BQ
BQ
BQ
Measured Works
C3 Retail Hi Street -Pioneer Park -Gurgaon
C3-3000 - Main Works
Bills of Quantities for Electrical Works
1 Please fill up rate both in figures and words in the Rate column by putting the rate figure first.
2 Please total up Sub Head wise and carry forward to Summary of Costs
Rate (RS.)
S.No: Description Unit Qty Amount (Rs.)
Supply Installation
SUB HEAD I – WIRING
1 Supply and wiring for primary light points for switch controlled
points with 1.5 sq. mm PVC insulated FRLS stranded /
multistranded copper conductor 1100 Volt grade wires in MS
surface/concealed conduit including cost of providing circuit
wiring with 2.5mm2 PVC insulated stranded copper conductor
1100V grade wire and including cost of providing G.I saddles
hangers supports from soffit of slab etc for surface conduiting,
ceiling conduiting and/or cost of cutting and filling chases for nos 274
recessed conduiting, and including the cost of providing and
fixing a 6 amp 240 Volt grid plate mounted switch with moulded
cover plate in zinc chromate passivated MS box and including the
cost of running 1.5 sq. mm PVC insulated FRLS copper earth
wire for loop earthing etc. complete as per specifications and as
required.
0
1.1 Supply and wiring for primary light points for two way switch
controlled points with 1.5 sq. mm PVC insulated FRLS stranded /
multistranded copper conductor 1100 Volt grade wires in MS
surface/concealed conduit including cost of providing circuit
wiring with 2.5mm2 PVC insulated stranded copper conductor
1100V grade wire and including cost of providing G.I saddles
hangers supports from soffit of slab etc for surface conduiting,
ceiling conduiting and/or cost of cutting and filling chases for nos 163
recessed conduiting, and including the cost of providing and
fixing a 6 amp 240 Volt grid plate mounted switch with moulded
cover plate in zinc chromate passivated MS box and including the
cost of running 1.5 sq. mm PVC insulated FRLS copper earth
wire for loop earthing etc. complete as per specifications and as
required.
1.2 Supply and wiring for primary light points for two way switch
controlled points with 1.5 sq. mm PVC insulated FRLS stranded /
multistranded copper conductor 1100 Volt grade wires without
MS surface/concealed conduit with cost of providing circuit
wiring with 2.5mm2 PVC insulated stranded copper conductor
1100V grade wire and including cost of providing G.I saddles
hangers supports from soffit of slab etc for surface conduiting,
ceiling conduiting and/or cost of cutting and filling chases for
recessed conduiting, and including the cost of providing and nos 162
fixing a 6 amp 240 Volt grid plate mounted switch with moulded
cover plate in zinc chromate passivated MS box and including the
cost of running 1.5 sq. mm PVC insulated FRLS copper earth
wire for loop earthing etc. complete as per specifications and as
required. (Emergency)
1 Please fill up rate both in figures and words in the Rate column by putting the rate figure first.
2 Please total up Sub Head wise and carry forward to Summary of Costs
Rate (RS.)
S.No: Description Unit Qty Amount (Rs.)
Supply Installation
3 Supply and wiring for primary light points for switch controlled
points as in item 1 above but in existing conduits complete as nos
required
0
4 Supply and wiring for primary light points for MCB /Occupancy
Sensor controlled points with 2.5 sq. mm PVC insulated FRLS
stranded/multistranded copper conductor 1100 Volt grade wires in
MS surface/concealed conduit including cost of providing G.I
saddles etc for surface conduiting and/or cost of cutting and filling
chases for recessed conduiting and including the cost of running nos 347
2.5 sq. mm PVC insulated FRLS copper earth wire for loop
earthing etc. complete as per specifications and as required. (Cost
of MCB included in the item for DB)
0
5 Supply and wiring for primary light points for MCB controlled
points as in item 4 above but in existing conduits complete as nos
required
0
6 Supply and wiring as in Item 4 above for emergency primary &
secondary light points max distance shall be approx 30m for MCB
controlled points but in existing conduits complete as required. nos 467
0
7 Supply and wiring for secondary light points with 1.5 sq. mm
PVC insulated FRLS stranded/multistranded copper conductor
1100 Volt grade wires in surface/concealed MS conduit including
cost of providing G.I saddles hangers supports from soffit of slab
etc for surface conduiting, ceiling conduiting and/or cost of
cutting and filling chases for recessed conduiting including the nos 2114
cost of running 1.5 sq. mm PVC insulated FRLS copper earth
wire for loop earthing complete as per specification and as
required.
0
8 Supply and wiring of secondary light point as of item no. 7 but in
PVC conduit as required. nos
0
9 Supply and wiring for secondary light points as in item 7 above
but in existing conduits complete as required nos
0
Bill No 2. Measured Works
C3 Retail Hi Street -Pioneer Park -Gurgaon
C3-3000 - Main Works
Bills of Quantities for Electrical Works
1 Please fill up rate both in figures and words in the Rate column by putting the rate figure first.
2 Please total up Sub Head wise and carry forward to Summary of Costs
Rate (RS.)
S.No: Description Unit Qty Amount (Rs.)
Supply Installation
10 Supply and wiring for Ceiling fan points with 1.5 sq. mm PVC
insulated FRLS stranded/multistranded copper conductor 1100
volt grade wires in MS surface/concealed conduit including cost
of providing G.I saddles etc for surface conduiting and/or cost of
cutting and filling chases for recessed conduiting and including
the cost of fan box with hook, providing and fixing a 6 amp 240
volt single pole grid plate mounted switch with moulded cover
plate in a recessed zinc chromate passivated MS box with space nos 3
for mounting an electronic fan regulator but including cost of
blank plates on the cover plate as required and 1.5 sq. mm PVC
insulated FRLS copper earth wire for loop earthing etc. complete
as per specification and as required.
0
11 Supply and wiring for Exhaust fan points with 1.5 sq. mm PVC
insulated FRLS stranded/multistranded copper conductor 1100
volt grade wires in MS surface/concealed conduit including cost
of providing G.I saddles etc for surface conduiting and/or cost of
cutting and filling chases for recessed conduiting and including
the cost of providing and fixing 3 pin 6 amp shuttered socket
outlet a 6 amp 240 volt single pole grid plate mounted switch with nos
moulded cover plate in a recessed zinc chromate passivated MS
box and 1.5 sq. mm PVC insulated FRLS copper earth wire for
loop earthing etc. complete as per specification and as required.
0
12 Supply and wiring for a 5 pin 240 volt 6 amp single phase and
neutral switch socket outlet with 1.5 sq. mm PVC insulated
FRLS stranded/multistranded copper conductor 1100 Volt grade
wires in 25 mm dia 16 SWG MS surface/concealed conduit
including cost of providing G.I saddles etc as required for surface
conduiting and/or cost of cutting and filling chases as required and
providing and fixing of a combined 5 pin 240 volt 6 amp socket
outlet with safety shutters and 6 amp 240 volt single pole grid nos 52
plate mounted switch with moulded cover plate in recessed zinc
chromate passivated MS box and including earthing of the 3rd
pin with 1.5 sq. mm PVC insulated FRLS copper earth wire
conductor wires complete as required.
0
13 Supply and wiring for a 5 pin 240 volt 6 amp single phase and
neutral switch socket outlet as in item 12 above but in existing
conduits complete as required.
0
14 Supply and wiring for a 5 pin 240 volt 6 amp single phase and
neutral switch socket outlet as in item 12 & 13 above but looping nos 180
points complete as required.
0
Bill No 2. Measured Works
C3 Retail Hi Street -Pioneer Park -Gurgaon
C3-3000 - Main Works
Bills of Quantities for Electrical Works
1 Please fill up rate both in figures and words in the Rate column by putting the rate figure first.
2 Please total up Sub Head wise and carry forward to Summary of Costs
Rate (RS.)
S.No: Description Unit Qty Amount (Rs.)
Supply Installation
15 Supply and wiring for 6 pin 240 volt 16 amp single phase and
neutral switch socket outlets (1 outlet wired on 1 circuit) with 4.0
sq. mm PVC insulated FRLS stranded/ multistranded copper
conductor 1100 volt grade wires in 25mm dia 16 SWG MS
surface/concealed conduit including cost of providing G.I saddles
etc as required for surface conduiting and/or cost of cutting and
filling chases as required and including providing and fixing of a
6 pin 240 volt 16 amp socket outlet with safety shutters and 16 nos 237
amp 240 volt single pole grid plate mounted switch with
moulded cover plate in a recessed zinc chromate passivated MS
box including earthing of the 3rd pin with 4.0 sq. mm 1100 volt
grade PVC insulated FRLS stranded/ multistranded copper earth
wire complete as required
0
16 Supply and wiring for 6 pin 240 volt 16 amp single phase and
neutral switch socket outlets as in item 15 above but in existing nos
conduits complete as required
0
17 Supply and wiring for 6 pin 240 volt 16 amp single phase and
neutral switch socket outlets (2 outlets wired on 1 circuit) with
PVC insulated FRLS stranded/multistranded copper conductor
1100 volt grade wires, 6.0 sq mm upto the first outlet and 4.0 sq
mm from first to the second outlet, in 25 mm dia 16 SWG MS
surface/concealed conduit including cost of providing G.I saddles
etc as required for surface conduiting and/or cost of cutting and
filling chases and including providing and fixing of a 6 pin 240
volt 16 amp socket outlet with safety shutters and 16 amp 240 volt nos
single pole grid plate mounted switch with moulded cover plate
in a recessed zinc chromate passivated MS box including earthing
of the 3rd pin with 6.0 and 4.0 sq. mm 1100 volt grade PVC
insulated FRLS stranded/ multistranded copper conductor wire
complete as required
0
18 Supply and wiring for 6 pin 240 volt 16 amp single phase and
neutral switch socket outlets with 2.5sq.mm PVC insulated FRLS
stranded/multistranded copper conductor 1100 volt grade wires in
25 mm dia M.S surface/concealed conduit including cost of
providing circuit wiring with 2.5sq.mm PVC insulated stranded
copper conductor 1100 volt grade wires and G.I saddles etc as
required for surface conduiting and/or cost of cutting and filling
chases as required and including providing and circuit) with PVC
insulated FRLS stranded/multistranded fixing of a 6 pin 240 volt
16 amp socket outlet with safety shutters and 16 amp 240 volt nos 20
single pole grid plate mounted switch with moulded cover plate
in a surface/recessed zinc chromate passivated MS box including
earthing of the 3rd pin with 2.5 sq. mm 1100 volt grade PVC
insulated FRLS stranded/ multistranded copper conductor wire
complete as required (For Lift Shaft)
Bill No 2. Measured Works
C3 Retail Hi Street -Pioneer Park -Gurgaon
C3-3000 - Main Works
Bills of Quantities for Electrical Works
1 Please fill up rate both in figures and words in the Rate column by putting the rate figure first.
2 Please total up Sub Head wise and carry forward to Summary of Costs
Rate (RS.)
