RH03 - D30 Distance Test Report
RH03 - D30 Distance Test Report
RH03 - D30 Distance Test Report
D30 PROTECTION
FEEDER 3 NYANDIWA
2
CUSTOMER : Republic of Kenya-
Ministry of Energy
PO NUMBER :
JOB NUMBER :
SITE ADRESS :
3
GE Multilin Customer
Representative Representative
NAME
4
SIGNATURE
DATE
5
1 D30 RELAY..........................................................................................................................3
1.1 RELAY DATA....................................................................................................3
1.2 VISUAL INSPECTION & SYSTEM CHECK...........................................................3
1.3 COMMUNICATIONS.........................................................................................3
1.4 POWER SUPPLY...............................................................................................3
1.5 CONTACT INPUTS...........................................................................................4
1.6 CONTACT OUPUTS..........................................................................................5
1.7 TERMINAL BLOCKS V&I CONNECTIONS...........................................................6
6
1.8 VOLTAGE AND CURRENT INPUTS METERING...................................................6
1.8.1 CT/VT SETTINGS.....................................................................................................................6
1.8.2 SIGNAL SOURCES...................................................................................................................6
1.8.3 BREAKERS 7
1.8.1 79 - AUTORECLOSE.................................................................................................................9
1.8.2 UNBALANCED SYSTEM TO IDENTIFY PHASES.............................................................10
1.8.3 BALANCED V&I SYSTEM....................................................................................................10
1.9 PROTECTION ELEMENTS...............................................................................11
1.9.1 PHASE DISTANCE (21) Z1 3 PHASE FAULT.......................................................................11
1.9.2 PHASE DISTANCE (21) Z2 3 PHASE FAULT.......................................................................12
1.9.3 GROUND DISTANCE (21) Z1................................................................................................13
7
1.9.4 GROUND DISTANCE (21) Z2................................................................................................14
1.10 PROTECTION SUMMARY................................................................................15
1.11 OPERATION TABLE........................................................................................16
2 ADDITIONAL COMMENTS/FACTS IMPACTING THE FIELD SERVICE/ETC.:.........................17
3 Open points:.....................................................................................................................17
8
1 D30 RELAY
MANUFACTURER GE MULTILIN
PANEL IDENTIFICATION H02+RH02
RELAY ORDER CODE D30-N03-HKH-F8L-H6N-M6N-P6C
SERIAL NUMBER AAAC16000150
9
SETTINGS DOCUMENT Customer propietary
FIRMWARE REVISION 6.0x
