Micom P630C: Transformer Differential Protection Device
Micom P630C: Transformer Differential Protection Device
Micom P630C: Transformer Differential Protection Device
P630C/EN M/B31
Technical Manual
P630C/EN M/C11
Technical Manual
Warning
When electrical equipment is in operation, dangerous voltage will be present in certain parts of the
equipment. Failure to observe warning notices, incorrect use, or improper use may endanger
personnel and equipment and cause personal injury or physical damage.
Before any work is done in the terminal strip area, the device must be isolated. Where stranded
conductors are used, wire end ferrules must be employed.
Proper and safe operation of this device depends on appropriate shipping and handling, proper
storage, installation and commissioning, and on careful operation, maintenance and servicing.
For this reason only qualified personnel may work on or operate this device.
Qualified Personnel
are individuals who
! are familiar with the installation, commissioning, and operation of the device and of the system to which it is being
connected;
! are able to perform switching operations in accordance with safety engineering standards and are authorized to
energize and de-energize equipment and to isolate, ground, and label it;
! are trained in the care and use of safety apparatus in accordance with safety engineering standards;
Note
The operating manual for this device gives instructions for its installation, commissioning, and operation. However, the
manual cannot cover all conceivable circumstances or include detailed information on all topics. In the event of
questions or specific problems, do not take any action without proper authorization. Contact the appropriate
Schneider Electric technical sales office and request the necessary information.
Any agreements, commitments, and legal relationships and any obligations on the part of Schneider Electric
including settlement of warranties, result solely from the applicable purchase contract, which
is not affected by the contents of the operating manual.
Modifications After Going to Press
Contents
3 Operation 3-1
3.1 Modular Structure 3-1
3.2 Operator-Machine Communication 3-2
3.3 Configuring the Measured Value (Function Group LOC) 3-3
Panels
3.4 Serial Interfaces 3-6
3.4.1 PC Interface (Function Group PC) 3-6
3.4.2 "Logical" (Function Group COMM1) 3-8
Communication Interface 1
3.4.3 "Logical" (Function Group COMM2) 3-17
Communication Interface 2
3.4.4 "Logical" (Function Group COMM3) 3-20
Communication Interface 3
3.5 Time Synchronization via the (Function Group IRIGB) 3-24
IRIG-B Interface
3.6 Configurable Function Keys (Function Group F_KEY) 3-25
3.7 Configuration and Operating Mode (Function Group INP) 3-27
of the Binary Inputs
3.8 Configuration, Operating Mode, (Function Group OUTP) 3-28
and Blocking of the Output Relays
3.9 Configuration and Operating Mode (Function Group LED) 3-31
of the LED Indicators
3.10 Main Functions of the P630C (Function Group MAIN) 3-33
3.10.1 Conditioning the Measured 3-33
Variables
3.10.2 Operating Data Measurement 3-35
3.10.3 Configuring and Enabling the 3-43
Protection Functions
3.10.4 Activation of Dynamic Parameters 3-45
3.10.5 Multiple Blocking 3-45
3.10.6 Blocked / Faulty 3-47
(OUT OF SERVICE)
3.10.7 Starting Signals and 3-48
Tripping Logic
3.10.8 Time Tagging and Clock 3-52
Synchronization
3.10.9 Resetting Mechanisms 3-53
3.10.10 Test Mode 3-54
3.11 Parameter Subset Selection (Function Group PSS) 3-55
3.12 Self-Monitoring (Function Group SFMON) 3-57
3.13 Operating Data Recording (Function Group OP_RC) 3-59
3.14 Monitoring Signal Recording (Function Group MT_RC) 3-60
3.15 Overload Data Acquisition (Function Group OL_DA) 3-61
3.16 Overload Recording (Function Group OL_RC) 3-64
3.17 Fault Data Acquisition (Function Group FT_DA) 3-67
3.18 Fault Recording (Function Group FT_RC) 3-75
4 Design 4-1
7 Settings 7-1
7.1 Device Identification 7-1
7.2 Configuration Parameters 7-4
7.3 Function Parameters 7-25
7.3.1 Global 7-25
7.3.2 General Functions 7-29
7.3.3 Parameter Subsets 7-38
9 Commissioning 9-1
9.1 Safety Instructions 9-1
9.2 Commissioning Tests 9-3
10 Troubleshooting 10-1
11 Maintenance 11-1
12 Storage 12-1
Appendix
A Glossary
B Signal List
C Terminal Connection Diagrams
The MiCOM P630C differential protection device is intended for the fast and selective
short-circuit protection of transformers, motors and generators.
General functions
The transformer differential protection device P630C has the following main functions:
All main functions are individually configurable and can be disabled or enabled by the
user as desired. By means of a straight-forward configuration procedure, the user can
adapt the device flexibly to the scope of protection required in each particular
application. Due to the powerful, freely configurable logic of the device, special
applications can be accommodated.
Global functions
In addition to the features listed above, as well as comprehensive self-monitoring, the
following global functions are available in the MiCOM P630C differential protection
device:
! 6 current-measuring inputs
! 2 binary signal inputs (optical couplers) with user-definable function assignment
! 8 output relays with user-definable function assignment
The nominal currents of the measuring inputs in the P630C can be set.
The nominal voltage range of the optical coupler inputs is 24 to 250 V DC without
internal switching. The auxiliary voltage for the power supply can be switched internally
from 110 to 250 V DC, 100 to 230 V AC to the range 24 to 60 V DC.
All output relays are suitable for both signals and commands.
Interfaces
Local control and display:
Information is exchanged through the local control panel, the PC interface, or the
optional communication interfaces.
The following function groups are provided in the P630C differential protection devices.
For a detailed description of these function groups, see Chapter 3.
2 Technical Data
2.1 Conformity
Notice
Applicable to P630C Version - 301 - 401 - 601
Declaration of conformity
(Per Article 10 of EC Directive 72/73/EC.)
The product designated ‘P630C Transformer Differential Protection Device’ has been
designed and manufactured in conformance with the European standards EN 60255-6
and EN 60010-1 and with the ‘EMC Directive’ and the ‘Low Voltage Directive’ issued by
the Council of the European Community.
Installation Position
Vertical ± 30°.
Degree of Protection
Per DIN VDE 0470 and EN 60529 or IEC 529.
IP 52.
Weight
Approx. 4.5 kg
Terminals
PC Interface (X6):
DIN 41652 connector, type D-Sub, 9-pin.
Communication Interface:
Optical fibers F-SMA fiber-optic connection
(X7, X8 and X31, X32): per IEC 874-2 orDIN 47258
for plastic fibre
or
ST fiber-optic connection
(ST is a registered trademark of
AT&T Lightguide Cable Connectors)
for glass fibre
or
Leads (X9, X10 and X33): M2 threaded terminal ends for wire cross-sections
up to 1.5 mm2.
