York Cond Unit Piping Guidelines
York Cond Unit Piping Guidelines
York Cond Unit Piping Guidelines
AI
R
AI
R
LD13304
Issue Date:
February 23, 2012
FORM 050.40-ES3
ISSUE DATE: 2/23/2012
IMPORTANT!
READ BEFORE PROCEEDING!
GENERAL SAFETY GUIDELINES
This equipment is a relatively complicated apparatus. which it is situated, as well as severe personal injury or
During installation, operation maintenance or service, death to themselves and people at the site.
individuals may be exposed to certain components or
conditions including, but not limited to: refrigerants, This document is intended for use by owner-authorized
materials under pressure, rotating components, and operating/service personnel. It is expected that these
both high and low voltage. Each of these items has the individual possess independent training that will en-
potential, if misused or handled improperly, to cause able them to perform their assigned tasks properly and
bodily injury or death. It is the obligation and respon- safely. It is essential that, prior to performing any task
sibility of operating/service personnel to identify and on this equipment, this individual shall have read and
recognize these inherent hazards, protect themselves, understood this document and any referenced mate-
and proceed safely in completing their tasks. Failure rials. This individual shall also be familiar with and
to comply with any of these requirements could result comply with all applicable governmental standards and
in serious damage to the equipment and the property in regulations pertaining to the task in question.
SAFETY SYMBOLS
The following symbols are used in this document to alert the reader to specific situations:
2 JOHNSON CONTROLS
FORM 050.40-ES3
ISSUE DATE: 2/23/2012
JOHNSON CONTROLS 3
FORM 050.40-ES3
ISSUE DATE: 2/23/2012
4 JOHNSON CONTROLS
FORM 050.40-ES3
ISSUE DATE: 2/23/2012
TABLE OF CONTENTS
SECTION 4 - PIPING...............................................................................................................................................41
DX Line Sizing Recommendations.................................................................................................................. 41
Actual Piping Routing Versus Original Piping Design..................................................................................... 41
Suction Lines................................................................................................................................................... 41
Liquid Lines..................................................................................................................................................... 44
JOHNSON CONTROLS 5
FORM 050.40-ES3
ISSUE DATE: 2/23/2012
6 JOHNSON CONTROLS
FORM 050.40-ES3
ISSUE DATE: 2/23/2012
SECTION 5 - CONTROLS.......................................................................................................................................89
Capacity Control Approaches.......................................................................................................................... 89
Variable Air Volume System............................................................................................................................ 89
ACCU Suction Pressure Control............................................................................................................ 90
Constant Volume System................................................................................................................................ 90
Supply Air Temperature Control............................................................................................................. 90
ACCU Discharge Temperature Control.................................................................................................. 90
ACCU Constant Volume Utilizing Suction Pressure Control.................................................................. 90
Economizer Operation .................................................................................................................................... 91
External BAS and Other Control Interfaces..................................................................................................... 91
Remote Setpoint Reset................................................................................................................................... 91
ACCU Condensing Unit Ambient Control .............................................................................................. 91
JOHNSON CONTROLS 7
FORM 050.40-ES3
ISSUE DATE: 2/23/2012
Oil Separator................................................................................................................................................... 98
Suction Accumulator........................................................................................................................................ 98
Refrigeration Flow Illustrations And Specialities (R-22 Examples).................................................................. 99
SECTION 7 - BRAZING.........................................................................................................................................107
General.......................................................................................................................................................... 107
Brazing Safety............................................................................................................................................... 107
Tools And Equipment Needed....................................................................................................................... 107
Procedures.................................................................................................................................................... 110
APPENDIX............................................................................................................................................................. 119
8 JOHNSON CONTROLS
FORM 050.40-ES3
ISSUE DATE: 2/23/2012
LIST OF FIGURES
JOHNSON CONTROLS 9
FORM 050.40-ES3
ISSUE DATE: 2/23/2012
10 JOHNSON CONTROLS
FORM 050.40-ES3
ISSUE DATE: 2/23/2012
LIST OF TABLES
TABLE 1 - Maximum Vertical Liquid Line Risers���������������������������������������������������������������������������������������������������������������44
TABLE 2 - Ratings - R-410A (60Hz - English Units) ����������������������������������������������������������������������������������������������56
TABLE 3 - Refrigerant Line Connections����������������������������������������������������������������������������������������������������������������56
TABLE 4 - Determine Suction Line Size/Capacity In Tons R-410A�������������������������������������������������������������������������60
TABLE 5 - Suction Line Condenser Temperature Correction Factor R-410A��������������������������������������������������������� 60
TABLE 6 - Minimum Refrigerant Capacity In Tons For Oil Entrainment Up Suction Risers R-410A����������������������� 62
TABLE 7 - Discharge And Liquid Line Capacities In Tons For Refrigerant R-410A������������������������������������������������ 64
TABLE 8 - HGBP Line Size Recommendations������������������������������������������������������������������������������������������������������66
TABLE 9 - Ratings - R-22 (English Units) ��������������������������������������������������������������������������������������������������������������69
TABLE 10 - Determine Suction Line Size Capacity In Tons For R-22��������������������������������������������������������������������73
TABLE 11 - Suction Line Condenser Temperature Correction Factor R-22������������������������������������������������������������ 73
TABLE 12 - Minimum Refrigerant Capacity In Tons For Oil Entrainment Up Suction Risers
(Type L Copper Tubing)�����������������������������������������������������������������������������������������������������������������������75
TABLE 13 - Discharge And Liquid Line Capacities In Tons For Refrigerant R-22�������������������������������������������������� 77
TABLE 14 - HGBP Line Size Recommendations����������������������������������������������������������������������������������������������������80
TABLE 15 - Refrigerant Charge In Pounds Per 100 Feet Of Liquid Line���������������������������������������������������������������� 84
TABLE 16 - Refrigerant Charge In Pounds Per 100 Feet Of Suction Line������������������������������������������������������������� 84
TABLE 17 - Pressure Drop Correction Factor���������������������������������������������������������������������������������������������������������94
TABLE 18 - Temperature Correction Factor������������������������������������������������������������������������������������������������������������94
TABLE 19 - TXV Valve Selection Based On Capacity��������������������������������������������������������������������������������������������95
TABLE 20 - Refrigerant Components, With Two Stacked Interlaced Coils With 2 TXV's And
1 LLSV Per Refrigerant Circuit R-22�������������������������������������������������������������������������������������������������102
TABLE 21 - Refrigerant Components, With 1 Full Face Dx Coil With 1 TXV Per Refrigerant Circuit R-22���������� 104
TABLE 22 - Brazing Flux��������������������������������������������������������������������������������������������������������������������������������������� 113
TABLE 23 - Suction Line Capacities In Tons For Refrigerant R-22���������������������������������������������������������������������� 119
TABLE 24 - Discharge And Liquid Line Capacities In Tons For Refrigerant R-22 ����������������������������������������������� 119
TABLE 25 - Suction Line Capacities In Tons For Refrigerant R-407C������������������������������������������������������������������ 120
TABLE 26 - Discharge And Liquid Line Capacities In Tons For Refrigerant R-407C ������������������������������������������� 120
TABLE 27 - Suction Line Capacities In Tons For Refrigerant R-410A������������������������������������������������������������������121
TABLE 28 - Discharge And Liquid Line Capacities In Tons For Refrigerant R-410A ������������������������������������������� 121
TABLE 29 - Minimum Refrigeration Capacity In Tons For Oil Entrainment Up Suction Risers
(Type L Copper Tubing)���������������������������������������������������������������������������������������������������������������������122
TABLE 30 - Minimum Refrigeration Capacity In Tons For Oil Entrainment Up Hot Gas Risers
(Type L Copper Tubing)���������������������������������������������������������������������������������������������������������������������123
TABLE 31 - Fitting Losses In Equivalent Feet Of Pipe (Screwed, Welded, Flanged And Brazed Connections)�� 124
TABLE 32 - Special Fitting Losses In Equivalent Feet Of Pipe (ASHRAE)���������������������������������������������������������� 124
TABLE 33 - Valve Losses In Equivalent Feet Of Pipe (ASHRAE)������������������������������������������������������������������������124
TABLE 34 - Refrigerant Charge In Pounds Per 100 Feet Of Suction Line����������������������������������������������������������� 125
TABLE 35 - Refrigerant Charge In Pounds Per 100 Feet Of Discharge Line������������������������������������������������������� 125
TABLE 36 - Refrigerant Charge In Pounds Per 100 Feet Of Liquid Line�������������������������������������������������������������� 125
TABLE 37 - HGBP Quick Line Selection���������������������������������������������������������������������������������������������������������������126
TABLE 38 - HGBP Line Sizing For R-22, R-407C And R-410A Refrigerants������������������������������������������������������� 126
JOHNSON CONTROLS 11
FORM 050.40-ES3
ISSUE DATE: 2/23/2012
Notes:
1. Application Guidelines outlined herein are in lined herein and are a requirement by Johnson
part based on ASHRAE Refrigeration standards. Controls. Any deviations or shortcomings must be
Manufacturers requirements are also incorporated addressed at startup and corrected prior to leav-
herein that are important to system and compo- ing the system on. Uncorrected shortcomings can
nent reliability. Any deviations to those outlined affect certain warranties (Reference the Installa-
can affect system operation and reliability. tion Guide form 050.40-CL1 that ships with every
ACCU).
2. Split-System external piping (Between ACCU
and AHU) is the responsibility of the Installing
Contractor. Split-System piping details are out-
12 JOHNSON CONTROLS
FORM 050.40-ES3
ISSUE DATE: 2/23/2012
This may sound like an over simplification, but that is • Electrical operating costs will be at their lowest
our system design goal. We hope this document com- level. This is the result of maximizing system effi-
pliments your existing HVAC system knowledge, en- ciency by minimizing suction and liquid refriger-
abling you to design highly reliable efficient solutions ant piping losses and penalties.
using YORK equipment. • The refrigerant charge requirement is minimized,
reducing initial system cost.
GENERAL EQUIPMENT INSTALLATION • This promotes environmental design responsibil-
AND LOCATION ity. Less refrigerant is available to escape into the
It is recommended that only experienced engineers de- environment, if a leak would occur.
sign remote piping systems. Experience in all aspects • The system benefits because the piping design is
of piping design, airside components, controls, and Air simpler, more direct, less complicated, and pro-
* Applies to YCUL and YLUA motes oil return.
JOHNSON CONTROLS 13
FORM 050.40-ES3
SECTION 1 - EQUIPMENT LOCATION
ISSUE DATE: 2/23/2012
• Sufficient clearances for air entrance to the con- It is important that the units be installed on a substan-
denser coil. tial base that will not settle. A one-piece concrete slab
with footers extended below the frost line is highly rec-
• Air discharge away from the condenser. ommended. Additionally, the slab should not be tied to
• Service access to the ACCU mechanical compo- the main building foundations as noise and vibration
nents and electrical panel. may be transmitted. Mounting holes are provided in
the steel base channel for bolting the unit to its founda-
• Avoid condenser air re-circulation. Recommend- tion.
ed the ACCU minimum clearances are:
For ground level installations, take precautions to pro-
• Side to wall – 6 feet tect the unit from tampering by, or injury to, unauthor-
• Rear to wall – 6 feet ized persons. Screws and/or latches on access panels
will prevent casual tampering. However, further safety
• Control panel to end wall – 4 feet precautions such as a fenced-in enclosure or locking
• Top – no obstructions allowed devices on the panels may be advisable.
• Distance between adjacent units – 10 feet For grassy areas; it is highly recommended that grass
areas surrounding a condensing unit or chiller, be far
• No more than one adjacent wall may be high- enough away so that there is no possibility of grass clip-
er than the unit pings fouling the condenser coils. It is recommended a
In installations where winter operation is intended and slab be poured, that would also offer a service area.
snow accumulations are expected, the condensing unit
ROOFTOP LOCATIONS
should be elevated to insure normal condenser airflow.
The roof structure must be capable of safely supporting the
Air-handling units can be mounted outdoors or indoors. entire operating weight of the unit and service personnel.
The location of the air-handling unit should allow for A consulting engineer should review/approve the location.
unobstructed airflow through the outside air and ex-
haust air openings, as well as easy access to the elec- Take care not to damage the roof. Consult the building
trical box and all access doors. Location of the units contractor or architect, if the roof is bonded. Isolators
should also be away from building flue stacks or ex- should be mounted under the base of the unit to mini-
haust ventilators to prevent reintroduction of contami- mize vibration.
nated air through the outside air intakes.
14 JOHNSON CONTROLS
FORM 050.40-ES3
SECTION 1 - EQUIPMENT LOCATION
ISSUE DATE: 2/23/2012
JOHNSON CONTROLS 15
FORM 050.40-ES3
SECTION 1 - EQUIPMENT LOCATION
ISSUE DATE: 2/23/2012
16 JOHNSON CONTROLS
FORM 050.40-ES3
ISSUE DATE: 2/23/2012
LD09135
JOHNSON CONTROLS 17
FORM 050.40-ES3
SECTION 2 - EQUIPMENT SELECTION
ISSUE DATE: 2/23/2012
SYS #2** SYS #1* (R-410a Glide is minimal). The coil capacity is deter-
mined by the type and amount of refrigerant used, the
temperature difference between the air and the liquid
refrigerant, and the amount of air passing over the coil.
A refrigerant distributor on each DX evaporator coil With regards to DX coil circuits – it is very important
circuit feeds low pressure, low temperature liquid re- that the number of Air Cooled Condenser Systems (or
frigerant to the coil tubes. It is critical that all the dis- circuits) be “interfaced” with the correct quantity of
tributor tubes are the same length so the pressure drop DX coil distributors (can be multiple), while allowing
across them will be equal and the refrigerant will be full face coverage and balanced capacity. See Figures
evenly distributed to the coil tubes. 3, 4 and 5(also reference SECTION 3 - COIL SELEC-
TION/CONFIGURATION for additional detail/clarifi-
As the liquid refrigerant passes through the coil tubes, cations).
heat is transferred from the supply air stream to the re-
frigerant. As heat is added to the liquid refrigerant, it Example #1
begins to evaporate much like water boiling on a stove.
Figure 3 on page 18 is for illustration purposes only.
The liquid-vapor mixture remains at a constant tem-
DX coil circuits may vary from “correct” version il-
perature and pressure until it completely vaporizes (for
lustration shown below as long as load is balanced and
R-22), while for R-407c the temperature and pressure
full face coverage is maintained.
will drop slightly due to the glide of the refrigerant
INCORRECT - Coil Load not balanced; is CORRECT - Coil Load is balanced; is Full Face per
split-faced; cannot be interfaced correctly. system; properly interfaced. LD13287
18 JOHNSON CONTROLS
FORM 050.40-ES3
SECTION 2 - EQUIPMENT SELECTION
ISSUE DATE: 2/23/2012
Example #2 Example #3
Figure 4 on page 19 is for illustration purposes only. Figure 5 on page 19 dual ACCU’s are for illustra-
DX coil circuits may vary from “correct” version il- tion purposes only (some applications may utilize dual
lustration shown below as long as load is balanced and ACCU’s to achieve greater tonnage packages. DX coil
full face coverage is maintained. circuits may vary from “correct” version illustration
shown below as long as load is balanced, full face cov-
erage is maintained, and access provision is provided). 2
Also note, ACCU % Split may vary from that shown
in this illustration..
INCORRECT - Coil Load not balanced; is CORRECT - Coil Load is balanced; is Full Face per
split-faced; cannot be interfaced correctly. system; properly interfaced.
LD13288
INCORRECT - Coil Load not balanced; is CORRECT - Coil Load is balanced; is Full Face per
split-faced; cannot be interfaced correctly. system; properly interfaced.
* Acess Provision
LD13289
JOHNSON CONTROLS 19
FORM 050.40-ES3
SECTION 2 - EQUIPMENT SELECTION
ISSUE DATE: 2/23/2012
Diaphragm
105ºF Capillary
210 psig Tube
Distributor
Evap. Coil
44ºF, 74 psig
Liquid Line
Valve Body Sensing Bulb
63ºF 59ºF, 100 psig
Superheat 108 psig
Spring
46ºF
78 psig 59ºF, 74 psig
Superheat Superheated
Adjustment
Screw (Set to 34 psig) Equalizer Line
LD09137
Figure 6 - THERMAL EXPANSION VALVE (TXV) COMPONENTS (CONDITIONS ARE WITH R-22)
20 JOHNSON CONTROLS
FORM 050.40-ES3
SECTION 2 - EQUIPMENT SELECTION
ISSUE DATE: 2/23/2012
YCUL0056EC
AIR TEMPERATURE ON CONDENSER (ºF)
SST 75ºF 80ºF 85ºF 90ºF 95ºF 100ºF
(ºF) TONS KW EER TONS KW EER TONS KW EER TONS KW EER TONS KW EER TONS KW EER
35.0 47.8 40.1 12.6 46.7 42.2 11.7 45.6 44.5 10.9 44.5 47.0 10.2 43.3 49.6 9.4 42.0 52.4 8.7
37.0 49.6 40.4 12.9 48.5 42.5 12.1 47.3 44.8 11.3 46.1 47.3 10.5 44.9 49.9 9.7 43.6 52.7 9.0
39.0 51.4 40.8 13.3 50.3 42.9 12.4 49.1 45.1 11.6 47.8 47.6 10.8 46.5 50.3 10.0 45.2 53.1 9.2
41.0 53.3 41.1 13.7 52.1 43.2 12.8 50.9 45.5 11.9 49.6 47.9 11.1 48.2 50.6 10.3 46.9 53.4 9.5
43.0
45.0
55.2
57.2
41.4
41.8
14.1
14.5
54.0
55.9
43.5
43.9
13.2
13.5
52.7
54.5
45.8
46.2
12.3
12.6
51.3
53.2
48.3
46.6
11.4
11.8
50.0
51.7
50.9
51.3
10.6
10.9
48.6
50.3
53.8
54.1
9.8
10.1
2
47.0 59.2 42.2 14.9 57.8 44.3 13.9 56.4 46.5 13.0 55.0 49.0 12.1 53.5 51.7 11.2 52.0 54.5 10.4
49.0 61.2 42.6 15.3 59.8 44.6 14.3 58.4 46.9 13.3 56.9 49.4 12.4 55.4 52.0 11.5 53.8 54.9 10.7
51.0 63.3 43.0 15.6 61.8 45.0 14.7 60.4 47.3 13.7 58.8 49.8 12.8 57.2 52.4 11.8 55.7 55.3 11.0
53.0 65.5 43.4 16.0 63.9 45.4 15.0 62.4 47.7 14.0 60.8 50.1 13.1 59.2 52.8 12.2 57.5 55.7 11.3
55.0 67.6 43.8 16.4 66.1 45.9 15.4 64.4 48.1 14.4 62.8 50.6 13.4 61.1 53.2 12.5 59.4 56.1 11.6
* ACCU Applies to YCUL and YLUA and other similar air cooled condensing units.
JOHNSON CONTROLS 21
FORM 050.40-ES3
SECTION 2 - EQUIPMENT SELECTION
ISSUE DATE: 2/23/2012
Typical OAT
YCUL0056EC
AIR TEMPERATURE ON CONDENSER (ºF)
SST 75ºF 80ºF 85ºF 90ºF 95ºF 100ºF
(ºF) TONS KW EER TONS KW EER TONS KW EER TONS KW EER TONS KW EER TONS KW EER
35.0 47.8 40.1 12.6 46.7 42.2 11.7 45.6 44.5 10.9 44.5 47.0 10.2 43.3 49.6 9.4 42.0 52.4 8.7
37.0 49.6 40.4 12.9 48.5 42.5 12.1 47.3 44.8 11.3 46.1 47.3 10.5 44.9 49.9 9.7 43.6 52.7 9.0
39.0 51.4 40.8 13.3 50.3 42.9 12.4 49.1 45.1 11.6 47.8 47.6 10.8 46.5 50.3 10.0 45.2 53.1 9.2
41.0 53.3 41.1 13.7 52.1 43.2 12.8 50.9 45.5 11.9 49.6 47.9 11.1 48.2 50.6 10.3 46.9 53.4 9.5
43.0 55.2 41.4 14.1 54.0 43.5 13.2 52.7 45.8 12.3 51.3 48.3 11.4 50.0 50.9 10.6 48.6 53.8 9.8
45.0 57.2 41.8 14.5 55.9 43.9 13.5 54.5 46.2 12.6 53.2 46.6 11.8 51.7 51.3 10.9 50.3 54.1 10.1
47.0 59.2 42.2 14.9 57.8 44.3 13.9 56.4 46.5 13.0 55.0 49.0 12.1 53.5 51.7 11.2 52.0 54.5 10.4
49.0 61.2 42.6 15.3 59.8 44.6 14.3 58.4 46.9 13.3 56.9 49.4 12.4 55.4 52.0 11.5 53.8 54.9 10.7
51.0 63.3 43.0 15.6 61.8 45.0 14.7 60.4 47.3 13.7 58.8 49.8 12.8 57.2 52.4 11.8 55.7 55.3 11.0
53.0 65.5 43.4 16.0 63.9 45.4 15.0 62.4 47.7 14.0 60.8 50.1 13.1 59.2 52.8 12.2 57.5 55.7 11.3
55.0 67.6 43.8 16.4 66.1 45.9 15.4 64.4 48.1 14.4 62.8 50.6 13.4 61.1 53.2 12.5 59.4 56.1 11.6
22 JOHNSON CONTROLS
FORM 050.40-ES3
SECTION 2 - EQUIPMENT SELECTION
ISSUE DATE: 2/23/2012
Electrical Data
Circuit 1 2 3 4
Compressor RLA 19.9/19.9 19.9/19.9
Compressor Start Current (LRA) 167.0/167.0 167.0/167.0
Fan FLA (each) 4.0 4.0
Single Point
Min. Circuit Ampacity 101.0
Min. Non-Fused Disconnect (Amps) 150.0
Min. Dual Element Fuse Size (Amps) 110.0
Max. Dual Element Fuse Size (Amps) 110.0
Min. Circuit Breaker (Amps) 110.0
Max. Circuit Breaker (Amps) 110.0
Wire Range (Lug Size) #10 - #1
Total Amps 95.6 Inrush (PW) Amps 167.0 Starter Type Across the Line
Compressor kW 49.6 Total Fan kW 5.6 Total kW 55.2
Notes:
Figure 9 - YORKWORKS CAPACITY RATING AT 95°F AIR TEMPERATURE AND 35°F SST
Electrical Data
Circuit 1 2 3 4
Compressor RLA 19.9/19.9 19.9/19.9
Compressor Start Current (LRA) 167.0/167.0 167.0/167.0
Fan FLA (each) 4.0 4.0
Single Point
Min. Circuit Ampacity 101.0
Min. Non-Fused Disconnect (Amps) 150.0
Min. Dual Element Fuse Size (Amps) 110.0
Max. Dual Element Fuse Size (Amps) 110.0
Min. Circuit Breaker (Amps) 110.0
Max. Circuit Breaker (Amps) 110.0
Wire Range (Lug Size) #10 - #1
Total Amps 95.6 Inrush (PW) Amps 167.0 Starter Type Across the Line
Compressor kW 53.2 Total Fan kW 5.6 Total kW 58.8
Notes:
Figure 10 - YORKWORKS CAPACITY RATING AT 95°F AIR TEMPERATURE AND 55°F SST
JOHNSON CONTROLS 23
FORM 050.40-ES3
SECTION 2 - EQUIPMENT SELECTION
ISSUE DATE: 2/23/2012
DXCHILLF
SMALL TONNAGE Jan 10, 2003
SCROLL CHILLER RATING REV. v4_30.yau
Issue date: 12/02
Figure 11 - DX CHILL CAPACITY RATING AT 95°F AIR TEMPERATURE AND 35°F SST
DXCHILLF
SMALL TONNAGE Jan 10, 2003
SCROLL CHILLER RATING REV. v4_30.yau
Issue date: 12/02
Figure 12 - DX CHILL CAPACITY RATING AT 95°F AIR TEMPERATURE AND 55°F SST
The same performance could be provided from the dx- Solution DX Coil Capacity Ratings
chill computer program, as shown in Figure 11 on page The YORKworks program is used to obtain a typical
24 and Figure 12 on page 24 for 35°F and 55°F rating. In this case, a “Solution” with 4 row, 12 fins per
SSTs. inch DX coil was rated. The YORKworks performance
The ACCU data points (from either the Engineering specifications are shown in Figure 13 on page 25 and
Guide chart, YORKworks or the dxchill computer rat- Figure 14 on page 25 for the entering air temperature
ing) can be used to construct the condensing unit cross of 80°F dry bulb/67°F wet bulb with 37°F and 49°F
plot. suction ETP's. These data points can be used to con-
struct the DX coil cross plot in Figure 15 on page 26.
