7UT612 Procedure
7UT612 Procedure
7UT612 Procedure
RELAY DETAILS
S. NO.
O.K
CHECK NAME PLATE DATA ACCORDING TO THE DRAWING
O.K
CHECK FOR TRANSPORTATION DAMAGE AND CORRECT POSITION
O.K
VERIFY TIGHTNEES OF EXTERNAL WIRING
2-ELECTRICAL CHECKS:
O.K
ALL CONNECTIONS CHECK ACCORDING TO WIRING DIAGRAM
O.K
AUX.SUPPLY CHECKED FOR RATING AND POLARITY
O.K
CASING EARTHING CHECK
All 7 programmable LEDs apply Test LEDs under Test mode (Hardware test). OK
Remarks
Test Inst. Used FREJA300
3- TRANSFORMER DATA:
RATIO: 132/13.8KV
MVA: 67 MVA
H.V SIDE VOLTAGE: 132KV
L.V SIDE VOLTAGE: 13.8KV
GROUP NO: DYN1
FREQUNCEY: 60 HZ
H.V SIDE C.T RATIO: 500/1
H.V SIDE C.T RATIO: 3000/1
IMPEDENCE VOLTAGE: 14%
H.V CALCULATED FULL LOAD CURRENT: 293.0 A = 0.586 A (sec value)
LV CALCULATED FULL LOAD CURRENT: 2803.0 A = 0.934 (sec value)
*** Full load current= Trans MVA/Root of 3* KV
Remarks
Test Inst. Used FREJA300
RESULT
OUTPUT TEST METHOD Contact
RELAY
(Energize only one at a time by soft ware) Checked REMARKS
No.
Remarks
Test Inst. Used FREJA300
CALCULATED
PH A PH B PH C
I D> KVG
TRIP P.U D.O
TRIP P.U D.O TRIP P.U D.O TRIP P.U D.O
0.1
CT INPUT 0.25 1.0 0.147 0.125 0.103 0.147 0.126 0.104 0.146 0.123 0.102 0.147 0.102
25
1 0.25
(HV Side) 0.5 1.0 0.293 0.249 0.205 0.293 0.250 0.207 0.292 0.248 0.205 0.293
0
0.207
0.49
1.0 1.0 0.586 0.498 0.410 0.586 0.502 0.413 0.586 0.497 0.410 0.586
8
0.411
0.34
0.25 1.73 0.41 0.35 0.287 0.403 0.342 0.285 0.403 0.344 0.286 0.401 0.285
CT INPUT 5
2 0.68
0.5 1.73 0.810 0.688 0.567 0.810 0.689 0.567 0.806 0.684 0.567 0.807
5
0.570
(LV Side)
1.37
1.0 1.73 1.620 1.377 1.134 1.621 1.374 1.138 1.619 1.381 0.139 1.613
7
1.134
Select any Phase in HVS and inject current until pickup led then go up until trip contact operate then go
down again tell the pickup led disappear for delta winding program the O/P contact for each phase you
test every time
TRIP = IDIFF>* Kvg*In Trans /In CT
TRIP h.v = IDIFF>*1.0* 293/(500/1)= 0.586*IDFF> A
TRIP l.v = IDIFF>*1.73* 2803/(3000/1)= 1.62*IDFF> A
P.U =85% TRIP VALUE
D.O =70% TRIP VALUE
MEASURED TIME @ 2 Is
SETTING TIME A B C
(S) H.V L.V H.V L.V H.V L.V
0.0 37.8ms 37.9ms 39.9ms 37.2ms 38.3ms 34.3ms
I DIFF>> Kvg CAL. Trip Trip value (A) TRIP TIME @ 2 Is (ms)
SETTING (A)
Ph A Ph B Ph C Ph A Ph B Ph C
CT INPUT 1
(HV WINDING) 1.5 In 1.0 0.879 0.879 0.876 0.878 27 27.4 28.4
CT INPUT 2
(LV WINDING) 1.5 In 1.73 2.43 2.418 2.418 2.425 27 27.4 27.6
Change the setting for I DIFF> to be 2 In then make pick up for I DIFF>> or make another contact for
I DIFF>> only
Remarks
Test Inst. Used FREJA300
I: slope 1
Operating angle
Slope1 M I1 (source1) I2 (source2) Measured slope
(Either one source)
0.5 0.293 0.81 27.9 0.24
0.25 1 0.586 1.62 27 0.24
1.5 0.879 2.43 27.7 0.23
Slope calculation: Slope = [A2 + B2] 1/2 A = [M - M x cos ]
2xM B = M x sin
I1= Kvg *M* I nsec W1 = 0.586 M where M constant , Kvg = (1.0) Ph-N
I2= Kvg *M* I nsec W2 = 1.62 M where M constant , Kvg = (1.73) Ph-N
The calculated slope 1 should be with in +-10% of setting
Inject same phase (L1) to High side & low side by stable current in table with phase shift 180 and
increase the angle of HS till Trip then calculate the slop by this angle
Remarks
Test Inst. Used FREJA300
II: slope 2 :
Operating angle
Slope2 M I1 (source1) I2 (source2) Measured slope
(Either one source)
1 0.586 1.62 59 0.49
0.50 1.5 0.879 2.43 58 0.48
2 1.172 3.24 51.1 0.34
Slope calculation: Slope = [A2 + B2] 1/2 A = [M - M x cos ]
2xM B = M x sin
Inject same phase(L1) to High side & low side by stable current in table with phase shift 180 and
increase the angle of HS till Trip then calculate the slop by this angle
Remarks
Test Inst. Used FREJA300
I 2nd HARMONICS :
INJECTED HV LV
SETTING
CURRENT REMARKS
% TRIP BLOCK TRIP BLOCK
(A)
15 1 <16% >16% <16% >16% -
II 5TH HARMONICS :
INJECTED HV LV
SETTING
CURRENT REMARKS
% TRIP BLOCK TRIP BLOCK
(A)
30 0.4 <30% >30% <30% >30% -
Remarks
Test Inst. Used FREJA300
Procedure:
1. Inject two different phase at same time at one side
2. Phase A>Id with fundamental harmonics
3. Phase B>Id with 2nd harmonics
4. 1 Cycle=60HZ=1/60 =0.01666 sec
Remarks
Test Inst. Used FREJA300
Notes:
1. For this table, 0 is considered even.
2. Use this row if the I0Process setting for the tested winding is I0 Elimination. The settings
are Address 1106 for Winding 1, Address 1126 for Winding 2, and Address 1146 for Winding 3.
3. Use this row if the I0Process setting for the tested winding is either without or I0 CORRECTION. The settings
are Address 1106 for Winding 1, Address 1126 for Winding 2, and Address 1146 for Winding 3.In tests 1-3 current
is injected in one phase at any time; therefore, use the rows for 1-phase faults. The
other fault types are given if the user wishes to expand the tests.
Remarks
Test Inst. Used FREJA300