Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

BS en 12098 1 2013 PDF

Download as pdf or txt
Download as pdf or txt
You are on page 1of 36

BS EN 12098-1:2013

BSI Standards Publication

Controls for heating systems


Part 1: Control equipment for hot water
heating systems
BS EN 12098-1:2013 BRITISH STANDARD

National foreword
This British Standard is the UK implementation of EN 12098-1:2013.
It supersedes BS EN 12098-1:1997 and BS EN 12098-2:2001 which are
withdrawn.
The UK participation in its preparation was entrusted to Technical
Committee RHE/16, Performance requirements for control systems.
A list of organizations represented on this committee can be
obtained on request to its secretary.
This publication does not purport to include all the necessary
provisions of a contract. Users are responsible for its correct
application.
© The British Standards Institution 2013. Published by BSI Standards
Limited 2013
ISBN 978 0 580 73039 9
ICS 91.140.10; 97.120
Compliance with a British Standard cannot confer immunity from
legal obligations.
This British Standard was published under the authority of the
Standards Policy and Strategy Committee on 31 August 2013.
Amendments issued since publication
Date Text affected
BS EN 12098-1:2013

EUROPEAN STANDARD EN 12098-1


NORME EUROPÉENNE
EUROPÄISCHE NORM August 2013

ICS 91.140.10; 97.120 Supersedes EN 12098-1:1996, EN 12098-2:2001

English Version

Controls for heating systems - Part 1: Control equipment for hot


water heating systems

Régulation pour les systèmes de chauffage - Partie 1: Mess-, Steuer- und Regeleinrichtungen für Heizungen - Teil
Equipement de régulation pour les systèmes de chauffage 1: Regeleinrichtungen für Warmwasserheizungen
à eau chaude

This European Standard was approved by CEN on 8 June 2013.

CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European
Standard the status of a national standard without any alteration. Up-to-date lists and bibliographical references concerning such national
standards may be obtained on application to the CEN-CENELEC Management Centre or to any CEN member.

This European Standard exists in three official versions (English, French, German). A version in any other language made by translation
under the responsibility of a CEN member into its own language and notified to the CEN-CENELEC Management Centre has the same
status as the official versions.

CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia,
Finland, Former Yugoslav Republic of Macedonia, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania,
Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland, Turkey and United
Kingdom.

EUROPEAN COMMITTEE FOR STANDARDIZATION


COMITÉ EUROPÉEN DE NORMALISATION
EUROPÄISCHES KOMITEE FÜR NORMUNG

CEN-CENELEC Management Centre: Avenue Marnix 17, B-1000 Brussels

© 2013 CEN All rights of exploitation in any form and by any means reserved Ref. No. EN 12098-1:2013: E
worldwide for CEN national Members.
BS EN 12098-1:2013
EN 12098-1:2013 (E)

Contents Page

Foreword ..............................................................................................................................................................4
Introduction .........................................................................................................................................................5
1 Scope ......................................................................................................................................................6
2 Normative references ............................................................................................................................6
3 Terms and definitions ...........................................................................................................................6
4 Functionality........................................................................................................................................ 12
4.1 Functional objective ........................................................................................................................... 12
4.2 Control equipment functionality ....................................................................................................... 13
5 Graphical symbols .............................................................................................................................. 13
6 Requirements ...................................................................................................................................... 13
6.1 Data protection .................................................................................................................................... 13
6.2 Characteristic heating curve ............................................................................................................. 13
6.3 Input signal – Sensors ....................................................................................................................... 14
6.4 Controller operation modes ............................................................................................................... 15
6.4.1 General ................................................................................................................................................. 15
6.4.2 Comfort operation mode .................................................................................................................... 15
6.4.3 Economy operation mode .................................................................................................................. 15
6.4.4 Building protection operation mode ................................................................................................. 16
6.4.5 Automatic operation mode ................................................................................................................ 16
6.5 Frost protection .................................................................................................................................. 16
6.6 Additional functions ........................................................................................................................... 16
6.6.1 General ................................................................................................................................................. 16
6.6.2 Summer/Winter switch function ........................................................................................................ 16
6.6.3 Set back function ................................................................................................................................ 16
6.6.4 Optimum start function ...................................................................................................................... 16
6.6.5 Optimum stop function ...................................................................................................................... 16
6.7 Switching times................................................................................................................................... 17
6.8 Manual Emergency Operation Mode (MEOM) .................................................................................. 17
6.9 Parameter settings.............................................................................................................................. 17
6.10 Factory settings / Default values....................................................................................................... 17
6.10.1 Characteristic heating curve ............................................................................................................. 17
6.10.2 Switching times / Operating condition ............................................................................................. 18
6.11 Switching relays.................................................................................................................................. 18
6.12 Electrical requirements ...................................................................................................................... 18
6.12.1 Electrical connections ........................................................................................................................ 18
6.12.2 Supply voltage .................................................................................................................................... 18
6.12.3 Electrical safety................................................................................................................................... 18
6.12.4 Electro magnetic compatibility.......................................................................................................... 18
6.13 Degree of protection ........................................................................................................................... 18
6.14 Environmentally induced stress due to temperature ...................................................................... 18
6.15 Materials .............................................................................................................................................. 19
6.16 Use of graphical symbols .................................................................................................................. 19
7 Test methods....................................................................................................................................... 19
7.1 Data protection .................................................................................................................................... 19
7.2 Controller operation modes ............................................................................................................... 19
7.3 Controller characteristic heating curve ............................................................................................ 19
7.4 Frost protection .................................................................................................................................. 24
7.5 Switching times................................................................................................................................... 24

2
BS EN 12098-1:2013
EN 12098-1:2013 (E)

7.6 Manual Emergency Operation Mode ................................................................................................. 24


