YHP−ECM High Pressure Fan Coil Units


Technical Guide - for internal distribution only
The Fan Coil Unit CONTENTS
with EC Brushless • YFCN–ECM version
Electronic Motor • Construction Page 4

and Inverter Board



• Models
• Dimensions, Weight, Water content
Page 5
Page 6
• EUROVENT Certification Page 10
YFCN and YHP fan coils combine a beautiful design with • Operation limits Page 13
very interesting performances in terms of sound level and
• Emission tables Page 14
energy consumption.
• Correction factors table Page 24
ECM models are available in five different models, for wall
• Water pressure drop Page 25
and ceiling installation, with casing and concealed.
All Johnson Controls fan coils take part to the Eurovent
program of fan coil performance certification. • YHP–ECM version
• Construction features Page 26
The ECM range makes use of the excellent experience gained • Dimensions, Weight, Water content Page 28
with the Cassette fan coils with inverter board, first in the world • Technical features Page 30
in production since 2009, and which have had great success • Main performance
on all markets. and technical characteristics Page 32
The innovative brushless and sensorless type synchronous • Operation limits Page 33
electronic motor with permanent magnets, is controlled by an • Emission tables Page 34
inverter board. The board is mounted on the unit, closed to the • Correction factors tables Page 40
motor, without the need to be cooled down by the air flow. • Water pressure drop Page 42

The air flow rate can be varied in continuous by means of • YFCN–ECM / YHP–ECM version
a 1-10 V signal generated by JCI controls or by independent
• Accessories Page 44
control systems. The continuous air flow control improves
• ECM configuration Page 59
the acoustic comfort and allows a more punctual reply to the
• Electronic controls Page 60
variation of the thermal loads and a greater stability of the
requested ambient temperature. • Controls and units MB version Page 62
• Management system
The extreme efficiency, also at low speed, for a network of fan coils Page 67
makes possible a great reduction in • PSM-DI and NET electronic boards Page 70
electric consumption (less than 50%
in comparison to YFCN and YHP–O
range motor) with absorption values
under normal operating conditions
that do not exceed 16 Watt for
YFCN−ECM models and do not
exceed 50 Watt for YHP−ECM
models on the entire range. The
excellent values of the YFCN and
YHP range in terms of sound levels
have been maintained in all working
conditions, without any resonance
phenomenon at any frequency.

The full compliance with the Electro-


magnetic Compatibility Directive and with
the other severe Standards in force is certified
by an independent institute.

Johnson Controls take part to the Eurovent program


of fan coil performance certification.
The official figures are published in the web site
www.eurovent-certification.com and in the web site www.certiflash.com.
The tested performances are:
• Cooling total emission at the following conditions: • Cooling sensible emission at the following conditions:
- Water temperature +7°C E.W.T. +12°C L.W.T. - Water temperature +7°C E.W.T. +12°C L.W.T.
The descriptions and illustrations provided in this publication are not binding:
- Entering air temperature +27°C dry bulb +19°C wet bulb - Entering air temperature +27°C dry bulb +19°C wet bulb Johnson Controls reserve the right, whilst maintaining the essential characteristics
• Heating emission (2 pipe units) at the following conditions: • Heating emission (4 pipe units) at the following conditions: of the types described and illustrated, to make, at any time,
- Entering water temperature +50°C - Water temperature +70°C E.W.T. +60°C L.W.T. without the requirement to promptly update this piece of literature,
- Entering air temperature +20°C - Entering air temperature +20°C
- Water flow rate as for the cooling conditions any changes that it considers useful for the purpose
• Fan absorption • Water pressure drop • Sound power of improvement or for any other manufacturing or commercial requirements.
YFCN–ECM version with centrifugal fan
Range includes 5 air flow rates (from 115 to 1395 m3/h)
and 5 models (for wall and ceiling installation, with
casing and concealed), each equipped with 3 or 4
row coil and with the possibility to add a 1 or 2 row
coil for 4 pipe systems.
It is the most comprehensive range, perfect to meet
all air-conditioning requirements of work environments
like offices, shops, restaurants and hotel rooms.

Page 4

YHP–ECM version with high pressure centrifugal fan


Range includes 3 air flow rates (from 350 to 1450 m3/h), each
equipped with 3 or 4 row coil and with the possibility to
add a 1 or 2 row coil for 4 pipe systems.
It is the most comprehensive range, perfect to
meet all air-conditioning requirements of work
environments like offices, shops, restaurants
and hotel rooms featuring ducted installations
with available pressure up to 80 Pa.

Page 26

3
YFCN–ECM
YFCN–ECM version

Construction
Outer casing
Made of strong synthetic lateral corners and from galvanized and pre-painted front steel panel.
The plastic top grid has fixed louvres and is reversible in order to distribute the air in two different directions.
Standard colours:
• Lateral corners and top grid: Pantone 427 C (light grey)
• Frontal panel: RAL 9003 (white)
• Other colours on request.

Inner casing
Made from 1 mm galvanized steel insulated with polyolefin (PO)
foam (class M1).

Filter
Polypropylene cellular fabric regenerating filter.
The filter frame of galvanized steel is inserted into
special plastic sliding guides fastened to the internal
structure for easy insertion and removal of the filter.
Filter presence is highlighted by a plastic front cover
featuring the same colour as the top grid.

Fan assembly
The fans have aluminium or plastic blades directly keyed on the motor with double aspiration and they are dynamically
and statically balanced during manufacture in order to have an extremely quiet operation.

Electronic motor
Three phase permanent magnet brushless electronic motor that is controlled with reconstructed current according to
a BLAC sinusoidal wave. The inverter board that controls the motor operation is powered by 230 Volt, single-phase and,
with a switching system, it generates a three-phase frequency modulated, wave form power supply. The electric power
supply required for the machine is therefore single-phase with voltage of 230-240V and frequency of 50-60Hz.

Coil
It is manufactured from drawn copper tube and the aluminium fins are mechanically bonded onto the tube by an
expansion process. The coil has two 1/2inch BSP internal connections and 1/8 inch BSP air vent and drain.
The coil is not suitable for use in corrosive atmosphere or in environments where aluminium may be subject to
corrosion.
The connections are on the left hand side facing the unit. On request we can deliver the unit with the
connections on the right end side. This operation can also be easily carried out on site during installation.

Condensate collection tray


Made of plastic (ABS UL94 HB) with
a "L-shaped" plastic fitted on the inner casing;
in the HC, VCB and CD model the tray
is insulated with polyolefin (PO) foam (class M1).
The outside diameter
of the condensate discharge pipe is 15mm.

Accessories and Controls


See page 44 and 60.

4
YFCN–ECM
YFCN–ECM version

Models

VC VC
Vertical Casing – Wall Installation Vertical Casing – Ceiling Installation

NOTE: the VC model can also be installed horizontally

100 (min.)
leaving behind a 100 mm gap for air intake.

100

VCB HC
Vertical Casing – Floor Installation Horizontal Casing

CD CD
Vertical Concealed Horizontal Concealed
100 (min.)

5
YFCN–ECM
YFCN–ECM version

Dimension, Weight, Water content

VC
Coil connections on the left B

A 170 158 C 158

133
530
630

100 71 44 125
100

55 55
A

Feet (optional)

HC - VCB
B

A 170 158 C 158


133
530

71 44 125

55 55

COIL CONNECTIONS
3 or 4 row coils Heating additional coil (1 or 2 rows)
Ø 1/2" F WATER OUTLET

T T
WATER INLET WATER INLET
WATER OUTLET SEE DRAWING

Ø 1/2" F
Ø 15 ext.
Ø 15 ext.
S
O

321

230
230
N

37 R

M P

H H
B B

6
YFCN–ECM
YFCN–ECM version

Dimension, Weight, Water content

PACKAGING

600

Dimension (mm)

Model 2 4 6 7 9
A 770 985 1200 1415 1415
B 225 225 225 225 255
C 454 669 884 1099 1099
H 205 205 205 205 235
M 145 145 145 145 170
N 260 260 260 260 270
O 460 460 460 460 450
P 185 185 185 185 210
R 105 105 105 105 110
S 475 475 475 475 465
T 55 55 55 55 85
V 260 260 260 260 290
Z 820 1035 1250 1465 1465

Weight (kg)

Weight with packaging Weight without packaging


Model 2 4 6 7 9 2 4 6 7 9
3 17,2 22,5 27,7 32,1 35,9 15,4 20,2 24,9 28,8 32,2
3+1 18,0 23,7 29,2 33,9 37,7 16,2 21,4 26,4 30,6 34,0
Rows

3+2 18,6 24,4 30,1 35,0 38,8 16,8 22,1 27,3 31,7 35,1
4 18,0 23,5 29,0 33,6 37,4 16,2 21,2 26,2 30,3 33,7
4+1 18,8 24,7 30,5 35,4 39,2 17,0 22,4 27,7 32,1 35,5

Water content (litres)

Model 2 4 6 7 9
3 0,6 0,9 1,6 1,7 1,9
Rows

4 0,8 1,3 2,2 2,4 2,8


+1 0,2 0,3 0,5 0,5 0,6
+2 0,4 0,6 1,0 1,0 1,2

7
YFCN–ECM
YFCN–ECM version

Dimension, Weight, Water content

CD Vertical Installation
Coil connections on the left
D G 10 F
22 22

Ø 15 ext.

133
511

71 44 125
230
12 12
100 29 H

D
119*

153

E*
* Supply frame dimension = E x 119 mm
17

12 12

Auxiliary condensate tray (optional)


CD Horizontal Installation
D
119*

H
153

E*
17

12 12
230 Ø 15 ext.
125 44 71
133

150 F 10
* Supply frame dimension = E x 119 mm
COIL CONNECTIONS
3 or 4 row coils Heating additional coil (1 or 2 rows)
Ø 1/2" F WATER OUTLET

U U
WATER INLET WATER INLET
WATER OUTLET

Ø 1/2" F
Ø 15 ext.
Ø 15 ext.
S
O

321

230
230
N

37 R

M P

H H
G G

8
YFCN–ECM
YFCN–ECM version

Dimension, Weight, Water content

PACKAGING

600

Dimension (mm)

Model 2 4 6 7 9
D 474 689 904 1119 1119
E 430 645 860 1075 1075
F 454 669 884 1099 1099
G 218 218 218 218 248
H 205 205 205 205 235
M 145 145 145 145 170
N 260 260 260 260 270
O 460 460 460 460 450
P 185 185 185 185 210
R 105 105 105 105 110
S 475 475 475 475 465
U 65 65 65 65 95
X 260 260 260 260 290
Y 820 820 1035 1250 1250

Weight (kg)

Weight with packaging Weight without packaging


Model 2 4 6 7 9 2 4 6 7 9
3 13,6 18,1 22,8 27,0 30,4 11,8 16,3 20,5 24,2 27,3
3+1 14,4 19,3 24,3 28,8 32,2 12,6 17,5 22,0 26,0 29,1
Rows

3+2 15,0 20,0 25,2 29,9 33,3 13,2 18,2 22,9 27,1 30,2
4 14,4 19,1 24,1 28,5 31,9 12,6 17,3 21,8 25,7 28,8
4+1 15,2 20,3 25,6 30,3 33,7 13,4 18,5 23,3 27,5 30,6

Water content (litres)

Model 2 4 6 7 9
3 0,6 0,9 1,6 1,7 1,9
Rows

4 0,8 1,3 2,2 2,4 2,8


+1 0,2 0,3 0,5 0,5 0,6
+2 0,4 0,6 1,0 1,0 1,2

9
YFCN–ECM
YFCN–ECM version

EUROVENT Certification www.eurovent-certification.com


www.certiflash.com

YFCN−ECM units with 3 row coil

2 pipe units.

The following standard rating conditions are used:

COOLING HEATING
Entering air temperature + 27°C d.b. + 19°C w.b. Entering air temperature + 20°C
Water temperature + 7°C E.W.T. + 12°C L.W.T. Entering water temperature + 50°C
Water flow rate as for the cooling conditions

Model YFCN−ECM 230 YFCN−ECM 430 YFCN−ECM 630


Inverter power 1 (E) 3 5 (E) 7,5 10 (E) 1 (E) 3 5 (E) 7,5 10 (E) 1 (E) 3 5 (E) 7,5 10 (E)
Speed MIN MED MAX MIN MED MAX MIN MED MAX
Air flow m /h
3
120 170 220 270 330 210 280 350 430 515 305 395 495 610 735
Cooling total emission (E) kW 0,74 0,98 1,19 1,39 1,61 1,42 1,80 2,19 2,58 2,97 1,97 2,45 2,94 3,46 3,99
Cooling sensible emission (E) kW 0,56 0,75 0,93 1,10 1,30 1,04 1,34 1,65 1,96 2,28 1,47 1,84 2,23 2,67 3,11
Heating (E) kW 0,92 1,24 1,53 1,81 2,13 1,70 2,20 2,70 3,21 3,74 2,35 2,96 3,59 4,25 4,95
Dp Cooling (E) kPa 2,2 3,7 5,0 6,6 8,6 7,9 12,0 17,0 22,6 28,9 5,5 8,0 11,1 14,8 19,0
Dp Heating (E) kPa 2,0 3,6 5,0 6,5 8,3 6,6 9,9 13,8 18,2 23,9 4,5 6,7 9,2 12,1 15,7
Fan (E) W 7,0 9,0 11,0 14,5 21,0 6,0 9,0 12,0 17,0 25,0 7,0 10,0 15,0 22,0 32,0
Sound power (E) Lw dB(A) 30 36 41 47 51 30 36 42 47 51 33 38 44 49 54
Sound pressure (*) Lp dB(A) 21 27 32 38 42 21 27 33 38 42 24 29 35 40 45

Model YFCN−ECM 730 YFCN−ECM 930


Inverter power 1 (E) 3 5 (E) 7,5 10 (E) 1 (E) 3 5 (E) 7,5 10 (E)
Speed MIN MED MAX MIN MED MAX
Air flow m3/h 400 500 610 755 890 605 785 945 1175 1395
Cooling total emission (E) kW 2,61 3,14 3,70 4,39 4,98 3,47 4,25 4,86 5,67 6,36
Cooling sensible emission (E) kW 1,93 2,35 2,79 3,35 3,84 2,65 3,31 3,83 4,56 5,20
Heating (E) kW 3,08 3,76 4,47 5,32 6,09 4,45 5,53 6,41 7,62 8,69
Dp Cooling (E) kPa 10,5 14,5 19,4 26,1 32,6 8,9 12,7 16,1 21,1 25,9
Dp Heating (E) kPa 8,4 11,9 16,1 21,5 26,8 7,7 11,0 13,9 18,3 22,5
Fan (E) W 9,0 13 18,5 28,5 41,0 16,0 25,0 41,0 65,0 99,0
Sound power (E) Lw dB(A) 37 43 48 53 57 44 50 55 60 64
Sound pressure (*) Lp dB(A) 28 34 39 44 48 35 41 46 51 55

(E) = Eurovent certified performance.


(*) = The sound pressure levels are 9 dB(A) lower than the sound power levels
and apply to the reverberant field of a 100 m3 room and a reverberation time of 0.5 sec.

10
YFCN–ECM
YFCN–ECM version

EUROVENT Certification www.eurovent-certification.com


www.certiflash.com

YFCN−ECM units with 4 row coil

2 pipe units.

The following standard rating conditions are used:

COOLING HEATING
Entering air temperature + 27°C d.b. + 19°C w.b. Entering air temperature + 20°C
Water temperature + 7°C E.W.T. + 12°C L.W.T. Entering water temperature + 50°C
Water flow rate as for the cooling conditions

Model YFCN−ECM 240 YFCN−ECM 440 YFCN−ECM 640


Inverter power 1 (E) 3 5 (E) 7,5 10 (E) 1 (E) 3 5 (E) 7,5 10 (E) 1 (E) 3 5 (E) 7,5 10 (E)
Speed MIN MED MAX MIN MED MAX MIN MED MAX
Air flow m /h
3
115 160 210 260 325 200 265 340 415 505 290 375 475 590 720
Cooling total emission (E) kW 0,78 1,07 1,33 1,59 1,88 1,44 1,84 2,28 2,73 3,19 2,06 2,61 3,20 3,86 4,54
Cooling sensible emission (E) kW 0,57 0,79 0,99 1,20 1,44 1,04 1,35 1,68 2,04 2,41 1,49 1,90 2,35 2,86 3,41
Heating (E) kW 0,94 1,30 1,63 1,98 2,37 1,70 2,19 2,75 3,31 3,91 2,43 3,12 3,87 4,71 5,60
Dp Cooling (E) kPa 3,2 5,5 8,0 11,0 14,8 4,0 6,1 8,9 12,2 16,1 8,2 12,4 17,8 24,8 33,0
Dp Heating (E) kPa 2,6 4,6 6,5 9,1 12,6 3,0 4,8 7,2 10,0 13,5 6,5 10,2 14,9 20,4 26,9
Fan (E) W 7,0 9,0 11,0 14,5 21,0 6,0 9,0 12,0 17,0 25,0 7,0 10,0 15,0 22,0 32,0
Sound power (E) Lw dB(A) 30 36 41 47 51 30 36 42 47 51 33 38 44 49 54
Sound pressure (*) Lp dB(A) 21 27 32 38 42 21 27 33 38 42 24 29 35 40 45

Model YFCN−ECM 740 YFCN−ECM 940


Inverter power 1 (E) 3 5 (E) 7,5 10 (E) 1 (E) 3 5 (E) 7,5 10 (E)
Speed MIN MED MAX MIN MED MAX
Air flow m3/h 380 475 585 735 875 575 755 910 1145 1365
Cooling total emission (E) kW 2,62 3,21 3,84 4,64 5,34 3,61 4,52 5,25 6,25 7,14
Cooling sensible emission (E) kW 1,91 2,36 2,84 3,47 4,03 2,71 3,43 4,03 4,87 5,63
Heating (E) kW 3,09 3,82 4,61 5,61 6,51 4,50 5,73 6,70 8,12 9,39
Dp Cooling (E) kPa 7,3 10,5 14,3 20,0 25,6 6,3 9,3 12,1 16,5 20,8
Dp Heating (E) kPa 6,0 8,5 11,8 16,7 21,0 5,2 7,7 9,9 13,5 17,0
Fan (E) W 9,0 13,0 18,5 28,5 41,0 16,0 25,0 41,0 65,0 99,0
Sound power (E) Lw dB(A) 37 43 48 53 57 44 50 55 60 64
Sound pressure (*) Lp dB(A) 28 34 39 44 48 35 41 46 51 55

(E) = Eurovent certified performance.


(*) = The sound pressure levels are 9 dB(A) lower than the sound power levels
and apply to the reverberant field of a 100 m3 room and a reverberation time of 0.5 sec.

11
YFCN–ECM
YFCN–ECM version

EUROVENT Certification www.eurovent-certification.com


www.certiflash.com

YFCN−ECM units with 1 row additional coil

4 pipe units.

The following standard rating conditions are used:

COOLING HEATING
Entering air temperature + 27°C d.b. + 19°C w.b. Entering air temperature + 20°C
Water temperature + 7°C E.W.T. + 12°C L.W.T. Water temperature + 70°C E.W.T. + 60°C L.W.T.

Model YFCN−ECM 230+1 YFCN−ECM 430+1 YFCN−ECM 630+1


Inverter power 1 (E) 3 5 (E) 7,5 10 (E) 1 (E) 3 5 (E) 7,5 10 (E) 1 (E) 3 5 (E) 7,5 10 (E)
Speed MIN MED MAX MIN MED MAX MIN MED MAX
Air flow m /h
3
120 170 220 270 330 210 280 350 430 515 305 395 495 610 735
Cooling total emission (E) kW 0,74 0,98 1,19 1,39 1,61 1,42 1,80 2,19 2,58 2,97 1,97 2,45 2,94 3,46 3,99
Cooling sensible emission (E) kW 0,56 0,75 0,93 1,10 1,30 1,04 1,34 1,65 1,96 2,28 1,47 1,84 2,23 2,67 3,11
Heating (E) kW 0,81 1,04 1,23 1,42 1,63 1,47 1,79 2,11 2,42 2,74 2,00 2,40 2,80 3,24 3,68
Dp Cooling (E) kPa 1,8 2,9 4,0 5,3 6,9 7,9 12,0 17,0 22,6 28,9 5,5 8,0 11,1 14,8 19,0
Dp Heating (E) kPa 1,3 1,9 2,6 3,4 4,3 4,5 6,4 8,5 10,9 13,6 1,5 2,1 2,8 3,6 4,5
Fan (E) W 7,0 9,0 11,0 14,5 21,0 6,0 9,0 12,0 17,0 25,0 7,0 10,0 15,0 22,0 32,0
Sound power (E) Lw dB(A) 30 36 41 47 51 30 36 42 47 51 33 38 44 49 54
Sound pressure (*) Lp dB(A) 21 27 32 38 42 21 27 33 38 42 24 29 35 40 45

Model YFCN−ECM 730+1 YFCN−ECM 930+1


Inverter power 1 (E) 3 5 (E) 7,5 10 (E) 1 (E) 3 5 (E) 7,5 10 (E)
Speed MIN MED MAX MIN MED MAX
Air flow m /h
3 400 500 610 755 890 605 785 945 1175 1395
Cooling total emission (E) kW 2,61 3,14 3,70 4,39 4,98 3,47 4,25 4,86 5,67 6,36
Cooling sensible emission (E) kW 1,93 2,35 2,79 3,35 3,84 2,65 3,31 3,83 4,56 5,20
Heating (E) kW 2,65 3,10 3,56 4,13 4,63 3,40 4,08 4,62 5,35 5,98
Dp Cooling (E) kPa 10,5 14,5 19,4 26,1 32,6 8,9 12,7 16,1 21,1 25,9
Dp Heating (E) kPa 2,9 3,9 4,9 6,4 7,8 4,6 6,3 7,8 10,1 12,3
Fan (E) W 9,0 13,0 18,5 28,5 41,0 16,0 25,0 41,0 65,0 99,0
Sound power (E) Lw dB(A) 37 43 48 53 57 44 50 55 60 64
Sound pressure (*) Lp dB(A) 28 34 39 44 48 35 41 46 51 55

(E) = Eurovent certified performance.


(*) = The sound pressure levels are 9 dB(A) lower than the sound power levels
and apply to the reverberant field of a 100 m3 room and a reverberation time of 0.5 sec.

12
YFCN–ECM
YFCN–ECM version

Operation limits
Highest water inlet temperature............................... + 85 °C
Lowest water inlet temperature................................ + 5 °C
for entering water temperatures below + 5°C, contact “YORK” technical department
Highest working pressure........................................ 1000 kPa (10 bars)

Note: For HC model the maximum installation height is 2,8 m.


On heating it must be payed attention to rooms where the floor temperature
is particularly low (for example less than 5°C).
In this situation the floor can cool the lower layer of air to a level that can stop
the uniform diffusion of the hot air coming from the unit.

