Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

STD 142

Download as pdf or txt
Download as pdf or txt
You are on page 1of 56

<< Back Home Next >>

OISD - STD - 142


First Edition
February, 1996

FOR RESTRICTED
CIRCULATION ONLY

INSPECTION OF
FIRE FIGHTING EQUIPMENT AND SYSTEMS

Prepared by:

COMMITTEE ON “INSPECTION OF FIRE FIGHTING EQUIPMENT AND SYSTEMS

OIL INDUSTRY SAFETY DIRECTORATE


7TH FLOOR, NEW DELHI HOUSE
27, BARAKHAMBA ROAD
NEW DELHI – 110 001
NOTE

OISD publications are prepared for use in the oil and gas
industry under the Ministry of Petroleum and Natural Gas. These
are the property of Ministry of Petroleum and Natural Gas and
shall not be reproduced or copied and loaned or exhibited to
others without written consent from OISD.

Though every effort has been made to assure the


accuracy and reliability of data contained in these documents,
OISD hereby expressly disclaims any liability or responsibility for
loss or damage resulting from their use.

These documents are intended only to supplement and


not replace the prevailing statutory requirements.
FOREWORD

The Oil Industry in India is 100 years old. Because of various


collaboration agreements, a variety of international codes, standards and
practices have been in vogue. Standardisation in design philosophies and
operating and maintenance practices at a national level was hardly in
existence. This, coupled with feed back from some serious accidents that
occurred in the recent past in India and abroad, emphasised the need for the
industry to review the existing state of art in designing, operating and
maintaining oil and gas installations.

With this in view, the Ministry of Petroleum and Natural Gas in 1986
constituted a Safety Council assisted by the Oil Industry Safety Directorate
(OISD) staffed from within the industry in formulating and implementing a
series of self regulatory measures aimed at removing obsolescence,
standardising and upgrading the existing standards to ensure safe
operations. Accordingly, OISD constituted a number of functional
committees of experts nominated from the industry to draw up standards
and guidelines on various subjects.

The present document on “Inspection of Fire Fighting Equipment and


Systems”, has been prepared by the Functional Committee on “Inspection of
Static Equipment”. This document is based on the accumulated knowledge
and experience of industry members and the various national and
international codes and practices. This document is meant to be used as
supplement and not as a replacement for existing codes and practices. It
shall be borne in mind that no standard can be a substitute for the
judgement of a responsible qualified Inspection Engineer. Suggestions are
invited from the users after it is put into practice to improve the document
further. Suggestions for amendments to this document should be addressed
to
The Co-ordinator,
Committee on “Inspection of Static Equipment”,
OIL INDUSTRY SAFETY DIRECTORATE
7th Floor, ‘New Delhi House’
27, Barakhamba Road
New Delhi – 110 001

This standard in no way supercedes the statutory requirements of


bodies like IBR, CCE, Factory Inspectorate or any other Government Body
which must be followed as applicable.
Committee on
INSPECTION OF FIRE FIGHTING EQUIPMENT AND SYSTEMS

--------------------------------------------------------------------------------------------------------------------------------
NAME REPRESENTING
--------------------------------------------------------------------------------------------------------------------------------
LEADER

Shri R. K. Sabharwal Indian Oil Corporation (R & P Division)


Shri Y. P. Ajmani Oil & Natural Gas Corporation
(Since March, 1993)

MEMBERS

Shri B. Ravi Indian Oil Corporation (Marketing)


Shri S. F. Kanchwala Bharat Petroleum Corporation Limited (Refinery)
Shri G. Somani Indian Oil Corporation (R & P Division)
Shri A. C. Kelkar Indian Oil Corporation (Marketing)
Shri P. K. Khaitan Oil & Natural Gas Corporation
Shri Sham Lal Oil & Natural Gas Corporation
Shri J. L. Vishwakarma Hindustan Petroleum Corporation Ltd., Bombay Refinery
Shri S. S. Murthy Hindustan Petroleum Corporation Ltd., Visakh Refinery
Shri V. Bharadwaj Bharat Petroleum Corporation Limited (Marketing)
Shri S. Neelakantan Madras Refineries Limited
Shri K. Narayanan Cochin Refineries Limited
Shri R. Rehman Hindustan Petroleum Corporation Ltd., (Marketing)

CO-OPTED MEMBERS

Shri P. L. Nigania Indian Oil Corporation, Gujarat Refinery


Shri A. A. Raichur Hindustan Petroleum Corporation Ltd., Bombay Refinery
Shri S. N. Banerjee Bharat Petroleum Corporation Limited (Refinery)
Shri K. Baskaran Madras Refineries Limited

MEMBER COORDINATOR

K.R. SONI Oil Industry Safety Directorate


--------------------------------------------------------------------------------------------------------------------------------
In addition to the above, various other experts from the industry contributed in the
preparation, review and finalisation of this document.
INSPECTION OF FIRE FIGHTING
EQUIPMENT AND SYSTEMS

CONTENTS
--------------------------------------------------------------------------------------------------------------------------------
SECTION DESCRIPTION PAGE NO.
--------------------------------------------------------------------------------------------------------------------------------
SEC-I

1.0 Introduction
2.0 Scope

SEC-II DRY CHEMICAL POWDER (DCP) FIRE EXTINGUISHING


SYSTEM

1.0 Definitions and types of DCP fire extinguishing systems


2.0 Design of DCP Cylinders
3.0 Construction
4.0 Performance characteristics
5.0 Inspection and testing of new extinguishers during construction
6.0 Periodic inspection of extinguishers/mobile equipment
7.0 Marking & Documentation
8.0 Condemning of cylinders
9.0 References

SEC-III CARBON DIOXIDE FIRE EXTINGUISHING SYSTEM

1.0 Definition & types of extinguishers


2.0 Design
3.0 Material of construction
4.0 Construction
5.0 Performance characteristics
6.0 Inspection & testing of new extinguishers & installations
7.0 Periodic inspection of extinguishers
8.0 Marking and documentation
9.0 Condemning of cylinders
10.0 References

SEC-IV HALON FIRE EXTINGUISHING SYSTEM

1.0 Definition and types


2.0 Design
3.0 Construction
4.0 Performance characteristics
5.0 Inspection and testing of new extinguishers & installations
during construction
6.0 Periodic inspection of extinguishers
7.0 Marking & Documentation
8.0 References
SEC-V FOAM FIRE EXTINGUISHING SYSTEM

1.0 Definition and types of extinguishers


2.0 Design
3.0 Material of construction
4.0 Construction
5.0 Performance characteristics
6.0 Inspection and testing of new extinguishers & installations
during construction
7.0 Periodic inspection of extinguishers
8.0 Marking & Documentation
9.0 Condemning of cylinders
10.0 References

SEC-VI WATER SPRINKLER SYSTEM

1.0 Definition and types


2.0 Design
3.0 Materials
4.0 Construction
5.0 Inspection and testing of sprinkler system
6.0 Documentation
7.0 References

SEC-VII FIXED WATER SPRAY SYSTEM FOR FIRE PROTECTION

1.0 Definition and applicability


2.0 Design
3.0 Construction
4.0 Acceptance tests
5.0 Periodic inspection and testing
6.0 Documentation
7.0 References
SECTION I

INSPECTION OF FIRE FIGHTING EQUIPMENT AND SYSTEMS


2.0 SCOPE
1.0 INTRODUCTION
This standard covers the design,
The complex nature of present day construction, inspection and testing
petroleum industry involving critical operating requirements of new and installed fire
conditions and high level of product fighting equipment and Installations. The
inventory call for an efficient fire fighting requirement given herein are MINIMUM. The
system. The fire fighting system should be Standard also covers performance
designed, constructed, tested and requirements of equipment.
maintained as per standard engineering
practice for safe and efficient operation. The This Standard covers the following
design of each fire fighting equipment or fire types of fire extinguishing systems:
fighting system shall be carried out as
described in the relevant chapters. Various 1) Dry Chemical Powder
fabrication and inspection stages shall be 2) Carbon dioxide
decided upon and a quality control/quality 3) Halon
assurance programme evolved to ensure 4) Foam
quality product. 5) Water Sprinkler
6) Fixed Water Spray

SECTION II

DRY CHEMICAL POWDER (DCP) FIRE EXTINGUISHING SYSTEM

1.0 DEFINITIONS AND TYPES OF compressed nitrogen, all mounted


DCP FIRE EXTINGUISHING on a truck or trailer.
SYSTEMS
1.1.3 Cylinder
1.1 DEFINITIONS
For this standard, a cylinder means
1.1.1 Extinguisher (DCP) Portable/ a cylindrical container/vessel
Trolley mounted: containing DCP or expellent gas as
the case may be.
DCP extinguisher consists of a
cylinder containing finely powdered 1.1.4 Cartridge
chemicals which are expelled by
means of an inert gas contained For this standard, cartridge is a
either in a compressed gas cartridge small cylinder containing expellent
located within the DCP cylinder as in gas and located within the DCP
case of portable extinguishers or cylinder.
stored in a separate cylinder located
outside DCP cylinder as in case of 1.1.5 Operating Pressure
trolley mounted extinguishers.
The operating pressure is the
1.1.2 Mobile DCP Tender: pressure developed in the DCP
container with the discharge nozzle
It consists of a cylindrical vessel closed, when the full designed
containing extinguishing agent i.e. quantity of expelling gas in a
DCP, and a series of cylinders cartridge or cylinder is released into
containing expellent gas i.e. it.
1.1.6 Test Pressure kg capacity range. Expellant gas is
located in a cylinder outside the
The hydrostatic pressure at which DCP container.
the container together with its cap
assembly and discharge hose is to 1.2.4 Mobile Tender
be tested.
Dry Powder Tender is of 1, 2, 3 & 4
Tons capacity on an automobile
chassis. The expellant gas is
1.1.7 Burst Pressure contained in a series of cylinders
mounted on a truck.
It is the pressure at which the
material fails. The burst pressure 2.0 DESIGN OF DCP CYLINDERS
test is conducted as a proof test to
ensure that the material is capable 2.1 DESIGN PRESSURE
of withstanding working pressure.
The burst pressure should be The portable trolley mounted fire
greater than 3 times the operating extinguishers and the DCP cylinder on
pressure. mobile tenders shall be designed to
withstand pressure of 22.5 kg/sq cm. The
1.2 TYPES OF DRY POWDER maximum operating pressure shall not
EXTINGUISHING EQUIPMENT & exceed 15kg/sq.cm. This pressure will be
SYSTEMS adequate to achieve required performance
characteristics.
The various types of
extinguishers/systems covered in 2.2 MATERIAL OF DCP CYLINDER
this standard are:
The material of various parts of the DCP
1.2.1 Portable cylinder shall be as given below:

Portable extinguishers have a i) Shell of all portable IS-513


maximum dry powder filled weight of cylinders upto 10 kg grade
10 kg. and a maximum gross weight capacity ‘EDD’or
of 23 kg. The expellant gas is “DD”
contained in a cartridge within the
cylinder. ii) Shell of all trolley IS-2002
mounted cylinders upto grade A or
1.2.2 Trolley Mounted 150kg IS-2041

In principle, the basic operation of iii) Shell of mobile tender IS-2002 gr


Trolley Mounted DCP Fire 2A or
Extinguishers and Portable DCP IS-2041.
Extinguishers are similar. Trolley
mounted extinguishers are iv) Nozzle pipe IS-1239/IS-1978
manufactured to 25.0, 50.0, 75.0,
100.0 and 150 Kg. capacity. The v) Flanges ASTM A-105 or
expellant gas is located in a cylinder Equivalent
outside the DCP container.
vi) Plunger and nozzle Type I of IS-
of all portable cylinders 319
upto 10 kg capacity
vii) Cap nozzle and Type I of IS-319/
drain plug of all trolley SS
1.2.3 Trailer Mounted
mounted extinguishers
upto 150 kg capacity.
Trailer Mounted extinguishers are
manufactured in the 200 kg to 500
viii) Discharge nozzle on IS-617 the body while all non-ferrous fittings shall be
trigger for cylinder, port- brazed.
able and trolley mounted
i) All welding shall be carried out using
ix) Washers for all sizes of IS-5382/IS- qualified welders and
extinguishers 2171 agreed welding procedures.

x) Inner container IS-513/IS-2171 ii) The weld joint design for the long
seam as well as the
2.3 DESIGN THICKNESS circumferential seam shall be
of the square edge butt type for
The thickness of plate material for plate thicknesses 3.0mm and less
the DCP cylinder shall be calculated as per and single “V” butt for
the formula given below: thicknesses higher than 3.0mm.

