Lighting Panel Schedule: S - V - I P - V - I - Cos Phi
Lighting Panel Schedule: S - V - I P - V - I - Cos Phi
Lighting Panel Schedule: S - V - I P - V - I - Cos Phi
Panel Number
Area WORKSHOP AND WAREHOUSE
Nominal Voltage 230 Volt (Phase to Neutral)
400 Volt (Phase to Phase)
Power Factor (Cos phi) 0.85
A 1 Phase
1 R 3.14 0.00 0.00 3 14
2 S 0.00 3.10 0.00 6 1
3 T 0.00 0.00 3.10 6 1
4 R 2.96 0.00 0.00
5 S 0.00 2.61 0.00
6 T 0.00 0.00 2.61
7 R OFFICE 3.26 0.00 0.00
8 S MEETING ROOM 0.00 6.52 0.00
9 T LABRORATORY, CHEMICAL AND STORAGE 0.00 0.00 9.78
10 R 0.00 0.00 0.00
11 S 0.00 0.00 0.00
12 T 0.00 0.00 0.00
13 R 0.00 0.00 0.00
14 S 0.00 0.00 0.00
15 T 0.00 0.00 0.00
16 R 0.00 0.00 0.00
17 S 0.00 0.00 0.00
18 T 0.00 0.00 0.00
19 R 0.00 0.00 0.00
20 S 0.00 0.00 0.00
21 T 0.00 0.00 0.00
22 R 0.00 0.00 0.00
23 S 0.00 0.00 0.00
24 T 0.00 0.00 0.00
25 R 0.00 0.00 0.00
26 S 0.00 0.00 0.00
27 T 0.00 0.00 0.00
AMPERE 9.36 12.24 15.50
3 12 14 2 0 0 0 0 0
kVA 83.78
Catatan
Nominal Voltage (3 phase) 400 Volt S = √3 • V • I MCB : (2/63, 4/63, 6/63, 10/63, 16/63, 20/63, 25/63, 32/63,
Arus Incoming 120.93 Ampere P = √3 • V • I • Cos phi 40/63, 50/63, 63/63, 80/125, 100/125, 125/125)AT/AF
Kapasitas Lighting Panel berdasar perhitungan 83.78 kVA 120.93 A ELCB : 6, 10, 16, 20, 25, 32, 40, 50, 63 A
Kapasitas Lighting Panel minimal 104.73 kVA MCCB : (16/100, 25/100, 32/100, 40/100, 50/100, 63/100, 80/100,
Kapasitas Lighting Panel yang dipilih 15.00 kVA 21.65 A 100/100, 125/160, 160/160, 200/200, 250/250)AT/AF
Safety Factor (SF) 1.25
Arus Incoming x SF 151.16 Ampere Untuk MCB dan ELCB, rating breaker yang tertulis di panel Schedule
MCCB incoming 32/63 AT/AF (sesuaikan rating di pasaran) cukup menggunakan rating Ampere Tripnya saja
2 Jika menggunakan Lighting Transformer, maka rating Lighting Panel dan Incoming Breakernya 5 Proteksi arus bocor (ELCB)
harus menyesuaikan kapasitas tranformer yang dipasang tersebut 30 mA : Perlindungan terhadap manusia (kontak
langsung) misal digunakan untuk instalasi
3 Keterangan Lampu & Receptacle listrik pada kamar mandi
Lamp_1 Silahkan ditulis sendiri 300 mA & 500 mA : Perlindungan terhadap bahaya kebakaran
Lamp_2 FL 2 x 36 Watt 43596 dan kontak tidak langsung
Lamp_3 Silahkan ditulis sendiri
kVA
RCP Recept_1 RCP
AC (W) (W)
750 680 150
1
4
4
1
2
3
6 1 8
Panel Number
Area WORKSHOP AND WAREHOUSE
Nominal Voltage 230 Volt (Phase to Neutral)
400 Volt (Phase to Phase)
Power Factor (Cos phi) 0.85
A 1 Phase
1 R CCR 3.72 0.00 0.00 10 1
2 S CCR 0.00 6.63 0.00 18
3 T CCR 0.00 0.00 3.72 10 1
4 R MV SWG ROOM 1 3.68 0.00 0.00 10
5 S MV SWG ROOM 2 0.00 3.68 0.00 10
6 T MV SWG ROOM 3 0.00 0.00 5.56 15 1
7 RCP 3PH Trafo Room 3.40 3.40 3.40 1
8 RCP 3PH Compressor Room 3.43 3.43 3.40 1
9 RCP 3PH MVSWG Room 3.40 3.40 3.40 1
10 R Transformer Room 1.95 0.00 0.00 6 2
11 S Toilet 1 dan 2 0.00 1.93 0.00 4 5
12 T Tangga 1 dan 2 0.00 0.00 2.23 7 1
