DS350GM Service - SkyAzul
DS350GM Service - SkyAzul
DS350GM Service - SkyAzul
SERVICE MANUAL
SkyAzúl will not be liable for errors contained in this manual or for incidental or consequential
damages in connection with the furnishing, performance, or use of this manual. This document
contains proprietary information, which is protected by copyright, and all rights are reserved.
No part of this document may be photocopied, reproduced, or translated to another language without
the prior written consent of SkyAzúl.
SkyAzúl reserves proprietary rights to all drawings, photos and the data contained therein. The
drawings, photos and data are confidential and cannot be used or reproduced without the written
consent of SkyAzúl. The drawings and/or photos are subject to technical modification without prior
notice.
SkyAzúl, Inc.
200 W. Main Street, Suite, 2A
Middletown, MD 21769
Fax 301-371-0029
info@skyazul.com
TABLE OF CONTENTS
1 GENERAL INFORMATION ................................................................................. 1
2 WARNINGS .................................................................................................... 2
3 FLOWCHARTS ................................................................................................ 3
3.1 GENERAL FLOWCHART...............................................................................3
3.2 ERROR CODE DISPLAY ...............................................................................4
3.3 LEVER LOCKOUT ACTIVATED ...................................................................13
3.4 BROKEN LENGTH CABLE...........................................................................14
3.5 NO DISPLAY ............................................................................................15
3.6 ANTI-TWO BLOCK PROBLEM .....................................................................17
3.7 LENGTH READING PROBLEM .....................................................................20
3.8 ANGLE READING PROBLEM .......................................................................23
3.9 LOAD READING PROBLEM.........................................................................25
3.10 BAD DATA TRANSFER BETWEEN CONSOLE & CENTRAL UNIT OR
INTERFERENCE PROBLEM..........................................................................26
4 DRAWINGS .................................................................................................. 29
4.1 DRAWING 1. ELECTRICAL WIRING FOR CENTRAL UNIT TO PRESSURE
TRANSDUCERS AND CRANE .....................................................................29
4.2 DRAWING 2. ELECTRICAL WIRING FOR CENTRAL UNIT TO CONSOLE...........30
4.3 DRAWING 3. ELECTRICAL WIRING FOR CENTRAL UNIT TO CABLE
REEL/ANTI-TWO BLOCK ............................................................................31
4.4 DRAWING 4. CENTRAL UNIT - PARTS LIST.................................................32
4.5 DRAWING 6. CABLE REEL - PARTS LIST .....................................................36
4.6 DRAWING 7. CENTRAL UNIT MAIN BOARD LAYOUT ...................................38
4.7 DRAWING 8. CONSOLE CONNECTION BOARD ............................................39
4.8 DRAWING 9. CENTRAL UNIT ANALOG INPUT MODULE ...............................40
5 PROCEDURES ............................................................................................... 41
5.1 PROCEDURE 1. STRAIN RELIEF INSTALLATION ...........................................41
5.2 PROCEDURE 2. EPROM LOCATION AND INSTALLATION ..............................42
5.3 PROCEDURE 3. MAIN BOARD REPLACEMENT .............................................43
5.4 PROCEDURE 4. PRESSURE TRANSDUCER ZERO ADJUSTMENT ....................44
5.4.1 USING GRAPHIC CONSOLE FOR ZERO-SETTING OF PRESSURE TRANSDUCER
& FORCE INPUTS ............................................................................ 44
5.5 PROCEDURE 5. LENGTH AND ANGLE SENSOR ADJUSTMENT ......................45
6 THEORY ....................................................................................................... 46
6.1 THEORY 1. OPERATION OF BOOM LENGTH SENSOR ...................................46
Measuring current:.............................................................................................46
Measuring voltage: ............................................................................................46
6.2 THEORY 2. OPERATION OF PISTON SIDE LOAD SENSOR .............................47
6.3 THEORY 3. OPERATION OF ROD SIDE LOAD SENSOR..................................48
6.4 THEORY 4. OPERATION OF ANGLE SENSOR ...............................................49
1 GENERAL INFORMATION
REFERENCE:
For system operation, refer to the operator’s manual for the console. This may differ from crane
manufacturer and model.
Section 3.1 is a general flow chart that directs you to detailed flow charts and sections.
Section 3.2 provides a list of error codes, error, cause, and possible action for the error.
Sections 3.3 – 3.11 provide detailed flow charts to define and correct the root cause.
Section 4 provides drawings that will be referenced for troubleshooting.
Section 5 provides procedures that will be referenced for troubleshooting.
Section 6 provides drawings for the theory of operation of all the different sensing devices used
in the DS350G Modular System. Use these reference drawings to better understand the
operation of the system.