PD iii) All welding shall be carried out using


t = —————- shielded metal arc welding
200 fj +P (SMAW) or gas tungsten arc
where welding (GTAW) techniques
only. The electrode for welding
t = minimum thickness of shell plate shall conform to AWS/ASME
exclusive of corrosion allowance in classification. The electrode
mm. diameter shall be chosen
P = Design pressure in kg/cm2 considering plate thickness to
D= outside diameter of DCP cylinder in be welded.
mm.
f= allowable stress value for the iv) All butt welds shall be full
material used in kg/mm2 penetration welds.
j= weld joint efficiency factor
v) All other requirements as outlined in
Thickness of the shell including section II of IS-2825 shall be
dished ends shall not be less than 2 mm for followed.
portable extinguishers upto 10 Kg, 3.15 mm
for 25 Kg, 50 Kg & 75 Kg and 6.3 mm for 3.2 SAFETY VALVE
100 Kg & above trolley mounted
extinguishers respectively. All trolley mounted DCP
extinguishers shall be provided with safety
2.4 CAPACITY valve preferably on its top dished end to
requirements of IS-2825.The set pressure
The capacity of portable shall be 17 Kg/sq.cm.
extinguishers shall be of 1, 2, 5 and 10 kg
weight of Dry Chemical Powder and of trolley 3.3 OPERATING PRESSURE
mounted extinguishers of 25, 50, 75, 100
and 150 Kg weight. The mobile tender Suitable test shall be done to
capacity shall be of 300 Kg, 500 Kg, 1, 2, 3 & demonstrate that sufficient space is provided
4 Tonnes by weight. so that internal pressure does not exceed 15
Kg/sq.cm. and the body shall not show any
sign of leakage if the discharge nozzle is
closed and the extinguisher is operated at 27
+ 2ºC.
3.0 CONSTRUCTION
3.4 DRY CHEMICAL POWDER
3.1 WELDING
The types of Dry Chemical Powder
The cylinder body shall be of welded and requirements shall be as per IS-4308
type. All ferrous fittings shall be welded to with Sp.Gr. in the range of 0.95 to 1.0.
Permanent marking of dry chemical powder
filling height shall be considered to avoid The extinguisher shall be painted
overpressurisation of cylinder. fire red conforming to shade No.536 of IS-5.
The paint shall conform to IS-2932.
3.5 EXPELLANT GAS
4.0 PERFORMANCE
The Expellant gas used shall be CHARACTERISTICS
carbon dioxide (CO2) or nitrogen (N2). The
maximum quantity of expellant gas to be The performance characteristics for
used for various capacities of Dry Chemical each size of extinguisher shall be as given
Powder Extinguishers shall be such that the below
internal pressure of the DCP cylinder shall at ----------------------------------------------------------
no point of time exceed 15 kg/sq.cm. Capacity of Duration of Throw Range
Extinghisher Discharge
3.6 HOSE ----------------------------------------------------------
(kg) (Sec.) (Mtrs.)
The length of the discharge hose 1-2 10 - 15 3-4.5
shall be as specified in IS-2171 and IS- 5 15 - 20 3.5 - 5.5
10658.The hoses shall be designed to 10 23-30 5 - 7.5
withstand the design pressure of the DCP 25 25-30 6-8
cylinder. 50 40-50 8-10
75 50-60 10-12
3.7 DISCHARGE NOZZLE 100 70-80 10-17
150 100-110 15-17
T he discharge nozzle shall be
designed to discharge the powder as per 5.0 INSPECTION AND TESTING OF
performance characteristics outlined in 4.0. NEW EXTINGUISHERS DURING
CONSTRUCTION
3.8 CAP/FILLER OPENING
5.1 SHELL AND ATTACHMENTS
The size of cap/filler opening shall
be as per IS-2171 (latest edition). 5.1.1 Material Identification

3.9 VENT HOLES Material used for the cylinder shell


shall be identified to ensure
Necessary vent holes shall be conformity with manufacturing
provided as per IS-2171 standard. Raw material/bought out
material for other components shall
3.10 SAFETY CLIP also be identified.

Safety clip shall be provided to 5.1.2 Welding


prevent accidental actuation of piercing
mechanism. The following checks shall be carried out
prior to, and during welding:

a) Review and approval of the welding


procedure.
3.11 COATING
b) Qualifying of the welding procedure
The internal and external surfaces of and welders.
the cylinder body shall be coated with Zinc or
lead-tin alloy. Thickness of Coating for c) Inspection of edge preparation and
various sizes shall be as specified in joint fit-up
standards IS-2171 and IS-10658.

3.12 PAINTING
d) Ensuring that during welding only external paint shall be 50 microns
approved procedure and approved minimum.
electrodes are being used.
5.2 SAFETY VALVES
5.1.3 Testing
Safety devices shall be tested at 17
The following tests shall be carried out after Kg/sq.cm gas per requirements of IS-2825.
completion of welding:
5.3 HOSE
i) Dye Penetrant Inspection:
A sample discharge hose of
Dye penetrant examination shall be minimum 0.5 mt length shall be tested upto
carried out on the fillet welds of all bursting which shall not be less than 45
nozzles and attachments. kg/sq.cm. Actual burst pressure of the hose
shall be recorded.
ii) Radiography
5.4 CARBON DIOXIDE CARTRIDGE
Spot Radiography of welds on all AND CYLINDER
cylinders shall be carried out using
X- rays/Gamma Rays. 10% of Requirements for CO2 cartridge and
the weld joints shall be cylinder are as specified in Section III of this
radiographed which shall include at Standard. When carbon-dioxide cylinder is
least 50% of the “T” joints. connected to trolley mounted DCP
Interpretation of radiographs shall be extinguisher, the valve of CO2 cylinder
as per IS-2825. should be provided with safety pin & seal.

iii) Hydraulic Test 5.5 PIERCING MECHANISM

Extinguisher shell/container and the The clearance between the cartridge


cap assembly with the hose holder and the plunger rod tip should be
assembly shall be tested to an sufficient to ensure clear opening in the
internal pressure of 30 kg/sq.cm. cartride seal when pierced.
The test pressure shall be held for a
minimum period of two and a half 5.6 REPAIRS
minutes.
i) Any repairs to welding shall be
iv) Bursting Test carried out as per IS-2825 and the
same offered for reradiography. In
One prototype shall be tested and case of repairs additional
certified by either of customer/third radiography shall also be done as
party inspector. Hydraulic burst test per IS-2825. Only one time repairs
shall be carried out on a shall be allowed.
prototype and no failure shall
occur at a pressure below 45 ii) Any extinguisher, which fails in
kg/sq.cm. Actual burst pressure hydrostatic test, shall be reoffered
shall be recorded. In case the for inspection. If the failure is in the
prototype does not rupture during parent metal then the extinguisher
Bursting Test then it should be shall be rejected. Weld failures shall
destroyed to prevent its use. be suitably repaired as per IS-2825
and reinspected.
v) Coating and Painting
5.7 PERFORMANCE TESTS
Internal and external coating and
external painting shall be checked Performance & expansion space
and coating thickness established tests etc. shall be carried out as per IS-
as per 3.11. The thickness of 2171/IS-10658.
6.0 PERIODIC INSPECTION OF v) Spring
EXTINGUISHERS/MOBILE
EQUIPMENT The spring is prone to lose its
stiffness.
6.1 LIKELY LOCATIONS OF
DETERIORATION vi) Nozzle

6.1.1 Corrosion The nozzle may be eroded due to


frequent use of extinguisher.
i) Internal Corrosion:
vii) Hose
Extinguisher (DCP Vessel) is prone
to internal corrosion at the interface The rubber hose is prone to ageing.
between the dry powder top level
and empty space. Corrosion may 6.2 FREQUENCY AND PROCEDURE
take place where the internal coating FOR INSPECTION
is damaged and or where there is a
holiday in the coating. The extinguisher and its
components shall be inspected at
ii) External Corrosion: frequencies specified and as per procedure
given below:
The external surface of the
extinguisher is prone to atmospheric 6.2.1 Body
corrosion particularly at areas where
paint has peeled off. Support ring of i) Visual Inspection
the fire extinguisher is prone to
water, soil and coercive corrosion. The shell of the DCP extinguisher
Metallic tubing for the transfer of shall be visually inspected
inert gas is likely to corrode due to externally once a month and
the atmosphere. internally once every three months
to check for any mechanical
6.1.2 Damage/Deterioration damage or corrosion.

i) Shell ii) Ultrasonic Inspection

Shell may be damaged due to Ultrasonic thickness measurements


improper handling. Dents/ of the shell shall be carried out once
deformations may occur. every three years and readings shall
be recorded.
ii) Neck Ring
iii) Hydrostatic Test
Neck rings are prone to breakage at
the weld joint. A Hydrostatic test of the cylinder
shell along with cap and hose
iii) Cap/Neck joint assembly shall be done at
30kg/sq.cm once every three years.
The thread joint between cap and
neck is prone to damage/wear/ iv) Performance Test
deterioration.
Check performance test as per IS-
iv) Cartridge Holder 2171 & IS-10658 on 1% of the
newly procured/refilled DCP
The cartridge holder is prone to extinguishers selected at random.
internal corrosion. Also the port
holes are prone to erosion. v) Rejection
attachment to the shell shall be
A DCP extinguisher body shall be checked.
removed from service and destroyed
when the following iv) Cap
conditions exist:
The threading of both cap and neck
a) When it is corroded or shall be checked. The thread
damaged to such an extent engagement shall be at least 16mm.
at repair is required. The cap washer shall be
checked for deformation and cracks.
b) When the shell threads are
damaged. v) Plunger

The plunger shall be checked


c) When it has failed in visually for any damage.
hydrotesting.
vi) Piercer
d) When the extinguisher has
been exposed to high The piercing mechanism shall be
temperatures due to checked for its proper functioning.
proximity of fire.
vii) Spring
vi) Coating and Painting
The spring shall be inspected for its
The internal coating and external shape, size and functional aspects.
painting shall be checked for
damage/deterioration once in three viii) Nozzle and Discharge Fittings
months. The coating thickness shall
be checked once every three years. The nozzle and other fittings shall
be checked for erosion.
6.2.2 Other Components
ix) Cartridge and Seal
The following components shall be
visually inspected once every three The cartridge and seal shall be
months. checked for damage if any.

i) Cartridge Holder x) Dry Chemical Powder

The cartridge holder shall be The dry chemical powder shall be


checked for any damage due checked for signs of caking.
to corrosion or erosion. The port
holes shall be checked for 6.2.3 Hose
elongation.
The hose condition shall be checked
ii) Inner container visually once a month. The hose on
the portable extinguisher shall be
The inner container shall be replaced every three years. The
checked for physical damages hoses on the trolley mounted
like elongation of holes due to extinguishers and on the mobile
corrosion etc. tender shall be hydrostatically
tested every three years and
iii) Neck ring/Shell attachments replaced every 6th year.

The soundness of the 6.2.4 Safety Valve


brazing/welding of the neck ring &
The safety valve shall be visually iv) Dry powder details viz. type, apparent
inspected for corrosion or damage density, moisture retention, fire
once every three months. The safety knockdown properties, free flowing
valve shall be bench tested at rated charateristics etc.
test pressure once every three
years. v) Operating & hyrostatic test pressure.

6.2.5 Gas Cartridge/Cylinder vi) Bursting test pressure.

The CO2 cartridge in the portable vii) Relief Valve testing and set pressure.
extinguishers and the CO2 cylinders
in the trolley mounted extinguishers viii) Internal/external coating details.
shall be inspected and tested as
outlined in Section III of this ix) Identification marking as per relevant
standard. code.

6.2.6 Extinguisher Trolley x) Type and quantity of Expellant Gas.

The lubrication of bearings/bushes 7.3 INSTALLED EXTINGUISHERS


and condition of wheel should be
checked/serviced once in three In addition to the required tag or
months. labels, a permanent file record shall be kept
for each extinguisher/installation. The record
7.0 MARKING AND DOCUMENTATION: shall include the following information as
applicable:
7.1 MARKING
i) Identification number
i) All DCP extinguishers shall have BIS
certification mark/punch on the ii) Date of manufacture
bottom ring.
iii) Name of manufacturer and
ii) All DCP extinguishers shall be manufacturer’s Sr. No.
permanently punched at the bottom
ring with Manufacturer’s name, year iv) Capacity of the extinguisher
of manufacture, Manufacturer’s Sr.
No. and Inspectors stamp. v) Location at which the extinguisher is
installed.
iii) The date of hydrostatic test and the
user’s identification number shall be vi) Date of installing the equipment.
clearly marked.
vii) The inspection date and the name of
iv) Marking of the dry chemical powder person or agency performing the
filling height. inspection.

7.2 NEW EXTINGUISHERS viii) The date when last recharged and
the name of the person performing
The manufacturer shall have BIS the recharge.
certification & shall furnish test certificates
giving the following information: ix) The hydrostatic test date and name
of the person or agency performing
i) Certificate number and date. the test.

ii) Size, type and capacity. x) Next hydro-test date.

iii) Material used for construction. xi) Inspection observations and


maintenance carried out.
4. IS-2825-Code for unfired pressure
8.0 CONDEMNING OF CYLINDERS vessels

DCP extinguishers shall be condemned as 5. ASME SEC VIII DIVN I-Boiler and
per the guidelines given in IS-2190. pressure vessel code

9.0 REFERENCES 6. BS-5423-Specification for portable


fire extinguishers
1. IS-2171-Specifications for portable
fire extinguishers 7. NFPA-10-Portable Fire
Extinguishers
2. IS-10658-Specifications for trolley
mounted fire extinguishers 8. IS-513-Cold-rolled low carbon steel
sheets & strips
3. IS-4308-Specifications for dry
powder for fire fighting 9. IS-2190-Code of Practice for
selection, installation &
maintenance of first-aid fire
extinguishers.
SECTION – III

CARBON DIOXIDE FIRE EXTINGUISHING SYSTEM

1.0 DEFINITION & TYPES OF


EXTINGUISHERS 1.2.3 Tender:

1.1 DEFINITION A carbon dioxide tender is one with


a large quantity of carbon dioxide.
1.1.1 CO2 Extinguishers & The typical tender has 16 carbon
Extinguishing Systems dioxide cylinders of 45.0 Kg.
capacity each.
The extinguishers & extinguishing
systems which employ CO2 1.2.4 Fixed Carbon Dioxide Fire
(conforming to IS-307) stored in Extinguishing Systems:
pressure containers for
extinguishing fires. The fixed carbon dioxide fire
extinguished systems are of two
1.1.2 Filling Ratio types:

The filling ratio of CO2 shall not i) Local Application Installation:


exceed 0.667. The filling ratio shall
be determined as the ratio of mass It consists of a fixed supply of
of CO2 in container to the mass of carbon dioxide, normally connected
water required to fill the container at to a fixed network of pipes, nozzles
15 deg. C. and discharge horns arranged to
discharge the gas directly on the
1.2 TYPES surface or object on which fire is
anticipated.
1.2.1 Portable:
ii) Total Flooding Installation:
Portable extinguishers are ones
which are small, hand operated and It consists of fixed supply of carbon
with all permanent fittings normally dioxide normally connected to a
not exceeding a gross weight of 23 fixed network of pipe, nozzles and
Kg. Portable extinguishers are discharge horns arranged to
manufactured in 2, 3 & 4.5 Kg. evenly distribute sufficient quantity of
capacity. the gas throughout the enclosure(s)
and capable of extinguishing fire
1.2.2 Trolley Mounted: within the enclosure(s) regardless of
location of fire.
Trolley mounted extinguishers are
larger versions of the portable 2.0 DESIGN
extinguishers. Basically the
operation of trolley mounted carbon 2.1 PORTABLE & TROLLEY MOUNTED
dioxide extinguishers and portable
carbon dioxide extinguishers are The portable and trolley mounted
similar. Since the weight of the carbon dioxide extinghisher cylinders shall
cylinder becomes heavy, these be designed as per Code IS:7285-1988.
cannot be transported by hand and
therefore require to be put on 2.2 FIXED CARBON DIOXIDE FIRE
trolleys. The 6.8, 9 & 22.5 Kg. EXTINGUISHING SYSTEM
carbon dioxide cylinders are trolley
mounted.
The thickness for distribution piping chemical
for fixed carbon dioxide fire extinguishing characteristics,
system shall be suitably calculated. The such that its
internal storage pressure for this calculation integrity under
shall not be less than the following: stress can be
predicted with
For 60 Kg/cm2g charging pressure, reliability. Special
an internal pressure of 70 Kg/cm2g at 27 corrosion resistant
deg. C. materials or
coatings may be
If higher storage temperatures are required in severely
approved for a given system, the internal corrosive
pressure at maximum temperature. atmosphere. Black
or galvanised steel
3.0 MATERIAL OF CONSTRUCTION pipe shall be either
ASTM A 106 or API
3.1.1 Materials for Portable & Trolley 5L Cast iron and
Mounted Carbon Dioxide non metallic pipe
Extinguishers shall not be used.