7.7 Optimum start-stop function .............................................................................................................. 24
7.7.1 General ................................................................................................................................................. 24
7.7.2 Test conditions .................................................................................................................................... 26
7.7.3 Test run................................................................................................................................................. 26
7.7.4 Test results start optimisation ........................................................................................................... 27
7.7.5 Test results stop optimisation ........................................................................................................... 29
7.7.6 Summer/Winter-switch........................................................................................................................ 29
7.8 Set back ................................................................................................................................................ 29
7.9 Parameter settings .............................................................................................................................. 29
7.10 Factory settings ................................................................................................................................... 29
7.11 Switching relays .................................................................................................................................. 29
7.12 Electrical test ....................................................................................................................................... 29
7.13 Degrees of protection ......................................................................................................................... 30
7.14 Environmental individual stress due to temperature ...................................................................... 30
8 Marking ................................................................................................................................................. 30
9 Documentation .................................................................................................................................... 30
9.1 Technical documents .......................................................................................................................... 30
9.2 Technical specifications ..................................................................................................................... 30
9.2.1 Controller.............................................................................................................................................. 30
9.2.2 Output signals ..................................................................................................................................... 31
9.2.3 Input signals (Sensors) ....................................................................................................................... 31
9.3 Instruction installation ........................................................................................................................ 31
9.4 User guideline ...................................................................................................................................... 31
Bibliography ...................................................................................................................................................... 32

3
BS EN 12098-1:2013
EN 12098-1:2013 (E)

Foreword
This document (EN 12098-1:2013) has been prepared by Technical Committee CEN/TC 247 “Building
Automation, Controls and Building Management”, the secretariat of which is held by SNV.

This European Standard shall be given the status of a national standard, either by publication of an identical
text or by endorsement, at the latest by February 2014, and conflicting national standards shall be withdrawn
at the latest by February 2014.

Attention is drawn to the possibility that some of the elements of this document may be the subject of patent
rights. CEN [and/or CENELEC] shall not be held responsible for identifying any or all such patent rights.

This document supersedes EN 12098-1:1996 and EN 12098-2:2001.

EN 12098, Controls for heating systems, currently consists of the following parts:

 Part 1: Control equipment for hot water heating systems (the present document);

 Part 3: Outside temperature compensated control equipment for electrical heating systems;

 Part 4: Optimum start-stop control equipment for electrical systems 1);

 Part 5: Start-stop schedulers for heating systems.

This standard is for products for Outside Temperature Compensated Controls for mechanical building services
and covers Outside Temperature Compensated Controls in residential and non-residential buildings. This
standard is part of a series of European Standards for Control for HVAC Applications. This standard,
therefore, contributes to the general European policy for energy saving, particularly in the fields of the
Construction Products Directive (89/106/EEC) Essential Requirements n°6 'Energy economy and heat
retention' (and its interpretative document) and of the Energy Performance of Building Directive (2002/91/CE).

This standard covers also controllers which contain an integrated optimum start or an optimum start-stop
control function.

According to the CEN-CENELEC Internal Regulations, the national standards organisations of the following
countries are bound to implement this European Standard: Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech
Republic, Denmark, Estonia, Finland, Former Yugoslav Republic of Macedonia, France, Germany, Greece,
Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal,
Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland, Turkey and the United Kingdom.

1) EN 12098-4:2005 is bound to be superseded in the future by an upcoming new edition of EN 12098-3.

4
BS EN 12098-1:2013
EN 12098-1:2013 (E)

Introduction
Equipment which controls the heating supply in buildings according to outside temperature and time is
necessary to reduce the energy consumption of heating plants. This equipment can bring about improved
comfort and energy savings.

For this purpose, an outside temperature compensated controller (OTC) is necessary.

This standard describes the main equipment characteristics and functions for reaching energy saving and
comfort objectives.

5
BS EN 12098-1:2013
EN 12098-1:2013 (E)

1 Scope
This European Standard applies to electronic control equipment for heating systems with water as the heating
medium and a flow water temperature up to 120 °C.

This control equipment controls and regulates the distribution and/or the generation of heat in relation to the
outside temperature and time and other reference variables.

This standard covers also controllers which contain an integrated optimum start or an optimum start-stop
control function.

Safety requirements on heating systems remain unaffected by this standard. The dynamic behaviour of the
valves and actuators are not covered in this standard.

A multi-distribution and/or multi-generation system needs a coordinated solution to prevent undesired


interaction and is not part of this standard.

2 Normative references
The following documents, in whole or in part, are normatively referenced in this document and are
indispensable for the application of this document. For dated references, only the edition cited applies. For
undated references, the latest edition of the referenced document (including any amendments) applies.

CEN/TS 15810, Graphical symbols for use on integrated building automation equipment

EN 60038, CENELEC standard voltages (IEC 60038)

EN 60529, Degrees of protection provided by enclosures (IP Code) (IEC 60529)

EN 60730-1, Automatic electrical controls for household and similar use — Part 1: General requirements
(IEC 60730-1)

3 Terms and definitions


For the purposes of this document, the following terms and definitions apply.

3.1
Outside Temperature Compensated Controller
OTC
instrument that controls and regulates the distribution and/or the generation of heat in relation to the outside
temperature and time and other reference variables

Note 1 to entry: The Outside Temperature Compensated function calculates the flow (supply) temperature in relation
to the outside temperature, based on the heating curve.

3.2
control equipment
equipment which consists of the OTC, sensor input signals and output signals, but does not include the
sensors and actuating equipment

Note 1 to entry: See Figure 1.