13 R Praying Room 0.00 0.00 0.00 3
14 S Pantry Office Stairway 0.00 0.00 0.00 4
15 T Compressor Room 0.00 0.00 3.79 12 1
16 R Office Room 1.88 0.00 0.00 6
17 S Conference Room 0.00 1.88 0.00 6
18 T RISE FLOOR 0.00 0.00 3.76 12
20 R Receptacle 1 Ph CCR 8.70 0.00 0.00
21 S Receptacle 1 Ph MV SWGR 0.00 8.70 0.00
22 T Receptacle 1 Ph Compressor, Traforoom,Conference Ro0.00 0.00 8.70
23 R 0.00 0.00 0.00
24 S 0.00 0.00 0.00
25 T 0.00 0.00 0.00
26 0.00 0.00 0.00
27 0.00 0.00 0.00
AMPERE 30.16 33.05 37.95
4 134 7 3 0 0 0 0 0 0
kVA 23.27
TARGET KONSUMSI 10-20 KVA
Catatan 68.4284775
Nominal Voltage (3 phase) 400 Volt MCB : (2/63, 4/63, 6/63, 10/63, 16/63, 20/63, 25/63, 32/63,
Arus Incoming 33.58 Ampere 40/63, 50/63, 63/63, 80/125, 100/125, 125/125)AT/AF
Kapasitas Lighting Panel berdasar perhitungan 23.27 kVA A ELCB : 6, 10, 16, 20, 25, 32, 40, 50, 63 A
Kapasitas Lighting Panel minimal 29.08 kVA MCCB : (16/100, 25/100, 32/100, 40/100, 50/100, 63/100, 80/100,
Kapasitas Lighting Panel yang dipilih 15.00 kVA A 100/100, 125/160, 160/160, 200/200, 250/250)AT/AF
Safety Factor (SF) 1.25
Arus Incoming x SF 41.98 Ampere Untuk MCB dan ELCB, rating breaker yang tertulis di panel Schedule
MCCB incoming 250/63 AT/AF cukup menggunakan rating Ampere Tripnya saja
2 Jika menggunakan Lighting Transformer, maka rating Lighting Panel dan Incoming Breakernya 23000 5 Proteksi arus bocor (ELCB)
harus menyesuaikan kapasitas tranformer yang dipasang tersebut 30 mA : Perlindungan terhadap manusia (kontak
langsung) misal digunakan untuk instalasi
3 Keterangan Lampu & Receptacle listrik pada kamar mandi
Lamp_1 Silahkan ditulis sendiri 300 mA & 500 mA : Perlindungan terhadap bahaya kebakaran
Lamp_2 FL 2 x 36 Watt dan kontak tidak langsung
Lamp_3 Silahkan ditulis sendiri
RCP
(W)
2000
1
1
1
3
LIGHTING PANEL SCHEDULE
A 1 Phase
1 R electrical room 2.82 0.00 0.00 13 1
2 S electrical room 0.00 2.57 0.00 12
3 T control room 0.00 0.00 3.43 14 6 2
4 R 5.65 0.00 0.00 26 2
5 S 0.00 6.72 0.00 31 2
6 T 0.00 0.00 3.27
7 R 4.09 0.00 0.00
8 S 0.00 3.27 0.00
9 T 0.00 0.00 3.27
10 R 0.00 0.00 0.00
11 S 0.00 0.00 0.00
12 T 0.00 0.00 3.85 6
13 R 0.00 0.00 0.00
14 S 0.00 0.00 0.00
15 T 0.00 0.00 0.00
16 R 0.00 0.00 0.00
17 S 0.00 0.00 0.00
18 T 0.00 0.00 0.00
19 R 0.00 0.00 0.00
20 S 0.00 0.00 0.00
21 T 0.00 0.00 0.00
22 R 0.00 0.00 0.00
23 S 0.00 0.00 0.00
24 T 0.00 0.00 0.00
25 R 0.00 0.00 0.00
26 S 0.00 0.00 0.00
27 T 0.00 0.00 0.00
AMPERE 12.56 12.56 13.83
96 6 7 6 0 0 0 0
kVA 8.57
Catatan
Nominal Voltage (3 phase) 380 Volt S = √3 • V • I MCB : (2/63, 4/63, 6/63, 10/63, 16/63, 20/63, 25/63, 32/63,
Arus Incoming 13.02 Ampere P = √3 • V • I • Cos phi 40/63, 50/63, 63/63, 80/125, 100/125, 125/125)AT/AF
Kapasitas Lighting Panel berdasar perhitungan 8.57 kVA 13.02 A ELCB : 6, 10, 16, 20, 25, 32, 40, 50, 63 A
Kapasitas Lighting Panel minimal 10.71 kVA MCCB : (16/100, 25/100, 32/100, 40/100, 50/100, 63/100, 80/10