24 JOHNSON CONTROLS
FORM 050.40-ES3
SECTION 2 - EQUIPMENT SELECTION
ISSUE DATE: 2/23/2012
LOOSE COIL
PERFORMANCE SPECIFICATION
Input Data
General Air Side Fluid Side
2
Application: Cooling Altitude (ft.) 0 Refrigeration R22
Tube Diameter: 1/2" Air Flow (cfm) 18000 Suction Temp. (ºF) 37.0
Tube Wall Thickness: 0.016" Face Velocity )ft/min): 501 No. Distributors: 4
Casing Material: Galvanized Steel EAT-DB (ºF): 80.0 Capacity Split: 50-50
Fin Material:
Fin Thickness:
Aluminum
0.006"
EAT-WB (ºF):
Max. APD (in. w.g):
67.0
2.00
Ref. Vol. (ft.³): 2.00 REFRIGERANT
Fin Height: 57.50" Req. LAT-WB (ºF) n/a TYPE
Fin Length: 90" Req. TMBH n/a
Dry Weight (lbs): 385.7
Note: Coil is not coated
Output Data
General Air Side Performance Fluid Side Performance
Rows: 4 LAT-DB (ºF): 50.51 RPD (PSI): 6.7
FPI: 12 LAT-WB (ºF) 49.65
No. of Circuits: 46 TMBH (ºF) 910.0
Suction: 2-1/8" SMBH 574.2
Liquid: 1-3/8" and 1-3/8" APD (in. w.g): 0.45
Distributor(s): 1126-11-5/16-25-30(ASC-11-7),1126-12-5/16-25-34
Note(s): All water, R22 DX and steam coils are certified in accordance to ARI Standard 410.
Figure 13 - YORKWORKS “SOLUTION” RATING - ENTERING AIR TEMP. 80°F DB/67°F WB AND 37°F ST
LOOSE COIL
PERFORMANCE SPECIFICATION
Input Data
General Air Side Fluid Side
Application: Cooling Altitude (ft.) 0 Refrigeration R22
Tube Diameter: 1/2" Air Flow (cfm) 18000 Suction Temp. (ºF) 49.0
Tube Wall Thickness: 0.016" Face Velocity )ft/min): 501 No. Distributors: 4
Casing Material: Galvanized Steel EAT-DB (ºF): 80.0 Capacity Split: 50-50
Fin Material: Aluminum EAT-WB (ºF): 67.0 Ref. Vol. (ft.³): 2.00
Fin Thickness: 0.006" Max. APD (in. w.g): 2.00
Fin Height: 57.50" Req. LAT-WB (ºF) n/a
Fin Length: 90" Req. TMBH n/a
Dry Weight (lbs): 385.7
Note: Coil is not coated
Output Data
General Air Side Performance Fluid Side Performance
Rows: 4 LAT-DB (ºF): 57.34 RPD (PSI): 2.3
FPI: 12 LAT-WB (ºF) 56.30
No. of Circuits: 46 TMBH (ºF) 592.1
Suction: 2-1/8" SMBH 437.9
Liquid: 1-1/8" and 1-1/8" APD (in. w.g): 0.44
Distributor(s): 1116-11-1/4-15-30(ASC-9-5),1116-12-1/4-15-34
Note(s): All water, R22 DX and steam coils are certified in accordance to ARI Standard 410.
592.1 MBH/12 = 49.3 Tons
LD09138
Figure 14 - YORKWORKS “SOLUTION” RATING - ENTERING AIR TEMP. 80°F DB/67°F WB AND 49°F ST
JOHNSON CONTROLS 25
FORM 050.40-ES3
SECTION 2 - EQUIPMENT SELECTION
ISSUE DATE: 2/23/2012
ACCU and DX Coil Balance Point Without point occurs at 53.8 tons and 46.9°F (SST and ETP*)
Suction Line Penalty saturated temperature. This following cross plot does
When the capacities of the ACCU and Solution DX not take the suction line penalty (losses) into account.
coil are plotted (Figure 15 on page 26), the balance
100
90
80
(37, 75.3)
SOLUTION DX Coil
70
ETP & SST
(55, 61.1)
60
Capacity, TR
50
(35, 43.3) (49, 49.0)
40
30
20
10
0
30 35 40 45 46.9 50 55
Saturated Suction Temperatures, °F
LD09139
Figure 15 - ACCU/DX COIL CROSS PLOTS - WITHOUT SUCTION LINE LOSSES (SHOWN FOR R-22)
*Both SST and ETP (saturated evaporating temperature) represent the actual design pressure/temperature relationship of the
refrigerant (by definition, when refrigerant liquid and vapor exist together, the condition is known as “saturated”). “ETP” indi-
cates the DX coil saturated evaporating temperature, while “SST” represents the ACCU design saturated suction temperature
taking “line loss” into account. (Reference Figure 16: 46.9°F ETP – 2°F Line Loss = 44.9°F SST ACCU Design).
26 JOHNSON CONTROLS
FORM 050.40-ES3
SECTION 2 - EQUIPMENT SELECTION
ISSUE DATE: 2/23/2012
ACCU and DX Coil Adjusted Balance Point 3. Next proceed vertically up to intersect with the
After Suction Line Penalty ACCU plot. This is the adjusted balance point af-
After the ETP has been determined from the cross plot, ter the suction line penalty.
the suction line penalty (which is typically 1°F to 2°F) Plotting a line through this point and in parallel to the
is subtracted from the ETP. To determine the adjusted initial DX coil line provides the new “system” line.
balance point, follow the steps below. The adjusted balance point occurs at 52.0 tons capacity
1. From the intersection of the ETP and SST, pro- for the 44.9°F ACCU SST. This results in about a 3% 2
ceed vertically down to the °F saturated tempera- reduction in system capacity. This provides a balance
ture axis. point in the 40°F to 45°F range, which is preferred for
both constant volume and variable air volume applica-
2. Then proceed horizontally 2°F to the left due to
tions (see Figure 16 on page 27).
the suction line penalty.
100
90
80
(37, 75.3)
SOLUTION DX Coil
70 Balance Point Without
System Line Suction Line Loss
(46.9 °F ETP, 53.8 TR)
ETP
60
Capacity, TR
(55, 61.1)
YCUL0056EC
SST
50
(49, 49.0)
30
20
10
2 °F Line
0
30 35 40 44.9 45 46.9 50 55
Figure 16 - ACCU/DX COIL CROSS PLOTS - ADJUSTED FOR SUCTION LINE LOSS (SHOWN FOR R-22)
JOHNSON CONTROLS 27
FORM 050.40-ES3
SECTION 2 - EQUIPMENT SELECTION
ISSUE DATE: 2/23/2012
140
130
120
110
100
90
80
Capacity, TR
70
60
50
40
30
20
10
0
30 35 40 45 50 55
Saturated Suction Temperatures, °F
LD09141
28 JOHNSON CONTROLS
FORM 050.40-ES3
SECTION 2 - EQUIPMENT SELECTION
ISSUE DATE: 2/23/2012
SYSTEM COMPARISON CONSIDERATION In this example, the smaller condensing unit (ACCU-1)
and the 6-row coil should be selected. This will re-
If the desired capacity falls between two condensing
sult in a more acceptable suction temperature of 45°F
unit sizes, it is preferable to use the smaller condensing
rather than 38°F. The benefits of using a higher suction
unit. For example, it may be possible to achieve a ca-
temperature include:
pacity of 100 tons with more than one condensing unit-
DX coil combination. Figure 18 on page 29 shows • Lower unit first cost;
that a small condensing unit coupled with a deep (6- 2
• Better full load efficiency with higher condensing
Row) cooling coil at a higher SST will provide nearly
unit EER;
the same capacity as a larger condensing unit coupled
with a shallower (4-row) coil at a lower suction tem- • Expanded part load flexibility with VAV systems
perature. by moving the system balance point away from
region of potential coil freeze-up;
• Better humidity control and reduced compressor
cycling.
6 ROW
ACCU-2
4 ROW
CAPACITY (TONS)
107
102
100
95
ACCU-1
38 41 42 45
JOHNSON CONTROLS 29
FORM 050.40-ES3
SECTION 2 - EQUIPMENT SELECTION
ISSUE DATE: 2/23/2012
METHOD #2 – BALANCE POINT/ Step 1 – Using the Engineering Guide “Ratings”, pick
CATALOGUED DATA METHOD a ACCU that can handle the tons load specified* (ex-
ample: 52 Tons). In this case we will use the same R-22
As an alternate to Method #1 Cross Plot, you can
YCUL0056EC Air Cooled Condensing Unit at 95°F
achieve virtually the same cross plot data by using
ambient, as selected in Method #1. The resultant SST
the Method #2, Catalogued Data Method. This is a
of the ACCU through interpolation is 45.3°F as refer-
two step method utilizing the Engineering Guide “Rat-
enced in Figure 19 on page 30.
ings Data”, and the design DX coil run from Solution
YORKworks (or Loose Coils in YORKworks), also
taking into account the suction line loss.
The following offers an example using the same design
as in Method #1:
Interpolation
52 Tons =
45.3 SST
30 JOHNSON CONTROLS
FORM 050.40-ES3
SECTION 2 - EQUIPMENT SELECTION
ISSUE DATE: 2/23/2012
Step 2 – Select the DX coil from YORKworks Solu- (LAT), “plus” any line loss (i.e. 56.1°F LAT – (8.8
tion Product or from Loose Coils using the ACCU de- °F ROT + 2 °F Line Loss) = a nominal 45.3°F SST
sign SST plus the line loss (i.e. 45.3°F SST + 2.0°F at the ACCU. Obviously the ROT factor can vary
Line Loss = 47.3°F ETP (DX Coil Saturated Suction beyond 8°F – 10°F, noting that a variance upward
Temperature); at the design 52.0 ton load (The load in will produce lower operating saturated suction tem-
tons should match closely the specified EAT Vs LAT perature/pressures; larger ACCU selections; and
Vs CFM). See Example Figure 20 on page 31. smaller row/fin DX coils while a variance downward 2
will produce higher saturated suction pressure/tem-
* As a rule-of-thumb (ROT), the ACCU design satu- peratures; smaller ACCU selections; and larger row/
rated suction temperature (SST) is a nominal 8°F to fin DX coils.
10°F below the DX Coil Leaving Air Temperature
47.3 °F ETP
(Saturated Suction
Temperature DX
Coil Design)
LD13286
Figure 20 - EXAMPLE FROM YORKWORKS LOOSE COILS PROGRAM (SHOWN FOR R-22)
JOHNSON CONTROLS 31
FORM 050.40-ES3
SECTION 2 - EQUIPMENT SELECTION
ISSUE DATE: 2/23/2012
32 JOHNSON CONTROLS
FORM 050.40-ES3
ISSUE DATE: 2/23/2012
Face Damper
Closes at a nominal 350 FPM face velocity
Air Flow (drop). Requires a control interface that
can vary per application. Always discuss
with Application Engineering.
DX Coils
DX Coil quantities and
arrangements can vary.
ld13290
Figure 21 - FACE DAMPER EXAMPLE
JOHNSON CONTROLS 33
FORM 050.40-ES3
SECTION 3 - COIL SELECTION/CONFIGURATION
ISSUE DATE: 2/23/2012
ACCU to DX Coil, Circuiting Interface Figures 23-27 illustrate the available coil arrange-
Always verify that the number of ACCU systems (or ments. Contact coil marketing for other arrangements
circuits) will properly interface with the DX coil circuit not shown.
quantities and allow full face coverage. Any one sys- Face-split DX coils must be configured to
tem must operate through a single LLSV located just provide full-face coverage at all condens-
ahead of the TXV (or branch). ing unit load steps. Johnson Controls
assumes no responsibility for compressor
DX COIL CIRCUITING failure if full-face coverage is not ap-
On many coil banks, two, or even all three of the meth- plied. Consult the factory, if application
ods of circuiting may be combined depending upon assistance is needed to convert split face
the cooling capacity and the level of control required. to full-face operation.
However, coil sections must be married or combined
so that they provide for full-face operation (see Figure
22 on page 34).
H2
There are numerous arrangements selectable through H1
YorkWorks (JCI Sales Selection Program). JCI Sales D2
can also request special quotation designs through their
factory Applications Engineering Group (Outside De- H1
signers can contact their local Sales JCI office to assist D1
in this). The coil designs fall into the two following D1
categories.
34 JOHNSON CONTROLS
FORM 050.40-ES3
SECTION 3 - COIL SELECTION/CONFIGURATION
ISSUE DATE: 2/23/2012
H2
H1
D2 H2
D1 D2
D1 H1
2 Distributor 2 Distributor 3
Circuits Face Split Circuits Row Split
SQ Required SQ Required
H6 H5 H2 H1
D2 D2 H3 H1 D6 D2
H2 H1
D4 D5 D1
D2
D3 D1
D4 H8 H7 H4 H3
D8 D4
D1 H4 H3 D3 D1
D7 D3
D3 H4 H2
JOHNSON CONTROLS 35
FORM 050.40-ES3
SECTION 3 - COIL SELECTION/CONFIGURATION
ISSUE DATE: 2/23/2012
H2
Single H2 Single
HDR H1
HDR H1 D2 H2 Body
Body D2
D1 H1 Single D1 D2
HDR
Body
D1 D1 H1
H6 H2 H1 H6 H5 H2 H1
Single D2 H3 H1 D6 D2
HDR D2
Body D6 D5 D1
D4 D2 D1
D3
Single
HDR
Body H5 H4 H3 H8 H7 H4 H3
D4 D8 D4
D1 D3 D1 D5
D3 D7 D3
H4 H2
Figure 26 - TALL/STACKED COIL DESIGNS - SQ SPECIAL (REQUIRES IN DEPTH INTERFACE WITH ACCU
ALLOWING FULL FACE COVERAGE.)
D2
H2 H1
D1
D4
100% Capacity
H4 H3
D3
TXV LLSV
4 Distributor
Circuits Face Split Condensing Unit
50 - 50% Interlaced DX Coil
LD09145 LD09148
Figure 27 - TALL/STACKED COIL DESIGN - Figure 28 - ONE COIL CIRCUIT PER REFRIG-
STANDARD ERANT CIRCUIT
36 JOHNSON CONTROLS
FORM 050.40-ES3
SECTION 3 - COIL SELECTION/CONFIGURATION
ISSUE DATE: 2/23/2012
Compressor #1
In the case of a tall/stacked coil with four coil circuits
piped to a ACCU with six compressors, the coil circuits
TXV LLSV would be face-split and interlaced with two interlaced
circuits on the lower coil section and two on the upper
(Figure 31 on page 38).
TXV LLSV
Compressor #2 Condensing Unit
When sizing TXV's, each TXV must be
DX Coil sized for the refrigerant circuit tonnage
divided by the number of DX coil liquid
LD09150
Do NOT use the above configuration. distributors. The TXV should be equal to
Compressor #1
or smaller than the calculated value.
TXV
Compressor #3
Feeds both Circuits LLSV
TXV
Compressor #2 Condensing Unit
DX Coil
LD09151
JOHNSON CONTROLS 37
FORM 050.40-ES3
SECTION 3 - COIL SELECTION/CONFIGURATION
ISSUE DATE: 2/23/2012
Comp 1 - 3
Hot gas must be fed to all coils to assure that full-face
operation is achieved. Since all applications have job
TXV1 specific operating characteristics, the hot gas bypass
valve setting must be field adjusted for the proper set-
TXV3 LLSV1 ting, after the system has been put into operation.
Comp 4 - 6
38 JOHNSON CONTROLS
FORM 050.40-ES3
SECTION 3 - COIL SELECTION/CONFIGURATION
ISSUE DATE: 2/23/2012
flow across the coil before the condensing unit is en- supply fan volume decreases in response. Conversely
ergized. The ACCU must never be operated unless the a lower duct static pressure indicates a need for in-
AHU fan is operating and air is flowing across the ac- creased zone airflow; therefore the supply fan volume
tive coil. Insufficient airflow will result in liquid re- increases in response. The change in supply air vol-
frigerant returning to the condensing unit, which could ume is accomplished using a variable frequency drive
damage the compressors by liquid slugging or washing or similar device.
oil from the bearing surfaces. In variable volume sys-
tems the minimum acceptable airflow for fixed speed In the air-handling unit a decrease in airflow through
or VAV systems is 350 FPM face velocity across each the DX coil will result in a corresponding decrease in
DX coil, as applied to split DX systems. (This may be the suction gas pressure while an increase in airflow
slightly different for standardized factory packages will result in an increase in the suction gas pressure.
such as packaged rooftops, which are designed, quali- Since the system is designed to maintain a constant
fied and tested under more controlled conditions.) This suction gas pressure, the compressors will be staged 3
is critical to assure that the TXV does not over-feed, on or off as needed to meet the increase or decrease
causing compressor failure. in load demand. The system should be designed to
operate smoothly avoiding transients that could upset
VAV SYSTEMS system balance and cause liquid flood back. Problems
can arise if the airflow decreases more quickly than the
Overhead variable air volume systems have been the compressor control can respond to the load change.
preferred method of air distribution since the early Therefore, consideration and limitations must be given
1970 ’s. Overhead VAV systems offered greater energy to VSD Acel/Decel times, with regard to extending the
efficiency and better control of building diversity than timing to a point that will accommodate proper chiller
constant volume systems. Unlike a constant volume compressor cycling, system temperature swings, etc.
system, in which the leaving air temperature is ad- This limitation will promote stable control of the Air
justed to satisfy the cooling load, in a VAV system the Cooled Condensing Unit and minimize fluctuations in
air temperature remains constant and the air volume is zone temperature. Review must also be given to VSD
varied to meet the cooling requirements. ramp-down speed with regard to smoke/fire damper
There are four basic components in a VAV system - an closure, so as not to produce excessive duct pressures
air-handling unit with airflow control (i.e., variable- that can damage the AHU or system. Under any cir-
speed drives), VAV boxes, zone thermostats and duct cumstances, a minimum of 350 FPM face velocity
static pressure sensors. All of these components must across the coil must be maintained for field erected DX
work together to provide good temperature control and split systems.
a comfortable environment. The zone thermostats con-
BUILDING AUTOMATION SYSTEM INTERFACE
trol the VAV boxes. As the zone temperature increases,
the VAV boxes open to allow greater airflow into the Control schemes involving complex Building Automa-
space and as the zone temperature decreases, the VAV tion Systems (BAS) are beyond the basic equipment or
boxes close to decrease the airflow to the space. optional factory packaged design capabilities. In these
cases, please contact the Field Support Center for as-
As the VAV boxes in the system open and close the sistance. This group provides solutions for expanded
static pressure in the ductwork changes. When a box interfacing with a third party BAS. They can also solve
opens, the duct static pressure decreases, and when unique sequencing challenges of the air handling unit
a box closes, the duct static pressure increases. The and matching condensing unit combination. BAS con-
duct static pressure sensor controls the air handling trol must adhere to all control guidelines outlined in
unit supply fan. Since an increase in duct pressure re- this manual.
lates to a decrease in the zone airflow required, the
JOHNSON CONTROLS 39
FORM 050.40-ES3
SECTION 3 - COIL SELECTION/CONFIGURATION
ISSUE DATE: 2/23/2012
40 JOHNSON CONTROLS
FORM 050.40-ES3
ISSUE DATE: 2/23/2012
SECTION 4 - PIPING
DX LINE SIZING RECOMMENDATIONS It is also important that the total equivalent feet of
piping be 150 feet or less (Always review IOM for
The piping must conform to the local codes. For the
maximum limitations).
best pipe sizing and design practices, refer to either
the information in this manual or the ASHRAE Refrig- ACTUAL PIPING ROUTING VERSUS
eration Handbook. These contain refrigerant line siz- ORIGINAL PIPING DESIGN
ing for full and minimum capacities and other pertinent
engineering information for a wide application range. It is extremely important that the piping design on a
The tables listed below are presented for the 35, 45 and ACCU system is correct to assure oil is returned and
55°F saturated suction temperatures, which are typical liquid slugging does not result. Often during instal-
for these systems. The tables are included at the end of lation, piping is not routed according to the original
this manual in the Appendix. designer’s specifications. Problems can often result
when piping is rerouted around obstacles. Whenever a
Table 23 – Suction Line Capacities in Tons for change is made to the routing of the piping, the install-
Refrigerant R-22 er should consult with the designer prior to making the
Table 24 – Discharge and Liquid Line Capacities in change. This will assure that the change will not affect
Tons for Refrigerant R-22 4
system oil return or cause liquid slugging.
Table 25 – Suction Line Capacities in Tons for
Refrigerant R-407c Proper refrigerant pipe selection and design is crucial
Table 26 – Discharge and Liquid Line Capacities in for efficient and reliable operation of the refrigeration
Tons for Refrigerant R-407c system. It is also important to keep liquid refrigerant/
Table 27 – Suction Line Capacities in Tons for oil slugs from entering the compressor and for assuring
Refrigerant R-410c oil return. Over-sizing the piping reduces the refrigerant
Table 28 – Discharge and Liquid Line Capacities in Tons pressure drop, but can inhibit oil return and adds unnec-
for Refrigerant R-410a essary first cost. On the other hand, under-sizing the pip-
Table 29 – Minimum Refrigeration Capacity in Tons for ing increases the refrigerant pressure drop, which affects
Oil Entrainment Up Suction Risers
system performance and lowers the efficiency.
(Type L Copper Tubing)
Table 30 – Minimum Refrigeration Capacity in Tons for For best results, use long radius elbows (short radius
Oil Entrainment Up Hot Gas Risers elbows have higher pressure drops) for everything
(Type L Copper Tubing) except oil traps. Also, clean copper tubing for refrig-
Table 31 – Fitting Losses in Equivalent Feet of Pipe eration and air conditioning application should be used
(Screwed, Welding, Flanged and Brazed throughout. Provisions must be made for piping con-
Connections) traction and expansion of 3/4” per 100’ of pipe.
