indicated.
13.55 These should comply with the requirements of
BS EN 737-1:1998 and BS EN 739:1998. In
Pipeline components particular, all loose assemblies should be provided
13.49 Pipeline components, which may be attached to with appropriate NIST connectors.
an MGPS, include various types of terminal unit,
AVSUs and other components such as emergency Bed-head trunking/walling systems
inlet ports and pressure control equipment.
13.56 These fittings should generally be in accordance
with BS EN ISO 11197:2004. Separate
Medical supply units compartments should be provided for electrical
13.50 These should comply with BS EN ISO 11197: services, nurse call/radio etc and medical gas
2004. The construction should provide segregation pipelines.
of FELV electrical services by means of partitions
13.57 Any flexible connecting assemblies used within the
or flexible conduit as appropriate. Access to “live”
fitting should comply with BS EN 739:1998.
components should be via panels that are
removable by means of tools only. Multi-purpose 13.58 The medical gas compartment should be provided
medical supply units should be constructed in such with ventilation by means of louvres, slots etc to
a manner to ensure that flexible hoses are not prevent the accumulation of any gas in the event
subject to excessive “kinking” or “twisting”. The of rupture of the medical gas pipeline services.
flexible hose materials should be free from volatile 13.59 In some departments, to engender a more
or organic compounds and be tested prior to domestic environment, medical gas and other
installation. Rigid units should be piped in copper. bedhead services are installed within concealed
13.51 When these fittings include flexible connecting recesses (or behind decorative panels, paintings
assemblies for the gas supply, the method of etc). In such cases, adequate provision must be
attachment to rigid pipework or terminal units made for ventilation, and the required space
should be by means of the appropriate NIST to permit connection and disconnection of
connector in accordance with BS EN 737-1:1998. equipment should be considered. The covers
should be clearly labelled to indicate that medical
13.52 The fittings should be provided with adequate
gas equipment is installed within/behind.
venting to allow escape of gas in the event of
rupture of one or all of the medical gas services. 13.60 There are three possible installation procedures:
13.53 The recommended height for rigid pendants is a. the connection between the pipeline and the
2000 mm above FFL. The maximum height for trunking should be considered as a second-fix,
pendants capable of vertical movement should be with the trunking being pre-piped and
2000 mm above FFL in the fully retracted certificated as having passed a first-fix test; after
position. brazing, the joints will be subject to a second-
fix test and leak-tested;
13.54 The use of medical air for pneumatically actuated
pendants is covered in Chapter 3. b. the connection between the trunking and the
pipework should be as paragraph 13.55;
c. the connection should be by mechanical
means, and the separate pipeline connections
should be staggered to prevent cross-connection

110
13 Pipeline installation

at a later date in the event of the necessity to 13.65 LVAs should be provided as follows:
dismount and reconnect. a. at the connection of the pipeline to any source
of supply;
Note
b. at the emergency inlet port (that is, it forms the
After any such disconnection and reconnection, it will emergency inlet point);
be necessary to carry out the full range of anti-
confusion tests. c. at the pipeline entry to a building;
d. at the pipeline exit from a building;
LVAs and AVSUs e. at the connection of branches to the main
13.61 All valves should be of the lever-ball type, having pipeline run;
flanged O-ring seal connections which open and f. at the connection to risers;
close with a 90-degree rotation: the handle should
be in line with the pipeline when open. g. at branches from risers to serve a number of
similar departments;
LVAs h. upstream, downstream and in the branch
13.62 LVAs should be capable of being locked with the connection to a ring-main.
valve in the open or closed position. Means of
physically isolating and blanking the pipeline both Notes
upstream and downstream of the valve should be a. Where departments on a floor are functionally very
provided. The means of isolation should be in the different, for example wards and diagnostic areas,
form of a spade that can be readily deployed. It it is preferable to run separate branches from the
should blank both the pipeline and the valve port risers.
and be visible when deployed. Each valve should
be provided with a set of “through” and “blanking” b. LVAs should not be installed where a leakage of
spades; they should be coloured white and red gas could cause an accumulation that is likely to
respectively. The valve flange should include the result in a hazardous atmosphere developing.
thread, and the bolts should be of sufficient length The assembly should include clear labelling of the
to permit loosening to allow removal/replacement service.
of the spades without loss of structural integrity
of the connection. Union-type connections with AVSUs
O-rings are permissible, but the securing nut must
13.66 AVSUs are provided for user access in an
also have sufficient thread length to permit venting
emergency (or for maintenance purposes). They
while maintaining the structural integrity of the
should be in accordance with the requirements
connection. A single key for each service is
above for LVAs except that security is achieved by
considered to provide sufficient security.
installing them in an enclosure with a lockable
13.63 In the event of leakage of the through or door designed such that it can be closed with the
blanking spade, gas must be capable of venting to valve either in the “open” or “closed” position.
atmosphere and must not be able to enter either
the valve port or the pipeline section blanked. Note
13.64 The appropriate NIST connector bodies with self- The views of the building operator should be sought as
sealing check valves and lockable blanking nuts to the level of security that will be required and hence
should be provided upstream and downstream of the range of keys.
the flanges. Gas identity and flow direction arrows
should be provided for each valve. 13.67 In an emergency, the user must be able to gain
access in order to operate the isolating valves
Note quickly and simply without the need for a key.
A single NIST connector will suffice in ring-main There are several methods of providing such
branch connections between the three closely spaced emergency access, for example break-glass panels
valves. and plastic push/pull-out inserts. Whichever
method is used must be safe and secure and must

111
Medical gases – HTM 02-01 Medical gas pipeline systems – Part A: Design, installation, validation and verification

clearly act as a deterrent to tampering without Pressure control equipment


introducing undue risk of injury to the user. Float
glass must not be used. The method of emergency 13.74 Medical gases may be distributed at a higher
access must be obvious and clearly labelled, and its pressure than the eventual nominal pipeline
use must be evident. distribution pressure at terminal units. Where this
is the case, the maximum pressure should not
13.68 AVSUs may be designed for a single pipeline exceed 1100 kPa, and the local pressure “control”
service or multi-services. Where the cover bears the equipment should be installed in an area that has
name of the gas service, it should be gas-specific. good ventilation and be in a position where it is
In the case of multi-service AVSUs, the design readily accessible for maintenance/service.
should permit the attachment of a hose assembly
to any one or more of the NIST connectors and be 13.75 The pressure control equipment should include
such that the door can then be closed and locked. duplex pressure-regulating valves, each with
The AVSU may include provision for pressure upstream and downstream isolating valves, safety
gauges/pressure switches by means of separate valves and NIST connectors. The safety valve
bosses. discharges should be run to the exterior of the
building; medical air and surgical air may be
13.69 The enclosure should have adequate ventilation to discharged within a plant space, for example
prevent the accumulation of gas in the event of a a plantroom above an operating department,
leak. Pipe entries and other penetrations should be provided it is terminated in a safe position.
sealed to prevent gas escape by routes other than
the vents or openings into the user space. The Pressure sensors
enclosure should be designed to facilitate sealing
of these entries on site. Gas identity and flow 13.76 Pressure sensors to provide the alarm function will
direction arrows should be provided for each valve. need to be fitted to pipeline distribution systems.
In all cases they should be installed in a location
13.70 Provision and location of AVSUs is covered in which is adequately ventilated and having access
Chapter 3. for maintenance. They may be incorporated
downstream of AVSUs. Where not incorporated
Note into an AVSU, the pressure sensor should be
AVSUs should not be installed in positions where they close to the AVSU so that it is accessible for
can be obscured or damaged, for example within the maintenance. Pressure sensors should be factory-
“swing” of a department door or behind partitions. set and be a replacement item. They should be
connected to the pipeline by means of a minimum
leak connector.
Specific labelling requirements
13.71 All AVSUs should be labelled to identify the Pressure gauges
individual rooms, sets of terminal units etc 13.77 Pressure gauges are not usually required outside
controlled. The upstream and downstream NIST the plantroom of an MGPS. If provided, however,
connectors should be clearly identified by a they should similarly be installed in an adequately
permanent label, securely fixed. ventilated location. They may be incorporated
13.72 In critical care areas, where dual circuits and/or within AVSUs, operating room supply fittings etc.
subdivisions of circuits occur, terminal units need They should be installed with isolation cocks.
to be correspondingly identified with the specific
AVSUs (see Figures 4 and 5). Test points
13.73 In the case of pneumatically-powered pendant 13.78 Each supply plant, that is, liquid facility, manifold
fittings where, typically, medical air (or surgical (main and ERM), compressor plant, PSA and
air) is used for the power source, the AVSU that blending plant, should be provided with a test
controls the pneumatically-powered devices should point comprising lockable valve and terminal unit.
be identified. This should be within the plantroom or enclosure,
and be sited immediately upstream of the
distribution pipeline isolating valve.

112
13 Pipeline installation

Emergency inlet port position which – except for air – should be


external.
13.79 Medical oxygen and 400 kPa medical air systems
should be provided with an emergency inlet port 13.83 The commissioning of medical gas pipeline line
to the pipeline distribution system. This should be pressure regulators, warning and alarm systems,
located downstream from the main source of and pressure settings is crucial to the performance
supply line valve isolation point to permit of anaesthetic equipment and patient safety; once
connection of a temporary supply plant. The commissioned, medical gas pipelines are
emergency inlet should comprise an LVA, an subject to strict permit-to-work procedures.
additional non-return valve on the emergency inlet Decommissioning a complete system is highly
side and a connection that can be blanked, to disruptive to patient care and introduces
which the emergency inlet can be made. considerable risk.
13.80 An emergency inlet port is not required for 13.84 The Pressure Systems and Transportable Gas
700 kPa surgical air systems. Containers Regulations 1989 require pressure
safety devices to be periodically tested. It is not
Line pressure alarms and safety valves appropriate to test an MGPS by either raising
the line pressure regulator setting or manually
13.81 The purpose of the line pressure alarm is to warn unseating the relief valve. Such action could result
users that the nominal line operating pressure is in failure of anaesthetic equipment and – if the
out of limits and that gas mixtures, whether safety valve to fails to reseat – considerable gas loss
supplied by a blender/mixer, an anaesthetic and further hazard. Medical gas pipeline line
machine or patient ventilator, may deviate from distribution systems should be provided with a
the clinically desired proportion. Local action can pressure relief device downstream of the line
then be taken to adjust the mixture, or when an pressure regulator connected by means of a
anaesthetic machine is in use the reserve cylinders three-way cock so that the safety device can be
can be brought into use. The low-pressure alarm exchanged for a “certificated” replacement in
for nitrous oxide/oxygen mixture supply pipelines accordance with the frequency required by the
will warn of possible demand valve regulator Regulations.
failure so that a portable cylinder can be made
available. The high/low pressure limits have been Other systems
set to accommodate the design of most types of
anaesthetic equipment where differential pressure 13.85 Quench dump pipes from magnetic resonance
or low pressure may affect performance. imaging (MRI) cryostatic units should be sized
to pass the high flows resulting from magnet
13.82 The line pressure safety valve provides limited quenching. They should be routed to safe areas
safety from differential pressure effects since the and protected from obstruction. Failure to install
pressure at which maximum discharge occurs will adequately sized pipework will result in the venting
result in a differential much greater than that for of asphyxiant helium and/or nitrogen at low
which the anaesthetic equipment has been temperatures into the working environment,
designed. They are therefore strictly system with potentially fatal results.
protection devices. All safety valves should have
a separate discharge pipe that is run to a safe

113
Medical gases – HTM 02-01 Medical gas pipeline systems – Part A: Design, installation, validation and verification

14 Accommodation

Design and construction of plant and


manifold rooms Note
It is permissible to accommodate medical compressed
Location of manifold rooms air plant, vacuum plant and AGS disposal system
14.1 Cylinder gas/liquid supply systems should not pumps in general plant areas accommodating such
be located in the same room as medical air equipment as air handling units, water service systems
compressors, PSA systems or vacuum plants. etc. They should not, however, be located with heating
or hot water service equipment or equipment likely to
14.2 Manifold rooms, emergency/reserve manifold produce any fumes or odour.
rooms for PSA systems, VIE installations and
medical compressed air systems should be located
Access
to take account of the risk assessment, but should
also take account of the location of the medical gas 14.7 Access to manifold rooms should be from the open
cylinder storage area. air, not from corridors or other rooms.
14.3 All manifolds, including the emergency reserve 14.8 Normal commercial lorry access is suitable for gas
manifolds, may be located within the same room. cylinder delivery vehicles, but consideration should
Manifold rooms should be located on an external be given to the provision of a raised level loading
wall(s) to facilitate ventilation, which will be bay to reduce cylinder handling hazards.
required at high and low level. Internally sited 14.9 Two doors should preferably be provided in a
manifold room and cylinder stores may require manifold room. One should be large enough to
mechanical ventilation. facilitate cylinder handling and must be in an
14.4 The emergency/reserve manifold for liquid oxygen outside wall. Exits must be free of all obstructions.
systems has traditionally been located within the Doors must open outwards. All doors must
VIE compound, but it is preferable to site the normally be locked to prevent unauthorised access,
manifold separately. For new installations, these but should be provided with means of entry and
emergency/reserve manifolds should be located exit in an emergency (for example by a push-bar
separately. arrangement on the inside).
14.5 In the case of surgical air the volume of gas used 14.10 Internal walls and ceilings, including any internal
is relatively small even though the instantaneous doors of the manifold room, should be of a suitable
flow rates are high. Therefore, it may be more non-combustible two-hour fire-resistant material as
convenient to include the manifold within the defined in BS 476-4:1970 and BS 476 Parts 20–23
operating department. (1987). Internal doors should be avoided where
practicable. Smoke detectors should be provided.
14.6 The surgical air 700 kPa manifold room may be
Automatic fire suppression should be considered.
used as the ready-use store for a small number of
Manifold rooms should not be located near high-
spare cylinders to be used on anaesthetic machines.
dependency wards.

114
14 Accommodation

Construction and layout of manifold rooms plantroom is deep-plan, mechanical ventilation


should be provided. The ambient temperature
14.11 The manifold room will contain the manifolds
of manifold rooms and plantrooms should be
as well as cylinder racks holding sufficient spare
maintained within the range of 10–40°C. The
cylinders to replace one bank of each manifold
ventilation rates should ensure that the plantroom
and the emergency/reserve manifold. (For nitrous
temperature does not exceed ambient temperature
oxide/oxygen manifolds, sufficient spare capacity
by more than 10°C.
for two banks of cylinders should be provided.)
Further replacement cylinders should be supplied 14.18 Manifold rooms may be used to store small
from the medical gas cylinder store. The size of the numbers of nitrous oxide/oxygen cylinders
manifold room should therefore be determined by intended for portable use; these are taken from the
the risk assessment. Adequate space should also be main cylinder store for the purpose of temperature
allowed for cylinder handling. equilibration, before being delivered to wards etc.
14.12 A typical automatic manifold with two duty and 14.19 To achieve temperature equilibration, additional
two stand-by cylinders is 1.8 m long and 0.6 m heating may be required; the natural ventilation
deep. One extra cylinder on each bank adds must not be reduced. Where such heating is
approximately 0.5 m to the overall length, so that provided, it should be by indirect means, for
a 2 x 6 manifold is approximately 4 m long. example steam, hot water or warm air. Naked
flames and exposed electric elements should not be
14.13 All medical gas manifolds may be installed in
used, and excessive surface temperature should be
the same room. Additional floor area should be
avoided. If necessary, cylinders should be protected
provided to accommodate separate storage racks
from excessive heat. Any primary heat source
for each gas. The racks should be designed along
should be located in a safe position, preferably
the lines of those on the manifolds, but the stored
remote from the manifold room.
cylinders may be closer together. Racks should
conform to ISO 32:1977. With the exception of 14.20 Cylinder recognition charts, supplied by the
small cylinders of N2O/O2 mixtures, under no medical gas supplier, should be prominently
circumstances should rooms contain gas cylinders displayed as appropriate.
other than those appropriate to their manifolds.
Lighting
Heating and ventilation
14.21 Manifold rooms should be provided with lighting
14.14 Ventilation louvres should be provided at both to an illumination level of 150 lux by means of
high and low level for all manifold rooms, to allow bulkhead lighting fittings to BS EN 60529:1992.
circulation of air. As a guide, separated openings Plantrooms other than manifold rooms should be
equivalent to at least 1.5% of the total area of the provided with a lighting level of 200 lux.
walls and floor should be provided. For example,
given a manifold room 5.0 x 4.0 x 2.4 m with a Noise control
total area of the walls and ceiling of 63.2 m2, the 14.22 Plantrooms should be designed and constructed to
total free open area for ventilation required is ensure the satisfactory control of noise emission.
1 m2. The effect of two vacuum pumps or compressors
14.15 Air intakes for compressor inlets should, if running together, in the case of duplex
possible, be located externally. However, they installations, and three or more in the case of
should not be installed as an alternative to the multiplex installations, will be to increase the free-
provision of adequate ventilation for cooling field noise level outside the plantroom by 5 dBA
purposes. for each additional pump or compressor operation
over and above the specified limits. Consideration
14.16 All ventilation louvres should be vermin/bird-
should be given to providing acoustic enclosures to
proof.
reduce the free-field noise levels in noise-sensitive
14.17 PSA and medical air compressors liberate, under areas adjacent to plantrooms.
maximum flow conditions, considerable heat.
14.23 Acoustic enclosure and/or plantroom design
Moreover, these plants aspirate air for breathing
must not inhibit normal cooling functions or
purposes. Generous natural ventilation should be
maintenance activities.
provided, and where this is not possible if the

115
Medical gases – HTM 02-01 Medical gas pipeline systems – Part A: Design, installation, validation and verification

14.24 Free-field noise levels should be given to the where necessary to prevent the transmission of
architect to assist in acoustic design of the noise and vibration along the pipelines and
plantrooms. conduits. Electrical bonding will be required.
14.25 The discharge from some vacuum pumps may
Labelling/signage
require silencing.
14.28 Labelling for medical gas systems, equipment and
14.26 Compressors and pumps should be mounted on
accommodation should be in accordance with
properly-selected anti-vibration mounting, where
Appendix K.
necessary, to minimise transfer of noise and
vibration to the structure of the building.
14.27 All pipework and electrical conduits connected to
the plant should be fitted with flexible connectors

116
15 Validation and verification

15.1 This chapter covers the validation and verification coupling comprises two joints and a “T” comprises
and filling for use of MGPS. The requirements for three joints. On a minor modification, from which
AGS disposal systems are also covered in paragraphs existing terminal units would not be removed, the
15.169–15.178. carcass pressure test can also be omitted. All other
tests would be required, including a working
15.2 This chapter describes the tests required and the
pressure test.
test methods. The contractor should provide
instrumentation for the functional tests. The 15.6 The programme of tests is divided into three
Quality Control Pharmacist normally provides phases:
instrumentation for the quality tests. Calibration
a. tests and checks on the pipeline carcass;
certificates should be available for all
instrumentation. Tests are listed in Appendix A b. tests and commissioning of the complete
with the associated forms. pipeline system (with terminal units installed)
for safety, performance and particulate
15.3 The objective of testing and commissioning is to
contamination using test gas;
ensure that all the necessary safety and performance
requirements of the MGPS will be met. Testing and c. filling of the systems with specific gases for the
commissioning procedures will be required for new purposes of identity and quality tests of the
installations, additions to existing installations and specific gases prior to use for patient care.
modifications to existing installations. The scope of 15.7 The basic rationale for the tests is depicted as a
work will dictate the specific test programme decision tree in Figure 36.
required. This is described in more detail in
paragraphs 15.12–15.14.
Notes
15.4 For modifications and extensions (except for the
Systems that are not to be taken immediately into use
final connection), all work should be performed
should be filled with medical air and maintained at
with an inert gas shield; thus, it is essential that a
operating pressure. Systems other than medical,
physical break is employed between the pipeline
surgical or dental air supplied from compressors
being modified/extended and the system in use.
should be filled with medical air from cylinders.
(This will usually be by deploying “spades” in
AVSUs and LVAs, or by cutting and capping the Commissioning of liquid supply systems prior to
pipe.) Prohibition labels should be affixed to all handover should be avoided. (Under “no flow”
terminal units in the system affected in occupied conditions, liquid will evaporate and oxygen will blow
areas. off to atmosphere.)
15.5 For small extensions comprising fewer than 20
15.8 The personnel and test equipment needed for these
brazed joints per gas service, all the tests may be
tests are listed together with the test requirements
performed with the working gas – the carcass
in Table 27. The particulate contamination test for
pressure tests being replaced by a system leakage
all pipeline systems may be checked using medical
test of the complete extension. An extension
air to establish that the pipeline has been
comprising more connections would, however, be
constructed correctly and is not contaminated.
deemed to be a small installation, requiring all the
Successful completion of the commissioning tests
appropriate tests to be carried out, up to the final
normally indicates the end of the installation
connection; the final connection would be tested at
contract. The systems may then be left under
pipeline distribution pressure. For the purpose of
pressure, filled with medical air, for an indefinite
ascertaining the number of joints, a straight
period. Responsibility for the system during this

117
Medical gases – HTM 02-01 Medical gas pipeline systems – Part A: Design, installation, validation and verification

Figure 36 Decision tree for testing and commissioning

Pre-Contract Works
Extension/ Test existing
Completely No modification to system for
new system? existing system performance

Yes
Prepare total
Install system system
to carcass/first performance
fix stage specification

Carry out Carry out visual checks Valves


remedial work carcass tests leakage
cross-connection

No
Pass?
Yes
Yes
Remedial No Carry out Complete
work to remedial work installation to
carcass? 2nd fix stage

Carry out leakage


system tests cross-connection supply system performance
AVSU/TU/NIST function & performance safety valves
pipeline system performance alarm systems
No
Pass?
No
Yes
OK to
Yes Purge with
purge Carry out
test gas or
installation particulate test
working gas
only?

