Micropilot FMR51 FMR52 TI
Micropilot FMR51 FMR52 TI
Micropilot FMR51 FMR52 TI
TI01040F/00/EN/01.12
71162672
Table of contents Micropilot FMR51, FMR52
Table of contents
2 Endress+Hauser
Micropilot FMR51, FMR52 Table of contents
Registered trademarks . . . . . . . . . . . . . . . . . . . . . . . 88
Patents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
Endress+Hauser 3
Micropilot FMR51, FMR52
Symbol Meaning
DANGER!
DANGER This symbol alerts you to a dangerous situation. Failure to avoid this situation will result in serious
A0011189-EN
or fatal injury.
WARNING!
WARNING This symbol alerts you to a dangerous situation. Failure to avoid this situation can result in serious
A0011190-EN
or fatal injury.
CAUTION!
CAUTION This symbol alerts you to a dangerous situation. Failure to avoid this situation can result in minor
A0011191-EN
or medium injury.
NOTICE!
NOTICE This symbol contains information on procedures and other facts which do not result in personal
A0011192-EN
injury.
Electrical symbols
Symbol Meaning
Direct current
A0011197 A terminal to which DC voltage is applied or through which direct current flows.
Alternating current
A0011198 A terminal to which alternating voltage is applied or through which alternating current flows.
Ground connection
A grounded terminal which, as far as the operator is concerned, is grounded via a grounding system.
A0011200
Equipotential connection
A connection that has to be connected to the plant grounding system: This may be a potential
A0011201
equalization line or a star grounding system depending on national or company codes of practice.
Symbol Meaning
Allowed
Indicates procedures, processes or actions that are allowed.
A0011182
Preferred
Indicates procedures, processes or actions that are preferred.
A0011183
Forbidden
Indicates procedures, processes or actions that are forbidden.
A0011184
Tip
Indicates additional information.
A0011193
Reference to documentation
Refers to the corresponding device documentation.
A0011194
4 Endress+Hauser
Micropilot FMR51, FMR52
Symbol Meaning
Reference to page
Refers to the corresponding page number.
A0011195
Reference to graphic
Refers to the corresponding graphic number and page number.
A0011196
Symbols in graphics
Symbol Meaning
A, B, C, ... Views
Hazardous area
- Indicates a hazardous area.
A0011187
Symbol Meaning
Safety instructions
Observe the safety instructions contained in the associated Operating Instructions.
Endress+Hauser 5
Micropilot FMR51, FMR52
100%
D
E
F
0%
A0017870
Input
The reflected radar impulses are received by the antenna and transmitted into the electronics. A
microprocessor evaluates the signal and identifies the level echo caused by the reflection of the radar impulse
at the product surface. The unambiguous signal identification is accomplished by the PulseMaster® eXact
software together with the Multi-echo tracking algorithms, based on many years of experience with time-of-
flight technology.
The distance D to the product surface is proportional to the time of flight t of the impulse:
D = c · t/2,
with c being the speed of light.
Based on the known empty distance E, the level L is calculated:
L=E–D
The reference point R of the measurement is located at the process connection. For details see the
dimensional drawing:
• FMR51: (® ä 62)
• FMR52: (® ä 65)
The Micropilot is equipped with functions to suppress interference echoes. The user can activate these
functions. Together with the multi-echo tracking algorithms they ensure that interference echoes (i.e. from
edges and weld seams) are not interpreted as level echo.
6 Endress+Hauser
Micropilot FMR51, FMR52
Output
The Micropilot is commissioned by entering an empty distance "E" (=zero), a full distance "F" (=span) and
application parameters. The application parameters are automatically adapt into the instrument to the
process conditions. For models with a current output, the factory adjustment for zero point "E" and span "F"
is 4 mA and 20 mA. For digital outputs and the display module, the factory adjustment for zero point "E" and
span "F" is 0 % and 100 %.
A linearization with max. 32 points, based on a table entered either manually or semi-automatically, can be
activated locally or remotely. This function provides a measurement in engineering units and a linear output
signal for spheres, horizontal cylindrical tanks and vessels with conical outlet.
A0013773-EN
å2 Life cycle
Engineering
• Universal measuring principle
• Measurement unaffected by medium properties
• Hardware and software developed according to SIL IEC 61508
Procurement
• Endress+Hauser being the world market leader in level measurement guarantees asset protection
• Worldwide support and service
Installation
• Special tools are not required
• Reverse polarity protection
• Modern, detachable terminals
• Main electronics protected by a separate connection compartment
Commissioning
• Fast, menu-guided commissioning in only a few steps on site or from the control room
• Plain text display in national languages reduces the risk of error or confusion
• Direct local access of all parameters
• Short instruction manual at the device
Operation
• Multi-echo tracking: Reliable measurement through self-learning echo-search algorithms taking into
account the short-term and long-term history in order to check the found echoes for plausibility and to
suppress interference echoes.
• Diagnostics in accordance with NAMUR NE107
Maintenance
• HistoROM: Data backup for instrument settings and measured values
• Exact instrument and process diagnosis to assist fast decisions with clear details concerning remedies
• Intuitive, menu-guided operating concept in national languages saves costs for training, maintenance and
operation
• Cover of the electronics compartment can be opened in hazardous areas
Retirement
• Order code translation for subsequent models
• RoHS-conforming (Restriction of certain Hazardous Substances), unleaded soldering of electronic
components
• Environmentally sound recycling concept
Endress+Hauser 7
Micropilot FMR51, FMR52
Input
Measured variable The measured variable is the distance between the reference point and the product surface.
Subject to the empty distance entered "E" the level is calculated.
Alternatively, the level can be converted into other variables (volume, mass) by means of linearization (32
points).
Media groups
Media groups DK (er) Example
D > 10 conducting liquids, e.g. aqueous solutions, dilute acids and alkalis
8 Endress+Hauser
Micropilot FMR51, FMR52
A0018833
Calm product surface (e.g. intermittent filling, filling from bottom, immersion tubes)
Antenna size
A B C D A B C D A B C D A B C D
3
(9.9) 4
5 5 (13)
(16) (16)
8 8 8
8
(26) (26) (26) (26)
10 10 10
(32) 12 (32) (32)
15 15 (39) 15 15 15
(49) (49) (49) (49) (49)
25 20 25
25
(82) (65) (82)
(82)
30 30
A0018858
35 (98) (99)
(110)
40 40 40 40 40
(131) (131) (131) (131) (131)
A0018859 45
(148)
60
(197)
70
A0018860 (229)
A0018862
Legend
Measuring range of the standard version
Measuring range for the "Advanced dynamics" application package (product structure: feature 540: "Application
Package", Option EM: "Advanced dynamics")
Endress+Hauser 9
Micropilot FMR51, FMR52
A0018835
Antenna size
B C D B C D A B C D A B C D
2
(6.6) 2.5
(8)
3
(9.9)
4
(13)
5 5 5 5 5
(16) (16) (16) (16) (16)
35
(110)
A0018866
Legend
Measuring range of the standard version
Measuring range for the "Advanced dynamics" application package (product structure: feature 540: "Application
Package", Option EM: "Advanced dynamics")
10 Endress+Hauser
Micropilot FMR51, FMR52
A0018837
Antenna size
B C D B C D B C D B C D
1
(3.2)
2 2
(6.6) (6.6)
2.5
(8.2)
3 3
(9.8) (9.8)
4
(13)
5 5 5 5
(16) (16) (16) (16)
7.5
A0018867 8 8
(25)
(26) (26) 10
10
(32) (32)
12
A0018868
(39)
15 15
(49) (49)
A0018869
20
(65)
A0018870
Legend
Measuring range of the standard version
Measuring range for the "Advanced dynamics" application package (product structure: feature 540: "Application
Package", Option EM: "Advanced dynamics")
Endress+Hauser 11
Micropilot FMR51, FMR52
A0018840
A0018842
A, B, C, D C, D
20 20
(66) (66)
A0018851 A0018852
12 Endress+Hauser
Micropilot FMR51, FMR52
1) Product structure, feature 540: "Application package", option EM: "Advanced dynamics"
Endress+Hauser 13
Micropilot FMR51, FMR52
Output
Output signal HART
Switch output
For HART devices, the switch output is available as an option. See product structure, feature 20:
"Power Supply, Output", option B: "2-wire; 4-20mA HART, switch output"
Devices with PROFIBUS PA and FOUNDATION Fieldbus always have a switch output.