Table 32 – Special Fitting Losses in Equivalent Feet of
Pipe (ASHRAE) SUCTION LINES
Table 33 – Valve Losses in Equivalent Feet of Pipe
(ASHRAE)
Figure 21 on page 33 (see Appendix) shows suc-
Table 34 – Refrigerant Charge in Pounds Per 100 Feet of
tion line sizing recommendations, which are typically
Suction Line based on 2°F (nominal 3 PSI for R-22 and R-407c, and
Table 35 – Refrigerant Charge in Pounds Per 100 Feet of 4.5 PSI for R-410a) loss. As was illustrated in SEC-
Discharge Line TION 2 - EQUIPMENT SELECTION, a typical 2°F
Table 36 – Refrigerant Charge in Pounds Per 100 Feet of drop in suction pressure can reduce the system capac-
Liquid Line ity by about 3%. Therefore, it is good practice to design
Table 37 – HGBP Quick Line Selection) the suction piping with no more than a 2°F line loss at
Table 38 – HGBP Line Sizing for R-22, R-407c and full load.
R-410a Refrigerants
Additionally, care must be taken not to oversize the suc-
Keeping the condensing unit and air-handler as close tion piping, because oil return can be compromised to the
together as possible is recommended. This is important compressors. The horizontal suction line runs should be
for assuring oil return and compressor reliability. sloped ½” per 10 linear feet in the direction of refriger-
ant flow to promote moving oil toward the compressors.
Trapped sections of the suction line must be avoided.
JOHNSON CONTROLS 41
FORM 050.40-ES3
SECTION 4 - PIPING
ISSUE DATE: 2/23/2012
ACCU
CORRECT
Suction Line pitched in direction of
flow into ACCU suction inlet
connection.
INCORRECT
Section of Suction Line.
EVAPORATOR COIL
LD13291
AIR COOLED
CONDENSING UNIT
AIR HANDLING UNIT
INCORRECT
Unwanted Trapped
Section Of Suction
Line
LD13292
42 JOHNSON CONTROLS
FORM 050.40-ES3
SECTION 4 - PIPING
ISSUE DATE: 2/23/2012
Trapped sections of suction line must not All suction lines with a vertical rise exceeding 3’ should
be formed between the DX coil suction have an oil trap at the bottom and top (inverted) of the
riser and the ACCU suction inlet. Suction riser. A maximum suction line rise of 40’ is recom-
lines should pitch directly into the Air mended (Always consult Application Engineering on
Cooled Condensing Unit (ACCU) suc- risers over 40 feet). Any riser in excess of 20’ should
tion inlet. Also, lack of a riser just off the have a trap installed mid-way up the riser (e.g. 14’ for
DX coil (where DX coil is above ACCU) a 28’ total rise). An inverted trap should be placed at
can produce compressor crankcase oil the top of a single suction riser. Use long radius elbows
dilution during the off cycle by allowing wherever possible, except when fabricating oil return
refrigerant vapor to condense and drain traps at the bottom of the vertical riser, which should
excessive liquid refrigerant into the com- use short radius 45° street elbows. Short radius elbows
pressor. Examples of “correct and incor- will minimize the amount of oil trapped in the system.
rect trapped sections of suction line” are See Figure 34 on page 43.
shown in Figure 32. (2) Short Radius 45º
Street Elbows
Oil and refrigerant, which condenses in the line during
off periods, must drain into the compressor and will be
boiled off by the compressor heater. This prevents oil
and liquid refrigerant slugging of the compressors. 4
It is recommended that a suction line
should never be run under ground.
90º Short Radius
Underground runs cause problematic Elbow
LD09154
refrigerant condensation in suction lines
and often create suction line traps. Always Figure 34 - SUCTION OIL LINE TRAP
consult Application Engineering when
underground piping is specified. Other
means, above ground piping, should
always be presented at the bidding stage. If the DX coil is above the ACCU, the suction piping
must rise above the top of the coil to form an inverted
Orders should never be accepted without underground trap. See Figure 35 on page 43. The inverted trap
piped details worked out, and having Application Engi- will keep liquid refrigerant from condensing in the
neering SQ (Special Quotation) acceptance. Figure 33 evaporator, during the off cycle, and draining into the
on page 42 offers an example of when underground compressors. An oil trap should be installed at the bot-
piping is never acceptable. tom of the vertical rise. This is recommended by ex-
pansion valve manufacturers to keep the oil away from
Many systems require suction risers, because the DX the bulb during operation.
coil is located at a lower level than the condensing unit.
These suction risers must be sized to ensure oil entrain-
ment up the riser at the lowest step of loading. In some DX COIL
cases double suction risers may be required. Refer to
Table 29 on page 122 and Table 30 on page 123 (see
Appendix) or the ASHRAE Refrigeration Handbook for
oil return at the minimum STEP to find the minimum
capacity which is required to maintain good oil entrain-
ment for a given line size. Also, see Determining the
TO COMPRESSORS
Need for Double Suction Risers on Page 62. LD09155
JOHNSON CONTROLS 43
FORM 050.40-ES3
SECTION 4 - PIPING
ISSUE DATE: 2/23/2012
44 JOHNSON CONTROLS
FORM 050.40-ES3
SECTION 4 - PIPING
ISSUE DATE: 2/23/2012
JOHNSON CONTROLS 45
FORM 050.40-ES3
SECTION 4 - PIPING
ISSUE DATE: 2/23/2012
EXAMPLES OF ACCU-DX COIL PIPING The illustration below shows one refrigerant circuit,
ARRANGEMENTS when the ACCU is less than 20 feet above the AHU in-
terlaced DX coil. The horizontal suction line run should
When the ACCU is located above the AHU, DX coil,
be sloped a minimum of ½ inch per 10 feet from the
double suction risers may be required to ensure good
suction riser, toward the compressors to proper oil flow.
oil return to the ACCU, if there is not adequate tonnage
Double suction risers are shown for illustration only.
and velocity up a single riser. Most applications will
Most applications will need only single risers. In lieu
only need single suction risers; however, double ris-
of double suction risers, the vertical suction riser can be
ers are shown in the following diagrams for illustration
downsized for proper oil entrainment at minimum re-
purpose only. Only one refrigerant circuit is illustrated.
duced load, providing the overall suction line pressure
This will be similar for the second circuit.
drop doesn’t exceed a nominal 2°F.
FACTORY MOUNTED
SUCTION GAS
CONNECTION
CHECK
VALVE
EQUALIZER
LINE
FILTER DRIER
LIQUID LINE
SOLENOID VALVE
Figure 36 - PIPING WHEN ACCU IS LESS THAN 20 FT. ABOVE THE DX COIL
46 JOHNSON CONTROLS
FORM 050.40-ES3
SECTION 4 - PIPING
ISSUE DATE: 2/23/2012
This illustration shows one refrigerant circuit when the Double suction risers are shown for illustration only.
ACCU is 20 feet or more above the AHU, DX coil. Most applications will need only single risers. In lieu
An oil trap is required mid way up the vertical rise. of double suction risers, the vertical suction riser can
The horizontal suction line must be sloped a minimum be downsized for proper oil entrainment at minimum
of ½" per 10 ft. toward the compressors for oil flow. reduced load, providing the overall suction line pres-
sure drop doesn’t exceed a nominal 2°F.
FACTORY MOUNTED
SUCTION GAS
CONNECTION
Suction Line
LD13285
CHECK
VALVE
EQUALIZER
LINE
FILTER DRIER
LIQUID LINE
SOLENOID VALVE
LD13284a
JOHNSON CONTROLS 47
FORM 050.40-ES3
SECTION 4 - PIPING
ISSUE DATE: 2/23/2012
SUCTION LINE
DISTRIBUTOR
WITH HOT GAS
CONNECTION
CHECK
VALVE
HOT GAS
BYPASS
FACTORY MOUNTED
LIQUID STOP VALVE
LIQUID
LINE
OPTIONAL FACTORY MOUNTED FILTER DRIER
HOT GAS BYPASS VALVE
(SEE FIGURE 36, DETAIL A)
LIQUID LINE
SOLENOID VALVE
SIGHT GLASS -
MOISTURE INDICATOR
THERMAL
EXPANSION
VALVES
**
** CLOSE COUPLED
(3 FT NOM. MAX.)
CAN INCLUDE ELBOWS
LD13293
48 JOHNSON CONTROLS
FORM 050.40-ES3
SECTION 4 - PIPING
ISSUE DATE: 2/23/2012
This illustration shows one refrigerant circuit when Use Table 1 - Maximum Vertical Distance
the ACCU is lower than the AHU interlaced DX coil. for DX Coil Above the ACCU for the total
Again the horizontal suction line must be sloped a min- equivalent piping lengths.
imum of ½" per 10 ft. toward the compressors for oil
flow. In lieu of double suction risers, the vertical suc-
tion riser can be downsized for proper oil entrainment
at minimum reduced load, providing the overall suc-
tion line pressure drop doesn’t exceed a nominal 2°F.
DISTRIBUTOR
WITH HOT GAS
LIQUID LINE CONNECTION
HOT GAS SOLENOID VALVE
BYPASS
THERMAL
EXPANSION
LIQUID LINE VALVE
SIGHT GLASS -
MOISTURE
INDICATOR
FACTORY
MOUNTED
SUCTION GAS
CONNECTION **
** CLOSE COUPLED
(3 FT NOM. MAX. TOTAL
LINEAR HORIZONTAL RUN)
THERMAL CAN INCLUDE ELBOWS
EXPANSION
VALVE
SUCTION LINE
FACTORY MOUNTED
LIQUID STOP VALVE
JOHNSON CONTROLS 49
FORM 050.40-ES3
SECTION 4 - PIPING
ISSUE DATE: 2/23/2012
This illustration shows one refrigerant circuit when lustration only. Most applications will need only single
the ACCU is less than 20 ft. above the AHU with two risers. In lieu of double suction risers, the vertical suc-
stacked interlaced DX coils for full face coverage. The tion riser can be downsized for proper oil entrainment
horizontal suction line must be sloped a minimum of at minimum reduced load, providing the overall suc-
½" per 10 ft. from the suction riser toward the compres- tion line pressure drop doesn’t exceed a nominal 2°F.
sors for oil flow. Double suction risers are shown for il-
FACTORY MOUNTED
LIQUID STOP VALVE CHECK VALVE
DISTRIBUTOR
LIQUID LINE
WITH HOT GAS
CONNECTION
THERMAL
EXPANSION VALVE
LIQUID LINE
SOLENOID VALVE
FILTER DRIER
SIGHT GLASS -
MOISTURE INDICATOR
CHECK
VALVE
** CLOSE COUPLED
(3 FT NOM. MAX. TOTAL
LINEAR HORIZONTAL RUN)
** CAN BE STRAIGHT RUN
DISTRIBUTOR
WITH HOT GAS
CONNECTION
Figure 40 - PIPING WHEN ACCU IS LESS THAN 20 FT. ABOVE STACKED DX COILS
50 JOHNSON CONTROLS
FORM 050.40-ES3
SECTION 4 - PIPING
ISSUE DATE: 2/23/2012
This illustration shows one refrigerant circuit when the Double suction risers are shown for illustration only.
ACCU is more than 20 ft. above the AHU with two Most applications will need only single risers. In lieu
stacked interlaced DX coils for full face coverage. An of double suction risers, the vertical suction riser can
oil trap is required mid way up the vertical rise. The be downsized for proper oil entrainment at minimum
horizontal suction line must be sloped a minimum of reduced load, providing the overall suction line pres-
½" per 10 ft. from the suction riser toward the com- sure drop doesn’t exceed a nominal 2°F.
pressors for oil flow.
FACTORY MOUNTED
SUCTION GAS
CONNECTION
Suction Line
LD13285 4
SEE DETAIL A
Optional HGBP Valve, factory installed in
OPTIONAL ACCU. Run 1/4" capillary to a point on the
FACTORY top of the suction line away from ACCU.
FACTORY MOUNTED
** HOT GAS DETAIL A
MOUNTED LIQUID
STOP VALVE BYPASS NOTE: 410a ACCU's utilized seperate
VALVE
HGBP control valves and solenoid valves.
(SEE
DETAIL A)
SUCTION GAS
RISERS LIQUID LINE
CHECK
VALVE
EQUALIZER
LINE
FILTER DRIER
LIQUID LINE
SOLENOID VALVE
Figure 41 - PIPING WHEN ACCU IS MORE THAN 20 FT. ABOVE STACKED DX COILS
JOHNSON CONTROLS 51
FORM 050.40-ES3
SECTION 4 - PIPING
ISSUE DATE: 2/23/2012
This illustration shows one refrigerant circuit when lieu of double suction risers, the vertical suction riser
the ACCU is at the same level as the AHU with two can be downsized for proper oil entrainment at mini-
stacked interlaced DX. The horizontal suction line mum reduced load, providing the overall suction line
must be sloped a minimum of ½" per 10 ft. from the pressure drop doesn’t exceed a nominal 2°F.
suction riser toward the compressors for oil flow. In
SUCTION LINE
DISTRIBUTOR
WITH HOT GAS
CONNECTION
THERMAL
EXPANSION VALVE
FACTORY MOUNTED
LIQUID STOP VALVE
LIQUID
OPTIONAL FACTORY LINE
MOUNTED HOT GAS
BYPASS VALVE FILTER DRIER
(SEE FIGURE 36,
DETAIL A)
LIQUID LINE
SOLENOID VALVE
** DISTRIBUTOR
WITH HOT GAS
CONNECTION
52 JOHNSON CONTROLS
FORM 050.40-ES3
SECTION 4 - PIPING
ISSUE DATE: 2/23/2012
This illustration shows one refrigerant circuit when the Use Table 1 - Maximum Vertical Distance
ACCU is lower than the AHU with two stacked inter- for DX Coil Above the ACCU for the total
laced coils. The horizontal suction line must be sloped equivalent piping lengths.
a minimum of ½" per 10 ft. from the suction riser to-
ward the compressors for oil flow. In lieu of double
suction risers, the vertical suction riser can be down-
sized for proper oil entrainment at minimum reduced
load, providing the overall suction line pressure drop
doesn’t exceed a nominal 2°F.
CHECK
VALVE DISTRIBUTOR
WITH HOT GAS
CONNECTION
HOT GAS
BYPASS
LIQUID LINE 4
SOLENOID VALVE
THERMAL
EXPANSION VALVE
FILTER DRIER
SIGHT GLASS -
MOISTURE INDICATOR
LIQUID LINE
CHECK
VALVE
FACTORY
MOUNTED ** ** CLOSE COUPLED
SUCTION GAS (3 FT NOM. MAX. TOTAL LINEAR
CONNECTION HORIZONTAL RUN)
CAN INCLUDE ELBOWS
SUCTION LINE
FACTORY MOUNTED
LIQUID STOP VALVE
JOHNSON CONTROLS 53
FORM 050.40-ES3
SECTION 4 - PIPING
ISSUE DATE: 2/23/2012
PIPING – SIZE AND SELECTION PRACTICES Making the Initial YORKworks Selection
OVERVIEW Given the following required initial data, acquire the
Pipe sizing is critical to oil management as well as line YORKworks ACCU selection for this project:
loss considerations. Oil management states that oil
• Refrigerant Type (This example uses the more
should return to the compressor at the same rate that it
current R-410a)
leaves the compressor. Line loss limitations protect the
chiller against low suction pressure faults as well as an • Capacity required (73.5 tons)
excessive loss in capacity at the ACCU.
• Design Ambient Temperature (95°F)
The following JCI pipe line loss limitations parallel
• Design ACCU Saturated Suction Temperature
ASHRAE refrigeration standards. Practices base line
(SST). Generally a nominal 10°F below the LAT of
sizing as follows:
the DX Coil can be assumed. Note the following:
• Liquid Lines not to exceed a value of about 1°F • This example will assume 55°F LAT - 10°F =
line loss 45° SST at the ACCU.
• Suction Lines not to exceed a value of about 2°F • It should be noted here that if DX Coil Rows
line loss and FPI, or airside PD are already specified,
• Hot Gas Bypass (HGBP) line sizing is outlined in you can select the DX Coil first to identify
Table 37 and 38 of this form the DX Coil SST and then subtract the indus-
try standard 2°F suction line loss to acquire
• Maximum Suction, Liquid and Hot Gas Bypass the estimated SST design of the ACCU.
(HGBP) line equivalent feet allowed is a nomi-
nal 150 equivalent feet (100 EF on YCAV/YCIV This example offers model YCUL0072EE46 from
product – HGBP is not applicable). YORKworks Sales/Marketing Electronic Tool. (see
following and Figure 44 on page 55). This example
The following paragraphs and pages offer line sizing also notes the minimum tons for HGBP (optional).
examples using R-410a and R-22/R-407c refrigerant,
as well as specific table references found in the back
of this guide.
If YORKworks is not available, you can
use the Sales Engineering Guide in part
to acquire the initial data mentioned.
Engineer Guides can be downloaded from
the www.JCI.com website.
54 JOHNSON CONTROLS
FORM 050.40-ES3
SECTION 4 - PIPING
ISSUE DATE: 2/23/2012
Sales/Marketing
YORKworks Program
Electronic Tool
LD15947
Note: Compressors 5, 4, 2, & 1 shown in this Note - Select HGBP line size based on the
sequence. Compressors 6 & 3 N/A in this system. minimum/nominal part load rang of 17.7 tons
LD16013
JOHNSON CONTROLS 55
FORM 050.40-ES3
SECTION 4 - PIPING
ISSUE DATE: 2/23/2012
50 AND 60HZ
50 – 90 TON
175 – 316 KW
R-410A
LD15949
56 JOHNSON CONTROLS
FORM 050.40-ES3
SECTION 4 - PIPING
ISSUE DATE: 2/23/2012
4
12'
DX COIL
LD09157a
The Following is Referenced for Determining All Refrigerant Lines must be sloped
Equivalent Feet of Pipe: ½” per 10 feet minimum in direction
• 3’ horizontally of refrigerant flow to support good oil
management (Oil comes back to the com-
• 12’ vertically up pressor at the same rate that it leaves the
• 10’ horizontally compressor).
• (2) 90° long radius elbows Maximum allowable pipe runs must not
exceed 150 equivalent feet (100 Equiva-
lent feet for YCAV and YCIV). Reference
LONG RADIUS ELBOWS “Dealing with Excessive Line Lengths”
ACCU
on page 59 of this guide.
10'
12'
DX COIL
3'
LD09158a
JOHNSON CONTROLS 57
FORM 050.40-ES3
SECTION 4 - PIPING
ISSUE DATE: 2/23/2012
58 JOHNSON CONTROLS
FORM 050.40-ES3
SECTION 4 - PIPING
ISSUE DATE: 2/23/2012
JOHNSON CONTROLS 59
FORM 050.40-ES3
SECTION 4 - PIPING
ISSUE DATE: 2/23/2012
Suction Line Full Load Duty Selection Equivalent Feet of Pipe Correction
Procedure In this example, the equivalent feet of pipe length from
Continuing the R-410a example above as outlined in the following page shows 41 equivalent feet using the
the assumptions on page 57 and percent system split 1-5/8” suction line selected. This, along with the actual
on page 58, make an initial system #1 suction line se- tonnage will be used in calculating the final line loss.
lection using Table 27 on page 121 in the Appendix
(Also Table 4 on page 60 of this example). Calculating Final Line Loss - Calculating the actual
Δt line loss using the formula under note 4 of Table 4
Given the 41.9 actual tons in this example, the initial on page 60 calculates to 2.16°F line loss (Loss from
line size selection would suggest a 1-5/8” suction line DX Coil to ACCU):
at the design 45° SST assumption, based on the short
equivalent feet run in this example. The initial line ca- Δt = 2.16°F falls at about the 2°F allowable line loss,
pacity per 100 equivalent feet of 1-5/8” pipe shows and is best suited in this example. An initial check
27.5 tons. would show going one size larger at 2-1/8 would push
the Δt well under the design 2°F line loss to 0.69°F
Condensing Temperature Correction and although would work, is not the best selection in
this example.
The 1-5/8" line size capacity is next corrected for the
actual 120°F condensing temperature noted in the as- This line loss is used to determine the required suction
sumption example. The correction factor is selected temperature design of the DX Coil (i.e. 45°F @ ACCU
from bottom of Table 27 on page 121, also listed in + 2.16°F = 47.16°F SST DX Coil Design). This line
this example under Table 5 on page 60 (i.e. 27.5 Ta- loss can also be used to determine the ACCU SST with
ble tons x 0.89 = 24.47 adj. tons). a given DX Coil SST (i.e. DX Coil °F SST – calculated
Table 4 - DETERMINE SUCTION LINE SIZE/CA- line loss °F = °F SST @ ACCU.
PACITY IN TONS R-410A Reference PIPING EXAMPLE #2 for
Saturated Suction Temperature, R-22 and R-407c Refrigerants.
Line Size ºF -R-410a
35 45 55
Type L Cooper ∆t = 2 ºF ∆t = 2 ºF ∆t = 2 ºF
OD Inches ∆p = 4.11 ∆p = 4.87 ∆p = 5.34
7/8 4.06 5.00 6.10 Suction Line Equivalent Feet Review
1 1/8 8.20 10.00 13.00
In this example the Suction Line Equivalent Feet Esti-
1 3/8 14.27 17.50 20.70
mation comes to 41 Equivalent Feet (Reference Figure
1 5/8 22.50 27.50 32.60 49 on page 61).
2 1/8 46.51 56.50 67.50
Table 5 - SUCTION LINE CONDENSER TEMPER-
1 5/8 81.96 96.50 118.00 ATURE CORRECTION FACTOR R-410A
3 1/8 130.50 157.00 187.50 CONDENSING SUCTION DISCHARGE
NOTES: TEMPERATURE °F LINE LINE
1. ∆p = Pressure drop due to line friction, psi per 100 feet equiva- 80 1.17 0.82
lent length. 90 1.10 0.89
2. ∆t = Change in saturation temperature corresponding to pressure 100 1.04 0.96
drop, per 100 feet.
110 0.96 1.03
3. Line capacity for other saturation temperatures ∆t and equivalent
120 0.89 1.10
lengths Le.
∆ 130 0.81 1.16
Line capacity = Table capacity
∆ NOTE: Some tables may present the data differently, but through
4. Saturation temperature ∆t for other capacities and equivalent the formulas the output is the same.
lengths Le
∆t =Table ∆t
60 JOHNSON CONTROLS
FORM 050.40-ES3
SECTION 4 - PIPING
ISSUE DATE: 2/23/2012
Suction Line Piping Equivalent Feet Estimation Equivalent Feet of pipe is used in deter-
Line Sizing (Diameter) is based on the total equivalent mining the final line loss on the previous
feet of pipe run for each given suction line. Any change page 60, as well as to assure you are
in the selected pipe size diameter will vary the equiva- within the maximum 150 equivalent feet
lent feet of pipe (See Figure 49 on page 61 losses design criteria.
for various pipe diameters). So it is important to re-
visit Table 4 on page 60 and Figure 49 on page 61 Determining Pipe Fitting Loss
if the line size diameter selection has changed. In this
From Figure 49 tabulate the equivalent feet loss for
example the linear feet estimation and fittings BOM
each fitting itemized (see left). Keep in mind vertical
are outlined in Figure 46 on page 57 with equivalent
suction “risers” in excess of 20’ must include an inter-
feet estimates tabulated below.
mediate trap at mid point, and if suction risers exceed
Suction Piping Equivalent Feet Tabulation 40’, always discuss with JCI Application Engineering
Using 1-5/8” Diameter Pipe: (or Include in Special Quotation in YORKworks - SQ).
