Danfoss 131B0312 Programming Guide PDF
Danfoss 131B0312 Programming Guide PDF
Programming Guide
VLTp AutomationDrive
MG33MD22
Contents
1 Introduction 1-1
1.1.1 Approvals 1-1
1.1.2 Symbols 1-1
1.1.3 Abbreviations 1-1
1.1.4 Definitions 1-2
1.1.5 Electrical Wiring - Control Cables 1-6
5 Troubleshooting 5-1
5.1.1 Warnings/Alarm Messages 5-1
6 Index 6-1
1 1
1 Introduction
1.1.3 Abbreviations
Programming Guide
Software version: 6.5x Alternating current AC
American wire gauge AWG
This Programming Guide can be used for all FC 300 adjustable Ampere/AMP A
frequency drives with software version 6.5x. Automatic Motor Adaptation AMA
The software version number can be seen from 15-43 Software Current limit ILIM
Version. Degrees Celsius °C
Direct current DC
1.1.1 Approvals Drive Dependent D-TYPE
Electro Magnetic Compatibility EMC
Electronic Thermal Relay ETR
Adjustable frequency drive FC
Gram g
Hertz Hz
Horsepower hp
Kilohertz kHz
Local Control Panel LCP
Meter m
Millihenry Inductance mH
1.1.2 Symbols Milliampere mA
Millisecond ms
Symbols used in this guide.
Minute min
Motion Control Tool MCT
NOTE! Nanofarad nF
Indicates something to be noted by the reader. Newton Meters Nm
Nominal motor current IM,N
1 1
1.1.4 Definitions PM,N
Rated motor power (nameplate data in kW or HP).
Adjustable frequency drive:
IVLT,MAX TM,N
Maximum output current. Rated torque (motor).
IVLT,N
Rated output current supplied by the Adjustable frequency UM
drive. Instantaneous motor voltage.
UVLT, MAX
UM,N
Maximum output voltage.
Rated motor voltage (nameplate data).
Input:
Control command
Break-away torque
Start and stop the connected motor by means of LCP and
digital inputs.
Torque
Functions are divided into two groups.
175ZA078.10
Functions in group 1 have higher priority than functions in Pull-out
group 2.
Motor:
Motor Running
Torque generated on output shaft and speed from zero
rpm to max. speed on motor.
rpm
fJOG
Motor frequency when the jog function is activated (via
digital terminals). ηVLT
fM The efficiency of the Adjustable frequency drive is defined
Motor frequency. as the ratio between the power output and the power
input.
fMAX
Maximum motor frequency.
Start-disable command
fMIN A stop command belonging to the group 1 control
Minimum motor frequency. commands - see this group.
fM,N
Rated motor frequency (nameplate data). Stop command
IM See Control commands.
Motor current (actual).
References:
IM,N
Analog Reference
Rated motor current (nameplate data).
A signal transmitted to the analog inputs 53 or 54, can be
nM,N voltage or current.
Rated motor speed (nameplate data).
Binary Reference
ns A signal transmitted to the serial communication port.
Synchronous motor speed
Preset Reference
A defined preset reference to be set from -100% to +100%
2 × par . 1 − 23 × 60 s
ns = of the reference range. Selection of eight preset references
par . 1 − 39
via the digital terminals.
1 1
Pulse Reference Initializing
A pulse frequency signal transmitted to the digital inputs If initialization is carried out (14-22 Operation Mode), the
(terminal 29 or 33). Adjustable frequency drive returns to the default setting.
RefMAX Intermittent Duty Cycle
Determines the relationship between the reference input An intermittent duty rating refers to a sequence of duty
at 100% full scale value (typically 10 V, 20 mA) and the cycles. Each cycle consists of an on-load and an off-load
resulting reference. The maximum reference value set in period. The operation can be either periodic duty or non-
3-03 Maximum Reference. periodic duty.
RefMIN LCP
Determines the relationship between the reference input The Local Control Panel makes up a complete interface for
at 0% value (typically 0 V, 0 mA, 4 mA) and the resulting control and programming of the Adjustable frequency
reference. The minimum reference value set in drive. The control panel is detachable and can be installed
3-02 Minimum Reference. up to 10 ft [3 m] from the Adjustable frequency drive, i.e.,
in a front panel by means of the installation kit option.
Miscellaneous:
Analog Inputs lsb
The analog inputs are used for controlling various Least significant bit.
functions of the Adjustable frequency drive. msb
There are two types of analog inputs: Most significant bit.
Current input, 0-20 mA and 4-20 mA
Voltage input, 0-10 V DC (FC 301) MCM
Voltage input, -10 - +10 V DC (FC 302FC 102). Short for Mille Circular Mil, an American measuring unit for
cable cross-section. 1 MCM = 0.5067 mm2.
Analog Outputs
The analog outputs can supply a signal of 0–20 mA, 4–20 Online/Offline Parameters
mA. Changes to online parameters are activated immediately
after the data value is changed. Changes to offline
Automatic Motor Adaptation, AMA
parameters are not activated until you enter [OK] on the
AMA algorithm determines the electrical parameters for
LCP.
the connected motor at standstill.
Process PID
Brake Resistor
The PID control maintains the desired speed, pressure,
The brake resistor is a module capable of absorbing the
temperature, etc. by adjusting the output frequency to
braking energy generated in regenerative braking. This
match the varying load.
regenerative braking energy increases the intermediate
circuit voltage and a brake chopper ensures that the PCD
power is transmitted to the brake resistor. Process Control Data
1 1
Slip Compensation Power Factor
The Adjustable frequency drive compensates for the motor The power factor is the relation between I1 and IRMS.
slip by giving the frequency a supplement that follows the
measured motor load keeping the motor speed almost 3 x U x I 1 cos ϕ
Power factor =
constant. 3 x U x I RMS
Smart Logic Control (SLC) The power factor for 3-phase control:
The SLC is a sequence of user-defined actions executed
when the associated user-defined events are evaluated as I 1 x cos ϕ1 I1
= = since cos ϕ1 = 1
I RMS I RMS
true by the Smart Logic Controller. (Par. group 13-** Smart
Logic Control (SLC). The power factor indicates to which extent the Adjustable
frequency drive imposes a load on the line power supply.
STW
The lower the power factor, the higher the IRMS for the
Status Word
same hp [kW] performance.
FC Standard Bus
Includes RS-485 bus with FC protocol or MC protocol. See I RMS = I 12 + I 52 + I 72 + .. + I n2
8-30 Protocol.
In addition, a high power factor indicates that the different
Thermistor harmonic currents are low.
A temperature-dependent resistor placed where the The adjustable frequency drive's built-in DC coils produce a
temperature is to be monitored (Adjustable frequency high power factor, which minimizes the imposed load on
drive or motor). the line power supply.
Trip
A state entered in fault situations, e.g., if the Adjustable WARNING
frequency drive is subject to an over-temperature or when The voltage of the Adjustable frequency drive is dangerous
the Adjustable frequency drive is protecting the motor, whenever connected to line power. Incorrect installation of
process or mechanism. Restart is prevented until the cause the motor, Adjustable frequency drive or serial communi-
of the fault has disappeared and the trip state is cancelled cation bus may cause death, serious personal injury or
by activating reset or, in some cases, by being damage to the equipment. Consequently, the instructions
programmed to reset automatically. Trip may not be used in this manual, as well as national and local rules and
for personal safety. safety regulations, must be complied with.
Trip Locked
A state entered in fault situations when the Adjustable Safety Regulations
frequency drive is protecting itself and requiring physical 1. The line power supply to the Adjustable
intervention, e.g., if the Adjustable frequency drive is frequency drive must be disconnected whenever
subject to a short circuit on the output. A locked trip can repair work is to be carried out. Make sure that
only be canceled by cutting off line power, removing the the line power supply has been disconnected and
cause of the fault, and reconnecting the Adjustable that the necessary time has elapsed before
frequency drive. Restart is prevented until the trip state is removing motor and line power supply plugs.
cancelled by activating reset or, in some cases, by being 2. The [OFF] button on the control panel of the
programmed to reset automatically. Trip may not be used Adjustable frequency drive does not disconnect
for personal safety. the line power supply and consequently it must
VT Characteristics not be used as a safety switch.
Variable torque characteristics used for pumps and fans. 3. The equipment must be properly grounded, the
user must be protected against supply voltage
VVCplus
and the motor must be protected against
If compared with standard voltage/frequency ratio control,
overload in accordance with applicable national
Voltage Vector Control (VVCplus ) improves the dynamics
and local regulations.
and the stability, both when the speed reference is
changed and in relation to the load torque. 4. The ground leakage current exceeds 3.5 mA.
5. Protection against motor overload is not included
60° AVM in the factory setting. If this function is desired,
Switching pattern called 60° Asynchronous Vector set 1-90 Motor Thermal Protection to data value
Modulation (14-00 Switching Pattern). ETR trip 1 [4] or data value ETR warning 1 [3].
1 1
6. Do not remove the plugs for the motor and line activated in error, be delayed or fail to occur
power supply while the Adjustable frequency entirely. When used in situations where safety is
drive is connected to line power. Make sure that critical, e.g., when controlling the electromagnetic
the line power supply has been disconnected and brake function of a hoist application, these
that the necessary time has elapsed before control signals must not be relied on exclusively.
removing motor and line power plugs.
7. Please note that the Adjustable frequency drive
WARNING
has more voltage sources than L1, L2 and L3, High Voltage
when load sharing (linking of DC intermediate Touching the electrical parts may be fatal - even after the
circuit) or external 24 V DC are installed. Make equipment has been disconnected from line power.
sure that all voltage sources have been discon- Also make sure that other voltage inputs have been
nected and that the necessary time has elapsed disconnected, such as external 24V DC, load sharing
before commencing repair work. (linkage of DC intermediate circuit), as well as the motor
connection for kinetic backup.
Warning against unintended start
Systems where adjustable frequency drives are installed
1. The motor can be brought to a stop by means of
must, if necessary, be equipped with additional monitoring
digital commands, bus commands, references or
and protective devices according to the valid safety
a local stop, while the Adjustable frequency drive
regulations, e.g., law on mechanical tools, regulations for
is connected to line power. If personal safety
the prevention of accidents, etc. Modifications on the
considerations (e.g., risk of personal injury caused
adjustable frequency drives by means of the operating
by contact with moving machine parts following
software are allowed.
an unintentional start) make it necessary to
ensure that no unintended start occurs, these
stop functions are not sufficient. In such cases, NOTE!
the line power supply must be disconnected or Hazardous situations shall be identified by the machine
the Safe Stop function must be activated. builder/ integrator who is responsible for taking necessary
preventive means into consideration. Additional
2. The motor may start while setting the
monitoring and protective devices may be included, always
parameters. If this means that personal safety
according to valid national safety regulations, e.g., law on
may be compromised (e.g., personal injury caused
mechanical tools, regulations for the prevention of
by contact with moving machine parts), motor
accidents.
starting must be prevented, for instance by use
of the Safe Stop function or secure disconnection
of the motor connection. NOTE!
Crane, Lifts and Hoists:
3. A motor that has been stopped with the line
The controlling of external brakes must always have a
power supply connected may start if faults occur
redundant system. The Adjustable frequency drive can in
in the electronics of the Adjustable frequency
no circumstances be the primary safety circuit. Comply
drive through temporary overload or if a fault in
with relevant standards, e.g.,
the power supply grid or motor connection is
Hoists and cranes: IEC 60204-32
remedied. If unintended start must be prevented
Lifts: EN 81
for personal safety reasons (e.g., risk of injury
caused by contact with moving machine parts),
the normal stop functions of the Adjustable Protection Mode
frequency drive are not sufficient. In such cases, Once a hardware limit on motor current or DC link voltage
the line power supply must be disconnected or is exceeded, the Adjustable frequency drive will enter
the Safe Stop function must be activated. “Protection mode”. “Protection mode” means a change of
the PWM modulation strategy and a low switching
NOTE! frequency to minimize losses. This continues 10 sec after
When using the Safe Stop function, always follow the the last fault and increases the reliability and the
instructions in the section Safe Stop of the VLT robustness of the Adjustable frequency drive while re-
AutomationDrive Design Guide. establishing full control of the motor.
In hoist applications, “protection mode” is not usable
4. Control signals from or internally within the because the Adjustable frequency drive will usually not be
Adjustable frequency drive may in rare cases be able to leave this mode again and therefore it will extend
the time before activating the brake – which is not
recommended.
1 1
The “protection mode” can be disabled by setting NOTE!
14-26 Trip Delay at Inverter Fault to zero which means that It is recommended to disable protection mode in hoisting
the Adjustable frequency drive will trip immediately if one applications (14-26 Trip Delay at Inverter Fault = 0)
of the hardware limits is exceeded.
1 1
In rare cases, and depending on the installation, very long control cables and analog signals may result in 50/60 Hz ground
loops due to noise from line power supply cables.
If this occurs, it may be necessary to break the shield or insert a 100 nF capacitor between shield and chassis.
The digital and analog inputs and outputs must be connected separately to the common inputs (terminal 20, 55, 39) of the
Adjustable frequency drive to avoid ground currents from both groups to affect other groups. For example, switching on
the digital input may disturb the analog input signal.
130BA681.10
PNP (Source) 130BT106.10
+24 V DC
12 13 18 19 27 29 32 33 20 37
130BT107.11
+24 V DC
0 VDC
NPN (Sink)
Digital input wiring
12 13 18 19 27 29 32 33 20 37
1.1.6 Start/Stop
NOTE!
Control cables must be shielded/armored.
1 1
1.1.8 Speed Up/Down
130BA021.12
12 +24V
18 Par. 5-10
1.1.7 Pulse Start/Stop
27 Par. 5-12
Terminal 18 = 5-10 Terminal 18 Digital InputLatched start,
[9]
Terminal 27= 5-12 Terminal 27 Digital InputStop inverse, [6]
29 Par. 5-13
Terminal 37 = Safe stop (where available)
32 Par. 5-14
37
1 1
1 1
2 How to Program
2 2
130BA018.13
2.1 The Graphical and Numerical Local
Control Panels
Status 1(0) a
The easiest programming of the Adjustable frequency
1234rpm 10,4A 43,5Hz
drive is performed by the Graphical LCP (LCP 102). It is
necessary to consult the Adjustable frequency drive Design
Guide, when using the Numeric Local Control Panel (LCP 1 b
101). 43,5Hz
Ca
ck
n
Ba
ce
l
2. Menu keys and LEDs - changing parameters and
switching between display functions.
3. Navigation keys and LEDs (LEDs).
Info
3 On OK
4. Operation keys and LEDs.
Warn.
All data is displayed in a graphical LCP display, which can
show up to five items of operating data while displaying Alarm
[Status].
Hand Auto
Display lines 4
on Off on Reset
a. Status line: Status messages displaying icons and
graphic.
b. Line 1-2: Operator data lines displaying data
defined or chosen by the user. By pressing the 2.1.2 The LCD Display
[Status] key, up to one extra line can be added.
The LCD display has back lighting and a total of 6 alpha-
c. Status line: Status messages displaying text.
numeric lines. The display lines show the direction of
rotation (arrow), the chosen Set-up as well as the
programming Set-up. The display is divided into three
sections.
130BP074.10
2 2
Status ! 1(1)
Top section below the display and LEDs are used for parameter set-up,
43 RPM 5.44 A 25.3 kW
including choice of display indication during normal
1.4 Hz operation.
Middle section
2.9%
130BP045.10
Quick Main Alarm
! Pwr.card temp (W29) Status
Menu Menu Log
Bottom section
Auto Remote Running
• Quick Set-up
LEDs
• Changes Made
Info NOTE!
An active HAND-OFF-AUTO signal via the digital inputs has
higher priority than the control keys [Hand on] – [Auto on].
Navigation Keys
The four navigation arrows are used to navigate between [Reset] is used for resetting the Adjustable frequency drive
the different choices available in [Quick Menu], [Main after an alarm (trip). It can be selected as Enable [1] or
Menu] and [Alarm Log]. Use the keys to move the cursor. Disable [0] via 0-43 [Reset] Key on LCP.
[OK] is used for choosing a parameter marked by the The parameter shortcut can be carried out by holding
cursor and for enabling the change of a parameter. down the [Main Menu] key for 3 seconds. The parameter
shortcut allows direct access to any parameter.
Local Control Key for local control is found at the bottom
of the LCP. 2.1.3 Quick Transfer of Parameter Settings
between Multiple Adjustable
Frequency Drives
130BP046.10
Hand
Off
Auto
Reset Once the set-up of a Adjustable frequency drive is
on on
complete, we recommend that you store the data in the
LCP or on a PC via MCT 10 Set-up Software Tool.
drive via the LCP. [Hand on] also starts the motor, and it is
Alarm
now possible to enter the motor speed data by means of Status
Quick Main
Log
Menu Menu
the arrow keys. The key can be selected as Enable [1] or
Disable [0] via 0-40 [Hand on] Key on LCP
External stop signals activated by means of control signals
Ca
n
Ba
ce
l
On OK
• [Hand on] - [Off] - [Auto on]
• Reset Warn.
• Reversing
• Hand Auto
Set-up select bit 0 - Set-up select bit 1 on
Off on Reset
• Quick stop
Data storage in LCP digits after a possible decimal point. The larger the
2 2 1. Go to 0-50 LCP Copy numeric value for a parameter, the fewer digits displayed
after the decimal point.
2. Press the [OK] key
Ex.: Current readout 5.25A; 15.2A 105A.
3. Select “All to LCP”
4. Press the [OK] key Operating variable: Unit:
All parameter settings are now stored in the LCP indicated 16-00 Control Word hex
by the progress bar. When 100% is reached, press [OK]. 16-01 Reference [Unit] [unit]
16-02 Reference [%] %
130BP063.10
2 2
Status 1 (1)
16-85 FC Port CTW 1 hex 778 RPM 0.86 A 4.0 kW
16-86 FC Port REF 1 hex
16-90 Alarm Word State: 0 off 0 (off )
When: -
16-92 Warning Word Do: -
16-94 Ext. Status Word
Auto Remote Running
Status screen I
This readout state is standard after start-up or initialization. 2.1.6 Parameter Set-up
Use [INFO] to obtain information about the measurement
links to the displayed operating variables (1.1, 1.2, 1.3, 2 The Adjustable frequency drive can be used for practically
and 3). all assignments, which is why the number of parameters is
See the operating variables shown in the screen below. quite large. The Adjustable frequency drive offers a choice
between two programming modes - a Main Menu and a
Quick Menu mode.
130BP041.10
Status 1 (1)
799 RPM 7.83 A 36.4 kW The former provides access to all parameters. The latter
1.1 takes the user through a few parameters making it
0.000 possible to start operating the Adjustable frequency drive.
1.2
Regardless of the mode of programming, you can change
53.2% a parameter both in the main menu and quick menu
2
Auto Remote Ramping modes.
Status 1 (1)
207RPM 5.25A 24.4 kW
1.1
6.9Hz 1.3
1.2
Auto Remote Running
Parameter Setting
2 2 0-01 Language
1-20 Motor Power [kW] [kW]
1-22 Motor Voltage [V]
1-23 Motor Frequency [Hz]
1-24 Motor Current [A]
1-25 Motor Nominal Speed [rpm]
5-12 Terminal 27 Digital Input [0] No function*
1-29 Automatic Motor [1] Enable complete AMA
Adaptation (AMA)
3-02 Minimum Reference [rpm]
3-03 Maximum Reference [rpm]
3-41 Ramp 1 Ramp up Time [sec]
3-42 Ramp 1 Ramp Down Time [sec]
3-13 Reference Site
Press
Quick
Menu Q2 Quick Menu OK
130BP066.10
1107 RPM 3.84 A 1 (1)
Main Menu 2.1.12 Changing a Text Value
0 - ** Operation/Display
If the selected parameter is a text value, change the text
1 - ** Load/Motor
2 - ** Brakes
value with the [▲] [▼] navigation keys.
The up key increases the value, and the down key
3 - ** Reference / Ramps
decreases the value. Place the cursor on the value you
want to save and press [OK].
130BP068.10
same regardless of the programming mode. In main menu 740RPM 10.64 A 1 [1]
Basic Settings 0-0*
mode, the parameters are divided into groups. The first
digit of the parameter number (from the left) indicates the 0 -01 Language
15-30 Fault Log: Error Code to 15-32 Alarm Log: Time contain
130BP070.10
2 2
729RPM 6.21A 1(1)
Load depen. setting 1- 6* a fault log which can be read out. Choose a parameter,
press [OK], and use the [▲] [▼] navigation keys to scroll
1 - 60 Low speed load
compensation through the value log.
16 0%
Use 3-10 Preset Reference as another example:
Choose the parameter, press [OK], and use the [▲] [▼]
navigation keys to scroll through the indexed values. To
2.1.14 Infinitely Variable Change of change the parameter value, select the indexed value and
Numeric Data Value press [OK]. Change the value by using the [▲] [▼] keys.
Press [OK] to accept the new setting. Press [CANCEL] to
If the chosen parameter represents a numeric data value, abort. Press [Back] to leave the parameter.
select a digit with the [◀] [▶] navigation keys.
2.1.17 How to Program on the Numerical
Local Control Panel
130BP073.10
1. Numerical display.
2. Menu keys and LEDs - changing parameters and
switching between display functions.
3. Navigation keys and LEDs (LEDs).
Change the selected digit infinitely variably with the [▲] 4. Operation keys and LEDs.
[▼] navigation keys.
Display line: Status messages displaying icons and numeric
The chosen digit is indicated by the cursor. Place the
value.
cursor on the digit you want to save and press [OK].
LEDs
130BP072.10
22.8
LCP keys
130BP077.10
2 2 [Menu] Select one of the following modes:
rpm
• Status Setup 1
• Quick Setup
• Main Menu
A 17
130BP078.10
130BA191.10
Setup 1
3 On OK
[Back] for stepping backwards
Arrow [▲] [▼] keys are used for navigating between
Warn.
commands and within parameters.
Alarm
Auto 130BP079.10
4 Hand Reset
Off
on on
Status Mode
P 2-03 Setup 1
NOTE!
Parameter copy is not possible with LCP 101 Numerical
Local Control Panel.
130BP046.10
Recommended initialization (via 14-22 Operation Mode)
Hand Auto
Off Reset
on on
1. Select 14-22 Operation Mode
2. Press [OK]
3. Select “Initialization”
[Hand on] enables control of the Adjustable frequency
4. Press [OK]
drive via the LCP. [Hand on] also starts the motor and it is
5. Cut off the line power supply and wait until the display
now possible to enter the motor speed data by means of
turns off.
the arrow keys. The key can be selected as Enable [1] og
6. Reconnect the line power supply - the Adjustable frequency
Disable [0] via 0-40 [Hand on] Key on LCP.
drive is now reset.
External stop signals activated by means of control signals
or a serial bus will override a 'start' command via the LCP.
The following control signals will still be active when 14-22 Operation Mode initializes all except:
[Hand on] is activated: 14-50 RFI Filter
8-30 Protocol
2 2
3 Parameter Descriptions
• Mechanical brake
• Overvoltage Control
3-** References and ramping parameters includes DigiPot
function
0-01 Language
3.2 Parameters: 0-** Operation and Display Option: Function:
Polski Part of Language package 4
Parameters related to the fundamental functions of the
3 3 Adjustable frequency drive, function of the LCP buttons
Russian Part of Language package 3
130BP075.10
3 3
OR
130BP076.10
After the link is complete, 0-13 Readout: Linked
Set-ups will read {1,2} to indicate that all ‘not
changeable during operation’ parameters are
now the same in Set-up 1 and Set-up 2. If there
are changes to a "not changeable during
0-12 This Set-up Linked to operation" parameter, e.g., 1-30 Stator Resistance
Option: Function: (Rs) in Set-up 2, they will also be changed
automatically in Set-up 1. A switch between
To enable conflict-free changes from one set-up
Set-up 1 and Set-up 2 during operation is now
to another during operation, link set-ups
possible.
containing parameters that are not changeable
during operation. The link will ensure the [0] * Not linked
proper synchronization of the ‘not changeable [1] Set-up 1
during operation’ parameter values when [2] Set-up 2
moving from one set-up to another during [3] Set-up 3
operation. ‘Not changeable during operation’ [4] Set-up 4
parameters can be identified by the label FALSE
in the parameter lists in the section Parameter
Lists.
0-20 Display Line 1.1 Small 0-20 Display Line 1.1 Small
Option: Function: Option: Function:
[1614] Motor Current Phase current of the motor [1651] Pulse Reference Frequency in Hz connected to
frequency from the Adjustable [1652] Feedback [Unit] Reference value from
frequency drive in percent. programmed digital input(s).
[1616] Torque [Nm] Actual motor torque in Nm [1653] Digi Pot Reference
[1617] * Speed [RPM] Speed in RPM (revolutions per [1657] Feedback [RPM]
minute), i.e., the motor shaft [1660] Digital Input Signal states form the 6 digital
speed in closed-loop. terminals (18, 19, 27, 29, 32 and
33). There are 16 bits in total,
[1618] Motor Thermal Thermal load on the motor,
but only six of them are used.
calculated by the ETR function.
Input 18 corresponds to the
[1619] KTY sensor leftmost of the used bits. Signal
temperature low = 0; Signal high = 1.
[1620] Motor Angle [1661] Terminal 53 Switch Setting of input terminal 54.
[1621] Torque [%] High Res. Setting Current = 0; Voltage = 1.
[1622] Torque [%] Present motor load as a
[1662] Analog Input 53 Actual value at input 53 either
percentage of the rated motor
as a reference or protection
torque.
value.
[1625] Torque [Nm] High
[1663] Terminal 54 Switch Setting of input terminal 54.
[1630] DC Link Voltage Intermediate circuit voltage in
Setting Current = 0; Voltage = 1.
the Adjustable frequency drive.
[1664] Analog Input 54 Actual value at input 54 either
[1632] Brake Energy /s Present braking energy
as reference or protection value.
transferred to an external brake
resistor. [1665] Analog Output 42 Actual value at output 42 in mA.
Stated as an instantaneous [mA] Use 6-50 Terminal 42 Output to
value. select the value to be shown.
[1633] Brake Energy /2 min Braking energy transferred to an [1666] Digital Output [bin] Binary value of all digital
external brake resistor. The mean outputs.
power is calculated continuously [1667] Freq. Input #29 [Hz] Actual value of the frequency
for the most recent 120 seconds. applied at terminal 29 as an
[1634] Heatsink Temp. Present heatsink temperature of impulse input.
the Adjustable frequency drive. [1668] Freq. Input #33 [Hz] Actual value of the frequency
The cut-out limit is 203°±9°F [95° applied at terminal 33 as an
±5°C]; cutting back in occurs at impulse input.
158°F ±9°F [70°C ± 5°C].
[1669] Pulse Output #27 Actual value of impulses applied
[1635] Inverter Thermal Percentage load of the inverters. [Hz] to terminal 27 in digital output
[1636] Inv. Nom. Current Nominal current of the mode.
Adjustable frequency drive. [1670] Pulse Output #29 Actual value of impulses applied
[1637] Inv. Max. Current Maximum current of the [Hz] to terminal 29 in digital output
Adjustable frequency drive. mode.
[1638] SL Controller State State of the event executed by [1671] Relay Output [bin]
the control. [1672] Counter A Application dependent (e.g., SLC
Control)
[1639] Control Card Temp. Temperature of the control card.
[1673] Counter B Application dependent (e.g., SLC
[1650] External Reference Sum of the external reference as
Control)
a percentage, i.e., the sum of
analog/pulse/bus. [1674] Prec. Stop Counter Display the actual counter value.
0-20 Display Line 1.1 Small 0-20 Display Line 1.1 Small
Option: Function: Option: Function:
[1675] Analog In X30/11 Actual value at input X30/11 [3019] Wobble Delta Freq.
either as reference or protection
value. [3110]
Scaled
Bypass Status Word 3 3
[1676] Analog In X30/12 Actual value at input X30/12 [3111] Bypass Running
either as reference or protection Hours
value. [3401] PCD 1 Write to MCO
[3402] PCD 2 Write to MCO
[1677] Analog Out X30/8 Actual value at output X30/8 in
[3403] PCD 3 Write to MCO
[mA] mA. Use 6-60 Terminal X30/8
[3404] PCD 4 Write to MCO
Output to select the value to be
[3405] PCD 5 Write to MCO
shown.
[3406] PCD 6 Write to MCO
[1678] Analog Out X45/1
[3407] PCD 7 Write to MCO
[mA]
[3408] PCD 8 Write to MCO
[1679] Analog Out X45/3
[3409] PCD 9 Write to MCO
[mA]
[3410] PCD 10 Write to MCO
[1680] Fieldbus CTW 1 Control word (CTW) received
[3421] PCD 1 Read from
from the bus master.
MCO
[1682] Fieldbus REF 1 Main reference value sent with [3422] PCD 2 Read from
control word from the bus MCO
master. [3423] PCD 3 Read from
[1684] Comm. Option STW Extended serial communication MCO
option status word. [3424] PCD 4 Read from
MCO
[1685] FC Port CTW 1 Control word (CTW) received
[3425] PCD 5 Read from
from the bus master.
MCO
[1686] FC Port REF 1 Status word (STW) sent to the [3426] PCD 6 Read from
bus master. MCO
[1690] Alarm Word One or more alarms in a Hex [3427] PCD 7 Read from
code. MCO
[3428] PCD 8 Read from
[1691] Alarm Word 2 One or more alarms in a Hex
MCO
code.
[3429] PCD 9 Read from
[1692] Warning Word One or more warnings in a Hex MCO
code. [3430] PCD 10 Read from
[1693] Warning Word 2 One or more warnings in a Hex MCO
code. [3440] Digital Inputs
[3441] Digital Outputs
[1694] Ext. Status Word One or more status conditions in
[3450] Actual Position
a Hex code.
[3451] Commanded Position
[1836] Analog Input X48/2
[3452] Actual Master
[mA]
Position
[1837] Temp. Input X48/4
[3453] Slave Index Position
[1838] Temp. Input X48/7
[3454] Master Index Position
[1839] Temp. Input X48/10
[3455] Curve Position
[1860] Digital Input 2
[3456] Track Error
[1890] Process PID Error
[3457] Synchronizing Error
[1891] Process PID Output
[3458] Actual Velocity
[1892] Process PID Clamped
[3459] Actual Master
Output
Velocity
[1893] Process PID Gain
[3460] Synchronizing Status
Scaled Output
3 3 [3462]
[3464]
Program Status
MCO 302 Status
dependent* 9999 ] the Q1 Personal Menu, accessible via
the [Quick Menu] key on the LCP. The
[3465] MCO 302 Control parameters will be displayed in the Q1
[3470] MCO Alarm Word 1 Personal menu in the order they are
[3471] MCO Alarm Word 2 programmed into this array parameter.
[4285] Active Safe Func. Delete parameters by setting the value
[4286] Safe Option Info to ‘0000’.
[9913] Idle time For example, this can be used to
[9914] Paramdb requests in provide quick, simple access to just one
queue or up to 50 parameters which require
changing on a regular basis (e.g., for
[9917] tCon1 time
plant maintenance reasons) or by an
[9918] tCon2 time
OEM to enable simple commissioning of
[9919] Time Optimize
their equipment.
Measure
[9920] HS Temp. (PC1)
[9921] HS Temp. (PC2) 3.2.4 0-3* LCP Custom Readout
[9922] HS Temp. (PC3)
[9923] HS Temp. (PC4) It is possible to customize the display elements for various
[9924] HS Temp. (PC5) purposes: *Custom Readout. Value proportional to speed
[9925] HS Temp. (PC6) (linear, squared or cubed depending on unit selected in
[9926] HS Temp. (PC7) 0-30 Custom Readout Unit) *Display Text. Text string stored
[9927] HS Temp. (PC8) in a parameter.
[1] * Enabled
3.2.5 0-4* LCP Keypad
[2] Password Avoids unauthorized resetting. If
0-43 [Reset] Key on LCP is included in the
Enable, disable and password protect individual keys on
Quick Menu, then define the password in
the LCP.
0-65 Quick Menu Password.
0-40 [Hand on] Key on LCP
[7] Enabled Resets the Adjustable frequency drive
Option: Function: without OFF without setting it in Off mode.
[0] * Disabled No effect when [Hand on] is pressed.
[8] Password Resets the Adjustable frequency drive
Select [0] Disabled to avoid accidental
without OFF without setting it in Off mode. A password
start of the Adjustable frequency drive in
is required when pressing [Reset] (see [2]).
Hand on mode.
[4] Hand Off/On Same as [3] but a password is required [2] All from LCP Copies all parameters in all set-ups
w. Passw. (see [2]). from the LCP memory to the
Adjustable frequency drive memory.
[9] Enabled, ref =
0
3.3 Parameters: 1-** Load and Motor 1-01 Motor Control Principle
Option: Function:
3.3.1 1-0* General Settings
Select which motor control principle to
[4] Torque open Enables the use of torque open-loop in VVC+ 1-02 Flux Motor Feedback Source
loop mode (1-01 Motor Control Principle). The
Option: Function:
torque PID parameters are set in parameter
Select the interface at which to receive
group 7-1*.
feedback from the motor.
[5] Wobble Enables the wobble functionality in
[0] Motor feedb. P1-02
30-00 Wobble Mode to 30-19 Wobble Delta
[1] * 24V encoder A and B channel encoder, which can
Freq. Scaled.
only be connected to the digital input
[6] Surface Enables the surface winder control specific terminals 32/33. Terminals 32/33 must
Winder parameters in parameter group 7-2* and be programmed to No operation.
7-3*.
[2] MCB 102 Encoder module option which can be
[7] Extended Specific parameters in parameter group 7-2* configured in parameter group 17-1*
PID Speed to 7-5*. FC 302 only.
OL
[3] MCB 103 Optional resolver interface module
[8] Extended Specific parameters in parameter group 7-2*
which can be configured in parameter
PID Speed to 7-5*.
group 17-5*
CL
[5] Constant The function provides a constant power in the 1-06 Clockwise Direction
Power field weakening area. This parameter defines the term “Clockwise” corresponding to
The torque shape of motor mode is used as a the LCP direction arrow. Used for easy change of direction of
limit in generator mode. This is done to limit the shaft rotation without swapping motor wires. (Valid from SW
power in generatoric mode that otherwise version 5.84)
becomes considerable larger than in motor Option: Function:
mode, due to the high DC link voltage available
[0] * Normal Motor shaft will turn in clockwise
in generator mode.
direction when the Adjustable
Pshaft W = ωmech rad / s × T Nm frequency drive is connected U ->
This relationship with the constant power is U; V -> V, and W -> W to motor.
illustrated in the following graph: [1] Inverse Motor shaft will turn in counter
T[Nm] P[W] clockwise direction when the
130BB655.10
Tnom
Adjustable frequency drive is
Pnom P connected U -> U; V -> V, and W -
> W to motor.
T
ωnom 2ωnom ω [rad/S]
NOTE!
This parameter cannot be changed while the motor is
running.
1-26 Motor Cont. Rated Torque 1-29 Automatic Motor Adaptation (AMA)
Range: Function: Option: Function:
output. This parameter is available [2] Enable Performs a reduced AMA of the stator
Application [0.1 - Enter the value from the motor • For the best adaptation of the Adjustable
frequency drive,, run AMA on a cold motor.
dependent* 10000.0 nameplate data. The default value
Nm] corresponds to the nominal rated • AMA cannot be performed while the motor is
output. This parameter is available running.
when 1-10 Motor Construction is set
• AMA cannot be performed on permanent magnet
to PM, non salient SPM [1], i.e., the motors.
parameter is valid for PM and non-
salient SPM motors only.
NOTE!
1-29 Automatic Motor Adaptation (AMA) It is important to set motor parameter group 1-2*
correctly, since these form part of the AMA algorithm. An
Option: Function:
AMA must be performed to achieve optimum dynamic
The AMA function optimizes dynamic motor motor performance. It may take up to 10 min, depending
performance by automatically optimizing the on the power rating of the motor.
advanced motor parameters (1-30 Stator
Resistance (Rs) to 1-35 Main Reactance (Xh)) at
motor standstill.
NOTE!
Avoid generating external torque during AMA.
Activate the AMA function by pressing [Hand
on] after selecting [1] or [2]. See also the
section Automatic Motor Adaptation in the NOTE!
Design Guide. After a normal sequence, the If one of the settings in parameter group 1-2* is changed,
display will read: "Press [OK] to finish AMA". 1-30 Stator Resistance (Rs) to 1-39 Motor Poles, the
After pressing the [OK] key, the Adjustable advanced motor parameters, will return to default setting.
frequency drive is ready for operation.
moment of inertia of the rotor and the iron loss resistance 1-33 Stator Leakage Reactance (X1)
(1-36 Iron Loss Resistance (Rfe)). Range: Function:
Parameter groups 1-3* and 1-4* cannot be adjusted while
Application [Application Set the stator leakage reactance of
the motor is running.
P 1-34
dependent* dependant] the motor using one of these
methods: 3 3
130BA065.12
P 1-30 P 1-33
I1 Rs X1δ X'2δ 1. Run an AMA on a cold
motor. The Adjustable
frequency drive will
measure the value from
U1 the motor.
P 1-36 P 1-35 P 1-31
RFe Xh R'r
2. Enter the X1 value
manually. Obtain the
value from the motor
supplier.
Figure 3.1 Motor equivalent diagram for an asynchronous
3. Use the X1 default setting.
motor
The Adjustable frequency
drive establishes the
setting on the basis of the
NOTE! motor nameplate data.
A simple check of the X1 + Xh sum value is to divide the
line to line motor voltage by the sqrt(3) and divide this 1-34 Rotor Leakage Reactance (X2)
value by the motor no load current. [VL-L/sqrt(3)]/INL = X1
Range: Function:
+ Xh. These values are important to properly magnetize
Application dependent* [Application dependant]
the motor. For high pole motors it is highly recommended
to perform this check. 1-35 Main Reactance (Xh)
Range: Function:
1-30 Stator Resistance (Rs) Application [Application Set the main reactance of the
Range: Function: dependent* dependant] motor using one of these methods:
Application dependent* [Application dependant] 1. Run an AMA on a cold
motor. The Adjustable
1-31 Rotor Resistance (Rr)
frequency drive will
Range: Function: measure the value from
Application [Application Fine-tuning Rr will improve shaft the motor.
dependent* dependant] performance. Set the rotor
2. Enter the Xh value
resistance value using one of these
manually. Obtain the value
methods:
from the motor supplier.