Water flow limits for 3 row coil (l/h)

Model YFCN−ECM 230 YFCN−ECM 430 YFCN−ECM 630 YFCN−ECM 730 YFCN−ECM 930
Lowest 100 100 150 150 200
Highest 500 750 1000 1500 2000

Water flow limits for 4 row coil (l/h)

Model YFCN−ECM 240 YFCN−ECM 440 YFCN−ECM 640 YFCN−ECM 740 YFCN−ECM 940
Lowest 100 150 150 200 300
Highest 750 1000 1500 2000 2250

Water flow limits for 1 row additional coil (l/h)

Model YFCN−ECM 2 YFCN−ECM 4 YFCN−ECM 6 YFCN−ECM 7 YFCN−ECM 9


Lowest 50 50 100 100 100
Highest 250 350 500 650 750

Water flow limits for 2 row additional coil (l/h)

Model YFCN−ECM 2 YFCN−ECM 4 YFCN−ECM 6 YFCN−ECM 7 YFCN−ECM 9


Lowest 50 100 100 100 100
Highest 250 350 500 650 750

Motor electrical data (max. absorption)

Model YFCN−ECM 2 YFCN−ECM 4 YFCN−ECM 6 YFCN−ECM 7 YFCN−ECM 9


230/1 W 21,0 25,0 32,0 41,0 99,0
50Hz A 0,18 0,22 0,28 0,34 0,81

13
YFCN–ECM
YFCN–ECM version

Cooling emission of 3 row coil


Entering air temperature: 27°C – R.H.: 50%

WT: 7/12 °C WT: 8/13 °C WT: 10/15 °C WT: 12/17 °C


Model Vdc
Qv Pc Ps Qw Dp(c) Pc Ps Qw Dp(c) Pc Ps Qw Dp(c) Pc Ps Qw Dp(c)
ECM m3/h kW kW l/h kPa kW kW l/h kPa kW kW l/h kPa kW kW l/h kPa
10 330 1,74 1,29 299 7,9 1,55 1,21 266 6,4 1,14 1,06 196 3,7 0,92 0,92 159 2,5
7,5
YFCN 270 1,50 1,10 258 6,1 1,34 1,03 230 4,9 0,99 0,90 171 2,9 0,79 0,79 135 1,9

230
5 220 1,28 0,92 220 4,6 1,14 0,87 196 3,7 0,85 0,75 147 2,2 0,67 0,67 115 1,4
3 170 1,05 0,75 181 3,3 0,94 0,70 162 2,7 0,71 0,61 121 1,6 0,54 0,54 93 1,0
1 120 0,80 0,56 137 2,0 0,72 0,52 123 1,6 0,54 0,46 93 1,0 0,40 0,40 69 0,6
10 515 3,20 2,27 550 32,9 2,86 2,14 493 27 2,17 1,87 373 16,3 1,65 1,65 283 9,9
7,5
YFCN 430 2,78 1,96 478 25,8 2,49 1,84 429 21,2 1,89 1,60 326 12,8 1,42 1,42 243 7,6

430
5 350 2,36 1,64 406 19,3 2,12 1,55 365 15,9 1,62 1,35 278 9,7 1,19 1,19 204 5,6
3 280 1,94 1,34 334 13,7 1,75 1,26 300 11,3 1,33 1,09 229 6,9 0,97 0,97 167 3,9
1 210 1,52 1,04 262 8,9 1,37 0,98 236 7,4 1,05 0,85 181 4,6 0,75 0,75 129 2,5
10 735 4,29 3,10 738 21,6 3,84 2,92 661 17,6 2,89 2,55 498 10,6 2,25 2,25 386 6,7
7,5 610 3,73
YFCN 2,66 641 16,8 3,34 2,50 574 13,8 2,52 2,18 434 8,3 1,92 1,92 331 5,1

630
5 495 3,16 2,23 544 12,6 2,84 2,09 488 10,3 2,15 1,83 370 6,3 1,61 1,61 277 3,7
3 395 2,63 1,84 453 9,1 2,37 1,72 407 7,5 1,80 1,50 310 4,6 1,33 1,33 229 2,7
1 305 2,12 1,46 365 6,3 1,91 1,38 329 5,2 1,46 1,20 251 3,2 1,06 1,06 182 1,8
10 890 5,36 3,83 921 37,1 4,08 3,60 702 30,4 3,65 3,15 627 18,5 2,78 2,78 478 11,3
7,5 755 4,72 3,34
YFCN 812 29,7 4,24 3,14 729 24,4 3,22 2,74 555 14,9 2,42 2,42 416 8,8

730
5 610 3,98 2,78 684 22 3,58 2,62 615 18,1 2,73 2,28 470 11,1 2,01 2,01 346 6,4
3 500 3,38 2,34 581 16,5 3,04 2,20 523 13,6 2,33 1,92 400 8,4 1,70 1,70 292 4,8
1 400 2,80 1,92 482 11,9 2,52 1,81 434 9,8 1,94 1,57 333 6,1 1,39 1,39 240 3,4
10 1395 6,86 5,16 1180 25,4 6,11 4,86 1051 20,6 4,53 4,27 780 12 3,73 3,73 642 8,4
7,5 1175 6,11 4,53 1051 20,7 6,7
YFCN 5,45 4,27 938 16,8 4,06 3,74 698 9,9 3,27 3,27 563

930
5 945 5,23 3,81 900 15,8 4,68 3,59 804 12,8 3,50 3,14 602 7,6 2,75 2,75 474 4,9
3 785 4,58 3,29 787 12,4 4,09 3,10 704 10,2 3,08 2,71 529 6,1 2,38 2,38 409 3,8
1 605 3,73 2,65 642 8,7 3,34 2,49 575 7,1 2,52 2,17 434 4,3 1,92 1,92 330 2,6

Legend
Correction factors for different R.H. WT = Water temperature
Pc = Cooling total emission
R.H. WT: 7/12°C 8/13°C 10/15°C 12/17°C Ps = Cooling sensible emission
Pc 0,95 0,94 1,00 1,00 Qw = Water flow
48% Ps 1,00 1,00 1,00 1,00 Dp(c) = Water pressure drop
Pc 0,90 0,88 1,00 1,00 Vdc = Inverter Power
46% Ps 1,00 1,00 1,00 1,00 Qv = Air flow

14
YFCN–ECM
YFCN–ECM version

Cooling emission of 3 row coil


Entering air temperature: 26°C – R.H.: 50%

WT: 7/12 °C WT: 8/13 °C WT: 10/15 °C WT: 12/17 °C


Model Vdc
Qv Pc Ps Qw Dp(c) Pc Ps Qw Dp(c) Pc Ps Qw Dp(c) Pc Ps Qw Dp(c)
ECM m3/h kW kW l/h kPa kW kW l/h kPa kW kW l/h kPa kW kW l/h kPa
10 330 1,54 1,21 265 6,4 1,35 1,14 232 5,0 1,01 1,01 173 3,0 0,84 0,84 145 2,1
7,5
YFCN 270 1,33 1,03 229 4,9 1,17 0,97 201 3,9 0,86 0,86 147 2,2 0,72 0,72 123 1,6

230
5 220 1,14 0,87 195 3,7 1,00 0,81 172 3,0 0,70 0,70 121 1,6 0,61 0,61 105 1,2
3 170 0,94 0,70 161 2,7 0,82 0,66 142 2,1 0,58 0,56 100 1,1 0,49 0,49 85 0,8
1 120 0,71 0,53 122 1,6 0,63 0,49 108 1,3 0,45 0,42 77 0,7 0,37 0,37 63 0,5
10 515 2,85 2,14 490 26,9 2,52 2,01 433 21,5 1,81 1,73 311 11,8 1,51 1,51 259 8,5
7,5
YFCN 430 2,48 1,84 426 21,1 2,19 1,73 377 16,9 1,58 1,49 272 9,4 1,30 1,30 223 6,5

430
5 350 2,11 1,55 362 15,8 1,88 1,45 323 12,7 1,36 1,25 233 7,1 1,09 1,09 187 4,8
3 280 1,73 1,26 298 11,2 1,54 1,18 265 9,0 1,12 1,01 193 5,1 0,89 0,89 153 3,3
1 210 1,36 0,98 234 7,3 1,21 0,92 208 5,9 0,89 0,79 153 3,4 0,69 0,69 118 2,1
10 735 3,82 2,92 658 17,6 3,37 2,74 580 14 2,40 2,36 413 7,6 2,05 2,05 353 5,7
7,5 610 3,32
YFCN 2,50 571 13,7 2,93 2,35 504 11 2,10 2,02 361 6,0 1,76 1,76 302 4,3

630
5 495 2,82 2,10 485 10,3 2,49 1,96 429 8,2 1,80 1,69 309 4,6 1,47 1,47 253 3,2
3 395 2,35 1,73 404 7,5 2,08 1,62 358 6,0 1,51 1,39 260 3,4 1,22 1,22 209 2,3
1 305 1,90 1,38 326 5,1 1,68 1,29 289 4,1 1,23 1,11 211 2,3 0,97 0,97 167 1,5
10 890 4,78 3,61 822 30,4 4,23 3,38 727 24,3 3,04 2,92 523 13,4 2,54 2,54 437 9,7
7,5 755 4,22 3,15
YFCN 725 24,3 3,73 2,95 642 19,5 2,70 2,54 464 10,9 2,21 2,21 381 7,6

730
5 610 3,56 2,62 611 18 3,15 2,55 542 14,5 2,29 2,12 394 8,2 1,84 1,84 317 5,5
3 500 3,02 2,21 520 13,6 2,68 2,07 462 10,9 1,96 1,78 337 6,2 1,56 1,56 268 4,1
1 400 2,51 1,81 431 9,8 2,23 1,70 383 7,9 1,64 1,46 281 4,5 1,28 1,28 220 2,9
10 1395 6,09 4,87 1048 20,6 5,35 4,57 920 16,3 4,06 4,06 699 9,9 3,40 3,40 585 7,1
7,5 1175 5,43 4,27 934 5,7
YFCN 16,8 4,77 4,01 821 13,3 3,56 3,56 613 7,8 2,99 2,99 513

930
5 945 4,66 3,60 801 12,8 4,10 3,37 705 10,2 3,00 3,00 515 5,8 2,51 2,51 432 4,2
3 785 4,07 3,10 700 10,1 3,59 2,91 617 8,1 2,55 2,50 438 4,3 2,17 2,17 373 3,2
1 605 3,33 2,49 572 7,1 2,94 2,33 505 5,7 2,10 2,01 361 3,1 1,75 1,75 302 2,2

Legend
Correction factors for different R.H. WT = Water temperature
Pc = Cooling total emission
R.H. WT: 7/12°C 8/13°C 10/15°C 12/17°C Ps = Cooling sensible emission
Pc 0,95 0,94 1,00 1,00 Qw = Water flow
48% Ps 1,00 1,00 1,00 1,00 Dp(c) = Water pressure drop
Pc 0,90 0,88 1,00 1,00 Vdc = Inverter Power
46% Ps 1,00 1,00 1,00 1,00 Qv = Air flow

15
YFCN–ECM
YFCN–ECM version

Cooling emission of 3 row coil


Entering air temperature: 25°C – R.H.: 50%

WT: 7/12 °C WT: 8/13 °C WT: 10/15 °C WT: 12/17 °C


Model Vdc
Qv Pc Ps Qw Dp(c) Pc Ps Qw Dp(c) Pc Ps Qw Dp(c) Pc Ps Qw Dp(c)
ECM m3/h kW kW l/h kPa kW kW l/h kPa kW kW l/h kPa kW kW l/h kPa
10 330 1,35 1,14 232 5,0 1,15 1,06 198 3,8 0,93 0,92 159 2,5 0,76 0,76 131 1,8
7,5
YFCN 270 1,17 0,97 200 3,9 1,00 0,90 172 3,0 0,79 0,79 135 1,9 0,65 0,65 111 1,3

230
5 220 1,00 0,81 171 3,0 0,86 0,76 147 2,3 0,67 0,67 115 1,4 0,55 0,55 94 1,0
3 170 0,82 0,66 141 2,1 0,71 0,61 122 1,6 0,54 0,54 93 1,0 0,45 0,45 77 0,7
1 120 0,63 0,49 108 1,3 0,54 0,46 93 1,0 0,40 0,40 69 0,6 0,33 0,33 57 0,4
10 515 2,51 2,01 432 21,6 2,18 1,87 375 16,7 1,65 1,65 284 10,1 1,36 1,36 235 7,1
7,5
YFCN 430 2,19 1,73 376 16,9 1,90 1,61 327 13,1 1,42 1,42 244 7,7 1,17 1,17 202 5,5

430
5 350 1,86 1,45 320 12,7 1,62 1,35 278 9,9 1,19 1,19 205 5,7 0,99 0,99 170 4,0
3 280 1,53 1,18 264 9,0 1,34 1,10 230 7,1 0,97 0,97 168 4,0 0,81 0,81 139 2,8
1 210 1,21 0,92 207 5,9 1,05 0,85 181 4,6 0,75 0,75 130 2,5 0,63 0,63 108 1,8
10 735 3,37 2,74 579 14,1 2,91 2,56 501 10,8 2,25 2,25 387 6,8 1,86 1,86 319 4,8
7,5 610 2,93
YFCN 2,35 503 11 2,54 2,19 436 8,5 1,93 1,93 331 5,2 1,59 1,59 274 3,6

630
5 495 2,49 1,97 428 8,3 2,16 1,83 371 6,4 1,61 1,61 277 3,8 1,33 1,33 229 2,7
3 395 2,08 1,62 357 6,0 1,81 1,51 310 4,7 1,34 1,34 230 2,7 1,11 1,11 190 1,9
1 305 1,68 1,29 288 4,1 1,46 1,20 251 3,2 1,06 1,06 183 1,8 0,88 0,88 151 1,3
10 890 4,22 3,39 726 24,4 3,67 3,16 631 18,9 2,78 2,78 479 11,5 2,30 2,30 396 8,1
7,5 755 3,72 2,96
YFCN 640 19,6 3,24 2,76 557 15,2 2,43 2,43 417 9,0 2,01 2,01 345 6,4

730
5 610 3,14 2,46 541 14,5 2,74 2,29 471 11,3 2,02 2,02 347 6,5 1,67 1,67 287 4,6
3 500 2,67 2,07 460 10,9 2,33 1,93 401 8,5 1,71 1,71 293 4,9 1,41 1,41 243 3,4
1 400 2,22 1,70 382 7,9 1,94 1,58 334 6,2 1,34 1,40 230 3,4 1,16 1,16 200 2,4
10 1395 5,35 4,58 920 16,4 4,59 4,28 789 12,4 3,73 3,73 642 8,5 3,07 3,07 528 6,0
7,5 1175 4,77 4,01 820 4,7
YFCN 13,4 4,10 3,74 706 10,2 3,28 3,28 563 6,8 2,70 2,70 464

930
5 945 4,09 3,37 703 10,2 3,53 3,15 607 7,8 2,76 2,76 474 5,0 2,27 2,27 391 3,5
3 785 3,58 2,91 616 8,1 3,09 2,71 532 6,2 2,38 2,38 409 3,9 1,96 1,96 337 2,7
1 605 2,93 2,34 503 5,7 2,54 2,18 436 4,4 1,92 1,92 331 2,6 1,59 1,59 273 1,9

Legend
Correction factors for different R.H. WT = Water temperature
Pc = Cooling total emission
R.H. WT: 7/12°C 8/13°C 10/15°C 12/17°C Ps = Cooling sensible emission
Pc 0,95 0,94 1,00 1,00 Qw = Water flow
48% Ps 1,00 1,00 1,00 1,00 Dp(c) = Water pressure drop
Pc 0,90 0,88 1,00 1,00 Vdc = Inverter Power
46% Ps 1,00 1,00 1,00 1,00 Qv = Air flow

16
YFCN–ECM
YFCN–ECM version

Cooling emission of 4 row coil


Entering air temperature: 27°C – R.H.: 50%

WT: 7/12 °C WT: 8/13 °C WT: 10/15 °C WT: 12/17 °C


Model Vdc
Qv Pc Ps Qw Dp(c) Pc Ps Qw Dp(c) Pc Ps Qw Dp(c) Pc Ps Qw Dp(c)
ECM m3/h kW kW l/h kPa kW kW l/h kPa kW kW l/h kPa kW kW l/h kPa
10 325 2,02 1,44 348 16,9 1,81 1,35 312 13,8 1,37 1,18 235 8,3 1,04 1,04 179 5,0
7,5
YFCN 260 1,71 1,20 294 12,5 1,53 1,13 264 10,3 1,16 0,98 200 6,2 0,87 0,87 149 3,7

240
5 210 1,43 0,99 245 9,1 1,28 0,93 220 7,5 0,97 0,81 168 4,6 0,72 0,72 123 2,6
3 160 1,15 0,79 197 6,2 1,03 0,74 178 5,1 0,79 0,65 136 3,1 0,57 0,57 98 1,8
1 115 0,84 0,57 145 3,6 0,76 0,54 131 3,0 0,58 0,47 100 1,9 0,41 0,41 71 1,0
10 505 3,44 2,40 592 18,5 3,09 2,26 531 15,2 2,34 1,96 403 9,2 1,74 1,74 299 5,4
7,5
YFCN 415 2,94 2,03 506 14 2,64 1,91 454 11,5 2,01 1,66 346 7,0 1,47 1,47 253 4,0

440
5 340 2,45 1,68 421 10,1 2,20 1,58 379 8,4 1,68 1,37 290 5,1 1,21 1,21 208 2,8
3 265 1,98 1,35 340 7,0 1,78 1,26 307 5,8 1,37 1,10 235 3,6 0,97 0,97 167 1,9
1 200 1,54 1,04 266 4,5 1,40 0,98 240 3,7 1,08 0,85 185 2,3 0,75 0,75 129 1,2
10 720 4,88 3,40 839 37,4 4,39 3,19 755 30,9 3,35 2,78 577 19 2,46 2,46 423 10,8
7,5 590 4,14
YFCN 2,86 713 28,1 3,73 2,69 642 23,2 2,86 2,34 492 14,3 2,07 2,07 356 8,0

640
5 475 3,43 2,35 590 20,2 3,10 2,21 533 16,7 2,38 1,92 409 10,4 1,70 1,70 293 5,7
3 375 2,80 1,90 481 14,1 2,53 1,79 434 11,7 1,95 1,55 335 7,3 1,37 1,37 236 3,9
1 290 2,20 1,49 379 9,2 1,99 1,40 343 7,7 1,54 1,22 265 4,8 1,07 1,07 184 2,5
10 875 5,74 4,02 987 29,1 5,16 3,78 888 24 3,94 3,30 677 14,7 2,91 2,91 501 8,5
7,5 735 4,98 3,46
YFCN 857 22,7 4,49 3,25 771 18,7 3,43 2,84 590 11,5 2,50 2,50 431 6,5

740
5 585 4,13 2,84 710 16,3 3,72 2,67 639 13,5 2,85 2,32 491 8,3 2,06 2,06 354 4,6
3 475 3,45 2,36 593 11,9 3,11 2,21 535 9,8 2,39 1,93 412 6,1 1,70 1,70 293 3,3
1 380 2,81 1,91 484 8,3 2,54 1,79 437 6,9 1,96 1,56 337 4,3 1,38 1,38 237 2,3
10 1365 7,70 5,60 1324 23,7 6,87 5,27 1182 19,3 5,14 4,61 883 11,4 4,04 4,04 695 7,4
7,5 1145 6,74 4,85 1160 18,8 5,7
YFCN 6,03 4,56 1037 15,3 4,52 3,98 778 9,1 3,50 3,50 602

940
5 910 5,65 4,01 972 13,8 5,06 3,77 871 11,3 3,81 3,29 656 6,8 2,89 2,89 497 4,1
3 755 4,87 3,42 837 10,6 4,36 3,21 750 8,7 3,30 2,80 567 5,2 2,48 2,48 426 3,1
1 575 3,89 2,70 669 7,1 3,49 2,54 601 5,9 2,65 2,21 456 3,6 1,95 1,95 335 2,0

Legend
Correction factors for different R.H. WT = Water temperature
Pc = Cooling total emission
R.H. WT: 7/12°C 8/13°C 10/15°C 12/17°C Ps = Cooling sensible emission
Pc 0,95 0,94 1,00 1,00 Qw = Water flow
48% Ps 1,00 1,00 1,00 1,00 Dp(c) = Water pressure drop
Pc 0,90 0,88 1,00 1,00 Vdc = Inverter Power
46% Ps 1,00 1,00 1,00 1,00 Qv = Air flow

17
YFCN–ECM
YFCN–ECM version

Cooling emission of 4 row coil


Entering air temperature: 26°C – R.H.: 50%

WT: 7/12 °C WT: 8/13 °C WT: 10/15 °C WT: 12/17 °C


Model Vdc
Qv Pc Ps Qw Dp(c) Pc Ps Qw Dp(c) Pc Ps Qw Dp(c) Pc Ps Qw Dp(c)
ECM m3/h kW kW l/h kPa kW kW l/h kPa kW kW l/h kPa kW kW l/h kPa
10 325 1,80 1,35 310 13,8 1,59 1,27 273 11 1,14 1,09 195 6,0 0,95 0,95 163 4,3
7,5
YFCN 260 1,52 1,13 262 10,2 1,35 1,06 232 8,2 0,97 0,91 166 4,5 0,79 0,79 136 3,1

240
5 210 1,27 0,93 219 7,5 1,13 0,87 194 6,0 0,82 0,75 140 3,3 0,66 0,66 113 2,3
3 160 1,03 0,75 176 5,1 0,91 0,70 157 4,1 0,66 0,60 114 2,3 0,52 0,52 90 1,5
1 115 0,75 0,54 130 3,0 0,67 0,51 115 2,4 0,49 0,43 85 1,4 0,38 0,38 65 0,9
10 505 3,07 2,26 528 15,1 2,72 2,11 467 12,1 1,96 1,82 338 6,8 1,59 1,59 274 4,6
7,5
YFCN 415 2,63 1,92 452 11,5 2,33 1,79 400 9,2 1,69 1,54 291 5,2 1,35 1,35 232 3,4

440
5 340 2,19 1,58 376 8,3 1,94 1,48 334 6,7 1,42 1,27 244 3,8 1,11 1,11 191 2,4
3 265 1,77 1,27 304 5,7 1,57 1,18 271 4,6 1,15 1,01 198 2,6 0,89 0,89 153 1,7
1 200 1,38 0,98 238 3,7 1,23 0,92 212 3,0 0,91 0,79 156 1,7 0,69 0,69 119 1,1
10 720 4,36 3,20 750 30,8 3,87 3,00 666 24,7 2,82 2,58 486 14 2,25 2,25 388 9,3
7,5 590 3,71
YFCN 2,70 638 23,1 3,29 2,52 567 18,6 2,41 2,17 415 10,6 1,90 1,90 326 6,9

640
5 475 3,08 2,21 529 16,6 2,74 2,07 470 13,4 2,01 1,78 346 7,7 1,56 1,56 268 4,9
3 375 2,51 1,79 431 11,6 2,23 1,67 384 9,4 1,65 1,44 283 5,4 1,26 1,26 217 3,3
1 290 1,98 1,40 340 7,6 1,77 1,31 304 6,2 1,31 1,13 225 3,6 0,98 0,98 169 2,2
10 875 5,13 3,79 883 23,9 4,55 3,55 782 19,2 3,31 3,06 569 10,8 2,67 2,67 459 7,3
7,5 735 4,46 3,26
YFCN 766 18,6 3,96 3,05 680 15 2,89 2,63 497 8,5 2,29 2,29 394 5,6