Linear Length Feet = 3’ + 12’ + 10’ = 25’ When using Figure 49, note that the tube
Total Estimated Equivalent Length Feet = size is listed as nominal. Always use the 4
+ 3.0’ [horizontally] size closest to the actual (i.e. Actual 1-5/8”
+ 4.2’ [(2) 45° Street fittings] would use a nominal 1-1/2” size as in this
[~2.1 eq. feet/elbow*] example).
+ 4.0’ [(1) 90° Standard fitting]
[~4.0 eq. feet/elbow*]
+ 7.8’ [(3) 90° Long radius elbows]
[~2.6 eq. feet /elbow*]
+ 12’ [vertically]
+ 10’ [horizontally]
= 41.0’ → equivalent
90°
° Flow Straight-Through Flow
° Std.a
90° Long b 90°° ° Std.a
45° 45°° 180°
°
Radius Streeta Streeta Std.a Through
Branch No Reduced Reduced
Nominal Reduction 1/4 1/2
Pipe or
Tube 1/2d
Size, in. d 3/4d d
3/8 1.4 0.9 2.3 0.7 1.1 2.3 2.7 0.9 1.2 1.4
1/2 1.6 1.0 2.5 0.8 1.3 2.5 3.0 1.0 1.4 1.6
3/4 2.0 1.4 3.2 0.9 1.6 3.2 4.0 1.4 1.9 2.0
1 2.6 1.7 4.1 1.3 2.1 4.1 5.0 1.7 2.2 2.6
1-1/4 3.3 2.3 5.6 1.7 3.0 5.6 7.0 2.3 3.1 3.3
1-1/2 4.0 2.6 6.3 2.1 3.4 6.3 8.0 2.6 3.7 4.0
2 5.0 3.3 8.2 2.6 4.5 8.2 10.0 3.3 4.7 5.0
2-1/2 6.0 4.1 10.0 3.2 5.2 10.0 12.0 4.1 5.6 6.0
3 7.5 5.0 12.0 4.0 6.4 12.0 15.0 5.0 7.0 7.5
3-1/2 9.0 5.9 8.2 4.7 7.3 15.0 18.0 5.9 8.0 9.0
4 10.0 6.7 10.0 5.2 8.5 17.0 21.0 6.7 9.0 10.0
5 13.0 8.2 12.0 6.5 11.0 21.0 25.0 8.2 12.0 13.0
6 16.0 10.0 15.0 7.9 13.0 25.0 30.0 10.0 14.0 16.0
LD09160
JOHNSON CONTROLS 61
FORM 050.40-ES3
SECTION 4 - PIPING
ISSUE DATE: 2/23/2012
Refrigeration capacity in tons is based on 90°F liquid temperature and superheat as indicated by the temperature in the table.
The saturated condensing and suction conditions are referenced to the dewpoint for R-407C. For other liquid line tempera-
tures, use correction factors to the capacity given in the table below.
LIQUID TEMPERATURE, °F
REFRIGERANT
50 60 70 80 100 110 120 130 140
R-410A 1.21 1.16 1.11 1.05 0.94 0.89 0.82 0.76 0.68
62 JOHNSON CONTROLS
FORM 050.40-ES3
SECTION 4 - PIPING
ISSUE DATE: 2/23/2012
Red.
Evap. Tee
45o Str.
Ells
LD09061
JOHNSON CONTROLS 63
FORM 050.40-ES3
SECTION 4 - PIPING
ISSUE DATE: 2/23/2012
Table 7 - DISCHARGE AND LIQUID LINE CAPACITIES IN TONS FOR REFRIGERANT R-410A
LINE SIZE DISCHARGE LINES (∆t = 1 ºF, ∆p = 4.75psi) LINE SIZE LIQUID LINES
64 JOHNSON CONTROLS
FORM 050.40-ES3
SECTION 4 - PIPING
ISSUE DATE: 2/23/2012
90°
° Flow Straight-Through Flow
° Std.a
90° Long 90°° ° Std.a
45° 45°° 180°
°
Radius b Streeta Streeta Std.a Through
Branch No Reduced Reduced
Nominal Reduction 1/4 1/2
Pipe or
Tube 1/2d
Size, in. d 3/4d d
3/8 1.4 0.9 2.3 0.7 1.1 2.3 2.7 0.9 1.2 1.4
1/2 1.6 1.0 2.5 0.8 1.3 2.5 3.0 1.0 1.4 1.6
3/4 2.0 1.4 3.2 0.9 1.6 3.2 4.0 1.4 1.9 2.0
1 2.6 1.7 4.1 1.3 2.1 4.1 5.0 1.7 2.2 2.6
1-1/4 3.3 2.3 5.6 1.7 3.0 5.6 7.0 2.3 3.1 3.3
1-1/2 4.0 2.6 6.3 2.1 3.4 6.3 8.0 2.6 3.7 4.0
2 5.0 3.3 8.2 2.6 4.5 8.2 10.0 3.3 4.7 5.0
2-1/2 6.0 4.1 10.0 3.2 5.2 10.0 12.0 4.1 5.6 6.0
3 7.5 5.0 12.0 4.0 6.4 12.0 15.0 5.0 7.0 7.5
3-1/2 9.0 5.9 8.2 4.7 7.3 15.0 18.0 5.9 8.0 9.0
4 10.0 6.7 10.0 5.2 8.5 17.0 21.0 6.7 9.0 10.0
5 13.0 8.2 12.0 6.5 11.0 21.0 25.0 8.2 12.0 13.0
6 16.0 10.0 15.0 7.9 13.0 25.0 30.0 10.0 14.0 16.0
LD09160
JOHNSON CONTROLS 65
FORM 050.40-ES3
SECTION 4 - PIPING
ISSUE DATE: 2/23/2012
66 JOHNSON CONTROLS
FORM 050.40-ES3
SECTION 4 - PIPING
ISSUE DATE: 2/23/2012
LD15950
Figure 52 - HGBP LINE SIZE RECOMMENDATIONS LINE GRAPHS FOR R-22, R-407C AND R-410A
Determining Final HGBP Line Sizing Looking at 17.7 tons @ 29 EF plots a point between a
Given the design of 29 equivalent feet (EF) of HGBP 7/8” line size and a 1-1/8”. Given the minimum tons
pipe run, and the minimum turndown capacity of 17.7 are offered as 100% of the minimum turndown com-
tons, determine from either Table 8 on page 66 pressor, the selection is somewhat conservative and
or Figure 52 on page 67 the best line size using would suggest the closer of the two curves. In this case
R-410a. the final HGBP selection would suggest a 7/8” line
size as acceptable.
Using Table 8 on page 66 would suggest an initial
selection of 7/8” given the short equivalent feet of pipe
run. Referencing Figure 52 on page 67 allows a
more detailed view of the selection.
JOHNSON CONTROLS 67
FORM 050.40-ES3
SECTION 4 - PIPING
ISSUE DATE: 2/23/2012
PIPING EXAMPLE #2 – LINE SIZING PRACTICE USING R-22 (R-407C SIMILAR) REFRIGERANT
• Suction Lines not to exceed a value of about 2°F • Design Ambient Temperature (95°F)
line loss • Design ACCU Saturated Suction Temperature
• Hot Gas Bypass (HGBP) line sizing is outlined in (SST). Generally a nominal 10°F below the LAT
Table 14 on page 80 or Figure 60 on page 80 of the DX Coil can be assumed. Note the follow-
of this form ing:
• Maximum Suction, Liquid and Hot Gas Bypass • This example will assume 55°F LAT - 10°F =
(HGBP) line equivalent feet allowed is a nomi- 45° SST ESTIMATE at the ACCU
nal 150 equivalent feet (100 EF on YCAV/YCIV • It should be noted here that if DX Coil Rows
product – HGBP is not applicable). and FPI, or airside PD are already specified,
The following paragraphs and pages offer line sizing you can select the DX Coil first to identify
Example #2 using R-22 (R-407c refrigerant is virtually the DX Coil SST and then subtract the indus-
the same and will not be covered as an example), as try standard 2°F suction line loss to acquire
well as specific table references found in the back of the estimated SST design of the ACCU.
this guide. Reference Example #1 for R-410a Refriger- This example offers model YCUL0076EC46 out of the
ant Systems. Sales Engineering Guide. See below and Figure 53.
Figure 53 also notes under Physical Data the minimum
nominal tons for HGBP (Optional).
68 JOHNSON CONTROLS
FORM 050.40-ES3
SECTION 4 - PIPING
ISSUE DATE: 2/23/2012
PIPING EXAMPLE #2 – LINE SIZING PRACTICE USING R-22 (R-407C SIMILAR) REFRIGERANT
FORM 150.63-EG1 (308)
4
Air-Cooled Scroll Condensing Units
Style C
15 – 130 TON
53 – 457 kW
R-22 & HFC-407C
60 Hz
LD15952
Through interpolation the 70 tons It is noted that the 70 tons specified in this
required equates to a 46°F SST vs example has a slightly warmer SST but is
the original estimate of 45°F SST. acceptable for this design LAT of 55°F.
JOHNSON CONTROLS 69
FORM 050.40-ES3
SECTION 4 - PIPING
ISSUE DATE: 2/23/2012
PIPING EXAMPLE #2 – LINE SIZING PRACTICE USING R-22 (R-407C SIMILAR) REFRIGERANT
TABLE 9 - RATINGS - R-22 (ENGLISH UNITS) (CONT'D)
12'
DX COIL
LD09157a
70 JOHNSON CONTROLS
FORM 050.40-ES3
SECTION 4 - PIPING
ISSUE DATE: 2/23/2012
PIPING EXAMPLE #2 – LINE SIZING PRACTICE USING R-22 (R-407C SIMILAR) REFRIGERANT
The Following is Referenced for Determining In this continued example, we have System #1 at a
Equivalent Feet of Pipe: nominal 39 tons (3 nominal 13 ton scrolls) and System
• 3’ horizontally #2 at a nominal 30 tons (3 nominal 10 tons scrolls).
This example will address system #1 only, noting that
• 12’ vertically up
system #2 is selected in the same manner.
• 10’ horizontally
• (2) 90° long radius elbows 1. All Refrigerant Lines must be sloped ½” per 10
feet minimum in direction of refrigerant flow to
LONG RADIUS ELBOWS
support good oil management (Oil comes back to
ACCU the compressor at the same rate that it leaves the
10' compressor).
2. Maximum allowable pipe runs must not exceed
150 equivalent feet (100 Equivalent feet for
YCAV and YCIV). Reference “Dealing with Ex-
12' cessive Line Lengths” on page 72 of this guide.
DX COIL
JOHNSON CONTROLS 71
FORM 050.40-ES3
SECTION 4 - PIPING
ISSUE DATE: 2/23/2012
PIPING EXAMPLE #2 – LINE SIZING PRACTICE USING R-22 (R-407C SIMILAR) REFRIGERANT
Calculating the Final System Capacity 150’ equivalent lengths (100 equivalent feet for YCAV
Given the specified total ACCU capacity of 70 tons (Ref- or YCIV), always contact JCI Application Engineering
erence Table 9 on page 69), and the percent split for for direction. In virtually all cases the direction will be
system #1 of 57% (Reference Figure 56 on page 71), to move the DX Coil and the ACCU closer together,
the system #1 capacity to size for is (70 x 0.57) 39.9 tons. or the pipe run will need to be re-routed and short-
System #2 would be calculated in the same manner. ened following practices outlined in this guide.
Design Data and Assumptions Suction Line Full Load Duty Selection
Procedure
The following offers the accumulated design data and
assumptions from the previous example pages. Note Continuing the R-22 example above as outlined in
that this is the required minimum information neces- the assumptions on page 72 and percent system split
sary for determining piping line sizing requirements. on page 71, make an initial system #1 suction line se-
lection using Table 23 on page 119 in the Appendix
Reference PIPING EXAMPLE #1 for (Also Table 10 on page 73 of this example).
R-410a Refrigerants noting that R-407c
refrigerants are very similar to R-22 as in Given the 39.9 actual tons in this example, the initial
this example. line size selection would suggest a 2-1/8” suction line
at the design 46° SST assumption, based on the short
equivalent feet run in this example. The initial line ca-
pacity per 100 equivalent feet of 2-1/8” pipe shows
Example Design Data/Assumptions 36.85 tons by interpolation.
• ACCU: R-22, YCUL0076EC, 70.0 tons @ full
load (System #1 is only addressed in this example) Condensing Temperature Correction
• 95°F ambient (the condensing temperature is typi- The 2-1/8” line size capacity is next corrected for the
cally about 25°F above the design ambient tem- actual 120°F condensing temperature noted in the as-
perature or about 120°F in this example. This is sumption example. The correction factor is selected
generally the same for other ACCU refrigerant from Table 11 on page 73 (i.e. 36.85 Table tons x
types . . . always verify if uncertain) 0.92 = 33.9 adj. tons).
• 46°F saturated suction temperature Equivalent Feet of Pipe Correction
• System #1 capacity of 39.9 tons In this example, the equivalent feet of pipe length from
• System #1 minimum capacity of 13.0 tons the following page shows 45.1 equivalent feet using the
2-1/8” suction line selected. This, along with the actual
• Arrangement - DX Coil below the ACCU ar-
tonnage will be used in calculating the final line loss.
rangement with lengths, traps and fittings count
as outlined in Figure 54 on page 70 and Figure Calculating Final Line Loss - Calculating the actual
55 on page 71) Δt line loss using the formula under note 4 of Table 10
on page 73 calculates to 1.2°F line loss (Loss from
Example Design Data – Computer Rating DX Coil to ACCU):
Not field available for R-22 and R-407c (Contact Ap- 1.8
Actual L e Actual capacity
plication Engineering).
∆t = Table∆t
Table L e Table capacity
Dealing with Excessive Line Lengths
In estimating the line size diameter it is important to note
that the “maximum” equivalent pipe length must not ex- 1.8
45.1 39.9
ceed a nominal 150 equivalent feet (100 equivalent feet Δt = 2
for YCAV or YCIV). Note also that any change in your 100 33.9
initial pipe diameter will vary the equivalent feet of pipe
for any fixed pipe length and trap/fitting count. Also, Δt = 1.2°F falls within the 2°F allowable line loss, and
when pipe run initial estimates exceed the maximum is best suited in this example. An initial check would
72 JOHNSON CONTROLS
FORM 050.40-ES3
SECTION 4 - PIPING
ISSUE DATE: 2/23/2012
PIPING EXAMPLE #2 – LINE SIZING PRACTICE USING R-22 (R-407C SIMILAR) REFRIGERANT
show going one size smaller at 1-5/8 would push the Δt Table 11 - SUCTION LINE CONDENSER TEM-
well over the design 2°F line loss to around 3.5°F and PERATURE CORRECTION FACTOR R-22
would create excessive suction line pressure losses and CONDENSING SUCTION DISCHARGE
a potential for low suction faults and reduced capacity. TEMPERATURE °F LINE LINE
80 1.12 0.82
1. This line loss is used to determine the required
90 1.07 0.89
suction temperature design of the DX Coil (i.e.
100 1.03 0.96
46°F @ ACCU + 1.2°F = 47.2°F SST DX Coil
Design. This line loss can also be used to deter- 110 0.97 1.03
mine the ACCU SST with a given DX Coil SST 120 0.92 1.10
(i.e. DX Coil °F SST – calculated line loss °F = °F 130 0.87 1.16
SST @ ACCU. 140 0.82 1.22
NOTES:
1. ∆p = Pressure drop due to line friction, psi per 100 feet equiva-
lent length.
2. ∆t = Change in saturation temperature corresponding to pressure
drop, per 100 feet.
3. Line capacity for other saturation temperatures ∆t and equivalent
lengths Le.
∆
Line capacity = Table capacity
∆
4. Saturation temperature ∆t for other capacities and equivalent
lengths Le
∆t =Table ∆t
JOHNSON CONTROLS 73
FORM 050.40-ES3
SECTION 4 - PIPING
ISSUE DATE: 2/23/2012
PIPING EXAMPLE #2 – LINE SIZING PRACTICE USING R-22 (R-407C SIMILAR) REFRIGERANT
Suction Line Piping Equivalent Feet Estimation Suction Piping Equivalent Feet Tabulation
Line Sizing (Diameter) is based on the total equivalent using 2 1/8” Diameter Pipe
feet of pipe run for each given suction line. Any change Linear Length Feet = 3’ + 12’ + 10’ = 25’
in the selected pipe size diameter will vary the equiv- Total Estimated Equivalent Length Feet =
alent feet of pipe (See Figure 57 on page 74 losses
for various pipe diameters). So it is important to re-visit + 3.0’ [horizontally]
Table 10 on page 73 and Figure 57 on page 74 if + 5.2’ [(2) 45° Street fittings]
the line size diameter selection has changed. [~2.6 eq. feet /elbow*]
+ 5.0’ [(1) 90° Street fittings]
In this example the linear feet estimation and fittings [~5.0 eq. feet /elbow*]
BOM are outlined in Figure 55 on page 71 with + 9.9’ [(3) 90° Long radius elbows]
equivalent feet estimates tabulated below. [~3.3 eq. feet /elbow*]
+ 12.0’ [vertically]
Equivalent Feet of pipe is used in de-
+ 10.0’ [horizontally]
termining the final line loss (Δt) on the
= 45.1’ Equivalent Feet Pipe Length
previous page 72, as well as to assure you
are within the maximum 150 equivalent Determining Pipe Fitting Loss
feet design criteria (100 EF for YCAV and From Figure 57 on page 74 tabulate the equivalent
YCIV product). feet loss for each fitting itemized (see left). Keep in
mind vertical suction “risers” in excess of 20’ must in-
Suction Line Equivalent Feet Review clude an intermediate trap at mid point, and if suction
In this example the Suction Line Equivalent Feet Esti- risers exceed 40’, always discuss with JCI Applica-
mation comes to 45.1 Equivalent Feet (Reference Page tion Engineering (or Include in Special Quotation in
74). YORKworks - SQ).
90°
° Flow Straight-Through Flow
° Std.a
90° Long 90°° ° Std.a
45° 45°° 180°
°
Radius b Streeta Streeta Std.a Through
Branch No Reduced Reduced
Nominal Reduction 1/4 1/2
Pipe or
Tube 1/2d
Size, in. d 3/4d d
3/8 1.4 0.9 2.3 0.7 1.1 2.3 2.7 0.9 1.2 1.4
1/2 1.6 1.0 2.5 0.8 1.3 2.5 3.0 1.0 1.4 1.6
3/4 2.0 1.4 3.2 0.9 1.6 3.2 4.0 1.4 1.9 2.0
1 2.6 1.7 4.1 1.3 2.1 4.1 5.0 1.7 2.2 2.6
1-1/4 3.3 2.3 5.6 1.7 3.0 5.6 7.0 2.3 3.1 3.3
1-1/2 4.0 2.6 6.3 2.1 3.4 6.3 8.0 2.6 3.7 4.0
2 5.0 3.3 8.2 2.6 4.5 8.2 10.0 3.3 4.7 5.0
2-1/2 6.0 4.1 10.0 3.2 5.2 10.0 12.0 4.1 5.6 6.0
3 7.5 5.0 12.0 4.0 6.4 12.0 15.0 5.0 7.0 7.5
3-1/2 9.0 5.9 8.2 4.7 7.3 15.0 18.0 5.9 8.0 9.0
4 10.0 6.7 10.0 5.2 8.5 17.0 21.0 6.7 9.0 10.0
5 13.0 8.2 12.0 6.5 11.0 21.0 25.0 8.2 12.0 13.0
6 16.0 10.0 15.0 7.9 13.0 25.0 30.0 10.0 14.0 16.0
LD09160
74 JOHNSON CONTROLS
FORM 050.40-ES3
SECTION 4 - PIPING
ISSUE DATE: 2/23/2012
PIPING EXAMPLE #2 – LINE SIZING PRACTICE USING R-22 (R-407C SIMILAR) REFRIGERANT
When using Figure 57, note that the liquid condensing temperature. Our Design criteria/
tube size is listed as nominal. Always use assumptions on page xx show the liquid condensing
the size closest to the actual (i.e. Actual temperature to be 120°F.
2-1/8” would use a nominal 2” size as in
this example) We must now adjust for the actual liquid temperature
leaving the condenser. Using Table 12 on page 75
“Liquid Temperature, °F” chart/note, we find the cor-
Determining the Need for Double Suction rection value for 105°F liquid condensing temperature
Risers (120°F CT - 15°F sub cooling) to be 0.935 times the
Double suction risers are required where the turndown 7.7 = 7.2 ton minimum allowable turndown. With the
capacity of the ACCU system is less than the suction actual minimum load being 13 tons > the adjusted 7.2
line piping minimum refrigerant capacity for oil en- minimum, the need for double suction risers is not re-
trainment up a vertical riser, as outlined in the appen- quired in this example.
dix Table 29 on page 122 (also Table 12 on page 75 It should be noted here that over sizing a
in this example). suction line can lead to the possible need
In this continued example, referencing Table 9 on page
for double suction risers, keeping in mind 4
that any unnecessary piping is unwanted
69, "Physical Data" shows a minimum load for sys-
piping. While accepting a slightly higher
tem #1 at 13 tons. Using Table 12 on page 75, for
(say less than 10% higher than the 2.0°F
the 2-1/8” suction line selected in this example (with
target) °F suction line loss can possibly
46°F SST and 56°F Suction Gas Temp assuming 10°F
eliminate the need for double suction ris-
superheat at minimum load), use the value closest to
ers. You can also consider just downsizing
the 46°F SST of 40°F (in chart), with a suction gas
the vertical riser portion.
temperature of (40 + 10) 50°F. This offers a 7.7 nomi-
nal ton minimum allowable turndown based on a 90°F
Table 12 - MINIMUM REFRIGERANT CAPACITY IN TONS FOR OIL ENTRAINMENT UP SUCTION RISERS (TYPE
L COPPER TUBING)
SATURATION SUCTION PIPE O.D., IN.
1/ 2 5/ 8 3/ 4 7/ 8 1-1/8 1-3/8 1-5/8 2-1/8 2-5/8 3-1/8 3-5/8 4-1/8
REFRIGERANT SUCTION GAS TEMP.,
AREA, IN2
TEMP., °F °F 0.233 0.348 0.484 0.825 1.256 1.780 3.094 4.770 6.812 9.213 11.97
-30 0.07 0.12 0.20 0.30 0.59 0.99 1.53 3.05 5.25 8.19 11.95 16.57
-40 -10 0.07 0.12 0.20 0.30 0.58 0.97 1.51 3.00 5.16 8.06 11.75 16.30
10 0.07 0.12 0.20 0.30 0.58 0.98 1.52 3.02 5.19 8.11 11.82 16.40
-10 0.09 0.16 0.26 0.39 0.76 1.28 1.97 3.94 6.77 10.57 15.41 21.38
-20 10 0.09 0.15 0.25 0.38 0.74 1.26 1.95 3.89 6.68 10.42 15.20 21.09
30 0.09 0.15 0.26 0.39 0.75 1.27 1.96 3.92 6.73 10.51 15.33 21.26
10 0.11 0.20 0.33 0.49 0.96 1.63 2.52 5.03 8.63 13.48 19.65 27.26
R-22 0 Correction30
Liquid 0.11 0.19
Factor: Based on the0.32 0.49 120°F
assumption 0.94 condensing
1.60 2.47 temperature
4.93 8.47 13.22 19.29 26.75
50 0.11 0.20 0.32 0.49 0.95 1.61 2.49 4.97 8.54 13.33 19.44 26.96
minus the normal design 15°F sub-cooling @ 95°F ambient = (120 - 15) = 105°F
30 0.14 0.25 0.41 0.62 1.20 2.03 3.15 6.28 10.78 16.84 24.56 34.06
Liquid Temperature. By interpolation the correction factor = 0.935 in this example.