6
BS EN 12098-1:2013
EN 12098-1:2013 (E)

Key
1 OTC
2 output signals
3 input signals: reference variables
4 input signal: controlled variable
5 actuating equipment
6 heat generation & distribution

Figure 1 — Control equipment for heating systems

3.3
actuating equipment
equipment by which the controller affects the controlled variable

3.4
controlled variable (input signal)
supply water temperature and/or boiler water temperature as a result of the heating curve in accordance to the
reference variables

3.5
output signals
signals generated by the OTC controller for operating the actuating equipment

3.6
reference variables (input signal)
outside temperature with or without other influences or variables (e.g. room temperature) used to determine
the setpoint of the controlled variable

3.7
outside temperature
reference variable that is measured with a sensor fitted outside the building, mainly intended to measure the
ambient air temperature

3.8
room temperature
resulting room temperature in the building that arises in comfort, economy or building protection operation
mode of the OTC controller and that can be different for individual rooms

7
BS EN 12098-1:2013
EN 12098-1:2013 (E)

3.9
characteristic heating curve
relation between the setpoint value of the controlled variable (e.g. flow water temperature) and the reference
variables (outside temperature) defined by two or more parameters and depending on operation mode and
additional variables

Note 1 to entry: The flow water temperature is a function of the outside temperature and the present room temperature
setpoint. The supply water temperature as function of the outside temperature is graphically represented by the heating
curve.

3.10
comfort operation mode
operating period between the switch-on time and the switch-off time for normally occupied rooms

3.11
economy operation mode (reduced mode)
operating period between the switch-off time and the switch-on time, maintaining a reduced room temperature
compared to the comfort room temperature

3.12
building protection operation mode (reduced mode)
operating period between the switch-off time and the switch-on time, maintaining a room temperature required
for building protection

3.13
automatic operation
mode of operation of equipment when significant control functions are not overridden by the user

Note 1 to entry: The operation mode is selected automatically according to the scheduler, actual date and time.

3.14
summer/winter switch function
summer/winter switch is used to seasonal switch on/off the heating depending on a function of the outside
temperature

3.15
set back function
function to switch off heat generation when the operation mode changes from comfort to economy or building
protection until the calculated or measured room temperature drops below the economy or building protection
set point, the operation mode switches back to comfort mode or the calculated switch-on time of the
optimisation start function is reached

3.16
optimum start function
function that calculates the optimum pre-heat time to reach the comfort temperature level at the beginning of
the comfort time period

Note 1 to entry: See Figure 2.

8
BS EN 12098-1:2013
EN 12098-1:2013 (E)

Key
1 comfort room temperature
2 reduced room temperature
A(0) beginning of comfort occupation period
A(x) switch-on time with start optimisation (variable start)
A(y) switch-on time without start optimisation (fixed start)
B(0) end of comfort occupation period without stop optimisation (fixed stop)
B(x) switch-off time with stop optimisation (variable stop)
C = A(0) - B(0) comfort occupation period
A(x) - A(0) optimum start period
B(x) - B(0) optimum stop period
W time period of wasted heat (energy saving potential with start optimisation)

Figure 2 — Temperature time curve with optimiser function

The optimum start and the optimum stop functions are illustrated by Figure 3. Heating periods are different from scheduled
occupation periods. These differences, due to thermal inertia, depend mainly on heating loads (or temperatures
differences). A start and/or stop optimiser controls these switching points, using outside and/or room temperatures or their
differences in relation to setpoints.

9
BS EN 12098-1:2013
EN 12098-1:2013 (E)

Key
S schedule occupation period
O heating operation status
R room temperature profile
1 comfort room temperature
2 reduced room temperature
3 comfort occupation period
4 optimum start period
5 main controller function
6 optimum stop period
7 set back period

Figure 3 — Example Optimum start and stop function

3.17
adaptive optimum start function
added function to optimum start function, which recalculates the parameters used to determine the switch-on
time, based on measured room temperature

3.18
optimum stop function
switches off or reduces the heat generation at the earliest possible point in time so that the room temperature
will drop max. 0,5 K below the comfort setpoint when the operation mode changes from comfort mode to
economy or building protection mode

Note 1 to entry: See Figure 2.

3.19
adaptive optimum stop function
added function to optimum stop function, which recalculates the parameters used to determine the switch-off
time, based on measured room temperature

3.20
scheduler
function which switches heating modes affecting the heating control system (see Figure 3) according to a
program which includes memorised switch times, reproducing periods or periodic cycles, daily, weekly or
yearly, and may also include periods of derogation

3.21
switch points and time periods

10
BS EN 12098-1:2013
EN 12098-1:2013 (E)

3.21.1
switch on time
point in time at which the controller increase the setpoint for boiler/flow temperature in order to reach the
comfort room temperature

Note 1 to entry: If the optimum start function is applied the switch on time is automatically determined by the controller
otherwise it is determined by the scheduler.

3.21.2
optimum start period
optimal pre heat period between the switch on time and the beginning of comfort occupation period

3.21.3
beginning of comfort occupation period
user programmed switch point when the comfort room temperature is bound to be reached

3.21.4
comfort occupation period
operating period during which comfort room temperature is bound to be maintained

3.21.5
end of comfort occupation period
user programmed switch point when the room temperature is allowed to decrease under the comfort room
temperature and for which the room temperature setpoint is switched to Economy and/or Building Protection
setpoint

3.21.6
switch off time
point in time at which the controller decreases the setpoint for boiler/flow water temperature

Note 1 to entry: If the optimum stop function is applied the switch off time is automatically determined by the controller
otherwise it is determined by the scheduler.

3.21.7
optimum stop period
operating period between the optimal switch off time and the end of comfort occupation period

3.21.8
derogation
function or set of functions for user interaction to temporary override the operation mode

Note 1 to entry: There are different possibilities for derogation functions. Two examples of temporary override of the
program by derogation and recovery of the periodic program are shown in Figure 4:

− Upper Diagram: “derogation manual start” initiates a predefined timer which switches the mode to comfort. After the
timer is elapsed, the mode defined by the scheduler is applied.

− Lower Diagram: “derogation manual start” changes the mode until the next programmed switch time.