740
5 585 3,69 2,68 635 13,4 3,28 2,50 565 10,8 2,41 2,15 414 6,2 1,89 1,89 325 4,0
3 475 3,09 2,22 531 9,8 2,75 2,08 473 7,9 2,02 1,79 348 4,5 1,56 1,56 269 2,8
1 380 2,52 1,80 434 6,8 2,25 1,68 387 5,6 1,66 1,45 286 3,2 1,26 1,26 217 2,0
10 1365 6,84 5,28 1177 19,3 6,02 4,95 1035 15,3 4,40 4,40 757 8,7 3,69 3,69 635 6,3
7,5 1145 6,00 4,57 1031 15,3 4,9
YFCN 5,28 4,28 908 12,1 3,74 3,68 643 6,5 3,19 3,19 549

940
5 910 5,03 3,78 866 11,2 4,44 3,54 764 8,9 3,16 3,04 544 4,9 2,64 2,64 454 3,5
3 755 4,33 4,00 745 8,6 3,83 3,01 659 6,9 2,74 2,59 472 3,8 2,27 2,27 390 2,7
1 575 3,47 2,54 597 5,8 3,07 2,38 528 4,7 2,22 2,04 382 2,6 1,78 1,78 307 1,7

Legend
Correction factors for different R.H. WT = Water temperature
Pc = Cooling total emission
R.H. WT: 7/12°C 8/13°C 10/15°C 12/17°C Ps = Cooling sensible emission
Pc 0,95 0,94 1,00 1,00 Qw = Water flow
48% Ps 1,00 1,00 1,00 1,00 Dp(c) = Water pressure drop
Pc 0,90 0,88 1,00 1,00 Vdc = Inverter Power
46% Ps 1,00 1,00 1,00 1,00 Qv = Air flow

18
YFCN–ECM
YFCN–ECM version

Cooling emission of 4 row coil


Entering air temperature: 25°C – R.H.: 50%

WT: 7/12 °C WT: 8/13 °C WT: 10/15 °C WT: 12/17 °C


Model Vdc
Qv Pc Ps Qw Dp(c) Pc Ps Qw Dp(c) Pc Ps Qw Dp(c) Pc Ps Qw Dp(c)
ECM m3/h kW kW l/h kPa kW kW l/h kPa kW kW l/h kPa kW kW l/h kPa
10 325 1,59 1,27 273 11 1,37 1,18 236 8,5 1,04 1,04 179 5,1 0,86 0,86 148 3,6
7,5
YFCN 260 1,34 1,06 231 8,2 1,16 0,99 200 6,3 0,87 0,87 149 3,7 0,72 0,72 123 2,6

240
5 210 1,12 0,88 193 6,0 0,98 0,81 168 4,6 0,72 0,72 124 2,7 0,60 0,60 103 1,9
3 160 0,91 0,70 156 4,1 0,79 0,65 136 3,2 0,57 0,57 99 1,8 0,47 0,47 82 1,3
1 115 0,67 0,51 115 2,4 0,58 0,47 100 1,9 0,40 0,40 68 0,9 0,34 0,34 59 0,7
10 505 2,71 2,12 466 12,1 2,35 1,97 405 9,4 1,74 1,74 300 5,5 1,43 1,44 246 3,9
7,5
YFCN 415 2,32 1,79 399 9,2 2,02 1,67 347 7,2 1,48 1,48 254 4,1 1,22 1,22 210 2,9

440
5 340 1,94 1,48 333 6,7 1,69 1,38 290 5,2 1,22 1,22 209 2,9 1,01 1,01 174 2,1
3 265 1,57 1,19 269 4,6 1,37 1,10 235 3,6 0,93 0,93 160 1,8 0,81 0,81 139 1,4
1 200 1,23 0,92 211 3,0 1,08 0,86 185 2,4 0,74 0,72 127 1,2 0,63 0,63 108 0,9
10 720 3,86 3,00 664 24,8 3,36 2,80 578 19,3 2,47 2,47 424 11,1 2,05 2,05 352 7,8
7,5 590 3,28
YFCN 2,53 565 18,6 2,87 2,35 493 14,6 2,08 2,08 357 8,1 1,72 1,72 296 5,8

640
5 475 2,72 2,08 469 13,4 2,38 1,93 410 10,5 1,71 1,71 294 5,8 1,42 1,42 244 4,1
3 375 2,22 1,68 382 9,4 1,95 1,56 335 7,4 1,34 1,32 230 3,8 1,14 1,15 196 2,8
1 290 1,76 1,32 302 6,2 1,54 1,12 265 4,9 1,07 1,03 184 2,5 0,90 0,90 154 1,8
10 875 4,54 3,56 780 19,2 3,95 3,32 679 15 2,92 2,92 502 8,7 2,42 2,42 416 6,1
7,5 735 3,94 3,06
YFCN 678 15 3,44 2,85 591 11,7 2,51 2,51 432 6,7 2,08 2,08 358 4,7

740
5 585 3,27 2,51 562 10,8 2,86 2,34 491 8,5 2,07 2,07 356 4,7 1,71 1,71 295 3,4
3 475 2,74 2,08 471 7,9 2,39 1,94 412 6,2 1,63 1,63 281 3,1 1,42 1,42 244 2,4
1 380 2,24 1,69 385 5,5 1,96 1,57 337 4,4 1,35 1,32 232 2,2 1,15 1,15 198 1,7
10 1365 6,01 4,96 1033 15,3 5,18 4,62 891 11,7 4,05 4,05 696 7,5 3,33 3,33 573 5,3
7,5 1145 5,27 4,29 906 12,2 4,1
YFCN 4,55 3,99 783 9,3 3,50 3,50 603 5,8 2,89 2,89 497

940
5 910 4,43 3,54 762 9,0 3,83 3,30 659 6,9 2,90 2,90 498 4,2 2,39 2,39 411 2,9
3 755 3,82 3,02 657 6,9 3,31 2,81 569 5,3 2,48 2,48 427 3,2 2,05 2,05 353 2,2
1 575 3,06 2,38 526 4,7 2,66 2,22 457 3,6 1,95 1,95 336 2,1 1,62 1,62 278 1,5

Legend
Correction factors for different R.H. WT = Water temperature
Pc = Cooling total emission
R.H. WT: 7/12°C 8/13°C 10/15°C 12/17°C Ps = Cooling sensible emission
Pc 0,95 0,94 1,00 1,00 Qw = Water flow
48% Ps 1,00 1,00 1,00 1,00 Dp(c) = Water pressure drop
Pc 0,90 0,88 1,00 1,00 Vdc = Inverter Power
46% Ps 1,00 1,00 1,00 1,00 Qv = Air flow

19
YFCN–ECM
YFCN–ECM version

Heating emission of 3 row coil


Entering air temperature: 20°C

WT: 70/60 °C WT: 60/50 °C WT: 50/40 °C WT: 50/45 °C WT: 45/40 °C
Model Vdc
Qv Ph Qw Dp(c) Ph Qw Dp(c) Ph Qw Dp(c) Ph Qw Dp(c) Ph Qw Dp(c)
ECM m3/h kW l/h kPa kW l/h kPa kW l/h kPa kW l/h kPa kW l/h kPa
10 330 3,64 313 6,7 2,78 239 4,3 1,92 165 2,3 2,22 383 10 1,80 309 7,0
7,5
YFCN 270 3,09 265 5,0 2,36 203 3,2 1,63 140 1,7 1,89 324 7,5 1,52 262 5,2

230
5 220 2,61 224 3,7 1,99 171 2,4 1,38 119 1,3 1,59 274 5,6 1,29 222 3,9
3 170 2,10 181 2,5 1,61 138 1,6 1,12 96 0,9 1,28 221 3,8 1,04 179 2,7
1 120 1,55 133 1,5 1,19 102 1,0 0,83 71 0,5 0,95 163 2,2 0,77 132 1,6
10 515 6,33 544 25,2 4,86 418 16,3 3,39 291 8,9 3,87 665 37,9 3,14 540 26,7
7,5
YFCN 430 5,43 467 19,2 4,17 359 12,5 2,91 250 6,8 3,32 571 28,9 2,69 463 20,4

430
5 350 4,55 391 14,1 3,50 301 9,1 2,44 210 5,0 2,78 478 21,2 2,26 388 14,9
3 280 3,70 318 9,8 2,85 245 6,4 1,99 171 3,5 2,26 389 14,7 1,84 316 10,4
1 210 2,85 245 6,2 2,20 189 4,0 1,54 133 2,2 1,74 300 9,3 1,42 244 6,6
10 735 8,37 719 16 6,41 551 10,3 4,45 383 5,6 5,11 879 24,1 4,14 712 17
7,5 610 7,17
YFCN 616 12,2 5,50 473 7,9 3,82 329 4,3 4,38 753 18,4 3,55 610 12,9

630
5 495 6,04 520 9,0 4,64 399 5,9 3,23 278 3,2 3,69 635 13,6 3,00 515 9,6
3 395 4,97 427 6,4 3,82 328 4,2 2,66 229 2,3 3,03 522 9,6 2,46 424 6,8
1 305 3,95 339 4,3 3,04 261 2,8 2,12 182 1,5 2,41 415 6,4 1,96 337 4,5
10 890 10,25 882 26,7 7,87 677 17,3 5,49 472 9,5 6,26 1077 40,1 5,08 874 28,3
7,5 755 8,94 769
YFCN 21 6,87 591 13,6 4,79 412 7,5 5,46 939 31,5 4,43 762 22,2

730
5 610 7,50 645 15,4 5,77 496 10 4,03 347 5,5 4,58 788 23,2 3,72 640 16,4
3 500 6,30 542 11,3 4,85 417 7,4 3,93 338 4,1 3,85 662 17 3,13 538 12,1
1 400 5,16 444 8,0 3,98 342 5,2 2,79 240 2,9 3,15 542 12 2,56 441 8,5
10 1395 14,95 1285 22,9 11,42 982 14,7 7,90 679 8,0 9,13 1570 34,5 7,38 1270 24,2
7,5 1175 13,06 1123 18,1 9,99
YFCN 859 11,6 6,92 595 6,3 7,98 1372 27,2 6,46 1111 19,1

930
5 945 10,94 941 13,2 8,38 720 8,5 5,81 500 4,6 6,68 1149 19,9 5,41 931 14
3 785 9,40 809 10,1 7,21 620 6,5 5,00 430 3,6 5,74 988 15,3 4,66 801 10,7
1 605 7,55 649 6,9 5,79 498 4,5 4,03 347 2,4 4,61 793 10,4 3,74 643 7,3

Legend
WT = Water temperature
Ph = Emission
Qw = Water flow
Dp(c) = Water pressure drop
Vdc = Inverter Power
Qv = Air flow

20
YFCN–ECM
YFCN–ECM version

Heating emission of 4 row coil


Entering air temperature: 20°C

WT: 70/60 °C WT: 60/50 °C WT: 50/40 °C WT: 50/45 °C WT: 45/40 °C
Model Vdc
Qv Ph Qw Dp(c) Ph Qw Dp(c) Ph Qw Dp(c) Ph Qw Dp(c) Ph Qw Dp(c)
ECM m3/h kW l/h kPa kW l/h kPa kW l/h kPa kW l/h kPa kW l/h kPa
10 325 4,01 344 12,9 3,07 264 8,3 2,14 184 4,5 2,45 421 19,4 1,98 341 13,6
7,5
YFCN 260 3,33 286 9,3 2,56 220 6,0 1,78 153 3,3 2,03 350 14 1,65 284 9,9

240
5 210 2,75 237 6,7 2,12 182 4,3 1,48 127 2,4 1,68 289 10 1,37 235 7,1
3 160 2,18 187 4,4 1,68 144 2,9 1,17 101 1,6 1,33 229 6,6 1,08 186 4,7
1 115 1,57 135 2,5 1,21 104 1,6 0,85 73 0,9 0,96 165 3,7 0,78 134 2,6
10 505 6,60 568 12,9 5,07 436 8,4 3,54 304 4,6 4,04 694 19,5 3,28 563 13,7
7,5
YFCN 415 5,57 479 9,6 4,29 369 6,2 3,00 258 3,4 3,41 586 14,5 2,77 476 10,2

440
5 340 4,59 394 6,8 3,53 304 4,4 2,48 213 2,5 2,81 484 10,3 2,29 394 7,3
3 265 3,67 316 4,6 2,83 243 3,0 1,99 171 1,7 2,24 386 6,9 1,83 314 4,9
1 200 2,83 244 2,9 2,19 188 1,9 1,54 132 1,1 1,73 298 4,4 1,41 243 3,1
10 720 9,43 811 27,4 7,26 624 17,8 5,08 437 9,8 5,76 991 41,2 4,68 805 29,1
7,5 590 7,90
YFCN 679 20,1 6,09 523 13,1 4,27 367 7,2 4,83 830 30,2 3,93 675 21,4

640
5 475 6,48 557 14,2 5,00 430 9,2 3,51 302 5,1 3,96 681 21,3 3,23 555 15,1
3 375 5,21 448 9,6 4,02 346 6,3 2,83 243 3,5 3,19 548 14,5 2,59 446 10,3
1 290 4,05 348 6,2 3,13 269 4,1 2,21 190 2,3 2,48 426 9,3 2,02 347 6,6
10 875 10,93 940 20,7 8,41 723 13,5 5,88 505 7,4 6,68 1149 31,2 5,43 933 22
7,5 735 9,39 808
YFCN 15,9 7,23 622 10,3 5,06 435 5,7 5,74 987 23,9 4,66 802 16,9

740
5 585 7,73 664 11,3 5,95 512 7,3 4,17 359 4,1 4,72 812 16,9 3,84 660 12
3 475 6,38 549 8,0 4,92 423 5,2 3,45 297 2,9 3,90 671 12,1 3,17 546 8,6
1 380 5,16 444 5,5 3,98 342 3,6 2,80 241 2,0 3,15 542 8,3 2,57 442 5,9
10 1365 16,03 1379 19,8 12,27 1055 12,8 8,50 731 6,9 9,79 1685 29,8 7,93 1364 20,9
7,5 1145 13,82 1188 15,2 10,58
YFCN 910 9,8 7,35 632 5,3 8,44 1452 22,9 6,84 1176 16,1

940
5 910 11,37 978 10,8 8,72 750 7,0 6,06 521 3,8 6,94 1194 16,3 5,63 969 11,4
3 755 9,69 834 8,2 7,44 640 5,3 5,18 446 2,9 5,92 1019 12,3 4,81 826 8,7
1 575 7,58 652 5,3 5,82 501 3,4 4,07 350 1,9 4,63 796 8,0 3,76 647 5,6

Legend
WT = Water temperature
Ph = Emission
Qw = Water flow
Dp(c) = Water pressure drop
Vdc = Inverter Power
Qv = Air flow

21
YFCN–ECM
YFCN–ECM version

Heating emission of 1 row additional coil


Entering air temperature: 20°C

WT: 80/70 °C WT: 75/65 °C WT: 70/60 °C WT: 65/55 °C WT: 60/50 °C WT: 55/45 °C
Model Vdc
Qv Ph Qw Dp(c) Ph Qw Dp(c) Ph Qw Dp(c) Ph Qw Dp(c) Ph Qw Dp(c) Ph Qw Dp(c)
ECM m3/h kW l/h kPa kW l/h kPa kW l/h kPa kW l/h kPa kW l/h kPa kW l/h kPa
10 330 2,04 176 6,3 1,84 158 5,3 1,63 140 4,3 1,43 123 3,5 1,22 105 2,7 1,018 88 2,0

YFCN 7,5 270 1,78 153 4,9 1,60 138 4,1 1,42 122 3,4 1,24 107 2,7 1,07 92 2,1 0,888 76 1,6

2
5 220 1,54 132 3,8 1,38 119 3,2 1,23 106 2,6 1,08 93 2,1 0,92 79 1,6 0,77 66 1,2
3 170 1,29 111 2,8 1,16 100 2,4 1,04 89 1,9 0,91 78 1,6 0,78 67 1,2 0,65 56 0,9
1 120 1,02 87 1,8 0,92 79 1,5 0,81 70 1,3 0,71 61 1,0 0,61 53 0,8 0,512 44 0,6
10 515 3,41 293 19,4 3,08 264 16,4 2,74 236 13,6 2,41 207 11 2,07 178 8,6 1,74 150 6,4

YFCN 7,5 430 3,01 259 15,6 2,72 234 13,2 2,42 208 10,9 2,13 183 8,8 1,83 158 6,9 1,54 132 5,2

4
5 350 2,62 225 12,2 2,36 203 10,3 2,11 181 8,5 1,85 159 6,9 1,60 137 5,4 1,34 115 4,0
3 280 2,22 191 9,1 2,01 172 7,7 1,79 154 6,4 1,57 135 5,2 1,36 117 4,1 1,139 98 3,0
1 210 1,82 157 6,4 1,64 141 5,4 1,47 126 4,5 1,29 111 3,6 1,11 96 2,9 0,935 80 2,1
10 735 4,61 396 6,4 4,14 356 5,4 3,68 317 4,5 3,22 277 3,6 2,76 238 2,8 2,303 198 2,0

YFCN 7,5 610 4,05 348 5,1 3,64 313 4,3 3,24 278 3,6 2,83 244 2,9 2,43 209 2,2 2,029 174 1,6

6
5 495 3,50 301 4,0 3,15 271 3,3 2,80 241 2,8 2,45 211 2,2 2,11 181 1,7 1,76 151 1,3
3 395 3,00 258 3,0 2,70 232 2,5 2,40 206 2,1 2,10 181 1,7 1,81 155 1,3 1,509 130 1,0
1 305 2,50 215 2,2 2,25 194 1,9 2,00 172 1,5 1,76 151 1,2 1,51 130 1,0 1,263 109 0,7
10 890 5,77 496 11,2 5,20 447 9,5 4,63 398 7,8 4,06 349 6,3 3,50 301 4,9 2,929 252 3,7

YFCN 7,5 755 5,15 443 9,2 4,64 399 7,8 4,13 355 6,4 3,63 312 5,2 3,12 268 4,0 2,616 225 3,0

7
5 610 4,43 381 7,1 4,00 344 6,0 3,56 306 4,9 3,13 269 4,0 2,69 231 3,1 2,258 194 2,3
3 500 3,86 332 5,5 3,48 299 4,7 3,10 267 3,9 2,72 234 3,1 2,35 202 2,4 1,969 169 1,8
1 400 3,30 284 4,2 2,97 256 3,5 2,65 228 2,9 2,33 200 2,4 2,01 173 1,9 1,685 145 1,4
10 1395 7,46 641 17,6 6,72 578 14,9 5,98 514 12,3 5,24 451 9,9 4,51 388 7,7 3,772 324 5,7

YFCN 7,5 1175 6,67 574 14,5 6,01 517 12,2 5,35 460 10,1 4,69 404 8,2 4,04 347 6,4 3,379 291 4,7

9
5 945 5,75 495 11,2 5,18 446 9,4 4,62 397 7,8 4,05 348 6,3 3,48 300 4,9 2,919 251 3,7
3 785 5,08 437 9,0 4,58 394 7,6 4,08 351 6,3 3,58 308 5,1 3,08 265 3,9 2,582 222 2,9
1 605 4,23 364 6,5 3,82 328 5,5 3,40 292 4,6 2,99 257 3,7 2,57 221 2,9 2,158 186 2,1

Legend
WT = Water temperature
Ph = Emission
Qw = Water flow
Dp(c) = Water pressure drop
Vdc = Inverter Power
Qv = Air flow

22
YFCN–ECM
YFCN–ECM version

Heating emission of 2 row additional coil


Entering air temperature: 20°C

WT: 65/55 °C WT: 60/50 °C WT: 55/45 °C WT: 50/40 °C WT: 45/40 °C WT: 45/35 °C
Model Vdc
Qv Ph Qw Dp(c) Ph Qw Dp(c) Ph Qw Dp(c) Ph Qw Dp(c) Ph Qw Dp(c) Ph Qw Dp(c)
ECM m3/h kW l/h kPa kW l/h kPa kW l/h kPa kW l/h kPa kW l/h kPa kW l/h kPa
10 330 2,48 214 16,7 2,15 184 13,1 1,81 155 9,9 1,47 126 7,0 1,39 239 21,6 1,13 97 4,5

YFCN 7,5 270 2,13 183 12,7 1,84 158 10 1,55 133 7,5 1,26 109 5,3 1,19 205 16,5 0,97 84 3,4

2
5 220 1,81 155 9,6 1,56 134 7,5 1,32 113 5,7 1,07 92 4,0 1,01 174 12,4 0,83 71 2,6
3 170 1,49 128 6,8 1,29 111 5,3 1,10 94 4,1 0,89 77 2,9 0,84 144 8,9 0,69 59 1,9
1 120 1,13 97 4,2 0,98 84 3,3 0,83 71 2,5 0,68 58 1,8 0,63 109 5,4 0,52 45 1,2
10 515 3,90 335 7,6 3,36 289 5,9 2,82 243 4,4 2,29 197 3,1 2,18 375 9,8 1,76 151 2,0

YFCN 7,5 430 3,40 292 5,9 2,93 252 4,7 2,47 212 3,5 2,00 172 2,5 1,90 327 7,7 1,54 132 1,6

4
5 350 2,90 249 4,5 2,50 215 3,5 2,11 181 2,6 1,71 147 1,9 1,62 279 5,8 1,32 113 1,2
3 280 2,43 209 3,3 2,10 181 2,6 1,77 152 1,9 1,44 124 1,4 1,36 234 4,3 1,11 95 0,9
1 210 1,94 166 2,2 1,67 144 1,7 1,41 121 1,3 1,15 99 0,9 1,08 186 2,8 0,89 76 0,6
10 735 5,63 484 17,8 4,87 419 14 4,11 353 10,5 3,35 288 7,5 3,15 542 23 2,59 223 4,9

YFCN 7,5 610 4,88 419 13,8 4,22 363 10,9 3,56 306 8,2 2,91 250 5,8 2,73 470 17,9 2,25 194 3,8

6
5 495 4,14 356 10,3 3,58 308 8,1 3,03 260 6,2 2,47 213 4,4 2,32 398 13,4 1,92 165 2,9
3 395 3,46 297 7,5 3,00 258 5,9 2,53 218 4,5 2,09 180 3,3 1,96 336 9,9 1,62 139 2,1
1 305 2,83 243 5,3 2,45 211 4,2 2,08 178 3,2 1,70 146 2,3 1,58 272 6,9 1,32 113 1,5
10 890 7,01 603 31,1 6,07 522 24,5 5,14 442 18,6 4,20 361 13,3 3,93 675 40,2 3,27 281 8,7

YFCN 7,5 755 6,17 530 24,8 5,34 460 19,6 4,52 389 14,8 3,70 318 10,6 3,45 594 32,1 2,88 248 6,9

7
5 610 5,20 447 18,4 4,51 388 14,5 3,82 328 11 3,13 269 7,9 2,91 501 23,8 2,44 209 5,2
3 500 4,47 384 14,1 3,88 333 11,1 3,28 282 8,4 2,69 232 6,1 2,50 431 18,2 2,10 180 4,0
1 400 3,72 320 10,2 3,23 277 8,1 2,74 235 6,1 2,24 193 4,4 2,08 358 13,2 1,75 151 2,9
10 1395 9,60 825 54 8,31 714 42,6 7,02 604 32,2 5,74 493 22,9 - - - 4,45 383 15

YFCN 7,5 1175 8,49 730 43,5 7,35 632 34,3 6,22 535 26 5,08 437 18,5 - - - 3,94 339 12,1

9
5 945 7,22 621 32,7 6,25 538 25,8 5,29 455 19,5 4,33 372 14 - - - 3,36 289 9,1
3 785 6,28 540 25,6 5,45 468 20,2 4,61 396 15,3 3,77 324 11 - - - 2,93 252 7,2
1 605 5,12 440 17,8 4,44 381 14,1 3,76 323 10,7 3,08 265 7,7 - - - 2,40 206 5,0