2.3 Tests
Type tests
All tests per EN 60255-6§ or IEC 255-6.
Electromagnetic
compatibility (EMC)
Interference Suppression
Per EN 55022§ or IEC CISPR 22, Class A.
_______________________________________________________________
§
For this EN, ENV or IEC standard, the DIN EN, DINV ENV or DIN IEC edition,
respectively, was used in the test.
Insulation
Voltage Test
Per DIN EN 61010 or IEC 255-5.
2 kV AC, 60 s.
Direct voltage (2.8 kV DC) must be used for the voltage test of the power supply inputs.
The PC interface must not be subjected to the voltage test.
Mechanical robustness
Vibration Test
Per EN 60255-21-1§ or IEC 255-21-1, test severity class 1.
Frequency range in operation: 10 to 60 Hz, 0.035 mm and 60 to 150 Hz, 0.5 g
Frequency range during transport: 10 to 150 Hz, 1 g
Seismic Test
Per EN 60255-21-3,§ test procedure A, class 1.
Frequency range:
5 to 8 Hz, 3.5 mm / 1.5 mm, 8 to 35 Hz, 10 / 5 m/s2, 3 x 1 cycle
Voltage Test
Per IEC 255-5.
2.5 kV AC, 1 s.
Direct voltage (2.8 kV DC) must be used for the voltage test of the power supply inputs.
The PC interface must not be subjected to the voltage test.
Environment
Temperatures
Recommended temperature range: -5°C to +55°C (23°F to 131°F)
Limit temperature range: -25°C to +70°C (-13°F to 158°F)
Humidity
≤ 75 % relative humidity (annual mean),
56 days at ≤ 95 % relative humidity and 40°C (104°F), condensation not permissible.
Solar Radiation
Direct solar radiation on the front of the device must be avoided.
Measurement inputs
Current
Nominal current: 1 and 5 A AC (adjustable).
Nominal consumption per phase: < 0.1 VA at Inom
Load rating:
continuous: 4 Inom (20 A)
for 10 s: 30 Inom (150 A)
for 1 s: 100 Inom (500 A)
Nominal surge current: 250 Inom (1250 A)
Frequency
Nominal frequency fnom: 50 Hz and 60 Hz (adjustable)
Operating range: 0.95 to 1.05 fnom.
Frequency protection: 40 to 70 Hz
Output relays
Rated voltage: 250 V DC, 250 V AC
Continuous current: 5 A
Short-duration current: 30 A for 0.5 s
Making capacity: 1000 W (VA) at L/R = 40 ms
Breaking capacity: 0.2 A at 220 V DC and L/R = 40 ms
4 A at 230 V AC and cos ϕ = 0.4
Power supply
Nominal auxiliary voltage VA,nom:
100 to 250 V DC / 100 to 230 V AC and 24 to 60 V DC (internal switching)
Nominal consumption:
Initial position: approx. 8 W
Active position: approx. 10 W
2.6 Interfaces
Communication interfaces
The communication unit can have three communication channels – depending on the
version. Channels 1 and 3 are designed for wire connection or fiber-optic connection,
whereas Channel 2 is intended for wire connection only.
Wire Leads
Per RS 485 or RS 422, 2 kV isolation
Distance to be bridged:
Point-to-point connection: max. 1200 m
Multipoint connection: max. 100 m
IRIG-B interface
B122 format
Amplitude-modulated signal
Carrier frequency: 1 kHz
BCD-coded dating information
Measured data, indications and counters: see Chapter 8 “Information and Control
Functions”
2.8 Settings
Main function
Minimum output pulse for trip command: 0.1 to 10 s (adjustable)
Differential protection
Operating time at Id = 10·Idiff> with harmonic blocking disabled or at Id > Idiff>>>:
min. 13 ms / typ. 15 ms
Operating time at Id = 2.5·Idiff> with harmonic blocking disabled:
min. 19 ms / typ. 21 ms
Operating time at Id = 2.5·Idiff> with harmonic blocking enabled:
min. 30 ms / typ. 33 ms
Starting resetting ratio of measuring system:
0.9 or 1.0 (adjustable)
Definite-time and
inverse-time
overcurrent protection
Operate time inclusive of output relay (measured variable from 0 to 2-fold operate value):
≤ 40 ms, approx. 30 ms
Reset time (measured variable from 2-fold operate value to 0):
≤ 40 ms, approx. 30 ms
Starting resetting ratio of starting element:
Set pickup value ≥ 0.3: approx. 0.95
Set pickup value < 0.3: approx. 0.92
2.10 Deviations
Definitions
‘Reference Conditions’
Sinusoidal signals at nominal frequency fnom, total harmonic distortion ≤ 2 %,
ambient temperature 20 °C (68°F), and nominal auxiliary voltage VA,nom.
'Deviation'
Deviation relative to the setting under reference conditions.
Differential protection
Measuring system for Id ≥ 0.2 Iref: ± 5 %
Inrush stabilization: ± 10 %
Definite-time and
inverse-time
overcurrent protection
Pickup values: ± 5 %
Thermal
overload protection
Pickup value Θ: ± 5 %
Definitions
‘Reference Conditions’
Sinusoidal signals at nominal frequency fnom, total harmonic distortion ≤ 2 %,
ambient temperature 20 °C (68°F), and nominal auxiliary voltage VA,nom.
'Deviation'
Deviation relative to the setting under reference conditions.
Definite-time stages
Measuring current I greater 2-fold pickup value: ± 1 % + 10 ms
Inverse-time stages
Measuring current I greater 2-fold reference current: ± 5 % + 10 to 25 ms
For IEC characteristic 'extremely inverse' and for thermal overload protection:
± 7.5 % + 10 to 25 ms
Definitions
‘Reference Conditions’
Sinusoidal signals at nominal frequency fnom, total harmonic distortion ≤ 2 %,
ambient temperature 20°C (68°F), and nominal auxiliary voltage VA,nom.
'Deviation'
Deviation relative to the corresponding nominal value under reference conditions.