1. Run an AMA on a cold
3. Use the Xh default setting.
motor. The Adjustable
The Adjustable frequency
frequency drive will
drive establishes the
measure the value from
setting on the basis of the
the motor. All compen-
motor nameplate data.
sations are reset to 100%.
3 3 dependent*
Application
poles.
dependent*
NOTE!
Poles ~nn@ 50Hz ~nn@60Hz 1-50 Motor Magnetisation at Zero Speed will not have effect
2 2700–2880 3250–3460
when 1-10 Motor Construction = [1] PM, non-salient SPM.
4 1350–1450 1625–1730
6 700–960 840–1153 1-51 Min Speed Normal Magnetising [RPM]
Range: Function:
The table shows the number of poles for normal speed Size [10 - 300 Set the required speed for normal
ranges of various motor types. Define motors designed for related* RPM] magnetizing current. If the speed is set
other frequencies separately. The motor pole value is lower than the motor slip speed,
always an even number, because it refers to the total 1-50 Motor Magnetisation at Zero Speed
number of poles, not pairs of poles. The Adjustable and 1-51 Min Speed Normal Magnetising
frequency drive creates the initial setting of 1-39 Motor [RPM] are of no significance.
Poles based on 1-23 Motor Frequency and 1-25 Motor Use this parameter along with
Nominal Speed. 1-50 Motor Magnetisation at Zero Speed.
See .
1-40 Back EMF at 1000 RPM
Range: Function: NOTE!
Application [Application Set the nominal back EMF for 1-51 Min Speed Normal Magnetising [RPM] will not have
dependent* dependant] the motor when running at 1000 effect when 1-10 Motor Construction = [1] PM, non-salient
RPM. This parameter is only SPM.
active when 1-10 Motor
Construction is set to PM motor
1-52 Min Speed Normal Magnetising [Hz]
[1] (Permanent Magnet Motor).
FC 302 only. Range: Function:
Application dependent* [Application dependant]
NOTE!
When using PM motors, it is 1-53 Model Shift Frequency
recommended to use brake Range: Function:
resistors. Application Flux Model shift
dependent* [Application Enter the frequency value for shift
dependant] between two models for
1-41 Motor Angle Offset
determining motor speed. Choose
Range: Function: the value based on settings in
0* [-32768 - Enter the correct offset angle between the PM 1-00 Configuration Mode and
32767 ] motor and the index position (single-turn) of the 1-01 Motor Control Principle. There
attached encoder or resolver. The value range of are two options: shift between Flux
0–32768 corresponds to 0–2 * pi (radians). To model 1 and Flux model 2; or shift
obtain the offset angle value: After Adjustable between Variable Current mode and
frequency drive start-up, apply DC hold and Flux model 2.FC 302 only.
enter the value of 16-20 Motor Angle into this This parameter cannot be adjusted
parameter. while the motor is running.
This parameter is only active when 1-10 Motor
Flux model 1 – Flux model 2
Construction is set to PM, non-salient SPM [1]
This model is used when
(Permanent Magnet Motor).
1-00 Configuration Mode is set to
Speed closed-loop [1] or Torque [2]
and 1-01 Motor Control Principle is
set to Flux w/motor feedback [3].
130BA146.11
dependent* 1000.0 V] frequency point to manually form a
Flux model 1 Flux model 2 U/f characteristic matching the
motor.
P 1-53 fout The frequency points are defined
Figure 3.2 1-00 Configuration in 1-56 U/f Characteristic - F.
Mode = [1] Speed closed-loop or This parameter is an array
[2] Torque and 1-01 Motor Control parameter [0-5] and is only
Principle = [3] Flux w/motor accessible when 1-01 Motor Control
feedback Principle is set to U/f [0].
Variable
current Flux model 2
model
P 1-53 fout
NOTE!
1-64 Resonance Dampening will not have effect when
1-10 Motor Construction = [1] PM, non-salient SPM.
1-81 Min Speed for Function at Stop [RPM] [5] Comp cnt Same as [3] but the number of pulses counted
Range: Function: stop w/o during ramp-down to 0 rpm is deducted from
r the counter value entered in 1-84 Precise Stop
Size related* [0 - 600 RPM] Set the speed at which to activate
Counter Value.
1-80 Function at Stop.
This reset function can, for example, be used to
compensate for the extra distance done during
1-82 Min Speed for Function at Stop [Hz]
ramping down and to reduce the impact of
Range: Function:
gradual wear on mechanical parts.
Size related* [ 0.0 - 20.0 Hz]
The precise stop functions are advantageous in
1-83 Precise Stop Function
applications where high precision is required.
Option: Function: If you use a standard stop command the accuracy is
[0] Precise Only optimal when the operational speed of, for determined by the internal task time. That is not the case
* ramp example, the conveyor belt is constant. This is when you use the precise stop function; it eliminates the
stop an open-loop control. Achieves high repetitive task time dependence and increases the accuracy substan-
precision at the stopping point. tially.
The Adjustable frequency drive tolerance is normally given
[1] Cnt stop Counts the number of pulses, typically from an
by its task time. However, by using its special precise stop
with reset encoder and generates a stop signal after a pre-
function the tolerance is independent of the task time
programmed number of pulses - 1-84 Precise
because the stop signal immediately interrupts the
Stop Counter Value - has been received at T29 or
execution of the Adjustable frequency drive program. The
T33 [30].
precise stop function gives a highly reproducible delay
This is a direct feedback with one-way closed-
from the stop signal is given until the ramping down
loop control.
starts. A test must be done to find this delay as it is a sum
The counter function is activated (starts timing)
of sensor, PLC, Adjustable frequency drive and mechanical
at the edge of the start signal (when it changes
parts.
from stop to start). After each precise stop, the
To ensure optimum accuracy, there should be at least 10
number of pulses counted during ramp-down to
cycles during ramping down, see 3-42 Ramp 1 Ramp Down
0 rpm is reset.
Time, 3-52 Ramp 2 Ramp down Time, 3-62 Ramp 3 Ramp
[2] Cnt stop Same as [1] but the number of pulses counted down Time and 3-72 Ramp 4 Ramp Down Time .
w/o reset during ramp-down to 0 rpm is deducted from The precise stop function is set up here and enabled from
the counter value entered in 1-84 Precise Stop DI T29 or T33.
Counter Value.
This reset function can, for example, be used to
compensate for the extra distance done during
NOTE!
ramping down and to reduce the impact of
This parameter cannot be adjusted while the motor is
gradual wear on mechanical parts.
running.
NOTE!
If [20] is selected, 4-18 Current Limit must be set to 150%.
NOTE!
Ensure that the chosen supply voltage follows the specifi-
cation of the thermistor element utilized.
130BA152.10
Threshold level).
39 42 50 53 54 55
FC 302 can handle three types of KTY sensors, defined in
1-95 KTY Sensor Type. The actual sensor temperature can be
OFF
read out from 16-19 KTY sensor temperature.
12 13 18 19 27 29 32 33 20 37
ON
PTC / Thermistor <800 Ω >2.7 kΩ R
130BB917.10
4000
The B option MCB 112 PTC Thermistor option offers ATEX
approved monitoring of motor temperature. Alternatively,
3 3
3500
NOTE!
Resistance [Ohm]
2500
2000
Only ATEX Ex-e approved motors may be used for this
function. See motor nameplate, approval certificate, data
1500 sheet or contact motor supplier.
1000
When controlling an Ex-e motor with “Increased Safety”, it
500 is important to ensure certain limitations. The parameters
that must be programmed are presented in the following
0
-25 0 25 50 75 100 125 150
application example.
Temperature [°C]
NOTE! current
1-23 Motor Frequency Enter the same value as for
If the temperature of the motor is utilized through a
4-19 Max Output Frequency
thermistor or KTY sensor, the PELV is not complied with in
4-19 Max Output Frequency Motor nameplate, possibly
the event of short circuits between motor windings and
reduced for long motor cables,
sensor. In order to comply with PELV, the sensor must be
sinus filter or reduced supply
extra isolated.
voltage
4-18 Current Limit Forced to 150% by 1-90 [20]
3.3.10.3 ETR 5-15 Terminal 33 Digital [80] PTC Card 1
Input
The calculations estimate the need for a lower load at
5-19 Terminal 37 Safe Stop [4] PTC 1 Alarm
lower speed due to less cooling from the fan incorporated
14-01 Switching Frequency Check that the default value fulfils
in the motor.
the requirement for Motor
t [s]
175ZA052.11
1000
14-26 Trip Delay at Inverter 0
600
Fault
500
400
CAUTION
300
200
130BA151.11
+24V
GND
Range: Function:
OFF
B
A
1-96 KTY Thermistor Resource of a machine current greater than 1.5 times the rated
Option: Function: current, shut down is immediate.
100%
80 %
40 %
5 Hz 15 Hz 25 Hz 50 Hz
Figure 3.7 Example of ATEX ETR thermal limitation curve.
x-axis: fm [Hz]
y-axis: Im/Im,n x 100 [%]
1-98 ATEX ETR interpol. points freq. 1-99 ATEX ETR interpol points
current
[0] = 5 Hz [0] = 40%
[1] = 15 Hz [1] = 80%
[2] = 25 Hz [2] = 100%
[3] = 50 Hz [3] = 100%
If power monitoring is set to Off [0] or Warning [1], the [2] Trip Monitors for a short-circuit or disconnection of
brake function remains active, even if the monitoring limit the brake resistor, or a short-circuit of the brake
is exceeded. This may lead to thermal overload of the IGBT. If a fault occurs, the Adjustable frequency
resistor. It is also possible to generate a warning via a drive cuts out while displaying an alarm (trip
relay/digital output. The measuring accuracy of the power locked).
monitoring depends on the accuracy of the resistance of [3] Stop and Monitors for a short-circuit or disconnection of
the resistor (better than ± 20%). trip the brake resistor, or a short-circuit of the brake
IGBT. If a fault occurs, the Adjustable frequency
2-15 Brake Check
drive ramps down to coast and then trips. A trip
Option: Function: lock alarm is displayed (e.g., warning 25, 27 or
Select type of test and monitoring function to 28).
check the connection to the brake resistor, or
[4] AC brake Monitors for a short-circuit or disconnection of
whether a brake resistor is present, and then
the brake resistor, or a short-circuit of the brake
display a warning or an alarm in the event of a
IGBT. If a fault occurs, the Adjustable frequency
fault.
drive performs a controlled ramp-down. This
NOTE! option is available for FC 302 only.
The brake resistor disconnection function is
[5] Trip Lock
tested during power-up. However, the
brake IGBT test is performed when there is NOTE!
no braking. A warning or trip disconnects Remove a warning arising in connection with Off [0] or
the brake function. Warning [1] by cycling the line power supply. The fault
must be corrected first. For Off [0] or Warning [1], the
The testing sequence is as follows: Adjustable frequency drive keeps running even if a fault is
located.
130BA074.12
Start 1=on
term.18 0=off
3 3 Par 1-71
Start delay time
Par 2-21
Activate brake
Shaft speed speed
Par 1-74
Start speed
Output current
Pre-magnetizing
current or
DC hold current Par 2-20
Par 1-76 Start current/
Release brake current
Par 2-23 Par 2-00 DC hold current
Brake delay time
130BA642.12
II
MotorSpeed
Premag Torque Ramp Brake Ramp 1 upp. 3-41 Ramp 1 downp. 3-42 Stop Activate
Time Release Delay Brake
p. 2-27 Time p. 2-24 Delay
p. 2-25 p. 2-23
Torque Ref. 2-26
Torqueref.
Relay
Gain Boost Factor
p. 2-28
GainBoost
Mech.Brake
1 2 3
Figure 3.8 Brake release sequence for hoist mechanical brake control
I) Activate brake delay: The Adjustable frequency drive starts again from the mechanical brake engaged position.
II) Stop delay: When the time between successive starts is shorter than the setting in 2-24 Stop Delay, the Adjustable frequency drive starts
without applying the mechanical brake (e.g., reversing).
•
for Torque [2], Nm.
Range: Function: [1] Remote Use remote reference in both hand mode
0.00 %* [-100.00 - 100.00 %] and auto mode.
NOTE!
When set to Local [2], the Adjustable
frequency drive will start with this
setting again following a 'power-down'.
130BA059.12
Y
Relative Z Resulting [2] Analog input 54
actual
X Z=X+X*Y/100 reference [7] Frequency input 29
[8] Frequency input 33
[11] Local bus reference
[20] * Digital pot.meter
130BA278.10
Z
[21] Analog input X30-11
0
*Y /10
X+X
[22] Analog input X30-12
[29] Analog Input X48/2
X
3-17 Reference Resource 3
Option: Function:
Select the reference input to be
Y
used for the third reference signal.
-100 0 100 %
3-15 Reference Resource 1,
P 3-14
3-16 Reference Resource 2 and
3-17 Reference Resource 3 define up
3-15 Reference Resource 1 to three different reference signals.
Option: Function: The sum of these reference signals
defines the actual reference.
Select the reference input to be used
for the first reference signal. [0] No function
3-15 Reference Resource 1, [1] Analog input 53
3-16 Reference Resource 2 and [2] Analog input 54
3-17 Reference Resource 3 define up to [7] Frequency input 29
three different reference signals. The [8] Frequency input 33
sum of these reference signals [11] * Local bus reference
defines the actual reference. [20] Digital pot.meter
[0] No function [21] Analog input X30-11
[1] * Analog input 53 [22] Analog input X30-12
[2] Analog input 54 [29] Analog Input X48/2
[7] Frequency input 29
3-18 Relative Scaling Reference Resource
[8] Frequency input 33
[11] Local bus reference Option: Function:
[20] Digital pot.meter Select a variable value to be added to the
[21] Analog input X30-11 (General Purpose I/O Option Module) fixed value (defined in 3-14 Preset Relative
Reference). The sum of the fixed and
[22] Analog input X30-12 (General Purpose I/O Option Module) variable values (labeled Y in the figure
[29] Analog Input X48/2 below) is multiplied by the actual reference
(labeled X in the figure below). The result
3-16 Reference Resource 2 is then added to the actual reference (X
Option: Function: +X*Y/100) to give the resulting actual
Select the reference input to be reference.
used for the second reference
130BA059.12
Y
signal. 3-15 Reference Resource 1, Relative Z Resulting
actual
X Z=X+X*Y/100 reference
3-16 Reference Resource 2 and
3-17 Reference Resource 3 define up
to three different reference signals.
The sum of these reference signals [0] * No function
defines the actual reference.
130BA872.10
RPM
Option: Function:
P 4-13
[1] Analog input High-limit
3 3
53 Reference
ns
[2] Analog input P 4-11
Low limit
54
[7] Frequency
P 3-*1 P 3-*2 Time
input 29 Ramp (X)Up Ramp (X) Down
Time (Acc) Time (Dec)
[8] Frequency
tacc tdec
input 33
[11] Local bus
reference If S-ramps are selected, then set the level of non-linear jerk
[20] Digital compensation required. Set jerk compensation by defining
pot.meter the proportion of ramp-up and ramp-down times where
[21] Analog input acceleration and deceleration are variable (i.e., increasing
X30-11 or decreasing). The S-ramp acceleration and deceleration
[22] Analog input settings are defined as a percentage of the actual ramp
X30-12 time.
[29] Analog Input
X48/2
NOTE!
This parameter cannot be adjusted while the motor is
running.
Range: Function:
3-42 Ramp 1 Ramp Down Time
50 %* [Application Enter the proportion of the total
Range: Function:
dependant] ramp-down time (3-42 Ramp 1 Ramp
Application Enter the ramp-down time, i.e., the Down Time) where the deceleration
dependent* [Application deceleration time from the torque decreases. The larger the
dependant] synchronous motor speed ns to 0 percentage value, the greater the jerk
RPM. Choose a ramp-down time such compensation achieved, and thus the
that no overvoltage arises in the lower the torque jerks in the
inverter due to regenerative application.
operation of the motor, and such
that the generated current does not
exceed the current limit set in 3.5.4 3-5* Ramp 2
4-18 Current Limit. The value 0.00
corresponds to 0.01 s in speed mode. Choosing ramp parameters, see parameter group 3-4*.
See ramp-up time in 3-41 Ramp 1
3-50 Ramp 2 Type
Ramp up Time.
Option: Function:
tdec s x ns RPM
Par . 3 − 42 = Select the ramp type, depending on
ref RPM
requirements for acceleration/deceleration. A
3-45 Ramp 1 S-ramp Ratio at Accel. Start linear ramp will give constant acceleration
Range: Function: during ramping. An S-ramp will give non-
50 %* [Application Enter the proportion of the total linear acceleration, compensating for jerk in
dependant] ramp-up time (3-41 Ramp 1 Ramp up the application.
Time) in which the acceleration torque [0] * Linear
increases. The larger the percentage [1] S-ramp Acceleration with lowest possible jerk
value, the greater the jerk compen- Const Jerk
sation achieved, and thus the lower [2] S-ramp S-ramp based on the values set in 3-51 Ramp
the torque jerks occurring in the Const Time 2 Ramp up Time and 3-52 Ramp 2 Ramp down
application. Time
Range: Function:
3-52 Ramp 2 Ramp down Time
50 %* [Application Enter the proportion of the total
Range: Function:
dependant] ramp-down time (3-52 Ramp 2 Ramp
Application Enter the ramp-down time, i.e., the down Time) where the deceleration
dependent* [Application deceleration time from the rated torque decreases. The larger the
dependant] motor speed ns to 0 RPM. Choose a percentage value, the greater the jerk
ramp-down time such that no compensation achieved, and thus the
overvoltage arises in the inverter due lower the torque jerks in the
to regenerative operation of the application.
motor, and such that the generated
current does not exceed the current
limit set in 4-18 Current Limit. The 3.5.5 3-6* Ramp 3
value 0.00 corresponds to 0.01 sec. in
speed mode. See ramp-up time in Configure ramp parameters, see 3-4*.
3-51 Ramp 2 Ramp up Time.
3-60 Ramp 3 Type
tdec s x ns RPM
Par . 3 − 52 =
ref RPM
Option: Function:
Select the ramp type, depending on
3-55 Ramp 2 S-ramp Ratio at Accel. Start requirements for acceleration and
Range: Function: deceleration. A linear ramp will give constant
50 %* [Application Enter the proportion of the total acceleration during ramping. An S-ramp will
dependant] ramp-up time (3-51 Ramp 2 Ramp up give non-linear acceleration, compensating
Time) in which the acceleration torque for jerk in the application.
increases. The larger the percentage [0] * Linear
value, the greater the jerk compen- [1] S-ramp Accelerates with lowest possible jerk.
sation achieved, and thus the lower Const Jerk
the torque jerks in the application. [2] S-ramp S-ramp based on the values set in 3-61 Ramp
Const Time 3 Ramp up Time and 3-62 Ramp 3 Ramp down
Time
Range: Function:
3-72 Ramp 4 Ramp Down Time
50 %* [Application Enter the proportion of the total
Range: Function:
dependant] ramp-down time (3-72 Ramp 4 Ramp
Application Enter the ramp-down time, i.e., the Down Time) where the deceleration
dependent* [Application deceleration time from the rated torque decreases. The larger the
dependant] motor speed ns to 0 RPM. Choose a percentage value, the greater the jerk
ramp-down time such that no compensation achieved, and thus the
overvoltage arises in the inverter due lower the torque jerks in the
to regenerative operation of the application.
motor, and such that the generated
current does not exceed the current
limit set in 4-18 Current Limit. The 3.5.7 3-8* Other Ramps
value 0.00 corresponds to 0.01 sec. in
speed mode. See ramp-up time in 3-80 Jog Ramp Time
3-71 Ramp 4 Ramp up Time.
Range: Function:
tdec s x ns RPM
Par . 3 − 72 = Application [0.01 - Enter the jog ramp time, i.e., the
ref RPM
dependent* 3600.00 s] acceleration/deceleration time
3-75 Ramp 4 S-ramp Ratio at Accel. Start between 0 RPM and the rated motor
frequency ns. Ensure that the resultant
Range: Function:
output current required for the given
50 %* [Application Enter the proportion of the total
jog ramp time does not exceed the
dependant] ramp-up time (3-71 Ramp 4 Ramp up
current limit in 4-18 Current Limit. The
Time) in which the acceleration torque
jog ramp time starts upon activation
increases. The larger the percentage
of a jog signal via the LCP, a selected
value, the greater the jerk compen-
digital input, or the serial communi-
sation achieved, and thus the lower
cation port. When jog state is
the torque jerks in the application.
disabled, the normal ramping times
are valid.
130BA070.10
RPM
130BA069.10
RPM
3 3 high limit
P 1-25
high limit
Reference
Motor speed
P 1-25
P 3-19 Motor speed
Jog speed
Qstop
tjog s x ns RPM
Par . 3 − 80 =
Δ log speed ( par . 3 − 19) RPM
Decrease or Clear. To activate the function, at least one 3-93 Maximum Limit
digital input must be set up to Increase or Decrease. Range: Function:
the Digital Potentiometer is used for fine
tuning of the resulting reference.
3 3
3-94 Minimum Limit
Range: Function:
-100 %* [-200 - 200 Set the minimum permissible value for
%] the resultant reference. This is advisable
if the Digital Potentiometer is used for
fine tuning of the resulting reference.
3.6 Parameters: 4-** Limits/Warnings 4-14 Motor Speed High Limit [Hz]
Range: Function:
3.6.1 4-1* Motor Limits
Size related* [ par. 4-12 - par. 4-19 Hz]
3 3 Define torque, current and speed limits for the motor, and
the reaction of the Adjustable frequency drive when the
NOTE!
Max. output frequency cannot exceed 10% of the inverter
limits are exceeded. switching frequency (14-01 Switching Frequency).
A limit may generate a message on the display. A warning
will always generate a message on the display or on the
4-16 Torque Limit Motor Mode
serial communication bus. A monitoring function may
initiate a warning or a trip, upon which the Adjustable Range: Function:
frequency drive will stop and generate an alarm message. Application dependent* [Application dependant]
NOTE!
[16] Analog input X30-12
inv 3 3
Max. output frequency cannot exceed 10% of the inverter
switching frequency (14-01 Switching Frequency). 3.6.2 4-3* Motor Feedback Monitoring
4-20 Torque Limit Factor Source The parameter group includes monitoring and handling of
Option: Function: motor feedback devices such as encoders, resolvers, etc.
Select an analog input for scaling the 4-30 Motor Feedback Loss Function
settings in 4-16 Torque Limit Motor
Option: Function:
Mode and 4-17 Torque Limit Generator
Select which reaction the Adjustable
Mode from 0% to 100% (or inverse).
frequency drive should take if a
The signal levels corresponding to
feedback fault is detected. The
0% and 100% are defined in the
selected action is to take place when
analog input scaling, e.g., parameter
the feedback signal differs from the
group 6-1*. This parameter is only
output speed where its range is
active when 1-00 Configuration Mode
specified in 4-31 Motor Feedback
is in Speed Open-loop or Speed
Speed Error during its time frame set
Closed-loop.
in 4-32 Motor Feedback Loss Timeout.
[0] * No function
[0] Disabled
[2] Analog in 53
[1] Warning
[4] Analog in 53 inv
[2] * Trip
[6] Analog in 54
[3] Jog
[8] Analog in 54 inv
[4] Freeze Output
[10] Analog in X30-11
[5] Max Speed
[12] Analog in X30-11
[6] Switch to Open Loop
inv
[7] Select Setup 1
[14] Analog in X30-12
[8] Select Setup 2
[16] Analog in X30-12
[9] Select Setup 3
inv
[10] Select Setup 4
4-21 Speed Limit Factor Source Option [11] stop & trip
Option: Function: Warning/Alarm 61 Feedback Error is related to the Motor
Select an analog input for scaling Feedback Loss Function.
the settings in 4-19 Max Output
Frequency from 0% to 100% (or vice 4-31 Motor Feedback Speed Error
versa). The signal levels Range: Function:
corresponding to 0% and 100% are 300 RPM* [1 - 600 RPM] Select the max. allowed tracking error
defined in the analog input scaling, in speed from the calculated and the
e.g., parameter group 6-1*. This actual mechanical shaft output
parameter is only active when speeds.
1-00 Configuration Mode is in Torque
Mode.
[0] * No function
[2] Analog input 53
[4] Analog input 53 inv
[6] Analog input 54
[8] Analog input 54 inv
[10] Analog input X30-11
[12] Analog input X30-11
inv
130BA064.10
Imotor
Range: Function:
ILIM ON REF Application [Application Enter the nHIGH value. When the
(P 4-18)
IHIGH
dependent* dependant] motor speed exceeds this limit, the
display reads Speed High. The 3 3
(P 4-51) signal outputs can be
programmed to produce a status
IN RANGE
signal on terminal 27 or 29 (FC
302 only) and on relay output 01
ILOW or 02 (FC 302 only). Program the
(P 4-50)
upper signal limit of the motor
nmotor [RPM] speed, nHIGH, within the normal
nMIN nLOW REF nHIGH nMAX working range of the Adjustable
(P 4-11) (P 4-52) (P 4-53) (P 4-13) frequency drive. Refer to Figure 3.9.
Figure 3.9 Adjustable Warnings
4-54 Warning Reference Low
Range: Function:
4-50 Warning Current Low -999999.999* [Application Enter the lower reference limit.
Range: Function: dependant] When the actual reference falls
0.00 A* [Application Enter the ILOW value. When the motor below this limit, the display
dependant] indicates Ref Low. The signal
current falls below this limit, the display
outputs can be programmed to
reads Current Low. The signal outputs
produce a status signal on
can be programmed to produce a
terminal 27 or 29 (FC 302 only)
status signal on terminal 27 or 29 (FC
and on relay output 01 or 02 (FC
302 only) and on relay output 01 or 02
302 only).
(FC 302 only). Refer to Figure 3.9.
3 3 ReferenceFeed-
backUnit*
dependant] limit. When the feedback
exceeds this limit, the display
Size related* [ 0.0 - par. 4-14 Hz]
NOTE!
This parameter cannot be adjusted while the motor is
running.
3.7 Parameters: 5-** Digital In/Out Digital input function Select Terminal
Start reversing [11] All
3.7.1 5-0* Digital I/O Mode Enable start forward [12] All
Enable start reverse [13] All
Parameters for configuring the input and output using
NPN and PNP.
Jog [14] All *term 29 3 3
Preset reference on [15] All
5-00 Digital I/O Mode Preset ref bit 0 [16] All
Preset ref bit 1 [17] All
Option: Function:
Preset ref bit 2 [18] All
Digital inputs and programmed digital outputs are
Freeze reference [19] All
pre-programmable for operation either in PNP or NPN
Freeze output [20] All
systems.
Speed up [21] All
[0] * PNP Action on positive directional pulses (↕). PNP systems Slow [22] All
are pulled down to GND.
Set-up select bit 0 [23] All
[1] NPN Action on negative directional pulses (↕). NPN Set-up select bit 1 [24] All
systems are pulled up to + 24V, internally in the Precise stop inverse [26] 18, 19
Adjustable frequency drive. Precise start, stop [27] 18, 19
Catch up [28] All
NOTE! Slow-down [29] All
Once this parameter has been changed, it must be Counter input [30] 29, 33
activated by performing a power cycle. Pulse input Edge Trigged [31] 29, 33
Pulse input Time Based [32] 29, 33
5-01 Terminal 27 Mode Ramp bit 0 [34] All
Option: Function: Ramp bit 1 [35] All
[0] * Input Defines terminal 27 as a digital input. Latched precise start [40] 18, 19
Latched precise stop [41] 18, 19
[1] Output Defines terminal 27 as a digital output.
inverse
External interlock [51]
5-02 Terminal 29 Mode
DigiPot Increase [55] All
Option: Function:
DigiPot Decrease [56] All
[0] * Input Defines terminal 29 as a digital input. DigiPot Clear [57] All
[1] Output Defines terminal 29 as a digital output. Digipot Hoist [58] All
Counter A (up) [60] 29, 33
This parameter is available for FC 302 only. Counter A (down) [61] 29, 33
Reset Counter A [62] All
3.7.2 Digital Inputs Counter B (up) [63] 29, 33
Counter B (down) [64] 29, 33
The digital inputs are used for selecting various functions Reset Counter B [65] All
in the Adjustable frequency drive. All digital inputs can be Mech. Brake Feedb. [70] All
set to the following functions: Mech. Brake Feedb. Inv. [71] All
PID Error Inv. [72] All
Digital input function Select Terminal
PID Reset I-part [73] All
No operation [0] All *term 32, 33
PID enable [74] All
Reset [1] All
PTC Card 1 [80] All
Coast inverse [2] All *term 27
Profidrive OFF2 [91]
Coast and reset inverse [3] All
Profidrive OFF3 [92]
Quick stop inverse [4] All
Start edge triggered [98]
DC brake inverse [5] All
Safe Option Reset [100]
Stop inverse [6] All
Start [8] All *term 18
Latched start [9] All
FC 300 standard terminals are 18, 19, 27, 29, 32 and 33.
MCB 101 terminals are X30/2, X30/3 and X30/4.
Reversing [10] All *term 19
Terminal 29 functions as an output only in FC 302.
Functions dedicated to only one digital input are stated in [10] Reversing (Default Digital input 19). Change the
the associated parameter. direction of motor shaft rotation. Select Logic
‘1’ to reverse. The reversing signal only
All digital inputs can be programmed to these functions: changes the direction of rotation. It does not
3 3 activate the start function. Select both
directions in 4-10 Motor Speed Direction. The
[0] No No reaction to signals transmitted to the
function is not active in process closed-loop.
operation terminal.
[11] Start Used for start/stop and for reversing on the
[1] Reset Resets Adjustable frequency drive after a
reversing same wire. Signals on start are not allowed at
TRIP/ALARM. Not all alarms can be reset.
the same time.
[2] Coast (Default Digital input 27): Coasting stop,
[12] Enable start Disengages the counter-clockwise movement
inverse inverted input (NC). The Adjustable frequency
forward and allows for the clockwise direction.
drive leaves the motor in free mode. Logic ‘0’
=> coasting stop. [13] Enable start Disengages the clockwise movement and
reverse allows for the counter-clockwise direction.
[3] Coast and Reset and coasting stop Inverted input (NC).
reset inverse Leaves motor in free mode and resets [14] Jog (Default Digital input 29): Use to activate jog
Adjustable frequency drive. Logic ‘0’ => speed. See 3-11 Jog Speed [Hz].
coasting stop and reset. [15] Preset Shifts between external reference and preset
[4] Quick stop Inverted input (NC). Generates a stop in reference on reference. It is assumed that External/preset [1]
inverse accordance with the quick-stop ramp time set has been selected in 3-04 Reference Function.
in 3-81 Quick Stop Ramp Time. When motor Logic '0' = external reference active; logic '1'
stops, the shaft is in free mode. Logic ‘0’ => = one of the eight preset references is active.
quick stop. [16] Preset ref Preset ref. bit 0,1, and 2 enables a choice
[5] DC brake Inverted input for DC braking (NC). Stops bit 0 between one of the eight preset references
inverse motor by energizing it with a DC current for a according to the table below.
certain time period. See 2-01 DC Brake Current [17] Preset ref Same as Preset ref bit 0 [16].
to 2-03 DC Brake Cut In Speed [RPM]. The bit 1
function is only active when the value in [18] Preset ref Same as Preset ref bit 0 [16].
2-02 DC Braking Time is different from 0. bit 2
Logic ’0’ => DC braking.
Preset ref. bit 2 1 0
[6] Stop inverse Stop Inverted function. Generates a stop
Preset ref. 0 0 0 0
function when the selected terminal goes
from logical level ‘1’ to ‘0’. The stop is Preset ref. 1 0 0 1
performed according to the selected ramp Preset ref. 2 0 1 0
time (3-42 Ramp 1 Ramp Down Time, Preset ref. 3 0 1 1
3-52 Ramp 2 Ramp down Time, 3-62 Ramp 3 Preset ref. 4 1 0 0
Ramp down Time, 3-72 Ramp 4 Ramp Down Preset ref. 5 1 0 1
Time). Preset ref. 6 1 1 0
NOTE! Preset ref. 7 1 1 1
When the Adjustable frequency drive is
at the torque limit and has received a [19] Freeze Freezes the actual reference, which is now the
stop command, it may not stop by itself. ref point of enable/condition for Speed up and Slow
To ensure that the Adjustable frequency to be used. If Speed up/down is used, the speed
drive stops, configure a digital output to change always follows ramp 2 (3-51 Ramp 2 Ramp
Torque limit & stop [27] and connect this up Time and 3-52 Ramp 2 Ramp down Time) in the
digital output to a digital input that is range 0 - 3-03 Maximum Reference.
configured as coast. [20] Freeze Freezes the actual motor frequency (Hz), which is
[8] Start (Default Digital input 18): Select start for a output now the point of enable/condition for Speed up
start/stop command. Logic ‘1’ = start, logic ‘0’ and Slow to be used. If Speed up/down is used,
= stop. the speed change always follows ramp 2
[9] Latched The motor starts, if a pulse is applied for min. (3-51 Ramp 2 Ramp up Time and 3-52 Ramp 2
start 2ms. The motor stops when Stop inverse is Ramp down Time) in the range 0 - 1-23 Motor
activated or a reset command (via DI) is Frequency.
given.
130BB463.10
Pulse
Reduced by %-value 1 0
Increased by %-value 0 1
Reduced by %-value 1 1
[32] Pulse time Time-based pulse input measures the duration
based between flanks. This gives a higher resolution at
[22] Slow Same as Speed up [21].
lower frequencies, but is not as precise at
[23] Set-up Select Set-up select bit 0 or Select Set-up select higher frequencies. This principle has a cut-off
select bit bit 1 to select one of the four set-ups. Set frequency which makes it unsuited for encoders
0 0-10 Active Set-up to Multi Set-up. with very low resolutions (e.g., 30 ppr) at low
[24] Set-up (Default Digital input 32): Same as Set-up select speeds.
select bit bit 0 [23].
1 Speed [rpm] Speed [rpm]
130BB462.10
[26] Precise Sends an inverted stop signal when the precise
stop inv. stop function is activated in 1-83 Precise Stop a Time[sec] b Time[sec]
Function.
Precise stop inverse function is available for
terminals 18 or 19.
[27] Precise Use when Precise ramp stop [0] is selected in
start, stop 1-83 Precise Stop Function.
a: very low encoder b: standard encoder
Precise start, stop is available for terminals 18
resolution resolution
and 19.
Precise start makes sure that the angle that the
Pulse
130BB464.10
5-18 Terminal X30/4 Digital Input [8] PTC 1 & This choice makes it possible to use a
Relay A/W combination of alarm and warning. Choice 8
Option: Function:
is only available when the MCB 112 PTC
[0] * No operation This parameter is active when option module thermistor card is connected.
MCB101 is installed in the Adjustable
frequency drive. Functions are described [9] PTC 1 & This choice makes it possible to use a
under 5-1* Digital Inputs Relay W/A combination of alarm and warning. Choice 9
is only available when the MCB 112 PTC
5-19 Terminal 37 Safe Stop thermistor card is connected.
Option: Function:
Choices 4–9 are only available when the MCB 112 PTC
[1] Safe Stop Coasts Adjustable frequency drive when safe
thermistor card is connected.
* Alarm stop is activated. Manual reset from LCP,
digital input or serial communication bus.
[4] Enable / no Ready for operation. No start or stop [24] Ready, voltage Adjustable frequency drive is ready for
warning command is been given (start/disable). OK operation and the AC line voltage is
No warnings are active. within the specified voltage range (see
[5] VLT running Motor is running and shaft torque is General Specifications section in the
[6] Running / no
present.
Output speed is higher than the speed [25] Reverse
Design Guide).
Reversing. Logic ‘1’ when CW rotation of
3 3
warning set in 1-81 Min Speed for Function at Stop the motor. Logic ‘0’ when CCW rotation
[RPM]. The motor is running and there are of the motor. If the motor is not rotating,
no warnings. the output will follow the reference.
[7] Run in Motor is running within the programmed [26] Bus OK Active communication (no timeout) via
range/no current and speed ranges set in the serial communication port.
warning 4-50 Warning Current Low to 4-53 Warning [27] Torque limit Use in performing a coasting stop and in
Speed High. There are no warnings. and stop torque limit condition. If the Adjustable
[8] Run on Motor runs at reference speed. No frequency drive has received a stop signal
reference / no warnings. and is at the torque limit, the signal is
warning Logic ‘0’.
[9] Alarm An alarm activates the output. There are [28] Brake, no brake Brake is active and there are no warnings.
no warnings. warning
[10] Alarm or An alarm or a warning activates the [29] Brake ready, no Brake is ready for operation and there are
warning output. fault no faults.
[11] At torque limit The torque limit set in 4-16 Torque Limit [30] Brake fault Output is Logic ‘1’ when the brake IGBT is
Motor Mode or 4-17 Torque Limit Generator (IGBT) short-circuited. Use this function to
Mode has been exceeded. protect the Adjustable frequency drive if
[12] Out of current The motor current is outside the range there is a fault on the brake modules. Use
range set in 4-18 Current Limit. the output/relay to cut out the AC line
[13] Below current, Motor current is lower than set in voltage from the Adjustable frequency
low 4-50 Warning Current Low. drive.
[14] Above current, Motor current is higher than set in [31] Relay 123 The relay is activated when Control Word
high 4-51 Warning Current High. [0] is selected in parameter group 8-**.
