Logic Controller - Modicon M221 - TM221C16R
Logic Controller - Modicon M221 - TM221C16R
Logic Controller - Modicon M221 - TM221C16R
Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Main
Range of product Modicon M221
Product or component type Logic controller
[Us] rated supply voltage 100...240 V AC
Discrete input number 9 discrete input conforming to IEC 61131-2 Type 1
Analogue input number 2 at input range: 0...10 V
Discrete output type Relay normally open
Discrete output number 7 relay
Discrete output voltage 5...125 V DC
5...250 V AC
Discrete output current 2A
Complementary
Discrete I/O number 16
Number of I/O expansion module <= 4 for transistor output
<= 4 for relay output
Supply voltage limits 85...264 V
Network frequency 50/60 Hz
Inrush current <= 40 A
Power consumption in VA <= 46 VA at 100...240 V with max number of I/O expansion module
<= 31 VA at 100...240 V without I/O expansion module
Power supply output current 0.325 A at 5 V for expansion bus
0.12 A at 24 V for expansion bus
Discrete input logic Sink or source (positive/negative)
Discrete input voltage 24 V
Discrete input voltage type DC
Analogue input resolution 10 bits
LSB value 10 mV
Conversion time 1 ms per channel + 1 controller cycle time for analog input
Permitted overload on inputs +/- 30 V DC for analog input with 5 min maximum
+/- 13 V DC for analog input permanent
2
Frequency meter
Single phase
Integrated connection type USB port with connector mini B USB 2.0
Non isolated serial link "serial 1" with connector RJ45 and interface RS485
Non isolated serial link "serial 2" with connector RJ45 and interface RS232/RS485
Supply Serial serial link supply at 5 V 200 mA
Transmission rate 1.2...115.2 kbit/s (115.2 kbit/s by default) for bus length of 15 m - communication protocol: RS485
1.2...115.2 kbit/s (115.2 kbit/s by default) for bus length of 3 m - communication protocol: RS232
480 Mbit/s - communication protocol: USB
Communication port protocol USB port : USB protocol - SoMachine-Network
Non isolated serial link : Modbus protocol master/slave - RTU/ASCII or SoMachine-Network
Local signalling 1 LED green for SD card access (SD)
1 LED red for BAT
1 LED green for SL1
1 LED green for SL2
1 LED per channel green for I/O state
1 LED red for module error (ERR)
1 LED green for PWR
1 LED green for RUN
Electrical connection Mini B USB 2.0 connector for a programming terminal
Terminal block, 3 terminal(s) for connecting the 24 V DC power supply
Connector, 4 terminal(s) for analogue inputs
Removable screw terminal block for inputs
Removable screw terminal block for outputs
Cable distance between devices Shielded cable: 10 m for fast input
Unshielded cable: 30 m for output
Unshielded cable: 30 m for digital input
Unshielded cable: 1 m for analog input
Insulation 2300 V AC between output and internal logic
Non-insulated between analogue inputs
500 V AC between input and internal logic
Non-insulated between analogue input and internal logic
1500 V AC between supply and ground
500 V AC between sensor power supply and ground
500 V AC between input and ground
1500 V AC between output and ground
2300 V AC between supply and internal logic
500 V AC between sensor power supply and internal logic
500 V AC between Ethernet terminal and internal logic
2300 V AC between supply and sensor power supply
Marking CE
Sensor power supply 24 V DC at 250 mA supplied by the controller
Mounting support Top hat type TH35-15 rail conforming to IEC 60715
Top hat type TH35-7.5 rail conforming to IEC 60715
Plate or panel with fixing kit
Height 90 mm
Depth 70 mm
Width 95 mm
Product weight 0.346 kg
Environment
Standards EN/IEC 61010-2-201
EN/IEC 60664-1
EN/IEC 61131-2
Product certifications ABS
EAC
DNV-GL
RCM
cULus
IACS E10
CSA
LR
Environmental characteristic Ordinary and hazardous location
Resistance to electrostatic discharge 4 kV on contact conforming to EN/IEC 61000-4-2
8 kV in air conforming to EN/IEC 61000-4-2
Resistance to electromagnetic fields 10 V/m ( 80 MHz...1 GHz) conforming to EN/IEC 61000-4-3
3
3 V/m ( 1.4 GHz...2 GHz) conforming to EN/IEC 61000-4-3
1 V/m ( 2...2.7 GHz) conforming to EN/IEC 61000-4-3
Resistance to magnetic fields 30 A/m 50/60 Hz conforming to EN/IEC 61000-4-8