i. Shell : IS:7285 - 1988. iii. Fittings : Class 150 and cast iron
fittings shall not be
ll. Discharge used. All fittings
valve : IS:3224 - 1979. shall be forged
conforming to
iii. Safety ASTMA-105 and
device : IS:5903 - 1970. rating of fittings
shall be of minimum
iv. Syphon class 1500 for a
tube : IS:407 Alloy 2 charged pressure of
for Brass 60 Kg/sq.cm.
IS:1545 for
Copper iv. Connecting hoses: Flexible hoses
IS:738 for used shall be double wire braided
Aluminium rubber covered hose. However, it is
preferred that all connecting hoses
v. Hose : Wire braided rubber and its fittings shall be metallic only.
hose.
vi. Discharge v. Copper Tubing: Copper tubing in this
horn : Non-metallic such system shall meet
as fibre glass, the requirements of
polyethylene Code IS:2501 - 1972.
etc.
vi. Nozzles: Leaded tin bronze to
3.1.2 Materials for Fixed Carbon IS:318.
Dioxide Fire Extinguishing
System

i. Cylinders: As per IS:7285 -


1988. 4.0 CONSTRUCTION

ii. Piping :Piping 4.1 CYLINDER FABRICATION AND


shall be of non DIMENSIONS
combustible
material having
physical and
Cylinders shall be made strictly as A discharge tube shall be provided
per Code IS:7285 from hot or cold drawn to 2 & 3 Kg. capacity extinguishers
seamless tube, rolled or extruded. fitted to discharge valve by swivel
joints.
Fabrication/jointing by welding shall
not be acceptable. Any attempt at welding A hose of not less than 10 mm
for joining and/or rectification will call for diameter shall be provided for 4.5,
rejection of the cylinder. 6.8, 9 and 22.5 Kg. capacity fire
extinguishers. The length of the
The shape of the body shall be hose shall be not less than 1 m for
cylindrical with the difference between 4.5 & 6.8 Kg., 2 m for 9 Kg. and 5 m
maximum and minimum external dia shall for 22.5 Kg capacity fire
not exceed 2% of the nominal internal dia. extinguishers respectively.

The filling ratio of CO2 shall not 4.4.2 Fixed Carbon Dioxide Fire
exceed 0.667. The filling ratio shall be Extinguishing System
determined as the ratio of mass of CO2 in
container to the mass of water required to fill All valves under constant high
the container at 15 deg. C. pressure shall have a minimum
bursting pressure of 420 Kg/cm2
4.2 PAINTING and those not under constant
pressure shall have a minimum
The extinguisher shall be painted bursting pressure of 350 Kg/cm2 g.
externally with suitable primer followed by
synthetic enamel paint of fire red conforming Design nozzle discharge pressure
to shade no. 536 of IS:5 and the paint shall shall not be less than 20.6 Kg/cm2
conform to IS:2932. g.

4.3 HOSES All pipes and fittings, including


manifold, shall have a minimum
4.3.1 Portable & Trolley Mounted bursting pressure of 350 Kg/cm2 g.
Extinguishers
The complete distribution system
Hoses for portable and trolley shall be free from leakage when
mounted cylinders shall be wire tested at a pneumatic pressure of
braided rubber hose having a 140 Kg/cm2 g with nozzle outlets
minimum bursting pressure of 275 closed.
Kg/cm2g in controlled discharge and
140 Kg/cm2g in un-controlled All pipe sections having dead ends
discharge system. shall be fitted with suitable pressure
relief devices designed to operate
4.3.2 Fixed Systems between 168 and 210 Kg/cm2.

Connecting hoses shall be either Nozzles used in the system shall be


wire braided rubber hose or metallic capable of withstanding a minimum
hose with a minimum burst pressure shut off pressure of 140 Kg/cm2 g.
of 420 Kg/cm2.

4.4 DISCHARGE FITTINGS/HEADS/ The discharge header shall be


VALVES provided with suitable flushing
arrangement to ensure easy
4.4.1 Portable & Trolley Mounted elimination of foreign material, which
Extinguishers can clog the spray nozzles.
The complete distribution system d. Inspection of surface
shall be generally made as per IS: defects and removal by
6382 - 1984. grinding, if any.

5.0 PERFORMANCE e. Thickness measurements to


CHARACTERISTICS confirm for minimum agreed
finished thickness.
The performance characteristics for
each size of the extinguisher shall be as iii. Testing
shown below:
___________________________________ The following tests shall be carried
Nominal size of Discharge Time (Sec.) out after completion of extinguisher
Extinguisher (Kg.) Min. Max. cylinder:

2 8 18 a. Visual
3 10 20
4.5 10 24 The internal and external surfaces of
6.8 10 30 the cylinder shall be inspected.
9 12 36 Surface defects of more than 5% of
22.5 20 60 the shell thickness shall be ground
off and the final thickness at that
6.0 INSPECTION & TESTING OF NEW area shall be not less than the
EXTINGUISHERS & calculated minimum wall thickness
plus corrosion allowance.
INSTALLATIONS
b. Dye Penetrant Inspection
6.1 PORTABLE/TROLLEY MOUNTED
EXTINGUISHER
Dye Penetrant examination shall be
carried out on all the formed and
6.1.1 Shell & Attachments knuckled areas.
i. Material Identification c. Hydrostatic Stretch Test
Material used for the cylinder shell Each finished cylinder shall be
shall be identified and if required subjected to hydrostatic stretch test
tested to ensure conformity with at a pressure of 250 Kg/cm2g.
manufacturing standard. Raw Permanent stretch suffered by
material/bought out material for the cylinder shall not exceed the
other components shall also be following limits:
identified.
1. In case of cylinders below
ii. Fabrication 20 litre water capacity -
10% of the total stretch
The following checks shall be suffered during the test,
carried out: and,

a. Review and approval of 2. In other cases - 10% of the


process of manufacturing. total stretch suffered during
the test or 1/5,000 of the
b. Ensuring that no welding original volume of the
has been carried out. cylinder whichever is less.

c. Inspection prior to closing in d. Pneumatic Test


operation.
Cylinders, which have passed
hydrostatic stretch test, shall be
subjected to a pneumatic test for inspection. If the failure is in the
pressure equal to 60% of the parent metal then the extinguisher
test pressure and shall show shall be rejected.
no signs of leak.
6.2 FIXED CARBON DIOXIDE FIRE
e. Leakage Test EXTINGUISHER SYSTEM

The extinguisher without its 6.2.1 Cylinders


attachment shall be shelved for 7
days after filling and shall be Refer 6.1.1 of this section.
checked/weighed at the end of the
period. There shall be no loss of 6.2.2 Piping & Fitting
mass.
i. Material Identification
f. Bursting Test of Prototype Cylinders
Piping & fitting materials shall be
One cylinder of the first batch which identified and if required tested to
has been earlier successfully tested ensure conformity with
hydrostatically shall be subjected to manufacturing standards.
hydrostatic pressure till it bursts.
ii. Fabrication
The nominal hoop stress
corresponding to the pressure at The following checks shall be
which destruction occurs shall carried out prior to and during
be calculated and this value shall welding:
not be less than 0.95 of the
minimum specified tensile strength a. Review and approval of
of the material of the cylinder. The welding procedure.
cylinder shall burst without
fragmentation. b. Qualification of the welding
procedure and welders.
g. Coating & Painting
c. Inspection of edge
The thickness of external paint shall preparation and joint fit up.
be 100 microns minimum.
d. Ensuring that during welding
6.1.2 Hose only approved procedure
and approved
A sample discharge hose with length electrodes are being used.
of not less than 300 mm shall be
tested upto bursting which shall not iii. Testing
be less than 275 Kg/cm2 when there
is controlled discharge and 140 a. Radiography
Kg/cm2 when there is no controlled
discharge at nozzle. Actual burst
Spot radiography of
pressure of the hose shall be
minimum 10 % of the welds
recorded.
of pipes shall be carried out.
Bursting pressure of hose used in
b. Hydrostatic Test
tender shall be minimum 350
Kg/cm2.
The system shall be
hydrostatically tested to the
6.1.3 Repairs required test pressure.
Any extinguisher, which fails in c. Pneumatic Test
hydrostatic test, shall be re-offered
The complete distribution
system shall be free from iv. Hose
leakage when tested at a
pneumatic pressure of 140 The hose is prone to ageing.
Kg/cm2g.
v. Discharge Nozzle
6.2.3 Safety Valves
Discharge nozzle may be clogged
Safety devices shall be tested at the due to foreign material.
required pressure.
vi. Piping systems are prone to external
6.2.4 Hose corrosion/thinning.

A sample discharge hose shall be vii. Valves used in the system may
tested upto bursting pressure, which fail/get jammed.
shall not be less than that specified.
Actual burst pressure of the hose 7.2 FREQUENCY AND PROCEDURE
shall be recorded. FOR PERIODIC INSPECTION

6.2.5 Repairs The extinguisher and its


components shall be inspected at
Suitable weld repairs shall be frequencies specified and as per procedure
carried out as necessary. given below:

7.0 PERIODIC INSPECTION OF 7.2.1 Portable Extinguishers


EXTINGUISHERS
i. Body of Cylinder
7.1 LIKELY LOCATION OF
DETERIORATION a. Visual Inspection

7.1.1 Corrosion The shell of the extinguisher shall be


visually inspected externally
The external side of the once a month to check for any
extinguishers, support, valves and mechanical damage or corrosion.
discharge nozzles are prone to Special attention shall be given to
atmospheric corrosion. surface below clamping rings.

7.1.2 Damage/Deterioration b. Hydrostatic Test

i. Shell A hydrostatic test of the cylinder


shell along with assembly shall be
Shell may be damaged due to done before every refilling or once in
improper handling. Dents/ 5 years as per IS-2190 whichever is
deformations may occur. earlier.

Ultrasonic thickness inspection of


ii. Neck Joint shell shall be carried out during each
hydrotest.
The thread joint between cap and
neck is prone to damage/wear/ c. Painting
deterioration.
The painting shall be checked for
iii. Nozzle damage/ deterioration once in three
months. The coating thickness shall
The nozzle may be eroded due to be checked once in 3 years.
frequent use of extinguishers.
d. Refilling
Ultrasonic thickness measurements
Loss in weight of cylinder shall be of the shell shall be carried out once
checked once in three months. every three years and readings shall
Refilling shall be done if loss in be recorded.
weight is more than 10%.
c. Hydrostatic test
ii. Other Components
The cylinder shall be hydrotested at
The following components shall be 210 Kg/cm2 when the cylinder is
visually inspected once every three sent for refilling or once in 5 years
months. as per IS-2190 whichever is earlier.

a. Nozzle & Discharge Fittings d. Painting

The nozzle and other fittings The external painting shall be


shall be checked for erosion visually checked for damage/
etc. during refilling. deterioration once in three months.
The coating thickness shall be
b. Trolley checked once every three years.

Trolley shall be checked for e. Refilling


proper functioning.
Loss in weight of cylinders shall be
iii. Hose checked once in three months.
Refilling shall be done if loss in
The hose condition shall be checked weight is more than 10%.
visually once in three
months. The hose on the ii) Other Components
portable extinguishers shall be
replaced within three years. The following components shall be
visually inspected once a month.
iv. Gas Cylinder
a. Piping
The weight shall be checked &
recorded. Piping shall be inspected for
evidence of corrosion. Thickness
v. Safety Valve shall be gauged every three years.

The safety valve shall be overhauled b. Pipe Hangers/Straps


& reset during refilling or after
5 years whichever is earlier. Pipe hangers/straps shall be
examined to check that the pipe is
7.2.2 FIXED CARBON DIOXIDE FIRE securely supported. Surfaces
EXTINGUISHER SYSTEM underneath pipe supports shall be
checked once every three years to
i. Body of the Cylinder check for corrosion.

a. Visual Inspection c. Nozzle

The shell shall be visually inspected Nozzles shall be checked to


externally once a month to check for determine that the orifices are clear
any mechanical damage or and unobstructed. When nozzle
corrosion. seals are provided, they shall be
checked for signs of deterioration
b. Ultrasonic Inspection and replaced if necessary. Nozzles
shall be checked for proper position
and alignment. v. Gross, tare and net weight in Kgs.
and water capacity in litres.
d. Container Bracketing/Supports
v. Nature of heat treatment.
Bracketing/supports shall be
checked to determine that their All the markings (except the
condition is satisfactory. manufacturers marking which may
be on the base) shall be punched on
iii. Hose the neck of the cylinder.

The condition of hose shall be 8.1.2 Marking on the Valve


checked visually once in three
months. The hose shall be Valve fitted to the cylinder shall be
hydrostatically tested every three clearly and durably marked in
years and replaced within 6 years. accordance with the following
provision by stamping, engraving or
iv. Safety Valve similar process.

The safety valve shall be overhauled i. The specification of the valve.