2 WARNINGS
The LMI is an operational aid that warns a crane operator of approaching overload conditions
and overhoist conditions that could cause damage to equipment and personnel. Therefore, the
device is not, and shall not be, a substitute for good operator judgment, experience and use of
accepted safe crane operating procedures.
The responsibility for the safe crane operation shall remain with the crane operator who shall
ensure that all warnings and instructions supplied are fully understood and observed.
Prior to operating the crane, the operator must carefully and thoroughly read and understand
the information in the crane’s operating manuals to ensure that the operator knows the
operation and limitations of indicator and crane.
The PAT Load Moment Indicator (LMI) DS 350 Modular has been designed to provide the crane
operator with the essential information required to operate the machine within the designed
parameters. Using different sensing devices, the DS 350 Modular LMI monitors various crane
functions and provides the operator with a continuous display of the crane’s capacity. The
display continually changes as the crane moves through the motions needed to make a lift.
If non-permitted conditions are approached, the DS 350 LMI will warn the operator by sounding
an audible alarm and lighting a warning light. In addition the LMI system has the capability to
provide a signal to the solenoids and thereby locking out those functions that may aggravate the
crane’s condition.
3 FLOWCHARTS
3.1 GENERAL FLOWCHART
This section explains how to handle a problem that may arise with the PAT DS 350 Modular LMI.
The procedures are given in flowchart format for the following sections. Start with the general
flowchart below that will guide you to one of the detailed flowcharts shown in this section. The
drawings and procedures that are referenced in these sections can be found in Sections 4 and 5.
What’s Wrong?
PROBLEM: Error code displayed. Lever lockout activated. Warning lights on.
E89 Change of the The operating mode switch Lower the load and set the
operating code during in the console was used operating mode switch correctly
lifting a load. during lifting a load. to the code assigned to the
actual operating mode of the
crane.
Note:
If an error message is displayed which is not contained in above list, please contact the PAT service
department.
PROBLEM: The lever lockout system of the crane is activated. Crane movements “hoist up”, “telescope
out”, and “boom down” are stopped. Crane is not in overload or two-block condition.
Start
Use the key switch and the LMI by-pass button on the console to
override the LMI. Refer to the Operator’s Handbook for LMI override
instructions (pages12 and 13).
Corrected YES
NO
NO YES
3.5 NO DISPLAY
PROBLEM: Blank console display with no warning light shown. All crane moments have
been stopped.
START
YES
Measure voltage on the main board terminal strip between X1:1 (+12/24V) and X1:2
(ground). This is an input voltage from the crane.
Refer to Drawing 1 in Section 4.
YES
Measure voltage on the main board between X1:3 (+12/24V) and X1:4 (ground).
This is an output voltage to the console.
Refer to Drawing 1 in Section 4.
YES
NEXT PAGE
PREVIOUS PAGE
Measure voltage in the console between X1:1 (+12/24V) and X1:2 (ground).
Refer to Drawing 2 & 8 in Section 4.
YES
YES
END
START
YES
YES
Turn power off or disconnect wire from connection board X1:31 in central unit. Remove the
bypass plug and measure the resistance at the boom nose box between terminals 1 and 6
with a ohmmeter. This checks the function of the Anti-Two Block switch.
Switch closed = 0Ohms (weight installed)
Switch open => 1 Megaohm (weight removed)
Pug the bypass plug into the boom nose box.
Refer to Drawing 3 in Section 4.
Yes
Next Page
PREVIOUS PAGE
Ensure the byass plug is plugged into the boom nose box. Measure the A2B signal in the cable
reel between X1:Brown and X2:Red wires on the slip ring with an ohmmeter.
Switch closed =4700 ±500Ohms
Switch open => 1 Megaohm
Reconnected slip ring wires.
Refer to Drawing 2 & 6 Section 4.
Fault in wiring between boom nose box and cable reel. Check
for damaged length cable and wiring.
Correct? No
Refer to Drawing 3 Section 4.
If broken length cable, Refer to Section 3.4.
Measure the A2B signal in the cable reel between terminal 7 and 8 with an ohmmeter.
Switch closed =4700 ±500Ohms
Switch open => 1 Megaohm
Reconnected slip ring wires.
Refer to Drawing 3 Section 4.
Measure the A2B signal in the boom base box between terminals 5 and 6
with an ohmmeter.
Switch closed =4700 ±500Ohms
Switch open => 1 Megaohm
Reconnected slip ring wires.
Refer to Drawing 3 Section 4.