Operating data
measurement
Measuring input currents: ± 1 %
Internally formed residual currents: ± 2 %
Internally formed differential and restraining currents: ± 2 %
Phase angle: ± 1 °
Internal clock
With free running internal clock: < 1 min/month
Depth: Up to 30 signals
Overload memory
Number: The 8 most recent overload events
Fault memory
Number: The 8 most recent fault events
Scope for fault values: Sampled data for all measured currents
Depth for fault values: Max. number of periods per fault set by the user;
820 periods in total for all faults, that is
16.4 s (for fnom = 50 Hz) or 13.7 s (for fnom = 60 Hz)
Signals
Time resolution: 1 ms
Fault values
Time resolution: 20 sampled values per cycle
Phase currents
Dynamic range: 33 Inom
where:
Vsal: Secondary accuracy limiting voltage (e.m.f.) of the CT
nn: Rated accuracy limit factor of the CT
nb: Actual accuracy limit factor of the CT
Isn: Rated secondary current (nominal secondary current) of the CT
Rct: Secondary winding resistance of the CT
Rbn: Rated resistive burden (secondary connected) of the CT
Rb: Actual resistive burden (secondary connected) of the CT
Kn: Rated transformation ratio of the CT
Kssc: Rated symmetrical short-circuit current factor
Kd: Dimensioning factor for the CT
The current transformer can be dimensioned for the minimum required secondary
accuracy limiting voltage acc. to IEC 60044-1, 2.3.4:
Alternatively, the current transformer can also be dimensioned for the minimum required
rated accuracy limit factor acc. to IEC 60044-1, 2.3.3:
nn ≥ K d ⋅ K ssc ⋅
(R ct + Rb ) = K ⋅ K ⋅ (Pct + Pb )
(R ct + Rbn ) d ssc (Pct + Pbn )
The equivalent power quantities in the equation above are defined as follows:
2
Pct = R ct ⋅ Isn
2
Pbn = R bn ⋅ Isn
2
Pb = R b ⋅ Isn
where:
R l: One-way lead resistance from CT to relay
RRel: Resistive burden of relay’s CT input
The relation between secondary accuracy limiting voltage acc. to IEC 60044-1, 2.3.4 and
rated accuracy limit factor acc. to IEC 60044-1, 2.3.3 is given as follows:
P P + Pbn
Vsal = nn ⋅ Isn ⋅ R ct + bn = nn ⋅ ct
Isn Isn
The rated knee point voltage Vk acc. to IEC 60044-1-am1, 2.3.12 is lower than the
secondary accuracy limiting voltage Vsal acc. to IEC 60044-1, 2.3.4. It is not possible to
give a general relation between Vk and Vsal, but normally Vk may be considered to be
80 % to 85 % of Vsal.
For the differential protection of the P630C the dimensioning factor Kd for the CTs
considering external faults has been determined empirically:
The diagram according to figure 2-1 represents the empirically determined dimensioning
factor Kemp as a function of the primary impedance ratio (system impedance ratio) Xp/Rp.
4,5
3,5
Kem p 2,5
2
1,5
0,5
0
0 10 20 30 40 50 60 70 80
Xp/Rp
This CT requirement assures through fault stability of the differential element. Due to
saturation discriminator CT requirement is independent of the current sensitivity given by
the set basic threshold Idiff> of the tripping characteristic.
For the maximum fault current with an internal fault static saturation up to 4 times is
permissible. This corresponds to a dimensioning factor Kd of 0.25:
3 Operation
The P630C, a numeric device, is part of the MiCOM P 30 family of devices. Figure 3-1
shows the basic hardware structure of the P630C.
The external analog and binary quantities – electrically isolated – are converted to the
internal processing levels by input transformers and optical couplers. Commands and
signals generated by the device internally are transmitted to external destinations via
floating contacts. The external auxiliary voltage is connected to the power supply unit
which provides the auxiliary voltages that are required internally.
The following interfaces are available for the exchange of information between operator
and device:
All setting parameters and signals as well as all measured variables and control
functions are arranged within the branches of the menu tree following a scheme that is
uniform throughout the device family. The main branches are:
‘Parameters’ branch
This branch carries all settings, including the device identification data, the configuration
parameters for adapting the device interfaces to the system, and the function parameters
for adapting the device functions to the process. All values in this group are stored in
non-volatile memory, which means that the values will be preserved even if the power
supply fails.
‘Operation’ branch
This branch includes all information relevant for operation such as measured operating
data and binary signal states. This information is updated periodically and consequently
is not stored. In addition, various control parameters are grouped here, for example
those for resetting counters, memories and displays.
‘Events’ branch
The third branch is reserved for the recording of events. Therefore all information
contained in this group is stored. In particular, the start/end signals during a fault, the
measured fault data, and the sampled fault records are stored here and can be read out
at a later time.
Settings and signals are displayed either in plain text or as addresses, in accordance
with the user’s choice. The Appendix documents the settings and signals of the P630C
in the form of an ‘address list’. This address list is complete and thus contains all
settings, signals and measured variables used with the P630C.
The configuration of the local control panel also permits the installation of Measured
Value 'Panels’ on the LCD display. Different Measured Value Panels are automatically
displayed for specific system operating conditions. Priority increases from normal
operation to operation under overload conditions, operation during a ground fault, and
finally to operation following a short circuit in the system. Thus the P630C provides the
measured data relevant for the prevailing conditions.
The P630C provides Measured Value Panels that display the measured values relevant
at a given time.
During normal power system operation, the Operation Panel is displayed. When an
event occurs, the display switches to the appropriate Event Panel – provided that
measured values have been selected for the Event Panels. In the event of an overload
event or a ground fault, the display will automatically switch back to the Operation Panel
at the end of the event. In the event of a fault, the Fault Panel remains active until the
LED indicators or the fault memories are reset.
Operation Panel
The Operation Panel is displayed after the set return time has elapsed, provided that at
least one measured value has been configured.
The user can select the measured operating values that will be displayed on the
Operation Panel by setting an 'm out of n' parameter. If more measured values are
selected for display than the LCD display can accommodate, the display will switch to
the next set of values at intervals defined by the setting at L O C : H o l d - t i m e f o r
P a n e l s or when the appropriate keys on the local control panel are pressed.
Fault Panel
The Fault Panel is displayed in place of another data panel when there is a fault,
provided that at least one measured value has been configured. The Fault Panel
remains on display until the LED indicators or the fault memories are reset.
The user can select the measured fault values that will be displayed on the Fault Panel
by setting an 'm out of n' parameter. If more measured values are selected for display
than the LCD display can accommodate, the display will switch to the next set of values
at intervals defined by the setting at L O C : H o l d - t i m e f o r P a n e l s or when the
appropriate keys on the local control panel are pressed.
Overload Panel
The Overload Panel is automatically displayed in place of another data panel when there
is an overload, provided that at least one measured value has been configured. The
Overload Panel remains on display until the overload ends, unless a fault occurs. In this
case, the display switches to the Fault Panel.
The user can select the measured values that will be displayed on the Overload Panel
by setting an 'm out of n' parameter. If more measured values are selected for display
than the LCD display can accommodate, the display will switch to the next set of values
at intervals defined by the setting at L O C : H o l d - t i m e f o r P a n e l s or when the
appropriate keys on the local control panel are pressed.
If the communication unit with two communication channels is installed, settings for two
"logical" communication interfaces will be available. The settings for "logical"
communication interface 1 (COMM1) can be assigned to physical communication
channels 1 or 2 (see section entitled 'Main Functions'). If the COMM1 settings have been
assigned to communication channel 2, then this means that the settings for "logical"
communication interface 2 (COMM2) will automatically be active for communication
channel 1. Communication with the P630C via communication channel 2 is only possible
when the PC interface is inactive. As soon as communication occurs through the PC
interface, communication channel 2 is "dead".