[15] Out of speed Output frequency is outside the [32] Mechanical Enables control of an external mechanical
range frequency ranges set in 4-52 Warning brake control brake, see description in the section
Speed Low and 4-53 Warning Speed High. Control of Mechanical Brake, and
[16] Below speed, Output speed is lower than the setting in parameter group 2-2*
low 4-52 Warning Speed Low. [33] Safe stop Indicates that the safe stop on terminal
[17] Above speed, Output speed is higher than the setting activated (FC 37 has been activated.
high in 4-53 Warning Speed High. 302 only)
[18] Out of Feedback is outside the range set in [40] Out of ref Active when the actual speed is outside
feedback range 4-56 Warning Feedback Low and range settings in 4-52 Warning Speed Low to
4-57 Warning Feedback High. 4-55 Warning Reference High.
[19] Below Feedback is below the limit set in [41] Below Active when actual speed is below speed
feedback low 4-56 Warning Feedback Low. reference low reference setting.
[20] Above Feedback is above the limit set in [42] Above Active when actual speed is above speed
feedback high 4-57 Warning Feedback High. reference high reference setting
[21] Thermal The thermal warning turns on when the [43] Extended PID
warning temperature exceeds the limit in the Limit
motor, the Adjustable frequency drive, [45] Bus Ctrl Controls output via bus. The state of the
the brake resistor, or the thermistor. output is set in 5-90 Digital & Relay Bus
[22] Ready, no Adjustable frequency drive is ready for Control. The output state is retained in
thermal operation and there is no over- the event of bus timeout.
warning temperature warning. [46] Bus Ctrl On at Controls output via bus. The state of the
[23] Remote, ready, Adjustable frequency drive is ready for timeout output is set in 5-90 Digital & Relay Bus
no thermal operation and is in [Auto on] mode. Control. In the event of a bus timeout,
warning There is no over-temperature warning. the output state is set high (On).
[47] Bus Ctrl Off at Controls output via bus. The state of the the Smart Logic Action [33] Set dig. out. A
timeout output is set in 5-90 Digital & Relay Bus low is executed.
Control. In the event of a bus timeout, [82] SL Digital See 13-52 SL Controller Action. The input
the output state is set low (Off). Output C will go high whenever the Smart Logic
3 3 [51] MCO controlled Active when a MCO 302 or MCO 305 is
connected. The output is controlled from
Action [40] Set dig. out. A high is
executed. The input will go low whenever
option. the Smart Logic Action [34] Set dig. out. A
[55] Pulse output low is executed.
[60] Comparator 0 See parameter group 13-1*. If Comparator [83] SL Digital See 13-52 SL Controller Action. The input
0 is evaluated as TRUE, the output will go Output D will go high whenever the Smart Logic
high. Otherwise, it will be low. Action [41] Set dig. out. A high is
[61] Comparator 1 See parameter group 13-1*. If Comparator executed. The input will go low whenever
1 is evaluated as TRUE, the output will go the Smart Logic Action [35] Set dig. out. A
high. Otherwise, it will be low. low is executed.
[62] Comparator 2 See parameter group 13-1*. If Comparator [84] SL Digital See 13-52 SL Controller Action. The input
2 is evaluated as TRUE, the output will go Output E will go high whenever the Smart Logic
high. Otherwise, it will be low. Action [42] Set dig. out. A high is
[63] Comparator 3 See parameter group 13-1*. If Comparator executed. The input will go low whenever
3 is evaluated as TRUE, the output will go the Smart Logic Action [36] Set dig. out. A
high. Otherwise, it will be low. low is executed.
[64] Comparator 4 See parameter group 13-1*. If Comparator [85] SL Digital See 13-52 SL Controller Action. The input
4 is evaluated as TRUE, the output will go Output F will go high whenever the Smart Logic
high. Otherwise, it will be low. Action [43] Set dig. out. A high is
[65] Comparator 5 See parameter group 13-1*. If Comparator executed. The input will go low whenever
5 is evaluated as TRUE, the output will go the Smart Logic Action [37] Set dig. out. A
high. Otherwise, it will be low. low is executed.
[70] Logic Rule 0 See parameter group 13-4*. If Logic Rule [120] Local reference Output is high when 3-13 Reference Site =
0 is evaluated as TRUE, the output will go active [2] Local or when 3-13 Reference Site = [0]
high. Otherwise, it will be low. Linked to hand auto at the same time as
[71] Logic Rule 1 See parameter group 13-4*. If Logic Rule the LCP is in [Hand on] mode.
1 is evaluated as TRUE, the output will go
Reference site Local Remote
high. Otherwise, it will be low.
set in referenc reference
[72] Logic Rule 2 See parameter group 13-4*. If Logic Rule
3-13 Reference e active
2 is evaluated as TRUE, the output will go
Site active [121]
high. Otherwise, it will be low.
[120]
[73] Logic Rule 3 See parameter group 13-4*. If Logic Rule Reference site: 1 0
3 is evaluated as TRUE, the output will go Local
high. Otherwise, it will be low. 3-13 Reference Site
[74] Logic Rule 4 See parameter group 13-4*. If Logic Rule [2]
4 is evaluated as TRUE, the output will go Reference site: 0 1
high. Otherwise, it will be low. Remote
[75] Logic Rule 5 See parameter group 13-4*. If Logic Rule 3-13 Reference Site
5 is evaluated as TRUE, the output will go [1]
high. Otherwise, it will be low. Reference site:
[80] SL Digital See 13-52 SL Controller Action. The output Linked to Hand/
Output A will go high whenever the Smart Logic Auto
Action [38] Set dig. out. A high is Hand 1 0
executed. The output will go low
Hand -> off 1 0
whenever the Smart Logic Action [32] Set
Auto -> off 0 0
dig. out. A low is executed.
Auto 0 1
[81] SL Digital See 13-52 SL Controller Action. The input
Output B will go high whenever the Smart Logic
Action [39] Set dig. out. A high is
executed. The input will go low whenever
[121] Remote Output is high when 3-13 Reference Site = 5-31 Terminal 29 Digital Output
reference Remote [1] or Linked to hand/auto [0]
Option: Function:
active while the LCP is in [Auto on] mode. See
[0] * No operation Functions are described under 5-3* Digital
above.
[122] No alarm Output is high when no alarm is present.
[123] Start command Output is high when there is an active
Outputs
This parameter only applies to FC 302 3 3
active Start command (i.e., via digital input bus 5-32 Term X30/6 Digi Out (MCB 101)
connection or [Hand on] or [Auto on]), Option: Function:
and no Stop or Start command is active.
[0] * No operation This parameter is active when
[124] Running Output is high when the Adjustable
option module MCB 101 is
reverse frequency drive is running counter
mounted in the Adjustable
clockwise (the logical product of the
frequency drive. Functions are
status bits ‘running’ AND ‘reverse’).
described under 5-3* Digital
[125] Drive in hand Output is high when the Adjustable Outputs
mode frequency drive is in [Hand on] mode (as
indicated by the LED light above [Hand [1] Control ready
on]). [2] Drive ready
[126] Drive in auto Output is high when the Adjustable [3] Drive rdy/rem ctrl
mode frequency drive is in [Hand on] mode (as [4] Enable / no warning
indicated by the LED above [Auto on]). [5] Running
[151] ATEX ETR cur. Selectable if 1-90 Motor Thermal Protection [6] Running / no warning
alarm is set to [20] or [21]. If the alarm 164 [7] Run in range/no warn
ATEX ETR cur.lim.alarm is active, the [8] Run on ref/no warn
output will be 1. [9] Alarm
[152] ATEX ETR freq. Selectable if 1-90 Motor Thermal Protection [10] Alarm or warning
alarm is set to [20] or [21]. If the alarm 166 [11] At torque limit
ATEX ETR freq.lim.alarm is active, the [12] Out of current range
output will be 1. [13] Below current, low
[153] ATEX ETR cur. Selectable if1-90 Motor Thermal Protection [14] Above current, high
warning is set to [20] or [21]. If the alarm 163 [15] Out of speed range
ATEX ETR cur.lim.warning is active, the
[16] Below speed, low
output will be 1.
[17] Above speed, high
[154] ATEX ETR freq. Selectable if 1-90 Motor Thermal Protection
[18] Out of feedb. range
warning is set to [20] or [21]. If the warning 165
[19] Below feedback, low
ATEX ETR freq.lim.warning is active, the
[20] Above feedback, high
output will be 1.
[21] Thermal warning
[188] AHF Capacitor The capacitors will be turned on at 20%
[22] Ready,no thermal W
Connect (hysteresis of 50% gives an interval of
[23] Remote,ready,no TW
10%–30%). The capacitors will be discon-
nected below 10%. The off delay is 10 s [24] Ready, Voltage OK
and will restart if the nominal power goes [25] Reverse
above 10% during the delay. 5-80 AHF [26] Bus OK
Cap Reconnect Delay is used to guarantee [27] Torque limit & stop
a minimum off-time for the capacitors. [28] Brake, no brake war
[189] External fan The internal logics for the internal fan [29] Brake ready, no fault
control control is transferred to this output to [30] Brake fault (IGBT)
make it possible to control an external [31] Relay 123
fan (relevant for HP duct cooling). [32] Mech brake ctrl
[33] Safe stop active
5-30 Terminal 27 Digital Output
[38] Motor feedback error
Option: Function:
[39] Tracking error
[0] * No operation Functions are described under 5-3* Digital [40] Out of ref range
Outputs
[41] Below reference, low
[42] Above ref, high
5-32 Term X30/6 Digi Out (MCB 101) 5-33 Term X30/7 Digi Out (MCB 101)
Option: Function: Option: Function:
[43] Extended PID Limit [0] * No operation This parameter is active when
3 3 [45]
[46]
Bus ctrl.
Bus ctrl, 1 if timeout
option module MCB 101 is
mounted in the Adjustable
[47] Bus ctrl, 0 if timeout frequency drive. Functions are
[51] MCO controlled described under 5-3* Digital
[55] Pulse output Outputs
5-33 Term X30/7 Digi Out (MCB 101) 5-40 Function Relay
Option: Function: Array [9]
[61] Comparator 1 (Relay 1 [0], Relay 2 [1], Relay 3 [2] (MCB 113), Relay 4 [3] (MCB
113), Relay 5 [4] (MCB 113), Relay 6 [5] (MCB 113), Relay 7 [6]
[62]
[63]
Comparator 2
Comparator 3 (MCB 105), Relay 8 [7] (MCB 105), Relay 9 [8] (MCB 105)) 3 3
[64] Comparator 4 Option: Function:
[65] Comparator 5 [0] * No operation All digital and relay outputs are
[70] Logic rule 0 default set to “No Operation”.
[71] Logic rule 1 [1] Control ready The control card is ready. For
[72] Logic rule 2 example, Feedback from a drive
[73] Logic rule 3 where the control is supplied by an
[74] Logic rule 4 external 24 V (MCB 107) and the
[75] Logic rule 5 main power to drive is not detected.
[80] SL digital output A
[2] Drive ready Drive is ready to operate. Line power
[81] SL digital output B and control supplies are OK.
[82] SL digital output C
[3] Drive rdy/rem ctrl The Adjustable frequency drive is
[83] SL digital output D
ready for operation and is in auto on
[84] SL digital output E
mode
[85] SL digital output F
[120] Local ref active [4] Enable / no warning Ready for operation. No start or stop
[121] Remote ref active commands have been applied (start/
[122] No alarm disable). No warnings are active.
[123] Start command activ [5] Running Motor is running, and shaft torque
[124] Running reverse present.
[125] Drive in hand mode [6] Running / no Output speed is higher than the
[126] Drive in auto mode warning speed set in 1-81 Min Speed for
[151] ATEX ETR cur. alarm Function at Stop [RPM] Min Speed for
[152] ATEX ETR freq. alarm Function at Stop [RPM]. The motor is
[153] ATEX ETR cur. warning running and no warnings.
[154] ATEX ETR freq. warning
[7] Run in range/no Motor is running within the
[189] External Fan Control warn programmed current and speed
[190] Safe Function active ranges set in 4-50 Warning Current
[191] Safe Opt. Reset req. Low and 4-53 Warning Speed High.
[192] RS Flipflop 0 No warnings.
[193] RS Flipflop 1
[8] Run on ref/no warn Motor runs at reference speed. No
[194] RS Flipflop 2
warnings.
[195] RS Flipflop 3
[196] RS Flipflop 4 [9] Alarm An alarm activates the output. No
warnings
[197] RS Flipflop 5
[198] RS Flipflop 6 [10] Alarm or warning An alarm or a warning activates the
[199] RS Flipflop 7 output.
[21] Thermal warning Thermal warning turns on when the [31] Relay 123 Digital output/relay is activated
temperature exceeds the limit either when Control Word [0] is selected in
in motor, Adjustable frequency drive, parameter group 8-**.
brake resistor, or connected [32] Mech brake ctrl Selection of mechanical brake
thermistor. control. When selected parameters in
[22] Ready,no thermal W Adjustable frequency drive is ready parameter group 2-2* are active. The
for operation and there is no output must be reinforced to carry
overtemperature warning. the current for the coil in the brake.
Usually solved by connecting an
[23] Remote,ready,no TW Adjustable frequency drive is ready
external relay to the selected digital
for operation and is in auto on
output.
mode. There is no overtemperature
warning. [33] Safe stop active (FC 302 only) Indicates that the safe
stop on terminal 37 has been
[24] Ready, Voltage OK Adjustable frequency drive is ready
activated.
for operation and the AC line
voltage is within the specified [36] Control word bit 11 Activate relay 1 by control word
voltage range (see General Specifi- from the serial communication bus.
cations section in Design Guide). No other functional impact in the
Adjustable frequency drive. Typical
[25] Reverse Logic ‘1’ when CW rotation of the
application: controlling auxiliary
motor. Logic ‘0’ when CCW rotation
device from the serial communi-
of the motor. If the motor is not
cation bus. The function is valid
rotating, the output will follow the
when FC profile [0] in 8-10 Control
reference.
Word Profile is selected.
[26] Bus OK Active communication (no timeout)
[37] Control word bit 12 Activate relay 2 FC 302 only) by
via the serial communication port.
control word from serial communi-
cation bus. No other functional
[43] Extended PID Limit [70] Logic rule 0 See parameter group 13-4*(Smart
[45] Bus ctrl. Controls digital output/relay via bus. Logic Control). If Logic Rule 0 in SLC
The state of the output is set in is TRUE, the output will go high.
5-90 Digital & Relay Bus Control. The Otherwise, it will be low.
output state is retained in the event
[71] Logic rule 1 See parameter group 13-4*(Smart
of bus timeout.
Logic Control). If Logic Rule 1 in SLC
[46] Bus ctrl, 1 if timeout Controls output via bus. The state of is TRUE, the output will go high.
the output is set in 5-90 Digital & Otherwise, it will be low.
Relay Bus Control. In the event of a
[72] Logic rule 2 See parameter group 13-4*(Smart
bus timeout, the output state is set
Logic Control). If Logic Rule 2 in SLC
high (On).
is TRUE, the output will go high.
[47] Bus ctrl, 0 if timeout Controls output via bus. The state of Otherwise, it will be low.
the output is set in 5-90 Digital &
[73] Logic rule 3 See parameter group 13-4*(Smart
Relay Bus Control. In the event of a
Logic Control). If Logic Rule 3 in SLC
bus timeout, the output state is set
is TRUE, the output will go high.
low (Off).
Otherwise, it will be low.
[51] MCO controlled Active when a MCO 302 or MCO 305
[74] Logic rule 4 See parameter group 13-4*(Smart
is connected. The output is
Logic Control). If Logic Rule 4 in SLC
controlled from option.
is TRUE, the output will go high.
Otherwise, it will be low.
[84] SL digital output E See 13-52 SL Controller Action. Output [121] Remote ref active Output is high when 3-13 Reference
E is low on Smart Logic Action [36]. Site = Remote [1] or Linked to hand/
Output E is high on Smart Logic auto [0] while the LCP is in [Auto on]
Action [42]. mode. See above.
[85] SL digital output F See 13-52 SL Controller Action. Output [122] No alarm Output is high when no alarm is
F is low on Smart Logic Action [37]. present.
Output F is high on Smart Logic [123] Start command Output is high when the Start
Action [43]. activ command high (i.e., via digital input,
[120] Local ref active Output is high when 3-13 Reference bus connection or [Hand on] or
Site = [2] Local or when [Auto on]), and a Stop has been last
3-13 Reference Site = [0] Linked to command.
hand auto at the same time as the [124] Running reverse Output is high when the Adjustable
LCP is in [Hand on] mode. frequency drive is running counter
clockwise (the logical product of the
status bits ‘running’ AND ‘reverse’).
130BA171.10
Selected
Array [9] Event
(Relay 1 [0], Relay 2 [1], Relay 3 [2] (MCB 113), Relay 4 [3] (MCB
113), Relay 5 [4] (MCB 113), Relay 6 [5] (MCB 113), Relay 7 [6]
3 3
Relay
output
(MCB 105), Relay 8 [7] (MCB 105), Relay 9 [8] (MCB 105))
Option: Function: On Delay Off Delay
P 5-41 P 5-42
[151] ATEX ETR cur. alarm Selectable if 1-90 Motor Thermal
Protection is set to [20] or [21]. If the
Selected
alarm 164 ATEX ETR cur.lim.alarm is Event
active, the output will be 1.
Relay
[152] ATEX ETR freq. Selectable if 1-90 Motor Thermal output
alarm Protection is set to [20] or [21]. If the
alarm 166 ATEX ETR freq.lim.alarm is On Delay
P 5-41
active, the output will be 1.
130BA172.10
Connect
[189] External Fan Control The internal logics for the internal
Selected
fan control is transferred to this Event
output to make it possible to control
an external fan (relevant for HP duct
Relay
cooling).
output
[192] RS Flipflop 0
[193] RS Flipflop 1 On Delay Off Delay
P 5-41 P 5-42
[194] RS Flipflop 2
[195] RS Flipflop 3
[196] RS Flipflop 4 If the selected event condition changes before the on or
[197] RS Flipflop 5 off delay timer expires, the relay output is unaffected.
[198] RS Flipflop 6
[199] RS Flipflop 7 3.7.5 5-5* Pulse Input
5-41 On Delay, Relay
The pulse input parameters are used to define an
Array [9], (Relay 1 [0], Relay 2 [1], Relay 3 [2], Relay 4 [3], Relay 5 appropriate window for the impulse reference area by
[4], Relay 6 [5], Relay 7 [6], Relay 8 [7], Relay 9 [8]) configuring the scaling and filter settings for the pulse
Range: Function: inputs. Input terminals 29 or 33 act as frequency reference
0.01 s* [0.01 - 600.00 s] Enter the delay of the relay cut-in inputs. Set terminal 29 (5-13 Terminal 29 Digital Input) or
time. Select one of available terminal 33 (5-15 Terminal 33 Digital Input) to Pulse input
mechanical relays and MCB 105 in an [32]. If terminal 29 is used as an input, then set
array function. See 5-40 Function Relay. 5-01 Terminal 27 Mode to Input [0].
Relay 3-6 are included in MCB 113.
130BA076.10
Ref.
(RPM)
High Range: Function:
ref.
value Application [-999999.999 - Enter the high reference
P 5-53/
100 Hz* [0 - 110000 Enter the low frequency limit Application [-999999.999 -
Hz] corresponding to the low motor shaft dependent* 999999.999
speed (i.e., low reference value) in ReferenceFeed-
5-52 Term. 29 Low Ref./Feedb. Value. Refer backUnit]
to the diagram in this section.
This parameter is available for FC 302 5-54 Pulse Filter Time Constant #29
only. Range: Function:
100 [1 - Enter the pulse filter time constant. The
5-51 Term. 29 High Frequency ms* 1000 ms] pulse filter dampens oscillations of the
Range: Function: feedback signal, which is an advantage if
100 Hz* [0 - 110000 Enter the high frequency limit there is a lot of noise in the system. A high
Hz] corresponding to the high motor shaft time constant value results in better
speed (i.e. high reference value) in damping, but also increases the time delay
5-53 Term. 29 High Ref./Feedb. Value. through the filter. This parameter is available
This parameter is available for FC 302 for FC 302 only.
only. This parameter cannot be adjusted while the
motor is running.
5-52 Term. 29 Low Ref./Feedb. Value
5-55 Term. 33 Low Frequency
Range: Function:
Range: Function:
0.000 Reference- [-999999.999 - Enter the low reference
FeedbackUnit* 999999.999 value limit for the motor 100 Hz* [0 - 110000 Enter the low frequency
ReferenceFeed- shaft speed [RPM]. This is Hz] corresponding to the low motor shaft
backUnit] also the lowest feedback speed (i.e., low reference value) in
value, see also 5-57 Term. 5-57 Term. 33 Low Ref./Feedb. Value.
33 Low Ref./Feedb. Value.
Set terminal 29 to digital 5-56 Term. 33 High Frequency
input (5-02 Terminal 29 Range: Function:
Mode =input [0] (default) 100 Hz* [0 - 110000 Enter the high frequency
and 5-13 Terminal 29 Hz] corresponding to the high motor shaft
Digital Input = applicable speed (i.e., high reference value) in
value). 5-58 Term. 33 High Ref./Feedb. Value.
This parameter is
available for FC 302 only.
130BA089.11
Range: Function:
0.000 * [-999999.999 - Enter the low reference value High output
999999.999 ] [RPM] for the motor shaft speed.
3 3
value
P 5-60(term27)
This is also the low feedback
P 5-63(term29)
value, see also 5-52 Term. 29 Low
Ref./Feedb. Value.
5-60 Terminal 27 Pulse Output Variable 5-66 Terminal X30/6 Pulse Output Variable
Option: Function: Select the variable for read-out on terminal X30/6.
[106] Power This parameter is active when option module MCB 101 is
installed in the Adjustable frequency drive.
3 3 [107] Speed
[108] Torque Same options and functions as parameter group 5-6*.
NOTE!
This parameter cannot be adjusted while the motor is
running.
CCW This parameter group selects digital and relay outputs via
A a serial communication bus setting.
NOTE!
This parameter cannot be adjusted while the motor is
running.
3.8 Parameters: 6-** Analog In/Out 6-01 Live Zero Timeout Function
Option: Function:
3.8.1 6-0* Analog I/O Mode
[21] Coast and
130BT103.10
[RPM]
6-00 Live Zero Timeout Time Par 6-xx
'High Ref./ 1500
Range: Function: Feedb. Value'
1200
10 s* [1 - Enter the Live Zero Timeout time period. Live Zero
99 s] Timeout Time is active for analog inputs, i.e., 900
[0] * Off
Range: Function:
[1] Freeze Frozen at the present value 0.14 [Application Enter the low current value. This
output mA* dependant] reference signal should correspond to
[2] Stop Overruled to stop the minimum reference value, set in
3-02 Minimum Reference. The value
[3] Jogging Overruled to jog speed must be set at >2mA in order to
[4] Max. speed Overruled to max. speed activate the Live Zero Timeout
Function in 6-01 Live Zero Timeout
[5] Stop and Overruled to stop with subsequent trip
Function.
trip
[20] Coast
6-25 Terminal 54 High Ref./Feedb. Value 6-34 Term. X30/11 Low Ref./Feedb. Value
Range: Function: Range: Function:
Application [-999999.999 - Enter the analog input 0.000 * [-999999.999 - Sets the analog input scaling
dependent* 999999.999
ReferenceFeed-
scaling value that
corresponds to the
999999.999 ] value to correspond to the low
voltage value (set in 6-30 Terminal 3 3
backUnit] maximum reference X30/11 Low Voltage).
feedback value set in
3-03 Maximum Reference. 6-35 Term. X30/11 High Ref./Feedb. Value
Application [-999999.999 - Enter the analog input Range: Function:
dependent* 999999.999 scaling value that 100.000 * [-999999.999 - Sets the analog input scaling
ReferenceFeed- corresponds to the 999999.999 ] value to correspond to the high
backUnit] maximum reference voltage value (set in
feedback value set in 6-31 Terminal X30/11 High
3-03 Maximum Reference. Voltage).
6-26 Terminal 54 Filter Time Constant 6-36 Term. X30/11 Filter Time Constant
Range: Function: Range: Function:
0.001 s* [0.001 - Enter the time constant. This is a first- 0.001 s* [0.001 - 10.000 s] A 1st order digital low pass filter
10.000 s] order digital low pass filter time time constant for suppressing
constant for suppressing electrical noise electrical noise on terminal X30/11.
in terminal 54. A high time constant
value improves dampening but also NOTE!
increases the time delay through the This parameter cannot be changed while the motor is
filter. running.
3.8.6 6-5* Analog Output 1 [107] Speed Taken from 3-03 Maximum Reference. 20mA =
value in 3-03 Maximum Reference
Parameters for configuring the scaling and limits for [108] Torque Torque reference related to 160% torque.
analog output 1, i.e., Terminal 42. Analog outputs are
[109] Max Out 0Hz = 0mA,4-19 Max Output Frequency =
current outputs: 0/4 – 20mA. Common terminal (terminal
Freq 20mA.
39) is the same terminal and has the same electrical
potential for analog common and digital common [113] PID
connection. Resolution on analog output is 12 bit. Clamped
Output
6-50 Terminal 42 Output
[119] Torque %
Option: Function: lim
Select the function of Terminal 42 as an [130] Output 0Hz = 4mA, 100Hz = 20mA
analog current output. Depending on the freq.
selection the output is either a 0-20mA or 4-20mA
4-20mA output. The current value can be [131] Reference 3-00 Reference Range [Min-Max] 0% = 4mA;
read out in LCP in 16-65 Analog Output 42 4-20mA 100% = 20mA
[mA]. 3-00 Reference Range [-Max-Max] -100% =
[0] * No When no signal on the analog output. 4mA; 0% = 12 mA; +100% = 20 mA
operation [132] Feedback
[52] MCO 4-20mA
0-20mA [133] Motor cur. Value is taken from 16-37 Inv. Max. Current.
[53] MCO 4-20mA Inverter max. current (160% current) is equal
4-20mA to 20mA.
[100] Output 0Hz = 0mA; 100Hz = 20mA.
Example: Inverter norm current (11kW) = 24A.
frequency
160% = 38.4A. Motor norm current = 22A
[101] Reference 3-00 Reference Range [Min - Max] 0% = 0mA;
Readout 11.46mA.
100% = 20mA
16 mA x 22 A
3-00 Reference Range [-Max - Max] -100% = 38.4 A
+ 4 mA = 13.17 mA
[135] Torq.%
4-16 Torque Limit Motor Mode.
i .e . 10 mA :
20
x 100 = 200 %
3 3
10
nom 4-20 torque setting.
130BA075.11
Current
mA (mA)
20
[136] Power Taken from 1-20 Motor Power [kW]
4-20mA
[137] Speed Taken from 3-03 Maximum Reference. 20mA =
0/4
4-20mA Value in 3-03 Maximum Reference. 0% Analog Analog 100% Variable for
output Min Output Max output
Scale Scale example: Speed
par. 6-52 (RPM)
[138] Torque Torque reference related to 160% torque.
par. 6-51
4-20mA
[139] Bus ctrl. An output value set from serial communi- 6-53 Terminal 42 Output Bus Control
0-20 mA cation bus process data. The output will work Range: Function:
independently of internal functions in the
0.00 %* [0.00 - 100.00 %]
Adjustable frequency drive.
[140] Bus ctrl. An output value set from serial communi- 6-54 Terminal 42 Output Timeout Preset
4-20 mA cation bus process data. The output will work Range: Function:
independently of internal functions in the 0.00 %* [0.00 - 100.00 %]
Adjustable frequency drive.
6-55 Analog Output Filter
[141] Bus ctrl 4-54 Warning Reference Low defines the
Option: Function:
0-20mA t.o. behavior of the analog output in case of bus
timeout. The following readout analog parameters from
selection in 6-50 Terminal 42 Output have a filter
[142] Bus ctrl 4-54 Warning Reference Low defines the selected when 6-55 Analog Output Filter is on:
4-20mA t.o. behavior of the analog output in case of bus
timeout. Selection 0-20mA 4-20mA
[149] Torque % Analog output at zero torque = 12mA. Motor current (0 - Imax) [103] [133]
lim 4-20mA Motoric torque will increase the output Torque limit (0 - Tlim) [104] [134]
current to max torque limit 20mA (set in Rated torque (0 - Tnom) [105] [135]
4-16 Torque Limit Motor Mode). Power (0 - Pnom) [106] [136]
Generative torque will decrease the output to Speed (0 - Speedmax) [107] [137]
torque limit Generator Mode (set in
4-17 Torque Limit Generator Mode) [0] * Off Filter off
Ex: 4-16 Torque Limit Motor Mode : 200% and
4-17 Torque Limit Generator Mode: 200%. [1] On Filter on
20mA = 200% Motoric and 4mA = 200%
Generatoric.
3.8.7 6-6* Analog Output 2 MCB 101
0mA 4mA 12 mA 20 mA
130BB372.10
Par 4-17
(200%)
0% Torque Par 4-16
(200%)
Analog outputs are current outputs: 0/4 - 20mA. Common
terminal (terminal X30/8) is the same terminal and
electrical potential for analog common connection.
Resolution on analog output is 12 bit.
[150] Max Out Fr 0hz = 0mA,4-19 Max Output Frequency =
6-60 Terminal X30/8 Output
4-20mA 20mA.
Option: Function:
6-51 Terminal 42 Output Min Scale Select the function of Terminal X30/8 as an
Range: Function: analog current output. Depending on the
selection the output is either a 0-20mA or
0.00 %* [0.00 - 200.00 %]
4-20mA output. The current value can be
3 3 [0] * No
[mA].
[105] Torq relate The torque is related to the motor torque [138] Torque Torque reference related to 160% torque.
to rated setting. 4-20mA
[139] Bus ctrl. An output value set from serial communi-
[106] Power Taken from 1-20 Motor Power [kW].
0-20 mA cation bus process data. The output will work
[107] Speed Taken from 3-03 Maximum Reference. 20mA = independently of internal functions in the
value in 3-03 Maximum Reference Adjustable frequency drive.
[108] Torque Torque reference related to 160% torque. [140] Bus ctrl. An output value set from serial communi-
[109] Max Out In relation to 4-19 Max Output Frequency. 4-20 mA cation bus process data. The output will work
Freq independently of internal functions in the
[113] PID Adjustable frequency drive.
Clamped [141] Bus ctrl 4-54 Warning Reference Low defines the
Output 0-20mA t.o. behavior of the analog output in case of bus
[119] Torque % timeout.
lim
[142] Bus ctrl 4-54 Warning Reference Low defines the
[130] Output 0hz = 4mA, 100hz = 20mA
4-20mA t.o. behavior of the analog output in case of bus
freq.
timeout.
4-20mA
[149] Torque % Torque% Lim 4-20mA: Torque reference.
lim 4-20mA 3-00 Reference Range [Min-Max] 0% = 4mA;
100% = 20mA
3 3
4mA; 0% = 12 mA; +100% = 20 mA kW]) = 24 A. 160% = 38.4 A. Motor norm
current = 22 A Readout 11.46mA.
[150] Max Out Fr In relation to 4-19 Max Output Frequency.
20 mA x 22 A
= 11.46 mA
4-20mA 38.4 A
If the norm motor current is equal to 20mA,
6-61 Terminal X30/8 Min. Scale
the output setting of 6-52 Terminal 42
Range: Function: Output Max Scale is:
0.00 %* [0.00 - 200.00 %] I VLT x 100
Max 38.4 x 100
= = 175 %
I Motor 22
6-62 Terminal X30/8 Max. Scale Norm
[104] Torque rel The torque setting is related to setting in
Range: Function:
to lim 4-16 Torque Limit Motor Mode
100.00 %* [0.00 - 200.00 %]
0-20mA
20 mA / desired maximum current x 100 % [105] Torque rel The torque is related to the motor torque
20 − 4 to rated setting.
i .e . 10 mA : x 100 = 160 %
10
motor
6-63 Terminal X30/8 Bus Control
torque
Range: Function: 0-20mA
0.00 %* [0.00 - 100.00 %] [106] Power Taken from 1-20 Motor Power [kW].
0-20mA
6-64 Terminal X30/8 Output Timeout Preset
[107] Speed Taken from 3-03 Maximum Reference. 20mA
Range: Function: 0-20mA = value in 3-03 Maximum Reference
0.00 %* [0.00 - 100.00 %] [108] Torque ref. Torque reference related to 160% torque.
0-20mA
3.8.8 6-7* Analog Output 3 MCB 113 [109] Max Out In relation to 4-19 Max Output Frequency.
Freq 0–
Parameters for configuring the scaling and limits for 20mA
analog output 3, Terminal X45/1 and X45/2. Analog [130] Output freq. 0hz = 4mA, 100hz = 20mA
outputs are current outputs: 0/4 – 20mA. Resolution on 4–20 mA
analog output is 11 bit. [131] Reference 3-00 Reference Range [Min-Max] 0% = 4mA;
4–20 mA 100% = 20mA
6-70 Terminal X45/1 Output
3-00 Reference Range [-Max-Max] -100% =
Option: Function: 4mA; 0% = 12 mA; +100% = 20 mA
Select the function of Terminal X45/1 as an [132] Feedback 4–
analog current output. 20 mA
[0] No When no signal on the analog output. [133] Motor cur. Value is taken from 16-37 Inv. Max. Current.
operation 4–20 mA Inverter max. current (160% current) is equal
[52] MCO 305 to 20mA.
0-20mA Example: Inverter norm current (15 hp [11
[53] MCO 305 kW]) = 24 A. 160% = 38.4 A. Motor norm
4-20mA current = 22 A Readout 11.46mA.
[100] Output 0hz = 0mA; 100hz = 20mA. 16 mA x 22 A
= 9.17 mA
38.4 A
frequency
If the norm motor current is equal to 20mA,
0-20mA
the output setting of 6-52 Terminal 42
[101] Reference 3-00 Reference Range [Min - Max] 0% = 0mA;
Output Max Scale is:
0-20mA 100% = 20mA I VLT x 100
Max 38.4 x 100
3-00 Reference Range [-Max - Max] -100% = = = 175 %
I Motor 22
0mA; 0% = 10mA; +100% = 20 mA Norm
6-70 Terminal X45/1 Output 6-72 Terminal X45/1 Output Max Scale
Option: Function: Range: Function:
[135] Torque% The torque setting is related to the motor maximum output (100%), calculate the
130BA877.10
[138] Torque 4–20 Torque reference related to 160% torque. [mA]
mA
[139] Bus ctrl. An output value set from the serial 20
0-20 mA communication bus process data. The
output will work independently of internal
functions in the Adjustable frequency drive.
[140] Bus ctrl. An output value set from the serial
4-20 mA communication bus process data. The
output will work independently of internal 0/4
functions in the Adjustable frequency drive. 0% Analogue Analogue 100% Variable for
output Min Output Max output
[141] Bus ctrl. 4-54 Warning Reference Low defines the Scale Scale example:Speed
0-20mA, behavior of the analog output in case of bus par. 6-71 par. 6-72 [RPM]
timeout timeout.
[142] Bus ctrl. 4-54 Warning Reference Low defines the 6-73 Terminal X45/1 Output Bus Control
4-20mA, behavior of the analog output in case of bus
Range: Function:
timeout timeout.
0.00%* [0.00–100.00%] Holds the level of Analog Output 3
[150] Max Out In relation to 4-19 Max Output Frequency.
(terminal X45/1) if controlled by bus.
Freq
4-20mA 6-74 Terminal X45/1 Output Timeout Preset
6-71 Terminal X45/1 Output Min Scale Range: Function:
Range: Function: 0.00%* [0.00– Holds the preset level of Analog Output
100.00%] 3 (terminal X45/1).
0.00%* [0.00– Scale the minimum output of the selected
In case of a bus timeout and a timeout
200.00%] analog signal at terminal X45/1 as a
function is selected in 6-70 Terminal
percentage of the maximum signal value,
X45/1 Output the output will preset to
e.g., if 0mA (or 0hz) is desired at 25% of
this level.
the maximum output value, then program
25%. Scaling values up to 100% can never
be higher than the corresponding setting 3.8.9 6-8* Analog Output 4 MCB 113
in 6-72 Terminal X45/1 Max. Scale.
Parameters for configuring the scaling and limits for
6-72 Terminal X45/1 Output Max Scale
analog output 4. Terminal X45/3 and X45/4. Analog
Range: Function: outputs are current outputs: 0/4 – 20mA. Resolution on
100%* [0.00– Scale the maximum output of the selected analog output is 11 bit.
200.00%] analog signal at terminal X45/1. Set the value
6-80 Terminal X45/3 Output
to the maximum value of the current signal
output. Scale the output to give a current Option: Function:
lower than 20 mA at full scale, or 20 mA at Select the function of Terminal X45/3 as an
an output below 100% of the maximum analog current output.
signal value. If 20mA is the desired output [0] * No operation Same selections available as for 6-70 Terminal
current at a value between 0–100% of the X45/1 Output
full-scale output, program the percentage
value in the parameter, i.e., 50% = 20mA. If a
current between 4 and 20mA is desired at
7-04 Speed PID Differentiation Time 7-06 Speed PID Lowpass Filter Time
Range: Function: Range: Function:
tiator. The gain is proportional with the higher than 1.6 Hz, the PID regulator
speed at which errors change. Setting
this parameter to zero disables the
does not react.
Practical settings of 7-06 Speed PID 3 3
differentiator. This parameter is used Lowpass Filter Time taken from the
with 1-00 Configuration Mode Speed number of pulses per revolutions from
closed-loop [1] control. encoder:
Application [0.0 - Enter the speed controller differentiation Encoder PPR 7-06 Speed PID
dependent* 200.0 time. The differentiator does not react to Lowpass Filter Time
ms] constant error. It provides gain propor-
512 10 ms
tional to the rate of change of the speed
1,024 5 ms
feedback. The quicker the error changes,
2,048 2 ms
the stronger the gain from the differen-
4,096 1 ms
tiator. The gain is proportional with the
speed at which errors change. Setting
this parameter to zero disables the Note that severe filtering can be
differentiator. This parameter is used detrimental to dynamic performance.
with 1-00 Configuration Mode Speed This parameter is used with 1-00 Config-
closed-loop [1] control. uration Mode Speed closed-loop [1] and
Torque [2] control.
7-05 Speed PID Diff. Gain Limit The filter time in flux sensorless must
be adjusted to 3–5 ms.