11
BS EN 12098-1:2013
EN 12098-1:2013 (E)

Key
1 comfort room temperature
A and B programmed switch times
2 reduced room temperature
C derogation manual start
D programmable duration

Figure 4 — Examples of derogation

3.22
valve protection function (valve exercise function)
anti-jamming function for valves in which the valves should be moved periodically during longer off periods

3.23
pump protection function (pump exercise function)
anti-jamming function for pump in which the pumps should be switched on during longer off periods

3.24
frost protection function
function in all operation modes (except manual emergency operation) to prevent the heating system from
freezing by providing specific output signals

3.25
Manual Emergency Operation Mode
MEOM
mode in which the controller is inactive and the actuating equipment is manipulated manually

4 Functionality

4.1 Functional objective

The objective of outside temperature compensated control equipment is to save energy by reducing waste
potential and supply losses performing these main functions:

12
BS EN 12098-1:2013
EN 12098-1:2013 (E)

a) to control supply temperature so that the room temperature can be maintained at the desired level, as
determined by comfort and energy optimisation criteria, estimating the heat demand from measurements
of the outside temperature with or without other reference variables;

b) to alter the heat supply to follow a scheduled change in order to match occupancy patterns.

OTC control equipment also incorporates a frost protection function and a manual emergency operation
mode.

4.2 Control equipment functionality

See Figure 5:

Figure 5 — Block-scheme of control equipment

5 Graphical symbols
Graphical symbols are described in CEN/TS 15810. Plain language can be used instead of, or in conjunction
with, graphical symbols.

6 Requirements

6.1 Data protection

Actual time and date shall be retained for at least 12 h on failure of the power supply. All other data input on
commissioning shall be retained.

6.2 Characteristic heating curve

The range of characteristic heating curve(s) shall be displayed graphically by the manufacturer on the unit
and/or in the technical documents e.g. as shown in Figure 6.

13
BS EN 12098-1:2013
EN 12098-1:2013 (E)

Key
1 boiler / supply-water temperature (°C)
2 outside temperature (°C)
NOTE The graphical representation using a reversed temperature axis is also often used.

Figure 6 — Example of characteristic heating curves

The relations between the adjustable setting parameters and the characteristic heating curves shall be shown.

The average flow water temperature shall not deviate from the set temperature points on the characteristic
heating curve by more than ± 3 K.

Characteristic heating curves are defined for different temperature ranges:

 heating system for high temperature as oil/gas burners or district heating and flow/return temperatures of
90 °C/70 °C;

 heating system for medium temperature as oil/gas burners with flow/return temperatures of 70 °C/50 °C;

 heating system for low temperature heat generation systems as renewable energies (solar/heat pump)
with flow/return temperatures of 55 °C/45 °C;

 heating system for floor heating applications with flow/return temperatures of 35 °C/28 °C.

At least one of this temperature ranges shall be provided by the controller. The characteristic heating curves
shall be adaptable to the related building.

6.3 Input signal – Sensors

The tolerances in Table 1 are required from sensors in the indicated ranges:

14
BS EN 12098-1:2013
EN 12098-1:2013 (E)

Table 1 — Sensor accuracy

Temperature range Sensor accuracy

Room temperature + 15 °C to + 25 °C ± 0,8 K

Boiler water temp. or 0 °C to + 60 °C ± 1,0 K


Flow water temperature
Outside temperature - 10 °C to + 18 °C ± 1,0 K

Outside these temperature ranges no sensor accuracy is specified in this standard.

6.4 Controller operation modes

6.4.1 General

Controllers shall facilitate at least automatic operation mode, comfort operation mode and one reduced
operation mode (economy / building protection). The current operation mode shall be displayed.

The following operation modes shall be available by switching manually:

 comfort;

 economy and/or building protection;

 automatic.

6.4.2 Comfort operation mode

Operation mode of occupied rooms. The flow water temperature is a function of the heating curve, based on
the outside temperature and the comfort room temperature setpoint.

6.4.3 Economy operation mode

Operation mode for rooms which do not need to be in the comfort operation mode for an extended period of
time for energy saving.

The flow water temperature is a function of the heating curve, based on the outside temperature and the
economy room temperature setpoint.

For the change from comfort to economy operation mode , the controller shall allow a reduction of the
boiler/flow water temperature of at least 20 % of the difference between the water temperature during comfort
operation and the comfort room temperature (e.g. 20 °C).

TW,R <= TW,C - 0,2(TW,C – TR,C)

where

TW,R is the economy flow water temperature;

TW,C is the comfort flow water temperature;

TR,C is the comfort room temperature.

15
BS EN 12098-1:2013
EN 12098-1:2013 (E)

6.4.4 Building protection operation mode

Mode of operation to protect the building from damages caused by low temperatures and humidity.

The flow water temperature is a function of the heating curve, based on the outside temperature and the
building protection room temperature setpoint. The building protection setpoint temperature is below the
economy setpoint temperature.

6.4.5 Automatic operation mode

The operation mode (Comfort, Economy and/or Building Protection) is selected automatically according to the
scheduler, actual date and time.

6.5 Frost protection

In all operating modes (except for manual emergency operation mode operation) a frost protection function
shall be effective if the boiler flow water temperature falls to minimum of 5 °C or the outdoor temperature falls
below 2 °C (can be lower for system with fluid frost protection (e.g. Glycol)). The pump operates, the valve
opens. If the flow water temperature drops below 5 °C the heat generation shall be switched on.

6.6 Additional functions

6.6.1 General

These functions are optional. If implemented the requirements of the corresponding function in this subclause
have to be fulfilled.

6.6.2 Summer/Winter switch function

When the attenuated outside temperature exceeds the summer/winter heating limit a change to summer
operation will take place. When the attenuated outside temperature falls below the summer/winter heating limit
a change to winter operation will take place. The summer/winter heating limit shall be adjustable.

In summer operation mode the summer/winter switch function switches off the heat generation and the pump
and closes the valves.

6.6.3 Set back function

During set back period the reduced room temperature setpoint is valid. The function switches off the heat
generation and the pump and closes the valves until the calculated or measured room temperature drops
below the reduced setpoint.

6.6.4 Optimum start function

The optimum start function calculates the pre-heat time to reach the comfort temperature level at the
beginning of the comfort time period within a limit of +/- 30 min. Once the comfort level is reached the room
temperature shall stay within +/- 0,5 K around the comfort room temperature.