& reset once in a year. Visual
inspection shall be done once in ii. Year and quarter of manufacturing.
three months.
iii. Manufacture symbol
v. Copper Tubing
iv. Working pressure.
Copper tubing shall be inspected
visually every three months for v. The name or chemical symbol of the
corrosion/damage visually. gas for which the valve is to be
used (in our case CO2)
vi. All Systems
vi. The type of screw thread on the
All systems shall be thoroughly outlet, namely left hand (LH) or
inspected and tested for proper right hand (RH).
operation by competent personnel
annually. vii. Inspector’s stamp.

8.0 MARKING AND DOCUMENTATION 8.2 DOCUMENTATION

8.1 MARKING 8.2.1 New Extinguishers/Installation

8.1.1 Marking On New Cylinders The manufacturer shall furnish test


certificates giving the following
All Carbon Dioxide cylinders shall be information:
permanently punched with the
following: i. Certificate number and date.

i. Manufacturer’s name & identification ii. Size, type and capacity.


number
iii. Materials used for construction.
ii. IS-2878.
iv. Hydrostatic test pressure.
iii. Carbon Dioxide.
v. Any other test as stipulated in
iv. Working pressure, test pressure and code/OISD Std
the date of hydrostatic stretch test.
vi. Records of non-destructive tests rough usage exists to the extent that
carried out. the cylinder appears to be
weakened appreciably.
vii. Relief valve testing, if any.
Any cylinder which fails to pass the
viii. Painting details. periodic examination or test or which
loses in its tare weight by over 5% or
ix. Identification marking as per which for any other defect is found
relevant Code. to be unsafe for use shall be
destroyed by flattening it as a whole
8.2.2 Installed Extinguishers/ or after being cut into pieces in such
Installations a manner that the pieces cannot
again be joined together by welding
In addition to the required tag or or otherwise to form a cylinder.
labels a permanent tag record shall
be kept for each extinguisher/ All markings on the cylinder shall be
installation. The record shall include defaced before it is destroyed.
the following information as History sheets of such cylinders
applicable. shall be closed and kept for one
year. Reports of the details of such
i. Identification number. closed history cards shall be sent to
the Chief Controller or Explosives, in
ii. Date of manufacture. writing, on the 1st of January, April,
July and October every year.
iii. Name of manufacturer.
10.0 REFERENCES
iv. Capacity of extinguisher.
1. ASTM A-53, A-106, API 5L :
v. Location at which the extinguisher is Specifications for seamless /ERW
installed. mild steel pipes.

vi. Date of installing the equipment. 2. IS:1239-Specifications for mild steel


tubes, tubulars & other wrought
vii. The inspection date and name of the steel fittings
person or agency
performing the inspection. 3. IS:6382- Code of Practice for design
& installation of fixed
viii. The date when last recharged and carbondioxide fire extinguishing
name of the person or agency system.
performing the charge.
4. IS:7285- Specification for seamless
ix. The hydrostatic test date and name manganese steel cylinders for high
of the person or agency pressure liquified gases.
performing the test.
5. IS:3224- Specification for valve
x. Next hydrotest date. fittings for compressed gas
cylinders excluding LPG cylinders.
xi. Inspection observations and
maintenance carried out. 6. IS:5903- Recommendation for
safety devices for gas cylinders.
9.0 CONDEMNING OF CYLINDERS
7. IS:2190- Code of Practice for
Carbon Dioxide cylinder may be selection, installation &
condemned when it leaks, or when maintenance of first-aid fire
internal or external corrosion, extinguishers
denting, bulging or evidence of
8. IS-2878- Specifications for portable
fire extinguisher, carbon dioxide 9. IS-307 - Carbon-dioxide gas
type.

SECTION - IV

HALON FIRE EXTINGUISHING SYSTEM

1.0 DEFINITION AND TYPES :


i) Portable
1.1 DEFINITION:
The Portable Halon cylinders shall
1.1.1. Halon: be designed as pressure vessel to
Code IS 2825.
The extinguishers and the
extinguishing system which employs ii) Total Flooding and Local
Halon stored in a pressure container Application Systems:
for extinguishing fires.
The thickness for distribution piping
1.1.2 Normally Occupied Area: for total Flooding and Local
Application Systems shall be
One which is intended for calculated in accordance with
occupancy. relevant Code. The internal storage
pressure for this calculation shall not
1.2 TYPES OF HALON be less than the following :
EXTINGUISHING SYSTEMS:
For 25 kg/sq.cm (360 psig) charging
1.2.1 Portable: pressure, an internal pressure of 43
kg/sq.cm (620 psi) at 55 deg C.
Portable extinguishers have
capacities of 1.25, 2.5, 4.0, 5.0, and For 42 kg/sq.cm (600 psig) charging
6.5 Kg of Halon with a max gross wt pressure, an internal pressure of 70
of 23 Kg. Halon 1301 is not to be kg/sq.cm (1000 psi) at 55 deg C.
filled in portable extinguishers.
If higher storage temperature are
1.2.2 Total Flooding System: approved for a given system, the
internal pressure at maximum temp.
In this system, Halon is arranged to
discharge into and fill to the proper 2.1 MATERIALS OF CONSTRUCTION :
concentration in an enclosed space
or enclosure. 2.1.1 Materials for Portable Halon
Cylinders:

1.2.3 Local Application System : The material of various parts of


Halon cylinder shall be as given
In Local Application System, a below:
supply of Halon is arranged to
discharge directly on the burning i. Shell : IS: 513 Grade
material. or DD IS : 6240

2.0 DESIGN: ii. Neck Ring: IS : 2062, IS : 1875,


IS : 7283, IS : 9550.
53, 106, API 5L or IS 1239. Cast
iii. a. Valve Body: Leaded Tin Bronze iron and non-metallic pipe shall not
Grade LTB-2 of IS : be used.
318
iii. FITTINGS:
b. Nozzle: Extruded Brass
Section Grade I Class 150 and Cast iron fittings shall
of IS: 291. not be used. All fittings shall be
forged conforming to ASTM A 105
iv. Spring :IS: 4454 (Part I) and rating of fittings shall be as
Grade I. given below

v. Piercer/Spindle : IS : 6528. Charged Pressure Fitting Rating (Min)

vi. Siphon Tube : Brass Copper, Alloy No: 25 kg/sq.cm (360 psi) Class 600
2 of IS:407 or IS :
1545. 42 kg/sq.cm (600 psi) Class 1200

vii. a. Sealing Nuts: Extruded Brass iv. CONNECTING HOSES:


Section of
All connecting hose and its fittings
b. Piercer disc: Grade I of IS : 291 shall be metallic only. Non metallic
or hoses and fittings shall not be used.

c Discharge: Type I of IS : 319. v. COPPER TUBING:


Fitting
Copper tubing in this system shall
viii. Washer : Rubber of IS : 937. meet the requirements of IS-2501.

ix. Sealing Disc : Copper of IS :1972. 3.0 CONSTRUCTION:

2.1.2 Materials for Total Flooding and 3.1 CYLINDER FABRICATION:


Local Application Systems:
i) The fabrication of portable cylinder
i. CYLINDERS: body shall be by welding.
ii) All welding shall be carried out as
Fire extinguisher manufacturers are per agreed welding procedure,
presently using CO2 cylinders for using qualified welders.
filling Halon with the approval of
Chief Controller of Explosives, India. iii) The weld joint design for the
Refer CO2 Fire Extinguishing circumferential seam for portable
System Section for material of cylinder shall be of square edge butt
Cylinders. type for plate thickness 3.0 mm and
less and single V butt for
ii. PIPING: thickness higher than 3.0
mm.
Piping shall be of non-combustible
material having physical and iv) All welding shall be carried out using
chemical characteristics, such that Shielded Metal Arc Welding
its integrity under stress can be or Gas Tungsten Arc Welding
predicted with reliability. Special Process only. The electrode for
corrosion resistant materials like welding shall conform to AWS /
Cupro-nickels or coatings may be ASME / IS classification. The
required in severely corrosive electrode diameter shall not be more
atmosphere. Black or galvanised than 2.5 mm for SMAW and
steel pipe shall be either ASTM A
1.6 mm for GTAW while In squeeze grip valve assembly, the
welding portable cylinders. safety pin shall be provided for prevention of
accidental operation which shall be fitted on
v) All welds shall be full penetration cantilever hinged grip lever through valve
welds. body.

vi) There shall not be any longitudional 3.6 HOSE:


seam in the portable cylinders and
the number of circumferential seams Hoses for portable cylinders of 4.0,
shall not be greater than two. 5.0 and 6.5 kg capacity shall be braided
hose having a bursting pressure of not less
vii) Joints shall be radiographed to IS- than 5 MN/m2 (50 kgf/cm2). It shall have a
2825 nominal bore of 10 mm and a length of not
less than 300 mm.
3.2 CYLINDER DIMENSION:
3.7 DISCHARGE FITTINGS:
The shape of the body shall be
cylindrical and filling ratio shall not be more The discharge nozzle of the portable
than 75% by volume. cylinder shall be screwed to valve body/hose
or it can be an integral part of valve body.
3.3 COATING: The design of the nozzle and area of the
orifice shall be such that it satisfies the
On all internal and external surfaces performance requirements given in 4.0 of
of body of the portable cylinders, either of this Standard.
the following anticorrosive treatment shall be
applied and thickness of coating shall be 3.8 PRESSURE INDICATOR:
measured as given in IS: 3203.
Pressure indicator shall be fitted to
i. Lead tin alloy (tin not less than 10%) the extinguisher to indicate its internal
shall be applied by hot dipping pressure. The indicator shall be marked
process or by electrical process, suitably with pressure at which the
thickness not less than 0.012 mm. extinguisher shall be charged and also
indicate when it is wholly or partially
released.

ii. Copper coating by suitable process, 4.0 PERFORMANCE CHARCTERISTIC:


thickness not less than 0.005 mm.
The performance characteristics for
3.4 PAINTING: each size of extinguisher shall be as given
below:
The extinguisher shall be painted ----------------------------------------------------------------------
Capacity Min period Max period to Range of
externally with suitable primer followed by of for which discharge 95% throw of
synthetic enamel paint of fire red conforming extinguisher throw of jet of contents jet ( not
to shade No: 536 of IS: 5 and the paint shall will be
conform to IS: 2932. less than)
maintained
(kg) (second) (second) (meter)
3.5 SAFETY SYSTEM: ----------------------------------------------------------------------
1.25 8 14 2
In a portable extinguisher with a 2.50 8 16 2
4.00 10 20 3
spring loaded piercing device, the safety clip 5.00 12 24 4
shall be provided for prevention of accidental 6.50 14 28 4
operation of piercing mechanism and
discharge of contents. 5.0 INSPECTION AND TESTING OF
NEW EXTINGUISHERS AND
INSTALLATIONS DURING
CONSTRUCTION: The extinguisher having 1.25 kg
capacity shall be hydrostatically
5.1 PORTABLE EXTINGUISHER: tested at an internal pressure of
2.5 MN/M2 (25 kgf/cm2) for a
5.1.1 Shell and Attachments: period of 60 seconds. The test
shall not reveal any leakage or
i. Material Identification: visible distortion.

Material used for cylinder shell shall For higher capacities, it shall be
be identified and if required tested to tested at 3 MN/M2 (30
ensure conformity with kgf/cm2) for a period of 60 seconds.
manufacturing standard. Raw
material / bought out material for The test shall be carried out before
other components shall also be the extinguishers are painted
identified. and after heat treatment, if any.

ii. Fabrication: d. Leakage Test:

The following checks shall be The fire extinguisher after being


carried out prior to and during covered by a inverted glass
welding: transparent jar shall be dipped in
suitable water tank filled with water
a. Review and approval of welding for 24 hours, the level of which is
procedure, sufficiently higher than the height of
fire extinguisher. There shall not
b. Qualification of the welding be any collection of even a single
procedure and welders, bubble on the inside top of
the inverted glass after a lapse of 24
c. Inspection of edge preparation hours. The airbubble collected in
and joint fit-up, first 6 hours shall be neglected.

e. Drop Test:
iii. Testing: This test shall be done as per IS:
11108.
The following tests shall be carried out after
completion of welding: f. Ultimate Failure Test:
a. Dye Penetrant Inspection: On a prototype test, Mechanical
failure shall not occur at a pressure
Dye Penetrant examination shall be less than 40kgf/cm2 g.
carried out on fillet welds of all
nozzles and attachments. g. Coating And Painting:
b. Radiography: The thickness of anti corrosion
coating shall be 25 microns min and
All welds of cylinders shall be 100% that of external paint shall be 75
radiographed. Interpretations of microns minimum.
radiography shall be as per IS:
2825.
5.1.2 Hose:
C. Hydrostatic Test:
A sample discharge hose with ensure conformity with
nominal bore of 10 mm and a length manufacturing standards.
of not less than 300 mm shall be
tested upto bursting which shall not ii. Fabrication:
be less than 50 kg/cm² g. Actual
burst pressure of the hose shall be The following checks shall be
recorded. carried out prior to and during
welding:
5.1.3 Pressure Indicator:
a. Review and approval of
Ensure that the pressure indicator welding procedure.
as in 3.8 of this Section is fitted to
the extinguisher. b. Qualification of the welding
procedure and welders.
5.1.4 Repairs:
c. Inspection of edge preparation
i. Any repairs to welding shall be and joint fit up.
carried out as per IS: 2825. Only
one time repair shall be allowed. d. Ensuring that during welding
ii. Any extinguisher which fails in only approved procedure and
hydrostatic test shall be reoffered for approved electrodes are being
inspection. If the failure is in the used.
parent metal then the extinguisher
shall be rejected. iii. Testing:

The weld failure shall be suitably a. Radiography :


repaired as per IS : 2825 and
reinspected /tested. Spot radiography of the welds
of pipes shall be carried out.