If tests are run on the P630C, the user is advised to activate the test mode so that the
PC or the control system will evaluate all incoming signals accordingly (see section
entitled 'General Functions').
Communication between the device and a PC is through the PC interface. In order for
data transfer between the P630C and the PC to function, several settings must be made
in the P630C.
An operating program is available as an accessory for P630C control (see Chapter 13).
Depending on the design version of the communication unit (see Technical Data),
several interface protocols are available. The protocol as per IEC 60870-5-103 is
supported for all versions. The following user-selected interface protocols are available
for use with the P630C:
In order for data transfer to function properly, several settings must be made in the
P630C.
The communication interface can be blocked through a binary signal input. In addition, a
signal or measured-data block can also be imposed through a binary signal input.
3-7 "Logical" communication interface 1: settings for the IEC 60870-5-103 interface protocol
3-8 "Logical" communication interface 1: settings for the IEC 870-5-101 interface protocol
3-9 "Logical" communication interface 1: settings for the ILS_C interface protocol
3-12 "Logical" communication interface 1: settings for the COURIER interface protocol
Checking spontaneous
signaling
For interface protocols per IEC 60870-5-103, IEC 870-5-101 or ILS-C, there is the option
of selecting a signal for testing purposes. This transmission of this signal to the control
station as ‘sig. start‘ or ‘sig. end‘ can then be triggered via the local control panel.
Checking spontaneous
signaling
There is the option of selecting a signal for testing purposes. This transmission of this
signal to the control station as ‘sig. start‘ or ‘sig. end‘ can then be triggered via the local
control panel.
Digital network:
! Asynchronous data interface of a primary multiplexing equipment
Enabling
In order to use InterMiCOM, communication interface COMM3 has to be included in the
device configuration by way of the setting C O M M 3 : F u n c t i o n g r o u p C O M M 3 . This
setting parameter is only visible if the relevant optional communication module is fitted.
After configuration of COMM3, all addresses associated with this function group (setting
parameters, binary state signals etc.) become visible.
The function group can then be enabled or disabled at C O M M 3 : G e n e r a l e n a b l e
USER.
Telegram configuration
The communication baud rate can be set (at C O M M 3 : B a u d r a t e ) so as to meet the
transmission channel requirements. Source address (C O M M 3 : So u r c e a d d r e s s )
and receiving address (C O M M 3 : R e c e i vi n g a d d r e s s ) can be set to differing values
to prevent InterMiCOM communication internal to the device.
Using the InterMiCOM interface, eight independent binary signals can be transmitted in
each direction. For the assignment of functions to the send signals (C O M M 3 : F c t.
a s s i g n m . s e n d 1 , … ), any signal from the "Binary Outputs" selection table can be
selected. For the receive signals (C O M M 3 : F c t. a s s i g n m . r e c . 1 , … ), any signal
from the "Binary Inputs" selection table can be chosen.
! Binary signals 1 to 4:
Choice of Blocking or Direct intertrip for the operating mode.
! Binary signals 5 to 8:
Choice of Permissive or Direct intertrip for the operating mode.
Speed
fast
Blocking
Permissive
slow
low
high high
Direct
Security Intertrip Dependability
Communication monitoring
Timer stage C O M M 3 : T i m e - o u t c o m m .fa u l t is used for monitoring the
transmission channel. This timer is retriggered whenever a 100% valid telegram is
received. The wide setting range allows adaptation to the actual channel transmission
times. This is particularly important for time-critical schemes such as the blocking
scheme. After this timer stage has elapsed, alarm signals C O M M 3 :
C o m m u n i c a ti o n s fa u l t and SF M O N : C o m m u n i c .fa u l t C O M M 3 are issued
and the received signals are set to their user-defined default values (C O M M 3 : D e fa u l t
va l u e r e c . 1 , …), thus ensuring that the relay protection logic will continue to operate
in a pre-determined failsafe way. When the InterMiCOM interface is used in connection
with the PSIG (protective signaling) function, the alarm signals can be configured to the
corresponding PSIG input signals using the C O M M 3 : Si g .a s g . c o m m .fa u l t
setting.
‚COMM3: Time-out
comm.fault'
t 0
‚COMM3:
(Re-)Trigger
Communications fault'
‚COMM3: Time-out
link fail.'
t 0
‚COMM3:
Comm. link failure'
Supervision of
communication link quality
For each received message, InterMiCOM carries out a syntax check and updates the
proportion of corrupted messages within the last 1000 received messages. These ratio
results are provided as continuously updated values (C O M M 3 : N o . te l . e r r o r s p .u .)
and as maximum value (C O M M 3 : N o . t . e r r . , m a x , s t o r e d ) . The user may declare the
percentage of corrupted messages that can be allowed compared to total messages
transmitted (C O M M 3 : L i m i t te l e g r . e r r o r s ), before an alarm is raised (C O M M 3 :
L i m . e x c e e d . , t e l . e r r . and SF M O N : L i m .e xc e e d . , t e l . e r r . ). All corrupted
messages are counted (C O M M 3 : N o . te l e g r a m e r r o r s ). This counter as well as the
stored maximum ratio of corrupted messages can be reset via C O M M 3 : R e s e t N o .
tel.errors.
Commissioning tools
The actual values of send and receive signals can be read from the device as physical
state signals (C O M M 3 : Sta te s e n d 1 , … and C O M M 3 : Sta te r e c e i ve 1 , …).
In addition, InterMiCOM provides two test facilities for commissioning of the protection
interface.
For the loop back test, the send output is directly linked back to the receive input of the
same device. The test can be triggered via C O M M 3 : L o o p b a c k t e s t . The device
then sends the bit pattern (set as equivalent decimal number at C O M M 3 : L o o p b a c k
s e n d ) for the preset time C O M M 3 : H o l d t i m e f o r t e s t . Only for this test, the
source address is set to "0", a value that is not used for regular peer-to-peer
communication.
While the hold time is running, the test result can be checked by reading out the
measured operating data values C O M M 3 : L o o p b a c k r e s u l t and C O M M 3 :
L o o p b a c k r e c e i v e . Once the hold time has expired, the loop back test is terminated
and InterMiCOM reverts to the normal sending mode (i.e. sending the updated values of
the configured send signals, using the set source address).
Thus in case of communication problems, the loop back test can be used to verify or to
exclude a device malfunction. The transmission channel including the receiving device
can be checked manually by setting individual signals (C O M M 3 : S e n d s i g n a l f o r
te s t) to user-defined test values (C O M M 3 : L o g . s t a t e f o r t e s t ). After triggering the
test via C O M M 3 : S e n d s i g n a l , t e s t , the preset signal is sent with the preset value
for the set hold time C O M M 3 : H o l d ti m e fo r te s t. The 7 remaining signals are not
affected by this test procedure and are sent with their updated values. During this time,
the received signal can be checked from the receiving device, e.g. by reading the
physical state signal. Once the hold time has expired, the test mode is reset
automatically and the updated values of all 8 signals are transmitted again.