S.No: Description Unit Qty Amount (Rs.)
Supply Installation
0
19 Wiring as in item 18 above but looped from an adjacent 16amp
switch socket outlet as required and providing and fixing of a
modular type 6 pin 240 Volt 16 amp shuttered socket outlet and a
modular type 16 amp 240 volt single pole grid plate mounted nos 50
switch in a recessed GI boxes with internal wiring and moulded
front plates as per approved sample complete as required. (For
Lift shaft)
0
20 Providing and fixing following three phase and neutral
weatherproof socket outlet, interlocked plug and sockets IP55
weatherproof enclosure, complete as required. The cost shall 0
include providing as required.
0
a) 4 pole & earth 32 amp 415 volts three phase and neutral
interlocked socket outlet as required. nos
0
b) Plug Top for above sockets nos
0
21 Supplying and drawing recessed/surface MS conduiting system
including cost of providing G.I, saddles etc for surface conduiting
and/or cost of cutting and filling chases for recessed conduiting 0
complete as per specifications, as required and as below.
0
a) 25 mm 16 SWG m 8572
b) 32 mm 16 SWG m 857
c) 40 mm 14 SWG m
d) 50 mm 14 SWG m
0
22 Supply and fixing IS embossed GI surface conduiting system
including cost of providing G.I saddles etc for surface conduiting
complete as per specification, as required and as below. 0
a) 25 mm m
b) 32 mm m
0
23 Providing of Ceiling mounting Ultrasonic-cum-Passive InfraRed
Occupancy sensor of Lutron or equivalent make alongwith power
pack for power circuit operation or equivalent complete with 0
mounting accessories etc. as reqd.(for Toilet/Staircase/corridor)
0
a) 500 sqft coverage Cat No LOS-CDT-500-WH./Eq nos
0
25 Supply & fixing of PVC steel reinforced flexible conduit with 3 x
1.5 sq.mm copper conductor for down take the ceiling point up m
to the false ceiling complete as required
0
TOTAL SUB-HEAD I carried over to Summary 0
0
Bill No 2. Measured Works
C3 Retail Hi Street -Pioneer Park -Gurgaon
C3-3000 - Main Works
Bills of Quantities for Electrical Works
1 Please fill up rate both in figures and words in the Rate column by putting the rate figure first.
2 Please total up Sub Head wise and carry forward to Summary of Costs
Rate (RS.)
S.No: Description Unit Qty Amount (Rs.)
Supply Installation
SUB HEAD II – COMMUNICATION 0
0
1 Providing and fixing of a single telephone cord grid plate mounted
outlet unit (RJ-11) with moulded cover plate in recessed zinc
chromate passivated MS box complete as required for telephone nos 1
system.
0
2 Wiring for telephone points with 0.61 4-pair unarmoured copper
conductor PVC insulated telephone wires in existing m
conduit/raceways complete as required for telephone system
0
3 Wiring for telephone points with 0.61 2-pair unarmoured copper
conductor PVC insulated telephone wires in existing m
conduit/raceways complete as required for telephone system
0
4 Supply and fixing of the following sheet steel clad wall/recess
mounting telephone tag block of IDC type constructed from 16
SWG sheet steel, finished with red oxide coating of two coats of
paint, with hinged gasketted door and complete with adequately 0
rated and sized telephone terminal block to receive incoming and
outgoing wires including termination of cables as required.
0
a) 5pair/10 pair nos
b) 20 pair nos
c) 30 pair nos 0
d) 50 pair nos
e) 100 pair nos 0
f) 150 pair nos 0
g) 200 pair nos 0
h) 400 pair nos
0
4 Supply, laying in existing conduits/surface and testing and
commissioning of the following multi core 0.61 mm annealed
tinned copper conductor PVC insulated and PVC sheathed and
overall PVC sheathed unarmoured telephone cables generally 0
conforming to ITD s/WS-11-B and IS 1554 Part I as required and
including making terminal joints, complete as required.
a) 10 pair m
b) 30 pair m
c) 50 pair m
0
5 Supply and fixing of metal box of following sizes is recess
complete with laminated sheet cover including painting as 0
required.
0
a) 200 mm x 150 mm x 100 mm nos
0
Bill No 2. Measured Works
C3 Retail Hi Street -Pioneer Park -Gurgaon
C3-3000 - Main Works
Bills of Quantities for Electrical Works
1 Please fill up rate both in figures and words in the Rate column by putting the rate figure first.
2 Please total up Sub Head wise and carry forward to Summary of Costs
Rate (RS.)
S.No: Description Unit Qty Amount (Rs.)
Supply Installation
6 Supply and laying of polyethylene insulated PVC sheathed overall
shielded multi stranded annealed tinned copper conductor for
communication in the existing conduits as required. 0
a) 2 core 1.5 sq mm m
b) 3 core 1.5 sq mm m
0
7 Supplying, laying, testing and commissioning of 4-pair Non-
plenum Enhanced Cat 6 unshielded twisted pair computer cable
with 24 AWG solid copper conductors in existing m
concealed/surface raceways/conduits in partition wall, complete as
required.
0
TOTAL SUB-HEAD II carried over to Summary 0
0
SUB HEAD III – SUBMAINS AND CABLES 0
0
1 Wiring for Submains with PVC FRLS insulated stranded copper
conductor 1100 volt (P+N+E) grade wires in existing
surface/concealed conduit and making suitable end connections 0
complete as required and as below.
0
a) 3 x 2.5 sq mm m 30
b) 3 x 4.0 sq mm m 20
c) 3 x 6.0 sq mm m 20
d) 3 x 10 sq mm m 20
e) 6 x 4.0 sq mm m 20
f) 6 x 10 sq mm m 20
g) 6 x 16 sq mm m 20
0
2 Supply and laying in cable Tray/clamped to wall with suitable
clamps saddles and bolts/ in ground including the cost of digging
and back filling with sand and brick protection as required and
including testing and commissioning of the following 1100 volt
grade armoured XLPE insulated and sheathed aluminium
conductor armoured cable complete as required. The costs shall
include providing a gap of 1D between all the cables being laid 0
and properl clamping with cable clamps and ties. Prices shall
include providing and fixing of Identification tags for all cables
and route markers for cables in ground etc. as per specification
and or as per direction of Project in-charge.
0
a 4 core 300 Sq mm m
b 3 –1/2 core 400 Sq mm m
c 3 –1/2 core 300 Sq mm m
d 3 –1/2 core 240 Sq mm m
e 3 –1/2 core 185 Sq mm m
f 3 –1/2 core 150 Sq mm m
g 3 –1/2 core 120 Sq mm m
h 3 –1/2 core 95 Sq mm m
Bill No 2. Measured Works
C3 Retail Hi Street -Pioneer Park -Gurgaon
C3-3000 - Main Works
Bills of Quantities for Electrical Works
1 Please fill up rate both in figures and words in the Rate column by putting the rate figure first.
2 Please total up Sub Head wise and carry forward to Summary of Costs
Rate (RS.)
S.No: Description Unit Qty Amount (Rs.)
Supply Installation
i 3 –1/2 core 70 Sq mm m
j 3 –1/2 core 50 Sq mm m
k 4 core 35 Sq mm m
l 4 core 25 Sq mm m
m 4 core 16 Sq mm m
n 4 core 16 Sq mm copper
o 4 core 10 Sq mm m
p 4 core 10 Sq mm copper
q 4 core 6 Sq mm m
r 4 core 6 Sq mm copper
s 2 core 10 Sq mm m
t 2 core 10 Sq mm copper
u 2 core 6 Sq mm m
v 2 core 6 Sq mm copper
0
3 Cable end termination XLPE insulated 1100 Volt grade cables
including the cost of crimping tinned copper heavy duty lugs,
double compression glands, insulation tape etc. complete as 0
required and as below.
0
a 4 core 300 Sq mm nos
b 3 –1/2 core 400 Sq mm nos
c 3 –1/2 core 300 Sq mm nos
d 3 –1/2 core 240 Sq mm nos
e 3 –1/2 core 185 Sq mm nos
f 3 –1/2 core 150 Sq mm nos
g 3 –1/2 core 120 Sq mm nos
h 3 –1/2 core 95 Sq mm nos
i 3 –1/2 core 70 Sq mm nos
j 3 –1/2 core 50 Sq mm nos
k 4 core 35 Sq mm nos
l 4 core 25 Sq mm nos
m 4 core 16 Sq mm nos
n 4 core 10 Sq mm nos
o 4 core 6 Sq mm nos
p 2 core 10 Sq mm nos
q 2 core 6 Sq mm nos
0
4 Supply and fixing of perforated M.S sheet steel slotted cable trays
with vertical sides on both ends as per approved design and MS
angle supports spaced 1000 mm apart throughout the length as
specified, including the cost of 1 meter MS rod hangers, hooks, 0
dash fasteners, painting etc. for suspension from ceiling as
required
0
a) 150 mm x 50 mm x 50 mm x 1.6 mm m 640
b) 300 mm x 50 mm x 50 mm x 1.6 mm m 654
c) 450 mm x 50 mm x 50 mm x 2.0 mm m
d) 600 mm x 75 mm x 75 mm x 2.0 mm m 957
e) 750 mm x 75 mm x 75 mm x 2.0 mm m
Bill No 2. Measured Works
C3 Retail Hi Street -Pioneer Park -Gurgaon
C3-3000 - Main Works
Bills of Quantities for Electrical Works
1 Please fill up rate both in figures and words in the Rate column by putting the rate figure first.
2 Please total up Sub Head wise and carry forward to Summary of Costs
Rate (RS.)