b. Hydrostatic Test:
5.2 TOTAL FLOODING AND LOCAL
APPLICATION SYSTEMS: The system shall be
hydrostatically tested to the
5.2.1 CYLINDERS: test pressure recommended
by designer/vendor of the
These are generally made using system.
CO2 cylinders with the approval of
Chief Controller of Explosives, CO2 5.2.3 Safety Valves:
Fire Extinguishing System Section
may be referred for inspection etc. Safety devices shall be tested at the
Halon cylinders of 75 kg capacity is required pressure.
tested to a pressure of 124 bar.
5.2.4 Hose:
5.2.2 Piping and Fitting:
A sample discharge hose shall be
i. Material Identification: tested upto bursting pressure, which
shall not be less than 100 kg/cm2.
Piping and fitting materials shall be Actual burst pressure of the hose
identified and if required tested to shall be recorded.
5.2.5 Repairs:
Discharge nozzle may be clogged
Any piping system, which fails in due to foreign material.
hydrostatic test, shall be reoffered
for inspection. The weld failure shall 6.2 FREQUENCY AND PROCEDURE
be suitably repaired and reinspected FOR INSPECTION:
/tested.
The extinguisher and its
6.0 PERIODIC INSPECTION OF components shall be inspected at
EXTINGUISHERS: frequencies specified and as per
procedure given below.
6.1 LIKELY LOCATION OF
DETERIORATION: 6.2.1 Portable Extinguishers:

6.1.1. Corrosion: i. Body of cylinder:

The external side of the a. Visual Inspection:


extinguishers, support, valves and
discharge nozzles are prone to The shell of the extinguisher shall be
atmospheric corrosion. visually inspected externally once a
month to check for any mechanical
6.1.2. Damage / Deterioration: damage or corrosion.

i) Shell: b. Hydrostatic Test:

Shell may be damaged due to A hydrostatic test of the cylinder


improper handling. Dents/ shell along with assembly shall be
deformations may occur. done before every refilling or once in
5 years whichever is earlier.
ii) Neck Ring: Ultrasonic thickness inspection of
shell shall be carried out during each
Neck rings are prone to breakage at hydrotest.
weld joint.

iii) Neck Joint: c. Painting:

The thread joint between cap and The painting shall be checked for
neck is prone to damage/deterioration once in three
damage/wear/deterioration. months.

d. Rejection Limit:
iv) Nozzle:
A Halon extinguisher shall be
The nozzle may be eroded due to
removed from service and destroyed
frequent use of extinguishers.
when the following condition exists:
v) Spring: 1. When the cylinder is
corroded or damaged to
The spring is prone to lose its such an extent that repairs
stiffness. by welding, brazing or by
use of patch work is
vi) Hose: required.
The hose is prone to ageing. 2. When the cylinder or shell
threads are damaged.
vii) Discharge Nozzle:
3. When the cylinder has been to check for any mechanical
exposed to high damage or corrosion.
temperature due to
proximity of fire. b. Ultrasonic Inspection:

ii. Other Components: Ultrasonic thickness measurements


of the shell shall be carried out once
The following components shall be every three years and readings shall
visually inspected once every three be recorded.
months.
c. Hydrostatic Test:
a. Neck Ring:
The cylinder shall be hydrotested
The soundness of the when the cylinder is sent for refilling
brazing/welding of the neck ring to or as per statutory requirements
the shell shall be checked. whichever is earlier.

b. Spring: d. Painting:

The spring shall be inspected for The external painting shall be


corrosion. checked for damage/deterioration
once in three months. The coating
c. Nozzle and Discharge Fitting: thickness shall be checked once
every three years.
The nozzle and other fittings shall be
checked for erosion. ii. Other Components:

d. Squeeze Grip Valve: The following components shall be


visually inspected once every six
The squeeze grip valve shall be months.
checked for damage.

iii. Hose: a. Piping:


The hose condition shall be checked
visually once in three months. The Piping shall be inspected for
hose on the portable extinguishers evidence of corrosion. Thickness
shall be replaced within three years. shall be gauged every three years.

iv. Pressure Indicator: b. Pipe Hangers /Straps:

Pressure indicator shall be Pipe hangers/straps shall be


inspected every three months examined to check that the pipe is
visually and calibrated at the time of securely supported.
recharging.
c. Nozzle:
6.2.2 Total Flooding and Local
Application Systems: Nozzles shall be checked to
determine that the orifices are clear
i. Body of the Cylinder and unobstructed. Where nozzle
seals are provided they shall be
a. Visual Inspection: checked for signs of deterioration
and replaced if necessary. Nozzles
The shell shall be visually inspected shall be checked for proper position
externally once every three months and alignment.
d. Container Bracketing /Supports:
iii) Materials used for construction.
Bracketing/ supports shall be
checked to determine that their iv) Hydrostatic test pressure.
condition is satisfactory.
v) Relief valve testing, if any.
iii. Hose:
vi) Painting details.
The condition of hose shall be
checked visually once in three vii) Identification marking as per
months. The hose shall be relevant code.
hydrostatically tested every three
years and replaced within 6 years. 7.2 INSTALLED EXTINGUISHERS /
INSTALLATIONS:
iv. Safety Valve:
In addition to the required tag or
The safety valve shall be visually labels, a permanent tag record shall
inspected for damage once every be kept for each extinguisher/
three months and same shall be installation. The record shall include
bench tested annually. the following information as
applicable.
v. Pressure Indicator:
i) Identification number
Pressure indicator shall be
inspected visually every three ii) Date of manufacture
months for corrosion/damage
visually.

iii) Name of manufacturer


vi. Copper Tubing:
iv) Capacity of extinguisher
Copper tubing shall be inspected
visually every three months for v) Location at which the
corrosion/ damage visually. extinguisher is installed

vii. All Systems: vi) Date of installing the equipment

All systems shall be thoroughly vii) The inspection date and name
inspected and tested for proper of the person or agency
operation by competent personnel performing the inspection
annually.
viii) The pressure test record
7.0 MARKING & DOCUMENTATION:
ix) The date when last recharged
7.1 NEW EXTINGUISHERS / and the name of the person
INSTALLATION: or agency performing the
charge
The manufacturer shall furnish test
certificates giving the following information: x) The hydrostatic test date and
the name of the person or
i) Certificate number and date. agency performing the test

ii) Size, type and capacity. xi) Next hydrotest date


6) IS : 1239- Specifications for mild
xii) Inspection observations and steel tubes, tubulars and other
maintenance carried out wrought steel fittings

8.0 REFERENCE S: NOTE: Serious concern has recently been


expressed regarding depletion of
1) IS : 11108 Specification for Portable stratospheric ozone layer by halon.
Fire Extinguishers - Halon 1211 The ozone layer acts as a
Type. protective barrier shielding the
earth from harmful effects of solar
2) IS : 2825 Code for Unfired Pressure ultraviolet radiations. While search
Vessels. for an “ideal substitute” for halons
is continuing, it has been decided
3) NFPA : 12 A- Halon 1301 Fire to completely stop indigenous
Extinguishing Systems; 12 B- Halon production of halons in India by
1211 Fire Extinguishing Systems 2010 consistent with Montreal
Protocol. Steps have also been
4) ASTM A 53, A106- Mild steel piping initiated to reduce release of halons
specifications to atmosphere by actions like
discontinuing discharge of halons
5) API 5L- Mild steel piping from extinguishers/systems during
specifications their maintenance & testing,
arranging recovery of halons from
discarded halon extinguishers etc.

SECTION - V

FOAM FIRE EXTINGUISHING SYSTEM

1.0 DEFINITION & TYPES OF The capacity of a foam fire engine is


EXTINGUISHERS more when compared to a portable
fire extinguisher and it is mounted
1.1. DEFINITION on wheels. The fire engines are of
50 lit and 150 lit capacity. The
A system consisting of water supply, difference between a portable foam
foam supply, proportionating equipment, extinguisher and a fire engine is only
foam makers, discharge devices and other in respect of its capacity.
allied equipment for the purpose of
adequately distributing foam over a hazard is 1.2.3 Mobile
called a Foam Fire Extinguishing System.
1.2 TYPES This includes any foam producing
unit with capacity more than 150
1.2.1 Portable litres which is mounted on wheels
and which may be self propelled or
The type in which the foam towed by a vehicle. These units may
producing equipment, materials, be connected to a suitable water
hose etc are transported by hand. supply or may utilise a pre mixed
The total liquid capacity of the inner foam solution.
and outer containers when filled to
the specified level shall be 9 liters. 1.2.4 Semi Fixed Systems

1.2.2 Foam Fire Engine/Trolley i. The type in which the system is


Mounted Foam Extinguisher equipped with fixed discharge
outlets connected to piping, which
terminates at a safe distance. The The sizes for discharge outlets and
fixed piping installations may or may connected piping for semi fixed
not include a foam maker. foam fire extinguishing system shall
Necessary foam producing materials be calculated in accordance with
are transported to the location after requirements specified in OISD-116.
the fire starts and are connected to
the piping. 2.5 FIXED SYSTEM

ii. The type in which foam solutions are Since none of the Indian Refineries
pumped through the area from a have fixed foam fire extinguishing
central foam station, the solution system, it is not covered in this
being delivered through hose lines Standard.
to portable foammakers such as
monitors, foam towers etc. 3.0 MATERIAL OF CONSTRUCTION

1.2.5 Fixed Systems 3.1.1 Material for Portable Chemical


Foam Extinguishers
These are complete installations i. Shell : IS : 513 Grade D.
piped from a central foam station,
discharging through fixed delivery ii. Inner Container: IS 410 - Cu Zn 37
outlets, to the hazard to be alloy or Polyethylene
protected. Any required pumps are to IS : 7328.
permanently installed.

iii. Syphon Tube : IS : 513 Grade

2.0 DESIGN iv. Neck Ring : Leaded Tin


Bronze
2.1 PORTABLE conforming
to Gr 2
The portable foam type fire of IS : 318.
extinguishers shall be designed and
constructed as per code IS : 933, v. Cap : —do—-
934, 10204.
vi. Seating Valve : —do—-
2.2 FOAM FIRE ENGINE/TROLLEY
MOUNTED FOAM EXTINGUISHER vii. Plunger rod for
double seal : —do—
The 50 lit capacity foam type fire
engine shall be designed and viii. Nozzle : —do—-
constructed as per code IS : 5507.
The 150 lit capacity foam type fire ix. Plunger for : Extruded
engine shall be constructed as per Brass Single Seal
code IS : 10474. conforming
to Grade
2.3 MOBILE 2 of IS: 291
or Type 1
The foam trailor with a foam tank of of IS : 319.
capacity 500 lit. and above, mounted
on trailor chassis and having a x. Nozzle : —do—-
water-cum-foam monitor on the
trailor, the system to be made as per xi. Cap Joint Washer: Natural rubber
user’s requirements. free from impurities and acid and
alkaline resistant or Buffalo leather
2.4 SEMI FIXED SYSTEM to IS: 581.
3.1.2 Materials for Portable Mechanical Fitting: —do—-
Foam Extinguishers
vii. Washers: Natural rubber free from
i. Shell : MS GR D, IS:513 - impurities .Acid and
1973 alkaline resistant.
ii. Syphon Tube: Brass Alloy No.2,
IS:407 -1966 viii .Wheels: Cast Iron conforming to FG
iii. Neck Ring: LTB 2, IS:318 - 200 of SS 210 or of MS.
1962
iv. Cap : LTB 2, ix. Cap & Nozzle: Plastics IS : 933.
IS:318 - 1962
v. Nozzle : LTB 2, x. Cap & Nozzle for
IS:318 - 1962 inner container : Plastics IS:7328
vi. Plunger : Brass GR 2, IS:291
1961
vii. Washer : Rubber, 3.1.4 Materials for Mobile Foam Trailor
Type 1A, IS:5382 -
1969 i. Foam Tank: IS : 2002/2062 or SS 410S.

viii. Spring : GR I, IS: ii. Piping: ASTM A 53, API 5L,


4454 (Part 1) - 1975 IS 1239
shall be treated for
corrosion resistance
iii. Fittings: IS : 903.
ix. Piercer : 04 GR 13, IS:6528 -
1972 iv. Hose Reel: IS : 884.

x. Hose : Shall withstand v. Hand Line Hoses: Type II of IS : 636.


Bursting PR of 50
Kg/CM2 3.1.5 Materials for semi fixed Foam Fire
Extinguishing System
xi. Gas Cartridge: IS 4947 - 1977 with
anticorrosive i. Piping: ASTM A 53, API 5L,
coating. IS-1239

3.1.3 Materials for Foam Fire ii. Fittings: ASTM A


Engines/Trolley Mounted Foam 105.
Extinguisher
4.0 CONSTRUCITON
i. Shell :IS : 2002/2062 or
SS410S 4.1 FABRICATION OF PORTABLE
EXTINGUISHERS/FOAM FIRE
ii. Inner Container : IS : 513 Grade O TRAILOR
or Cu Zn alloy to
IS:410. 4.1.1 Welding

iii. Neck Ring: Leaded Tin Bronze of The cylinder body shall be welded.
Gr.2 of IS:318 All ferrous fittings shall be welded to
the body while all non-ferrous fittings
iv. Cap: Extruded Brass Confo-rming shall be brazed.
to Grade 1 of IS : 291
or Type 1 of IS : 319. i) All welding shall be carried out using
qualified welders and agreed
v. Nozzle : —do—- welding procedures.

vi Discharge
ii) The weld joint design shall be of
square butt type for plate thickness The body of the 50 lit and 150 lit
3.0 mm and less and single V butt capacity foam fire engine shall be
for thickness higher than 3.0 mm. cylindrical with an outside diameter
of 300 plus or minus 15 mm and
iii) All welding shall be carried out using 400 plus or minus 15 mm
shielded metal arc welding and gas respectively.
tungsten arc welding techniques
only. The electrode for welding shall 4.1.3 Hose
conform to AWS/ASME
classification. The electrode The discharge hose shall have a
diameter shall not be more than 2.5 length and bore as specified in IS :
mm for SMAW and 1.6 mm for 5507. The hose shall have a
GTAW. minimum bursting pressure of 32
kgf/sq.cm.
iv) All butt welds shall be full
penetration welds. 4.1.4 Discharge Nozzle

v) All other requirements as outlined in The discharge nozzle shall be


Section II of IS: 2825 shall be designed to discharge the foam as
followed. per performance characteristics
outlined in para 5.0 of this Section.