3.5 Time Synchronization via the IRIG-B Interface (Function Group IRIGB)
If a GPS receiver with an IRIG-B connection is available, for example, then the internal
clock in the P630C can be synchronized to GPS time through the optional IRIG-B
interface. The user must keep in mind that the IRIG-B signal contains only one piece of
information about the date (the day as numbered since the beginning of the year). On
the basis of this piece of information about the date, the P630C calculates the current
date (DD.MM.YY) based on the year set in the P630C.
Ready to synchronize
Once the IRIG-B interface has been enabled and is receiving a signal, the P630C
checks the received signal for plausibility. Non-plausible signals are rejected by the
P630C. If a correct signal is not received by the P630C continuously, then the
synchronization function is no longer ready.
The P630C has four freely configurable function keys. Figure 3-19 illustrates their
operation using function key F1 as an example. This function key is not enabled unless
the associated password F _ K E Y : P a s s w o r d f u n c t . k e y 1 has been entered first.
Once the password has been entered, the function key remains active for no longer than
the set time F _ K E Y : R e t u r n t i m e f c t . k e y s . Thereafter, the function key is disabled
until the password is entered again. The same rules apply to function keys F2, F3 and
F4.
The two menu jump lists are composed via L O C : F c t. m e n u j m p l i s t x (x: 1 or 2).
Up to 16 functions can be selected, including setting parameters, event counters and /or
event recordings.
Key response
If the backlighting of the LCD display is switched off, pressing a function key or the read
key will initially result in switching on the backlighting. Pressing the key a second time
will then trigger the selected function (as for the other keys).
3-19 Configuration and operating mode of the function keys. The associated function can be a single function or a menu jump list.
3.7 Configuration and Operating Mode of the Binary Inputs (Function Group INP)
The P630C has optical coupler inputs for processing binary signals from the system. The
functions that will be activated in the P630C by triggering these binary signal inputs are
defined by the configuration of the binary signal inputs. The trigger signal must persist for
at least 30 ms in order to be recognized by the P630C.
In this manual, we assume that the required functions (marked 'EXT' in the address
description) have been assigned to binary signal inputs by configuration.
The P630C has output relays for the output of binary signals. The binary signals to be
issued are defined by configuration.
Depending on the I/O module under consideration, the output relays have either make
contacts, changeover contacts or both (see the Terminal Connection Diagrams in the
Appendix). For relays with make contacts, the energize-on-signal (ES) mode
corresponds to normally-open operation. The normally-energized (NE) mode means that
the polarity of the driving signal is inverted, such that a logic "0" maintains the relay
normally-closed. For relays with changeover contacts, these more common descriptions
are not applicable.
Latching is disabled manually from the local control panel or through an appropriately
configured binary signal input either at the onset of a new fault or at the onset of a new
system disturbance, depending on the operating mode selected.
If, on the other hand, a serious hardware error has been detected by the self-monitoring
function (see the error messages leading to blocking according to Chapter 10) then all
output relays are reset whatever the set operating mode or signal configuration.
3-21 Configuration, setting the operating mode, and blocking the output relays
The P630C has 17 LED indicators for the indication of binary signals. Five of the LED
indicators are permanently assigned to functions. The other LED indicators are freely
configurable.
The secondary phase currents of the system transformers are fed to the P630C. The
measured variables are – electrically isolated – converted to normalized electronics
levels. Air-gap transformers are used in the phase current path to suppress aperiodic
signal components. The analog quantities are digitized and are thus available for further
processing.
Settings that do not refer to nominal quantities are converted by the P630C to nominal
quantities. For this purpose, the user must set the secondary nominal currents of the
system transformers.
The connection arrangement of the measuring circuits must be set in the P630C.
Figure 3-24 shows the standard connection. The phase of the digitized currents is
rotated 180° by this setting.
The P630C has an operating data measurement function for the display of currents and
voltages measured by the P630C during normal power system operation; quantities
derived from these measured values are also displayed. For the display of measured
values, set lower thresholds need to be exceeded. If these lower thresholds are not
exceeded, the value not measured is displayed. The following measured variables are
displayed:
3-25 Measured operating data for the phase currents, ends a and b
3-27 Measured operating data for the residual currents, ends a and b
Angle determination
The P630C determines the angle between the following currents if the associated
currents exceed the lower threshold of 0.033 Inom:
! Angle between the phase currents for each end of the transformer
! Angle between the currents of the same phase between two ends of the transformer
3-29 Determination of the angle between the phase currents of the transformer ends
By means of a straight-forward configuration procedure, the user can adapt the unit
flexibly to the range of functions required in each particular high voltage substation. By
including the relevant protection functions in the device configuration and canceling all
others, the user creates an individual device appropriate to the application. Parameters,
signals and measured values of canceled protection functions are not displayed on the
local control panel. Functions of general applicability such as operating data recording
(OP_RC) or main functions (MAIN) cannot be canceled.
Canceling a protection
function
The following conditions have to be met before a protection function can be canceled:
If the above conditions are met, proceed through the Configuration Parameters branch of
the menu tree to access the setting parameter relevant for the device function to be
canceled. If you wish to cancel the LIMIT function group, for example, access the setting
parameter L I M I T : F u n c t i o n g r o u p L I M I T and set its value to Without. Should
you wish to re-include the function group in the device configuration, set the value to
With.
For several of the protection functions, it is possible to switch the duration of the set hold
time to other settings - the "dynamic parameters" – through an appropriately configured
binary signal input. If the hold time is set to 0 s, the switching is effective while the binary
signal input is being triggered.
Four multiple blockings may be defined via 'm out of n' parameters. The items available
for selection are found in the Address List. Thereby the functions defined by the
selection may be blocked via an appropriately configured binary signal input.
If the protective functions are blocked, this condition is signaled by a steady light from
yellow LED indicator H 2 on the local control panel and also by a signal through the
output relay configured for M AIN : Bl o c k e d /fa u l ty. In addition, the user can select
the functions that will produce the M AIN : Bl o c k e d /fa u l ty signal by setting an ‘m out
of n’ parameter.
Starting signals
The trip signals of differential protection and ground differential protection (Br: Restricted
earth fault protection) plus the general startings of the definite-time and inverse-time
overcurrent protection are combined into one common general starting.
Trip command
The P630C has four trip commands. The functions to effect a trip can be selected by
setting an 'm out of n' parameter independently for each of the four trip commands. The
minimum trip command time may be set. The trip signals are present only as long as the
conditions for the signal are satisfied.
For each of the four trip commands, the user can specify by way of the appropriate
setting whether it will operate in latching mode. If the latching mode is selected, the trip
command persists until it is reset from the local control panel or via an appropriately
configured binary signal.
