CIRED2007 0161 Paper
CIRED2007 0161 Paper
CIRED2007 0161 Paper
! " # $ % &
0161
the PCC. It must be calculated under normal operating Rsc ⋅ ( Pcustomer + ∆Pcustomer ) + X sc ⋅ (Qcustomer + ∆Qcustomer )
∆utotal = =
conditions for the network and at maximum generation; U B2
it is used for protection coordination. Rcc ⋅ Pcustomer + X cc ⋅ Qcustomer Rcc ⋅ ∆Pcustomer + X cc ⋅ ∆Qcustomer (3)
= + =
3. Minimum operating threephase short circuit power in U B2 U B2
the PCC. It is the minimum value of the threephase short = ∆ustady − state + ∆u
circuit current in the PCC under normal operating where Rsc and Xsc are the resistive and reactive parts of the
conditions. It must be calculated at minimum generation short-circuit complex impedance Zsc.
(HV network) and with no dispersed generation (MV By focusing on the rapid variation ∆u, being the short
network). circuit power Ssc in a given bus inversely proportional to the
4. Minimum conventional threephase short circuit power in short circuit impedance Zsc in the same bus, one can obtain:
the PCC. It is the minimum value of the threephase short Rsc ⋅ ∆Pcustomer + X sc ⋅ ∆Qcustomer
circuit power under the most critical N-1 conditions of ∆u = =
U B2
the HV network (backfeed for MV network) and with
Rsc X
minimum generation (i.e. without dispersed generation ⋅ ∆Pcustomer + sc ⋅ ∆Qcustomer
on the MV network). Z Z sc
= sc
U B 2 Z sc
The last two Ssc values are useful for coordinating
Rsc X
protections (network/customer) and for evaluating power ⋅ ∆Pcustomer + sc ⋅ ∆Qcustomer
Z Z sc
quality levels. = sc =
S sc
∆Pcustomer ∆Qcustomer
CORRELATION BETWEEN SHORT CIRCUIT +
1+τ 2 1
+1
POWER AND RAPID VOLTAGE CHANGES 2
τ α (τ ) ⋅ ∆Pcustomer + β (τ ) ⋅ ∆Qcustomer
= = =
In order to analyze the rapid voltage changes (RVC) to S k '' S sc
which HV and MV customers are subject, it is possible to ∆S customer (α (τ ) ⋅ cos ϕ starting + β (τ ) ⋅ sin ϕ starting )
make reference to Figure 1, which represents the network = =
S sc
impedance upstream of the delivery point (Zsc).
∆S customer
= γ (τ , ϕ starting ) (4)
customer S sc
where cosϕstarting is the power factor of the instantaneous
power change ∆Scustomer and is the ratio (Xsc/Rsc).
Connection point As shown in Figure 2, in case of high τ values, in equation
(4) it is possible to neglect the contribution due to ∆P and to
make reference to following simpler equation (5).
∆utotal ≈ ∆Scustomer S sc (5)
Such approximation is only valid in case of HV networks,
whereas in case of MV networks it is valid only at a short
Figure 1 – Schematic diagram aimed at evaluating Ssc on HV and MV
networks
distance from the HV/MV substation (high values of Xsc/Rsc,
see Figure 2).
According to this scheme, it is possible to notice that any
Gamma Alfa Beta
variation in the current required by customers causes a RVC 1,1
on the PCC, that affects any customer connected to the same 1,05
1
! " # $ % &
0161
Table I – Kt values for connections to the HV network Table II – Kt values for connections to the MV network
(HV customers and HV-MV substations) (MV customers and MV-LV substations)
Srated Srated
Kt,HV/MV substations Kt,HV customers Kt,MV/LV substations Kt,MV customers
(kVA) (kVA)
16 0,30 0,50 100 2,00 4,00
25 0,25 0,40 250 1,60 2,80
40 0,20 0,30 400 1,50 2,50
63 0,15 0,25 630 1,43 2,30
1000 - 1,80
2500 - 1,30
A possible interpolation (dotted line in Figure 2) between 5000 - 0,80
the values given to parameter Kt in the above tables and a
continuous function of Srated is the following:
Figure 4 shows the values of Kt for MV networks, along
HV and MV customers :
with the relevant interpolating function.
K t ,customer = 2 S rated (7)
5
Kt
KtUtenti
Cust
K t ,substation = 1,3 S rated (8)
4
3.5
Kt (1)
KtCabine
Subst
Kt
KtUtenti
Cust
Kt
KtCabine
Subst
It is important to notice that in this formula, which is valid
3
Kt 2.5
for both HV and MV networks, Srated is expressed in MVA.