6.6.5 Optimum stop function

The optimum stop function calculates the optimum switch-off time so that the room temperature at the end of
the comfort period is within the allowable temperature decrease of -0,5 K of the comfort temperature level.

16
BS EN 12098-1:2013
EN 12098-1:2013 (E)

6.7 Switching times

A time switching function is required for changing operating modes. Setting and accuracy requirements for the
switching times and clock are shown in Table 2.

Table 2 — Switching time and clock

SWITCHING TIMES CLOCK


Minimum No. Resolution of Accuracy Resolution Accuracy
of settings settings of setting
Digital clock 4/day ≤ 0,5 h ± 1 min ≤ 1 min ± 30 min/
year
Analogue 4/day for a ≤ 0,5 h for a ± 10 min ≤ 10 min ± 30 min/
clock clock 24-h day clock year
2/day for a ≤ 2 h for a a
weekly clock weekly clock
a The minimum switching period shall be no longer than 4 h.

6.8 Manual Emergency Operation Mode (MEOM)

Due to a failure of the connected hardware like a sensor error or an abnormal operation of the control
equipment the heat flow may be interrupted.

For such abnormal situation the control equipment shall have a MEOM providing a possibility to restart the
heat distribution.

This MEOM shall be activated in a user-friendly way like a switch or an easy available parameter.

If an independent control function of the heat generator is available and functional, the MEOM shall:

 turn on flow water pump;

 switch off the control function regarding the motor drive or define a fix value for the valve;

 enable heat generation.

6.9 Parameter settings

The following setting facilities shall be provided for the user:

Actual time, switching times, characteristic heating curve parameters (e.g. gradient, offset, temperature
setpoints).

NOTE A method for adjusting manually the parameters of the characteristic heating curve can be found in the paper
of J. Tödtli listed in the Bibliography.

6.10 Factory settings / Default values

6.10.1 Characteristic heating curve

A factory setting of the heating curve has to be implemented in the OTC and described in the technical
documentation.

17
BS EN 12098-1:2013
EN 12098-1:2013 (E)

6.10.2 Switching times / Operating condition

The default time for a reduced temperature shall be a minimum of 8 h per day (e.g. 10 pm to
6 am). The default setting shall be described in the technical documents.

6.11 Switching relays

The ratings of the relay contacts are to be declared in the technical documents and shall be designed for the
following minimum number of switching operations in Table 3.

Table 3 — Switching operations

Actuating equipment Number of switching


Operations

Motor-Drive 800 000


Burner 300 000
Pump 30 000

6.12 Electrical requirements

6.12.1 Electrical connections

The electrical connections to the main power supply and external cables shall be designed according to
EN 60730-1.

6.12.2 Supply voltage

EN 60038 shall be applied for the selection of the nominal voltage of the controller.

6.12.3 Electrical safety

The controller shall be designed to comply with one of the following protective classes to EN 60730-1:

 Protective class I;

 Protective class II;

 Protective class III.

6.12.4 Electro magnetic compatibility

The emissions of and immunity to electro magnetic interference shall satisfy the requirements of EMC
Directive.

6.13 Degree of protection

The degree of protection of the controller shall comply with EN 60529. The OTC shall fulfil at least IP 20.

6.14 Environmentally induced stress due to temperature

The OTC controller shall withstand the stress due to temperature according to Table 4.

18
BS EN 12098-1:2013
EN 12098-1:2013 (E)

Table 4 — Ambient temperatures

Product Ambient temperature in Ambient temperature


operation transport and storage
Controller + 5 °C to + 50 °C - 20 to + 60 °C

6.15 Materials

The heat and fire resistance, creeping current and corrosion resistance shall correspond with the
requirements of EN 60730-1.

6.16 Use of graphical symbols

Used graphical symbols shall be in accordance with CEN/TS 15810.

7 Test methods

7.1 Data protection

The control unit shall be supplied with nominal voltage and put into operation. The data shall be set according
to the manufacturer information. In case of control units with a re-chargeable power storage, the minimum
charging time shall be completed before testing. The supply voltage shall be switched off for 12 h. It shall then
be switched on again and tested for correct retention of data as time, date and parameters of heating curve.

7.2 Controller operation modes

Check if automatic, comfort and at least one reduced operation mode is provided by the controller.

To check the reduced operation mode test points should be selected of the highest and lowest heating curve
at an outside temperature of – 10 °C. The reduction in the boiler / flow water temperature shall meet the
requirements of 6.5.

7.3 Controller characteristic heating curve

This test will check the ability to adapt the controller to the building types and heating systems and confirms
the accuracy of the equipment in controlling the manipulated variable to a selected manufacturer's curve.

The ability to adapt the controller to the building types and heating systems is tested using reference
characteristic heating curves. Four reference characteristic heating curves were defined to represent the
demand for heating energy of a reference building in relation to the temperature ranges defined in 6.2. They
were derived from a thermal building simulation.

For each heating system to which the manufacturer claims support the test has to be performed with the
corresponding reference characteristic heating curve. For each of these references characteristic heating
curves a heating curve of the controller has to be selected. The heating curve in the controller has to be higher
or equal to the corresponding reference characteristic heating curve.

The conformance of the implemented heating curve with the reference characteristic heating curve is tested
for four load scenarios (outside temperatures). All test conditions are listed in Table 5.

19
BS EN 12098-1:2013
EN 12098-1:2013 (E)

Table 5 — Flow water temperatures on the reference heating curves for the 4 outside temperatures

Outside Temperatures setpoints on the reference heating


temperature curves for heating system (Tf/ Tr) [°C]
(TO) [°C] (90/70) (70/55) (55/45) (35/28)
- 10 90,0 70,0 55,0 35,0
- 2,5 75,6 59,7 47,8 31,5
5 60,2 48,7 40,1 27,9
12,5 43,2 36,5 31,6 24,1
Key
Tf = design flow temperature
Tr = design return temperature
TO = outside temperature

Key
1 outside temperature (°C)
2 boiler / supply-water temperature (°C)

Figure 7 — Graphical representation of the reference characteristic hearting curves

The controller is connected to an outside temperature simulator which can either be a signal directly
connected to the sensor input or a sensor placed in a controlled liquid bath.