NEXT PAGE
PREVIOUS PAGE
Turn system power off. Check Anti-Two-Block signal in central unit with ohmmeter
measure between X1:31 and X1:32.
Anti-Two-Block switch closed = 4700 Ohms ±50 0Ohms
Anti-Two-Block switch open => 1 Megaohm.
Refer to Drawing 3 in Section 4.
YES
Disconnect X1:31 and X1:32. Check main board function by installing a temporary
resistor, 4700 Ohms between X1-31 and X1-32 in central unit. With resistor connected
alarm should be inactive.
Refer to Drawing 3 in Section 4.
End
PROBLEM: Length displayed incorrect. Crane is not in “out of load chart” condition.
START
Check mechanical adjustment of length potentiometer in cable reel. With boom fully retracted, reset
potentiometer by turning it slowly counter-clockwise until it reaches a soft stop.
Refer to Drawing 6 in Section 4 and Adjustment Procedure 5 in Section 5.
YES
Check out clutch in big gear wheel of length transducer. Extend and retract boom
to ensure that clutch is not slipping on potentiometer axle.
Refer to Drawing 6 in Section 4 and Adjustment Procedure 5 in Section 5.
NEXT PAGE
PREVIOUS PAGE
Measure supply to length transducer in cable reel between terminal 1 (ground) and 3 (+12/24v)
Refer to Drawing 3 in Section 4.
Correct? NO Faulty wiring between central unit and length transducer. Check wiring
Measure signal from length transducer in cable reel. The return signal is a current output and must
be measured in series. Set Voltmeter to measure amps. Remove Wire #2 from X1:2 in the cable reel
and connect one voltmeter lead to wire #2 and the other lead to X1:2. The measurement should be
between 4-20ma. 4ma with the boom fully retracted and the length potentiometer set fully counter-
clockwise to a soft stop. 20ma with the length potentiometer turned completely clockwise 10 turns to
the soft stop. Refer to Drawings 3 & 6 in Section 4.
Replace length potentiometer assembly. Remove slip ring body from shaft and
remove gear wheel from potentiometer axle. Unscrew mounting plate and
remove potentiometer assembly from mounting plate. Remove assembly wires
Correct? NO from terminal block. Connect new assembly to terminal block. Reinstall
mounting plate, gear wheel and slip rings. With boom fully retracted, reset
potentiometer by turning it slowly counter-clockwise until it reaches a soft stop.
Refer to Drawing 6 in Section 4 and adjustment Procedure 5 in Section 5.
YES
Measure signal from length transducer in central unit. The return signal is a current output and must
be measured in series. Set Voltmeter to measure amps. Remove Wire #2 from X1:27 in the central
unit and connect one voltmeter lead to wire #2 and the other lead to X1:27. The measurement
should be between 4-20ma. 4ma with the boom fully retracted and the length potentiometer set fully
counter-clockwise to a soft stop. 20ma with the length potentiometer turned completely clockwise 10
turns to the soft stop. Refer to Drawing 3 & 6 in Section 4.
YES
NEXT PAGE
PREVIOUS PAGE
Measure length signal of amplified output on analog input module between test
point MP0 and X1:3. The measurement should be between 0.5-4.5v.
0.5v(500mv) with the boom fully retracted and the length potentiometer set fully
counter-clockwise to a soft stop OR 4.5v with the length potentiometer turned
completely clockwise 10 turns to the soft stop.
Refer to Drawing 9 in Section 4.
YES
END
PROBLEM: Angle displayed incorrect. Crane is not in “out of load chart” condition.
START
YES
Place the boom at 0°. Measure the angle sensor supply voltage in the central unit
between terminals X1:26 (+12/24v) and X1:28 (ground).
Refer to Drawing 3 in Section 4.
YES
Open cable reel cover. Measure the angle sensor supply voltage in the
cable reel between terminals X1:1 (+12/24v) and X1:3 (ground).
Refer to Drawing 3 in Section 4.
NEXT PAGE
PREVIOUS PAGE
Measure signal from angle transducer in cable reel. The return signal is a current
output and must be measured in series. Set Voltmeter to measure amps. Remove
Wire #4 from X1:4 in the cable reel and connect one voltmeter lead to wire #4 and
the other lead to X1:4. The measurement should be between 4-20ma. 20ma with the
boom at 0° or 4ma with the boom a 90° .
Refer to Drawing 3 & 6 in Section 4.
YES
Measure signal from angle transducer in central unit. The return signal is a current
output and must be measured in series. Set Voltmeter to measure amps. Remove
Wire #4 from X1:4 in the central unit and connect one voltmeter lead to wire #4 and
the other lead to X1:4. The measurement should be between 4-20ma. 20ma with the
boom at 0° or 4ma with the boom at 90° .