Legend
WT = Water temperature
Ph = Emission
Qw = Water flow
Dp(c) = Water pressure drop
Vdc = Inverter Power
Qv = Air flow

23
YFCN–ECM
YFCN–ECM version

Air flow and correction factors for emission


with different available pressures

Qv (m3/h) K1 K2
Model Vdc
Ap (Pa) Ap (Pa) Ap (Pa)
ECM 0 5 10 15 20 25 30 35 40 0 5 10 15 20 25 30 35 40 0 5 10 15 20 25 30 35 40
10 330 312 288 257 223 171 88 − − 1,00 0,95 0,89 0,82 0,73 0,60 0,32 − − 0,95 0,88 0,80 0,72 0,58 0,29 − −

8,5 307 276 251 213 162 92 29 − − 1,00 0,91 0,85 0,75 0,61 0,36 0,06 − − 1,00 0,90 0,83 0,73 0,59 0,34 0,03 − −

7,5 270 252 219 178 103 − − − − 1,00 0,94 0,84 0,72 0,46 − − − − 1,00 0,94 0,83 0,70 0,44 − − − −
YFCN 6,5 248 227 187 130 56 − − − − 1,00 0,93 0,80 0,60 0,26 − − − − 1,00 0,92 0,78 0,58 0,24 − − − −

2 5
3
220 187 126

170 122 45
55







1,00 0,88 0,65 0,30

1,00 0,77 0,32 −







1,00 0,86 0,63 0,27

1,00 0,75 0,29 −






2 144 82 − − − − − − − 1,00 0,65 − − − − − − − 1,00 0,63 − − − − − − −

1 120 68 − − − − − − − 1,00 0,64 − − − − − − − 1,00 0,62 − − − − − − −

10 515 499 477 448 401 332 247 100 − 1,00 0,97 0,94 0,89 0,82 0,71 0,56 0,22 − 0,97 0,93 0,88 0,80 0,69 0,54 0,19 −

8,5 459 444 419 377 323 229 54 − − 1,00 0,97 0,93 0,85 0,76 0,58 0,10 − − 1,00 0,97 0,92 0,84 0,74 0,56 0,07 − −

7,5 430 396 363 320 240 89 − − − 1,00 0,93 0,87 0,79 0,63 0,24 − − − 1,00 0,92 0,86 0,77 0,61 0,21 − − −
YFCN 6,5 394 374 333 272 135 − − − − 1,00 0,95 0,87 0,74 0,41 − − − − 1,00 0,95 0,86 0,73 0,39 − − − −

4 5
3
350 308 255 107

280 227 99 −






1,00 0,90 0,78 0,37

1,00 0,84 0,43 −







1,00 0,89 0,76 0,35

1,00 0,83 0,41 −






2 233 170 − − − − − − − 1,00 0,78 − − − − − − − 1,00 0,76 − − − − − − −

1 210 126 − − − − − − − 1,00 0,67 − − − − − − − 1,00 0,65 − − − − − − −

10 735 696 673 622 558 431 286 168 − 1,00 0,95 0,93 0,87 0,80 0,66 0,47 0,27 − 0,95 0,92 0,86 0,78 0,64 0,45 0,24 −

8,5 650 628 583 525 421 269 110 − − 1,00 0,97 0,91 0,84 0,71 0,49 0,18 − − 1,00 0,97 0,90 0,82 0,69 0,47 0,15 − −

7,5 610 564 528 437 284 129 − − − 1,00 0,94 0,89 0,77 0,55 0,25 − − − 1,00 0,93 0,87 0,75 0,53 0,22 − − −
YFCN 6,5 558 510 457 340 189 − − − − 1,00 0,93 0,85 0,68 0,41 − − − − 1,00 0,92 0,83 0,66 0,39 − − − −

6 5
3
495 432 352 154

395 319 151 82







1,00 0,89 0,76 0,38

1,00 0,84 0,46 0,24







1,00 0,88 0,74 0,36

1,00 0,82 0,44 0,21






2 351 221 − − − − − − − 1,00 0,70 − − − − − − − 1,00 0,68 − − − − − − −

1 305 177 − − − − − − − 1,00 0,65 − − − − − − − 1,00 0,63 − − − − − − −

10 890 846 815 756 699 590 486 341 191 1,00 0,96 0,93 0,87 0,82 0,72 0,62 0,46 0,25 0,95 0,92 0,86 0,81 0,70 0,60 0,44 0,22

8,5 805 756 703 652 560 437 279 114 − 1,00 0,95 0,89 0,84 0,75 0,62 0,42 0,14 − 1,00 0,94 0,88 0,83 0,73 0,60 0,40 0,11 −

7,5 755 696 637 558 459 300 140 − − 1,00 0,93 0,87 0,79 0,68 0,48 0,21 − − 1,00 0,93 0,86 0,77 0,66 0,46 0,18 − −
YFCN 6,5 703 637 560 449 336 175 − − − 1,00 0,92 0,83 0,70 0,56 0,30 − − − 1,00 0,91 0,82 0,68 0,54 0,27 − − −

7 5
3
610 532 443 313 133

500 398 255 83 −






1,00 0,89 0,78 0,59 0,26

1,00 0,83 0,59 0,18 −






1,00 0,88 0,76 0,57 0,23

1,00 0,81 0,57 0,15 −





2 452 348 178 − − − − − − 1,00 0,81 0,47 − − − − − − 1,00 0,79 0,45 − − − − − −

1 400 279 − − − − − − − 1,00 0,75 − − − − − − − 1,00 0,73 − − − − − − −

10 1395 1310 1225 1180 1125 1060 1000 930 860 1,00 0,95 0,90 0,87 0,84 0,80 0,77 0,73 0,68 0,94 0,89 0,86 0,82 0,78 0,75 0,71 0,66

8,5 1265 1175 1080 1020 960 880 800 720 640 1,00 0,94 0,88 0,84 0,80 0,75 0,70 0,64 0,59 1,00 0,93 0,86 0,82 0,78 0,73 0,68 0,62 0,57

7,5 1175 1075 970 910 840 750 650 545 450 1,00 0,93 0,85 0,81 0,77 0,70 0,63 0,54 0,46 1,00 0,92 0,84 0,80 0,75 0,68 0,61 0,52 0,44
YFCN 6,5 1085 980 865 790 700 605 500 350 200 1,00 0,92 0,83 0,78 0,71 0,63 0,54 0,39 0,21 1,00 0,91 0,82 0,76 0,69 0,61 0,52 0,37 0,18

9 5
3
945 835 680 580 460 315 160

785 620 400 230 50 − −




1,00 0,90 0,77 0,68 0,57 0,40 0,18

1,00 0,83 0,59 0,35 − − −




1,00 0,89 0,75 0,66 0,55 0,38 0,15

1,00 0,81 0,57 0,33 − − −



2 700 500 200 − − − − − − 1,00 0,77 0,34 − − − − − − 1,00 0,75 0,32 − − − − − −

1 605 390 − − − − − − − 1,00 0,71 − − − − − − − 1,00 0,69 − − − − − − −

Legend
Qv = Air flow
K1 = Correction factors for Total cooling emission
K2 = Correction factors for Sensible cooling emission and Heating emission
Ap = Available pressure
Vdc = Inverter Power

24
YFCN–ECM
YFCN–ECM version

Water pressure drop

3 row coil 4 row coil


Dp - kPa Dp - kPa
50 50

40 40

30 730 30
640

20 20

430 740

930
10 630 10
240 940
9 9
8 8
7 7
6 6
440
5 5
230
4 4

3 3

2 2

Water Water
1 flow (l/h) 1 flow (l/h)
100 200 300 400 600 800 1000 1500 100 200 300 400 600 800 1000 1500

The water pressure drop figures


refer to a mean water temperature of 10°C; °C 20 30 40 50 60 70 80
for different temperatures, multiply
the pressure drop figures by the correction factors K. K 0,94 0,90 0,86 0,82 0,78 0,74 0,70

1 row additional coil 2 row additional coil


Dp - kPa Dp - kPa
60 60
50 50

40 40

30 30 7- 9

20 20

10 10 2 6
9 9
8 4 8
7 7- 9 7
6 6
5 5

4 4

3 2 3 4
6
2 2

Water Water
1 flow (l/h) 1 flow (l/h)
50 60 80 100 200 300 400 600 800 1000 50 60 80 100 200 300 400 600 800 1000

The water pressure drop figures


refer to a mean water temperature of 65°C; °C 40 50 60 70 80
for different temperatures, multiply
the pressure drop figures by the correction factors K. K 1,14 1,08 1,02 0,96 0,90

25
YHP–ECM
YHP–ECM version

Construction features
Casing
Made of 1 mm galvanized steel insulated with polyolefin (PO) foam (class M1).

Filter
Polypropylene cellular fabric regenerating filter.
The filter frame of galvanized steel is inserted into special plastic sliding
guides fastened to the internal structure for easy insertion and removal
of the filter.

Fan assembly
The fans have aluminium or plastic blades directly keyed on
the motor with double aspiration and they are dynamically and
statically balanced during manufacture in order to have an
extremely quiet operation.

Electronic motor
Three phase permanent magnet brushless electronic motor that is controlled with reconstructed current according to
a BLAC sinusoidal wave. The inverter board that controls the motor operation is powered by 230 Volt, single-phase and,
with a switching system, it generates a three-phase frequency modulated, wave form power supply. The electric power
supply required for the machine is therefore single-phase with voltage of 230-240V and frequency of 50-60Hz.

Coil
It is manufactured from drawn copper tube and the aluminium fins are
mechanically bonded onto the tube by an expansion process.
The coil has two 1/2 inch BSP internal connections and 1/8 inch
BSP air vent and drain.
The coil is not suitable for use in corrosive atmosphere or in
environments where aluminium may be subject to corrosion.
The connections are on the left hand side looking from the
air outlet of the unit (see picture).
On request or on site the connections can be moved
to the other side.

Condensate collection tray


Made from plastic (ABS UL94 HB) with a “L”-shape fitted on the inner
casing; the tray is insulated with polyolefin (PO) foam (class M1). The outside
diameter of the condensate discharge pipe is 15mm.

Accessories and Controls


See pages 44 and 60.

26
YHP–ECM
YHP–ECM version

27
YHP–ECM
YHP–ECM version

Dimension, Weight, Water content

Vertical Installation
Coil connections on the left
D G 10 F
22 22

Ø 15 ext.

133
511

71 44 125
230
12 12
100 29 H

D
119*

153

E*
* Supply frame dimension = E x 119 mm
17

12 12

Auxiliary condensate tray (optional)


Horizontal Installation
D
119*

H
153

E*
17

12 12
230 Ø 15 ext.
125 44 71
133

150 F 10
* Supply frame dimension = E x 119 mm

COIL CONNECTIONS

3 or 4 row coils Heating additional coil (1 or 2 rows)

O WATER OUTLET S WATER OUTLET

N 321
37

U
R
M

P
H

H
G
G

WATER
INLET
WATER
INLET

230 Ø 1/2" F 230


Ø 15 Ø 15 Ø 1/2" F
ext. ext.

28
YHP–ECM
YHP–ECM version

Dimension, Weight, Water content

PACKAGING

600

Dimension (mm)

Model 1 2 3
D 689 904 1119
E 645 860 1075
F 669 884 1099
G 218 248 248
H 205 235 235
M 145 170 170
N 260 270 270
O 460 450 450
P 185 210 210
R 105 110 110
S 475 465 465
U 65 95 95
X 260 290 290
Y 820 1035 1250

Weight (kg)

Weight with packaging Weight without packaging


Model 1 2 3 1 2 3
3 19,1 26,1 30,4 17,3 23,5 27,3
3+1 20,3 27,6 32,2 18,5 25,0 29,1
Rows

3+2 21,0 28,5 33,3 19,2 25,9 30,2


4 20,1 27,4 31,9 18,3 24,8 28,8
4+1 21,3 28,9 33,7 19,5 26,3 30,6

Water content (litres)

Model 1 2 3
3 0,9 1,6 1,9
Rows

4 1,3 2,2 2,8


+1 0,3 0,5 0,6
+2 0,6 1,0 1,2

29
YHP–ECM
YHP–ECM version

Technical features

YHP−ECM units with 3 and 4 row coil

2 pipe units.

The following standard rating conditions are used:

COOLING HEATING
Entering air temperature + 27°C d.b. + 19°C w.b. Entering air temperature + 20°C
Water temperature + 7°C E.W.T. + 12°C L.W.T. Entering water temperature + 50°C
Water flow rate as for the cooling conditions

Model YHP−ECM 130 YHP−ECM 230 YHP−ECM 330


Inverter power 5 7 9 4 6 8 4,5 6,5 8,5
Speed MIN MED MAX MIN MED MAX MIN MED MAX
Air flow m3/h 240 280 325 420 485 560 720 820 950
Available pressure Pa 35 50 65 35 50 65 35 50 65
Cooling total emission kW 1,55 1,76 1,98 2,66 2,98 3,33 4,21 4,64 5,16
Cooling sensible emission kW 1,16 1,33 1,51 2,02 2,28 2,57 3,27 3,64 4,10
Heating kW 1,91 2,18 2,48 3,25 3,46 4,10 5,33 5,94 6,68
Dp Cooling kPa 8,9 11,1 13,7 9,0 11,0 13,4 10,5 12,4 15,0
Dp Heating kPa 7,3 9,0 11,3 7,4 9,1 11,1 8,6 10,2 12,3
Fan W 24 32 43 30 44 64 50 71 102
Sound power outlet dB(A) 45 48 52 45 49 52 50 53 56
Sound power intlet + radiated dB(A) 52 54 58 51 55 58 56 60 63
Sound pressure outlet (*) dB(A) 36 39 43 36 40 43 41 44 47
Sound pressure intlet + radiated (*) dB(A) 43 45 49 42 46 49 47 51 54
Plenum code 9066363 9069222 9066368

Model YHP−ECM 140 YHP−ECM 240 YHP−ECM 340


Inverter power 5 7 9 4 6 8 4,5 6,5 8,5
Speed MIN MED MAX MIN MED MAX MIN MED MAX
Air flow m3/h 240 280 325 420 485 560 720 820 950
Available pressure Pa 35 50 65 35 50 65 35 50 65
Cooling total emission kW 1,69 1,93 2,19 2,91 3,29 3,70 4,49 4,98 5,58
Cooling sensible emission kW 1,25 1,43 1,64 2,15 2,44 2,77 3,42 3,82 4,32
Heating kW 2,05 2,36 2,69 3,52 3,99 4,53 5,72 6,40 7,21
Dp Cooling kPa 5,4 6,8 8,5 15,1 18,7 23,0 9,1 10,9 13,3
Dp Heating kPa 4,4 5,5 7,0 12,4 15,4 19,0 7,5 9,0 10,9
Fan W 24 32 43 30 44 64 50 71 102
Sound power outlet dB(A) 45 48 52 45 49 52 50 53 56
Sound power intlet + radiated dB(A) 52 54 58 51 55 58 56 60 63
Sound pressure outlet (*) dB(A) 36 39 43 36 40 43 41 44 47
Sound pressure intlet + radiated (*) dB(A) 43 45 49 42 46 49 47 51 54
Plenum code 9066363 9069222 9066368


(*) = The sound pressure levels are 9 dB(A) lower than the sound power levels
and apply to the reverberant field of a 100 m3 room and a reverberation time of 0.5 sec.

30
YHP–ECM
YHP–ECM version

Technical features

YHP−ECM units with 1 row additional coil

4 pipe units.

The following standard rating conditions are used:

COOLING HEATING
Entering air temperature + 27°C d.b. + 19°C w.b. Entering air temperature + 20°C
Water temperature + 7°C E.W.T. + 12°C L.W.T. Water temperature + 70°C E.W.T. + 60°C L.W.T.

Model YHP−ECM 130+1 YHP−ECM 230+1 YHP−ECM 330+1


Inverter power 5 7 9 4 6 8 4,5 6,5 8,5
Speed MIN MED MAX MIN MED MAX MIN MED MAX
Air flow m3/h 240 280 325 420 485 560 720 820 950
Available pressure Pa 35 50 65 35 50 65 35 50 65
Cooling total emission kW 1,55 1,76 1,98 2,66 2,98 3,33 4,21 4,64 5,16
Cooling sensible emission kW 1,16 1,33 1,51 2,02 2,28 2,57 3,27 3,64 4,10
Heating kW 1,64 1,83 2,02 2,62 2,89 3,19 3,97 4,33 4,79
Dp Cooling kPa 8,9 11,1 13,7 9,0 11,0 13,4 10,5 12,4 15,0
Dp Heating kPa 5,5 6,6 8,0 3,4 4,1 4,9 6,0 7,0 8,3
Fan W 24 32 43 30 44 64 50 71 102
Sound power outlet dB(A) 45 48 52 45 49 52 50 53 56
Sound power intlet + radiated dB(A) 52 54 58 51 55 58 56 60 63
Sound pressure outlet (*) dB(A) 36 39 43 36 40 43 41 44 47
Sound pressure intlet + radiated (*) dB(A) 43 45 49 42 46 49 47 51 54
Plenum code 9066363 9069222 9066368


(*) = The sound pressure levels are 9 dB(A) lower than the sound power levels
and apply to the reverberant field of a 100 m3 room and a reverberation time of 0.5 sec.

31
YHP–ECM
YHP–ECM version

Main performance and technical characteristics


2 pipe units. The following standard rating conditions are used:

COOLING HEATING
Entering air temperature + 27°C d.b. + 19°C w.b. Entering air temperature + 20°C
Water temperature + 7°C E.W.T. + 12°C L.W.T. Entering water temperature + 50°C
AVAILABLE PRESSURE: 0 Pa Water flow rate as for the cooling conditions

Model YHP−ECM 130 YHP−ECM 230 YHP−ECM 330


Vdc 1 3 5 7,5 10 1 3 5 7,5 10 1 3 5 7,5 10
Air flow m3/h 350 425 515 625 730 610 760 920 1120 1250 770 985 1180 1425 1450
Cooling total emission kW 2,10 2,43 2,80 3,21 3,57 3,55 4,18 4,78 5,45 5,86 4,43 5,30 6,01 6,82 6,90
Cooling sensible emission kW 1,60 1,39 2,20 2,56 2,89 2,76 3,30 3,84 4,48 4,87 3,46 4,22 4,88 5,64 5,72
Heating kW 2,62 3,08 3,59 4,18 4,70 4,40 5,24 6,08 7,05 7,65 5,63 6,87 7,91 9,14 9,26
Dp Cooling kPa 15,2 19,7 25,2 32,1 38,6 15,0 20,0 25,3 32,0 36,2 11,5 15,7 19,6 24,5 25,0
Dp Heating kPa 12,7 16,3 20,7 26,4 31,7 12,3 16,3 20,6 26,0 30,1 9,3 12,9 16,1 20,2 20,7
Fan W 18 25,5 37 56 83 24 37 59 100 132 32 49 76 122 136
Sound power Lw dB(A) 47 53 57 62 66 47 53 58 63 66 52 57 61 65 66
Sound pressure (*) Lp dB(A) 38 44 48 53 57 38 44 49 54 57 43 48 52 56 57

Model YHP−ECM 140 YHP−ECM 240 YHP−ECM 340


Vdc 1 3 5 7,5 10 1 3 5 7,5 10 1 3 5 7,5 10
Air flow m3/h 350 425 515 625 730 610 760 920 1120 1250 770 985 1180 1425 1450
Cooling total emission kW 2,33 2,74 3,19 3,70 4,14 3,97 4,73 5,47 6,32 6,84 4,74 5,74 6,58 7,54 7,63
Cooling sensible emission kW 1,75 2,08 2,45 2,88 3,28 2,98 3,60 4,22 4,96 5,41 3,62 4,46 5,17 6,02 6,10
Heating kW 2,88 3,41 4,03 4,75 5,39 4,88 5,89 6,90 8,10 8,84 6,06 7,42 8,63 10,04 10,18
Dp Cooling kPa 9,5 12,5 16,4 21,3 26,0 26,1 35,4 45,9 59,1 67,8 10,0 13,9 17,7 22,5 23,0
Dp Heating kPa 7,7 10,1 13,6 17,5 21,5 21,7 29,4 37,8 48,7 56,1 8,2 11,4 14,7 18,6 19,0
Fan W 18 25,5 37 56 83 24 37 59 100 132 32 49 76 122 136
Sound power Lw dB(A) 47 53 57 62 66 47 53 58 63 66 52 57 61 65 66
Sound pressure (*) Lp dB(A) 38 44 48 53 57 38 44 49 54 57 43 48 52 56 57

4 pipe units. The following standard rating conditions are used:

COOLING HEATING
Entering air temperature + 27°C d.b. + 19°C w.b. Entering air temperature + 20°C
Water temperature + 7°C E.W.T. + 12°C L.W.T. Water temperature + 70°C E.W.T. + 60°C L.W.T.
AVAILABLE PRESSURE: 0 Pa

Model YHP−ECM 130+1 YHP−ECM 230+1 YHP−ECM 330+1


Vdc 1 3 5 7,5 10 1 3 5 7,5 10 1 3 5 7,5 10
Air flow m3/h 350 425 515 625 730 610 760 920 1120 1250 770 985 1180 1425 1450
Cooling total emission kW 2,10 2,43 2,80 3,21 3,57 3,55 4,18 4,78 5,45 5,86 4,43 5,30 6,01 6,82 6,90
Cooling sensible emission kW 1,60 1,39 2,20 2,56 2,89 2,76 3,30 3,84 4,48 4,87 3,46 4,22 4,88 5,64 5,72
Heating kW 2,13 2,44 2,78 3,17 3,43 3,38 3,93 4,46 4,96 5,31 4,15 4,91 5,54 6,24 6,28
Dp Cooling kPa 15,2 19,7 25,2 32,1 38,6 15,0 20,0 25,3 32,0 36,2 11,5 15,7 19,6 24,5 25,0
Dp Heating kPa 8,7 11,0 13,9 17,5 20,2 5,4 7,0 8,8 10,6 11,9 6,5 8,7 10,8 13,3 13,4
Fan W 18 25,5 37 56 83 24 37 59 100 132 32 49 76 122 136
Sound power Lw dB(A) 47 53 57 62 66 47 53 58 63 66 52 57 61 65 66
Sound pressure (*) Lp dB(A) 38 44 48 53 57 38 44 49 54 57 43 48 52 56 57

Vdc = Inverter Power


(*) = The sound pressure levels are 9 dB(A) lower than the sound power levels
and apply to the reverberant field of a 100 m3 room and a reverberation time of 0.5 sec.

