Steel Interchange: Modern Steel's Monthly Steel Interchange Is For You!
Steel Interchange: Modern Steel's Monthly Steel Interchange Is For You!
Steel Interchange: Modern Steel's Monthly Steel Interchange Is For You!
” about something
related to structural steel design or construction,
Modern Steel’s monthly Steel Interchange is for you!
steel
Send your questions or comments to solutions@aisc.org. interchange
Holes in Baseplates You state that you have determined the nominal strength of
The 9th Edition of the AISC Manual of Steel Construction the plate. The AISC Specification defines nominal strength as:
contained hole sizes for baseplates that are smaller than “Strength of a structure or component (without the resistance
those shown in the 14th Edition Manual. Can the hole factor or safety factor applied) to resist load effects, as
sizes in the 9th Edition still be used? If so can they be determined in accordance with this Specification.” The nominal
used with standard washers instead of the plate washers strength will be the same regardless of whether the design is
shown in the 14th Edition Manual? done using LRFD or ASD. The plate will also have the same
nominal strength, when subjected to the same loading and
The answer to both questions is yes. There is nothing that restraints, regardless of whether it is in a building, a hopper, an
prohibits the use of holes smaller than the maximums airplane or a ship.
recommended in Table 14-2 of the 14th Edition Steel Construction Once the nominal strength has been determined, the
Manual. It should be noted, however, that using the smaller holes engineer need only multiply by a resistance factor, φ, or divide
will require more exacting placement of the anchors and that by a safety factor, Ω, to get the available strength in LRFD or
misplaced anchors are a relatively common issue—the reason ASD, respectively. However, the φ and Ω factors in the AISC
larger holes were adopted since the 1989 publication you cite. Specification have been developed for use with buildings in
The larger washer plates are necessary due to the larger hole conjunction with the loads and load factors defined in ASCE-
sizes. ASTM F844 washers are sufficient when used with the 7. It may not be appropriate to apply these factors, intended
hole sizes provided in the 9th Edition Manual. The information for buildings, to the design of a hopper. It seems the demand
provided in the Manual has been reproduced here. side is much more of a problem than the resistance side,
though the two are not mutually exclusive. Your ability to
9th Ed. Manual Recommended Hole Sizes define the demand will have an effect on the load factors used.
Anchor Rod Diamer (in.) Hole Diameter (in.) The Commentary to Chapter B of the AISC Specification
w 1z provides some background related to the development of
LRFD as it relates to structural steel building construction.
d 1x
It also provides references to other related papers and texts.
1 12
By reading these documents you should be able to develop a
14 1w better understanding of how ASD and LRFD are related and
12 2 how best to “convert” from one to the other. For the design of
1w 24 buildings considered in the Specification, a simple conversion of
2 22 1.5 is usually deemed sufficient to move from ASD to LRFD.
22 32 This would not necessarily apply to other applications.
The Eurocode devotes significant space to the development
Larry S. Muir, P.E. of resistance factors and/or load factors and considers such
variables as location, type of infill and loading (eccentric
Design of Structures Outside the Scope of discharge, local patch loading and unsymmetrical filling),
the Specification the structural type and the size and type of operation. It
I am trying to design the face of a hopper, which is in also provides very specific requirements related to analysis
compression. I have found many examples that appear to assumptions and procedures. These are the sorts of factors that
be based on ASD and can calculate the nominal strength need to be taken into account. The AISC Specification does not
of the plate from these. How do I determine the com- consider these factors because hoppers fall outside its scope. You
pressive strength of the plate using LRFD? must use your own engineering knowledge and judgment to
determine the appropriate design methods for your application.
The design of hoppers falls outside the scope of the AISC I suspect various sectors have developed their own guidelines
Specification, which “sets forth criteria for the design, based on their own experiences, conditions and needs.
fabrication and erection of structural steel buildings and other It is not unusual for engineers to base the design of steel
structures, where other structures are defined as structures structures other than buildings on the provisions in the
designed, fabricated and erected in a manner similar to Specification. However, care, based on understanding of the
buildings, with building-like vertical and lateral load resisting- Specification provisions, must be exercised when this done.
elements.” I will, however, try to provide some guidance. Larry S. Muir, P.E.
Erection Aids Larry Muir is director of technical assistance and Charlie Carter is vice president and chief
structural engineer, both with AISC. Keith Landwehr is a consultant to AISC.
Who is responsible (erector, fabricator, owner or engineer)
for the design and supply of erection aids on a project?
Steel Interchange is a forum to exchange useful and practical professional ideas and
information on all phases of steel building and bridge construction. Opinions and
Per the Code of Standard Practice Section 1.8.1, the erector is suggestions are welcome on any subject covered in this magazine.
responsible for means methods and safety of erection of the steel The opinions expressed in Steel Interchange do not necessarily represent an official position of
frame. Erection aids fall under means and methods. Neither the the American Institute of Steel Construction and have not been reviewed. It is recognized that the
design of structures is within the scope and expertise of a competent licensed structural engineer,
owner nor the engineer of record is responsible for showing, architect or other licensed professional for the application of principles to a particular structure.
designing or providing erection aids in the contract documents. If you have a question or problem that your fellow readers might help you solve, please
Responsibility for designing and providing erection aids is forward it to us. At the same time, feel free to respond to any of the questions that you
have read here. Contact Steel Interchange via AISC’s Steel Solutions Center:
not addressed specifically in the AISC Code of Standard Practice,
1 E Wacker Dr., Ste. 700, Chicago, IL 60601
and therefore is a contractual issue between the erector and tel: 866.ASK.AISC • fax: 312.803.4709
solutions@aisc.org
NOVEMBER 2014