Switch output
Switching behavior Binary (conductive or non-conductive), switches when the programmable switch point is
reached
Insulation voltage floating, Insulation voltage 1 350 VDC to power supply aund 500 VAC to ground
Switch point freely programmable, separately for switch-on and switch-off point
Switching delay freely programmable from 0 to 100 sec. , separately for switch-on and switch-off point
14 Endress+Hauser
Micropilot FMR51, FMR52
Linearization The linearization function of the device allows the conversion of the measured value into any unit of length
or volume. Linearization tables for calculating the volume in cylindrical tanks are pre-programmed. Other
tables of up to 32 value pairs can be entered manually or semi-automatically.
Galvanic isolation All circuits for the outputs are galvanically isolated from each other.
Manufacturer ID 17 (0x11)
HART device variables The measured values can be freely assigned to the device variables.
Measured values for PV (primary variable)
• Level linearized
• Distance
• Electronic temperature
• Relative echo amplitude
• Analog output adv. diagnostics
Measured values for SV, TV, FV (second, third and fourth variable)
• Level linearized
• Distance
• Terminal voltage
• Electronic temperature
• Absolute echo amplitude
• Relative echo amplitude
• Area of incoupling
Manufacturer ID 17 (0x11)
Endress+Hauser 15
Micropilot FMR51, FMR52
Manufacturer ID 0x452B48
Number of VCRs 44
16 Endress+Hauser
Micropilot FMR51, FMR52
Permanent entries 1
Client VCRs 0
Server VCRs 10
Source VCRs 43
Sink VCRs 0
Subscriber VCRs 43
Publisher VCRs 43
Slot time 4
Transducer Blocks
Block Content Output values
Setup Transducer Block Contains all parameters for a standard commissioning • Level or volume 1)
procedure (Channel 1)
• Distance (Channel 2)
Advanced Setup Transducer Contains all parameters for a more detailed configuration no output values
Block of the device
Display Transducer Block Contains all parameters for the configuration of the no output values
display module
Expert Configuration Contains parameters which require detailed knowledge no output values
Transducer Block of the functionalities of the device
Expert Information Contains information about the state of the device no output values
Transducer Block
Service Sensor Transducer Contains parameters which can only be operated by no output values
Block Endress+Hauser service personnel
Service Information Contains information on the state of device which is no output values
Transducer Block relevant for service operations
Data Transfer Transducer Contains parameters which allow to backup the device no output values
Block configuration in the display module and to restore it into
the device.
Function Blocks
Block Content Number of Number of Execution Functionality
permanent instantiable time
blocks blocks
Resource Block The Resource Block contains all the data 1 0 - enhanced
that uniquely identifies the field device.
It is an electronic version of a nameplate
of the device.
Endress+Hauser 17
Micropilot FMR51, FMR52
Up to 20 blocks can be instantiated in the device altogether, including the blocks already instantiated
on delivery.
18 Endress+Hauser
Micropilot FMR51, FMR52
Power supply
Terminal assignment 2-wire: 4-20mA HART
2- w
4-2 ire le
0 v el
H A mA
[21 RT
4-2
0m
A ]
ope
A
n Sp
a
711 re pa
HA 20mA
08x rt
xx
RT
4...
+
1 -
1 2 4 5 6
mm
2
10
+ +
–
–
4...20 mA
3 B
7 +
1-c 1 -
1 2 4 5 han
nel 4-2 2
ove 0m
[16
] rvo A
ltag
ep
rote
ctio
n
+ + 711
286
– 17
–
4...20 mA
3
A0011294
Endress+Hauser 19
Micropilot FMR51, FMR52
10
9
8
2- w
4-2 ire
0
HA mA
[02 RT
PF
S
A /03
] ope
n Sp
a
711 re pa
HA 20 mA
08x rt
3+ ++ xx
31 --
RT
4...
42 +
7
1 -
mm
2 6
4-
10
+ +
–
-
³250W 4...20 mA
1 2 3 4 5 B
3+ 11 +
3 -
4-2 4
0m +
2-c
A/ 1 -
han 4-2 2
4- [17
nel
ove FIE 0mA
] rvo LD /
ltag
ep
BU
ro S
tec
tion
+ + 711
286
– 19
-
³250W 4...20 mA
1 2 3 4 5
A0013759
20 Endress+Hauser
Micropilot FMR51, FMR52
14
13
12
2- w
4-2 ire le
0 v el
HA mA
[04 RT
4-2
0m
A /05
]
A
ope
A
n Sp
20m
a
711 re pa
HA 20mA
08x rt
xx
+
4 ...
3 -
RT
11
4 ...
4 +
1 -
mm
2
+
10
+
1 –
-
4...20 mA
9 8
+ +
2 –
-
4...20 mA
3 5 6 7 4
B
+ +
1 –
+
- 3 -
4...20 mA 4-2 4
10 0m +
9 8 2-c
A/ 1 -
han
nel 4- 2
[17
ove FIE 20mA
] rvo LD /
ltag
ep
B U
ro S
tec
tion
+ + 711
28 6
2 – 19
-
4...20 mA
3 5 6 7 4
A0013923
This version is also suited for single-channel operation. In this case, current output 1 (terminals 1 and
2) must be used.
Endress+Hauser 21
Micropilot FMR51, FMR52
13
12
11
2- w
4-2 ire
0
HA mA
[08 RT
A ]
= V
ope
48
n Sp
4...
a
711 re pa
HA 20 mA
08x rt
10.
L+ xx
1 L-
RT
4...
2 +
10 9
3 -
mm
4 8
10
7
+
-
³250W 4...20 mA
6
1 2 3 4 5
A0011340
!CAUTION
To ensure electrical safety:
► Do not disconnect the protective connection (7).
► Disconnect the supply voltage before disconnecting the protective earth (8).
Connect protective earth to the internal ground terminal (8) before connecting the supply voltage. If
necessary, connect the potential matching line to the external ground terminal (12).
In order to ensure electromagnetic compatibility (EMC): Do not only ground the device via the
protective earth conductor of the supply cable. Instead, the functional grounding must also be
connected to the process connection (flange or threaded connection) or to the external ground
terminal.
An easily accessible power switch must be installed in the proximity of the device. The power switch
must be marked as a disconnector for the device (IEC/EN61010).
22 Endress+Hauser
Micropilot FMR51, FMR52
13
12
11
2- w
4-2 ire
0
HA mA
[09 RT
A ]
~
3V
ope
n
..25
Sp
a
711 re pa
HA 20 mA
9 0.
08x rt
xx
L
1 N
RT
4...
2 +
10 9
3 -
mm
4 8
10
7
+
-
³250W 4...20 mA
6
1 2 3 4 5
A0018965
!CAUTION
To ensure electrical safety:
► Do not disconnect the protective connection (7).
► Disconnect the supply voltage before disconnecting the protective earth (8).
Connect protective earth to the internal ground terminal (8) before connecting the supply voltage. If
necessary, connect the potential matching line to the external ground terminal (12).
