Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

T 60 Diff Simulator

Download as xlsx, pdf, or txt
Download as xlsx, pdf, or txt
You are on page 1of 4

This Excel spreadsheet presents the simulation of the UR T60/T35 transformer biased differential protection, and is built to provide

customers,
with a tool for excersizing different transformer setups, and test scenarios. The simulation can be used to verify the biased differential settings, the differentia
and restraint metering on the relay, and the correct operation of the element, under test conditions.
Some rules to follow, when working with the simulation program:
1) Enter all settings and test currents only into the allocated cells!
2) Enter "0" MVA for all windings you don't use in your transformer setup menu.
3) Enter "0" angle for Winding 1, and enter the angles of the other transformer windings With Respect To (WRT) Winding 1 in negative degrees. See the exa
4) Enter the settings of the Differential/Restraint characteristic without exceeding the ranges set on the relay.
5) The magnitudes and angles of the test currents should be entered on the spreadsheet as applied on relay terminals.
For example, that if we have a 100MVA transformer, 230kV/69kV Y/D30 degrees, with CT(w1) 500:5, and CT(w2) 1000:5, and we want to
simulate balanced conditions(differential current = 0), the entered transformer setup, and the test currents for Winding 1 and Winding 2 will look as per the

Note the angles of the entered test currents for Winding 2 are shifted by 180 degrees. This shift com
inversed polarity connections of the winding CTs connected to the relay terminals. From the example,

phA(W2) = -30 -180 = -210 degrees, phB(W2) = - 150-180 = -330, and for ph C(W2) = - 270-180
o provide customers,
d differential settings, the differential

1 in negative degrees. See the example below.

0:5, and we want to


1 and Winding 2 will look as per the picture below:

ed by 180 degrees. This shift comes from the


relay terminals. From the example, the angles of W2 phases will be:

30, and for ph C(W2) = - 270-180 = -90 degrees


TRANSFORMER SETTINGS AND CTs
Nomber of Windings: 2 DIFF / RSTR CHARACTERISTIC
W1 W2 W3 W4 W5 W6 DIFFERENTIAL- RESTRAINT GRAPH
Rated(MVA) 5.25 1.75 0 0 0 0 Diff. min. PKP 0.25 Slope1 28.0
Nom. (kV) 12.47 1.45 0 0 0 0 Kneepoint 1 2.00
Connection DELTA DELTA DELTA DELTA WYE WYE Kneepoint 2 8.00 Slope2 80.0
Grounding NO NO NO NO YES YES
Angle WRT 0 0 -20 -340 0 0 Pre-calculated graph points >>Pre-calculated ratio of the point from the
CT primary 300 1200 1200 1200 3000 1000 Id/Ir, (%) Ph A Ph B Ph C characteristic, corresponding to the same
CT sec. tap 5 5 5 5 5 5 28.0 28.0 28.0 restraint as per the actual Id/Ir ratio. The trip
Inom. Prim. 243.1 696.8 #DIV/0! #DIV/0! #DIV/0! #DIV/0! occurs, when the actual Id/Ir ratio,(%) is bigger
Inom.Sec. 4.051 2.903 #DIV/0! #DIV/0! #DIV/0! #DIV/0! than the pre-calculated Id/Ir ratio, (%)
Rotations ABC Select Magnitude Ref. Winding: 1 ACTUAL VALUES
TEST CURRENTS I diff, pu
Magnitude Ref. Winding #: 1
Operating Characteristic
IA IB IC 12
W1 11 DIFFERENTIAL CURRENTS
Magnitude 3.00 3.00 3.00 Iad Ibd Icd
10
Angle 0.0 -120.0 -240.0 Magnitude 0.60 0.60 0.60
9
W2 Angle 0.0 -120.0 -240.0
Magnitude 0.00 0.00 0.00 8

Angle -180.0 -300.0 -60.0 7 RESTRAINT CURRENTS


W3 6 Iar Ibr Icr
Magnitude 0.00 0.00 0.00 Magnitude 0.60 0.60 0.60
5
Angle -20.0 -20.0 -20.0
4
W4 Actual Differential/Restraint Ratio
Magnitude 0.00 0.00 0.00 3 Actual ph A % ph B % ph C %
Angle -180.0 -300.0 -60.0 2 Id/Ir ratio 100.0 100.0 100.0
W5 1
Magnitude 0.00 0.00 0.00 0 DIFF. OPERATION
Angle -180.0 -300.0 -60.0 0 1 2 3 4 5 6 7 8 9 10 11 12 TRIP
Slope characteristics Iad Ibd Icd I restr, pu
W6 Ia Ib Ic
Magnitude 0.00 0.00 0.00 Trip Trip Trip
Angle 0.0 0.0 0.0

magn. Ref. Winding 0


WYE NO ABC 1 auto
DELTA YES ACB 2 1
ZIG-ZAG 3 2
4 3
5 4
6 5
6

You might also like