NOTE In case of attenuated outside temperature it is essential that the tester makes sure that the outside
temperature value used to control the controlled variable is the required one.

20
BS EN 12098-1:2013
EN 12098-1:2013 (E)

For all of the selected scenarios of Table 5, the deviation of the setpoint of the controlled variable to the
reference temperature is calculated:

ΔT (HC,T0) = T (HC, T0) – TRef(HC, T0)

where

T(HC, T0) is the temperature setpoint of heating curve at outside temperature;

TRef(HC, T0) is the temperature on the reference heating curve at the outside temperature;

ΔT (HC, T0) is the difference of the temperature setpoint of heating curve and the temperature of the
reference heating curve at the outside temperature;

HC: is the the index for the heating curve and corresponding reference heating curve
(1: (90/70), 2: (70/55), 3: (55/45), 4: (35/28));

T0 is the outside temperature.

The ability to adapt the heating curves to building types and heating systems is given, when the following
criteria are met.

 1 ΔT (HC, T0) ≥ 0

 2 ΔT (HC, T0) < 4 % of (TRef (HC, T0) – 20 °C) or

ΔT (HC, T0) < 2K

21
BS EN 12098-1:2013
EN 12098-1:2013 (E)

Key
1 flow water temperature setpoint
2 outside temperature
C1, C2 examples for Test cases (case 1, 2)
HCctr heating curve of the controller
HCref reference heating curve
a criteria: 4 % of (HC, T0) – 20 °C
b criteria: ΔT (HC,T0) < 2K

Figure 8 — Example of the test of the accuracy of the heating curve

Figure 8 shows an example with two test cases (C1 and C2) of the accuracy of the selected heating curve in
the controller compared to the reference heating curve. In both cases the controller heating curve meets the
requirements:

 Case C1: ΔT(HC,T0=5 °C) > 0 , ΔT(HC,T0=5 °C) > 4 % of (TRef(HC, T0=5 °C) – 20 °C), but < 2 K

Test passed successfully

 Case C2: ΔT(HC,T0=-10 °C) > 0 , ΔT(HC,T0=-10 °C) > 2 K, but < 4 % of (TRef(HC, T0=-10 °C) – 20 °C)

Test passed successfully

22
BS EN 12098-1:2013
EN 12098-1:2013 (E)

Key
1 OTC control device (device under test)
2 device for signal transformation of the analogue sensor output to a normalised digital control variable (C)
3 calculation of the flow water temperature
4 device for signal transformation of the simulated flow water temperature to an analogue sensor input signal of the
controller (e.g. liquid bath, programmable resistor)
O output signal of OTC control device to control the flow water temperature (analogue)
I input signal to the OTC control device for the flow water temperature
C normalised control variable
T simulated flow water temperature variable
TO outside temperature

Figure 9 — Test system block diagram

The accuracy of the equipment in controlling the manipulated variable to a selected manufacturer's curve is
tested at least at one of the selected test points of Table 5.

A closed loop test system will be used to test the controller performance. The outside temperature shall be
simulated e.g. by a fixed precision resistor or by other appropriate means, with an accuracy of ± 0,1K. The
controlled variable (boiler / flow water temperature) shall also be simulated with an accuracy of ± 0,1K, e.g. by
a variable precision resistor or by an associated sensor immersed in a liquid bath.

The tests should be performed so that the dynamic components of the sensor, the controller and the test
equipment do not influence the results. A suitable test system is shown in Figure 9.

The actual value of the controlled variable T should be changed according to the following procedure:

1) Measure the controller output and produce a normalised value (C):

• C = 0 or 1 : for an on/off output signal.

• C = 0 or 0,5 or 1 : for a tri-state output signal.

23
BS EN 12098-1:2013
EN 12098-1:2013 (E)

• C = 0 .. 1 : for an analogue output signal

(measured with an accuracy of ± 1 %)

2) Setpoint calculation: Calculate the value of the manipulated variable T [°C] using the formula below,
and change the manipulated variable to this value.

T(t) = T(t − ∆t) + (2 * C − 1) ⋅ F ⋅ ∆t

where

T(t) is the manipulated variable at time t;

∆t is the time step, i.e. how often the test system updates the value T [sec];

F is a constant representing the response of the closed loop system.

It is recommended that ∆t = 1 s and that F = 10K/3 600s (corresponding to 10 K/h).

The test should be run until the controlled variable reaches a steady state value or in case of periodic variation
until three full cycles have been completed. The final value of the controlled variable is the steady state value
or the mean value calculated over three full cycles in the case of periodic variation. This final value shall then
be recorded and compared against the corresponding point on the characteristic heating curve as stated by
the manufacturer.

The recorded temperature T shall not deviate by more then +/- 3K from the setpoint calculated by the
controller based on the characteristic heating curve. The test result includes the accuracy of the sensors and
test equipment.

7.4 Frost protection

Test by reducing boiler / flow water temperature below + 5 °C and check pump, valve and burner outputs.

All relevant signals shall be on or fully open in all operating modes, except in manual emergency operation.

7.5 Switching times

The number of switching times per day and per week and their switching resolution and accuracy shall be
visually checked to be conform with the requirements of Table 2 in 6.7.

The accuracy of the switching times is to be confirmed by switching from comfort mode to a reduced mode
and reverse (complete cycle) by observing relevant output(s).

The resolution of settings and the accuracy of the clock have to be checked against the requirements of
Table 2 in 6.7.

7.6 Manual Emergency Operation Mode

When the OTC is set to manual emergency operation mode the outputs of the system has to be checked
against the requirement in 6.8.

7.7 Optimum start-stop function

7.7.1 General

This test checks if the controller is able to optimise the switch on and switch off times for the heating system.

