Heating and Ventilation Systems - HTM 03-01
Heating and Ventilation Systems - HTM 03-01
Heating and Ventilation Systems - HTM 03-01
Policy Estates
HR / Workforce Performance
Management IM & T
Planning Finance
Clinical Partnership Working
ii
Preface
About Health Technical Memoranda main source of specific healthcare-related guidance for
estates and facilities professionals.
Engineering Health Technical Memoranda (HTMs)
give comprehensive advice and guidance on the design, The core suite of nine subject areas provides access to
installation and operation of specialised building and guidance which:
engineering technology used in the delivery of healthcare. • is more streamlined and accessible;
The focus of Health Technical Memorandum guidance • encapsulates the latest standards and best practice in
remains on healthcare-specific elements of standards, healthcare engineering;
policies and up-to-date established best practice. They are
applicable to new and existing sites, and are for use at • provides a structured reference for healthcare
various stages during the whole building lifecycle. engineering.
DISPOSAL CONCEPT
RE-USE
DESIGN & IDENTIFY
OPERATIONAL OPERATIONAL
MANAGEMENT REQUIREMENTS
Ongoing SPECIFICATIONS
MAINTENANCE TECHNICAL & OUTPUT
Review
PROCUREMENT
COMMISSIONING
CONSTRUCTION
INSTALLATION
Healthcare providers have a duty of care to ensure that Structure of the Health Technical
appropriate engineering governance arrangements are in Memorandum suite
place and are managed effectively. The Engineering
Health Technical Memorandum series provides best The series of engineering-specific guidance contains a
practice engineering standards and policy to enable suite of nine core subjects:
management of this duty of care. Health Technical Memorandum 00
It is not the intention within this suite of documents to Policies and principles (applicable to all Health
unnecessarily repeat international or European standards, Technical Memoranda in this series)
industry standards or UK Government legislation. Where Health Technical Memorandum 01
appropriate, these will be referenced. Decontamination
Healthcare-specific technical engineering guidance is a Health Technical Memorandum 02
vital tool in the safe and efficient operation of healthcare Medical gases
facilities. Health Technical Memorandum guidance is the
iii
Heating and ventilation systems – HTM 03-01: Specialised ventilation for healthcare premises – Part A
Health Technical Memorandum 03 Electrical Services – Electrical safety guidance for low
Heating and ventilation systems voltage systems
Health Technical Memorandum 04 In a similar way Health Technical Memorandum 07-02
Water systems will simply represent:
Health Technical Memorandum 05 Environment and Sustainability – EnCO2de.
Fire safety
All Health Technical Memoranda are supported by the
Health Technical Memorandum 06 initial document Health Technical Memorandum 00
Electrical services which embraces the management and operational policies
from previous documents and explores risk management
Health Technical Memorandum 07
issues.
Environment and sustainability
Some variation in style and structure is reflected by the
Health Technical Memorandum 08
topic and approach of the different review working
Specialist services
groups.
Some subject areas may be further developed into topics
DH Estates and Facilities Division wishes to acknowledge
shown as -01, -02 etc and further referenced into Parts A,
the contribution made by professional bodies,
B etc.
engineering consultants, healthcare specialists and
Example: Health Technical Memorandum 06-02 Part A NHS staff who have contributed to the review.
will represent:
S T R Y S TA N D A
DU RD
IN S
& EUROPEAN
NAL ST
HTM 07
IO HTM 02
T
AN
NA
INTER
CUMENTS
Sustainability Gases
RDS
HTM 00
RDS
INTER
Policies and
Principles
DA
NA
AN
IO
ST
T
NA
DO
IC
Y S TA N D Systems
IF
C
EC
D
HTM 05 HTM 04
O
Fire
SP
U Water
C
M Safety Systems H
EN T
TS AL
HE
iv
Executive summary
v
Heating and ventilation systems – HTM 03-01: Specialised ventilation for healthcare premises – Part A
Acknowledgements
vi
Contents
Preface
Executive summary
Acknowledgements
Chapter 1 Introduction 1
Preamble
Ventilation in healthcare premises
Reasons for ventilation
Ventilation – application examples
Statutory requirements
Health and Safety at Work etc Act 1974
COSHH
Fire regulations
Plants installed in units manufacturing medicinal products
Plants installed in laboratories
Codes of practice and other guidance
Design and validation process
Ventilation – terms in use
Ventilation
Air-conditioning
Specialised ventilation
Local exhaust ventilation
Chapter 2 Provision of ventilation in healthcare buildings 8
Natural ventilation
Extract ventilation systems
Supply-only ventilation
Supply and extract ventilation
Comfort cooling
Air-conditioning
Specialised ventilation
Local exhaust ventilation
Ventilation for general areas
Acceptable methods
Use of natural ventilation
Mixed mode ventilation
Mechanical extract ventilation
Mechanical supply systems
Balanced ventilation
Cascade ventilation
Recirculation systems
Chilled beams
Split comfort air-conditioners
Dilution ventilation and clean air-flow paths
Mechanical ventilation systems
System selection
vii
Heating and ventilation systems – HTM 03-01: Specialised ventilation for healthcare premises – Part A
viii
Contents
Design need
General requirements
Acceptable types
Selection
Location
Control
Filtration
General requirements
Definition of filter terms
Selection
Location
Control
Energy recovery
General requirements
Location
Control
Attenuation
General requirements
Acceptable types and location
Chapter 5 Air distribution system 31
Air distribution arrangements
Ductwork distribution systems
Ductwork materials and construction
Fire aspects, damper types and locations
Duct sections
Standard ductwork fittings
Thermal insulation
Noise generation within the ductwork
Volume control damper locations
Cleaning and access door locations
Flexible ducting
Diffuser and grille selection and sizing
Transfer grille – size and location
Pressure stabilisers – size and location
Chapter 6 Automatic controls 37
General requirements
Objectives of the control system
Location of controls
Fire aspects
Time switching
Start-up control
Set-back control
Use control
Environmental control
Temperature control methods and application
Humidity control methods and application
Multi-zone control methods and application.
Alarms and indication
Chapter 7 Specialised ventilation systems 45
General information
Air-movement control
Temperature and humidity control
Removal and dilution of waste anaesthetic gases
ix
Heating and ventilation systems – HTM 03-01: Specialised ventilation for healthcare premises – Part A
Fire aspects
Door protection
Systems design
Operating department ventilation systems
General
Fire aspects
Door protection
Standard air-movement control schemes
Air terminals and air distribution within rooms
Automatic control
Ventilation of operating department ancillary areas
Reception
Sterile pack bulk store
Recovery
Ultra-clean ventilation systems
General requirements
Types of UCV system
Filters
Noise level
Lighting and operating lights
Controls and instrumentation
Extract systems
Hood extract systems
Bench extract systems
Safety cabinet and fume-cupboard extract systems
Plantroom ventilation
General requirements
Assessment of ventilation levels
Choice of ventilation system
Ventilation of hydrotherapy suites
General requirements
Control of hydrotherapy pool installations
Chapter 8 Validation of specialised ventilation systems 66
Definitions
Commissioning
Location of dampers and test holes
Commissioning personnel
Commissioning brief
Pre-commissioning checks
Standard of installation
Cleanliness of installation
Certification of equipment
Equipment tests
Dynamic commissioning
Air-handling and distribution system
Room-air distribution
Air-conditioning plant
Control system
Specific performance standards
Air movement
Plant capacity and control
Noise levels – general
Filter challenge
x
Contents
Bacteriological sampling
Ventilation system commissioning/validation report
Validation of UCV operating suites
General
Basic requirement
UCV unit validation procedure
Test and measuring conditions
Test and measuring equipment
Test grid – vertical units
Test grid – horizontal units
UCV terminal challenge tests (vertical and horizontal systems)
Vertical UCV terminal air velocity tests
Horizontal UCV terminal air velocity test
UCV entrainment test (vertical systems only)
UCV visualisation
UCV noise level
UCV control system checks
UCV theatre microbiological tests
UCV validation report
General
Air intake
Damper
Ducting
Fan
Attenuator/silencer
Filter
Appendix 1 Use and function of typical equipment used in ventilation systems 81
Heater coil/battery
Humidifier
Chiller battery/cooling coil
Eliminator
Drainage system
Access doors and observation ports
Energy recovery
Typical plant
Appendix 2 Recommended air-change rates 83
Appendix 3 Hierarchy of cleanliness 84
Appendix 4 Leakage flows in m3/s through closed door gaps 85
Appendix 5 Recommended air-flow rates in m3/s through a doorway between rooms of different
cleanliness to control cross-contamination 86
Appendix 6 Typical approximate pressures in an operating suite when a given door is open 87
Appendix 7 Operating suites standard design solutions 88
Appendix 8 Design of air-movement control schemes for operating theatres 97
General
Peripheral room type
Single flow
Parallel multi-flow
Parallel/series multi-flow
Series multi-flow (unbalanced)
Series multi-flow (balanced)
Bay
Air-movement control in peripheral rooms
Single flow rooms
xi
Heating and ventilation systems – HTM 03-01: Specialised ventilation for healthcare premises – Part A
xii
1 Introduction
1
Heating and ventilation systems – HTM 03-01: Specialised ventilation for healthcare premises – Part A
2
1 Introduction
commissioned, operated and maintained. The local Commission’s Health Services Advisory Committee
exhaust ventilation (LEV) section of COSHH in:
requires that the plant be inspected and tested at
• ‘Safe working and the prevention of infection in
least every 14 months by a competent person and
clinical laboratories and similar facilities’;
that management maintain comprehensive records
of its performance, repair and maintenance. • ‘The management, design and operation of
microbiological containment laboratories’.
1.12 Certain substances have workplace exposure limits
(WELs) set out in the Health and Safety Executive’s
(2005) Guidance Note EH40 – ‘Workplace
Note
exposure limits: containing the list of workplace If the ventilation plant has been installed to dilute or
exposure limits for use with the Control of contain harmful substances (the definition of which
Substances Hazardous to Health Regulations 2002 now includes microorganisms), its failure may expose
(as amended)’. If specialised ventilation systems are people to unacceptable levels of hazard. Proven failures
provided in order to achieve these standards, they can give rise to a civil suit against the designers and
will be subject to the COSHH Regulations as operators by the individuals who have been affected.
above. This would be in addition to the actions brought as a
result of breaching the statutory requirements.
Fire regulations
1.13 The fire regulations require that, if ventilation Codes of practice and other guidance
ductwork penetrates the compartment or
subcompartment of a building, it should be 1.17 All ventilation systems should conform to
designed and installed so as to contain the spread of the principles set out in the Health and Safety
fire (see Health Technical Memorandum 05-02 – Commission’s Approved Code of Practice and
‘Guidance in support of functional provisions for guidance document ‘Legionnaires’ disease: the
healthcare premises’ for further guidance). control of Legionella bacteria in water systems’
(commonly known as L8), and Health Technical
Plants installed in units manufacturing medicinal Memorandum 04-01 – ‘The control of Legionella,
products hygiene, “safe” hot water, cold water and drinking
water systems’.
1.14 Plants installed in units manufacturing medicinal
products to the standards set out in the current 1.18 The Department of Health publication
European guide to good manufacturing practice ‘The Health Act 2006: code of practice for the
(http://ec.europa.eu/enterprise/pharmaceuticals/ prevention and control of healthcare associated
eudralex/homev4.htm) may also be subject to infections’ is a code of practice that has been
particular legislation with regard to their operation brought out to help NHS bodies to plan and
in addition to that mentioned above. implement how they can prevent and control
healthcare-associated infections. It sets out criteria
1.15 Records should be kept of equipment design and by which managers of NHS organisations are
commissioning information. The Health and Safety to ensure that patients are cared for in a clean
Executive, Medicines Inspectorate and other environment and where the risk of healthcare-
interested bodies have a statutory right to inspect associated infections is kept as low as possible.
them at any time. All records should be kept for at Specialised ventilation systems often play a central
least five years. role in achieving this objective.
Plants installed in laboratories This document deals with the healthcare-specific
1.16 Specialised ventilation plants installed in aspects of ventilation. Basic information on the design,
laboratories dealing with research, development installation, commissioning and testing of ventilation
or testing, whether involving drugs, animals or systems is contained in documents produced by the
genetically modified organisms, may be subject to following (see the References section):
particular legislation with regard to their operation • the Chartered Institute of Building Services
in addition to that mentioned above. Further Engineers (CIBSE);
information is given by the Health & Safety
3
Heating and ventilation systems – HTM 03-01: Specialised ventilation for healthcare premises – Part A
• International and British Standards (ISO and Design and validation process
BS EN); 1.19 It is essential, when undertaking the design of a
• the Building Services Research and Information specialised ventilation system, that the project be
Association (BSRIA); considered as a whole. The process model set out in
Table 1 should ensure that all relevant factors are
• trade associations such as the Heating and considered.
Ventilating Contractors’ Association (HVCA).
4
1 Introduction
1.23 Ventilating equipment may be required in order to h. specialised imaging, X-ray and scanning unit;
remove smells, dilute contaminants and ensure that j. pathology containment laboratories;
a supply of fresh air enters a space.
k. mortuary and dissection suite;
Air-conditioning m. research laboratories;
1.24 Air-conditioning is the ability to heat, cool, n. sterile services department;
dehumidify and filter air. For full air-conditioning,
p. emerging treatment technologies, including
humidification may also be provided. This means
gene therapy and stem cell units.
that the climate within a space being supplied by
an air-conditioning plant can be maintained at a 1.27 Ventilation may be provided in a wide variety of
specific level regardless of changes in outside air ways. These will include:
conditions or the activities within the space. Air-
• extensive purpose-built air-handling units
conditioning equipment may be required in order
housed in their own plantrooms;
to provide close control of “comfort conditions”
within a space. • proprietary “packaged” systems often sited
outside on a roof; or
Specialised ventilation
• wall-mounted electric fans located at the point
1.25 In healthcare premises, certain activities will of use.
necessitate the provision of ventilation equipment
1.28 A fixed volume of air may be supplied, often
with additional special features in order to achieve
expressed in terms of the resulting number of air
and maintain specific conditions. These may be
changes per hour (ac/h), within the space being
needed in order to assist with the treatment of
ventilated. Alternatively the volume of air supplied
patients or maintain the health and safety of staff.
may be varied in order to maintain a specific
The precise reason for providing specialised
pressure relationship between the area supplied
ventilation will depend upon the intended
and other surrounding areas. In some situations
application. The list below indicates some of the
a combination of both methods may be adopted.
more typical reasons:
1.29 Modern plants should be fitted with the means to
a. to remove, contain or dilute specific
recover energy from the extract air without causing
contaminants and fumes;
contamination of the incoming supply air.
b. to ensure the isolation of one space from
1.30 Ultra-clean systems use the same basic plant and
another;
equipment as standard air-conditioning systems,
c. to preserve a desired air-flow path from a clean but are in addition fitted with a terminal device
to a less clean area; that supplies the air in a unidirectional manner to
the working area. Their standard of filtration will
d. to provide control of the cleanliness of a space;
5
Heating and ventilation systems – HTM 03-01: Specialised ventilation for healthcare premises – Part A
be capable of delivering air with a very low particle 1.34 In laboratories, pharmaceutical manufacturing
count to the space that they serve. facilities and operating suites, LEV systems usually
take the form of semi-open-fronted cabinets within
Local exhaust ventilation which the hazardous substance is manipulated.
These cabinets either have their own filtered air
1.31 Local exhaust ventilation (LEV) is a term used to
supply or are fed with air from the room. The
describe systems installed to prevent hazardous
air extracted from the cabinet is passed through
substances from entering the general atmosphere
a high-efficiency filter before being discharged
of the room in which they are being used. Their
either to the atmosphere or back into the room.
primary function is to protect staff from the effects
Microbiological safety cabinets, laboratory fume
of their work activity.
cupboards, cytotoxic drug cabinets and fixed or
1.32 Simple LEV systems comprise a receptor or capture mobile disinfection enclosures are all examples of
hood, extract ductwork and a fan. These are used to this type of facility.
contain industrial types of hazard such as fumes
1.35 Mortuaries and dissection suites may have LEV
from welding processes, gas discharges from
systems incorporated within the dissection table,
standby battery banks and dust from woodworking
specimen bench and bone saw.
machinery.
1.36 The layout of a typical plant that conforms to the
1.33 The vapour given off when large quantities of
regulations for healthcare applications is shown in
chemicals are decanted into ready-use containers
Figure 1. For an explanation of the equipment used
and fumes from X-ray film processing units are
in the diagram, see Appendix 1.
examples of chemical hazards often controlled by
LEV systems.
6
Figure 1 Example of a typical operating theatre ventilation system
Energy
Primary recovery Chiller & Heater
MD filter device eliminator battery VC D
Intake
Attenuator Attenuator
Fog Supply fan & Secondary
coil blast plate filter
Drainage
FD
system
Trimmer
battery
Pressure
Operating room Anaesthetic room stabiliser
Lay up
prep room
Corridor
Extract Extract
1 Introduction
7
Heating and ventilation systems – HTM 03-01: Specialised ventilation for healthcare premises – Part A
2 P
rovision of ventilation in healthcare
buildings
2.1 Planning constraints caused by a building’s shape (of a design that facilitates natural ventilation)
and/or the functional relationships of specific areas should be provided.
will invariably result in some measure of deep
planning, thus reducing the opportunity for natural Note
ventilation.
If natural ventilation is “single-sided”, it will usually
2.2 However, ventilation costs can be minimised by only be effective for a three-metre depth within the
ensuring that, where practicable, core areas are space. Beyond that it will need to be supplemented by
reserved for those rooms that need to have mixed-mode or forced ventilation.
mechanical ventilation. Examples are:
• sanitary facilities, dirty utilities and those rooms 2.7 Current guidance restricts the opening of windows
where clinical or functional requirements have for safety reasons; also, as many designs are top-
specific environmental needs; and hung, their ability to permit natural ventilation is
limited. It may therefore be necessary to provide
• those rooms where – for reasons of privacy, dedicated ventilation openings in the fabric of the
absence of solar gain etc – windowless building to allow a sufficient natural flow of air
accommodation is acceptable. into and out of the space.
2.3 Other spaces appropriate to core areas are those 2.8 In all cases, excessive heat gain, indoor air-quality
which have only transient occupation and therefore requirements or external noise may limit or
require little or no mechanical ventilation (for preclude the use of natural ventilation.
example circulation and storage areas).
2.9 Detailed guidance on natural ventilation can be
found in CIBSE’s (2005) Applications Manual
Natural ventilation AM10 – ‘Natural ventilation in non-domestic
2.4 Natural ventilation is usually created by the effects buildings’.
of wind pressure. It will also occur if there is a
temperature difference between the inside and the Extract ventilation systems
outside of a building. The “thermo-convective”
effect frequently predominates when the wind 2.10 Extract ventilation is required in sanitary facilities,
speed is low, and will be enhanced if there is a dirty utilities and rooms where odorous but
difference in height between inlet and outlet non-toxic fumes are likely; this is to ensure air
openings. movement into the space. A single fan/motor unit
should be provided to meet this need. There is no
2.5 Ventilation induced by wind pressures can induce healthcare requirement to provide a separate foul/
high air-change rates through a building, provided dirty extract system.
air is allowed to move freely within the space from
the windward to the leeward side. However, in 2.11 WCs should have an extract rate as set out
most healthcare applications, internal subdivisions in Approved Document F of the Building
will restrict or prevent this effect. Regulations. Where WCs are located in shower and
bathroom spaces, the ventilation required for the
2.6 It is almost impossible to maintain consistent flow WC will normally be adequate for the whole space.
rates and ensure that minimum ventilation rates
will be achieved at all times. However, this Supply-only ventilation
variability is normally acceptable in such areas as
office accommodation, staff areas, library/seminar 2.12 Mechanical supply ventilation is required in areas
rooms and dining rooms, where opening windows where it is important to maintain a positive
8
2 Provision of ventilation in healthcare buildings
9
Heating and ventilation systems – HTM 03-01: Specialised ventilation for healthcare premises – Part A
that reasonably clear air paths are maintained. 2.34 Information on specialised extract systems is given
Beyond this distance – in areas where clear air paths in Chapter 7.
cannot be maintained and in areas where high
minimum air-change rates are specified – Mechanical supply systems
mechanical ventilation should be provided. 2.35 Where mechanical supply systems are required,
2.27 Further information can be found in Health the fresh air should be tempered and filtered before
Technical Memorandum 55 – ‘Windows’, BS 5925 being delivered to the space in order to avoid
and CIBSE’s (2005) Applications Manual AM10 – discomfort.
‘Natural ventilation in non-domestic buildings’. 2.36 The air should be heated using a constant or
variable temperature source, but generally only to
Mixed mode ventilation
the space air temperature. In most instances, the
2.28 Mixed mode ventilation is an assisted form of low pressure hot water (LPHW) heating system
natural ventilation. Fans are fitted in purpose- should offset any fabric loss so that set-back room
made damper-controlled ventilation openings. temperatures can be maintained during unoccupied
Alternatively, a separate draw- or blow-through periods without the need for the ventilation system
ventilation unit may be installed. In both cases the to operate.
dampers and fans are controlled by temperature
and occupancy sensors to ensure a minimum Balanced ventilation
air-flow rate while taking advantage of natural 2.37 A balanced ventilation system is a combination
ventilation effects when present. of both a supply and an extract system of equal
2.29 Where natural or mixed mode ventilation is volume; either a single space or a whole building
adopted with complex air paths, the designer may be considered to be balanced.
should produce an air-flow diagram in order to 2.38 A balanced system is necessary in instances where
ensure correct provision of air-transfer devices. it is essential to maintain consistent air movement
CIBSE’s (2000) Applications Manual AM13 – within an area (for example treatment rooms).
‘Mixed mode ventilation’ gives guidance.
Cascade ventilation
Mechanical extract ventilation
2.39 In operating departments, it is normal practice to
2.30 General extract systems can vary in complexity
supply air to the operating room and allow it to
from a single wall-mounted fan to a ducted air flow through less clean areas – corridors, utility
system with dual extract fans. rooms etc (from where it is eventually extracted).
2.31 Replacement air either is provided by a central
supply system or enters the building through gaps Recirculation systems
in the structure or purpose-made openings. Unless 2.40 Air recirculation systems are normally used in
special precautions are taken, the latter may result HEPA-filtered clean rooms where the extract air is
in an unacceptable level of draughts occurring in significantly cleaner than the outside supply and
winter, and possible risk of unacceptable levels of where odour levels are not significant.
noise transmission.