No
Pass?

No

Has
System Connect to System now to system been
to be taken No
medical air be taken into maintained
into use supply source use? under
now? pressure?

No Yes Fill to working


pressure and
OK to leave pressurised Yes
Yes Purge and fill
purge with working
installation gas
only?

Carry out gas


identity and
quality tests

No
Pass?

Yes

Carry out
No No
performance Completely
Pass? tests of total new system?
system
Yes

Yes
Remove
Construction
labels

System
available for
use

118
15 Validation and verification

period needs to be clearly defined in the contract; MGPS after handover should be permitted access
the Authorised Person (MGPS) ultimately during contract work. This should be included in
responsible for the day-to-day management of the the contract agreement.

Table 27 Personnel and test equipment requirements


Paragraph Test Personnel Equipment
15.12: Pipeline carcass Labelling and marking CSO and CR Visual
Sleeving and supports CSO and CR Visual and tape
Leakage CSO and CR Pressure-measuring device
Cross-connection CSO and CR Pressure-measuring device

15.13: Pipeline system Leakage CSO, CR and AP Pressure-measuring device


Closure of AVSUs and LVAs CSO, CR and AP Pressure-measuring device
Zoning of AVSUs and CSO, CR and AP Open probes or special test device
terminal unit identification
Cross-connection CSO, CR and AP Open probes or special test device
Flow and pressure drop at CSO, CR and AP Special test device, certified probes
individual terminal units,
mechanical function and
correct installation
NIST connectors CSO, CR and AP Full bore NIST probes and nut
System performance CSO, CR and AP Metered leaks and special test device
Supply systems CSO, CR and AP Visual
Pressure safety valves CSO, CR and AP Visual
Warning and alarm systems CSO, CR and AP Visual
As-fitted drawings CSO and AP Visual
Purging and filling CSO and CR Gas source and delivery equipment
Particulate contamination (see CSO, CR, AP and Particulate matter test device (PMTD)
note after paragraph 15.8) QC (MGPS)
Gas quality CR, QC (MGPS) PMTD, oil, moisture, CO, CO2, SO2 and
and AP N2 oxides measuring devices, O2 and N2O
analysers
Gas identification CR, QC (MGPS) O2 analyser and N2O meter
and AP
AGS disposal systems CR and AP(1) Metered leaks and AGS test device
Key:
CR Contractor’s representative.
AP Authorised Person (MGPS).
CSO Contract Supervising Officer (for tests on the pipeline distribution system, CSO responsibility would normally
involve witnessing of the test documentation).
QC (MGPS) Quality Controller (Medical Gas Pipeline Systems)
Note:
1. The QC (MGPS) can perform this test

119
Medical gases – HTM 02-01 Medical gas pipeline systems – Part A: Design, installation, validation and verification

Tests on the pipeline system


Note
15.13 The following tests and checks must be carried out
In some circumstances an MGPS may not be taken
after complete installation of the pipeline system:
into use immediately after construction and will be
left filled with medical air. In these circumstances, the a. tests for leakage on each MGPS;
particulate contamination and odour/taste tests may be b. tests of AVSUs for closure, correct service
carried out before purging and filling with the working and control of the terminal units in the zone:
gas (see paragraphs 15.81–15.82). checks for correct labelling of AVSUs for zone
reference and identity of terminal units
15.9 All supply systems and their major components controlled and flow direction indication;
should have certificates (as specified in Model
c. tests of LVAs for closure and identification;
Engineering Specification C11 – ‘Medical gases’)
which show that they meet the design requirements d. tests for cross-connection, flow, pressure drop,
of the pipeline system. mechanical function and correct identity of the
terminal units: checks for correct labelling and
15.10 Only contractors who are registered to BS EN ISO
association with AVSUs (this is only required
9001:2000/BS EN ISO 13485:2003 with their
when, within a specific area, there are separate
scope of registration defined to include
circuits for the same service, for example dual/
commissioning should undertake engineering
split circuits);
validation and verification.
e. tests for mechanical function and identity of
Note NIST connectors;
BS EN ISO 9001:2000 registration is also f. performance tests of the pipeline system;
recommended for independent medical gas testing g. functional tests of all supply systems;
agencies but is not necessary for appropriately trained
and appointed hospital-based QCs (MGPS). h. checks of safety valve certification;
(A national register of QCs (MGPS) is to be prepared j. tests of warning systems;
during the lifetime of this Health Technical
Memorandum.) k. tests for particulate contamination/odour/taste:
these may be carried out immediately after
installation, using medical air, or after purging
15.11 All relevant tests should be carried out by the
and filling with the specified gases. It is
persons listed in Table 27 and witnessed by the
intended that the Quality Controller (MGPS)
appropriate persons, who must record the results
is handed over a system that is purged clear of
of the tests in writing for the hospital authority.
gross particulate contamination before being
filled with the working gases. However, it is
Summary of tests accepted that this may not always be possible.
If the system is not to be taken into immediate
Tests and checks on the pipeline carcass
use, the tests for particulate contamination and
15.12 The following tests must be carried out after odour/taste should be carried out with medical
installation of the pipeline carcass but before air, and the system then left under pressure (see
concealment: paragraph 15.93);
a. visual check of pipeline labelling, marking,
sleeving and support; Note
b. leakage test; Nitrous oxide and nitrous oxide/oxygen mixture are
not tested for odour.
c. tests for cross-connection;
d. valve tests for closure, zoning and leakage. m. tests for anaesthetic gas scavenging disposal
(These tests will be repeated as part of the systems.
pipeline system tests and the contractor may
wish to defer closure and leakage, but may
choose to carry out a zoning check.)

120
15 Validation and verification

Tests before use test can be carried out by using the medical air
compressor system, provided that the quality tests
15.14 The following tests must be carried out after
have been satisfactorily carried out to demonstrate
purging and filling with the working gas:
that the criteria set out in Table 30 have been met
a. tests for particulate contamination (see and that the air supply plant is continuously
paragraphs 15.93 and 15.130–15.136); monitored for moisture during the test.
b. tests for gas identity; 15.19 Such a compressor system can also be used for the
c. tests for gas quality. single point performance tests etc and for initial
purging and particulate testing of these systems.
Once tests have been completed, the system
General requirements for testing should be maintained under pressure by means of
15.15 The tests described in this document are air supplied from medical gas cylinders until filled
generally carried out, in the order given, for new with the working gas, when full QC checks will be
installations. It may be necessary to amend the test carried out.
programme for modifications or extensions to
existing systems. Care must be taken, however, Note
to ensure that the basic principles are followed.
The use of portable, non-medical air compressors is
Paragraphs 15.32–15.44 give details of the tests
not appropriate. Not only should a Quality Controller
required for modifications/extensions to existing
(MGPS) check all compressors before use, but also
systems.
QC checks during use are important. Preferably, an
on-line dew-point meter should be fitted to the plant
Note or pipeline system.
When tests and/or purging are/is carried out on
systems fed by sources serving an operational hospital, 15.20 When employing compressors for this type of test,
it is essential to ensure that the flows generated during it is important that the system demand should not
any tests do not result in interruption of continuity or exceed the maximum flow capacity of the dryers,
impairment of adequacy of supply in the operational otherwise wet air will result. It is suggested that the
areas. total flow required by the system under test should
not be more than 75% of the flow capacity of the
15.16 Testing for leakage is normally carried out in two dryers.
stages: the first to the pipeline carcass, the second 15.21 It is also important not to introduce such a
to the completed distribution system, which will compressor after identity checks have taken place.
include terminal units and medical supply units as
appropriate. 15.22 Special care will be required when carrying out
QC checks, as some synthetic oils cannot be
15.17 Purging and testing must be carried out with detected using portable equipment.
clean, oil-free, dry air or nitrogen, except for those
tests where medical air or the specific working 15.23 Special connectors will be needed to introduce test
gas is prescribed. All test gases must meet the gas into different pipeline systems. These must
particulate contamination requirements set out in be of distinctive construction and permanently
paragraphs 15.130–15.136. The shield gas may be labelled with their function and the contractor’s
used for the tests on the pipeline carcass described name. The location of special connectors on the
in paragraphs 15.49–15.56. Cylinders of medical site must be recorded and should be subject to
air will normally be used as the source of test gas routine inspection under a planned preventative
for oxygen, nitrous oxide, nitrous oxide/oxygen maintenance (PPM) system. They should be
and helium/oxygen systems in order to prevent the removed from site when work is complete and the
possibility of contamination with oil. contractor should record their removal.
15.18 However, in the case of a large oxygen system, for 15.24 New terminal units are supplied with “Do not use”
example a new-build, the use of cylinders will be labels. These labels should remain in place until
impracticable for the total system performance the final identity and quality tests have been
test. As it may be undesirable to commission the completed. They are then removed by the
liquid supply system, the total system performance Authorised Person (MGPS).

121
Medical gases – HTM 02-01 Medical gas pipeline systems – Part A: Design, installation, validation and verification

15.25 In the case of existing systems, “Do not use” labels calibration records. On-site pre- and post-testing
should be affixed to all terminal units within the calibration of equipment against an appropriate
section being modified. standard will be performed at the discretion of the
Quality Controller (MGPS).
15.26 The results of all tests must form part of the
permanent records of the hospital and should show 15.31 In a completely new installation, flow meters,
details of the services and areas tested. Examples of anaesthetic trolleys etc should not be moved into
the appropriate forms are given in Appendix A. All rooms until validation and verification tests have
signatories are entitled to copies of the test forms. been satisfactorily completed.
The procedure for filing and retaining these forms
should be included in the local MGPS operational Note
policy.
In existing installations, particular care must be taken
15.27 For total system pressure tests on oxygen, nitrous to ensure that medical gas equipment left in areas
oxide and nitrous oxide/oxygen mixture, the where work or testing is taking place is, and remains,
system under test must be physically isolated from disconnected from the system.
the source of supply (for example by the use of
Medical and nursing staff should be made aware of this
spades). In the case of compressed air and vacuum
situation by the posting of appropriate exclusion
systems, the pressure at the plant must be
notices and terminal unit “Do not use” labels.
respectively below and above pipeline distribution
pressure.
Modifications, extensions or repairs to
15.28 All errors found during testing must be rectified, existing systems
and the relevant systems must be retested as
appropriate before the records are signed. 15.32 Where modifications, extensions or repairs to
existing systems are carried out, the tests and the
15.29 The contractor (MGPS) must provide all sequence of tests summarised in paragraphs 15.12–
engineering forms, labour, materials, instruments 15.14 should be followed as far as possible.
and equipment required to carry out the tests
described in this chapter. In the case of engineering 15.33 The permit-to-work system should always be
tests, this must include all cylinders of test gas followed whenever any work is carried out on an
together with “open” bore NIST connector probes, existing system. The Authorised Person (MGPS)
pressure-measuring equipment and gas specificity/ should act on behalf of the management and
flow pressure testing device(s), metered leaks and therefore would not normally be a member of the
AGS disposal system test equipment. The Quality installation contractor’s staff.
Controller (MGPS) will be responsible for 15.34 Whenever modifications or extensions are carried
supplying all QC forms, unless otherwise out, it may be advisable but not always possible to
requested by the trust, calibrated test equipment, test both the existing system and the new system
connections etc. separately before the break-in is made. Existing
systems should, if possible, be tested to determine
Note their performance and to identify any potential
If there is to be a delay between completion of the limitations that may arise as a result of
MGPS and when it is taken into use, it will be modifications.
necessary to carry out the particulate and odour test 15.35 Where there is any doubt as to the cleanliness,
prior to purging and filling with specific gases. In such it is in the interest of both the contractor and
cases the contractor must also provide labour, materials management for particulate tests to be carried out
and equipment to carry out these tests. on the existing system prior to any break-in, and
it is the responsibility of the hospital authority to
15.30 The Quality Controller (MGPS) should provide ensure that these tests are carried out prior to the
the test equipment specified in Appendices D, E design phase of any modifications or extensions.
and F. The Quality Controller (MGPS) should
provide all equipment for gas quality and identity 15.36 It is the responsibility of the hospital’s
testing. It should be regularly serviced and management to ensure that any required remedial
calibrated to an appropriate standard and the work is carried out on an existing system before
Quality Controller (MGPS) should maintain extensions are added.

122
15 Validation and verification

15.37 No system should be modified during the process 15.44 The break-in to the existing system should be
of testing. It is important that any modifications carried out with an inert gas shield where possible,
are documented and that any additional testing for example where AVSUs have been installed, and
required, as a consequence of those modifications, a downstream blanking plate has been deployed.
is performed. A leak test must be carried out using a suitable
leak detection fluid on this final joint at working
15.38 A permit-to-work (or another form of appropriate
pressure, and the joint purged with the working
document) must be issued if additional works
gas.
are to be carried out during the commissioning
process, even though a permit will not have been 15.45 Connection of the upstream side of the AVSU into
issued for the original commissioning. the existing system will usually be made without
use of the shield gas. This joint can be purged with
15.39 The tests for particulate contamination of any
the working gas (exiting via the AVSU upstream
extension or modification may be carried out with
NIST).
medical air, prior to connection and handover
to the Quality Controller (MGPS), although in
extensions comprising fewer than 20 joints, the Note
working gas will generally be used to perform all In some articulated pendant fittings, it is not always
tests. possible to achieve the specified pressure requirements
15.40 The Quality Controller (MGPS) will normally
for surgical air and vacuum. In the case of surgical
carry out all checks, including a repeat of the air, it is most likely to be a potential problem in
particulate matter test, using the working gas. orthopaedic operating rooms. As these normally
include an ultra-clean system into which can be
15.41 The exact tests to be carried out will depend incorporated surgical air (and other terminal units),
on the nature of the modification/extension. supplied by rigid pipework, there may not be a
A specification should be prepared for the problem in practice. If the static pressure exceeds the
performance of the completed system. This nominal pressure during flow by more than 25%,
specification should be as close as possible to that the possibility of installing hoses with a greater bore
given in Table 28. should be considered. In the case of vacuum, the flows
15.42 Some older compressed air systems will have been required during surgery are less than those used during
designed to provide 250 L/min at the terminal testing.
unit in accordance with Health Technical
Memorandum 22 (1978). It may not be possible Requirements for pipeline carcass tests
for such systems to provide 350 L/min, as specified 15.46 If sectional testing is performed, it is essential that
in Table 19, and there may be circumstances where as-fitted drawings are available so that the extent of
this would be acceptable. This should be clearly the system(s) under test can be identified. For the
stated in the specification for the performance of purpose of the leakage test, all pressure gas systems
the completed system. However, every effort may be interlinked, provided that the test can be
should be made to comply with the performance performed at the highest pressure required. (This
and quality specifications given here, although also has the advantage that the pipeline carcass
particular care must be taken to avoid degradation could be assigned to a different service.)
of air quality arising from dryer units working at
flow rates above their design specification.
Notes
15.43 It may be necessary to repeat some of the system
In the event of a leak, it will be necessary to test each
performance tests (such as flow and pressure drop)
system separately.
at selected terminal units on the completed system
to demonstrate satisfactory performance (see It is advantageous to perform the tests with nitrogen,
paragraph 15.77). To ensure a valid result from since – in the event of a leak or cross-connection –
such a test, it should be performed when flows in remedial action can be taken immediately.
the system are representative of typical maximum When connecting systems together, vacuum systems
demands. should not be included, as particulates from an
unpurged vacuum system may be drawn into any
part of any pressure gas system by venturi effects.

123
Medical gases – HTM 02-01 Medical gas pipeline systems – Part A: Design, installation, validation and verification

Table 28 Validation and verification: pressure during pipeline system tests


Medical Nominal pipeline Test flow Test location Min. pressure Plant pressure
gas distribution (L/min) at design flow (kPa)
pressure (kPa) (measured measured on the
at terminal test gauge (kPa)
unit outlet)
O2 100 Operating rooms (ORs) and 380 430–490
400 anaesthetic rooms (ARs)
10 All other terminal units
N2O 400 15 All terminal units 380 430–490
Medical air 80 Critical care areas, SCBU, HDU, 380 430–490
(400 kPa) 400 ORs and ARs
20 All other terminal units
Surgical air 700 350 All terminal units 700 kPa at See Chapter 4
(700 kPa) 350 L/min (max
900 kPa at no flow
conditions)(1)
O2/N2O 275 LRDP rooms (inhalationary gasps) 310(2) 430–490
mixtures 400
20 All other terminal units 380
He/O2 400 80 Critical care areas only 380 430–490
Vacuum 55.3 kPa (400 mm 40 All terminal units 400 kPa 550–650 mm
Hg) below standard (300 mm Hg) Hg (typical plant
atmospheric operating range)
pressure of
101.3 kPa
(760 mm Hg)
Notes:
1. Downstream of the local regulator measured at the terminal unit.
2. The peak flow of 275 L/min must be achieved for 5 seconds at a minimum pressure of 310 kPa (310 kPa is the minimum
pressure required for the operation of a demand regulator).

Labelling and marking Leakage


15.47 A visual check must be made on each pipeline 15.49 The aim of this test is to establish that there is no
system to ensure that the pipelines are labelled in leakage from the piped medical gas systems. This
accordance with the contract specification, and is demonstrated by the use of electronic pressure-
that the terminal unit base blocks are marked in measuring equipment with a minimum resolution
accordance with BS EN 737-1:1998. The results of 0.2 kPa in 1000 kPa and 0.5 kPa in 2000 kPa.
of the checks are recorded on Form B1.
Note
Sleeving and supports With suitable equipment it is possible to carry out this
15.48 A visual check must be made on each pipeline test during a relatively short period to minimise the
system to ensure that the pipelines are sleeved, effect of temperature change.
where required, and supported in accordance with
Table 25. The results of the checks are recorded on 15.50 During a test period of two hours, the maximum
Form B1. pressure loss should be less than 0.2 kPa for
400 kPa systems and vacuum, and 0.5 kPa for
700 kPa systems. No allowance is normally made
for variation of pressure with temperature; if,
however, the accuracy of the available pressure-

124
15 Validation and verification

measuring equipment is in doubt and recourse is Leakage from total compressed medical
made to a 24-hour test, Appendix B contains
gas systems
information on the method of calculation. Systems
must be tested at a working pressure of 18.0 bar 15.59 This test must be carried out on the completed
for medical compressed air systems for surgical use, system with all terminal units, AVSUs, pressure
10.0 bar for all other compressed medical gas safety valves and pressure transducers fitted. Once
systems and 5.0 bar for vacuum systems the test pressure has been applied, the system
constructed in copper (1 bar for systems should be isolated from the plant. For the purpose
constructed in plastic). of this test, the supply system extends from the last
valve(s) nearest to the plant detailed on the
15.51 This test should be carried out with AVSUs, LVAs
appropriate schematic drawing. This point should
and other service valves open; any safety valves and
be identified on the contract drawings. The test is
pressure-sensing devices installed may be removed
performed at pipeline distribution pressure.
and the connections blanked off. The results of the
test may be recorded on Form B1. 15.60 During a test period of two hours, the maximum
pressure loss should be less than 0.2 kPa for
Cross-connection 400 kPa systems and vacuum, and 0.5 kPa for
700 kPa systems. The test results may be recorded
15.52 Before performing these tests, any links between on Form B3.
systems should be removed and all pipelines
should be at atmospheric pressure with all AVSUs
Leakage into total vacuum systems
etc open.
15.61 Prior to testing, the vacuum plant should be
15.53 A single pressure source should be applied to the
operated to allow any moisture in the system to
inlet of the system to be tested and at least one
evaporate. With the system at pipeline distribution
terminal unit base block on all other systems
pressure and with the source isolated, the pressure
should be fully open.
increase in the pipeline must not exceed 1 kPa
15.54 Each terminal unit base block on the pipeline after one hour. There is no additional allowance
under test should be opened in turn, checked for for temperature correction in this test.
flow and then re-blanked. (To permit refitting of
15.62 The test results may be recorded on Form B4.
blanking caps, it is necessary to partially open at
least one base unit – but it is still necessary to
achieve a detectable flow.) When the test on one Closure of area valve service units and
pipeline has been completed, the pressure source line valve assemblies
should be removed and the pipeline should be left 15.63 For pressurised systems, the system upstream of
open to atmospheric pressure by removing at least the closed AVSU under test must be maintained at
one base block blanking plate. pipeline distribution pressure and the downstream
15.55 The test is repeated for other systems, one at a line pressure should be reduced to about 100 kPa.
time. The downstream pressure must be recorded, and
there should be no change in pressure over a
15.56 The results may be recorded on Form B2. period of 15 minutes.

