Annex 5-Electrical Installation Certificate For Design & Construction
Annex 5-Electrical Installation Certificate For Design & Construction
Annex 5-Electrical Installation Certificate For Design & Construction
CONSTRUCTION (ANNEX 5)
(LESS THAN OR EQUAL 1.0 MW SUPPLY - LV Metered Customers)
(REQUIREMENTS FOR ELECTRICAL INSTALLATIONS - BS 7671 [IET WIRING REGULATIONS)
DETAILS OF THE CUSTOMER
Name of the Customer Customer
Electricity Account
No. and
Electric Utility
Address of the Customer Contact No./
Email/
Fax
DETAILS OF THE CONTRACTOR
SEA Registration
Name of the Contractor
No.
Contact No./
Address of the Contractor
Email/
Fax
…………..kW roof top grid connected solar power installation at the above address.
Page 1 of 3
Main Protective Conductors
Connection / continuity verified
2
Earthing conductor Material ................................ csa ..................... mm
SCHEDULES
The attached Schedules are part of this document and this Certificate is valid only when they are attached to it.
............ Schedules of Inspections are attached.
The extent of liability of the signatory or signatories is limited to the work described above as the subject of this Certificate.
a. If there are more than one inverter in the installation, provide the particulars of each inverter in the same format in additional
sheets.
b.The test certificates/ compliance certificates from independent agencies or accredited agency or one of the following institutions
in Sri Lanka, should be submitted to prove the mentioned values
Page 2 of 3
SCHEDULE OF INSPECTIONS (for new installation work only) for
ROOOF TOP SOLAR POWER INSTALLATION LESS THAN OR EQUAL TO 1 MW SUPPLY
NOTE 1: This form is suitable for many types of smaller installation, not exclusively domestic.
All items inspected in order to confirm, as appropriate, compliance with the relevant clauses in BS
7671. The list of items and associated examples where given are not exhaustive.
NOTE 2: Insert to indicate an inspection has been carried out and the result is
satisfactory, or N/Ato indicate that the inspection is not applicable to a
particular item.
ITEM Outcome
DESCRIPTION
NO See Note 2
1.1 Any connections with Earth on the D.C. side is electrically connected so as to avoid
corrosion
1.2 The protective measures of non-conducting location and earth-free local equipotential
bonding are not on the D.C. side.(712.410.3.6)
1.5 Protection by the use of Class II or equivalent insulation has been adopted on D.C.
side of cell (712.412)
1.6 Overloaded protection is omitted from the PV array string if the cable current-carrying
capacity is rated to at least 1.25 of the short circuit current. Short circuit current
protection is provided at connection to the mains(712.433.1),(712.434.1)
1.7 To minimize voltage induced by lighting, the area of all wiring loops are as small as
possible (712.444,4,4)
1.8 PV modules comply with the requirements of the relevant equipment standards.
(712.511.1)
1.9 PV modules have been installed in such a way that there is enough heat dissipation
under conditions of maximum solar radiation for the site.( 712.511.2.1)
1.10 The selection and erection of equipment shall facilitate safe maintenance (712.513.1)
1.11 PV string cables ,PV array cables and PV main D.C. cables have been selected and
erected so as to minimize the risk of Earth faults and short circuits. (712.522.8.1)
1.12 Wiring systems withstand the expected external influences such as wind, temperature
and solar radiation. (712.522.8.3)
1.13 Isolation for maintenance on D.C. and A.C. sides is provided (712.537.2.1.1)
1.15 All junction boxes carry label warning about energization after loss of
mains.(712.537.2.2.5.1)
1.16 Protective bonding conductors run in close contact with D.C. and A.C. PV system
cables (712.54)
1.17 Electrical Single line diagram of the installation is attached with the certificate.