This course deals with the study of electrical system design, installation and cost estimation for single
and multi-family dwelling units guided by the provisions of the Philippine Electrical Code (PEC) and
other relevant laws and stndards.
M o n d a y, F e b r u a r y 1 5 , 2 0 1 0
PROBLEM:
A single family dwelling is to be circuited with the following requirements as shown on the figure
above. Determine the:
SOLUTION
1. From the Figure above, determine the number of lighting outlets. By direct counting, there are 8 light
outlets.
3. Determine the size of conductor wire for circuit - 1 . Refer to Table 9.1 or 11.1. use 2 pieces 2.0
mm2 or No. 14 TW copper wire having an ampacity of 15 amperes that is much largr than the 3.48
amperes computed maximum load.
4. Determine the size of the Conduit Pipe. Refer to Table . The smallest diameter of a conduit pipe that
could accommodate up to 3 pieces of No.14 TW conductor wire is 13 mm diameter. therefore, specify
13 mm diameter conduit pipe.
5. determine the size or rating of the fuse protective device. Refer to Table . Use 15 amperes fuse
In Table , the maximum ampacity load of a or 2.0 mm2 No.14 AWG copper wire is 15 amperes. 80 % of
15 is 12, the maximum allowable load of the circuit sufficient enough to carry the 3.48 amperes
computed load for a maximum 100 watts per light outlet. therefore the use of 2.0 mm2 or No.14 TW is
safe.
SOLUTION
"For each single receptacle shall be considered at no less than 180 watts rating."
It simply mean that, each convenience outlet, is considered to have a maximum load of not less than
180 watts per plug or gang. thus:
1. From Figure above, there are 6 convenience receptacles for small appliance load. considering that
there are two plug outlet, the total number of plug will be:
5. Determine the Size of the conduit pipe. for the 2 - No. 12 TW wire, refer to Table . Use 13 mm
conduit pipe.
6. Determine the Over Current fuse protection. Refer to Table . under the column of fuse and breaker
rating, the 20 amperes fuse can safely carry a maximum load of 16 amperes the 80 % of 20 amperes
fuse can safely carry a maximum load of 16 amperes the 80% of 20 amperes load permitted by the
National Electrical Code on No. 12 circuit wire.
COMMENT:
1. On convenience outlet receptacle, the National Electrical Code provides that, " Each single
receptacle shall be considered at no less than 180 watts rating."
2. Examining the values given on Table , the 2.0 mm2 or No. 14 AWG TW copper wire has an allowable
ampacity rating of 15 amperes. Granting that only 80 % of this 15 amperes is considered the derated
value, still 12 amperes is very much larger than the 9.36 amperes computed as maximum load for 6-
convenience outlet. Why specify a bigger 3.5 mm2or No. 12 AWG conductor wire?
3. Although the 2.0 mm2or No. 14 AWG wire conductor could safely carry the 9.36 amperes computed
load, considering its 15 amperes ampacity rating,yet, we cannot do so because the Code specifically
mandated the use of 3.5 mm2or No. 12 AWG copper wire as the minimum size for all types of
convenience outlet wiring except, for an appliance with limited load wherein a 2.0 mm2or No.14 AWG
wire is permitted.
SOLUTION
3. Determine the size of the service conductor wire. Refer to Table 9.1 or 11.1.
4. For the 15.65 amperes load, use 2 pieces 3.5mm2or No.12 AWG TW copper wire
5. Determine the Size of the Conduit Pipe (if reqd) to Table. Two pieces No. 12 AWG wire can be
accommodated comfortably in a 13 mm diameter conduit pipe. Specify 13 mm diameter conduit pipe.
6. Determine the size or rating of the Over-current Protection. Refer to Table . For the 15.65 amperes
load use 20 amperes fuse rating.
COMMENTS:
The fuse rating is 20 amperes. Granting that it will be derated at 80 % x 20, the 16 amperes derated
value is still higher than the computed load of 15.65 amperes. Therefore, the 20 amperes fuse over
current protection is accepted.
The size of service entrance being the supply conductor and equipment for delivering energy from the
electricity supply to the wiring system of the building, is also computed based on the total load
supplied by the branch circuit. Continuing the solution, we have the following:
3. Find the Size of the Service Wire. Refer 22.8 amperes to Table . Use 2- 8.0 mm2or No.8 TW copper
wire
4. Determine the size of conduit pipe for the service wire. Refer Table , for No.8 TW copper wire, use
20 mm diameter conduit pipe.