Requirements for pipeline system tests 15.64 For vacuum systems, the systems on the supply
plant side of the closed valve must be maintained
15.57 There must be no links between the pipeline at pipeline distribution pressure and the terminal
systems. Engineering (pressure) tests should be unit side should be at about 15 kPa. The upstream
carried out with electronic pressure-measuring (terminal unit side) pressure must be recorded, and
equipment with a minimum resolution of 0.2 kPa there should be no change in vacuum over a period
in 1000 kPa, and 0.5 kPa in 2000 kPa. of 15 minutes.
15.58 The scope of the system and scale of provision of 15.65 For LVAs, a similar test procedure is adopted.
terminal units, AVSUs, LVAs and warning and There is no change in the time for vacuum.
alarm system panel indicators should be checked
for compliance with Table 11 and any deficiencies
noted.

125
Medical gases – HTM 02-01 Medical gas pipeline systems – Part A: Design, installation, validation and verification

Note Notes
The reduced residual pressure is intended to take into These tests can be performed at the same time as the
account any potential terminal unit leakage on the cross-connection/terminal unit pressure drop tests.
assumption that it is unlikely any such leakage would
Where pneumatically activated pendant fittings are
equate to that of the valve under test; there would be
installed, a check should be made to ensure that the
less certainty if the pressures were reduced to zero.
source of air has been taken from the correct AVSU
zone.
15.66 The test results may be recorded on Forms B5A
and B5B. 15.69 The test results may be recorded on Forms B5A
and B5B.
Zoning of AVSUs and terminal unit
identification Cross-connection
15.67 This test is performed to ensure that each AVSU 15.70 All systems must be checked to ensure that there is
in the pipeline controls only those terminal units no cross-connection between pipelines for different
intended by the design. Each terminal unit must gases and vacuum. The tests should not commence
be checked to ensure that it is for the correct until all installations are complete and plant
service and that it is in accordance with BS EN operational. (The tests can be performed using
737-1:1998; unambiguous cross-referenced “test” gas or “working” gas.)
labelling of AVSUs and terminal units controlled
by them is essential. It is particularly important Note
to establish correct identification where dual or
separate circuits have been installed; often it is not Oxygen and vacuum can be tested simultaneously,
obvious by the spatial relationship of AVSUs and followed by medical air and surgical air simultaneously,
terminal units which of the AVSUs controls which followed by the other gases, that is, nitrous oxide and
terminal unit arrays. nitrous oxide/oxygen mixture. (Helium/oxygen
mixture usage is increasing, and pipeline systems may
Notes be encountered. Also, carbon dioxide pipelines are
being installed.)
The contractor may wish to carry out this test as part
of the carcass tests before any section of the pipeline is 15.71 The sequence of the test is, first, to open all valves
“enclosed”. on all systems (for example AVSUs, LVAs and any
Terminal-unit first-fix back blocks inadvertently other valves). For oxygen and vacuum systems, the
fitted upside-down will result in inverted second-fix main plant isolation valves should be opened (the
components, unless gas-specific components are main plant isolation valves on other systems
deliberately removed. Therefore, a selection of terminal remain closed). A check must be made to ensure
unit second-fixes, for example one per ward area, that there is a flow at every oxygen terminal unit
should be removed and examined to ensure that no and suction at every vacuum terminal unit, and
gas-specific components have been removed. that the systems are at the correct operating
pressure; there must be no flow at any other
15.68 The test is performed by turning off an individual terminal unit for the other gases.
AVSU and venting the zone to atmospheric 15.72 For the next stage, the main isolation valves for
pressure. A check is then made to establish that medical air and surgical air, if present, are opened.
only those terminal units controlled by the AVSU (It is not necessary to return the oxygen and
are at atmospheric pressure. All other terminal vacuum systems to atmospheric pressure.) A check
units, including those for other gas services, should is made to ensure that there is a flow at every
be at the operating pressure. Once a zone has been medical air terminal unit and every surgical air
vented, it is not necessary to repressurise. The terminal unit and that the operating pressure is
other AVSUs are then tested successively. correct; there must be no flow from the nitrous
oxide and/or nitrous oxide/oxygen mixture
terminal units, if present, and helium/oxygen,
if present.

126
15 Validation and verification

15.73 The process is then repeated for nitrous oxide – 15.78 It must be demonstrated for each terminal unit
again there is no necessity to return any of the that the appropriate gas-specific probe can be
previously tested systems to atmospheric pressure. inserted, captured and released, and it should be
A check is made to ensure that there is flow at visually confirmed that an anti-swivel pin is
every nitrous oxide terminal unit and that the present, or absent, in terminal units with a
operating pressure is correct; there must be no flow horizontal or vertical axis, respectively.
from the nitrous oxide/oxygen terminal units and
helium/oxygen terminal units (if present). Notes
15.74 The process is then repeated for nitrous oxide/ Terminal units to BS EN 737-1:1998 need not be
oxygen mixture, and finally helium/oxygen challenged with the full complement of BS 5682:1998
mixture. (If other medical gases are encountered, test probes.
for example carbon dioxide, the sequential testing
The terminal unit should be fitted complete with bezel
methodology will continue.) As before, there is
plates etc. The clearance hole should be reasonably
no necessity to return any of the previously tested
concentric with the terminal unit rim – it must not be
systems to atmospheric pressure. Checks are made
in contact.
to ensure that there is no flow from any system
that is still isolated at the plant.
15.79 The results of the tests may be recorded on
Form B7A.
Note
15.80 All NIST connectors must be checked to ensure
The tests can be carried out on a total system basis, that gas flow is achieved when the correct NIST
departmental basis or sub-departmental basis, having probe is inserted and mechanical connection
previously checked for cross-connection up to the made. The correct identification of gas flow
appropriate AVSUs. When carrying out the tests on a direction should be confirmed for AVSUs (that is,
sectional basis, it is essential that as-fitted drawings are which are the upstream and downstream NIST
available such that the extent of the system(s) can be connectors). NIST connectors can be checked
established. when performing other tests on AVSUs and LVAs.
15.75 This test must be repeated in full if any subsequent
modifications are made to the pipeline system. Note
15.76 The test results may be recorded on Form B6.
Whereas it should not be necessary to carry out
these tests on AVSUs bearing a CE Mark, in
certain circumstances factory-assembled units are
Flow and pressure drop at individual dismantled for installation purposes and can be
terminal units, mechanical function and subsequently incorrectly re-assembled. In the case of
correct installation LVAs (whether or not CE marked), disassembly and
subsequent incorrect re-assembly or, indeed, insertion
15.77 These tests can be carried out as part of the cross-
into an incorrect line, is also possible.
connection tests above using appropriate test
devices as described in Appendix C with the The primary purpose of the test is to ensure that
correct probes inserted for the pipeline(s) under whenever it is necessary to make a connection, the
test. The pressure must achieve the values given in appropriate connectors will be to hand; the test is
Table 28 at the specified flows. a further safety aid, although it is assumed that
personnel making connections to NIST fittings are
Note appropriately qualified and authorised to do so.
When performing these tests as part of the cross-
15.81 It must be demonstrated (except for vacuum) for
connection tests, there is the possibility that the
each NIST connector that the self-sealing device
400 kPa and vacuum test devices could be connected
substantially reduces the flow of gas when the
to the incorrect service, particularly a vacuum and
connector is removed without hazard to personnel
oxygen reversal. The instruments used, therefore,
or reduction in pipeline pressure.
should include appropriate directional check valves.
(There is a possibility of damaging the gauges.
Alternatively an open probe can be used to determine
pressure or vacuum.)

127
Medical gases – HTM 02-01 Medical gas pipeline systems – Part A: Design, installation, validation and verification

Note Note
Personnel should take care not to stand in front of the In principle it is permissible, although unlikely to be
NIST connector when performing this test. practicable for large installations, to test all systems
simultaneously, particularly oxygen and vacuum,
15.82 The results may be recorded on Form B7B. where terminal units are installed in pairs and where
they require different metered leaks (this includes
Performance tests on the pipeline vacuum when testing oxygen will not significantly
increase the time needed).
system
15.83 The performance of individual pipeline systems is
measured by introducing a sufficient number of Functional tests of supply systems
calibrated metered leaks (with orifice sizes
15.85 All supply systems must be tested for normal
providing different flows that replicate the range of
and emergency operation, according to the
medical devices for which the pipeline is designed;
manufacturers’ manuals and contract
see Table 12) to represent the total “diversified”
specifications. For the purpose of the tests, the
system design flow, less the flow generated by the
systems must be connected to both the normal and
test device. Thereafter, a representative number
stand-by power supplies. The results of these tests
of terminal units (see note below) are tested for
should be recorded on Form B9.
pressure and flow: the diversified flows should be
derived from the data in Tables 13, 15, 16, 18, 20
and 21. Pressure safety valves
15.86 Pressure safety valves are not tested. They should
Notes be examined to ensure that they are correctly rated
for the pipeline system and are in accordance with
In a 28-bed ward module a representative number
the contract specification. Each should be provided
would be in the order of two terminal units furthest
with a test certificate confirming the certificated
from the AVSU, two near the entrance, and the
discharge pressure. Records of safety valve details
treatment room, if applicable for each gas and vacuum.
should be noted on Form B10.
In an operating department, a representative number
15.87 Check that the specified pressure safety valves, line
would be one terminal unit in each operating suite and
valves and non-return valves have been fitted.
20% of terminal units in recovery for each gas and
vacuum. For oxygen, one metered leak should be 15.88 Verify that the pressure safety valves are certified
100 L/min to represent oxygen “flush”. to operate in accordance with the contract
specification and conform to BS EN ISO 4126-1:
It is not necessary to insert metered leaks into the
2004.
actual number of terminal units used to calculate the
“diversified” design flow, provided the numbers used
are evenly distributed and orifice sizes are selected to Warning and alarm systems
achieve this flow. 15.89 The operation of warning and alarm systems
should be tested in all normal operating and
15.84 The metered leaks should be stamped or similarly emergency modes. Particular attention should be
be identified to show the flow (air equivalent) at, paid to the following:
for example, 10, 20, 100, and 275 L/min for
a. that all systems operate within the specified
400 kPa systems, and 350 L/min for 700 kPa
tolerance limits at all operating parameters and
systems; the results of the tests may be recorded on
fault conditions, and can be seen and heard as
Form B8.
specified in Tables 23 and 24;
b. that systems react correctly following return to
normal status;
c. that all indicator panels and switches are
correctly marked;

128
15 Validation and verification

d. that all functions on all indicator panels operate drawings have been recorded and the results may
correctly; be recorded on Form B12.
e. that the system will operate from the essential
supply stand-by power source; Filling with medical air
f. that all indicator panels are labelled to show the 15.93 An indefinite time may elapse after completion
areas they serve, or as detailed in the contract of the MGPS before the system is taken into use.
specifications. The installation contract may be written in the
expectation that this will happen. In such
15.90 The following tests should also be carried out: circumstances the contract should require that
a. for central indicator panels, check that the the particulate contamination and odour tests
operation of the mute switch cancels the specified in paragraphs 15.130–15.136 are carried
audible alarm and converts the flashing signals out as an interim measure, using medical air as
to steady, for all systems and conditions; the test gas. Satisfactory completion of these
particulate contamination and odour tests may
b. for repeater indicator panels, check that the then signify the completion of the construction
mute switch cancels the audible alarm and that contract.
the flashing signals are converted to steady only
on the central alarm panel, for all systems and 15.94 It is the responsibility of the client to ensure that
conditions; proper provision is made in a specific contract for
the maintenance of the systems, their integrity, and
c. for area indicator panels, check that the any special connectors that may be required during
operation of the mute switch cancels the this interim period.
audible only, for all systems and conditions;
15.95 All MGPS should be left filled with medical air at
d check power failure operates red “system fault” pipeline distribution pressure until they are filled
indicator and the audible alarm; with the specific working gas shortly before use.
e. check that a contact line fault operates the The medical vacuum pipeline need not be
“system fault” indicator, the main alarm maintained under vacuum.
displays and the audible alarm; 15.96 Provision should be made for regular running and
f. check audible reinstatement for each alarm maintenance of all supply plant during such an
panel; interim period.
g. check that the audible signal can be 15.97 Details of the work carried out, as well as records
continuously muted via operation of the of the system pressures, should be recorded. This
internal push-button for gas service alarm information is required in order to demonstrate
conditions only; that the systems have been satisfactorily
maintained under pressure during this interim
h. check for correct identification of each gas period. Tests for particulate contamination should
service on alarm panels and “departmental” or be carried out after the systems are filled with the
plant specifying labels; specific gas. The extent of the tests is at the
j. check that each alarm panel emits the correct discretion of the Quality Controller (MGPS).
(two-tone) audible alarm. (Some manufacturers 15.98 The “Danger – do not use” label should remain
supply panels set for a single tone – in use, staff affixed to each terminal unit until all testing is
may confuse this sound with that emitted by completed.
some models of patient monitoring
equipment.) 15.99 When the construction contract has finished, the
contractor should record the removal of all special
15.91 The results of the tests are recorded on Form B11. connectors and cylinders from site.

Verification of as-fitted drawings


15.92 The as-fitted drawings should be checked to
ensure that all variations from the contract

129
Medical gases – HTM 02-01 Medical gas pipeline systems – Part A: Design, installation, validation and verification

has been completed satisfactorily under a permit-


Note to-work system.
Special connectors and cylinders may be required to
15.104 Three types of work are identified:
maintain the systems under pressure. This may be
some time prior to the admission of patients. In such a. new;
circumstances some contracts require systems to be b. extension/upgrade; and
completed and certificated for the purpose of practical
completion and handover to the client. c. repair.
For new installations, for example a new ward, a
Purging and filling with specific gases new department, or a complete hospital, the
Quality Controller (MGPS) will prepare a report
15.100 Each pipeline system must be purged with the containing details of tests carried out and an
specific working gas shortly before use. The inventory of outlets tested.
following conditions should apply:
15.105 For extensions, upgrades and repairs, the permit
a. all sources of test gas must be disconnected; will provide the minimum report, although a
b. all special connectors must be removed from longer report may be provided at the discretion of
site; the Quality Controller (MGPS).
c. each pipeline system must be at atmospheric 15.106 Inclusion of details such as the mounting order of
pressure with all AVSUs open; terminal units observed at the time of test should
be confirmed by signature of the Authorised
d. each system must be filled to pipeline Person (MGPS) on the report.
distribution pressure with the specific gas
from the supply system; 15.107 This inventory should be checked by the
Authorised Person (MGPS) to ensure that all
e. with the supply system on, each terminal unit terminal units have been identified and tested.
must be purged at a known flow with a NIST connectors will also need to be identified.
volume of gas at least equal to the volume of The Authorised Person (MGPS) should then
the pipeline section being tested; amend a copy of the Quality Controller (MGPS)
f. all oxygen, nitrous oxide, nitrous oxide/ report, confirming in writing that the system can
oxygen mixtures and helium/oxygen mixture be taken into use.
discharged during the process must be 15.108 Although a structured approach to testing should
released to a safe place. be adopted, access and time limitations to parts
15.101 The results of the purging process may be of the MGPS may lead to some disruption of
recorded on Form B13. proposed test regimes.
15.102 Purging is not necessary for vacuum systems.
Note
Note Important: These tests are described in the context
of commissioning and repair/alteration to existing
It may be possible to carry out the tests outlined in
systems. However, it must be remembered that
paragraphs 15.57–15.90 with the working gases,
quarterly testing is also required by this Health
either sequentially or consecutively, followed by the
Technical Memorandum and in accordance with
appropriate pharmaceutical test. After the tests,
Tables 28 and 29 for medical air generated by on-site
“certification” arrangements should be put in place
air compressors, synthetic air from gas blending plant,
such that the client takes over responsibility for
and oxygen from oxygen concentrators using
managing the system.
compressor plant. The Authorised Person (MGPS)
should liaise with the Quality Controller (MGPS) to
Pharmaceutical testing ensure that these tests are carried out and recorded.
15.103 When modifying existing systems, the test
programme is agreed by the Quality Controller
(MGPS) and Authorised Person (MGPS) and the
system is taken back into use only after testing

130
15 Validation and verification

depending on such factors as the extent and


Notes nature of the work and the age and condition of
The role, responsibilities and relationships of the existing systems.
Authorised Persons (MGPS) – in the context of both
15.112 The Ph. Eur. should be seen as a basic minimum
existing and new installations, where the Authorised
standard when examining medical gas quality,
Person (MGPS) may not have responsibility for the
as its principal application is to the manufacture
systems when in use – is covered in Part B.
and distribution of medicines according to well-
Although precluded by adherence to the procedures established manufacturing processes. It is not
recommended in this Health Technical Memorandum, intended to deal with the endless possibilities for
there have been instances when a system undergoes contamination that are introduced by an MGPS,
further modifications after a Quality Controller or the types of failure that might occur with on-
(MGPS) has started testing. It is very important that site generation of gases.
any modifications are documented and that any
15.113 Occasionally, the Quality Controller (MGPS)
additional testing required as a consequence of those
may need to resort to more sophisticated testing
modifications is performed. Use of the permit-to-work
than is permitted by the use of portable
form should be considered in these cases.
equipment.
If it is necessary to modify systems during or after
15.114 Oxygen, helium/oxygen mixture, nitrous oxide,
completion of testing, the Authorised Person (MGPS)
and nitrous oxide/oxygen mixtures discharged
and Quality Controller (MGPS) will identify the
during the process must be released to a safe
extent of retesting that is required.
place. These tests are not required on a vacuum
If the system has been completed and all
system for any work including modifications or
documentation handed over to the client or operator
new works.
of the building, any further modification must be
carried out strictly in accordance with the permit-to- 15.115 These test procedures are based on existing
work procedure. practice. The particulate contamination test is
subjective in that it requires the QC to make a
The importance of NIST connectors in facilitating
judgement on whether or not particles are visible
engineering and pharmaceutical testing and their value
on the filter.
during shutdowns and emergency situations should
not be underestimated. All LVAs are fitted with 15.116 The oil, water, carbon monoxide and carbon
upstream and downstream NIST connectors. dioxide, sulphur dioxide and oxides of nitrogen
tests can be carried out with detector tubes, but
advances in detection technology have produced
Quality of medical gas systems a range of suitable alternative instruments.
The use of detector tubes giving a quantitative
General response is recommended, but if other equipment
15.109 The objective of these tests is to establish whether is used for validation purposes, it must provide a
the pipeline has been contaminated during level of repeatability, resolution and accuracy at
construction or modification. The tests indicate least equivalent to that of detector tubes and
whether work has affected a gas, but they are must be calibrated to appropriate Standards.
not tests that indicate compliance with 15.117 An electronic dew-point meter should be used in
pharmaceutical specifications for licensed preference to water content measurements.
products.
15.118 Detector tubes give a quantitative response and
15.110 Particulate contamination and odour tests may are not intended for re-use. They should be
have been carried out prior to filling with the agent-specific, since non-agent-specific (polytest)
working gas, particularly if the system has been tubes can respond to various agents such as
left for some time before use. However, the volatile inorganic compounds, giving misleading
Quality Controller (MGPS) will define the extent results.
of repetition of these tests, after the systems have
been filled with the specific working gas. 15.119 However, it is recommended that the use of
polytest tubes be considered as an optional
15.111 The Quality Controller (MGPS) will also define general test for contamination of pipelines on a
the extent of all other pharmaceutical testing, representative sample of terminal units.

