Data sheet 3RT1364-6AP36

Contactor, AC-1, 350 A/400 V/40 °C, S10, 4-pole, 100-250 V AC/DC, 2 NO+2 NC,
Connection rail/ screw terminal

product brand name SIRIUS


product designation Contactor
product type designation 3RT13
General technical data
size of contactor S10
product extension
● function module for communication No
● auxiliary switch Yes
power loss [W] for rated value of the current
● at AC in hot operating state 100 W
● at AC in hot operating state per pole 25 W
● without load current share typical 2.5 W
insulation voltage
● of main circuit with degree of pollution 3 rated value 1 000 V
● of the auxiliary and control circuit with degree of pollution 690 V
3 rated value
surge voltage resistance
● of main circuit rated value 8 kV
● of auxiliary circuit rated value 6 kV
reference code according to IEC 81346-2 Q
Substance Prohibitance (Date) 03/27/2017
Ambient conditions
installation altitude at height above sea level maximum 2 000 m
ambient temperature
● during operation -40 ... +60 °C
● during storage -40 ... +70 °C
relative humidity minimum 10 %
relative humidity at 55 °C according to IEC 60068-2-30 95 %
maximum
Main circuit
number of poles for main current circuit 4
number of NO contacts for main contacts 4
operational current
● at AC-1 at 400 V at ambient temperature 40 °C rated 350 A
value
● at AC-1
— up to 690 V at ambient temperature 40 °C rated 350 A
value
— up to 690 V at ambient temperature 60 °C rated 300 A
value
— up to 1000 V at ambient temperature 40 °C rated 275 A
value

3RT13646AP36 Subject to change without notice


7/5/2023
Page 1/5 © Copyright Siemens
— up to 1000 V at ambient temperature 60 °C rated 250 A
value
● at AC-3
— at 400 V rated value 205 A
minimum cross-section in main circuit at maximum AC-1 rated 240 mm²
value
operating power
● at AC-3 at 400 V rated value 110 kW
no-load switching frequency
● at AC 300 1/h
● at DC 300 1/h
Control circuit/ Control
type of voltage AC
type of voltage of the control supply voltage AC/DC
control supply voltage at AC
● at 50 Hz rated value 100 ... 250 V
● at 60 Hz rated value 100 ... 250 V
control supply voltage at DC
● rated value 100 ... 250 V
operating range factor control supply voltage rated value of
magnet coil at DC
● initial value 0.8
● full-scale value 1.1
operating range factor control supply voltage rated value of
magnet coil at AC
● at 50 Hz 0.85 ... 1.1
● at 60 Hz 0.85 ... 1.1
apparent pick-up power of magnet coil at AC
● at 50 Hz 220 VA
● at 60 Hz 220 VA
apparent holding power of magnet coil at AC
● at 50 Hz 7 VA
● at 60 Hz 7 VA
closing power of magnet coil at DC 190 W
holding power of magnet coil at DC 2.5 W
closing delay
● at AC 25 ... 60 ms
● at DC 25 ... 60 ms
opening delay
● at AC 45 ... 80 ms
● at DC 45 ... 80 ms
control version of the switch operating mechanism Standard A1 - A2
Auxiliary circuit
number of NC contacts for auxiliary contacts 2
● attachable 2
● instantaneous contact 2
number of NO contacts for auxiliary contacts 2
● attachable 2
● instantaneous contact 2
operational current at AC-15
● at 230 V rated value 4A
● at 400 V rated value 3A
● at 500 V rated value 2A
● at 690 V rated value 2A
operational current at DC-13
● at 24 V rated value 3A
● at 48 V rated value 1.5 A
● at 110 V rated value 0.55 A
● at 125 V rated value 0.55 A
● at 220 V rated value 0.3 A
UL/CSA ratings
contact rating of auxiliary contacts according to UL A600 / Q300