2.41 Recirculation is also routinely used in the canopy
2.32 If individual systems are used, the ventilation can section of ultra-clean operating theatre ventilation
be operated intermittently, provided it continues to systems.
run for at least 15 minutes after the room is vacated
(as with light-switch-operated fans in individual 2.42 Where the designer is considering the installation
toilets). of an air recirculation system, due account must be
taken of:
2.33 If general exhaust systems are used, filtered and
tempered replacement air should be provided via a. minimum fresh-air-supply volume required
a central supply plant to adjoining lobbies or by the Building Regulations Part F – Non-
corridors, to prevent the risk of discomfort caused domestic Buildings;
by the ingress of cold air. Fire compartmentation b. prevention of contamination of supply air from
requirements must be maintained. vitiated air in extract systems;
10
2 Provision of ventilation in healthcare buildings
c. prevention of stratification occurring within 2.50 Whether single or multiple systems are used, it is
plenum chambers and mixing boxes, which essential that the designer give due consideration to
may result in freezing of downstream coils; the source of electrical supply, location of the heat
rejection unit, environmental effects to the
d. ensuring sufficient velocities through control
refrigerant used and drainage provision for the
dampers (ideally 5–6 m/s) to provide suitable
cooling-coil condensate.
authority and good shut-off;
2.51 Recirculated room air affects indoor air quality
e. modulating control of mixing to provide
and may increase the risk of healthcare-associated
optimum on-plant conditions;
infection (HCAI). Split units should therefore not
f. use of “free cooling” by cycling the dampers to be used in critical care areas.
minimum fresh air when the enthalpy of the
2.52 The units should be easily accessible for cleaning
outside air is greater than that of the extract air
and maintenance.
under conditions when cooling is required.
Dilution ventilation and clean air-flow paths
Chilled beams
2.53 Dilution ventilation has been used to control levels
2.43 The use of chilled beams for the provision of
of hazardous substances in a space. This approach
heating, cooling and ventilation is increasingly
in itself is no longer considered acceptable.
common in healthcare premises.
COSHH requires that known hazardous substances
2.44 Active chilled beams providing tempered, filtered should be substituted for safe alternatives. If this is
air to the room can provide effective local control not possible, they should be controlled at source by
of environmental conditions. using a closed system (such as an anaesthetic gas
2.45 Care should be taken in positioning chilled scavenging unit) or a protective enclosure (such
beams to ensure that cold draughts are avoided, as a fume cupboard). A good level of background
particularly when used in the cooling mode. The ventilation will assist in diluting any casual release
control settings should ensure that the external of the substance.
elements of the beam are always above dew-point. 2.54 The exposure of staff to casual spillages of
Manufacturers of these devices are able to provide substances such as medical gases in anaesthetic
specific advice on the siting and design limits of rooms should in the first instance be dealt with by
their equipment. establishing a clean air-flow path. Air should be
2.46 Chilled beam units should be easily accessible for supplied at high level and extracted at low level
cleaning and maintenance. directly behind the anaesthetic equipment position.
The philosophy of establishing a clean air-flow path
Split comfort air-conditioners – from the air-supply point, to the staff, on to the
patient, and out via a low-level extract – would also
2.47 Split comfort air-conditioners, room conditioners apply in recovery rooms and birthing rooms. A
or cassette units are used increasingly where suitable air-change rate will provide background
there is a small local requirement for cooling for dilution ventilation as an additional safeguard. This
operational purposes. They can provide an effective approach ensures that “all reasonable steps are taken
economic solution to cooling needs where a central to prevent or control exposure (of staff ) to the
refrigeration system is not practicable. hazardous substance” as required by COSHH.
2.48 A fresh-air make-up system to the standard 2.55 In operating theatres, patients will be on a closed
required by the Building Regulations Part F – breathing circuit in a room with a high air-change
Non-domestic Buildings must be provided. rate. Under these circumstances, the dilution effect
2.49 Split units may be used for single applications or would be considered sufficient to control any casual
as multiple linked units that can independently exposure to anaesthetic gases.
provide either heating or cooling – all served by a
single outdoor unit. These systems help to maintain
a more precise temperature control across multiple
rooms, with maximum energy efficiency.
11
Heating and ventilation systems – HTM 03-01: Specialised ventilation for healthcare premises – Part A
12
3 Assessment of service requirement
Selection of design criteria room air, rather than the actual temperature of the
supply air, which is the critical factor. The
External design conditions maximum recommended supply-to-room-air
temperature differential is:
3.1 The most accurate data that is available for the
summer and winter conditions at the site should be • summer cooling: –7 K
used. The Met Office can supply data for the • winter heating: +10 K.
United Kingdom (www.metoffice.gov.uk).
3.10 In areas that have high heat gains from equipment
3.2 Healthcare ventilation systems will normally be (for example critical care areas), the summer
“full fresh air”. cooling temperature differential limit given
3.3 Local adjustments, such as for height above sea above may result in excessive air-change rates.
level, exposure factor or other climate peculiarities, A differential of up to –10 K is acceptable in these
should be made as appropriate. circumstances, providing the supply-air diffusers
are of a type that provide good mixing.
Internal design conditions 3.11 If a humidifier is fitted, it is necessary to keep
3.4 The design conditions selected within patient supply-air humidity below 70% during winter in
areas must strike a balance between the comfort order to minimise the risk of condensation on cold
requirements of staff and patients, who often have surfaces.
very different levels of clothing and activity.
Air purity
3.5 Recommendations for the dry resultant
temperature and humidity of individual spaces are 3.12 In healthcare premises, the standard of filtration
shown on Activity DataBase A-sheets. Appendix 2 will depend on the activities within the occupied
gives a summary. spaces. With the exception of specialist areas (for
example manufacturing pharmacies), aerobiological
Minimum fresh-air requirements requirements are not stringent, and filtration is
only required to:
3.6 The dilution of body odours is the critical factor
in determining ventilation requirements. Where a. maintain hygienic conditions for the health and
natural ventilation or full fresh-air systems are used, welfare of occupants, or for processes such as
all ventilation air will be fresh. food preparation;
3.7 Where odour dilution is the overriding factor, it is b. protect finishes, fabrics and furnishings in order
recommended that 10 litres per second per person to reduce redecoration costs;
should be taken as the minimum ventilation rate. c. protect equipment either within the supply air
3.8 In non-standard applications such as laboratories, system (that is, to prevent blocking of coils), or
aseptic suites, operating departments etc, the in the space itself to prevent dust build-up.
particular requirements for each area should be 3.13 Given that almost all viable particles originate
considered independently in order to determine the from the occupants of a space and not from the
overriding minimum requirement for ventilation. incoming air, dilution is the more important factor
aerobiologically. Therefore, for general areas a G4
Limiting supply air conditions
filter is suitable. More critical areas will require an
3.9 For most applications in healthcare buildings, it is F7 filter. High-efficiency particulate air (HEPA)
the temperature differential between the supply and
13
Heating and ventilation systems – HTM 03-01: Specialised ventilation for healthcare premises – Part A
filters are required only in ultra-clean systems calculation of air infiltration. Pressure testing
(information on filter grades is given in Chapter 4). enables the true infiltration rate to be established.
In all cases the requirements of the appropriate
Humidity control requirements section of the Building Regulations Part L2 must
3.14 Providing humidification is expensive in terms be met.
of plant, running costs and maintenance, and
Summertime temperatures
therefore its use should be restricted to where it is
necessary for physiological or operational reasons. 3.23 The calculation method for determining the
summertime temperature is described in CIBSE’s
3.15 Humidification was originally required for some
Guide A. It is very important to select the time
healthcare applications (for example operating
of day and time of year of peak loadings for the
theatres) in order to control the risk associated with
calculations. These will be dependent on the
the use of flammable anaesthetic gases. The use
building orientation and proportion of solar to
of such gases has now ceased. Humidification is
total heat gain. In establishing design values, the
therefore no longer required unless there is a very
design risk – having regard to the function and
specific application requirement.
occupancy of the building – should be considered.
Noise levels 3.24 Calculations and thermal modelling should
3.16 Noise will be generated by fans, ductwork fittings, be undertaken to see whether, during the
dampers and grilles. The specified maximum noise summertime, internal temperatures in patient areas
level will depend on the activities within the will exceed 28oC dry bulb for more than 50 hours
occupied spaces. per year. It can generally be assumed that for a
naturally ventilated building, the internal
3.17 Attention must be given to the reduction of tonal temperature will be approximately 3 K above
components. High tonal components from air the external shade temperature. For a building
diffusers etc can seriously disturb concentration with simple mechanical ventilation, the internal
over longer periods even when the overall noise temperature can never be less than the external
level is low. Broadband noise causes less annoyance. shade temperature and will invariably be higher.
3.18 Attenuation should be incorporated into the The relationship between preferred indoor
ductwork system or plant arrangement as necessary temperatures and mean outside temperature is
to reduce noise from fans and plant items in order discussed in CIBSE’s Guide A.
to achieve acceptable limits within rooms at the 3.25 Where calculations indicate that internal
design air flows. temperatures will exceed the selected design for
3.19 The designer must also consider noise escaping to a period that exceeds the building design risk,
the external environment, and this must not be methods of reducing temperature rise should be
unacceptable to occupants of adjacent areas or implemented. Options include:
buildings. • reducing solar and casual gains;
3.20 The overall noise levels should not exceed the • the use of chilled beams or ceilings;
values given in Health Technical Memorandum
08-01 – ‘Acoustics’. • increasing ventilation rates; or
14
3 Assessment of service requirement
3.28 Where ventilation systems provide tempered air to 3.35 Once the lowest required supply temperature of the
spaces that have supplementary LPHW to offset air-handling unit (AHU) has been established, and
the building fabric losses, the plant’s heating load an allowance made for temperature rise through the
should be based on the design values of the external fan and ductwork (usually 1 K for low-pressure
winter temperature and internal air temperature, systems), the off-plant enthalpy can be established
and the calculated total air volume (including a from a psychrometric chart or table.
suitable allowance for leakage).
3.36 The cooling loads for all plants on the chilled
3.29 Where the ventilation system is the only means of water system should be calculated at each of
heating a space, an increase in load equivalent to the individual peak times in order to accurately
the calculated fabric heat losses from the space establish the required (diversified) capacity of the
should be added to the ventilation load. A check of chiller.
supply temperature difference should be made. If it
exceeds 10 K, the ventilation supply volume should Annual energy consumption
be increased to suit. 3.37 Annual energy consumptions of heating-only
ventilation systems are simple to calculate, based
Condensation risk
on supply-to-external air temperature rise, and
3.30 A check should be made to ensure that the selected frequency of occurrence of external temperature
air condition will not lead to surface condensation data (see CIBSE’s Guide A).
on low-temperature elements of the ventilated
3.38 Minimum air volumes are usually fixed by the
space.
room loads or fresh-air requirements; however, the
3.31 Where there are local sources of moisture that designer may increase air flow to some rooms or
would require excessive levels of ventilation to zones in order to balance loads (as detailed in
avoid condensation, the designer should consider paragraphs 3.42–3.71).
the capture and removal of moisture at the source
3.39 The method of zoning and control can significantly
of the evaporation via an exhaust hood or similar
influence energy consumption.
device.
3.40 The concept of load and plant operation charts
3.32 In intermittently heated buildings, it is necessary to
is outlined in CIBSE’s Guide A. The method
consider the condensation risk at night set-back
requires the designer to establish the minimum and
conditions as well as during normal operation.
maximum loads on all zones across the range of
Calculation methods for this assessment are given
external temperatures between winter and summer
in CIBSE’s Guide A.
design conditions. Once the load chart is complete,
the plant chart converts the loads to supply
Peak cooling load
temperatures, which are then superimposed on
3.33 In addition to the base data of air-flow rates and external air temperatures.
temperatures, when calculating cooling loads, the
3.41 When all temperatures for all zones are plotted
designer must take into account:
on the plant operation chart, set-points and
a. solar cooling loads; resetting schedules can be established. From this
b. surface conduction cooling loads; information, the outputs of individual heaters,
coolers and humidifiers can be established at any
c. internal gain cooling loads; given external temperature. When those loads are
d. cooling loads due to high-level humidity computed against annual frequency of occurrence
control; of external temperatures (as given in CIBSE’s
Guide A), the annual energy consumption of
e. method of control of internal conditions; individual elements, and thus the air-conditioning
f. fluctuations in internal temperatures. system, can be established.
3.34 When the peak internal loads have been assessed
and a suitable allowance made for non-coincidence,
the supply temperature can be calculated.
15
Heating and ventilation systems – HTM 03-01: Specialised ventilation for healthcare premises – Part A
16
3 Assessment of service requirement
plant, a multi-stage direct expansion cooling separation of 4 m between them, with the discharge
coil with refrigerant piped from an adjacent mounted at a higher level than the intake.
compressor/condensing plant could be considered.
3.63 Discharges from LEV systems should preferably be
If this option is selected, a refrigerant gas detector
vertical and usually not less than 3 m above roof
mounted in the base of the duct and an alarm
level. They should not be fitted with a cowl that
system audible to the end-user will also need to be
could cause the discharge to be deflected
provided (as dictated by the COSHH Regulations).
downwards.
3.55 Clean, dry steam is preferred for humidification,
3.64 Each intake and discharge point should be fitted
provided that the boiler water treatment does
with corrosion-resistant weatherproof louvres or
not render the steam unusable for direct
cowls to protect the system from driving rain
humidification.
(BS EN 13030, Class B).
3.56 If a suitable supply of steam cannot be obtained
3.65 It is recommended that louvres be sized based on a
from the steam main, a steam generator should
maximum face velocity of 2 m/s in order to prevent
be provided locally, or a self-generating humidifier
excessive noise generation and pressure loss.
installed. The location of a local steam generator is
critical if condensate is to drain back into it. 3.66 The inside of the louvres should be fitted with a
mesh of not less than 6 mm and not more than
Inlet and discharge sizing and location 12 mm to prevent leaves being drawn in and
infestation by vermin.
3.57 Air intakes and discharge points should preferably
be located at high level, to minimise the risks of 3.67 The duct behind a louvre should be self-draining.
noise nuisance to surrounding buildings, If this is not practicable, it should be tanked and
contamination and vandalism. provided with a drainage system.
3.58 Intakes and discharges should be designed and 3.68 Cleaning access must be provided either from the
located so that wind speed and direction have a outside via hinged louvres or by access doors in
minimal effect on the plant throughput. the plenum behind the louvre. Where a common
plenum is provided, cleaning access should be via a
3.59 Helicopter landing pads in the vicinity of
walk-in door.
ventilation intakes and discharges can result in
large short-term pressure changes. This can cause
Heat-rejection devices
pressure surges in supply systems and reverse air
flows in extracts. Exhaust fumes from the helicopter 3.69 The design conditions given in Chapter 2 make no
may also be drawn into intakes. allowance for the elevated temperatures that can
occur on the roof of buildings. Refrigeration
3.60 Intake points should be situated away from cooling
condensers and cooling towers should, if
towers, boiler flues, vents from oil storage tanks,
practicable, be shaded from direct solar radiation,
fume cupboards and other discharges of
or the design should be adjusted to take account of
contaminated air, vapours and gases, and places
the gain.
where vehicle exhaust gases may be drawn in.
3.70 Air-cooled condensers should be the first choice for
3.61 Where intakes have necessarily to be sited at or
heat rejection from any refrigeration plant.
near ground level, the area around them should be
paved or concreted to prevent soil or vegetation 3.71 Evaporative cooling systems should not be used
being drawn in. They should also be caged or in healthcare premises unless limitations of space
located within a compound to prevent rubbish mean that they are the only way that the cooling
being left in the vicinity. The likely proximity of load can be met. If they are used, guidance on
vehicle exhausts should be taken into account when preventing and controlling legionellae must be
determining the protected area around the intake. closely followed (see Health Technical
Memorandum 04-01 – ‘The control of Legionella,
3.62 The discharge from a general extract system must
hygiene, “safe” hot water, cold water and drinking
be located so that vitiated air cannot be drawn back
water systems’; and the Health and Safety
into the supply-air intake or any other fresh-air
Commission’s Approved Code of Practice and
inlet. Ideally, the extract discharge will be located
guidance document ‘Legionnaires’ disease: the
on a different face of the building from the supply
control of Legionella bacteria in water systems’
intake(s). In any event, there must be a minimum
(commonly known as L8)).
17
Heating and ventilation systems – HTM 03-01: Specialised ventilation for healthcare premises – Part A
4 A
ir-handling unit design and specification
guidance
18
4 Air-handling unit design and specification guidance
4.13 Plants should have a high standard of airtightness. style movable steps. The installation of distribution
The double-skin method of construction with ductwork and other electrical or mechanical
insulation sandwiched between two metal faces is services should provide sufficient clearance to allow
recommended. The panels may be available in a the pulpit steps to be easily wheeled into position.
variety of colours at no additional cost. This can
aid identification by colour-coding of units in AHU drainage system
a plantroom (for example green for general 4.21 All items of plant that could produce moisture
ventilation; blue for theatres; red for laboratories must be provided with a drainage system. The
and isolation facilities; grey for extract etc). system will comprise a drainage tray, glass trap,
4.14 The inside of the plant should be as smooth as air break and associated drainage pipework.
possible. Channels, rolled angles or formed sections 4.22 The drainage tray should be constructed of a
that could trap or hold moisture should be kept to corrosion-resistant material – stainless steel is
a minimum. If stiffeners are required, they should preferred – and be so arranged that it will
be fitted externally. If internal bracing has to be completely drain. To prevent “pooling”, it is
fitted, it must be of a design that will not trap or essential that the drain connection should not have
hold moisture. an up-stand and that a slope of approximately 1 in
4.15 Air flow across air treatment components such 20 in all directions should be incorporated to the
as filters, heat exchangers and humidifiers will be drain outlet position. The tray must be completely
influenced by the pattern of the approaching air accessible or, for smaller units, easily removable for
stream. If unsatisfactory conditions are created, the inspection and cleaning.
performance of the component will be reduced.
4.16 Access to items that require routine service such as
filters, fog coils and chiller batteries should be via
hinged doors. The doors should be large enough
(for example 500 mm minimum) to allow easy
access. Items requiring infrequent access, such as
attenuators, may be via bolted-on, lift-off panels.
All doors and panels should be close-fitting and
without leaks.
4.17 Care should be taken during installation to ensure
that electrical and mechanical services are not
installed in positions that will reduce or impede
access.
4.18 It can be difficult to turn off AHUs in order to
inspect filters and drainage trays. Viewing ports and
internal illumination will therefore facilitate routine
patrol inspection of such items. Viewing ports
should be at a convenient height. In double-stacked
units, placing the viewing ports at the bottom of
Removable drainage tray
the access doors of the upper unit will remove the
need to use temporary ladders or steps when
carrying out patrol inspections. 4.23 Each drainage tray should be provided with its own
drain trap. The drain trap should be of the clear
4.19 Internal illumination should be provided by
(borosilicate) glass type. This permits the colour of
fittings to at least IP55 rating. Fittings should be
the water seal to be observed, thus giving an early
positioned so that they provide both illumination
indication of corrosion, biological activity or
for inspection and task lighting. All lights in a unit
contamination within the duct. The trap should
should be operated by a single switch.
have a means for filling and incorporate couplings
4.20 Access to AHUs and items in the distribution to facilitate removal for cleaning. It should be
system such as filters or heater/chiller batteries located in an easily visible position where it will
should be via fixed ladders and platforms or pulpit- not be subject to casual knocks. The pipework
19
Heating and ventilation systems – HTM 03-01: Specialised ventilation for healthcare premises – Part A
connecting it to the drainage tray should have a 4.32 The quality of motorised dampers is critical. They
continuous fall of not less than 1 in 20. should:
4.24 Traps fitted to plant located outside or in unheated • be rigid;
plantrooms may need to be trace-heated in winter.
• have square connections fitted with end and
The trace-heating must not raise the temperature of
edge seals of a flexible material; and
water in the trap above 5oC.
• have minimal play in linkages.
4.25 Water from each trap must discharge via a clear air
gap of at least 15 mm above the unrestricted spill- The leakage on shut-off should be less than 2%.
over level of either an open tundish connected to a 4.33 A manually operated isolating damper should
foul drainage stack by way of a second trap, or a be installed between the main AHU and its
floor gully (or channel). A support should be distribution system to enable the unit to be isolated
provided to ensure that the air gap cannot be when cleaning is in progress.
reduced. More than one drain trap may discharge
into the tundish providing each has its own air 4.34 Some systems will require the fitting of a main
break. volume control damper so that the design air-flow
rate can be set at commissioning. The damper
4.26 Drainage pipework may be thermoplastic, copper
should be lockable in any position. If it will also
or stainless steel. Glass should not be used. The be used for plant isolation, it should be capable of
pipework should be a minimum diameter of being reset to give the design air flow without the
22 mm and have a fall of at least 1 in 60 in the need for remeasurement.
direction of flow. It should be well supported and
located so as not to inhibit access to the AHU. 4.35 Internal plant-isolating dampers are not required.
Neither is the provision of fittings for shut-off
Layout of AHU plates between items within a unit.
4.27 The AHU should be arranged so that most items
Vibration
are under positive pressure. Any item of plant
requiring a drain should be on the positive pressure 4.36 Vibration from a remote plantroom can be
side of the fan. A recommended layout is given in transmitted by the structure of the building, may
Figure 1. be regenerated and may sometimes be magnified
many times. Units should be selected to have the
4.28 A separate extract unit will generally be required for
minimum vibration generation and to be installed
the area served by each supply unit. on suitable anti-vibration mounts. Pipe and
4.29 An energy recovery system will normally be fitted ductwork should incorporate anti-vibration
between the supply and extract units. couplings, preferably in two planes at right
angles, as close to the vibration source as possible.
Provision of dampers Consideration should be given to the use of anti-
vibration pipe hangers and supports.
4.30 Fire- or smoke-actuated dampers should be
provided at the locations required by Health
Sequence of components
Technical Memorandum 05-02 – ‘Guidance in
support of functional provisions for healthcare 4.37 The following arrangement of plant components is
premises’ (see also paragraph 5(c) in Appendix 1 typical, although in many instances not all elements
and paragraph 6.21). will be required:
4.31 Motorised low-leakage shut-off dampers should a. fresh-air intake;
be located immediately behind the intake and b. motorised isolation/smoke damper;
discharge of each supply and extract system
respectively. They should be of the opposed-blade c. frost/fog coil;
type, opening through a full 90 degrees, and must d. prefilter;
close automatically in the event of power failure or
plant shut-down to prevent any reversal of the e. energy-recovery device;
system air flow.
20
4 Air-handling unit design and specification guidance
f. attenuator (these may be located in the intake 4.44 Axial flow or propeller fans are generally only used
and discharge duct if they are of a suitable type in local through-the-wall systems or systems with
– see also paragraph 4.166); very low-pressure requirements.
g. fan; 4.45 Cross-flow fans have very low operating efficiencies,
and thus their use is restricted to applications such
h. blast plate;
as fan-coil units.
j. attenuator (see (f ));
Location and connection
k. chiller battery;
4.46 Fans are normally positioned to “blow through” the
m. eliminator;
central plant so that the cooling coil and humidifier
n. heater-battery; drains will be under positive pressure.
p. humidifier; 4.47 The fan performance figures given by
q. final filter; manufacturers in their catalogue data are based on
tests carried out under ideal conditions, which
r. manual isolation/volume control damper. include long uniform ducts on the fan inlet/outlet.
4.38 There may be instances where this arrangement is These standard test connections are unlikely to
not appropriate, and the plant arrangement should occur in practice; the designer should therefore
be planned accordingly. ensure as far as is practical that the fan performance
will not be significantly de-rated by the system.
This objective can be approached by ensuring that
Fans
the fan inlet flow conditions comprise uniform
General requirements axial flow velocities with low levels of turbulence.