Range: Function:
5.0* [1.0 - Set a limit for the gain provided by the differ-
20.0 ] entiator. Since the differential gain increases at
higher frequencies, limiting the gain may be
useful. For example, set up a pure D-link at low
frequencies and a constant D-link at higher
frequencies. This parameter is used with
1-00 Configuration Mode Speed closed-loop [1]
control.
Feedback
175ZA293.11
130BA871.10
Disturbed feedback signal
3 3 n1 n2
Motor
Motor
130BC026.10
Speed
7-09
Torque Time
Limit
Motor
Speed
0.6 t (Sec.)
7-09
7-34 Process PID Integral Time 3.9.5 7-4* Advanced Process PID Ctrl.
Range: Function:
the setpoint and the feedback Parameter group 7-4* is only used if 1-00 Configuration
Mode is set to [7] Extended PID speed CL or [8] Extended
3 3 signal. The integral time is the time
needed by the integrator to reach PID Speed OL.
the same gain as the proportional 7-40 Process PID I-part Reset
gain.
Option: Function:
[0] * No
7-35 Process PID Differentiation Time
[1] Yes Select Yes [1] to reset the I-part of the process PID
Range: Function:
controller. The selection will automatically revert to No
0.00 s* [0.00 - Enter the PID differentiation time. The [0]. Resetting the I-part makes it possible to start from
10.00 s] differentiator does not react to a constant a well-defined point after changing something in the
error, but provides a gain only when the process, e.g., changing a textile roll.
error changes. The shorter the PID differ-
entiation time, the stronger the gain from 7-41 Process PID Output Neg. Clamp
the differentiator.
Range: Function:
7-36 Process PID Diff. Gain Limit -100 %* [Application Enter a negative limit for the
Range: Function: dependant] process PID controller output.
7-45 Process PID Feed Fwd Resource 7-51 Process PID Feed Fwd Gain
Option: Function: Range: Function:
[1] Analog input 53 1.00* [0.00 - The feed forward is used to obtain the
[2]
[7]
Analog input 54
Frequency input 29
100.00 ] desired level, based on a well-known signal
available. The PID controller then only takes 3 3
[8] Frequency input 33 care of the smaller part of the control,
[11] Local bus reference necessary because of unknown characters.
[20] Digital pot.meter The standard feed fwd factor in 7-38 Process
PID Feed Forward Factor is always related to
[21] Analog input X30-11
the reference whereas 7-51 Process PID Feed
[22] Analog input X30-12
Fwd Gain has more choices. In winder
[32] Bus PCD Selects a bus reference configured by
applications, the feed fwd factor will typically
8-02 Control Word Source. Change
be the line speed of the system.
8-42 PCD write configuration for the
bus used in order to make the feed-
7-52 Process PID Feed Fwd Ramp up
forward available in 7-48 PCD Feed
Forward. Use index 1 for feed-forward Range: Function:
[748] (and index 2 for reference 0.01 s* [0.01 - 10.00 s] Controls the dynamics of the feed
[1682]). forward signal when ramping up.
7-46 Process PID Feed Fwd Normal/ Inv. Ctrl. 7-53 Process PID Feed Fwd Ramp down
Option: Function: Range: Function:
[0] * Normal Select Normal [0] to set the feed forward factor to 0.01 s* [0.01 - 10.00 s] Controls the dynamics of the feed
treat the FF resource as a positive value. forward signal when ramping down.
3.10 Parameters: 8-** Communications and 8-03 Control Word Timeout Time
Options Range: Function:
communication has stopped. The
3.10.1 8-0* General Settings
3 3 function selected in 8-04 Control Word
Timeout Function will then be carried
8-01 Control Site out. The timeout counter is triggered by
Option: Function: a valid control word.
The setting in this parameter overrides
the settings in 8-50 Coasting Select to 8-04 Control Word Timeout Function
8-56 Preset Reference Select. Select the timeout function. The timeout function activates when
the control word fails to be updated within the time period
[0] * Digital and Control by using both digital input and
specified in 8-03 Control Word Timeout Time.
ctrl.word control word.
Option: Function:
[1] Digital only Control by using digital inputs only.
[0] * Off Resumes control via serial bus (Serial
[2] Controlword only Control by using control word only. communication bus or standard) using the
most recent control word.
8-02 Control Word Source
[1] Freeze output Freezes output frequency until communi-
Select the source of the control word: one of two serial interfaces cation resumes.
or four installed options. During initial power-up, the Adjustable
frequency drive automatically sets this parameter to Option A [3] [2] Stop Stops with auto-restart when communi-
if it detects a valid Serial communication bus option installed in cation resumes.
slot A. If the option is removed, the Adjustable frequency drive [3] Jogging Runs the motor at JOG frequency until
detects a change in the configuration, sets 8-02 Control Word communication resumes.
Source back to default setting RS-485, and the Adjustable
[4] Max. speed Runs the motor at maximum frequency
frequency drive then trips. If an option is installed after initial
until communication resumes.
power-up, the setting of 8-02 Control Word Source will not
change but the Adjustable frequency drive will trip and display: [5] Stop and trip Stops the motor, then resets the Adjustable
Alarm 67 Option Changed. frequency drive in order to restart: via the
When you retrofit a bus option into a Adjustable frequency drive Serial communication bus, via the reset
that did not have a bus option installed to begin with, you must button on the LCP or via a digital input.
take an ACTIVE decision to move the control to bus-based. This [7] Select setup 1 Changes the set-up upon reestablishment of
is done for safety reasons in order to avoid an accidental change. communication following a control word
Option: Function: timeout. If communication resumes causing
[0] None the timeout situation to disappear,
[1] FC RS485 8-05 End-of-Timeout Function defines
[2] FC USB whether to resume the set-up used before
[3] * Option A the timeout or to retain the set-up
endorsed by the timeout function.
[4] Option B
[5] Option C0 [8] Select setup 2 See [7] Select setup 1
[6] Option C1 [9] Select setup 3 See [7] Select setup 1
[30] External Can
[10] Select setup 4 See [7] Select setup 1
NOTE! [26] Trip
This parameter cannot be adjusted while the motor is
running. NOTE!
The following configuration is required in order to change
8-03 Control Word Timeout Time the set-up after a timeout:
Set 0-10 Active Set-up to [9] Multi set-up and select the
Range: Function:
relevant link in 0-12 This Set-up Linked to.
1.0 s* [Application Enter the maximum time expected to
dependant] pass between the reception of two
consecutive messages. If this time is
exceeded, it indicates that the serial
NOTE! alarms
[2] Trigger
This is only valid for Profibus.
alarm/
warn.
- Disable [0]: Do not send extended
diagnosis data even if they appear in 8-08 Readout Filtering
the Adjustable frequency drive. The function is used if the speed feedback value readouts on
- Trigger on alarms [1]: Send extended serial communication bus are fluctuating. Select filtered if the
diagnosis data when one or more function is required. A power-cycle is required for changes to
alarms appear in alarm 16-90 Alarm take effect.
Word or 9-53 Profibus Warning Word. Option: Function:
- Trigger alarms/warn. [2]: Send extended [0] * Motor Data Std- Select [0] for normal bus
diagnosis data if one or more alarms or Filt. readouts.
warnings appear in alarm 16-90 Alarm
[1] Motor Data LP- Select [1] for filtered bus
Word, 9-53 Profibus Warning Word, or
Filter readouts of the following
warning 16-92 Warning Word.
parameters:
The content of the extended diagnosis frame is 16-10 Power [kW]
as follows: 16-11 Power [hp]
[16] T37 DI status The input will go high whenever T37 has
8-10 Control Word Profile
0 V and will go low whenever T37 has 24
Select the interpretation of the control and status words V
corresponding to the installed Serial communication bus. Only
[21] Thermal The thermal warning turns on when the
the selections valid for the Serial communication bus installed in
warning temperature exceeds the limit in the
slot A will be visible in the LCP display.
motor, the Adjustable frequency drive, the
For guidelines in selection of FC profile [0] and PROFIdrive profile
brake resistor, or the thermistor.
[1] please refer to the Serial communication via RS 485 Interface
section. [30] Brake fault Will go high when the brake IGBT is short-
For additional guidelines in the selection of PROFIdrive profile [1], (IGBT) circuited.
ODVA [5] and CANopen DSP 402 [7], please refer to the
[40] Out of ref If Comparator 0 is evaluated as TRUE, the
Instruction Manual for the installed Serial communication bus.
range input will go high. Otherwise, it will be
Option: Function: low.
[0] * FC profile
[60] Comparator 0 If Comparator 0 is evaluated as TRUE, the
[1] PROFIdrive profile
input will go high. Otherwise, it will be
[5] ODVA low.
[7] CANopen DSP 402
[61] Comparator 1 If Comparator 1 is evaluated as TRUE, the
[8] MCO
input will go high. Otherwise, it will be
8-13 Configurable Status Word STW low.
Option: Function: [62] Comparator 2 If Comparator 2 is evaluated as TRUE, the
[0] No function The input is always low. input will go high. Otherwise, it will be
low.
[1] * Profile Default Depended on the profile set in
8-10 Control Profile. [63] Comparator 3 If Comparator 3 is evaluated as TRUE, the
input will go high. Otherwise, it will be
[2] Alarm 68 Only The input will go high whenever Alarm 68
low.
is active and will go low whenever no
alarm 68 is active [64] Comparator 4 If Comparator 4 is evaluated as TRUE, the
input will go high. Otherwise, it will be
[3] Trip excl Alarm The input will go high whenever Trip on
low.
68 other alarms is active, and then Alarm 68
is active. [65] Comparator 5 If Comparator 5 is evaluated as TRUE, the
input will go high. Otherwise, it will be
[10] T18 DI status The input will go high whenever T18 has
low.
24 V and will go low whenever T18 has 0
V. [70] Logic Rule 0 If Logic Rule 0 is evaluated as TRUE, the
input will go high. Otherwise, it will be
[11] T19 DI status The input will go high whenever T19 has
low.
24 V and will go low whenever T19 has 0
V.
8-13 Configurable Status Word STW 8-13 Configurable Status Word STW
Option: Function: Option: Function:
[71] Logic Rule 1 If Logic Rule 1 is evaluated as TRUE, the input will go low whenever the Smart
input will go high. Otherwise, it will be
low.
Logic Action [37] Set dig. out. A low is
executed 3 3
[72] Logic Rule 2 If Logic Rule 2 is evaluated as TRUE, the [86] ATEX ETR cur. Selectable if par. 1-90 is set to [20] or [21].
input will go high. Otherwise, it will be alarm If the alarm 164 ATEX ETR cur.lim.alarm is
low. active, the output will be 1.
[73] Logic Rule 3 If Logic Rule 3 is evaluated as TRUE, the [87] ATEX ETR freq. Selectable if par. 1-90 is set to [20] or [21].
input will go high. Otherwise, it will be alarm If the alarm 166 ATEX ETR freq.lim.alarm is
low. active, the output will be 1.
[74] Logic Rule 4 If Logic Rule 4 is evaluated as TRUE, the [88] ATEX ETR cur. Selectable if par. 1-90 is set to [20] or [21].
input will go high. Otherwise, it will be warning If the alarm 163 ATEX ETR cur.lim.warning
low. is active, the output will be 1.
[75] Logic Rule 5 If Logic Rule 5 is evaluated as TRUE, the [89] ATEX ETR freq. Selectable if par. 1-90 is set to [20] or [21].
input will go high. Otherwise, it will be warning If the warning 165 ATEX ETR
low. freq.lim.warning is active, the output will
be 1.
[80] SL digital out A SL Controller Action. The input will go
high whenever the Smart Logic Action [90] Safe Function
[38] Set dig. out. A high is executed. The active
input will go low whenever the Smart [91] Safe Opt. Reset
Logic Action [32] Set dig. out. A low is req.
executed.
8-14 Configurable Control Word CTW
[81] SL digital out B SL Controller Action. The input will go
Option: Function:
high whenever the Smart Logic Action
[39] Set dig. out. A high is executed. The Selection of control word bit 10 if it is active
input will go low whenever the Smart low or active high
Logic Action [33] Set dig. out. A low is [0] None
executed. [1] * Profile
[82] SL digital out C SL Controller Action. The input will go default
high whenever the Smart Logic Action [2] CTW Valid,
[40] Set dig. out. A high is executed. The active low
input will go low whenever the Smart [3] Safe Option
Logic Action [34] Set dig. out. A low is Reset
executed. [4] PID error When enabled, it inverts the resulting error
inverse from the process PID controller. Available
[83] SL digital out D SL Controller Action. The input will go
only if "Configuration Mode" is set to
high whenever the Smart Logic Action
"Surface Winder," "Extended PID Speed OL"
[41] Set dig. out. A high is executed. The
or "Extended PID Speed CL."
input will go low whenever the Smart
Logic Action [35] Set dig. out. A low is [5] PID reset I When enabled, resets the I-part of the
executed. part process PID controller. Equivalent to
7-40 Process PID I-part Reset. Available only if
[84] SL digital out E SL Controller Action. The input will go
"Configuration Mode" is set to "Surface
high whenever the Smart Logic Action
Winder," "Extended PID Speed OL" or
[42] Set dig. out. A high is executed. The
"Extended PID Speed CL."
input will go low whenever the Smart
Logic Action [36] Set dig. out. A low is [6] PID enable When enabled, enables the extended
executed. process PID controller. Equivalent to
7-50 Process PID Extended PID. Available only
[85] SL digital out F SL Controller Action. The input will go
if "Configuration Mode" is set "Extended PID
high whenever the Smart Logic Action
Speed OL" or "Extended PID Speed CL."
[43] Set dig. out. A high is executed. The
3 3 Option:
[0] * FC
Function:
Communication according to the FC Protocol
dependent* dependant] permissible delay time
between transmitting a
as described in the VLT AutomationDrive request and receiving a
Design Guide, RS485 Installation and Set-up. response. Exceeding this delay
time will cause control word
[1] FC MC Select the protocol for the FC (standard) port.
timeout.
[2] * Modbus RTU
8-37 Max Inter-Char Delay
8-31 Address
Range: Function:
Range: Function:
Application [Application Specify the maximum
Size related* [ 1. - 255. ]
dependent* dependant] permissible time interval
8-32 FC Port Baud Rate between receiving two bytes.
This parameter activates
Option: Function:
timeout if transmission is
[0] 2400 Baud Baud rate selection for the FC (standard) interrupted.
port. This parameter is active only
[1] 4800 Baud when 8-30 Protocol is set to FC
[2] * 9600 Baud MC [1] protocol.
[3] 19200 Baud
[4] 38400 Baud
3.10.4 8-4* FC MC protocol set
[5] 57600 Baud
[6] 76800 Baud
8-40 Telegram selection
[7] 115200 Baud
Option: Function:
8-33 Parity / Stop Bits [1] * Standard telegram 1 Enables use of freely configurable
Option: Function: messages or standard messages for
[0] * Even Parity, 1 Stop Bit the FC port.
[1] Odd Parity, 1 Stop Bit [100] None
[2] No Parity, 1 Stop Bit [101] PPO 1
[3] No Parity, 2 Stop Bits [102] PPO 2
[103] PPO 3
8-34 Estimated cycle time
[104] PPO 4
Range: Function:
[105] PPO 5
0 ms* [0 - In a noisy environments, the interface may [106] PPO 6
1000000 ms] be blocked by due to overload of bad
[107] PPO 7
frames. This parameter specifies the time
[108] PPO 8
between two consecutive frames on the
[200] Custom telegram 1 Enables use of freely configurable
network. If the interface does not detect
messages or standard messages for
valid frames in that time it flushes the
the FC port.
receive buffer.
[202] Custom telegram 3
8-35 Minimum Response Delay
8-41 Parameters for signals
Range: Function:
Option: Function:
10 ms* [Application Specify the minimum delay time
[0] * None This parameter contains a
dependant] between receiving a request and
list of signals available for
transmitting a response. This is used
selection in 8-42 PCD
for overcoming modem turnaround
write configuration and
delays.
8-43 PCD read configu-
ration.
[2] Logic AND [1] Bus Activates the Reverse command via the serial
[3] * Logic OR communication port or Serial communication
bus option .
8-52 DC Brake Select
[2] Logic Activates the Reverse command via the Serial
Option: Function:
AND communication bus/serial communication port,
Select control of the DC brake via the terminals AND additionally via one of the digital inputs.
(digital input) and/or via the serial communi-
cation bus. [3] * Logic OR Activates the Reverse command via the Serial
communication bus/serial communication port
NOTE! OR via one of the digital inputs.
Only selection [0] Digital input is available
when 1-10 Motor Construction is set to [1] 8-55 Set-up Select
PM non-salient SPM. Option: Function:
Select control of the Adjustable frequency drive
[0] Digital Activates Start command via a digital input. set-up selection via the terminals (digital input)
input and/or via the serial communication bus.
[1] Bus Activates Start command via the serial
[0] Digital Activates the set-up selection via a digital
communication port or serial communication
input input.
option.
8-56 Preset Reference Select These parameters are used for monitoring the bus
Option: Function: communication via the Adjustable Frequency Drive Port.
Select control of the Adjustable frequency drive 8-80 Bus Message Count
Preset Reference selection via the terminals Range: Function:
(digital input) and/or via the serial communi-
0* [0 - 0 ] This parameter shows the number of valid
cation bus.
messages detected on the bus.
[0] Digital Activates Preset Reference selection via a digital
input input. 8-81 Bus Error Count
[1] Bus Activates Preset Reference selection via the Range: Function:
serial communication port or serial communi- 0* [0 - 0 ] This parameter shows the number of messages
cation option. with faults (e.g., CRC fault), detected on the bus.
Address, the hardware switch must be set to [417] Torque Limit Generator Mode
126 or 127 (i.e. all switches set to ‘on’).
[590] Digital & Relay Bus Control
Otherwise this parameter will display the
[593] Pulse Out #27 Bus Control
actual setting of the switch.
[595] Pulse Out #29 Bus Control
[597] Pulse Out #X30/6 Bus Control
9-22 Telegram Selection
[653] Term 42 Output Bus Ctrl
Displays the Profibus telegram configuration.
[663] Terminal X30/8 Bus Control
Option: Function: [673] Terminal X45/1 Bus Control
[1] Standard telegram 1 [683] Terminal X45/3 Bus Control
[100] * None [748] PCD Feed Forward
[101] PPO 1 [890] Bus Jog 1 Speed
[102] PPO 2 [891] Bus Jog 2 Speed
[103] PPO 3 [1472] Legacy Alarm Word
[104] PPO 4 [1473] Legacy Warning Word
[105] PPO 5 [1474] Leg. Ext. Status Word
[106] PPO 6 [1500] Operating Hours
[107] PPO 7 [1501] Running Hours
[108] * PPO 8 Read only. [1502] kWh Counter
[200] Custom telegram 1 [1600] Control Word
[202] Custom telegram 3 [1601] Reference [Unit]
[1602] Reference %
9-23 Parameters for Signals [1603] Status Word
Array [1000] [1605] Main Actual Value [%]
Read only [1609] Custom Readout
Option: Function: [1610] Power [kW]
This parameter contains a [1611] Power [hp]
list of signals available for [1612] Motor Voltage
selection in 9-15 PCD [1613] Frequency
Write Configuration and [1614] Motor Current
9-16 PCD Read Configu- [1615] Frequency [%]
ration. [1616] Torque [Nm]
[0] * None [1617] Speed [RPM]
[15] Readout: actual setup [1618] Motor Thermal
[302] Minimum Reference [1619] KTY sensor temperature
[303] Maximum Reference [1620] Motor Angle
[312] Catch up/slow Down Value [1621] Torque [%] High Res.
[341] Ramp 1 Ramp up Time [1622] Torque [%]
[342] Ramp 1 Ramp Down Time [1625] Torque [Nm] High
[351] Ramp 2 Ramp up Time [1630] DC Link Voltage
[352] Ramp 2 Ramp down Time [1632] Brake Energy /s
[380] Jog Ramp Time [1633] Brake Energy /2 min
[381] Quick Stop Ramp Time [1634] Heatsink Temp.
[411] Motor Speed Low Limit [RPM] [1635] Inverter Thermal
[412] Motor Speed Low Limit [Hz] [1638] SL Controller State
[413] Motor Speed High Limit [RPM] [1639] Control Card Temp.
[414] Motor Speed High Limit [Hz] [1650] External Reference
This parameter is unique to LCP and serial communication 9-81 Defined Parameters (2)
busses. See also 0-11 Programming Set-up. Array [116]
9-71 Profibus Save Data Values No LCP access
Read only
Option: Function:
Parameter values changed via Profibus are not
Range: Function:
automatically stored in non-volatile memory. 0* [0 - 9999 ] This parameter displays a list of all the defined
Use this parameter to activate a function that Adjustable frequency drive parameters available
stores parameter values in the EEPROM non- for Profibus.
volatile memory, so changed parameter values
will be retained at power-down. 9-82 Defined Parameters (3)
Array [116]
[0] * Off Deactivates the non-volatile storage function.
No LCP access
[1] Store all Stores all parameter values for all set-ups in the Read only
setups non-volatile memory. The selection returns to
Range: Function:
Off [0] when all parameter values have been
0* [0 - 9999 ] This parameter displays a list of all the defined
stored.
Adjustable frequency drive parameters available
for Profibus.
10-11 Process Data Config Write 10-12 Process Data Config Read
Select the process write data for I/O assembly instances 101/151. Select the process read data for I/O assembly instances 101/151.
Elements [2] and [3] of this array can be selected. Elements [0] Elements [2] and [3] of this array can be selected. Elements [0]
and [1] of the array are fixed. and [1] of the array are fixed.
3 3 Option: Function: Option: Function:
[593] Pulse Out #27 Bus Control [1610] Power [kW]
[595] Pulse Out #29 Bus Control [1611] Power [hp]
[597] Pulse Out #X30/6 Bus Control [1612] Motor Voltage
[653] Term 42 Output Bus Ctrl [1613] Frequency
[663] Terminal X30/8 Bus Control [1614] Motor Current
[673] Terminal X45/1 Bus Control [1615] Frequency [%]
[683] Terminal X45/3 Bus Control [1616] Torque [Nm]
[748] PCD Feed Forward [1617] Speed [RPM]
[890] Bus Jog 1 Speed [1618] Motor Thermal
[891] Bus Jog 2 Speed [1619] KTY sensor temperature
[1680] Fieldbus CTW 1 [1620] Motor Angle
[1682] Fieldbus REF 1 [1621] Torque [%] High Res.
[1685] FC Port CTW 1 [1622] Torque [%]
[1686] FC Port REF 1 [1625] Torque [Nm] High
[3310] Sync Factor Master [1630] DC Link Voltage
[3311] Sync Factor Slave [1632] Brake Energy /s
[3401] PCD 1 Write to MCO [1633] Brake Energy /2 min
[3402] PCD 2 Write to MCO [1634] Heatsink Temp.
[3403] PCD 3 Write to MCO [1635] Inverter Thermal
[3404] PCD 4 Write to MCO [1638] SL Controller State
[3405] PCD 5 Write to MCO [1639] Control Card Temp.
[3406] PCD 6 Write to MCO [1650] External Reference
[3407] PCD 7 Write to MCO [1651] Pulse Reference
[3408] PCD 8 Write to MCO [1652] Feedback [Unit]
[3409] PCD 9 Write to MCO [1653] Digi Pot Reference
[3410] PCD 10 Write to MCO [1657] Feedback [RPM]
[1660] Digital Input
10-12 Process Data Config Read
[1661] Terminal 53 Switch Setting
Select the process read data for I/O assembly instances 101/151. [1662] Analog Input 53
Elements [2] and [3] of this array can be selected. Elements [0]
[1663] Terminal 54 Switch Setting
and [1] of the array are fixed.
[1664] Analog Input 54
Option: Function: [1665] Analog Output 42 [mA]
[0] * None [1666] Digital Output [bin]
[15] Readout: actual setup [1667] Freq. Input #29 [Hz]
[1472] Legacy Alarm Word [1668] Freq. Input #33 [Hz]
[1473] Legacy Warning Word [1669] Pulse Output #27 [Hz]
[1474] Leg. Ext. Status Word [1670] Pulse Output #29 [Hz]
[1500] Operating Hours [1671] Relay Output [bin]
[1501] Running Hours [1672] Counter A
[1502] kWh Counter [1673] Counter B
[1600] Control Word [1674] Prec. Stop Counter
[1601] Reference [Unit] [1675] Analog In X30/11
[1602] Reference % [1676] Analog In X30/12
[1603] Status Word [1677] Analog Out X30/8 [mA]
[1605] Main Actual Value [%] [1678] Analog Out X45/1 [mA]
[1609] Custom Readout [1679] Analog Out X45/3 [mA]
function filters out bits in the Main Actual 10-32 Devicenet Revision
Value that should not be sent if they change. Range: Function:
Application [0 - 65535 ] View the DeviceNet revision
10-22 COS Filter 3 dependent* number. This parameter is used
Range: Function: for EDS file creation.
0* [0 - 65535 ] Enter the value for COS Filter 3, to set up the
Application [0 - 65535 ] View the DeviceNet revision
filter mask for PCD 3. When operating in COS
dependent* number. This parameter is used
(Change-Of-State), this function filters out bits
for EDS file creation.
in PCD 3 that should not be sent if they
change.
10-33 Store Always
Option: Function:
10-23 COS Filter 4
[0] * Off Deactivates non-volatile storage of data.
Range: Function:
0* [0 - 65535 ] Enter the value for COS Filter 4 to set up the [1] On Stores parameter data received via DeviceNet in
filter mask for PCD 4. When operating in COS EEProm non-volatile memory as default.
(Change-Of-State), this function filters out bits
in PCD 4 that should not be sent if they 10-39 Devicenet F Parameters
change. Array [1000]
No LCP access
Range: Function:
3.12.4 10-3* Parameter Access
0* [0 - 0 ] This parameter is used to configure the Adjustable
frequency drive via DeviceNet and build the EDS
Parameter group providing access to indexed parameters
file.
and defining programming set-up.
[1] Store all Stores all parameter values from the active set-
setups up in the non-volatile memory. The selection
returns to Off [0] when all values have been
stored.
[2] Store all Stores all parameter values for all set-ups in the
setups non-volatile memory. The selection returns to
Range: Function: [0] Off Link Speed and Link Duplex can be configured in
12-13 Link Speed and 12-14 Link Duplex.
[dd:hh:mm:ss] Read only. Displays the lease time left for the
[1] On
current DHCP-assigned IP address.
12-13 Link Speed
12-06 Name Servers
Option: Function:
Option: Function:
Forces the link speed for each port at 10 or 100
IP addresses of Domain Name Servers. Can
Mbps. If 12-12 Auto Negotiation is set to: ON,
be automatically assigned when using DHCP.
this parameter is read only and displays the
[0] Primary DNS
actual link speed. “None” is displayed if no link
[1] Secondary DNS
is present.
[0] * None
[1] 10 Mbps
Running
Starting and stopping the SLC:
Coast
Warning Start timer Starting and stopping the SLC can be done by
Torque limit Set Do X low selecting .On [1]. or .Off [0]. in 13-00 SL Controller Mode.
Digital inpute X 30/2 Select set-up 2
... ... The SLC always starts in state 0 (where it evaluates event
[0]). The SLC starts when the Start Event (defined in
Par. 13-43 13-01 Start Event) is evaluated as TRUE (provided that On
Logic Rule Operator 2
[1] is selected in 13-00 SL Controller Mode). The SLC stops
when the Stop Event (13-02 Stop Event) is TRUE. 13-03 Reset
SLC resets all SLC parameters and start programming from
... scratch.
...
[6] Current limit Current limit [6] The motor current [20] Alarm (trip) Alarm (trip) [20] A (trip) alarm is active.
limit, set in 4-18 Current Limit, has been
[21] Alarm (trip lock) Alarm (trip lock) [21] A (Trip lock) alarm
exceeded.
is active.
[7] Out of current Out of current range [7] The motor
[22] Comparator 0 Comparator 0 [22] Use the result of
range current is outside the range set in
comparator 0.
4-18 Current Limit.
[23] Comparator 1 Comparator 1 [23] Use the result of
[8] Below I low Below I low [8] The motor current is
comparator 1.
lower than set in 4-50 Warning Current
Low. [24] Comparator 2 Comparator 2 [24] Use the result of
comparator 2.
[9] Above I high Above I high [9] The motor current is
higher than set in 4-51 Warning Current [25] Comparator 3 Comparator 3 [25] Use the result of
High. comparator 3.
[10] Out of speed Out of speed range [10] The speed is [26] Logic rule 0 Logic rule 0 [26] Use the result of logic
range outside the range set in 4-52 Warning rule 0.
Speed Low and 4-53 Warning Speed [27] Logic rule 1 Logic rule 1 [27] Use the result of logic
High. rule 1.
[11] Below speed low Below speed low [11] The output speed [28] Logic rule 2 Logic rule 2 [28] Use the result of logic
is lower than the setting in rule 2.
4-52 Warning Speed Low.
[29] Logic rule 3 Logic rule 3 [29] Use the result of logic
[12] Above speed Above speed high [12] The output rule 3.
high speed is higher than the setting in
[33] Digital input DI18 Digital input DI18 [33] Use the result of
4-53 Warning Speed High.
digital input 18.
[13] Out of feedb. Out of feedb. Range [13] The feedback
[34] Digital input DI19 Digital input DI19 [34] Use the result of
range is outside the range set in
digital input 19.
4-56 Warning Feedback Low and
4-57 Warning Feedback High. [35] Digital input DI27 Digital input DI27 [35] Use the result of
digital input 27.
[14] Below feedb. low Below feedb. Low [14] The feedback is
below the limit set in 4-56 Warning [36] Digital input DI29 Digital input DI27 [35] Use the result of
Feedback Low. digital input 29.
[15] Above feedb. Above feedb. High [15] The feedback is [37] Digital input DI32 Digital input DI32 [37] Use the result of
high above the limit set in 4-57 Warning digital input 32.
Feedback High.
[38] Digital input DI33 Digital input DI33 [38] Use the result of
[16] Thermal warning Thermal warning [16] The thermal digital input 33.
warning turns on when the
[39] Start command Start command [39] A start command is
temperature exceeds the limit in the
issued.
motor, the Adjustable frequency drive,
the brake resistor or the thermistor. [40] Drive stopped Drive stopped [40] A stop command
(Jog, Stop, Qstop, Coast) is issued –
[17] Mains out of Mains out of range [17] The AC line
and not from the SLC itself.
range voltage is outside the specified voltage
range. [41] Reset Trip Reset Trip [41] A reset is issued
3 3 [43] Ok key
performed.
Reset SLC
13 parameters (13-**).
130BB672.10
Comparator Operator
[81] Digital input x46/5 Par. LC-10
[82] Digital input x46/7 Comparator Operand
3 3 [6] Motor power Motor power [6] [kW] or [hp] [54] Running Running [54] The motor is running.
[7] Motor voltage Motor voltage [7] [V] [55] Reversing Reversing [55] The output is high when
the Adjustable frequency drive is
[8] DC-link voltage DC-link voltage [8] [V]
running counter clockwise (the logical
[9] Motor thermal Motor thermal [9] Expressed as a product of the status bits “running”
percentage. AND “reverse”)
[10] Drive thermal VLT thermal [10] Expressed as a [56] In range In range [56] The motor is running
percentage. within the programmed current and
[11] Heat sink temp. Heatsink temp [11] Expressed as a speed ranges set in 4-50 Warning
percentage. Current Low to 4-53 Warning Speed High.
[12] Analog input Analog input AI53 [12] Expressed as a [60] On reference On reference [60] The motor is running
AI53 percentage. on reference.
[13] Analog input Analog input AI54 [13] Expressed as a [61] Below reference, Below reference, low [61] The motor is
AI54 percentage. low running below the value given in
4-54 Warning Reference Low
[14] Analog input Analog input AIFB10 [14] [V]. AIFB10 is
AIFB10 internal 10V supply. [62] Above ref, high Above reference, high [62] The motor is
running above the value given in
[15] Analog input Analog input AIS24V [15] [V] Analog
4-55 Warning Reference High
AIS24V input AICCT [17] [°]. AIS24V is switch
mode power supply: SMPS 24V. [65] Torque limit Torque limit [65] The torque limit, set in
4-16 Torque Limit Motor Mode or
[17] Analog input Analog input AICCT [17] [°]. AICCT is
4-17 Torque Limit Generator Mode, has
AICCT control card temperature.
been exceeded.
[18] Pulse input FI29 Pulse input FI29 [18] Expressed as a
[66] Current limit Current limit [66] The motor current
percentage.
limit, set in 4-18 Current Limit, has been
[19] Pulse input FI33 Pulse input FI33 [19] Expressed as a exceeded.
percentage.
[67] Out of current Out of current range [67] The motor
[20] Alarm number Alarm number [20] The error number. range current is outside the range set in
4-18 Current Limit.
[21] Warning number
[22] Analog input [68] Below I low Below I low [68] The motor current is
x30 11 lower than set in 4-50 Warning Current
[23] Analog input Low.
x30 12 [69] Above I high Above I high [69] The motor current is
[30] Counter A Counter A [30] Number of counts higher than set in 4-51 Warning Current
[31] Counter B Counter B [31] Number of counts High.
[50] FALSE False [50] Enters the fixed value of false [70] Out of speed Out of speed range [70] The speed is
in the comparator. range outside the range set in 4-52 Warning
Speed Low and 4-53 Warning Speed High.
[51] TRUE True [51] Enters the fixed value of true
in the comparator. [71] Below speed low Below speed low [71] The output speed
is lower than the setting in
[52] Control ready Control ready [52] The control board
4-52 Warning Speed Low.
receives supply voltage
[72] Above speed Above speed high [72] The output speed
[53] Drive ready Drive ready [53] The Adjustable
high is higher than the setting in
frequency drive is ready for operation
4-53 Warning Speed High.
and applies a supply signal on the
control board. [75] Out of feedb. Out of feedb. Range [75] The feedback is
range outside the range set in 4-56 Warning
[82] Mains out of Line power out of range [82] The AC line [120] SL Time-out 0 SL Timeout 0 [120] The result of SLC
range voltage is outside the specified voltage timer 0.
range. [121] SL Time-out 1 SL Timeout 1 [121] The result of SLC
[85] Warning Warning [85] A warning is active. timer 1.
[86] Alarm (trip) Alarm (trip) [86] A (trip) alarm is active. [122] SL Time-out 2 SL Timeout 2 [122] The result of SLC
timer 2.
[87] Alarm (trip lock) Alarm (trip lock) [87] A (Trip lock) alarm
is active. [123] SL Time-out 3 SL Timeout 3 [123] The result of SLC
timer 3.
[90] Bus OK Bus OK [90] Active communication (no
timeout) via the serial communication [124] SL Time-out 4 SL Timeout 4 [124] The result of SLC
port. timer 4.
[91] Torque limit & Torque limit & stop [91] If the Adjustable [125] SL Time-out 5 SL Timeout 5 [125] The result of SLC
stop frequency drive has received a stop timer 5.
signal and is at the torque limit, the [126] SL Time-out 6 SL Timeout 6 [126] The result of SLC
signal is logic “0”. timer 6.
[92] Brake fault Brake fault (IGBT) [92] The brake IGBT is [127] SL Time-out 7 SL Timeout 7 [127] The result of SLC
(IGBT) short circuited. timer 7.
[93] Mech. brake Mech. brake control [93] The mechanical [130] Digital input Digital input DI18 [130] Digital input 18.
control brake is active. DI18 High = True.
[94] Safe stop active [131] Digital input Digital input DI19 [131] Digital input 19.
[100] Comparator 0 Comparator 0 [100] The result of DI19 High = True.
comparator 0.
[132] Digital input Digital input DI27 [132] Digital input 27.
[101] Comparator 1 Comparator 1 [101] The result of DI27 High = True.
comparator 1.
[133] Digital input Digital input DI29 [133] Digital input 29.
[102] Comparator 2 Comparator 2 [102] The result of DI29 High = True.
comparator 2.
[134] Digital input Digital input DI32 [134] Digital input 32.
[103] Comparator 3 Comparator 3 [103] The result of DI32 High = True.
comparator 3.
[135] Digital input Digital input DI33 [135] Digital input 33.
[104] Comparator 4 Comparator 4 [104] The result of DI33 High = True.
comparator 4.
[150] SL digital output SL digital output A [150] Use the result
[105] Comparator 5 Comparator 5 [105] The result of A of the SLC output A.
comparator 5.
The Reset-Set Flip Flops hold the signal until set/reset. [27] Logic
13-51 SL Controller Event [1]
rule 1
13-52 SL Controller Action [1] [24] Stop
130BB959.10
Par. 13-15
RS-FF Operand S
13-15 RS-FF Operand S
Par. 13-16
RS-FF Operand R Option: Function:
[0] False
[1] True
[2] Running
Two parameters are used and the output can be used in
[3] In range
the logic rules and as events.