20 50 0.14 0.24 0.40 0.61 1.19 2.01 3.11 6.21 10.66 16.65 24.28 33.68
70 0.14 0.24 0.40 0.61 1.19 2.01 3.11 6.20 10.65 16.63 24.25 33.64
50 0.17 0.30 0.50 0.76 1.48 2.49 3.86 7.70 13.22 20.64 30.11 41.76
40 70 0.17 0.30 0.49 0.74 1.45 2.45 3.78 7.55 12.96 20.24 29.52 40.94
90 0.17 0.30 0.49 0.74 1.45 2.45 3.78 7.55 12.97 20.26 29.54 40.98
Refrigeration capacity in tons is based on 90°F liquid temperature and superheat as indicated by the temperature in the table.
The saturated condensing and suction conditions are referenced to the dewpoint for R-407C. For other liquid line tempera-
tures, use correction factors to the capacity given in the table below.
LIQUID TEMPERATURE, °F
REFRIGERANT
50 60 70 80 100 110 120 130 140
R-22 1.16 1.12 1.08 1.04 0.98 0.91 0.87 0.82 0.78
JOHNSON CONTROLS 75
FORM 050.40-ES3
SECTION 4 - PIPING
ISSUE DATE: 2/23/2012
PIPING EXAMPLE #2 – LINE SIZING PRACTICE USING R-22 (R-407C SIMILAR) REFRIGERANT
76 JOHNSON CONTROLS
FORM 050.40-ES3
SECTION 4 - PIPING
ISSUE DATE: 2/23/2012
PIPING EXAMPLE #2 – LINE SIZING PRACTICE USING R-22 (R-407C SIMILAR) REFRIGERANT
Table 13 - DISCHARGE AND LIQUID LINE CAPACITIES IN TONS FOR REFRIGERANT R-22
LINE SIZE DISCHARGE LINES (∆t = 1 ºF, ∆p = 3.03 psi) LINE SIZE LIQUID LINES
NOTES:
Capacities are in tons of refrigeration.
∆p = Pressure drop due to line friction, psi per 100 feet
equivalent length.
∆t = Change in saturation temperature corresponding to
Liquid Line Piping Equivalent Feet Estimation
pressure drop, per °F per 100 feet.
Line capacity for other saturation temperatures ∆t and Line Sizing (Diameter) is based on the total equiva-
equivalent lengths Le. lent feet of pipe run for each given liquid line. Any
Line capacity = Table capacity change in the selected pipe size diameter will vary the
∆ equivalent feet of pipe (See Figure 57 on page 74
∆
losses for various pipe diameters). So it is important
to re-visit Figure 57 on page 74 and the “Calculat-
Saturation temperature ∆t for other capacities and equivalent ing Final Liquid Line Loss” on page 79 if the line size
lengths Le diameter has changed.
∆t =Table ∆t
In this example the linear feet estimation and fittings
BOM are outlined in Figure 55 on page 71 with
equivalent feet estimates tabulated as follows.
Equivalent Feet of pipe is used in de-
termining the final line loss as outlined
below, as well as to assure you are within
the maximum 150 equivalent feet design
criteria (100 equivalent feet on YCAV and
YCIV product).
JOHNSON CONTROLS 77
FORM 050.40-ES3
SECTION 4 - PIPING
ISSUE DATE: 2/23/2012
PIPING EXAMPLE #2 – LINE SIZING PRACTICE USING R-22 (R-407C SIMILAR) REFRIGERANT
90°
° Flow Straight-Through Flow
° Std.a
90° Long b 90°° ° Std.a
45° 45°° 180°
°
Radius Streeta Streeta Std.a Through
Branch No Reduced Reduced
Nominal Reduction 1/4 1/2
Pipe or
Tube 1/2d
Size, in. d 3/4d d
3/8 1.4 0.9 2.3 0.7 1.1 2.3 2.7 0.9 1.2 1.4
1/2 1.6 1.0 2.5 0.8 1.3 2.5 3.0 1.0 1.4 1.6
3/4 2.0 1.4 3.2 0.9 1.6 3.2 4.0 1.4 1.9 2.0
1 2.6 1.7 4.1 1.3 2.1 4.1 5.0 1.7 2.2 2.6
1-1/4 3.3 2.3 5.6 1.7 3.0 5.6 7.0 2.3 3.1 3.3
1-1/2 4.0 2.6 6.3 2.1 3.4 6.3 8.0 2.6 3.7 4.0
2 5.0 3.3 8.2 2.6 4.5 8.2 10.0 3.3 4.7 5.0
2-1/2 6.0 4.1 10.0 3.2 5.2 10.0 12.0 4.1 5.6 6.0
3 7.5 5.0 12.0 4.0 6.4 12.0 15.0 5.0 7.0 7.5
3-1/2 9.0 5.9 8.2 4.7 7.3 15.0 18.0 5.9 8.0 9.0
4 10.0 6.7 10.0 5.2 8.5 17.0 21.0 6.7 9.0 10.0
5 13.0 8.2 12.0 6.5 11.0 21.0 25.0 8.2 12.0 13.0
6 16.0 10.0 15.0 7.9 13.0 25.0 30.0 10.0 14.0 16.0
LD09160
78 JOHNSON CONTROLS
FORM 050.40-ES3
SECTION 4 - PIPING
ISSUE DATE: 2/23/2012
PIPING EXAMPLE #2 – LINE SIZING PRACTICE USING R-22 (R-407C SIMILAR) REFRIGERANT
Calculating Final Liquid Line Loss When applying HGBP to both systems,
Calculating the actual Δt line loss using the formula keep in mind that System #2 may have a
under Δt of Table 13 on page 77 calculates to 0.33°F different compressor capacity as in this
line loss and approximates the 1.0°F design loss and example of a nominal 10 tons as refer-
validates the selection (See following): enced in Table 9.
JOHNSON CONTROLS 79
FORM 050.40-ES3
SECTION 4 - PIPING
ISSUE DATE: 2/23/2012
PIPING EXAMPLE #2 – LINE SIZING PRACTICE USING R-22 (R-407C SIMILAR) REFRIGERANT
LD16017
Figure 60 - HGBP LINE SIZE RECOMMENDATIONS LINE GRAPHS FOR R-22, R-407C AND R-410A
Determining Final HGBP Line Sizing 80 allows a more detailed view of the selection.
Given the design of 30 equivalent feet (EF) of HGBP Looking at 13.0 tons @ 30 EF plots a point between
pipe run, and the minimum turndown capacity of 13.0 a 7/8” line size and a 1-1/8”. Given the minimum tons
tons, determine from either Table 14 on page 80 or are offered as 100% of the minimum turndown com-
Figure 60 on page 80 the best line size using R-22. pressor, the selection is somewhat conservative and
would suggest the closer of the two curves. In this case
Using Table 14 on page 80 would suggest an ini- the final HGBP selection would suggest a 1-1/8” line
tial selection of 1-1/8”. Referencing Figure 60 on page size as the best selection.
80 JOHNSON CONTROLS
FORM 050.40-ES3
SECTION 4 - PIPING
ISSUE DATE: 2/23/2012
When charging a system it is important to note that the ACCU Refrigerant Charge
charge is best executed on a “design ambient” day. The ACCU refrigerant charge can be taken directly
from the IOM under “Physical Data” (Reference Fig-
When “initially” charging a split system, best practice
ure 61 on page 82). As a rule of thumb, each sys-
is to first weigh in the charge estimate, keeping in mind
tem condenser coil(s) can hold a pump down charge
this is only an estimate and is the first step. Once the cor-
of approximately 1.5 times the “operating” charge
rect charge is weighed in, a nominal 15°F sub-cooling
catalogued for the condenser coil system (Reference
(Always review target sub-cooling value specified in
Figure 61 on page 82).
IOM) at the condenser coil outlet must be measured
(nominal 10°F on YCAV and YCIV Product). Special It is important to note here that the place- 4
note here is the sub-cooling must also be accompanied ment of the Liquid Line Solenoid valve is
by a “clear liquid line site glass”. Increasing the sub- critical and must be located at the evapo-
cooling a few degrees may be required to clear the rator, close to the TXV’s. This location
glass (again, on a design ambient day). allows the refrigerant charge to be stored
in the Liquid Line as well as the ACCU
Non-Design Ambient Days - On non-design ambient during pumpdown.
days, some degree of innovativeness must be exer-
cised. Keep in mind that the lower the ambient from
design, the higher the sub-cooling (i.e. a properly
charged system of say 17°F sub-cooling at 95°F Am-
bient, might reflect 28°F~ sub-cooling when at 50°F
ambient as an example). It should also be noted in the
Service Log that this charge should be reviewed again
at some closer design ambient (i.e. within 10°F of the
design ambient).
A packaged system with an apparent low charge should
not have the charge removed and re-weighed as a norm.
When charging a system it should be not-
ed that the initial charge before running a
compressor should be at least 80% of the
final design charge (Running a compres-
sor with a system under 80% can damage
the compressor due to inadequate cooling
and poor oil return). Also keep in mind,
initial overcharging is also detrimental to
the compressor.
JOHNSON CONTROLS 81
FORM 050.40-ES3
SECTION 4 - PIPING
ISSUE DATE: 2/23/2012
LD16012
Figure 61 - ACCU REFRIGERANT CHARGE
Evaporator Coil Refrigerant Charge In replicating the Evaporator Coil selection in York-
The DX Coil evaporator charge is only a rough weight Works “Loose Coils” to acquire the estimated Re-
estimate. This weight can vary depending on load, etc. frigerant Charge, reference the selection under “Fluid
The weight estimate can be acquired through York- Weight” as indicated in Figure 62 on page 83. Note
Works (See Figure 62 on page 83) or by estimating that the Loose Coil run shows the refrigerant “Fluid
the coil volume in cubic feet and applying the follow- Wt.” per coil. In this example you must multiply the
ing calculation: Fluid Wt. times the total number of coils. Once you
determine the total Evaporator Coil(s) weight you must
1. [Estimated Refrigerant Weight = Coil Vol. Cu. Ft. multiply it times the System #1 % Split as shown in
calculated x 20% x “Constant” 78 (Refrigerant Figure 62 on page 83:
Density/Cu Ft~)]
2. [This example would calculate [1.37 Cu. Ft. “Fig As in this example some systems (Or cir-
62” x 0.20 x 78 = 21.37 lbs Refrigerant Charge cuits) have uneven splits. When splitting
estimate per coil] x 2 Coils = 42.7 lbs total Evapo- the charge per the number of systems,
rator Coil(s) charge] always factor the percent split (i.e. 50/50;
55/45; 60/40, etc.).
3. [(Multiply the % Split x Total calculated charge =
charge per system) = 42.7 x 55% = 23.5 lbs charge
for System #1]. This may vary somewhat from
YORKworks, but again is an estimate.
82 JOHNSON CONTROLS
FORM 050.40-ES3
SECTION 4 - PIPING
ISSUE DATE: 2/23/2012
4
2 Systems (Circuits)
With 55/45 Split
LD16011
JOHNSON CONTROLS 83
FORM 050.40-ES3
SECTION 4 - PIPING
ISSUE DATE: 2/23/2012
84 JOHNSON CONTROLS
FORM 050.40-ES3
SECTION 4 - PIPING
ISSUE DATE: 2/23/2012
Summary: Step #1 Charge Estimates • Step #2 – Set the Sub-Cooling (Always review
(Weigh-in Charge) target sub-cooling value specified in IOM) at a
nominal 15°F - 17°F~ (nominal 10°F on YCAV/
System #1 Summary:
YCIV Product).
65.00 Lb 410a - ACCU (Figure 61)
a. Sub-cooling should be reviewed at the con-
19.80 Lb 410a - DX Coil (Evap)
denser coil outlet at the liquid line service
5.71 Lb 410a - Split-System Piping
valve (except YCAV/YCIV).
90.51 Lb 410a Total Weigh-in Charge
b. YCAV/YCIV’s with “remote evaporators”
System #2 Summary: or with “packaged evaporators” require Sub-
65.00 Lb 410a - ACCU (Figure 61) cooling to be measured at or close to the
16.20 Lb 410a - DX Coil (Evap)* flash tank.
5.71 Lb 410a - Split-System Piping • Step #3 – Clear the Sight Glass with a solid col-
86.91 Lb 410a Total Weigh-in Charge umn of liquid (basically add charge to raise the
sub-cooling number until glass is clear). DO NOT
*DX Coil Total Charge of 36 lbs – System #1 OVER CHARGE!
charge of 19.8 lbs = Sys #2 Charge of 16.2 lbs
This is the approximate operating charge ACCU Pumpdown Holding Charge Capability 4
which is estimated for the system. The Review
system should never be started with less Pumpdown capacity of a system is important in re-
than 80% of the operating charge in the moving the refrigerant from the low side of the system
system. Following the weigh-in charge and store it on the high side between the compressor
estimate, it is essential to then “Trim” to (As applicable, against the Internal Check Valve on
the final system operating charge. Scrolls), up to the LLSV at the DX Coil (The impor-
tance of the LLSV being located at the DX Coil is to
Trimming the Charge utilize the liquid line for pump down storage).
Trimming the charge should be performed on a design Pumpdown minimizes migration of the liquid refrig-
ambient day with all condenser fans running, at normal erant into the compressor and/or unwanted storage in
head pressures, and the “system” fully loaded. the suction line during the off cycle. Failure to provide
proper pump down storage can result in refrigerant
Being as much as 10°F below design ambient is ac-
liquid slugging and bearing lubrication washout at the
ceptable, but it is important to note that a “lower ambi-
compressor.
ent” means “higher” sub-cooling numbers (i.e. If a sys-
tem is “correctly” charged on a design day of say 16°F Generally, most if not all split-systems piped with the
sub-cooling, then at 10°F below this ambient the sub- above understanding have sufficient high side pump
cooling value may read some higher number). Some down capability. Those that don’t follow piping guide-
innovativeness is required on the part of the Technician lines outlined herein, or where oversized evaporator
to produce meaningful numbers, and ultimately a cor- coils come into play, may not have sufficient pump
rect charge. down capability and may require correcting the piping
arrangement and/or adding liquid refrigerant receiver
Following Step #1 (Weigh-in Charge), it is essential
(always consult with Application Engineering on Liq-
now to trim the charge using steps #2 and #3:
uid Refrigerant Receivers).
JOHNSON CONTROLS 85
FORM 050.40-ES3
SECTION 4 - PIPING
ISSUE DATE: 2/23/2012
Pumpdown Requirements for Example #1 a 5% factor for return bends and headers, and then ap-
using R-410a Refrigerant plying the refrigerant density/cu ft. The above example
Rule of Thumb Selection - The YCUL0072EE46 total calculates to 0.811 cu ft per coil times 2 coils/system =
system #1 operating and pump-down charge is 90.51 1.622 cu ft per system x 79.79 refrigerant density for
lbs (see Step #1 above). As a rule of thumb, each sys- R-410a = 129 lb refrigerant. A typical condenser can
tem condenser coil(s) can hold a pump down charge only hold 70% of the required charge (allowing 20%
of 1.5 times the “operating” charge catalogued for the for refrigerant gas and 10% for safety margin). This
condenser coil system (see design data Engineering closer review shows an available pumpdown volume
Guide or IOM). For this YCUL example, the operating of 90 lbs (129 x 70%) which will easily hold the 86 lbs
charge catalogued is 65 lb as noted in step #1 above. adjusted charge (again, discounting liquid line charge).
Using the rule-of-thumb of 65 lb x 1.5 allows a holding Obviously acquiring the correct rows, tube diameter,
charge estimate of 98 Lb. Given the proper piping prac- wall thickness, tube lengths and tube quantities is
tice of locating the LLSV at the Evaporator Coil, which cumbersome and not an easy undertaking and would
provides adequate pumpdown storage of the liquid line require “factory” review by your Sales/Marketing Ap-
charge, adjusts the pumpdown volume necessary to 86 plication Engineering support group.
lb (65 ACCU + 19.8 Coil + 1.2 Suction Line). The 86
lb is well within the available 98 lb estimate providing The following offers an example for calculating the
adequate pumpdown capacity. suggested maximum refrigerant pumpdown as out-
lined above. In this example, there are two coils, so the
Calculated Selection - A closer estimate of condenser total refrigerant pumpdown volume is approximately
coil charge holding capability would entail calculating 90 lbs (45.29 x 2 coils):
the total condenser coil tube volume in cubic feet plus
Example:
Solve for Cubic Inches – Example: 3/8" copper tube with .014" tube wall x 98" long x 144 tubes
Solve R = 0.375" – (.014" x 2) = 0.347" Inside diameter/2 = 0.1735" Radius
A = πr2 x Coil Tube Length x # of Tubes x Return Bend Add-on Factor
A = 3.1416 x 0.17352 x 98" x 144 tubes = 1334.56 cubic inches x 1.05 Return Bend Factor = 1401.28
Cubic Inches to Cubic Feet = cubic inches ÷ 1728 = 1401.28 ÷ 1728 = 0.811 cubic feet
R-410a Refrigerant Density @ 40°F = 79.79 lb/ft3 (R-22 = 79.05; R134a = 79.90)
Ref. Wt Cond. Coil Can Hold = 79.79 x 0.811 Cubic Foot = 64.71 lb Refrigerant x 70% = 45.29 lb Ref PD/Coil
86 JOHNSON CONTROLS
FORM 050.40-ES3
SECTION 4 - PIPING
ISSUE DATE: 2/23/2012
AIR HANDLING UNIT DX COIL Install a trapped condensate drain line at unit drain
CONDENSATE DRAIN PIPING connection (See Figure 64 on page 87) according to
all governing codes. “H” dimension must be at least
The majority of cooling coils are located in the air han-
1/2 inch greater than negative pressure (I.W.G.) in unit
dling units so that the supply air is drawn through them.
drain pan. To determine “H” dimension, first deter-
This results in the condensate being subjected to nega-
mine the negative static pressure in the unit. Always
tive (-) static pressure. Unless some means of pressure
assume the worst conditions, such as dirty filters in the
equalization is provided in the condensate drain, the
return air circuit to fan.
air rushing back through the drain pipe will cause the
condensate to build up in the drain pan.
As the unit continues to operate, the accumulated wa-
ter will be carried with the air stream, overfilling the
drain pan causing possible water leaks into the supply
duct and/or causing water damage in the building. A
trap must be installed to prevent this condensate water
build-up. (See Figure 63 on page 87 and Figure 64
on page 87) On initial startup, it may be necessary
to fill the trap manually or, after the unit has operated 4
sufficiently for a small amount of condensate to col-
lect in the drain pan, turn off the unit, and the trap will
LD06343
automatically fill.
Figure 64 - DRAIN TRAP PIPING FOR DRAW-
THROUGH UNIT
Example:
Negative Static Pressure = 5.5”
Minimum of 1/2” = 0.5”
“H” Dimension = 6.0”
LD06342-3
JOHNSON CONTROLS 87
FORM 050.40-ES3
SECTION 4 - PIPING
ISSUE DATE: 2/23/2012
88 JOHNSON CONTROLS
FORM 050.40-ES3
ISSUE DATE: 2/23/2012
SECTION 5 - CONTROLS
JOHNSON CONTROLS 89
FORM 050.40-ES3
SECTION 5 - CONTROLS
ISSUE DATE: 2/23/2012
90 JOHNSON CONTROLS
FORM 050.40-ES3
SECTION 5 - CONTROLS
ISSUE DATE: 2/23/2012
ECONOMIZER OPERATION The remote unit start-stop allows for connection to ex-
ternal devices. Compressors or systems should never
The following applies to both variable air volume and
be repeatedly cycled off and on using cycling contacts.
constant volume systems.
Excessive cycling may cause lubrication problems in
The building system controls should incorporate an the compressors resulting from insufficient run time.
outside air temperature or enthalpy sensor (an enthalpy The same logic should be applied when using a BAS
sensor allows use of the lowest load air which can save system. The same logic should be applied when using
energy for the customer) to sequence economizer or a BAS system that talks directly to the microprocessor,
mechanical cooling operation. ASHRAE 90.1 requires using the RS485 port.
that mechanical cooling be available, while the econo-
Additionally, condensing unit dry contacts are avail-
mizer is operating above 25% system load. The econo-
able, as standard, for compressor run indication and
mizer can and should be locked out when the ACCU
unit alarm identification. (Note that alarm contacts
mechanical cooling system load drops to 25% or low-
"OPEN" on a fault).
er. This is to prevent coil frosting and liquid slugging
at the lowest step of compressor unloading (4, 5 or 6 REMOTE SETPOINT RESET
compressor units only).
If remote set point reset is utilized with ACCU dis-
When incorporating economizer operation, the hot gas charge air temperature control, do not reset the set point
bypass valve(s) on the ACCU condensing units should repeatedly to control temperature. Using this method
be energized during all steps of loading. This will re- may cause excessive cycling of the compressors. Com-
duce compressor cycling and allow the TXV to control pressor cycling with very short run periods can cause
satisfactorily at reduced cooling loads on the DX coil. compressors to fail due to lack of lubrication.
EXTERNAL BAS AND OTHER CONTROL The rule to follow is to adjust the control of dampers, 5
INTERFACES fans, vanes, etc., and not the ACCU set point to control
air temperature. If remote set point is utilized, it should
Dry contacts can be wired in series with the zone input
be used to adjust capacity as a result of load changes,
thermostats (Figure 67 on page 90) to permit remote
which may occur as building occupancy changes. Re-
control from a separate building automation system, if
mote set point reset is also commonly used for night
desired.
or weekend setback. These are examples of occasional
If remote unit start-stop is desired, a separate set of changes, which are typically used for temperature re-
dry contacts can be wired in series with the air-proving set.
switch (Figure 67 on page 90) in the condensing
unit. ACCU Condensing Unit Ambient Control
On newer 031-02550-000 Control Boards The standard units are designed to operate in out-
utilizing DAT control, there is a separate door ambient temperatures of 25°F (-3.9°C) to 115°F
run permissive provision (Start-stop) (46.1°C). When the ACCU operates with an econo-
between terminals 13 and 51 that must mizer system, experience suggests that the low ambi-
be utilized in lieu of “in series with the ent control should be programmed to the 40 F to 45
Flow Switch”. F range. Extremely low loads will cause refrigerant
control and compressor cycling problems. (See the
An air-proving switch is required to confirm that suf- Hot Gas Bypass on Page 98 in SECTION 3 - COIL
ficient air is flowing across the DX coil, whether at the SELECTION/CONFIGURATION) For those applica-
full load design CFM or the minimum allowable CFM tions where these units can operate below 25°F or with
for the selected coil in VAV applications. Enough air economizer systems below the 40 F outdoor range, the
must flow over the coil at the minimum condition to ACCU must include the optional low ambient kit. For
assure that there is no liquid refrigerant carry-over to operation above 115°F, the optional high ambient kit is
the compressor, which will cause potential mechanical needed for operation up to 125°F.
wear and compressor failure.