131
Health Technical Memorandum 02-01: Medical gas pipeline systems – Part A

15.120 Users must be aware of the limitations of all types Particulate matter
of detection equipment, including ambient
15.130 MGPS should be free from particulate
operating conditions and cross-sensitivities
contamination, as they have been constructed
specified for each type of detector tube.
using chemically cleaned, capped components
15.121 These tests must be carried out on a and joined in a controlled process using a filtered
representative sample of terminal units/NISTs in shield gas.
each system at the discretion of the Quality
15.131 However, on-site contamination can occur
Controller (MGPS).
from ingress of building materials, dust etc. The
15.122 If terminal units are being tested, the sample presence of such particles can adversely affect the
must include, as a minimum, the most distant quality of the delivered gases. Therefore, tests to
terminal unit on each branch. This may be the indicate their absence are important.
first terminal unit to be tested, but care must
15.132 New systems should be purged until the
be taken to ensure, for example, that a new
particulate filter is completely clear of visible
extension connected to old pipework is first well
particles when viewed in a good light.
purged via a terminal unit/NIST connector as
close as possible to the junction of the systems so 15.133 Older systems may exhibit particulates, even after
as to avoid the spread of any contamination into considerable purging, as they can be released or
the extension. carried along by the gas stream after disruption of
the system, reverse gas flow, pressure waves down
15.123 It will not normally be necessary to test the most
the pipe, or physical vibration.
distant terminal unit if distal NIST connectors
are provided.
Note
15.124 Depending on the results of this test, the Quality
When connecting new pipework to an older (possibly
Controller (MGPS) should decide the number
contaminated) system it may be advisable to perform
and location of additional terminal units/NISTs
the first purge via the inlet NIST of the first AVSU, or
to be tested.
the first terminal unit of the new system, in order to
reduce the possible spread of contamination into the
Note new system.
Provision of NISTs throughout an MGPS is to be
encouraged, as this will greatly facilitate testing, 15.134 Where it is evident that extended purging may
particularly QC testing. not completely clear the system of particulates,
a decision to accept the level of contamination
15.125 These tests are summarised in Table 28. present, agree a cleansing procedure or, in very
exceptional circumstances, condemn the system
15.126 All sources of supply should be tested for quality
will be made.
before the pipeline distribution system is filled
with the working gas. This test is not intended 15.135 The test for particulate matter should be carried
as a test of certificated gases but is to ensure out at every terminal unit on a new system. It
that supply source equipment (manifolds, can be carried out either after completion of
compressors, VIEs etc) does not compromise the the construction phase using medical air (see
quality of such gases when delivering them to the paragraph 15.93) or after the system has been
pipeline systems. filled with the specified gas. Once the system is
filled with working gas, it would not normally be
15.127 When extending existing systems, supply sources
necessary to repeat the test at every terminal unit.
will not normally be retested before being used to The actual number of terminal units sampled is
fill the extension with the working gases. at the discretion of the Quality Controller
15.128 For new installations, quality tests should be (MGPS). It would, however, be necessary to
carried out on the plant as well as on the pipeline repeat the test in full where there is insufficient
distribution system. evidence to show that the system has been
satisfactorily maintained under operating pressure
15.129 The results of the test may be recorded on
with medical air for the interim period.
Form B14.

132
15 Validation and verification

15.136 When tested with a membrane filter at a flow not 15.143 A representative sample of terminal units on both
less than 150 L/min for 30 s, the filter must be new and modified medical compressed air and
free from visible particles when viewed in good oxygen concentrator systems supplied by
light. A suitable test device is described in compressor plant may be checked at the
Appendix D. discretion of the Quality Controller (MGPS).
15.144 Care should be taken in siting the test point to
Notes ensure a representative sample.
When testing surgical air terminal units, a flow of
350 L/min for 30 s should be used. Water
When testing nitrous oxide/oxygen mixture terminal 15.145 This test is intended to identify contamination of
units, a flow of 275 L/min for 30 s should be used. the pipeline system by moisture. It should not be
confused with the test for compressor plant dryer
When testing helium/oxygen mixture systems, oxygen- performance, although it may indicate a failure in
free nitrogen is used at the manifold and this will the dryer system.
require special connectors.
When tests and/or purging is carried out with the Notes
sources of supply serving an operational hospital, it
When testing terminal units supplied via low pressure,
is essential to ensure that the test flows used are not
flexible connecting assemblies, it is often found that
detrimental to the continuity or adequacy of supply in
– on initial testing – moisture levels exceed the
operational areas. When a flow rate of 150 L/min or
0.05 mg/L limit; this is the result of desorption of
more may not be possible without compromising the
minute quantities of moisture into the gas stream. This
hospital system, a lower flow rate should be used at the
is particularly noticeable where the test flow is low, and
discretion of the Quality Controller (MGPS).
should not cause undue concern. The Quality
Controller (MGPS) should establish, however, that the
Oil elevated readings at such terminal units result from
this effect and not water contamination of the
15.137 This test should be carried out at the plant test
pipeline. (For example, the results should be compared
point of all newly installed medical/surgical
with the readings achieved at nearby terminal units
compressed air plant and for all medical/surgical
supplied by copper pipework.) New developments in
compressed air plant on a quarterly basis.
hose materials may lead to hoses with reduced water
15.138 When break-ins to a tested (and compliant) vapour permeability characteristics.
medical/surgical air system have been completed,
The effects of flow rate through dryer units and
repetition of this test will not normally be
sampling times on detection equipment indications
required.
should also be taken into account when measuring
15.139 Work involving strip-down of compressor plant water content.
and subsequent replacement of oil-sealing
components may require a follow-up oil test, 15.146 The plant test point and a representative sample
at the discretion of the Quality Controller of terminal units distributed throughout the
(MGPS). pipeline systems should be tested for total water
content. The water content must not exceed
15.140 Oil may be present as liquid, aerosol or vapour,
67 vpm (equivalent to an atmospheric pressure
and an appropriate test device is described in
dew-point of approximately –46°C). The typical
Appendix E.
water content of medical gas cylinders is normally
15.141 The total oil content should be in accordance below 5 vpm. Water vapour content may be
with Table 28. measured using the appropriate test device
15.142 It is desirable to carry out this test at a plant test described in Appendix E (see also paragraph
point before any pipeline system is supplied 15.117).
by that plant so as to prevent inadvertent
contamination of the distribution system.

133
Health Technical Memorandum 02-01: Medical gas pipeline systems – Part A

Sulphur dioxide
Note
15.152 The most distant terminal units in medical/
Older compressor/dryer combinations may fail to
surgical air pipeline systems supplied from a
meet the Ph. Eur. requirement of 67 vpm. In these
compressor plant, and oxygen terminal units
circumstances, the Quality Controller (MGPS) will
supplied from a PSA plant, must be tested for
decide whether application of the older atmospheric
sulphur dioxide. (It will not normally be
dew-point limit of –40°C (127 vpm) is acceptable
necessary to test more than five terminal units in
(Health Technical Memorandum 2022: 1997).
a single system.) The concentration should not
exceed 1 ppm v/v.
Carbon monoxide
15.153 When break-ins to a tested (and compliant)
15.147 The most distant terminal units on each branch medical/surgical air system have been completed,
of a medical/surgical air pipeline system supplied repetition of this test (and those in paragraphs
from a compressor plant and PSA systems must 15.111–15.114) will not normally be required.
be tested for carbon monoxide, although it would
not normally be necessary to test more than five Oxides of nitrogen (NO and NO2)
terminal units. The concentration of carbon
15.154 The most distant terminal units in medical/
monoxide should not exceed 5 ppm v/v. This may
surgical air pipeline systems supplied from a
be measured at up to five terminal units in each
compressor plant, and oxygen terminal units
system using the appropriate test devices
supplied from a PSA plant, must be tested for
described in Appendix E.
oxides of nitrogen. (It will not normally be
15.148 When break-ins to a tested (and compliant) necessary to test more than five terminal units in
medical/surgical air system have been completed, a single system.) The concentration should not
repetition of this test will not normally be exceed 2 ppm v/v.
required.
15.155 When break-ins to a tested (and compliant)
medical/surgical air system have been completed,
Carbon dioxide
repetition of this test (and those in paragraphs
15.149 The most distant terminal unit on each branch 15.111–15.114) will not normally be required.
of a medical/surgical air pipeline system supplied
from a compressor or an oxygen concentrator Important:
plant must be tested for carbon dioxide. See Note (d) in Table 29 on disparity between Ph. Eur.
15.150 The concentration of carbon dioxide must not and EH40 with reference to acceptable levels of
exceed 500 ppm v/v in medical air or 300 ppm sulphur dioxide and oxides of nitrogen.
v/v in oxygen from an oxygen concentrator plant.
15.151 When break-ins to a tested (and compliant) Nitrogen
medical/surgical air system have been completed, 15.156 Oxygen-free nitrogen is used as the inert gas
repetition of this test will not normally be shield, and all terminal units of all gas systems
required. should be tested to ensure that the systems have
been adequately purged.
Notes
15.157 For oxygen systems and nitrous oxide/oxygen, an
Increasing or fluctuating carbon dioxide readings in air oxygen analyser must be used to ensure that the
or PSA-generated oxygen can be an early indication of oxygen concentration is not less than that given
dryer failure or poor compressor maintenance. in Table 30.
Carbon dioxide is no longer used as an inert shield gas 15.158 For nitrous oxide systems, an instrument based
during pipeline brazing. on thermal conductivity, or an infrared meter,
If carbon dioxide has been installed (see Chapter 11), must be used to check that the system has been
the test methodology should be at the discretion of the adequately purged at every terminal unit.
Quality Controller (MGPS). 15.159 If a thermal conductivity meter is used, it will be
necessary to prove absence of carbon dioxide

134
15 Validation and verification

(which could have been used inadvertently as a


shield gas) by the use of a chemical reagent tube.

Pipeline odour/taste
15.160 An odour test is performed because it
incorporates, qualitatively, many impurity checks,
as several contaminants are detectable by odour.
This test is normally carried out as the final test
with the working gases, except for nitrous oxide,
nitrous oxide/oxygen and carbon dioxide, which
should not be inhaled. The odour threshold of
particulate matter is approximately 0.3 mg/m3.
15.161 In certain circumstances (see paragraph 15.93),
it may be carried out as the first test after
completion of construction of the pipeline
installation using medical air as the test gas. In
such circumstances, a pipeline odour/taste test
can be carried out on nitrous oxide and nitrous
oxide/oxygen systems.
15.162 In addition to all new terminal units, a
representative sample of terminal units on
existing parts of the systems must be checked.

Notes
For some time it has been known that materials
used in the construction of low-pressure connecting
assemblies can present an odour. This was recognised
in the 1984 version of BS 5682:
“Plastics materials currently in use will release small
quantities of volatile organic matter into the gas stream
throughout the life of the plastics components of the
material. The quantities released appear to be below the
levels normally considered toxic but, as yet, insufficient
research has been carried out to be able to identify and
quantify these components, therefore no tests are
recommended.”
More recent work has shown that the quantities of
those agents that can be identified are significantly
below levels considered to be toxic. It is possible that
developments in hose material structure will result in
the reduction of odour (and moisture retention).
The Quality Controller (MGPS) should perform
additional oil and polytest analyses if indistinct odours
are detected where flexible hoses are not involved.
New developments in hose materials may lead to hoses
that are odour-free and do not leach chemicals into the
gas stream.

135
Health Technical Memorandum 02-01: Medical gas pipeline systems – Part A

Table 29 Quality specifications for medical gas pipeline tests (working gases)
Gas and Particulates Oil Water CO CO2 NO SO2 Poly- Odour
source and test tube
NO2 (Optional)

Oxygen Free from visible ≤0.1 ≤67 vpm ≤5 mg/ ≤300 ≤2 ≤1 No None
from PSA particles in a 75 L mg/m3 (≤0.05 mg/L, m3; ppm ppm ppm discoloration
plant sample atmospheric dew- ≤5 ppm v/v v/v v/v
point of –46°C) v/v
Nitrous Free from visible – ≤67 vpm – – – – No SAFETY
oxide particles in a 75 L (≤0.05 mg/L, discoloration Not
sample atmospheric dew- performed
point of –46°C)
Nitrous Free from visible – ≤67 vpm – – – – No SAFETY
oxide/ particles in a 75 L (≤0.05 mg/L, discoloration Not
oxygen sample atmospheric dew- performed
mixture point of –46°C)
Medical Free from visible ≤0.1 ≤67 vpm ≤5 mg/ ≤900 ≤2 ≤1 No None
and surgical particles in a 75 L mg/m3 (≤0.05 mg/L, m3; mg/ ppm ppm discoloration
air sample (for medical atmospheric dew- ≤5 ppm m3; v/v v/v
air) and 175 L point of –46°C) v/v ≤500
sample (for surgical ppm
air) v/v
Dental Free from visible ≤0.1 ≤1020 vpm ≤5 mg/ ≤900 ≤2 ≤1 No None
compressed particles in a 75 L mg/m3 (≤0.78 mg/L, m3; mg/ ppm ppm discoloration
air sample atmospheric dew- ≤5 ppm m3; v/v v/v
point of –20°C) v/v ≤500
ppm
v/v
Synthetic Free from visible – ≤67 vpm – – – – No None
air particles in a 75 L (≤0.05 mg/L, discoloration
sample atmospheric dew-
point of –46°C)
Oxygen Free from visible – ≤67 vpm – – – – No None
from bulk particles in a 75 L (≤0.05 mg/L, discoloration
liquid or sample atmospheric dew-
cylinders point of –46°C)
Helium/ Free from visible – ≤67 vpm – – – – No None
oxygen particles in a 75 L (≤0.05 mg/L, discoloration
mixture sample atmospheric dew-
O2, <30% point of –46°C)
Notes:
a. The quality of the gases delivered at the terminal units should also comply with the specifications given in the current
edition of the Ph. Eur. (see Table 30). Additionally, contamination introduced by the MGPS, and not limited by the Ph. Eur.
specification, should not exceed levels that might pose a threat to patients. It should be borne in mind that the safe levels for
medical gases delivered to patients are likely to be significantly lower than those permitted for healthy individuals.
In addition to the monograph, the official standards section of the general notices should be read.
b. The tests for oil, carbon monoxide, carbon dioxide, sulphur dioxide and oxides of nitrogen are not normally carried out when
the source of supply is from cylinders or cryogenic systems, although it should be noted that rare instances of oil contamination
arising from the pipeline have occurred.
c. Synthetic air will be tested for identity as shown in Table 30. A GLC (gas-liquid chromatography) test for nitrogen is possible
but not without practical difficulties. Nitrogen content will, therefore, usually be inferred from oxygen analyser test results.

136
15 Validation and verification

d. The Health and Safety Executive has revised its guidance on exposure limits for sulphur dioxide, nitrogen monoxide and
nitrogen dioxide.
Occupational exposure standards (OESs) for nitric oxide, nitrogen dioxide and sulphur dioxide were removed from EH40 in
the Amendment of April 2003.
Time-weighted averages (TWAs) for nitrogen monoxide and nitrogen dioxide are now suggested as no greater than 1 ppm, and
limits for sulphur dioxide exposure as less than 1 ppm for both 8-hour TWA OES and 15-minute STEL (short-term exposure
limit).
Some breathing air standards seek to limit the levels of such contaminants to 10% of the 8-hour TWA, as medical gases
are intended for use by people who are not in the best of health. Therefore it is suggested, when testing for these specific
compounds, or any contaminants not listed in the Ph. Eur., that a limit of 10% of the OES should be confirmed.
e. See Note following paragraph 15.146.

Table 30 Ph. Eur. quality specifications for medical gases


Gas and Oil Water CO CO2 NO and SO2 Odour/Taste
source NO2
Oxygen from – ≤67 vpm (≤0.05 mg/L, ≤5 mg/m3; ≤300 ppm – – None
bulk liquid or atmospheric dew-point of ≤5 ppm v/v v/v
cylinders –46°C)
Oxygen from 0.1 ≤67 vpm (≤0.05 mg/L, ≤5 mg/m3; ≤300 ppm ≤2 ppm v/v ≤1 ppm v/v None
PSA plant mg/m3 atmospheric dew-point of ≤5 ppm v/v v/v
–46°C)
Nitrous oxide – ≤67 vpm (≤0.05 mg/L, ≤5 mg/m3; ≤300 ppm ≤2 ppm v/v – N/A
atmospheric dew-point of ≤5 ppm v/v v/v
–46°C)
Nitrous – ≤67 vpm (≤0.05 mg/L, ≤5 mg/m3; ≤300 ppm ≤2 ppm v/v – N/A
oxide/oxygen atmospheric dew-point of ≤5 ppm v/v v/v
mixture –46°C)
Medical and 0.1 ≤67 vpm (≤0.05 mg/L, ≤5 mg/m3; ≤900 mg/m3; ≤2 ppm v/v ≤1 ppm v/v None
surgical air mg/m3 atmospheric dew-point of ≤5 ppm v/v ≤500 ppm
–46°C) v/v
Synthetic air – ≤67 vpm (≤0.05 mg/L, – – – – None
atmospheric dew-point of
–46°C)
Helium/ – ≤67 vpm (≤0.05 mg/L, ≤5 mg/m3; ≤300 ppm ≤2 ppm v/v – None
oxygen atmospheric dew-point of ≤5 ppm v/v v/v
mixture O2, –46°C)
<30%

Note
Particulate level tests and polytests are NOT included in the Ph. Eur.

137
Health Technical Memorandum 02-01: Medical gas pipeline systems – Part A

Gas identification 15.166 When testing pipelines for helium/oxygen


mixture, an initial test is carried out with nitrogen
15.163 The identity of the gas must be tested at terminal
connected after completing the particulate test.
units on medical gas pipeline systems. This would
An oxygen analyser is used and all terminal
include all new terminal units, whether on a new
units are tested. After a zero reading is achieved,
installation or a modification or extension, and
product cylinders are connected and the system
a representative sample of terminal units on an
is purged. A second test is performed with an
existing system, which may have been affected by
oxygen analyser; the oxygen content should be as
the work. All systems must have been filled with
in Table 31.
the specific gas according to paragraph 15.100.
15.167 The nominal gas concentration at specific
15.164 The composition of all compressed gases must be
terminal units is given in Table 31; vacuum must
positively identified. This can be accomplished
be identified by observation of suction at the
using an oxygen analyser for oxygen, nitrous
terminal unit.
oxide/oxygen and air, and a thermal conductivity
or infrared meter for nitrous oxide.
Test results
15.165 When checking the identity of nitrous oxide and
15.168 The test results for quality and gas identity may
nitrous oxide/oxygen mixture, the gas should be
be recorded on Form B15.
discharged in a manner that minimises pollution
and personnel exposure.

Table 31 Gas concentrations for identification purposes


Gas and source Paramagnetic oxygen Thermal conductivity Carbon dioxide detector Vacuum probe
analyser reading (TC)/infrared (IR) tube indication if TC meter
instrument reading used
Oxygen from liquid or Minimum 99.5% – – –
cylinders
Oxygen from Minimum 94.0% – – –
concentrator
Nitrous oxide –0.2% Indicates “nitrous ≤300 ppm v/v –
oxide” or gives a
reading of 100% ±
2.0% (TC), ≥98% (IR)
Nitrous oxide/oxygen 50.0% ± 2.0% 50.0% ± 2.0% – –
mixture
Medical, surgical and 20.9% ± 0.5% – – –
dental air
Synthetic air 95–105% of nominal – – –
value of 21.0–22.5%
Vacuum – – – Suction present
Nitrogen shield gas 0% 0% (IR) – –
Helium/oxygen – –
mixture:
Test 1. 0% 0%
Test 2. 20.9% ± 0.5% 20.9% ± 0.5%
Note:
The tolerance of the measuring instrument should be allowed in addition. For oxygen concentrator plant (PSA) supplied system,
the minimum concentration must be 94% oxygen. A vacuum gauge may be used to obtain a quantitative reading of vacuum level
and verify terminal unit performance.

138
15 Validation and verification

AGS disposal systems 15.174 The test should be carried out as described in
Appendix K of BS 6834:1987. The test device
General is inserted into each terminal unit in turn and
checked for pressure at flows of 80 L/min and
15.169 BS 6834:1987 specifies the tests to be carried out
130 L/min for BS systems, and 50 L/min and
on AGS disposal systems that comply with the 80 L/min for ISO systems. Adjustment is then
British Standard. The tests specified are designed made if necessary.
to ensure adequate performance and that the
safety provisions of receiving systems will be met. 15.175 The test device and a number of metered leaks
are then inserted into the system to replicate
15.170 The responsibility for the tests should be
the design flow. The measurements above are
clearly identified at the contract stage for new repeated. If the test results are satisfactory, the test
installations, in the same way as for the medical device is removed and substituted by a metered
gas pipeline system. In general, the contractor leak.
should carry out the tests, which should be
witnessed by the Authorised Person (MGPS).
Note
Performance tests The test device is designed to replicate either type of
receiving system for which the disposal system has
15.171 All equipment should be tested to ensure that
been designed (see paragraph 15.73).
it performs satisfactorily during continuous
operation under full load for one hour.
15.176 The other terminal units are then tested in turn
15.172 All electrically powered equipment should be by substituting the test device for each metered
tested as follows: leak including the test device.
• check for correct rotation;
Note
• check the current through the powered device
at full load. For the purposes of diversity, it may be assumed that in
any operating department only one receiving system
15.173 The disposal system should be tested to ensure for each operating room is in use at any time. (In a
that it meets the requirements set out in the table typical theatre suite with two terminal units in the
below, with the number of terminal units for operating room and one in the anaesthetic room, the
which it has been designed in use. total number of metered leaks used for testing is two;
Disposal system standard that is, one being placed in an operating room
terminal unit and the other in the anaesthetic room
Pressure drop Flow rate
terminal unit.)
BS 6834: ISO DIS BS 6834: ISO DIS
1987 7396-2: 1987 7396-2: 15.177 The operation of user-controlled switches, power-
2005 2005 on indicators and alarm systems should also be
Maximum 1 kPa 1 kPa 130 L/min 80 L/min checked.
Minimum 4 kPa 2 kPa 80 L/min 50 L/min
15.178 AGSS terminal units should be checked for
Maximum 20 kPa 15 kPa This check is made correct mechanical operation and that the check
static (–ve) (–ve) before performing the valve operates satisfactorily.
pressure flow tests

Requirements before a medical gas


Note pipeline system is taken into use
Since the preparation of BS 6834:1987, developments
in anaesthesiology have resulted in reduced flows being General
used. Depending on local circumstances, it may be 15.179 Before a system is used, the appropriate persons
possible to commission systems for different flows in must certify in writing that the tests and
accordance with ISO DIS 7396-2:2005. Details of the procedures required in paragraphs 15.46–15.100
test flows should be recorded in the commissioning and 15.109–15.178 have been completed, and
documentation. that all systems comply with the requirements.