IP ADDRESS 192.168. 1. 65
MODBUS ADDRESS 254
PROTECTION ELEMENTS 21P, 21G, 79
10
1.2 VISUAL INSPECTION & SYSTEM CHECK
TEST DATE
Equipment integrity: OK 20/03/2017
LED test: OK 20/03/2017
Frontal display: OK 20/03/2017
Keypad: OK 20/03/2017
Equipment grounding: OK 20/03/2017
11
1.3 COMMUNICATIONS
TEST DATE
Ethernet communication: OK 20/03/2017
Serial communication: OK 20/03/2017
IRIG-B NA 20/03/2017
SNTP NA 20/03/2017
Configuration file download (Factory
OK 20/03/2017
default.urs)
Configuration file upload (D30: OK 20/03/2017
12
D30_NdhiToNdannyiwa_20032017.urs)
MEASURE DATE
Supply type: DC 108.1 Vdc 20/03/2017
13
1.5 CONTACT INPUTS
15
1.6 CONTACT OUPUTS
CONTACT
RELAY TERMINALS NAME OPERATE TEST DATE
TYPE
H1b-H1c Cont Op 1 OFF NA NA NA
H2b-H2c Cont Op 2 OFF NA NA NA
H3b-H3c Cont Op 3 OFF NA NA NA
H4b-H4c Cont Op 4 OFF NA NA NA
M1b-M1c Cont Op 1 OFF NA NA NA
16
M2b-M2c CB 79 CMD AR 1 CLOSE NO OK 20/03/2017
CBBLOCKtoBCU On DISABL
M3b-M3c CB BLOCK BCU NA NA
(VO5) ED
M4b-M4c CB 79 LOCKOU AR 1 LO NO OK 20/03/2017
P1b-P1c Cont Op 9 OFF NA NA NA
P2b-P2c CB TRIP TC1 GEN TRIP On (VO1) NO OK 20/03/2017
P3b-P3c CB TRIP TC2 GEN TRIP On (VO1) NO OK 20/03/2017
P4b-P4c Cont Op 12 OFF NA NA NA
P5b-P5c InitCBFtoBCU GEN TRIP On (VO1) NO OK 20/03/2017
P6b-P6c Cont Op 14 OFF NA NA NA
17
P7b-P7c Cont Op 15 OFF NA NA NA
P8b-P8c Cont Op 16 OFF NA NA NA
18
1.7 TERMINAL BLOCKS V&I CONNECTIONS
CT Feeder F1 VT BANK F5
CURRENTS VOLTAGES
A 1 1
B 2 2
XCT-1 VA VT-1
C 3 3
N 4 4
19
1.8 VOLTAGE AND CURRENT INPUTS METERING
CT SETTINGS
PARAMETER CT F1
Phase CT Primary 250 OK
20
Phase CT Secondary 1 OK
Ground CT Primary 250 OK
Ground CT Secondary 1 OK
VT SETTINGS
PARAMETER VT F5
Phase VT Connection Wye OK
Phase VT Secondary 63.5 V OK
Phase VT Ratio 300 :1 OK
Auxiliary VT Connection Vbg OK
Auxiliary VT Secondary 63.5 V OK
21
Auxiliary VT Ratio 300 :1 OK
SIGNAL SOURCES
PARAMETER SCR 1 SRC2
Name Feeder BusSyc
Phase CT F1 None
Ground CT F1 None
Phase VT F5 None
Aux VT None F5
22
1.8.3 BREAKERS
BREAKERS
SETTING PARAMETER
Breaker 1 Function Enabled
Breaker 1 Push Button Control Disabled
Breaker 1 Name Bkr 1
23
Breaker 1 Mode 3-Pole
Breaker 1 Open OFF
Breaker 1 Block Open OFF
Breaker 1 Close ManualClsCMD On(H6c)
Breaker 1 Block Close OFF
Breaker 1 Phase A/3-Pole Closed CB CLOSED On(M5c)
Breaker 1 Phase A/3-Pole Opened CB OPEN On(M5a)
Breaker 1 Phase B Closed OFF
Breaker 1 Phase B Opened OFF
Breaker 1 Phase C Closed OFF
24
Breaker 1 Phase C Opened OFF
Breaker 1 Toperate 0.070 s
Breaker 1 External Alarm OFF
Breaker 1 Alarm Delay 0.000 s
Breaker 1 Manual Close Recal Time 0.000 s
Breaker 1 Out Of Service OFF
Breaker 1 Events Enabled
26
Breaker 2 Phase C Opened OFF
Breaker 2 Toperate 0.070 s
Breaker 2 External Alarm OFF
Breaker 2 Alarm Delay 0.000 s
Breaker 2 Manual Close Recal Time 0.000 s
Breaker 2 Out Of Service OFF
Breaker 2 Events Disabled
27
1.8.1 79 - AUTORECLOSE
AUTORECLOSE 1
SETTING PARAMETER
Function Enabled
Initiate AR INIT On (VO2)
Block 79 BLOCK/OUT On (VO3)
Max Number Of Shots 2
Reduce Max to 1 OFF
Reduce Max to 2 OFF
28
Reduce Max to 3 OFF
Manual Close ManualClsCMD On(H6c)
Manual Reset from LO OFF
Reset Lockout if Breaker Closed On