Refer to Drawing 3 & 6 in Section 4.
YES
Measure angle signal analog input module between test point MP0(AGND) and X1:4
(ang sig). The measurement should be between 0.5-4.5v. 0.5v(500mv) with the
boom at 0° or 4.5v with the boom at 90° .
Refer to Drawing 9 in Section 4.
END
Reset length potentiometer. With fully retracted boom, turn potentiometer axle
Correct? NO
counter-clockwise until it stops . Refer to Section 3.7.
YES
YES
Check power supply to pressure transducers (piston and rod side). Check each transducer by
unpluging the transducer cable from transducer. Measure voltage at the cable connection
between A (+12/24v) and C (ground) at each connector.
Refer to Drawing 1 in Section 4.
YES
Fault in pressure transducer cable.
Correct? YES
Refer to Drawing 1 in Section 4.
NEXT PAGE
NO
Main board defective. Replace main board.
Refer to Drawing 4 in Section 4 and Replacement
Procedure 3 in Section 5.
3.10 BAD DATA TRANSFER BETWEEN CONSOLE & CENTRAL UNIT OR INTERFERENCE
PROBLEM
PREVIOUS PAGE
Measure signal from pressure transducers in central unit. The return signal is a current output and must
be measured in series. Set Voltmeter to measure amps.
Piston Side, remove Wire #2 from X1:21 in the central unit and connect one ammeter lead to wire #2
and the other lead to X1:21. The measurement should be between 4-20ma (4ma when there is no
pressure in the hydraulic lines; 0 psi).
Rod Side, remove Wire #2 from X1:24 in the central unit and connect one voltmeter lead to wire #2
and the other lead to X1:24. The measurement should be between 4-20ma
(4ma when there is no pressure in the hydraulic lines; 0 psi).
Refer to Drawing 1 in Section 4.
No Fault in cable
YES
Measure pressure transducer signals on the analog input module between test points:
Piston Side, MP0 (ground) and X1:1 .
Rod Side, MP0 (ground) and X1:2.
The measurements should be between 0.5-4.5v (0.5v(500mv) at 0psi to 4.5v at 4410psi).
Refer to Drawing 4 & 9 in Section 4.
END
START
ON
Make sure that the eprom's are correct and plugged into the Eprom Module on
the main board.
Refer to Procedure 2 in Section 5.
YES OFF
Measure process voltage on the Main Board in the central unit between
MP42 (+5v) and MP0 (ground). Refer to Drawing 4 & 7 in Section 4.
YES
NEXT PAGE
PREVIOUS PAGE
YES
YES
Find out which component of the crane electric is spiking out (e.g. dump valve, outrigger
relay). Install a diode or resistor across terminals of spiking component. Diode type
such as 1N4001 can be used (watch + and - connection for diode).
Refer to Crane Electrical Diagrams.
END
4 DRAWINGS
4.1 DRAWING 1. ELECTRICAL WIRING FOR CENTRAL UNIT TO PRESSURE
TRANSDUCERS AND CRANE
9
10
12 13 14
2 11
17
15
2
16
10
8
4 3 5 1
2 4
5
11 6
3
1
10
7
BOARD P/N
MP24 024-352-300-001
MP1 = KGND
MP4 = +5V
MP8 = +9V
MP9 = +6V
MP24 -= +BATT
MP25 -= +UBS console,
sensors, DI’s
MP26 -= GND
MP29 -= +5V hand
MP26 terminal
MP4
MP9 LED’S
H08 - LOAD
MP8
H11 H09 - A2B
DI1 H10 - MAIN IN/OUT
THRU H11 - POWER
DI6 H12 - TxD
H8 H10
H12
7776
H9 K10
69 68
36 35 67 66
34 33 65 64
32 31
30 29 62 61
28 27 60 59
26 2 5 8 57
5 24
23 2 54 53
2 21 52 51
20 19
18 17
16 15
14 13
12 11 1
MP1
10 9
87
654 MP25
3
21
X1
MP5
+5V
MP2
+7V MP3 MP4
-24V +24V
J5
MP6
J4
MP7 4
MP0 J3
GND
1
X5
MP1
+UB
8
J2 7
6
J1 5
4
3
2
1
X1
MP1 = AGND
MP8 = +5V
MP1-7 = Input channels 1-7 0.5V/4mA…2.5V/20mA
MP14 = +13V REF02
MP16 -= HESIN input voltage
MP17 = app 5.4V clamp for inputs
5 PROCEDURES
5.1 PROCEDURE 1. STRAIN RELIEF INSTALLATION
SYSTEM
SY
ST
EM
DATA
DA
TA
TL
K
TLK
NOTE: Use care when lifting the CPU module board and analog input module from the main
board because these boards have pins on the bottom side which insert into the main
board.