In order to ensure electromagnetic compatibility (EMC): Do not only ground the device via the
protective earth conductor of the supply cable. Instead, the functional grounding must also be
connected to the process connection (flange or threaded connection) or to the external ground
terminal.
An easily accessible power switch must be installed in the proximity of the device. The power switch
must be marked as a disconnector for the device (IEC/EN61010).
Endress+Hauser 23
Micropilot FMR51, FMR52
2-
F4IEwire
-20L lev
mD
ABU el
FA
P IE/F S
06/ LD
[2 F B PFS
A 07]
2 U S
op en Sp
a
7110 re pa
US
0283x4 rt
3+ ++ x5x7
B
31 --
/LFDF
PIAE
42 +
F
2
1 2-
mm
4-
10
3
1
B
3+ 6 +
3 -
4-2 4 +
0m
2-c
A/ 1 -
han
nel 4-2 2
4- [17
]
ove
rvo
FIE 0mA
LD /
ltag BU
1 ep
rote S
ctio
n
711
286
19
A0011341
24 Endress+Hauser
Micropilot FMR51, FMR52
+
1
3+ 2
3+
+
-
4-
4-
A0015909 A0015910
Endress+Hauser 25
Micropilot FMR51, FMR52
Device plug connectors For the versions with fieldbus plug connector (M12 or 7/8"), the signal line can be connected without
opening the housing.
1 Signal +
4 3 –
2 not connected
1 + 2 nc 3 Signal -
4 Ground
A0011175
1 3 1 Signal -
2 Signal +
2 4 3 Screen
4 Not connected
A0011176
26 Endress+Hauser
Micropilot FMR51, FMR52
"Power Supply, "Approval" 2) Terminal voltage U at Maximum load R, depending on the supply voltage U0 at the
Output" 1) the device supply unit
Ex ia / IS 10.4 to 30 V 3)
0
10 20 30 35 U0 [V]
10.4 21.4
A0017140
4)
• Ex d(ia) / XP 12 to 35 V R [W]
• Ex ic(ia)
• Ex nA(ia) 500
• Ex ta / DIP
Ex ia + Ex d(ia) / IS + XP 12 to 30 V 4)
0
10 20 30 35 U0 [V]
12 23
A0019136
"Power Supply, Output" 1) "Approval" 2) Terminal voltage U at Maximum load R, depending on the supply voltage U0 at the
the device supply unit
• Ex ia / IS 12 to 30 V 3)
0
• Ex ia + Ex d(ia) / IS + XP
10 20 30 35 U0 [V]
12 23
A0019136
Endress+Hauser 27
Micropilot FMR51, FMR52
"Power Supply, Output" 1) "Approval" 2) Terminal voltage U at the Maximum load R, depending on the supply voltage U0 at the
device supply unit
500
0
10 20 30 U0 [V]
12 23
A0017055
28 Endress+Hauser
Micropilot FMR51, FMR52
Polarity sensitive No
Nominal current 3.6 to 22 mA, the start-up current for multidrop mode can be parametrized (is set to
3.6 mA on delivery)
Nominal current 14 mA
Endress+Hauser 29
Micropilot FMR51, FMR52
Ui 17.5 V
Ii 550 mA
Pi 5.5 W
Ci 5 nF
Li 10 mH
Cable specification • Standard device cable is sufficient for the power supply of the device.
• Minimum cross-section: (® ä 30)
• For ambient temperature TU³60 °C (140 °F): use cable for temperature TU +20 K.
HART
• A normal device cable suffices if only the analog signal is used.
• A shielded cable is recommended if using the HART protocol. Observe grounding concept of the plant.
30 Endress+Hauser
Micropilot FMR51, FMR52
Overvoltage protection If the measuring device is used for level measurement in flammable liquids which requires the use of
overvoltage protection according to DIN EN 60079-14, standard for test procedures 60060-1 (10 kA, pulse
8/20 ms), overvoltage protection has to be ensured by an integrated or external overvoltage protection
module.
Technical data
Endress+Hauser 31
Micropilot FMR51, FMR52
Performance characteristics
Reference operating • Temperature = +24 °C (+75 °F) ±5 °C (±9 °F)
conditions • Pressure = 960 mbar abs. (14 psia) ±100 mbar (±1.45 psi)
• Humidity = 60 % ±15 %
• Reflector: metal plate with a minimum diameter of 1 m (40 in)
• No major interference reflections inside the signal beam
Maximum measured error Typical data under reference operating conditions: DIN EN 61298-2, percentage values in relation to the
span.
digital analog 1)
4 (0.16)
D [mm] ([in])
2 (0.08)
0
-2 (-0.08)
-4 (-0.16)
32 Endress+Hauser
Micropilot FMR51, FMR52
R
20 (0.79)
D [mm] ([in])
3 (0.12)
0
-3 (-12)
-20 (-0.79)
å 12 Maximum measured error in near-range applications; values for version with the "Advanced dynamics"
application package
D Maximum measured error
D Distance from the reference point R
A Lower edge of the antenna
Reaction time The reaction time can be parametrized. The following step response times (as per DIN EN 61298-2) 1)are
valid if the damping is switched off:
Influence of ambient The measurements are carried out in accordance with EN 61298-3
temperature • Digital (HART, PROFIBUS PA):
– Standard version: average TK = 2 mm/10 K; maximum 5 mm
– Version with advanced dynamics 2): average TK = 5 mm/10 K; maximum 15 mm
• Analog (current output):
– zero point (4 mA): average TK = 0.02 %/10 K
– span (20 mA): average TK = 0.05 %/10 K
Influence of gas layer High pressures reduce the propagation velocity of the measuring signals in the gas/vapor above the fluid.
This effect depends on the kind of gas/vapor and of its temperature. This results in a systematic measuring
error that gets bigger as the distance increases between the reference point of the measurement (flange) and
1) According to DIN EN 61298-2 the response time is the time which passes after a sudden change of the input signal until the output signal for the first time
assumes 90% of the steady-state value.
2) Feature 540 "Application Package", option EM
Endress+Hauser 33
Micropilot FMR51, FMR52
the product surface. The following table illustrates this measured error for a few typical gases/vapors (with
regard to distance; a positive value means that too large a distance is being measured):
°C °F 1 bar (14,5 psi) 10 bar (145 psi) 50 bar (725 psi) 100 bar (1450 psi) 160 bar (2320 psi)
310 590 - - - 22 % -
When the pressure is known and constant, this measured error can, for example, be compensated by
means of a linearization.
Gas phase compensation with PROFIBUS devices can receive the signal of an external pressure sensor through the bus and use it to
external pressure sensor perform a pressure dependent time-of-flight correction. In the case of saturated steam in the temperature
(PROFIBUS PA, in range from 100 to 350 °C (212 to 662 °f), for example, the measuring error of the distance measurement
preparation) can be reduced by this method from up to 29 % (without compensation) to less than 3 % (with
compensation).
34 Endress+Hauser
Micropilot FMR51, FMR52
Installation
Installation conditions Mounting position
A0016882
Vessel installations
A0018944
Endress+Hauser 35
Micropilot FMR51, FMR52
A0016890
3
1
A0017123
36 Endress+Hauser
Micropilot FMR51, FMR52
Optimization options
• Antenna size
The bigger the antenna, the smaller the beam angle a and the fewer interference echoes (® ä 38).
• Mapping
The measurement can be optimized by means of electronic suppression of interference echoes.
• Antenna alignment
Take into account the marker on the flange or threaded connection (® ä 41) (® ä 43) .
• Stilling well
A stilling well can be applied to avoid interferences (® ä 44).
• Metallic screens mounted at a slope
They spread the radar signals and can, therefore, reduce interference echoes.
