Ambient conditions
Ambient temperature
● during operation -25 ... +60 °C
● during storage -55 ... +80 °C
Main circuit
Number of poles for main current circuit 4
Number of NO contacts for main contacts 2
Number of NC contacts for main contacts 2
Operating current
● at AC-1
— up to 690 V at ambient temperature 40 °C 22 A
rated value
— up to 690 V at ambient temperature 60 °C 20 A
rated value
● at AC-2 at AC-3 at 400 V
— per NO contact rated value 16 A
— per NC contact rated value 9 A
Connectable conductor cross-section in main circuit
at AC-1
● at 60 °C minimum permissible 2.5 mm²
● at 40 °C minimum permissible 4 mm²
Operating current
● at 1 current path at DC-1
— at 24 V rated value 20 A
— at 110 V rated value 2.1 A
— at 220 V rated value 0.8 A
— at 440 V rated value 0.6 A
● with 2 current paths in series at DC-1
— at 24 V rated value 20 A
— at 110 V rated value 12 A
— at 220 V rated value 1.6 A
— at 440 V rated value 0.8 A
Operating current
Auxiliary circuit
Number of NC contacts
● for auxiliary contacts
— instantaneous contact 0
Number of NO contacts
● for auxiliary contacts
— instantaneous contact 0
Operating current at AC-12 maximum 10 A
Operating current at AC-15
● at 230 V rated value 10 A
● at 400 V rated value 3 A
Operating current at DC-12
● at 48 V rated value 6 A
● at 60 V rated value 6 A
● at 110 V rated value 3 A
● at 125 V rated value 2 A
● at 220 V rated value 1 A
● at 600 V rated value 0.15 A
Operating current at DC-13
● at 24 V rated value 10 A
● at 48 V rated value 2 A
● at 60 V rated value 2 A
● at 110 V rated value 1 A
● at 220 V rated value 0.3 A
● at 600 V rated value 0.1 A
Contact reliability of auxiliary contacts 1 faulty switching per 100 million (17 V, 1 mA)
UL/CSA ratings
Yielded mechanical performance [hp]
● for single-phase AC motor
— at 110/120 V rated value 1 hp
— at 230 V rated value 2 hp
Contact rating of auxiliary contacts according to UL A600 / Q600
Short-circuit protection
Design of the fuse link
● for short-circuit protection of the main circuit
— with type of coordination 1 required gG NH 3NA, DIAZED 5SB, NEOZED 5SE: 35 A
— with type of assignment 2 required gG NH 3NA, DIAZED 5SB, NEOZED 5SE: 20 A
● for short-circuit protection of the auxiliary switch fuse gG: 10 A
required
Connections/Terminals
Type of electrical connection
● for main current circuit screw-type terminals
● for auxiliary and control current circuit screw-type terminals
Type of connectable conductor cross-sections
● for main contacts
— solid 2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), 2x 4 mm²
— single or multi-stranded 2x (0,5 ... 1,5 mm²), 2x (0,75 ... 2,5 mm²), 2x 4 mm²
— finely stranded with core end processing 2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
● at AWG conductors for main contacts 2x (20 ... 16), 2x (18 ... 14), 2x 12
Type of connectable conductor cross-sections
● for auxiliary contacts
Certificates/approvals
other
Further information
Information- and Downloadcenter (Catalogs, Brochures,…)
http://www.siemens.com/industrial-controls/catalogs
Industry Mall (Online ordering system)
https://mall.industry.siemens.com/mall/en/en/Catalog/product?mlfb=3RT2518-1BB40
Cax online generator
http://support.automation.siemens.com/WW/CAXorder/default.aspx?lang=en&mlfb=3RT2518-1BB40
Service&Support (Manuals, Certificates, Characteristics, FAQs,...)
https://support.industry.siemens.com/cs/ww/en/ps/3RT2518-1BB40
Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, EPLAN macros, ...)
http://www.automation.siemens.com/bilddb/cax_de.aspx?mlfb=3RT2518-1BB40&lang=en
1 R1 R3 3 A1 +
1. 2. 3. 4.
29.8
57.5
50
1. 2. 3. 4.
2 R2 R4 4 A2 -
5 1.2
3.8
5
A2 (-) 2 R2 R4 4