Reset Lockout On Manual Close On
Breaker Closed BREAKER 1 CLOSED
Breaker Open BREAKER 1 OPEN
Block Time Upon Manual Close 10.00 s
Dead Time Shot 1 0.50 s
Dead Time Shot 2 5.00 s
29
Dead Time Shot 3 3.00 s
Dead Time Shot 4 4.00 s
Add Delay 1 OFF
Delay 1 0.00 s
Add Delay 2 OFF
Delay 2 0.00 s
Reset Lockout Delay 25.00 s
Reset Time 25.00 s
Incomplete Sequence Time 10.00 s
Events Enabled
30
31
1.8.2 UNBALANCED SYSTEM TO IDENTIFY PHASES
VOLTAGE CURRENT
INJECTION READ VALUE INJECTION READ VALUE
TERMINAL F5 TERMINAL F1
Vph-g Vph-g
V Angle V Angle I Mag I Angle I Mag I Angle
Mag Mag
32
A 10 V 0º 300 0 1A 0º 24.96 0
METERING OK METERING OK
33
1.8.3 BALANCED V&I SYSTEM
VOLTAGE CURRENT
READ VALUE READ VALUE
INJECTION INJECTION
TERMINAL F5
Vph-g Vph-g TERMINAL F1
V Angle V Angle I Mag I Angle I Mag I Angle
Mag Mag
A 63.5 V 0º 19.05 0 1A 0º 249.8 -359.6
34
METERING OK METERING OK
35
1.9 PROTECTION ELEMENTS
36
1.9.1 PHASE DISTANCE (21) Z1 3 PHASE FAULT
37
The following graph shows distance function
characteristics
38
SETTING
Phase INJECTION TESTED VALUE CONCLUSION
VALUE
RESULT
TERM V V PKP &
I Mag I Angle test TIME (OK/NO DATE
(SRC1) Mag Angle TIME
T OK)
A 1.35A -90ª 8V↓ 0ª
Quad
5.93 Ω
diagram
B 1.35ª -210ª 8V↓ -120ª TO 40.7ms OK 20/03/17
Reach=5.11
5.037
Ω
C 1.35A 30ª 8V↓ 120ª 0s
39
CONTACT 21BLOCK On (VO6) OFF P2 P3 P5…..LED#1
OUTPUTS OK
ACTIVATED 21BLOCK On (VO6) ON NONE
40
41
1.9.2 PHASE DISTANCE (21) Z2 3 PHASE FAULT
42
The following graph shows distance function
characteristics
43
SETTING
Phase INJECTION TESTED VALUE CONCLUSION
VALUE
RESULT
TERM V V PKP &
I Mag I Angle test TIME (OK/NO DATE
(SRC1) Mag Angle TIME
T OK)
A 0.53 ↑ A -90ª 18V↓ 0ª
Quad
diagram 15 Ω to
B 0.53 ↑ A -210ª 18V↓ -120ª 432.3ms OK 20/03/17
Reach=12.7 12
Ω
C 0.53 ↑ A 30ª 18V↓ 120ª 0.4 s
44
CONTACT 21BLOCK On (VO6) OFF P2 P3 P5…..LED#3
OUTPUTS OK
ACTIVATED 21BLOCK On (VO6) ON NONE
45
46
1.9.3 GROUND DISTANCE (21) Z1
47
The following graph shows distance function
characteristics
48
SETTING
Phase INJECTION TESTED VALUE CONCLUSION
VALUE
RESULT
TERM V V PKP &
I Mag I Angle test TIME (OK/NO DATE
(SRC1) Mag Angle TIME
T OK)
A 0.8 A -90ª 7.1V↓ 0ª
Quad
diagram 8.875
B - - 7.1V↓ -120ª 37.5ms OK 20/03/17
Reach=5.11 to 5 Ω
Ω
C - - 7.1V↓ 120ª 0s
49
CONTACT 21BLOCK On (VO6) OFF P2 P3 P5 …LED#2
OUTPUTS OK
ACTIVATED
21BLOCK On (VO6) ON NONE
50
51
1.9.4 GROUND DISTANCE (21) Z2
52
The following graph shows distance function
characteristics
53
SETTING
Phase INJECTION TESTED VALUE CONCLUSION
VALUE
RESULT
TERM V V PKP &
I Mag I Angle test TIME (OK/NO DATE
(SRC1) Mag Angle TIME
T OK)
A 0.6 A↓ -90ª 8V 0ª
Quad
diagram
B - - 8V -120ª 12.6Ω 420.5ms OK 20/03/17
Reach=12.7
8Ω
C - - 8V 120ª 0.4s
54
CONTACT 21BLOCK On (VO6) OFF P2 P3 P5…LED#4
OUTPUTS OK
ACTIVATED
21BLOCK On (VO6) ON NONE
55
1.10 PROTECTION SUMMARY
56
57
58
1.11 OPERATION TABLE
D30
Protection operation Table
FUNCTION
CB TRIP CB TRIP InitCBFtoB AR INIT
TC1 TC2 CU On
21P Z1 X X X
21P Z2 X X X
59
79 X
21G Z1 X X X X
21G Z2 X X X X
60
61
2 Additional Comments/Facts impacting the Field
Service/etc.:
62
Load recroachment blocked tested.
Led revised
Fault locator checked.
AR 79 tested, 2 cycles, initialization,
63
3 Open points:
64
65
66