COMMENT:
1. A demand factor of 80% was applied considering that not all receptacles and outlets are being used
simultaneously.
2. These type of loads are classified as non-continuous load. From Table 9.1, the 5.5 mm2or
No.10 AWG copper wire conductor has 30 amperes ampacity which is bigger than 22.8 amperes as
computed. However, we do not specify the use of No.10 AWG wire because the code limits the use of
8.0 mm2or No.8 AWG, conductor as minimum size for Service Entrance.
2. Use 2 pieces 30 amperes fuse parallel connection 60 amperes 2 pole single throw (PST) 250 volts
safety switch
3. Provide 2-double branch circuit cut out with two 15 and 2-20 amperes fuse respectively.
The protection of branch circuit is tapped to the hot line of live wire. The grounded line being in
neutral zero voltage is not protected with fuse. this is one advantage of the MULTI-GROUND SYSTEM
being adopted by the electric cooperative implemented by the RURAL ELECTRIFICATION PROGRAM
of the government. The branch circuit and cutout should be doubled because the engaged voltage in
the line is only 230 V while the other is zero being grounded ( see figure)
Other electric service system on the other hand, are classified as LINE TO LINE SERVICE wherein the
engaged voltage is 115/230 volts which requires FUSE PROTECTIO FOR BOTH LINES.
NOTE:
The quantity of materials is subject to change depending upon the area and the choice of the
designing engineers. For open onstallation, conduit pipe can be changed to split knobs or PDX wires.
SOLUTION:
Examining the lighting plan of the above figure, there are 19 lighting outlets. Split the 19 outlets into
two circuits A and B.
1. The PEC provides that 100 watts be the maximum load per light outlet. thus, for 10 light outlets at
100 watts, multiply:
3. Find the size of Branch circuit wire. Refer to Table 9.1 or 11.1. For 4.35 amperes, use 2.0 mm2 TW
copper wire.
4. Find the rating of overcurrent protection. Refer to Table. for 4.35 A, use 15 amperes trip breaker.
5. Determine the size of conduit pipe. Refer to Table , for No. 14 TW copper wire, use 13 mm conduit
pipe.
2. Determine the Size of the Branch circuit Wire. Refer to Table 9.1 or 11.1. For 3.91 A load, use 2.0
mm2or No.14 TW copper wire.
3. Determine the size of the conduit pipe. Refer to Table. For 2 pieces No. 14 TW copper wire, use the
13 mm minimum size of conduit pipe.
4. Determine the size or rating of the overcurrent Protection. Refer to Table. For 3.91 A load, use 15 A
load fuse of trip breaker.
C. Circuit - 3 For small appliance load
Section 3.3.1.2 of the the PEC specif 180 watts load limit per convenience outlet. Thus,
1. Find the number of appliance load outlet and the current load.
6 outlets x 2 gang per outlet x 180 watts
12 x 180 = 2,160 watts
Divide: 2160 watts/230 volts = 9.39 A
2. Determine the Size of the Service Wire conductor. Refer to Table 9.1 or 11.1. For the 9.39 A load,
specify the minimum wire gauge for convenience outlet.
3. Determine the Size of the conduit pipe. Refer to Table. For 2 pieces No.12 TW copper wire. Use 13
mm diameter conduit pipe.
4. Solve for the Size or Rating of the Over current Protection. Refer to Table. For 9.39 A on No. 12 TW
copper wire specify:
20 A fuse or trip breaker.
1. The load of circuit 4 is identical with circuit . Use the same size of wire, conduit, and wire protection
rating.
4. Determine the Size of the Branch Circuit wire. Refer to Table 9.1 or 11.1. For the 27.82 A, use 8.0
mm2 or No. 8 TW copper wire.
5. Determine the Size of Conduit pipe. Refer to Table. For 2 pieces No.8 wire use 200 mm diameter
pipe.
6. Find the Size or Rating of the Fuse or Trip Breaker. Refer to Table. For appliance load, use 40 A fuse
or trip breaker.
3. Solve for the Size of the Branch circuit wire. Refer to Table 9.1 or 11.1 . For 10.86 A convenience
outlet use 2 pcs 3.5 mm2 or No. 12 TW copper wire.
