T 60 Diff Simulator
T 60 Diff Simulator
T 60 Diff Simulator
customers,
with a tool for excersizing different transformer setups, and test scenarios. The simulation can be used to verify the biased differential settings, the differentia
and restraint metering on the relay, and the correct operation of the element, under test conditions.
Some rules to follow, when working with the simulation program:
1) Enter all settings and test currents only into the allocated cells!
2) Enter "0" MVA for all windings you don't use in your transformer setup menu.
3) Enter "0" angle for Winding 1, and enter the angles of the other transformer windings With Respect To (WRT) Winding 1 in negative degrees. See the exa
4) Enter the settings of the Differential/Restraint characteristic without exceeding the ranges set on the relay.
5) The magnitudes and angles of the test currents should be entered on the spreadsheet as applied on relay terminals.
For example, that if we have a 100MVA transformer, 230kV/69kV Y/D30 degrees, with CT(w1) 500:5, and CT(w2) 1000:5, and we want to
simulate balanced conditions(differential current = 0), the entered transformer setup, and the test currents for Winding 1 and Winding 2 will look as per the
Note the angles of the entered test currents for Winding 2 are shifted by 180 degrees. This shift com
inversed polarity connections of the winding CTs connected to the relay terminals. From the example,
phA(W2) = -30 -180 = -210 degrees, phB(W2) = - 150-180 = -330, and for ph C(W2) = - 270-180
o provide customers,
d differential settings, the differential