139
Health Technical Memorandum 02-01: Medical gas pipeline systems – Part A

This must include certification that all drawings Operational policy


and manuals required by the contract have been
15.182 A procedure must be available in accordance with
supplied and as-fitted drawings are correct (see
Part B, and must ensure continuity of supply of
Form B16).
cylinders and bulk liquid. This will incorporate a
15.180 All certificates must be dated and signed by the procedure for recording delivery, handling and
appropriate witnesses, by the contract-supervising storage of full and empty cylinders, with an
officer and by the representative of the contractor. indication of who is responsible for these
activities. The supplier must certify the
15.181 For modifications or extensions to existing
composition of the cylinder contents. All
systems, the performance tests for flow and
deliveries of bulk liquid oxygen should be
pressure drop (as described in paragraphs 15.41–
tested for conformance to the product licence
15.43) should be carried out on the completed
specification before dispatch by the supplier, and
system if practicable. If the performance is in
should be supplied with a certificate indicating
accordance with the specification prepared (as
compliance.
described in paragraphs 15.32–15.44), the system
may be taken into use, provided that all the other
Cylinder storage and handling
tests have been satisfactorily completed.
15.183 There should be recorded visual checks for correct
Note labelling, including batch numbers (see Part B).
In many cases, the extension/modification will be Removal of construction labels
relatively small and unlikely to significantly affect the
performance of the system. 15.184 When all tests have been completed satisfactorily,
the “Danger – do not use” labels affixed to
terminal units should be removed on the
authority of, or by, the Authorised Person
(MGPS).

140
Appendix A – Testing, commissioning and
filling for use: forms to be
completed during testing and
commissioning of piped medical
gases systems
Form
Summary of tests B0
Carcass tests
Labelling and marking B1
Sleeving and supports B1
Leakage test B1
Cross-connection test B2
System tests
Leakage test B3
Vacuum leakage test B4
AVSUs – closure and zoning tests B5A
LVAs – closure and zoning tests B5B
Cross-connection test B6
Functional test of terminal units B7A
Functional tests of NIST connectors B7B
Design flow performance test B8
Functional test of supply system B9
Pressure safety valves B10
Warning systems B11
Verification of drawings B12
Purging and filling B13
Quality B14
Gas identification B15
Certificate of completion B16

141
Medical gases – HTM 02-01 Medical gas pipeline systems – Part A: Design, installation, validation and verification

Medical Gas Pipeline Carcass Tests Form B0 (Sheet of Sheets)


Hospital ........................................................................................ Scheme .............................................................................
File Number . ................................................................................ Date ..................................................................................
Summary of Tests
This is to certify that the following tests have been carried out:

System Form Test carried out satisfactorily


Carcass tests
Labelling and marking B1
Sleeving and supports B1
Leakage test B1
Cross-connection test B2
System tests
Leakage test B3
Vacuum leakage test B4
Area valve service units – closure and zoning test B5A
Line valve assemblies B5B
Cross-connection test B6
Functional tests of terminal units B7A
Functional tests of NIST connectors B7B
Design flow performance tests B8
Sources of supply B9
Pressure safety valves B10
Warning systems B11
Verification of drawings B12
Purging and filling B13
Quality B14
Gas identification B15
Permit-to-work form
Construction labels removed

Contract Supervising Officer


Status ............................................................................................. Signed ...............................................................................
Date ............................................................................................. Name ...............................................................................
All appropriate tests satisfactorily carried out. System may now be taken into use.
Authorised Person (MGPS)
Status ............................................................................................. Signed ...............................................................................
Date ............................................................................................. Name ...............................................................................

142
Appendix A – Test forms

Medical Gas Pipeline Carcass Tests Form B1 (Sheet of Sheets)


Hospital ........................................................................................ Scheme .............................................................................
File Number . ................................................................................ Date ..................................................................................
Part 1 – Leakage test, labelling and marking, sleeving and supports
This is to certify that a LEAKAGE test in accordance with paragraphs 15.49–15.51 was carried out on the piped system on this
scheme and that during the test, a pressure, as shown in column 2 below, was held as follows. A certified gauge number was
used.

Section tested Test pressure Hours on test Pressure drop Pressure loss Pass/Fail
(kPa) (kPa) (kPa/h) <0.2/2h
(400 kPa systems)
<0.5/2h
(700 kPa systems)

Part 2 – Links between systems


For the purpose of carrying out this test, the following links have been made:
......................................................................................................................................................................................................
......................................................................................................................................................................................................
This is to certify that the above tests have been carried out and that the following links have been removed:
......................................................................................................................................................................................................
......................................................................................................................................................................................................
Contractor’s Representative
Status ............................................................................................. Signed ...............................................................................
Date ............................................................................................. Name ...............................................................................
Contract Supervising Officer
Status ............................................................................................. Signed ...............................................................................
Date ............................................................................................. Name ...............................................................................

143
Medical gases – HTM 02-01 Medical gas pipeline systems – Part A: Design, installation, validation and verification

Medical Gas Pipeline Carcass Tests Form B2 (Sheet of Sheets)


Hospital ........................................................................................ Scheme .............................................................................
File Number . ................................................................................ Date ..................................................................................
Cross-connection test
This is to certify that a CROSS-CONNECTION test in accordance with paragraphs 15.52–15.55 was carried out on the
following medical gas pipeline systems:

......................................................................................................................................................................................................
......................................................................................................................................................................................................
......................................................................................................................................................................................................
......................................................................................................................................................................................................
......................................................................................................................................................................................................
......................................................................................................................................................................................................
......................................................................................................................................................................................................
......................................................................................................................................................................................................
......................................................................................................................................................................................................
......................................................................................................................................................................................................
......................................................................................................................................................................................................
......................................................................................................................................................................................................
......................................................................................................................................................................................................
......................................................................................................................................................................................................
......................................................................................................................................................................................................
......................................................................................................................................................................................................
......................................................................................................................................................................................................
......................................................................................................................................................................................................
......................................................................................................................................................................................................
......................................................................................................................................................................................................
......................................................................................................................................................................................................
......................................................................................................................................................................................................
......................................................................................................................................................................................................
......................................................................................................................................................................................................
......................................................................................................................................................................................................
......................................................................................................................................................................................................
......................................................................................................................................................................................................

No cross-connections between these systems were found.


Contractor’s Representative
Status ............................................................................................. Signed ...............................................................................
Date ............................................................................................. Name ...............................................................................

144
Appendix A – Test forms

Medical Gas Pipeline Total System Tests Form B3 (Sheet of Sheets)


Hospital ........................................................................................ Scheme .............................................................................
File Number . ................................................................................ Date ..................................................................................
Leakage test from total compressed gas system
This is to certify that a LEAKAGE test in accordance with paragraphs 15.59–15.60 was carried out on the piped system on this
scheme and that during the test, a pressure of was held for hours with a pressure drop of kPa.

Section tested Test pressure Hours on test Pressure drop Pressure loss Pass/Fail
(kPa) (kPa) (kPa/h) <0.2/2h
(400 kPa systems)
<0.5/2h
(700 kPa systems)

Contractor’s Representative
Status ............................................................................................. Signed ...............................................................................
Date ............................................................................................. Name ...............................................................................
Contract Supervising Officer
Status ............................................................................................. Signed ...............................................................................
Date ............................................................................................. Name ...............................................................................
Witnessed on behalf of .................................................................................................................................................................
By ............................................................................................. Status ...............................................................................
Signed ........................................................................................... Date ...............................................................................

145
Medical gases – HTM 02-01 Medical gas pipeline systems – Part A: Design, installation, validation and verification

Medical Gas Pipeline Total System Tests Form B4 (Sheet of Sheets)


Hospital ........................................................................................ Scheme .............................................................................
File Number . ................................................................................ Date ..................................................................................
Leakage into total vacuum system test
This is to certify that a LEAKAGE test in accordance with paragraph 15.61 was carried out on the piped vacuum system at a
system pressure of kPa. The pressure increase after 1 hour was kPa (max 10 kPa).

Contractor’s Representative
Status ............................................................................................. Signed ...............................................................................
Date ............................................................................................. Name ...............................................................................
Contract Supervising Officer
Status ............................................................................................. Signed ...............................................................................
Date ............................................................................................. Name ...............................................................................
Witnessed on behalf of .................................................................................................................................................................
By ............................................................................................. Status ...............................................................................
Signed ........................................................................................... Date ...............................................................................

146
Appendix A – Test forms

Medical Gas Pipeline Total System Tests Form B5A (Sheet of Sheets)
Hospital ........................................................................................ Scheme .............................................................................
File Number . ................................................................................ Date ..................................................................................
Area Valve Service Units – closure and zoning tests
This is to certify that CLOSURE and ZONING of the AVSUs was tested in accordance with paragraphs 15.63–15.68 on the
pipeline system as follows:

AVSU number Test pressure Downstream/upstream Terminal units controlled Terminal unit labelling
(kPa) pressure change after (total no)
15 min (kPa)

Contractor’s Representative
Status ............................................................................................. Signed ...............................................................................
Date ............................................................................................. Name ...............................................................................
Contract Supervising Officer
Status ............................................................................................. Signed ...............................................................................
Date ............................................................................................. Name ...............................................................................
Witnessed on behalf of .................................................................................................................................................................
By ............................................................................................. Status ...............................................................................
Signed ........................................................................................... Date ...............................................................................

147
Medical gases – HTM 02-01 Medical gas pipeline systems – Part A: Design, installation, validation and verification

Medical Gas Pipeline Total System Tests Form B5B (Sheet of Sheets)
Hospital ........................................................................................ Scheme .............................................................................
File Number . ................................................................................ Date ..................................................................................
Line Valve Assemblies – closure and zoning tests
This is to certify that CLOSURE and ZONING of the LVAs was tested in accordance with paragraphs 15.63–15.65 on the
pipeline system as follows:

LVA number Test pressure Downstream/upstream Terminal units controlled Terminal unit labelling
(kPa) pressure change after (total no)
15 min (kPa)

Contractor’s Representative
Status ............................................................................................. Signed ...............................................................................
Date ............................................................................................. Name ...............................................................................
Contract Supervising Officer
Status ............................................................................................. Signed ...............................................................................
Date ............................................................................................. Name ...............................................................................
Witnessed on behalf of .................................................................................................................................................................
By ............................................................................................. Status ...............................................................................
Signed ........................................................................................... Date ...............................................................................

148
Appendix A – Test forms

Medical Gas Pipeline Total System Tests Form B6 (Sheet of Sheets)


Hospital ........................................................................................ Scheme .............................................................................
File Number . ................................................................................ Date ..................................................................................
Cross-connection test
This is to certify that a CROSS-CONNECTION test in accordance with paragraphs 15.70–15.74 was carried out on the
following medical gas pipeline systems:

......................................................................................................................................................................................................
......................................................................................................................................................................................................
......................................................................................................................................................................................................
......................................................................................................................................................................................................
......................................................................................................................................................................................................
......................................................................................................................................................................................................
......................................................................................................................................................................................................
......................................................................................................................................................................................................
......................................................................................................................................................................................................
......................................................................................................................................................................................................
......................................................................................................................................................................................................
......................................................................................................................................................................................................
......................................................................................................................................................................................................
......................................................................................................................................................................................................
......................................................................................................................................................................................................
......................................................................................................................................................................................................
......................................................................................................................................................................................................
......................................................................................................................................................................................................
......................................................................................................................................................................................................
......................................................................................................................................................................................................
......................................................................................................................................................................................................
......................................................................................................................................................................................................
......................................................................................................................................................................................................
Contractor’s Representative
Status ............................................................................................. Signed ...............................................................................
Date ............................................................................................. Name ...............................................................................
Contract Supervising Officer
Status ............................................................................................. Signed ...............................................................................
Date ............................................................................................. Name ...............................................................................
Witnessed on behalf of .................................................................................................................................................................
By ............................................................................................. Status ...............................................................................
Signed ........................................................................................... Date ...............................................................................

149
Medical gases – HTM 02-01 Medical gas pipeline systems – Part A: Design, installation, validation and verification

Medical Gas Pipeline Total System Tests Form B7A (Sheet of Sheets)
Hospital ........................................................................................ Scheme .............................................................................
File Number . ................................................................................ Date ..................................................................................
Functional tests of terminal units
(in accordance with the contract specification and paragraphs 15.77–15.78)
System ....................................................................................................................
Specified flow .................................. L/min Specified pressure drop . ................................. kPa

Terminal unit Room number Specified flow Specified pressure Mechanical Gas specificity
number achieved drop achieved function
Yes/No Yes/No

Contractor’s Representative
Status ............................................................................................. Signed ...............................................................................
Date ............................................................................................. Name ...............................................................................
Contract Supervising Officer
Status ............................................................................................. Signed ...............................................................................
Date ............................................................................................. Name ...............................................................................
Witnessed on behalf of .................................................................................................................................................................
By ............................................................................................. Status ...............................................................................
Signed ........................................................................................... Date ...............................................................................

150
Appendix A – Test forms

Medical Gas Pipeline Total System Tests Form B7B (Sheet of Sheets)
Hospital ........................................................................................ Scheme .............................................................................
File Number . ................................................................................ Date ..................................................................................
Functional tests NIST connectors
(in accordance with the contract specification and paragraphs 15.80–15.81)
System ....................................................................................................................

NIST gas Location or identification Room Gas specificity Self-sealing


number Pass/Fail Adequate/Inadequate

Contractor’s Representative
Status ............................................................................................. Signed ...............................................................................
Date ............................................................................................. Name ...............................................................................
Contract Supervising Officer
Status ............................................................................................. Signed ...............................................................................
Date ............................................................................................. Name ...............................................................................
Witnessed on behalf of .................................................................................................................................................................
By ............................................................................................. Status ...............................................................................
Signed ........................................................................................... Date ...............................................................................

151
Medical gases – HTM 02-01 Medical gas pipeline systems – Part A: Design, installation, validation and verification

Medical Gas Pipeline Total System Tests Form B8 (Sheet of Sheets)


Hospital ........................................................................................ Scheme .............................................................................
File Number . ................................................................................ Date ..................................................................................
Design flow performance
(in accordance with paragraphs 15.83–15.84)
System gas . .............................................................. System design flow ................................ (L/min)

Total number of terminal units in system at test flow(s) of:

Total flow Single point test flows


40 L/min 80 L/min 100 L/min 275 L/min 350 L/min
L/min (Pass/Fail)

Contractor’s Representative
Status ............................................................................................. Signed ...............................................................................
Date ............................................................................................. Name ...............................................................................
Contract Supervising Officer
Status ............................................................................................. Signed ...............................................................................
Date ............................................................................................. Name ...............................................................................
Witnessed on behalf of .................................................................................................................................................................
By ............................................................................................. Status ...............................................................................
Signed ........................................................................................... Date ...............................................................................

152
Appendix A – Test forms

Medical Gas Pipeline Total System Tests Form B9 (Sheet of Sheets)


Hospital ........................................................................................ Scheme .............................................................................
File Number . ................................................................................ Date ..................................................................................
Functional tests of supply systems
This is to certify that the following sources of supply have been tested in accordance with paragraph 15.85 and the attached sheets
and found to comply with the specification.

Source of supply Contractor’s Representative Contract Supervising Officer


Name/Signature Name/Signature
Manifold

Manifold

Manifold

Liquid oxygen plant

Air compressor

Vacuum plant

Oxygen concentrator

Witnessed on behalf of .................................................................................................................................................................


By ............................................................................................. Status ...............................................................................
Signed ........................................................................................... Date ...............................................................................

153
Medical gases – HTM 02-01 Medical gas pipeline systems – Part A: Design, installation, validation and verification

Medical Gas Pipeline Total System Tests Form B10 (Sheet of Sheets)
Hospital ........................................................................................ Scheme .............................................................................
File Number . ................................................................................ Date ..................................................................................
Pressure safety valves
The pressure safety valves fitted to the pipeline systems have been inspected together with their certification and are in accordance
with the contract specification and paragraphs 15.86–15.88.

Location Valve number Position Pipeline Certified discharge B/A (%)


distribution pressure (B)
pressure (A)

If certificates are not provided, do not sign.


Contractor’s Representative
Status ............................................................................................. Signed ...............................................................................
Date ............................................................................................. Name ...............................................................................
Contract Supervising Officer
Status ............................................................................................. Signed ...............................................................................
Date ............................................................................................. Name ...............................................................................
Witnessed on behalf of .................................................................................................................................................................
By ............................................................................................. Status ...............................................................................
Signed ........................................................................................... Date ...............................................................................

154
Appendix A – Test forms

Medical Gas Pipeline Total System Tests Form B11 (Sheet of Sheets)
Hospital ........................................................................................ Scheme .............................................................................
File Number . ................................................................................ Date ..................................................................................
Warning systems
This is to certify that WARNING SYSTEMS on the following medical gas pipeline systems have been tested in accordance with
paragraphs 15.89–15.91 as follows:

System O2 N2O N2O/O2 MA-4 Surgical air VAC

Specified warrning pressure

Observed warning pressure

Warning given

Return to normal

Marking

All functions on all stations

Stand-by power

Contractor’s Representative
Status ............................................................................................. Signed ...............................................................................
Date ............................................................................................. Name ...............................................................................
Contract Supervising Officer
Status ............................................................................................. Signed ...............................................................................
Date ............................................................................................. Name ...............................................................................
Witnessed on behalf of .................................................................................................................................................................
By ............................................................................................. Status ...............................................................................
Signed ........................................................................................... Date ...............................................................................

155
Medical gases – HTM 02-01 Medical gas pipeline systems – Part A: Design, installation, validation and verification

Medical Gas Pipeline Total System Tests Form B12 (Sheet of Sheets)
Hospital ........................................................................................ Scheme .............................................................................
File Number . ................................................................................ Date ..................................................................................
Verification of drawings
This is to certify that in accordance with paragraph 15.92, the as-fitted drawings of the following systems record all variations from
the contract drawings:

System Drawing numbers Contractor’s Contract Supervising Date


Representative Officer
Status/Name Status/Name

O2

N2O

N2O/O2

MA-4

Surgical air

VAC

AGS

Helium/oxygen mixture

Carbon dioxide

Witnessed on behalf of .................................................................................................................................................................


By ............................................................................................. Status ...............................................................................
Signed ........................................................................................... Date ...............................................................................

156
Appendix A – Test forms

Medical Gas Pipeline Total System Tests Form B13 (Sheet of Sheets)
Hospital ........................................................................................ Scheme .............................................................................
File Number . ................................................................................ Date ..................................................................................
Purging and filling
This is to certify that medical gas systems have been purged and filled with medical air/O2 free nitrogen/the working gases (delete
as appropriate) in accordance with paragraphs 15.93–15.99 and/or 15.100–15.101 as follows:

Action O2 N2O N2O/O2 MA-4 Surgical VAC H2/O2 CO2


mixture air mixture

Special connectors/cylinders
removed from site

Filling

Purging all terminal units

Venting

Tick if particulate tests have been


performed and specifications met

Tick if odour tests have been


performed and specifications met

Contractor’s Representative
Status ............................................................................................. Signed ...............................................................................
Date ............................................................................................. Name ...............................................................................
Contract Supervising Officer
Status ............................................................................................. Signed ...............................................................................
Date ............................................................................................. Name ...............................................................................
Witnessed on behalf of .................................................................................................................................................................
By ............................................................................................. Status ...............................................................................
Signed ........................................................................................... Date ...............................................................................