24
BS EN 12098-1:2013
EN 12098-1:2013 (E)

If the optimum start/stop function is based on adaptive learning, the controller might be pre-adjusted or the
test can be run the number of days declared by the manufacturer in order to let the adaptive start and stop
function learn the thermal dynamics of the room and heating system.

The optimum start-stop function test is done in a simulation environment. The real controller is connected to a
simulated environment of the heating system and the building (represented by one single room). The
simulation setup is illustrated in Figure 10.

Figure 10 — Concept of the optimum start-stop simulation test

The block “Model of heating system” consist of the heat generation, distribution and heat emission. The heat
emission shall be done by a radiator model.

 The heat generation is modelled in a simplified manner. The output of the heat generation is the
maximum flow water temperature. The dynamic behaviour is determined by the following calculation
model using the return temperature:

P
=Tf − Tr
m ⋅ cW

where


m is the massflow

cW is the heat capacity of water

Tr is the return temperature calculated from the heating system model

Tf is the flow water temperature

P is the power of the heat generator in dependence on the system and the demand of the room
model PModel (Boiler: 2 PModel, Heat pump: 1,1 PModel, District heating: 5 PModel)

25
BS EN 12098-1:2013
EN 12098-1:2013 (E)

 The model of the heat distribution shall include the mixing valve and the pump. The valve position is
based on the controller output. It can be done by on/off, on/off/stop or analogue signals. A model of the
actuator (time for opening and closing) has to be integrated. The pump can only be switched on
(maximum water flow) or off (no water flow).

Key
Tr room temperature
To outside temperature
T water temperature
1 heat generation
2 heat distribution
3 heat emission

Figure 11 — Model of the heating system

7.7.2 Test conditions

The test is performed for two different outside temperatures of + 5 °C and – 5 °C. The outside temperature is
constant during a test run. The test shall be possible for controllers with and without a room temperature input.
The test shall be done at least with one of the 3 heat generators (Boiler, Heat pump, District heating).

7.7.3 Test run

The same constant outside temperature is applied to the controller and the simulation environment. The test
starts in comfort operation mode. The test runs in real time. During an initialisation phase the controller and
the simulation model shall be harmonised and the controller shall control the flow water temperature according
to the selected heating curve and outside temperature. The model calculates the flow water temperature, the
return temperature and the room temperature. The test is performed according to the time table in Table 6.

Table 6 — Time table of optimisation test

17:00 Test start – Comfort mode


22:00 Start of economic mode
7:00 Start of comfort mode
9:00 Test end – Comfort mode

26
BS EN 12098-1:2013
EN 12098-1:2013 (E)

7.7.4 Test results start optimisation

The test result is the verification if the function is working properly. The time difference between the comfort
temperature level is reached and the start of the comfort period shall be within +/- 30 min. Once the comfort
level is reached the room temperature shall stay within +/- 0,5 K around the comfort room temperature. The
interpretation of the test results is illustrated in the following Figure 12 and Figure 13.

Key
1 comfort temperature level
2 beginning of the comfort time period

Figure 12 — Tolerances for time and temperature at the beginning of the comfort time period for an
optimum start function

27
BS EN 12098-1:2013
EN 12098-1:2013 (E)

a)
Key
1 The comfort level is reached before the beginning of the comfort period within the time tolerance. The room
temperature exceeds the setpoint and remains within the temperature tolerance.
2 The comfort level is reached at the beginning of comfort period. The room temperature falls below the comfort
setpoint and remains within the tolerances.
3 The comfort level is reached after the beginning of the comfort period within the time tolerance. The room
temperature remains within the tolerances.

b)
Key
4 The comfort level is reached at the beginning of the comfort period, but the room temperature sinks below the lower
limit of the temperature after the time tolerance period.
5 The comfort level is reached before the beginning of the comfort period within the time tolerance, but the room
temperature exceeds the temperature tolerance after the time tolerance period.
6 The comfort level is reached before beginning of the comfort period within the time tolerance, but the room
temperature exceeds the temperature tolerance within the time tolerance period.

c)
Key
7 The comfort level is reached too early.
8 The comfort level is reached too late.
9 The comfort level is reached too late.

Figure 13 — Interpretation of the results of the optimum start tests

28
BS EN 12098-1:2013
EN 12098-1:2013 (E)

7.7.5 Test results stop optimisation

The test result is the verification that the function is working properly. The function is working properly when:

 the switch-off time is before the end of the comfort period;

 the room temperature at the end of the comfort period is below the temperature setpoint in comfort mode
but not more than the defined value of the acceptable temperature reduction (-0,5 K);

 the switch-off time is not identical for the simulation at - 5 °C and 5 °C.

7.7.6 Summer/Winter-switch

The outside temperature is changed from 15 °C to 20 °C and vice versa. The manufacturer declares the time
needed to switch between summer and winter mode and vice versa. During the test, the controller shall be in
comfort mode. If the controller operates with a room temperature sensor, the room temperature shall be
20 °C.

The test result is the verification that the function is working properly. This means the controller switches the
heating off in summer time and on in winter time.

7.8 Set back

The set back test is performed during the optimum start-stop function test for an outside temperature of
+ 5 °C.

The test checks the pump/boiler signal of the controller. The switch off time is recorded. The room
temperature when the pump/boiler switches on is detected.

The test result is the verification that the function is working properly.

The requirements of the function are fulfilled, when:

 the pump/boiler is switched off within 15 min after the start of the reduced period;

 the pump/boiler is switched on again when the room temperature reaches the reduced temperature
setpoint (+/- 1 K).

7.9 Parameter settings

The setting facilities as described in 6.9 have to be checked if they are available and clearly indicated.

7.10 Factory settings

The default settings described in the technical document shall be checked against the minimum settings
described in 6.10.

7.11 Switching relays

The technical documentation has to be checked against the requirements in 6.11.

7.12 Electrical test

The technical documentation has to be checked against the requirements in 6.12.