32
YHP–ECM
YHP–ECM version

Operation limits
Highest water inlet temperature............................... + 85 °C
Lowest water inlet temperature................................ + 5 °C
for entering water temperatures below + 5°C, contact “YORK” technical department
Highest working pressure........................................ 1000 kPa (10 bars)

Water flow limits for 3 row coil (l/h)

Model YHP−ECM 130 YHP−ECM 230 YHP−ECM 330


Lowest 100 150 200
Highest 750 1000 2000

Water flow limits for 4 row coil (l/h)

Model YHP−ECM 140 YHP−ECM 240 YHP−ECM 340


Lowest 150 150 300
Highest 1000 1500 2250

Water flow limits for 1 row additional coil (l/h)

Model YHP−ECM 1 YHP−ECM 2 YHP−ECM 3


Lowest 50 100 100
Highest 350 500 750

Water flow limits for 2 row additional coil (l/h)

Model YHP−ECM 1 YHP−ECM 2 YHP−ECM 3


Lowest 100 100 100
Highest 350 500 750

Motor electrical data (max. absorption)

Model YHP−ECM 1 YHP−ECM 2 YHP−ECM 3


230/1 W 83 132 136
50Hz A 0,67 1,04 1,07

33
YHP–ECM
YHP–ECM version

Cooling emission of 3 row coil


Entering air temperature: 27°C – R.H.: 50% – Available pressure: 0Pa

WT: 7/12 °C WT: 8/13 °C WT: 10/15 °C WT: 12/17 °C


Model Vdc
Qv Pc Ps Qw Dp(c) Pc Ps Qw Dp(c) Pc Ps Qw Dp(c) Pc Ps Qw Dp(c)
ECM m3/h kW kW l/h kPa kW kW l/h kPa kW kW l/h kPa kW kW l/h kPa
10 730 3,84 2,86 660 44,0 3,43 2,70 590 35,8 2,56 2,37 440 21,1 2,08 2,08 358 14,4
7,5
YHP 625 3,46 2,54 595 36,5 3,09 2,40 531 29,8 2,32 2,10 399 17,7 1,84 1,84 316 11,7

130
5 515 3,02 2,19 519 28,7 2,70 2,06 464 23,5 2,03 1,80 349 14,0 1,58 1,58 272 8,9
3 425 2,62 1,87 451 22,4 2,35 1,76 404 18,3 1,77 1,54 304 11,0 1,35 1,35 232 6,8
1 350 2,26 1,60 389 17,2 2,02 1,50 347 14,1 1,53 1,31 263 8,6 1,15 1,15 198 5,1
10 1250 6,31 4,82 1085 41,3 5,62 4,55 967 33,5 4,17 4,01 717 19,5 3,50 3,50 602 14,2
7,5
YHP 1120 5,88 4,44 1011 36,5 5,24 4,19 901 29,6 3,90 3,68 671 17,3 3,22 3,22 554 12,2

230
5 920 5,15 3,82 886 28,9 4,60 3,59 791 23,5 3,43 3,15 590 13,9 2,77 2,77 476 9,4
3 760 4,50 3,28 774 22,8 4,02 3,09 691 18,6 3,02 2,71 519 11,1 2,38 2,38 409 7,2
1 610 3,83 2,75 659 17,1 3,43 2,59 590 14,0 2,58 2,26 444 8,4 1,99 1,99 342 5,2
10 1450 7,44 5,67 1280 28,6 6,62 5,34 1139 23,1 4,90 4,70 843 13,4 4,10 4,10 705 9,7
7,5 1425 7,36
YHP 5,59 1266 28,0 6,55 5,28 1127 22,7 4,84 4,63 832 13,1 4,05 4,05 697 9,5

330
5 1180 6,48 4,84 1115 22,4 5,78 4,56 994 18,2 4,29 3,99 738 10,6 3,50 3,50 602 7,3
3 985 5,71 4,20 982 18,0 5,10 3,95 877 14,6 3,80 3,46 654 8,6 3,04 3,04 523 5,7
1 770 4,77 3,44 820 13,1 4,27 3,24 734 10,7 3,20 2,83 550 6,3 2,49 2,49 428 4,0

Cooling emission of 3 row coil


Entering air temperature: 26°C – R.H.: 50% – Available pressure: 0Pa

WT: 7/12 °C WT: 8/13 °C WT: 10/15 °C WT: 12/17 °C


Model Vdc
Qv Pc Ps Qw Dp(c) Pc Ps Qw Dp(c) Pc Ps Qw Dp(c) Pc Ps Qw Dp(c)
ECM m /h3
kW kW l/h kPa kW kW l/h kPa kW kW l/h kPa kW kW l/h kPa
10 730 3,42 2,71 588 35,9 3,01 2,54 518 28,4 2,26 2,26 389 17,0 1,90 1,90 327 12,3
7,5
YHP 625 3,08 2,40 530 29,8 2,71 2,25 466 23,7 2,01 2,01 346 13,7 1,68 1,68 289 10,0

130
5 515 2,69 2,06 463 23,4 2,37 1,93 408 18,7 1,69 1,67 291 10,1 1,45 1,45 249 7,6
3 425 2,33 1,77 401 18,3 2,06 1,66 354 14,6 1,47 1,43 253 8,0 1,24 1,24 213 5,8
1 350 2,01 1,51 346 14,1 1,78 1,41 306 11,3 1,28 1,21 220 6,2 1,06 1,06 182 4,4
10 1250 5,61 4,56 965 33,6 4,92 4,29 846 26,5 3,81 3,81 655 16,7 3,19 3,19 549 12,0
7,5
YHP 1120 5,23 4,19 900 29,7 4,59 3,94 789 23,4 3,51 3,51 604 14,4 2,94 2,94 506 10,4

230
5 920 4,58 3,60 788 23,5 4,03 3,38 693 18,6 3,01 3,01 518 11,0 2,53 2,53 435 8,0
3 760 4,01 3,10 690 18,6 3,53 2,90 607 14,7 2,59 2,59 445 8,4 2,17 2,17 373 6,1
1 610 3,41 2,59 587 14,0 3,01 2,43 518 11,1 2,14 2,09 368 6,1 1,82 1,82 313 4,5
10 1450 6,61 5,35 1137 23,2 5,79 5,03 996 18,2 4,47 4,47 769 11,4 3,74 3,74 643 8,2
7,5 1425 6,53
YHP 5,28 1123 22,7 5,73 4,96 986 17,9 4,41 4,41 759 11,1 3,69 3,69 635 8,0

330
5 1180 5,76 4,57 991 18,2 5,06 4,28 870 14,4 3,81 3,81 655 8,6 3,19 3,19 549 6,2
3 985 5,08 3,96 874 14,6 4,46 3,71 767 11,5 3,31 3,31 569 6,7 2,77 2,77 476 4,9
1 770 4,24 3,24 729 10,6 3,74 3,04 643 8,4 2,65 2,61 456 4,5 2,27 2,27 390 3,4

Legend Note
Correction factors for different R.H. WT = Water temperature For air side
Pc = Cooling total emission pressure drop higher
R.H. WT: 7/12°C 8/13°C 10/15°C 12/17°C Ps = Cooling sensible emission than 0Pa use
Pc 0,95 0,94 1,00 1,00 Qw = Water flow correction factors
48% Ps 1,00 1,00 1,00 1,00 Dp(c) = Water pressure drop at page 40 and 41.
Pc 0,90 0,88 1,00 1,00 Vdc = Inverter Power
46% Ps 1,00 1,00 1,00 1,00 Qv = Air flow

34
YHP–ECM
YHP–ECM version

Cooling emission of 3 row coil


Entering air temperature: 25°C – R.H.: 50% – Available pressure: 0Pa

WT: 7/12 °C WT: 8/13 °C WT: 10/15 °C WT: 12/17 °C


Model Vdc
Qv Pc Ps Qw Dp(c) Pc Ps Qw Dp(c) Pc Ps Qw Dp(c) Pc Ps Qw Dp(c)
ECM m3/h kW kW l/h kPa kW kW l/h kPa kW kW l/h kPa kW kW l/h kPa
10 730 3,01 2,55 518 28,6 2,59 2,38 445 21,9 2,08 2,08 358 14,6 1,72 1,72 296 10,3
7,5
YHP 625 2,71 2,26 466 23,8 2,34 2,11 402 18,3 1,85 1,85 318 11,9 1,52 1,52 261 8,3

130
5 515 2,37 1,94 408 18,7 2,05 1,81 353 14,4 1,59 1,59 273 9,1 1,31 1,31 225 6,4
3 425 2,06 1,66 354 14,6 1,78 1,55 306 11,3 1,36 1,36 234 6,9 1,12 1,12 193 4,9
1 350 1,77 1,41 304 11,3 1,54 1,32 265 8,7 1,16 1,16 200 5,2 0,96 0,96 165 3,7
10 1250 4,93 4,29 848 26,7 4,23 4,02 728 20,3 3,50 3,50 602 14,4 2,88 2,88 495 10,1
7,5
YHP 1120 4,59 3,95 789 23,6 3,95 3,69 679 18,0 3,23 3,23 556 12,4 2,66 2,66 458 8,7

230
5 920 4,03 3,39 693 18,7 3,47 3,16 597 14,3 2,77 2,77 476 9,5 2,28 2,28 392 6,7
3 760 3,53 2,91 607 14,8 3,05 2,72 525 11,4 2,38 2,38 409 7,3 1,97 1,97 339 5,1
1 610 3,00 2,43 516 11,2 2,60 2,27 447 8,6 1,99 1,99 342 5,3 1,64 1,64 282 3,7
10 1450 5,79 5,03 996 18,4 4,96 4,71 853 13,9 4,10 4,10 705 9,8 3,37 3,37 580 6,9
7,5 1425 5,73
YHP 4,97 986 18,0 4,91 4,64 845 13,6 4,05 4,05 697 9,6 3,33 3,33 573 6,7

330
5 1180 5,05 4,29 869 14,5 4,34 4,01 746 11,0 3,51 3,51 604 7,4 2,88 2,88 495 5,2
3 985 4,46 3,72 767 11,6 3,84 3,47 660 8,9 3,04 3,04 523 5,8 2,50 2,50 430 4,1
1 770 3,73 3,04 642 8,5 3,22 2,84 554 6,5 2,49 2,49 428 4,1 2,05 2,05 353 2,9

Legend Note
Correction factors for different R.H. WT = Water temperature For air side
Pc = Cooling total emission pressure drop higher
R.H. WT: 7/12°C 8/13°C 10/15°C 12/17°C Ps = Cooling sensible emission than 0Pa use
Pc 0,95 0,94 1,00 1,00 Qw = Water flow correction factors
48% Ps 1,00 1,00 1,00 1,00 Dp(c) = Water pressure drop at page 40 and 41.
Pc 0,90 0,88 1,00 1,00 Vdc = Inverter Power
46% Ps 1,00 1,00 1,00 1,00 Qv = Air flow

35
YHP–ECM
YHP–ECM version

Cooling emission of 4 row coil


Entering air temperature: 27°C – R.H.: 50% – Available pressure: 0Pa

WT: 7/12 °C WT: 8/13 °C WT: 10/15 °C WT: 12/17 °C


Model Vdc
Qv Pc Ps Qw Dp(c) Pc Ps Qw Dp(c) Pc Ps Qw Dp(c) Pc Ps Qw Dp(c)
ECM m3/h kW kW l/h kPa kW kW l/h kPa kW kW l/h kPa kW kW l/h kPa
10 730 4,47 3,26 769 29,7 3,99 3,07 686 24,2 2,99 2,68 514 14,4 2,36 2,36 406 9,4
7,5
YHP 625 3,98 2,87 685 24,3 3,56 2,70 612 19,8 2,68 2,36 461 11,8 2,08 2,08 358 7,5

140
5 515 3,43 2,44 590 18,7 3,07 2,29 528 15,3 2,32 2,00 399 9,2 1,77 1,77 304 5,6
3 425 2,94 2,07 506 14,3 2,64 1,94 454 11,7 2,00 1,69 344 7,1 1,50 1,50 258 4,2
1 350 2,51 1,75 432 10,8 2,25 1,64 387 8,9 1,71 1,43 294 5,4 1,26 1,26 217 3,1
10 1250 7,35 5,37 1264 77,1 5,59 5,07 961 63,1 4,97 4,45 855 38,0 3,92 3,92 674 24,6
7,5
YHP 1120 6,80 4,93 1170 67,1 6,10 4,64 1049 55,1 4,61 4,07 793 33,3 3,59 3,59 617 21,1

240
5 920 5,89 4,20 1013 52,1 5,28 3,95 908 42,8 4,01 3,46 690 26,0 3,06 3,06 526 15,9
3 760 5,08 3,59 874 40,3 4,57 3,38 786 33,1 3,48 2,95 599 20,2 2,60 2,60 447 12,0
1 610 4,27 2,97 734 29,6 3,84 2,80 660 24,4 2,93 2,44 504 15,0 2,15 2,15 370 8,6
10 1450 8,24 6,07 1417 26,3 7,34 5,71 1262 21,4 5,46 4,99 939 12,5 4,38 4,38 753 8,4
7,5 1425 8,13
YHP 5,98 1398 25,8 7,25 5,63 1247 20,9 5,40 4,92 929 12,3 4,32 4,32 743 8,2

340
5 1180 7,09 5,15 1219 20,2 6,33 4,84 1089 16,5 4,74 4,23 815 9,7 3,71 3,71 638 6,3
3 985 6,19 4,44 1065 15,9 5,53 4,17 951 13,0 4,15 3,64 714 7,7 3,20 3,20 550 4,8
1 770 5,11 3,61 879 11,3 4,57 3,39 786 9,3 3,45 2,95 593 5,6 2,62 2,62 451 3,4

Cooling emission of 4 row coil


Entering air temperature: 26°C – R.H.: 50% – Available pressure: 0Pa

WT: 7/12 °C WT: 8/13 °C WT: 10/15 °C WT: 12/17 °C


Model Vdc
Qv Pc Ps Qw Dp(c) Pc Ps Qw Dp(c) Pc Ps Qw Dp(c) Pc Ps Qw Dp(c)
ECM m /h3
kW kW l/h kPa kW kW l/h kPa kW kW l/h kPa kW kW l/h kPa
10 730 3,97 3,07 683 24,2 3,50 2,88 602 19,2 2,57 2,57 442 11,0 2,16 2,16 372 8,0
7,5
YHP 625 3,55 2,70 611 19,8 3,12 2,53 537 15,7 2,22 2,18 382 8,5 1,90 1,90 327 6,4

140
5 515 3,06 2,30 526 15,2 2,70 2,15 464 12,2 1,93 1,85 332 6,6 1,61 1,61 277 4,8
3 425 2,63 1,95 452 11,7 2,32 1,82 399 9,3 1,67 1,57 287 5,2 1,37 1,37 236 3,6
1 350 2,24 1,65 385 8,8 1,98 1,54 341 7,1 1,44 1,32 248 4,0 1,16 1,16 200 2,7
10 1250 6,56 5,08 1128 63,1 5,79 4,77 996 50,3 4,14 4,13 712 27,5 3,58 3,58 616 21,0
7,5
YHP 1120 6,07 4,65 1044 55,0 5,37 4,37 924 44,0 3,85 3,78 662 24,1 3,28 3,28 564 18,0

240
5 920 5,26 3,96 905 42,7 4,65 3,72 800 34,2 3,35 3,21 576 18,9 2,80 2,80 482 13,6
3 760 4,54 3,38 781 33,0 4,02 3,17 691 26,5 2,92 2,74 502 14,8 2,38 2,38 409 10,3
1 610 3,82 2,80 657 24,3 3,39 2,63 583 19,5 2,47 2,27 425 11,1 1,97 1,97 339 7,4
10 1450 7,31 5,72 1257 21,4 6,42 5,36 1104 16,9 4,77 4,77 820 9,9 3,99 3,99 686 7,1
7,5 1425 7,22
YHP 5,64 1242 20,9 6,34 5,29 1090 16,5 4,70 4,70 808 9,6 3,94 3,94 678 6,9

340
5 1180 6,30 4,85 1084 16,4 5,54 4,54 953 13,0 4,04 4,04 695 7,4 3,39 3,39 583 5,3
3 985 5,50 4,18 946 13,0 4,85 3,91 834 10,3 3,43 3,37 590 5,5 2,92 2,92 502 4,1
1 770 4,55 3,40 783 9,3 4,01 3,18 690 7,4 2,86 2,73 492 4,0 2,37 2,39 407 2,9

Legend Note
Correction factors for different R.H. WT = Water temperature For air side
Pc = Cooling total emission pressure drop higher
R.H. WT: 7/12°C 8/13°C 10/15°C 12/17°C Ps = Cooling sensible emission than 0Pa use
Pc 0,95 0,94 1,00 1,00 Qw = Water flow correction factors
48% Ps 1,00 1,00 1,00 1,00 Dp(c) = Water pressure drop at page 40 and 41.
Pc 0,90 0,88 1,00 1,00 Vdc = Inverter Power
46% Ps 1,00 1,00 1,00 1,00 Qv = Air flow

36
YHP–ECM
YHP–ECM version

Cooling emission of 4 row coil


Entering air temperature: 25°C – R.H.: 50% – Available pressure: 0Pa

WT: 7/12 °C WT: 8/13 °C WT: 10/15 °C WT: 12/17 °C


Model Vdc
Qv Pc Ps Qw Dp(c) Pc Ps Qw Dp(c) Pc Ps Qw Dp(c) Pc Ps Qw Dp(c)
ECM m3/h kW kW l/h kPa kW kW l/h kPa kW kW l/h kPa kW kW l/h kPa
10 730 3,50 2,88 602 19,3 3,02 2,69 519 14,8 2,37 2,37 408 9,5 1,95 1,95 335 6,7
7,5
YHP 625 3,12 2,54 537 15,8 2,70 2,37 464 12,1 2,08 2,08 358 7,6 1,72 1,72 296 5,4

140
5 515 2,69 2,16 463 12,2 2,33 2,01 401 9,4 1,77 1,77 304 5,7 1,46 1,46 251 4,0
3 425 2,31 1,83 397 9,3 2,01 1,70 346 7,2 1,50 1,50 258 4,3 1,24 1,24 213 3,0
1 350 1,98 1,54 341 7,1 1,72 1,43 296 5,5 1,27 1,27 218 3,2 1,05 1,05 181 2,2
10 1250 5,79 4,78 996 50,6 5,02 4,47 863 39,1 3,93 3,93 676 25,1 3,25 3,25 559 17,7
7,5
YHP 1120 5,36 4,38 922 44,2 4,65 4,09 800 34,2 3,60 3,60 619 21,5 2,98 2,98 513 15,2

240
5 920 4,64 3,73 798 34,3 4,03 3,48 693 26,6 3,06 3,06 526 16,2 2,54 2,54 437 11,4
3 760 4,01 3,18 690 26,6 3,49 2,96 600 20,7 2,61 2,61 449 12,2 2,16 2,16 372 8,6
1 610 3,37 2,63 580 19,6 2,94 2,45 506 15,3 2,16 2,16 372 8,8 1,79 1,79 308 1,79
10 1450 6,42 5,37 1104 17,0 5,52 5,01 949 12,9 4,38 4,38 753 8,5 3,60 3,60 619 5,9
7,5 1425 6,34
YHP 5,29 1090 16,6 5,45 4,94 937 12,7 4,32 4,32 743 8,3 3,56 3,56 612 5,8

340
5 1180 5,53 4,55 951 13,1 4,77 4,24 820 10,0 3,71 3,71 638 6,4 3,06 3,06 526 4,5
3 985 4,84 3,92 832 10,3 4,18 3,65 719 7,9 3,20 3,20 550 4,9 2,64 2,64 454 3,4
1 770 4,00 3,19 688 7,4 3,46 2,97 595 5,7 2,62 2,62 451 3,4 2,16 2,16 372 2,4

Legend Note
Correction factors for different R.H. WT = Water temperature For air side
Pc = Cooling total emission pressure drop higher
R.H. WT: 7/12°C 8/13°C 10/15°C 12/17°C Ps = Cooling sensible emission than 0Pa use
Pc 0,95 0,94 1,00 1,00 Qw = Water flow correction factors
48% Ps 1,00 1,00 1,00 1,00 Dp(c) = Water pressure drop at page 40 and 41.
Pc 0,90 0,88 1,00 1,00 Vdc = Inverter Power
46% Ps 1,00 1,00 1,00 1,00 Qv = Air flow

37
YHP–ECM
YHP–ECM version

Heating emission of 3 row coil


Entering air temperature: 20°C – Available pressure: 0Pa

WT: 70/60 °C WT: 60/50 °C WT: 50/40 °C WT: 50/45 °C WT: 45/40 °C
Model Vdc
Qv Ph Qw Dp(c) Ph Qw Dp(c) Ph Qw Dp(c) Ph Qw Dp(c) Ph Qw Dp(c)
ECM m3/h kW l/h kPa kW l/h kPa kW l/h kPa kW l/h kPa kW l/h kPa
10 730 8,03 691 36,9 6,15 529 23,8 4,26 366 12,9 4,90 843 55,5 3,97 683 39,0
7,5
YHP 625 7,11 611 29,8 5,45 469 19,2 3,78 325 10,5 4,34 746 44,8 3,52 605 31,5

130
5 515 6,09 524 22,7 4,67 402 14,7 3,25 280 8,0 3,72 640 34,1 3,02 519 24,0
3 425 5,21 448 17,2 3,99 343 11,1 2,78 239 6,1 3,18 547 25,9 2,58 444 18,2
1 350 4,43 381 12,9 3,40 292 8,4 2,37 204 4,6 2,70 464 19,5 2,19 377 13,7
10 1250 13,06 1123 34,1 9,98 858 21,9 6,90 593 11,8 7,97 1371 51,2 6,45 1109 35,9
7,5
YHP 1120 12,02 1034 29,4 9,19 790 18,9 6,36 547 10,3 7,34 1262 44,3 5,94 1022 31,1

230
5 920 10,33 888 22,6 7,90 679 14,5 5,48 471 7,9 6,31 1085 33,9 5,11 879 23,8
3 760 8,88 764 17,3 6,80 585 11,1 4,72 406 6,1 5,42 932 26,0 4,39 755 18,3
1 610 7,42 638 12,6 5,69 489 8,1 3,95 340 4,4 4,53 779 19,0 3,67 631 13,3
10 1450 15,89 1367 24,9 12,13 1043 16,0 8,38 721 8,6 9,70 1668 37,5 7,84 1348 26,2
7,5 1425 15,68 1348
YHP 24,3 11,97 1029 15,6 8,27 711 8,4 9,58 1648 36,6 7,74 1331 25,6

330
5 1180 13,54 1164 18,8 10,34 889 12,1 7,16 616 6,5 8,27 1422 28,3 6,69 1151 19,8
3 985 11,71 1007 14,6 8,96 771 9,4 6,21 534 5,1 7,15 1230 21,9 5,79 996 15,4
1 770 9,57 823 10,2 7,33 630 6,6 5,08 437 3,6 5,84 1004 15,3 4,73 814 10,8

Heating emission of 4 row coil


Entering air temperature: 20°C – Available pressure: 0Pa

WT: 70/60 °C WT: 60/50 °C WT: 50/40 °C WT: 50/45 °C WT: 45/40 °C
Model Vdc
Qv Ph Qw Dp(c) Ph Qw Dp(c) Ph Qw Dp(c) Ph Qw Dp(c) Ph Qw Dp(c)
ECM m /h
3
kW l/h kPa kW l/h kPa kW l/h kPa kW l/h kPa kW l/h kPa
10 730 9,18 789 24,2 7,03 605 15,6 4,88 420 8,5 5,61 965 36,4 4,54 781 25,6
7,5
YHP 625 8,06 693 19,3 6,18 531 12,4 4,29 369 6,8 4,92 846 29,0 3,99 686 20,4

140
5 515 6,82 587 14,4 5,24 451 9,3 3,65 314 5,1 4,17 717 21,6 3,38 581 15,2
3 425 5,76 495 10,7 4,43 381 6,9 3,09 266 3,8 3,52 605 16,1 2,86 492 11,3
1 350 4,85 417 7,9 3,73 321 5,1 2,60 224 2,8 2,96 509 11,8 2,41 415 8,4
10 1250 15,00 1290 62,1 11,52 991 40,2 8,02 690 22 9,16 1576 93,3 7,43 1278 65,8
7,5
YHP 1120 13,73 1181 53,1 10,54 906 34,4 7,35 632 18,8 8,38 1441 79,8 6,80 1170 56,3