157
Health Technical Memorandum 02-01: Medical gas pipeline systems – Part A

Medical Gas Pipeline Total System Tests Form B14 (Sheet of Sheets)
Hospital ........................................................................................ Scheme .............................................................................
File Number . ................................................................................ Date ..................................................................................
Quality specifications for medical gas piepline tests (working gases). This is to certify that medical gas systems have been tested in
accordance with paragraphs 15.109–15.162 as follows:
Gas and Particulates Oil Water CO CO2 NO SO2 Poly- Odour Tick when
source and test tube parameters
NO2 (Optional) are met
Oxygen Free from visible ≤0.1 ≤67 vpm ≤5 ≤300 ≤2 ≤1 No None
from PSA particles in a 75 L mg/m3 (≤0.05 mg/L, mg/ ppm ppm ppm discoloration
plant sample atmospheric dew- m3; v/v v/v v/v
point of –46°C) ≤5
ppm
v/v
Nitrous Free from visible – ≤67 vpm – – – – No SAFETY
oxide particles in a 75 L (≤0.05 mg/L, discoloration Not
sample atmospheric dew- performed
point of –46°C)
Nitrous Free from visible – ≤67 vpm – – – – No SAFETY
oxide/ particles in a 75 L (≤0.05 mg/L, discoloration Not
oxygen sample atmospheric dew- performed
mixture point of –46°C)
Medical Free from visible ≤0.1 ≤67 vpm ≤5 ≤900 ≤2 ≤1 No None
and particles in a 75 L mg/m3 (≤0.05 mg/L, mg/ mg/ ppm ppm discoloration
surgical air sample (for medical atmospheric dew- m3; m3; v/v v/v
air) and 175 L point of –46°C) ≤5 ≤500
sample (for surgical ppm ppm
air) v/v v/v
Dental Free from visible ≤0.1 ≤1020 vpm ≤5 ≤900 ≤2 ≤1 No None
compressed particles in a 75 L mg/m3 (≤0.78 mg/L, mg/ mg/ ppm ppm discoloration
air sample atmospheric dew- m3; m3; v/v v/v
point of –20°C) ≤5 ≤500
ppm ppm
v/v v/v
Synthetic Free from visible – ≤67 vpm – – – – No None
air particles in a 75 L (≤0.05 mg/L, discoloration
sample atmospheric dew-
point of –46°C)
Oxygen Free from visible – ≤67 vpm – – – – No None
from bulk particles in a 75 L (≤0.05 mg/L, discoloration
liquid or sample atmospheric dew-
cylinders point of –46°C)
Helium/ Free from visible – ≤67 vpm – – – – No None
oxygen particles in a 75 L (≤0.05 mg/L, discoloration
mixture sample atmospheric dew-
O2, <30% point of –46°C)
Contractor’s Representative
Status ............................................................................................. Signed ...............................................................................
Date ............................................................................................. Name ...............................................................................
Contract Supervising Officer
Status ............................................................................................. Signed ...............................................................................
Date ............................................................................................. Name ...............................................................................
Quality Controller
Status ............................................................................................. Signed ...............................................................................
Date ............................................................................................. Name ...............................................................................
Witnessed on behalf of .................................................................................................................................................................
By ............................................................................................. Status ...............................................................................
Signed ........................................................................................... Date ...............................................................................
Appendix A – Test forms

Medical Gas Pipeline Total System Tests Form B15 (Sheet of Sheets)
Hospital ........................................................................................ Scheme .............................................................................
File Number . ................................................................................ Date ..................................................................................
Identification of medical gas pipeline working gases
This is to certify that medical gas systems have been tested in accordance with paragraphs 15.163–15.167 and the results are as
follows (insert values for gases – tick for vacuum):

Gas and source Paramagnetic oxygen Thermal conductivity/ Carbon dioxide Vacuum probe
analyser reading infra-red instrument detector tube indication
reading if TC meter used
Oxygen from liquid or
– – –
cylinders

Oxygen from
– – –
concentrator

Nitrous oxide –

Nitrous oxide/oxygen
– –
mixture

Medical, surgical and


– – –
dental air

Synthetic air – – –

Vacuum – – –

Nitrogen shield gas – –

Helium/oxygen mixture
Test 1 – –
Test 2

Contractor’s Representative
Status ............................................................................................. Signed ...............................................................................
Date ............................................................................................. Name ...............................................................................
Contract Supervising Officer
Status ............................................................................................. Signed ...............................................................................
Date ............................................................................................. Name ...............................................................................
Quality Controller
Status ............................................................................................. Signed ...............................................................................
Date ............................................................................................. Name ...............................................................................
Witnessed on behalf of .................................................................................................................................................................
By ............................................................................................. Status ...............................................................................
Signed ........................................................................................... Date ...............................................................................

159
Medical gases – HTM 02-01 Medical gas pipeline systems – Part A: Design, installation, validation and verification

Certificate of Completion Form B16


Hospital ........................................................................................ NHS Trust .........................................................................
Medical Gas Installations – Location . .........................................................................................................................................
This is to confirm that the following tests have been performed:
Mechanical functions tests
B1 to B11 inclusive
Quality and gas identity tests
B13 to B15 inclusive
in accordance with Health Technical Memorandum 02-01 Part A, Chapter 15, and that the results are satisfactory.

Signed .............................................................................................
Quality Controller (MGPS)

Signed .............................................................................................
Contractor’s Representative (MGPS)

Signed .............................................................................................
Authorised Person (MGPS) on behalf of Trust/other

Witnessed .......................................................................................
Trust/other Building operator/owner

Date ................................................................................................

We, Trust/FM Contractor

accept responsibility for the systems above and undertake to carry out any future work in accordance with the recommendations of
Health Technical Memorandum 02-01 and the permit-to-work procedures.

Signed .............................................................................................

Date ................................................................................................

160
Appendix B – Gas pressure variation with
temperature

General 5. Care must be taken to express pressure and


temperature in absolute values.
1. Tests are specified for leakage of the pipeline
carcass and the pipeline systems. During these tests, 6. Pressure is normally expressed in “gauge” pressure:
pressure changes may occur that are caused by Absolute pressure = gauge pressure + atmospheric
temperature changes rather than leakage. pressure.
2. Pressure changes due to temperature difference may 7. Temperature is normally expressed in °C.
be calculated according to the Gas Laws (see the
‘Glossary’ in Part B). Examples
3. It is assumed that the temperature in the pipeline 8. The carcass of a medical air pipeline is tested for
is uniform in all branches. If substantial runs are leakage at a working pressure of 14.0 bar pressure.
external, an average temperature should be chosen. The temperature is 13°C at the beginning of the
test and 17°C at the end of the test:
Calculation
P1 = 14.0 + 1.0 = 15.0 bar
4. The change in gas pressure with temperature is as
follows: T1 = 273 + 13 = 286 K

P1/T2 = P2/T1 T2 = 273 + 17 = 290 K.

where: 9. Therefore, using Equation (1):

P1 = the initial absolute pressure of a fixed volume P2 = (15 x 290)/286


of gas; = 15.21 bar (absolute pressure)
= 14.21 bar (gauge pressure).
P2 = the final absolute pressure of a fixed volume of
gas; 10. That is, gauge pressure should read 14.21 bar at the
end of the test, assuming that no leakage has
T1 = the initial absolute temperature; occurred.
T2 = the final absolute temperature.
Therefore:
P2 = (P1 x T2)/T1. (1)

161
Medical gases – HTM 02-01 Medical gas pipeline systems – Part A: Design, installation, validation and verification

Appendix C – Pressure-drop test device

General Orifices
1. Special test devices are required to measure the 11. The orifices should be selected from the
pressure at specified flows at each terminal unit. information on the manufacturer’s data sheets or
from practical testing.
2. Suitable test devices are commercially available or
may be constructed in accordance with the outline 12. These devices should be checked against a
specification given below. flowmeter before use.

Measurement principle Flowmeter


3. Flow at a specified pressure may be measured either 13. A bobbin flowmeter calibrated to a flow of 40 L/
with a calibrated orifice or with a flowmeter. min may be used to measure flow under vacuum.
4. Pressure may be measured with a bourdon gauge.
Pressure gauge
5. A gas-specific probe conforming to BS 5682:1998
should be used to connect the device to the 14. A 50 mm bourdon gauge with an appropriate full
terminal unit. scale reading and interval should be used as follows:

6. The test device is connected to the terminal unit Test pressure kPa Scale Scale interval
by the gas-specific probe and the pressure at the 400 0–7 bar 0.1 bar
specified flow is read on the gauge. 700 0–11 bar 0.5 bar
Vacuum 0–100 kPa 5 kPa (50 mm Hg)
Functional requirements (0–760 mm Hg)
7. The test device should consist of the following 1 bar = 100 kPa
components: approximately

• gas-specific probe to BS 5682:1998;


• body on/off valve pressure gauge; Note
• orifice or flowmeter. Generally it is found that three separate test devices
for 400 kPa, 700 kPa and vacuum provide greater
8. The body may be of a design that allows exchange convenience. Because the test methodology in
of the following components: Chapter 15 has the potential for exposing the 400 kPa
a. gas-specific probes; and vacuum devices to pressure or vacuum, it is
desirable that they include an appropriate directional
b. calibrated orifices; check valve.
c. pressure gauges.
9. An on/off valve may be incorporated into the body.
10. The complete assembly should be tested for leaks.

162
Appendix D – Membrane filter test device

General Test equipment


1. The function of this test device is to collect 6. The following equipment is required:
particulate material which may be present in the
a. a membrane filter holder;
pipeline.
b. a supply of white hydrophobic membrane filters
2. Filter holders appropriate to the pressure
of not more than 0.45 µm pore size and with
encountered are commercially available.
high mechanical strength;
3. The filter holder should be specified for use at
c. a means of connecting the filter to the pipeline;
pipeline-distribution pressure and be oxygen-
compatible. d. a means of controlling the flow through the
filter, which is connected downstream of the
Measurement principle filter. One method of achieving this is to use the
appropriate Amal jets to achieve a minimum
4. A known volume of gas is passed through a flow of 150 L/min at 400 kPa and 350 L/min at
membrane filter that will collect all visible particles. 700 kPa;
5. Hydrophobic membrane filters of pore size e. all equipment must be oxygen-compatible and
0.45 µm should be used. hoses should be antistatic.

163
Health Technical Memorandum 02-01: Medical gas pipeline systems – Part A

Appendix E – Equipment for contaminant


testing

General Measurement principle


1. The function of these tests is to establish whether 3. A known volume of gas is passed through a tube
the pipeline has been contaminated during packed with an absorbent, which is coated with
construction or modification. The specifications for specific colorimetric reagents. The reagents react
the permissible concentrations of each component quantitatively with the compound to be measured
are summarised in Table 20. and produce a colour change along the length of
the tube, which is proportional to the concentration
2. Simple equipment that is of the required sensitivity
of the compound being measured.
and is suitable for use on site is commercially
available. 4. Tubes are available with appropriate sensitivities for
the measurement of oil, water, carbon monoxide
and carbon dioxide, sulphur dioxide, and higher
oxides of nitrogen.

Notes
Non-agent-specific detector tubes are difficult to
interpret and are not recommended because of their
qualitative and non-quantitative response.

164
Appendix F – Equipment for gas identification

General Nitrous oxide


1. The function of these tests is positively to identify 5. The nitrous oxide sensor should not give greater
medical gases by measuring their oxygen, nitrous than ±1% response in the presence of 100%
oxide and nitric oxide content. oxygen, 100% nitrogen or 100% carbon dioxide.
An infrared/fuel cell meter is now commercially
2. Portable equipment of the required specificity and available.
sensitivity is commercially available.
3. Thermal conductivity meters do not give a positive Specification
identification of nitrous oxide in the presence of
6. The equipment should be portable, preferably
carbon dioxide, and should not be used as a sole
battery-powered, with digital or analogue indication
means of identification of nitrous oxide. A specific
of 0–100% to one decimal place. The battery
nitrous oxide meter should be used. If carbon
should give at least eight hours’ continuous running
dioxide pipelines are present, for example in IVF
between recharging or replacement.
(in vitro fertilisation) clinics, a carbon dioxide
detector tube should be used. 7. An accuracy better than ±1% is required, with a
zero stability of 2.5% per day.
Specificity 8. The response time must be not more than
15 seconds to 90% of the final reading.
Oxygen
4. Oxygen-specific sensors using different
measurement principles are currently in
manufacture. The oxygen sensor should not give
greater than ±1% response in the presence of 100%
nitrous oxide or 100% nitrogen.

Notes
A paramagnetic meter is the specified instrument for
identity of oxygen.

165
Health Technical Memorandum 02-01: Medical gas pipeline systems – Part A

Appendix G – Pressure loss data

Pipeline pressure-drop calculations


1. Example: Calculate the pressure drop in a 15 mm diameter pipe, 12 m in length, carrying medical air at a design
flow rate of 800 L/min.

Solution
2. The pressure drop Δp across the pipe can be calculated from the formula:
Δp =  Measured length of pipe
Nearest length of pipe from Table A1
× [ Design flow
Nearest flow from Table A1 ]2
× Pressure drop from Table A1
(2)
3. From Table A1, the nearest length to 12 m is 15 m and the nearest flow rate to the design flow of 800 L/min is
711 L/min in the 15 m column, at which there is a pressure drop of 21 kPa across a 15 mm diameter, 15 m
length of pipe.
4. Using these values, Equation (2) gives a pressure drop across the 12 m pipe of:

15 711 [ ]
12 × 800 2 × 21

= 21.3 kPa.
5. If this loss is unacceptable, use the next (higher) pipe size, that is 22 mm. The nearest flow rate to 800 L/min is
now 1135 L/min, representing a pressure loss of 7 kPa over 15 m.
6. In this instance:
Δp = 2.8 kPa.

Table A1 Section of pressure drop table for medical air


Old BS New British Standard size (BS EN 1057: R250, Table X) Distance from source at 400 kPa for 7, 14 and
659 size 21 kPa (0.07, 0.14 and 0.21 bar) pressure loss
Nominal Outside Wall Mean internal diameter 8 m (25 ft) 15 m (50 ft)
bore diameter thickness
(inches) (mm) (mm) (mm) (inches)
3/ 12 0.6 10.8 0.4252 311 455 564 209 307 382
8
½ 15 0.7 13.6 0.5354 579 845 1038 391 572 711
¾ 22 0.9 20.2 0.7953 1677 2441 3023 1135 1656 2053
1 28 1.2 26.2 1.0315 3363 4881 6034 2283 3320 4109
¼ 35 1.2 32.6 1.2835 6023 8720 10,758 4096 5943 7344
1½ 42 1.2 39.6 1.5591 10103 14,587 17,963 6883 9963 12,290
7. It is possible to insert the above formula into a spreadsheet and use mathematical functions to calculate required
pressure drops (see Tables A2–A5).

166
Table A2 Pipeline pressure loss: 400 kPa (4 bar) pipelines
British Standard Size Tube
Distance from source (m) at 400 kPa for 7, 14, 21 kPa (1, 2, 3 psi) pressure loss
BS EN 1057: R250, Table X
Outside Pressure loss 8 15 30 61 91 122 152 183 213 244 274 305 335 366 396 427 457
Diameter (kPa)
(mm) Free air flow rate (L/min)
12 7 311 209 141 95 75 64 56 50 46 43 40 37 35 34 32 31 30
14 455 307 207 139 110 94 82 74 68 63 59 55 52 50 47 45 44
21 564 382 258 174 138 117 103 93 85 78 73 69 65 62 59 57 55
15 7 579 391 263 177 140 119 105 94 86 80 75 70 66 63 60 58 56
14 845 572 386 260 207 175 154 139 127 118 110 104 98 93 89 85 82
21 1038 711 481 325 258 219 192 173 159 147 137 129 122 117 111 107 102
22 7 1677 1135 768 518 411 349 307 277 254 235 220 207 196 186 178 170 164
14 2441 1656 1123 759 604 513 451 407 373 345 323 304 288 274 262 251 241
21 3023 2053 1395 945 751 638 562 507 465 431 403 379 359 342 326 313 301
28 7 3363 2283 1547 1047 832 706 622 560 514 476 445 419 397 378 361 346 332
14 4881 3320 2257 1530 1218 1035 912 823 754 699 653 615 583 555 530 508 488
21 6034 4109 2800 1901 1514 1287 1135 1024 938 870 814 767 726 691 660 633 609
35 7 6023 4096 2783 1886 1500 1275 1124 1013 928 861 805 758 718 683 653 626 602
14 8720 5943 4051 2752 2192 1865 1644 1483 1360 1261 1180 1111 1053 1002 957 918 883
21 10758 7344 5018 3415 2723 2317 2044 1845 1692 1569 1468 1383 1310 1248 1192 1143 1099
42 7 10103 6883 4685 3180 2533 2154 1899 1713 1570 1456 1362 1283 1215 1157 1105 1060 1019
14 14587 9963 6806 4633 3694 3145 2775 2504 2296 2130 1993 1878 1780 1694 1619 1553 1493
21 17963 12290 8421 5743 4584 3904 3446 3112 2855 2648 2478 2335 2213 2107 2014 1932 1858
54 7 14974 10588 7487 5294 4323 3743 3348 3056 2830 2647 2496 2368 2257 2161 2076 2001 1933
14 21176 14974 10588 7487 6113 5294 4735 4323 4002 3743 3529 3348 3192 3056 2937 2830 2734

Appendix G – Pressure loss data


21 25935 18339 12968 9169 7487 6484 5799 5294 4901 4585 4323 4101 3910 3743 3597 3466 3348
76 7 37754 26696 18877 13348 10899 9438 8442 7706 7135 6674 6292 5969 5692 5449 5236 5045 4874
14 53392 37754 26696 18877 15413 13348 11939 10899 10090 9438 8899 8442 8049 7706 7404 7135 6893
21 65392 46239 32696 23119 18877 16348 14622 13348 12358 11560 10899 10339 9858 9438 9068 8738 8442
Examples:
1 122 m of 28 mm pipe would carry 706 L/min of free air per minute with a pressure loss of 0.07 bar (7 kPa), or 1287 L/min with a loss of 0.21 bar (21 kPa).
ie: 122/122 x (706/706)2 x 7
2 A flow of 1200 L/min in 122 m of 28 mm pipe would result in a pressure loss of 18.26 kPa. ie: 122/122 x (1200/1287)2 x 21
167

3 140 m of 28 mm pipe would carry 800 L/min with a pressure loss of 9.92 kPa. ie: 140/152 x (800/912)2 x 14
Table A3 Pipeline pressure loss: 700 kPa (7 bar) pipelines
168

Health Technical Memorandum 02-01: Medical gas pipeline systems – Part A


British Standard Size
Tube BS EN 1057: Distance from source (m) at 700 kPa for 7, 14, 34 kPa (1, 2, 5 psi) pressure loss
R250, Table X
Outside Pressure 8 15 30 61 91 122 152 183 213 244 274 305 335 366 396 427 457
Diameter loss (kPa)
(mm) Free air flow rate (L/min)
12 7 408 276 186 125 99 84 74 67 61 56 53 50 47 45 43 41 39
14 599 405 274 185 147 124 109 99 90 84 78 74 70 66 63 61 58
34 979 664 450 304 242 205 181 163 149 138 129 122 115 110 105 100 96
15 7 759 514 347 234 186 158 139 125 114 106 99 93 88 84 80 77 74
14 1112 754 510 345 274 232 205 184 169 156 146 138 130 124 118 114 109
34 1811 1231 836 566 450 383 337 304 279 258 242 227 215 205 196 188 180
22 7 2192 1488 1009 682 542 460 406 366 335 310 290 273 259 246 235 225 217
14 3198 2175 1478 1001 797 677 597 538 493 457 428 403 381 363 347 332 320
34 5180 3533 2410 1638 1306 1111 980 884 811 752 704 663 628 598 571 548 527
28 7 4387 2984 2027 1374 1093 929 819 739 677 628 587 553 524 498 476 456 439
14 6382 4351 2963 2013 1604 1364 1203 1086 995 923 863 813 771 734 701 672 646
34 10290 7038 4816 3283 2620 2232 1970 1779 1632 1514 1417 1335 1266 1205 1152 1105 1063
35 7 7841 5345 3638 2470 1968 1674 1476 1332 1221 1132 1059 998 945 900 860 825 793
14 11380 7775 5307 3612 2881 2453 2165 1954 1792 1662 1556 1466 1389 1323 1264 1212 1166
34 18271 12528 8599 5876 4696 4003 3536 3194 2931 2720 2547 2401 2276 2168 2073 1988 1912
42 7 13128 8964 6113 4159 3316 2823 2490 2248 2061 1912 1789 1686 1598 1521 1454 1394 1341
14 19010 13012 8901 6070 4847 4129 3646 3293 3021 2803 2624 2473 2344 2232 2134 2047 1969
34 30392 20892 14381 9849 7881 6723 5942 5371 4930 4577 4286 4042 3833 3651 3491 3349 3223
Examples:
1 122 m of 28 mm pipe would carry 929 L/min of free air per minute with a pressure loss of 0.07 bar (7 kPa), or 2232 L/min with a loss of 0.34 bar (34 kPa).
ie: 122/122 x (929/929)2 x 7
2 A flow of 1800 L/min in 122 m of 28 mm pipe would result in a pressure loss of 22.11 kPa. ie: 122/122 x (1800/2232)2 x 34
3 140 m of 28 mm pipe would carry 1100 L/min with a pressure loss of 10.78 kPa. ie: 140/152 x (1100/1203)2 x 14
Table A4 Pipeline pressure loss: 1100 kPa (11 bar) pipelines