JOHNSON CONTROLS 91
FORM 050.40-ES3
SECTION 5 - CONTROLS
ISSUE DATE: 2/23/2012
92 JOHNSON CONTROLS
FORM 050.40-ES3
ISSUE DATE: 2/23/2012
THERMAL EXPANSION VALVE (TXV) • pressure drop in the liquid line and the liquid line
components
The sizing and application of the TXV is crucial to the
operation of the system. Incorrect sizing could allow The refrigerant type (i.e. 410a, R-22, R-407C, etc.) can
liquid over feeding and subsequent compressor fail- usually be found on the job schedule or in the specifi-
ures. Each TXV should be sized for the maximum load cation. The DX coil capacity and saturated evaporating
of the coil it is feeding. This does not mean that the temperature should be taken from the coil selection (re-
TXV must have a nominal capacity greater than the member, one TXV is used per distributor). The liquid
maximum load. A valve with a lower nominal capacity temperature at the inlet of the TXV can be calculated
could be selected because typically TXV’s are capable starting with the design ambient temperature. If the de-
of providing 15% more capacity than the rated value. sign ambient temperature isn't available, the ambient
For example, if a coil has a design cooling load of 31.2 temperature can be estimated using the climate data
TR, a nominal 30 or 40 TR valve might be considered. found in Chapter 27 of the ASHRAE Fundamentals
In this case a nominal 30 TR valve could be a better Handbook (use the 1% Cooling DB/MWB temperature
selection. for the city closest to the jobsite). The pressure drop in
the liquid line and the liquid line components should
If two distributors are applied to one refrigerant circuit, be calculated, or at least estimated with the greatest ac-
the TXV should be sized to match the capacity of the curacy possible.
evaporator coil and distributor that it feeds. Taking the
example above, if a condensing unit circuit of 31.2 TR Example
supplied two evaporator coils with equal capacity, each
TXV should be sized for 15.6 TR. Each coil would re- Size a R-22 thermostatic expansion valve for each cir-
quire a distributor and each distributor requires its own cuit of a YCUL0076EC condensing unit. For this ex-
TXV. ample:
An important factor in valve selection is the amount of • Each of the two evaporating coils has a design
capacity reduction available on the system. Typically, saturated evaporating temperature of 47°F (ETP).
the minimum capacity at which a TXV can maintain • The design ambient outside air temperature is 95°F 6
stable refrigerant flow is approximately 30% of its
nominal rating. Thus, if a TXV has a nominal capac- • Each liquid line pressure drop is 10 PSI (including
ity of 40.3 TR, it should not be applied to any system piping, valves, filter-driers and sight glasses).
with a part load capacity less than 12.1 TR. Operating • Circuit #1 has a capacity of 37.5 TR
a TXV at capacities less than 30% can result in TXV
overfeeding and lead to a compressor failure (due to • Circuit #2 has a capacity of 31.2 TR (based on
refrigerant slugging, oil dilution, or liquid refrigerant 45°F SST, 2°F suction line loss).
washout of the compressor). 1. Calculate the pressure drop across the TXV’s at
the design condition as follows:
Selection of the correct TXV is essential for proper
operation of the refrigeration system. Fortunately, it
design ambient
is not a difficult procedure.
temperature Add 25ºF to obtain saturated condensing
As a minimum, the following details must be known in temperature.
order to select and size the TXV: 95°F + 25°F = 120°F
JOHNSON CONTROLS 93
FORM 050.40-ES3
SECTION 6 - NECESSARY COMPONENTS
ISSUE DATE: 2/23/2012
However, the maximum load for the TXV’s will occur at 2. Knowing the saturated evaporator temperature
the minimum operational discharge pressure (typically (47°F ETP) and the actual pressure drop across the
200 psig) which is based on the fan cycling set points TXV (77 PSI), find the pressure drop correction
for the ACCU condensing unit. Thus, the pressure drop factor from the TXV manufacturer’s catalog. (Use
across the valve at maximum TXV load becomes: the 40°F ETP row for any ETP between 40°F and
55°F.) By interpolating between the values shown
Condensing pressure → 200 PSIG in Table 17 on page 94 (shaded blocks), it can
Evaporating pressure at 47°F → - 79 PSIG be determined that the factor for this example will
Difference → 121 PSI be approximately 0.88 (CF Pressure Drop).
initial pressure drop across TXV at
maximum load/low differential pressure
3. Next, determine the liquid refrigerant temperature
(without component pressure drops)
entering the TXV when the discharge pressure
is 200 psig (101°F CTP or saturated condensing
Add in the liquid piping, liquid line components, dis- temperature).
tributor and coil pressure drops:
saturated sub-cooling liquid
condensing – temperature = refrigerant
Liquid line and components pressure drop → 10 PSI temperature temperature
Distributor pressure drop → 30 PSI (typical) 101°F - 15 °F (15-17°F typical) = 86°F
DX coil pressure drop → +4 PSI (from coil selection)
Total component pressure drop → 44 PSI 4. Find the liquid refrigerant temperature correction
factor for the TXV’s in the manufacturer ‘s cata-
Subtract the total component pressure drop from the log. Interpolation between tabulated values may
initial pressure drop across the TXV to obtain the ac- be necessary. For this example based on the val-
tual pressure drop across the TXV. ues in the shaded blocks found in Table 18 on page
94, the correction factor for the liquid tempera-
Inlet pressure → 121 PSI ture will be 1.08 (CF Liquid Temperature).
Pressure drop → - 44 PSI
Actual pressure drop
across the TXV. → 77 PSI
94 JOHNSON CONTROLS
FORM 050.40-ES3
SECTION 6 - NECESSARY COMPONENTS
ISSUE DATE: 2/23/2012
5. Now, using the design DX coil circuit capacity OVE 30: 29.0 TR X 1.15 = 33.4 TR
for each circuit (37.5 and 31.2 TR respectively), OVE 40: 38.3 TR X 1.15 = 44.0 TR
find the valves listed in the catalog which have ca-
So, based on the capacities calculated for each
pacities that most closely match the coil capacity
valve as listed above, the OVE 40 TXV should
for R-22. In this example, the capacities of both
be selected for Circuit #1 (for 37.5 tons) and the
circuits fall between the nominal capacities of the
OVE 30 should be selected for Circuit #2 (for
OVE 30 and OVE 40 TXV’s listed in the Table 19
31.2 tons).
on page 95 (see the shaded blocks). Again, for
ETP’s between 40°F and 55°F ETP, use the 40°F 6. A check should also be made to make certain that
ETP column. the valve is not oversized at the minimum circuit
Values in the table above are from the capacity. An approximation of the minimum cir-
Sporlan Valve catalog and subject to cuit capacity can be determined by multiplying 6
change. See TXV valve manufacturer’s the circuit capacity by the ratio of 1 (compressor)
catalog for up to date information to size over the number of compressors applied on that
valve and select thermostatic charge type. circuit, which is 3 per circuit for this example.
circuit 1/3 compressors minimum
In this example, both the OVE 30 and the OVE 40 capacity x per circuit = circuit capacity
valves should be considered. First, check for actual ca-
pacity after applying correction factors. Circuit 37.5 x 0.33 = 12.5 TR
#1:
Valve X CF, CF, Actual Circuit 31.2 x 0.33 = 10.3 TR
Capacity Drop X Liquid = Valve #2
Pressure Temp Capacity
The minimum capacity of the TXV can be deter-
OVE 30: 30.5 X 0.88 X 1.08 = 29.0 TR
mined by multiplying the nominal TXV capacity
OVE 40: 40.3 X 0.88 X 1.08 = 38.3 TR
by 30% (0.30). This value should be lower than
As mentioned earlier, most TXV ’s have some reserve the minimum circuit capacity.
capacity, so it is better to select a valve lower in capac- nominal minimum
ity than the maximum capacity of the system, than to TXV x 30% = circuit
select a valve that has greater capacity than the maxi- capacity capacity
mum capacity of the system. Oversized TXV's can
cause wide cycle swings resulting in poor temperature TXV
and humidity control and lead to liquid carry-over to Circuit #1: 40.3 x 0.30 = 12.1 TR
the compressors at low loads. Thus, in this example: TXV
Circuit #2: 30.5 x 0.30 = 9.2 TR
JOHNSON CONTROLS 95
FORM 050.40-ES3
SECTION 6 - NECESSARY COMPONENTS
ISSUE DATE: 2/23/2012
Thus, for the two valves selected in our example, Mounting of the sensing bulb is extremely important.
the valves can operate at the maximum load/mini- Oil leaving the DX coil must not influence the bulb,
mum discharge pressure condition and minimum which must be mounted radially on the suction line at
circuit capacity condition without any difficulty. either the 4 or 8 o ‘clock position about 6” to 8” from
the coil on the horizontal line leaving the coil (Figure
7. Make certain to select the proper thermostatic
69 on page 96). The bulb should be mounted com-
charge, based on evaporator temperature and re-
pletely flat. Two perforated copper straps should firmly
frigerant type.
secure the bulb to provide good thermal contact with
8. Always include an external equalizer on the TXV. the suction line. Thermally insulate the bulb from the
The equalizer will prevent the refrigerant pressure air with a vapor barrier, so that the ambient air temper-
drop across the distributor and coil from affecting ature does not affect the bulb sensing. The sub-cooling
the superheat setting of the valve. and superheat should be checked and adjusted when
the unit is operating at design conditions. The equal-
9. The TXV should include the maximum operating
izing line should be piped just downstream of the bulb
pressure (MOP) feature. This MOP will restrict
on the same horizontal line. The equalizing line must
the maximum opening of the valve, if the suction
enter at the top of the suction line pipe.
pressure becomes too high due to abnormally high
suction gas temperatures, which typically occur at LIQUID LINE SOLENOID VALVES
start-up. For low ambient applications, the non-
migrating bulb charge may be required. If the am- A solenoid valve (Figure 70 on page 96) is simply
bient of the TXV can reach a temperature lower a two-position valve that is electronically actuated by
than its sensing bulb temperature, a non-migrating energizing or de-energizing a solenoid coil.
charge must be used. When using a non-migrating
charge, the MOP feature may not be available.
Use one TXV for each DX distributor/coil section
within the refrigerant circuit, as depicted in Figure 76
on page 100 and Figure 77 on page 101. The TXV
should be mounted on the horizontal liquid line as
close to the distributor inlet as possible (Not to exceed LD16278
24”). The bulb should be mounted on the outlet of the Figure 70 - LIQUID LINE SOLENOID VALVE
specific coil suction line and never in the common suc-
tion line.
Insulation
Bulb
Figure 69 - THERMAL EXPANSION BULB MOUNTING POSITIONS RADIALLY ON THE SUCTION PIPING
96 JOHNSON CONTROLS
FORM 050.40-ES3
SECTION 6 - NECESSARY COMPONENTS
ISSUE DATE: 2/23/2012
SIGHT GLASS
A sight-glass (SG) moisture-indicator (Figure 71 on
page 97) is designed to detect moisture in the refrig- LD16280
erant. One sight glass is required in each refrigerant
circuit between the LLSV and the TXV. It should be Figure 72 - SEALED FILTER DRIER
mounted as close to the TXV as possible and down-
stream of the filter-drier. In cases where long liquid
lines are encountered, two glasses, one at the condens-
er (ACCU) and one at the DX coil, are recommended. IN
6
OUT
LD16281
JOHNSON CONTROLS 97
FORM 050.40-ES3
SECTION 6 - NECESSARY COMPONENTS
ISSUE DATE: 2/23/2012
LD16282
SUCTION FILTER
Suction line filter-driers can be mounted in the suction
line, but are not needed on new systems, if care is taken
to keep the suction lines clean during installation.
LD16283
98 JOHNSON CONTROLS
FORM 050.40-ES3
SECTION 6 - NECESSARY COMPONENTS
ISSUE DATE: 2/23/2012
JOHNSON CONTROLS 99
FORM 050.40-ES3
SECTION 6 - NECESSARY COMPONENTS
ISSUE DATE: 2/23/2012
FACTORY MOUNTED
LIQUID STOP VALVE HOT GAS
BYPASS
LIQUID LINE
DISTRIBUTORS
WITH HOT GAS
CONNECTIONS
THERMAL
EXPANSION CHECK
VALVE VALVES
FILTER DRIER
LIQUID LINE
SOLENOID VALVE
SIGHT GLASS -
MOISTURE INDICATOR
LD13928
THERMAL
EXPANSION
VALVE
Figure 76 - INSTALLATION WITH TWO INTERLACED COILS (OR JUST ONE COIL PER CIRCUIT)
FACTORY MOUNTED
LIQUID STOP VALVE CHECK VALVE
DISTRIBUTOR
LIQUID LINE
WITH HOT GAS
CONNECTION
THERMAL
EXPANSION VALVE
LIQUID LINE
SOLENOID VALVE
6
FILTER DRIER
SIGHT GLASS -
MOISTURE INDICATOR
CHECK
VALVE
** CLOSE COUPLED
(3 FT NOM. MAX. TOTAL
LINEAR HORIZONTAL RUN)
** CAN BE STRAIGHT RUN
DISTRIBUTOR
WITH HOT GAS LD13295
CONNECTION
Table 20 - REFRIGERANT COMPONENTS, WITH TWO STACKED INTERLACED COILS WITH 2 TXV'S AND
1 LLSV PER REFRIGERANT CIRCUIT R-22 (REFER TO FIGURE 76)
Tons a) Filter-Drier(s) b) Moisture Indicator b)
f) Bulb charge is type “VN” used primarily when the valve body will see colder temperatures than what the sensing bulb will see, preventing bulb charge migration.
You should consider using a VGA or VCP100 charge with the added MOP feature on all applications where the AHU is located indoors and/or if the TXV body will
always see warmer temperatures than the bulb.
Table 21 - REFRIGERANT COMPONENTS, WITH 1 FULL FACE DX COIL WITH 1 TXV PER REFRIGERANT
CIRCUIT R-22 (REFER TO FIGURE 77)
ACCU Tons a) Filter-Drier(s) b) & d) Moisture Indicator b) & d)
SYS #1 SYS #2 SYS #1 SYS #2
SYS Cores -
60 HZ Unit SYS #1 BODY - Qty BODY - Qty Cores - Qty BODY - Qty CAP - Qty BODY - Qty CAP - Qty
#2 Qty
P/N P/N P/N P/N P/N P/N P/N P/N
0016EC 15.2 15.2 --- 1 * --- --- 1 ** --- ---
026-36510 * --- --- 026-15305 ** --- ---
0026EC 20.8 20.8 ---- 1 * --- --- 1 ** --- ---
026-36510 * --- --- 026-15305 ** --- ---
0030EC 25.9 25.9 ---- 1 * --- --- 1 ** --- ---
026-36510 * --- --- 026-15305 ** --- ---
0036EC 31.2 31.2 ---- 1 2 --- --- 1 1 --- ---
026-30598 026-18328 --- --- 026-32397 026-32800 --- ---
0040EC 37.7 37.7 ---- 1 2 --- --- 1 1 --- ---
026-30598 026-18328 --- --- 026-32397 026-32800 --- ---
0046EC 42.3 21.1 21.1 1 * 1 * 1 ** 1 **
026-36510 * 026-36510 * 026-15305 ** 026-15305 **
0050EC 46.9 25.9 21.3 1 * 1 * 1 ** 1 **
026-36510 * 026-36510 * 026-15305 ** 026-15305 **
0056EC 51.7 25.9 25.9 1 * 1 * 1 ** 1 **
026-36510 * 026-36510 * 026-15305 ** 026-15305 **
0060EC 56.2 30.6 25.6 1 2 1 * 1 1 1 **
026-30598 026-18328 026-36510 * 026-32397 026-32800 026-15305 **
0066EC 62.2 31.1 31.1 1 2 1 2 1 1 1 1
026-30598 026-18328 026-30598 026-18328 026-32397 026-32800 026-32397 026-32800
0076EC 68.9 37.5 31.4 1 2 1 2 1 1 1 1
026-30598 026-18328 026-30598 026-18328 026-32397 026-32800 026-32397 026-32800
0080EC 77.0 38.5 38.5 1 2 1 2 1 1 1 1
026-30598 026-18328 026-30598 026-18328 026-32397 026-32800 026-32397 026-32800
0086EC 83.6 45.5 38.1 1 2 1 2 1 1 1 1
026-30598 026-18328 026-30598 026-18328 026-32397 026-32800 026-32397 026-32800
0090EC 90.1 45.0 45.0 1 2 1 2 1 1 1 1
026-30598 026-18328 026-30598 026-18328 026-32397 026-32800 026-32397 026-32800
0096EC 90.8 50.4 40.4 1 2 1 2 1 1 1 1
026-21055 026-18328 026-30598 026-18328 026-32398 026-32800 026-32397 026-32800
0100EC 98.4 49.2 49.2 1 2 1 2 1 1 1 1
026-21055 026-18328 026-21055 026-18328 026-32398 026-32800 026-32398 026-32800
0106EC 108.9 60.5 48.4 1 2 1 2 1 1 1 1
026-21055 026-18328 026-21055 026-18328 026-32398 026-32800 026-32398 026-32800
0120EC 122.1 61.1 61.1 1 2 1 2 1 1 1 1
026-21055 026-18328 026-21055 026-18328 026-32398 026-32800 026-32398 026-32800
0130EC 133.6 74.3 59.3 1 3 1 2 1 1 1 1
026-16960 026-18328 026-21055 026-18328 026-32399 026-32800 026-32398 026-32800
0140EC 144.4 74.2 74.2 1 3 1 3 1 1 1 1
026-16960 026-18328 026-16960 026-18328 026-32399 026-32800 026-32399 026-32800
* In-Line Type ** Included w/Body
a) R-22, 95° F ambient and 45° SST, TXV's listed in table should be reviewed for SST's more than 3 degrees above or below 45° F
b) YORK P/N shipped loose with the standard ACCU Condensing unit
c) YORK P/N not included with the standard ACCU Condensing unit separately from
Baltimore Parts Center phone 800-932-1701 or fax 800-932-1702
d) Good for the typical 40° F to 50° SST range
e) The above are applicable for R-407C systems too
NOTE: Add -000 suffix to all part numbers in this table
f) Bulb charge is type “VN” used primarily when the valve body will see colder temperatures than what the sensing bulb will see, preventing bulb charge migration.
You should consider using a VGA or VCP100 charge with the added MOP feature on all applications where the AHU is located indoors and/or if the TXV body will
always see warmer temperatures than the bulb.
SECTION 7 - BRAZING
BRAZING SAFETY
• Wear suitable protective clothing. Safety goggles
with tinted lenses and gloves are required.
• Beware of brazing near combustible materials. If im-
possible to avoid, use suitable heat shield material to
prevent damage or combustion from occurring.
LD09165
• Be sure to have an adequate means of dealing with
Figure 78 - HAND HELD TORCH
a fire, such as fire hose, fire extinguishers, etc.
• Ventilate confined areas. Use ventilating fans and
exhaust hoods to carry all fumes and gases away TOOLS AND EQUIPMENT NEEDED
from work, and air supplied respirators as required. 7
1. Torch and Fuel Source
• Clean base metals thoroughly, A surface contami-
nant of unknown composition on base metals may The heating source most commonly used in brazing is the
add to fume hazard and may cause a too rapid hand held torch (Figure 78 on page 107). The type of
breakdown of flux, leading to over heating. torch offering the most versatility is a conventional ox-
ygen-acetylene torch, however, a special swirl-combus-
• Use sufficient flux. Flux protects base metals and tion tip torch (TurboTorch™ is one such example) using
filler metal during heating cycle. Full flux cover- MAPP (Methyl acetylene-propadiene mixture) or Pro-
age reduces fuming, Also, consult your MSDS pane/Air mixtures can be used very effectively on smaller
(Material Safety Data Sheet) regarding specific jobs. Oxy-acetylene rigs are the most complex because
hazards associated with brazing flux. they require both oxygen and acetylene tanks, regulators
• Heat metals broadly. Heat the base metals broadly for both tanks, hoses, valves and typically a cart to hold
and uniformly. Intense localized heating uses up the whole apparatus (Figure 79 on page 108).
flux, increases danger of fuming.
Depending on the size of the tanks, a typical oxy-acet-
• Know your base metals. A cadmium coating on a ylene rig can weigh quite a bit. The advantage of using
base metal will volatilize and produce toxic fumes the fuel/air mix rig is the size, weight and portability
during heating. Zinc coatings (galvanized) will issue. The disadvantage is that they generally are not as
also fume when heated. Learn to recognize these effective at quickly heating larger braze joints.
LD09166
3. Solvent
LD09167
Alcohol or any commercially available, safety ap-
proved, non-residue forming solvent that will remove
Figure 80 - TUBING CUTTER
oil or grease from the fittings and pipe.
The type of flux needed will normally depend on the 000. No flux is required with this filler alloy when us-
brazing time and temperatures. ing it to braze clean copper to copper joints. This alloy
liquefies at 1495° F and has a flow point of 1325° F.
The finished joint color will be gray in appearance.
Do not use Silver/Phosphorous materials
to join ferrous materials as brittle phos-
phate compounds will be formed at the
interface. Also note that these filler metals
have a unique characteristic called the
“Flow Point”. The ”Flow Point” is de-
fined as the temperature at which the filler
LD09170 metal is fluid enough to capillary through
Figure 83 - FLUX a joint even though not completely liquid
(i.e. above the liquids temperature).
For light walled joints use a low temperature flux For brazing copper to brass or steel and any combina-
(AWS specification FB3A), generally white in color tion of brass and steel together, use AWS classification
(YORK part number 044-00372-000). “BAG-20” which has a nominal composition of 30%
For heavier wall, higher temperature work, use a black silver, 38% Copper and 32% Zinc. Popular brand name
flux . (AWS specification. FB3C ) (YORK part number equivalents are Handy Harman Braze 300, Engelhard
044-00371-000). Industries Engelhard No. A-13 and J.W. Harris Safety
Silv 30. The YORK part number for this filler metal is
Be sure to follow the manufacturer’s instructions and 001-06056-000. This alloy flows at 1410°F. The fin-
safety recommendations when working with brazing ished joint color will be yellow.
flux. Most fluxes are acidic and can cause skin reac-
Other alloys may be used as substitutes for
tions. Protect exposed skin and always wear eye pro-
the above, providing they meet or exceed
tection when working with flux.
the specifications of the suggested alloys.
The flux is generally applied using an acid brush,
which may be part of the flux container or if necessary
purchase separately.
7. Nitrogen MUST Be Used While Brazing!
5. Wet Cloths
The importance of brazing with nitrogen cannot be
A couple of wet cloths soaking in a pail of clean water
over-emphasized. POE oils used with the newer refrig-
are always handy to have available. First of all, it may be 7
erants such as R134a or R-407c make this even more
necessary to wrap a wet cloth around parts of an assem-
important due to their solvent powers. The sludge that
bly such as a thermal expansion valve (TXV) or solenoid
will form in the system as a result of brazing without
valve during the brazing operation to prevent the braz-
nitrogen is severe and easily identified after a compres-
ing heat from damaging the valve components/gaskets.
sor failure. Don’t gamble with your compressor war-
Second, the wet cloths can be used to carefully wipe a
ranty, follow proper nitrogen brazing procedures!
finished braze joint to remove residual flux (if used) and
to provide a professional looking finished joint. A regulated supply of nitrogen must be available to
purge the piping and then sustain a small flow of ni-
6. Filler Metal trogen through the piping while brazing the fittings,
Two types of filler metal are recommended by Johnson otherwise the heat applied during brazing will cause
Controls. oxides to form inside the piping which may later pro-
mote compressor failures or plug filter driers.
