Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

1-Gfs® Fitting Assembly

Download as pdf or txt
Download as pdf or txt
You are on page 1of 10

1- GFS® FITTING ASSEMBLY

Using a Pipe-Cutting Tool, make the required


cut in the valley of two corrugations to the
GFS® CSST, ensuring full circular rotations
are made in the same direction.

Using a Stripper/Safety Knife, cut the yellow sleeve


approximately 30 mm from tubing end. The cut
should be made in the valley of two corrugations,
taking care and ensuring the minimum amount of
material is removed.

Also, care should be taken when rotating the


knife ensuring the cut is only deep enough to
remove the yellow sleeve.

Apply Slight pressure to the cutting tool between


rotations to ensure that the tube is free from sharp
edges, burrs and that a clean cut is achieved.

Push the GFS® CSST firmly into the GFS®


Fitting ensuring the tube is fully inserted, and
has bottomed-out against the stop of the fitting
body.
Once the GFS® tube is fully inserted into the
GFS® Fitting, remove the yellow plastic
transportation ring situated between the GFS®
Hex and Compression Nut.

Tighten the assembled joint by hand, then


using two spanners (one to hold the hex on the
fitting, the other to tighten the nut) tighten to
achieve a mechanically secure gas tight seal.

Ensure all joints are mechanically sound before conducting a pressure drop gas
tighten test.

Once satisfied the installation is gas tight, wrap


any exposed CSST and nut with self-
amalgamating tape. This is to prevent
corrosion threat that may occur from the
ingression of corrosive debris or cleaning
products.

Important: The tape should run onto the back nut, leaving sufficient space to
apply an earthing connection to the back nut or fitting body.
2-Burrying GFS® CSST
GFS® CSST may be directly buried in concrete floors.
Pipe laid in concrete shall be installed in accordance with (Figure 5 ). After the
piping is laid and prior to pouring screed the entire run of GFS® CSST that is to
be buried must be examined visually and manually. The installer must closely
inspect the jacket over the entire length to check for any damage or voids which
could affect corrosion resistance. Repair any damage by wrapping with tape. Tape
wrapping must be done using GFS® CSST self-bonding silicone tape.
-Where pipework is to be installed in solid floors it shall run parallel or at 90° to
the walls.
-Pipework shall not be buried in structural elements of the floor, such as concrete
slabs or structural toppings. Pipework shall not be buried in power-floated floors
that form part of the structure.
-Pipework in acoustic floors shall only be installed with the agreement of the
building designer.
-Pipework that is to be buried in a solid floor shall be suitably protected against
corrosion and degradation.
-Pipework installed in solid floors shall be protected against failure caused by
movement.

Figure 5 Typical examples of pipework installed in solid floors (a)


Figure 5 Typical examples of pipework installed in solid floors (b)

Figure 1 Typical examples of pipework installed in solid floors

Figure 5 Typical examples of pipework installed in solid floors (c)


GFS® is suitable for exterior, exposed use. GFS® CSST covered with the yellow
polyethylene jacket which has been tested for ultraviolet attack. Any exposed
stainless steel should be covered with self-amalgamating tape.
External pipework shall be protected against the risk of mechanical damage.
Buried external pipework shall be inherently resistant to, or otherwise adequately
protected against, corrosion and degradation.
Pipework shall have a minimum depth of cover as given in Table 7.

Table 7 Minimum depths of cover

Buried metallic pipework (other than proprietary systems intended for


underground use) shall only be installed when appropriate and where:
- a risk assessment has been carried out; and
- an inspection strategy has been developed and provided to the gas consumer.
In all cases, GFS® fittings shall not be buried below ground.
3-Bonding
A gas installation within a property with an electrical supply shall have a main
protective bonding conductor connecting the pipework to the electrical
installation’s main earth terminal, as specified in BS 7671.

It is possible for stray currents to be transmitted through the gas pipework.


Therefore, to avoid electric shock or a spark which could ignite the gas, it is
important to maintain electrical continuity in the pipework at all times.