3RT13646AP36 Subject to change without notice


7/5/2023
Page 2/5 © Copyright Siemens
Short-circuit protection
product function short circuit protection No
design of the fuse link
● for short-circuit protection of the main circuit
— with type of assignment 2 required gG: 400 A (500 V, 100 kA)
● for short-circuit protection of the auxiliary switch required gG: 10 A (690 V, 1 kA)
Installation/ mounting/ dimensions
mounting position For vertical mounting surface can be rotated +/-180°, and with 0° rotation can
be tilted forward or backward +/- 30°, or standing
fastening method screw fixing
● side-by-side mounting Yes
height 196 mm
width 140 mm
depth 153 mm
required spacing
● with side-by-side mounting
— forwards 20 mm
— upwards 10 mm
— downwards 10 mm
— at the side 0 mm
● for grounded parts
— forwards 20 mm
— upwards 10 mm
— at the side 10 mm
— downwards 10 mm
● for live parts
— forwards 20 mm
— upwards 10 mm
— downwards 10 mm
— at the side 10 mm
net weight 3.85 kg
Connections/ Terminals
type of electrical connection
● for main current circuit Connection bar, broadened > 275A required
● for auxiliary and control circuit screw-type terminals
● at contactor for auxiliary contacts Screw-type terminals
● of magnet coil Screw-type terminals
connectable conductor cross-section for auxiliary contacts
● solid or stranded 1 ... 4 mm²
● finely stranded with core end processing 0.75 ... 2.5 mm²
type of connectable conductor cross-sections
● for auxiliary contacts
— solid 1x (1 ... 4mm²), 2x (1 ... 4mm²)
— solid or stranded 1x (1 ... 4mm²), 2x (1 ... 4mm²)
— finely stranded with core end processing 1x (0.75 ... 2.5 mm²), 2x (0.75 ... 2.5 mm²)
● for AWG cables for auxiliary contacts 1x (AWG 18 ... 14), 2x (AWG 18 ... 14)
AWG number as coded connectable conductor cross
section
● for auxiliary contacts 18 ... 14
Safety related data
product function
● mirror contact according to IEC 60947-4-1 Yes
● positively driven operation according to IEC 60947-5-1 No
protection class IP on the front according to IEC 60529 IP00; IP20 with box terminal/cover
touch protection on the front according to IEC 60529 finger-safe, for vertical contact from the front with box terminal/cover
Communication/ Protocol
product function bus communication No
Certificates/ approvals
General Product Approval EMC Test Certificates

3RT13646AP36 Subject to change without notice


7/5/2023
Page 3/5 © Copyright Siemens
Confirmation Special Test Certific-
ate

other Railway

Confirmation Miscellaneous Special Test Certific-


ate

Further information
Siemens has decided to exit the Russian market (see here).
https://press.siemens.com/global/en/pressrelease/siemens-wind-down-russian-business
Siemens is working on the renewal of the current EAC certificates.
Please contact your local Siemens office on the status of validity of the EAC certification if you intend to import or offer to supply these products to an
EAC relevant market (other than the sanctioned EAEU member states Russia or Belarus).
Information on the packaging
https://support.industry.siemens.com/cs/ww/en/view/109813875
Information- and Downloadcenter (Catalogs, Brochures,…)
https://www.siemens.com/ic10
Industry Mall (Online ordering system)
https://mall.industry.siemens.com/mall/en/en/Catalog/product?mlfb=3RT1364-6AP36
Cax online generator
http://support.automation.siemens.com/WW/CAXorder/default.aspx?lang=en&mlfb=3RT1364-6AP36
Service&Support (Manuals, Certificates, Characteristics, FAQs,...)
https://support.industry.siemens.com/cs/ww/en/ps/3RT1364-6AP36
Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, EPLAN macros, ...)
http://www.automation.siemens.com/bilddb/cax_de.aspx?mlfb=3RT1364-6AP36&lang=en
Characteristic: Tripping characteristics, I²t, Let-through current
https://support.industry.siemens.com/cs/ww/en/ps/3RT1364-6AP36/char
Further characteristics (e.g. electrical endurance, switching frequency)
http://www.automation.siemens.com/bilddb/index.aspx?view=Search&mlfb=3RT1364-6AP36&objecttype=14&gridview=view1

43 NO
13 NO

31 NC
21 NC
A1 +

1L1

3L2

5L3

7L4

-Q
44 NO
14 NO

32 NC
22 NC
A2 -

2T1

4T2

6T3

8T4

3RT13646AP36 Subject to change without notice


7/5/2023
Page 4/5 © Copyright Siemens
last modified: 3/18/2022

3RT13646AP36 Subject to change without notice


7/5/2023
Page 5/5 © Copyright Siemens