2
1.5
0,7
Kt Cust 1
0,6
Kt Subst 0.5
Kt Cust
0,5 0
Kt Subst
0 0.5 1 1.5 2 2.5 3 3.5 4 4.5 5 5.5 6
0,4
Kt
MVA
0,3
0,2
MVA
40 50 60 70
In case of energization of HV/MV or MV/LV transformers
(inrush current), the parameter Kt would certainly be higher,
Fi as it can even reach 4-6 or 6-11 respectively. However, it
gure 3 – Discrete values and interpolating function
has to be noticed that the energization is not usually carried
for Kt on HV networks
! " # $ % '&
0161
out during ordinary service; for this reason, it is not taken connected shows a minimum conventional Ssc below the
into consideration in the present methodology. threshold value for rapid variations of 5%.
CORRELATION AMONG VOLTAGE Sk'' max operating
CHANGES, Ssc, AND CUSTOMER RATED
5000
Sk'' min operating
Sk'' min conventional
POWER THROUGH PARAMETER KT
4500
Threshold deltaU=3% for customers
4000 Threshold deltaU=5% for customers
Sk'' [MVA]
2500
MV network) according to the following equation:
2000
∆S
∆u = customer γ (τ , ϕ starting ) = 1500
S sc (9) 1000
S S
= K t ⋅ customer γ (τ , ϕ starting ) ≈ Kt ⋅ customer 500
S sc S sc 0
0 20 40 60 80 100 120 140
voltage variation to be expected on the PCC (∆ulim) MV Figure 4 – Application of the methodology proposed to the analysis of
networks and the parameter Kt related to the power variation Ssc on the RTN: busses with HV customers
that the customer requires, it is possible to calculate the
value of Ssc necessary for each network bus: CONCLUSION – ONGOING RESEARCH
Scustomer (10) The paper proposes a methodology to correlate rapid
S sc ≈ Kt ⋅ voltage changes to the load variation and to the short circuit
∆u
For instance, if relations (8) e (9) are adopted for Kt and if a power in the point of common coupling.
maximum rapid voltage change of 5% is to be expected in The method has been based on theoretical considerations
the PCC, this results in: and studies: as a consequence, further investigations are
needed about the assumptions adopted.
HV and MV customers: In particular, field studies and analysis are needed to assess
S sc ,cust ,5 = 40 S rated (11) if the behaviour of customers (in terms of fast load
variations) is correctly modelled by the parameters Kt.
HV/MV and MV/LV substations: Once such parameters will be confirmed with on-field
S sc ,subst ,5 = 26 Srated (12) evidence, it will be possible to make use of the proposed
approach by a regulatory point of view.
Some first results indicate that the short circuit power levels
APPLICATION OF THE METHODOLOGY available on the Italian HV networks (132-150 kV) are
The application of the above-described methodology to the typically higher than the minimum levels calculated with the
analysis of the Ssc on the busses of the Italian Transmission procedure proposed.
Network1 (RTN – “Rete di trasmissione nazionale”) gave As for MV networks, the data collected from the monitoring
some interesting results. campaign on the voltage quality will allow for a better
In particular, none of the busses to which HV/MV tuning of the parameters used in the methodology proposed.
substations are connected shows a minimum operating Ssc or
a conventional minimum Ssc (N-1) lower than the prescribed REFERENCES
values. [1] Towards Voltage Quality Regulation in Europe: An
As regards customers, the results are as follows (see also ERGEG Public Consultation Paper, E06-EQS-09-03
Figure 4): 06-DEC-2006 available on www.ceer-eu.org
• none of the busses to which HV customers are [2] Italian Regulator Resolution n. 250/04, available on
connected shows a minimum operating Ssc below the www.autorita.energia.it
threshold value for rapid variations of 3%; [3] Consultation document 34/06, about technical rules
• there is an extremely limited number of busses with a for the connection to HV and MV distribution
minimum conventional Ssc below the threshold value for networks, available on www.autorita.energia.it
rapid variations of 3%; nevertheless, it is far above the [4] F. Villa, A. Porrino, R. Chiumeo, S. Malgarotti, “The
threshold value for rapid variation of 5%; power quality monitoring of the MV network
promoted by the Italian regulator. Objectives,
• none of the busses to which HV customers are organisation issues, 2006 statistics", Proc. of CIRED
2007- Wien
1 The Ssc values on RTN are communicated by TERNA (Italian TSO)
according to Italian Regulator Deliberation n. 250/04.
! " # $ % &