240
5 920 11,67 1004 39,9 8,96 771 25,8 6,26 538 14,2 7,13 1226 59,9 5,79 996 42,3
3 760 9,92 853 30,0 7,63 656 19,4 5,33 458 10,7 6,06 1042 45,0 4,92 846 31,8
1 610 8,19 704 21,4 6,31 543 13,9 4,41 379 7,7 5,01 862 32,2 4,07 700 22,8
10 1450 17,44 1500 22,6 13,33 1146 14,5 9,22 793 7,9 10,65 1832 34,0 8,62 1483 23,9
7,5 1425 17,19 1478
YHP 22,1 13,14 1130 14,2 9,10 783 7,7 10,50 1806 33,2 8,50 1462 2,33

340
5 1180 14,71 1265 16,8 11,26 968 10,8 7,80 671 5,9 8,99 1546 25,2 7,28 1252 17,7
3 985 12,63 1086 12,8 9,68 832 8,3 6,72 578 4,5 7,72 1328 19,3 6,25 1075 13,6
1 770 10,27 883 8,9 7,88 678 5,8 5,48 471 3,1 6,28 1080 13,4 5,09 875 9,4

Legend Note
WT = Water temperature For air side
Ph = Emission pressure drop higher
Qw = Water flow than 0Pa use
Dp(c) = Water pressure drop correction factors
Vdc = Inverter Power at page 40 and 41.
Qv = Air flow

38
YHP–ECM
YHP–ECM version

Heating emission of 1 row additional coil


Entering air temperature: 20°C – Available pressure: 0Pa

WT: 80/70 °C WT: 75/65 °C WT: 70/60 °C WT: 65/55 °C WT: 60/50 °C WT: 55/45 °C
Model Vdc
Qv Ph Qw Dp(c) Ph Qw Dp(c) Ph Qw Dp(c) Ph Qw Dp(c) Ph Qw Dp(c) Ph Qw Dp(c)
ECM m3/h kW l/h kPa kW l/h kPa kW l/h kPa kW l/h kPa kW l/h kPa kW l/h kPa
10 730 4,28 368 28,8 3,85 331 24,4 3,43 295 20,2 3,01 259 16,3 2,59 223 12,7 2,18 187 9,5
7,5
YHP 625 3,94 339 25,0 3,56 306 21,1 3,17 273 17,5 2,78 239 14,1 2,39 206 11,0 2,01 173 8,2

1
5 515 3,46 298 19,9 3,12 268 16,8 2,78 239 13,9 2,44 210 11,2 2,10 181 8,8 1,76 151 6,6
3 425 3,03 261 15,7 2,73 235 13,3 2,44 210 11,0 2,14 184 8,9 1,84 158 7,0 1,55 133 5,2
1 350 2,65 228 12,4 2,39 206 10,5 2,13 183 8,7 1,87 161 7,0 1,61 138 5,5 1,36 117 4,1
10 1250 6,65 572 17,2 5,98 514 14,5 5,31 457 11,9 4,64 399 9,6 3,97 341 7,4 3,3 284 5,4
7,5
YHP 1120 6,21 534 15,3 5,58 480 12,9 4,96 427 10,6 4,33 372 8,5 3,71 319 6,6 3,09 266 4,8

2
5 920 5,59 481 12,7 5,02 432 10,7 4,46 384 8,8 3,90 335 7,1 3,34 287 5,5 2,79 240 4,0
3 760 4,92 423 10,2 4,43 381 8,5 3,93 338 7,0 3,44 296 5,7 2,95 254 4,4 2,46 212 3,2
1 610 4,23 364 7,8 3,81 328 6,6 3,38 291 5,4 2,96 255 4,3 2,54 218 3,4 2,12 182 2,5
10 1450 7,83 673 19,2 7,05 606 16,2 6,28 540 13,4 5,50 473 10,8 4,73 407 8,4 3,96 341 6,3
7,5 1425 7,78
YHP 669 19,0 7,01 603 16,0 6,24 537 13,3 5,47 470 10,7 4,70 404 8,3 3,94 339 6,2

3
5 1180 6,91 594 15,4 6,22 535 13,0 5,54 476 10,8 4,86 418 8,7 4,18 359 6,8 3,5 301 5,0
3 985 6,11 525 12,4 5,51 474 10,5 4,91 422 8,7 4,30 370 7,0 3,70 318 5,5 3,1 267 4,1
1 770 5,17 445 9,2 4,66 401 7,8 4,15 357 6,5 3,64 313 5,2 3,13 269 4,1 2,63 226 3,0

Heating emission of 2 row additional coil


Entering air temperature: 20°C – Available pressure: 0Pa

WT: 65/55 °C WT: 60/50 °C WT: 55/45 °C WT: 50/40 °C WT: 45/40 °C WT: 45/35 °C
Model Vdc
Qv Ph Qw Dp(c) Ph Qw Dp(c) Ph Qw Dp(c) Ph Qw Dp(c) Ph Qw Dp(c) Ph Qw Dp(c)
ECM m /h
3
kW l/h kPa kW l/h kPa kW l/h kPa kW l/h kPa kW l/h kPa kW l/h kPa
10 730 5,22 449 7,5 4,49 386 5,9 3,77 324 4,4 3,05 262 3,1 2,92 502 9,7 2,33 200 2,0
7,5
YHP 625 4,69 403 6,3 4,04 347 4,9 3,40 292 3,7 2,75 237 2,6 2,62 451 8,1 2,10 181 1,6

1
5 515 4,10 353 4,9 3,53 304 3,9 2,97 255 2,9 2,41 207 2,0 2,29 394 6,4 1,84 158 1,3
3 425 3,57 307 3,9 3,08 265 3,0 2,59 223 2,3 2,10 181 1,6 1,99 342 5,0 1,61 138 1,0
1 350 3,09 266 3,0 2,67 230 2,3 2,24 193 1,8 1,82 157 1,2 1,73 298 3,9 1,40 120 0,8
10 1250 8,50 731 24,7 7,35 632 19,4 6,19 532 14,6 5,04 433 10,3 4,76 819 32,0 3,88 334 6,7
7,5
YHP 1120 7,91 680 21,7 6,83 587 17,1 5,76 495 12,9 4,69 403 9,1 4,42 760 28,1 3,61 310 5,9

2
5 920 6,92 595 17,2 5,98 514 13,5 5,05 434 10,2 4,11 353 7,2 3,87 666 22,2 3,17 273 4,7
3 760 6,06 521 13,6 5,24 451 10,7 4,42 380 8,1 3,60 310 5,7 3,39 583 17,6 2,78 239 3,7
1 610 5,17 445 10,3 4,47 384 8,1 3,77 324 6,1 3,08 265 4,3 2,89 497 13,3 2,38 205 2,8
10 1450 10,32 888 47,3 8,94 769 37,3 7,55 649 28,2 6,17 531 20,1 5,78 994 61,2 4,78 411 13,1
7,5 1425 10,20 877
YHP 46,3 8,83 759 36,5 7,47 642 27,6 6,10 525 19,7 5,71 982 60,0 4,73 407 12,8

3
5 1180 8,97 771 37,0 7,77 668 29,1 6,57 565 22,0 5,37 462 15,7 5,03 865 47,8 4,17 359 10,3
3 985 7,91 680 29,6 6,85 589 23,4 5,80 499 17,7 4,74 408 12,6 4,43 762 38,3 3,68 316 8,2
1 770 6,62 569 21,6 5,73 493 17,1 4,85 417 12,9 3,97 341 9,2 3,71 638 28,0 3,09 266 6,0

Legend Note
WT = Water temperature For air side
Ph = Emission pressure drop higher
Qw = Water flow than 0Pa use
Dp(c) = Water pressure drop correction factors
Vdc = Inverter Power at page 40 and 41.
Qv = Air flow

39
YHP–ECM
YHP–ECM version

Air flow and emission correction factors


with different available pressure

Emission correction factors


for high speed figures at 10 V signal

Qv (m3/h) K1 K2
Model Vdc
Ap (Pa) Ap (Pa) Ap (Pa)
ECM 0 10 20 30 40 50 60 70 80 0 10 20 30 40 50 60 70 80 0 10 20 30 40 50 60 70 80
10 730 695 648 595 540 480 423 355 280 1,00 0,97 0,92 0,87 0,81 0,75 0,68 0,59 0,49 1,00 0,96 0,91 0,85 0,79 0,72 0,65 0,56 0,46
9,5 720 670 620 570 510 450 387 315 240 0,99 0,94 0,89 0,84 0,78 0,71 0,63 0,54 0,43 0,99 0,94 0,88 0,82 0,76 0,68 0,60 0,51 0,40
9 692 647 595 540 480 420 350 275 190 0,96 0,92 0,87 0,81 0,75 0,68 0,59 0,48 0,36 0,96 0,91 0,85 0,79 0,72 0,65 0,56 0,45 0,33
8,5 661 620 570 510 450 385 310 280 125 0,93 0,89 0,84 0,78 0,71 0,63 0,53 0,49 0,25 0,93 0,88 0,82 0,76 0,68 0,60 0,50 0,46 0,23
8 650 600 543 485 420 355 273 180 − 0,92 0,87 0,82 0,75 0,68 0,59 0,48 0,34 − 0,91 0,86 0,79 0,73 0,65 0,56 0,45 0,31 −
7,5 625 575 520 460 395 317 230 137 − 0,90 0,85 0,79 0,72 0,64 0,54 0,42 0,27 − 0,89 0,83 0,77 0,70 0,61 0,51 0,39 0,24 −

YHP 7 692 550 492 430 360 280 185 − − 0,96 0,82 0,76 0,69 0,60 0,49 0,35 − − 0,96 0,80 0,73 0,66 0,57 0,46 0,32 − −

1
6,5 573 520 465 400 320 235 130 − − 0,85 0,79 0,73 0,65 0,55 0,43 0,26 − − 0,83 0,77 0,70 0,62 0,52 0,40 0,23 − −
6 555 500 440 367 285 180 − − − 0,83 0,77 0,70 0,61 0,50 0,34 − − − 0,81 0,74 0,67 0,58 0,47 0,31 − − −
5,5 540 476 410 332 245 140 − − − 0,81 0,74 0,66 0,56 0,44 0,27 − − − 0,79 0,71 0,63 0,53 0,41 0,25 − − −
5 515 450 380 296 200 − − − − 0,78 0,71 0,63 0,51 0,37 − − − − 0,76 0,68 0,60 0,48 0,34 − − − −
4 472 400 320 226 105 − − − − 0,74 0,65 0,55 0,41 0,21 − − − − 0,71 0,62 0,52 0,38 0,19 − − − −
3 425 347 252 132 − − − − − 0,68 0,58 0,45 0,26 − − − − − 0,65 0,55 0,42 0,24 − − − − −
2 384 295 187 − − − − − − 0,63 0,51 0,35 − − − − − − 0,60 0,48 0,32 − − − − − −
1 350 250 115 − − − − − − 0,59 0,45 0,23 − − − − − − 0,56 0,42 0,21 − − − − − −
10 1250 1195 1140 1075 1010 940 860 780 680 1,00 0,97 0,94 0,91 0,87 0,83 0,78 0,73 0,66 1,00 0,97 0,93 0,89 0,85 0,80 0,75 0,69 0,62
9,5 1245 1075 1115 1050 980 900 820 722 715 1,00 0,96 0,93 0,89 0,85 0,80 0,75 0,69 0,68 1,00 0,95 0,92 0,87 0,83 0,78 0,72 0,65 0,65
9 1220 1155 1090 1020 945 860 770 665 535 0,98 0,95 0,91 0,87 0,83 0,78 0,72 0,65 0,55 0,98 0,94 0,90 0,86 0,81 0,75 0,69 0,61 0,51
8,5 1200 1135 1065 990 907 815 715 593 440 0,97 0,94 0,90 0,86 0,81 0,75 0,68 0,59 0,47 0,97 0,93 0,88 0,84 0,78 0,72 0,65 0,55 0,43
8 1160 1092 1020 940 853 755 645 510 315 0,95 0,92 0,87 0,83 0,77 0,71 0,63 0,53 0,36 0,94 0,90 0,86 0,80 0,74 0,67 0,59 0,49 0,32
7,5 1120 1048 970 890 800 695 570 410 − 0,93 0,89 0,85 0,80 0,74 0,67 0,58 0,44 − 0,92 0,87 0,82 0,77 0,71 0,63 0,54 0,40 −

YHP 7 1080 1005 927 840 740 630 490 300 − 0,91 0,87 0,82 0,77 0,70 0,62 0,51 0,34 − 0,89 0,85 0,79 0,73 0,66 0,58 0,47 0,31 −

2
6,5 1040 960 880 785 685 560 400 − − 0,89 0,84 0,79 0,73 0,66 0,57 0,44 − − 0,87 0,82 0,76 0,70 0,62 0,53 0,40 − −
6 1000 920 835 735 625 485 285 − − 0,86 0,82 0,76 0,70 0,62 0,51 0,33 − − 0,84 0,79 0,73 0,66 0,58 0,47 0,29 − −
5,5 960 880 785 685 560 400 − − − 0,84 0,79 0,73 0,66 0,57 0,44 − − − 0,82 0,76 0,70 0,62 0,53 0,40 − − −
5 920 830 737 625 495 300 − − − 0,82 0,76 0,70 0,62 0,52 0,34 − − − 0,79 0,73 0,66 0,58 0,48 0,31 − − −
4 840 750 640 510 340 − − − − 0,77 0,71 0,63 0,53 0,38 − − − − 0,73 0,67 0,59 0,49 0,34 − − − −
3 760 655 535 370 − − − − − 0,71 0,64 0,55 0,41 − − − − − 0,68 0,60 0,51 0,37 − − − − −
2 680 560 400 160 − − − − − 0,66 0,57 0,44 0,20 − − − − − 0,62 0,53 0,40 0,18 − − − − −
1 610 475 280 − − − − − − 0,61 0,50 0,32 − − − − − − 0,57 0,46 0,29 − − − − − −
10 1450 1395 1350 1310 1260 1205 1145 1075 990 1,00 0,97 0,95 0,93 0,91 0,88 0,85 0,82 0,77 1,00 0,97 0,95 0,92 0,90 0,87 0,83 0,79 0,74
9,5 1445 1390 1345 1295 1245 1185 1115 1030 935 1,00 0,97 0,95 0,93 0,90 0,87 0,84 0,79 0,74 1,00 0,97 0,94 0,92 0,89 0,85 0,81 0,76 0,71
9 1440 1385 1340 1280 1225 1155 1075 975 850 0,99 0,97 0,95 0,92 0,89 0,86 0,82 0,76 0,69 0,99 0,96 0,94 0,91 0,88 0,84 0,79 0,73 0,65
8,5 1435 1380 1335 1270 1195 1110 1015 900 750 0,99 0,97 0,95 0,91 0,88 0,83 0,78 0,72 0,63 0,99 0,96 0,94 0,90 0,86 0,81 0,76 0,69 0,59
8 1430 1370 1305 1230 1145 1050 940 800 630 0,99 0,96 0,93 0,90 0,85 0,80 0,74 0,66 0,55 0,99 0,96 0,92 0,88 0,83 0,78 0,71 0,62 0,51
7,5 1425 1345 1265 1180 1085 970 845 690 500 0,99 0,95 0,91 0,87 0,82 0,76 0,69 0,59 0,46 0,99 0,94 0,90 0,85 0,80 0,73 0,65 0,55 0,42

YHP 7 1360 1290 1210 1120 1015 895 760 590 − 0,96 0,92 0,89 0,84 0,78 0,72 0,63 0,52 − 0,95 0,91 0,87 0,82 0,76 0,68 0,60 0,48 −

3
6,5 1320 1240 1160 1060 955 825 660 460 − 0,94 0,90 0,86 0,81 0,75 0,67 0,57 0,43 − 0,93 0,89 0,84 0,78 0,72 0,64 0,53 0,39 −
6 1270 1190 1100 995 880 735 570 − − 0,91 0,88 0,83 0,77 0,71 0,62 0,51 − − 0,90 0,86 0,81 0,74 0,67 0,58 0,47 − −
5,5 1220 1140 1040 930 800 645 450 − − 0,89 0,85 0,80 0,74 0,66 0,56 0,42 − − 0,87 0,83 0,77 0,70 0,62 0,52 0,38 − −
5 1180 1080 980 865 725 545 − − − 0,87 0,82 0,76 0,70 0,61 0,49 − − − 0,85 0,79 0,73 0,66 0,57 0,45 − − −
4 1080 982 870 730 560 350 − − − 0,82 0,77 0,70 0,62 0,50 0,34 − − − 0,79 0,74 0,67 0,58 0,46 0,31 − − −
3 985 875 745 570 350 − − − − 0,77 0,70 0,63 0,51 0,34 − − − − 0,74 0,67 0,59 0,47 0,31 − − − −
2 890 760 595 − − − − − − 0,71 0,63 0,53 − − − − − − 0,68 0,60 0,49 − − − − − −
1 770 600 405 − − − − − − 0,64 0,53 0,39 − − − − − − 0,60 0,49 0,35 − − − − − −

Legend
Qv = Air flow
K1 = Correction factors for Total cooling emission
K2 = Correction factors for Sensible cooling emission and Heating emission
Ap = Available pressure
Vdc = Inverter Power

40
YHP–ECM
YHP–ECM version

Air flow table, correction factors for emission


and Watts absorbed by the motor with different available pressures

Qv (m3/h) Qv % W
Model Vdc
Ap (Pa) Ap (Pa) Ap (Pa)
ECM 0 10 20 30 40 50 60 70 80 0 10 20 30 40 50 60 70 80 0 10 20 30 40 50 60 70 80
10 730 695 648 595 540 480 423 355 280 1,00 0,95 0,89 0,82 0,74 0,66 0,58 0,49 0,38 80 77 73 68 63 59 54 49 44
9,5 720 670 620 570 510 450 387 315 240 0,99 0,92 0,85 0,78 0,70 0,62 0,53 0,43 0,33 75 71 67 63 58 53 49 44 40
9 692 647 595 540 480 420 350 275 190 0,95 0,89 0,82 0,74 0,66 0,58 0,48 0,38 0,26 69 65 61 57 53 49 44 40 35
8,5 661 620 570 510 450 385 310 280 125 0,91 0,85 0,78 0,70 0,62 0,53 0,42 0,38 0,17 63 60 56 52 48 44 39 38 30
8 650 600 543 485 420 355 273 180 − 0,89 0,82 0,74 0,66 0,58 0,49 0,37 0,25 − 59 55 51 47 43 40 35 31 −
7,5 625 575 520 460 395 317 230 137 − 0,86 0,79 0,71 0,63 0,54 0,43 0,32 0,19 − 54 51 47 43 39 35 31 27 −

YHP 7 692 550 492 430 360 280 185 − − 0,95 0,75 0,67 0,59 0,49 0,38 0,25 − − 55 46 43 39 35 32 27 − −

1
6,5 573 520 465 400 320 235 130 − − 0,78 0,71 0,64 0,55 0,44 0,32 0,18 − − 44 42 39 36 32 28 24 − −
6 555 500 440 367 285 180 − − − 0,76 0,68 0,60 0,50 0,39 0,25 − − − 41 38 35 32 29 25 − − −
5,5 540 476 410 332 245 140 − − − 0,74 0,65 0,56 0,45 0,34 0,19 − − − 38 35 32 29 25 22 − − −
5 515 450 380 296 200 − − − − 0,71 0,62 0,52 0,41 0,27 − − − − 35 32 29 26 22 − − − −
4 472 400 320 226 105 − − − − 0,65 0,55 0,44 0,31 0,14 − − − − 29 26 23 20 17 − − − −
3 425 347 252 132 − − − − − 0,58 0,48 0,35 0,18 − − − − − 24 21 18 15 − − − − −
2 384 295 187 − − − − − − 0,53 0,40 0,26 − − − − − − 20 17 15 − − − − − −
1 350 250 115 − − − − − − 0,48 0,34 0,16 − − − − − − 17 14 12 − − − − − −
10 1250 1195 1140 1075 1010 940 860 780 680 1,00 0,96 0,91 0,86 0,81 0,75 0,69 0,62 0,54 132 132 131 125 119 113 106 99 91
9,5 1245 1075 1115 1050 980 900 820 722 715 1,00 0,94 0,89 0,84 0,78 0,72 0,66 0,58 0,57 132 128 123 117 111 104 97 89 89
9 1220 1155 1090 1020 945 860 770 665 535 0,98 0,92 0,87 0,82 0,76 0,69 0,62 0,53 0,43 126 121 115 109 103 96 89 81 71
8,5 1200 1135 1065 990 907 815 715 593 440 0,96 0,91 0,85 0,79 0,73 0,65 0,57 0,47 0,35 119 113 107 101 94 87 80 71 61
8 1160 1092 1020 940 853 755 645 510 315 0,93 0,87 0,82 0,75 0,68 0,60 0,52 0,41 0,25 109 103 97 91 85 78 70 61 49
7,5 1120 1048 970 890 800 695 570 410 − 0,90 0,84 0,78 0,71 0,64 0,56 0,46 0,33 − 99 93 88 82 76 68 60 51 −

YHP 7 1080 1005 927 840 740 630 490 300 − 0,86 0,80 0,74 0,67 0,59 0,50 0,39 0,24 − 88 83 78 72 66 60 52 42 −

2
6,5 1040 960 880 785 685 560 400 − − 0,83 0,77 0,70 0,63 0,55 0,45 0,32 − − 78 73 69 64 58 52 44 − −
6 1000 920 835 735 625 485 285 − − 0,80 0,74 0,67 0,59 0,50 0,39 0,23 − − 71 67 62 57 51 44 35 − −
5,5 960 880 785 685 560 400 − − − 0,77 0,70 0,63 0,55 0,45 0,32 − − − 64 60 55 50 44 37 − − −
5 920 830 737 625 495 300 − − − 0,74 0,66 0,59 0,50 0,40 0,24 − − − 58 53 49 44 38 30 − − −
4 840 750 640 510 340 − − − − 0,67 0,60 0,51 0,41 0,27 − − − − 47 43 38 33 28 − − − −
3 760 655 535 370 − − − − − 0,61 0,52 0,43 0,30 − − − − − 37 33 29 24 − − − − −
2 680 560 400 160 − − − − − 0,54 0,45 0,32 0,13 − − − − − 29 25 21 16 − − − − −
1 610 475 280 − − − − − − 0,49 0,38 0,22 − − − − − − 23 19 16 − − − − − −
10 1450 1395 1350 1310 1260 1205 1145 1075 990 1,00 0,96 0,93 0,90 0,87 0,83 0,79 0,74 0,68 136 136 136 136 136 136 134 130 124
9,5 1445 1390 1345 1295 1245 1185 1115 1030 935 1,00 0,96 0,93 0,89 0,86 0,82 0,77 0,71 0,64 136 136 136 136 134 131 126 121 114
9 1440 1385 1340 1280 1225 1155 1075 975 850 0,99 0,96 0,92 0,88 0,84 0,80 0,74 0,67 0,59 134 134 134 131 128 123 118 111 101
8,5 1435 1380 1335 1270 1195 1110 1015 900 750 0,99 0,95 0,92 0,88 0,82 0,77 0,70 0,62 0,52 132 132 130 126 121 115 108 99 88
8 1430 1370 1305 1230 1145 1050 940 800 630 0,99 0,94 0,90 0,85 0,79 0,72 0,65 0,55 0,43 129 125 121 116 110 103 95 86 74
7,5 1425 1345 1265 1180 1085 970 845 690 500 0,98 0,93 0,87 0,81 0,75 0,67 0,58 0,48 0,34 122 116 111 105 98 91 82 73 62