The data stored in the operating data memory, the monitoring signal memory and the
event memories are date-and time-tagged. For correct tagging, date and time need to be
set at the P630C.
Via an appropriately configured binary signal input, the time of different devices may be
synchronized by means of a pulse. The P630C evaluates the rising edge. This is used to
set the clock to the next full minute, rounding either up or down. If several start/end
signals occur (bouncing of a relay contact), the last edge is evaluated.
Stored data such as event logs, fault values etc, can be cleared in a number of ways.
The following mechanisms are available:
! Automatic resetting of the event signals indicated by LED indicators (provided that the
LED operating mode has been set accordingly) and of the display of measured event
data on the local control panel whenever a new event occurs.
! Resetting of LED indicators and measured event data on the local control panel by
pressing the reset key (‘Clear’ key ‘C’) located on the panel
! Selective resetting of a particular memory type (only the fault memory, for example)
from the local control panel or through appropriately configured binary signal inputs
! General reset
In the first two cases listed above only the displays on the local control panel are cleared
but not the internal memories such as the fault memory.
In the event of a cold restart, namely simultaneous failure of both internal battery and
power supply, all stored signals and values will be lost.
3-39 General reset, LED reset and measured event data reset from the local control panel
If tests are run on the P630C, the user is advised to activate the test mode so that all
incoming signals via the serial interfaces will be marked accordingly.
With the P630C, four independent parameter subsets may be pre-set. The user may
switch between parameter subsets during operation without interrupting the protection
function.
If, after the supply voltage is turned on, no logic value of ‘1’ is present at any of the
binary signal inputs selected for the parameter subset selection, then the parameter
subset selected via a function parameter will become active once the stored energy time
has elapsed. The previous parameter subset remains active while the stored energy
timer stage is running.
Parameter subset selection may also occur during a starting condition. When subset
selection is handled via binary signal inputs, a maximum inherent delay of approximately
100 ms must be taken into account.
Settings for which only one address is given in the following sections are equally
effective for all four parameter subsets.
Comprehensive monitoring routines in the P630C ensure that internal faults are detected
and do not lead to malfunctions.
Cyclic tests
After startup has been successfully completed, cyclic self-monitoring tests will be run
during operation. In the event of a positive test result, a specified monitoring signal will
be issued and stored in a non-volatile memory – the monitoring signal memory – along
with the assigned date and time (see also Monitoring Signal Recording).
The self-monitoring function monitors the built-in battery for any drop below the minimum
acceptable voltage level. If the associated monitoring signal is displayed, then the
battery should be replaced within a month, since otherwise there is the danger of data
loss if the supply voltage should fail. Chapter 11 gives further instructions on battery
replacement.
Signaling
The monitoring signals are also signaled via the output relay configured SF M O N :
W a r n i n g . The output relay operates as long as an internal fault is detected.
Device response
The response of the P630C to monitoring signals takes one of the following forms
depending on the signal.
! Signaling Only
If there is no malfunction associated with the monitoring signal, then only a signal is
issued, and there are no further consequences. This situation exists, for example,
when internal data acquisition memories overflow.
! Selective Blocking
If a fault is diagnosed solely in an area that does not affect the protective functions,
then only the affected area is blocked. This would apply, for example, to the detection
of a fault on the communication module or in the area of the PC interface.
! Warm Restart
If the self-monitoring function detects a fault that might be eliminated by a system
restart, for example a fault in the hardware, then a procedure called a warm restart is
automatically initiated. During this procedure, as with any startup, the computer
system is reset to a defined state. A warm restart is characterized by the fact that no
stored data and, in particular, no setting parameters are affected by the procedure. A
warm restart can also be triggered manually by control action. During a warm restart
sequence the protective functions and the communication through serial interfaces
will be blocked. If the same fault is detected after a warm restart has been triggered
by the self-monitoring system, then the protective functions remain blocked but
communication through the serial interfaces will usually be possible again.
! Cold Restart
If a corrupted parameter subset is diagnosed in the checksum test during self-
monitoring, then a cold restart is carried out. This is necessary because the
protection device cannot identify which parameter in the subset is corrupt. A cold
restart causes all internal memories to be reset to a defined state. This means that all
the protection device settings are also erased after a cold restart. The settings that
then apply are shown underlined in the column ‘Range of Values’ in the Address List
(see Appendix). In order to establish a safe initial state, the default values have been
selected so that the protective functions are blocked. Both the monitoring signal that
triggered the cold restart and the value indicating parameter loss are entered in the
monitoring signal memory.
3-43 Operating data recording and the counter of signals relevant to system operation
The monitoring signals generated by the self-monitoring function are recorded in the
monitoring signal memory. A listing of all possible entries in this monitoring signal
memory is given in the address list (see Appendix). The memory depth allows for a
maximum of 30 entries. If more than 29 monitoring signals occur without interim memory
clearance, the SFMON: O v e r f l o w M T _ R C signal is entered as the last entry.
Monitoring signals prompted by a hardware fault in the protection device are always
entered in the monitoring signal memory. Monitoring signals prompted by a peripheral
fault can be entered into the monitoring signal memory, if desired. The user can select
this option by setting an 'm out of n' parameter (see Self-Monitoring).
If at least one entry is stored in the monitoring signal memory, this fact is signaled by the
red LED indicator H 3 on the local control panel. Each new entry is indicated by a
flashing light.
The monitoring signal memory can only be cleared manually by a control action. Entries
in the monitoring signal memory are not even cleared automatically if the corresponding
test in a new test cycle has a negative result. The contents of the monitoring signal
memory can be read from the local control panel or through the PC or communication
interface. The time and date information assigned to the individual entries can be read
out through the PC or communication interface or from the local control panel.
Counter of monitoring
signals
The number of entries stored in the monitoring signal memory is displayed on the
MT_RC: N o . m o n i t . s i g n a l s . counter.
In the event of an overload, the P630C determines the following measured overload
data:
! Overload duration
! Measured overload data derived from the measured operating data of the thermal
overload protection function THRM1. For this function, the following values are
determined:
" Status of the thermal replica
" Load current
" Object temperature
" Time remaining before trip
" Offset of the thermal replica
Acquisition of the
measured overload data of
thermal overload protection
The measured overload data are derived from the measured operating data of the
thermal overload protection function. They are stored at the end of the overload event.
Time tag
The date that is assigned to each overload event by the internal clock is stored. An
overload event’s individual start or end signals are likewise time-tagged by the internal
clock. The date and time assigned to the overload events when the event begins can be
read out from the overload memory at the local control panel or through the PC and ILSA
interfaces. The time information (relative to the onset of the overload event) that is
assigned to the signals can be retrieved from the overload memory or through the PC or
communication interfaces.