British Standard
Size Tube BS EN Distance from source (m) at 1100 kPa for 7, 14, 34 kPa (1, 2, 5 psi) pressure loss
1057: R250, Table X
Outside Pressure 8 15 30 61 91 122 152 183 213 244 274 305 335 366 396 427 457
Diameter loss (kPa)
(mm) Free air flow rate (L/min)
12 7 487 356 252 177 144 124 112 102 94 88 84 79 75 72 69 67 65
14 689 503 355 249 204 177 158 144 133 124 118 111 106 102 98 94 91
34 1084 791 560 392 321 277 249 227 210 197 185 176 167 161 154 148 143
15 7 867 634 448 314 257 222 199 181 168 157 148 141 134 128 124 119 115
14 1226 895 633 444 363 314 281 257 238 222 209 199 189 181 174 168 162
34 1929 1409 996 698 572 494 443 403 373 350 330 313 298 285 275 264 256
22 7 2332 1703 1205 845 692 598 535 487 452 423 399 378 360 345 332 319 309
14 3294 2405 1701 1193 977 844 755 689 638 597 562 534 509 487 468 451 436
34 5185 3787 2678 1878 1537 1328 1189 1084 1005 939 886 840 801 767 737 710 686
28 7 4469 3263 2308 1618 1325 1145 1025 935 866 809 764 724 691 660 636 612 591
14 6311 4608 3259 2286 1872 1616 1448 1320 1223 1143 1078 1022 976 933 897 864 835
34 9935 7255 5130 3598 2946 2544 2279 2077 1926 1799 1698 1609 1535 1469 1412 1359 1315
35 7 7718 5636 3985 2795 2289 1976 1771 1614 1495 1397 1319 1250 1192 1141 1097 1056 1021
14 10898 7959 5628 3947 3231 2791 2500 2279 2112 1973 1862 1765 1684 1611 1549 1492 1442
34 17157 12530 8860 6213 5087 4394 3936 3587 3325 3107 2932 2779 2651 2537 2439 2348 2271
42 7 12550 9166 6481 4545 3721 3214 2879 2624 2432 2272 2144 2033 1940 1855 1784 1718 1661
14 17724 12944 9152 6418 5255 4538 4066 3706 3435 3209 3029 2871 2739 2620 2519 2426 2345
34 27902 20377 14409 10104 8273 7145 6401 5834 5407 5052 4768 4519 4312 4125 3966 3819 3692

Appendix G – Pressure loss data


Examples:
1 122 m of 28 mm pipe would carry 1145 L/min of free air per minute with a pressure loss of 0.07 bar (7 kPa), or 2544 L/min with a loss of 0.34 bar (34 kPa).
ie: 122/122 x (1145/1145)2 x 7
2 A flow of 2200 L/min in 122 m of 28 mm pipe would result in a pressure loss of 25.43 kPa. ie: 122/122 x (2200/2544)2 x 34
3 140 m of 28 mm pipe would carry 1300 L/min with a pressure loss of 10.39 kPa. ie: 140/152 x (1300/1448)2 x 14
169
Table A5 Pipeline pressure loss (vacuum)
170

Health Technical Memorandum 02-01: Medical gas pipeline systems – Part A


British Standard
Size Tube BS EN Distance from source (m) at 59 kPa (450 mm Hg) for 1.3, 2.6, 3.9, 6.5 kPa (10, 20, 30, 50 mm Hg) pressure loss
1057: R250, Table X
Outside Pressure 8 15 30 61 91 122 152 183 213 244 274 305 335 366 396 427 457
Diameter loss (kPa)
(mm) Free air flow rate (L/min)
12 1.3 – – – – – – – – – – – – – – – – –
2.6 47 – – – – – – – – – – – – – – – –
3.9 60 40 – – – – – – – – – – – – – – –
6.5 82 55 – – – – – – – – – – – – – – –
15 1.3 59 – – – – – – – – – – – – – – – –
2.6 89 59 40 – – – – – – – – – – – – – –
3.9 113 76 51 – – – – – – – – – – – – – –
6.5 153 103 69 46 – – – – – – – – – – – – –
22 1.3 173 116 78 52 41 – – – – – – – – – – – –
2.6 260 174 117 79 62 53 46 42 – – – – – – – – –
3.9 330 222 149 100 79 67 59 53 49 45 42 40 – – – – –
6.5 445 301 203 137 108 92 81 73 67 62 57 54 51 49 46 45 43
28 1.3 350 236 159 106 84 71 63 56 51 48 44 42 40 – – – –
2.6 525 353 238 160 127 107 94 85 78 72 67 63 60 57 54 52 50
3.9 666 448 303 204 161 137 120 108 99 92 86 81 76 73 69 66 64
6.5 900 607 412 278 220 187 164 148 135 125 117 110 104 99 95 91 87
35 1.3 637 427 288 193 153 130 114 102 94 87 81 76 72 69 65 63 60
2.6 947 638 431 290 230 195 171 154 141 131 122 115 109 103 99 95 91
3.9 1198 808 548 369 293 248 218 197 180 167 156 147 139 132 126 121 116
6.5 1614 1091 743 503 399 339 298 269 246 228 213 200 190 180 172 165 158
42 1.3 1074 724 488 328 260 220 194 174 160 148 138 130 123 117 111 107 103
2.6 1598 1079 731 493 391 331 291 262 240 222 208 196 185 176 168 161 155
3.9 2016 1363 926 626 497 422 371 334 306 283 265 249 236 224 214 205 197
6.5 2706 1833 1254 851 677 574 506 456 417 387 361 340 322 306 293 280 270
54 1.3 2191 1480 1001 674 535 453 399 359 329 304 284 268 253 241 230 220 212
2.6 3246 2196 1493 1010 802 681 599 540 494 458 428 403 381 363 346 332 319
3.9 4083 2766 1889 1281 1019 865 762 687 629 582 545 513 485 462 441 423 406
6.5 5448 3699 2549 1737 1384 1176 1037 935 856 794 742 699 662 630 601 576 554
76 1.3 5521 3773 2563 1733 1377 1169 1029 927 849 786 735 692 655 623 595 570 548
2.6 8070 5563 3807 2586 2058 1749 1541 1389 1273 1179 1103 1038 983 936 894 857 823
3.9 10041 6968 4801 3274 2609 2219 1957 1765 1617 1499 1402 1320 1250 1190 1137 1090 1048
6.5 13166 9233 6439 4421 3533 3009 2655 2396 2197 2037 1906 1796 1701 1619 1547 1483 1426
108 1.3 12874 9140 6543 4552 3732 3280 2879 2628 2433 2276 1919 2036 1941 1858 1785 1712 1641
2.6 18207 12874 9235 6578 5274 4552 4071 3716 3441 3219 3035 2879 2745 2628 2525 2422 2325
3.9 22494 15905 11374 8114 6509 5657 5030 4592 4251 3976 3750 3557 3391 3247 3119 2992 2870
6.5 29238 20675 14708 10520 8445 7343 6538 5968 5526 5169 4873 4623 4408 4220 4055 3889 3730
Examples:
1 122 m of 28 mm pipe would carry 71 L/min of free air per minute with a pressure loss of 10 mm Hg (1.3 kPa), or 187 L/min with a loss of 50 mm Hg (6.5 kPa).
ie: 122/122 x (71/71)2 x 1.3
2 A flow of 120 L/min in 122 m of 28 mm pipe would result in pressure loss of 2.99 kPa. ie: 122/122 x (120/137)2 x 3.9
3 140 m of 28 mm pipe would carry 90 L/min with a pressure loss of 2.20 kPa. ie: 140/152 x (90/94)2 x 2.6
Appendix G – Pressure loss data

8. Another alternative is to derive graphs from the tables, although it may be necessary to draw several graphs,
at different scales, to obtain accurate results.
9. The graphs of flow vs pressure drop provide a pressure loss per metre of pipe, not a total pressure loss. This figure
must be multiplied by the length of the pipe in order to find the actual total pressure drop.
10. Because a pipe and the fittings in the system cause frictional resistance to the gas flow, a pressure loss occurs that
is greater than that which would occur if the gas were flowing through the same distance of straight pipe.
11. Each valve, fitting etc is allocated a “length” equivalent in frictional resistance to a straight piece of pipe of the
same diameter. This length is hence known as the equivalent length of the fitting.
12. To calculate design flows, the sum of the lengths of the straight runs of pipe plus the sums of the equivalent
lengths of all of the fittings etc in that run are added.
13. In practice many designers simply add 25–30% to the total measured length or use only 60–75% of the
allocated pressure drop when sizing.
14. Equivalent lengths of some fittings are given in Tables A6 and A7.

Table A6 Equivalent lengths for copper fittings


6 mm 8 mm 10 mm 12 mm 15 mm 22 mm 28 mm 35 mm 42 mm 54 mm 76 mm
Ball valve 0.10 0.10 0.20 0.30 0.30 0.60 0.90 0.90 1.10 1.20 1.20
Tee (Thru’) 0.12 0.15 0.18 0.21 0.32 0.42 0.54 0.70 0.82 1.05 1.56
Tee (Branch) 0.46 0.52 0.70 0.80 0.95 1.26 1.60 2.10 2.45 3.14 4.67
90° Elbow 0.17 0.20 0.25 0.33 0.47 0.63 0.80 1.05 1.23 1.58 2.36

Table A7 Equivalent lengths for ABS (acrylonitrile butadiene styrene) vacuum fittings
40 mm 50 mm 70 mm 100 mm 125 mm
Tee (Thru’) 0.95 1.23 1.65 2.20 2.56
Tee (Branch) 2.76 3.38 4.57 6.12 7.68
90° elbow 1.25 1.71 2.44 3.08 3.84

171
Appendix H – Checklist for planning/installing/
upgrading a cryogenic liquid
supply system

1. Information given in this Appendix can be used to • Will other facilities be lost/reduced, for example
determine the need for a particular capacity or type car-parking space?
of supply system. Many of the factors described will
• It will be less economical in terms of delivery
also apply to planning an upgrade to an installation
charges and unit gas costs to deliver large loads
by way of increase in system size or a change of
(for example 20 tons) using rigid vehicles
system type.
(maximum 12 tons). Articulated vehicles will
2. Some factors that should be considered are outlined deliver the largest loads but may require
below. roadway/access modifications.
• Cranage access for vessels.
Delivery frequency
• When choosing liquid cylinder systems, will
• Does current frequency cause logistical problems adequate ventilation be available?
for the supplier/your site?
• Emergency supply location.
Calculating consumption • Pipeline protection and possible need for dual
• Consumption is rising at approximately 10% feeds.
per annum. It doubles in seven years. • Pipeline extension into other sites if applicable,
• Use pharmacy records for cylinder/liquid for example two hospitals supplied from the
consumption. Look for peaks in demand, for same VIE system. There are possible insurance
example winter influenza epidemics. issues with this arrangement.

• When average and peak flow rates are known, • Modifications to the alarm system may have to
calculate the required size of the emergency be made.
supply. • Alarm panel + telemetry in waterproof
enclosures.
Age of current system • Are alarms compatible with the existing system?
• The secondary supply of older VIE systems will • Alarm arrangement for dual (but separate) tank
be a compressed gas cylinder manifold, which installations.
may have very limited capacity. Consideration
should be given to either a single VIE plus fully • Cable ducts and trays: examine possible routes.
automatic manifold or, preferably, a dual VIE • Possible need to move gates/fences to install new
system. pipework.

Siting of system and the site survey • Clearance of trees/building.

• What planning restrictions apply (vessel size, • Sealing windows of adjacent buildings.
noise etc)? • Position of frame for valve tree (fix to fence for
• What are convenient locations for cylinder/ rigidity?).
liquid delivery? • Position of emergency gate.
• Advantages of separating primary and secondary • Position of fill couplings must allow driver to see
supplies, if space is available. tank gauges.

172
Appendix H – Checklist for planning/installing/upgrading a cryogenic liquid supply system

• Cabling and alarm runs for the emergency • What, if any, commitment is required by the gas
supply manifold (ESM). company?
• Availability and presentation of alarms for ESM. • How will gas prices vary during this period?
• Power and lighting during work. • Is there any agreement to provide, for example,
modified roadway facilities if rigid vehicular
• Drainage – catch pits, diversions, pad resizing.
deliveries are too frequent to be convenient to
supplier? Or if such roadway modifications take
Costs place within a defined timescale, new rates etc
• Make sure all costs are allowed for, for example: may need to be negotiated.
(i) Site inspection. • Check defects liability (usually 12 months).
(ii) Cost of continuing delivery using rigid
and non-articulated vehicles. Emergency provision
(iii) Gas charge/HCM (hundred cubic metres) • Examine the vulnerability of current system and
and any inflation likely. main feeds to hospital.

(iv) Facility charges (rental). • Consider minimum size of manifold plus


cylinder storage to meet four-hour supply
(v) Delivery charge for equipment. requirement. Is a second VIE a better option?
(vi) Loan charges and changes in interest rate • Operational requirements of ESM.
on any loan if the installer funds any part
of the installation. • Protection/housing/security of ESM.

(vii) Road/compound loans will be seen as £x • Alarm/monitoring systems and power supplies
added to gas price over y years. for ESM and its accommodation.

(viii) Climate change levy. System shutdown during installation


(ix) Professional fees (consultancy). • Often it will be necessary to interrupt site
(x) Planning permission. supplies during connection of new plant.
How will this be managed?
(xi) Building Regulations clearance.
• Disruption of two hospitals simultaneously if
(xii) All civil engineering work. plant to be upgraded is supplying both sites.
(xiii) Quoted price for gas/facilities/delivery • Examine planned plant and pipework systems
charges may be dependent on payment carefully to ascertain the best way of minimising
by direct debit. downtime and facilitating engineering and
(xiv) Introduction/modification and pharmaceutical testing.
maintenance of services, for example • While installing, fit extra valves to allow
lighting, power supplies, drainage. for future expansion and emergency supply
(xv) Engineering and pharmaceutical testing. manifolds to protect vulnerable parts of the
system.
(xvi) Additional emergency provision and any
associated cylinder charges. • Fit NIST fittings wherever this will facilitate
system purging.
(xvii) Modifications to alarm and telephone
systems. • Fit test points/emergency inlet ports as
recommended in this guidance or investigate
(xviii) Security.
any likely requirement for additional (local)
(xix) Charges for ESM cylinders during manifolds to support high-dependency areas.
installation (may have to be charged and
then recovered).
(xx) Cranage charges.
(xxi) Contingency 10%.

173
Medical gases – HTM 02-01 Medical gas pipeline systems – Part A: Design, installation, validation and verification

Paperwork supplier may be able to arrange multi-cylinder


pallets.
• Site survey details.
• Road base preparation, if required, must be
• Register of contractors with contact names/ completed in an early phase of the work to allow
telephone numbers. necessary access for cranes and, eventually,
• Keep a record of all dates, for example: delivery vehicles.
(i) tender invitation; • Road surfacing/kerbing/drainage/lighting.
(ii) tender open; • Retaining walls around compound if required,
for example on sloping sites.
(iii) tender close;
• Maintaining rights of way.
(iv) award and regret letters to tenderers.
• Oxygen compound civil engineering work.
• Copies of all letters to/from contractors.
• If you are changing supplier, your original
• NICEIC (National Inspection Council for supplier will need to remove old equipment
Electrical Installation Contracting) test before plinth can be extended to fit new vessels.
certificate for electrics.
• Electrics for alarms, tank, lighting and, possibly,
• Validation and verification results (engineering vehicle pump.
and pharmaceutical).
• Floodlighting and telephone line.
• Health and safety policies of contractors.
• Plan vehicular parking during (and after) work.
• Method statements from contractors.
• The old plinth may require skimming to provide
• Insurance agreement with gas supplier for VIE a reasonable surface.
system(s).
• MGPS operational policy protocols. Installation
• If an ESM (as a third means of supply) is
Health and safety installed first, this can be used to supply the
• Health and safety policy (contractors and hospital system during vessel replacement.
their employees, and subcontractors and their • Decide who arranges emergency cylinder
employees, must comply when employed by the supplies for ESM. When plinth extensions are
trust and working on trust properties). required, specify oxygen-compatible sealant for
• Inform contractors of specific site hazards. gaps between old and new plinth sections.
• Hazard notices on site and on final installation. • Remember to post health and safety notices
during the work.
• Lighting during installation and for completed
compound. • Alarm systems will not be fully functional until
system is fully commissioned. Therefore, all staff
• Road markings and signage.
must be kept aware of the different alarm
situation.
Preparation
• Concrete will need two to three days to harden
• Carefully plan phasing of building work to on any pad extension.
maximise efficiency of installation programme.
(Remember concrete plinths will take three days • The first vessel filling is a very noisy procedure
to harden before vessels can be sited.) with much vapour and can take several hours
(consider restrictions).
• Plan phasing of engineering and QC testing to
avoid wasting APs’/QCs’ time. • Concrete sample testing will be required during
new plinth construction.
• Consider methods of maintaining supplies
during essential shutdowns. Cylinder supplies • Use temporary steel sheeting to support a new
may be needed during commissioning. Gas vessel on tarmac alongside the plinth.

174
Appendix H – Checklist for planning/installing/upgrading a cryogenic liquid supply system

• Access for cranage must be kept open (car • Proximity of flammables and vital services
parking control). during installation – vulnerability to mechanical
damage (cutting discs etc), welding and cutting
• Drainage (may have to move existing drains/
flames/sparks.
soakaways and create new pipe runs; remember
oxygen separation distances). • Power and lighting supplies during work.
• Road markings and signage. • Water supply (washing and concrete) during
work.
• Possible new kerbs/footpaths.
• Electrical supplies: single phase can be used for Follow-up
lighting, alarms etc but three-phase 60 A supply
will be needed for delivery vehicle pump if • Routine maintenance and monitoring of
appropriate. complete installation.

• Earth bonding/lightning protection for fences. • Cylinder changes and stock management for
ESM.
• Alarm interface/telemetry boxes at a sensible
height for viewing. • Establish system management arrangements for
vessels supplying more than one site (see Part B,
• Lagging of liquid lines. Appendix G).
• If using 200 bar unregulated cylinders for • Update MGPS operational policy and any
supply during installation or on ESM, take relevant insurance policies.
care that they are not mixed up with 137 bar
cylinders.

175
Medical gases – HTM 02-01 Medical gas pipeline systems – Part A: Design, installation, validation and verification

Appendix J – Upgrading surgical air systems

Background b. Is the compressor plant capable of meeting


the increased duty cycle?
1. An increasing number of surgical air pipeline Overheating and premature plant failure may
systems are designed to operate at a line pressure result if this is not the case. The system may
above the nominal 700 kPa, for example 1000– be supplying both surgical and medical air.
1100 kPa. This enables the system to deliver 350 L/ Plant failure/flow reduction resulting from an
min (at 700 kPa) at the front of the surgical air overburdened surgical air system may have
terminal unit. serious consequences in terms of medical air
2. Such a system will comprise a high-pressure supply provision, particularly as this is the
pipeline installation, in the order of 1000–1100 kPa recommended driving gas for patients’
and local pressure regulation (for example adjacent ventilators.
to the operating suite) such that the maximum This guidance recommends the use of separate
static pressure does not exceed 900 kPa. plant for surgical air/medical air, but this may
not always be the case with older Health
3. Existing Health Technical Memorandum 2022 Technical Memorandum 2022 plant.
systems run at a line pressure of 700 kPa and will
provide a flow of 250 L/min at the front of the c. Are the pressure safety valves (PSVs) suitably
terminal unit. rated?
PSVs on pipelines and the receiver will need
4. Users must be made aware (preferably by written to be changed to meet the new operating
report) that such systems will not meet the conditions. Certificated replacement PSVs
demands of some modern air tools and that use should be used.
of such tools may result in both a lack of tool
performance and frequent low-pressure alarms on d. Are pressure switches suitably rated and
the surgical air system. adjusted?
Pressure switches on plant and pipelines will
5. Tools are available that require a flow up to 500 L/ need to be changed or adjusted accordingly.
min at an operating pressure of 1400 kPa. Such
tools will require discrete cylinder supplies. e. Has the pipeline been suitably pressure-
tested?
Modifying “old” systems There may be occasions when existing 4 bar
systems (or parts thereof ) are proposed for use at
6. Increasing line pressure to meet the latest 7 bar or higher. 4 bar systems are only tested to
recommended flow rates is often proposed, but 10 bar; they will need to be retested at 18 bar to
needs to take account of the following: ensure a leak-free high-pressure system.
a. Is the compressor receiver suitable for use at f. Will you still be insured?
the proposed pressures? If the pipeline system contains large diameter
A typical “old” 700 kPa system will employ a pipe (120 mm or above), the insurance
receiver operating at typically 10 bar pressure. company should be consulted to ascertain
A “new” system, with a typical line pressure whether the system would be capable of
of 10.5 bar, requires a receiver operating at a withstanding not only the pipeline operating
typical pressure of 13 bar. pressure but also any test pressure that may
Ensure that the test, design and working be applied during system refurbishment or
pressures of the current receiver are acceptable, extension. Many insurance companies will not
and that the capacity of the receiver is allow testing of pipe diameters greater than
appropriate to the new demand.