[4] On reference
[5] Torque limit
130BB960.10
3 3 [30]
[31]
SL Time-out 0
SL Time-out 1
[100]
[101]
RS Flipflop 6
RS Flipflop 7
[32] SL Time-out 2
13-16 RS-FF Operand R
[33] Digital input DI18
[34] Digital input DI19 Option: Function:
[35] Digital input DI27 [0] False
[36] Digital input DI29 [1] True
[37] Digital input DI32 [2] Running
[38] Digital input DI33 [3] In range
[39] Start command [4] On reference
[40] Drive stopped [5] Torque limit
[41] Reset Trip [6] Current limit
[42] Auto-reset Trip [7] Out of current range
[43] Ok key [8] Below I low
[44] Reset key [9] Above I high
[45] Left key [10] Out of speed range
[46] Right key [11] Below speed low
[47] Up key [12] Above speed high
[48] Down key [13] Out of feedb. range
[50] Comparator 4 [14] Below feedb. low
[51] Comparator 5 [15] Above feedb. high
[60] Logic rule 4 [16] Thermal warning
[61] Logic rule 5 [17] Mains out of range
[70] SL Time-out 3 [18] Reversing
[71] SL Time-out 4 [19] Warning
[72] SL Time-out 5 [20] Alarm (trip)
[73] SL Time-out 6 [21] Alarm (trip lock)
[74] SL Time-out 7 [22] Comparator 0
[75] Start command given [23] Comparator 1
[76] Digital input x30/2 [24] Comparator 2
[77] Digital input x30/3 [25] Comparator 3
[78] Digital input x30/4 [26] Logic rule 0
[79] Digital input x46/1 [27] Logic rule 1
[80] Digital input x46/3 [28] Logic rule 2
[81] Digital input x46/5 [29] Logic rule 3
[82] Digital input x46/7 [30] SL Time-out 0
[83] Digital input x46/9 [31] SL Time-out 1
[84] Digital input x46/11 [32] SL Time-out 2
[85] Digital input x46/13 [33] Digital input DI18
[90] ATEX ETR cur. warning [34] Digital input DI19
[91] ATEX ETR cur. alarm [35] Digital input DI27
[92] ATEX ETR freq. warning [36] Digital input DI29
[93] ATEX ETR freq. alarm [37] Digital input DI32
[94] RS Flipflop 0 [38] Digital input DI33
[95] RS Flipflop 1 [39] Start command
[96] RS Flipflop 2 [40] Drive stopped
[97] RS Flipflop 3 [41] Reset Trip
[98] RS Flipflop 4 [42] Auto-reset Trip
13-16 RS-FF Operand R All parameters in this parameter group are array
Option: Function: parameters with index 0 to 2. Select index 0 to program
Timer 0, select index 1 to program Timer 1, and so on.
[43] Ok key
[44]
[45]
Reset key
Left key
13-20 SL Controller Timer
Range: Function:
3 3
[46] Right key Application [Application Enter the value to define the
[47] Up key dependent* dependant] duration of the FALSE output
[48] Down key from the programmed timer. A
[50] Comparator 4 timer is only FALSE if it is started
[51] Comparator 5 by an action (i.e., Start timer 1
[60] Logic rule 4 [29]) and until the given timer
[61] Logic rule 5 value has elapsed.
[70] SL Time-out 3
[71] SL Time-out 4
3.14.6 13-4* Logic Rules
[72] SL Time-out 5
[73] SL Time-out 6
Combine up to three boolean inputs (TRUE / FALSE inputs)
[74] SL Time-out 7 from timers, comparators, digital inputs, status bits and
[75] Start command given events using the logical operators AND, OR, and NOT.
[76] Digital input x30/2 Select Boolean inputs for the calculation in 13-40 Logic Rule
[77] Digital input x30/3 Boolean 1, 13-42 Logic Rule Boolean 2 and 13-44 Logic Rule
[78] Digital input x30/4 Boolean 3. Define the operators used to logically combine
[79] Digital input x46/1 the selected inputs in 13-41 Logic Rule Operator 1 and
[80] Digital input x46/3 13-43 Logic Rule Operator 2.
[81] Digital input x46/5
[82] Digital input x46/7 Par. LC-41 Par. LC-43
130BB673.10
Logic Rule Operator 1 Logic Rule Operator 2
[83] Digital input x46/9 Par. LC-40
Logic Rule Boolean 1
[84] Digital input x46/11
Par. LC-42
[85] Digital input x46/13 Logic Rule Boolean 2 ...
...
[90] ATEX ETR cur. warning ...
...
[91] ATEX ETR cur. alarm
[92] ATEX ETR freq. warning Par. LC-44
Logic Rule Boolean 3
[93] ATEX ETR freq. alarm
[94] RS Flipflop 0
[95] RS Flipflop 1 Priority of calculation
[96] RS Flipflop 2
The results of 13-40 Logic Rule Boolean 1, 13-41 Logic Rule
Operator 1 and 13-42 Logic Rule Boolean 2 are calculated
[97] RS Flipflop 3
first. The outcome (TRUE / FALSE) of this calculation is
[98] RS Flipflop 4
combined with the settings of 13-43 Logic Rule Operator 2
[99] RS Flipflop 5
and 13-44 Logic Rule Boolean 3, yielding the final result
[100] RS Flipflop 6
(TRUE / FALSE) of the logic rule.
[101] RS Flipflop 7
13-40 Logic Rule Boolean 1
3.14.5 13-2* Timers Array [6]
Option: Function:
Use the result (TRUE or FALSE) from timers directly to [0] * False Select the first Boolean (TRUE or
define an event (see 13-51 SL Controller Event), or as FALSE) input for the selected logic
Boolean input in a logic rule (see 13-40 Logic Rule Boolean rule.
1, 13-42 Logic Rule Boolean 2 or 13-44 Logic Rule Boolean 3). See 13-01 Start Event ([0] - [61])
A timer is only FALSE when started by an action (i.e., Start and 13-02 Stop Event ([70] - [75])
timer 1 [29]) until the timer value entered in this for further description.
parameter is elapsed. Then it becomes TRUE again.
[1] True
[2] Running
3 3 [3]
[4]
In range
On reference
[60]
[61]
Logic rule 4
Logic rule 5
[5] Torque limit [70] SL Time-out 3
[6] Current limit [71] SL Time-out 4
[7] Out of current range [72] SL Time-out 5
[8] Below I low [73] SL Time-out 6
[9] Above I high [74] SL Time-out 7
[10] Out of speed range [75] Start command given
[11] Below speed low [76] Digital input x30/2
[12] Above speed high [77] Digital input x30/3
[13] Out of feedb. range [78] Digital input x30/4
[14] Below feedb. low [79] Digital input x46/1
[15] Above feedb. high [80] Digital input x46/3
[16] Thermal warning [81] Digital input x46/5
[17] Mains out of range [82] Digital input x46/7
[18] Reversing [83] Digital input x46/9
[19] Warning [84] Digital input x46/11
[20] Alarm (trip) [85] Digital input x46/13
[21] Alarm (trip lock) [90] ATEX ETR cur. warning Selectable if 1-90 Motor Thermal
[22] Comparator 0 Protection is set to [20] or [21]. If
[23] Comparator 1 the alarm 164 ATEX ETR
[24] Comparator 2 cur.lim.alarm is active, the output
[25] Comparator 3 will be 1.
[26] Logic rule 0 [91] ATEX ETR cur. alarm Selectable if1-90 Motor Thermal
[27] Logic rule 1 Protection is set to [20] or [21]. If
[28] Logic rule 2 the alarm 166 ATEX ETR
[29] Logic rule 3 freq.lim.alarm is active, the output
[30] SL Time-out 0 will be 1.
[31] SL Time-out 1 [92] ATEX ETR freq. warning Selectable if 1-90 Motor Thermal
[32] SL Time-out 2 Protection is set to [20] or [21]. If
[33] Digital input DI18 the alarm 163 ATEX ETR
[34] Digital input DI19 cur.lim.warning is active, the
[35] Digital input DI27 output will be 1.
[36] Digital input DI29 [93] ATEX ETR freq. alarm Selectable if 1-90 Motor Thermal
[37] Digital input DI32 Protection is set to [20] or [21]. If
[38] Digital input DI33 the warning 165 ATEX ETR
[39] Start command freq.lim.warning is active, the
[40] Drive stopped output will be 1.
[41] Reset Trip
[94] RS Flipflop 0
[42] Auto-reset Trip
[95] RS Flipflop 1
[43] Ok key
[96] RS Flipflop 2
[44] Reset key
[97] RS Flipflop 3
[45] Left key
[98] RS Flipflop 4
[46] Right key
[99] RS Flipflop 5
[47] Up key
[100] RS Flipflop 6
[48] Down key
[101] RS Flipflop 7
[50] Comparator 4
[51] Comparator 5
3 3 [80]
[81]
Digital input x46/3
Digital input x46/5
13-41 Logic Rule Operator 1, and 13-42 Logic
Rule Boolean 2. DISABLED [0] (factory
[82] Digital input x46/7 setting). select this option to ignore
[83] Digital input x46/9 13-44 Logic Rule Boolean 3.
[84] Digital input x46/11 [0] * DISABLED
[85] Digital input x46/13 [1] AND
[90] ATEX ETR cur. warning Selectable if 1-90 Motor Thermal [2] OR
Protection is set to [20] or [21]. If [3] AND NOT
the alarm 164 ATEX ETR [4] OR NOT
cur.lim.alarm is active, the output [5] NOT AND
will be 1.
[6] NOT OR
[91] ATEX ETR cur. alarm Selectable if 1-90 Motor Thermal [7] NOT AND NOT
Protection is set to [20] or [21]. If [8] NOT OR NOT
the alarm 166 ATEX ETR
freq.lim.alarm is active, the output 13-44 Logic Rule Boolean 3
will be 1. Array [6]
[92] ATEX ETR freq. warning Selectable if1-90 Motor Thermal Option: Function:
Protection is set to [20] or [21]. If [0] * False Select the third Boolean (TRUE or
the alarm 163 ATEX ETR FALSE) input for the selected logic
cur.lim.warning is active, the rule. See 13-01 Start Event ([0] -
output will be 1. [61]) and 13-02 Stop Event ([70] -
[75]) for further description.
[93] ATEX ETR freq. alarm Selectable if 1-90 Motor Thermal
Protection is set to [20] or [21]. If [1] True
the warning 165 ATEX ETR [2] Running
freq.lim.warning is active, the [3] In range
output will be 1. [4] On reference
[94] RS Flipflop 0 [5] Torque limit
[95] RS Flipflop 1 [6] Current limit
[96] RS Flipflop 2 [7] Out of current range
[97] RS Flipflop 3 [8] Below I low
[98] RS Flipflop 4 [9] Above I high
[99] RS Flipflop 5 [10] Out of speed range
[100] RS Flipflop 6 [11] Below speed low
[101] RS Flipflop 7 [12] Above speed high
[13] Out of feedb. range
13-43 Logic Rule Operator 2 [14] Below feedb. low
Array [6] [15] Above feedb. high
Option: Function: [16] Thermal warning
Select the second logical operator to be [17] Mains out of range
used on the Boolean input calculated in [18] Reversing
13-40 Logic Rule Boolean 1, 13-41 Logic Rule [19] Warning
Operator 1, and 13-42 Logic Rule Boolean 2, [20] Alarm (trip)
and the Boolean input coming from [21] Alarm (trip lock)
13-42 Logic Rule Boolean 2. [22] Comparator 0
[13-44] signifies the Boolean input of [23] Comparator 1
13-44 Logic Rule Boolean 3. [24] Comparator 2
[13-40/13-42] signifies the Boolean input [25] Comparator 3
calculated in 13-40 Logic Rule Boolean 1,
[26] Logic rule 0
3 3 [13]
[14]
Out of feedb. range
Below feedb. low
[78]
[79]
Digital input x30/4
Digital input x46/1
[15] Above feedb. high [80] Digital input x46/3
[16] Thermal warning [81] Digital input x46/5
[17] Mains out of range [82] Digital input x46/7
[18] Reversing [83] Digital input x46/9
[19] Warning [84] Digital input x46/11
[20] Alarm (trip) [85] Digital input x46/13
[21] Alarm (trip lock) [90] ATEX ETR cur. warning Selectable if 1-90 Motor Thermal
[22] Comparator 0 Protection is set to [20] or [21]. If
[23] Comparator 1 the alarm 164 ATEX ETR
[24] Comparator 2 cur.lim.alarm is active, the output
[25] Comparator 3 will be 1.
[26] Logic rule 0 [91] ATEX ETR cur. alarm Selectable if 1-90 Motor Thermal
[27] Logic rule 1 Protection is set to [20] or [21]. If
[28] Logic rule 2 the alarm 166 ATEX ETR
[29] Logic rule 3 freq.lim.alarm is active, the output
[30] SL Time-out 0 will be 1.
[31] SL Time-out 1 [92] ATEX ETR freq. warning Selectable if 1-90 Motor Thermal
[32] SL Time-out 2 Protection is set to [20] or [21]. If
[33] Digital input DI18 the alarm 163 ATEX ETR
[34] Digital input DI19 cur.lim.warning is active, the
[35] Digital input DI27 output will be 1.
[36] Digital input DI29 [93] ATEX ETR freq. alarm Selectable if 1-90 Motor Thermal
[37] Digital input DI32 Protection is set to [20] or [21]. If
[38] Digital input DI33 the warning 165 ATEX ETR
[39] Start command freq.lim.warning is active, the
[40] Drive stopped output will be 1.
[41] Reset Trip
[94] RS Flipflop 0
[42] Auto-reset Trip
[95] RS Flipflop 1
[43] Ok key
[96] RS Flipflop 2
[44] Reset key
[97] RS Flipflop 3
[45] Left key
[98] RS Flipflop 4
[46] Right key
[99] RS Flipflop 5
[47] Up key
[100] RS Flipflop 6
[48] Down key
[101] RS Flipflop 7
[50] Comparator 4
[51] Comparator 5 13-52 SL Controller Action
[60] Logic rule 4 Array [20]
[61] Logic rule 5 Option: Function:
[70] SL Time-out 3
[0] * DISABLED Select the action corresponding to the SLC
[71] SL Time-out 4 event. Actions are executed when the
[72] SL Time-out 5 corresponding event (defined in 13-51 SL
[73] SL Time-out 6 Controller Event) is evaluated as true. The
[74] SL Time-out 7 following actions are available for selection:
[75] Start command given
*DISABLED [0]
[76] Digital input x30/2
[77] Digital input x30/3 [1] No action No action [1]
[3] Select set-up Select set-up 2 [3] - changes the active set- [15] Select preset Select preset reference 5 [15] – selects preset
2 up 0-10 Active Set-up) to ‘2’. ref 5 reference 5.
If the set-up is changed, it will merge with If the active preset reference is changed, it
other set-up commands coming from either will merge with other preset reference
the digital inputs or via a serial communi- commands coming from either the digital
cation bus. inputs or via a serial communication bus.
[4] Select set-up Select set-up 3 [4] - changes the active set- [16] Select preset Select preset reference 6 [16] – selects preset
3 up (0-10 Active Set-up) to ‘3’. ref 6 reference 6.
If the set-up is changed, it will merge with If the active preset reference is changed, it
other set-up commands coming from either will merge with other preset reference
the digital inputs or via a serial communi- commands coming from either the digital
cation bus. inputs or via a serial communication bus.
[5] Select set-up Select set-up 4 [5] - changes the active set- [17] Select preset Select preset reference 7 [17] - selects preset
4 up (0-10 Active Set-up) to ‘4’. ref 7 reference 7.
If the set-up is changed, it will merge with If the active preset reference is changed, it
other set-up commands coming from either will merge with other preset reference
the digital inputs or via a serial communi- commands coming from either the digital
cation bus. inputs or via a serial communication bus.
[10] Select preset Select preset reference 0 [10] – selects preset [18] Select ramp 1 Select ramp 1 [18] - selects ramp 1.
ref 0 reference 0.
[19] Select ramp 2 Select ramp 2 [19] - selects ramp 2.
If the active preset reference is changed, it
will merge with other preset reference [20] Select ramp 3 Select ramp 3 [20] - selects ramp 3.
commands coming from either the digital [21] Select ramp 4 Select ramp 4 [21] - selects ramp 4.
inputs or via a serial communication bus.
[22] Run Run [22] - issues a start command to the
[11] Select preset Select preset reference 1 [11] – selects preset Adjustable frequency drive.
ref 1 reference 1.
[23] Run reverse Run reverse [23] - issues a start reverse
If the active preset reference is changed, it
command to the Adjustable frequency
will merge with other preset reference
drive.
commands coming from either the digital
inputs or via a serial communication bus. [24] Stop Stop [24] - issues a stop command to the
Adjustable frequency drive.
[12] Select preset Select preset reference 2 [12] – selects preset
ref 2 reference 2. [25] Qstop Q stop [25] - issues a quick stop command
If the active preset reference is changed, it to the Adjustable frequency drive.
will merge with other preset reference
[26] Dcstop Dcstop [26] - issues a DC stop command to
commands coming from either the digital
the Adjustable frequency drive.
inputs or via a serial communication bus.
[27] Coast Coast [27] - the Adjustable frequency drive
[13] Select preset Select preset reference 3 [13] – selects preset
coasts immediately. All stop commands
ref 3 reference 3.
including the coast command stop the SLC.
If the active preset reference is changed, it
will merge with other preset reference [28] Freeze output Freeze output [28] - freezes the output
commands coming from either the digital frequency of the Adjustable frequency
inputs or via a serial communication bus. drive.
[30] Start timer 1 Start timer 1 [30] - starts timer 1, see [73] Start timer 6 Start Timer 6 [73] - Start Timer 6, see
13-20 SL Controller Timer for further 13-20 SL Controller Timer for further
description. description.
[31] Start timer 2 Start timer 2 [31] - starts timer 2, see [74] Start timer 7 Start Timer 7 [74] - Start Timer 7, see
13-20 SL Controller Timer for further p13-20 SL Controller Timer for further
description. description.
[32] Set digital out Set digital output A low [32] - any output
A low with SL output A will be low.
[33] Set digital out Set digital output B low [33] - any output
B low with SL output B will be low.
[34] Set digital out Set digital output C low [34] - any output
C low with SL output C will be low.
[35] Set digital out Set digital output D low [35] - any output
D low with SL output D will be low.
[36] Set digital out Set digital output E low [36] - any output
E low with SL output E will be low.
[37] Set digital out Set digital output F low [37] - any output
F low with SL output F will be low.
[38] Set digital out Set digital output A high [38] - any output
A high with SL output A will be high.
[39] Set digital out Set digital output B high [39] - any output
B high with SL output B will be high.
[40] Set digital out Set digital output C high [40] - any output
C high with SL output C will be high.
[41] Set digital out Set digital output D high [41] - any output
D high with SL output D will be high.
[42] Set digital out Set digital output E high [42] - any output
E high with SL output E will be high.
[43] Set digital out Set digital output F high [43] - any output
F high with SL output Fwill be high.
NOTE! NOTE!
The output frequency value of the Adjustable frequency Switching frequencies higher than 5.0 kHz lead to
drive must never exceed 1/10 of the switching frequency. automatic derating of the maximum output of the
When the motor is running, adjust the switching frequency Adjustable frequency drive.
in 4-11 Motor Speed Low Limit [RPM] until the motor is as
noiseless as possible. See also 14-00 Switching Pattern and 14-03 Overmodulation
the section Special Conditions in the VLT AutomationDrive
Option: Function:
Design Guide, MG33BXYY.
[0] Off Select Off [0] for no overmodulation of the output
voltage, in order to avoid torque ripple on the
14-01 Switching Frequency motor shaft. This feature may be useful for
Select the inverter switching frequency. Changing the switching applications such as grinding machines.
frequency can help to reduce acoustic noise from the motor.
[1] * On Select On [1] to enable the overmodulation
Default depend on power size.
function for the output voltage. This is the right
Option: Function: choice when it is required that the output voltage
[0] 1.0 kHz is higher than 95% of the input voltage (typical
[1] 1.5 kHz Default switching frequency for when running oversynchronously). The output
500–1,600 hp [355–1,200 kW], 690 voltage is increased according to the degree of
V overmodulation.
[2] 2.0 kHz Default switching frequency for Overmodulation leads to increased torque ripple
350–1,075 hp [250–800 kW], 400 V as harmonics are increased.
and 50–400 hp [37–315 kW], 690 V
130BA097.12
3 3
12 13 18 19 27 29 32 33 20 37
FC 302 monitoring of the Adjustable frequency drive will
still remain active.
14-40 VT Level
Range: Function:
66 %* [40 - 90 %]
NOTE!
This parameter cannot be adjusted while the motor is
running.
[2] On 75%
[3] On 100%
[4] Auto (Low temp
env.)
Range: Function:
3.15.7 14-8* Options
NOTE!
This is required for
14-80 Option Supplied by External 24VDC
correct compensation
in flux mode Option: Function:
(1-01 Motor Control [0] No Select No [0] to use the adjustable frequency drive's
Principle) 24V DC supply.
Heatsink temperature 29 X D
Heatsink sensor 39 X D
Control card temperature 65 X D
Power card temperature 6 2) X D
Heatsink temperature1) 244 X D
Heatsink sensor 1) 245 X D
Power card temperature 1) 247
Table 3.3 Table for selection of choice of action when selected alarm appears
D = Default setting. x = possible selection.
1) Only high power drives
In FC small and medium A69 is only a warning
with SLC events). Events in this context are defined as a 15-21 Historic Log: Value
change in one of the following areas: Array [50]
Range: Function:
1. Digital input
3 3 2. Digital outputs (not monitored in this SW release)
Status word Decimal value. See
16-03 Status Word for
3. Warning word description after
converting to binary
4. Alarm word
value.
5. Status word Control word Decimal value. See
6. Control word 16-00 Control Word for
description.
7. Extended status word
Extended Decimal value. See
Events are logged with value, and time stamp in msec. The status word 16-94 Ext. Status Word for
time interval between two events depends on how often description.
events occur (maximum once every scan time). Data
logging is continuous but if an alarm occurs, the log is
saved and the values can be viewed on the display. This 15-22 Historic Log: Time
feature is useful, for example when carrying out service Array [50]
following a trip. View the historic log contained in this
Range: Function:
parameter via the serial communication port or via the
0 ms* [0 - 2147483647 View the time at which the logged
display.
ms] event occurred. Time is measured in
15-20 Historic Log: Event ms since Adjustable frequency drive
Array [50] start. The max. value corresponds to
approx. 24 days which means that the
Range: Function:
count will restart at zero after this
0* [0 - 255 ] View the event type of the logged events.
time period.
15-42 Voltage
15-53 Power Card Serial Number
Range: Function:
Range: Function:
0* [0 - 0 ] View the FC type. The readout is identical to the FC
0* [0 - 0 ] View the power card serial number.
300 Series power field of the type code definition,
characters 11-12.
15-59 CSIV Filename
15-43 Software Version Range: Function:
Range: Function: Application [0 - 0 ] Shows the currently used CSIV
dependent* (Costumer Specific Initial Values)
0* [0 - 0 ] View the combined SW version (or ‘package
filename.
version’) consisting of power SW and control SW.
3 3 options.
Range: Function:
0* [0 - 8 ] Value indicates source of current faults including
short circuit, overcurrent, and phase imbalance
(from left):
1-4 Inverter
5-8 Rectifier
0 No fault recorded
3 3 0
Range:
[0 -
Function:
View the signal states from the active digital inputs. [0] * Current
= 0; Voltage = 1.
0 0 0 0 0 0 0 0 0 0 0 0 0 00 00
16-66 Digital Output [bin]
130BA894.10
DI T -33
DI T -32
DI T -29 Range: Function:
DI T -27
DI T -19
0* [0 - 15 ] View the binary value of all digital outputs.
DI T -18
DI T -37
DI X30/4 16-67 Pulse Input #29 [Hz]
DI X30/3
DI X30/2 Range: Function:
DI X46/13
DI X46/11 0* [0 - 130000 ] View the actual frequency rate on terminal
DI X46/9
DI X46/7 29.
DI X46/5
DI X46/3
DI X46/1 16-68 Freq. Input #33 [Hz]
Range: Function:
0* [0 - 130000 ] View the actual value of the frequency
16-61 Terminal 53 Switch Setting
applied at terminal 33 as an impulse input.
Option: Function:
View the setting of input terminal 53. Current 16-69 Pulse Output #27 [Hz]
= 0; Voltage = 1.
Range: Function:
[0] * Current 0* [0 - 40000 ] View the actual value of pulses applied to
[1] Voltage terminal 27 in digital output mode.
[2] Pt 1000 [°C]
[3] Pt 1000 [°F] 16-70 Pulse Output #29 [Hz]
[4] Ni 1000 [°C] Range: Function:
[5] Ni 1000 [°F] 0* [0 - 40000 ] View the actual value of pulses at terminal 29
in digital output mode.
16-62 Analog Input 53
This parameter is available for FC 302 only.
Range: Function:
0.000* [-20.000 - 20.000 ] View the actual value at input 53.
Range: Function:
16-84 Comm. Option STW
0.000 * [-20.000 - 20.000 ] View the actual value at input
X30/11 of MCB 101.
Range: Function:
0* [0 - 65535 ] View the extended Serial communication bus
16-76 Analog In X30/12 comm. option status word.
For more information, please refer to the
Range: Function:
relevant Serial communication bus manual.
0.000 * [-20.000 - 20.000 ] View the actual value at input
X30/12 of MCB 101.
0* [-200 - View the two-byte status word (STW) sent to • Bit 3: Valve
200 ] the bus master. Interpretation of the status
• Bit 4: Pressure transmitter
word depends on the serial communication
bus option installed and the control word • Bit 5: Flow transmitter
• Bit 9: Filter
16-90 Alarm Word
• Bit 10: Drive cooling fan
Range: Function:
• Bit 11: Drive system health check
0* [0 - 4294967295 ] View the alarm word sent via the serial
communication port in hex code. • Bit 12: Warranty
Example:
The Preventive Maintenance Word shows
040Ahex.
Position 1 2 3 4
hex value 0 4 0 A
NOTE!
This parameter cannot be adjusted while the motor is
3.18.3 17-5* Resolver Interface
running.
Parameter group 17-5* is used for setting parameters for
the MCB 103 resolver option.
Usually the resolver feedback is used as motor feedback 17-59 Resolver Interface
from permanent magnet motors with 1-01 Motor Control Activate the MCB 103 resolver option when the resolver
Principle set to Flux with motor feedback. parameters are selected.
Resolver parameters cannot be adjusted while the motor is To avoid damage to resolvers, 17-50 Poles – 17-53 Transformation
running. Ratio must be adjusted before activating this parameter. 3 3
17-50 Poles Option: Function:
Range: Function: [0] * Disabled
2* [2 - 2 ] Set the number of poles on the resolver. [1] Enabled
The value is stated in the data sheet for resolvers.
3.18.4 17-6* Monitoring and Application
17-51 Input Voltage
Range: Function: This parameter group is used for selecting additional
7.0 V* [2.0 - 8.0 V] Set the input voltage to the resolver. The functions when the MCB 102 Encoder option or MCB 103
voltage is stated as an RMS value. Resolver option is fitted into option slot B as speed
The value is stated in the data sheet for feedback.
resolvers. Monitoring and application parameters cannot be adjusted
while the motor is running.
17-52 Input Frequency
17-60 Feedback Direction
Range: Function:
Change the detected encoder rotation direction without
10.0 kHz* [2.0 - 15.0 Set the input frequency to the changing the wiring to the encoder.
kHz] resolver.
Option: Function:
The value is stated in the data sheet
for resolvers. [0] * Clockwise
[1] Counter clockwise
17-53 Transformation Ratio
NOTE!
Range: Function: This parameter cannot be adjusted while the motor is
0.5* [0.1 - 1.1 ] Set the transformation ratio for the resolver. running.
The transformation ration is:
V Out
T ratio =
17-61 Feedback Signal Monitoring
V In
Select which reaction the Adjustable frequency drive should take
The value is stated in the data sheet for
if a faulty encoder signal is detected.
resolvers.
The encoder function in 17-61 Feedback Signal Monitoring is an
electrical check of the hardware circuit in the encoder system.
17-56 Encoder Sim. Resolution
Option: Function:
Set the resolution and activate the encoder emulation function
[0] Disabled
(generation of encoder signals from the measured position from
a resolver). Needed when necessary to transfer the speed or [1] * Warning
position information from one drive to another. To disable the [2] Trip
function, select [0]. [3] Jog
[4] Freeze Output
Option: Function:
[5] Max Speed
[0] * Disabled
[6] Switch to Open Loop
[1] 512
[7] Select Setup 1
[2] 1024
[8] Select Setup 2
[3] 2048
[9] Select Setup 3
[4] 4096
[10] Select Setup 4
[11] stop & trip
Time [s]
30-02 Wobble Delta Frequency [%]
Range: Function:
30-00 Wobble Mode 25 %* [0 - 100 %]
Option: Function:
30-03 Wobble Delta Freq. Scaling Resource
The standard speed open-loop mode in
Option: Function:
1-00 Configuration Mode is extended with a
wobble function. In this parameter, it is Select which drive input should be
possible to select which method to be used used to scale the delta frequency
for the wobbler. The parameters can be set setting.
as absolute values (direct frequencies) or as [0] * No function
relative values (percentage of other [1] Analog input 53
parameters). The wobble cycle time can be [2] Analog input 54
set as an absolute value or as independent [3] Frequency input 29 FC 302 only
up and down times. When using an absolute
[4] Frequency input 33
cycle time, the up and down times are
configured through the wobble ratio. [7] Analog input X30/11
[8] Analog input X30/12
[0] * Abs. Freq.,
[15] Analog Input X48/2
Abs. Time
[1] Abs. Freq., 30-04 Wobble Jump Frequency [Hz]
Up/ Down Range: Function:
Time
0.0 [Application The jump frequency is used to
[2] Rel. Freq.,
Hz* dependant] compensate for the inertia in the traverse
Abs. Time
system. If a jump in the output frequency
is required in the top and in the bottom
of the wobble sequence, the frequency
30-04 Wobble Jump Frequency [Hz] 30-12 Wobble Random Ratio Min.
Range: Function: Range: Function:
jump is set in this parameter. If the 0.1* [Application dependant] Enter the minimum allowed
limit warning or trip (warning/alarm 12) 30-19 Wobble Delta Freq. Scaled
or an overvoltage warning or trip Range: Function:
(warning/alarm 7). This parameter can
0.0 Hz* [0.0 - 1000.0 Hz] Readout parameter. View the actual
only be changed in stop mode
wobble delta frequency after scaling
has been applied.
30-05 Wobble Jump Frequency [%]
Range: Function:
0 %* [0 - 100 %] 3.20.2 30-2* Adv. Start Adjust
30-06 Wobble Jump Time 30-20 High Starting Torque Time [s]
Range: Function: Range: Function:
Application [Application This parameter determines 0.00 s* [0.00 - 60.00 s] High starting torque time for PM motor
dependent* dependant] the slope of the jump ramp in flux mode without feedback. This
at the max. and min. parameter is available for FC 302 only.
wobble frequency.
30-21 High Starting Torque Current [%]
30-07 Wobble Sequence Time
Range: Function:
Range: Function:
100.0 %* [Application High starting torque current for
10.0 s* [1.0 - 1000.0 s] This parameter determines the wobble dependant] PM motor in flux mode without
sequence period. This parameter can feedback. This parameter is
only be changed in stop mode. available for FC 302 only.
Wobble time = tup + tdown
30-22 Locked Rotor Protection
30-08 Wobble Up/ Down Time
Locked Rotor Protection for PM motor in flux mode without
Range: Function: feedback. This parameter is available for FC 302 only.
5.0 s* [0.1 - 1000.0 s] Defines the individual up and down Option: Function:
times for each wobble cycle.
[0] * Off
[1] On
30-09 Wobble Random Function
Option: Function: 30-23 Locked Rotor Detection Time [s]
[0] * Off Locked Rotor Detection Time for PM motor in flux mode without
[1] On feedback. This parameter is available for FC 302 only.
Range: Function:
30-10 Wobble Ratio
0.10 s* [0.05 - 1.00 s]
Range: Function:
1.0* [0.1 - 10.0 ] If the ratio 0.1 is selected: tdown is 10 times
greater than tup.
3.20.3 30-8* Compatibility
If the ratio 10 is selected: tup is 10 times
greater than tdown. 30-80 d-axis Inductance (Ld)
Range: Function:
30-11 Wobble Random Ratio Max. Application [Application Enter the value of the d-axis
Range: Function: dependent* dependant] inductance. Obtain the value
10.0* [Application dependant] Enter the maximum allowed from the permanent magnet
wobble ratio. motor data sheet. The d-axis
inductance cannot be found
by performing an AMA.
3.21 Parameters: 35-** Sensor Input Option 35-06 Temperature Sensor Alarm Function
Select the alarm function:
3.21.1 35-0* Temp. Input Mode (MCB 114)
Option: Function:
35-02 Term. X48/7 Temp. Unit 35-15 Term. X48/4 Temp. Monitor
Select the unit to be used with temperature input X48/7 settings This parameter gives the possibility of enabling or disabling the
and readouts: temperature monitor for terminal X48/4. The temperature limits
can be set in 35-16 Term. X48/4 Low Temp. Limit and 35-17 Term.
Option: Function:
X48/4 High Temp. Limit.
[60] * °C
Option: Function:
[160] °F
[0] * Disabled
35-03 Term. X48/7 Input Type [1] Enabled
View the temperature sensor type detected at input X48/7:
35-16 Term. X48/4 Low Temp. Limit
Option: Function:
Range: Function:
[0] * Not Connected
Application dependent* [Application dependant]
[1] PT100 2-wire
[3] PT1000 2-wire 35-17 Term. X48/4 High Temp. Limit
[5] PT100 3-wire Range: Function:
[7] PT1000 3-wire Application dependent* [Application dependant]
35-25 Term. X48/7 Temp. Monitor 3.21.5 35-4* Analog Input X48/2 (MCB 114)
This parameter gives the possibility of enabling or disabling the
temperature monitor for terminal X48/7. The temperature limits 35-42 Term. X48/2 Low Current
can be set in 35-26 Term. X48/7 Low Temp. Limit and 35-27 Term.
X48/7 High Temp. Limit.
Range:
4.00 [Application
Function:
Enter the current (mA) that
3 3
Option: Function: mA* dependant] corresponds to the low reference
[0] * Disabled value, set in 35-44 Term. X48/2 Low
[1] Enabled Ref./Feedb. Value. The value must be
set at > 2mA in order to activate the
35-26 Term. X48/7 Low Temp. Limit Live Zero Timeout Function in
Range: Function: 6-01 Live Zero Timeout Function.
Application dependent* [Application dependant]
35-43 Term. X48/2 High Current
35-27 Term. X48/7 High Temp. Limit
Range: Function:
Range: Function: 20.00 mA* [Application Enter the current (mA) that
Application dependent* [Application dependant] dependant] corresponds to the high
reference value (set in
3.21.4 35-3* Temp. Input X48/10 (MCB 114) 35-45 Term. X48/2 High Ref./Feedb.
Value).
3 3
4 Parameter Lists
4.1.1 Conversion
Examples:
0s --> conversion index 0
0.00s --> conversion index -2
0ms --> conversion index -3
0.00ms --> conversion index -5
+ = active
- = not active
4 4
1-01 Motor Control Principle Flux Flux
Flux open- Flux closed-
U/f mode VVC+ U/f mode open- closed-
loop loop
loop loop
1-00 Configuration Mode
[0] Speed Open-loop + + + -
[1] Speed Closed-loop - + - +
[2] Torque - - - +
[3] Process + + + -
[4] Torque Open-loop - + - -
[5] Wobble + + + +
[6] Surface Winder + + + -
[7] Ext. PID Open-loop + + + -
[8] Ext. PID Closed-loop - + - +
9) Not AC brake
Par. Parameter description Default value 4-set-up FC 302 Change Conver- Type
No. only during sion
# operation index
0-0* Basic Settings
0-01 Language [0] English 1 set-up TRUE - Uint8
0-02 Motor Speed Unit [0] RPM 2 set-ups FALSE - Uint8 4 4
0-03 Regional Settings [0] International 2 set-ups FALSE - Uint8
0-04 Operating State at Power-up (Hand) [1] Forced stop, ref=old All set-ups TRUE - Uint8
0-09 Performance Monitor 0.0 % All set-ups TRUE -1 Uint16
0-1* Set-up Operations
0-10 Active Set-up [1] Set-up 1 1 set-up TRUE - Uint8
0-11 Edit Set-up [1] Set-up 1 All set-ups TRUE - Uint8
0-12 This Set-up Linked to [0] Not linked All set-ups FALSE - Uint8
0-13 Readout: Linked Set-ups 0 N/A All set-ups FALSE 0 Uint16
0-14 Readout: Edit Set-ups / Channel 0 N/A All set-ups TRUE 0 Int32
0-15 Readout: actual setup 0 N/A All set-ups FALSE 0 Uint8
0-2* LCP Display
0-20 Display Line 1.1 Small 1617 All set-ups TRUE - Uint16
0-21 Display Line 1.2 Small 1614 All set-ups TRUE - Uint16
0-22 Display Line 1.3 Small 1610 All set-ups TRUE - Uint16
0-23 Display Line 2 Large 1613 All set-ups TRUE - Uint16
0-24 Display Line 3 Large 1602 All set-ups TRUE - Uint16
0-25 My Personal Menu ExpressionLimit 1 set-up TRUE 0 Uint16
0-3* LCP Cust. Readout
0-30 Unit for User-defined Readout [0] None All set-ups TRUE - Uint8
0-31 Min Value of User-defined Readout 0.00 CustomReadoutUnit All set-ups TRUE -2 Int32
100.00 CustomRea-
0-32 Max Value of User-defined Readout doutUnit All set-ups TRUE -2 Int32
0-37 Display Text 1 0 N/A 1 set-up TRUE 0 VisStr[25]
0-38 Display Text 2 0 N/A 1 set-up TRUE 0 VisStr[25]
0-39 Display Text 3 0 N/A 1 set-up TRUE 0 VisStr[25]
0-4* LCP Keypad
0-40 [Hand on] Key on LCP null All set-ups TRUE - Uint8
0-41 [Off] Key on LCP null All set-ups TRUE - Uint8
0-42 [Auto on] Key on LCP null All set-ups TRUE - Uint8
0-43 [Reset] Key on LCP null All set-ups TRUE - Uint8
0-44 [Off/Reset] Key on LCP null All set-ups TRUE - Uint8
0-45 [Drive Bypass] Key on LCP null All set-ups TRUE - Uint8
0-5* Copy/Save
0-50 LCP Copy [0] No copy All set-ups FALSE - Uint8
0-51 Set-up Copy [0] No copy All set-ups FALSE - Uint8
0-6* Password
0-60 Main Menu Password 100 N/A 1 set-up TRUE 0 Int16
0-61 Access to Main Menu w/o Password [0] Full access 1 set-up TRUE - Uint8
0-65 Quick Menu Password 200 N/A 1 set-up TRUE 0 Int16
0-66 Access to Quick Menu w/o Password [0] Full access 1 set-up TRUE - Uint8
0-67 Bus Password Access 0 N/A All set-ups TRUE 0 Uint16
Par. Parameter description Default value 4-set-up FC 302 Change Conver- Type
No. only during sion
# operation index
1-0* General Settings
1-00 Configuration Mode null All set-ups TRUE - Uint8
4 4 1-01 Motor Control Principle null All set-ups FALSE - Uint8
1-02 Flux Motor Feedback Source [1] 24V encoder All set-ups x FALSE - Uint8
1-03 Torque Characteristics [0] Constant torque All set-ups TRUE - Uint8
1-04 Overload Mode [0] High torque All set-ups FALSE - Uint8
1-05 Local Mode Configuration [2] As mode par 1-00 All set-ups TRUE - Uint8
1-06 Clockwise Direction [0] Normal All set-ups FALSE - Uint8
1-1* Motor Selection
1-10 Motor Construction [0] Asynchron All set-ups FALSE - Uint8
1-2* Motor Data
1-20 Motor Power [kW] ExpressionLimit All set-ups FALSE 1 Uint32
1-21 Motor Power [HP] ExpressionLimit All set-ups FALSE -2 Uint32
1-22 Motor Voltage ExpressionLimit All set-ups FALSE 0 Uint16
1-23 Motor Frequency ExpressionLimit All set-ups FALSE 0 Uint16
1-24 Motor Current ExpressionLimit All set-ups FALSE -2 Uint32
1-25 Motor Nominal Speed ExpressionLimit All set-ups FALSE 67 Uint16
1-26 Motor Cont. Rated Torque ExpressionLimit All set-ups FALSE -1 Uint32
1-29 Automatic Motor Adaptation (AMA) [0] Off All set-ups FALSE - Uint8
1-3* Addl. Motor Data
1-30 Stator Resistance (Rs) ExpressionLimit All set-ups FALSE -4 Uint32
1-31 Rotor Resistance (Rr) ExpressionLimit All set-ups FALSE -4 Uint32
1-33 Stator Leakage Reactance (X1) ExpressionLimit All set-ups FALSE -4 Uint32
1-34 Rotor Leakage Reactance (X2) ExpressionLimit All set-ups FALSE -4 Uint32
1-35 Main Reactance (Xh) ExpressionLimit All set-ups FALSE -4 Uint32
1-36 Iron Loss Resistance (Rfe) ExpressionLimit All set-ups FALSE -3 Uint32
1-37 d-axis Inductance (Ld) ExpressionLimit All set-ups x FALSE -4 Int32
1-39 Motor Poles ExpressionLimit All set-ups FALSE 0 Uint8
1-40 Back EMF at 1000 RPM ExpressionLimit All set-ups x FALSE 0 Uint16
1-41 Motor Angle Offset 0 N/A All set-ups FALSE 0 Int16
1-5* Load-Indep. Setting
1-50 Motor Magnetization at Zero Speed 100 % All set-ups TRUE 0 Uint16
1-51 Min Speed Normal Magnetizing [RPM] ExpressionLimit All set-ups TRUE 67 Uint16
1-52 Min Speed Normal Magnetizing [Hz] ExpressionLimit All set-ups TRUE -1 Uint16
1-53 Model Shift Frequency ExpressionLimit All set-ups x FALSE -1 Uint16
1-54 Voltage reduction in fieldweakening 0V All set-ups FALSE 0 Uint8
1-55 U/f Characteristic - U ExpressionLimit All set-ups TRUE -1 Uint16
1-56 U/f Characteristic - F ExpressionLimit All set-ups TRUE -1 Uint16
1-58 Flystart Test Pulses Current 30 % All set-ups FALSE 0 Uint16
1-59 Flystart Test Pulses Frequency 200 % All set-ups FALSE 0 Uint16
1-6* Load-Depend. Settg.