4.48 Where the outlet duct is larger than the fan
4.39 The fan should be selected for efficiency and
minimum noise level, but the overriding factor discharge connections, there should be a gradual
should be the selection of a fan characteristic such transition, with a following section of straight duct
that the air quantity is not greatly affected by having a length equivalent to three duct diameters.
system pressure changes due to filters becoming 4.49 The design of the fan inlet connection must be
dirty or due to external wind effects. carefully considered to avoid swirl in the air stream.
When the air spins in the same direction as the
Acceptable types impeller, the performance and power consumption
4.40 Fans can be of the axial, centrifugal, cross-flow, of the fan are reduced. When the air spins in
mixed-flow or propeller type, depending on the the opposite direction to the impeller, power
requirements of the system. consumption and noise will increase with hardly
any pressure increase. Air-stream swirl is usually
4.41 Where used, centrifugal fans should preferably induced by large variations across the fan’s inlet
be of the backward-blade type. Alternatively, eye, caused by the air passing round a tight bend
where noise levels are more critical and pressure immediately before the eye.
requirements are lower, forward-curved blade fans
are acceptable. For high-power applications, 4.50 Where a centrifugal fan is located with a free inlet,
aerofoil-blade fans are appropriate. the clear distance between the suction opening and
the nearest wall should be not less than half the
4.42 In all cases the fan power performance diameter of the inlet. If two fans with free inlets are
requirements of the Building Regulations Part L2 positioned within the same chamber, their adjacent
must be met. suction openings should be at least one (inlet)
diameter apart.
Selection
4.51 Airtight flexible joints should be provided at the
4.43 Generally, large ventilation systems will use fan’s inlet and outlet connections. They should be
centrifugal fans due to their efficiency, non- equal in cross-section to the points of connection,
overloading characteristics and developed pressures. and be neither longer than 200 mm nor shorter
than 100 mm.
21
Heating and ventilation systems – HTM 03-01: Specialised ventilation for healthcare premises – Part A
4.52 For centrifugal fans, a diffuser screen/blast plate Extract fan drive arrangements
should be fitted immediately downstream of their
4.57 Where the fan drive is via a motor-driven belt-and-
discharge.
pulley arrangement, it should be located external to
the air stream.
Supply fan drive arrangements
4.58 The fan drive and motor may be located inside
4.53 Where the fan drive is via a motor-driven belt and
the duct within the air stream, provided the motor
pulley, it should be external to the air stream. This
windings are protected from over-temperature by a
arrangement has the following advantages:
thermister and lockout. The drive train should be
a. the fire risk is reduced; easily visible through a viewing port, have internal
b. the drive is visible, so it is simple to check that illumination, and be accessible via a lockable
the belt is still there; hinged door.
c. particles shed from the drive belt are outside of 4.59 Where the system air is explosive, aggressive or
the air stream; has a high moisture content, the extract fan motor
must be located outside the air stream. This is
d. if the belt slips, the “burning rubber smell” is generally achieved with axial fans by using a
not transmitted down into occupied areas of the bifurcated unit.
premises;
e. noise generated by the motor and drive will not Control
be transmitted along the ductwork; 4.60 Fans in healthcare applications are generally either
f. waste heat is excluded from the system; single- or two-speed. Where there is a requirement
for two-speed operation, this is generally via a local
g. the drive may be through a V-belt or toothed user control (for example in a hood-extract system
belt and pulley. The latter has the advantage of to provide a boost facility) or via a time schedule
eliminating belt squeal on start-up and has a for energy saving during unoccupied periods.
longer service life. It is particularly suitable
where the fan’s drive motor is fitted with a soft 4.61 Normally, only a single motor is required with a
start. standby motor available for fitting as necessary,
or fitted, but not belted. Twin, run and standby
4.54 The drive train should be easily visible without the motors – with the standby being jockeyed around
need to remove access covers. Protecting the drive – are not required.
train with a mesh guard is the preferred option.
For weatherproof units designed to be located 4.62 Where there is a specified requirement for standby
outside, the fan drive will be external to the duct, fans, the system should incorporate an automatic
but enclosed. It should be easily visible through a changeover facility activated via an air-flow sensor.
viewing port with internal illumination and be Fault indication should be provided.
accessible via a lockable hinged door. 4.63 In terms of start-up and operation, fans are
4.55 For direct-coupled fan and motor units, the motor increasingly becoming computer-controlled.
may be within the air stream, provided the motor Inverter-drive, variable-speed and soft-start systems
windings are protected from over-temperature by a are becoming a standard approach. Most healthcare
thermister and lockout relay. applications require known amounts of air to be
delivered while the system is in use. Constant-
4.56 For induction-drive “plug” motor arrangements volume systems that deliver specified air-change
(where the motor is fitted within the fan and is rates are therefore the norm. Duct- or room-
integral to it) and in-line axial fans with a pod pressure-controlled, variable-speed systems have a
motor, the fan/motor combination may be within very limited application in healthcare.
the air stream, provided the motor windings are
protected from over-temperature by a thermister 4.64 It is necessary to ensure that – should the computer
and lockout relay. control system or its software develop a fault – the
fan can be switched to a direct-start, fixed-speed
manual operation. This is particularly important
for critical care systems serving operating suites,
high-dependency care units of any type, isolation
22
4 Air-handling unit design and specification guidance
23
Heating and ventilation systems – HTM 03-01: Specialised ventilation for healthcare premises – Part A
24
4 Air-handling unit design and specification guidance
25
Heating and ventilation systems – HTM 03-01: Specialised ventilation for healthcare premises – Part A
supplying it should be provided with a dirt pocket, moisture; it is not necessary to install a
pressure-reducing valve and steam trap installed as dehumidifier to reduce the humidity of the
close as practicable to the humidifier so that the incoming air if it already exceeds 70%. The
steam condition at entry is as dry as possible. humidifier control system should ensure that the
A temperature switch on the condensate line humidifier is switched off when the fan is not
(or equivalent design provision by the humidifier running.
manufacturer) should be incorporated to prevent
4.114 It is usual to isolate the humidifier upon selection
“spitting” on start-up.
of set-back operation. In addition, on system shut-
4.108 Most operational problems with mains steam down, low air flow or fan failure, the humidifier
humidifiers arise because of back-pressure in the should be isolated.
condensate discharge line, which will result in
4.115 If a water-supplied local steam generator is
flooding into the duct. Unless the condensate
unused for a period exceeding 48 hours, it must
from the device can be discharged and collected
automatically self-drain (that is, all water content
at atmospheric pressure, it should be discharged
must drain out – including that contained in the
directly to drain.
supply pipework – all the way back to the running
4.109 Some steam generators incorporate a heated tank main) and remain empty.
that requires regular cleaning and descaling. The
design must allow the steam-supply manifold to be Filtration
physically isolated from the air duct in order to
prevent contamination of the air stream by General requirements
cleaning agents while this is taking place.
4.116 The purpose of filtration is to reduce the level of
Location airborne contamination in an air stream. It is
generally carried out in stages.
4.110 Careful siting of the humidifier lance is required to
4.117 Filters must be securely housed and sealed in well-
prevent the steam impinging onto the side(s) of
the duct, condensing and generating excess fitting frames that minimise air bypass. Air bypass
moisture. significantly reduces filtration efficiency: the
higher the filter grade, the greater the effect.
Control Mounting frames should be designed so that the
air flow pushes the filter into its housing to help
4.111 Accurate humidity control can only be provided minimise air bypass. Mounting frames that
on single-zone systems or multi-zone systems with withdraw so that the filter can be changed without
zonal humidifiers. In the former, humidity sensors having to reach into the unit are preferred.
control the humidifier for low-level humidity
control and override the temperature controls to 4.118 Neither the filter media nor any material used in
open the cooling-coil valve for high-level humidity the construction of the filters should be capable of
control. sustaining combustion. The filter media should be
such that particles of it do not detach and become
4.112 Multi-zone systems are more usually controlled by carried away by the air flow.
a minimum humidity sensor located in the supply
duct(s) following the last heater-battery. 4.119 Filters need to be readily accessible for
replacement; therefore, a hinged access door
4.113 Overriding controls separate from the normal should be provided. The upstream side of the filter
plant humidistat should be installed. Their should be visible for inspection through a viewing
purpose is to prevent excessive condensation in the port with internal illumination.
conditioned space when starting up. A time delay
should be incorporated into the humidifier control 4.120 All filters should be provided with a means of
system such that the humidifier does not start visually checking the differential pressure across
until 30 minutes after the ventilation/plant start- them. Direct-reading dial-type gauges marked with
up. In addition, a high-limit humidistat should be clean and dirty sectors are preferred.
installed to limit the output of the humidifier so 4.121 A complete spare set of filters must be provided to
that the saturation in the duct does not exceed the client at handover.
70%. This humidistat is to control the added
26
4 Air-handling unit design and specification guidance
27
Heating and ventilation systems – HTM 03-01: Specialised ventilation for healthcare premises – Part A
4.132 In urban or other areas of high atmospheric • housing it in a ”safe change” unit that permits
pollution, a higher standard of filtration may be the filter to be ejected into a bag and sealed
justified to reduce the level of staining to internal without staff having to come into direct contact
finishes. with it.
4.138 In view of the costs and problems associated
Extract air filters with placing HEPA filters in extracts, it is
4.133 Extract filtration will generally only be required recommended that a full risk assessment be carried
where heat-recovery devices are installed. There are out at the design stage. This should include
a very limited number of specialised applications defining the need for HEPA filters in an extract;
(microbiological safety cabinets and similar LEV validation of its performance at installation; the
systems) where contaminated air is required to be method of safely changing a contaminated filter;
filtered prior to discharge to atmosphere. If it is and its subsequent disposal.
safe for staff to work in a room without wearing 4.139 ULPA filters are very expensive and are designed
respiratory protective equipment, it is safe to to remove particles below a size that are either
discharge the room air to atmosphere without surgically or aerobiologically significant. There
filtration. would have to be exceptional circumstances in
order to justify their use in healthcare ventilation
Return-air filters systems.
4.134 Return-air filters are used to reduce the load on
HEPA filters in recirculating applications such as Activated carbon filters
ultra-clean operating suite ventilation canopies and 4.140 Activated carbon filters are able to remove gases
pharmacy aseptic suites. and vapours from the air stream and are graded
according to the range of substances they can
28
4 Air-handling unit design and specification guidance
remove. They are not normally fitted in air- 4.148 The following are the minimum energy transfer
conditioning supply systems. efficiencies required for devices handling equal air
volumes:
4.141 They are occasionally fitted retrospectively because
the main air intake has been poorly sited and is • run-around coil – 45%;
drawing in traffic fumes. Where used, they must
• plate heat exchanger – 50%;
be protected by a particulate air filter.
• thermal wheel – 65%;
4.142 Activated carbon filters are more commonly used
in specialised fume-extraction systems when the • any other energy-recovery device – 50%.
location of the discharge means that dilution 4.149 If a plate heat exchanger is chosen, the plates
cannot be relied upon to disperse noxious fumes. should be constructed of metal. An internal bypass
is not always required but, if fitted, plastic should
Location
not be used for the internal dampers and drive
4.143 The primary filter should be positioned on the gears.
inlet side of the supply fan, downstream of the
4.150 Whichever energy-recovery device is chosen, the
frost coil. The secondary filter, when fitted, should
extract side will need to be protected by a G3 filter
be on the positive-pressure side of the fan. This
and provided with a drainage system (as described
will prevent air being drawn into the system after
above) to remove condensate.
the filter and capture any particles shed by items of
equipment within the AHU. Location
4.144 The filter installation must be arranged to provide 4.151 Energy-recovery devices should be located
easy access to filter media for cleaning, removal or downstream of the fog coil and prefilter, prior
replacement, with side or front withdrawal as to the cooling coil or main heater-battery on the
required. supply side. If heat pipes are selected, it may be
possible to use them to replace the fog coil.
Control
4.145 Differential-pressure transducers should be Control
provided to remotely monitor and alarm on 4.152 It is essential to consider the control of both the
excessive filter pressure drop. In critical care areas, energy-recovery device and the fog/frost coil when
dirty-filter indication lights should be provided at assessing the economics of recovery, as all energy
the point of use. provided by the frost coil will directly reduce the
heat exchange of the recovery device. To this end,
Energy recovery the off-coil setting of the frost coil should be the
minimum possible to protect the primary filter
General requirements (for example +2oC).
4.146 Energy recovery must be fitted to all healthcare 4.153 The control of the energy-recovery device should
ventilation systems. It may be omitted only where be fully integrated with that of the main plant to
it would clearly be uneconomic (for example to a ensure maximum economic benefit.
single WC extract system).
4.154 Plate heat exchangers and heat pipes can be self-
4.147 For systems in healthcare premises, a plate heat controlling in the sense that energy will transfer
exchanger or “run-around coil” system is suitable. across the device from the extract to the supply at
Thermal wheels may be used providing they are winter design values and from the intake to the
fitted with a purge sector. The small amounts of extract discharge at summer design values, thus
air leakage across these devices are not considered obviating the need for a bypass and sophisticated
significant. Other systems such as heat pumps or control system.
heat pipes are also suitable. Selection should be
based on the relative locations of the supply and
extract units, ease of maintenance and practicality.
Cleaning access will be required to both sides of
any energy-recovery device.
29
Heating and ventilation systems – HTM 03-01: Specialised ventilation for healthcare premises – Part A
30
5 Air distribution system
5.3 The site will often dictate the main routing of 5.9 In instances where moisture levels and/or corrosive
ductwork systems but, in general, the design should elements in the air being conveyed are very high,
seek to make the layout as symmetrical as possible; aluminium, stainless steel, PVC or GRP (glass-
that is, the pressure loss in each branch should be reinforced plastic) ducts should be used. Stainless
as nearly equal as possible. This will aid regulation or black steel are the only suitable materials for
and may reduce the number and variety of duct high-temperature ductwork.
fittings that are needed. 5.10 In inherently wet areas, such as the base of fresh-air
5.4 Main distribution ductwork should not be routed inlet ducts and some extract systems, the ductwork
above sleeping areas. Where there is no alternative may require draining to prevent a build-up of
route, additional acoustic insulation is required. standing water. The layout of the drains should be
as specified in Chapter 4.
5.5 Where auxiliary air-conditioning units, fans, filters
or trimming devices are installed in the distribution 5.11 Where builders’ work ducts or plenum chambers
system, they must be independently supported and are used, these may be constructed of various
fitted with a suitable drainage system, where materials. However, all such ducts must be
31
Heating and ventilation systems – HTM 03-01: Specialised ventilation for healthcare premises – Part A
rendered and sealed to prevent dust-shedding. 5.20 An access hatch should be provided adjacent to
A greater allowance may need to be made for each fire damper so that its correct operation can be
leakage. directly observed. The hatch must be suitably sized
to permit inspection, testing and maintenance.
5.12 Galvanised, black and stainless steel ductwork
should be manufactured and installed to the 5.21 Smoke-diverting dampers must be provided on
current HVCA specification for sheet metal recirculation air systems to automatically divert any
ductwork DW144, but excluding the use of smoke-contaminated return air to the outside of
bolt-through supports. the building in the event of a fire. It should be
arranged such that the normal open smoke-
5.13 GRP and PVC ductwork should be manufactured
diverting damper on the return-air branch to the
and installed to the current HVCA specification for
input unit closes and all the return air is exhausted
plastic ductwork DW154.
through the extract fan. Guidance is available in
5.14 Flexible ductwork is unsuitable for air distribution Health Technical Memorandum 05-02 and
in healthcare applications. It should only be used BS 5588-9.
to make the final connection to a terminal (see
paragraphs 5.53–5.54). Duct sections
5.15 Where phenolic-board ductwork is considered, care 5.22 Ducting is generally available in rectangular,
should be taken to ensure that it is fabricated to a circular and flat oval sections, although other
quality standard and installed strictly in accordance sections may be manufactured for particular
with the manufacturers’ instructions. Its pressure situations.
rating and degree of support should be suitable for
5.23 Rectangular ducting is most common on low-
the application, and the duct should be fitted with
pressure systems for the following reasons:
mechanical protection where required.
• it can be readily adapted to fit into the space
5.16 The inside of the ductwork should be free from
available;
structural projections and as smooth as possible.
Flanged gasketed joints between sections are • fittings are cheaper than those for circular or flat
preferred. oval ductwork;
• it can be readily joined to such component
Fire aspects, damper types and locations
items as heating and cooling coils, and filters.
5.17 It is essential that all relevant fire aspects of ducting
5.24 When sizing ductwork, the designer should take
systems are agreed with the fire officer before the
into account:
design is finalised.
• installation and operating costs;
5.18 Ductwork must be fire-stopped where it penetrates
fire compartment walls, floors and enclosures, • space limitations imposed by the structure and
cavity barriers and subcompartment walls other services;
or enclosures, and must be provided with • operating noise levels;
weatherproof collars where roofs or external
walls are penetrated. • requirements of regulation at the
commissioning stage.
5.19 Fusible-link and automatically controlled fire
dampers should be provided at the locations 5.25 For overall economy and performance, the aspect
required by Health Technical Memorandum 05-02. ratio should be as close to 1:1 as possible, since
The fire-damper mounting frame must be securely high aspect ratios increase the pressure loss, heat
attached to the building fabric. Where a fire gains or losses and overall cost (for example,
damper is not mounted directly in a fire changing the aspect ratio from 1:1 to 1:4 can
compartment wall, it must be correctly supported typically increase the installed cost of the ductwork
and the ductwork between it and the firewall must by 40% and add 25% to the heat gains or losses).
possess the same fire rating as the firewall that it 5.26 Circular ducting is preferable for high-pressure
penetrates. The fire-rated portion of ductwork systems and for systems operating at high negative
must not be penetrated by test holes or inspection pressures. In the latter case, additional stiffening
hatches. rings may be necessary. Machine-formed spirally-
32
5 Air distribution system
33
Heating and ventilation systems – HTM 03-01: Specialised ventilation for healthcare premises – Part A
34
5 Air distribution system
5.54 Flexible ducting will cause a significant frictional b. spread – defined as the width of the 0.5 m/s
loss and may be difficult to clean without damage. isovel; and
It should never be used in lieu of a bend. Where
c. drop – defined as the vertical distance from the
installed, it should take the most direct route and
centre line of the terminal to the bottom edge of
be as short as possible, never exceeding 1 m in
the 0.25 m/s isovel.
length.
5.60 It is necessary to consider each of these parameters
Diffuser and grille selection and sizing in both summer and winter conditions to ensure
satisfactory operation of the air-terminal device, as
5.55 The effectiveness of all ventilation and air-
warm jets behave very differently from cold jets.
conditioning systems depends on the methods
by which air is introduced to, and vitiated air is 5.61 A warm jet tends to rise until it attaches itself to
removed from, the space. The usual results of poor a horizontal surface, while a cold jet falls. Care
air-terminal selection and/or positioning are: must be taken to ensure that this does not lead to
unacceptable temperature gradients in winter, or
• draughts;
excessive air velocities in the occupied zone in
• stagnation; summer.
• poor air quality; 5.62 In order to ensure satisfactory air movement
• large temperature gradients; and within a space, it is necessary to consider
interaction between air movement from adjacent
• excessive noise. terminals and ceiling-mounted fixtures (light
5.56 Air can be supplied to a space in a number of ways, fittings etc), as well as interaction between air
although any device can be broadly placed into one movement and room surfaces.
of two categories: 5.63 If the supply and extract terminals are too close,
a. that producing a diffused supply; or short-circuiting may occur; if they are too far
apart, stagnant zones may be formed. Where two
b. that producing a perpendicular jet. opposing air streams meet, the individual velocities
Diffusers may be radial or linear, and normally must not be greater than 0.25 m/s.
utilise the Coanda effect (that is, adhesion of the air 5.64 Supply and extract grilles and diffusers should
stream to an adjacent surface) to reduce the risk of be fitted with opposed-blade dampers for fine
excessive room-air movement. A perpendicular jet balancing purposes.
is formed by discharging air through grilles, louvres
or nozzles, which are generally adjustable. 5.65 Further guidance on the selection of grilles and
diffusers is given in CIBSE’s Guide B.
5.57 Supply air terminals can be incorporated into any
room surface (for example floors, walls (high or low 5.66 In operating theatres, supply terminals must be able
level) and desktop). to produce a down-flow movement of air in the
operating zone, 1 m above floor level. The
5.58 As they operate on the jet principle, the use of side- following supply terminals are acceptable:
wall and linear grilles is restricted to areas where
air-change rates are fewer than ten per hour. • ceiling-mounted diffusers with fixed directional
Perforated rectangular diffusers can provide vanes that provide a downward turbulent air
acceptable conditions within the occupied zone flow are the preferred option;
at up to 15 air changes per hour. In areas where a • plenum boxes fitted with perforated screens
higher air-change rate is required, square or circular that produce a parallel downward flow;
ceiling-mounted diffusers should be used.
• linear ceiling-mounted diffusers that provide
5.59 The performance of supply air-terminal devices is a downward air curtain around the operating
based on three criteria: zone (additional supply terminals may be
a. throw – defined as perpendicular or parallel located within the area bounded by the linear
distance from the terminal to the point at which diffusers to provide ventilation within the air-
the air velocity is 0.5 m/s isovel; curtained zone).
5.67 Nozzles or jets of any type are not acceptable in
an operating theatre. Side-wall-mounted linear
35
Heating and ventilation systems – HTM 03-01: Specialised ventilation for healthcare premises – Part A
diffusers that utilise the Coanda effect to send air 5.75 Fire precautions for pressure stabilisers are the
across the ceiling and “drop” it into the operating same as for transfer grilles. For sizing criteria,
zone are not suitable. see Chapter 7.
5.76 Pressure stabilisers should be of the balanced-blade
Transfer grille – size and location
type, with the facility to make fine adjustments to
5.68 Air-transfer grilles in walls, partitions or doors form the pressure setting. They should be silent in
an integral part of the building’s air distribution operation and give a seal as tight as practicable
system. Modern doorsets have very low leakage when closed. The materials of construction and
rates, so cannot be relied upon to permit even quite method of assembly should allow for cleaning and
small air flows. Failure to make adequate provision disinfection.
for air to move from room to room will result in
5.77 Pressure stabilisers should be installed in a visible
excessive pressure differentials and “door whistle”.
location so that their operation can be readily
5.69 Transfer grilles are required in locations where there observed.
is a significant imbalance between the supply and
5.78 Cross-talk attenuators may be necessary where
extract rates in a room. They will relieve any
noise intrusion between adjacent spaces can arise
pressure differential that may affect the operation
and where confidentiality is required. In these
of the spaces and/or the ventilation system, and
cases, the pressure stabiliser and cross-talk
permit air flow in a known direction.
attenuator should be mounted in a short length
5.70 Care needs to be taken to ensure that the of ductwork within the ceiling void.
positioning of transfer grilles does not interfere
5.79 Pressure stabilisers may need to be fitted with a
with the fire or smoke integrity of the building. In
stand-off baffle on their discharge side to prevent
general, air-transfer grilles should not be installed
a sight line in situations where a laser will be used.
within fire-resisting boundaries, although if this is
Baffles may also be required to preserve privacy
unavoidable, they should be fitted with fire or
or to prevent discharge air causing draughts or
smoke dampers.
disturbing the air-distribution pattern in an
5.71 Where installed, transfer grilles should be of the adjoining room. They are also useful in low-level
non-vision type and sized for a maximum face locations to prevent the air-flow path being
velocity of 1.5 m/s. obstructed by portable equipment.