4.1.2 Cylinder Dimensions 4.1.5 Coating


Cylinder dimensions shall be such
that a space is provided in the body On all surfaces of body of the inner
above the specified liquid levels and container, sealing disc and spindle
shall be sufficient in volume to shall be coated with lead-tin alloy.
ensure that, when the discharge The thickness of the coating shall be
nozzle is temporarily closed and the 0.012 mm minimum.
extinguisher put into operation at a
temperature of 21 plus or minus 2 4.1.6 Painting
deg C, the pressure exerted shall
not exceed 15 kgf/sq.cm. The The extinguisher shall be painted
temperature shall be the fire red conforming to Shade No 536
temperature of the solution and not of IS : 5. The paint shall conform to
the atmospheric temperature. IS : 2932.
4.2 MOBILE FOAM FIRE TRAILOR
This requirement may be satisfied AND SEMI FIXED FOAM
by providing an air space of not less EXTINGUISHING SYSTEM
than 5% of the total volume of the
extinguisher.
4.2.1 Fabrication 3.0 mm and less and single V butt
for thickness higher than 3.0 mm.
The construction of foam tank of the
mobile foam trailor and piping of the iii) All welding shall be carried out using
semi fixed foam extinguishing shielded metal arc welding and gas
system shall be welded tungsten arc welding techniques
only. The electrode for
i) All welding shall be carried out using welding shall conform to AWS/ASME
qualified welders and agreed classification. The
welding procedures.
iv) All butt welds shall be full
ii) The weld joint design shall be of penetration welds
square butt type for plate thickness
4.2.2 Painting
The foam trailor and piping shall be e. Inspection of surface defects and
painted fire red conforming to Shade removal by grinding, if any.
No 536 of IS : 5. The paint shall
conform to IS : 2932. f. Thickness measurements to confirm
for minimum agreed finished
5.0 PERFORMANCE thickness.
CHARACTERISTICS
---------------------------------------------------------- iii. Testing
Capacity of Min period during Throw Maximum
extinguisher/ which the jet shall range The following tests shall be carried out after
period for
Fire Engine/ be maintained min 90% completion of welding.
Trolley discharge
Litres Sec Mtr Sec a. Visual
---------------------------------------------------------------------
9 30 6 90
50 60 10 180 The internal and external surfaces of
--------------------------------------------------------------------- the cylinder shall be inspected
and a surface defect of more than
6.0 INSPECTION & TESTING OF NEW 5% of the shell thickness shall be
EXTINGUISHERS & ground off and the final
INSTALLATIONS DURING thickness in that same area shall be
CONSTRUCTION not less than the calculated
minimum wall thickness plus
6.1 PORTABLE EXTINGUISHERS corrosion allowance.
AND FOAM FIRE
ENGINES/TRAILORS b. Dye Penetrant Inspection

Dye Penetrant examination shall be


6.1.1 Shell & Attachments
carried out on all the formed and
knuckled areas and all fillet welds of
i. Material Identification.
all nozzles and attachments.
Material used for the cylinder shell c. Radiography
shall be identified and if required
tested to ensure conformity with Spot radiography of the welds on all
manufacturing standard. Raw cylinders shall be carried out. 10%
material/ bought out material for of the weld joint shall be
other components shall also be radiographed which shall include
identified. at least 50% of the T joints.
Interpretation of the radiographs
ii. Fabrication shall be as per IS : 2825.
The following checks shall be carried out. d. Hydraulic Test
a. Review and approval of the welding Extinguisher shell/container and the
procedure. cap assembly shall be tested to
an internal pressure of 25 kgf/
b. Qualification of the welding sq.cm. The test pressure shall be
procedure and welders. held for a minimum period of five
minutes continuously.
c. Inspection of edge preparation and
joint fit-up. e. Bursting Test
d. Ensuring that during welding only Hydraulic burst test shall be carried
approved procedure and approved out on a prototype and no
electrodes are being used. failure shall occur at a
pressure below 60 kgf /sq.cm and
35 kgf/sq.cm for portable 6.2 FOAM TRAILOR AND SEMI FIXED
extinguisher and engines SYSTEM
respectively. Actual burst pressures
shall be recorded. 6.2.1 Tank and Piping

f. Coating and Painting i. Material Identification.

The extinguisher, after performance Material used for the tank shell shall
and hydraulic test shall be be identified and if required tested to
thoroughly cleaned with water ensure conformity with
free from chemical solution. The manufacturing standard. Raw
water shall then be completely material/bought out material for
drained off and the interior of the other components shall also be
body shall be examined after 24 identified.
hours. It shall be free from all
traces of rust. Superficial rust ii. Fabrication
stains, which could be rubbed off
with a dry cloth, may be ignored. The following checks shall be
The thickness of the coating shall be carried out.
not less than 0.012 mm. The overall
dry film thickness of external paint a. Review and approval of the welding
shall be 100 microns minimum. procedure.

6.1.2 Hose b. Qualification of the welding


procedure and welders.
A sample discharge hose of
minimum 0.5 mtr length shall be c. Inspection of edge preparation and
tested upto bursting, which shall not joint fit-up.
be less than 32 kgf/sq.cm. Actual
burst pressure of the hose shall be d. Ensuring that during welding only
recorded. approved procedure and approved
electrodes are being used.
6.1.3 CAP (Plastic)
e. Inspection of surface defects and
For Testing Impact Resistance A removal by grinding if any.
steel hammer weighing 5 kg shall be
allowed to drop vertically from a f. Thickness measurements to confirm
height of 1 m on to the fire engine for minimum agreed finished
cap moulding fitted to an engine. thickness.
The engine shall be held such that
the direction of the hammer blow is iii. Testing
vertically down on to the top of the
moulding. Thereafter the engine The following tests shall be carried
should be tested for internal out after completion of welding.
hydraulic pressure of 25 kgf/sq.cm
for a period of 5 minutes without a. Visual
leakage.
The internal and external surfaces of
6.1.4 Repairs the tank shall be inspected and a
surface defect of more than 5% of
Any extinguisher, which fails in the shell thickness shall be ground
hydrostatic test, shall be re-offered off and the final thickness to that
for inspection. If the failure is in the same area shall be not less than the
parent metal then the extinguisher calculated minimum wall thickness
shall be rejected. plus corrosion allowance.
b. Dye Penetrant Inspection The external surface of the
extinguisher is prone to atmospheric
Dye Penetrant examination shall be corrosion particularly at areas where
carried out on all fillet welds of paint has peeled off. Support ring of
nozzles and attachments. the fire extinguisher is prone to
water, soil and coercive corrosion.
c. Radiography Pipe and pipe supports are likely to
corrode due to atmospheric action.
Spot radiography of the welds on all
tanks and piping shall be carried out 7.1.2 Damage/Deterioration
as per relevant code.
i. Shell
d. Hydrostatic Test
Shell may be damaged due to
The bulk tanks of the fire tender improper handling. Dents/
shall be hydrotested to a pressure of deformations may occur.
0.3 bar.

All piping except that handling ii. Neck Ring


expanded foam for other than
subsurface application shall be Neck ring is prone to breakage at
subjected to a hydrostatic pressure weld joint.
test at 14.0 kg/sq.cm or 3.5
kg/sq.cm in excess of the maximum iii. Cap/ Neck Joint
pressure anticipated whichever is
greater. All operating devices and The threaded joint between cap and
equipment shall be tested for proper neck is prone to
function. All normally dry horizontal damage/wear/deterioration.
piping shall be inspected for proper
drainage. iv. Spring
6.3 REPAIRS The spring is prone to loose its
stiffness.
Suitable repairs to welding in tank
shall be carried out as necessary. v. Nozzle
7.0 PERIODIC INSPECTION OF The nozzle may be eroded due to
EXTINGUISHERS frequent use.

7.1 LIKELY LOCATIONS OF vi. Hose


DETERIORATION
It may show cracks/signs of ageing.
7.1.1 Corrosion
7.2 FREQUENCY AND PROCEDURE
i. Internal Corrosion. FOR PERIODIC INSPECTION

Extinguisher and tank internal The extinguisher and its


surface is prone to corrosion. The components shall be inspected at
corrosion may take place where the frequencies specified and as per
internal coating is damaged and or procedure given below:
where there is a holiday in the
coating. 7.2.1 Portable Extinguishers and Foam
Fire Engine/Trolley Mounted Fire
ii. External Corrosion. Extinguisher

i. Body
a. Visual Inspection The following components shall be
inspected once in three months.
The shell of the extinguisher
shall be visually inspected once a. Inner Container
a month to check for any
mechanical damage or Withdraw the inner container for
corrosion. checking visually the sealing
system.
b. Ultrasonic Inspection
b. Neck Ring
Ultrasonic thickness
measurements of the shell shall The soundness of the
be carried out once in three years brazing/welding of the neck ring
and readings shall be recorded. to the shell shall be checked.

c. Hydrostatic Test c. Cap

A hydrostatic test of the cylinder The threading of both cap and


shell with cap shall be done once ring shall be checked. The cap
in three years. Rusty or corroded washer shall be checked for
extinguishers should be deformation.
subjected to a pressure test even
if they are not due for it and even d. Plunger
if their performance is
satisfactory. The plunger shall be checked
visually for any damage.
d. Coating and Painting
e. Piercer
The internal coating and external
painting shall be checked for The piercer mechanism shall be
damage/deterioration once in checked for its proper
three months. The coating functioning.
thickness shall be checked once
every three years. f. Spring

e. Rejection Limit The spring shall be inspected for


its shape, size and functional
An extinguisher shall be removed aspects.
from service and destroyed when
the following conditions exist: g. Nozzle and Discharge Fittings

1) When an extinguisher is The nozzle and other fittings shall be


corroded or damaged to such an checked for erosion.
extent that repairs by welding,
brazing or by use of patchwork h. Wheels
is required.
Wheels shall be checked for
2) When the cylinder or shell mobility.
threads are damaged.
iii. Hose
3) When the cylinder has been
exposed to high temp due to The hose condition shall be checked
proximity of fire. visually once in three months. The
hose of the engine and mobile trailor
ii. Other Components shall be hydrostatically tested every
three years and replaced every 6th Shall be checked visually for proper
year. functioning once every year.

7.2.2. Mobile & Semi-fixed Installations viii. Relief Valve

i. Foam Chambers/pourers on all Relief valves shall be bench tested


storage tanks once every three years.

Visual inspection to be done once in 8.0 MARKING & DOCUMENTATION


four months and pressure testing as
and when tank is taken out of 8.1 NEW ENTINGUISHER
service for M&I.
The manufacturer shall submit with
each order of fire fighting equipment
a test certificate confirming that the
ii. Foam Tanks fire fighting equipment have been
manufactured and tested in
These shall be visually inspected accordance with the required
every day for leakage etc. A Standard.
thorough internal/external
inspection, thickness survey and The test certificate shall clearly
checking for leakage by water filling furnish the following information:
shall be done once in 3 years or
earlier if necessary. i. Certificate number and date,

iii. Accessory Equipment ii. Size, type and capacity,

Proportionating devices, foam iii. Material used for construction,


maker, aspirator shall be visually
inspected once in 4 months. iv. Foam properties,

iv. Piping v. Hydrostatic test pressure,

Above ground piping shall be vi. Bursting test pressure,


examined for external corrosion and
proper drainage once in three vii. Internal/external coating details,
months. Pressure testing of normally
dry piping shall be done during M&I viii. Identification marking as per
of the tank or earlier in case visual relevant code.
inspection indicate questionable
strength due to corrosion or 8.2 INSTALLED SYSTEMS:
mechanical damage.
In addition to the required tag or
v. Control Valves labels, a permanent file record shall
be kept for each installation. The
Shall be checked visually once in record shall include the following
three years. information as applicable:

vi. Vapour Seals i. Identification number,

Shall be checked visually once every ii. Date of manufacturing /


year. commissioning,

vii. Automatic and Manual Actuating iii. Name of manufacturer,


Devices
iv. Capacity,
v. Location at which it is installed, 3. IS 951 - Crash tender combined
foam and carbon dioxide, functional
vi. Date of installation, requirements

vii. The inspection date and the name 4. IS 2097 - Specification for foam
of the person or agency making branches
performing the inspection,
5. IS 2190 - Code of practice for
viii. The date when last recharged and selection, installation & maintenance
the name of the person of first aid fire extinguishers
performing the recharge,
6. IS 4989 - Specifications for foam
ix. The hydrostatic test date and the concentrate for producing
name of the person or agency mechanical foam for fire fighting.
performing the test,
7. IS 5490 - Refills for portable fire
x. Next hydrotest date, extinguishers & chemical fire
engines
xi. Inspection observation and
maintenance carried out. 8. IS 5507 Chemical fire engine, 50
litre capacity, foam type
9.0 CONDEMNING OF CYLINDERS
9. IS 8150 - Chemical foam engine, 4
Foam cylinders may be condemned litre capacity - for marine use
when it leaks or when internal or external
corrosion, denting, bulging or evidence of 10. IS 10204 - Portable fire
rough usage exists to the extent that the extinguishers - mechanical foam
cylinders are likely to be weakened type
appreciably.
11. NFPA 11A - Low expansion foam &
Any cylinder which fails to pass combined agent systems
periodic examination or test or which for any
other defect is found to be unsafe for use 12. NFPA 11C - Mobile foam apparatus
shall be destroyed by flattening it as a whole
or after being cut into pieces in such manner 13. NFPA 16 - Installation of deluge
that the pieces cannot be again joined foam water sprinkler systems and
together by welding or otherwise to form a foam water spray systems
cylinder.
14. NFPA 20 - Installation of centrifugal
10.0 REFERENCE fire pumps

1. IS 933 - Portable chemical fire 15. OISD 116 - Fire protection facilities
extinguisher - foam type. for petroleum refineries and oil/gas
processing plants.
2. IS 934 - Portable chemical fire
extinguisher soda acid type

SECTION VI

WATER SPRINKLER SYSTEM


1.0 DEFINITION AND TYPES: 1.1 DEFINITIONS:
1.1.1 Sprinkler System: A local alarm unit is an assembly of
apparatus so constructed and
A sprinkler system, for fire protection installed that any flow of water from a
purposes, is an integrated system of sprinkler system equal to or greater
underground and overhead piping than that from a single automatic
designed in accordance with fire sprinkler of the smallest orifice size
protection engineering standards. installed on the system will result in
The installation includes one or an audible alarm on the premises
more water supplies. The portion of within 5 minutes after such flow
the sprinkler system above ground begins.
is a network for specially sized or
hydraulically designed piping 1.2 TYPES OF SPRINKER SYSTEMS:
installed generally overhead and to
which sprinklers are attached in a 1.2.1 Wet-Pipe Systems:
systematic pattern. The valve control
in each system riser is located in the A system having automatic sprinklers
system riser or its supply piping. attached to a piping system containing
Each sprinkler system riser includes water and connected to a water supply
a device for actuating an alarm so that water discharges immediately
when the system is in operation. The from sprinklers activated by fire.
system is usually activated by heat
or smoke detector or manually and 1.2.2 Dry-Pipe Systems:
discharge water over the fire
affected area. A system having automatic sprinklers
attached to a piping system with
1.1.2 Risers: nitrogen or air, under pressure, the
release of which permits the water
Risers are vertical pipes in a pressure to open a valve known as a
sprinkler system. dry pipe valve. The water then flows
into the sprinkler piping system and
1.1.3 System Riser: out through the sprinklers.

