Earthing Resistance Calculations Is 3043
Earthing Resistance Calculations Is 3043
Earthing Resistance Calculations Is 3043
EARTHING RESISTANCE
CALCULATION
CONTRACT NO :
PROJECT :
CLIENT :
SITE :
UNDER REVIEW
CONFIDENTIAL
Index of Revisions
Rev. Sheet Prepared, revised Checked Approved Remark, kind of revision
Name Date Name Name Date Status
Table of Contents
Section Page
General Notes 4
Calcualtion Basis 5
Earthing Resistance for Strip and Pipe electroed 7
Earthing Resistance for Strip, Cable and Pipe electroed 9
3/9
GENERAL NOTES
1. This document is an annexure to GS E&C Main document " Grounding Calculations" Document no.
2. The calculations have been done based on GI Strip and Pipe data considered from IS:3043
3 The Calculations are subject to revision as & when the main document gets revised due to change in any Data
PURPOSE
This calculation describe the Grounding calculation of the
REFERANCE DOCUMENTS
1
2
3
4
5
6
4/9
The following formulas are used for the spesification IS:3043 for calculations of Main Earthing Loop Resistance for Pipe Electrode and
Strip Electrode and theselection of Cross sectional area of Earth Conductor.
5/9
The earth conductor to be selected on the basis of highest fault current, i.e., 48.69 kA at 415 Bus Voltage
Hence, the GI Strip used for the main earthing mat is 65 x 10 mm² = 1 Nos.
Total surface area of GI Strip and GI Pipe = (A)+(B) = : 279.65 Sq. Meter
EARTH RESISTANCE :
Resistance for each strip electode :
Rs = 100 x ρ loge 2L2 Ohms : 0.0784 Ohm
2ÕL wT
Nos. of Strip Electrode in parallel : 1
Resistance for all parallel Strip Eelctroed : 0.0784 Ohm ………………………………. ( C )
Resistance for all parallel GI Pipe Electroed = R2 = (Rp/N) = 0.344 Ohm …………………………………(D)
= R1 x R2 = 0.0638 Ohm
(R1 +R2)
Grounding system is valid for the combined resistance less than 1.0 Ohm
SUMMARY
A. GI STRIP ELECTRODE
SIZE OF ELECTRODE
NO. OF ELECTRODE
WIDTH (mm) HEIGHT (mm)
65 10 1
B. GI PIPE ELECTRODE
SIZE OF ELECTRODE
NO. OF ELECTRODE
LENGTH (mm) DIA (mm)
3500 50 50
7/9
Project Name Project No. Sheet / of
0 0 7/9
ELECTRICAL
EARTHING REASISTANCE CALCULATION
AS PER IS:3043
Document No. 0 Rev. No. A Class 1
The earth conductor to be selected on the basis of highest fault current, i.e., 48.69 kA at 415 Bus Voltage
Hence, the GI Strip used for the main earthing mat is 65 x 10 mm² = 1 Nos.
2ÕL wT
Nos. of Strip Electrode in parallel : 1
Resistance for all parallel Strip Eelctroed : 0.2685 Ohm ………………………………. ( A )
TOTAL EARTH RESISTANCE FOR STRIP AND CABLE R1 = (A) + (B) = 0.4290 Ohm
Grounding system is valid for the combined resistance less than 1.0 Ohm
SUMMARY
A. GI STRIP ELECTRODE
SIZE OF ELECTRODE
NO. OF ELECTRODE
WIDTH (mm) HEIGHT (mm)
65 10 1
B. EARTING CABLE
CABLE TYPE
LENGTH OF CABLE (METER)
CONDUCTOR DIA (mm²)
Cu 70 500
C. GI PIPE ELECTRODE
SIZE OF ELECTRODE
NO. OF ELECTRODE
LENGTH (mm) DIA (mm)
2500 50 8
9/9