S.No: Description Unit Qty Amount (Rs.)
Supply Installation
f) 1200 mm x 75 mm x 75 mm x 2.0 mm m 157
0
5 Supply and fixing of perforated GI slotted cable trays (for terrace)
with vertical sides on both ends as per approved design and GI
angle supports spaced 1000 mm apart throughout the length as
specified, including the cost of 1 meter GI rod hangers, hooks, 0
dash fasteners, wall brackets etc. for suspension from ceiling /
wall as required
0
a) 150 mm x 50 mm x 50 mm x 1.6 mm m
b) 300 mm x 50 mm x 50 mm x 1.6 mm m
c) 450 mm x 50 mm x 50 mm x 2.0 mm m
0
6 Supply and fixing M.S Ladder type cable trays with (vertical for
power/LV shaft) vertical sides on both ends as per approved
design of the following sizes and 15 x 30 x15 mm MS channel 0
supports spaced 250 mm apart throughout the length.
0
a) 300 x 25 x50 x 25 mm channel, 2 mm thickness(40 x 40 x 6 mm
MS angle and 10 mm MS Rod) m
0
b) 450 x 25 x50 x 25 mm channel, 2 mm thickness(40 x 40 x 6 mm
MS angle and 10 mm MS Rod) m
0
c) 600 x 50 x75 x 25 mm channel, 2 mm thickness (50 x 50 x 6 mm
MS angle and 12 mm MS Rod) m
0
0
7 Supply and fixing of additional length of MS rod hangers / MS
Channel duly painted with 2 coats of spray paint for supporting
the Cable Trays, complete for extension of the supports. The rate Kg 240.8
shall be proportionately applicable to the length of rod/channel
actually required.
0
8 Supply and laying of the following Hume pipe including
excavation, refilling as required for cable entry including the cost 0
of sealing the ends as required complete
0
a) 200 mm dia m
b) 150 mm dia m
0
9 Supply and laying of following DWC HDPE P1/2C including
excavation, refilling, cutting the road and making good for the 0
same with sealing of ends as required.
a) 63 mm outer dia m
b) 120 mm outer dia m
c) 200 mm outer dia m
0
Bill No 2. Measured Works
C3 Retail Hi Street -Pioneer Park -Gurgaon
C3-3000 - Main Works
Bills of Quantities for Electrical Works
1 Please fill up rate both in figures and words in the Rate column by putting the rate figure first.
2 Please total up Sub Head wise and carry forward to Summary of Costs
Rate (RS.)
S.No: Description Unit Qty Amount (Rs.)
Supply Installation
10 Providing and making of manhole chamber with masonry bricks
and plastering inside with 1:3:6 and fixing of Heavy duty frame 0
and pre cast RCC cover as required.
0
a) 450 x 450 x 500 mm nos
b) 600 x 600 x 900 mm nos
0
11 Supplying and fixing in recess/surface following sizes of outdoor
type Powder coated box with suitable knockouts and terminal
block as required. The cost shall include cutting, filling chases and
making good the civil works as required. (The box shall be as per 0
design to be approved by the Architects)
0
a) 100 mm wide x 40 mm deep (16 SWG) m
b) 150 mm wide x 40 mm deep (16 SWG) m
c) 200 mm wide x 40 mm deep (14 SWG) m
d) 250 mm wide x 40 mm deep (14 SWG) m
0
TOTAL SUB HEAD III carried over to Summary 0
0
SUB HEAD IV – DISTRIBUTION SYSTEM 0
0
1 Supply, erection, testing and commissioning of the following
sheet steel clad wall recess mounting dust and vermin proof
distribution boards constructed from 16 SWG sheet steel IP 42
construction, finished with rust proof powder coated paint with
hinged gasketted door and housing the following complete with
suitably rated PVC insulated copper busbars with interconnections 0
and neutral bar assembly, earthing terminals complete as
approved by Architects. Padlocking facility shall be provided on
the door.
a 8 way SPN 0
1-40 amp DP 10 kA MCB with thermal magnetic protective
releases incoming with 1-40 amp DP 30 mA ELCB incoming and
6 nos 6/16/20 amps SP 10 kA MCB with thermal magnetic nos 9
releases out goings.
0
b. 12 way SPN 0
Bill No 2. Measured Works
C3 Retail Hi Street -Pioneer Park -Gurgaon
C3-3000 - Main Works
Bills of Quantities for Electrical Works
1 Please fill up rate both in figures and words in the Rate column by putting the rate figure first.
2 Please total up Sub Head wise and carry forward to Summary of Costs
Rate (RS.)
S.No: Description Unit Qty Amount (Rs.)
Supply Installation
1-40 amp DP 10 kA MCB with thermal magnetic protective
releases incoming with 1-40 amp DP 30 mA ELCB incoming and
12 nos 6/16/20 amps SP 10 kA MCB with thermal magnetic nos 3
protective releases out goings.
0
c. 6 way TPN (per phase isolation) 0
1-63 amp TPN 10 kA MCB with thermal magnetic protective
releases incoming with 3 single phase banks each comprising of
1-63 amp DP 30 mA ELCB incoming and 6 nos 6/16/20 amps nos 1
SP 10 kA MCB with thermal magnetic protective releases out
goings.
0
d. 8 way TPN (per phase isolation) 0
1-63 amp TPN 10 kA MCB with thermal magnetic protective
releases incoming with 3 single phase banks each comprising of
1-63 amp DP 30 mA ELCB incoming and 8 nos 6/16/20/32 amps nos 14
SP 10 kA MCB with thermal magnetic protective releases out
goings.
e. 12 way TPN (per phase isolation) 0
1-63 amp TPN 10 kA MCB with thermal magnetic protective
releases incoming with 3 single phase banks each comprising of
1-63 amp DP 30 mA ELCB incoming and 12 nos 6/16/20/32 nos 9
amps SP 10 kA MCB with thermal magnetic protective releases
out goings.
0
f. 8 way TPN (with timer on 2 phases)
1-63 amp TPN 10 kA MCB with thermal magnetic protective
releases incoming with 0
0
- 1 single phase bank comprising of 1- 63 amp DP 30 mA ELCB
incoming and 8 nos 6/16/20 amps SP 10 kA MCB with thermal 0
magnetic protective releases out goings
0
- 2 single phase banks each comprising of 1-63 amp DP 30 mA
ELCB incoming with 63 amp ON position latched contactor and
24 hours programe timer for operation of incoming and 8 nos nos 9
6/16/20 amps SP 10 kA MCB with thermal magnetic protective
releases out goings
0
g. 12 way TPN (with timer on 2 phases) 0
1-63 amp TPN 10 kA MCB with thermal magnetic protective
releases incoming with 0
0
- 1 single phase bank comprising of 1- 63 amp DP 30 mA ELCB
incoming and 12 nos 6/16/20 amps SP 10 kA MCB with thermal 0
magnetic protective releases out goings
0
Bill No 2. Measured Works
C3 Retail Hi Street -Pioneer Park -Gurgaon
C3-3000 - Main Works
Bills of Quantities for Electrical Works
1 Please fill up rate both in figures and words in the Rate column by putting the rate figure first.
2 Please total up Sub Head wise and carry forward to Summary of Costs
Rate (RS.)
S.No: Description Unit Qty Amount (Rs.)
Supply Installation
- 2 single phase banks each comprising of 1-63 amp DP 30 mA
ELCB incoming with 60 amp ON position latched contactor and
24 hours programe timer for operation of incoming and 12 nos nos
6/16/20 amps SP 10 kA MCB with thermal magnetic protective
releases out goings
0
h. 8 way TPN (with timer on 3 phases) 0
1-63 amp TPN 10 kA MCB with thermal magnetic protective
releases incoming with 0
0
3 single phase banks each comprising of 1-63 amp DP 30 mA
ELCB incoming with 60 amp ON position latched contactor and
24 hours programe timer for operation of incoming and 8 nos nos
6/16/20 amps SP 10 kA MCB with thermal magnetic protective
releases out goings
0
i. 12 way TPN (with timer on 3 phases) 0
1-63 amp TPN 10 kA MCB with thermal magnetic protective
releases incoming with 0
0
- 3 single phase banks each comprising of 1-63 amp DP 30 mA
ELCB incoming with 60 amp ON position latched contactor and
24 hours programe timer for operation of incoming and 12 nos nos
6/16/20 amps SP 10 kA MCB with thermal magnetic protective
releases out goings
0
j. 6 way VTPN (Cleaning outlet DB/Sump) 0
1-63 amp TPN 10 kA MCB with thermal magnetic protective
releases incoming with 6 nos 32 amp TP 10 kA MCB with nos
thermal magnetic protective releases out goings
0
k. 8 way VTPN 0
. 1-100 amp TPN 10 kA MCCB with thermal magnetic protective
releases incoming with 8 nos 63 amp TP 10 kA MCB with nos
thermal magnetic protective releases out goings
0
l. 12 way VTPN 0
. 1-100 amp TPN 25 kA MCCB with thermal magnetic protective
releases incoming with 12 nos 63 amp DP 10 kA MCB with nos 1
thermal magnetic protective releases out goings
0
m. 1-630 amp TPN 25 kA MCCB with thermal magnetic protective
releases in MS box nos
0
n 1-400 amp TPN 25 kA MCCB with thermal magnetic protective
releases in MS box nos
0
n 1-315 amp TPN 25 kA MCCB with thermal magnetic protective
releases in MS box nos
0
Bill No 2. Measured Works
C3 Retail Hi Street -Pioneer Park -Gurgaon
C3-3000 - Main Works
Bills of Quantities for Electrical Works
1 Please fill up rate both in figures and words in the Rate column by putting the rate figure first.
2 Please total up Sub Head wise and carry forward to Summary of Costs
Rate (RS.)
S.No: Description Unit Qty Amount (Rs.)