The aboveground supply pipe 1.2.3 Pre-Action System:


directly connected to the water
supply. A system having automatic sprinklers
attached to a piping system containing
1.1.4 Feed Mains: air that may or may not be under
pressure. A supplementary fire
Mains supplying risers or cross detection system installed in the same
mains. area actuates the sprinkler system
opening the valve and permitting water
1.1.5 Cross Mains: into the sprinkler system.

Pipes directly supplying the lines in 1.2.4 Deluge System:


which the sprinklers are placed.
A system having open sprinklers
1.1.6 Branch Line: attached to a piping system
connected to a water supply through
Lines of pipe from the point of a valve which is opened by the
attachment to the cross main upto operation of a fire detection system
the end sprinkler, in which the installed in the same areas as the
sprinklers are directly placed. sprinklers; opening of the valve leads
to water discharge from all sprinklers
1.1.7 Sprinkler Alarms: through the piping system.
1.2.5 Combined Dry-Pipe and Pre-
Action System: 2.5 HANGERS:

A system having automatic sprinklers The maximum distance between


attached to a piping system hangers shall not exceed 3.7 mtr. (
containing air under pressure with a 12') for 1 1/4" size pipes and 4.6 mtr.
supplemental fire detection system (15') for sizes 1 1/2" and larger.
installed in the same areas as the
sprinkler. Actuation of fire detection 2.6 SPRINKLERS:
system activates tripping devices
which open dry -pipe valves The sprinklers may be of orifice size
simultaneously and without loss of air 12.7, 15.9 & 19.1 mm. The size of
pressure in the system. It also opens orifice of the sprinkler shall be
approved air exhaust valves of the selected on the basis of level of
system with water, which usually exposure of fire. Large orifice
precedes the opening of the sprinklers should be used where
sprinklers. The fire detection system exposure is severe. Sprinklers shall
also serves as an automatic fire not be used for system working
alarm system. pressure exceeding 12.5 kg/sq.cm.
(175 psi).
2.0 DESIGN:
2.7 SPRINKLER ALARMS:
Conventional Sprinkler systems shall
be designed for a max working All remote sprinkler water flow alarm
pressure of 12.5 kg/sq.cm. (175 psi). systems shall be installed in
Sprinklers used in high voltage accordance with the following
electrical systems, control rooms, applicable NFPA Standards:
electronic systems etc. shall be
designed to relevant specifications. i) NFPA 71, Central Station Signalling
Systems
2.1 FITTINGS:
ii) NFPA 72B, Auxiliary Protective
Fittings used in Sprinkler system shall Signalling Systems
be designed to withstand the working
pressures involved, but not less than iii) NFPA 72C, Remote Station
12.5 kg/sq.cm. (175 psi) of water. Protective Signalling.

2.2 COUPLINGS & UNIONS: iv) NFPA 72D, Proprietary Protective


Signalling.
Screwed unions shall not be used on
pipe larger than 1 1/2". 2.8 RELIEF VALVES:

2.3. REDUCERS & BUSHINGS: A wet pipe system shall be provided


with a relief valve not less than 1/4" in size
A one piece reducer fitting shall be set to operate at pressure not greater than
used wherever a change is made in 12.5kg/sq.cm (175 psi). However, when the
the size of the pipe. maximum system pressure exceeds 11.8
kg/sq.cm (165 psi), the relief valve shall be
2.4 VALVES: set to operate at 0.6 kg/sq.cm (10 psi) in
excess of the maximum system pressure.
Drain valves and test valves shall be
designed to withstand 12.5 kg.sq.cm A dry pipe system shall have an
(175 psi) of water. Check valves shall approved relief valve which shall be provided
be installed in each connection if between compressor and controlling valve
there is more than one source of set to relieve at a pressure of 0.3kg/sq.cm (5
water supply.
psi) in excess of maximum system air
pressure. Welded and seamless steel pipe for ordinary
uses, Specification for Black and

Hot dipped Zinc Coated (Galvanised) pipes


2.9 PRESSURE GAUGES: ANSI/ASTM A120

The pressure gauges shall be of Specification for Black and Hot dipped Zinc
approved type and shall have a maximum coated (Galvanised) welded and seamless
limit not less than twice the normal working steel pipe for fire protection use
pressure at the point installed. It shall be ASTM A 795
installed on the following locations:
Specification for welded and seamless steel
i. Wet Pipe system pipe ANSI/ASTM A 106 Wrought steel pipe
ANSI B 36.10
On the sprinkler riser, above and
below each alarm clock valve. (Wet Specification for Electrical resistance welded
Pipe System) steel pipe
ASTM A 135
ii. Dry Pipe System
3.2 Copper Tube (Drawn Seamless)
a) On the water side and air
side of dry pipe Specification for seamless copper tube
valve. ASTM B 75

b) At the pump supplying the Specification for seamless copper water


air receiver. tube
ASTM B 88
c) At the air receiver.
Specification & general requirements for
d) In each independent pipe wrought seamless copper and copper alloy
from air supply to tube
dry pipe system and ASTM B 251

e) At the exhausters and Brazing filler metal AWS A 5.8


accelerators. (Dry Pipe
System) Solder Metal ASTM B 32

iii. Others 3.3 Pipe Thickness:

a) Above and below preaction All welded and seamless steel pipe
valve and below deluge shall have the minimum wall thickness for
valve pressure upto 20.0 kg/sq.cm (300 psi) as
per the following.
b) On air supply to Preaction
and Deluge valve. For sizes upto 4 inch ..Sch 40
(Preaction & Deluge
Systems.) For 6 inch to 12 inches ..Sch 30

3.0 MATERIALS: For 14 inch and above ..Sch 20

Pipe or tubes used in sprinkler Also refer Clause 5.8 of OISD Std
systems shall be of materials given below: 116 for guidelines on Material Specifications.

3.1 Ferrous Piping (Welded &


Seamless)
4.0 CONSTRUCTION: ii) Discs shall be retrieved.

4.1 THREADED PIPE AND FITTINGS: iii) Opening in piping shall be smooth.

Joining compound or tape shall be iv) All slag and other welding residue
applied to the threads of the pipe and not in shall be removed.
the fitting.
v) Fittings or shaped contoured nipples
Headers shall have end flange to of any length shall not
flushout the lines for removing the scales. penetrate beyond the internal
diameter of the piping.
4.2 PIPE BEND:
When reducing a pipe size in the run
The minimum radius of a pipe bend of a main, cross main, or branch, a
shall conform to the following: suitable reducing fitting designed for
that purpose shall be used.
Pipe size Min radius of bend
Torch cutting and welding shall not
2" and less 6d be permitted as means of modifying or
repairing sprinkler systems.
2-1/2 and
above 5d Pipe joined with mechanical groove
shall be joined by a listed combination of
where ‘d‘ is the nominal diameter of fittings, gaskets and grooves. When grooves
the pipe. are cut or rolled on the pipe they shall be
dimensionally compatible with the fitting.
4.3 WELDING:
Mechanical grooved coupling
All ferrous piping and fittings shall be including gaskets used on dry pipe
welded while all copper alloy piping and shall be marked for dry pipe service.
fittings shall be brazed.
5.0 INSPECTION & TESTING OF
All welding shall be carried out using WET/DRY SPRINKLER SYSTEMS
qualified welders and welding procedures in
compliance with the requirements of AWS D 5.1 SPRINKLER PIPING AND
10.9, Level Ar-3. FITTINGS:

Welding procedure, welders and i) MATERIAL:


welding machine operators shall be qualified
as per ASME SEC IX. Pipe / fittings shall be checked /
tested to ensure conformance with
Welding shall not be performed if the required standards.
there is impingement of rain, snow, sleet or
high wind on the weld area. ii) FABRICATION:

When welded outlets are formed: Inspection of the following shall be


carried out prior to and during
i) Holes in piping shall be cut to full welding:
inside diameter of fitting or
shaped/contoured nipple. a) Review and approval of the
welding procedure,

b) Qualification of welding
procedure and welders,
5.2.2. Hydrostatic Test:
c) Inspection of edge preparation
and joint fit up, All new systems including guard
piping shall be hydrostatically tested
d) Ensuring that during welding for 2 hours at not less than 13.8
only approved procedure and kg/sq.cm (200 psi) pressure or at
approved electrodes are being 3.4 kg.sq.cm (50 psi) in excess of
used. max. pressure, when the max
pressure to be maintained in the
iii) TESTING: system is in excess of 10.3
kg/sq.cm (150 psi). The test
Radiography of the welds shall be pressure shall be read from a gauge
carried out for 10 % of the weld located at a suitable point in the
joints on all piping and fittings with individual system or portion of the
size 2" and greater. system being tested.

5.2. ACCEPTANCE TESTS : 5.2.3. Permissible Leakage:

5.2.1. Flushing of Underground The inside sprinkler piping shall be


Connections: installed in such a manner that there
will be no visible leakage when the
Underground mains and leading system is subjected to the
connections to system risers shall hydrostatic test pressure.
be flushed before connection is
made to sprinkler piping in order to 5.2.4 Test Blanks:
remove foreign materials which may
have entered the underground Whenever a test blank is used, it
piping during the course of the shall be of the self-indicating type.
installation. For all systems, the Test blanks shall have red painted
flushing operations shall be lugs protruding beyond the flange in
continued until water is clear. such a way as to clearly indicate
their presence. The installer shall
Underground lines and leading have all test blanks numbered so as
connections shall be flushed at a to keep track of their use and assure
flow rate as given in the Table below their removal after the work is
or at hydraulically calculated water completed.
demand rate of the system,
whichever is greater. 5.2.5 Specific Test for Dry- Pipe
---------------------------------------------------------- Systems
Pipe Flow Flow Rate
Size Rate (USGPM) (L/min) i. Differential dry-pipe valves:
----------------------------------------------------------
4" 390 1476 The clapper of the differential type
6" 880 3331 dry-pipe valve shall be held off its
8" 1560 5905 seat during any test in excess of
10" 2440 9235 3.4kg/sq.cm (50 psi) to prevent
12" 3520 13323 damaging the valve.
----------------------------------------------------------
The above mentioned flow rates ii. Air test:
ensure a flow velocity of 3 mt/sec as
required by NFPA. The pneumatic system is subjected
to an air pressure of 2.8 kg.sq.cm
Provision shall be made for the (40 psi) and allowed to stand for 24
disposal of water issuing from test hours. All leaks which allow a loss
outlets to avoid property damage. of pressure by 0.1 kg/sq.cm (1.5 psi)
in 24 hours shall be rectified.
iii. Operating test of Dry-Pipe valve: All piping & its components shall be
examined to determine condition and proper
A working test of the dry-pipe valve drainage at intervals of not more than one
alone and with quick opening year as per OISD Standard 116.
device, if installed, shall be made
before acceptance by opening the Threaded portion of the lines
system test pipe. Trip and water connecting the deluge release valve, block
delivery times shall be measured valve, diaphram unit spring and water alarm
from the time inspector’s test pipe is turbine shaft shall be checked more
opened and shall be recorded. critically.

5.2.6 Performance Test 6.0 DOCUMENTATION:

Frequency of performance tests The manufacturer shall furnish test


shall be as per OISD-116. certificates giving the following information:

5.2.7 Test of Drainage Facility: i. Certificate Number & Date,

Test for drainage facilities shall be ii. Hydraulic Calculations,


made while the control valve is wide
open. The main drain valve shall be iii. Materials used for Construction,
opened and remains open until the
system pressure stabilizes. iv. Hydrostatic test pressure,

5.3 LIKELY LOCATIONS OF v Coating details, if any,


DETERIORATION:
vi. Location at which it is installed,
5.3.1 External Corrosion
vii. Date of installation,
System components installed
outdoors or in the presence of a viii. The inspection date and name of
corrosive atmosphere are prone to the person or agency
atmospheric corrosion. performing the inspection,

5.3.2 Internal Corrosion ix. The acceptance test date and the
name of the person or agency
This will vary depending upon the performing the tests,
water chemistry.
x. Next test date,
5.4 FREQUENCY AND PROCEDURE
xi. Inspection observations and
FOR INSPECTION:
maintenance carried out.
During weekly, or other scheduled
plant inspection, equipment shall be 7.0 REFERENCE:
checked for obvious defects such as broken
or missing parts, nozzle loading, or other 1. NFPA 13 - Installation of Sprinkler
evidence of impaired protection. systems

Strainers, except individual nozzle 2. ASTM Material specifications - A


strainers shall be thoroughly inspected after 120/ A 795/ A 135/ A 106/ B 36.10/
each operation, or flow test and cleaned, if B 75/ B 88/B 32/B 251
necessary. Routine inspection and cleaning
shall be performed at intervals of not more 3. OISD 116 - Fire protection facilities
than 12 months or more frequently based on for petroleum refineries and oil/gas
experience. processing plants
SECTION - VII

FIXED WATER SPRAY SYSTEM FOR FIRE PROTECTION


Fixed water spray system, also High velocity water spray systems
called procto-sprays or drenchers, are are installed to extinguish oil fires
meant to protect an equipment from involving liquids with flash point of
exposure to extraneous heat. 65°C or higher. Medium velocity
water spray systems are installed to
1.0 DEFINITION AND APPLICABILITY control the burning and to provide
cooling and/or exposure protection.
1.1 DEFINITION:
1.1.4 Automatic Fire Detection
1.1.1 Water Spray: Equipment:

Water in a form having a Equipment which will automatically


predetermined pattern, particle size, detect heat, flame, smoke,
velocity and density discharged from flammable gases, or other
specially designed nozzles or conditions likely to produce fire or
devices is termed as water spray. explosion and cause automatic
actuation of alarm and protection
equipment. The detector rating shall
1.1.2 Water Spray Nozzles: be atleast 30°C above the highest
ambient temperature. The detection
A special discharge device, which piping and equipment shall be
will distribute the water in special, supported independently as far as
directional pattern, peculiar to it, possible. The system should
when supplied with water under actuate the deluge valve within 20
pressure. seconds.