Overload logging
Protection signals during an overload event are logged in chronological order with
reference to the specific event. A total of eight overload events, each involving a
maximum of 200 start or end signals, can be stored in the non-volatile overload
memories. After eight overload events have been logged, the oldest overload log will be
overwritten, unless memories have been cleared in the interim. If more than 199 start or
end signals have occurred during a single overload event, then OL_ R C : O ve r l . m e m .
o ve r fl o w will be entered as the last signal.
In addition to the signals, the measured overload data are also entered in the overload
memory.
The overload recordings can be read from the local control panel or through the PC or
communication interfaces.
When there is a fault in the power system, the P630C collects the following measured
fault data:
! Running time
! Fault duration
! Fault currents
! Differential current of all three measuring systems
! Second and fifth harmonic of the differential current
! Restraining current of all three measuring systems
Running time and fault
duration
The running time is defined as the time between the start and end of the general starting
signal that is generated within the P630C, and the fault duration is defined as the time
between the start and end of the F T _ R C : R e c o r d . i n p r o g r e s s signal.
The difference in time between the start of the fault and the fault data acquisition time is
determined by the P630C and displayed.
Acquisition of the
differential and restraining
currents
The P630C stores the differential and restraining current data determined at the
acquisition time by the differential protection function. Moreover, the values for the
second and fifth harmonic of the differential current are stored.
Differential and restraining currents are stored as per-unit quantities referred to Iref.
Fault counting
Faults are counted and identified by sequential number.
Time tag
The date that is assigned to each fault by the internal clock is stored. A fault’s individual
start or end signals are likewise time-tagged by the internal clock. The date and time
assigned to a fault when the fault begins can be read out from the fault memory at the
local control panel or through the PC and communication interfaces. The time
information (relative to the onset of the fault) that is assigned to the signals can be
retrieved from the fault memory or through the PC or communication interfaces.
Fault logging
Protection signals during a fault, including the signals during the settable pre-fault and
post-fault times, are logged in chronological order with reference to the specific fault. A
total of eight faults, each involving a maximum of 200 start or end signals, can be stored
in the non-volatile fault memories. After eight faults have been logged, the oldest fault
record will be overwritten, unless memories have been cleared in the interim. If more
than 199 start or end signals have occurred during a single fault, then F T _ R C : F a u l t
m e m . o ve r fl o w will be entered as the last signal. If the time and date are changed
during the pre-fault time, the signal F T _ R C : F a u l ty ti m e ta g is generated.
In addition to the fault signals, the measured fault data are also entered in the fault
memory.
The fault logs can be read from the local control panel or through the PC or
communication interfaces.
The pre-fault time is exactly adhered to if it is shorter than the set maximum recording
time. Otherwise; the pre-fault time is set to the maximum recording time minus a
sampling increment and the post-fault time is set to zero.
If the maximum recording time is exceeded, the analog values for the oldest fault are
overwritten, but not the binary values. If more than eight faults have occurred since the
last reset, then all data for the oldest fault are overwritten.
The analog data of the fault record can only be read out through the PC or
communication interfaces.
When the supply voltage is interrupted or after a warm restart, the values of all faults
remain stored.
The P630C is designed for the protection of transformers as well as for the protection of
motors and generators and of other two-winding arrangements.
Vector group matching is achieved by the straightforward input of the relevant vector
group identification number. For special applications, zero-sequence current filtering may
be deactivated. For conditions where it is possible to load the transformer with a voltage
in excess of the nominal voltage, the overfluxing restraint prevents inappropriate tripping.
For application as differential protection device for motors or generators, the harmonic
restraint (inrush compensation) can be deactivated. The start-up of directly switched
asynchronous motors represents a problem in differential protection due to transient
transformer saturation caused by a displacement of the start-up current for relatively high
primary time constants. Even under these unfavorable measurement conditions, the
P630C exhibits an excellent stable performance due to the application of a saturation
discriminator.
All observations below are based on the assumption that the system current
transformers are connected to the P630C in standard configuration (see Conditioning of
the Measured Variables). In particular, the application as transformer differential
protection device presupposes that winding ‘a’ corresponds to the high voltage side of
the transformer. For a non-standard connection, the appropriate settings must be
selected (see Chapter 7).
Enabling or disabling
differential protection
Differential protection can be disabled or enabled from the local control panel. Moreover,
enabling can be done separately for each parameter subset.
Amplitude matching
In order to set the amplitude matching for the protected object, a reference power -
identical for all windings - needs to be defined. For two-winding arrangements, the
nominal power will usually be the reference power. The individual reference currents for
each winding of the protected object are then calculated by the P630C on the basis of
the set reference power and the set primary nominal voltages of the transformer.
Sref Sref
IB,a = IB,b =
3 ⋅ Vnom,a 3 ⋅ Vnom,b
with
The P630C calculates the matching factors on the basis of the reference currents and
the set primary nominal currents of the system transformers.
Inom,a Inom,b
k am,a = k am,b =
Iref ,a Iref ,b
with
The P630C checks that the reference currents and matching factors are within their
permissible ranges. The matching factors must satisfy the following conditions:
Should the P630C calculate reference currents or matching factors not satisfying the
above conditions then a warning will be issued and the P630C will be blocked
automatically.
The measured values of the phase currents of the windings of the protected object are
multiplied by the relevant matching factors and are then available for further processing.
Consequently, all threshold values and measured values always refer back to the
relevant reference currents rather than to the transformer nominal currents or the
nominal currents of the device.
kam,a > 16
kam,b > 16
kmax-1
3-59 Vector diagram for vector group matching with a transformer having the vector group Yd5
The following table lists the required operations for all vector groups that may occur. The
indices in the formulae have the following meaning:
am: amplitude-matched
s: amplitude- and vector group-matched
x: phase A, B or C
y: measuring system 1, 2 or 3
z: winding a, b, c or d
x+1: cyclically trailing phase
x-1: cyclically leading phase
a I am,x,a − I am,0,a
0 I am,x,z − I am,0,z
1 1
[
⋅ I am,x,z − I am,x +1,z ]
3
2 I am,0,z − I am,x +1,z
3 1
[
⋅ I am,x −1,z − I am,x +1,z ]
3
4 I am,x −1,z − I am,0,z
b 5 1
[
⋅ I am,x −1,z − I am,x,z ]
3
6 I am,0,z − I am,x,z
7 1
[
⋅ I am,x +1,z − I am,x,z ]
3
8 I am,x +1,z − I am,0,z
9 1
[
⋅ I am,x +1,z − I am,x −1,z ]
3
10 I am,0,z − I am,x −1,z
11 1
[
⋅ I am,x,z − I am,x −1,z ]
3
a I am,x,a
0 I am,x,z
1 1
[ ]
⋅ I am,x,z − I am,x +1,z + I am,0,z
3
2 I am,0,z
3 1
[ ]
⋅ I am,x −1,z − I am,x +1,z + I am,0,z
3
4 I am,x −1,z
b 5 1
[ ]
⋅ I am,x −1,z − I am,x,z + I am,0,z
3
6 I am,0,z
7 1
[ ]
⋅ I am,x +1,z − I am,x,z + I am,0,z
3
8 I am,x +1,z
9 1
[ ]
⋅ I am,x +1,z − I am,x −1,z + I am,0,z
3
10 I am,0,z
11 1
[ ]
⋅ I am,x,z − I am,x −1,z + I am,0,z
3
I am,0,z =
1
[
⋅I +I +I
3 am,A,z am,B,z am,C,z
]
z: winding a or b
Iam: amplitude-matched current
Vector group matching is via a straight-forward input of the vector group identification
number provided that the phase currents of the high and low voltage side(s) are
connected in standard configuration (see Conditioning of the Measured Variables). For
other configurations, special considerations apply (see chapter 7). An anti-clockwise
rotating field needs to be taken into account by making the appropriate setting at the
P630C. The P630C will then automatically form the complementary value of the set
vector group ID to the number 12 (vector group ID = 12 – set ID).