5.72 In photographic darkrooms, lightproof transfer
grilles are recommended.
5.73 Cross-talk attenuators may be necessary where
noise intrusion between adjacent spaces can arise
and where confidentiality is required (see also
paragraphs 5.42–5.46).
36
6 Automatic controls
6.1 Various options for control of single and multi- Objectives of the control system
zone air-conditioning systems are given in CIBSE
6.8 The primary objective of a ventilation or air-
Guide B.
conditioning plant control system is to keep the
space served within the required environmental
General requirements control limits, at the appropriate times – regardless
6.2 The basic requirements for an automatic control of external conditions or internal loads – and with
system are as follows: the minimum energy consumption.
• facilities to start, set-back and stop the plant; 6.9 Control of most systems will be via a building
management system (BMS). This will enable the
• facilities to control the volumetric air flow; operating conditions and control tolerances to be
• facilities to control the system or room pressure; set and monitored. Often, it is not possible to
accurately predict building load variation at the
• temperature control and indication;
design stage. Information provided by monitoring
• humidity control and indication; the operation of the plant via a BMS will enable
optimum set-points to be established and energy
• devices to monitor and indicate the plant’s
consumption reduced. The BMS may also be set
operating state;
to log the actual energy consumed by the system
• alarms to indicate plant failure, low air flow and together with that recovered by the energy-recovery
filter state. device. This will provide a useful check on overall
6.3 The control functions provided will depend on the operating efficiency and provide evidence that
purpose of the ventilation system. energy targets are being achieved.
6.4 There will also be a need to determine the control 6.10 A BMS incorporating self-adaptive control
strategy in the event of a fire either within the zone algorithms that automatically adjust the set-point
being served or within an adjoining zone. to suit the usage and load is preferred. The
provision of movement sensors within the
6.5 Designers should consider whether it is necessary controlled space in order to determine the actual
for the supply and extract fans to be interlocked – occupancy will facilitate this process.
either so that the supply fan will not operate unless
air flow is established within the extract system, or 6.11 The failure of specialised ventilation systems
vice-versa depending on the required pressures can have grave consequences for the delivery of
within the rooms being served. healthcare. Control systems should therefore be
simple, robust and reliable.
6.6 The sequence switching of units in order to prevent
transient reverse air flows will be particularly 6.12 Computer-software-driven control systems are
important in laboratories and pharmacies that becoming the norm in building services. However,
contain fume cupboards, safety cabinets and other healthcare ventilation systems need to be available
LEV systems. for operation outside of normal working periods
when software support is not available. Should the
6.7 Alarms should be provided to show “filter fault” software fail, it will be left to site staff, who may
and “low air flow”. The “filter fault” alarm should have little knowledge of the control algorithms,
be initiated by a predetermined increase of pressure to restart the ventilation system. It is therefore
differentials across the filter. The “low air flow” essential to ensure that a simple means of restarting
alarm should be initiated when the supply-air critical systems in the event of a software failure is
quantity falls to 80% of the design value. provided (see also paragraphs 4.62–4.63).
37
Heating and ventilation systems – HTM 03-01: Specialised ventilation for healthcare premises – Part A
Location of controls 6.20 In all critical care areas, the ventilation system
should continue to operate unless smoke starts to
6.13 Whether within the plant, duct or room, sensors
enter the AHU. A notice should be affixed to the
should be located to provide accurate measurement
fire control panel stressing the need to liaise with
of the condition of the air being monitored.
departmental staff before switching off fan units.
6.14 Sensors and control items such as control valves
6.21 All supply AHUs should have a smoke sensor
should be located close to the element being sensed
mounted in the main supply duct immediately
or plant item being controlled in order to minimise
downstream of the AHU. In the event of a fire in
time lags within the system, which may create over-
the AHU or smoke being drawn into the system
shoot of conditions beyond the design envelope
from an outside source, it should cause the supply-
and result in additional energy consumption.
air fire damper to close and shut down the AHU.
6.15 There are practical advantages in locating
all control valves for an AHU in a bank (at a Time switching
convenient height) at one end of the unit. (This
should not result in an additional control lag.) 6.22 Facilities to start, set-back and stop the plant
should be provided in the plantroom. Remote start
6.16 Some applications require intermittent mechanical and set-back control and indication, if required,
ventilation, frequently at a high air-change rate (for should be provided at a manned staff location
example in bathrooms and treatment rooms). Local (for example at the reception or staff base).
controls to facilitate this mode of operation should
be placed in a prominent position to encourage 6.23 Many ventilation systems may be completely shut
economical use. down when the area served is not in active use (for
example operating theatres). Alternatively, where
6.17 Local controls that enable the user to select more there is a need to maintain a background condition,
than one mode of operation should be clearly the ventilation output can be reduced by “setting
labelled to identify the particular mode selected. back” the system. This will significantly reduce
Where the system allows different room pressures energy consumption and extend the life of filters
to be selected, a direct-reading pressure gauge and other system components.
should be fitted within the eye line of the users
to provide an independent confirmation of the Start-up control
resultant mode of operation. A clear description
6.24 The plant’s start control should contain a control
of the selectable modes of operation should be
mounted adjacent to the control switch. logic that will start the plant in the sequence set out
in the algorithms in Figures 2–5.
Fire aspects
Set-back control
6.18 A fire control panel should be mounted at the
6.25 Where variable-speed controls are installed, the
entrance of the area that the ventilation serves.
Access to the panel should be restricted to the fire set-back facility for each plant should depress the
officer and include independent on/off controls control temperature to around 15oC; exclude any
and an indication of the supply and extract systems. humidification and cooling from the system;
and reduce the supply and extract air volumes to
6.19 In certain critical care areas, it is preferable to around 50%. The extract fan can also be turned off
maintain the supply ventilation in case of a fire as long as the desired direction of air movement
within the area. For example, in an operating from clean to less clean will be maintained.
department, while undergoing surgery, the patient
cannot always be easily moved without significant Use control
risk. In the event of a fire in a staff or support
6.26 The installation of movement detectors allows
area of the department, or adjoining zone, the
for “use control” of ventilation systems. A simple
continued supply of air to a theatre will maintain it
control logic that reduces the system to a “set-back”
at a positive pressure and protect the patient and
condition if there has been no movement detected
staff from the effects of smoke. This will allow time
in the space for, say, 30 minutes and that switches
for the patient to be stabilised so that he/she can be
the system “off ” if no movement is detected for
safely evacuated if necessary.
one hour is recommended for many applications,
38
6 Automatic controls
PLANT OFF
FROST/FOG COIL – ON
RELEASE HEATER/CHILLER
RELEASE HUMIDIFIER
PLANT RUNNING
HUMIDIFIER CONDENSATE
39
Heating and ventilation systems – HTM 03-01: Specialised ventilation for healthcare premises – Part A
PLANT RUNNING
INITIATE SHUTDOWN
DISABLE ALARMS
PLANT OFF
40
6 Automatic controls
PLANT RUNNING
INITIATE SET-BACK
DISABLE ALARMS
41
Heating and ventilation systems – HTM 03-01: Specialised ventilation for healthcare premises – Part A
INITIATE RESTART
RELEASE CHILLER
RELEASE HUMIDIFIER
PLANT RUNNING
HUMIDIFIER CONDENSATE
42
6 Automatic controls
including operating suites (see paragraphs specified temperature range to suit the user
7.31–7.90). requirement with a control tolerance of ±1 K. All
other control set-points should be selectable either
6.27 A variation on this can be provided by linking
on the control panel or at the BMS interface.
ventilation controls to the lighting. For example, in
an operating theatre, the system may be off outside 6.34 Where local control is provided, an indication of
of working hours, could run at set-back when the temperature will be required locally or at a staff
general lighting is switched on, and increase to full base (if appropriate) using an analogue or digital
speed when the operating lamp is switched on. indicator. The indicator should be large enough
As with movement detection, a 30-minute run-on to be read from the normal working position (for
should be provided at each stage when the lights are example at the operating table in a theatre). This
turned off. may be mounted in a supervisory control panel,
with the signal repeated on the main system control
6.28 Either of the above control strategies may be
panel or BMS. It is important that this indicator
refined by linking to the BMS to provide a
displays the actual measured temperature and not
control logic related to normal working hours and
the selected temperature.
associated “real-time” movement within the zone
being controlled. This should result in significant
Frost coil control
energy savings.
6.35 Steam-supplied fog/frost batteries must be operated
Environmental control as on/off devices with their sensor mounted
upstream of the battery. This will give “open loop”
Temperature control methods and application control. A set-point of +1oC is recommended.
6.36 LPHW-supplied frost batteries should be
General controlled using the proportional mode. Their
6.29 All control valves must fail-safe, that is, close in sensor should be located downstream of the battery
the event of power or air-flow failure, with the to give “closed loop” control. A set-point of
exception of the fog/frost battery control valve, between 2oC and 5oC is recommended.
which should open upon power or air-flow failure. 6.37 If the temperature downstream of the frost battery,
6.30 Control valves should be located in an accessible as sensed by a serpentine thermostat, falls below
position. Isolation valves should be provided to the required set-point over any part of the coil, the
enable the control valve to be removed for service plant must automatically shut down in order to
without the need to drain-down the system. prevent damage to the other batteries. The
serpentine thermostat must not be in direct contact
6.31 Care should be taken to ensure that the installation
with the coil.
of control valves and their associated pipework do
not obstruct access to the AHU inspection doors Off-plant control
and hatches.
6.38 The control logic must prevent the chiller and pre-
Room temperature control heater being on at the same time.
6.32 The limits for room temperature set-point are
Humidity control methods and application
generally between 16oC and 25oC depending on
the particular application, and in some specialised 6.39 In order to prevent excessive condensation when
instances (for example operating departments) are starting up from a total plant shut-down, a time
adjustable within a predetermined range by the delay should be incorporated into the control
user. system such that the humidifier does not start until
30 minutes after the ventilation plant starts up.
6.33 The selection of temperature set-point for each
room or zone may be by a control facility in 6.40 Irrespective of the method of control, a high-limit
the room/zone or be carried out remotely at the humidistat should be installed to ensure that when
control panel or BMS. Where the control device is the humidifier operates, the condition of the air
mounted within the room/zone and is adjustable in the duct does not exceed 70% saturated,
by the user, it should be marked either “raise” and particularly during plant start-up.
“lower” or “+” and “–”. It should control within a
43
Heating and ventilation systems – HTM 03-01: Specialised ventilation for healthcare premises – Part A
6.41 With certain types of steam humidifier, it may be within the central plant, with trimmer heater-
necessary to install a thermostat in the condensate batteries on individual zones.
line from the humidifier’s steam supply, to ensure
that the steam at the control valve is as dry as Alarms and indication
possible before it is injected into the air supply. 6.48 Supply and extract systems should include indicator
6.42 The humidifier and cooling-coil control must be lamps on the control panels to confirm the
interlocked so that they cannot be on at the same operational status of each system. Where the usage
time. is on a regular daily pattern, time control with a
user-operated, timed manual override should be
6.43 The humidifier control system should ensure that
provided.
it is switched off with the fan. It is preferable to
design the control system so that the humidifier 6.49 Where a system is provided for a particular space,
is isolated for an adequate time before the fan is the indicator should be in, or immediately adjacent
turned off so as to purge humid air from the to, that space, and local controls should be
system. provided with labels clearly defining their function
(for example isolation suites).
6.44 All control valves must fail-safe (that is, close in the
event of power failure), and the humidifier must be 6.50 The “plant failure” and “low air flow” alarm should
interlocked with the low air-flow switch. be initiated by a paddle switch or other device
located in the main air-supply duct. This should
Multi-zone control methods and application. operate when the air quantity fails to reach or falls
to around 80% of the design value and will give
6.45 Close control of all air-conditioning parameters
indication of fan failure, closed damper, left-open
may be difficult to achieve with multi-zone
access door, or any other eventuality that could
systems, since each zone will in theory require a
cause a reduction of air quantity. Monitoring the
reheater and humidifier to give total control of
current drawn by the fan motor is not a substitute
humidity, if that is what is required. In reality, such
for a sensing device that is directly affected by the
close control is rarely required. It is therefore usual
air flow.
with multi-zone systems to provide control of zonal
temperature only, with humidity control, where 6.51 The “filter fault alarm” should be initiated by a
fitted, being based on average conditions within all predetermined increase of pressure differential
zones, or minimum conditions within one zone. across the filters, thereby indicating a dirty filter.
6.46 Where there is a requirement for close control of 6.52 Direct-reading gauges or manometers should be
air-conditioning parameters in a number of zones installed across filters to give maintenance staff an
(for example an operating department), separate indication of their condition.
plants should be provided for each zone in order
6.53 Visual indication should be provided at a manned
to avoid the need for expensive over-cooling and
staff location (for example the reception or staff
reheating of individual zones.
base), on the main control panel and on the BMS
6.47 The control of most multi-zone systems within to show “plant failure” and “low air flow”.
healthcare premises is based on off-coil control
44
7 Specialised ventilation systems
45
Heating and ventilation systems – HTM 03-01: Specialised ventilation for healthcare premises – Part A
aspects of ventilation system design and required for this aspect. It is important that the
specification. design makes the best possible use of the air
available, as excessive supply air flows for the
b. A set of standard solutions for the design of
control of air movement should not be used. The
general operating theatre suites to conform to
amount of air supplied will be determined by the
past and new standards is given in paragraphs
number of doors and desired air-change rate.
7.31–7.90, and those for UCV theatres in
paragraphs 7.91–7.147. 7.7 Airborne contaminants may enter a room via the
following routes:
c. The CIBSE guides A and B contain basic
information on ventilation design, which can be a. through the supply air;
applied to most applications.
b. shed directly by the room occupants;
d. Where a British or European standard exists
c. as a result of work activities;
that is specific to the application (for example a
clean room), it should be used as the basis of the d. transferred from adjacent spaces.
design requirement. 7.8 Particles entering with the supply air can be
e. Air should always move from clean to less clean controlled by the selection of suitable filter grades.
areas. A hierarchy of room cleanliness is given in 7.9 Particles shed directly by the room occupants can
Appendix 3. be controlled by:
f. Differential pressure will prevent contamination a. restricting access to essential persons only;
between areas when doors are closed.
Information on air leakage through closed doors b. the choice of the occupants’ clothing;
and hatches for a range of differential pressures c. the room’s air-change rate.
is given in Appendix 4.
7.10 Particles arising as a result of the work activity can
g. The flow of air will prevent contamination be controlled by:
between areas when doors are open.
Information on air leakage through open doors a. enclosing, semi-enclosing, or otherwise, the
and hatches for a range of differential pressures work-based source;
is given in Appendix 6. b. the room air-change rate.
h. If anaesthetic gases are used, 15 air changes per 7.11 The transfer of particles from adjacent spaces can
hour will be required. be controlled by:
j. A methodology for calculating a design solution a. differential pressure;
for a non-standard suite of operating rooms is
given in Appendix 8. This may be adapted as b. clean air-flow paths.
necessary to suit other less complex applications 7.12 Air-change rates are given in Appendix 2. These
where air is required to cascade from clean to figures have been found to give sufficient dilution
less clean areas. of airborne contaminants, provided the mixing of
7.5 The supply of air to a room has four main room air is reasonably uniform.
functions: 7.13 Downward-displacement turbulent air distribution
a. to dilute airborne contamination; is generally preferred. The supply and extract
diffusers should be positioned to ensure that all
b. to control air movement such that the transfer parts of the room are actively ventilated and that,
of airborne contaminants from less clean to where necessary, staff will be in a clean air-flow
cleaner areas is minimised; path (see Chapter 5 for additional guidance on
c. to control the temperature and, if necessary, the supply terminals).
humidity of the space; 7.14 Horizontal-flow room-air distribution with or
d. to assist the removal of, and dilute, waste gases without a Coanda effect can be a source of draughts
where used. and difficult to set up correctly. Its use should be
confined to non-critical areas.
7.6 Because of the complexities of controlling air-
movement patterns, much design effort will be
46
7 Specialised ventilation systems
47
Heating and ventilation systems – HTM 03-01: Specialised ventilation for healthcare premises – Part A
will be related to the relative cleanliness of the Additional information for UCV theatres is given
areas being considered. Appendix 5 gives air- in paragraphs 7.91–7.147.
flow rates for open-door protection related to
door/opening size and classification of the General
adjoining areas. 7.33 The supply of air to an operating room has four
7.25 Pressure stabilisers enable the room’s differential main functions:
pressure to be set when the doors are shut, thus a. to dilute airborne contamination;
providing closed-door protection. When a door is
opened, the stabilisers will close, forcing air to be b. to control air movement within the suite such
directed through the doorway, thus providing that the transfer of airborne contaminants from
open-door protection. less clean to cleaner areas is minimised;
7.26 The recommended air-flow rates to achieve this c. to control the temperature and, if necessary, the
are given in Appendix 4. Provided that the dilution humidity of the space;
criteria in Appendix 2 are met, the occasional small d. to assist the removal of, and dilute, waste
back-flows created (when two doors are opened anaesthetic gases.
simultaneously or when there is a high temperature
difference across an open door) will have little 7.34 Because of the complexities of controlling air-
effect on the overall air cleanliness of the affected movement patterns, much design effort will be
room. required for this aspect. It is important that the
design makes the best possible use of the air
7.27 In applications where it is critical to maintain available, as excessive supply air flows for the
a specific air flow and/or pressure regime (for control of air movement should not be used. The
example isolation rooms), all windows in the zone amount of air supplied to the operating room will
should be locked shut or sealed. Trickle vents, if be determined by the number of doors and desired
fitted, should also be sealed. air-change rate.
Systems design 7.35 The detailed considerations upon which the supply
air-flow rate is based are as follows.
7.28 The design of the ventilation system for an
area depends on the overall configuration of the Dilution of airborne bacterial contaminants
department. Where the department is served by
more than one AHU, the control of the units may 7.36 Airborne contaminants may enter an operating
need to be interlocked so that reverse air-flow room via the following routes:
patterns do not occur. a. through the supply air;
7.29 Dual-duct high-velocity systems have advantages, b. shed by operating staff;
but are noisy, costly, and may give rise to
unacceptable values of humidity. Single-duct, c. through surgical activities;
low-velocity/pressure systems are preferred. d. transferred from adjacent spaces.
7.30 Extract grilles should be sited and balanced to 7.37 Supply flow rates for the main rooms of the
promote air movement in the desired direction. operating suite are given in Appendix 7. For the
other areas where room sizes and activities vary
Operating department ventilation from site to site, air-change rates are given in
systems Appendix 2. These figures have been found to
give sufficient dilution of airborne bacterial
7.31 The information given in this section relates to contaminants, provided the mixing of room air is
general operating suites. It is also applicable to reasonably uniform.
other types of theatre suite such as maternity,
burns, cardiac etc. The standard values given may 7.38 Downward-displacement air distribution is
need to be adjusted to reflect non-standard room preferred, and may be either turbulent or parallel
sizes, pressure regimes and air-change rates. downward flow. For turbulent flow, supply-air
diffusers should be positioned either in the centre
7.32 A method of obtaining a design solution for of each quadrant of the ceiling or along a line
non-standard theatres is given in Appendix 8. between the centres of each quadrant. This should
48
7 Specialised ventilation systems
ensure that all parts of the room are actively between rooms and doors are held partially open
ventilated and that there will be adequate air by air pressure.
movement at the operating table. Parallel
downward flow is provided by a perforated plenum Temperature and humidity control
terminal centred above the operating table (see 7.48 Supply flow rates to achieve the required room
Chapter 5 for additional guidance on supply conditions are calculated conventionally, taking
terminals). account of all heat and moisture gains and losses,
7.39 Suspended, articulated pendants in theatres require and of maximum permissible temperature
significant structural steelwork in the ceiling void differences between the room and supply air. In
to cater for the loads imposed by the resulting most applications the base heating load will be
bending moments. It is important to ensure that provided by a heating system, or the room being
the void is deep enough to accommodate both the considered will be within the heated building
steelwork and the ventilation ducts. However, the envelope.
location of the steelwork must not prevent a 7.49 Temperature differences of up to 10 K for winter
suitable layout of the ventilation ductwork and the heating and 7 K for summer cooling must not be
appropriate positioning of supply air terminals – exceeded.
the correct ventilation of an operating theatre
plays a significant role in controlling healthcare- 7.50 It is acceptable for the humidity to swing
associated infections and should not therefore be uncontrolled between 35% and 60% saturation.
compromised by the need to facilitate the
movement of equipment. Removal and dilution of waste anaesthetic gases
7.40 Horizontal-flow distribution with or without a 7.51 Anaesthetic gases are subject to workplace exposure
Coanda effect can be difficult to set up correctly limits. The air-movement scheme should ensure
and is unlikely to be as effective in theatre that staff are in a clean air-flow path (see paragraphs
applications. It should not be used in new 7.20–7.21).
installations; however, space constraints may force 7.52 Air extracted from operating suites should not
its retention or replacement when refurbishing be recirculated, as it may contain malodorous
existing installations. Where fitted, the supply contaminants; however, an energy-recovery system
grilles will require a means of directional must be fitted in the extract in order to reduce
adjustment. the plant’s energy consumption (see paragraphs
7.45 For general operating theatres, the air supply is 4.146–4.154).
filtered in the AHU. Terminal or HEPA filters are
not generally required. Fire aspects
7.53 When considering overall air-flow movement,
Control of air movement within the suite careful thought needs to be given to the operation
7.46 The design of the system should seek to minimise of the ventilation system in order to limit smoke
the movement of contaminated air from less clean spread in the event of a fire. However, this is a
to cleaner areas. Transfer grilles enable air to pass highly staffed department with a low fire risk/load
in either direction between rooms of equal class status, and these factors need to be recognised
and pressure. Pressure stabilisers operate in one when developing the fire strategy. It is considered
direction only; they allow excess air to be directed satisfactory to treat the complete operating
to the area desired and assist in maintaining room- department as a single fire compartment providing
pressure differentials. there are at least two exits from it. Over-
compartmentalisation can lead to difficulties in
7.47 The relative locations of supply and extract establishing clean air-flow paths and room-air
terminals and their design air-volume rates will dilution rates, which in turn may lead to an
determine the basic air flow between adjacent increased risk of healthcare-associated infections.
spaces. Transfer grilles and pressure stabilisers will Staff areas within the department should be treated
permit and control the flow of air between spaces, as a subcompartment (see paragraphs 6.19–6.21).
ensuring a flow from the clean to less clean areas of
the suite. Failure to provide such devices will lead
to uncontrolled air flows when personnel move
49
Heating and ventilation systems – HTM 03-01: Specialised ventilation for healthcare premises – Part A
50
7 Specialised ventilation systems
operating-suite layouts. These were satisfactory 1 Typical conventional theatre – room sizes as
design solutions for “standard” sized rooms within Health Building Note 26.
the suite, but were never intended to be universal
2 Typical UCV theatre – room sizes as Health
for any sized room or suite. Health Building Note
Building Note 26.