Supply Installation
o. 1-250 amp TPN 15 kA MCCB with thermal magnetic protective
releases in MS box nos
0
p. 1-200 amp TPN 15 kA MCCB with thermal magnetic protective
releases in MS box nos
0
q. 1-160 amp TPN 15 kA MCCB with thermal magnetic protective
releases in MS box nos
0
r 1-100 amp TPN 15 kA MCCB with thermal magnetic protective
releases in MS box nos
0
s 1-63 amp TPN 15 kA MCCB with thermal magnetic protective
releases in MS box nos
0
s. 63 amp TPN 10 kA MCB in MS box nos
0
t 32 amp TPN 10 kA MCB in MS box nos
0
2 Design manufacture, supply installation testing and
commissioning of 2000VA rating of Inverter system for a constant
secondary voltage of 240 volts at 50 Hz, single phase, batteries
backup of minimum 1 hour duration including, batteries, battery nos
chargers, rectifiers, transformers, controls, protection and
instruments etc complete as required.
0
3 Sandwich Rising Mains -Aluminium Rising Main
Supply, installation, testing and commissioning of the following
totally enclosed, dust and vermin proof (IP 42 ingress protection)
Low impedance, compact Sandwich type Rising Main system
with Aluminium Bus Bars rated for insulation voltage of 690 volts
and 25 kA rms fault level having provisions for tapping power as
required and including the cost of all required accessories like
clamps, elbows, end covers, flexible connections etc. and
including the cost of providing 2 nos 25 x 6 mm GI earthing strips
for body earthing and including the cost of support arrangement 0
for fixing along walls and including the cost of expansion joints,
and including the cost of Fire barrier of CBRI approved material
of 2 hours rating at all fire rated wall/floor/slab/beam crossing.
complete as per specifications, as required and as below.
0
a) 800 amps m 42
0
Bill No 2. Measured Works
C3 Retail Hi Street -Pioneer Park -Gurgaon
C3-3000 - Main Works
Bills of Quantities for Electrical Works
1 Please fill up rate both in figures and words in the Rate column by putting the rate figure first.
2 Please total up Sub Head wise and carry forward to Summary of Costs
Rate (RS.)
S.No: Description Unit Qty Amount (Rs.)
Supply Installation
4 Copper Rising Main
Supply, installation, testing and commissioning of the following
rating Copper Conductor Bus Trunking system suitable for use in
three phase 415 volts 50 cycle AC supply system with 5
conductors (3P+2N) with provision for tapping off power through
tap off plugs and provided with all accessories like clamps, 0
elbows, end covers, flexible connections etc. complete as per
specifications and as required.
0
a) 630 amps m 42
0
5 Design, manufacture, supplying, fixing in position, testing and
commissioning Adopter cum end feed box of the following
MCCB with thermal magnetic releases and short circuit protection
with ON/OFF indicating lamp and Voltmeter with Selector switch
including interconnections earthing, including adopter box 0
suitable to connect XLPE Aluminium cable etc. to the Rising
Mains as in Item 2a above, complete as required.
0
a. 800 amp TPN MCCB and suitable to accomodate 2 no. 3.5 core
XLPE Cable rating as per Schematic nos 2
b. 630 amp TPN MCCB and suitable to accomodate 2 no. 4 core
XLPE Cable rating as per Schematic nos 2
0
6 Supply, installation, testing and commissioning of following
rating TPN plug in type Tap-off Boxes suitable for use with
800/630 amp rising mains as per item . above, to feed power
supply from the rising mains including 25 kA TPN (3P+N) 0
MCCB and including provision to terminate outgoing cables as
per schematic, bonding to earth etc. complete as per specifications
and as required
1 Please fill up rate both in figures and words in the Rate column by putting the rate figure first.
2 Please total up Sub Head wise and carry forward to Summary of Costs
Rate (RS.)
S.No: Description Unit Qty Amount (Rs.)
Supply Installation
Approval shall be obtained from DHBVNL for the shop drawings
before fabrication. 0
The metering panel shall comprise the following 0
i Trivector Meter of Secure make, accuracy class 0.5 0
ii 3 nos cast resin CT's of 5/1 amps CT ratio, 15VA burden and
accuracy class 0.5 (CT make shall be Concord) 0
ii 1 no. 3 phase potential transformer of Concord make approved by
DHBVNL 0
- Ratio 11000V/sqrt3/110/sqrt3 0
- VA Burden 100VA 0
- Class 0.5 0
The metering panel shall be complete with all interconnections
etc. as above including calibration of instruments as per Nos 1
DHBVNL
0
2 HT PANELS 0
0
2.1 HT PANEL NEAR METERING ROOM 0
0
Supply, installation, testing and commissioning of a Indoor type
One panel totally enclosed sheet steel clad floor mounting, vermin
proof, fully interlocked horizontal isolation, extensible, horizontal
draw out, air insulated, metal clad switchboard having single /
double isolation features complete with circuits as detailed below.
The switchboard would be complete with necessary PVC
insulated copper busbars, small wiring, labels, cable eyes, cable 0
termination to receive XLPE cables, foundation bolts and suitable
for operation on 11 kV 3 phase, 50 cycle, earthed system with a
rupturing capacity of 350 MVA (18.37 kA) at 11 KV
1 Please fill up rate both in figures and words in the Rate column by putting the rate figure first.
2 Please total up Sub Head wise and carry forward to Summary of Costs
Rate (RS.)
S.No: Description Unit Qty Amount (Rs.)
Supply Installation
The switchboard shall be complete with all interconnections, label
wiring, etc as required and as per direction The switchboard shall
be complete with earth bus, all interconnections, labels wiring, etc nos 1
as required
0
3.1 Supply, installation, testing and commissioning of following
rating 11000/433 volt delta/star, indoor mounting Dry type (Cast
Resin) transformer with IP 33 enclosure and fittings, (Vector
Group DYn II) and OFF load tap-links of +/-2-1/2,+/-5%,- 7-
1/2%,-10% -15% on HT side to give constant secondary voltage
of 433 volts. The transformer shall be provided with winding
temperature alarm & trip protection. The transformer to be
provided with cable termination box on HT side to receive 0
armoured 11 kV XLPE cable and on the L.T. side arrangement to
receive Bus Duct connection with all fittings & accessories
complete as required as per specification. (The transformer should
have space to accommodate 1 no. CT for Restricted earth fault.)
0
a) 2000 kVA nos 1
b) 1500 kVA nos 3
0
3.2 Supply, installation, testing and commissioning of following
11000/433 volt delta/star, indoor mounting Dry type transformer
(VPI/Cast Resin) (vector group DYn II) with fittings, complete
and integral with dry type ON load tap changer OLG make having
ON load taps of +5 to -15% in steps of 1.25% volts on HT side to
give constant secondary voltage of 433 volts.The OLTC shall have
class H insulation copper tungsten alloy fixed & roller contacts,
glass silicon cables for connections, cooling fans in enclosure and
shall be complete with RTC Panel. The transformer shall be
provided with winding temperature alarm & trip protection and
shall be available for cable terminations on HT side to receive 0
armoured XLPE cable and on the L.T. side arrangement to receive
aluminium bus ducts as per detailed specification and as required.
The transformer and OLTC shall be guaranteed for operation,
integration and satisfactory performance by the transformer
manufacturer as per site conditions. The cost shall include
providing and fixing of 150 x 50 x 6 mm channels as required at
site as per specification
1 Please fill up rate both in figures and words in the Rate column by putting the rate figure first.
2 Please total up Sub Head wise and carry forward to Summary of Costs
Rate (RS.)
S.No: Description Unit Qty Amount (Rs.)
Supply Installation
4 Supply, laying in existing trench/hume pipe or in ground
including digging laying and back filling with sand brick cashing
and testing and commissioning of following 11000 volt grade
earthed type, armoured aluminium conductor XLPE cable 0
complete as required.
0
a) 3 core 300 sq mm m
b) 3 core 185 sq mm m
0
5 Supplying and making end termination with brass compression
gland and aluminium lugs for following size of PVC insulated and
PVC sheathed / XLPE aluminium conductor cable of 11 kV grade 0
as required.
0
a) 3 core 300 sq mm nos
b) 3 core 185 sq mm nos
0
6 Supply, installation, testing and commissioning of the following
extensible cubicle type indoor/Outdoor mounting Powder coated,
modular compartmentalized IP 42, dead front, dust and vermin
proof, floor mounting 2 mm thick sheet steel clad switchboard 0
suitable for use at 415 volts 3 phase 4 wire 50 cycle system and to
withstand a symmetrical fault level as indicated in the Panel
Annexure.
0
NOTE : The following provisions shall be required to be made in
the switchboard detailed below 0
0
a. The Switchboard shall have provision for entry of all XLPE
cables/bus duct from the top/bottom as required. 0
0
b. All live accessible parts shall be shrouded and all equipment shall
be finger touch proof. The busbar insulation shall be with heat
shrinkable sleeves. SMC/DMC shrouds and busbar supports shall 0
be used..
0
c. Suitable tinned copper extension links for incoming/outgoing
cables shall be provided wherever required 0
0
d. Control circuits includes breaker control switch, auto manual
selector switch, anti pumping relay, spring charging trip
indication, TIMER, control wiring, Auxiliary contactors MCB's as 0
required at site.
0
e. All the incomer breakers shall be interlocked with micro PLC's to
avoid parallel operation. Stabilized separate power supply to be 0
provided for micro PLC with in the panel.
0
f. All incomers having microprocessors breakers shall have neutral
CT 0
Bill No 2. Measured Works
C3 Retail Hi Street -Pioneer Park -Gurgaon
C3-3000 - Main Works
Bills of Quantities for Electrical Works
1 Please fill up rate both in figures and words in the Rate column by putting the rate figure first.
2 Please total up Sub Head wise and carry forward to Summary of Costs
Rate (RS.)
S.No: Description Unit Qty Amount (Rs.)