1-60 Low Speed Load Compensation 100 % All set-ups TRUE 0 Int16
1-61 High Speed Load Compensation 100 % All set-ups TRUE 0 Int16
1-62 Slip Compensation ExpressionLimit All set-ups TRUE 0 Int16
1-63 Slip Compensation Time Constant ExpressionLimit All set-ups TRUE -2 Uint16
1-64 Resonance Dampening 100 % All set-ups TRUE 0 Uint16
Par. Parameter description Default value 4-set-up FC 302 Change Conver- Type
No. only during sion
# operation index
1-65 Resonance Dampening Time Constant 5 ms All set-ups TRUE -3 Uint8
1-66 Min. Current at Low Speed 100 % All set-ups x TRUE 0 Uint32
1-67 Load Type [0] Passive load All set-ups x TRUE - Uint8
1-68 Minimum Inertia ExpressionLimit All set-ups x FALSE -4 Uint32
1-69 Maximum Inertia ExpressionLimit All set-ups x FALSE -4 Uint32 4 4
1-7* Start Adjustments
1-71 Start Delay 0.0 s All set-ups TRUE -1 Uint8
1-72 Start Function [2] Coast/delay time All set-ups TRUE - Uint8
1-73 Flying Start null All set-ups FALSE - Uint8
1-74 Start Speed [RPM] ExpressionLimit All set-ups TRUE 67 Uint16
1-75 Start Speed [Hz] ExpressionLimit All set-ups TRUE -1 Uint16
1-76 Start Current 0.00 A All set-ups TRUE -2 Uint32
1-8* Stop Adjustments
1-80 Function at Stop [0] Coast All set-ups TRUE - Uint8
1-81 Min Speed for Function at Stop [RPM] ExpressionLimit All set-ups TRUE 67 Uint16
1-82 Min Speed for Function at Stop [Hz] ExpressionLimit All set-ups TRUE -1 Uint16
1-83 Precise Stop Function [0] Precise ramp stop All set-ups FALSE - Uint8
1-84 Precise Stop Counter Value 100000 N/A All set-ups TRUE 0 Uint32
1-85 Precise Stop Speed Compensation Delay 10 ms All set-ups TRUE -3 Uint8
1-9* Motor Temperature
1-90 Motor Thermal Protection [0] No protection All set-ups TRUE - Uint8
1-91 Motor External Fan [0] No All set-ups TRUE - Uint16
1-93 Thermistor Resource [0] None All set-ups TRUE - Uint8
1-94 ATEX ETR cur.lim. speed reduction 0.0 % 2 set-ups x TRUE -1 Uint16
1-95 KTY Sensor Type [0] KTY Sensor 1 All set-ups x TRUE - Uint8
1-96 KTY Thermistor Resource [0] None All set-ups x TRUE - Uint8
1-97 KTY Threshold level 80 °C 1 set-up x TRUE 100 Int16
1-98 ATEX ETR interpol. points freq. ExpressionLimit 1 set-up x TRUE -1 Uint16
1-99 ATEX ETR interpol points current ExpressionLimit 2 set-ups x TRUE 0 Uint16
Par. Parameter description Default value 4-set-up FC 302 Change Conver- Type
No. only during sion
# operation index
2-0* DC Brake
2-00 DC Hold Current 50 % All set-ups TRUE 0 Uint8
4 4 2-01 DC Brake Current 50 % All set-ups TRUE 0 Uint16
2-02 DC Braking Time 10.0 s All set-ups TRUE -1 Uint16
2-03 DC Brake Cut-in Speed [RPM] ExpressionLimit All set-ups TRUE 67 Uint16
2-04 DC Brake Cut-in Speed [Hz] ExpressionLimit All set-ups TRUE -1 Uint16
2-05 Maximum Reference MaxReference (P303) All set-ups TRUE -3 Int32
2-1* Brake Energy Funct.
2-10 Brake Function null All set-ups TRUE - Uint8
2-11 Brake Resistor (ohm) ExpressionLimit All set-ups TRUE 0 Uint16
2-12 Brake Power Limit (kW) ExpressionLimit All set-ups TRUE 0 Uint32
2-13 Brake Power Monitoring [0] Off All set-ups TRUE - Uint8
2-15 Brake Check [0] Off All set-ups TRUE - Uint8
2-16 AC brake Max. Current 100.0 % All set-ups TRUE -1 Uint32
2-17 Over-voltage Control [0] Disabled All set-ups TRUE - Uint8
2-18 Brake Check Condition [0] At Power-up All set-ups TRUE - Uint8
2-19 Over-voltage Gain 100 % All set-ups TRUE 0 Uint16
2-2* Mechanical Brake
2-20 Release Brake Current ImaxVLT (P1637) All set-ups TRUE -2 Uint32
2-21 Activate Brake Speed [RPM] ExpressionLimit All set-ups TRUE 67 Uint16
2-22 Activate Brake Speed [Hz] ExpressionLimit All set-ups TRUE -1 Uint16
2-23 Activate Brake Delay 0.0 s All set-ups TRUE -1 Uint8
2-24 Stop Delay 0.0 s All set-ups TRUE -1 Uint8
2-25 Brake Release Time 0.20 s All set-ups TRUE -2 Uint16
2-26 Torque Ref 0.00 % All set-ups TRUE -2 Int16
2-27 Torque Ramp Time 0.2 s All set-ups TRUE -1 Uint8
2-28 Gain Boost Factor 1.00 N/A All set-ups TRUE -2 Uint16
Par. Parameter description Default value 4-set-up FC 302 Change Conver- Type
No. only during sion
# operation index
3-0* Reference Limits
3-00 Reference Range null All set-ups TRUE - Uint8
3-01 Reference/Feedback Unit null All set-ups TRUE - Uint8 4 4
3-02 Minimum Reference ExpressionLimit All set-ups TRUE -3 Int32
3-03 Maximum Reference ExpressionLimit All set-ups TRUE -3 Int32
3-04 Reference Function [0] Sum All set-ups TRUE - Uint8
3-1* References
3-10 Preset Reference 0.00 % All set-ups TRUE -2 Int16
3-11 Jog Speed [Hz] ExpressionLimit All set-ups TRUE -1 Uint16
3-12 Catch up/slow-down Value 0.00 % All set-ups TRUE -2 Int16
3-13 Reference Site [0] Linked to Hand / Auto All set-ups TRUE - Uint8
3-14 Preset Relative Reference 0.00 % All set-ups TRUE -2 Int32
3-15 Reference Resource 1 null All set-ups TRUE - Uint8
3-16 Reference Resource 2 null All set-ups TRUE - Uint8
3-17 Reference Resource 3 null All set-ups TRUE - Uint8
3-18 Relative Scaling Reference Resource [0] No function All set-ups TRUE - Uint8
3-19 Jog Speed [RPM] ExpressionLimit All set-ups TRUE 67 Uint16
3-4* Ramp 1
3-40 Ramp 1 Type [0] Linear All set-ups TRUE - Uint8
3-41 Ramp 1 Ramp-up Time ExpressionLimit All set-ups TRUE -2 Uint32
3-42 Ramp 1 Ramp-down Time ExpressionLimit All set-ups TRUE -2 Uint32
3-45 Ramp 1 S-ramp Ratio at Accel. Start 50 % All set-ups TRUE 0 Uint8
3-46 Ramp 1 S-ramp Ratio at Accel. End 50 % All set-ups TRUE 0 Uint8
3-47 Ramp 1 S-ramp Ratio at Decel. Start 50 % All set-ups TRUE 0 Uint8
3-48 Ramp 1 S-ramp Ratio at Decel. End 50 % All set-ups TRUE 0 Uint8
3-5* Ramp 2
3-50 Ramp 2 Type [0] Linear All set-ups TRUE - Uint8
3-51 Ramp 2 Ramp-up Time ExpressionLimit All set-ups TRUE -2 Uint32
3-52 Ramp 2 Ramp-down Time ExpressionLimit All set-ups TRUE -2 Uint32
3-55 Ramp 2 S-ramp Ratio at Accel. Start 50 % All set-ups TRUE 0 Uint8
3-56 Ramp 2 S-ramp Ratio at Accel. End 50 % All set-ups TRUE 0 Uint8
3-57 Ramp 2 S-ramp Ratio at Decel. Start 50 % All set-ups TRUE 0 Uint8
3-58 Ramp 2 S-ramp Ratio at Decel. End 50 % All set-ups TRUE 0 Uint8
3-6* Ramp 3
3-60 Ramp 3 Type [0] Linear All set-ups TRUE - Uint8
3-61 Ramp 3 Ramp-up Time ExpressionLimit All set-ups TRUE -2 Uint32
3-62 Ramp 3 Ramp-down Time ExpressionLimit All set-ups TRUE -2 Uint32
3-65 Ramp 3 S-ramp Ratio at Accel. Start 50 % All set-ups TRUE 0 Uint8
3-66 Ramp 3 S-ramp Ratio at Accel. End 50 % All set-ups TRUE 0 Uint8
3-67 Ramp 3 S-ramp Ratio at Decel. Start 50 % All set-ups TRUE 0 Uint8
3-68 Ramp 3 S-ramp Ratio at Decel. End 50 % All set-ups TRUE 0 Uint8
3-7* Ramp 4
3-70 Ramp 4 Type [0] Linear All set-ups TRUE - Uint8
3-71 Ramp 4 Ramp-up Time ExpressionLimit All set-ups TRUE -2 Uint32
3-72 Ramp 4 Ramp-down Time ExpressionLimit All set-ups TRUE -2 Uint32
3-75 Ramp 4 S-ramp Ratio at Accel. Start 50 % All set-ups TRUE 0 Uint8
Par. Parameter description Default value 4-set-up FC 302 Change Conver- Type
No. only during sion
# operation index
3-76 Ramp 4 S-ramp Ratio at Accel. End 50 % All set-ups TRUE 0 Uint8
3-77 Ramp 4 S-ramp Ratio at Decel. Start 50 % All set-ups TRUE 0 Uint8
3-78 Ramp 4 S-ramp Ratio at Decel. End 50 % All set-ups TRUE 0 Uint8
3-8* Other Ramps
4 4 3-80 Jog Ramp Time ExpressionLimit All set-ups TRUE -2 Uint32
3-81 Quick Stop Ramp Time ExpressionLimit 2 set-ups TRUE -2 Uint32
3-82 Quick Stop Ramp Type [0] Linear All set-ups TRUE - Uint8
3-83 Quick Stop S-ramp Ratio at Decel. Start 50 % All set-ups TRUE 0 Uint8
3-84 Quick Stop S-ramp Ratio at Decel. End 50 % All set-ups TRUE 0 Uint8
3-9* Digital Pot. meter
3-90 Step Size 0.10 % All set-ups TRUE -2 Uint16
3-91 Ramp Time 1.00 s All set-ups TRUE -2 Uint32
3-92 Power Restore [0] Off All set-ups TRUE - Uint8
3-93 Maximum Limit 100 % All set-ups TRUE 0 Int16
3-94 Minimum Limit -100 % All set-ups TRUE 0 Int16
3-95 Ramp Delay ExpressionLimit All set-ups TRUE -3 TimD
Par. Parameter description Default value 4-set-up FC 302 Change Conver- Type
No. only during sion
# operation index
4-1* Motor Limits
4-10 Motor Speed Direction null All set-ups FALSE - Uint8
4-11 Motor Speed Low Limit [RPM] ExpressionLimit All set-ups TRUE 67 Uint16 4 4
4-12 Motor Speed Low Limit [Hz] ExpressionLimit All set-ups TRUE -1 Uint16
4-13 Motor Speed High Limit [RPM] ExpressionLimit All set-ups TRUE 67 Uint16
4-14 Motor Speed High Limit [Hz] ExpressionLimit All set-ups TRUE -1 Uint16
4-16 Torque Limit Motor Mode ExpressionLimit All set-ups TRUE -1 Uint16
4-17 Torque Limit Generator Mode 100.0 % All set-ups TRUE -1 Uint16
4-18 Current Limit ExpressionLimit All set-ups TRUE -1 Uint32
4-19 Max Output Frequency 132.0 Hz All set-ups FALSE -1 Uint16
4-2* Limit Factors
4-20 Torque Limit Factor Source [0] No function All set-ups TRUE - Uint8
4-21 Speed Limit Factor Source [0] No function All set-ups TRUE - Uint8
4-3* Motor Speed Mon.
4-30 Motor Feedback Loss Function [2] Trip All set-ups TRUE - Uint8
4-31 Motor Feedback Speed Error 300 RPM All set-ups TRUE 67 Uint16
4-32 Motor Feedback Loss Timeout 0.05 s All set-ups TRUE -2 Uint16
4-34 Tracking Error Function null All set-ups TRUE - Uint8
4-35 Tracking Error 10 RPM All set-ups TRUE 67 Uint16
4-36 Tracking Error Timeout 1.00 s All set-ups TRUE -2 Uint16
4-37 Tracking Error Ramping 100 RPM All set-ups TRUE 67 Uint16
4-38 Tracking Error Ramping Timeout 1.00 s All set-ups TRUE -2 Uint16
4-39 Tracking Error After Ramping Timeout 5.00 s All set-ups TRUE -2 Uint16
4-5* Adj. Warnings
4-50 Warning Current Low 0.00 A All set-ups TRUE -2 Uint32
4-51 Warning Current High ImaxVLT (P1637) All set-ups TRUE -2 Uint32
4-52 Warning Speed Low 0 RPM All set-ups TRUE 67 Uint16
outputSpeedHighLimit
4-53 Warning Speed High (P413) All set-ups TRUE 67 Uint16
4-54 Warning Reference Low -999999.999 N/A All set-ups TRUE -3 Int32
4-55 Warning Reference High 999999.999 N/A All set-ups TRUE -3 Int32
-999999.999 Reference-
4-56 Warning Feedback Low FeedbackUnit All set-ups TRUE -3 Int32
999999.999 Reference-
4-57 Warning Feedback High FeedbackUnit All set-ups TRUE -3 Int32
4-58 Missing Motor Phase Function null All set-ups TRUE - Uint8
4-6* Speed Bypass
4-60 Bypass Speed From [RPM] ExpressionLimit All set-ups TRUE 67 Uint16
4-61 Bypass Speed From [Hz] ExpressionLimit All set-ups TRUE -1 Uint16
4-62 Bypass Speed to [RPM] ExpressionLimit All set-ups TRUE 67 Uint16
4-63 Bypass Speed To [Hz] ExpressionLimit All set-ups TRUE -1 Uint16
Par. Parameter description Default value 4-set-up FC 302 Change Conver- Type
No. only during sion
# operation index
5-0* Digital I/O mode
5-00 Digital I/O Mode [0] PNP All set-ups FALSE - Uint8
4 4 5-01 Terminal 27 Mode [0] Input All set-ups TRUE - Uint8
5-02 Terminal 29 Mode [0] Input All set-ups x TRUE - Uint8
5-1* Digital Inputs
5-10 Terminal 18 Digital Input null All set-ups TRUE - Uint8
5-11 Terminal 19 Digital Input null All set-ups TRUE - Uint8
5-12 Terminal 27 Digital Input null All set-ups TRUE - Uint8
5-13 Terminal 29 Digital Input null All set-ups x TRUE - Uint8
5-14 Terminal 32 Digital Input null All set-ups TRUE - Uint8
5-15 Terminal 33 Digital Input null All set-ups TRUE - Uint8
5-16 Terminal X30/2 Digital Input null All set-ups TRUE - Uint8
5-17 Terminal X30/3 Digital Input null All set-ups TRUE - Uint8
5-18 Terminal X30/4 Digital Input null All set-ups TRUE - Uint8
5-19 Terminal 37 Safe Stop null 1 set-up TRUE - Uint8
5-20 Terminal X46/1 Digital Input [0] No operation All set-ups TRUE - Uint8
5-21 Terminal X46/3 Digital Input [0] No operation All set-ups TRUE - Uint8
5-22 Terminal X46/5 Digital Input [0] No operation All set-ups TRUE - Uint8
5-23 Terminal X46/7 Digital Input [0] No operation All set-ups TRUE - Uint8
5-24 Terminal X46/9 Digital Input [0] No operation All set-ups TRUE - Uint8
5-25 Terminal X46/11 Digital Input [0] No operation All set-ups TRUE - Uint8
5-26 Terminal X46/13 Digital Input [0] No operation All set-ups TRUE - Uint8
5-3* Digital Outputs
5-30 Terminal 27 Digital Output null All set-ups TRUE - Uint8
5-31 Terminal 29 digital Output null All set-ups x TRUE - Uint8
5-32 Term X30/6 Digi Out (MCB 101) null All set-ups TRUE - Uint8
5-33 Term X30/7 Digi Out (MCB 101) null All set-ups TRUE - Uint8
5-4* Relays
5-40 Function Relay null All set-ups TRUE - Uint8
5-41 On Delay, Relay 0.01 s All set-ups TRUE -2 Uint16
5-42 Off Delay, Relay 0.01 s All set-ups TRUE -2 Uint16
5-5* Pulse Input
5-50 Term. 29 Low Frequency 100 Hz All set-ups x TRUE 0 Uint32
5-51 Term. 29 High Frequency 100 Hz All set-ups x TRUE 0 Uint32
0.000 ReferenceFeed-
5-52 Term. 29 Low Ref./Feedb. Value backUnit All set-ups x TRUE -3 Int32
5-53 Term. 29 High Ref./Feedb. Value ExpressionLimit All set-ups x TRUE -3 Int32
5-54 Pulse Filter Time Constant #29 100 ms All set-ups x FALSE -3 Uint16
5-55 Term. 33 Low Frequency 100 Hz All set-ups TRUE 0 Uint32
5-56 Term. 33 High Frequency 100 Hz All set-ups TRUE 0 Uint32
0.000 ReferenceFeed-
5-57 Term. 33 Low Ref./Feedb. Value backUnit All set-ups TRUE -3 Int32
5-58 Term. 33 High Ref./Feedb. Value ExpressionLimit All set-ups TRUE -3 Int32
5-59 Pulse Filter Time Constant #33 100 ms All set-ups FALSE -3 Uint16
5-6* Pulse Output
5-60 Terminal 27 Pulse Output Variable null All set-ups TRUE - Uint8
Par. Parameter description Default value 4-set-up FC 302 Change Conver- Type
No. only during sion
# operation index
5-62 Pulse Output Max Freq #27 ExpressionLimit All set-ups TRUE 0 Uint32
5-63 Terminal 29 Pulse Output Variable null All set-ups x TRUE - Uint8
5-65 Pulse Output Max Freq #29 ExpressionLimit All set-ups x TRUE 0 Uint32
5-66 Terminal X30/6 Pulse Output Variable null All set-ups TRUE - Uint8
5-68 Pulse Output Max Freq #X30/6 ExpressionLimit All set-ups TRUE 0 Uint32 4 4
5-7* 24V Encoder Input
5-70 Term 32/33 Pulses per Revolution 1024 N/A All set-ups FALSE 0 Uint16
5-71 Term 32/33 Encoder Direction [0] Clockwise All set-ups FALSE - Uint8
5-8* I/O Options
5-80 AHF Cap Reconnect Delay 25 s 2 set-ups x TRUE 0 Uint16
5-9* Bus Controlled
5-90 Digital & Relay Bus Control 0 N/A All set-ups TRUE 0 Uint32
5-93 Pulse Out #27 Bus Control 0.00 % All set-ups TRUE -2 N2
5-94 Pulse Out #27 Timeout Preset 0.00 % 1 set-up TRUE -2 Uint16
5-95 Pulse Out #29 Bus Control 0.00 % All set-ups x TRUE -2 N2
5-96 Pulse Out #29 Timeout Preset 0.00 % 1 set-up x TRUE -2 Uint16
5-97 Pulse Out #X30/6 Bus Control 0.00 % All set-ups TRUE -2 N2
5-98 Pulse Out #X30/6 Timeout Preset 0.00 % 1 set-up TRUE -2 Uint16
Par. Parameter description Default value 4-set-up FC 302 Change Conver- Type
No. only during sion
# operation index
6-0* Analog I/O Mode
6-00 Live Zero Timeout Time 10 s All set-ups TRUE 0 Uint8
4 4 6-01 Live Zero Timeout Function [0] Off All set-ups TRUE - Uint8
6-1* Analog Input 1
6-10 Terminal 53 Low Voltage 0.07 V All set-ups TRUE -2 Int16
6-11 Terminal 53 High Voltage 10.00 V All set-ups TRUE -2 Int16
6-12 Terminal 53 Low Current 0.14 mA All set-ups TRUE -5 Int16
6-13 Terminal 53 High Current 20.00 mA All set-ups TRUE -5 Int16
6-14 Terminal 53 Low Ref./Feedb. Value 0 ReferenceFeedbackUnit All set-ups TRUE -3 Int32
6-15 Terminal 53 High Ref./Feedb. Value ExpressionLimit All set-ups TRUE -3 Int32
6-16 Terminal 53 Filter Time Constant 0.001 s All set-ups TRUE -3 Uint16
6-2* Analog Input 2
6-20 Terminal 54 Low Voltage 0.07 V All set-ups TRUE -2 Int16
6-21 Terminal 54 High Voltage 10.00 V All set-ups TRUE -2 Int16
6-22 Terminal 54 Low Current 0.14 mA All set-ups TRUE -5 Int16
6-23 Terminal 54 High Current 20.00 mA All set-ups TRUE -5 Int16
6-24 Terminal 54 Low Ref./Feedb. Value 0 ReferenceFeedbackUnit All set-ups TRUE -3 Int32
6-25 Terminal 54 High Ref./Feedb. Value ExpressionLimit All set-ups TRUE -3 Int32
6-26 Terminal 54 Filter Time Constant 0.001 s All set-ups TRUE -3 Uint16
6-3* Analog Input 53
6-30 Terminal X30/11 Low Voltage 0.07 V All set-ups TRUE -2 Int16
6-31 Terminal X30/11 High Voltage 10.00 V All set-ups TRUE -2 Int16
6-34 Term. X30/11 Low Ref./Feedb. Value 0 ReferenceFeedbackUnit All set-ups TRUE -3 Int32
6-35 Term. X30/11 High Ref./Feedb. Value ExpressionLimit All set-ups TRUE -3 Int32
6-36 Term. X30/11 Filter Time Constant 0.001 s All set-ups TRUE -3 Uint16
6-4* Analog Input 4
6-40 Terminal X30/12 Low Voltage 0.07 V All set-ups TRUE -2 Int16
6-41 Terminal X30/12 High Voltage 10.00 V All set-ups TRUE -2 Int16
6-44 Term. X30/12 Low Ref./Feedb. Value 0 ReferenceFeedbackUnit All set-ups TRUE -3 Int32
6-45 Term. X30/12 High Ref./Feedb. Value ExpressionLimit All set-ups TRUE -3 Int32
6-46 Term. X30/12 Filter Time Constant 0.001 s All set-ups TRUE -3 Uint16
6-5* Analog Output 1
6-50 Terminal 42 Output null All set-ups TRUE - Uint8
6-51 Terminal 42 Output Min Scale 0.00 % All set-ups TRUE -2 Int16
6-52 Terminal 42 Output Max Scale 100.00 % All set-ups TRUE -2 Int16
6-53 Terminal 42 Output Bus Control 0.00 % All set-ups TRUE -2 N2
6-54 Terminal 42 Output Timeout Preset 0.00 % 1 set-up TRUE -2 Uint16
6-55 Terminal 42 Output Filter [0] Off 1 set-up TRUE - Uint8
6-6* Analog Output 2
6-60 Terminal X30/8 Output null All set-ups TRUE - Uint8
6-61 Terminal X30/8 Min. Scale 0.00 % All set-ups TRUE -2 Int16
6-62 Terminal X30/8 Max. Scale 100.00 % All set-ups TRUE -2 Int16
6-63 Terminal X30/8 Bus Control 0.00 % All set-ups TRUE -2 N2
6-64 Terminal X30/8 Output Timeout Preset 0.00 % 1 set-up TRUE -2 Uint16
6-7* Analog Output 3
6-70 Terminal X45/1 Output null All set-ups TRUE - Uint8
Par. Parameter description Default value 4-set-up FC 302 Change Conver- Type
No. only during sion
# operation index
6-71 Terminal X45/1 Min. Scale 0.00 % All set-ups TRUE -2 Int16
6-72 Terminal X45/1 Max. Scale 100.00 % All set-ups TRUE -2 Int16
4 4
6-74 Terminal X45/1 Output Timeout Preset 0.00 % 1 set-up TRUE -2 Uint16
6-8* Analog Output 4
6-80 Terminal X45/3 Output null All set-ups TRUE - Uint8
6-81 Terminal X45/3 Min. Scale 0.00 % All set-ups TRUE -2 Int16
6-82 Terminal X45/3 Max. Scale 100.00 % All set-ups TRUE -2 Int16
6-83 Terminal X45/3 Bus Control 0.00 % All set-ups TRUE -2 N2
6-84 Terminal X45/3 Output Timeout Preset 0.00 % 1 set-up TRUE -2 Uint16
Par. Parameter description Default value 4-set-up FC 302 Change Conver- Type
No. only during sion
# operation index
7-0* Speed PID Ctrl.
7-00 Speed PID Feedback Source null All set-ups FALSE - Uint8
4 4 7-02 Speed PID Proportional Gain ExpressionLimit All set-ups TRUE -3 Uint16
7-03 Speed PID Integral Time ExpressionLimit All set-ups TRUE -4 Uint32
7-04 Speed PID Differentiation Time ExpressionLimit All set-ups TRUE -4 Uint16
7-05 Speed PID Diff. Gain Limit 5.0 N/A All set-ups TRUE -1 Uint16
7-06 Speed PID Lowpass Filter Time ExpressionLimit All set-ups TRUE -4 Uint16
7-07 Speed PID Feedback Gear Ratio 1.0000 N/A All set-ups FALSE -4 Uint32
7-08 Speed PID Feed Forward Factor 0% All set-ups FALSE 0 Uint16
7-09 Speed PID Error Correction w/ Ramp 300 RPM All set-ups TRUE 67 Uint32
7-1* Torque PI Ctrl.
7-12 Torque PI Proportional Gain 100 % All set-ups TRUE 0 Uint16
7-13 Torque PI Integration Time 0.020 s All set-ups TRUE -3 Uint16
7-2* Process Ctrl. Feedb
7-20 Process CL Feedback 1 Resource [0] No function All set-ups TRUE - Uint8
7-22 Process CL Feedback 2 Resource [0] No function All set-ups TRUE - Uint8
7-3* Process PID Ctrl.
