Aogc 036 Sa DSC 001 (B1)
Aogc 036 Sa DSC 001 (B1)
Aogc 036 Sa DSC 001 (B1)
Revision B0 B1
Issued for TENDER TENDER
Date 92.11.21 93.06.31
Consultant
TABLE OF CONTENTS
Page
1.0 INTRODUCTION 4
1.1 Terms and Definitions 4
2.0 REFERENCES, CODES AND STANDARDS 5
3.0 SITE CONDITION AND DEFINITIONS 5
3.1 Site Condition 5
4.0 DESIGN BASIS FOR ACTIVE FIRE PROTECTION 6
4.1 Mobile and Portable Equipment 6
5.0 FIRE AND GAS DETECTION SYSTEM 6
5.1 Flammable Gas Detection 7
5.2 Toxic Gas Detection 8
5.3 Manual Alarm Call Point 9
1.0 INTRODUCTION
Arvandan Oil and Gas company intends to construct an 8" N.B. buried flowline
from Sohrab WH1 to South Azadegan North Cluster.
Sohrab Field is located at North of Azadegan Field, and 115 Km North West of
Ahwaz right along the international border with Iraq.
Drawings
IPS Standards
International Codes and Standards
The design and considerations shall be based on the following site conditions:
Minimum temperature(absolute): +4 o C
Maximum ambient temperature: +55 o C
Maximum sun temper: +85 o C
Maximum wind velocity: 115 km/hr
Annual mean humidity: 60%
Maximum relative humidity: 90%
For detailed specification about fire Portable and Wheeled Extinguishers refer to:
Fire extinguisher Specification, AOGC-036-SA-ESS-001
The objective of the fire and gas detection is to facilitate an early warning to
personnel of potentially dangerous situations in terms of flammable or toxic
atmospheres (gas) or fires .
The early warning signal will enable personnel to take remedial actions to reduce
effects of the dangerous situation and, certainly at least as important, personnel are
made aware of a dangerous situation.
The fire and gas detection system should be provided to perform, but not be limited
to, the following duties:
To monitor all designated areas for fire;
To monitor all areas where flammable or toxic materials might be present in
the course of normal operations;
To provide a facility for raising a fire alarm;
To alert personnel in the control room of any fire or gas emergence situation;
To alert personnel in the control room of any fault detected by self test
facilities;
All fire and gas display and information facilities shall be centralized in main fire
alarm panel in the control room.
The selection of fire detectors for various areas on an installation shall be based
upon an evaluation of the prime fire indications and ambient conditions. For major
hazard areas, two different detection principles will be used.
Flammable gas detectors shall be located taking into account the following
criteria:
The most likely sources of leakage;
The proximity to possible sources of ignition;
The environment (dust, sand storms, humidity, vibrations and alignment).
The density of gas leak; detector shall be positioned under the expected leak
source for heavier than air gases and above the expected leak source for lighter
than air gases.
5.1.1.1.1 Location
Gas detectors shall be installed near probable leak sources which could lead to
the formation of flammable gas clouds and includes the following locations:
Pig Launchers/Receivers
Chemical Storage Shelter
Diesel Generator Shelter
Wellhead facilities(unmanned Area)
For flammable gas detectors located open area shall be provided two out of N
(2ooN) voting system. When two out of N, (2ooN) logic is achieved at 50% LEL,
the alarms and actions shall be activate as bellow:
A common audible alarm and visual alarm in central control room (CCR).
Audible and visual alarm in the concerned fire zone
Emergency shutdown unit (ESD1) shall be initiate within concerned fire zone
For single alarm at 50% LEL only a visual alarm on operating station shall be
notified .
The H2S toxic gas detectors typically will be located at the following locations:
Pig Launchers/Receivers
Chemical Storage shelter
Wellhead facilities(unmanned Area)
In addition to the automatic fire detection system, Manual alarm call points shall be
installed throughout the plant. They shall be used by personnel to raise an alarm.
These shall be installed in process areas and enclosed areas.
Call points shall be of the “break-glass” push-button type. Manual alarm call points
shall activate audible and visual alarm to the main control room, and relevant area.
The operator in the control room can also manually activate all audible/visual
alarms in the plant.
Manual Alarm Call points should be mounted at a height of 1.4 meter above floor
level and there should not be more than 30 meter walking distance to a manual fire
alarm button from any point on the installation.