Supply Installation
0
g. All fault level breaking capacity indicates shall be IC.S value at
415 volts 0
0
h Space Heater/ light/air filter shall be provided for each vertical
compartment 0
0
i Padlocking facility shall be provided on all outgoing feeders. 0
0
j Link and drops from ACB/MCCB shall be designed for full rated
current of ACB/MCCB ratings at same current density as of Main 0
Bus Bar
0
FOR - RETAIL 0
0
A. Main LT PANEL 0
The Configuration of the Panel shall be as per Annexure
enclosed . 0
0
The Switchboard shall be complete with all interconnections,
risers, internal wiring, labels etc. complete as required nos 1
0
B. DG SYNC PANEL WITH PLC SYNCHRONIZATION 0
0
The Configuration of the Panel shall be as per Annexure enclosed
and as per Main Electrical Schematic 0
0
PLC AUTO LOAD MANAGEMENT 0
0
1 NO. CONTROL PANEL having PLC based DG Logic suitable
for Automatic Mains Failure, Auto Changeover/ Interlocking
Auto Synchronizing and Auto Load Searching & Management
Functions of 2 no 1500 kVA DG Sets, 1 no 750 KVA DG Sets 0
with manual over-ride complete as per specifications, as required
and comprising of
0
# Programmable Logic Controller (PLC) of Siemens/Allan Bradley
make 0
0
# Synchronization Relay 0
0
# One Battery charger consisting of 0
a) Transformer/Rectifier 0
b) DC. Ammeter 0
c) DC. Voltmeter 0
d) Charging rate selector switch 0
e) OFF/Trickle/Boost. 0
0
# 3 sets of D.C. Control relays incorporating engine Start/Stop,
three attempt starting facility and failure to start lock out. 0
0
Bill No 2. Measured Works
C3 Retail Hi Street -Pioneer Park -Gurgaon
C3-3000 - Main Works
Bills of Quantities for Electrical Works
1 Please fill up rate both in figures and words in the Rate column by putting the rate figure first.
2 Please total up Sub Head wise and carry forward to Summary of Costs
Rate (RS.)
S.No: Description Unit Qty Amount (Rs.)
Supply Installation
# 3 sets of relays for automatic start of the DG set pumps when the
DG voltage reaches the desired level and for automatic stopping
of the pumps when DG set is shutdown and shutdown the 0
capacitor panel .
0
# 1 set of relays for automatic closing and opening of the mains, and
alternator circuit breakers on the Synchronization Panel for 0
automatic operation as per detailed specifications.
0
# 3 sets of Auto/Manual/ Test selector switches 0
0
# 3 Selector switches for engine control OFF/ON 0
0
# 3 sets of 4 Push buttons - Start, Stop, Reset, Test. 0
0
# 3 sets of 3 Indicating lamps "Load on set" "Load on Mains"
"Set fails to start". 0
0
# 3 sets of 4 Indicating lamps for shutdown for "Low oil pressure"
"High water Temp." " overspeed" "low fuel" 0
0
# 3 counters to indicate number of times set has operated. 0
0
# 3 Hour meters to indicate the number of hours each set has
operated 0
0
# 12 window annunciation 0
0
PLC & INTERLOCKING 0
0
System Configuration 0
2 no. 1500 kVA and 1 no 750 KVA DG Sets shall be in
Synchronization, Auto Load Management 0
0
# PLC shall provide for each DG Set 0
0
a) Engine Start/Stop, three attempt staring facility and failure to start
lock out. 0
0
b) Automatic start of the DG set pumps, cooling towers, DG
Ventilation fans when the DG voltage reaches the desired level
and for automatic stopping of the pumps when DG set shutdown. 0
0
c) Monitoring of DG safeties 0
0
d) Indication for “Load on set” “Load on Mains” “Set fails to start”
“Low oil pressure” “High water temp.” “overspeed” “low fuel”. 0
0
e) Counters to indicate the no. of times set has operated. 0
Bill No 2. Measured Works
C3 Retail Hi Street -Pioneer Park -Gurgaon
C3-3000 - Main Works
Bills of Quantities for Electrical Works
1 Please fill up rate both in figures and words in the Rate column by putting the rate figure first.
2 Please total up Sub Head wise and carry forward to Summary of Costs
Rate (RS.)
S.No: Description Unit Qty Amount (Rs.)
Supply Installation
0
f) Hour meter 0
0
# The PLC shall provide auto mains failure, auto change-over, auto
load management and Synchronization of 2 no. 1500 kVA and 1
no 750 KVA DG Sets and by automatic closing and opening of
the alternator and bus section circuit breakers on the 0
Synchronization PAnel for automatic operation
0
# The PLC shall provide Interlocking as per schematic drawings
0
0
# In the event of Manual override of the PLC following shall be
provided. 0
0
a) Auto/Manual/Test selector switch for each DG Set. 0
0
b) Engine control Start/Stop/Test/Reset for each DG Set. 0
0
c) Indications for “Load on set” “Load on Mains” “Set fails to start”
“Low oil pressure” “High water temp.” “overspeed” “low fuel” 0
0
d) Starting of the DG set pumps, cooling towers, DG ventilation fans
when DG voltage reaches the desired level and for automatic
stopping of the pumps when DG set is shutdown for each DG Set. 0
0
# Power monitor for all; DG sets only and for the following
functions 0
0
PLC Shall Provide for each DG set 0
0
# Automatic start of the DG set pumps, cooling towers, DG
Ventilation fans when the DG voltage reaches the desired level
and for automatic stopping of the pumps when DG set Shut down 0
# Monitoring of DG safeties. 0
# Indication for " Load on Set" "Load on Mains" "Set fails to start"
" Low oil pressure" "High water temp." "overspeed" "low fuel"
"Low Water (coolent) Pressure" " Low/high Battery voltage" " 0
Weak Battery warning"
0
The Switchboard shall be extensible as per drawing enclosed
complete with all interconnections, inter panel wiring from PLC
to DG/TRAFO/BC/ Breaker risers, internal wiring, labels etc nos 1
complete as required
0
C 600 KVAR CAPACITOR PANEL 0
0
Bill No 2. Measured Works
C3 Retail Hi Street -Pioneer Park -Gurgaon
C3-3000 - Main Works
Bills of Quantities for Electrical Works
1 Please fill up rate both in figures and words in the Rate column by putting the rate figure first.
2 Please total up Sub Head wise and carry forward to Summary of Costs
Rate (RS.)
S.No: Description Unit Qty Amount (Rs.)
Supply Installation
The Configuration of the Panel shall be as per Annexure
enclosed . 0
0
The Switchboard shall be complete with all interconnections,
risers, internal wiring, labels etc. complete as required nos 1
0
D 450 KVAR CAPACITOR PANEL 0
0
The Configuration of the Panel shall be as per Annexure
enclosed .
0
The Switchboard shall be complete with all interconnections,
risers, internal wiring, labels etc. complete as required nos 1
0
E Main Panel-Core A 0
0
The Configuration of the Panel shall be as per Annexure
enclosed . 0
0
The Switchboard shall be complete with all interconnections,
risers, internal wiring, labels etc. complete as required nos 1
0
F Main Panel-Core B 0
0
The Configuration of the Panel shall be as per Annexure
enclosed . 0
0
The Switchboard shall be complete with all interconnections,
risers, internal wiring, labels etc. complete as required nos 1
0
G Main Panel-Core C 0
0
The Configuration of the Panel shall be as per Annexure
enclosed . 0
0
The Switchboard shall be complete with all interconnections,
risers, internal wiring, labels etc. complete as required nos 1
0
H Basement Ventilation Panel-I 0
0
The Configuration of the Panel shall be as per Annexure
enclosed . 0
0
The Switchboard shall be complete with all interconnections,
risers, internal wiring, labels etc. complete as required nos 1
0
I Basement Ventilation Panel-II 0
0
The Configuration of the Panel shall be as per Annexure
enclosed . 0
0
Bill No 2. Measured Works
C3 Retail Hi Street -Pioneer Park -Gurgaon
C3-3000 - Main Works
Bills of Quantities for Electrical Works
1 Please fill up rate both in figures and words in the Rate column by putting the rate figure first.
2 Please total up Sub Head wise and carry forward to Summary of Costs
Rate (RS.)
S.No: Description Unit Qty Amount (Rs.)
Supply Installation
The Switchboard shall be complete with all interconnections,
risers, internal wiring, labels etc. complete as required nos 1
0
J Core A-Ground Floor Meterboard 0
0
The Configuration of the Panel shall be as per Annexure
enclosed . 0
0
The Switchboard shall be complete with all interconnections,
risers, internal wiring, labels etc. complete as required nos 1
0
K Core A-First Floor Meterboard 0
0
The Configuration of the Panel shall be as per Annexure
enclosed . 0
0
The Switchboard shall be complete with all interconnections,
risers, internal wiring, labels etc. complete as required nos 1
0
L Core A-Second Floor Meterboard 0
0
The Configuration of the Panel shall be as per Annexure
enclosed . 0
0
The Switchboard shall be complete with all interconnections,
risers, internal wiring, labels etc. complete as required nos 1
0
M Core B-Ground & First Floor Meterboard 0
0
The Configuration of the Panel shall be as per Annexure
enclosed . 0
0
The Switchboard shall be complete with all interconnections,
risers, internal wiring, labels etc. complete as required nos 1
0
N Core B-Second Floor Meterboard 0
0
The Configuration of the Panel shall be as per Annexure
enclosed . 0
0
The Switchboard shall be complete with all interconnections,
risers, internal wiring, labels etc. complete as required nos 1
0
O Core C-Ground Floor Meterboard 0
0
The Configuration of the Panel shall be as per Annexure
enclosed . 0
0
The Switchboard shall be complete with all interconnections,
risers, internal wiring, labels etc. complete as required nos 1
0
Bill No 2. Measured Works
C3 Retail Hi Street -Pioneer Park -Gurgaon
C3-3000 - Main Works
Bills of Quantities for Electrical Works
1 Please fill up rate both in figures and words in the Rate column by putting the rate figure first.
2 Please total up Sub Head wise and carry forward to Summary of Costs
Rate (RS.)
S.No: Description Unit Qty Amount (Rs.)