7-30 Process PID Normal/Inverse Control [0] Normal All set-ups TRUE - Uint8
7-31 Process PID Anti Windup [1] On All set-ups TRUE - Uint8
7-32 Process PID Controller Start Value 0 RPM All set-ups TRUE 67 Uint16
7-33 Process PID Proportional Gain 0.01 N/A All set-ups TRUE -2 Uint16
7-34 Process PID Integral Time 10000.00 s All set-ups TRUE -2 Uint32
7-35 Process PID Differentiation Time 0.00 s All set-ups TRUE -2 Uint16
7-36 Process PID Differentiation Gain Limit 5.0 N/A All set-ups TRUE -1 Uint16
7-38 Process PID Feed Forward Factor 0% All set-ups TRUE 0 Uint16
7-39 On Reference Bandwidth 5% All set-ups TRUE 0 Uint8
7-4* Adv. Process PID I
7-40 Process PID I-part Reset [0] No All set-ups TRUE - Uint8
7-41 Process PID Output Neg. Clamp -100 % All set-ups TRUE 0 Int16
7-42 Process PID Output Pos. Clamp 100 % All set-ups TRUE 0 Int16
7-43 Process PID Gain Scale at Min. Ref. 100 % All set-ups TRUE 0 Int16
7-44 Process PID Gain Scale at Max. Ref. 100 % All set-ups TRUE 0 Int16
7-45 Process PID Feed Fwd Resource [0] No function All set-ups TRUE - Uint8
7-46 Process PID Feed Fwd Normal/ Inv. Ctrl. [0] Normal All set-ups TRUE - Uint8
7-48 PCD Feed Forward 0 N/A All set-ups x TRUE 0 Uint16
7-49 Process PID Output Normal/ Inv. Ctrl. [0] Normal All set-ups TRUE - Uint8
7-5* Adv. Process PID II
7-50 Process PID Extended PID [1] Enabled All set-ups TRUE - Uint8
7-51 Process PID Feed Fwd Gain 1.00 N/A All set-ups TRUE -2 Uint16
7-52 Process PID Feed Fwd Ramp-up 0.01 s All set-ups TRUE -2 Uint32
7-53 Process PID Feed Fwd Ramp-down 0.01 s All set-ups TRUE -2 Uint32
7-56 Process PID Ref. Filter Time 0.001 s All set-ups TRUE -3 Uint16
7-57 Process PID Fb. Filter Time 0.001 s All set-ups TRUE -3 Uint16
Par. Parameter description Default value 4-set-up FC 302 Change Conver- Type
No. only during sion
# operation index
8-0* General Settings
8-01 Control Site [0] Digital and ctrl. word All set-ups TRUE - Uint8
8-02 Control Word Source null All set-ups TRUE - Uint8 4 4
8-03 Control Word Timeout Time 1.0 s 1 set-up TRUE -1 Uint32
8-04 Control Word Timeout Function null 1 set-up TRUE - Uint8
8-05 End-of-Timeout Function [1] Resume set-up 1 set-up TRUE - Uint8
8-06 Reset Control Word Timeout [0] Do not reset All set-ups TRUE - Uint8
8-07 Diagnosis Trigger [0] Disable 2 set-ups TRUE - Uint8
8-08 Readout Filtering null All set-ups TRUE - Uint8
8-1* Ctrl. Word Settings
8-10 Control Word Profile [0] FC profile All set-ups TRUE - Uint8
8-13 Configurable Status Word STW null All set-ups TRUE - Uint8
8-14 Configurable Control Word CTW [1] Profile default All set-ups TRUE - Uint8
8-3* FC Port Settings
8-30 Protocol [0] FC 1 set-up TRUE - Uint8
8-31 Address 1 N/A 1 set-up TRUE 0 Uint8
8-32 FC Port Baud Rate null 1 set-up TRUE - Uint8
8-33 Parity / Stop Bits [0] Ev. Par. 1 Stop Bit 1 set-up TRUE - Uint8
8-34 Estimated cycle time 0 ms 2 set-ups TRUE -3 Uint32
8-35 Minimum Response Delay 10 ms All set-ups TRUE -3 Uint16
8-36 Max Response Delay ExpressionLimit 1 set-up TRUE -3 Uint16
8-37 Max Inter-Char Delay ExpressionLimit 1 set-up TRUE -5 Uint16
8-4* FC MC protocol set
8-40 Telegram selection [1] Standard telegram 1 2 set-ups TRUE - Uint8
8-41 Parameters for signals 0 All set-ups FALSE - Uint16
8-42 PCD write configuration ExpressionLimit All set-ups TRUE 0 Uint16
8-43 PCD read configuration ExpressionLimit All set-ups TRUE 0 Uint16
8-5* Digital/Bus
8-50 Coasting Select [3] Logic OR All set-ups TRUE - Uint8
8-51 Quick Stop Select [3] Logic OR All set-ups TRUE - Uint8
8-52 DC Brake Select [3] Logic OR All set-ups TRUE - Uint8
8-53 Start Select [3] Logic OR All set-ups TRUE - Uint8
8-54 Reverse Select [3] Logic OR All set-ups TRUE - Uint8
8-55 Set-up Select [3] Logic OR All set-ups TRUE - Uint8
8-56 Preset Reference Select [3] Logic OR All set-ups TRUE - Uint8
8-57 Profidrive OFF2 Select [3] Logic OR All set-ups TRUE - Uint8
8-58 Profidrive OFF3 Select [3] Logic OR All set-ups TRUE - Uint8
8-8* AFD Port Diagnostics
8-80 Bus Message Count 0 N/A All set-ups TRUE 0 Uint32
8-81 Bus Error Count 0 N/A All set-ups TRUE 0 Uint32
8-82 Slave Messages Rcvd 0 N/A All set-ups TRUE 0 Uint32
8-83 Slave Error Count 0 N/A All set-ups TRUE 0 Uint32
8-9* Bus Jog
8-90 Bus Jog 1 Speed 100 RPM All set-ups TRUE 67 Uint16
8-91 Bus Jog 2 Speed ExpressionLimit All set-ups TRUE 67 Uint16
Par. Parameter description Default value 4-set-up FC 302 Change Conver- Type
No. only during sion
# operation index
9-00 Setpoint 0 N/A All set-ups TRUE 0 Uint16
9-07 Actual Value 0 N/A All set-ups FALSE 0 Uint16
4 4 9-15 PCD Write Configuration ExpressionLimit 1 set-up TRUE - Uint16
9-16 PCD Read Configuration ExpressionLimit 2 set-ups TRUE - Uint16
9-18 Node Address 126 N/A 1 set-up TRUE 0 Uint8
9-22 Telegram Selection [100] None 1 set-up TRUE - Uint8
9-23 Parameters for Signals 0 All set-ups TRUE - Uint16
9-27 Parameter Edit [1] Enabled 2 set-ups FALSE - Uint16
9-28 Process Control [1] Enable cyclic master 2 set-ups FALSE - Uint8
9-44 Fault Message Counter 0 N/A All set-ups TRUE 0 Uint16
9-45 Fault Code 0 N/A All set-ups TRUE 0 Uint16
9-47 Fault Number 0 N/A All set-ups TRUE 0 Uint16
9-52 Fault Situation Counter 0 N/A All set-ups TRUE 0 Uint16
9-53 Profibus Warning Word 0 N/A All set-ups TRUE 0 V2
9-63 Actual Baud Rate [255] No baud rate found All set-ups TRUE - Uint8
9-64 Device Identification 0 N/A All set-ups TRUE 0 Uint16
OctStr[
9-65 Profile Number 0 N/A All set-ups TRUE 0 2]
9-67 Control Word 1 0 N/A All set-ups TRUE 0 V2
9-68 Status Word 1 0 N/A All set-ups TRUE 0 V2
9-71 Profibus Save Data Values [0] Off All set-ups TRUE - Uint8
9-72 ProfibusDriveReset [0] No action 1 set-up FALSE - Uint8
9-75 DO Identification 0 N/A All set-ups TRUE 0 Uint16
9-80 Defined Parameters (1) 0 N/A All set-ups FALSE 0 Uint16
9-81 Defined Parameters (2) 0 N/A All set-ups FALSE 0 Uint16
9-82 Defined Parameters (3) 0 N/A All set-ups FALSE 0 Uint16
9-83 Defined Parameters (4) 0 N/A All set-ups FALSE 0 Uint16
9-84 Defined Parameters (5) 0 N/A All set-ups FALSE 0 Uint16
9-90 Changed Parameters (1) 0 N/A All set-ups FALSE 0 Uint16
9-91 Changed Parameters (2) 0 N/A All set-ups FALSE 0 Uint16
9-92 Changed Parameters (3) 0 N/A All set-ups FALSE 0 Uint16
9-93 Changed Parameters (4) 0 N/A All set-ups FALSE 0 Uint16
9-94 Changed parameters (5) 0 N/A All set-ups FALSE 0 Uint16
9-99 Profibus Revision Counter 0 N/A All set-ups TRUE 0 Uint16
Par. Parameter description Default value 4-set-up FC 302 Change Conver- Type
No. only during sion
# operation index
10-0* Common Settings
10-00 CAN Protocol null 2 set-ups FALSE - Uint8
10-01 Baud Rate Select null 2 set-ups TRUE - Uint8 4 4
10-02 MAC ID ExpressionLimit 2 set-ups TRUE 0 Uint8
10-05 Readout Transmit Error Counter 0 N/A All set-ups TRUE 0 Uint8
10-06 Readout Receive Error Counter 0 N/A All set-ups TRUE 0 Uint8
10-07 Readout Bus Off Counter 0 N/A All set-ups TRUE 0 Uint8
10-1* DeviceNet
10-10 Process Data Type Selection null All set-ups TRUE - Uint8
10-11 Process Data Config Write ExpressionLimit All set-ups TRUE - Uint16
10-12 Process Data Config Read ExpressionLimit All set-ups TRUE - Uint16
10-13 Warning Parameter 0 N/A All set-ups TRUE 0 Uint16
10-14 Net Reference [0] Off 2 set-ups TRUE - Uint8
10-15 Net Control [0] Off 2 set-ups TRUE - Uint8
10-2* COS Filters
10-20 COS Filter 1 0 N/A All set-ups FALSE 0 Uint16
10-21 COS Filter 2 0 N/A All set-ups FALSE 0 Uint16
10-22 COS Filter 3 0 N/A All set-ups FALSE 0 Uint16
10-23 COS Filter 4 0 N/A All set-ups FALSE 0 Uint16
10-3* Parameter Access
10-30 Array Index 0 N/A 2 set-ups TRUE 0 Uint8
10-31 Store Data Values [0] Off All set-ups TRUE - Uint8
10-32 Devicenet Revision ExpressionLimit All set-ups TRUE 0 Uint16
10-33 Store Always [0] Off 1 set-up TRUE - Uint8
10-34 DeviceNet Product Code ExpressionLimit 1 set-up TRUE 0 Uint16
10-39 Devicenet F Parameters 0 N/A All set-ups TRUE 0 Uint32
10-5* CANopen
10-50 Process Data Config Write. ExpressionLimit 2 set-ups TRUE - Uint16
10-51 Process Data Config Read. ExpressionLimit 2 set-ups TRUE - Uint16
Par. Parameter description Default value 4-set-up FC 302 Change Conver- Type
No. only during sion
operatio index
n
12-0* IP Settings
4 4 12-00 IP Address Assignment null 2 set-ups TRUE - Uint8
12-01 IP Address 0 N/A 1 set-up TRUE 0 OctStr[4]
12-02 Subnet Mask 0 N/A 1 set-up TRUE 0 OctStr[4]
12-03 Default Gateway 0 N/A 1 set-up TRUE 0 OctStr[4]
12-04 DHCP Server 0 N/A 2 set-ups TRUE 0 OctStr[4]
12-05 Lease Expires ExpressionLimit All set-ups TRUE 0 TimD
12-06 Name Servers 0 N/A 1 set-up TRUE 0 OctStr[4]
12-07 Domain Name 0 N/A 1 set-up TRUE 0 VisStr[48]
12-08 Host Name 0 N/A 1 set-up TRUE 0 VisStr[48]
12-09 Physical Address 0 N/A 1 set-up TRUE 0 VisStr[17]
12-1* Eth link par
12-10 Link Status [0] No Link All set-ups TRUE - Uint8
12-11 Link Duration ExpressionLimit All set-ups TRUE 0 TimD
12-12 Auto Negotiation [1] On 2 set-ups TRUE - Uint8
12-13 Link Speed [0] None 2 set-ups TRUE - Uint8
12-14 Link Duplex [1] Full Duplex 2 set-ups TRUE - Uint8
12-2* Process Data
12-20 Control Instance ExpressionLimit 1 set-up TRUE 0 Uint8
12-21 Process Data Config Write ExpressionLimit All set-ups TRUE - Uint16
12-22 Process Data Config Read ExpressionLimit All set-ups TRUE - Uint16
12-23 Process Data Config Write Size 16 N/A All set-ups TRUE 0 Uint32
12-24 Process Data Config Read Size 16 N/A All set-ups TRUE 0 Uint32
12-27 Master Address 0 N/A 2 set-ups FALSE 0 OctStr[4]
12-28 Store Data Values [0] Off All set-ups TRUE - Uint8
12-29 Store Always [0] Off 1 set-up TRUE - Uint8
12-3* EtherNet/IP
12-30 Warning Parameter 0 N/A All set-ups TRUE 0 Uint16
12-31 Net Reference [0] Off 2 set-ups TRUE - Uint8
12-32 Net Control [0] Off 2 set-ups TRUE - Uint8
12-33 CIP Revision ExpressionLimit All set-ups TRUE 0 Uint16
12-34 CIP Product Code ExpressionLimit 1 set-up TRUE 0 Uint16
12-35 EDS Parameter 0 N/A All set-ups TRUE 0 Uint32
12-37 COS Inhibit Timer 0 N/A All set-ups TRUE 0 Uint16
12-38 COS Filter 0 N/A All set-ups TRUE 0 Uint16
12-4* Modbus TCP
12-40 Status Parameter 0 N/A All set-ups TRUE 0 Uint16
12-41 Slave Message Count 0 N/A All set-ups TRUE 0 Uint32
12-42 Slave Exception Message Count 0 N/A All set-ups TRUE 0 Uint32
12-5* EtherCAT
12-50 Configured Station Alias 0 N/A 1 set-up FALSE 0 Uint16
12-51 Configured Station Address 0 N/A All set-ups TRUE 0 Uint16
12-59 EtherCAT Status 0 N/A All set-ups TRUE 0 Uint32
12-8* Oth. Eth. services
12-80 FTP Server [0] Disabled 2 set-ups TRUE - Uint8
Par. Parameter description Default value 4-set-up FC 302 Change Conver- Type
No. only during sion
operatio index
n
12-81 HTTP Server [0] Disabled 2 set-ups TRUE - Uint8
12-82 SMTP Service [0] Disabled 2 set-ups TRUE - Uint8
12-89 Transparent Socket Channel Port ExpressionLimit 2 set-ups TRUE 0 Uint16
12-9* Adv. Eth. services 4 4
12-90 Cable Diagnostic [0] Disabled 2 set-ups TRUE - Uint8
12-91 MDI-X [1] Enabled 2 set-ups TRUE - Uint8
12-92 IGMP Snooping [1] Enabled 2 set-ups TRUE - Uint8
12-93 Cable Error Length 0 N/A 1 set-up TRUE 0 Uint16
12-94 Broadcast Storm Protection -1 % 2 set-ups TRUE 0 Int8
12-95 Broadcast Storm Filter [0] Broadcast only 2 set-ups TRUE - Uint8
12-96 Port Config null 2 set-ups TRUE - Uint8
12-98 Interface Counters 4000 N/A All set-ups TRUE 0 Uint32
12-99 Media Counters 0 N/A All set-ups TRUE 0 Uint32
Par. Parameter description Default value 4-set-up FC 302 Change Conver- Type
No. only during sion
# operation index
13-0* SLC Settings
13-00 SL Controller Mode null 2 set-ups TRUE - Uint8
4 4 13-01 Start Event null 2 set-ups TRUE - Uint8
13-02 Stop Event null 2 set-ups TRUE - Uint8
13-03 Reset SLC [0] Do not reset SLC All set-ups TRUE - Uint8
13-1* Comparators
13-10 Comparator Operand null 2 set-ups TRUE - Uint8
13-11 Comparator Operator null 2 set-ups TRUE - Uint8
13-12 Comparator Value ExpressionLimit 2 set-ups TRUE -3 Int32
13-1* RS Flip Flops
13-15 RS-FF Operand S null 2 set-ups TRUE - Uint8
13-16 RS-FF Operand R null 2 set-ups TRUE - Uint8
13-2* Timers
13-20 SL Controller Timer ExpressionLimit 1 set-up TRUE -3 TimD
13-4* Logic Rules
13-40 Logic Rule Boolean 1 null 2 set-ups TRUE - Uint8
13-41 Logic Rule Operator 1 null 2 set-ups TRUE - Uint8
13-42 Logic Rule Boolean 2 null 2 set-ups TRUE - Uint8
13-43 Logic Rule Operator 2 null 2 set-ups TRUE - Uint8
13-44 Logic Rule Boolean 3 null 2 set-ups TRUE - Uint8
13-5* States
13-51 SL Controller Event null 2 set-ups TRUE - Uint8
13-52 SL Controller Action null 2 set-ups TRUE - Uint8
Par. Parameter description Default value 4-set-up FC 302 Change Conver- Type
No. only during sion
# operation index
14-0* Inverter Switching
14-00 Switching Pattern null All set-ups TRUE - Uint8
14-01 Switching Frequency null All set-ups TRUE - Uint8 4 4
14-03 Overmodulation [1] On All set-ups FALSE - Uint8
14-04 PWM Random [0] Off All set-ups TRUE - Uint8
14-06 Dead Time Compensation [1] On All set-ups TRUE - Uint8
14-1* Mains On/Off
14-10 Line Failure [0] No function All set-ups FALSE - Uint8
14-11 Line Voltage at Line Fault ExpressionLimit All set-ups TRUE 0 Uint16
14-12 Function at Mains Imbalance [0] Trip All set-ups TRUE - Uint8
14-13 Line Failure Step Factor 1.0 N/A All set-ups TRUE -1 Uint8
14-14 Kin. Backup Time Out 60 s All set-ups TRUE 0 Uint8
14-15 Kin. Backup Trip Recovery Level ExpressionLimit All set-ups TRUE -3 Uint32
14-2* Trip Reset
14-20 Reset Mode [0] Manual reset All set-ups TRUE - Uint8
14-21 Automatic Restart Time ExpressionLimit All set-ups TRUE 0 Uint16
14-22 Operation Mode [0] Normal operation All set-ups TRUE - Uint8
14-23 Typecode Setting null 2 set-ups FALSE - Uint8
14-24 Trip Delay at Current Limit 60 s All set-ups TRUE 0 Uint8
14-25 Trip Delay at Torque Limit 60 s All set-ups TRUE 0 Uint8
14-26 Trip Delay at Inverter Fault ExpressionLimit All set-ups TRUE 0 Uint8
14-28 Production Settings [0] No action All set-ups TRUE - Uint8
14-29 Service Code 0 N/A All set-ups TRUE 0 Int32
14-3* Current Limit Ctrl.
14-30 Current Lim Ctrl, Proportional Gain 100 % All set-ups FALSE 0 Uint16
14-31 Current Lim Ctrl, Integration Time 0.020 s All set-ups FALSE -3 Uint16
14-32 Current Lim Ctrl, Filter Time 1.0 ms All set-ups TRUE -4 Uint16
14-35 Stall Protection [1] Enabled All set-ups FALSE - Uint8
14-4* Energy Optimizing
14-40 VT Level 66 % All set-ups FALSE 0 Uint8
14-41 AEO Minimum Magnetization ExpressionLimit All set-ups TRUE 0 Uint8
14-42 Minimum AEO Frequency 10 Hz All set-ups TRUE 0 Uint8
14-43 Motor Cos-Phi ExpressionLimit All set-ups TRUE -2 Uint16
14-5* Environment
14-50 RFI 1 [1] On 1 set-up x FALSE - Uint8
14-51 DC Link Compensation [1] On 1 set-up TRUE - Uint8
14-52 Fan Control [0] Auto All set-ups TRUE - Uint8
14-53 Fan Monitor [1] Warning All set-ups TRUE - Uint8
14-55 Output Filter [0] No Filter All set-ups FALSE - Uint8
14-56 Capacitance Output Filter ExpressionLimit All set-ups FALSE -7 Uint16
14-57 Inductance Output Filter ExpressionLimit All set-ups FALSE -6 Uint16
14-59 Actual Number of Inverter Units ExpressionLimit 1 set-up x FALSE 0 Uint8
14-7* Compatibility
14-72 VLT Alarm Word 0 N/A All set-ups FALSE 0 Uint32
14-73 VLT Warning Word 0 N/A All set-ups FALSE 0 Uint32
14-74 VLT Ext. Status Word 0 N/A All set-ups FALSE 0 Uint32
Par. Parameter description Default value 4-set-up FC 302 Change Conver- Type
No. only during sion
# operation index
14-8* Options
14-80 Option Supplied by External 24 V DC [1] Yes 2 set-ups FALSE - Uint8
14-89 Option Detection [0] Protect Option Config. 1 set-up TRUE - Uint8
14-9* Fault Settings
4 4 14-90 Fault Level null 1 set-up TRUE - Uint8
Par. Parameter description Default value 4-set-up FC 302 Change Conver- Type
No. only during sion
# operation index
15-0* Operating Data
15-00 Operating Hours 0h All set-ups FALSE 74 Uint32
15-01 Running Hours 0h All set-ups FALSE 74 Uint32 4 4
15-02 kWh Counter 0 kWh All set-ups FALSE 75 Uint32
15-03 Power-ups 0 N/A All set-ups FALSE 0 Uint32
15-04 Over Temps 0 N/A All set-ups FALSE 0 Uint16
15-05 Over Volts 0 N/A All set-ups FALSE 0 Uint16
15-06 Reset kWh Counter [0] Do not reset All set-ups TRUE - Uint8
15-07 Reset Running Hours Counter [0] Do not reset All set-ups TRUE - Uint8
15-1* Data Log Settings
15-10 Logging Source 0 2 set-ups TRUE - Uint16
15-11 Logging Interval ExpressionLimit 2 set-ups TRUE -3 TimD
15-12 Trigger Event [0] FALSE 1 set-up TRUE - Uint8
15-13 Logging Mode [0] Log always 2 set-ups TRUE - Uint8
15-14 Samples Before Trigger 50 N/A 2 set-ups TRUE 0 Uint8
15-2* Historic Log
15-20 Historic Log: Event 0 N/A All set-ups FALSE 0 Uint8
15-21 Historic Log: Value 0 N/A All set-ups FALSE 0 Uint32
15-22 Historic Log: Time 0 ms All set-ups FALSE -3 Uint32
15-3* Fault Log
15-30 Fault Log: Error Code 0 N/A All set-ups FALSE 0 Uint8
15-31 Fault Log: Value 0 N/A All set-ups FALSE 0 Int16
15-32 Fault Log: Time 0s All set-ups FALSE 0 Uint32
15-4* Drive Identification
15-40 FC Type 0 N/A All set-ups FALSE 0 VisStr[6]
15-41 Power Section 0 N/A All set-ups FALSE 0 VisStr[20]
15-42 Voltage 0 N/A All set-ups FALSE 0 VisStr[20]
15-43 Software Version 0 N/A All set-ups FALSE 0 VisStr[5]
15-44 Ordered Typecode String 0 N/A All set-ups FALSE 0 VisStr[40]
15-45 Actual Typecode String 0 N/A All set-ups FALSE 0 VisStr[40]
15-46 Adj Freq Dr Ordering No. 0 N/A All set-ups FALSE 0 VisStr[8]
15-47 Power Card Ordering No. 0 N/A All set-ups FALSE 0 VisStr[8]
15-48 LCP ID Num. 0 N/A All set-ups FALSE 0 VisStr[20]
15-49 SW ID Control Card 0 N/A All set-ups FALSE 0 VisStr[20]
15-50 SW ID Power Card 0 N/A All set-ups FALSE 0 VisStr[20]
15-51 Adj Freq Dr Serial No. 0 N/A All set-ups FALSE 0 VisStr[10]
15-53 Power Card Serial Number 0 N/A All set-ups FALSE 0 VisStr[19]
15-58 Smart Setup Filename ExpressionLimit 1 set-up FALSE 0 VisStr[16]
15-59 CSIV Filename ExpressionLimit 1 set-up FALSE 0 VisStr[16]
15-6* Option Ident
15-60 Option Mounted 0 N/A All set-ups FALSE 0 VisStr[30]
15-61 Option SW Version 0 N/A All set-ups FALSE 0 VisStr[20]
15-62 Option Ordering No 0 N/A All set-ups FALSE 0 VisStr[8]
15-63 Option Serial No 0 N/A All set-ups FALSE 0 VisStr[18]
15-70 Option in Slot A 0 N/A All set-ups FALSE 0 VisStr[30]
15-71 Slot A Option SW Version 0 N/A All set-ups FALSE 0 VisStr[20]
Par. Parameter description Default value 4-set-up FC 302 Change Conver- Type
No. only during sion
# operation index
15-72 Option in Slot B 0 N/A All set-ups FALSE 0 VisStr[30]
15-73 Slot B Option SW Version 0 N/A All set-ups FALSE 0 VisStr[20]
15-74 Option in Slot C0 0 N/A All set-ups FALSE 0 VisStr[30]
15-75 Slot C0 Option SW Version 0 N/A All set-ups FALSE 0 VisStr[20]
4 4 15-76 Option in Slot C1 0 N/A All set-ups FALSE 0 VisStr[30]
15-77 Slot C1 Option SW Version 0 N/A All set-ups FALSE 0 VisStr[20]
15-9* Parameter Info
15-92 Defined Parameters 0 N/A All set-ups FALSE 0 Uint16
15-93 Modified Parameters 0 N/A All set-ups FALSE 0 Uint16
15-98 Drive Identification 0 N/A All set-ups FALSE 0 VisStr[40]
15-99 Parameter Metadata 0 N/A All set-ups FALSE 0 Uint16
Par. Parameter description Default value 4-set-up FC 302 Change Conver- Type
No. only during sion
# operation index
16-0* General Status
16-00 Control Word 0 N/A All set-ups FALSE 0 V2
0.000 ReferenceFeed- 4 4
16-01 Reference [Unit] backUnit All set-ups FALSE -3 Int32
16-02 Reference % 0.0 % All set-ups FALSE -1 Int16
16-03 Status Word 0 N/A All set-ups FALSE 0 V2
16-05 Main Actual Value [%] 0.00 % All set-ups FALSE -2 N2
16-09 Custom Readout 0.00 CustomReadoutUnit All set-ups FALSE -2 Int32
16-1* Motor Status
16-10 Power [kW] 0.00 kW All set-ups FALSE 1 Int32
16-11 Power [hp] 0.00 hp All set-ups FALSE -2 Int32
16-12 Motor voltage 0.0 V All set-ups FALSE -1 Uint16
16-13 Frequency 0.0 Hz All set-ups FALSE -1 Uint16
16-14 Motor Current 0.00 A All set-ups FALSE -2 Int32
16-15 Frequency [%] 0.00 % All set-ups FALSE -2 N2
16-16 Torque [Nm] 0.0 Nm All set-ups FALSE -1 Int16
16-17 Speed [RPM] 0 RPM All set-ups FALSE 67 Int32
16-18 Motor Thermal 0% All set-ups FALSE 0 Uint8
16-19 KTY sensor temperature 0 °C All set-ups FALSE 100 Int16
16-20 Motor Angle 0 N/A All set-ups TRUE 0 Uint16
16-21 Torque [%] High Res. 0.0 % All set-ups FALSE -1 Int16
16-22 Torque [%] 0% All set-ups FALSE 0 Int16
16-25 Torque [Nm] High 0.0 Nm All set-ups FALSE -1 Int32
16-3* Drive Status
16-30 DC Link Voltage 0V All set-ups FALSE 0 Uint16
16-32 Brake Energy /s 0.000 kW All set-ups FALSE 0 Uint32
16-33 Brake Energy /2 min 0.000 kW All set-ups FALSE 0 Uint32
16-34 Heatsink Temp. 0 °C All set-ups FALSE 100 Uint8
16-35 Inverter Thermal 0% All set-ups FALSE 0 Uint8
16-36 Inv. Nom. Current ExpressionLimit All set-ups FALSE -2 Uint32
16-37 Inv. Max. Current ExpressionLimit All set-ups FALSE -2 Uint32
16-38 SL Controller State 0 N/A All set-ups FALSE 0 Uint8
16-39 Control Card Temp. 0 °C All set-ups FALSE 100 Uint8
16-40 Logging Buffer Full [0] No All set-ups TRUE - Uint8
VisStr[5
16-41 LCP Bottom Statusline 0 N/A All set-ups TRUE 0 0]
16-49 Current Fault Source 0 N/A All set-ups x TRUE 0 Uint8
16-5* Ref. & Feedb.
16-50 External Reference 0.0 N/A All set-ups FALSE -1 Int16
16-51 Pulse Reference 0.0 N/A All set-ups FALSE -1 Int16
0.000 ReferenceFeed-
16-52 Feedback [Unit] backUnit All set-ups FALSE -3 Int32
16-53 Digi Pot Reference 0.00 N/A All set-ups FALSE -2 Int16
16-57 Feedback [RPM] 0 RPM All set-ups FALSE 67 Int32
16-6* Inputs & Outputs
16-60 Digital Input 0 N/A All set-ups FALSE 0 Uint16
Par. Parameter description Default value 4-set-up FC 302 Change Conver- Type
No. only during sion
# operation index
16-61 Terminal 53 Switch Setting [0] Current All set-ups FALSE - Uint8
16-62 Analog Input 53 0.000 N/A All set-ups FALSE -3 Int32
16-63 Terminal 54 Switch Setting [0] Current All set-ups FALSE - Uint8
16-64 Analog Input 54 0.000 N/A All set-ups FALSE -3 Int32
4 4 16-65 Analog Output 42 [mA] 0.000 N/A All set-ups FALSE -3 Int16
16-66 Digital Output [bin] 0 N/A All set-ups FALSE 0 Int16
16-67 Freq. Input #29 [Hz] 0 N/A All set-ups x FALSE 0 Int32
16-68 Freq. Input #33 [Hz] 0 N/A All set-ups FALSE 0 Int32
16-69 Pulse Output #27 [Hz] 0 N/A All set-ups FALSE 0 Int32
16-70 Pulse Output #29 [Hz] 0 N/A All set-ups x FALSE 0 Int32
16-71 Relay Output [bin] 0 N/A All set-ups FALSE 0 Int16
16-72 Counter A 0 N/A All set-ups TRUE 0 Int32
16-73 Counter B 0 N/A All set-ups TRUE 0 Int32
16-74 Prec. Stop Counter 0 N/A All set-ups TRUE 0 Uint32
16-75 Analog In X30/11 0.000 N/A All set-ups FALSE -3 Int32
16-76 Analog In X30/12 0.000 N/A All set-ups FALSE -3 Int32
16-77 Analog Out X30/8 [mA] 0.000 N/A All set-ups FALSE -3 Int16
16-78 Analog Out X45/1 [mA] 0.000 N/A All set-ups FALSE -3 Int16
16-79 Analog Out X45/3 [mA] 0.000 N/A All set-ups FALSE -3 Int16
16-8* Fieldbus & FC Port
16-80 Fieldbus CTW 1 0 N/A All set-ups FALSE 0 V2
16-82 Fieldbus REF 1 0 N/A All set-ups FALSE 0 N2
16-84 Comm. Option Status 0 N/A All set-ups FALSE 0 V2
16-85 FC Port CTW 1 0 N/A All set-ups FALSE 0 V2
16-86 FC Port REF 1 0 N/A All set-ups FALSE 0 N2
16-9* Diagnosis Readouts
16-90 Alarm Word 0 N/A All set-ups FALSE 0 Uint32
16-91 Alarm word 2 0 N/A All set-ups FALSE 0 Uint32
16-92 Warning Word 0 N/A All set-ups FALSE 0 Uint32
16-93 Warning word 2 0 N/A All set-ups FALSE 0 Uint32
16-94 Ext. Status Word 0 N/A All set-ups FALSE 0 Uint32
Par. Parameter description Default value 4-set-up FC 302 Change Conver- Type
No. only during sion
# operation index
17-1* Inc. Enc. Interface
17-10 Signal Type [1] TTL (5V, RS4222) All set-ups FALSE - Uint8
17-11 Resolution (PPR) 1024 N/A All set-ups FALSE 0 Uint16 4 4
17-2* Abs. Enc. Interface
17-20 Protocol Selection [0] None All set-ups FALSE - Uint8
17-21 Resolution (Positions/Rev) ExpressionLimit All set-ups FALSE 0 Uint32
17-24 SSI Data Length 13 N/A All set-ups FALSE 0 Uint8
17-25 Clock Rate ExpressionLimit All set-ups FALSE 3 Uint16
17-26 SSI Data Format [0] Gray code All set-ups FALSE - Uint8
17-34 HIPERFACE Baud rate [4] 9600 All set-ups FALSE - Uint8
17-5* Resolver Interface
17-50 Poles 2 N/A 1 set-up FALSE 0 Uint8
17-51 Input Voltage 7.0 V 1 set-up FALSE -1 Uint8
17-52 Input Frequency 10.0 kHz 1 set-up FALSE 2 Uint8
17-53 Transformation Ratio 0.5 N/A 1 set-up FALSE -1 Uint8
17-56 Encoder Sim. Resolution [0] Disabled 1 set-up FALSE - Uint8
17-59 Resolver Interface [0] Disabled All set-ups FALSE - Uint8
17-6* Monitoring and App.
17-60 Feedback Direction [0] Clockwise All set-ups FALSE - Uint8
17-61 Feedback Signal Monitoring [1] Warning All set-ups TRUE - Uint8
Par. Parameter description Default value 4-set-up FC 302 Change Conver- Type
No. only during sion
# operation index
18-3* Analog Readouts
18-36 Analog Input X48/2 [mA] 0.000 N/A All set-ups TRUE -3 Int32
18-37 Temp. Input X48/4 0 N/A All set-ups TRUE 0 Int16
18-38 Temp. Input X48/7 0 N/A All set-ups TRUE 0 Int16
18-39 Temp. Input X48/10 0 N/A All set-ups TRUE 0 Int16
18-6* Inputs & Outputs 2
18-60 Digital Input 2 0 N/A All set-ups FALSE 0 Uint16
18-9* PID Readouts
18-90 Process PID Error 0.0 % All set-ups FALSE -1 Int16
18-91 Process PID Output 0.0 % All set-ups FALSE -1 Int16
18-92 Process PID Clamped Output 0.0 % All set-ups FALSE -1 Int16
18-93 Process PID Gain Scaled Output 0.0 % All set-ups FALSE -1 Int16
Par. Parameter description Default value 4-set-up FC 302 Change Conver- Type
No. only during sion
# operation index
30-0* Wobbler
30-00 Wobble Mode [0] Abs. Freq., Abs. Time All set-ups FALSE - Uint8
4 4 30-01 Wobble Delta Frequency [Hz] 5.0 Hz All set-ups TRUE -1 Uint8
30-02 Wobble Delta Frequency [%] 25 % All set-ups TRUE 0 Uint8
30-03 Wobble Delta Freq. Scaling Resource [0] No function All set-ups TRUE - Uint8
30-04 Wobble Jump Frequency [Hz] 0.0 Hz All set-ups TRUE -1 Uint8
30-05 Wobble Jump Frequency [%] 0% All set-ups TRUE 0 Uint8
30-06 Wobble Jump Time ExpressionLimit All set-ups TRUE -3 Uint16
30-07 Wobble Sequence Time 10.0 s All set-ups TRUE -1 Uint16
30-08 Wobble Up/Down Time 5.0 s All set-ups TRUE -1 Uint16
30-09 Wobble Random Function [0] Off All set-ups TRUE - Uint8
30-10 Wobble Ratio 1.0 N/A All set-ups TRUE -1 Uint8
30-11 Wobble Random Ratio Max. 10.0 N/A All set-ups TRUE -1 Uint8
30-12 Wobble Random Ratio Min. 0.1 N/A All set-ups TRUE -1 Uint8
30-19 Wobble Delta Freq. Scaled 0.0 Hz All set-ups FALSE -1 Uint16
30-2* Adv. Start Adjust
30-20 High Starting Torque Time [s] 0.00 s All set-ups x TRUE -2 Uint16
30-21 High Starting Torque Current [%] 100.0 % All set-ups x TRUE -1 Uint32
30-22 Locked Rotor Protection [0] Off All set-ups x TRUE - Uint8
30-23 Locked Rotor Detection Time [s] 0.10 s All set-ups x TRUE -2 Uint8
30-8* Compatibility (I)
30-80 d-axis inductance (Ld) ExpressionLimit All set-ups x FALSE -6 Int32
30-81 Brake Resistor (ohm) ExpressionLimit 1 set-up TRUE -2 Uint32
30-83 Speed PID Proportional Gain ExpressionLimit All set-ups TRUE -4 Uint32
30-84 Process PID Proportional Gain 0.100 N/A All set-ups TRUE -3 Uint16
Par. Parameter description Default value 4-set-up FC 302 Change Conver- Type
No. only during sion
# operation index
32-0* Encoder 2
32-00 Incremental Signal Type [1] TTL (5V, RS4222) 2 set-ups TRUE - Uint8
32-01 Incremental Resolution 1024 N/A 2 set-ups TRUE 0 Uint32 4 4
32-02 Absolute Protocol [0] None 2 set-ups TRUE - Uint8
32-03 Absolute Resolution 8192 N/A 2 set-ups TRUE 0 Uint32
32-04 Absolute Encoder Baudrate X55 [4] 9600 All set-ups FALSE - Uint8
32-05 Absolute Encoder Data Length 25 N/A 2 set-ups TRUE 0 Uint8
32-06 Absolute Encoder Clock Frequency 262.000 kHz 2 set-ups TRUE 0 Uint32
32-07 Absolute Encoder Clock Generation [1] On 2 set-ups TRUE - Uint8
32-08 Absolute Encoder Cable Length 0m 2 set-ups TRUE 0 Uint16
32-09 Encoder Monitoring [0] Off 2 set-ups TRUE - Uint8
32-10 Rotational Direction [1] No action 2 set-ups TRUE - Uint8
32-11 User Unit Denominator 1 N/A 2 set-ups TRUE 0 Uint32
32-12 User Unit Numerator 1 N/A 2 set-ups TRUE 0 Uint32
32-13 Enc.2 Control [0] No soft changing 2 set-ups TRUE - Uint8
32-14 Enc.2 node ID 127 N/A 2 set-ups TRUE 0 Uint8
32-15 Enc.2 CAN guard null 2 set-ups TRUE - Uint8
32-3* Encoder 1
32-30 Incremental Signal Type [1] TTL (5V, RS4222) 2 set-ups TRUE - Uint8
32-31 Incremental Resolution 1024 N/A 2 set-ups TRUE 0 Uint32
32-32 Absolute Protocol [0] None 2 set-ups TRUE - Uint8
32-33 Absolute Resolution 8192 N/A 2 set-ups TRUE 0 Uint32
32-35 Absolute Encoder Data Length 25 N/A 2 set-ups TRUE 0 Uint8
32-36 Absolute Encoder Clock Frequency 262.000 kHz 2 set-ups TRUE 0 Uint32
32-37 Absolute Encoder Clock Generation [1] On 2 set-ups TRUE - Uint8
32-38 Absolute Encoder Cable Length 0m 2 set-ups TRUE 0 Uint16
32-39 Encoder Monitoring [0] Off 2 set-ups TRUE - Uint8
32-40 Encoder Termination [1] On 2 set-ups TRUE - Uint8
32-43 Enc.1 Control [0] No soft changing 2 set-ups TRUE - Uint8
32-44 Enc.1 node ID 127 N/A 2 set-ups TRUE 0 Uint8
32-45 Enc.1 CAN guard null 2 set-ups TRUE - Uint8
32-5* Feedback Source
32-50 Source Slave [2] Encoder 2 2 set-ups TRUE - Uint8
32-51 MCO 302 Last Will [1] Trip 2 set-ups TRUE - Uint8
32-52 Source Master [1] Encoder 1 X56 2 set-ups TRUE - Uint8
32-6* PID Controller
32-60 Proportional factor 30 N/A 2 set-ups TRUE 0 Uint32
32-61 Derivative factor 0 N/A 2 set-ups TRUE 0 Uint32
32-62 Integral factor 0 N/A 2 set-ups TRUE 0 Uint32
32-63 Limit Value for Integral Sum 1000 N/A 2 set-ups TRUE 0 Uint16
32-64 PID Bandwidth 1000 N/A 2 set-ups TRUE 0 Uint16
32-65 Velocity Feed-Forward 0 N/A 2 set-ups TRUE 0 Uint32
32-66 Acceleration Feed-Forward 0 N/A 2 set-ups TRUE 0 Uint32
32-67 Max. Tolerated Position Error 20000 N/A 2 set-ups TRUE 0 Uint32
32-68 Reverse Behavior for Slave [0] Reversing allowed 2 set-ups TRUE - Uint8
32-69 Sampling Time for PID Control 1 ms 2 set-ups TRUE -3 Uint16
Par. Parameter description Default value 4-set-up FC 302 Change Conver- Type
No. only during sion
# operation index
32-70 Scan Time for Profile Generator 1 ms 2 set-ups TRUE -3 Uint8
32-71 Size of the Control Window (Activation) 0 N/A 2 set-ups TRUE 0 Uint32
32-72 Size of the Control Window (Deactiv.) 0 N/A 2 set-ups TRUE 0 Uint32
32-73 Integral limit filter time 0 ms 2 set-ups TRUE -3 Int16
4 4 32-74 Position error filter time 0 ms 2 set-ups TRUE -3 Int16
32-8* Velocity & Accel.