3. Remove CPU module board by taking out the 4 small Philips screws holding it in place.
4. Remove analog input module board by taking out the 6 small Philips screws holding it in
place.
5. Remove the relay from the main board, item 7 on Drawing 4 in Section 4.4.
6. Mark all connection wires before removing, to identify location for reconnecting. Disconnect
all X1 terminal wires from the main board.
7. Remove the 14 large Philips screws holding the main board in place.
8. Take notice of the orientation of the main board in the central unit. Remove main board and
place in the packing material that the replacement main board came in.
9. Carefully insert the new main board in place. Refer to Drawing 4 in Section 4.4 for location.
10. Insert the 14 Philips mounting screws, be sure to attach the ground wire to the KGND screw
in the lower left corner. Refer to Drawing 4.
11. Insert analog input module board by lining up the pins into the sockets X16 and X17 and the
6 screw holes.
12. Insert the 6 small Philips screws and washers.
13. Insert CPU module board by lining up the pins into the sockets X11 and X12 and the 4 screw
holes.
14. Insert the 4 small Philips screws and washers.
15. Insert the relay on to the main board, item 7 on Drawing 4.
16. Connect the X1 terminal wires to the main board. Refer to Drawings 1, 2 and 3.
17. Inspect the gasket for nicks, cuts, or damages. Refer to 031-300-340-003 DS 350 Central
Unit Gasket Recommendations, Revision - and 031-300-340-002 Central Unit Cover
Installation and Tightening Procedure, Revision A.
The display shows which transducer (piston-side, rod-side or force) is being zeroed and a
horizontal dial marks the present pressure (or force) difference in %. By pressing the + key, the
input pressure (or force) is adjusted upwards, and by pressing the minus (-)key, the input value is
adjusted downwards. When the plus (+) and minus (-) keys are pressed simultaneously, the
zero setting occurs automatically. Manual adjustments may be preformed using + or -.
The return key toggles between the piston-side, the rod-side, and the force zero-setting.
When the operator is finished, pressing the EXC or INFO key returns the console display to
normal.
6 THEORY
6.1 THEORY 1. OPERATION OF BOOM LENGTH SENSOR
The system sensors provide a 4 to 20mA output; however, due
to a fixed resistor circuit in the central unit, the input signal can
be measured using ammeter (current) or voltmeter (voltage).
The input signal operating window is 4 to 20mA, measured in
series at the analog input terminal OR 1.1 to 5.5V, measured in
parallel between the analog input and ground (GND) terminals.
At 4mA the voltage is 1.1V and at 20mA the voltage is 5.5V.
When troubleshooting this system, a current or voltage needs
to be measured to determine the status or condition of the
sensor.
Measuring current:
The ammeter A is used to measure current at the length
input signal. Remove the wire from X1:27 terminal in the central
unit and measure the current with the ammeter in series. The
measurement should be between 4..20mA.
Measuring voltage:
The voltmeter V is used to measure voltage between pins X1:27 (length
signal) and X1:28 (gnd) on the main board (024-352-300-001 /
9333103287). The resistors are there to show that at 4mA the voltage is
1.1V because current multiplied with resistance equals voltage; therefore,
4mA x 275 ohms (total resistance) = 1.1V.
The ammeter A is used to measure current at the piston side input signal. Remove the wire
from X1:21 terminal in the central unit and measure the current with the ammeter in series. The
measurement should be between 4..20mA.
Measuring voltage:
The ammeter A is used to measure current at the rod side input signal. Remove the wire
from X1:24 terminal in the central unit and measure the current with the ammeter in series. The
measurement should be between 4..20mA.
Measuring voltage:
The voltmeter V is used to measure voltage between pins X1:24 (rod side signal) and X1:25
(gnd) on the main board (024-352-300-001). The resistors are there to show that at 4mA the voltage is
1.1V because current multiplied with resistance equals voltage; therefore, 4mA x 275 ohms (total
resistance) = 1.1V.
The ammeter A is used to measure current at the angle input signal. Remove the wire from
X1:29 terminal in the central unit and measure the current with the ammeter in series. The
measurement should be between 4..20mA.
Measuring voltage:
The voltmeter is V used to measure voltage between pins X1:29 (angle signal) and X1:28 (gnd)
on the main board (024-352-300-001). The resistors are there to show that at 4mA the voltage is 1.1V
because current multiplied with resistance equals voltage; therefore, 4mA x 275 ohms (total
resistance) = 1.1V.