YHP 7 1360 1290 1210 1120 1015 895 760 590 − 0,94 0,89 0,83 0,77 0,70 0,62 0,52 0,41 − 111 106 101 95 88 81 72 62 −

3
6,5 1320 1240 1160 1060 955 825 660 460 − 0,91 0,86 0,80 0,73 0,66 0,57 0,46 0,32 − 102 97 92 86 80 72 62 51 −
6 1270 1190 1100 995 880 735 570 − − 0,88 0,82 0,76 0,69 0,61 0,51 0,39 − − 93 88 83 77 70 62 54 − −
5,5 1220 1140 1040 930 800 645 450 − − 0,84 0,79 0,72 0,64 0,55 0,44 0,31 − − 84 80 75 69 62 54 45 − −
5 1180 1080 980 865 725 545 − − − 0,81 0,74 0,68 0,60 0,50 0,38 − − − 76 71 66 61 54 46 − − −
4 1080 982 870 730 560 350 − − − 0,74 0,68 0,60 0,50 0,39 0,24 − − − 62 58 53 47 41 33 − − −
3 985 875 745 570 350 − − − − 0,68 0,60 0,51 0,39 0,24 − − − − 49 45 40 35 29 − − − −
2 890 760 595 − − − − − − 0,61 0,52 0,41 − − − − − − 39 35 31 − − − − − −
1 770 600 405 − − − − − − 0,53 0,41 0,28 − − − − − − 30 26 21 − − − − − −

Legend
Qv = Air flow
Qv % = Correction factors for Air flow
W = Watts absorbed by the motor
Ap = Available pressure
Vdc = Inverter Power

41
YHP–ECM
YHP–ECM version

Water pressure drop

3 row coil 4 row coil


Dp - kPa Dp - kPa
50 50

40 40

30 30
240

20 20

130

330
10 230 10 340
9 9
8 8
7 7
6 6
140
5 5

4 4

3 3

2 2

Water Water
1 flow (l/h) 1 flow (l/h)
100 200 300 400 600 800 1000 1500 2000 100 200 300 400 600 800 1000 1500 2000

The water pressure drop figures


refer to a mean water temperature of 10°C; °C 20 30 40 50 60 70 80
for different temperatures, multiply
the pressure drop figures by the correction factors K. K 0,94 0,90 0,86 0,82 0,78 0,74 0,70

1 row additional coil 2 row additional coil


Dp - kPa Dp - kPa
60 60 60
50 50 50

40 40 40

30 30 30 3
4
20 20 20

10 10 10 2
9 9 9
8 1 8 8 1
7 3 7 7 3
6 6 6
5 5 5

4 4 4

3 3 3 1
2 2
2 2 2

Water Water
1 flow (l/h) 1 1 flow (l/h)
50 60 80 100 200 300 400 600 800 1000 50 60 50
80 60100 80 100 200 300
200 400300 600
400 800
600
1000800 1000

The water pressure drop figures


refer to a mean water temperature of 65°C; °C 40 50 60 70 80
for different temperatures, multiply
the pressure drop figures by the correction factors K. K 1,14 1,08 1,02 0,96 0,90

42
Accessories and Controls for:

YFCN–ECM version with centrifugal fan

YHP–ECM version with high pressure centrifugal fan

43
Accessories
YFCN–ECM / YHP–ECM
for YFCN–ECM / YHP–ECM version

MBV
main coil 3 way valve
Control valve kit:
3 way valve, ON-OFF,
with electric motor and mounting kit
with micrometric lockshield valve.

Version YFCN–ECM
YHP–ECM
Model VC – HC – VCB – CD
Dimensions ± 10 mm

Mod. Dimensions (mm) Valve Micrometric lockshield valve Code


YFCN YHP A B C D E DN (Ø) Kvs DN (Ø) Kvs FITTED NOT FITTED
2–4 1 25 85 190 290 105 15 1/2” 1,6 15 1/2” F 2 9066561 9066560
6–7 2 25 85 190 290 105 20 3/4” 2,5 15 1/2” F 2 9060471 9060474
9 3 50 120 185 290 105 20 3/4” 2,5 15 1/2” F 2 9060471 9060474

ABV
additional coil 3 way valve
Control valve kit:
3 way valve, ON-OFF,
with electric motor and mounting kit
with micrometric lockshield valve.

Version YFCN–ECM
YHP–ECM
Model VC – HC – VCB – CD
Dimensions ± 10 mm

Mod. Dimensions (mm) Valve Micrometric lockshield valve Code


YFCN YHP A B C D DN (Ø) Kvs DN (Ø) Kvs FITTED NOT FITTED
2÷7 1–2 120 195 240 340 15 1/2” 1,6 15 1/2” F 2 9060472 9060475
9 3 135 200 235 330 15 1/2” 1,6 15 1/2” F 2 9060472 9060475

Kvs 2 Kvs 2,5


Dp - kPa Kvs 1,6
40

30

20

10
9
8
7
6
5
4

Water
1 flow (l/h)
100 200 300 400 600 800 1000 2000 3000 4000

44
Accessories
YFCN–ECM / YHP–ECM
for YFCN–ECM / YHP–ECM version

VS
simplified kit for 3 way valve
(concealed model only)
3 way valve, (ON-OFF)
with electric motor and mounting kit.
Valve with flat connection
without micrometric lockshield valve.

Version YFCN–ECM
YHP–ECM
Model CD
Dimensions ± 10 mm

Dimensions (mm) Main Additional


Mod. Main Additional Valve Code Valve Code
C
YFCN YHP A1 A2 B1 B2 DN (Ø) Kvs FITTED NOT FITTED DN (Ø) Kvs FITTED NOT FITTED
2–4 1 152 270 185 330 116 15 1/2” 1,6 9066571 9066570
6–7 2 152 268 185 330 124 20 3/4” 2,5 9060484 9060481 15 1/2” 1,6 9060483 9060480
9 3 177 270 210 327 124 20 3/4” 2,5 9060484 9060481

V2
2 way valve
for main and additional coil
Control valve kit:
2 way valve, ON-OFF,
with electric motor and mounting kit.

Version YFCN–ECM
YHP–ECM
Model VC – HC – VCB – CD
Dimensions ± 10 mm

Dimensions (mm) Main Additional


Mod. Main Additional Valve Code Valve Code
YFCN YHP A C D E H DN (Ø) Kvs FITTED NOT FITTED DN (Ø) Kvs FITTED NOT FITTED
2–4 1 149 180 438 186 456 15 1/2” 1,7 9060476 9060478
6–7 2 150 181 438 186 456 20 3/4” 2,8 9060477 9060479 15 1/2” 1,7 9060476 9060478
9 3 176 175 422 210 440 20 3/4” 2,8 9060477 9060479

Kvs 1,7 Kvs 2,5


Dp - kPa Kvs 1,6 Kvs 2,8
40

30

20

10
9
8
7
6
5
4

Water
1 flow (l/h)
100 200 300 400 600 800 1000 2000 3000 4000

45
Accessories
YFCN–ECM / YHP–ECM
for YFCN–ECM / YHP–ECM version

3 way double valve kit for 4 tube installation and single coil
The kit consists of:
• 2 special 3 way valves;
• 2 230 Volt ON-OFF actuators with internal safety micro switch;
• insulated pipe kit;
• external valve insulation sleeve.

Version YFCN–ECM
YHP–ECM
Model VC – HC – VCB – CD

–ECM Mod. FITTED NOT FITTED


Ø Kvs
YFCN YHP Code Type Code Type
1÷9 1÷3 3/4” 2,2 9066572W V3M4X2 9066562W V3S4X2

The kit uses a special 3 way valve which allows the transformation Kvs 2,2
Dp - kPa
of the fan coil, equipped with one single coil, into a 4 tube 40
installation. 30
The new 4X2 valve has been designed to keep the water flow
20
between flow and return perfectly separated, allowing its use
in parallel.
Therefore, it can be used on 4 pipe fan coil systems with one 10
9
single heat-exchange coil on board the fan coil. 8
7
6
5
Cold water
4

Hot water Single coil 2

Water
1 flow (l/h)
100 200 300 400 600 800 1000 2000 3000 4000

Double actuator electrical connections

COLD COLD

230 V a.c.

HOT HOT

230 V a.c.

46
Accessories
YFCN–ECM / YHP–ECM
for YFCN–ECM / YHP–ECM version

Balancing valves independent from the system pressure


• The balancing valve and a combined 2 way valve allow the regulation of the water
flow value autonomously, regardless of the system pressure, and the control of the
flow by using an ON/OFF electro-thermal actuator.
• The balancing valve allows you to balance the hydraulic system by supplying the
required water flow, for each fan- coil, and to maintain it even under partial load
conditions.
• A graduated ring nut placed under the valve allows you to set the flow rate value
and also allows direct reading of the set value.

Valve operation logic

• “p1” is the valve inlet pressure.


• “p3” is the outlet pressure.
• “p2” is the diaphragm activation pressure,
which allows differential pressure “p2” – “p3”
to be maintained at a constant value, in order
to guarantee the water to flow at the set value.

The minimum differential pressure “p1” – ”p3”,


required to guarantee the correct value of the
set water flow rate, is indicated in the diagrams
on page 48. This is an essential factor to size the
system pressure drop and pump pressure head.
The flow rate is kept at a constant value only if
the valve pressure drop is higher than the indicated value.

Minimum operating differential pressure

The minimum differential pressure and the balancing valve pressure drop must be considered to size the system
pumps.
Flow rate is constant if the pressure drop is higher than that indicated in the diagrams on page 48.
The following diagram shows an example of the flow rate trend according to the pressure drop and calibration
required.

Example DN 10 Model

LEGEND:
Qw = Water flow rate
Pd = Min. differential pressure
“p1” – ”p3” (bar)
Q1 = Area
with inconstant water flow
Q2 = Area
with constant water flow
S1 = Position of the adjustment valve
plunger
M1 = Position of the knob

47
Accessories
YFCN–ECM / YHP–ECM
for YFCN–ECM / YHP–ECM version

The valve upstream-downstream minimum differential pressure (“p1” – “p3”), which depends on the valve calibration
value, must be exceeded to access the constant flow rate field.

DN 10 Model DN 15 Model

DN 20 Model
LEGEND:
Pd = Min. differential pressure “p1” – ”p3” (bar)

E.g., when sizing the system pump, in which the DN 10 valves will be
installed and in which 210 l/h are constantly required for each device,
consider a useful pressure of 0.3 bar (to compensate the pressure drop
of the valve) for each balancing valve. Therefore, the pressure drop
values produced by the system balancing valves must be summed and
the pump must be sized to produce a pressure equal to or greater than
the value obtained previously.

Benefits
• Reduced dimensions.
• Easy installation on 2 or 4 pipe devices.
• Pre-regulation
of the nominal value set even with installed actuator.
• Easy display of the nominal value set.
Nominal values are indicated in 10 l/h without any conversion.
• Guarantee of constant flow rate set even with partial loads.
• Pre-regulation
can be blocked and leaded with the locking ring.

Technical features
DN Model Flow Rate Range (l/h) Kvs
DN 10 90 – 450 1,1
DN 15 150 – 1050 1,8
DN 20 180 – 1300 2,5

Operation limits of the balancing valves


• Maximum operating temperature 120°C • Minimum operating temperature -10°C
• Maximum operating pressure 16 bar • Maximum differential pressure 4 bar
• Maximum % of water/glycol mixture 50%

48
Accessories
YFCN–ECM / YHP–ECM
for YFCN–ECM / YHP–ECM version

Balancing valves for main coil

52

48
2 way valve for main coil and assembly kit.
The valve is supplied equipped with
230 Volt electro-thermal actuator for the ON/OFF control.
255
215

95
145
Version YFCN–ECM
YHP–ECM
Model VC – HC – VCB – CD

–ECM Mod. VALVE FITTED NOT FITTED


YFCN YHP DN Ø Range Code Type Code Type
1÷3 1 10 1/2” 90 – 450 9066660 V2OVBPM 90-450 9066650 V2OVBPS 90-450
4÷7 2–3 15 3/4” 150 – 1050 9066661 V2OVBPM 150-1050 9066651 V2OVBPS 150-1050
8–9 – 20 1” 180 – 1300 9066662 V2OVBPM 180-1300 9066652 V2OVBPS 180-1300

Balancing valves for additional coil


2 way valve for additional coil and assembly kit.

80
52
The valve is supplied equipped with
230 Volt electro-thermal actuator for the ON/OFF control.

155
180

275
Version YFCN–ECM 320
YHP–ECM
Model VC – HC – VCB – CD

–ECM Mod. VALVE FITTED NOT FITTED


YFCN YHP DN Ø Range Code Type Code Type
1÷5 1÷3 10 1/2” 90 – 450 9066663 V2OVBAM 90-450 9066653 V2OVBAS 90-450
6÷9 – 15 3/4” 150 – 1050 9066664 V2OVBAM 150-1050 9066654 V2OVBAS 150-1050

2 pipe system 4 pipe system

49
Accessories
YFCN–ECM / YHP–ECM
for YFCN–ECM / YHP–ECM version

BEL electric heater


1 PHASE 230V
Electric heater with integral: safety thermostat and relay control.

Version YFCN–ECM Version YFCN–ECM


YHP–ECM
Model VC – HC – VCB – CD Model CD

Size Size
YFCN–ECM Watt Code YFCN–ECM YHP–ECM Watt Code
– 650 9066491E – – 650 9066611
1000 9066492E 1000 9066612
2 600 9066482E 2 – 600 9066602
400 9066472E 400 9066592
1500 9066493E 1500 9066613
4 900 9066483E 4 1 900 9066603
600 9066473E 600 9066593
2000 9066495E 2000 9066615
6 1250 9066485E 6 2 1250 9066605
750 9066475E 750 9066595
2500 9066497E 2500 9066617
7–9 1500 9066487E 7–9 3 1500 9066607
1000 9066477E 1000 9066597

NOTE: for ECM range the controls


can control the electric heater only if there is no hot water supply.

ACTV extension condensate collection tray to cover valve assembly


(for vertical units)

19
0

Version YFCN–ECM
Model VC – VCB – CD (vertical)
0
Code 6060400 10

Version YHP–ECM
Code 6060400

50
Accessories
YFCN–ECM / YHP–ECM
for YFCN–ECM / YHP–ECM version

ACTH extension condensate collection tray to cover valve assembly


(for horizontal units)

Version YFCN–ECM
Model HC – CD (horizontal)
Connection side LEFT RIGHT
Type ACTH-SX ACTH-DX
Code 6060402 6060403

Version YHP–ECM
Connection side LEFT RIGHT
Type ACTH-SX ACTH-DX
Code 6060402 6060403

DRPV-C fitted condensate pump


(for vertical units)

Version YFCN–ECM
YHP–ECM
Model VC – VCB – CD (vertical)

Fitted Not Fitted


Type DRPV-C-M DRPV-C-S
Code 9066297 9066296

Height for vertical Water flow (l/h) depending on the length of horizontal flow

flow (m) 5m 10 m
1 7,6 7,2
2 5,6 5,2
3 4,0 3,7
4 3,2 2,9

DRPO-C fitted condensate pump


(for horizontal units)

Version YFCN–ECM
* With HC model the pump
Model HC – CD (horizontal) * can not be mounted; it is possible
to use VC model in horizontal position
Code 9066295 using GAP and FT.

Version YHP–ECM
Code 9066295

Height for vertical Water flow (l/h) depending on the length of horizontal flow

flow (m) 5m 10 m
1 7,6 7,2
2 5,6 5,2
3 4,0 3,7
4 3,2 2,9

51
Accessories
YFCN–ECM / YHP–ECM
for YFCN–ECM / YHP–ECM version

SCR plastic condensate drain pipe


with fast connection
(allows correct condensate drain)

YFCN–ECM

YHP–ECM

Version YFCN–ECM
YHP–ECM
Model HC – CD
Code 6060420

FT feet

Version YFCN–ECM
Model VC

Size L Code
2 430 9060150
4 645 9060150
6 860 9060150
7 1119 9060150
9 1119 9060151

GAP
Aluminium low intake grid
(to be installed with FT feet)

Version YFCN–ECM
Model VC

Size Code
2 9066542
4 9066543
6 9066545
7–9 9066547

52
Accessories
YFCN–ECM / YHP–ECM
for YFCN–ECM / YHP–ECM version

KAF frontal intake kit


Bottom closing panel and filter sliding guides.

Version YFCN–ECM
Model CD Version YHP−ECM

Size Code Size Code


2 9066502 1 9069071
4 9066503 2 9069072
6 9066505 3 9069073
7 9066507
9 9066508

RCPV rear closing panel


(for vertical units)

Version YFCN–ECM
Model VC – VCB

Size Code
2 9060180
4 9060181
6 9060182
7–9 9060183

RCPH bottom closing panel


(for horizontal units)

Version YFCN–ECM
Model HC

Size Code
2 9060190
4 9060191
6 9060192
7 9060193
9 9060194

53
Accessories
YFCN–ECM / YHP–ECM
for YFCN–ECM / YHP–ECM version

SAEM fresh air mixing damper


(factory mounted with feet and intake grid included, MV only)

(can not be motorized)

Version YFCN–ECM
Model VC

100
Size Code

65
A B L
2 186 78 454 9076332
4 186 78 669 9076333 B
A
6 186 78 884 9076335
7 186 78 1099 9076337
9 216 108 1099 9076338

SAE fresh air mixing damper


(not mounted, IV − IO only)

(can not be motorized)

Version YFCN–ECM

100
65
Model CD

Size A B L Code
B
2 186 78 454 9066532
4 186 78 669 9066533
6 186 78 884 9066535
7 186 78 1099 9066537
9 216 108 1099 9066538

FRD straight inlet flange


Can be used together with GRAG air inlet grid.
Made of galvanized steel.

Version YFCN–ECM
YHP–ECM
Model CD

Size
YFCN YHP Type A B C D G Code
2 – FRD - 2 454 390 32 216 16 9060720
4 1 FRD - 3/4 669 590 39,5 216 16 9060721
6 – FRD - 5/6 884 790 47 216 16 9060722
– 2 FRD - 4S 884 790 47 246 46 9038002
7 – FRD - 7 1099 990 54,5 216 16 9060723
9 3 FRD - 8/9 1099 990 54,5 246 46 9060724

54
Accessories
YFCN–ECM / YHP–ECM
for YFCN–ECM / YHP–ECM version

FR 90 90° inlet flange


Can be used together with GRAP air inlet grid.
Made of galvanized steel.

Version YFCN–ECM
YHP–ECM
Model CD

Size
YFCN YHP Type A B C D E Code
2 – FR90 - 2 454 390 32 216 11 9060710
4 1 FR90 - 3/4 669 590 39,5 216 11 9060711
6 – FR90 - 5/6 884 790 47 216 11 9060712
– 2 FR90 - 4S 884 790 47 246 41 9038001
7 – FR90 - 7 1099 990 54,5 216 11 9060713
9 3 FR90 - 8/9 1099 990 54,5 246 41 9060714

GRAP air inlet grid


To be used with FR 90 90° inlet flange.
Made of anodized aluminium.

Version YFCN–ECM
YHP–ECM
Model CD

Size
YFCN YHP Type Description B Code
2 – GRAP - 2 Grid 400x150 375 9060760
4 1 GRAP - 3/4 Grid 600x150 575 9060761
6 2 GRAP - 5/6 Grid 800x150 775 9060762
7–9 3 GRAP - 7/9 Grid 1000x150 975 9060763

GRAG air inlet grid


To be used with FRD straight inlet flange.
Made of anodized aluminium.

Version YFCN–ECM
YHP–ECM
Model CD

Size
YFCN YHP Type Description B Code
2 – GRAG - 2 Grid 400x200 375 9060764
4 1 GRAG - 3/4 Grid 600x200 575 9060765
6 2 GRAG - 5/6 Grid 800x200 775 9060766
7–9 3 GRAG - 7/9 Grid 1000x200 975 9060767

55
Accessories
YFCN–ECM / YHP–ECM
for YFCN–ECM / YHP–ECM version

FRC fresh air connection


(not mounted)

Version YFCN–ECM
Model CD

Size Type A Code


2÷9 FRC 100 98 6064191
2÷9 FRC 120 122 6064192

FMD straight outlet flange


Made of galvanized steel.

Version YFCN–ECM
YHP–ECM
Model CD

Size
YFCN YHP Type A B C D Code
2 – FMD - 2 452 390 31 152 9066372
4 1 FMD - 3/4 667 590 38,5 152 9066373
6 – FMD - 5/6 882 790 46 152 9066375
– 2 FMD - 4S 882 790 46 179 9069232
7 – FMD - 7 1097 990 53,5 152 9066377
9 3 FMD - 8/9 1097 990 53,5 179 9066378

FM 90 90° outlet flange


Made of galvanized steel
insulated with polyethylene lining.

Version YFCN–ECM
YHP–ECM
Model CD

Size
YFCN YHP Type A B C D Code
2 – FM90 - 2 452 390 31 152 9066382
4 1 FM90 - 3/4 667 590 38,5 152 9066383
6 – FM90 - 5/6 882 790 46 152 9066385
– 2 FM90 - 4S 882 790 46 179 9060242
7 – FM90 - 7 1097 990 53,5 152 9066387
9 3 FM90 - 8/9 1097 990 53,5 179 9066388

56
Accessories
YFCN–ECM / YHP–ECM
for YFCN–ECM / YHP–ECM version

BMA air outlet grid


Double louvre grid to be fitted to the duct,
to the FMD straight outlet flange
or to the FM 90 90° outlet flange.
Made of anodized aluminium.

Version YFCN–ECM
YHP–ECM
Model CD

Size
YFCN YHP Type B Code
2 – BMA - 2 375 9060750
4 1 BMA - 3/4 575 9060751
6 2 BMA - 5/6 775 9060752
7–9 3 BMA - 7/9 975 9060753

PRC air inlet spigot plenum


Made of galvanized steel
insulated with polyethylene lining.

Version YFCN–ECM All the plenums


YHP–ECM
Model CD are supplied with spigots
for the connection of flexible ducts.
Size
YFCN YHP Type A B C D Spigots Code
2 – PRC - 2 430 107 218 216 N° 2 9066462
4 1 PRC - 3/4 645 166 218 313 N° 2 9066463
6 – PRC - 5/6 860 160 218 270 N° 3 9066465
– 2 PRC - 4S 860 160 248 270 N° 3 9038050
7 – PRC - 7 1075 190 218 347,5 N° 3 9066467
9 3 PRC - 8/9 1075 190 248 347,5 N° 3 9066468

PMC spigot diffuser


Made of galvanized steel
insulated with polyethylene lining.