Kapasitas Lighting Panel yang dipilih 15.00 kVA 22.79 A 100/100, 125/160, 160/160, 200/200, 250/250)AT/AF
Safety Factor (SF) 1.25
Arus Incoming x SF 16.27 Ampere Untuk MCB dan ELCB, rating breaker yang tertulis di panel Schedule
MCCB incoming 32/63 AT/AF (sesuaikan rating di pasaran) cukup menggunakan rating Ampere Tripnya saja
2 Jika menggunakan Lighting Transformer, maka rating Lighting Panel dan Incoming Breakernya 5 Proteksi arus bocor (ELCB)
harus menyesuaikan kapasitas tranformer yang dipasang tersebut 30 mA : Perlindungan terhadap manusia (kontak
langsung) misal digunakan untuk instala
3 Keterangan Lampu & Receptacle listrik pada kamar mandi
Lamp_1 Silahkan ditulis sendiri 300 mA & 500 mA : Perlindungan terhadap bahaya kebakara
Lamp_2 FL 2 x 36 Watt dan kontak tidak langsung
Lamp_3 Silahkan ditulis sendiri
kVA
HB WO-01 Recept_1 LP-01
( Watt ) ( VA ) ( VA ) ( VA )
250 6000 180 2000
4
5
4
4
0 0 17 0
A 1 Phase
1 R 2.57 0.00 0.00 12
2 S 0.00 3.00 0.00 13 3 1
3 T 0.00 0.00 2.40 11 1
4 R 1.75 0.00 0.00 8 1
5 S 0.00 2.32 0.00 10 3
6 T 0.00 0.00 2.82 13 1
7 R 1.75 0.00 0.00 8 1
8 S 0.00 1.71 0.00 8
9 T 0.00 0.00 2.87 13 2
10 R 3.27 0.00 0.00
11 S 0.00 3.27 0.00
12 T 0.00 0.00 1.64
13 R 1.64 0.00 0.00
14 S 0.00 1.64 0.00
15 T 0.00 0.00 1.64
16 R 0.64 0.00 0.00 3
17 S 0.00 0.64 0.00 3
18 T 0.00 0.00 0.00
19 R 0.00 0.00 0.00
20 S 0.00 0.00 0.00
21 T 0.00 0.00 0.00
22 R 0.00 0.00 0.00
23 S 0.00 0.00 0.00
24 T 0.00 0.00 0.00
25 R 0.00 0.00 0.00
26 S 0.00 0.00 0.00
27 T 0.00 0.00 0.00
AMPERE 11.63 12.58 11.36
102 6 7 0 0 0 0 0
kVA 7.82
Catatan
Nominal Voltage (3 phase) 380 Volt S = √3 • V • I MCB : (2/63, 4/63, 6/63, 10/63, 16/63, 20/63, 25/63, 32/63,
Arus Incoming 11.89 Ampere P = √3 • V • I • Cos phi 40/63, 50/63, 63/63, 80/125, 100/125, 125/125)AT/AF
Kapasitas Lighting Panel berdasar perhitungan 7.82 kVA 11.89 A ELCB : 6, 10, 16, 20, 25, 32, 40, 50, 63 A
Kapasitas Lighting Panel minimal 9.78 kVA MCCB : (16/100, 25/100, 32/100, 40/100, 50/100, 63/100, 80/10
Kapasitas Lighting Panel yang dipilih 15.00 kVA 22.79 A 100/100, 125/160, 160/160, 200/200, 250/250)AT/AF
Safety Factor (SF) 1.25
Arus Incoming x SF 14.86 Ampere Untuk MCB dan ELCB, rating breaker yang tertulis di panel Schedule
MCCB incoming 32/63 AT/AF (sesuaikan rating di pasaran) cukup menggunakan rating Ampere Tripnya saja
2 Jika menggunakan Lighting Transformer, maka rating Lighting Panel dan Incoming Breakernya 5 Proteksi arus bocor (ELCB)
harus menyesuaikan kapasitas tranformer yang dipasang tersebut 30 mA : Perlindungan terhadap manusia (kontak
langsung) misal digunakan untuk instala
3 Keterangan Lampu & Receptacle listrik pada kamar mandi
Lamp_1 Silahkan ditulis sendiri 300 mA & 500 mA : Perlindungan terhadap bahaya kebakara
Lamp_2 FL 2 x 36 Watt dan kontak tidak langsung
Lamp_3 Silahkan ditulis sendiri
kVA
HB WO-01 Recept_1 LP-01
( Watt ) ( VA ) ( VA ) ( VA )
250 6000 180 2000
4
4
2
2
2
2
0 0 16 0