Endress+Hauser 37
Micropilot FMR51, FMR52
Beam angle
a
W = 2 . D . tan _
2
D
a
A0016891
The beam angle is defined as the angle a where the energy density of the radar waves reaches half the value
of the maximum energy density (3-dB-width). Microwaves are also emitted outside the signal beam and can
be reflected off interfering installations.
Beam diameter W as a function of beam angle a and measuring distance D:
FMR51
3 m (9.8 ft) 1.22 m (4 ft) 0.95 m (3.1 ft) 0.53 m (1.7 ft) 0.42 m (1.4 ft)
6 m (20 ft) 2.44 m (8 ft) 1.9 m (6.2 ft) 1.05 m (3.4 ft) 0.84 m (2.8 ft)
9 m (30 ft) 3.66 m (12 ft) 2.85 m (9.4 ft) 1.58 m (5.2 ft) 1.26 m (4.1 ft)
12 m (39 ft) 4.88 m (16 ft) 3.80 m (12 ft) 2.1 m (6.9 ft) 1.68 m (5.5 ft)
15 m (49 ft) 6.1 m (20 ft) 4.75 m (16 ft) 2.63 m (8.6 ft) 2.10 m (6.9 ft)
20 m (66 ft) 8.14 m (27 ft) 6.34 m (21 ft) 3.50 m (11 ft) 2.80 m (9.2 ft)
25 m (82 ft) 10.17 m (33 ft) 7.92 m (26 ft) 4.37 m (14 ft) 3.50 m (11 ft)
30 m (98 ft) - 9.50 m (31 ft) 5.25 m (17 ft) 4.20 m (14 ft)
35 m (115 ft) - 11.09 m (36 ft) 6.12 m (20 ft) 4.89 m (16 ft)
40 m (131 ft) - 12.67 m (42 ft) 7.00 m (23 ft) 5.59 m (18 ft)
FMR52
38 Endress+Hauser
Micropilot FMR51, FMR52
Endress+Hauser 39
Micropilot FMR51, FMR52
Measuring conditions • In case of boiling surfaces, bubbling or tendency for foaming use FMR53 or FMR54. Depending on its
consistence, foam can either absorb microwaves or reflect them off the foam surface. Measurement is
possible under certain conditions. For FMR50, FMR51 and FMR52, the additional option "Advanced
dynamics" is recommended in these cases (feature 540: "Application Package", option EM).
• In case of heavy steam development or condensate, the maximum measuring range of FMR50,
FMR51 and FMR52 may decrease depending on density, temperature and composition of the steam ®
use FMR53 or FMR54.
• For the measurement of absorbing gases such as ammonia NH3 or some fluorocarbons 3), please use
Levelflex or Micropilot FMR54 in a stilling well.
• The measuring range begins, where the beam hits the tank bottom. Particularly with dish bottoms or
conical outlets the level cannot be detected below this point.
• For stilling well applications, the zero should be positioned at the end of the tube, as the electromagnetic
waves do not propagate completely outside the tube. It must be taken into account that the accuracy may
be reduced in the area C. In order to guarantee the required accuracy in these cases, it is recommended to
position the zero-point at a distance C above the end of the tube (see figure).
• In case of media with a low dielectric constant (er = 1.5 to 4) 4) the tank bottom can be visible through the
medium at low levels (low height C). Reduced accuracy has to be expected in this range. If this is not
acceptable, we recommend positioning the zero point at a distance C (see figure) above the tank bottom
in these applications.
• In principle it is possible to measure up to the tip of the antenna with FMR51, FMR53 and FMR54.
However, due to considerations regarding corrosion and build-up, the end of the measuring range should
not be chosen any closer than A (see figure) to the tip of the antenna.
• When using FMR54 with planar antenna, especially for media with low dielectric constants, the end of
the measuring range should not be closer than 1 m (3.28 ft) to the flange.
• The smallest possible measuring range B depends on the antenna version (see figure).
• The tank height should be at least H (see table).
A
100%
H
B
C
0%
øD
A0018872
FMR51 50(1.97)
> 0.2 (0.7) 50 to 250 (1.97 to 9.84) > 0.3 (1.0)
FMR52 200(7.87)
40 Endress+Hauser
Micropilot FMR51, FMR52
A B
°
°
90
90
°
90
° °
°
90 90
90
90 90
° °
90 90
° °
A0018974
Nozzle mounting
The horn antenna should extend below the nozzle. Select version with antenna extension up to
500 mm (19.7 in), if necessary 5). Nozzle heights up to 500 mm (19.7 in) can be accepted if this should not
be possible due to mechanical reasons.
H
øD
A0016820
H < 85 mm (3.35 in) < 115 mm (4.53 in) < 210 mm (8.27 in) < 280 mm (11.0 in)
5) In the product structure: feature 610 "Accessory mounted", options OM, OU, OV.
Endress+Hauser 41
Micropilot FMR51, FMR52
Threaded connection
• Tighten with the hexagonal nut only.
• Tool : Hexagonal wrench 55 mm
• Maximum permissible torque: 60 Nm (44 lbf ft)
1) Other possible values for the thickness are multiples of the values listed (e.g. for PE: 7,6 mm (0.3 in), 11,4 mm
(0.45 in)
42 Endress+Hauser
Micropilot FMR51, FMR52
Alignment
• Align the antenna vertically to the product surface.
The maximum range may be reduced if the horn antenna is not vertically aligned.
• A marking at the flange or the boss enables alignment of the antenna. This marking must be aligned
towards the tank wall.
A B
°
°
90
90
°
90
° °
°
90 90
90
90 90
° °
90 90
° °
A0018974
Nozzle mounting
H
øD 1
A0016819
For flanges with PTFE cladding: Use spring washers (see figure) to compensate for the sagging of the
cladding.
It is recommended to tighten the the flange bolts periodically, depending on process temperature and
pressure.
Recommended torque: 60 to 100 Nm (44.25 to 73.75 lbf ft)
Endress+Hauser 43
Micropilot FMR51, FMR52
°
90
1
A0016841
• For horn antenna: Align the marking towards the slots of the stilling well.
• Measurements can be performed through an open full bore ball valve without any problems.
• After mounting, the housing can be turned 350° in order to simplify access to the display and the terminal
compartment.
44 Endress+Hauser
Micropilot FMR51, FMR52
Endress+Hauser 45
Micropilot FMR51, FMR52
A B A-A
A A 1
1 C
2 3
100%
100%
4
5
(5.91...19.7)
150…500
≤ 1 (0.04)
(5.91...19.7)
150…500
≤ 1 (0.04)
D 6
0%
0%
mm (in)
A0019009
46 Endress+Hauser
Micropilot FMR51, FMR52
Installation in bypass
°
90
1
°
90
A0019446
å 17 Installation in bypass
1 Marking for antenna alignment
2 Tank connectors
Endress+Hauser 47
Micropilot FMR51, FMR52
48 Endress+Hauser
Micropilot FMR51, FMR52
A
A-A
A A
≤ 1 (0.04)
2
C
(7.87) (7.87)
100% 200 200
3
4 B
4
3
(7.87) (7.87)
200
0%
200
mm (in)
A0019010
Endress+Hauser 49
Micropilot FMR51, FMR52
1
2
A0019142
If process temperatures are high, the device must be included in normal tank insulation to prevent the
electronics heating up as a result of heat radiation or convection. The insulation may not exceed beyond the
neck of the housing.
50 Endress+Hauser
Micropilot FMR51, FMR52
Environment
Ambient temperature range Measuring device –40 to +80 °C (–40 to +176 °F); –50 °C (–58 °F) with manufacturer declaration on
request
Local display –20 to +70 °C (–4 to +158 °F), the readability of the display may be impaired at
temperatures outside the temperature range.