26 – ‘Facilities for surgical procedures’ increased
the recommended size of the operating room from 3 Health Building Note 26 illustrated
approximately 35 m2 to 55 m2. Ancillary room conventional theatre.
sizes and air-change rates also increased. This meant 4 Health Building Note 26 illustrated theatre with
that the original standard solutions were no longer UCV terminal fitted.
appropriate for new-build installations.
5 Pre-2006 conventional theatre, single corridor
7.59 Because of the resulting increase in the volume of
(Health Technical Memorandum 2025; 1b).
air supplied to the theatre, provision needs to be
made to either actively remove it or allow it to 6 Pre-2006 UCV theatre, single corridor (Health
passively escape through pressure stabilisers. The Technical Memorandum 2025; 1a).
increase in room size has also made the number 7 Pre-2006 conventional theatre, two corridors
and position of air-supply terminals critical to the (Health Technical Memorandum 2025; 5b).
effective ventilation of the room.
8 Pre-2006 UCV theatre, two corridors (Health
7.60 Four new standard solutions have been developed Technical Memorandum 2025; 5a).
to reflect the current guidance on theatre suite
layout and room sizes given in Health Building 7.65 Details of these standard solutions are given in
Note 26, as well as the general increase in air- Appendix 7, which contains diagrams showing the
change rates. relationship of rooms and the various doors and
transfer devices between them, but these should
7.61 The most commonly used original standard not be regarded as architectural layouts. The
solutions have been revised and updated. They have schemes have been developed using the calculation
been retained in this guidance, as they will remain procedure described in Appendix 8. Important
applicable to older theatre suites that are being features of the solutions are:
refurbished to their original performance standards
or are being converted from conventional to UCV • Zone trimmer heaters – a trimmer heater-
theatres. They will also be applicable in existing battery is advocated when calculations indicate
operating departments where space constraints that the temperature differential between rooms
do not permit a complete upgrade to the latest may be greater than 2 K. Generally this will
standard of performance or where a pre-built only be the case in the preparation room when
“shell” is being fitted out. designated as a lay-up, although they are
sometimes required for anaesthetic rooms.
7.62 It is important to recognise that in any situation
where a non-standard room size or theatre suite • The preparation room (sterile pack store)/
layout is being considered, the designer must return operating room interface – these rooms are
to first principles when developing a solution. deemed to be of equal cleanliness, and thus a
Examples of non-standard configurations are: transfer grille is required between them, or the
door can be replaced with an opening wider
• cardiac theatres that typically have an operating than a standard door.
room 50% larger than a normal theatre, a
perfusion laboratory and no anaesthetic room; • Preparation room (lay-up)/operating room
interface – pressure stabilisers are recommended
• operating departments served by a central here to provide an air path when doors are
instrument lay-up preparation area rather than closed, while preventing back-flow when a door
individual preparation rooms; is opened elsewhere.
• balanced-flow theatres for infectious cases. • Operating room/anaesthetic room interface –
7.63 Appendix 8 contains a methodology for assisting pressure stabilisers, or in some cases carefully
the designer to arrive at a suitable solution. sized transfer grilles, are recommended here and
also between the anaesthetic room and corridor.
7.64 The new and revised standard design solutions are
The amount of air being passed through the
as follows:
51
Heating and ventilation systems – HTM 03-01: Specialised ventilation for healthcare premises – Part A
52
7 Specialised ventilation systems
and be accessible for cleaning and the removal of in Appendix 5 for the operating suite are not
fluff and lint. necessary for other areas of the department;
however, air-flow directions must be maintained
7.76 Wall-mounted passive-temperature and humidity
from the clean to the less clean areas.
sensors are not recommended.
7.84 All windows in the department should be double-
7.77 Controls should be provided to enable operating
glazed and hermetically-sealed in order to ensure
department ventilation plants to be closed down
that the desired air-flow pattern is maintained
when the operating suites are unoccupied (see also
under all external environmental conditions and to
paragraphs 6.26–6.28).
avoid infestation. Trickle vents, if fitted, should be
7.78 When in the “off ” mode, the control system should sealed.
ensure that the ventilation plant is automatically
reinstated if the space temperature falls below Systems design
15oC.
7.85 The design of the ventilation system for ancillary
7.79 The theatre’s control panel should include: rooms depends on the overall configuration of the
department. The ancillary rooms’ plant may need
• plant status indication;
to be interlocked to the theatre suite’s plants so that
• clearly-readable temperature and humidity reverse air-flow patterns do not occur.
gauges; and
7.86 Extract grilles should be sited and balanced to
• a means of adjusting the set-point for promote air movement along the clean and access
temperature (see paragraphs 6.32–6.34). corridors towards the reception/transfer areas.
The theatre’s ventilation-plant status indication This should not affect the air distribution in the
should also be located at the staff control base. operating suite(s).
53
Heating and ventilation systems – HTM 03-01: Specialised ventilation for healthcare premises – Part A
Ultra-clean ventilation systems within it. Other designs utilise slotted linear supply
terminals to produce an air curtain around the
General requirements clean zone together with laminar-flow diffusers to
provide a downward-displacement supply within it.
7.91 The design philosophy of a conventionally
Notwithstanding any variation in the design
ventilated operating suite is based on the need to philosophy, all UCV systems will be required to
dilute contaminants and control both the condition completely achieve the performance standards
and movement of air in an operating suite. Ultra- set out in Chapter 8.
clean ventilation (UCV) is a means of significantly
increasing the dilution effect by providing a large 7.95 As with conventional theatres, each UCV operating
volume of clean filtered air to the zone in which suite should have its own dedicated AHU to the
an operation is performed and sterile items are standard set out in Chapter 4.
exposed. Air is discharged above the operating 7.96 To ensure operational flexibility and permit routine
zone and, while not truly laminar, its downward maintenance, AHUs should not be shared between
displacement purges the clean zone of any suites.
contaminants and particles generated within it. The
air flow in and around the clean zone also serves to 7.97 In retrofit installations, site conditions may
prevent particles originating outside the zone from preclude individual AHUs for each suite. In these
entering. The resulting reduction in contaminants circumstances, an AHU may be shared between not
has been shown to significantly reduce post- more than two operating suites, providing each
operative sepsis following certain orthopaedic suite has its own control of temperature.
procedures. 7.98 An accessible air-flow measurement test-point
7.92 The number of bacteria that are present in the should be provided in the branch supply duct to
air at the wound site and exposed surgical items is each theatre so that the primary air volume to each
dependent on the operating team, their procedural UCV canopy can be determined.
discipline, choice of clothing and the type of UCV 7.99 In addition, the branch supply and extract should
system. Ultra-clean air is defined as that containing be capable of being physically isolated and the main
not more than 10 CFU/m3. air-flow rate reduced so that either suite can be
7.93 UCV systems are very successful in reducing taken out of use without detriment to operating
contaminants at the wound site, so it is often conditions in the other.
considered that there is no need for complex air- 7.100 An inherent feature of a UCV system is its large air
movement control schemes in the rest of the suite. flow, so it is essential to recirculate the air supplied
However, when designing the ventilation scheme, to the operating theatre and/or to recover its
it should be noted that the users may switch the energy in order to optimise operating costs.
UCV terminal to set-back when non-orthopaedic
surgery is taking place. This is because the high air- 7.101 The primary fresh-air volume supplied to a UCV
flow rate can cause increased moisture evaporation suite will be the same as in a conventional suite,
of exposed tissue, which may be detrimental to and it should be dispersed to the rooms in the
the surgical outcome. In recognition of this, the suite in the same manner. This is an important
ventilation scheme should be capable of providing aspect of the design. Requests by UCV suppliers
operating conditions to at least a conventional for increased primary air-supply volumes should
theatre standard throughout the suite with the be resisted.
UCV in set-back mode. It should also be 7.102 Laying-up in the clean zone is preferable for
remembered that suitable levels of ventilation will infection control reasons. Where a preparation
always be required in the peripheral rooms. room/sterile pack store is provided, a transfer grille
7.94 UCV systems can be designed and built from first should be installed in the preparation room/theatre
principles; or a range of bespoke modular units door.
of varying shapes and sizes are available, each 7.103 If the preparation room is intended to be used for
manufacturer having a slightly different approach laying-up instruments, a pressure stabiliser will
to UCV design. Some systems are fitted with be required between the preparation room and
partial or full walls to delineate the clean zone and theatre. It should be fitted with a stand-off baffle
direct a laminar or exponential downflow of air
54
7 Specialised ventilation systems
to prevent air transfer disturbing the ultra-clean 7.108 This arrangement is the preferred option for new
air-flow distribution. installations as it has the following advantages:
7.104 Separate scrub-up or disposal facilities are not • recirculation fans are located outside the theatre,
necessary for air cleanliness, although operational thus reducing noise. Multiple recirculation fans
policy may prefer such a provision. However, can be replaced by a single fan unit with its
a separate anaesthetic room should be provided. drive out of the air stream;
7.105 There is no aerobiological reason why two or more • casual heat gains from recirculation fan(s),
UCV systems should not be installed in a common canopy lights, equipment and people within the
area as long as adequate spacing is provided. This theatre can be removed by a chiller battery in
type of arrangement is known as a “barn theatre” the return air stream. This will prevent heat
and requires special design considerations and build-up in the theatre;
operational discipline.
• return-air filters can be changed without
7.106 The relative positions of the UCV units, needing access to the theatre, making routine
temperature control range and location of doors maintenance more feasible;
and openings to other areas will all significantly
• the opportunity exists to locate HEPA filters in
affect the air flow at the operating positions.
the primary supply duct rather than the theatre
terminal. This will reduce the number of filters
Types of UCV system
required and allow them to be changed without
Remote plant systems entering the theatre.
Auxiliary chiller
with eliminator Attenuator
Recirculation
fan
Drain
Primary conditioned
supply air from main
air handling unit
G3 filter
HEPA filters
UCV canopy with diffuser screen
Return air grille
Operating theatre
55
Heating and ventilation systems – HTM 03-01: Specialised ventilation for healthcare premises – Part A
7.110 Vertical-flow modular units comprise a ceiling- partial walls should be provided to control short-
mounted air-terminal module containing return- circuiting. For a 2.8 m × 2.8 m terminal, the
air filters, return-air fans, final filter and air partial walls should be not less than 1 m from the
diffuser. Primary air is supplied by a remote operating room walls. The clearance should be
air-conditioning unit at the volume and to the increased proportionally for larger terminals (that
standard required for a conventional operating is, 1.15 m for 3.2 m × 3.2 m units; and 1.25 m for
suite (see Figure 7). 3.5 m × 3.5 m units). In all cases, the side walls
should terminate at 2 m above floor level.
7.111 Horizontal- or cross-flow modular units comprise
a wall-mounted air-terminal module standing 7.114 Siting the return-air grilles around the periphery
vertically to produce a horizontal flow of air and of the theatre at low level will eliminate short-
containing final filter/diffuser, return-air filters circuiting, remove the need for partial walls and
and fans. The module may incorporate a full air- give an improved air-flow path. In any event, there
conditioning unit or be supplied with fresh air should be an air-out path on each face or in each
from a separate primary air-conditioning system. corner of the theatre. These may be provided by
combination of pressure stabilisers and passive or
Vertical-flow UCV systems active low-level extract grilles. Failure to provide
7.112 Vertical-flow systems have a superior performance air-out paths on all faces of the theatre may result
and are more effective at reducing infection risks. in the surplus air causing entrainment into the
Air-curtain or partial-wall systems are acceptable, clean zone.
but are known to be more susceptible to problems 7.115 Vertical systems should have a clean zone large
arising from performance deterioration, poor enough to encompass the operating site and all
operating-team discipline and high occupancy of the instrument trays likely to be needed for the
rates than is the case with full-wall systems. A full surgical procedures to be undertaken. Ophthalmic
wall is considered to be any wall terminating not and minor hand surgery would typically require a
more than 1 m above the finished floor level. 1.4 m circular or rectangular terminal. For major
7.113 Because of the large volume of air being moved in orthopaedic procedures, a minimum size of 2.8 m
a relatively small space, the siting of the return-air × 2.8 m will be required. This is the area projected
grilles can cause short-circuiting of the air on the floor under the supply air terminal within
discharged through the UCV terminal. If the the partial walls, full walls or air curtain. Any air
return-air grilles are positioned at high level, outside this zone cannot be guaranteed to be ultra-
Primary conditioned
supply air from main
air handling unit
Recirculation
fan
G3 filter
HEPA filters
UCV canopy with diffuser screen
Return air grille
Operating theatre
56
7 Specialised ventilation systems
clean although – given the dilution factor – the • partial-wall system = 0.38 m/s average;
level of microbiological contamination will be
• full-wall system = 0.30 m/s average.
much lower than the general level in a
conventional operating room. The use of lines or a 7.121 In order to ensure that the terminal quadrants
coloured area on the floor delineating the extent of are in balance, the average air velocity for each
the clean zone will assist staff and is therefore quadrant should not exceed ±6% of the measured
essential. average velocity for the terminal.
7.116 When upgrading an existing conventional theatre Air velocity 1 m above floor level:
to an ultra-clean standard, the only solution may • all systems = 0.2 m/s minimum within the
be the installation of a modular system. In these operating zone.
units, the heat gains from the return-air fans and
terminal lights may warrant the inclusion of 7.122 Chapter 8 gives details of the method of
supplementary cooling within the module. measurement.
However, issues of cooling-coil drainage, 7.123 Variable-speed recirculation fans with differential-
condensate removal and maintenance access within pressure control may be the most suitable solution
the space constraints of the module may make this for maintaining consistent performance and energy
option impracticable. The additional cooling load saving.
should then be accommodated by conditioning
the primary air to compensate. Horizontal UCV systems
7.117 If an existing AHU is to be retained, it may 7.124 Horizontal UCV air-flow systems have been
require modification to ensure that it achieves the shown to be less effective than vertical systems
minimum standards set out in Chapter 4. The fan and are not the preferred solution. There may
may need re-rating to accommodate the change in be occasions, however, where architectural,
system resistance. The cooling coil may also need engineering, economic or workload considerations
to be upgraded to cater for the increased load prevent the installation of a vertical-flow system
resulting from the return-air fans and terminal and only a horizontal-flow system can be installed.
lights. Failure to make adequate provision for this
may make the theatre unusable during prolonged 7.125 Horizontal- or cross-flow modular units comprise
warm spells. a wall-mounted air terminal standing vertically
to produce a horizontal flow of air across the
7.118 A factor affecting air-flow pattern is the supply-air operating field. The terminal module contains the
and room-air temperature difference. When the final filters, air diffuser, return-air grilles, filters
supply-air temperature is significantly above room and fans. The module may incorporate a full air-
temperature, buoyancy effects will reduce the conditioning unit or be supplied with fresh air
volume of air reaching the operating zone. If it from a separate primary air-conditioning system.
is anticipated at design stage that this will be a In the latter case, the return-air fan power may
regular occurrence, a system incorporating full warrant the inclusion of a supplementary cooling
walls should be used. Demountable extensions coil within the module.
that convert a partial wall to a full-wall unit are
available. 7.126 The system should have side-wall panels at least
2.4 m apart. The panels may fold to facilitate
7.119 Convection up-currents from the surgical team cleaning of the theatre. The minimum height of
and operating lamp tend to counter the movement the terminal should be 2.1 m, and a deflector at
of clean air towards the operating site; hence, the the top of the filter/diffuser will be acceptable as
air velocity reaching the operating level is critical. an alternative to a full roof. These dimensions
The minimum velocity given in paragraphs reflect currently available equipment and may
7.120–7.121 has been selected to take account of impose operational constraints in addition to a
these factors and is greater than the theoretical lower level of performance common to these
minimum value. systems.
7.120 For all vertical UCV systems, the design discharge
velocities will be as follows:
Air velocity 2 m above floor level:
57
Heating and ventilation systems – HTM 03-01: Specialised ventilation for healthcare premises – Part A
58
7 Specialised ventilation systems
7.140 The traditional means of light support is a central temperature of the air being supplied by the
column that passes through the UCV terminal UCV terminal;
and is rigidly fixed to the building structure. The
• a read-out sufficiently large to be clearly visible
position of the support therefore prevents air being
from the operating table that shows the relative
supplied at the centre of the terminal. Separate
humidity of the air being supplied by the UCV
supports displaced from the centre of the clean
terminal;
zone would lead to improved air flow.
• a red indicator light that will illuminate when
Note either the supply AHU or the UCV terminal
fails; either or both are switched off or the
This approach was advocated in the 1994 version
AHU and UCV terminal are at set-back;
of this guidance but at the time of writing, no UK
manufacturer has chosen to adopt this solution. • an amber indicator light that will illuminate
when the UCV terminal is at set-back and the
7.141 In horizontal units, the size or shape of the supply AHU is running;
specialised task luminaire has little effect on the • a green indicator light that will illuminate
air-flow pattern. when both the supply AHU and UCV terminal
are operating at full speed;
Controls and instrumentation
• a blue indicator light that will illuminate when
7.142 The functions of the supply AHU and extract the UCV terminal’s HEPA-filter resistance
ventilation should be continuously monitored causes the air delivered to fall below 80% of the
by a BMS control unit. The controls and design flow rate.
instrumentation for the main plant are set out in
Chapter 6. See Table 6.
7.143 UCV systems will additionally require: 7.144 The switching devices and indicators should
be incorporated in the surgeon’s panel and their
• a set-back facility that can reduce the air functions clearly labelled. In retrofit installations,
supplied through the UCV terminal to a an auxiliary panel for the UCV may be the most
volume that equates to an amount not less than practical option. If fitted, it should be mounted
25 air changes per hour of the operating room’s adjacent to the surgeon’s panel and their control
gross volume whilst still leaving the supply functions interlocked as necessary.
AHU operating at full speed;
7.145 When a system is designed to have partial walls
• a facility to turn off the entire system, the with full-wall extensions, a volume control facility
supply AHU and the UCV terminal (an may be incorporated to allow the system to be run
emergency stop is not required); with reduced velocity when the demountable full
• a read-out sufficiently large to be clearly visible walls are in place. It is the responsibility of the user
from the operating table that shows the to ensure correct operation of the system. To assist
59
Heating and ventilation systems – HTM 03-01: Specialised ventilation for healthcare premises – Part A
the user, an explanatory notice should be included multiple safety cabinets, cut-up benches, fume
on the theatre’s control panel. cupboards and specimen stores.
7.146 A direct-reading gauge should be fitted in the 7.151 Typical LEV systems found in healthcare premises
theatre to show a representative pressure drop include:
across the final filters. If the UCV control box
• microbiological safety cabinets and Category 3
is located out of the theatre and has a means
containment rooms;
of manually adjusting the return-air fan speed,
it should also be fitted with a direct-reading • fume cupboards and plate-staining equipment;
differential-pressure gauge. The means of adjusting • welding-fume extracts;
the return-air fan speed should be lockable to
prevent casual adjustment. The direct-reading • woodworking-machinery dust collectors;
gauges should be fitted with a means of indicating • battery-charging bay extracts;
the correct operating pressure range.
• powered plaster and bone saws;
7.147 The UCV-unit manufacturer’s control box should
be located in an accessible position, preferably in • pharmaceutical preparation cabinets and tablet
the operating department adjacent to the operating machines;
theatre that it serves. A service corridor, if • dissection benches, cut-up benches and some
provided, is an ideal location. The control box specimen stores;
should be clearly labelled with the identity of the
operating theatre that it serves. • isolation facilities for medium- and high-risk
infectious diseases;
Extract systems • dental furnaces, grinders and polishers.
7.148 Extracts may be provided for a variety of reasons 7.152 General design information and guidance for
including: LEV systems is produced by the Health and Safety
Executive (HSE) as HS(G)37. Information on the
• simple odour control (for example in a WC or
design and installation of microbiological safety
mortuary);
cabinets is given in BS5726 and that for fume
• to receive and remove moisture-laden air (for cupboards is given in BS EN 14175. Their
example in a kitchen); recommendations should be closely followed.
• as part of a combined supply/extract balanced 7.153 LEV systems are statutory items that are subject to
system (for example in an operating suite); an independent inspection and test at least every
• to capture a hazardous substance at source (for 14 months.
example a safety cabinet).
Hood extract systems
7.149 Devices that use an inflow of air to control
exposure of staff to hazardous substances are Special requirements
classified as LEV systems under the COSHH
7.154 Extract canopies are required over steam-and-heat-
Regulations.
emitting appliances, for example sterilizers, and
7.150 An LEV system may comprise a self-contained catering and washing equipment.
unit incorporating its own carbon filter such as a
7.155 Perimeter-drain gulleys and corrosion-proof grease
simple bench-top fume cupboard. Alternatively, it
eliminators should be provided on kitchen hoods.
may be a complete ventilation system comprising
a make-up air supply, multiple-exhaust-protected Typical arrangements
workstations, branch and central extract ductwork,
duplex extract fans and a high-level discharge 7.156 An air-flow velocity of 0.25 m/s to 0.5 m/s is
terminal. It may also incorporate a special filtration suitable to collect and remove evaporation of steam
system appropriate to the hazardous substance and cooking vapours. Excessive velocities are
being controlled. Such systems could be required wasteful of power and generate noise.
for workshops containing woodworking machinery 7.157 The lowest edge of the canopy should be 2 m
or large centralised pathology laboratories housing above finished floor level, with a minimum of
60
7 Specialised ventilation systems
300 mm overhang beyond the edge of the allow for cleaning). The minimum velocity across
equipment on all sides. any part of the grille should be 1 m/s. The grille
should be readily demountable to allow for
7.158 A compact arrangement of equipment (but with
cleaning.
access for maintenance) will minimise the canopy
area and hence reduce the air volume necessary to
Control of bench extract systems
achieve the optimum capture velocity.
7.165 Provided that it does not interfere with the
7.159 Hoods required for the control of heat gain and
operation of the department when not in use, the
vapours may be connected to the general extract
ventilation system for the bench extract and any
system when it is convenient to do so, but where
associated make-up supply can be shut down.
non-corrosive ductwork materials are necessary,
However, a run-on timer with a minimum setting
a separate discharge is preferred.
of 30 minutes must be provided. To this end, local
7.160 Lighting and internal divider plates are often or automatic-use control should be provided.
included in the perimeter of large canopies;
however, built-in shelving systems are not Safety cabinet and fume-cupboard extract systems
recommended as they interfere with the air flow 7.166 Safety cabinets and fume cupboards are devices
and constitute a maintenance problem. that use an inflow of air to control exposure of
staff to hazardous substances. The units, their
Control of hood extracts
exhaust systems, filters, fans and discharge
7.161 Provided that it does not interfere with the terminals are all classified as local exhaust
operation of the department when not in use, the ventilation (LEV) systems under the COSHH
ventilation system for the hood extract and any Regulations. The make-up air system to a room
associated supply make-up can be shut down. To that contains an LEV system should also be
this end, local or automatic-use control should be considered as an essential part of the system and
provided. be included in the LEV classification.