Supply Installation
P Core C-First Floor Meterboard 0
0
The Configuration of the Panel shall be as per Annexure
enclosed . 0
0
The Switchboard shall be complete with all interconnections,
risers, internal wiring, labels etc. complete as required nos 1
0
Q Core C-Second Floor Meterboard 0
0
The Configuration of the Panel shall be as per Annexure
enclosed . 0
0
The Switchboard shall be complete with all interconnections,
risers, internal wiring, labels etc. complete as required nos 1
0
R LIFT SWBD 0
0
The Configuration of the Panel shall be as per Annexure
enclosed . 0
0
The Switchboard shall be complete with all interconnections,
risers, internal wiring, labels etc. complete as required nos 1
0
S BASEMENT L& P SWBD AT Ist BASEMENT 0
0
The Configuration of the Panel shall be as per Annexure
enclosed . 0
0
The Switchboard shall be complete with all interconnections,
risers, internal wiring, labels etc. complete as required nos 1
0
T Signage Panel 0
0
The Configuration of the Panel shall be as per Annexure
enclosed . 0
0
The Switchboard shall be complete with all interconnections,
risers, internal wiring, labels etc. complete as required nos 1
0
FOR - PEPSICO 0
0
A. Main LT PANEL 0
The Configuration of the Panel shall be as per Annexure
enclosed . 0
0
The Switchboard shall be complete with all interconnections,
risers, internal wiring, labels etc. complete as required nos 1
0
B. DG SYNC PANEL WITH PLC SYNCHRONIZATION 0
0
Bill No 2. Measured Works
C3 Retail Hi Street -Pioneer Park -Gurgaon
C3-3000 - Main Works
Bills of Quantities for Electrical Works
1 Please fill up rate both in figures and words in the Rate column by putting the rate figure first.
2 Please total up Sub Head wise and carry forward to Summary of Costs
Rate (RS.)
S.No: Description Unit Qty Amount (Rs.)
Supply Installation
The Configuration of the Panel shall be as per Annexure enclosed
and as per Main Electrical Schematic 0
0
PLC AUTO LOAD MANAGEMENT 0
0
1 NO. CONTROL PANEL having PLC based DG Logic suitable
for Automatic Mains Failure, Auto Changeover/ Interlocking
Auto Synchronizing and Auto Load Searching & Management
Functions of 3 no 1250 kVA DG Sets with manual over-ride 0
complete as per specifications, as required and comprising of
0
# Programmable Logic Controller (PLC) of Siemens/Allan Bradley
make 0
0
# Synchronization Relay 0
0
# One Battery charger consisting of 0
a) Transformer/Rectifier 0
b) DC. Ammeter 0
c) DC. Voltmeter 0
d) Charging rate selector switch 0
e) OFF/Trickle/Boost. 0
0
# 3 sets of D.C. Control relays incorporating engine Start/Stop,
three attempt starting facility and failure to start lock out. 0
0
# 3 sets of relays for automatic start of the DG set pumps when the
DG voltage reaches the desired level and for automatic stopping
of the pumps when DG set is shutdown and shutdown the 0
capacitor panel .
0
# 1 set of relays for automatic closing and opening of the mains, and
alternator circuit breakers on the Synchronization Panel for 0
automatic operation as per detailed specifications.
0
# 3 sets of Auto/Manual/ Test selector switches 0
0
# 3 Selector switches for engine control OFF/ON 0
0
# 3 sets of 4 Push buttons - Start, Stop, Reset, Test. 0
0
# 3 sets of 3 Indicating lamps "Load on set" "Load on Mains"
"Set fails to start". 0
0
# 3 sets of 4 Indicating lamps for shutdown for "Low oil pressure"
"High water Temp." " overspeed" "low fuel" 0
0
# 3 counters to indicate number of times set has operated. 0
0
Bill No 2. Measured Works
C3 Retail Hi Street -Pioneer Park -Gurgaon
C3-3000 - Main Works
Bills of Quantities for Electrical Works
1 Please fill up rate both in figures and words in the Rate column by putting the rate figure first.
2 Please total up Sub Head wise and carry forward to Summary of Costs
Rate (RS.)
S.No: Description Unit Qty Amount (Rs.)
Supply Installation
# 3 Hour meters to indicate the number of hours each set has
operated 0
0
# 12 window annunciation 0
0
PLC & INTERLOCKING 0
0
System Configuration 0
3 no. 1250 kVA DGSets shall be in Synchronization, Auto Load
Management 0
0
# PLC shall provide for each DG Set 0
0
a) Engine Start/Stop, three attempt staring facility and failure to start
lock out. 0
0
b) Automatic start of the DG set pumps, cooling towers, DG
Ventilation fans when the DG voltage reaches the desired level
and for automatic stopping of the pumps when DG set shutdown. 0
0
c) Monitoring of DG safeties 0
0
d) Indication for “Load on set” “Load on Mains” “Set fails to start”
“Low oil pressure” “High water temp.” “overspeed” “low fuel”. 0
0
e) Counters to indicate the no. of times set has operated. 0
0
f) Hour meter 0
0
# The PLC shall provide auto mains failure, auto change-over, auto
load management and Synchronization of 3 no. 1250 kVA DG
Sets and by automatic closing and opening of the alternator and 0
bus section circuit breakers on the Synchronization PAnel for
automatic operation
0
# The PLC shall provide Interlocking as per schematic drawings
0
0
# In the event of Manual override of the PLC following shall be
provided. 0
0
a) Auto/Manual/Test selector switch for each DG Set. 0
0
b) Engine control Start/Stop/Test/Reset for each DG Set. 0
0
c) Indications for “Load on set” “Load on Mains” “Set fails to start”
“Low oil pressure” “High water temp.” “overspeed” “low fuel” 0
0
Bill No 2. Measured Works
C3 Retail Hi Street -Pioneer Park -Gurgaon
C3-3000 - Main Works
Bills of Quantities for Electrical Works
1 Please fill up rate both in figures and words in the Rate column by putting the rate figure first.
2 Please total up Sub Head wise and carry forward to Summary of Costs
Rate (RS.)
S.No: Description Unit Qty Amount (Rs.)
Supply Installation
d) Starting of the DG set pumps, cooling towers, DG ventilation fans
when DG voltage reaches the desired level and for automatic
stopping of the pumps when DG set is shutdown for each DG Set. 0
0
# Power monitor for all; DG sets only and for the following
functions 0
0
PLC Shall Provide for each DG set 0
0
# Automatic start of the DG set pumps, cooling towers, DG
Ventilation fans when the DG voltage reaches the desired level
and for automatic stopping of the pumps when DG set Shut down 0
# Monitoring of DG safeties. 0
# Indication for " Load on Set" "Load on Mains" "Set fails to start"
" Low oil pressure" "High water temp." "overspeed" "low fuel"
"Low Water (coolent) Pressure" " Low/high Battery voltage" " 0
Weak Battery warning"
0
The Switchboard shall be extensible as per drawing enclosed
complete with all interconnections, inter panel wiring from PLC
to DG/TRAFO/BC/ Breaker risers, internal wiring, labels etc nos 1
complete as required
0
C 450 KVAR CAPACITOR PANEL 0
0
The Configuration of the Panel shall be as per Annexure
enclosed . 0
0
The Switchboard shall be complete with all interconnections,
risers, internal wiring, labels etc. complete as required nos 2
0
D Basement Ventilation Panel-I 0
0
The Configuration of the Panel shall be as per Annexure
enclosed . 0
0
The Switchboard shall be complete with all interconnections,
risers, internal wiring, labels etc. complete as required nos 1
0
E Basement Ventilation Panel-II 0
0
The Configuration of the Panel shall be as per Annexure
enclosed . 0
0
The Switchboard shall be complete with all interconnections,
risers, internal wiring, labels etc. complete as required nos 1
0
F LIFT PANEL 0
0
Bill No 2. Measured Works
C3 Retail Hi Street -Pioneer Park -Gurgaon
C3-3000 - Main Works
Bills of Quantities for Electrical Works
1 Please fill up rate both in figures and words in the Rate column by putting the rate figure first.
2 Please total up Sub Head wise and carry forward to Summary of Costs
Rate (RS.)
S.No: Description Unit Qty Amount (Rs.)
Supply Installation
The Configuration of the Panel shall be as per Annexure
enclosed . 0
0
The Switchboard shall be complete with all interconnections,
risers, internal wiring, labels etc. complete as required nos 1
0
G Basement L&P SWBD AT 3rd basement 0
0
The Configuration of the Panel shall be as per Annexure
enclosed . 0
0
The Switchboard shall be complete with all interconnections,
risers, internal wiring, labels etc. complete as required nos 1
0
0
7 Supply, installation, testing and commissioning of triple pole and
neutral, totally enclosed, dust and vermin proof with IP 54 ingress
protection, indoor mounting, Compact Sandwich type low
Inductance Bus Duct with Aluminium bus bars rated as under to
withstand the stresses of a 40 kA symmetrical fault level at 415
volts including the cost of bends, expansion joints with 2 nos 60 0
x 6 mm Al strip for earthing, complete as per specification as
required and as below
0
a) 3200 amp TPN Aluminium Bus Duct m 35
b) 2500 amp TPN Aluminium Bus Duct m 150
c) 2000 amp TPN Aluminium Bus Duct m 187
d) 1250 amp TPN Aluminium Bus Duct m 42
0
8 Supply, installation, testing and commissioning of following triple
pole and neutral flexible End connections including rubber below
at DG and Transformer terminal suitable for busducts as in item 6 0
above complete as required.
0
a) 3200 amp TPN Aluminium Bus Duct nos 1
b) 2500 amp TPN Aluminium Bus Duct nos 5
c) 2000 amp TPN Aluminium Bus Duct nos 3
d) 1250 amp TPN Aluminium Bus Duct nos 1
0
9 Supply laying and termination control cabling with copper
conductor PVC insulated and PVC sheathed armoured cables on
existing tray including the cost of making connections, glands, 0
copper lugs, ferrules/cable tags complete as required as below:
0
a) 2 core 2.5 sq mm m 25
b) 4 core 2.5 sq mm m 25
c) 6 core 2.5 sq mm m 25
d) 12 core 2.5 sq. mm m 25
e) 24 core 2.5 sq mm m 25
Bill No 2. Measured Works
C3 Retail Hi Street -Pioneer Park -Gurgaon
C3-3000 - Main Works
Bills of Quantities for Electrical Works
1 Please fill up rate both in figures and words in the Rate column by putting the rate figure first.
2 Please total up Sub Head wise and carry forward to Summary of Costs
Rate (RS.)
S.No: Description Unit Qty Amount (Rs.)