Version YFCN–ECM All the plenums


YHP–ECM
Model CD are supplied with spigots
for the connection of flexible ducts.
Size
YFCN YHP Type A B C D Spigots Code
2 – PMC - 2 430 107 218 216 N° 2 9066362
4 1 PMC - 3/4 645 166 218 313 N° 2 9066363
6 – PMC - 5/6 860 160 218 270 N° 3 9066365
– 2 PMC - 4S 860 160 248 270 N° 3 9069222
7 – PMC - 7 1075 190 218 347,5 N° 3 9066367
9 3 PMC - 8/9 1075 190 248 347,5 N° 3 9066368

57
Accessories for YFCN–ECM YFCN–ECM
GRAFP air inlet grid with filter
To be fitted to the FR 90 90° inlet flange.
Made of anodized aluminium.

Version YFCN–ECM
Model CD

Size Type B Code


2 GRAFP - 2 375 9060770
4 GRAFP - 3/4 575 9060771
6 GRAFP - 5/6 775 9060772
7–9 GRAFP - 7/9 975 9060773

GRAFG air inlet grid with filter


To be fitted to the FRD straight inlet flange.
Made of anodized aluminium.

Version YFCN–ECM
Model CD

Size Type B Code


2 GRAFG - 2 375 9060774
4 GRAFG - 3/4 575 9060775
6 GRAFG - 5/6 775 9060776
7–9 GRAFG - 7/9 975 9060777

58
YFCN–ECM / YHP–ECM
YFCN–ECM / YHP–ECM version

YFCN–ECM / YHP–ECM configuration

For this fan coil configuration, the 1-10 Vdc signal, which controls the inverter, must be supplied
by a controller with the following signal specifications:
• Impedance < 100 Ω;
• Maximum speed 10Vdc;
• Fan OFF with V < 0,9Vdc.

YFCN–ECM / YHP–ECM electric wiring diagram

CONTROLLER
0Vdc
10Vdc
Impedance < 100 Ω
Signal 0,3/13V
Fan OFF with V < 0,9 Volt
Maximum speed 10 Volt

ECM BLAC board


Motor
fan connection
U M
PE L N 4 5 6 7 8 9 10 11 12 13 14 15
V 3 PE
MFC W
Digital Fault T1
Signals
DFS- T1
PE DFS+ Motor fan
0V thermal protector
10V connection
0-10Vdc
Input signal

ECM board
PE power supply
L N PE
N L

PE

LEGEND:
BLAC = Inverter circuit board M = Electronic motor CONTROLLER = Controller

59
YFCN–ECM / YHP–ECM
YFCN–ECM / YHP–ECM version

Wall electronic controls – YFCN–ECM / YHP–ECM version

Identification Code The control must always be connected with JPF-AU power unit (fitted on the unit)
JWC-AU 9066632K or with JP-AU power unit (not fitted on the unit).
• ON-OFF push button.
• Manual, automatic or centralized Summer/Winter switch.
• Manual or automatic 3 speed progressive push button.
• Summer/Winter/Fan/Auto mode push button.
• Electric heater activation button.
• Electronic room thermostat for fan control (ON-OFF).
• Electronic room thermostat for valve control (ON-OFF).
• Simultaneus thermostatic control of the valves and fan.
• It allows to control the low temperature cut-out thermostat (NTC).
• It allows to control the water valves (ON-OFF) and the electric heater managed as main heating
element or as an integration element.
• Energy saving push button.
N.B.: with 4 pipe installations and continuous chilled and hot water supply, it allows the automatic summer
winter change-over in accordance to the room temperature (-1°C = Winter, +1°C = Summer, Neutral
Zone 2°C).
Dimensions: 135x86x24 mm

Identification Code The control must always be connected with JPF-AU power unit (fitted on the unit)
JTM-B 9066331E or with JP-AU power unit (not fitted on the unit).
Wall control with display that allows controlling one or more units in Master/Slave mode.
The control is equipped with internal sensor to detect the room temperature, which can be defined as
a priority compared to the return air sensor on the fan coil.
The JTM-B control features the following functions:
• Switch the unit ON and OFF.
• Temperature set.
• Manual, centralized or automatic Summer/Winter switch.
• Set the fan speed (low, medium, high or autofan).
• Set the operation mode (fan only, cooling, heating; auto for 4 pipe systems with mode selection
depending on the air temperature).
• It allows to control the water valves (ON-OFF) and the electric heater managed as main heating
element or as an integration element.
• Time setting.
• Weekly ON/OFF program.
Dimensions: 110x72x25 mm

Identification Code
WM-S-ECM 9066644
0-10V control with display designed to be mounted on the wall or to be installed on a 503 wall box.

• ON-OFF switch.
• Manual 3 speed switch or automatic continuous speed control.
• Manual Summer/Winter switch.
• Summer/Winter/Fan/Auto mode push button.
• Electronic room thermostat for fan control (ON-OFF).
• Electronic room thermostat for valve control (ON-OFF).
• Simultaneus thermostatic control of the valves and fan.
• It allows to control the low temperature cut-out thermostat (NTC).

Dimensions: 132x87x23,6 mm

Description Identification Code


Power unit for JWC-AU and JTM-B remote control (fitted on the unit) JPF-AU 9066641
Power unit for JWC-AU and JTM-B remote control (not fitted on the unit) JP-AU 9066640

Power unit to be installed on the fan coil (fan coil interface).

• It controls the fan and the valves of the fan coil.


• It is connected to the electric supply.
• It receives the information required from the control.

Control power absorption: 2,3 VA

60
YFCN–ECM / YHP–ECM
YFCN–ECM / YHP–ECM version

Electronic control to be fitted – YFCN–ECM version

Identification Code
TMV-T-ECM 9060141

• ON-OFF switch.
• Manual 3 speed switch or automatic continuous speed control.
• Manual Summer/Winter switch.
• Continuous speed control based on the difference between ambient temperature and Set temperature
(speed switch in Auto position).
• Electronic room thermostat for fan or valve control (ON-OFF).
• Simultaneus thermostatic control of the valves and fan.
• It allows to control low temperature cut-out (NTC).
Control power absorption: 1,5 VA

Electronic control accessories

NTC low temperature cut-out thermostat


To be fitted between the coil fins; when connecting the control,
the NTC probe cable must be separated from the power supply wires.
To be used with the TMV-T-ECM, WM-S-ECM controls and the JP-AU power unit.
It stops the fan when the water temperature is lower than 28°C and it starts the fan when is higher than 33°C.

Version YFCN–ECM
YHP–ECM
Model VC – HC – VCB – CD
Code 3021090

T2 sensor to be placed on the water supply pipe upstream 3 way valves


(not to be used with 2 way valve).

The T2 sensor must be used as described below:


• Change-Over for the automatic switch of the operating mode.
If water temperature is lower than 20°C, cooling mode is set; on the other hand, if water temperature exceeds 30°C,
heating mode is set.
• It can be used on units with electric heater and hot water supply. The T2 priority probe activates the electric heater
or water valve, depending on the water temperature detected. If water temperature exceeds 34°C, the water valve
ON-OFF control is activated; on the other hand, if water temperature is lower than 30°C, the electric heater is
activated.
To be used with the JP-AU power unit.

Version YFCN–ECM
YHP–ECM
Model VC – HC – VCB – CD
Code 9025310

61
YFCN–ECM / YHP–ECM
YFCN–ECM / YHP–ECM version

Controls and units MB version

All the YFCN–ECM and YHP–ECM units can be supplied with a wide range of controls, which allows managing one
single unit or several units by using the Modbus RTU - RS 485 communication protocol. Units can be managed
according to the Master/Slave logic (up to 20 units) or by supervisory components. The system consists in a MB
board and a series of controls, such as the JTM-B control, the RT03 infra-red remote control, the PSM-DI multi-
function control and the NET supervisory program.

MB electronic board
Description Identification Code
MB electronic board fitted on the unit MB-ECM-M 9066334
MB electronic board supplied with separate packaging MB-ECM-S 9066335

The MB electronic board, to be mounted on the fan coil internal unit, is set
to carry out different functions and adjustment modes, in order to meet
the installation requirements. These modes are selected by setting
the configuration dip switches on the board.
• 2/4 pipe system.
• Fan ON/OFF thermostatic control.
• Valve ON/OFF thermostatic control and continuous ventilation.
• Valve and simultaneous ventilation ON/OFF
thermostatic control.
• Fan operation control depending
on the coil temperature (cut-out T3 probe fitted), which can be activated
only in heating mode or heating and cooling mode.
• Automatic switch of the operating mode
by means of T2 water probe (optional) applied on the 2 pipe system.
• Seasonal switch by means of remote contact.
• ON/OFF of the fan coil by means of the remote contact
(window or clock contact).
• Electric heater control.

By activating the cut-out T3 probe function, the fan is stopped in winter when the coil temperature is lower than 32°C
and started when the temperature reaches 36°C. In summer mode, the fan stops when the temperature inside the
coil exceeds 22°C and starts when it drops below 18°C.

The following connections are located on the power board:


• Receiver for infra-red remote control.
• JTM-B control.
• RS 485 serial connection to manage several fan coils in Master/Slave configuration
or to create a supervisory network.

62
YFCN–ECM / YHP–ECM
YFCN–ECM / YHP–ECM version

Controls and units MB version

JTM-B control
Description Identification Code
Wall control (to be used with MB board only) JTM-B 9066331E
Control fitted on the unit, for VC / VCB models
JTM-B-LM 9066646
(to be used with MB board only) - YFCN–ECM only
Control supplied with separate packaging, for VC / VCB models
JTM-B-LS 9066645
(to be used with MB board only) - YFCN–ECM only
Control fitted on the unit, for VC / VCB models
JTM-B-M-UP 9066648
(to be used with JP-AU power unit only) - YFCN–ECM only
Control supplied with separate packaging, for VC / VCB models
JTM-B-S-UP 9066647
(to be used with JP-AU power unit only) - YFCN–ECM only

Control with display that allows


controlling one or more units in Master/Slave mode.
The control is equipped with internal sensor
to detect the room temperature,
which can be defined as a priority compared
to the return air sensor on the fan coil.

The JTM-B control


features the following functions:
• Switch the appliance ON and OFF.
• Temperature set. Dimensions: 110x72x25 mm

• Modify the set point (when used as a +/- 3° variation


of the set point configured from NET supervisory program or PSM-DI).
• Set the fan speed (low, medium, high or autofan).
• Set the operation mode (fan only, cooling, heating;
auto for 4 pipe systems with mode selection depending on the air temperature).
• Time setting.
• Weekly ON/OFF program.
• Display and change of the fan coil operation parameters.

63
YFCN–ECM / YHP–ECM
YFCN–ECM / YHP–ECM version

Controls and units MB version

RT03 infra-red remote control


Description Identification Code
RT03 infra-red remote control with fitted receiver, for VC-HC-VCB models
RM-RT03 9066336
(to be used with MB board only) - YFCN–ECM only
RT03 infra-red remote control with receiver supplied with separate packaging
RS-RT03 9066337
(to be used with MB board only)
RT03 infra-red remote control supplied with separate packaging
RT03 3021203
(to be used with MB board only)
Receiver for RT03 infra-red remote control fitted on the unit, for VC-HC-VCB models
RM 9066339
(to be used with MB board only) - YFCN–ECM only
Receiver for RT03 infra-red remote control supplied with separate packaging
RS 9066338
(to be used with MB board only)

The infra-red remote control allows


setting by a remote position the fan coil operation parameters.

The RT03 infra-red remote control features the following functions:


• Switch the appliance ON and OFF.
• Temperature set.
• Set the fan speed (low, medium, high or autofan).
• Set the operation mode
(fan only, cooling, heating; auto for 4 pipe systems
with mode selection depending on the air temperature).
• Time setting.
• 24 hours ON/OFF program.

Installation example
with infra-red remote control

64
YFCN–ECM / YHP–ECM
YFCN–ECM / YHP–ECM version

Controls and units MB version

A group of YFCN–ECM and YHP–ECM units with MB electronic board can be connected via a serial link and can
consequently be managed at the same time by just one JTM-B control or RT03 infra-red remote control. Using
the special jumper present on the MB board, one unit must be configured as the master, and all the others as
slaves. It is clear that the remote control must be pointed at the receiver on the master unit. To avoid problems, it
is recommended to install and connect the receiver only on the master unit.

With JTM- B control


One control for each unit One control for more units (20 units max.)
(Maximum length of the connection cable = 20 m) (Maximum total length of the connection cable = 800 m)

Shielded cable
Belden 9841 type

With RT03 infra-red remote control


One control for each unit One control for more units (20 units max.)
(Maximum total length of the connection cable = 800 m)

Shielded cable
Belden 9841 type

T2 accessory for units with MB electronic board


Identification Code
T2 9025310

The T2 sensor can be combined with MB boards to be placed on the water supply pipe upstream 3 way valves
(not to be used with 2 way valve).
The T2 sensor must be used as described below:
- Change-Over for 2-pipe system for the automatic switch of the operating mode.
If water temperature is lower than 20°C, cooling mode is set; on the other hand, if water temperature exceeds 30°C,
heating mode is set.
- It can be used on units with electric heater and hot water supply. The T2 priority probe activates the electric heater
or water valve, depending on the water temperature detected. If water temperature exceeds 34°C, the water valve
ON-OFF control is activated; on the other hand, if water temperature is lower than 30°C, the electric heater is
activated.

65
YFCN–ECM / YHP–ECM
YFCN–ECM / YHP–ECM version

Controls and units MB version

PSM-DI multifunction control panel


Description Identification Code
Multifunction control (to be used with MB board only) PSM-DI 3021293

Another option available for the serial communication between the


units is the possibility to connect up to 60 YFCN–ECM and
YHP–ECM units in series and manage them with just one wall
mounted PSM-DI controller. The wall mounted controller
can be used to set the operating mode for each individual
unit connected, display the operating conditions of each
individual unit, and set the ON/OFF time sets for each day
of the week (the program can be set for all the units and for
a maximum of two groups of units).
If more than 60 units need to be connected, two or more
controllers must be used. Each unit must have a MB board.
The PSM-DI control is used to manage a series of fan coils,
up to a maximum of 60 units (the maximum length of the RS 485
connection cable must not exceed 800 m), from one single control
point.

The PSM-DI control communicates via a serial line with all the units connected, with the possibility of controlling
them all together or individually. In fact, the unique address of each individual fan coil means that all the units can
be called at the same time, or the individual unit called, to perform the following functions:
- display the current operating mode, the fan speed, the set point;
- display the room temperature measured on the individual unit;
- turn all the units ON and OFF at the same time or alternatively each unit individually;
- change the operating mode (fan only, heating, cooling, automatic changeover);
- change the set point;
- modify the values and operation parameters of the fan speed.

Each function can then be sent to all the units connected, or alternatively to each individual unit.

Different set points or operating modes can be set for each individual unit.

The PSM-DI panel can also be used for the time management of the units over the week. Four ON times and four
OFF times can be set on the units for each day of the week. A different Temperature set that will be considered as
Operation set for all connected appliances, can be set for each event. If the Temperature set is not entered for the
individual event, it must be set during programming for each individual unit or for the entire network.

Units without receiver or with receiver can be connected within the network: the former can receive instructions only
from the PSM-DI wall mounted panel; while the latter can receive information from both the wall mounted panel
(PSM-DI) and infra-red remote control. Use the infra-red remote control to force ON mode of the individual unit,
if ON/OFF daily time programming has been set. The unit will regain the settings from the PSM-DI panel during
execution of successive start-up program.

The PSM-DI panel cannot be used


together with the NET management program (see next page).

Note: set the configuration Dip Switches of each fan coil as illustrated in the remote control use manual, based on
the required solutions.
Note: the RS 485 network’s overall length must not exceed 700/800 metres.

66
YFCN–ECM / YHP–ECM
YFCN–ECM / YHP–ECM version

Management system for a network of fan coils

NET program for managing a network of MB fan coils


Description Identification Code
Hardware/software supervisory system (to be used with MB board only) NET 9079118

NET is a centralised control system


for networks of MB fan coils, based on software
that runs on LINUX™ operating system
(the program is provided pre-installed on a PC).
The NET software offers a practical
and economical solution for managing the units,
with the simple click of the mouse.

The main characteristics include:


- simplicity of use;
- an extremely complete and functional weekly program;
- possibility to access the historical operating data
for each individual appliance connected.

The program exploits all the potential of our units


with remote controls, representing an addition to the latter.

The NET program is a control tool


that can be used as a replacement for the remote control, or in parallel,
however the settings made using NET can have priority
over those made using the remote control.

The program can be used to:


- Create uniform groups
(groups of units on individual floors, in offices or rooms).
- Save weekly programs configured for different types of operation
(summer, winter, mid seasons, closing periods etc.);
these can then be recalled and activated with a simple click of the mouse.
Weekly on/off cycles can be set for individual units or groups of units.
- Set the operating conditions for each individual unit or groups of units
(operating mode, fan speed, temperature setting).
- Set the set point limits for each individual unit or groups of units.
- Switch each individual unit or groups of units ON or OFF.

67
YFCN–ECM / YHP–ECM
YFCN–ECM / YHP–ECM version

Management system for a network of fan coils

The main program screen can display and interact with the entire network of units. An individual unit, a group of
units or the entire network can be called so as to make modifications to the operating mode and the set point. The
user can then check the operating status of each individual unit, read the room temperature, the coil temperature
and the operating status of the condensate drain pump or any alarms.
“MONITORING” Screen

Displaying a unit
The “MONITORING” Screen
shows the units that
are connected to the network
and scanned by the program.

The icon of the terminal unit


provides the following information:

- Unit name ( 00.03.02)

- Set temperature ( SETP )

- Room temperature ( AT )

- Unit status: ON (Green) or OFF (Red)

- Mode: • Summer • Auto

• Winter • Fan only

- Fan speed: • Low • High

• Medium • AutoFan

68
YFCN–ECM / YHP–ECM
YFCN–ECM / YHP–ECM version

Management system for a network of fan coils

The “Weekly Program” can be used to set the unit operating parameters for each day of the week. Up to 20 different
weekly programs can be set.
“EVENT MANAGEMENT” Screen

Time bands are available for each day of the week. The time and the type of operation to be performed by the unit
can be set for each band. The time and the operating parameters can then be displayed before being sent to the
unit and implemented.

PC NET Software Power


input
Outputs
for system
Power
input
Outputs
for system
Power
input
Outputs
for system
60 units max. (*)
Connection
of a YFCN–ECM YFCN−ECM YFCN−ECM YFCN−ECM
or YHP–ECM network YHP−ECM YHP−ECM YHP−ECM
unit unit unit
with MB electronic board

MC2 Jumper to be closed.


End of network.

RS 485

USB-RS 485
CONVERTER NET
(*) In the event
of more than 60 units, add
one or more Router-S (see next page).

RS 485 serial connection cable


Shielded cable to be used:
Belden 9841, RS-485, 1x2x24 AWG SFTP, 120 Ohm

69
YFCN–ECM / YHP–ECM
YFCN–ECM / YHP–ECM version

PSM-DI and NET electronic boards

Identification Code
SIOS 3021292

SIOS is a board equipped with 8 relays


with potential free contact to control the activation
or deactivation of remote electric utilities.
Moreover, the board has 8 digital inlets to display
the actuators or external consents, such as motor or other.
The SIOS boards can be connected:
- inside a network managed by NET;
- to a PSM-DI panel (one SIOS for each PSM-DI panel).

Identification Code
Router-S 3021290

The Router-S is an electronic board that:


- allows creating networks with more than 60 units (minimum 2 Router-S are required)
or to divide the network (per floor, building, etc.);
- it allows creating a Master/Slave sub-network
to be controlled as an indipendent group.
The Router-S can be used
only inside a network managed by NET.
The number of Router-S to be used is: - up to 60 units: no Router-S
- from 61 to 120 units: 2 Router-S
- every 60 subsequent units: 1 additional Router-S

70
The Fan Coil Unit CONTENTS
with EC Brushless • YFCN–ECM version
Electronic Motor • Construction Page 4

and Inverter Board



• Models
• Dimensions, Weight, Water content
Page 5
Page 6
• EUROVENT Certification Page 10
YFCN and YHP fan coils combine a beautiful design with • Operation limits Page 13
very interesting performances in terms of sound level and
• Emission tables Page 14
energy consumption.
• Correction factors table Page 24
ECM models are available in five different models, for wall
• Water pressure drop Page 25
and ceiling installation, with casing and concealed.
All Johnson Controls fan coils take part to the Eurovent
program of fan coil performance certification. • YHP–ECM version
• Construction features Page 26
The ECM range makes use of the excellent experience gained • Dimensions, Weight, Water content Page 28
with the Cassette fan coils with inverter board, first in the world • Technical features Page 30
in production since 2009, and which have had great success • Main performance
on all markets. and technical characteristics Page 32
The innovative brushless and sensorless type synchronous • Operation limits Page 33
electronic motor with permanent magnets, is controlled by an • Emission tables Page 34
inverter board. The board is mounted on the unit, closed to the • Correction factors tables Page 40
motor, without the need to be cooled down by the air flow. • Water pressure drop Page 42

The air flow rate can be varied in continuous by means of • YFCN–ECM / YHP–ECM version
a 1-10 V signal generated by JCI controls or by independent
• Accessories Page 44
control systems. The continuous air flow control improves
• ECM configuration Page 63
the acoustic comfort and allows a more punctual reply to the
• Electronic controls Page 64
variation of the thermal loads and a greater stability of the
requested ambient temperature. • Controls and units MB version Page 66
• Management system
The extreme efficiency, also at low speed, for a network of fan coils Page 71
makes possible a great reduction in • PSM-DI and NET electronic boards Page 74
electric consumption (less than 50%
in comparison to YFCN and YHP–O
range motor) with absorption values
under normal operating conditions
that do not exceed 16 Watt for
YFCN−ECM models and do not
exceed 50 Watt for YHP−ECM
models on the entire range. The
excellent values of the YFCN and
YHP range in terms of sound levels
have been maintained in all working
conditions, without any resonance
phenomenon at any frequency.

The full compliance with the Electro-


magnetic Compatibility Directive and with
the other severe Standards in force is certified
by an independent institute.

Johnson Controls take part to the Eurovent program


of fan coil performance certification.
The official figures are published in the web site
www.eurovent-certification.com and in the web site www.certiflash.com.
The tested performances are:
• Cooling total emission at the following conditions: • Cooling sensible emission at the following conditions:
- Water temperature +7°C E.W.T. +12°C L.W.T. - Water temperature +7°C E.W.T. +12°C L.W.T.
The descriptions and illustrations provided in this publication are not binding:
- Entering air temperature +27°C dry bulb +19°C wet bulb - Entering air temperature +27°C dry bulb +19°C wet bulb Johnson Controls reserve the right, whilst maintaining the essential characteristics
• Heating emission (2 pipe units) at the following conditions: • Heating emission (4 pipe units) at the following conditions: of the types described and illustrated, to make, at any time,
- Entering water temperature +50°C - Water temperature +70°C E.W.T. +60°C L.W.T. without the requirement to promptly update this piece of literature,
- Entering air temperature +20°C - Entering air temperature +20°C
- Water flow rate as for the cooling conditions any changes that it considers useful for the purpose
• Fan absorption • Water pressure drop • Sound power of improvement or for any other manufacturing or commercial requirements.
Br

NE
ee

W
ze

al
Fr

lc

W
am
e

on
kit

tr
-
Re

ol
ce
ss

s
ed
Bo
xV
er
sio
n
YFCN−ECM Fan Coil Units www.eurovent-certification.com
Cod. 99A4660162 C/04/16
YFCN/YHP −ECM - 04/16

www.certiflash.com

YHP−ECM High Pressure Fan Coil Units


Technical Guide - for internal distribution only

You might also like