176
Appendix J – Upgrading surgical air systems

100 mm at 18 bar, as this pressure is likely to


compromise the pipe integrity.
The insurance company should be consulted on
any necessary amendments.
A new Written Scheme of Examination will
have to be prepared for the new system.
g. Labelling.
Ensure that all relevant labels are in place before
the system is accepted.
h. Other issues.
There may be other system defects discovered
during the upgrading process, for example lack
of pipeline support/protection.
There may also be a potential contamination
issue resulting from the transfer of particulate
matter from older, silver-soldered systems into
new inert gas shield brazed pipework, although
it should be noted that this is not an issue
limited to air systems. The Quality Controller
(MGPS) will advise on this and adopt
appropriate testing methods.
These issues will need to be addressed before the
system is accepted for use.
Ensure that any system amendments and
changes in working practices are documented in
the MGPS operational policy.

177
Medical gases – HTM 02-01 Medical gas pipeline systems – Part A: Design, installation, validation and verification

Appendix K – Signage requirements

Location Wording Notes


Medical Gas Plant Room – No unauthorised Entry Adjacent to or on external door
Fire action On door/wall
External or internal
Keep locked On door(s)
Noise Hazard (+ ear defender symbol)
Electric shock hazard Adjacent to, or on, external door
Permit-to-work must be used
Plant is connected to essential electricity supply “E” symbols can be used on switches etc
Danger 415 volts On plant/switchgear
Danger 240 volts On plant/switchgear
Danger rotating machines
Warning: These machines stop and start automatically without
Plantroom warning Posted adjacent to plant
Guards must be in position
Do not isolate without a Permit
Vac filters and exhausts
Biological symbol Also for AGSS units/exhausts/drain
flasks
Medical air intake Do not obstruct On external intakes only
Emergency Tel No
Gas Supplier
Estates External wall
Pharmacy
Porters
Health and Safety Law Internal wall
First aid Internal wall
Notes:
“Bacteria filter change procedure” sign is not available commercially and will have to be made locally.
No “Danger medical gas/vac/AGSS exhaust” sign is commercially available but “Danger explosive gases, no smoking, no naked
lights” is available and would suffice.
“Danger 440/240 volts”, “Warning: These machines stop and start automatically/without warning” and “Biohazard” labels
would need to be added to AGSS plant remote from main plantroom, plus any relevant plantroom notices.

178
Appendix K – Signage requirements

Location Wording Notes


Medical gases manifold room – No unauthorised entry Adjacent to or on external door
No parking Adjacent to or on external door
Approved personal protective equipment must be worn Adjacent to or on external door
Fire action Internal/external wall
Cylinder status tag On manifold cylinders
Valve open On line valves/ERM cyls
Valve closed On line valves/ERM cyls
Make sure cylinders are secure at all times Internal, near cylinders
Manifold room Danger No smoking External (on door or wall)
Danger compressed gas External (on door or wall)
Warning oxidising agent External (on door or wall)
Danger oxygen External (on door or wall)
Emergency Tel No
Gas suppliers
Estates External, on wall or door
Pharmacy
Porters
Keep locked On door
Notes:
Also required:
Cylinder ID charts, manifold cylinder change procedure, emergency manifold operating procedure.
Check with fire officer for any local fire brigade requirements for fitting “HAZCHEM” signs eg “HAZCHEM 2SE Cylinders”.

179
Medical gases – HTM 02-01 Medical gas pipeline systems – Part A: Design, installation, validation and verification

Location Wording Notes


Medical gases cylinder store – No unauthorised entry Adjacent to or on external door
No parking Adjacent to or on external door
Keep loading bay/doors clear Adjacent to or on external door
Approved personal protective equipment must be worn Adjacent to or on external door
Make sure cylinders are secure at all times Adjacent to cylinders
Fire action Internal/external wall
Full cylinders On bays
Empty cylinders On bays
Emergency exit keep clear May be already fitted
Main cylinder store Danger No smoking On door
Danger compressed gas On door
Warning oxidising agent External (on door or wall)
Danger oxygen External (on door or wall)
Emergency Tel No
Gas suppliers
Estates External wall
Pharmacy
Porters
Keep locked On door
Push bar to open Emergency exit and main door(s)
Notes:
“Danger liquid nitrogen” sign is available for a separate liquid nitrogen store (see BCGA CP30).
Cylinder ID chart(s) to be posted
Check with fire officer for any local fire brigade requirements for fitting “HAZCHEM” signs eg “HAZCHEM 2SE Cylinders”.

Location Wording Note


Medical gases cylinder store – No unauthorised entry Adjacent to or on external door
Make sure cylinders are secure at all times Adjacent to cylinders
Emergency Tel No
Gas suppliers
Estates External wall
Ready to use cylinder store Pharmacy
Porters
Danger No smoking On door
Danger compressed gas On door
Fire action Internal/external wall
Notes:
Post cylinder ID chart(s) and cylinder change procedure.
Check with fire officer for any local fire brigade requirements for fitting “HAZCHEM” signs, eg “HAZCHEM 2SE Cylinders”

180
Appendix K – Signage requirements

Location Wording Notes


Defines cylinder parking as per new Health
Medical gas cylinder parking area
Technical Memorandum
Emergency Tel No
Gas suppliers
Ward (cylinder parking bay)
Estates External wall
Pharmacy
Porters
Gas leak action On nurses’ station
Notes:
Post cylinder chart(s) and cylinder change procedure.
Operational policy may dictate posting of AVSU emergency operation and MGPS alarm responses.

Location Wording Notes


Maintenance in progress There may be other site safety notice requirements to fulfil
Medical gas test area
Confined space
Work area
Hot work in progress
Danger pressure test in progress
Danger nitrogen purging in progress
Notes:
These signs should be posted during installation/modification/maintenance of an MGPS.
Multiple signs may be required.

Location Wording Notes


Gas identity
Pipework
Flow direction

Location Wording Note


Gas identity On pipeline label
Line valves Flow direction
Key No

Location Wording Notes


In emergency break glass and shut off valve On/off positions to be shown on AVSU body
Gas identity
Flow direction
AVSUs
Area controlled
Key No
Valve No

Location Wording Notes


Area monitored
Responses may be posted nearby, in accordance with MGPS operational
Alarm displays Gas names
policy
Fault/normal/condition indicators

Location Signage will be determined by the equipment supplier but will usually include
VIE/ Liquid cylinders/PSA/synthetic air plant schematic, safety warnings and emergency actions

181
Medical gases – HTM 02-01 Medical gas pipeline systems – Part A: Design, installation, validation and verification

Appendix L – Important notes for use of medical


vacuum and anaesthetic gas
scavenging

Infectious disease units flows are unsuitable for use as dental vacuum,
which operates at much higher flow rates (typically
1. Medical vacuum should neither be extended to an 300 L/min). Medical vacuum systems should not
Infectious Diseases Unit (IDU) nor provided to be used to provide dental vacuum.
such a unit from a central vacuum system.
2. Portable suction units will be required. Anaesthetic gas scavenging (AGS)
Decontamination will require specialised protocols
and the advice of the infection control officer Active AGS systems (medical)
should be sought. 6. Active anaesthetic gas scavenging systems operate
at relatively high flow rates (80–130 L/min in a
Note BS 6834:1987 system; and 50–80 L/min in an
Systems already exist whereby an IDU is, by local ISO/DIS 7396-2:2005 system).
agreement, serviced via a central vacuum system. 7. It is unlikely that receiving systems designed for use
If such agreements exist, or are to be accepted, great with these scavenging systems will operate correctly
care must be taken to ensure that the exhausts of such with a medical vacuum system. Severe spillage of
a plant are kept well away from all air intakes and the waste gases into the operating area may occur.
plant is labelled to indicate its function. Ideally, the Therefore, medical vacuum systems should not be
plant should be housed in separate accommodation used as waste anaesthetic gas disposal systems.
but, where this is not possible, safety signage and strict
operational protocols are extremely important. Active AGS (dental)

Personnel changing filters, or carrying out work 8. Active AGS systems for use with dental nasal
on such a system, should wear personal protective scavenging masks operate by maintaining a flow of
equipment and follow protocols that have been devised air through the outer layer of a specially designed
in liaison with the infection control officer. concentric nose mask. Waste gases from the patient
pass from inner to outer layers of the mask and are
carried away to the exhaust termination by this air
Laser/surgical diathermy smoke stream.
extraction 9. The flow rate necessary to achieve effective removal
3. An additional contamination hazard can arise if of waste gases by such a method is in the order of
smoke from procedures employing laser or surgical 45 L/min, which is less than the flow rate achieved
diathermy equipment is exhausted using a cannula at a medical vacuum system terminal.
attached to the vacuum system. 10. Active dental scavenging systems using this type of
4. Clinical staff should be advised against this practice mask must therefore be driven (via a special flow
and either instructed to use dedicated laser smoke adjuster) from the dental vacuum system, a
removal units (incorporating dedicated, filtered, dedicated separate high-flow vacuum system, or an
portable vacuum pumps) or a specially designed active medical AGS system. In the case of a medical
laser smoke filter fitted to a medical vacuum system AGS system, the special flow adjuster would be
terminal unit. plugged directly into an AGS system wall terminal.
A receiver (air break) system would not be used
between the wall terminal and the special flow
Dental vacuum systems adjuster.
5. Medical vacuum systems operate at relatively low
flow rates at the terminal units (~40 L/min). Such

182
Appendix M – Oxygen usage data

Average oxygen flows based on bed numbers

2000

1500

1000
Flow (L/min)

500

200 400 600 800 1000 1200

Lower graph shows average flows to be expected in a typical acute hospital.

Upper graph shows flows to be expected when the hospital has specialties using
larger amounts of oxygen, eg those with multiple large critical care areas (>20 beds)
and an increased use of CPAP (>5 machines).

NB These graphs are issued for guidance only. There will be hospitals for which
average flows will, for a given number of beds, be higher or lower than the maxima
and minima shown here.

NB The flows are representative of oxygen provided from a VIE plant and do NOT
take into account additional consumption from compressed gas cylinders.

183
Medical gases – HTM 02-01 Medical gas pipeline systems – Part A: Design, installation, validation and verification

Appendix N – Pressure conversion table

Pressure Multiply units in left column by factor below


kPa lb/in2 lb/ft2 int atm kg/cm2 mm Hg in Hg ft water
@0°C @0°C @4°C
1 pound/sq in 6.895 1 144 0.0682 0.0703 51.713 2.0359 2.307
1 pound/sq ft 0.048 0.00694 1 0.0005 0.00052 0.3591 0.01414 0.01602
1 int atmosphere 101.3 14.696 2116.2 1 1.0333 760 29.921 33.9
1 kilogram/sq cm 98.07 14.223 2048.1 0.9678 1 735.56 28.958 32.81
1 mm Hg (1 torr) 0.133 0.0193 2.785 0.0013 0.00136 1 0.0394 0.0446
1 in Hg 3.387 0.4912 70.73 0.0334 0.0345 25.400 1 1.133
1 ft water 2.984 0.4335 62.42 0.0295 0.0305 22.418 0.8826 1
1 kilopascal (kPa) 1 0.145 20.92 0.0099 0.0102 7.519 0.295 0.3346

184
References

Acts and Regulations resistance of non-loadbearing elements of construction.


British Standards Institution, 1987.
(The) Control of Substances Hazardous to Health
Regulations 2002. SI 2002 No. 2677. HMSO, 2002. BS 476-23:1987. Fire tests on building materials and
http://www.opsi.gov.uk/si/si2002/20022677.htm structures. Methods for determination of the contribution
of components to the fire resistance of a structure. British
(The) Electromagnetic Compatibility Regulations Standards Institution, 1987.
2005. SI 2005 No. 281. HMSO, 2005.
http://www.opsi.gov.uk/si/si2005/20050281.htm BS 1710:1984. Specification for identification of
pipelines and services. British Standards Institution,
(The) Medicines Act 1968. HMSO, 1968. 1984.
(The) Pressure Systems and Transportable Gas BS 3928:1969. Method for sodium flame test for air
Containers Regulations 1989. SI 1989 No. 2169. filters (other than for air supply to IC engines and
HMSO, 1989. compressors). British Standards Institution, 1969.
http://www.opsi.gov.uk/si/si1989/Uksi_19892169_en_1.
htm BS 5499-5:2002. Graphical symbols and signs. Safety
signs, including fire safety signs. Signs with specific safety
(The) Public Health Act 1961. HMSO, 1961. meanings. British Standards Institution, 2002.
(The) Public Health (Drainage of Trade Premises) Act BS 5682:1998. Specification for probes (quick
1937. HMSO, 1937. connectors) for use with medical gas pipeline systems.
(The) Water Industry Act 1991. HMSO, 1991. British Standards Institution, 1998.
(The) Water Resources Act 1991. HMSO, 1991. BS 6834:1987. Specification for active anaesthetic gas
scavenging systems. British Standards Institution, 1987.
British Standards BS 7671:2001. Requirements for electrical installations.
BS 88. Cartridge fuses for voltages up to and including IEE Wiring Regulations. Sixteenth edition. British
1000 V ac and 1500 V dc. Standards Institution, 2001.

BS 341-3:2002. Transportable gas container valves. Valve BS EN 286-1:1998. Simple unfired pressure vessels
outlet connections. British Standards Institution, 2002. designed to contain air or nitrogen. Pressure vessels for
general purposes. British Standards Institution, 1998.
BS 476-4:1970. Fire tests on building materials and
structures. Non-combustibility test for materials. British BS EN 737-1:1998. Medical gas pipeline systems.
Standards Institution, 1970. Terminal units for compressed medical gases and vacuum.
British Standards Institution, 1998.
BS 476-20:1987. Fire tests on building materials and
structures. Method for determination of the fire resistance BS EN 737-2:1998. Medical gas pipeline systems.
of elements of construction (general principles). British Anaesthetic gas scavenging disposal systems. Basic
Standards Institution, 1987. requirements. British Standards Institution, 1998.

BS 476-21:1987. Fire tests on building materials BS EN 737-3:2000. Medical gas pipeline systems.
and structures. Methods for determination of the fire Pipelines for compressed medical gases and vacuum.
resistance of loadbearing elements of construction. British British Standards Institution, 2000.
Standards Institution, 1987. BS EN 737-4:1998. Medical gas pipeline systems.
BS 476-22:1987. Fire tests on building materials Terminal units for anaesthetic gas scavenging systems.
and structures. Methods for determination of the fire British Standards Institution, 1998.

185
Medical gases – HTM 02-01 Medical gas pipeline systems – Part A: Design, installation, validation and verification

BS EN 738-2:1999. Pressure regulators for use with BS EN ISO 4126-1:2004. Safety devices for protection
medical gases. Manifold and line pressure regulators. against excessive pressure. Safety valves. British Standards
British Standards Institution, 1999. Institution, 2004.
BS EN 739:1998. Low-pressure hose assemblies for use BS EN ISO 9001:2000. Quality management systems.
with medical gases. British Standards Institution, 1998. Requirements. British Standards Institution, 2000.
BS EN 740:1999, BS 5724-2.204:1999. Anaesthetic BS EN ISO 11197:2004. Medical supply units. British
workstations and their modules. Particular requirements. Standards Institution, 2004.
British Standards Institution, 1999.
BS EN ISO 13485:2003. Medical devices. Quality
BS EN 837-1:1998. Pressure gauges. Bourdon tube management systems. Requirements for regulatory
pressure gauges. Dimensions, metrology, requirements purposes. British Standards Institution, 2003.
and testing. British Standards Institution, 1998.
BS EN ISO 15001:2004. Anaesthetic and respiratory
BS EN 1044:1999. Brazing. Filler metals. British equipment. Compatibility with oxygen. British Standards
Standards Institution, 1999. Institution, 2004.
BS EN 1057:1996. Copper and copper alloys. Seamlesss, BS ISO 5011:2000. Inlet air cleaning equipment
round copper tubes for water and gas in sanitary and for internal combustion engines and compressors.
heating applications. British Standards Institution, 1996. Performance testing. British Standards Institution, 2000.
BS EN 1254-1:1998. Copper and copper alloys. ISO 32:1977. Gas cylinders for medical use. Marking for
Plumbing fittings. Fittings with ends for capillary identification of content. International Organization for
soldering or capillary brazing to copper tubes. British Standardization, 1977.
Standards Institution, 1998.
ISO 5145:2004. Cylinder valve outlets for gases and gas
BS EN 1412:1996. Copper and copper alloys. European mixtures. Selection and dimensioning. International
numbering system. British Standards Institution, 1996. Organization for Standardization, 2004.
BS EN 13348:2001. Copper and copper alloys. ISO 7396-1:2002. Medical gas pipeline systems.
Seamless, round copper tubes for medical gases or Pipelines for compressed medical gases and vacuum.
vacuum. British Standards Institution, 2001. International Organization for Standardization, 2002.
BS EN 60051-1:1999, IEC 60051-1:1997. Direct ISO/DIS 7396-2:2005. Medical gas pipeline systems.
acting indicating analogue electrical measuring Anaesthetic gas scavenging disposal systems. CEN/TC
instruments and their accessories. Definitions and general 215.
requirements common to all parts. British Standards
Institution, 1999. Department of Health publications
BS EN 60529:1992. Specification for degrees of Model Engineering Specification C11 – Medical gases.
protection provided by enclosures (IP code). British HMSO. 1995.
Standards Institution, 1992.
Model Engineering Specification C51 – Electrical
BS EN 60898-1:2003. Circuit-breakers for overcurrent requirements for specified equipment. HMSO, 1997.
protection for household and similar installations.
Circuit-breakers for ac operation. British Standards Firecode
Institution, 2003.
Health Technical Memorandum 81 – Fire precautions
BS EN 60947-2:2003. Specification for low-voltage in new hospitals. HMSO, 1996.
switchgear and controlgear. Circuit-breakers. British
Health Technical Memorandum 82 – Alarm and
Standards Institution, 2002.
detection systems. HMSO, 1996.
BS EN ISO 407:2004. Small medical gas cylinders. Pin-
index yoke-type valve connections. British Standards Health Building Notes (HBNs)
Institution, 2004.
HBN 26 (Volume 1) – Facilities for surgical
BS EN ISO 3549:2002. Zinc dust pigments for paints. procedures. The Stationery Office, 2004.
Specifications and test methods. British Standards
Institution, 2002.

186
References

Health Technical Memoranda (HTMs) Miscellaneous publications


Health Technical Memorandum 2007 – Electrical European Pharmacopoeia (Ph. Eur.) 2005 (5th
services supply and distribution. HMSO, 1993. (issued edition). European Directorate for the Quality of
in four parts) Medicines, 2005.
Health Technical Memorandum 2011 – Emergency http://www.pheur.org
electrical services. HMSO, 1993. (issued in 4 parts) Health & Safety Executive (1996). Anaesthetic agents:
Health Technical Memorandum 2014 – Abatement of controlling exposure under COSHH. HSE Books,
electrical interference. HMSO, 1993. (issued in 4 parts) 1996.

Health Technical Memorandum 2015 – Bedhead Health & Safety Executive (1996). EH40/2002 –
services. HMSO, 1994–95. (issued in 3 parts) Occupational exposure limits 2002. HSE Books, 2002.

Health Technical Memorandum 2022 (Supplement 1) British Compressed Gases Association (BCGA) (2000).
– Dental compressed air and vacuum systems. The Code of Practice 30 (CP30): The safe use of liquid
Stationery Office, 2002 nitrogen dewars up to 50 litres. BCGA, 2000.

Health Technical Memorandum 2025 – Ventilation in British Compressed Gases Association (BCGA) (2002).
healthcare premises. HMSO, 1994. (issued in 4 parts) Code of Practice 19 (CP19): Bulk liquid oxygen
storage at users’ premises. Revision 3. BCGA, 2002.
Other Department of Health publications European Commission. Directive 2001/83/EC of the
Advice on the implementation of the Health & Safety European Parliament and of the Council of 6
Commission’s occupational exposure standards for November 2001 on the Community code relating to
anaesthetic agents. Department of Health, 1996. medicinal products for human use. Official Journal of
the European Communities. 28.11.2001, L 311/67.
http://europa.eu.int/eur-lex/pri/en/oj/dat/2001/l_311/l_
31120011128en00670128.pdf
Medical gas pipe systems. Design and installation of QAS
3720.1/206). BSI/Department of Health, 1988.

187

You might also like