Ambient temperature limits The following diagrams take into account only function requirements. There may be further restrictions
for certified device versions. Please refere to the separate Safety Instructions (® ä 87).
With a temperature (Tp) at the process connection the admissible ambient temperature (Ta) is reduced
according to the following diagram (temperature derating):
FMR51 Ta
P1 P2
Seal:
• Viton GLT, –40 to 150 °C (–40 to 302 °F) P3
• Kalrez, –20 to 150 °C (–4 to 302 °F)
Housing: GT18 (316 L) Tp
Temperature unit: °C (°F) P5 P4
A0019351
Endress+Hauser 51
Micropilot FMR51, FMR52
FMR51 Ta
P1 P2
Seal:
• Viton GLT, –40 to 150 °C (–40 to 302 °F) P3
• Kalrez, –20 to 150 °C (–4 to 302 °F)
Housing: GT19 (Plastics PBT) Tp
Temperature unit: °C (°F) P5 P4
A0019351
FMR51 Ta
P1 P2
Seal:
• Viton GLT, –40 to 150 °C (–40 to 302 °F) P3
• Kalrez, –20 to 150 °C (–4 to 302 °F)
Housing: GT20 (Alu, coated) Tp
Temperature unit: °C (°F) P5 P4
A0019351
52 Endress+Hauser
Micropilot FMR51, FMR52
FMR51 Ta
Seal: Graphite, –40 to 250 °C (–40 to 482 °F) P1 P2
Housing: GT18 (316 L) P3
Temperature unit: °C (°F)
Tp
P5 P4
A0019351
FMR51 Ta
Seal: Graphite, –40 to 250 °C (–40 to 482 °F) P1 P2
Housing: GT19 (Plastics PBT) P3
Temperature unit: °C (°F)
Tp
P5 P4
A0019351
Endress+Hauser 53
Micropilot FMR51, FMR52
FMR51 Ta
Seal: Graphite, –40 to 250 °C (–40 to 482 °F) P1 P2
Housing: GT20 (Alu, coated) P3
Temperature unit: °C (°F)
Tp
P5 P4
A0019351
FMR51 Ta
Seal: Graphite, –196 to 450 °C (–321 to 842 °F) P1 P2
Housing: GT18 (316 L) P3
Temperature unit: °C (°F)
P6 Tp
P5 P4
A0019344
54 Endress+Hauser
Micropilot FMR51, FMR52
FMR51 Ta
Seal: Graphite, –196 to 450 °C (–321 to 842 °F) P1 P2
Housing: GT19 (Plastics PBT) P3
Temperature unit: °C (°F)
P6 Tp
P5 P4
A0019344
FMR51 Ta
Seal: Graphite, –196 to 450 °C (–321 to 842 °F) P1 P2
Housing: GT20 (Alu, coated) P3
Temperature unit: °C (°F)
P6 Tp
P5 P4
A0019344
Endress+Hauser 55
Micropilot FMR51, FMR52
FMR52 Ta
Antenna: Horn 50mm/2" P1 P2
Housing: GT18 (316 L) P3
Temperature unit: °C (°F)
Tp
P5 P4
A0019351
FMR52 Ta
Antenna: Horn 50mm/2" P1 P2
Housing: GT19 (Plastics PBT) P3
Temperature unit: °C (°F)
Tp
P5 P4
A0019351
56 Endress+Hauser
Micropilot FMR51, FMR52
FMR52 Ta
Antenna: Horn 50mm/2" P1 P2
Housing: GT20 (Alu, coated) P3
Temperature unit: °C (°F)
Tp
P5 P4
A0019351
FMR52 Ta
Antenna: Horn 80mm/2" P1 P2
Housing: GT18 (316 L) P3
Temperature unit: °C (°F)
Tp
P5 P4
A0019351
Endress+Hauser 57
Micropilot FMR51, FMR52
FMR52 Ta
Antenna: Horn 80mm/2" P1 P2
Housing: GT19 (Plastics PBT) P3
Temperature unit: °C (°F)
Tp
P5 P4
A0019351
FMR52 Ta
Antenna: Horn 80mm/2" P1 P2
Housing: GT20 (Alu, coated) P3
Temperature unit: °C (°F)
Tp
P5 P4
A0019351
58 Endress+Hauser
Micropilot FMR51, FMR52
Cleaning the antenna The antenna can get contaminated, depending on the application. The emission and reception of microwaves
can thus eventually be hindered. The degree of contamination leading to an error depends on the medium
and the reflectivity, mainly determined by the dielectric constant er.
If the medium tends to cause contamination and deposits, cleaning on a regular basis is recommended. Care
has to be taken not to damage the antenna in the process of a mechanical or hose-down cleaning. The
material compatibility has to be considered if cleaning agents are used! The maximum permitted
temperature at the flange should not be exceeded.
Electromagnetic compatibility Electromagnetic compatibility to all relevant requirements of the EN 61326- series and NAMUR
(EMC) recommendation EMC (NE21). For details see declaration of conformity. 7).
If only the analogue signal is used, unshielded interconnection lines are sufficient for the installation. In case
of using the digital signal (HART/ PA/ FF) use shielded interconnection lines. Use a shielded cable when
working with a digital communications signal.
Max. fluctuations during EMC- tests: < 0.5 % of the span. As an exception to this, the maximum
fluctuations may amount to 2 % of the span for devices with plastic housing and see-through lid (integrated
display and operating module SD02 or SD03) if strong electromagnetic interferences in the frequenency
range of 1 to 2 GHz are present.
6) This restriction is valid if the following options of the product structure have been selected at the same time: 030("Display, Operation") = C("SD02") or
E("SD03"); 040("Housing") = A("GT19").
7) Can be downloaded from www.endress.com.
Endress+Hauser 59
Micropilot FMR51, FMR52
Process
Process temperature range Sensor Seal 1) Process temperature range
Graphite, -40 ... 250°C / -40 ... 482°F –40 to +250 °C (–40 to 482 °F)
This range may be reduced by the selected process connection. The pressure rating (PN) specified on
the flanges refers to a reference temperature of 20 °C, for ASME flanges 100 °F. Pay attention to
pressure-temperature dependencies.
Please refer to the following standards for the pressure values permitted for higher temperatures:
• EN 1092-1: 2001 Tab. 18
With regard to their temperature stability properties, the materials 1.4435 and 1.4404 are grouped
under 13E0 in EN 1092-1 Tab. 18. The chemical composition of the two materials can be identical.
• ASME B 16.5a - 1998 Tab. 2-2.2 F316
• ASME B 16.5a - 1998 Tab. 2.3.8 N10276
• JIS B 2220
60 Endress+Hauser
Micropilot FMR51, FMR52
Mechanical construction
Dimensions Dimensions of the electronics housing
R100 98 (3.86)*
78 (3.07) 90 (3.54)
)
.07
(ø4
3.5
141.9 (5.59)
ø108.5 (ø4.27)
ø10
144 (5.67)
115.25 (4.54)
A0011666
R100
99.5 (3.92)*
78 (3.07) 90 (3.54)
7)
4.1
6 (ø
ø10
163 (6.42)
ø106 (ø4.17)
134.5 (5.3)
A0011346
R100
97 (3.82)*
78 (3.07) 90 (3.54)
7)
0
ø4.