29
BS EN 12098-1:2013
EN 12098-1:2013 (E)

7.13 Degrees of protection

The technical documentation has to be checked against the requirements in 6.13.

7.14 Environmental individual stress due to temperature

The technical documentation has to be checked against the requirements in 6.14.

8 Marking
Controllers shall be marked, at least, with the following data:

 manufacturers' name / Trade mark or Product identification;

 reference or type designation;

 power supply (voltage and consumption);

 frequency;

 terminal blocks: each terminal clearly designated.

9 Documentation

9.1 Technical documents

The following information shall be provided in the technical documents:

 technical specifications;

 instructions for installation;

 users guidelines.

This information shall be referenced to the marking on the equipment.

9.2 Technical specifications

9.2.1 Controller

 Dimension [mm]

 Power supply voltage (AC or DC) [V]

 Frequency [Hz]

 Power consumption [W]

 Electrical protection class

 Degree of protection (IP)

 Range of Ambient conditions (operation and storage temperature [°C] and humidity [%])

30
BS EN 12098-1:2013
EN 12098-1:2013 (E)

 Max. Clock: cycle per day

 Clock: setting switch resolution [min]

9.2.2 Output signals

 Type and Specification of Output signal (Transistor Output) [A], [V]

 Type and Specification of Output signal (Relay Output)

 maximum rating, for resistive and inductive load [A], [V]

 Specification of Output signal (0 V – 10 V)

9.2.3 Input signals (Sensors)

Specifications for outside temperature sensor, flow water temperature sensor, other applied compensating
sensors.

 Type e.g.: variable resistance sensors, thermistor, corresponding standard...

 Range (minimum-maximum) [°C]

9.3 Instruction installation

 Application and purpose of the controller: heat generators, emitters

 Mounting instructions

 Wiring plan
2
 Wire cross section, minimum / maximum for external wiring [mm ] Complete instruction concerning
control parameters and information on manual adjustment possibilities

9.4 User guideline

 Indications of temperatures, date and time

 Default program settings and adjustments

 Selection of operating modes

 Instruction for setting temperatures, date, time, on-off scheduling, derogation function

 Relation between the adjustable setting parameters and the heating curve

 Graphical representation of heating curve

 Indication of failure states and how to react

 Meaning of graphical symbols

31
BS EN 12098-1:2013
EN 12098-1:2013 (E)

Bibliography

[1] Jürg Tödtli, “Manual adjusting and self-adaptation of heating curves”, CLIMA 2000, the second World
Congress on Heating, Ventilation, Refrigerating and Air-Conditioning, Sarajevo, August 27 –
September 1, 1989, pp. 329-336 vol II

32
This page deliberately left blank
NO COPYING WITHOUT BSI PERMISSION EXCEPT AS PERMITTED BY COPYRIGHT LAW

British Standards Institution (BSI)


BSI is the national body responsible for preparing British Standards and other
standards-related publications, information and services.
BSI is incorporated by Royal Charter. British Standards and other standardization
products are published by BSI Standards Limited.

About us Revisions
We bring together business, industry, government, consumers, innovators Our British Standards and other publications are updated by amendment or revision.
and others to shape their combined experience and expertise into standards We continually improve the quality of our products and services to benefit your
-based solutions. business. If you find an inaccuracy or ambiguity within a British Standard or other
The knowledge embodied in our standards has been carefully assembled in BSI publication please inform the Knowledge Centre.
a dependable format and refined through our open consultation process.
Organizations of all sizes and across all sectors choose standards to help Copyright
them achieve their goals. All the data, software and documentation set out in all British Standards and
other BSI publications are the property of and copyrighted by BSI, or some person
Information on standards or entity that owns copyright in the information used (such as the international
We can provide you with the knowledge that your organization needs standardization bodies) and has formally licensed such information to BSI for
to succeed. Find out more about British Standards by visiting our website at commercial publication and use. Except as permitted under the Copyright, Designs
bsigroup.com/standards or contacting our Customer Services team or and Patents Act 1988 no extract may be reproduced, stored in a retrieval system
Knowledge Centre. or transmitted in any form or by any means – electronic, photocopying, recording
or otherwise – without prior written permission from BSI. Details and advice can
Buying standards be obtained from the Copyright & Licensing Department.
You can buy and download PDF versions of BSI publications, including British
and adopted European and international standards, through our website at Useful Contacts:
bsigroup.com/shop, where hard copies can also be purchased. Customer Services
If you need international and foreign standards from other Standards Development Tel: +44 845 086 9001
Organizations, hard copies can be ordered from our Customer Services team. Email (orders): orders@bsigroup.com
Email (enquiries): cservices@bsigroup.com
Subscriptions
Subscriptions
Our range of subscription services are designed to make using standards
Tel: +44 845 086 9001
easier for you. For further information on our subscription products go to
Email: subscriptions@bsigroup.com
bsigroup.com/subscriptions.
With British Standards Online (BSOL) you’ll have instant access to over 55,000 Knowledge Centre
British and adopted European and international standards from your desktop. Tel: +44 20 8996 7004
It’s available 24/7 and is refreshed daily so you’ll always be up to date. Email: knowledgecentre@bsigroup.com
You can keep in touch with standards developments and receive substantial
Copyright & Licensing
discounts on the purchase price of standards, both in single copy and subscription
format, by becoming a BSI Subscribing Member. Tel: +44 20 8996 7070
Email: copyright@bsigroup.com
PLUS is an updating service exclusive to BSI Subscribing Members. You will
automatically receive the latest hard copy of your standards when they’re
revised or replaced.
To find out more about becoming a BSI Subscribing Member and the benefits
of membership, please visit bsigroup.com/shop.
With a Multi-User Network Licence (MUNL) you are able to host standards
publications on your intranet. Licences can cover as few or as many users as you
wish. With updates supplied as soon as they’re available, you can be sure your
documentation is current. For further information, email bsmusales@bsigroup.com.

BSI Group Headquarters


389 Chiswick High Road London W4 4AL UK

You might also like