Supply Installation
0
10 Supplying, fixing, 9 liters dry CO2 Fire extinguishers with trolley
mounting brackets first filling etc. nos 2
0
11 Supplying and fixing 1000 mm wide 15 mm thick rubber matting
(complying with I.S.S.) and suitable to withstand 11 kV as m 50
required.
0
12 Supplying and fixing standard shock treatment charts in English
& Hindi plastic coated mounted on wooden frame with glass. nos 2
0
13 Supplying and fixing of danger plate of size 250 x 200 mm as per
approved sample written in English & Hindi for MV and HV nos 10
made of 2 mm thick sheet
0
14 Supplying First Aid Box Complete as approved by St. John
ambulance or Indian Red Cross. nos 2
0
15 Supplying and fixing fire buckets each painted red with fire
written out complete with sand filling, floor/wall mounting nos 5
brackets complete.
0
16 Supplying 11 kV grade rubber gloves as required set 2
0
17 Supply and fixing of dry chemical fire extinguisher 5 kg as per IS
2171 : 1976 mounted on wall hook nos 2
0
18 Supply, installation, testing and commissioning of 180 AH 24 volt
sealed maintenance free valve regulated lead acid (SMF/ VRLA)
battery banks alongwith fully automatic electronic thyristor
controlled constant voltage constant current Fast cum Boost
Battery Charger with DC distribution board including all standard
protections, fittings, indications, voltmeter, ammeter, accessories,
interconnections etc. complete as per specifications and as nos 1
required. The panel shall have two source of AC supply with AC
DP MCB of suitable rating duly interlocking and 6 nos DC MCB
of suitable rating as outgoing.
0
TOTAL SUB HEAD V carried over to Summary 0
0
SUB HEAD VI : EARTHING 0
0
1 Providing and making earthpits including the cost of 600 mm x
600 mm x 3.15 mm tinned copper plate electrode, 25 mm dia GI
perforated pipe, CI funnel with wiremesh charcoal, salt, all earth nos
work, masonry enclosure with RCC frame & cover plate complete
as per IS 3043:1987 as required.
0
Bill No 2. Measured Works
C3 Retail Hi Street -Pioneer Park -Gurgaon
C3-3000 - Main Works
Bills of Quantities for Electrical Works
1 Please fill up rate both in figures and words in the Rate column by putting the rate figure first.
2 Please total up Sub Head wise and carry forward to Summary of Costs
Rate (RS.)
S.No: Description Unit Qty Amount (Rs.)
Supply Installation
2 Providing and making earthpits including the cost of 600 mm x
600 mm x 6.3 mm GI plate electrode, 25 mm dia GI perforated
pipe, CI funnel with wiremesh charcoal, salt, all earth work, nos
masonry enclosure with RCC frame & cover plate complete as per
IS 3043:1987 as required.
0
3 Supplying and laying of the following earthing clamped to wall
with suitable clamps saddles and fixing bolts/soldering /riveting in
ground including the cost of digging and back filling as required 0
and complete as required to comply with IS 3043:1987. All joints
shall be timed.
0
a) 32 x 6 mm cu strip with heat shrinkable m
b) 32 x 6 mm tinned cu strip m
c) 50 mm x 6 mm Cu strip with heat shrinkable sleeve m
d) 50 x 6 mm tinned cu strip m
e) 65 mm x 10 mm GI strip m
f) 60 mm x 6 mm GI strip m
g) 50 mm x 10 mm GI strip m
h) 25 mm x 6 mm GI strip m
i) 8 SWG GI Wire m
j) 25 mm x 6 mm copper strip m
0
4 Providing and laying of GI pipe in ground from earth electrode as
required in ground 0
0
a) 65 mm dia m
b) 80 mm dia m
0
5 Providing and fixing of DMC/SMC insulator for supporting
neutral earth strips wherever as required. nos
0
6 Providing and fixing of copper wire 4 mm dia for earthing as
required. m
0
8 Supply and making of test joint as required. 0
0
a) 50 x 6 mm tinned copper nos
b) 65 x 10 mm GI strip nos
0
0
TOTAL SUB HEAD VI carried over to Summary 0
0
SUB HEAD VII : LIGHTNING PROTECTION 0
0
1 Air Terminal & Accessories 0
Bill No 2. Measured Works
C3 Retail Hi Street -Pioneer Park -Gurgaon
C3-3000 - Main Works
Bills of Quantities for Electrical Works
1 Please fill up rate both in figures and words in the Rate column by putting the rate figure first.
2 Please total up Sub Head wise and carry forward to Summary of Costs
Rate (RS.)
S.No: Description Unit Qty Amount (Rs.)
Supply Installation
Supplying, Erection & commissioning of External Lightning
Wide Area Protection System based on pro-active Early Streamer
Emission (ESE) Technology. Device shall emit electromagnetic
impulse in the form of a controlled emission of streamers into the
air microseconds earlier than naturally formed streamers. Device
confirming to NFC17-102 & UNE 21186 standards. Appropriate nos 1
mounting arrangement. The device shall be mounted at least 2
meter clear to the highest point on the rooftop with inline
coupling, guying system complete as required to cover the radius
of 60 m
0
5 Supplying fixing, testing and commissioning of LED type
Aviation lights, complete as per Philips, complete with flasher as nos 2
required.
0
6 Supplying, fixing, testing and commissioning of photochromatic
switch for automatic ON/OFF of Aviation light as required in nos 1
housing of outdoor type.
Bill No 2. Measured Works
C3 Retail Hi Street -Pioneer Park -Gurgaon
C3-3000 - Main Works
Bills of Quantities for Electrical Works
1 Please fill up rate both in figures and words in the Rate column by putting the rate figure first.
2 Please total up Sub Head wise and carry forward to Summary of Costs
Rate (RS.)
S.No: Description Unit Qty Amount (Rs.)
Supply Installation
0
TOTAL SUB HEAD VII carried over to Summary 0
0
SUB HEAD VIII : FIXTURES AND FITTINGS 0
0
1 Receiving, assembling, erection, connecting, testing and
commissioning of the following light fixtures complete with
housing, reflectors, all accessories i.e. copper wound ballast, HPF 0
condensors, starters, holders etc. complete as required
0
a) Bulk Head Fixtures nos 177
B) Fluorescent fixture 1x28/2x28 nos 2095
c) Compact Fluorescent fixture nos 1598
d) Flood light fixture / High Bay Luminaire 1 x 250 W nos 0
0
2 Supply, installation, testing and commissioning of 300 mm sweep
heavy duty Exhaust fans with louvers including all accessories
suitable for single phase 240 volts 50 Hz AC supply complete as nos
required.
0
3 Supply, installation, testing and commissioning of 450 mm sweep
heavy duty exhaust fans with louvers including all accessories
suitable for single phase 240 V 50 HZ AC supply complete as nos
required.
0
4 Supply, installation, testing and commissioning of modular type
electronic fan regulator in the existing box as required nos 1
0
5 Supply, installation, testing and commissioning of ceiling fan
1200 mm size as required. nos 3
0
6 Supply, installation, testing and commissioning of Wall mounting
Self contained battery backed up Emergency Lights with 1 x 20
watts flourescent lamp complete with batteries and charger
suitable for 30 minutes operation and circuitry for automatic
switch ‘ON’ on mains failure and standby ‘OFF’. The unit shall be nos
suitable for operation on single phase 240 volts 50 Hz AC supply
complete as required.
0
TOTAL SUB-HEAD VIII carried over to Summary 0
0
SUB HEAD IX : AUTOMATIC FIRE DETECTION
SYSTEM & PA SYSTEM 0
0
1 Supply, installation, testing and commissioning of plug-in type
intelligent addressable photo-electric smoke detectors including
the cost of supplying base plate, mounting accessories etc nos 653
complete as per specifications and as required.
0
Bill No 2. Measured Works
C3 Retail Hi Street -Pioneer Park -Gurgaon
C3-3000 - Main Works
Bills of Quantities for Electrical Works
1 Please fill up rate both in figures and words in the Rate column by putting the rate figure first.
2 Please total up Sub Head wise and carry forward to Summary of Costs
Rate (RS.)
S.No: Description Unit Qty Amount (Rs.)
Supply Installation
2 Supply, installation, testing and commissioning of plug-in type
fixed temperature or rate of rise cum fixed temperature intelligent
addressable Heat detectors including the cost of supplying base nos
plate, mounting accessories etc. complete as per specifications and
as required.
0
3 Supply, installation, testing and commissioning of plug-in type
intelligent addressable photo-thermal multi criteria detectors
including the cost of supplying base plate, mounting accessories nos
etc complete as per specifications and as required. (Electrical
Room)
0
4 Supply installation, testing and commissioning of Network panel
'10" Loop (200 Detectors, 100 Devices) (Fire Alarm Capability: 1
Loop x 100/125/150 detectors & 100/128/150 devices) wall recess
mounting microprocessor based networkable analogue
addressable Fire Control Panel expandable by minimum 1
additional loops with minimum 80 character LCD display, 4
access levels, 1000 events historical logging, flash E-PROM, 240
volts ac power supply, automatic battery charger, 24V sealed lead-
acid battery suitable operating the system for 30 minutes in
emergency condition. The Panel shall be Integrated with the PA 0
System and with suitable power amplifiers for hooter/strobes. The
Panel shall be suitable Integration with the BMS System and shall
include cost of supply of any additional modules, software and
interfaces as required for the same and as required by the Client.
The Panel shall provide either or all BACNET/RS485/LON
protocols as required.
1 Please fill up rate both in figures and words in the Rate column by putting the rate figure first.
2 Please total up Sub Head wise and carry forward to Summary of Costs
Rate (RS.)
S.No: Description Unit Qty Amount (Rs.)
Supply Installation
0
6 Supply, installation, testing and commissioning of dust and
vermin proof addressable analogue Manual Pull/call stations
including cost of all required modules, mounting accessories etc nos 80
with in-built isolator module in either detector or in base complete
as per specifications and as required.
0
7 Supply, installation, testing and commissioning of addressable
Zone Adaptor Module/Monitor Module for connecting
conventional devices, complete as per specifications and as nos 14
required.