(
3.5
ø111 (ø4.37) - 1°
141.5 (5.57)
ø10
144 (5.67)
ø108.5 (ø4.27)
117.1 (4.61)
A0011665
Endress+Hauser 61
Micropilot FMR51, FMR52
A B C D
55 55
(2.66)
(2.66)
67.5
67.5
(2.48)
63
R
100(3.94)
b
26 (1.02)
26 (1.02)
5 (0.2)
5 (0.2)
L
5 (0.2)
ød ød
øD
L
øA
ød mm (in)
A0017753
A Threaded connection
B Clamp adapter 2"/3"
C Flange version
D Threaded connection with antenna extension 100 mm (3.94 in)
R Reference point of the measurement
A B C D
121.4 (4.78)
115.4 (4.54)
55
(2.48)
63
R
26 (1.02)
100(3.94)
b
L
ød ød
5 (0.2)
øD
L
ød mm (in)
øD
øA
A0017755
62 Endress+Hauser
Micropilot FMR51, FMR52
(2.56)
65
R
b
3 (0.12)
L
ød
øD
140.1 (5.52)
B C
(2.48) 55
(2.66)
67.5
b
63
R
(2.09...17.8) (1.85)
47
26 (1.02)
b
L
53...453
ø27 (1.06)
ød
øD
L2
ød
øD mm (in)
A0017756
Horn antenna
Dimension 40 mm (1") 50 mm (2") 80 mm (3") 100 mm (4")
L 86 mm (3.39 in) 115 mm (4.53 in) 211 mm (8.31 in) 282 mm (11.1 in)
⌀d ⌀40 mm (1.57 in) ⌀48 mm (1.89 in) ⌀75 mm (2.95 in) ⌀95 mm (3.74 in)
L2 51 mm (2.01 in) 80 mm (3.15 in) 176 mm (6.93 in) 247 mm (9.72 in)
⌀d ⌀40 mm (1.57 in) ⌀48 mm (1.89 in) ⌀75 mm (2.95 in) ⌀95 mm (3.74 in)
b - - 30 mm (1.18 in) -
PN63
⌀D - - ⌀250 mm (9.84 in) -
Endress+Hauser 63
Micropilot FMR51, FMR52
b - - 36 mm (1.42 in) -
PN100
⌀D - - ⌀265 mm (10.4 in) -
b - - 44 mm (1.73 in) -
63 K
⌀D - - ⌀270 mm (10.6 in) -
b 19.1 mm (0.75 in) 23.9 mm (0.94 in) 23.9 mm (0.94 in) 25.4 mm (1 in)
150 lbs
⌀D ⌀152.4 mm (6 in) ⌀190.5 mm (7.5 in) ⌀228.6 mm (9 in) ⌀279.4 mm (11 in)
b 22.4 mm (0.88 in) 28.4 mm (1.12 in) 31.8 mm (1.25 in) 25.4 mm (1 in)
300 lbs
⌀D ⌀165.1 mm (6.5 in) ⌀209.5 mm (8.25 in) ⌀254 mm (10 in) ⌀279.4 mm (11 in)
64 Endress+Hauser
Micropilot FMR51, FMR52
A B C
92.6(3.65)
2.6 (0.1)
95 (3.74)
4 (0.16)
94(3.7)
5 (0.2)
b
R
ø48 (1.89) ø48 ø48 (1.89)
(0.54)
(0.54)
(0.54)
13.8
13.8
13.8
øa (1.89) øb øc
ød
D E F
119.6 (4.71)
121(4.76)
123 (4.84)
2.6 (0.1)
4 (0.16)
5 (0.2)
b
R
ø75 (2.95) ø75 ø75 (2.95)
28.6 (1.13)
28.6 (1.13)
28.6 (1.13)
øa (2.95) øb øc
ød
mm (in)
A0017748
⌀c PN16 ⌀102 mm (4.02 in) ⌀138 mm (5.43 in) ⌀158 mm (6.22 in) ⌀212 mm (8.35 in)
⌀d ⌀165 mm (6.5 in) ⌀200 mm (7.87 in) ⌀220 mm (8.66 in) ⌀285 mm (11.2 in)
Endress+Hauser 65
Micropilot FMR51, FMR52
b 19.1 mm (0.75 in) 23.9 mm (0.94 in) 23.9 mm (0.94 in) 25.4 mm (1 in)
⌀c 150 lbs ⌀92 mm (3.62 in) ⌀127 mm (5 in) ⌀158 mm (6.22 in) ⌀212 mm (8.35 in)
⌀d ⌀152.4 mm (6 in) ⌀190.5 mm (7.5 in) ⌀228.6 mm (9 in) ⌀279.4 mm (11 in)
⌀c 10 K ⌀96 mm (3.78 in) ⌀127 mm (5 in) ⌀151 mm (5.94 in) ⌀212 mm (8.35 in)
⌀d ⌀155 mm (6.1 in) ⌀185 mm (7.28 in) ⌀210 mm (8.27 in) ⌀280 mm (11 in)
Weight Housing
Part Weight
Materials Housing
2.1 1 2.2 5
4 3 9 8 7 6
A0013788
66 Endress+Hauser
Micropilot FMR51, FMR52
2.2 Cover of the terminal compartment 6 Dummy plug: nickel-plated brass (CuZn)
• Cover: PBT
• Cover seal: EPDM 7 Pressure relief stopper: nickel-plated brass (CuZn)
9 Identification
Nameplate: sticker
2.2 Cover of the terminal compartment 6 Dummy plug: nickel-plated brass (CuZn)
• Cover: AlSi10Mg(<0.1% Cu)
• Cover seal: EPDM 7 Pressure relief stopper: nickel-plated brass (CuZn)
Endress+Hauser 67
Micropilot FMR51, FMR52
FMR51
A B C D
7 7
1 7
3 3
2 2 2
E F G H
3 6 6 3
A0018961
Locking washer
Nordlock washer A4
(extension >100 mm, XT und HT
version)
68 Endress+Hauser
Micropilot FMR51, FMR52
Locking washer
FMR52
A B C
1 1 1
2 2 3
4 4 4
A0018951
A Dairy coupling
B Clamp adapter
C Flange version
4 Cladding PTFE
(in accordance with FDA 21 CFR 177.1550 and USP <88> Class
VI)
Endress+Hauser 69
Micropilot FMR51, FMR52
3.1
3.2
2.1 4
2.2
2.2 5.1
2.1 5.2
4
6
A0015473
70 Endress+Hauser
Micropilot FMR51, FMR52
Operability
Operating concept Operator-oriented menu structure for user-specific tasks
• Commissioning
• Operation
• Diagnostics
• Expert level
Quick and safe commissioning
• Guided menus ("Make-it-run" wizards) for applications
• Menu guidance with brief explanations of the individual parameter functions
Reliable operation
• Local operation in different languages (see product structure, feature "Additional Operation Language")
• Standardized operation at the device and in the operating tools
• Data storage device (HistoROM) for process and measuring device data with event logbook available at all
times - even if electronics modules are replaced
Efficient diagnostics increase measurement reliability
• Remedy information is integrated in plain text
• Diverse simulation options and line recorder functions
Local operation Order code for "Display; Operation", option C "SD02" Order code for "Display; Operation", option E "SD03"
(in preparation)
1 1
– –
+ +
E E
A0015544 A0015546
Display elements
• 4-line display
• In the case of order code for "Display; Operation", option E: white background lighting; switches to red in
event of device errors (in preparation)
• Format for displaying measured variables and status variables can be individually configured
• Permitted ambient temperature for the display: –20 to +60 °C (–4 to +140 °F)
The readability of the display may be impaired at temperatures outside the temperature range.