1.1.3 Water Spray System: 1.1.5. Exposure Protection:

A special fixed pipe system Application of fixed water spray on


connected to a reliable source of fire to the equipment to limit absorption
protection water supply, and of heat to a level which will minimize
equipped with water spray nozzles damage and prevent failure
for specific water discharge and irrespective of internal or external
distribution over the surface or area heat.
to be protected. The piping system
is connected to the water supply 1.2. APPLICABILITY:
through an automatically or
manually actuated valve, which Fixed water spray is applicable for
initiates the flow of water. An protection of specific hazards and equipment
automatic valve is actuated by and may be installed independently of or
operation of automatic detection supplementary to other form of fire
equipment installed in the same protection system or equipment.
area as the water spray nozzles. In
certain cases, the automatic High velocity water spray system are
detection equipment may also be installed for protection of the following:
located in another area.
i. Transformers, oil filled equipment of
The water spray system could be of power stations
high velocity or medium velocity.
ii. Turbo-alternators There are limitations to the use of
water spray, which shall be recognised.
ii. Oil fired boiler rooms, oil quenching Such limitations involve the nature of the
tanks etc. equipment to be protected, the physical and
chemical properties of the materials involved
Medium velocity water spray systems are and the environment of the hazard like
used for: electrical clearance, frothing etc.

i) General area protection Both medium and high velocity


water spray systems are designed at a
ii) Horizontal storage vessels (LPG minimum flow rate as stipulated in relevant
bullets etc.) OISD Standard. The density of water
application depends upon the flash point of
iii) Vertical storage tanks the liquids handled and also the ceiling
height distance of sprayers from the risk.
iv) Spheres There shall be atleast one sprayer to each 9
Sq.m. area of the floor of risk. The distance
v) Protection of specific spots/areas in between adjoining sprayers shall not exceed
an equipment. 3 metres. In case of vessels like
spheres/bullets, the number and distance of
2.0 DESIGN: sprayers shall be selected based on the
sprayers density, angle of discharge and the
Before a fixed water spray system is diameter of the vessel.
installed or existing equipment is modified,
complete specifications, hydraulic 2.1. SIZE OF WATER SPRAY
calculations and working plans shall be SYSTEMS:
prepared.
Many factors govern the size of a
The practical location of on the water spray system, including the nature of
piping and nozzles with respect to the hazard or combustibles involved, amount
surface to which the spray is to be applied or and type of equipment to be protected,
to the zone in which the spray is to be adequacy of other protection, and the size of
effective , is determined largely by the the area, which could be involved in a single
physical arrangement and the protection fire. The size of the system needed may be
needs of the installation requiring protection. minimized by taking advantage of possible
Once the criteria are established, the size of subdivision by fire walls, by limiting the
nozzles to be used, the angle of the nozzle potential spread of flammable liquids by
discharge cone and the water pressure dikes, curbs, or special drainage; by water
needed can be determined. curtains or heat curtains; or by combination
of these features.
The first factor to determine is the
water quantity required absorbing the Because most water spray system
expected release of heat from exposure or must perform as deluge type systems with
heat of combustion. When this is all nozzles or devices open, and because a
determined, a nozzle may be selected that high density of water discharge is often
will provide that quantity at a velocity needed, there is a heavy water demand.
adequate to overcome air currents and to
carry the spray to the equipment to be The size of a single water spray
protected. Each nozzle selected must also system be limited only by the available water
have the proper angle of discharge to cover supply so that the designed discharge rate
the area to be protected by the nozzle. will be calculated at the minimum pressures
for which the nozzles are effective.
Also refer para on Water Spray Experience has shown that in most
Application Rate in OISD Standard 116. installations, a design discharge rate of
3,000 gpm (11,356 lt/min) should not be
exceeded for a single system. Separate fire
areas should be protected by separate Also refer Annexure 1 of OISD
systems. Standard 116 for Typical Water Demand
Rate Calculations.
2.2 WATER SUPPLIES:
2.4 PIPE SIZES:
Fixed spray systems are usually
supplied from one or more of the following: Pipe sizes must be calculated for
each system in order that the water at the
i) Connection from a reliable spray nozzles will have adequate pressure.
waterworks system of adequate In medium velocity water spray systems,
capacity and pressure. water pressure at nozzle outlet shall be 1.4
to 3.5 kg/cm2.
ii) Automatic fire pumps having reliable
power and a water supply of 2.5 SELECTION AND USE OF SPRAY
adequate capacity and NOZZLES:
reliability.
The selection of spray nozzles takes
iii) An elevated (gravity) tank of into consideration such factors as the
adequate capacity and character of the hazard to be protected, the
elevation. purpose of the system, and possible severe
wind or draft conditions.
In some situations where the water
supply is extremely limited, a cycle system, High velocity spray nozzles,
which collects and reuses water, may be generally used in piped installations,
acceptable. It is imperative, however, that discharge in the form of a spray filled cone,
foreign material and fuel be separated from while low velocity spray nozzles usually
the water before it is returned to the water deliver a much finer spray in the form of
spray system. either a spray filled spheroid or cone. Due to
difference in size of orifices in the various
2.3 WATER DEMAND RATE: nozzles and the range of water particle sizes
produced by each type, nozzles of one type
The water supply must be adequate should not be substituted. In general, higher
to supply at the effective pressure all of the the velocity and the coarse the size of water
spray nozzles that may be expected to droplets, the greater the effective reach or
operate in a fire in the protected area. range of spray.
Additional water may be required for hose
streams and should be considered when the Some open (nonautomatic) spray
system is designed. The duration of the nozzles produce spray by giving the water
discharge required will vary according to the high rotary motion in spiral passages inside
nature of the hazard, the purpose for which the nozzle body.
the system is designed, and other factors
which can be evaluated only for each The sprayers shall not be less than
installation. 6 mm in orifice size and shall normally have
cone angles between 60° to 125°. Sprayers
Water demand is specified in terms with cone angles below 60° are permissible
of density of a uniformly distributed spray for local protections only. Sprayers shall be
measured in lt/min/sq.mtr (gpm/sq.ft) of area installed normal to the exposed area of the
protected. The discharge rate per unit of vessel and positioned at distance as
area depends on whether the spray system calculated from vessel diameter, spray cone
is installed for extinguishment of fire, control angles, density etc. Minimum clear distance
of fire, exposure protection, or prevention of between water spray nozzles and live
fire, and upon the characteristics of the uninsulated electrical components shall
materials involved. conform to the guidelines given in NFPA-13.

2.6 STRAINERS:
Strainers are ordinarily required in
the supply lines of fixed piping systems to Care shall be taken in the selection
prevent clogging of the nozzles. They should of nozzle types. Distance of ‘throw‘ or
be selected with baskets having holes small location of nozzle from surface shall be
enough to protect the smaller water limited by the nozzle‘s discharge
passages in the nozzles used. characteristics.

Water spray nozzles having very Care shall also be taken in the
small water passage may have their own selection of nozzles to waterways, which are
internal strainer as well as a supply line easily obstructed by debris, sediment, etc.,
strainer to remove larger foreign material. in the water.

2.7 DRAINAGE: 2.8.3 Piping:

Fixed pipe open nozzle water spray Pipes used in water spray systems
systems discharge large quantities of water. shall conform to ASTM A-53, A 106,API 5L
To limit the spread of flammable liquids, or IS 1239. Piping shall be designed to
special drainage and disposal facilities withstand a working pressure of not less
including fire traps should be provided. than 12.2 bars (175 psi).
Pitched floors, curbs, dikes, sumps or
trenches etc. designed for safe disposal may 2.8.4 Fittings:
be required alone or in combination as best
adapted for specific situation. All fittings shall be of a type
specifically approved for fire protection
The drainage system shall be adequate for: systems and of a design suitable for working
pressures involved, but not less than 12.2
a) Water discharged from fixed fire bars (175 psi) cold water pressures. Ferrous
protection systems at maximum flow fittings shall be of carbon steel.
conditions
Galvanized fittings shall be used
b) Water likely to be discharged by where galvanized pipe is required.
hose streams
2.8.5 Hangers:
c) Surface water
Hangers shall be of approved type
d) Cooling water normally discharged for use with the piping involved. Hangers
to the system. used out doors or in locations where
corrosive conditions exist shall be
2.8 MATERIALS: galvanized or suitably coated for protection
against the corrosive condition of the
Only approved materials and location.
devices shall be employed in the installation
of systems as described below: 2.8.6 Pressure Gauges:

2.8.1 Corrosion Protection: Pressure gauges shall be of


approved type and shall have a maximum
System components installed limit not less than twice the normal working
outdoors, or in the presence of a corrosive pressure when installed.
atmosphere, shall be constructed of
materials, which will resist corrosion, or be 2.8.7 Strainers:
covered with protective coatings. The
threaded ends of galvanized pipe, after Pipeline strainers shall be
installation, shall be protected against specifically approved for use in water supply
corrosion. connections. Strainer shall be capable of
removing from the water all solids of
2.8.2 Spray Nozzles: sufficient size, which can obstruct the spray
nozzle. In addition, the strainer shall be Joint compound or tape shall be
capable of continued operation without applied to threads of the pipe and not in the
serious increase in head loss, for a period fittings.
estimated to be ample when considering the
type of protection provided, the condition of Sprinkler headers shall have end
the water and similar local circumstances. flange to flushout the lines to remove the
Pipe strainer designs shall incorporate a scales.
flush out connection. Individual strainers for
spray nozzles where required, shall be of 4.0 ACCEPTANCE TESTS:
approved type.
4.1 FLUSHING OF PIPING:
2.2.8 Control Equipment:
Underground mains and lead-in
Automatic valves shall be special connections to the system risers shall be
system water control valves approved for the flushed thoroughly before connection is
use intended. made to the system piping in order to
remove foreign materials which may have
Automatic detection equipment shall entered the underground piping during the
be of a type listed by a testing laboratory for course of installation or which may have
the indented usage such as with special been present in the existing piping. All
systems water control valves. When used, system piping shall be flushed where
electrical type detection equipment shall practicable; otherwise, cleanliness shall be
meet the area electrical area classification determined by visual examination.
requirements.
4.2 HYDROSTATIC PRESSURE TEST :
3.0 CONSTRUCTION:
All new system piping shall be
3.1 HEADERS: hydrostatically tested in accordance with the
specifications.
Refer Criteria for Underground /
above ground network in OISD Standard 4.3 WATER DISCHARGE TEST:
116.
When practicable, full flow tests with
Weld Procedure and Welder water shall be made in system piping as a
qualification shall be done as per relevant means of checking the nozzle lay-out,
code before commissioning the job. discharge pattern, any obstructions and
determination of relation between design
Stagewise inspection with visual and criteria and actual performance and to
other NDE methods shall be carried out as ensure against clogging of the smaller piping
required. Repairs shall be carried out as per and the discharge devices by foreign matter
approved procedure and shall be carried by the water.
reinspected prior to final acceptance.
When practicable, the maximum
3.2 THREADED PIPES & FITTINGS: number of systems that may be expected to
operate in case of fire shall be in full
Steel pipe with wall thickness less operation simultaneously in order to check
than schedule 30 (in sizes 8" and larger) or the adequacy and condition of the water
schedule 40 (in sizes less than 8") shall not supply.
be joined by threaded fittings.
The discharge pressure at the
All threaded fittings and pipes shall highest, most remote nozzle shall be atleast
have threads cut to ANSI B2.1, Pipe that for which the system was designed.
Threads (except dry seal).
4.4. OPERATING TESTS:
All operating parts of the system Flow test on open head spray
shall be fully tested to ensure that they are in systems shall be made yearly or
operating condition. The operating tests shall more frequently as determined by
also include a test of automatic detection experience.
equipment.
5.2.2. Control Valves and Automatic
5.0 PERIODIC INSPECTION AND Detection Devices
TESTING:
Control valves and automatic
5.1 LIKELY LOCATIONS OF detection equipment shall be tested
DETERIORATION (CORROSION): annually by qualified personnel.

i. External Corrosion: Where normally opened valves are


closed following system operation or
System components installed test, suitable procedures shall be
outdoors or in a corrosive atmosphere shall instituted to ensure that they are
be constructed of materials, which will resist reopened and that the system is
corrosion, or be covered with protective promptly and properly restored to full
coatings. The threaded ends of galvanized normal operating condition. Main
pipe, after installation shall be protected drain flow test shall be made after
against corrosion. valves are reopened.

ii. Internal Corrosion: 5.2.3 Spray Nozzles:

This will vary depending upon the All spray nozzles shall be inspected
water chemistry and the system should be for proper positioning, external
checked for thickness at a pre-determined loading, and corrosion and cleaned
frequency. Threaded portion of the lines if necessary, at intervals of not more
connecting the deluge release valve, Clock than 12 months or more frequently if
valve diaphram unit spring, water alarm necessary based on experience.
turbine shaft shall be inspected more
critically. 5.2.4 Performance Test

5.2 FREQUENCY AND PROCEDURE Frequency of performance tests


FOR INSPECTION: shall be as per OISD-116.

During monthly, or other scheduled 5.2.5 Flushing:


plant inspections, equipment shall be
checked for obvious defects such as broken Lead-in connections to system risers
or missing parts, nozzle loading, or other shall be flushed atleast annually.
evidence of impaired protection.

Strainers, except individual nozzle


strainers shall be thoroughly inspected after
each operation, or flow test and cleaned, if
necessary. Routine inspection and cleaning
shall be performed at intervals as per OISD 6.0 DOCUMENTATION:
Standard 116.
The manufacturer shall furnish test
5.2.1 Piping System: certificates giving the following information:

At intervals of not more than one


year, all piping shall be examined to i) Certificate Number & Date,
determine condition and proper
drainage. ii) Hydraulic Calculations,
<< Back Home Next >>

You might also like