Resistance to fast transients 2 kV for power lines conforming to EN/IEC 61000-4-4
2 kV for relay output conforming to EN/IEC 61000-4-4
1 kV for Ethernet line conforming to EN/IEC 61000-4-4
1 kV for serial link conforming to EN/IEC 61000-4-4
1 kV for I/O conforming to EN/IEC 61000-4-4
Surge withstand 2 kV for power lines (AC) in common mode conforming to EN/IEC 61000-4-5
2 kV for relay output in common mode conforming to EN/IEC 61000-4-5
1 kV for I/O in common mode conforming to EN/IEC 61000-4-5
1 kV for shielded cable in common mode conforming to EN/IEC 61000-4-5
0.5 kV for power lines (DC) in differential mode conforming to EN/IEC 61000-4-5
1 kV for power lines (AC) in differential mode conforming to EN/IEC 61000-4-5
1 kV for relay output in differential mode conforming to EN/IEC 61000-4-5
0.5 kV for power lines (DC) in common mode conforming to EN/IEC 61000-4-5
Resistance to conducted disturbances 10 Vrms (0.15...80 MHz) conforming to EN/IEC 61000-4-6
3 Vrms (0.1...80 MHz) conforming to Marine specification (LR, ABS, DNV, GL)
10 Vrms (spot frequency (2, 3, 4, 6.2, 8.2, 12.6, 16.5, 18.8, 22, 25 MHz)) conforming to Marine
specification (LR, ABS, DNV, GL)
Electromagnetic emission Conducted emissions conforming to EN/IEC 55011 power lines (AC), 0.15...0.5 MHz : 79 dBμV/m
QP/66 dBμV/m AV
Conducted emissions conforming to EN/IEC 55011 power lines (AC), 0.5...300 MHz : 73 dBμV/m
QP/60 dBμV/m AV
Conducted emissions conforming to EN/IEC 55011 power lines, 10...150 kHz : 120...69 dBµV/m QP
Conducted emissions conforming to EN/IEC 55011 power lines, 1.5...30 MHz : 63 dBμV/m QP
Radiated emissions conforming to EN/IEC 55011 class A 10 m, 30...230 MHz : 40 dBμV/m QP
Conducted emissions conforming to EN/IEC 55011 power lines, 150...1500 kHz : 79...63 dBμV/m QP
Radiated emissions conforming to EN/IEC 55011 class A 10 m, 200...1000 MHz : 47 dBμV/m QP
Immunity to microbreaks 10 ms
Ambient air temperature for operation -10...55 °C for horizontal installation
-10...35 °C for vertical installation
Ambient air temperature for storage -25...70 °C
Relative humidity 10...95 % without condensation in operation
10...95 % without condensation in storage
IP degree of protection IP20 with protective cover in place
Pollution degree <= 2
Operating altitude 0...2000 m
Storage altitude 0...3000 m
Vibration resistance 3.5 mm (vibration frequency: 5...8.4 Hz) on symmetrical rail
1 gn (vibration frequency: 8.4...150 Hz) on symmetrical rail
3.5 mm (vibration frequency: 5...8.4 Hz) on panel mounting
1 gn (vibration frequency: 8.4...150 Hz) on panel mounting
Shock resistance 98 m/s² (test wave duration:11 ms)
Offer Sustainability
Sustainable offer status Green Premium product
RoHS (date code: YYWW) Compliant - since 1415 - Schneider Electric declaration of conformity
Schneider Electric declaration of conformity
REACh Reference not containing SVHC above the threshold
Reference not containing SVHC above the threshold
Product environmental profile Available
Product environmental
Product end of life instructions Available
End of life manual
4
Product data sheet TM221C16R
Esquemas de dimensiones
Dimensiones
5
Product data sheet TM221C16R
Montaje y aislamiento
Montaje en un segmento
6
Product data sheet TM221C16R
Montaje y aislamiento
7
Product data sheet TM221C16R
Montaje y aislamiento
Montaje
8
Product data sheet TM221C16R
Montaje y aislamiento
Distancia
9
Product data sheet TM221C16R
Conexiones y esquema
Entradas digitales
10
Product data sheet TM221C16R
Conexiones y esquema
Salidas de relé
11
Product data sheet TM221C16R
Conexiones y esquema
Entradas analógicas
0V Negro
AN1 Rojo
0V Negro
AN0 Rojo
12
Product data sheet TM221C16R
Conexiones y esquema
13
Product data sheet TM221C16R
Conexiones y esquema
Conexión SL1
SL1
1 RxD N.C.
2 TxD N.C.
3 RTS N.C.
4 N.C. D1
5 N.C. D0
6 CTS N.C.
7 N. C.* 5 V CC
8 Común Común
N.C.: no conectado
*: 5 V CC entregados por el controlador. No conectar.
14
Product data sheet TM221C16R
Conexiones y esquema
Conexión SL2
N.° RS485
1 N.C.
2 N.C.
3 N.C.
4 D1
5 D0
6 N.C.
7 N.C.
8 Común
N.C.: no conectado
15
Product data sheet TM221C16R
Curvas de rendimiento
Curvas de desclasificación
X: Temperatura ambiente
Y: Relación de entradas simultáneas en ON
X: Temperatura ambiente
Y: Relación de entradas simultáneas en ON
16