For copper-to-copper joints, use AWS classification
”BCuP-3” which has a nominal composition of 5% Sil- Set up the piping so that the first joint you braze is clos-
ver, 89% Copper and 6% Phosphorous. Popular brand est to the supply of nitrogen to the piping assembly and
name equivalents are Handy Harman Sil Fos 5, J.W. then continue to braze the joints in the direction of the
Harris Stay-Silv 5 and Englehard Industries Silvaloy 5. nitrogen flow.
The YORK part number for this material is 001-04708-
LD09171
LD09173
2. Cleaning
Brazing surfaces and filler metal must be cleaned to
bright metal before brazing (Figure 86 on page 110).
Prior to brazing, oil, grease, etc., should be removed
using an approved commercial safety solvent.
Oxides must be removed by wire brushing or crocus
LD09172
cloth.
Figure 85 - PIPE BRAZING WITHOUT NITROGEN Do not use steel wool, emery cloth or sandpaper!
3. Fit-up
It is very important to mask off openings in the piping
to ensure that all oxygen has been completely purged Braze joint strength is directly related to fit up clear-
from the assembly and that a small gentle flow of ni- ances. A general rule of thumb is that the joint internal
trogen is flowing through and past each piping joint clearance should be 0.002 to 0.005 inch (Figure 87 on
while it is being brazed and during the cooling process. page 110). This clearance range is necessary for cap-
If there are branch fittings, be sure you have purged the illary flow of the filler metal into the joint and it is the
branch piping section and that there is flow through the optimal clearance for joint strength.
branch before brazing. See Figure 84 on page 110 for Effects of joint thickness on tensile strength
results of brazing with nitrogen purge and Figure 85 on
Thickness of joint(mm)
page 110 for results when nitrogen is not used. 0.00 0.08 0.15 0.23 0.31 0.38 0.46 0.53 0.61
140,000 965.3
Failure to adequately purge the piping or promote
Tensile strength (MPa)
Tensile strength (psi)
120,000 827.4
flow past branch fittings will have nearly the same
effect as no nitrogen at all. 100,000 689.5
80,000 551.6
PROCEDURES
60,000 413.7
1. Cutting tubing
40,000 275.8
0.00 0.003 0.006 0.009 0.012 0.015 0.018 0.021 0.024
Pipe or tube ends should be cut off square and burrs re-
moved by reaming or filing, taking care that any metal Thickness of joint(inches)
debris or chips fall out of the piping. Reaming and filing LD09174
should be held to the absolute minimum necessary to
Figure 87 - JOINT THICKNESS VS TENSILE
remove the burrs. Care should be taken not to taper the STRENGTH
LD09176
LD09175
Do not use excessive flux. Flux is acid based and will
Figure 88 - CHECKING PIPE FIT contribute to system acid formation if allowed to get
into the system. See Figure 89 on page 111 and Fig-
ure 90 on page 111.
4. Fluxing
If the braze joint is copper to copper and you are us- Do not apply flux to any surface you do not want the
ing a self-fluxing silver/phosphorous filler metal, flux brazing filler metal to flow to and adhere.
is not required.
For best results, clean the length of the filler alloy you
All other situations require flux. Depending on the type are expecting to use with crocus cloth and then coat the
of joint, use either low temperature or high temperature filler metal with a light coating of flux (Figure 91 on
flux. High temperature flux should be used where pro- page 112). An old rule of thumb suggests that the di-
longed heating at higher temperatures is required, such ameter of the joint is approximately the length of filler
as when a heavy wall brass valve is being brazed to metal needed to properly braze the joint.
copper. If in doubt, use the high temperature flux.
Make sure the flux is stirred well. If the
flux is water based it may be necessary to 7
add water if the flux has thickened over
time. Flux should have a thin creamy
consistency similar to Pepto-Bismol™.
LD09179
After the flux visual condition tells you the tempera- When brazing a device such as a solenoid
ture is correct, you can touch the filler metal to the valve, TXV, hand valve, etc. into a line,
joint. If the joint is at the proper temperature the filler follow the manufacturer’s recommenda-
metal will begin to flow into the joint. As the joint fills tion, if one exists. Occasionally it may
up, move the flame back, reducing the temperature at be required to disassemble the device
the joint slightly and add a little more filler metal to for brazing purposes in order to avoid
provide a concave fillet. As stated previously, the fillet damage to the internal parts. In most
makes for a professional appearance, but adds very lit- cases, the device can be wrapped with wet
tle to the quality of the braze joint (Figure 94 on page cloths during the brazing and cool down
114). period (Figure 95). It is important that if
a solenoid, TXV or other closing device is
being brazed, it must be partially open in
order to allow Nitrogen to pass through
the device during the brazing and cool
down period. A manual device such as a
hand valve should be partially opened (not
backseated) so that the valve seat elasto-
mers are not damaged during brazing. It
should also be noted that there are com-
mercially available heat sink materials
that can be used to isolate brazing heat
from other components.
LD09181
cleaning a hot braze joint with a wet cloth. Figure 95 - USING WET CLOTH TO PROTECT
The water in the cloth will turn to steam COMPONENTS WHILE BRAZING
very quickly and if the cloth is allowed to
stay in contact with the hot joint for even
a short period of time, it will quickly con-
duct the heat of the braze joint through
the wet cloth.
CONDENSING UNIT/AIR HANDLING UNIT 5. Assure that the ACCU is programmed for the ap-
SYSTEM START-UP propriate load control. This will either be based on
Johnson Controls Service start-up is Suction Pressure (SP) or Discharge Air Tempera-
recommended and this will benefit the ture (DAT) control. When suction pressure control
customer, consulting engineer, installing is used, check to make sure that the suction pres-
mechanical contractor and YORK. sure transducers are installed and the controlling
thermostats or dry contacts (by others) are wired
into each refrigerant circuit. When DAT control is
used, check to make certain that sensor is properly
The following fundamental checks are recommended
mounted in a thoroughly mixed air-flow location
either prior to or during the system commissioning or
within the air duct or air handling unit.
start-up:
6. Insure that there is a minimum DX coil face ve-
1. Check that the proper equipment and refrigerant locity of 350 FPM for proper DX coil operation.
piping components have been installed in accor- The air-proving switch must be wired into the
dance with the Consulting Engineer’s specifica- condensing unit control circuit. This is needed to
tions. confirm that the air-flow is satisfactory for con-
2. Check the refrigerant piping for conformance to densing unit operation.
the latest ASHRAE Refrigeration Handbook prac- 7. Remote start-stop contacts are properly connected.
tices and/or 050.40-ES3 Piping Guidelines. As a
minimum, things to review for reasonableness are 8. If desired, a remote emergency cut-off is wired
the line sizes, slope, trapping, support, insulation, into the condensing unit.
suction riser (if single or double), and special note
9. Compressors run indication contacts are properly
to the placement and installation of the TXV Bulb
connected, if used.
and equalizer line.
10. Condensing unit alarm contacts are connected for
3. The refrigerant piping must have been leak
each refrigerant circuit, if used (N.O. indicates a
checked and evacuated following ASHRAE rec-
fault).
ommendations. Evacuate the system down to 500
microns. An acceptable leak rate is rise of 100 mi- 11. If remote reset of the DAT is desired, a check
crons in 10 minutes. should be made to see that the PWM input sig-
nal is properly wired (when the condensing unit
4. The system must be charged with the total system
is programmed for DAT). NOTE that newer 031-
refrigerant charge, which is required for the con-
02550-000 control boards can directly accept a
densing unit, DX coils and piping. Operating the
VDC or MA signal for temperature RESET. Re-
load condition, a check should be made of the sub-
view programming.
cooling and superheat. The IOM recommends, at
full load design, that the subcooling should be ad- 12. When remote load limiting is desired, check that
justed to 15 – 17°F by adding or removing charge, the contacts are properly connected to the ACCU 8
and the Suction Super Heat be adjusted to 15°F by condensing unit. This prevents condensing unit
use of the TXV. The subcooling and superheat are from loading beyond a desired value. This will
determined as follows: vary with the unit size and depend on the number
of compressors (see the condensing unit IOM).
13. The condensing unit is ready to be placed into op- 16. After the system is operating at design or full load
eration. condition, a check should be made of the sub-
cooling and superheat. The IOM recommends,
14. Leak check the system to assure that there are no
at full load design, that the subcooling should be
leaks at the compressors, fittings, and piping.
adjusted to 15°F – 17°F by adding or removing
15. A check of the oil level should be made after the charge, and the Suction Super Heat be adjusted
unit has been put into operation and adding a to 15°F by use of the TXV. The subcooling and
small amount of oil may be required to accom- superheat are determined as follows:
modate the additional piping runs. Adding about
• Sub-cooling = refrigerant liquid pressure
pint for each 100’ of piping may be appropriate.
converted to temperature minus the liquid
Adding too much oil can cause compressor dam-
line temperature.
age and jeopardize the warranty. This can increase
condensing unit power consumption too. The oil • Superheat = suction temperature minus the
level should be checked with the compressors off, suction pressure converted to temperature.
after the ACCU had been operating near design
or full load condition for a minimum of 10 min-
utes to preferably 30 minutes. The oil level should
meet the IOM recommendations.
INITIAL SYSTEM COMMISSIONING OR 3. The first compressor on a circuit will start after the
START-UP anti-recycle timer counts down, if the Zone Ther-
mostat input is closed and if safeties permit. The
The electrical power must be applied for 24 hours prior
liquid line solenoid valve will be energized, when
to starting the ACCU condensing unit. This will insure
the compressors start.
adequate time for the compressor heaters to boil off the
refrigerant in the oil sumps. 4. If more cooling is required, the next compressor
in the sequence will start after 150 seconds.
Basic ACCU System Requirements
5. If more cooling is required, the next compressor
Some basic things must be satisfied in order for the (if there are three compressors on the circuit) will
condensing unit to be allowed to operate and provide start after 150 seconds.
cooling. These include:
Compressor Lead/Lag Sequence per Circuit
1. The unit switch must be in the ON position.
The compressors within a refrigerant system rotate
2. Remote cycling contacts need to be closed. starts in sequence 1-2 (two compressor systems) or
3. The ACCU microcomputer Daily Schedule must 1-2-3 (three compressor systems) in a wrap-around
be programmed for the ACCU to operate. technique and will operate per the following rules of
protocol.
4. The air-proving switch must be satisfied (the
evaporator fan blower must be running, when any 1. The longest-off compressor within a system will
compressor is operating). start first.
5. A cooling load must be present. 2. The longest running compressor within a system
will turn off first.
6. The desired setpoint and range must be pro-
grammed into the microprocessor based on either 3. Selectable refrigerant system lead-lag is not avail-
Suction Pressure (SP) or Discharge Air Tempera- able, since the refrigerant systems operate inde-
ture (DAT) control. (Refer to the ACCU Installa- pendently.
tion, Operation, and Maintenance, IOM, for the
available settings.) Shutdown and Pump-down
As the cooling load decreases below the programmed
OPERATING SEQUENCE – CONDENSING setpoint range, the system will unload. The system will
UNIT not shut off the last compressor until the Zone Thermo-
stat input is opened.
When Using ACCU Suction Pressure Control
The following points must be recognized when using When the last system compressor is cycled off, pump-
suction pressure control: down occurs. The liquid line solenoid will be deener-
gized. The last compressor will be allowed to run until
1. The unit start switch needs to be ON. either the suction pressure falls below the suction pres-
2. Each condensing unit circuit operates indepen- sure cut-out or for 180 seconds, whichever occurs first.
dently for loading and unloading. The loading and Hot gas bypass is inhibited during pump-down.
unloading will occur on each circuit, based on the
suction pressure of that circuit. The condensing
unit includes anti-coincident timers (set at 60 sec-
onds) to insure that compressors in systems 1 and 9
2 will not start at the same time.
APPENDIX
Table 23 - SUCTION LINE CAPACITIES IN TONS FOR REFRIGERANT R-22
LINE SATURATED SUCTION TEMPERATURE, °F
SIZE -40 -20 0 20 40
TYPE L t = 2°F t = 1°F t = 0.5°F t = 2°F t = 1°F t = 0.5°F t = 2°F t = 1°F t = 0.5°F t = 2°F t = 1°F t = 0.5°F t = 2°F t = 1°F t = 0.5°F
COPPER
O.D. p = 0.77 p = 0.39 p = 0.19 p = 1.13 p = 0.57 p = 0.29 p = 1.60 p = 0.81 p = 0.40 p = 2.18 p = 1.1 p = 0.55 p = 2.87 p = 1.45 p = 0.73
1/2 0.10 0.07 0.05 0.17 0.12 0.08 0.27 0.18 0.12 0.40 0.27 0.19 0.58 0.40 0.27
5/8 0.19 0.13 0.09 0.32 0.22 0.15 0.50 0.34 0.23 0.75 0.52 0.35 1.10 0.74 0.51
3/4 0.33 0.23 0.15 0.55 0.38 0.26 0.86 0.59 0.40 1.30 0.88 0.60 1.80 1.30 0.87
7/8 0.52 0.35 0.24 0.85 0.58 0.40 1.30 0.91 0.62 2.00 1.40 0.93 2.90 2.00 1.30
1-1/8 1.10 0.72 0.49 1.70 1.20 0.80 2.70 1.90 1.30 4.00 2.80 1.90 5.80 4.00 2.70
1-3/8 1.80 1.30 0.90 3.00 2.10 1.40 4.70 3.20 2.20 7.00 4.80 3.30 10.00 6.90 4.80
1-5/8 2.90 2.00 1.40 4.80 3.30 2.30 7.40 5.10 3.50 11.10 7.60 5.30 15.90 11.00 7.60
2-1/8 6.10 4.20 2.90 10.00 6.90 4.70 15.40 10.70 7.30 22.90 15.90 10.90 32.80 22.80 15.70
2-5/8 10.80 7.50 5.10 17.70 12.20 8.40 27.30 18.90 13.00 40.50 28.10 19.40 58.00 40.30 27.80
3-1/8 17.30 12.00 8.20 28.20 19.50 13.40 43.60 30.20 20.80 64.60 44.80 31.00 92.30 64.20 44.40
3-5/8 25.80 17.80 12.30 42.00 29.10 20.00 64.80 44.90 31.00 96.00 66.70 46.10 137.00 95.40 66.10
4-1/8 36.50 25.20 17.40 59.30 41.10 28.30 91.40 63.40 43.80 135.20 94.00 65.10 193.00 134.40 93.20
5-1/8 65.30 45.20 31.20 106.10 73.60 50.80 163.30 113.50 78.50 241.50 168.10 116.50 344.40 240.20 166.70
6-1/8 105.20 72.93 50.30 170.70 118.50 81.90 262.50 182.60 126.40 387.90 270.30 187.50 552.70 385.80 268.1
NOTES:
Capacities are in tons of refrigeration.
Dp = pressure drop due to line friction, psi per 100 feet equivalent length.
Dt = change in saturation temperature corresponding to pressure drop, °F per 100 feet.
Table 24 - DISCHARGE AND LIQUID LINE CAPACITIES IN TONS FOR REFRIGERANT R-22
LINE SIZE DISCHARGE LINES (delta t = 1°F, delta p = 3.03 PSI) LINE SIZE LIQUID LINES
TYPE L SATURATED SUCTION TEMPERATURE, °F TYPE L VEL. = 100 Δt = 1°F
COPPER, O.D. -40 -20 0 20 40 COPPER, O.D. FPM Δp = 3.03
1/2 0.8 0.8 0.8 0.8 0.9 1/2 2.4 3.7
5/8 1.4 1.5 1.5 1.6 1.6 5/8 3.8 7.0
3/4 2.4 2.5 2.6 2.6 2.7 3/4 5.7 12.0
7/8 3.7 3.8 4.0 4.1 4.2 7/8 8.0 18.6
1-1/8 7.5 7.8 8.0 8.3 8.5 1-1/8 13.6 37.8
1-3/8 13.1 13.5 14.0 14.4 14.8 1-3/8 20.7 66.1
1-5/8 20.6 21.4 22.1 22.8 23.4 1-5/8 29.3 104.7
2-1/8 42.7 44.2 45.7 47.1 48.4 2-1/8 51.0 217.5
2-5/8 75.3 78.0 80.6 83.1 85.3 2-5/8 78.7 385.0
3-1/8 119.9 124.3 128.4 132.3 135.9 3-1/8 112.3 615.0
3-5/8 177.9 184.4 190.6 196.3 201.6 3-5/8 151.8 914.6
4-1/8 250.6 259.7 268.4 276.5 283.9 4-1/8 197.4 1291.0
5-1/8 447.0 463.3 478.7 493.2 506.4 5-1/8 307.6 –
6-1/8 717.1 743.2 768.0 791.2 812.5 6-1/8 442.2 –
1. Table capacities are in tons of refrigeration.
∆p = Pressure drop due to line friction, psi per 100 feet equivalent length.
∆t = Change in saturation temperature corresponding to pressure drop, Multiply table capacities by the following factors for
°F per 100 feet.
2. Line capacity for other saturation temperatures ∆t and equivalent lengths. condensing temperatures other than 105°F.
∆
Line capacity = Table capacity X CONDENSING SUCTION DISCHARGE
∆ TEMPERATURE, °F LINE LINE
3. Saturation temperature ∆t for other capacities and equivalent lengths Le ∆t 80 1.12 0.82
90 1.07 0.89
=Table ∆t 100 1.03 0.96
110 0.97 1.03
The refrigerant cycle for determining capacity is based on saturated gas leav- 120 0.92 1.10
ing the evaporator and no subcooling in the condenser. Discharge superheat 130 0.87 1.16 A
is 105°F. The saturated suction temperature is 40°F for liquid line sizing. 140 0.82 1.22
TYPE L t = 2°F t = 1°F t = 0.5°F t = 2°F t = 1°F t = 0.5°F t = 2°F t = 1°F t = 0.5°F t = 2°F t = 1°F t = 0.5°F t = 2°F t = 1°F t = 0.5°F
COPPER,
O.D. p = 0.69 p = 0.35 p = 0.18 p = 1.04 p = 0.53 p = 0.26 p = 1.50 p = 0.76 p = 0.38 p = 2.08 p = 1.05 p = 0.53 p = 2.81 p = 1.41 p = 0.71
1/2 0.1 0.1 0.0 0.1 0.1 0.1 0.2 0.2 0.1 0.4 0.2 0.2 0.5 0.4 0.3
5/8 0.2 0.1 0.1 0.3 0.2 0.1 0.4 0.3 0.2 0.7 0.5 0.3 1.0 0.7 0.5
3/4 0.3 0.2 0.1 0.4 0.3 0.2 0.7 0.5 0.3 1.1 0.8 0.5 3 .7 1.2 0.8
7/8 0.4 0.3 0.2 0.7 0.5 0.3 1.1 0.8 0.5 1.7 1.2 0.8 2.6 1.8 1.2
1-1/8 0.8 0.6 0.4 1.4 1.0 0.6 5.3 1.6 1.1 3.5 2.4 1.7 5.3 3.6 2.5
1-3/8 1.4 1.0 0.7 2.4 1.7 1.1 4.0 2.7 1.9 6.1 4.2 2.9 9.2 6.3 4.4
1-5/8 2.2 1.5 1.0 3.9 2.7 1.8 6.3 4.3 3.0 9.7 6.7 4.6 14.5 10.0 6.9
2-1/8 4.6 3.2 2.2 8.0 5.5 3.8 13.0 9.0 6.2 20.1 13.9 9.6 29.9 20.8 14.3
2-5/8 8.2 5.7 3.9 14.2 9.8 6.7 23.0 15.9 11.0 35.6 24.6 17.0 52.8 36.7 25.4
3-1/8 13.2 9.1 6.2 22.7 15.7 10.8 36.8 25.5 17.5 56.7 39.4 27.2 84.2 58.5 40.5
3-5/8 19.6 13.6 9.3 33.8 23.4 16.1 54.6 37.9 26.1 84.2 58.5 40.5 124.9 87.0 60.2
4-1/8 27.7 19.2 13.2 47.7 33.0 22.7 77.1 53.5 36.9 118.7 82.5 57.1 176.0 122.6 85.0
5-1/8 49.7 34.4 23.7 85.3 59.2 40.8 37.8 95.7 66.2 212.1 147.6 102.3 314.1 219.0 152.0
6-1/8 80.1 55.5 38.3 137.3 95.3 65.8 221.5 154.1 106.6 340.6 237.3 164.6 504.0 351.8 244.5
NOTES:
Capacities are in tons of refrigeration.
Dp = pressure drop due to line friction, psi per 100 feet equivalent length.
Dt = change in saturation temperature corresponding to pressure drop, °F per 100 feet.
Table 26 - DISCHARGE AND LIQUID LINE CAPACITIES IN TONS FOR REFRIGERANT R-407C
LINE SIZE DISCHARGE LINES (delta t = 1°F, delta p = 3.28 PSI) LINE SIZE LIQUID LINES
TYPE L SATURATED SUCTION TEMPERATURE, °F TYPE L VEL. = 100 Δt = 1°F
COPPER, O.D. -40 -20 0 20 40 COPPER, O.D. FPM Δp = 3.5
1/2 0.71 0.75 0.78 0.82 0.86 1/2 2.20 4.00
5/8 1.30 1.40 1.50 1.50 1.60 5/8 3.60 7.50
3/4 2.30 2.40 2.50 2.60 2.70 3/4 5.40 12.90
7/8 3.50 3.70 3.90 4.00 4.20 7/8 7.50 19.90
1-1/8 7.00 7.40 7.80 8.20 8.50 1-1/8 12.70 40.30
1-3/8 12.30 12.90 13.60 14.30 14.90 1-3/8 19.40 70.30
1-5/8 19.30 20.40 21.50 22.50 23.50 1-5/8 27.50 111.20
2-1/8 40.00 42.20 44.40 46.50 48.60 2-1/8 47.80 230.50
2-5/8 70.50 74.50 78.30 82.10 85.60 2-5/8 73.70 407.30
3-1/8 112.30 118.60 124.80 130.70 136.40 3-1/8 105.20 649.60
3-5/8 166.60 176.00 185.10 193.90 202.30 3-5/8 142.30 965.00
4-1/8 234.70 247.80 260.70 273.10 284.90 4-1/8 185.00 1360.00
5-1/8 418.50 441.90 464.90 487.00 508.10 5-1/8 288.30 –
6-1/8 671.30 708.90 745.70 781.20 815.00 6-1/8 414.40 –
1. Table capacities are in tons of refrigeration. Multiply table capacities by the following factors for
∆p = Pressure drop due to line friction, psi per 100 feet equivalent length.
∆t = Change in saturation temperature corresponding to pressure drop,
condensing temperatures other than 105°F.
°F per 100 feet.