7.167 Information on the design and installation of
Bench extract systems
microbiological safety cabinets is given in BS5726
Special requirements and that for fume cupboards is given in BS EN
14175. Their recommendations should be closely
7.162 Bench extract ventilation is required in followed. The Advisory Committee on Dangerous
departments such as pathology and mortuary Pathogens (ACDP) publishes ‘The Management,
where activities involve the release of malodorous Design and Operation of Microbiological
fumes or hazardous substances. Where hazardous Containment Laboratories’ covering the general
substances are being controlled, the system should environment in which they are used and
be designated an LEV. operational considerations.
7.163 Processes that produce hazardous vapours, fumes,
dusts or vapours should be enclosed or semi- Special requirements
enclosed in a suitable cabinet or exhaust-protected 7.168 The supply-air system should not distort the
workstation. unidirectional and stable air pattern required
for fume cupboards and microbiological safety
Typical arrangements cabinets. In general, supply-air ceiling diffusers
7.164 Each ventilated position will usually be should not discharge directly towards fume
accommodated in a continuous run of benching, cupboards or safety cabinets, unless the terminal
which should not be more than 650 mm from velocity is such that the air-flow pattern of the
front to rear and which should be provided with cabinet is unaffected. The design should ensure
a continuous upstand at the rear. Each position that high air-change rates and/or the opening and
should have a 1200 mm × 150 mm linear extract closing of doors do not have any adverse effect
grille mounted on a purpose-designed plenum box on the performance of safety cabinets or fume
(incorporating guide vanes as necessary), with its cupboards. A damped door-closure mechanism
face flush with the upstand. The bottom of the may help.
grille should be as close as practicable to the level
of the working surface (usually 75 mm above, to
61
Heating and ventilation systems – HTM 03-01: Specialised ventilation for healthcare premises – Part A
7.169 In order to safeguard the user, all safety cabinets discharge outlet, to maintain the duct within the
and fume cupboards must be fitted with a clear building under negative pressure. The discharge
indication that they are operating correctly. point on a flat roof should be through a 3 m high
Direct-reading gauges or falling-ball indicators terminal. This is required to safeguard staff who
are preferred (in addition to electronic pressure may need to periodically access the roof for
indicators). The system should be set to audibly maintenance. This requirement will also be
alarm if the face velocity falls below the minimum applicable to fume-cupboard discharges.
safe operating level.
7.176 Where this is impracticable, discharge into the
room via a double HEPA filter has been accepted;
Arrangements for safety cabinet installations
the preferred method, however, is to discharge
7.170 A Class 1 microbiological safety cabinet must above the roof line as above.
be specified for routine work involving Group 3
pathogens. It should be housed in a Category 3 Arrangements for fume-cupboard installations
containment room. Information on containment
7.177 The primary factors which contribute to the
rooms is issued by ACDP in ‘The Management,
effective performance of fume cupboards include:
Design and Operation of Microbiological
Containment Laboratories’. • an adequate volume of supply air;
7.171 Siting and installation of microbiological safety • an effective exhaust system to promote the safe
cabinets are of particular importance because: dispersal of waste products to atmosphere.
• protection afforded to the operator by the 7.178 The air velocities through sash openings must
cabinet depends on a specific and stable be sufficient to prevent hazardous materials from
unidirectional air flow through the open front; entering the laboratory while avoiding excess
flow rates that interfere with the investigation
• protection to the environment by the cabinet
process. The design velocity must be maintained
depends on HEPA filters. The exhaust air
irrespective of whether the sash opening is varied
should never be considered as totally free from
or whether doors or windows are open or closed.
microbiological hazard.
Variable air volume (VAV) cupboards are available,
7.172 Extract air from a microbiological safety cabinet which will offer a reduction in energy costs.
is HEPA-filtered prior to discharge to the outside.
7.179 The possibility of a fire or explosion which may
The extract ductwork should as far as practicable
not be contained by a fume cupboard must always
be kept under negative pressure while inside the
be considered. A fume cupboard should not,
building.
therefore, be sited in a position where exit to an
7.173 Current standards permit the installation of escape route will necessitate passing directly in
microbiological safety cabinets with integral fans, front of it.
provided that the extract ductwork can be kept
7.180 Fume-cupboard fans should be installed as near
short (that is, less than 2 m); such an installation,
as possible to the termination of the duct, thus
however, is likely to be noisy and is not
maintaining the maximum amount of ductwork at
recommended for use in new buildings.
negative pressure.
7.174 The discharge from the cabinet should be
7.181 Where there are adjacent buildings with opening
fitted with a back-draught damper. In multiple
windows, or where down-draughts occur, it may
installations where several cabinets discharge into
be necessary to increase the height of discharge
a common extract and discharge duct, it must be
ducts in order to achieve adequate dispersal. In
possible to isolate each cabinet from the system
complex locations, air-flow modelling or wind-
when not in use.
tunnel tests may be required to determine the
7.175 Roof-level discharge, wherever practicable, is optimum height of the stack (see also paragraph
preferred since it removes much of the uncertainty 7.174).
over air re-entering the building through
7.182 Fume cupboards for certain processes must have
ventilation inlets and/or windows. In such an
separate extract systems; however, if permissible,
installation, the extract fan should be situated
individual fume-cupboard exhaust systems may
separately from the cabinet and close to the
discharge via non-returning dampers into a single
62
7 Specialised ventilation systems
7.196 Replacement air should not be drawn through 7.206 The necessary free opening areas for a naturally
pipe trenches or fuel service ducts. Where metal ventilated plantroom may be calculated using the
ducts penetrate walls and floors, effective sealing method in the CIBSE Guides A and B.
should be provided to confine the ventilation
7.207 A combined natural and mechanical ventilation
to the boiler room and to meet fire protection
system should allow for natural extract at high
requirements. Penetration of fire-barrier walls by
level, to take advantage of convective forces in the
ventilation ducts should be avoided if possible.
room, with mechanical supply at low level. The
7.197 Fire dampers in plantroom ventilation ducts high-level natural ventilators should be sized to
should be electrically interlocked with the boiler cope with the total quantity of ventilation air,
plant. as above.
7.198 Care must be taken to prevent any noise generated 7.208 To prevent leakage of flue gases and to ensure that
in the plantroom emerging from natural or the flue draught is not impeded at any time, air
mechanical ventilation openings to the detriment pressure in the boiler room must not exceed the
of the surrounding environment. Particular care is prevailing outside pressure. Therefore, the fan
necessary with mechanical flue draughts and fan- duty should exceed the calculated total combined
diluted flue systems. combustion and ventilation air quantity by at least
7.199 Information on required air volumes in contained
25%. Fan-powered inlets should be arranged to
in the CIBSE Guides A and B. flow outside air into the space at a point where
cross-ventilation will ensure pick-up of heat
7.200 Where combustion plant is installed, the high-level without causing discomfort to occupiers.
(outlet) openings should be sized to cater for the
7.209 Where it is impractical to provide sufficient
total ventilating air quantity, and the low-level
(supply) openings sized to cater for the total natural ventilation to remove the heat emitted by
combined ventilating and combustion air quantity. the plant, both mechanical supply and extract will
be required.
Choice of ventilation system 7.210 The high-level extract should be sized to cater
7.201 Ventilation air may be introduced and exhausted for the total ventilating air quantity, and the low-
by either natural or mechanical means or a level supply should exceed the total combined
combination of both; however, where possible, combustion and ventilating air quantity by at least
natural systems are preferred. 25%, as above.
7.205 Where mechanical air supply is employed, 7.214 As far as practicable, recirculated pool air should
electrical interlocks with the boiler plant should be be provided to the ancillary changing and recovery
provided to prevent damage in the event of failure accommodation, with the only extract from the
of the supply fan(s) once the air volume is toilets, laundry/utility room and pool hall.
established.
64
7 Specialised ventilation systems
7.215 Supply air to the pool hall should be introduced 7.218 Night set-back temperature (in the range of
at high level and directed towards the perimeter to 21–25oC) and high humidity control (in the range
mitigate condensation, with extract air taken from of 60–75% sat) should be provided to override the
directly over the pool. time-clock in order to prevent condensation. The
exact set-points should be ascertained post-
Control of hydrotherapy pool installations installation.
7.216 The supply and extract fans should be interlocked 7.219 A remote indication panel should be provided in
so that the supply fan does not operate until flow the pool hall, giving a visual display of the pool
is established within the extract system. water and pool air temperature.
7.217 Time-clock control should be provided, with
a local override switch to extend the normal
operating period as required.
65
Heating and ventilation systems – HTM 03-01: Specialised ventilation for healthcare premises – Part A
Definitions Commissioning
Commissioning. Commissioning is the process of 8.1 Commissioning is an essential process for
advancing a system from physical completion to an ventilation systems. It is therefore important that
operating condition. It will normally be carried out adequate provision for the process be made at
by specialist commissioning contractors working in the design stage of the project. Procedures for
conjunction with equipment suppliers. Commissioning commissioning air-handling systems are given in
will normally be the responsibility of the main contractor. CIBSE Commissioning Codes and BSRIA
Application Guide Set COMPAK 1.
Validation. A process of proving that the system is fit
for purpose and achieves the operating performance 8.2 The duct-sizing procedure should take into account
originally specified. It will normally be a condition of the requirements of system balancing, and the
contract that “The system will be acceptable to the client position and number of regulating dampers
if at the time of validation it is considered fit for purpose included in the design should be sufficient for
and will only require routine maintenance in order to this purpose.
remain so for its projected life.”
Location of dampers and test holes
Commissioning is often subdivided into sections (for
8.3 Balancing/commissioning dampers should be
example AHU, automatic controls, air-side balance,
installed in each branch of the distribution
building fabric and fittings). Each section may be
ductwork.
commissioned by its specialist installer, and they are
often accepted in isolation. Validation differs from 8.4 Test holes for the measurement of air-flow should
commissioning in that its purpose is to look at the be provided at carefully selected points in main and
complete installation from air intake to extract all branch ducts. The number and spacing of holes
discharge and assess its fitness for purpose as a whole. are given in the BSRIA Application Guide Set
This involves examining the fabric of the building COMPAK 1. Their positions must be identified
being served by the system as well as inspecting the at the design stage.
ventilation equipment fitted and measuring the actual
8.5 The test positions need to be accessible for
ventilation performance.
commissioning to take place. They may also be
It is unlikely that “in-house” staff will possess the required for subsequent annual verification of the
knowledge or equipment necessary to validate critical system performance, so they should be capped to
ventilation systems such as those serving operating prevent air leakage but not covered by permanent
suites, pharmacy clean rooms and local exhaust lagging.
ventilation systems. Validation of these systems should
8.6 The measurement point should be in a straight
therefore be carried out by a suitably qualified
length of duct as far away as possible from any
Authorised Person appointed by the client.
upstream bends, dampers or other elements that
It is anticipated that training and certification in the could cause disturbance to the air flow. The actual
validation of specialised healthcare ventilation systems location should be:
for Authorised Persons will become available during
a. at least 1.5 duct diameters upstream of sources
the life of this Health Technical Memorandum.
of turbulence (such as dampers and bends);
b. if (a) is not possible, ten duct diameters
downstream of dampers, bends or tees, and five
66
8 Validation of specialised ventilation systems
duct diameters downstream of eccentric • full details of the design conditions, both inside
reducers; and out, for winter and summer together with
the control strategy;
c. where there is enough space round the duct to
insert the Pitot tube and to take readings; • the equipment manufacturer’s type-test data,
commissioning, operation and maintenance
d. where the duct has a constant cross-sectional
recommendations;
area.
• drawings showing the layout of the system,
8.7 Test holes for measuring total air-flow from a
positions of air-flow measurement test-points,
fan should be located either four duct diameters
dampers, regulating devices and filters within
upstream or ten duct diameters downstream of the
the duct runs, together with sizes of ducts
fan. Provision should also be made for ascertaining
and terminal fittings. It will save time if these
the direction and measuring the speed of rotation.
drawings are annotated with the design volumes
Commissioning personnel and static pressures required at each branch and
outlet point (see Table 7 for information to be
8.8 It is unlikely that one particular individual will included on schematic drawings);
have all of the required commissioning skills; a
commissioning team is therefore usually needed. • wiring diagrams for all electrical equipment
The objective of commissioning is to ensure that associated with the air-handling systems
the necessary performance and safety requirements including motor control circuit details and
are met. any interlocking and safety devices such as
emergency-stop buttons adjacent to the item of
8.9 During the commissioning process, a great deal of plant.
information will be generated, which will form an
8.12 CIBSE’s Commissioning Code A – ‘Air distribution
invaluable future source of reference about the
plant. It is essential to ensure that it is collected systems’ provides full guidance on the information
together in the form of a commissioning manual that will be required by the commissioning team.
and handed over to the client on completion of the 8.13 The designer should include in the contract
contract together with the as-fitted drawings. The documents instructions on verifying the accuracy
information should be both in hard copy and of test instruments, which should be supported by
electronic format. reference to relevant calibration certificates.
8.10 In order to be successful, the commissioning 8.14 On completion, the system should be operated
process must start before practical completion, as by the contractor as a whole and subject to
many parts of the system will become progressively performance tests in accordance with the contract
less accessible. The correct installation of those requirements. For critical systems, these should
parts will need to be witnessed, and leak-rate tests include independent validation of the system
carried out as construction proceeds. Failure to performance on behalf of the client.
establish responsibility for commissioning early
8.15 The commissioning process should be carried out
enough will delay the completion of the project or
in the order in which it appears in this guidance
lead to unsatisfactory plant performance.
document; that is, the static checks and visual
Commissioning brief inspections should be followed by the dynamic and
performance tests (as outlined in this chapter) and
8.11 The commissioning team will require a detailed finally the handover procedures.
brief from the system designer. This should include:
8.16 Prior to dynamic commissioning, it is essential that
• a user brief comprising a description of the builders’ work in the area served by the system is
installation and its intended mode of operation; complete, all rubbish and dust is removed, Institute
• the precise design requirements with regard of Plumbing service (IPS) panels are in position
to the scheme of air movement, room static and ceiling tiles are in place and clipped. Floors
pressures, supply and extract air-flow rates and should be mopped, and visible dust removed from
acceptable tolerances; all other surfaces.
8.17 Once the system is shown to meet the design
intent, the handover documentation should be
67
Heating and ventilation systems – HTM 03-01: Specialised ventilation for healthcare premises – Part A
completed. In the event of performance not being • that only approved sealants have been used in
acceptable, the matter should be dealt with in the installation;
accordance with the contract arrangements.
• that all components function correctly;
Pre-commissioning checks • that the satisfactory sealing of access doors and
viewing ports have been carried out;
8.18 The pre-commissioning checks consist of visual
inspection, manual operation of equipment, static • that air-pressure tests and air-leakage tests on
measurements and functional tests of individual ventilation ducting have been carried out in
components. They should be carried out prior to accordance with the methods set out in the
setting the system to work and undertaking the HVCA’s (1998) ‘DW/143 – A practical guide to
dynamic commissioning process set out in ductwork leakage testing’. It is usual to carry
paragraphs 8.29–8.42. out these tests a section at a time as the
ductwork is installed and before its insulation is
Standard of installation applied. The results must be recorded in the
commissioning manual;
8.19 During the installation of the system, the following
must be witnessed by either the client or his • that gaps around doors and hatches are as
representative: specified in the design;
• that the plant and installations have been • that the correct operation of pressure stabilisers,
provided and installed in accordance with the and control, isolating and non-return dampers
design specification and drawings; have been checked and installed in the correct
orientation for air flow;
68
8 Validation of specialised ventilation systems
• that test holes have been provided in their 8.22 Builders’ work ducts of brick or concrete must be
specified locations and are sealed with suitable surface-sealed to prevent the release of dust before
grommets; being taken into use.
• that control dampers are secured and their 8.23 The area around the supply-air intake must be free
quadrants fitted correctly; of vegetation, waste, rubbish, builders’ debris or
any other possible source of contamination.
• that any interlocks are operative and in
accordance with specification;
Certification of equipment
• that the electric circuits are completed, tested
8.24 The following test certificates should be assembled
and energised;
by the commissioning team and be available for
• that electric motors have been checked for inspection at any time during the contract period.
correct direction of rotation at both full speed They will form part of the handover information
and set-back; and should be placed in the commissioning
manual:
• that cooling and heating media are available
at correct temperatures and pressures, and in • type-test performance certificates for fans;
specified quantities;
• pressure-test certificates for:
• that the air-conditioning plant’s components
– heater-batteries;
and controls function correctly;
– cooling coils;
• that the air-conditioning plant’s interlocks and
safety controls function correctly; – humidifiers (if appropriate);
• that the plant is physically complete, insulation • type-test certificates for attenuators;
is applied, and all ducts and pipework are • type-test certificates for primary and secondary
identified as specified; filters;
• that the building housing the ventilation plant • individual test certificates for HEPA filters.
is generally in a fit condition for commissioning
and performance tests to commence – that is, Equipment tests
windows, doors, partitions etc are completed,
surfaces sealed and their final finish applied; 8.25 Prior to setting the system to work, the checks in
paragraphs 8.26–8.28 should be witnessed, and
• that the areas containing the ventilation plant proving tests should be carried out as detailed.
and those being served by it are clean;
• that access to all parts of the system is safe and Filters
satisfactory. 8.26 The quality of filter housing and, in particular, seals
is a critical factor in maintaining the efficacy of the
Cleanliness of installation filtration system by ensuring that air does not
8.20 During installation it must be established that bypass the filter panels. Therefore, the following
ductwork is being installed to the “advanced level” checks should be made:
as defined in the HVCA’s (2005) ‘TR/19 – Guide • filter seals should be fitted and in good
to good practice: internal cleanliness of ventilation condition;
systems’. This specifically includes ensuring that
ductwork sections arrive on site and are stored with • filters should be installed correctly with respect
their open ends sealed and that open ends remain to air flow;
sealed during installation to prevent the ingress of • bag filters should be installed so that the bags
builders’ dust. are vertical and their pockets free;
8.21 Should any doubt exist as to whether the guidance • HEPA filters should be installed in a sealed
has been observed, the ducts must be cleaned housing and their seals tested to DIN 1946 if
internally to restore them to this standard before specified;
being taken into use.
69
Heating and ventilation systems – HTM 03-01: Specialised ventilation for healthcare premises – Part A
Drainage arrangements 8.30 After the installation has been checked to ensure
that it is in a satisfactory and safe condition for
8.27 The drain should conform in all respects to start-up, it should be set to work and regulated to
the guidance given in this Health Technical enable the plant to meet its design specification.
Memorandum. In addition, the following must be The proportional balancing method described
proved: in CIBSE’s Commissioning Code A should be
• that the drain tray is easily removable; followed. The air-flow rates must be set within the
tolerances laid down in the design brief. This will
• that a clear trap is fitted and is easily removable; normally be the design air-flow rate +10% –0%,
• that the drain has a clear air gap of at least that is, the measured value must at least achieve the
15 mm; design but must not exceed it by more than 10%.
• that the pipework and trap are supported so 8.31 When combined supply and extract systems are to
that the air break cannot be reduced; be balanced and the area that they serve is to be at
or above atmospheric pressure, the supply should
• that the drain system from each drain tray is be balanced first with the extract fan switched off,
independent up to the air break; and then the extract balanced with the supply
• that the operation of the drainage system is fan(s) on.
proved by introducing water into the duct at 8.32 For combined systems where the area that they
the drain tray and observing that it completely serve is to be below atmospheric pressure, the
drains out. This check is to be repeated both at extract should be balanced first with the supply fan
normal speed and set-back once the fans have switched off and then the supply balanced with the
been commissioned. At this time, the clear trap extract fan on.
can be marked to indicate the normal water
level with the fan running. 8.33 On completion of the balance, all volume air flows
in supply and extract ducts and from grilles and
Fire dampers diffusers must be measured and recorded. The true
air-change rate can then be calculated from the data
8.28 The following must be witnessed, and proving tests
obtained.
should be carried out as detailed:
8.34 The main supply and extract duct-volume control
• the operation of all fire dampers;
dampers should be locked and their position
• access provided to enable the dampers to be marked.
visually inspected and/or re-set should be
8.35 All grille and diffuser volume-control registers
sufficient for the purpose;
should be locked to prevent alteration and their
• indication should be provided of the dampers’ final position marked.
position (open/tripped);
Room-air distribution
• indication of the fire dampers’ location should
be provided both on the ductwork and at a 8.36 Pressure-relief dampers and pressure stabilisers
visible point on the building fabric if the should be set to achieve the specified room’s
ductwork is concealed. static pressures and should be locked. The grille’s
direction-control vanes and diffuser cones must
be set to give the specified air-movement pattern.
Visualisation techniques may need to be employed
in order to prove that the required air-flow
pattern is being achieved. This may be a particular
70
8 Validation of specialised ventilation systems
requirement when commissioning LEV systems or external winter and summer design conditions
rooms that contain them. must be proved. Artificial loads will be required in
order to simulate the internal gains/losses and the
Air-conditioning plant external design conditions.
8.37 The specified flow rate and/or pressure drops must 8.46 On completion of the plant’s performance test,
be set for all heater-batteries, cooling coils and recording thermo-hygrographs should be placed
humidifiers. The methods described in CIBSE’s in each room/area served by the plant and also the
Commissioning Codes W and R should be supply-air duct upstream of the fog/frost coil. The
followed. On completion, their regulating devices plant should be run for 24 hours with all doors
must be locked to prevent alteration. closed. During this period, the inside conditions
must stay within the tolerances specified.
Control system Alternatively the BMS may be used to obtain the
8.38 The control system should not be commissioned information required.
until both the air distribution system and air-
conditioning equipment have been commissioned. Noise levels – general
8.47 The commissioning noise level is that measured
8.39 Because of the specialised nature of control systems
and the fact that each manufacturer’s system will with a sound-level meter in the unoccupied room,
contain its own specific components and settings, taking account of the external noise together with
the commissioning should be completed by the the noise generated by the ventilation system.
supplier and contractor before being witnessed by a Appendix 2 gives a summary for many applications.
representative of the client. Full details and design information are contained
in Health Technical Memorandum 08-01 –
8.40 The location of all control and monitoring sensors ‘Acoustics’.
should be checked and their accuracy proved.
8.48 The noise levels apply at the maximum velocity for
8.41 The control system’s ability to carry out its specified which the system is designed to operate. Acoustic
functions must be proved. In this respect it is commissioning tests should be carried out with
essential that control indication lights on the panel all plant and machinery running normally and
or mimic on the BMS actually relate to the running achieving the design conditions of air flow,
of a specific fan or movement of a damper. temperature and humidity.
8.42 If the plant is provided with a user’s control panel 8.49 An industrial-grade Type 2 sound-level meter fitted
in addition to the one located in the plantroom, with a muff will normally be sufficient to check the
the operation of both must be proved. This will noise level. Its accuracy should be checked using a
typically apply to operating departments and calibrated sound source before use.
laboratory systems.
8.50 The noise-level readings should be taken at typical
normal listening positions 1.5 m above floor level
Specific performance standards and at least 1 m from any surface, and not on any
line of symmetry. In critical care areas, the noise
Air movement
should be measured near to the centre of the room
8.43 The performance of the system should be measured and near to the centre of each quarter. The mean of
and compared with information provided by the the five readings should then be calculated.
designer.
