Design For Shear
Design For Shear
Design For Shear
Thus rearranging
EC2 (Cl. 9.2.2) specifies a minimum value for Asw/s such that,
Design procedures;
Determine design shear force Ved
Determine the concrete strut capacity for cot θ =1.0 and cot θ
=2.5 (θ = 22o and θ = 45o respectively)
Calculate
As f td / 0.87 f yk
100 kN/m
b = 225 mm
8m
2H16
Char. strength of concrete, fck = 30 N/mm2
Char. Strength of reinforcement, fyk = 500 N/mm2 d = 500 mm
• Calculate angle θ,
VEd
0.5 sin 1
0.18b df
w ck 1 f ck / 250
1 400 x10 3
0.5 sin
0.1822550030 1 30 / 250
0.5 sin 10.75 24.2
Use : 24.2 tan 0.45, cot 2.22
• Links arrangement
x = (400-217)/100
400kN
= 1.83m
217kN
217kN 400kN