32-80 Maximum Velocity (Encoder) 1500 RPM 2 set-ups TRUE 67 Uint32
32-81 Shortest Ramp 1.000 s 2 set-ups TRUE -3 Uint32
32-82 Ramp Type [0] Linear 2 set-ups TRUE - Uint8
32-83 Velocity Resolution 100 N/A 2 set-ups TRUE 0 Uint32
32-84 Default Velocity 50 N/A 2 set-ups TRUE 0 Uint32
32-85 Default Acceleration 50 N/A 2 set-ups TRUE 0 Uint32
32-86 Acc. up for limited jerk 100 ms 2 set-ups TRUE -3 Uint32
32-87 Acc. down for limited jerk 0 ms 2 set-ups TRUE -3 Uint32
32-88 Dec. up for limited jerk 0 ms 2 set-ups TRUE -3 Uint32
32-89 Dec. down for limited jerk 0 ms 2 set-ups TRUE -3 Uint32
32-9* Development
32-90 Debug Source [0] Controlcard 2 set-ups TRUE - Uint8
Par. Parameter description Default value 4-set-up FC 302 Change Conver- Type
No. only during sion
# operation index
33-0* Home Motion
33-00 Force HOME [0] Home not forced 2 set-ups TRUE - Uint8
33-01 Zero Point Offset from Home Pos. 0 N/A 2 set-ups TRUE 0 Int32 4 4
33-02 Ramp for Home Motion 10 N/A 2 set-ups TRUE 0 Uint32
33-03 Velocity of Home Motion 10 N/A 2 set-ups TRUE 0 Int32
33-04 Behavior during Home Motion [0] Reverse and index 2 set-ups TRUE - Uint8
33-1* Synchronization
33-10 Synchronization Factor Master (M:S) 1 N/A 2 set-ups TRUE 0 Int32
33-11 Synchronization Factor Slave (M:S) 1 N/A 2 set-ups TRUE 0 Int32
33-12 Position Offset for Synchronization 0 N/A 2 set-ups TRUE 0 Int32
33-13 Accuracy Window for Position Sync. 1000 N/A 2 set-ups TRUE 0 Int32
33-14 Relative Slave Velocity Limit 0% 2 set-ups TRUE 0 Uint8
33-15 Marker Number for Master 1 N/A 2 set-ups TRUE 0 Uint16
33-16 Marker Number for Slave 1 N/A 2 set-ups TRUE 0 Uint16
33-17 Master Marker Distance 4096 N/A 2 set-ups TRUE 0 Uint32
33-18 Slave Marker Distance 4096 N/A 2 set-ups TRUE 0 Uint32
33-19 Master Marker Type [0] Encoder Z positive 2 set-ups TRUE - Uint8
33-20 Slave Marker Type [0] Encoder Z positive 2 set-ups TRUE - Uint8
33-21 Master Marker Tolerance Window 0 N/A 2 set-ups TRUE 0 Uint32
33-22 Slave Marker Tolerance Window 0 N/A 2 set-ups TRUE 0 Uint32
33-23 Start Behavior for Marker Sync [0] Start Function 1 2 set-ups TRUE - Uint16
33-24 Marker Number for Fault 10 N/A 2 set-ups TRUE 0 Uint16
33-25 Marker Number for Ready 1 N/A 2 set-ups TRUE 0 Uint16
33-26 Velocity Filter 0 us 2 set-ups TRUE -6 Int32
33-27 Offset Filter Time 0 ms 2 set-ups TRUE -3 Uint32
33-28 Marker Filter Configuration [0] Marker filter 1 2 set-ups TRUE - Uint8
33-29 Filter Time for Marker Filter 0 ms 2 set-ups TRUE -3 Int32
33-30 Maximum Marker Correction 0 N/A 2 set-ups TRUE 0 Uint32
33-31 Synchronization Type [0] Standard 2 set-ups TRUE - Uint8
33-32 Feed Forward Velocity Adaptation 0 N/A 2 set-ups TRUE 0 Uint32
33-33 Velocity Filter Window 0 N/A 2 set-ups TRUE 0 Uint32
33-34 Slave Marker filter time 0 ms 2 set-ups TRUE -3 Uint32
33-4* Limit Handling
33-40 Behavior at End Limit Switch [0] Call error handler 2 set-ups TRUE - Uint8
33-41 Negative Software End Limit -500000 N/A 2 set-ups TRUE 0 Int32
33-42 Positive Software End Limit 500000 N/A 2 set-ups TRUE 0 Int32
33-43 Negative Software End Limit Active [0] Inactive 2 set-ups TRUE - Uint8
33-44 Positive Software End Limit Active [0] Inactive 2 set-ups TRUE - Uint8
33-45 Time in Target Window 0 ms 2 set-ups TRUE -3 Uint8
33-46 Target Window LimitValue 1 N/A 2 set-ups TRUE 0 Uint16
33-47 Size of Target Window 0 N/A 2 set-ups TRUE 0 Uint16
33-5* I/O Configuration
33-50 Terminal X57/1 Digital Input [0] No function 2 set-ups TRUE - Uint8
33-51 Terminal X57/2 Digital Input [0] No function 2 set-ups TRUE - Uint8
33-52 Terminal X57/3 Digital Input [0] No function 2 set-ups TRUE - Uint8
33-53 Terminal X57/4 Digital Input [0] No function 2 set-ups TRUE - Uint8
Par. Parameter description Default value 4-set-up FC 302 Change Conver- Type
No. only during sion
# operation index
33-54 Terminal X57/5 Digital Input [0] No function 2 set-ups TRUE - Uint8
33-55 Terminal X57/6 Digital Input [0] No function 2 set-ups TRUE - Uint8
33-56 Terminal X57/7 Digital Input [0] No function 2 set-ups TRUE - Uint8
33-57 Terminal X57/8 Digital Input [0] No function 2 set-ups TRUE - Uint8
4 4 33-58 Terminal X57/9 Digital Input [0] No function 2 set-ups TRUE - Uint8
33-59 Terminal X57/10 Digital Input [0] No function 2 set-ups TRUE - Uint8
33-60 Terminal X59/1 and X59/2 Mode [1] Output 2 set-ups FALSE - Uint8
33-61 Terminal X59/1 Digital Input [0] No function 2 set-ups TRUE - Uint8
33-62 Terminal X59/2 Digital Input [0] No function 2 set-ups TRUE - Uint8
33-63 Terminal X59/1 Digital Output [0] No function 2 set-ups TRUE - Uint8
33-64 Terminal X59/2 Digital Output [0] No function 2 set-ups TRUE - Uint8
33-65 Terminal X59/3 Digital Output [0] No function 2 set-ups TRUE - Uint8
33-66 Terminal X59/4 Digital Output [0] No function 2 set-ups TRUE - Uint8
33-67 Terminal X59/5 Digital Output [0] No function 2 set-ups TRUE - Uint8
33-68 Terminal X59/6 Digital Output [0] No function 2 set-ups TRUE - Uint8
33-69 Terminal X59/7 Digital Output [0] No function 2 set-ups TRUE - Uint8
33-70 Terminal X59/8 Digital Output [0] No function 2 set-ups TRUE - Uint8
33-8* Global Parameters
33-80 Activated Program Number -1 N/A 2 set-ups TRUE 0 Int8
33-81 Power-up State [1] Motor ON 2 set-ups TRUE - Uint8
33-82 Drive Status Monitoring [1] On 2 set-ups TRUE - Uint8
33-83 Behavior After Error [0] Coast 2 set-ups TRUE - Uint8
33-84 Behavior afterEsc. [0] Controlled stop 2 set-ups TRUE - Uint8
33-85 MCO Supplied by External 24VDC [0] No 2 set-ups TRUE - Uint8
33-86 Terminal at alarm [0] Relay 1 2 set-ups TRUE - Uint8
33-87 Terminal state at alarm [0] Do nothing 2 set-ups TRUE - Uint8
33-88 Status word at alarm 0 N/A 2 set-ups TRUE 0 Uint16
33-9* MCO Port Settings
33-90 X62 MCO CAN node ID 127 N/A 2 set-ups TRUE 0 Uint8
33-91 X62 MCO CAN baud rate [20] 125 Kbps 2 set-ups TRUE - Uint8
33-94 X60 MCO RS485 serial termination [0] Off 2 set-ups TRUE - Uint8
33-95 X60 MCO RS485 serial baud rate [2] 9600 Baud 2 set-ups TRUE - Uint8
Par. Parameter description Default value 4-set-up FC 302 Change Conver- Type
No. only during sion
# operation index
34-0* PCD Write Par.
34-01 PCD 1 Write to MCO 0 N/A All set-ups TRUE 0 Uint16
34-02 PCD 2 Write to MCO 0 N/A All set-ups TRUE 0 Uint16 4 4
34-03 PCD 3 Write to MCO 0 N/A All set-ups TRUE 0 Uint16
34-04 PCD 4 Write to MCO 0 N/A All set-ups TRUE 0 Uint16
34-05 PCD 5 Write to MCO 0 N/A All set-ups TRUE 0 Uint16
34-06 PCD 6 Write to MCO 0 N/A All set-ups TRUE 0 Uint16
34-07 PCD 7 Write to MCO 0 N/A All set-ups TRUE 0 Uint16
34-08 PCD 8 Write to MCO 0 N/A All set-ups TRUE 0 Uint16
34-09 PCD 9 Write to MCO 0 N/A All set-ups TRUE 0 Uint16
34-10 PCD 10 Write to MCO 0 N/A All set-ups TRUE 0 Uint16
34-2* PCD Read Par.
34-21 PCD 1 Read from MCO 0 N/A All set-ups TRUE 0 Uint16
34-22 PCD 2 Read from MCO 0 N/A All set-ups TRUE 0 Uint16
34-23 PCD 3 Read from MCO 0 N/A All set-ups TRUE 0 Uint16
34-24 PCD 4 Read from MCO 0 N/A All set-ups TRUE 0 Uint16
34-25 PCD 5 Read from MCO 0 N/A All set-ups TRUE 0 Uint16
34-26 PCD 6 Read from MCO 0 N/A All set-ups TRUE 0 Uint16
34-27 PCD 7 Read from MCO 0 N/A All set-ups TRUE 0 Uint16
34-28 PCD 8 Read from MCO 0 N/A All set-ups TRUE 0 Uint16
34-29 PCD 9 Read from MCO 0 N/A All set-ups TRUE 0 Uint16
34-30 PCD 10 Read from MCO 0 N/A All set-ups TRUE 0 Uint16
34-4* Inputs & Outputs
34-40 Digital Inputs 0 N/A All set-ups TRUE 0 Uint16
34-41 Digital Outputs 0 N/A All set-ups TRUE 0 Uint16
34-5* Process Data
34-50 Actual Position 0 N/A All set-ups TRUE 0 Int32
34-51 Commanded Position 0 N/A All set-ups TRUE 0 Int32
34-52 Actual Master Position 0 N/A All set-ups TRUE 0 Int32
34-53 Slave Index Position 0 N/A All set-ups TRUE 0 Int32
34-54 Master Index Position 0 N/A All set-ups TRUE 0 Int32
34-55 Curve Position 0 N/A All set-ups TRUE 0 Int32
34-56 Track Error 0 N/A All set-ups TRUE 0 Int32
34-57 Synchronizing Error 0 N/A All set-ups TRUE 0 Int32
34-58 Actual Velocity 0 N/A All set-ups TRUE 0 Int32
34-59 Actual Master Velocity 0 N/A All set-ups TRUE 0 Int32
34-60 Synchronizing Status 0 N/A All set-ups TRUE 0 Int32
34-61 Axis Status 0 N/A All set-ups TRUE 0 Int32
34-62 Program Status 0 N/A All set-ups TRUE 0 Int32
34-64 MCO 302 Status 0 N/A All set-ups TRUE 0 Uint16
34-65 MCO 302 Control 0 N/A All set-ups TRUE 0 Uint16
34-7* Diagnosis readouts
34-70 MCO Alarm Word 1 0 N/A All set-ups FALSE 0 Uint32
34-71 MCO Alarm Word 2 0 N/A All set-ups FALSE 0 Uint32
Par. Parameter description Default value 4-set-up FC 302 Change Conver- Type
No. only during sion
# operation index
35-0* Temp. Input Mode
35-00 Term. X48/4 Temp. Unit [60] °C All set-ups TRUE - Uint8
4 4 35-01 Term. X48/4 Input Type [0] Not Connected All set-ups TRUE - Uint8
35-02 Term. X48/7 Temp. Unit [60] °C All set-ups TRUE - Uint8
35-03 Term. X48/7 Input Type [0] Not Connected All set-ups TRUE - Uint8
35-04 Term. X48/10 Temp. Unit [60] °C All set-ups TRUE - Uint8
35-05 Term. X48/10 Input Type [0] Not Connected All set-ups TRUE - Uint8
35-06 Temperature Sensor Alarm Function [5] Stop and trip All set-ups TRUE - Uint8
35-1* Temp. Input X48/4
35-14 Term. X48/4 Filter Time Constant 0.001 s All set-ups TRUE -3 Uint16
35-15 Term. X48/4 Temp. Monitor [0] Disabled All set-ups TRUE - Uint8
35-16 Term. X48/4 Low Temp. Limit ExpressionLimit All set-ups TRUE 0 Int16
35-17 Term. X48/4 High Temp. Limit ExpressionLimit All set-ups TRUE 0 Int16
35-2* Temp. Input X48/7
35-24 Term. X48/7 Filter Time Constant 0.001 s All set-ups TRUE -3 Uint16
35-25 Term. X48/7 Temp. Monitor [0] Disabled All set-ups TRUE - Uint8
35-26 Term. X48/7 Low Temp. Limit ExpressionLimit All set-ups TRUE 0 Int16
35-27 Term. X48/7 High Temp. Limit ExpressionLimit All set-ups TRUE 0 Int16
35-3* Temp. Input X48/10
35-34 Term. X48/10 Filter Time Constant 0.001 s All set-ups TRUE -3 Uint16
35-35 Term. X48/10 Temp. Monitor [0] Disabled All set-ups TRUE - Uint8
35-36 Term. X48/10 Low Temp. Limit ExpressionLimit All set-ups TRUE 0 Int16
35-37 Term. X48/10 High Temp. Limit ExpressionLimit All set-ups TRUE 0 Int16
35-4* Analog Input X48/2
35-42 Term. X48/2 Low Current 4.00 mA All set-ups TRUE -5 Int16
35-43 Term. X48/2 High Current 20.00 mA All set-ups TRUE -5 Int16
35-44 Term. X48/2 Low Ref./Feedb. Value 0.000 N/A All set-ups TRUE -3 Int32
35-45 Term. X48/2 High Ref./Feedb. Value 100.000 N/A All set-ups TRUE -3 Int32
35-46 Term. X48/2 Filter Time Constant 0.001 s All set-ups TRUE -3 Uint16
5 Troubleshooting
5.1.1 Warnings/Alarm Messages If an alarm cannot be reset, the reason may be that its
cause has not been rectified, or the alarm is trip-locked
A warning or an alarm is signaled by the relevant LED on (see also table on following page).
the front of the Adjustable frequency drive and indicated
by a code on the display. Alarms that are trip-locked offer additional protection,
meaning that the line power supply must be switched off
A warning remains active until its cause is no longer
present. Under certain circumstances operation of the
before the alarm can be reset. After being switched back
on, the Adjustable frequency drive is no longer blocked
5 5
motor may still be continued. Warning messages may be and may be reset as described above once the cause has
critical, but are not necessarily so. been rectified.
In the event of an alarm, the Adjustable frequency drive Alarms that are not trip-locked can also be reset using the
will have tripped. Alarms must be reset to restart operation automatic reset function in 14-20 Reset Mode (Warning:
once their cause has been rectified. automatic wake-up is possible!)
This may be done in three ways: If a warning and alarm are marked against a code in the
1. By using the [RESET] control button on the LCP. table on the following page, this means that either a
warning occurs before an alarm, or that you can specify
2. Via a digital input with the “Reset” function.
whether it is a warning or an alarm that is to be displayed
3. Via serial communication/optional serial for a given fault.
communication bus.
Bit Hex Dec Alarm Word Alarm Word 2 Warning Word Warning Extended
Word 2 Status Word
Alarm Word Extended Status Word
0 00000001 1 Brake Check (A28) ServiceTrip, Read/ Brake Check (W28) reserved Ramping
Write
1 00000002 2 Heatsink temp. ServiceTrip, Heatsink temp. (W29) reserved AMA Running
(A29) (reserved)
2 00000004 4 Ground Fault (A14) ServiceTrip, Ground Fault (W14) reserved Start CW/CCW
Typecode/ NOT start_possible
Sparepart start_possible is
active, when the DI
selections [12] OR
[13] are active and
the requested
direction matches the
reference sign.
3 00000008 8 Ctrl.Card Temp ServiceTrip, Ctrl.Card Temp (W65) reserved Slow-down
(A65) (reserved) slow-down command
active, e.g., via CTW
bit 11 or DI
4 00000010 16 Ctrl. Word TO (A17) ServiceTrip, Ctrl. Word TO (W17) Catch Up
(reserved) catch up command
active, e.g., via CTW
bit 12 or DI
5 00000020 32 Overcurrent (A13) reserved Overcurrent (W13) reserved Feedback High
feedback > p4-57
6 00000040 64 Torque Limit (A12) reserved Torque Limit (W12) reserved Feedback Low
feedback < p4-56
7 00000080 128 Motor Th Over reserved Motor Th Over (W11) reserved Output Current High
(A11) current > p4-51
8 00000100 256 Motor ETR Over reserved Motor ETR Over (W10) reserved Output Current Low
(A10) current < p4-50
9 00000200 512 Inverter Overld. reserved Inverter Overld (W9) reserved Output Freq High
(A9) speed > p4-53
10 00000400 1,024 DC under-volt (A8) reserved DC under-volt (W8) Output Freq Low
speed < p4-52
11 00000800 2,048 DC overvoltage reserved DC overvoltage (W7) Brake Check OK
(A7) brake test NOT ok
Bit Hex Dec Alarm Word Alarm Word 2 Warning Word Warning Extended
Word 2 Status Word
12 00001000 4,096 Short Circuit (A16) reserved DC Voltage Low (W6) reserved Braking Max
BrakePower >
BrakePowerLimit
(p212)
13 00002000 8,192 Soft-charge Fault reserved DC Voltage High (W5) Braking
(A33)
14 00004000 16,384 Line Ph. Loss (A4) reserved Line Ph. Loss (W4) Out of Speed Range
15 00008000 32,768 AMA Not OK reserved No Motor (W3) OVC Active
16 00010000 65,536 Live Zero Error (A2) reserved Live Zero Error (W2) AC Brake 5 5
17 00020000 131,072 Internal Fault (A38) KTY error 10 V Low (W1) KTY Warn Password Timelock
number of allowed
password trials
exceeded - timelock
active
18 00040000 262,144 Brake Overload Fans error Brake Overload (W26) Fans Warn Password Protection
(A26) p0-61 =
ALL_NO_ACCESS OR
BUS_NO_ACCESS OR
BUS_READONLY
19 00080000 524,288 U phase Loss (A30) ECB error Brake Resistor (W25) ECB Warn Reference High
reference > p4-55
20 00100000 1,048,576 V phase Loss (A31) reserved Brake IGBT (W27) reserved Reference Low
reference < p4-54
21 00200000 2,097,152 W phase Loss (A32) reserved Speed Limit (W49) reserved Local Reference
reference site =
REMOTE -> auto on
pressed & active
22 00400000 4,194,304 Serial communi- reserved Serial communication bus reserved Protection Mode
cation bus Fault Fault (W34)
(A34)
23 00800000 8,388,608 24 V Supply Low reserved 24 V Supply Low (W47) reserved Unused
(A47)
24 01000000 16,777,216 Line Failure (A36) reserved Line Failure (W36) reserved Unused
25 02000000 33,554,432 1.8 V Supply Low reserved Current Limit (W59) reserved Unused
(A48)
26 04000000 67,108,864 Brake Resistor (A25) reserved Low Temp (W66) reserved Unused
27 08000000 134,217,728 Brake IGBT (A27) reserved Voltage Limit (W64) reserved Unused
28 10,000,000 268,435,456 Option Change reserved Encoder loss (W90) reserved Unused
(A67)
29 20,000,000 536,870,912 Drive Initialized Feedback Fault Feedback Fault (W61, Unused
(A80) (A61, A90) W90)
30 40,000,000 1,073,741,824 Safe Stop (A68) PTC 1 Safe Stop Safe Stop (W68) PTC 1 Safe Unused
(A71) Stop (W71)
31 80,000,000 2,147,483,648 Mech. brake low Dangerous Failure Extended Status Word Unused
(A63) (A72)
Table 5.2 Description of Alarm Word, Warning Word and Extended Status Word
The alarm words, warning words and extended status words can be read out via serial bus or optional serial communication
bus for diagnosis. See also 16-94 Ext. Status Word.
5 5 card.
WARNING/ALARM 2, Live zero error
Increase 14-26 Trip Delay at Inverter Fault
WARNING/ALARM 8, DC undervoltage
This warning or alarm will only appear if programmed by If the intermediate circuit voltage (DC link) drops below
the user in 6-01 Live Zero Timeout Function. The signal on the under voltage limit, the Adjustable frequency drive
one of the analog inputs is less than 50% of the minimum checks if a 24V DC backup supply is connected. If no 24V
value programmed for that input. This condition can be DC backup supply is connected, the Adjustable frequency
caused by broken wiring or faulty device sending the drive trips after a fixed time delay. The time delay varies
signal. with unit size.
Troubleshooting Troubleshooting:
Check connections on all the analog input Check that the supply voltage matches the
terminals. Control card terminals 53 and 54 for Adjustable frequency drive voltage.
signals, terminal 55 common. MCB 101 terminals
Perform input voltage test
11 and 12 for signals, terminal 10 common. MCB
109 terminals 1, 3, 5 for signals, terminals 2, 4, 6 Perform soft charge circuit test
common). WARNING/ALARM 9, Inverter overload
Check that the Adjustable frequency drive The Adjustable frequency drive is about to cut out because
programming and switch settings match the of an overload (too high current for too long). The counter
analog signal type. for electronic, thermal inverter protection gives a warning
at 98% and trips at 100%, while giving an alarm. The
Perform Input Terminal Signal Test.
Adjustable frequency drive cannot be reset until the
WARNING/ALARM 3, No motor counter is below 90%.
No motor has been connected to the output of the The fault is that the Adjustable frequency drive is
Adjustable frequency drive. overloaded by more than 100% for too long.
WARNING/ALARM 4, Mains phase loss Troubleshooting
A phase is missing on the supply side, or the line voltage Compare the output current shown on the LCP
imbalance is too high. This message also appears for a with the Adjustable frequency drive rated current.
fault in the input rectifier on the Adjustable frequency
Compare the output current shown on the LCP
drive. Options are programmed at 14-12 Function at Mains
with measured motor current.
Imbalance.
Display the Thermal Drive Load on the LCP and
Troubleshooting: Check the supply voltage and supply
monitor the value. When running above the
currents to the Adjustable frequency drive.
Adjustable frequency drive continuous current
WARNING 5, DC link voltage high rating, the counter should increase. When
The intermediate circuit voltage (DC) is higher than the running below the Adjustable frequency drive
high voltage warning limit. The limit is dependent on the continuous current rating, the counter should
Adjustable frequency drive voltage rating. The unit is still decrease.
active.
See the derating section in the Design Guide for more
WARNING 6, DC link voltage low details if a high switching frequency is required.
The intermediate circuit voltage (DC) is lower than the low
WARNING/ALARM 10, Motor overload temperature
voltage warning limit. The limit is dependent on the
According to the electronic thermal protection (ETR), the
Adjustable frequency drive voltage rating. The unit is still
motor is too hot. Select whether the Adjustable frequency
active.
drive gives a warning or an alarm when the counter
reaches 100% in 1-90 Motor Thermal Protection. The fault
occurs when the motor is overloaded by more than 100% Check the application for excessive current draw
for too long. on the motor.
Troubleshooting WARNING/ALARM 13, Overcurrent
Check for motor overheating. The inverter peak current limit (approximately 200% of the
rated current) is exceeded. The warning lasts about 1.5
Check if the motor is mechanically overloaded.
secs., then the Adjustable frequency drive trips and issues
Check that the motor current set in 1-24 Motor an alarm. This fault may be caused by shock loading or
Current is correct. fast acceleration with high inertia loads. If extended
Ensure that Motor data in parameters 1-20 mechanical brake control is selected, trip can be reset
through 1-25 are set correctly. externally.
If the generator torque limit is exceeded during 15-61 Option SW Version (for each option slot)
ramp-down, extend the ramp--down time. ALARM 16, Short circuit
If torque limit occurs while running, possibly There is short-circuiting in the motor or motor wiring.
increase the torque limit. Be sure the system can Remove power to the Adjustable frequency drive and
operate safely at a higher torque. repair the short circuit.
WARNING/ALARM 17, Control word timeout Check the sensors on the heatsink and control
There is no communication to the Adjustable frequency card.
drive. WARNING 25, Brake resistor short circuit
The warning will only be active when 8-04 Control Word The brake resistor is monitored during operation. If a short
Timeout Function is NOT set to OFF. circuit occurs, the brake function is disabled and the
If 8-04 Control Word Timeout Function is set to Stop and warning appears. The Adjustable frequency drive is still
Trip, a warning appears and the Adjustable frequency drive operational but without the brake function. Remove power
ramps down until it stops then displays an alarm. to the Adjustable frequency drive and replace the brake
Troubleshooting: resistor (see 2-15 Brake Check).
Check connections on the serial communication
5 5 cable.
WARNING/ALARM 26, Brake resistor power limit
The power transmitted to the brake resistor is calculated as
Increase 8-03 Control Word Timeout Time a mean value over the last 120 seconds of run time. The
calculation is based on the intermediate circuit voltage and
Check the operation of the communication
the brake resistance value set in 2-16 AC brake Max.
equipment.
Current. The warning is active when the dissipated braking
Verify a proper installation based on EMC is higher than 90% of the brake resistance power. If Trip [2]
requirements. is selected in 2-13 Brake Power Monitoring, the Adjustable
WARNING/ALARM 20, Temp. input error frequency drive will trip when the dissipated braking
The temperature sensor is not connected. energy reaches 100%.
WARNING/ALARM 21, Parameter error WARNING/ALARM 27, Brake chopper fault
The parameter is out of range. The parameter number is The brake transistor is monitored during operation and if a
reported in the LCP. The affected parameter must be set to short circuit occurs, the brake function is disabled and a
a valid value. warning is issued. The Adjustable frequency drive is still
operational but, since the brake transistor has short-
WARNING/ALARM 22, Hoist mechanical brake
circuited, substantial power is transmitted to the brake
Report value will show what kind it is. 0 = The torque ref.
resistor, even if it is inactive.
was not reached before timeout. 1 = There was no brake
Remove power to the Adjustable frequency drive and
feedback before timeout.
remove the brake resistor.
WARNING 23, Internal fan fault
WARNING/ALARM 28, Brake check failed
The fan warning function is an extra protective function
The brake resistor is not connected or not working.
that checks if the fan is running/mounted. The fan warning
Check 2-15 Brake Check.
can be disabled in 14-53 Fan Monitor ([0] Disabled).
ALARM 29, Heatsink temp
For the D, E, and F Frame filters, the regulated voltage to
The maximum temperature of the heatsink has been
the fans is monitored.
exceeded. The temperature fault will not reset until the
Troubleshooting: temperature falls below a defined heatsink temperature.
Check for proper fan operation. The trip and reset points are different based on the
Cycle power to the Adjustable frequency drive Adjustable frequency drive power size.
and make sure that the fan operates briefly at Troubleshooting:
start-up. Check for the following conditions.
Check the sensors on the heatsink and control Ambient temperature too high.
card. Motor cable too long.
WARNING 24, External fan fault Incorrect airflow clearance above and below the
The fan warning function is an extra protective function Adjustable frequency drive
that checks if the fan is running/mounted. The fan warning
Blocked airflow around the Adjustable frequency
can be disabled in 14-53 Fan Monitor ([0] Disabled).
drive.
Troubleshooting:
Damaged heatsink fan.
Check for proper fan operation.
Dirty heatsink.
Cycle power to the Adjustable frequency drive
and make sure that the fan operates briefly at ALARM 30, Motor phase U missing
start-up. Motor phase U between the Adjustable frequency drive
and the motor is missing.
Remove power from the Adjustable frequency drive and No. Text
check motor phase U. 1024-1284 Internal fault. Contact your Danfoss supplier or the
ALARM 31, Motor phase V missing Danfoss Service Department.
Motor phase V between the Adjustable frequency drive 1299 Option SW in slot A is too old
and the motor is missing. 1300 Option SW in slot B is too old
1302 Option SW in slot C1 is too old
Remove power from the Adjustable frequency drive and
1315 Option SW in slot A is not supported (not allowed)
check motor phase V.
1316 Option SW in slot B is not supported (not allowed)
ALARM 32, Motor phase W missing 1318 Option SW in slot C1 is not supported (not
Motor phase W between the Adjustable frequency drive allowed)
and the motor is missing. 1379-2819 Internal fault. Contact yourDanfoss supplier or 5 5
Remove power from the Adjustable frequency drive and DanfossService Department.
check motor phase W. 2820 LCP stack overflow
ALARM 43, Ext. supply ALARM 51, AMA check Unom and Inom
MCB 113 Ext. Relay Option is mounted without ext. 24 V The settings for motor voltage, motor current, and motor
DC. Either connect an ext. 24 V DC supply or specify that power are wrong. Check the settings in parameters 1-20 to
no external supply is used via 14-80 Option Supplied by 1-25.
External 24VDC [0]. A change in 14-80 Option Supplied by
ALARM 52, AMA low Inom
External 24VDC requires a power cycle.
The motor current is too low. Check the setting in
ALARM 45, Earth Fault 2 4-18 Current Limit.
Ground fault on start-up.
ALARM 53, AMA motor too big
Troubleshooting The motor is too big for the AMA to operate.
If a 24V DC power supply is used, verify proper WARNING 60, External interlock
supply power. A digital input signal is indicating a fault condition external
to the Adjustable frequency drive. An external interlock has
WARNING 47, 24V supply low commanded the Adjustable frequency drive to trip. Clear
The 24 V DC is measured on the control card. The external the external fault condition. To resume normal operation,
24V DC backup power supply may be overloaded; apply 24V DC to the terminal programmed for external
otherwise, contact your Danfoss supplier. interlock. Reset the Adjustable frequency drive.
WARNING 48, 1.8V supply low WARNING/ALARM 61, Tracking error
The 1.8V DC supply used on the control card is outside of An error between calculated speed and speed
allowable limits. The power supply is measured on the measurement from feedback device. The function Warning/
control card. Check for a defective control card. If an Alarm/Disabling setting is in 4-30 Motor Feedback Loss
option card is present, check for an overvoltage condition. Function. Accepted error setting in 4-31 Motor Feedback
WARNING 49, Speed limit Speed Error and the allowed time the error occur setting in
When the speed is not within the specified range in 4-32 Motor Feedback Loss Timeout. During a commissioning
4-11 Motor Speed Low Limit [RPM] and 4-13 Motor Speed procedure the function may be effective.
High Limit [RPM], the Adjustable frequency drive will show WARNING 62, Output frequency at maximum limit
a warning. When the speed is below the specified limit in The output frequency has reached the value set in
1-86 Trip Speed Low [RPM] (except when starting or 4-19 Max Output Frequency. Check the application to
stopping) the Adjustable frequency drive will trip. determine the cause. Possibly increase the output
ALARM 50, AMA calibration failed frequency limit. Be sure the system can operate safely at a
Contact your Danfoss supplier or Danfoss Service higher output frequency. The warning will clear when the
Department. output drops below the maximum limit.
ALARM 63, Mechanical brake low reset signal must be is be sent (via Bus, Digital I/O, or by
The actual motor current has not exceeded the “release pressing [RESET]).
brake” current within the “Start delay” time window. ALARM 72, Dangerous failure
WARNING/ALARM 65, Control card over temperature Safe Stop with Trip Lock. The dangerous failure alarm is
The cutout temperature of the control card is 176°F [80°C]. issued if the combination of safe stop commands is
unexpected. This is the case if the VLT enables X44/10 but
Troubleshooting
safe stop is somehow not enabled. Furthermore, if the is
• Check that the ambient operating temperature is the only device using safe stop (specified through
within limits.
selection [4] or [5] in 5-19 Terminal 37 Safe Stop), an
• Check for clogged filters. unexpected combination is activation of safe stop without
• Check fan operation. the X44/10 being activated. The following table 5 5
summarizes the unexpected combinations that lead to
• Check the control card.
Alarm 72. Note that if X44/10 is activated in selection 2 or
WARNING 66, Heatsink temperature low 3, this signal is ignored! However, the will still be able to
The Adjustable frequency drive is too cold to operate. This activate Safe Stop.
warning is based on the temperature sensor in the IGBT
WARNING 73, Safe stop auto restart
module.
Safe stopped. Note that with automatic restart enabled,
Increase the ambient temperature of the unit. Also, a
the motor may start when the fault is cleared.
trickle amount of current can be supplied to the
Adjustable frequency drive whenever the motor is stopped ALARM 74, PTC Thermistor
by setting 2-00 DC Hold/Preheat Current at 5% and Alarm related to the ATEX option. The PTC is not working.
1-80 Function at Stop ALARM 75, Illegal profile sel.
ALARM 67, Option module configuration has changed Parameter value must not be written while motor is
One or more options have either been added or removed running. Stop motor before writing MCO profile to
since the last power-down. Check that the configuration 8-10 Control Word Profile for instance.
change is intentional and reset the unit. WARNING 76, Power unit set-up
ALARM 68, Safe stop activated The required number of power units does not match the
Loss of the 24V DC signal on terminal 37 has caused the detected number of active power units.
filter to trip. To resume normal operation, apply 24V DC to Troubleshooting:
terminal 37 and reset the filter. When replacing an F-frame module, this will occur if the
ALARM 69, Power card temperaturePower card power specific data in the module power card does not
temperature match the rest of the Adjustable frequency drive. Please
The temperature sensor on the power card is either too confirm the spare part and its power card are the correct
hot or too cold. part number.
ALARM 79, Illegal power section configuration ALARM 94, End of curve
The scaling card is the incorrect part number or not Feedback is lower than the setpoint. This may indicate
installed. Also MK102 connector on the power card could leakage in the system. 22-50 End of Curve Function is set for
not be installed. alarm. Troubleshoot the system and reset the Adjustable
ALARM 80, Unit initialized to default value frequency drive after the fault has been cleared.
Parameter settings are initialized to default settings after a ALARM 95, Broken belt
manual reset. Reset the unit to clear the alarm. Torque is below the torque level set for no load, indicating
ALARM 81, CSIV corrupt a broken belt. 22-60 Broken Belt Function is set for alarm.
CSIV file has syntax errors. Troubleshoot the system and reset the Adjustable
frequency drive after the fault has been cleared.
5 5 ALARM 82, CSIV par. err.
CSIV failed to init a parameter. ALARM 96, Start delayed
Motor start has been delayed due to short-cycle
ALARM 83, Illegal option combination protection. 22-76 Interval between Starts is enabled.
The mounted options are not supported to work together. Troubleshoot the system and reset the Adjustable
ALARM 84, No safety option frequency drive after the fault has been cleared.
The safety option was removed without applying a general WARNING 97, Stop delayed
reset. Reconnect the safety option. Stopping the motor has been delayed due to short cycle
ALARM 88, Option detection protection. 22-76 Interval between Starts is enabled.
A change in the option layout has been detected. This Troubleshoot the system and reset the Adjustable
alarm occurs when 14-89 Option Detection is set to [0] frequency drive after the fault has been cleared.
Frozen configuration and the option layout for some reason WARNING 98, Clock fault
has changed. An option layout change has to be enabled Time is not set or the RTC clock has failed. Reset the clock
in 14-89 Option Detection before the change is accepted. If in 0-70 Date and Time.
the change of configuration is not accepted, it is only
possible to reset Alarm 88 (Trip-lock) when the option WARNING 163, ATEX ETR cur.lim.warning
configuration has been re-established/corrected. The warning limit of ATEX ETR rated current curve has
been reached. The warning is activated at 83% and de-
WARNING 89, Mechanical brake sliding activated at 65% of the permitted thermal overload.
The hoist brake monitor has detected a motor speed >
10rpm. ALARM 164, ATEX ETR cur.lim.alarm
The ATEX ETR permitted thermal overload has been
ALARM 90, Feedback mon. exceeded.
Check the connection to encoder/ resolver option and
eventually replace the MCB 102 or MCB 103. WARNING 165, ATEX ETR freq.lim.warning
The Adjustable frequency drive is running more than 50
ALARM 91, Analogue input 54 wrong settings sec. below the permitted minimum frequency (1-98 ATEX
Switch S202 has to be set in position OFF (voltage input) ETR interpol. points freq. [0]).
when a KTY sensor is connected to analog input terminal
54. ALARM 166, ATEX ETR freq.lim.alarm
The Adjustable frequency drive has operated more than 60
ALARM 92, No flow sec. (in a period of 600 sec.) below the permitted
A no-flow condition has been detected in the system. minimum frequency (1-98 ATEX ETR interpol. points freq. [0]).
22-23 No-Flow Function is set for alarm. Troubleshoot the
system and reset the Adjustable frequency drive after the ALARM 243, Brake IGBT
fault has been cleared. This alarm is only for F Frame drives. It is equivalent to
Alarm 27. The report value in the alarm log indicates
ALARM 93, Dry pump which power module generated the alarm:
A no-flow condition in the system with the Adjustable
frequency drive operating at high speed may indicate a ALARM 244, Heatsink temperature
dry pump. 22-26 Dry Pump Function is set for alarm. This alarm is only for F Frame adjustable frequency drives.
Troubleshoot the system and reset the Adjustable It is equivalent to Alarm 29. The report value in the alarm
frequency drive after the fault has been cleared. log indicates which power module generated the alarm.
ALARM 245, Heatsink sensor
This alarm is only for F Frame adjustable frequency drives.
It is equivalent to Alarm 39. The report value in the alarm
log indicates which power module generated the alarm.
5 5
Index
E
Electrical Terminals............................................................................. 0-6
A
Abbreviations....................................................................................... 0-1 Encoder Pulses................................................................................... 2-67
B F
Feedback..................................................................................... 4-9, 4-12
Braking
Braking............................................................................................... 4-8 Forward Open................................................................................. 2-107
Energy................................................................................................. 0-3 Freeze Output...................................................................................... 0-2
Break-away Torque............................................................................. 0-2 Fuses........................................................................................................ 4-9
Bus Controlled................................................................................... 2-67
G
C Graphical Display................................................................................ 1-1
Cabling............................................................................................... 2-108
Catch Up.............................................................................................. 2-51
H
Change-Of-State............................................................................. 2-107 Historic Log...................................................................................... 2-137
Changing
A Group Of Numeric Data Values............................................. 1-8
A Text Value...................................................................................... 1-8 I
Data..................................................................................................... 1-8 IGMP.................................................................................................... 2-108
Clockwise............................................................................................. 2-21 Incremental Encoder..................................................................... 2-143
Coasting......................................................................................... 0-2, 1-3 Indexed Parameters........................................................................... 1-9
Communication Option.................................................................... 4-9 Infinitely Variable Change Of Numeric Data Value................. 1-9
Configuration....................................................................... 2-84, 2-106 Initialization........................................................................................... 1-1
Control Cables...................................................................................... 0-7 Input Terminals.................................................................................... 4-6
Cooling................................................................................................. 2-26
Current Rating...................................................................................... 4-6 J
Jog............................................................................................................ 0-2
D
Data Log Settings........................................................................... 2-136 L
DC Link.................................................................................................... 4-6 Language
Package 1.......................................................................................... 2-2
Default Settings................................................................................... 1-1 Package 2.......................................................................................... 2-2
Definitions............................................................................................. 0-2 Package 3.......................................................................................... 2-2
Package 4.......................................................................................... 2-2
Derating.................................................................................................. 4-6
LCP............................................................................................................ 1-1
DeviceNet......................................................................................... 2-101
LEDs................................................................................................. 1-1, 1-2
Digital Input.......................................................................................... 4-7
Line Power Supply.............................................................................. 0-4
Display
Mode................................................................................................... 1-4 Local
Mode - Selection Of Readouts................................................... 1-4 Control Keys..................................................................................... 1-1
Reference........................................................................................... 2-3
Drive Identification........................................................................ 2-139
Reference.......................................................................................... 2-107
M Relay Outputs..................................................................................... 2-54
Main Reset..................................................................................... 4-6, 4-12, 1-3
Menu................................................................................................... 1-5
Menu Mode.............................................................................. 1-2, 1-8
Reactance........................................................................................ 2-16 S
MCB Safety Precautions.............................................................................. 0-4
113.................................................................... 2-54, 2-59, 2-75, 2-76 Serial Communication....................................................................... 0-2
114.................................................................................................. 2-154
Shielded/armored............................................................................... 0-7
Motor
Current.................................................................................... 4-6, 4-10 Speed Up/Down.................................................................................. 0-8
Data.......................................................................................... 4-7, 4-10 Start
Power............................................................................................... 4-10 Delay................................................................................................. 2-21
Protection....................................................................................... 2-24 Function.......................................................................................... 2-21
Status............................................................................................. 2-141
Start/Stop............................................................................................... 0-7
Multicast............................................................................................ 2-108
Stator Leakage Reactance............................................................. 2-16
Status
N Status.................................................................................................. 1-2
Network.................................................................. 2-105, 2-107, 2-108 Messages........................................................................................... 1-1
Numerical Local Control Panel....................................................... 1-9 Step-by-Step......................................................................................... 1-9
Supply Voltage..................................................................................... 4-9
Q W
Quick Warning Word.................................................................................... 2-85
Menu........................................................................................... 1-2, 1-5
Warnings................................................................................................ 4-1
Menu Mode.............................................................................. 1-2, 1-5
Transfer Of Parameter Settings Between Multiple Adjusta-
ble Frequency Drives...... 1-3
R
Rated Motor Speed............................................................................ 0-2
RCD........................................................................................................... 0-3
*MG33MD22*