4. Determine the Size of the conduit pipe. Refer to Table. For 2 - No.12 Tw copper wire, use 13 mm
conduit pipe.
5. Find the Size or Rating of the Over Current Protection. For the 10.86 A load, use 20 A fuse fuse or
trip breaker.
Article 6.7 of the Philippine Electrical Code provides that: "BRANCH CIRCUIT CONDUCTOR SUPPLYING
A MOTOR SHALL HAVE AN AMPACITY NOT LESS THAN 125% OF THE FULL LOAD CURRENT."
3. Find the Size of the Branch circuit service wire. Refer to Table. The 6.7 A can be served by a 2.0
No.14 TW copper wire, but the Code limits the size of convenience outlet to No. 12 AWG copper wire.
Specify No.12 THW copper wire for circuit 7 and 8.
4. Find the Size of the conduit pipe. Refer to Table. For two No.12 wire, use 13 mm conduit pipe.
5. Find the Size and Rating of the Branch Circuit Protection. The Code on branch circuit protection for
a single motor provides that" It shall be increased by 250% of the full load current of the motor." thus,
4.86 x 250% = 12.15 A. From Table for a continuous load use 2-30 AT breaker.
2. From Table , OPTIONAL CALCULATION for dwelling Unit, apply demand factor.
for the first 10000 w at 100%(df)...........10000 watts
3. The Neutral Conductor of a 3 - wire line to line supply system shall have an ampacity of not less
than 70% of the ungrounded(live wire) conductor or TWO TRADE SIZE SMALLER SIZE THAN THE
UNGROUNDED CONDUCTOR. (PEC specs) Therefore use 1- 22 mm2 Tw copper wire for the Neutral
line.
4. Determine the Size of the Conduit pipe. Refer to Table , use 32 mm diameter pipe.
5. For main Breaker, refer to Table . Use 2 - 100 A 2 - wires 250 V, 2 pole molded air circuity breaker.
COMMENT:
The total computed load is 63.37 A. The 30 mm2 copper wire could be used considering its 90 A
capacity. However, The NEC provides that:
" If the computed load exceeds 10000 watts, the conductor and overcurrent protection shall be rated
not less than 100 A.
THEREFORE USE 2 - 38 mm2 TW WIRE FOR THE MAIN FEEDER AND 2 - 100 A FOR THE MAIN
BREAKER.
LIGHTING:
CONVENIENCE OUTLET:
SOLUTION:
1. Determine the wattage required per square meter area. From, the wattage required per square meter
for dwelling units is 24 watts. Multiply:
5. Determine th Size of the Branch Circuit wire. From , the 1.74 A is very small load to be carried by 2.0
mm2 or No. 14 TW copper wire. Therefore, the No. 14 wire is safe.
6. Determine the Size of the conduit pipe. Refer to table, for 2- No.14 wire, use 13 mm conduit pipe.
7. Determine the size or rating of the branch circuit protection. Refer to table. For 2.0 mm2 or No.14
copper wire conductor, use 15 A fuse or trip breaker.
LOAD CURRENT = ( 1000 + 1100 + 500 + 175 + 300 + 100) / 230 volts
= 3175 watts/230 volts
= 13.81 A
2. Determine the size of the Branch circuit wire conductor. Refer to Table. For a convenience load of
13.81 A specify 3.5 mm2 or No. 12 TW copper wire, the minimum size required for convenience outlet.
3. Find the size of the conduit pipe. Refer to Table, for 2 pieces No.12 TW copper wire, use 13 mm
diameter pipe.
4. Find the Size or rating of the Protection device. See Table, for 13.81 A, use 1 - 20 A fuse.
COMMENT:
It is interesting to note that only one 20 A fuse protection was used because the current is a LINE TO
GROUND OR MULTI-GROUND SYSTEM where one line is zero voltage being grounded. Unlike the LINE
TO LINE SYSTEM of current supply, it is necessary to provide 2 fuses to protect the two line branch
circuit.
3. Find the size of Service Entrance. Refer to Table. For 22.15 A, use No. 8 TW copper wire, the
minimum size for service entrance.
4. For Main Protection, use 1-safety switch, 2 pole, 2 wires, 250 volts.
Under the preceding set-up, one safety switch could supply both lighting and convenience outlet at
different branch circuit without the use of fuse cutout. This is only applicable to the line to ground or
multi-ground system being used by the electric cooperative.