The main protective bonding conductor (main equipotential bonding connection)


shall be connected to the gas consumer’s fixed rigid pipework on the outlet of any
primary meter installation, if fitted:
a) as near as is practicable to the point of entry into the premises;
b) before any branch in the pipework;
c) in a position where it is accessible and can be visually inspected and fitted with a
warning label stating “Safety electrical connection. Do not remove.”; and
d) by a mechanically and electrically sound connection which is not subject to
corrosion.
The main protective bonding conductor (main equipotential bonding connection)
shall not be directly connected to any pliable corrugated (stainless-steel) tube or
pliable connectors from the outlet of the primary meter installation.

For internal meters, for verification purposes the bonding connection should be
within 600 mm of the meter outlet union.

For meters in outside meter boxes/compartments, the bonding connection should


preferably be inside the premises and within 600 mm of the point of entry of the
pipework into the premises.

Alternatively, the connection can be made within the box/compartment, but it is


essential that the bonding cable does not interfere with the integrity of the
box/compartment and the sealing of any sleeve (see Figure 2).
For guidance on equipotential bonding in multi-dwelling buildings see
IGEM/GM/5 [26].

When relocating a meter, an existing main protective bond conductor might be


satisfactory as found, or it might need to be altered. Where the bonding
conductor requires altering, any alterations should be carried out by an electrically
competent person, and inspected and tested in accordance with BS 7671.
Further guidance on the connection to installations containing pliable corrugated
(stainless-steel) tube can be obtained from the product manufacturer.

Figure 2 Main equipotential bonding


4- GFS® SYSTEM COMPONENTS
GFS® CSST system is manufactured in accordance with BS 7838 and BS EN
15266 which are specifies the requirements for material, design, manufacture,
testing, marking of stainless steel pliable corrugated gas tubing kits for buildings
with a maximum operating pressure less than or equal to 0,5 bars and a nominal
size range from DN 10 to DN 50.
· GFS® (CSST) is made from Stainless Metal Hose with a corrugated
construction conforming to EN 10380 standard, produced with 316L (1.4404) in
accordance with EN 10028-7
· Available in DN15, DN20, DN25, DN32, DN40, DN50 Nominal Bore
Dimensions.
· Based on its material properties, CSST offers a high resistance to corrosion.
· CSST is easy to bend and reduces the number of fittings and materials required
with standard rigid pipe installations.
· The corrugated tube is covered with an easy to identify yellow Jacket which is
both fire-retardant and resistant to UV (ultra-violets).
· Maximum Operating Pressure (MOP) shall not exceed 0.5 bar as per BS
EN15266.
· Maximum Operating Pressure (MOP) shall not exceed 0.75 bar as per BS 7838.

Table 1 GFS® Tubing Sizes


5- INSTALLATION IN DUCTS

-Vertical and horizontal ducts containing pipework shall be ventilated to ensure


that minor gas leakage does not cause the atmosphere within the duct to become
unsafe.
- Any ventilation opening shall be located such that air movement can occur
within the duct and hall lead to a safe place, preferably to outside air.
- Ducts shall be sealed from any cavity, wall or floor void through which they pass.
The duct can run freely through a number of storeys or take the form of an
enclosure at each storey level. Where ducts are continuous, ventilation can
normally be achieved by the provision of openings sized in accordance with Table
6 [see Figure 3)].
A duct, or an isolated section of duct contained solely within a room or space, can
be ventilated within that room or space, provided the room or space is ventilated
to normal occupational standards.

Table 6 Free Area of Ventilation Openings


6- SUPPORTING AND SUPPORT SPACING

-GFS® CSST shall be adequately supported in accordance with Table 5


-All pipework supports shall be suitable for the environment in which they are
installed and shall be designed to remain stable for the lifetime of the installation,
e.g. for external use corrosion resistant or UV-stabilized plastic.
-Where GFS® CSST is installed in protected areas, all supports shall be fire-
resistant, e.g. of metallic construction.
-The supports used shall be designed to prevent the pipework coming into contact
with surfaces of the structure which are likely to cause corrosion.
NOTE: Timber is a notable example of a material with which contact is unlikely
to cause corrosion. Other acceptable types of support include those made from
metal (see BS 1494-1) and plastic materials.

Table 5 Support Lengths

You might also like