0
8 Supply, installation, testing and commissioning of Intelligent
addressable Control Modules including the cost of supplying all
mounting accessories etc complete as per specifications and as nos 21
required.
0
9 Supply, installation, testing and commissioning of Intelligent
addressable Fault Isolator Modules including the cost of
supplying all mounting accessories complete as per specifications nos
and complete as required.
0
10 Supply, installation, testing and commissioning of wall or ceiling
mounted 240 Volt AC illuminated double sided pictorial exit signs
provided with appropriate direction arrow painted in green on
white with an 11W CFL Lamp including the cost of in-built
rechargeable batteries with charger suitable for 90 minute nos 56
operation and including the cost of accessories for surface/
recessed or ceiling suspended mounting complete as required.
0
11 Supply, installation, testing and commissioning of Network
Repeater panels complete as per specifications of item no 4 and as nos
required
0
12 Supply, installation, testing and commissioning of intelligent
addressable electronic high intensity hooters cum strobes/flashess
suitable for recess/surface mounting complete with all mounting nos 74
accessories etc and as required.
0
13 Supply, installation, testing and commissioning of metal casing
wall/ceiling mounted type. 6W, 8 OHM speaker with line nos 187
matching transformers as required
0
Bill No 2. Measured Works
C3 Retail Hi Street -Pioneer Park -Gurgaon
C3-3000 - Main Works
Bills of Quantities for Electrical Works
1 Please fill up rate both in figures and words in the Rate column by putting the rate figure first.
2 Please total up Sub Head wise and carry forward to Summary of Costs
Rate (RS.)
S.No: Description Unit Qty Amount (Rs.)
Supply Installation
14 Supply, laying, testing and commissioning of 2 core 1.5 sqmm
copper conductor FRLS PVC insulated 1100 volt wires in IS
embossed black enameled 25mm dia 16 SWG MS recessed and/or
surface conduiting system including cost of providing saddles etc
for surface conduiting and/or cost of cutting and filling chases for nos
recessed conduiting as required and including the cost of crimped
termination’s complete as required.
0
15 Supply, laying, testing and commissioning of 2 core 1.5 sqmm
copper conductor FRLS PVC insulated 1100 volt wires in existing
conduits including the cost of crimped termination’s complete as nos
required.
0
16 Supply, laying, testing and commissioning of 4 core 1.5 sqmm
copper conductor FRLS PVC insulated 1100 volt wires in IS
embossed black enameled 25mm dia 16 SWG MS recessed and/or
surface conduiting system including cost of providing saddles etc
for surface conduiting and/or cost of cutting and filling chases for nos
recessed conduiting as required and including the cost of crimped
termination’s complete as required.
0
17 Supply and fixing PVC sheathed galvanized steel GI flexible
conduit (for terrace) including all fittings complete as required as 0
below.
a) 25 mm dia m
0
Bill No 2. Measured Works
C3 Retail Hi Street -Pioneer Park -Gurgaon
C3-3000 - Main Works
Bills of Quantities for Electrical Works
1 Please fill up rate both in figures and words in the Rate column by putting the rate figure first.
2 Please total up Sub Head wise and carry forward to Summary of Costs
Rate (RS.)
S.No: Description Unit Qty Amount (Rs.)
Supply Installation
18 Supplying, laying, fixing, testing of FRLS armoured cable
660/1100 volt grade copper conductor on surface / cable tray as 0
required.
a) 2 core x 1.5 sq mm m
b) 4 core x 2.5 sq mm m
Note:
1 Please fill up rate both in figures and words in the Rate column by putting the rate figure first.
2 Please total up Sub Head wise and carry forward to Summary of Costs
Rate (RS.)
S.No: Description Unit Qty Amount (Rs.)
Supply Installation
SUB HEAD I : DIESEL GENERATOR SETS
Note:
1 Please fill up rate both in figures and words in the Rate column by putting the rate figure first.
2 Please total up Sub Head wise and carry forward to Summary of Costs
Rate (RS.)
S.No: Description Unit Qty Amount (Rs.)
Supply Installation
The Acoustic Enclosure, fabricated from high quality sheet steel
of minimum 2 mm thickness finished with powder coating shall
be of weather proof construction, designed to reduce noise level to
maximum 75 dB at 1 m distance. The enclosure shall be provided sets 6
with a forced ventilation system to restrict the temperature rise
within the enclosure to permissible limits.
6 Supply and fixing of flame proof level switch 1.0 m length (low &
high) for overflow tanks with all accessories as required for nos 6
automatic start / stop of gear pump.
Note:
1 Please fill up rate both in figures and words in the Rate column by putting the rate figure first.
2 Please total up Sub Head wise and carry forward to Summary of Costs
Rate (RS.)
S.No: Description Unit Qty Amount (Rs.)
Supply Installation
3.1 Piping
a) 125 mm dia m 1500
b) 100 mm dia m
Note:
1 Please fill up rate both in figures and words in the Rate column by putting the rate figure first.
2 Please total up Sub Head wise and carry forward to Summary of Costs
Rate (RS.)
S.No: Description Unit Qty Amount (Rs.)
Supply Installation
3.6 125 mm dia Y /POT strainers nos 14
3.7 100 mm dia Y /POT strainers nos 2
3.8 Pressure gauges nos 52
3.9 Temperature gauges (Industrial type) nos 20
3.10 Ball valves / gate valves 50 mm nos 10
3.11 Ball valve/gate valve (brass) 25 mm nos 0
3.12 Ball valve / gate valve 12 mm / 15 mm nos 0
INCOMING
2 nos 250 amps 35 kA TPN MCCB with rotary handle and neutral
link
BUSBAR
Electrolytic high conductivity aluminium three phase and neutral
busbars rated at 300 amps having a maximum current density of 1
amp per sq mm suitable to with stand symmetrical fault level of
31 MVA at 415 volts. The neutral busbar is to be of 50% capacity.
Bill No 2. Measured Works
C3 Retail Hi Street -Pioneer Park -Gurgaon
C3-3000 - Main Works
Bills of Quantities for DG,Associated Electrical & Mechanical Works
Note:
1 Please fill up rate both in figures and words in the Rate column by putting the rate figure first.
2 Please total up Sub Head wise and carry forward to Summary of Costs
Rate (RS.)
S.No: Description Unit Qty Amount (Rs.)
Supply Installation
OUTGOINGS
Note:
1 Please fill up rate both in figures and words in the Rate column by putting the rate figure first.
2 Please total up Sub Head wise and carry forward to Summary of Costs
Rate (RS.)
S.No: Description Unit Qty Amount (Rs.)
Supply Installation
B DG AUX PANEL (PEPSICO) no 1
DETAILS ARE NOT GIVEN IN SLD
Note:
1 Please fill up rate both in figures and words in the Rate column by putting the rate figure first.
2 Please total up Sub Head wise and carry forward to Summary of Costs
Rate (RS.)
S.No: Description Unit Qty Amount (Rs.)
Supply Installation
Note:
1 Please fill up rate both in figures and words in the Rate column by putting the rate figure first.
2 Please total up Sub Head wise and carry forward to Summary of Costs
Rate (RS.)
S.No: Description Unit Qty Amount (Rs.)
Supply Installation
0
2 Associated Civil works for 20/15 KL Underground Bulk Oil
(HSD) Storage Tank including excavation, PCC, RCC, Brick
works, Plaster, backfilling with soil and covering the area with LS
fine river sand etc. & miscellaneous works as per drawing
approved and as directed by Project-in-Charge.
Note:
1 Please fill up rate both in figures and words in the Rate column by putting the rate figure first.
2 Please total up Sub Head wise and carry forward to Summary of Costs
Rate (RS.)
S.No: Description Unit Qty Amount (Rs.)
Supply Installation
3 Supply, laying testing and commissioning of Oil piping with class
C MS pipes laid in existing masonry trenches/ hume pipes
including the cost of bends, flanges, gaskets supports, clamps etc.
and including the cost of surface preparation of pipes, application
of primer paint coat and polymeric 4 mm thick tape (Pypekote 4
mm) and including the cost of hydraulic testing before wrapping
of rust preventing tape complete as per specification, as required
and as below.
a) 80 mm NB (Fill pipe) m 60
b) 50 mm NB (Suction piping) m 50
c) 40 mm NB m 100
d) 25 mm NB m 160
4 Extra for item no. 3(b) & 3(c) above laying of 1 no pipe class C in
ground including excavation, sand cushioning, brick protective
covering and refilling the trench etc. as required as detailed below.
a) 50 mm m 0
b) 40 mm m 200
c) 25 mm m 200
Note:
1 Please fill up rate both in figures and words in the Rate column by putting the rate figure first.
2 Please total up Sub Head wise and carry forward to Summary of Costs
Rate (RS.)
S.No: Description Unit Qty Amount (Rs.)
Supply Installation
7 Supply and erection of canopy type MS structure made out of 40
mm medium class MS pip (class B), 25 x 25 x 3 mm angle iron
from work and 14 SWG GI sheet structure shall be grouted in
1:2:4 CC foundation for handing 4 nos 9 lit each fire fighting set 4
buckets including providing buckets with two coats of
anticorrosive paints etc. complete as required.
Note:
1 Please fill up rate both in figures and words in the Rate column by putting the rate figure first.
2 Please total up Sub Head wise and carry forward to Summary of Costs
Rate (RS.)
S.No: Description Unit Qty Amount (Rs.)
Supply Installation
a) 3.5 core x 50 sq mm m 90
b) 3 core x 10 sq mm m 1500
c) 3 core x 6 sq mm m 480
Note:
1 Please fill up rate both in figures and words in the Rate column by putting the rate figure first.
2 Please total up Sub Head wise and carry forward to Summary of Costs
Rate (RS.)
S.No: Description Unit Qty Amount (Rs.)
Supply Installation
6 Supply, fabrication, installation and commissioning of perforated
cable tray complete with bends reducers, tees, hangers suspended
from the ceiling with 40 x 40 x 5 mm MS angle and 10 mm dia
MS rod duly painted as required at site.
a) 150 x 50 x 1.6 mm m 140
b) 300 x 50 x 2 mm m 150
c) 450 x 50 x 2 mm m 10
a) 25 mm x 6 mm GI strip m 30
b) 8 SWG GI Wire m 2070