Operating elements
• In the case of order code "Display; Operation", Option C: local operation with 3 push buttons ( , , ) E
• In the case of order code for "Display; Operation", option E: external operation via touch control; 3 optical
keys: , , (in preparation)
E
Endress+Hauser 71
Micropilot FMR51, FMR52
A0013137
6 8
3
2
1 4 5 7
A0013764
72 Endress+Hauser
Micropilot FMR51, FMR52
2 3
PROFIBUS DP
ENDRESS + HAUSER
PROFIBUS PA
T
4 4 4
A0015775
1 Segment coupler
2 Computer with Profiboard/Proficard and operating tool (e.g. FieldCare)
3 PLC (Progrommable Logic Controller)
4 Transmitter
5 Additional functions (valves etc.)
Endress+Hauser 73
Micropilot FMR51, FMR52
IN
BT
FF-HSE
1
FF-H1 SB 2
PS BT
LD 4
3
BT ENDRESS + HAUSER
– +
%
PS
FF-H1
BT
1
2
A0017188
74 Endress+Hauser
Micropilot FMR51, FMR52
3 –
+
E
2 1
A0014019
1 Service interface (CDI) of the measuring device (= Endress+Hauser Common Data Interface)
2 Commubox FXA291
3 Computer with "FieldCare" operating tool
Endress+Hauser 75
Micropilot FMR51, FMR52
Integration in tank gauging The Endress+Hauser Tank Side Monitor NRF590 provides integrated communications for sites with multiple
system tanks, each with one or more sensors on the tank, such as radar, spot or average temperature, capacitive
probe for water detection and/or pressure sensors. Multiple protocols out of the Tank Side Monitor
guarantee connectivity to nearly any of the existing industry standard tank gauging protocols. Optional
connectivity of analog 4...20 mA sensors, digital I/O and analog output simplify full tank sensor integration.
Use of the proven concept of the intrinsically safe HART bus for all on-tank sensors yields extremely low
wiring costs, while at the same time providing maximum safety, reliability and data availability.
1 2 3
4 5
8 NXA820
16...253 VAC
A0017982
76 Endress+Hauser
Micropilot FMR51, FMR52
1 1 2
ENDRESS+HAUSER ENDRESS+HAUSER
RN 221N RN 221N
FXN 520
20...45 VDC
-
.
A0011278
The number of instruments which can be connected in mutidrop mode can be calculated by the
"FieldNetCalc" program. A description of this program can be found in Technical Information TI 400F
(Multidrop Conncector FXN520). The program is available form your Endress+Hauser sales
organisation or in the internet at: www.de.endress.com/Download (text search = "Fieldnetcalc").
Endress+Hauser 77
Micropilot FMR51, FMR52
C-Tick symbol The measuring system meets the EMC requirements of the "Australian Communications and Media
Authority (ACMA)".
Ex approval • ATEX
• IEC Ex
• CSA (in Vorbereitung)
• FM (in Vorbereitung)
• NEPSI (in Vorbereitung)
• TIIS (in Vorbereitung)
Additional safety instructions must be observed for applications in hazardous areas. They are contained in
the separate "Safety Instructions" (XA) document, which is included in the scope of delivery. Reference is
made to the XA on the nameplate of the device.
Details on the available certificats as well as the associated XAs can be found in the Associated
documentation chapter in the Safety instructions section: (® ä 87).
Dual seal according to The devices Micropilot FMR5x have been designed according to ANSI/ISA 12.27.01 as dual seal devices,
ANSI/ISA 12.27.01 allowing the user to waive the use and save the cost of installing external secondary process seals in the
conduit as required by the process sealing sections of ANSI/NFPA 70 (NEC) and CSA 22.1 (CEC). These
instruments comply with the North-American installation practice and provide a very safe and cost-saving
installation for pressurized applications with hazardous fluids.
Further information can be found in the control drawings of the relevant devices.
Functional Safety Used for level monitoring (MIN, MAX, range) up to SIL 3 (homogeneous or inhomogeneous redundancy),
independently assessed by TÜV Rhineland as per IEC 61508. Other information see documentation
SD01087F: "Functional Safety Manual".
Sanitary compatibility FMR52 with flange cladding made of PTFE conforms to FDA 21 CFR 177.1550 and USP <88> Class VI
3A and EHEDG approval with Tri-Clamp process connection.
The leak-tight connections can be cleaned with the cleaning methods usually used in this industry
without leaving residues.
The 316L housing (GT18), option B in the order attribute 40, is not suitable for applications which
need a 3A approval.
AD2000 The pressure retaining material 316L (1.4435/1.4404) corresponds to AD2000 - W2/W10.
Pressure Equipment Directive The Micropilot is not subject to the scope of the Pressure Equipment Directive 97/23/EC, as it does not
have a pressure-bearing housing according to article 1, section 2.1.4 of the directive.
Radio standard The devices Micropilot FMR50, FMR51, FMR52, FMR56 and FMR57 are conform with the LPR (Level
EN302729-1/2 Probing Radar) standard EN302729-1/2. The devices are allowed to be used inside or outside of closed bins
or tanks in countries of th EU and the EFTA. Precondition is that the country itself already has implemented
the directive.
At present, the following countries have already implemented the directive:
Belgium, Bulgaria, Germany, Denmark, Estonia, France, Greece, Great Britain, Ireland, Iceland, Italy,
Liechtenstein, Lithuania, Latvia, Malta, Netherland, Norway, Austria, Poland, Romania, Sweden,
Switzerland, Slovakia, Spain, Czech Republic and Cyprus.
All countries not mentioned above are at present in the implementation phase.
78 Endress+Hauser
Micropilot FMR51, FMR52
For the use of the devices outside of closed bins or tanks, the following has to be observed:
1. The installation has to be done by trained personnel.
2. The antenna of the device has to be mounted on a fixed place and vertically to the bottom.
3. The mounting place has to be in a distance of at least 4 km to the mentioned astronomical stations or
an appropriate permission has to be issued by the national authority. If the device is mounted at a
distance of 4 to 40 km from the stations mentioned, the maximum mounting height is restricted to
15 m (49 ft).
Astronomical stations
Country Name of the station Geographical latitude Geographical longitude
Radio standard The devices Micropilot FMR50, FMR51, FMR52, FMR53, FMR54, FMR56 and FMR57 are conform with
EN302372-1/2 the TLPR (Tanks Level Probing Radar) standard EN302372-1/2 and can always be used in closed tanks or
bins. For installation, points a to f in Annex B of EN302372-1 have to be taken into account.
FCC / Industry Canada This device complies with Part 15 of the FCC rules. Operation is subject to the following two conditions: (1)
This device may not cause harmful interference, and (2) this device must accept any interference received,
including interference that may cause undesired operation.
Canada CNR-Gen Section 7.1.3
This device complies with Industry Canada licence-exempt RSS standard(s). Operation is subject to the
following two conditions: (1) This device may not interference, and (2) this device must accept any
interference, including interference that may cause undesired operation of the device.
Endress+Hauser 79
Micropilot FMR51, FMR52
Le présent appareil est conforme aux CNR d'Industrie Canada applicables aux appareils radio exempts de
licence. L'exploitation est autorisée aux deux conditions suivantes : (1) l'appareil ne doit pas produire de
brouillage, et (2) l'utilisateur de l'appareil doit accepter tout brouillage radioélectrique subi, même si le
brouillage est susceptible d'en compromettre le fonctionnement.
[Any] changes or modifications not expressly approved by the party responsible for compliance could void the
user's authority to operate the equipment.
Track record FMR5x is the upgrade model of the corresponding FMR2xx series.
80 Endress+Hauser
Micropilot FMR51, FMR52
Ordering information
Ordering information Detailed ordering information is available from the following sources:
• In the Product Configurator on the Endress+Hauser website: www.endress.com ® Select country ®
Instruments ® Select device ® Product page function: Configure this product
• From your Endress+Hauser Sales Center: www.endress.com/worldwide
Product Configurator - the tool for individual product configuration
• Up-to-the-minute configuration data
• Depending on the device: Direct input of measuring point-specific information such as measuring
range or operating language
• Automatic verification of exclusion criteria
• Automatic creation of the order code and its breakdown in PDF or Excel output format
• Ability to order directly in the Endress+Hauser Online Shop
5-point linearity protocol (in The following notes must be taken into account if option F4 ("5 point linearity protocol") has been
preparation) selected in feature 550 ("Calibration").