8.51 In the event of a contractual deficiency, a Type 1
Plant capacity and control precision-grade sound-level meter should be used,
and the noise level determined by the procedure
8.44 When setting to work and proving the design, given in Health Technical Memorandum 08-01.
both the contractor responsible for the air-handling
plant and the control specialist should attend the Filter challenge
site together and jointly commission the system.
General ventilation filters
8.45 If any doubt exists as to the capacity of the installed
system, its ability to achieve the specified internal 8.52 In-situ performance tests will not normally be
design conditions with the plant operating at required for primary and secondary filters and
71
Heating and ventilation systems – HTM 03-01: Specialised ventilation for healthcare premises – Part A
their housings. However, filters should be visually 8.58 Should the HEPA filter fail this test, it must be
inspected for grade, tears, orientation and fit within replaced. Should the filter mounting seal or
their housings. Filters should be clean and a housing fail this test, it may be repaired and the test
replacement set should be available. Bag filters repeated.
should be installed so that their bags are vertical,
and spaced so that air can move through them Bacteriological sampling
freely. Any filter found to be wet should be replaced
and the cause investigated. General ventilation systems
8.59 Bacteriological sampling will not normally
HEPA filters (for exhaust protective enclosures and be required for either general or local exhaust
laboratories) ventilation (LEV) systems unless otherwise
8.53 Pathogenic material may be discharged through specified.
damaged or badly installed HEPA terminal filters.
The complete installation must be tested using Conventional operating rooms
the method set out in BS EN: 14644 ‘Method of 8.60 Before commencing bacteriological testing,
Testing for the Determination of Filter Installation the room and its ventilation system should
Leaks’. have achieved a steady state condition (see also
8.54 The challenge tests may be carried out using either paragraph 8.75).
of the following techniques: 8.61 The level of airborne bacteria introduced by the
• use DOP to provide the challenge and a supply air should be checked by closing all doors
photometer to detect leaks; and leaving the operating room empty with the
ventilation system running for 15 minutes.
• use a discrete particle counter (DPC) to detect An active air sampler set to take at least a 1 m3
leaks. (In order to obtain a sufficient challenge, sample and mounted in the centre of the room
it may be necessary to temporarily remove the approximately 1 m above floor level should then
supply AHU’s secondary filters.) be activated remotely. Aerobic cultures on non-
8.55 In both cases, the upstream challenge should be selective media should not exceed ten bacterial and/
measured. A measurement of particle penetration or fungal colony forming units per cubic metre
through a representative section of the HEPA-filter (CFU/m3).
media is then taken and used as the reference 8.62 The results should be examined to establish
background level. These two readings enable the the broad category of organisms present. A high
range of the detecting instrument to be set. preponderance of fungal organisms may be an
8.56 A challenge aerosol of inert particles of the indication of inadequate filtration for the particular
type produced by a DOP generator should be installation. Precise guidance is inappropriate and
introduced into the air, upstream of the HEPA will depend on local circumstances.
filter. The downstream face of the filter, its 8.63 A check of airborne bacteria should be carried
mounting seal and housing would then be scanned out during a surgical operation. Unless there are
for leakage using a photometer. A leak should be unusually high numbers of personnel or extensive
deemed to have occurred if a steady and repeatable activity in the room, the number of airborne
reading on the photometer at any point exceeds bacterial and/or fungal CFU averaged over any five-
0.01% of the upstream reading. minute period would be unlikely to exceed 180 per
8.57 Alternatively, a DPC may be used. For the DPC m3.
method, the filter face is sampled at several points
to establish the smallest non-penetrating particle The Hospital Infection Society has issued guidance
size. This will directly relate to the grade of filter on the microbiological testing of operating theatres
under test. The filter face, its seal and housing (www.his.org.uk/_db/_documents/OTIC-final.pdf ).
are then scanned, and if a significant number of Information on the additional validation testing
particles at or above this size are detected, there is of UCV operating suites is given in paragraphs
deemed to be a leak at or near the test position. 8.66–8.164.
72
8 Validation of specialised ventilation systems
Ventilation system commissioning/validation 8.69 The following regime of inspection and testing
report should be applied to the validation of new
installations designed to provide ultra-clean
8.64 Following commissioning and/or validation, a full
conditions in an operating suite. The test regime
report detailing the findings should be produced.
has been devised to ensure that the system, as
The system will only be acceptable to the client
installed, fully achieves the design requirement for
if at the time of validation it is considered fit for
these systems as set out in paragraphs 7.91–7.147.
purpose and will only require routine maintenance
in order to remain so for its projected life.
Basic requirement
8.65 The report should conclude with a clear statement
8.70 The operating suite to be validated should be
as to whether the ventilation system achieved or
physically complete with final finishes applied. All
did not achieve the required standard. A copy of
ventilation systems serving it should be operating
the report should be lodged with the following
correctly and delivering their design air-flow rates.
groups:
8.71 In order to avoid preloading the UCV terminal’s
• the user department;
recirculation ducts and HEPA filters, the operating
• infection control (where required); suite should be free of any obvious dust and at least
“builders clean” before the recirculation fans are set
• estates and facilities.
to work (see also paragraph 8.16).
Validation of UCV operating suites 8.72 The validation procedure for a conventional theatre
suite should have been satisfactorily completed to
General the standard set out in this chapter prior to
attempting to validate the UCV unit. In particular:
8.66 Commissioning of a UCV terminal will normally
be carried out by its supplier. Commissioning of • the supply AHU will have achieved the
the AHU, fire dampers, distribution ductwork and minimum standard;
control systems may be undertaken by different • the operation of all fire dampers will have been
teams. It is therefore important to recognise that proved;
the UCV terminal is only one element of the
specialised ventilation system serving the operating • the supply and extract air-flow rates as measured
suite, and it cannot be accepted in isolation. in ducts and at room terminals will achieve their
design values +10% –0% (see paragraph 8.30);
8.67 In order to ensure that the complete system
operates correctly, it will be necessary to validate • the room’s differential pressures will be correct.
the system as a whole from the air intake through 8.73 Evidence of the satisfactory achievement of the
to the extract discharge. foregoing standards should be available for
8.68 It is unlikely that in-house staff will possess the inspection and independently measured as
knowledge or equipment necessary to undertake necessary prior to validating the UCV unit.
this process. Therefore, a suitably qualified
Authorised Person appointed by the client should UCV unit validation procedure
carry out the validation of ultra-clean operating 8.74 Tests to validate the suitability and performance of
theatre ventilation systems. an ultra-clean operating suite should be undertaken
in the order that they appear in Table 8. Should an
Note item fail to meet the required standard, it should be
It is anticipated that training in the validation rectified and successfully retested before passing on
of specialised healthcare ventilation systems for to the next test.
Authorised Persons will become available during the
life of this Health Technical Memorandum.
73
Heating and ventilation systems – HTM 03-01: Specialised ventilation for healthcare premises – Part A
Table 8 Summary of test regime projected by the inside dimensions of the side walls
or boundary air curtain. A suitably marked test
1. C
hallenge tests to ensure that: sheet will provide a consistent standard of test grid.
• the UCV terminal unit is correctly assembled and
sealed so that no air will bypass the filters; 8.79 The test grid should comprise test squares of
280 mm each side.
• the terminal filters are correctly sealed in their
housings; 8.80 The test grid should be aligned along the centre
• the terminal filters are of the same grade, of uniform lines of the terminal footprint with its centre under
quality and undamaged. the centre point of the terminal.
2. A
ir velocity measurements to ensure that: 8.81 Any test square with 80% or more of its area within
• a sufficient quantity of air is being delivered by the the UCV footprint should be used as a test
terminal; position.
• the terminal quadrants are in balance; 8.82 An inner zone should be designated that is not
• the air flow has sufficient velocity to reach the working less than 36% of the total footprint. It should be
plane. made up of a number of test squares distributed
3. A
n entrainment test to ensure that contaminants arising symmetrically about the terminal footprint’s centre-
outside of the UCV terminal footprint are not drawn into line. Regardless of the shape of the terminal
it. footprint, the inner zone should comprise a
4. V
isualisation techniques to gain an understanding of the minimum grid of 6 × 6 test squares.
overall system performance. 8.83 Unless specified otherwise, a test position should be
5. N
oise measurement to ensure that working conditions are in the geometric centre of a test square.
satisfactory.
8.84 Test position 1 should be the leftmost test square
6. C
ontrol system checks to ensure that the system operates
as specified.
in the row nearest to the operating room wall that
houses the surgeon’s panel.
7. B
iological monitoring to determine how effective the
system is in use. 8.85 Figure 8 shows a grid for a 2.8 m × 2.8 m terminal.
74
8 Validation of specialised ventilation systems
Surgeon’s panel
1 2 3 4 5 6 7 8 9 10
A + + + + + + + + + +
1
A + B + x x x x x x x + +
280 mm
C + x x x x x x x + +
280 mm D + x x x x x x x + +
E + x x x x x x x + +
Measure velocity
+ at 2 m above floor
F + x x x x x x x + +
level
Measure velocity G + x x x x x x x + +
x at 2 m and 1 m
above floor level H + x x x x x x x + +
I + + + + + + + + + +
Centre point
J + + + + + + + + + +
• use DOP to provide the challenge and a UCV terminal unit clean zone leak test
photometer to detect leaks;
8.94 This test will confirm that there is no unfiltered air
• use a DPC to detect leaks. (In order to obtain bypassing the HEPA filter.
a sufficient challenge, it may be necessary to
8.95 The joints and service penetration points under the
temporarily remove the supply AHU’s
UCV terminal within its side walls or boundary air
secondary filters.)
curtain should be scanned to prove that there are
8.91 In both cases, the upstream challenge should be no leaks.
measured. A measurement of particle penetration
8.96 A leak is defined as a significant rise above the
through a representative section of the HEPA-filter
background level.
media is then taken and used as the reference
background level. These two readings enable the Terminal HEPA filter seal leak test
range of the detecting instrument to be set.
8.97 This test will confirm that there is no unfiltered air
8.92 For the DOP test, this should be set as the
bypassing the HEPA filter’s seal.
reference level, and a leak will be declared
significant if penetration greater than 0.01% of the 8.98 Each HEPA filter’s seal should be scanned to prove
range is detected (see paragraph 8.56 for details). that there are no leaks.
8.93 For the DPC method, the filter face is scanned to 8.99 A leak is defined as a significant rise above the
establish the smallest non-penetrating particle size. background level.
If significant particles at or above this size are
detected when subsequent scans are made, there Terminal HEPA filter media leak test
is deemed to be a leak at or near the test position 8.100 This test will confirm that the HEPA filters have
(see paragraph 8.57 for details). not sustained damaged while being installed.
75
Heating and ventilation systems – HTM 03-01: Specialised ventilation for healthcare premises – Part A
8.101 The face of each HEPA filter should be scanned to 8.108 Readings are to be taken at the test positions –
prove that there are no leaks. with the instrument probe facing the wall that
houses the surgeon’s panel – commencing at the
8.102 A leak is defined as a significant rise above the
first test position. Readings are taken either
background level.
working along the row from left to right and back,
Vertical UCV terminal air velocity tests or for all test positions in one quadrant at a time.
8.109 When all the test positions under one half of
Test set-up the terminal have been covered, readings of
a. The terminal face diffuser screen should be in temperature and humidity are taken at the
place for these tests. specified height in the centre of the terminal.
The read-outs on the surgeon’s panel should be
b. Take spot readings to establish that the room is recorded at the same time.
within the specified temperature and humidity
test conditions. 8.110 Having completed one half of the test grid, the
operating lamp arms and any other stem arms
c. Set out the test grid as described in paragraphs should be swung round through 180 degrees and
8.78–8.85. the test stand reversed so that the wall that houses
d. Swing the operating lamp arms and any other the surgeon’s panel is behind the test person.
stem arms so that they align to present the least Readings are recommenced starting at the right of
resistance to air flow, are perpendicular to the the test row and working from right to left or a
front edge of the test sheet, and face the back quadrant at a time, as above.
edge. Any lamp and equipment heads should
as far as practicable be outside of the UCV UCV high level discharge velocity test
terminal footprint. 8.111 Measurements of air velocity are to be taken at
every test position 2 m above floor level, and the
Test instrument results averaged.
8.103 The measuring instrument should be a hot- 8.112 The average of the total readings taken is to be not
wire anemometer with a digital read-out. The less than:
instrument resolution should be at least 0.01 m/s,
have a tolerance of ±0.015 m/s or 3% of the • 0.38 m/s for a partial-wall system;
reading, and be calibrated down to 0.15 m/s or • 0.30 m/s for a full-wall system.
lower. An alternative instrument may be used,
8.113 The average air velocity for each quadrant should
providing it is of no lesser specification.
not exceed ±6% of the measured average velocity
Test method for the terminal.
8.104 The instrument should be mounted on a test stand UCV low level air velocity test
and set to record a mean reading over a ten-second
8.114 Measurements of air velocity are to be taken at
sample interval.
each of the inner zone test positions 1 m above
8.105 It is recommended that a printer be linked to floor level.
the test instrument so that readings are recorded
8.115 The measured velocity at every test position in
automatically. Alternatively they could be
downloaded to a computer or data logger at the the inner (operating) zone should be not less than
end of the test. 0.2 m/s.
8.106 The test stand should be positioned at each test Horizontal UCV terminal air velocity test
point in turn and the reading taken when the
instrument has stabilised. Test set-up
8.107 When taking a reading, the test person should a. Set out the line of test positions as described
not stand within the same quadrant as the test previously.
instrument.
b. Swing the operating lamp arms and any other
stem arms so that they align to present the least
76
8 Validation of specialised ventilation systems
resistance to air flow and are perpendicular to 8.127 UCV systems having permanently fitted full side
the line of test positions. walls do not need to be tested, as the side walls
physically prevent entrainment.
Test instrument
Principle of the test
8.116 See paragraph 8.103.
8.128 A source of particles is produced outside of the
Test method UCV terminal and is used to challenge the system.
8.117 The instrument should be mounted on a test stand A detector is placed within the ultra-clean air flow
and set to record a mean reading over a ten-second and used to determine the percentage penetration
sample interval. of the test particles at predefined locations under
the UCV terminal footprint. The source and
8.118 It is recommended that a printer be linked to detector are moved in tandem around the UCV
the test instrument so that readings are recorded canopy and pairs of readings taken, from which
automatically. Alternatively, they could be the percentage penetration at specified locations
downloaded to a computer or data logger at the is calculated. The degree of penetration should be
end of the test. below specified maximum limits if entrainment is
8.119 The test stand should be positioned on each test to be declared not significant.
point in turn and the reading taken when the 8.129 The entrainment test may be carried out using
instrument has stabilised. either of the following techniques:
8.120 When taking readings, the test person should • use DOPs to provide the challenge source at
stand well downstream of the instrument. the specified release position and a photometer
8.121 Readings are to be taken at the test positions – to measure the entrainment; or
with the instrument probe facing the UCV • duct non-HEPA-filtered air to the specified
terminal – commencing at the first test position release position and use a DPC to measure the
on the left and working along the row from left entrainment.
to right at the specified height.
8.122 The instrument should be reset to the next Test set-up
specified height and the test repeated, and so on. a. The terminal face diffuser screen should be in
8.123 Readings of temperature and humidity should be place for these tests.
taken at the specified height in the centre of the b. The test should be performed without any
terminal. The read-outs on the surgeon’s panel equipment in place beneath or closely adjacent
should be recorded at the same time. to the UCV terminal.
77
Heating and ventilation systems – HTM 03-01: Specialised ventilation for healthcare premises – Part A
Test equipment
a. Challenge source, measuring instrument and
Note
detector head The use of DOP for testing is gradually being phased
out and replaced by a natural challenge measured with
8.130 The challenge and detector equipment should be
a DPC. At the time of writing research is under way
chosen so that:
to more precisely define a challenge source unit for
• the tracer particles are mainly within the size natural particles. It is anticipated that such a unit,
range 0.3–5 μm and thus capable of remaining together with a matching test methodology, will
airborne for a substantial time; become available during the life of this Health
• the particles used should not be able to Technical Memorandum.
penetrate the terminal filters in sufficient
numbers to cause a background count that is The detector
more than 0.1% of the challenge count;
8.133 This may be a photometer or a DPC. It is
• the choice of particle and detector will enable recommended that a printer be linked to the
a minimum of a three-logarithm (1000-fold) test instrument so that readings are recorded
range of counts to be recorded between the automatically. The instrument should be capable
highest (that is, source) and lowest (that of sampling a minimum of 28.3 L of air (1 ft3)
is, background) readings expected. per minute and, in the case of the DPC, provide
(A concentration of approximately 105 particles readings for particle size ranges from 0.3 µm to
per cubic metre of source air has been shown to 5 µm and greater. The instrument should be
be adequate.) compliant with the requirements of BS EN ISO
14644-1. An alternative instrument may be used
b. Challenge source – DOP providing it is of no lesser specification.
8.131 The DOP generator should be able to produce
a cloud of test particles in the form of a visible Test positions and orientation of source and
smoke. The test smoke should be delivered via an detector
aperture so that it flows vertically downward from 8.134 The test positions should be at the centre of each
the lowermost edge of the partial wall, on the test square, as defined for the velocity test.
outside of the UCV canopy.
8.135 For rectangular UCV terminals, measurements
of penetration are to be taken at the four corner
Note test squares of the test grid and at intermediate
To prevent undue contamination of the theatre and positions along the line of test squares between the
filters with deposits of oil, DOP should only be corners. The number of intermediate test positions
released for the minimum amount of time necessary to should be as equally spaced as possible around the
complete the test. periphery, with no fewer than three and no more
than five complete test squares between test
positions.
c. Challenge source – natural particles
8.136 A further series of measurements are to be
8.132 The source unit should be a fan/blower or other
obtained around the periphery of the inner zone.
method that takes non-HEPA-filtered air and
Measurements of penetration are to be taken at the
expels it via a delivery head at the specified release
four corner test squares of the inner zone of the
position to provide the particle challenge. The
test grid and, if necessary, at intermediate positions
challenge air should be delivered vertically
along the line of test squares between the corners
downwards from the lowermost edge of the partial
as equally spaced as possible, with no fewer than
wall, on the outside of the UCV canopy, parallel
three and no more than five complete test squares
to the air flow coming from the diffusers. The
between test positions.
challenge air velocity should be the same as the
measured average velocity at 2 m for the terminal 8.137 A single measurement should be taken at the
under test. geometric centre of the UCV terminal footprint.
The centre measurement should be taken with the
78
8 Validation of specialised ventilation systems
79
Heating and ventilation systems – HTM 03-01: Specialised ventilation for healthcare premises – Part A
Control functions
UCV validation report
8.156 The operation of all control functions provided
on the surgeon’s panel should be proved for 8.163 Following validation, a full report detailing the
conformity with the design specification. findings should be produced. The report should
conclude with a clear statement as to whether the
8.157 If an auxiliary panel has been fitted, its
UCV theatre suite achieved or did not achieve the
interlocking with the control functions of the standard set out above.
main surgeon’s panel must be proved to conform
to the design specification. 8.164 A copy of the report should be lodged with the
following groups:
Panel indicator lights • operating department;
8.158 The panel indicator lights should illuminate as • infection control;
appropriate when the control functions are selected
or warning levels are reached. • estates and facilities.
80
Appendix 1 – Use and function of typical
equipment used in ventilation
systems
A1.1 Typical equipment used in ventilation systems is d. plant-isolating dampers are fitted so that
listed below together with a brief description of the main plant can be isolated from its air
both function and use. distribution duct system. They are manually
operated, and enable cleaning and maintenance
General of the air-conditioning equipment to be carried
out.
A1.2 The equipment built into the ventilation system
and its ductwork should be of a type that will
neither cause nor sustain combustion.
Ducting
A1.6 Ducting is the means by which air is conveyed
A1.3 No materials that could sustain biological activity
from the intake to its point of use. It is usually
should be used in the construction or assembly of
constructed of galvanised steel and will normally be
the system.
insulated to reduce noise and conserve energy.
Ducts can also be formed in concrete, brickwork,
Air intake stainless steel or plastic, and may be rigid or
A1.4 An uncontaminated air supply to the system is flexible.
essential. In order to achieve this, the air intake
should be positioned so that air discharged from Fan
extract systems or other sources of dubious quality
A1.7 A fan is a series of rotating blades that move the air
cannot be drawn in. Exhaust fumes from vehicles
in the direction required. Fans are usually powered
can present particular problems. The area
by electric motors either directly connected to them
surrounding the intake will need to be kept clean
or driven through belts and pulleys. A fan may be
and free of vegetation and waste material in order
arranged to either force air into or draw air from a
to reduce the possibility of biohazards or fire. The
ductwork system.
intake itself should be protected by a louvre and
mesh screen to prevent rainwater, vermin and leaves
etc entering the system. Attenuator/silencer
A1.8 An attenuator is a device that will contain and
Damper absorb the noise emitted by a fan. It may be
required to reduce disturbance caused by noise
A1.5 Several types of damper may be fitted:
breaking out through the air intake and also noise
a. automatic dampers fitted immediately behind transmitted along the ductwork to the conditioned
the air intake and extract louvres. They will space.
automatically close when the system is shut
down in order to prevent an uncontrolled Filter
circulation of air;
A1.9 A filter consists of a labyrinth of fibrous material
b. balance dampers are fitted into each branch contained in a frame. It is designed to capture
of the air distribution ductwork system so that and hold particles being carried in the air stream.
the design air-flow rate can be set during the Because of the size range and number of particles
commissioning process; that exist in air, no filter can remove them all.
c. where ductwork passes through a fire The purpose of filtration is to reduce their number
compartment wall, ceiling or floor, a fire and/or and size range to an acceptable level. Filters of
smoke damper may be required; progressively higher grades are fitted through the
ventilation system:
81
Heating and ventilation systems – HTM 03-01: Specialised ventilation for healthcare premises – Part A
82
Appendix 2 – Recommended air-change rates
Pressure Supply Noise Temp Comments (for further
Application Ventilation AC/hr
(Pascals) filter (NR) (°C) information see Chapter 6)
General ward S/N 6 – G4 30 18–28
Communal ward toilet E 6 –ve – 40 –
Single room S/E/N 6 0 or –ve G4 30 18–28
Single room WC E 3 –ve – 40 –
Clean utility S 6 +ve G4 40 18–28
Dirty utility E 6 –ve – 40 –
See Health Building Note
Ward isolation room – – – – – –
04-01 (Supplement 1)
Infectious diseases Extract filtration may be
E 10 –5 G4 30 18–28
isolation room required
Neutropeanic patient
S 10 +10 H12 30 18–28
ward
Isolation room may be –ve
Critical care areas S 10 +10 F7 30 18–25
pressure
Birthing room S&E 15 –ve G4 40 18–25 Provide clean air-flow path
Isolation room may be –ve
SCBU S 6 +ve F7 30 18–25
pressure
Preparation room (lay-up) S >25 35 F7 40 18–25
Preparation room/bay *50 NR if a bay in a UCV
S 10 25 F7 40* 18–25
(sterile pack store) theatre
Operating theatre S 25 25 F7 40 18–25
H10 or *Fresh-air rate; excludes
UCV operating theatre S 25* 25 50 18–25
greater recirculation
Anaesthetic room S&E 15 >10 F7 40 18–25 Provide clean air-flow path
Theatre sluice/dirty utility E >20 –5 – 40 –
Recovery room S&E 15 0 F7 35 18–25 Provide clean air-flow path
Catheterisation room S 15 +ve F7 40 18–22
Endoscopy room S 15 +ve F7 40 18–25
Endoscopy cleaning E >10 –ve – 40 –
Day-case theatre S 15 +ve F7 40 18–25
Treatment room S 10 +ve F7 35 18–25
# See EGGMP (Orange
Pharmacy aseptic suite S 20 # H14 – 18–22
guide) a
Category 3 or 4 # See ACDP guide; *Filter in
# >20 # H14* – 18–22
containment room extract
S = 10
Post-mortem room S&E –ve G4 35 18–22 Provide clean air-flow path
E = 12
Fan accessible from outside
Specimen store E – –ve – – –
of store
8–22oC indicates the range over which the temperature may float.