2. Line capacity for other saturation temperatures ∆t and equivalent lengths. CONDENSING SUCTION DISCHARGE
TEMPERATURE, °F LINE LINE
∆
Line capacity = Table capacity X 80 1.16 0.81
∆ 90 1.09 0.89
3. Saturation temperature ∆t for other capacities and equivalent lengths Le ∆t 100 1.03 0.96
110 0.97 1.03
=Table ∆t 120 0.90 1.10
130 0.83 1.16
The refrigerant cycle for determining capacity is based on saturated gas leav-
140 0.76 1.19
ing the evaporator and no subcooling in the condenser. Discharge superheat
is 105°F. The saturated suction temperature is 40°F for liquid line sizing.
TYPE L t = 1°F t = 0.5°F t = 1°F t = 0.5°F t = 1°F t = 0.5°F t = 1°F t = 0.5°F t = 1°F t = 0.5°F t = 1°F t = 0.5°F
COPPER,
O.D. p = 0.42 p = 0.21 p = 0.635 p = 0.318 p = 0.925 p = 0.463 p = 1.285 p = 0.643 p = 1.73 p = 0.865 p = 2.25 p = 1.125
1/2 0.06 0.04 0.11 0.08 0.18 0.13 0.29 0.20 0.43 0.29 0.61 0.42
5/8 0.12 0.08 0.21 0.14 0.35 0.24 0.54 0.37 0.80 0.55 1.15 0.79
3/4 0.21 0.14 0.36 0.25 0.60 0.41 0.92 0.63 1.37 0.94 1.96 1.34
7/8 0.33 0.22 0.57 0.38 0.92 0.63 1.43 0.98 2.12 1.45 3.02 2.08
1-1/8 0.67 0.46 1.15 0.79 1.88 1.28 2.90 1.99 4.29 2.95 6.12 4.22
1-3/8 1.18 0.80 2.02 1.38 3.28 2.25 5.06 3.47 7.49 5.15 10.65 7.34
1-5/8 1.87 1.27 3.20 2.19 5.20 3.56 8.00 5.50 11.84 8.16 16.82 11.62
2-1/8 3.90 2.66 6.66 4.57 10.80 7.42 16.60 11.43 24.53 16.94 34.82 24.06
2-5/8 6.92 4.74 11.81 8.11 19.15 13.16 29.37 20.24 43.30 29.96 61.42 42.54
3-1/8 11.10 7.59 18.88 12.98 30.56 21.03 46.84 32.36 69.12 47.78 97.93 67.88
3-5/8 16.54 11.32 28.12 19.33 45.48 31.32 69.66 48.14 102.68 71.03 145.29 100.82
4-1/8 23.37 16.04 39.75 27.34 64.13 44.26 98.29 67.89 144.70 100.22 204.80 142.08
5-1/8 41.90 28.80 71.16 49.04 114.79 79.27 175.44 121.50 257.95 179.21 365.02 253.76
6-1/8 67.56 46.54 114.71 79.08 184.50 127.75 282.30 195.66 414.50 287.76 586.12 407.59
NOTES:
Capacities are in tons of refrigeration.
Dp = pressure drop due to line friction, psi per 100 feet equivalent length.
Dt = change in saturation temperature corresponding to pressure drop, °F per 100 feet.
Table 28 - DISCHARGE AND LIQUID LINE CAPACITIES IN TONS FOR REFRIGERANT R-410A
LINE SIZE DISCHARGE LINES (delta t = 1°F, delta p = 4.75 PSI) LINE SIZE LIQUID LINES
SATURATED SUCTION TEMPERATURE, °F delta
TYPE L TYPE L VEL. = Δt = 1°F Δt = 5°F
p = 4.75
COPPER, O.D. COPPER, O.D. 100 FPM Δp = 4.75 Δp = 23.3
-60 -40 -20 0 20 40
1/2 1.13 1.17 1.22 1.26 1.30 1.33 0.50 2.00 4.60 10.81
5/8 2.11 2.20 2.29 2.36 2.43 2.49 0.63 3.20 8.60 20.24
3/4 3.59 3.74 3.88 4.02 4.14 4.23 0.75 4.70 14.30 33.53
7/8 5.53 5.76 5.99 6.19 6.38 6.52 0.88 6.70 22.60 52.92
1-1/8 11.16 11.64 12.09 12.50 12.88 13.17 1-1/8 11.40 45.80 106.59
1-3/8 19.39 20.21 21.00 21.72 22.37 22.88 1-3/8 17.40 79.70 185.04
1-5/8 30.63 31.92 33.16 34.30 35.33 36.14 1-5/8 24.60 125.90 291.48
2-1/8 63.20 65.88 68.44 70.78 72.90 74.57 2-1/8 42.80 260.70 601.13
2-5/8 111.20 115.90 120.41 124.53 128.25 131.20 2-5/8 66.00 459.70 1056.39
3-1/8 177.12 184.62 191.80 198.36 204.29 208.98 3-1/8 94.20 733.00 1680.52
3-5/8 262.44 273.54 284.19 293.90 302.70 309.64 3-5/8 127.40 1087.50 2491.00
4-1/8 369.45 385.08 400.07 413.75 426.13 435.90 4-1/8 165.70 1530.20 3500.91
5-1/8 658.32 686.18 712.88 737.26 759.31 776.72 5-1/8 258.20 2729.80 6228.40
6-1/8 1054.47 1099.10 1141.87 1180.91 1216.24 1244.13 6-1/8 371.10 4383.70 9980.43
1. Table capacities are in tons of refrigeration. Multiply table capacities by the following factors for
∆p = Pressure drop due to line friction, psi per 100 feet equivalent length.
condensing temperatures other than 105°F.
∆t = Change in saturation temperature corresponding to pressure drop,
°F per 100 feet. CONDENSING SUCTION DISCHARGE
2. Line capacity for other saturation temperatures ∆t and equivalent lengths. TEMPERATURE, °F LINE LINE
∆ 80 1.16 0.81
Line capacity = Table capacity X 90 1.09 0.89
∆
100 1.03 0.96
3. Saturation temperature ∆t for other capacities and equivalent lengths Le ∆t
110 0.97 1.03
120 0.90 1.10
=Table ∆t
130 0.83 1.16
The refrigerant cycle for determining capacity is based on saturated gas leav-
140 0.76 1.19
ing the evaporator and no subcooling in the condenser. Discharge superheat A
is 105°F. The saturated suction temperature is 40°F for liquid line sizing.
Table 29 - MINIMUM REFRIGERATION CAPACITY IN TONS FOR OIL ENTRAINMENT UP SUCTION RISERS
(TYPE L COPPER TUBING)
SATURATION SUCTION PIPE O.D., IN.
1/2 5/8 3/4 7/8 1-1/8 1-3/8 1-5/8 2-1/8 2-5/8 3-1/8 3-5/8 4-1/8
REFRIGERANT SUCTION GAS
AREA, IN2
TEMP., °F TEMP., °F 0.233 0.348 0.484 0.825 1.256 1.780 3.094 4.770 6.812 9.213 11.97
-30 0.07 0.12 0.20 0.30 0.59 0.99 1.53 3.05 5.25 8.19 11.95 16.57
-40 -10 0.07 0.12 0.20 0.30 0.58 0.97 1.51 3.00 5.16 8.06 11.75 16.30
10 0.07 0.12 0.20 0.30 0.58 0.98 1.52 3.02 5.19 8.11 11.82 16.40
-10 0.09 0.16 0.26 0.39 0.76 1.28 1.97 3.94 6.77 10.57 15.41 21.38
-20 10 0.09 0.15 0.25 0.38 0.74 1.26 1.95 3.89 6.68 10.42 15.20 21.09
30 0.09 0.15 0.26 0.39 0.75 1.27 1.96 3.92 6.73 10.51 15.33 21.26
10 0.11 0.20 0.33 0.49 0.96 1.63 2.52 5.03 8.63 13.48 19.65 27.26
R-22 0 30 0.11 0.19 0.32 0.49 0.94 1.60 2.47 4.93 8.47 13.22 19.29 26.75
50 0.11 0.20 0.32 0.49 0.95 1.61 2.49 4.97 8.54 13.33 19.44 26.96
30 0.14 0.25 0.41 0.62 1.20 2.03 3.15 6.28 10.78 16.84 24.56 34.06
20 50 0.14 0.24 0.40 0.61 1.19 2.01 3.11 6.21 10.66 16.65 24.28 33.68
70 0.14 0.24 0.40 0.61 1.19 2.01 3.11 6.20 10.65 16.63 24.25 33.64
50 0.17 0.30 0.50 0.76 1.48 2.49 3.86 7.70 13.22 20.64 30.11 41.76
40 70 0.17 0.30 0.49 0.74 1.45 2.45 3.78 7.55 12.96 20.24 29.52 40.94
90 0.17 0.30 0.49 0.74 1.45 2.45 3.78 7.55 12.97 20.26 29.54 40.98
-30 0.06 0.10 0.17 0.25 0.49 0.84 1.29 2.58 4.44 6.92 10.10 14.01
-40 -10 0.06 0.10 0.17 0.26 0.51 0.86 1.33 2.65 4.55 7.10 10.35 14.36
10 0.06 0.11 0.18 0.27 0.52 0.88 1.37 2.73 4.69 7.32 10.67 14.81
-10 0.08 0.14 0.23 0.34 0.67 1.13 1.75 3.49 6.00 9.36 13.65 18.93
-20 10 0.08 0.14 0.23 0.35 0.68 1.15 1.78 3.56 6.11 9.54 13.92 19.30
30 0.08 0.14 0.24 0.36 0.70 1.18 1.83 3.65 6.28 0.80 14.29 19.82
10 0.10 0.18 0.29 0.45 0.87 1.47 2.27 4.53 7.78 12.14 17.71 24.56
R-407C 0 0 0.10 0.18 0.30 0.46 0.89 1.51 2.33 4.65 7.98 12.46 18.17 25.20
50 0.10 0.19 0.31 0.47 0.91 1.54 2.38 4.76 8.17 12.76 18.61 25.82
30 0.13 0.23 0.38 0.58 1.12 1.90 2.94 5.86 10.06 15.71 22.92 31.79
20 50 0.13 0.23 0.39 0.59 1.14 1.93 2.98 5.95 10.22 15.95 23.27 32.28
70 0.13 0.24 0.39 0.60 1.16 1.96 3.03 6.05 10.40 16.24 23.68 32.85
50 0.16 0.29 0.47 0.71 1.39 2.35 3.64 7.26 12.47 19.46 28.39 39.38
40 70 0.16 0.29 0.48 0.73 1.41 2.39 3.70 7.38 12.68 19.79 28.87 40.05
90 0.17 0.30 0.49 0.74 1.44 2.44 3.77 7.52 12.92 20.17 29.42 40.82
-30 0.09 0.16 0.26 0.39 0.76 1.29 2.00 3.98 6.84 10.68 15.58 21.61
-40 -10 0.09 0.16 0.26 0.40 0.78 1.32 2.04 4.07 6.99 10.90 15.90 22.06
10 0.09 0.16 0.27 0.41 0.79 1.34 2.08 4.15 7.12 11.12 16.22 22.50
-10 0.11 0.20 0.33 0.50 0.98 1.66 2.56 5.12 8.79 13.72 20.01 27.76
-20 10 0.11 0.21 0.34 0.51 1.00 1.69 2.62 5.22 8.97 14.01 20.43 28.35
30 0.12 0.21 0.35 0.52 1.02 1.73 2.67 5.33 9.15 14.29 20.84 28.91
10 0.14 0.25 0.42 0.63 1.23 2.08 3.21 6.41 11.01 17.19 25.08 34.79
R-410A 0 30 0.14 0.26 0.43 0.64 1.26 2.12 3.28 6.55 11.25 17.57 25.62 35.54
50 0.15 0.26 0.44 0.66 1.28 2.17 3.35 6.68 11.48 17.92 26.14 36.25
30 0.19 0.34 0.56 0.85 1.65 2.79 4.32 8.61 14.80 23.10 33.69 46.74
20 50 0.19 0.35 0.57 0.87 1.69 2.85 4.41 8.81 15.13 23.62 34.45 47.78
70 0.20 0.35 0.58 0.88 1.72 2.91 4.50 8.97 15.42 24.07 35.11 48.70
50 0.21 0.37 0.61 0.93 1.81 3.06 4.73 9.44 16.22 25.32 36.93 51.22
40 70 0.21 0.38 0.63 0.95 1.85 3.13 4.84 9.65 16.58 25.88 37.75 52.36
90 0.22 0.39 0.64 0.97 1.88 3.19 4.93 9.83 16.89 26.37 38.46 53.35
Refrigeration capacity in tons is based on 90°F liquid temperature and superheat as indicated by the tem-
perature in the table. The saturated condensing and suction conditions are referenced to the dewpoint for
R-407C. For other liquid line temperatures, use correction factors to the capacity given in the table below.
LIQUID TEMPERATURE, °F
REFRIGERANT
50 60 70 80 100 110 120 130 140
R-22 1.16 1.12 1.08 1.04 0.96 0.91 0.87 0.82 0.78
R-407C 1.21 1.16 1.11 1.05 0.94 0.89 0.83 0.77 0.70
R-410A 1.21 1.16 1.11 1.05 0.94 0.89 0.82 0.76 0.68
Table 30 - MINIMUM REFRIGERATION CAPACITY IN TONS FOR OIL ENTRAINMENT UP HOT GAS RISERS
(TYPE L COPPER TUBING)
SATURATION SUCTION PIPE O.D., IN.
1/2 5/8 3/4 7/8 1-1/8 1-3/8 1-5/8 2-1/8 2-5/8 3-1/8 3-5/8 4-1/8
REFRIGERANT SUCTION GAS
AREA, IN2
TEMP., °F TEMP., °F 0.233 0.348 0.484 0.825 1.256 1.780 3.094 4.770 6.812 9.213 11.97
110 0.23 0.42 0.69 1.04 2.02 3.42 5.29 10.56 18.15 28.33 41.32 57.31
80 140 0.22 0.39 0.65 0.98 1.91 3.23 5.00 9.98 17.15 26.77 39.04 54.15
170 0.21 0.38 0.62 0.94 1.84 3.11 4.80 9.58 16.46 25.70 37.49 52.00
120 0.24 0.43 0.71 1.07 2.09 3.53 5.46 10.90 18.72 29.22 42.62 59.12
90 150 0.23 0.40 0.67 1.01 1.96 3.32 5.13 10.25 17.60 27.48 40.08 55.60
180 0.22 0.39 0.64 0.96 1.88 3.17 4.90 9.78 16.81 26.24 38.27 53.09
130 0.25 0.44 0.73 1.11 2.16 3.65 5.64 11.26 19.34 30.20 44.05 61.10
R-22 100 160 0.23 0.41 0.68 1.03 2.01 3.41 5.27 10.51 18.05 28.18 41.11 57.02
190 0.22 0.40 0.65 0.99 1.92 3.25 5.02 10.02 17.21 26.86 39.18 54.34
140 0.25 0.45 0.75 1.13 2.21 3.73 5.77 11.52 19.79 30.89 45.06 62.50
110 170 0.24 0.42 0.70 1.06 2.06 3.48 5.38 10.73 18.44 28.79 41.99 58.24
200 0.22 0.40 0.66 0.99 1.93 3.27 5.06 10.09 17.33 27.06 39.46 54.74
150 0.26 0.46 0.76 1.15 2.25 3.80 5.87 11.72 20.14 31.44 45.85 63.60
120 180 0.24 0.43 0.70 1.06 2.07 3.50 5.41 10.81 18.56 28.98 42.27 58.63
210 0.23 0.41 0.67 1.01 1.97 3.34 5.16 10.30 17.70 27.63 40.30 55.90
110 0.42 0.69 1.05 2.04 3.46 5.34 10.66 18.32 28.60 41.72 57.87
80 140 0.22 0.40 0.66 0.99 1.93 3.27 5.05 10.08 17.31 27.02 39.42 54.67
170 0.21 0.38 0.63 0.95 1.85 3.13 4.84 9.66 16.60 25.91 37.79 52.42
120 0.24 0.43 0.71 1.07 2.07 3.51 5.42 10.83 18.60 29.03 42.35 58.74
90 150 0.23 0.41 0.67 1.02 1.98 3.35 5.19 10.35 17.78 27.76 40.49 56.17
180 0.22 0.39 0.65 0.98 1.90 3.22 4.97 9.93 17.06 26.63 38.83 53.87
130 0.24 0.44 0.72 1.09 2.13 3.60 5.56 11.10 19.07 29.77 43.42 60.23
R-407C 100 160 0.23 0.42 0.69 1.05 2.04 3.44 5.32 10.62 18.25 28.49 41.55 57.63
190 0.22 0.40 0.66 1.00 1.94 3.28 5.07 10.12 17.39 27.15 39.60 54.93
140 0.25 0.45 0.73 1.11 2.16 3.66 5.65 11.28 19.38 30.25 44.12 61.21
110 170 0.24 0.42 0.70 1.06 2.06 3.49 5.39 10.76 18.49 28.86 42.10 58.39
200 0.23 0.41 0.67 1.01 1.98 3.34 5.17 10.31 17.71 27.65 40.32 55.93
150 0.25 0.45 0.75 1.13 2.20 3.71 5.74 11.45 19.68 30.72 44.80 62.15
120 180 0.24 0.43 0.71 1.07 2.09 3.53 5.46 10.91 18.73 29.25 42.66 59.17
210 0.23 0.41 0.68 1.03 2.01 3.40 5.26 10.49 18.03 28.14 41.04 56.93
110 0.30 0.54 0.88 1.33 2.60 4.40 6.80 13.56 23.30 36.38 53.06 73.60
80 140 0.28 0.50 0.82 1.24 2.41 4.08 6.31 12.60 21.64 33.79 49.28 68.36
170 0.25 0.45 0.74 1.11 2.17 3.67 5.67 11.32 19.44 30.35 44.27 61.41
120 0.30 0.54 0.90 1.36 2.64 4.47 6.91 13.80 23.70 37.00 53.96 74.85
90 150 0.28 0.50 0.83 1.25 2.43 4.11 6.36 12.69 21.79 34.02 49.62 68.83
180 0.25 0.45 0.75 1.13 2.21 3.73 5.77 11.52 19.79 30.89 45.05 62.49
130 0.31 0.55 0.91 1.37 2.67 4.51 6.98 13.93 23.93 37.36 54.49 75.59
R-410A 100 160 0.27 0.48 0.80 1.20 2.34 3.96 6.13 12.23 21.01 32.79 47.83 66.35
190 0.26 0.46 0.76 1.15 2.23 3.77 5.84 11.65 20.01 31.24 45.56 63.19
140 0.31 0.55 0.91 1.37 2.67 4.52 6.99 13.95 23.96 37.41 54.56 75.69
110 170 0.27 0.49 0.80 1.21 2.36 3.99 6.16 12.30 21.13 32.98 48.11 66.73
200 0.26 0.46 0.76 1.15 2.24 3.79 5.86 11.70 20.10 31.37 45.76 63.47
150 0.30 0.54 0.90 1.36 2.64 4.47 6.91 13.80 23.70 37.00 53.97 74.86
120 180 0.27 0.48 0.80 1.21 2.35 3.98 6.15 12.28 21.09 32.92 48.02 66.61
210 0.26 0.46 0.76 1.15 2.23 3.78 5.84 11.66 20.03 31.27 45.61 63.27
Refrigeration capacity in tons is based on 90°F liquid temperature and superheat as indicated by the tem-
perature in the table. The saturated condensing and suction conditions are referenced to the dewpoint for
R-407C. For other liquid line temperatures, use correction factors to the capacity given in the table below.
LIQUID TEMPERATURE, °F
REFRIGERANT
-40 -20 0 40
R-22 0.91 0.94 0.97 1.03
R-407C 0.88 0.92 0.96 1.04
R-410A 0.91 0.94 0.97 1.02
Table 31 - FITTING LOSSES IN EQUIVALENT FEET OF PIPE (SCREWED, WELDED, FLANGED AND
BRAZED CONNECTIONS)
SMOOTH BEND ELBOWS SMOOTH BEND TEES
90° 90° LONG 90° 45° 45° 180° FLOW STRAIGHT-THROUGH FLOW
STD.a RADIUSb STREETa STD.a STD.a STD.a THROUGH
NOMINAL NO REDUCED REDUCED
BRANCH
PIPE OR REDUCTION 1/4 1/2
TUBE
SIZE, IN.
3/4d 1/2d
d d
3/8 1.4 0.9 2.3 0.7 1.1 2.3 2.7 0.9 1.2 1.4
1/2 1.6 1.0 2.5 0.8 1.3 2.5 3.0 1.0 1.4 1.6
3/4 2.0 1.4 3.2 0.9 1.6 3.2 4.0 1.4 1.9 2.0
1 2.6 1.7 4.1 1.3 2.1 4.1 5.0 1.7 2.2 2.6
1-1/4 3.3 2.3 5.6 1.7 3.0 5.6 7.0 2.3 3.1 3.3
1-1/2 4.0 2.6 6.3 2.1 3.4 6.3 8.0 2.6 3.7 4.0
2 5.0 3.3 8.2 2.6 4.5 8.2 10.0 3.3 4.7 5.0
2-1/2 6.0 4.1 10.0 3.2 5.2 10.0 12.0 4.1 5.6 6.0
3 7.5 5.0 12.0 4.0 6.4 12.0 15.0 5.0 7.0 7.5
3-1/2 9.0 5.9 8.2 4.7 7.3 15.0 18.0 5.9 8.0 9.0
4 10.0 6.7 10.0 5.2 8.5 17.0 21.0 6.7 9.0 10.0
5 13.0 8.2 12.0 6.5 11.0 21.0 25.0 8.2 12.0 13.0
6 16.0 10.0 15.0 7.9 13.0 25.0 30.0 10.0 14.0 16.0
3/8 1.4 0.8 0.3 0.7 0.5 0.3 1.5 0.8 1.5 1.1
1/2 1.8 1.1 0.4 0.9 0.7 0.4 1.8 1.0 1.8 1.5
3/4 2.5 1.5 0.5 1.2 1.0 0.5 2.8 1.4 2.8 2.2
1 3.2 2.0 0.7 1.6 1.2 0.7 3.7 1.8 3.7 2.7
1-1/4 4.7 3.0 1.0 2.3 1.8 1.0 5.3 2.6 5.3 4.2
1-1/2 5.8 3.6 1.2 2.9 2.2 1.2 6.6 3.3 6.6 5.0
2 8.0 4.8 1.6 4.0 3.0 1.6 9.0 4.4 9.0 6.8
2-1/2 10.0 6.1 2.0 5.0 3.8 2.0 12.0 5.6 12.0 8.7
3 13.0 8.0 2.6 6.5 4.9 2.6 14.0 7.2 14.0 11.0
3-1/2 15.0 9.2 3.0 7.7 6.0 3.0 17.0 8.5 17.0 13.0
4 17.0 11.0 3.8 9.0 6.8 3.8 20.0 10.0 20.0 16.0
5 24.0 15.0 5.0 12.0 9.0 5.0 27.0 14.0 27.0 20.0
6 29.0 22.0 6.0 15.0 11.0 6.0 33.0 19.0 33.0 25.0
Table 38 - HGBP LINE SIZING FOR R-22, R-407C AND R-410A REFRIGERANTS
NOTE: When HGBP selections fall between two line sizes, always use the line size closest to the selection point.
NOTES