The five points of the linearity protocol are evenly distributetd across the measuring range (0% to 100%). In
order to define the measuring range, Empty calibration (E) and Full calibration (F) have to be specified 8).
The following restrictions have to be taken into account when defining E and F:
R
A
200 (7.87)
E
F
mm (in)
A0017983
Minimum distance between reference point (R) and Minimum span Maximum value for "empty
100% level calibration"
The selected values of Empty calibration and Full calibration are only used to record the linearity
protocol and are reset to their antenna specific default values thereafter. If values different from the
default are required, they must be ordered as a customized parametrization (® ä 82).
8) If E and F are not specified, antenna dependent default values will be used instead.
Endress+Hauser 81
Micropilot FMR51, FMR52
Customized parametrization If the option IJ "Customized parametrization HART", IK "Customized parametrization PA" or IL "Customized
parametrization FF" has been selected in feature 570 "Service", customer specific presettings can be selected
for the following parameters:
Setup ® Adv. Setup ® Current output 1/2 ® Failure mode HART • Min
• Max
• Last valid value
82 Endress+Hauser
Micropilot FMR51, FMR52
Accessories
Device-specific
Accessory accessories
Description
222 (8.74)
mm (in)
A0015466
35°
65
)
(6.1
°
155
mm (in)
A0015472
The weather protection cover can be ordered together with the device (product structure, feature 620 "Accessory Enclosed",
option PB "Weather Protection Cover").
Alternatively, it can be separately ordered as an accessory; order code 71132889.
Endress+Hauser 83
Micropilot FMR51, FMR52
Accessory Description
A0019128
• Material:
– Plastics PBT
– 316L (in preparation)
• Suitable for the display modules:
– SD02 (push buttons)
– SD03 (touch control) (in preparation)
• Connection cable:
– Cable with M12 plug; supplied with the FHX50; up to 30 m (98 ft)
– Customer supplied standard cable; up to 60 m (196 ft)
• If the remote display is to be used, the Micropilot must be ordered in the version "Prepared for display FHX50" (feature
030, option L or M). For the FHX50, on the other hand, the option A: "Prepared for display FHX50" has to be selected in
feature 050: "Option Measurement Device".
• If a Micropilot has not been ordered in the version "Prepared for display FHX50", but is nevertheless to be equipped with
an FHX50, it is essential to select the option B: "Not prepared for display FHX50" in feature 050: "Option Measurement
Device" of the FHX50. In this case, a retrofit kit, needed to prepare the Micropilot for the remote display, is supplied
together with the FHX50.
For details refer to the document SD01007F.
Accessory Description
ø96 (3.78)
84 Endress+Hauser
Micropilot FMR51, FMR52
Accessory Description
ød
³ DN150
ø116 (4.57)
450 (17.72)
mm (in)
A0019144
Accessory Description
Commubox FXA291 Connects Endress+Hauser field devices with CDI interface (= Endress+Hauser Common
Data Interface) to the USB interface of a computer.
For details refer to Technical Information TI00405C
Accessory Description
HART Loop Converter Evaluates the dynamic HART variables and converts them to analog current signals or
HMX50 limit values.
For details refer to Technical Information TI00429F and Operating Instructions
BA00371F
Accessory Description
Endress+Hauser 85
Micropilot FMR51, FMR52
Accessory Description
Fieldgate FXA320 Gateway for remote monitoring of connected 4-20mA measuring devices via web
browser.
For details refer to Technical Information TI00025S and Operating Instructions
BA00053S
Accessory Description
Fieldgate FXA520 Gateway for remote diagnosis and parametrization of connected HART measuring devices
via web browser.
For details refer to Technical Information TI00025S and Operating Instructions
BA00051S
Accessory Description
Field Xpert SFX100 Compact, flexible and robust industry handheld terminal for remote parametrization and
measured value inspection via the HART output or via FOUNDATION Fieldbus .
For details refer to Operating Instructions BA00060S
Graphic Data Manager The graphic data manager Memograph M provides information on all the relevant process
Memograph M variables. Measured values are recorded correctly, limit values are monitored and
measuring points analyzed. The data are stored in the 256 MB internal memory and also
on an SD card or USB stick.
For details refer to Technical Information TI00133R and Operating Instructions
BA00247R
RN221N Active barrier with power supply for safe separation of 4 to 20 mA current circuits.
Provides bi-directional HART transmission.
For details refer to Technical Information TI00073R and Operating Instructions
BA00202R
RNS221 Transmitter supply for 2-wire sensors or transmitters exclusively for non-Ex areas.
Provides bi-directional communication using the HART communication sockets.
For details refer to Technical Information TI00081R and Operating Instructions
KA00110R
86 Endress+Hauser
Micropilot FMR51, FMR52
Documentation
The following document types are available:
• On the CD supplied with the device
• In the Download Area of the Endress+Hauser Internet site: www.endress.com ® Download
Safety Instructions (XA) Depending on the approval, the following Safety Instructions (XA) are supplied with the device. They are an
integral part of the Operating Instructions.
Feature 010 Approval Available for Safety Instructions HART Safety Instructions
PROFIBUS
FOUNDATION Fieldbus
BD ATEX: II 1/2/3 G Ex ic [ia Ga] IIC T6-T1 Ga/Gb/Gc • FMR51 XA00678F XA00686F
• FMR52
BL ATEX: II 1/2/3 G Ex nA [ia Ga] IIC T6-T1 Ga/Gb/Gc • FMR51 XA00678F XA00686F
• FMR52
Endress+Hauser 87
Micropilot FMR51, FMR52
Feature 010 Approval Available for Safety Instructions HART Safety Instructions
PROFIBUS
FOUNDATION Fieldbus
For certified devices the relevant Safety Instructions (XA) are indicated on the nameplate.
If the device is prepared for the remote display FHX50 (product structure: feature 030: Display, Operation",
option L or M), the Ex marking of some certificates changes according to the following table 9):
Registered trademarks
HARTÒ
Registered trademark of the HART Communication Foundation, Austin, USA
9) The marking of certificates not mentioned in this table are not affected by the FHX50.
88 Endress+Hauser
Micropilot FMR51, FMR52
PROFIBUSÒ
Registered trademark of the PROFIBUS User Organization, Karlsruhe, Germany
FOUNDATIONTM Fieldbus
Registered trademark of the Fieldbus Foundation, Austin, Texas, USA
KALREZÒ, VITONÒ
Registered trademark of DuPont Performance Elastomers L.L.C., Wilmington, USA
TEFLONÒ
Registered trademark of E.I. DuPont de Nemours & Co., Wilmington, USA
TRI CLAMPÒ
Registered trademark of Alfa Laval Inc., Kenosha, USA
Patents
This product may be protected by at least one of the following patents.
Further patents are pending.
US Patents EP Patents
6.140.940 -
- 882 955
6.606.904 -
6.640.628 -
- 1 389 337
6.779.397 -
7.201.050 -
7.412.337 -
7.552.634 -
7.730.760 -
7.819.002 -
- 1 774 616
7.966.141 -
8.040.274 -
8.049.371 -
Endress+Hauser 89
Instruments International
Endress+Hauser
Instruments International AG
Kaegenstrasse 2
4153 Reinach
Switzerland
Tel.+41 61 715 81 00
Fax+41 61 715 25 00
www.endress.com
info@ii.endress.com
TI01040F/00/EN/01.12
71162672
CCS/EH-COSIMA ProMoDo