Notes: 1
18–22oC indicates the range over which the temperature should be capable of being controlled.
S = suppy
E = extract
N = natural ventilation
a–E uropean guidelines on good manufacturing practice published by the Medicines and Healthcare products Regulatory
Agency (MHRA)
83
Heating and ventilation systems – HTM 03-01: Specialised ventilation for healthcare premises – Part A
84
Appendix 4 – Leakage flows in m3/s through
closed door gaps
Designers’ notes:
The door gaps assumed are 4 mm along the bottom, 3 mm at the top and sides, and 2 mm between double leaves.
If doors are fitted with cold smoke seals, these will significantly reduce the door leakage rate when new and undamaged. It is
therefore recommended that provision for the design leakage be factored into the size of the appropriate transfer grille or pressure
stabiliser. Failure to do this will result in air-gap whistles and doors being held partially open by air pressure.
Factory-assembled door-sets with a steel frame and pre-hung leaves are becoming common. There is effectively no leakage across
these doors when closed. Therefore, when this type of door assembly is fitted, the door leakage can be ignored and the design air
flow into the room reduced accordingly. The design air flow would then become that required either (i) for open door protection
(Appendix 5), or (ii) to achieve the specified air-change rate – whichever is the greater.
85
Heating and ventilation systems – HTM 03-01: Specialised ventilation for healthcare premises – Part A
86
Appendix 6 – Typical approximate pressures in
an operating suite when a given
door is open
87
Heating and ventilation systems – HTM 03-01: Specialised ventilation for healthcare premises – Part A
Is it a new build
operating suite?
YES NO
It is a refurbishment
Is it a
conventional suite?
Is it a scheme
based on a standard
layout from
NO YES HTM 03-01?
NO YES
Does it have NO
a “lay-up” prep?
YES
YES
Do the room NO
sizes accord with
HBN 26 Vol 1?
YES
88
Appendix 7 – Operating suite standard design solutions
Room Size (m3)‡ Air-change rate (AC/hr) Nominal pressure (Pa) Flow rate (m3/s)
Theatre 165 25 25 1.15
Anaesthetic 57 15 >10 0.24
Lay-up-prep 36 >25 35 0.28**
Scrub * – 25 –
Notes:
‡ Derived from Health Building Note 26.
* This is a separate scrub and is not considered as being part of the theatre volume.
** Interchange is not permitted between the theatre and lay-up prep; therefore, as in Appendix 5, an air-flow protection of
0.28 m3/s is required as a minimum (but see also the “designers’ notes” in Appendix 4).
The volume of air to be extracted from the theatre should be determined by subtracting the air flow required for door protection
at the key door from the total air entering the space. The balance should be equally divided between the passive or active extract
locations.
The extracts within the theatre may be either passive and fitted with pressure stabilisers, or active and connected to the extract
system. They should where possible be located at low level and positioned to promote the ventilation of all areas of the space
Corridor 0
KEY TO SYMBOLS
>10 0.24
Supply volume (m3/s)
Anaesthetic Scrub
0.24 15
Extract volume (m3/s)
89
Heating and ventilation systems – HTM 03-01: Specialised ventilation for healthcare premises – Part A
Corridor 0
KEY TO SYMBOLS
>10 0.24
Supply volume (m3/s)
Anaesthetic Scrub
0.24 15
Extract volume (m3/s)
90
Appendix 7 – Operating suite standard design solutions
LLE
Scrub
KEY TO SYMBOLS
1.15
Supply volume (m3/s)
91
Heating and ventilation systems – HTM 03-01: Specialised ventilation for healthcare premises – Part A
1.15
Supply volume (m3/s)
92
Appendix 7 – Operating suite standard design solutions
Standard layout 5 (Health Technical Memorandum 2025 existing standard plan “1b”) –
typical layout for a conventional theatre suite
Note
This layout and data is for historical purposes only. The information is to be used for the evaluation of existing
systems, the fitting out of existing shell schemes or rebalancing following ventilation system cleaning.
Room Size Air-change rate (AC/hr) Nominal pressure (Pa) Flow rate (m3/s)
Theatre 20 25 0.65
Anaesthetic 15 >10 0.15
Existing theatre suite
Lay-up prep – 35 0.34*
to be measured on site
Scrub – 25 –
Disposal – –5 0.41
Notes:
* See the “designers’ notes” in Appendices 4 and 5.
The disposal layout detailed will remain the same should a hatch be utilised instead of a door onto the outer corridor
0 Corridor
KEY TO SYMBOLS
Scrub
LLE
93
Heating and ventilation systems – HTM 03-01: Specialised ventilation for healthcare premises – Part A
Standard layout 6 (Health Technical Memorandum 2025 existing standard plan “1a”) –
typical layout for a UCV theatre suite
Note
This layout and data is for historical purposes only. The information is to be used for the evaluation of existing
systems, the fitting out of existing shell schemes or rebalancing following ventilation system cleaning.
If difficulties are experienced with entrainment around the periphery of the UCV, adding a low-level active or
passive extract in the location indicated will usually resolve the problem.
Room Size Air-change rate (AC/hr) Nominal pressure (Pa) Flow rate (m3/s)
Theatre 20 25 0.75*
Anaesthetic 15 >10 0.15
Existing theatre suite
Sterile pack store prep 10 25 0.1
to be measured on site
Scrub – 25 –
Disposal – –5 0.41
Notes:
* Primary fresh-air-flow volume
The disposal layout detailed will remain the same should a hatch be utilised instead of a door onto the outer corridor
0 Corridor
KEY TO SYMBOLS
94
Appendix 7 – Operating suite standard design solutions
Standard layout 7 (Health Technical Memorandum 2025 existing standard plan “5b”) –
typical layout for a conventional theatre suite
Note
This layout and data is for historical purposes only. The information is to be used for the evaluation of existing
systems, the fitting out of existing shell schemes or rebalancing following ventilation system cleaning.
Room Size Air-change rate (AC/hr) Nominal pressure (Pa) Flow rate (m3/s)
Theatre 20 25 0.65
Anaesthetic 15 >10 0.15
Existing theatre suite
Lay-up prep >20 35 0.34*
to be measured on site
Scrub – 25 –
Disposal – 0 0.1
Notes:
* See the “designers’ notes” in Appendices 4 and 5.
The disposal layout detailed will remain the same should a hatch be utilised instead of a door onto the outer corridor.
Alternatively the disposal room could be omitted and replaced with a disposal hatch between the theatre and corridor
0 Corridor
KEY TO SYMBOLS
0 Service corridor
95
Heating and ventilation systems – HTM 03-01: Specialised ventilation for healthcare premises – Part A
Standard layout 8 (Health Technical Memorandum 2025 existing standard plan “5a”) –
typical layout for a UCV theatre suite
Note
This layout and data is for historical purposes only. The information is to be used for the evaluation of existing
systems, the fitting out of existing shell schemes or rebalancing following ventilation system cleaning.
If difficulties are experienced with entrainment around the periphery of the UCV, adding a low-level active or
passive extract in the location indicated will usually resolve the problem.
Room Size Air-change rate (AC/hr) Nominal pressure (Pa) Flow rate (m3/s)
Theatre 20 25 0.75*
Anaesthetic 15 >10 0.15
Existing theatre suite
Sterile pack store prep 10 25 0.1
to be measured on site
Scrub – 25 –
Disposal – 0 0.1
Notes:
* Primary fresh-air-flow volume only
The disposal layout detailed will remain the same should a hatch be utilised instead of a door onto the outer corridor.
Alternatively the disposal room could be omitted and replaced with a disposal hatch between the theatre and corridor
0 Corridor
KEY TO SYMBOLS
0 Service corridor
96
Appendix 8 – Design of air-movement control
schemes for operating theatres
97
Heating and ventilation systems – HTM 03-01: Specialised ventilation for healthcare premises – Part A
Bay
Parallel multi-flow rooms
A8.11 A room which has a permanent opening to the
A8.14 The pressure difference across the closed doors
operating room may be considered as a bay off the
must be relieved, but transfer grilles are not
latter (for example a scrub). Two categories exist:
appropriate where two doors lead to areas of
• open bay – the opening is larger than a different pressures, because reverse flow could
normal single door opening. The bay may occur when the other door is open. For this reason,
be considered as part of the main room; pressure stabilisers are used.
• semi-open bay – the opening is no larger than
a normal single door opening. In this case it is
possible to protect the bay from the main room
S
by provision of air supply or extract in the bay,
or by passing air to or from another area.
98
Appendix 8 – Design of air-movement control schemes for operating theatres
L E
L M S H
Parallel multi-flow
(low-pressure room)
E M
S H L
Series multi-flow
(unbalanced)
99
Heating and ventilation systems – HTM 03-01: Specialised ventilation for healthcare premises – Part A
H L
H H L
H
Bay (semi-open)
Note: the pressure stabiliser
may be replaced by
Bay (open) mechanical extract
100
Appendix 8 – Design of air-movement control schemes for operating theatres
101
Heating and ventilation systems – HTM 03-01: Specialised ventilation for healthcare premises – Part A
adjusted to be the value required with the doors figures shown in Appendix 6 are based on the
closed. This is shown in Figure A1. temperature differences that will normally occur
in practice, assuming heat gains and losses in
Door leakage flows accordance with Appendix 4.
A8.44 For an air-movement control scheme to work A8.46 At step 11 of the air-flow design process, the
satisfactorily, it is essential that the estimates of temperature differences across the doors of all
door-gap leakage made at the design stage are rooms classed as “sterile” are calculated. Worksheet
closely related to those which are achieved in WS6 is recommended for the calculations, using
practice. The calculation of gap-flows is the following criteria:
complicated by the fact that such flows generally a. assume that the operating room is being
fall into the transition region between laminar and controlled at 20oC and calculate the incoming
turbulent flow and hence do not follow the normal air-supply temperature as shown on worksheet
flow equations. The gaps assumed are 4 mm along WS6;
the bottom, 3 mm at the top and sides, and 2 mm
between double leaves. Doors should not have b. the calculation should be repeated for both
wider gaps than these. Tighter gaps would result in summer and winter conditions, with an
lower flow-rate requirements and hence lower fan operation in progress;
power, but care should be taken to ensure that all c. assume all doors are closed;
doors in the suite have similar gap dimensions. It
may be possible to ignore the door leakage and so d. use the room supply flow rates from WS1;
reduce the air-flow requirement (see the “designers’ e. use the inward air flows through air-transfer
notes” in Appendix 4). devices and closed door leakages from WS2a
to WS2E;
Room temperature estimation f. the formula used in worksheet WS6 is as
A8.45 The air-flow rate required to prevent back-flow follows:
through an open door is dependent on the
(t Q + t Q + . . . + tnQn) + 0.828H
temperature difference across the door. The design T= 1 1 2 2
(Q + Q + . . . Q )
1 2 n
P2 P1 Pressure difference
102
Appendix 8 – Design of air-movement control schemes for operating theatres
[ ]
stabiliser is required to ensure that the correct
∆T + 1
Qnew = Qold protection air-flow is available to pass through
2
the door.
A8.48 These options should be considered in this order,
A8.52 If the “excess” air is greater than 0.42 m3/s, a
and (i), (ii) and (iii) should be investigated
transfer grille is acceptable because at all times
thoroughly before proceeding to (iv) or (v). The
the air-flow will exceed the flow required for
mechanical supply may need to be increased in
door protection.
order to achieve the desired air-change rates.
By pressure stabilisers to the corridor
Relief of excess air from operating room
A8.53 If it is undesirable to pass operating room air
when all doors are closed through the anaesthetic room, it may be passed
A8.49 As the mechanical supply to the operating room directly to a corridor via a separate pressure
is sized to provide an appropriate flow outward stabiliser.
through any door which is opened, it follows that
A8.54 If there is sufficient “excess” air, the transfer grille
when all doors are closed, there will be more air
solution at paragraph A8.52 should be adopted, as
supplied to the operating room than can exit from
it provides the simplest solution and, once set up,
it via leaks etc. This “excess” air can be relieved by
will require no further maintenance. With less
either of the two methods described in paragraphs
excess air, it is recommended that the air be passed
A8.50–8.54.
through the anaesthetic room via the pressure
By transfer devices via the anaesthetic room stabilisers as at paragraph A8.51, thus keeping the
number of pressure stabilisers to a minimum. Both
A8.50 For door protection, the transfer devices in the these solutions increase the air-change rate in the
anaesthetic room are typically designed to pass anaesthetic room, but care should be taken to
0.47 m3/s at a differential pressure of 14 Pa. When avoid passing excessive amounts through that
the doors are closed, the differential pressure will would cause discomfort to the occupants.
change to 11 Pa between theatre and anaesthetic
103
Heating and ventilation systems – HTM 03-01: Specialised ventilation for healthcare premises – Part A
Transitional
Ro
Corridor 1.
patients/staff
Pass through
Supply
2.
hatch
3.
Preparation
Clean (sterile supply Sterile
Sterile bay
Scrub Anaesthetic store)
(semi-open) 4.
Sterile Parallel/series 5.
multi-flow
Series multi-flow 6.
(balanced)
Operating
room
7.
Disposal hatch
Pass through 8.
Corridor 9.
Dirty
outer
(disposal)
10.
11.
12.
13.
14.
104
Appendix 8 – Design of air-movement control schemes for operating theatres
Enter heat/loss/gain data and calculate supply air flow rates for temperature control only.
2 WS1
Categorise room types, eg sterile, clean etc
Enter air flows required for bacterial contamination control or air change rate, whichever is the
3 WS1
greater; add supply and extract volumes (SD, ED) on the plan
Select from
4 Define peripheral room types, see paragraphs A8.5–A8.11, and select appropriate worksheets
WS2a to WS2e
Selected worksheets
5 Locate air transfer devices, enter details on worksheets and locate on the plan and Figure A2
from WS2a to WS2e
For each peripheral room, determine air flows through doors when open and calculate
6 as above
mechanical supply or extract and transfer device flows
7 Select “Key Door” and calculate air supply for operating room WS3
YES
10 Calculate supply and extract flow rates for corridor(s) WS4, WS5
11 Calculate room temperatures (all doors closed) and ∆T’s WS6a and WS6b
NO
105
Heating and ventilation systems – HTM 03-01: Specialised ventilation for healthcare premises – Part A
Room name
1. Summer temperature control
Heat gain kW
2. Acceptable ∆t C
3. Air flow rate (SG)
= Gain m3/s
∆t × 1.2
5. Acceptable ∆t C
SD or ED
S
10. Air movement control
m3/s
Air flow rate for air movement
control SAMC or EAMC
E
(from WS2, WS3 or WS4)
m3/s
106
Appendix 8 – Design of air-movement control schemes for operating theatres
Nominal pressure: Pa
Pa ∆t Out In Remarks
Flow required through doorway to give protection
Structural leakage
Total
(( ∑ – ∑ )) m3
SSAMC
AMC OUT – ∑IN
∑OUT IN m3/s
/s
or
or
E (( ∑ – ∑IN )) m3
EAMC
AMC IN – ∑OUT
∑OUT m3/s
/s
Transfer
Transfer SSAMC or E to WS1
AMC or EAMC
AMC to WS1
Consider door to ........................... closed
Consider door to ........................... closed
Pa ∆t Out In Remarks
Pa ∆t Out In Remarks
Closed door leakage
Closed door leakage
Structural leakage
Total
Total
107
Heating and ventilation systems – HTM 03-01: Specialised ventilation for healthcare premises – Part A
Nominal pressure: Pa
Door from this room to ...................................................... (room of equal cleanliness) is not to be protected.
A transfer grille is located in, or adjacent to, this door
Out In Remarks
Flow required through doorway to give protection
Total
Total
or OUT – IN = Z˝
Select larger of A1 or A2
Surveyor
108 (AP(V)/CP(V)) ...................................................................... Date ................................................
Appendix 8 – Design of air-movement control schemes for operating theatres
Out In Remarks
Flow required through open doorway to give protection
Total
Out In Remarks
Flow required through open doorway to give protection
Total
Total
Out In Remarks
Flow required through open doorway to give protection. See Appendix 6
Total
Out In Remarks
Flow required through open doorway to give protection
Total
Lower
Flow through transfer device (TD1) to protect pressure TD1
door 1 = Q1 at resultant
∆P ............................ Door 2
110
Surveyor (AP(V)/CP(V)) ...................................................................... Date ................................................
Appendix 8 – Design of air-movement control schemes for operating theatres
Nominal pressure: Pa
Note: If the room is of the open bay type (ie opening is larger than normal single doorway), the room should be considered part of
the main room. No air movement control considerations need then be made, and this sheet can be discarded. Supply and/or
extract flow will be based on air distribution considerations.
Out In Remarks
Flow required through opening to give protection
Total
– pressure stabiliser
Note: A door from the bay is considered with the peripheral room to which it leads or, if it leads to the corridor, it is considered with
the main room
111
Heating and ventilation systems – HTM 03-01: Specialised ventilation for healthcare premises – Part A
Nominal pressure: Pa
Note: To avoid considering each door open in turn, the “key door” concept is introduced. This is the door which requires the
greatest mechanical flow when open. See paragraph A8.33
Out In Remarks
Flow required through doorway to give protection
Mechanical extract
Total
Total
112
Surveyor (AP(V)/CP(V)) ...................................................................... Date ................................................
Appendix 8 – Design of air-movement control schemes for operating theatres
Nominal pressure: Pa
Out In Remarks
Flow required through doorway to give protection
Note: this sheet to be used for each individual operating theatre suite (or pair of suites if they share a preparation room)
113
Heating and ventilation systems – HTM 03-01: Specialised ventilation for healthcare premises – Part A
Anaesthetic
Air flow to corridor All doors closed
(key door open)
m3/s m3/s
From preparation
From scrub
From anaesthetic
Total (a)
Air flow to corridor
From disposal
From other source
Total (b)
Consider corridor ventilation (see Appendix 3) and calculate air volume required, based on 7 AC/hr (see Note 1)
m3/s
If the air flow from the operating suite (a) and (b) is greater than the calculated required volume, no further supply air is necessary
m3/s
Air extract
The size of the extract plant should be of the order of 10% below the supply to assist in maintaining the
department under positive pressure relative to the outside departments
m3/s
Notes: 1. In the case of a multi-theatre operating department, the air balance for the corridor should be considered as a separate
exercise, taking into account the final dispersal of excess air.
2. Omit these if only one corridor in operating suite.
3. The extract volume includes 0.24 m3/s from the anaesthetic room for a balanced condition
114
Surveyor (AP(V)/CP(V)) ...................................................................... Date ................................................
Appendix 8 – Design of air-movement control schemes for operating theatres
Transfer grilles, pressure relief dampers and pressure stabilisers Worksheet WS7
Reference:
References
118
References
BS EN 779:2002. Particulate air filters for general Health Technical Memorandum 58 – Internal
ventilation. Determination of the filtration performance. doorsets. The Stationery Office, 2005.
BS EN 1822-1:1998. High efficiency air filters (HEPA Health Technical Memorandum 04-01 – The control
and ULPA). Classification, performance testing, marking. of Legionella, hygiene, “safe” hot water, cold water
and drinking water systems. The Stationery Office,
BS EN 1822-2:1998. High efficiency air filters (HEPA
2006.
and ULPA). Aerosol production, measuring equipment,
particle counting statistics. Health Technical Memorandum 05-02 – Guidance in
support of functional provisions for healthcare
BS EN 1822-3:1998. High efficiency air filters (HEPA
premises. The Stationery Office, 2007.
and ULPA). Testing flat sheet filter media.
Health Technical Memorandum 08-01 – Acoustics.
BS EN 1822-4:2000. High efficiency air filters (HEPA
The Stationery Office, 2007.
and ULPA). Determining leakage of filter element (scan
method). Model Engineering Specification C04 – Mechanical
ventilation and air conditioning systems. The
BS EN 1822-5:2000. High efficiency air filters (HEPA
Stationery Office, 1997.
and ULPA). Determining the efficiency of filter element.
BS EN 12464-1:2002. Light and lighting. Lighting of Chartered Institution of Building
work places. Indoor work places.
Services publications
BS EN 12469:2000. Biotechnology. Performance criteria
Applications Manual AM10 – Natural ventilation in
for microbiological safety cabinets.
non-domestic buildings. CIBSE, 2005.
BS EN 13030:2001. Ventilation for buildings.
Applications Manual AM13 – Mixed mode
Terminals. Performance testing of louvres subjected to
ventilation. CIBSE, 2000.
simulated rain.
Commissioning Code A: Air distribution systems.
BS EN 14175-2:2003. Fume cupboards. Safety and
CIBSE 1996.
performance requirements.
Commissioning Code R: Refrigerating systems. CIBSE
BS EN ISO 14644-1:1999. Cleanrooms and associated
2002.
controlled environments. Classification of air cleanliness.
Commissioning Code W: Water distribution systems.
BS EN ISO 14644-4:2001. Cleanrooms and associated
CIBSE 2003.
controlled environments. Design, construction and start-
up. Guide A: Environmental design. CIBSE, 2006.
BS EN 60601-2-41:2000, IEC 60601-2-41:2000. Guide B: Heating, ventilating, air conditioning and
Medical electrical equipment. Particular requirements for refrigeration. CIBSE, 2005.
safety. Particular requirements for the safety of surgical Lighting guide LG2: Hospitals and health care
luminaires and luminaires for diagnosis. buildings. CIBSE, 1989.
Health Building Note 26 – Facilities for surgical DW/144 – Specification for sheet metal ductwork,
procedures. The Stationery Office, 2004. low, medium & high pressure/velocity air systems.
HVCA Publications, 1998.
Health Facilities Note 30 – Infection control in the
built environment. The Stationery Office, 2002. DW/154 – Specification for plastics ductwork. HVCA
Publications, 2000.
Health Technical Memorandum 55 – Windows.
The Stationery Office, 1998. TR/19 – Guide to good practice: internal cleanliness
of ventilation systems. HVCA Publications, 2005.
119
Heating and ventilation systems – HTM 03-01: Specialised ventilation for healthcare premises – Part A
120