Tripping Characteristics
The differential and restraining current variables for each measurement system are
calculated from the current variables after amplitude and vector group matching. The
formation of the restraining variables differs between two- and three-winding protection.
The following equations are valid for uniformly defined current arrows relative to the
protected equipment, that is the current arrows of all windings point either towards the
protected object or away from it.
I d ,y = I s,y ,a + I s,a,b
3-61 Forming the differential and restraining currents for the three measuring systems
The tripping characteristic of the differential protection device P630C has two knees. The
first knee is dependent on the setting of the basic threshold value D I F F : I d i f f > P S x
and is on the load line for single-side feed. The second knee of the tripping characteristic
is defined by the setting D I F F : I R , m 2 P S x .
The characteristic equations for the three different ranges are given below. Figure 3-62
shows the tripping characteristic.
Id I >
= diff
I ref I ref
Characteristic equation for the range 0.5 ⋅ I diff > < I R ≤ I R,m 2 :
Id I > I
= (1 − 0.5 ⋅ m1 ) ⋅ diff + m1 ⋅ R
I ref I ref I ref
Id I > I I
= (1 − 0.5 ⋅ m1 ) ⋅ diff + (m1 − m2 ) ⋅ R,m 2 + m2 ⋅ R
I ref I ref I ref I ref
8.00
Id / Iref
Tripping area
6.00
ic
rist
4.00
e f acte
eed
-sid char
7
0.
=
t
sin ren
m2
for lt cur
gle
2.00
Fau
Blocking area
0.3
m1 =
12200e.DS4
IR,m2 / Iref = 4.0
Id> / Iref = 0.2
Inrush stabilization
(harmonic restraint)
When an unloaded transformer is connected, the inrush current at unfavorable switching
instants such as for voltage zero, may have values that exceed the transformer nominal
current several times over. It takes some time for the current to assume its small
stationary value. Since the high inrush current flows on the connected side only, the
tripping characteristic of differential protection may give rise to a trip unless stabilizing
action is taken. The fact that the inrush current has a high proportion of harmonics
having twice the system frequency offers a possibility of stabilization against tripping by
the inrush current.
The P630C filters the differential current. The fundamental wave I(f0) and second
harmonic components I(2*f0) of the differential current are determined. If the ratio
I(2*f0) / I(f0) exceeds a specific adjustable value in at least one measuring system,
tripping is blocked optionally in one of the following modes:
There will be no blocking if the differential current exceeds the set threshold
DIFF: Idiff>> PSx.
Saturation discriminator
Up to a certain limit, stability in the event of external faults is ensured by means of the
bias. Due to the triple-slope tripping characteristic, the stabilization is particularly
pronounced for high currents. However, as an additional safeguard for through-currents
with transformer saturation, the P630C is provided with a saturation discriminator.
After each zero crossing of the restraining current, the saturation discriminator monitors
the occurrence of the differential current over time. For internal faults, the differential
current appears after a zero crossing together with the restraining current. In the case of
passing currents with transformer saturation, however, a differential current will not
appear until transformer saturation begins. Accordingly, a locking signal is generated on
the basis of level monitoring of the differential current as compared to the restraining
current, and thus the desired through-stabilization is achieved. Locking is restricted to
the measuring system where an external fault was detected.
There will be no blocking if the differential current exceeds the set threshold
DIFF: Idiff>> PSx.
Overfluxing restraint
If the transformer is loaded with a voltage in excess of the nominal voltage, saturation
effects occur. Without stabilization, these could lead to differential protection tripping.
The fact that the current of the protected object under saturation conditions has a high
proportion of harmonics having five times the system frequency serves as the basis of
stabilization.
The P630C filters the differential current and determines the fundamental component
I(f0) and the fifth harmonic component I(5*f0). If the ratio I(5*f0) / I(f0) exceeds the set
value D I F F : O v e r I ( 5 f 0 ) / I ( f 0 ) P S x in at least one measuring system, and if the
restraining current is smaller than 4·Iref , then tripping is blocked selectively for one
measuring system.
There will be no blocking if the differential current exceeds the set threshold
DIFF: Idiff>> PSx.
In the P630C, two three-stage definite-time overcurrent protection functions (DTOC1 and
DTOC2) are implemented. For each DTOC function, a read-only parameter is provided
for the assignment to one of the transformer ends. The DTOC function will then monitor
the phase currents, the negative-sequence current and the residual current for the
selection. Function group DTOC1 will serve as an example to illustrate the operation of
the DTOC protection functions. Function group DTOC2 is equivalent.
Enabling or disabling
DTOC protection
DTOC protection can be disabled or enabled from the local control panel. Moreover,
enabling can be done separately for each parameter subset.
The first stage of the DTOC protection function can optionally be blocked by the inrush
stabilization function of differential protection.
Negative-sequence current
stages
The P630C calculates the negative-sequence current from the three phase currents
based on the formulas shown below. The rotary field direction setting is taken into
account.
a = e j120°
a 2 = e j240°
The first stage of the DTOC protection function can optionally be blocked by the inrush
stabilization function of differential protection.
These timer stages can be blocked by way of appropriately configured binary signal
inputs. Furthermore, the timer stages can – depending on the setting - be blocked
automatically for single-pole or multi-pole startings.
General starting
If the current exceeds one of the set thresholds of the phase current stages, a general
starting decision is issued. The user can select whether the starting of the residual
current stages should be taken into account in the general starting decision. The general
starting triggers a timer stage. Once this stage has elapsed, a signal is issued.
In the P630C, two three-stage inverse-time overcurrent protection functions (IDMT1 and
IDMT2) are implemented. For each IDMT function, a read-only parameter is provided for
the assignment to one of the transformer ends. The IDMT function will then monitor the
phase currents, the negative-sequence current and the residual current for the selection.
Function group IDMT1 will serve as an example to illustrate the operation of the IDMT
protection functions. Function group IDMT2 is equivalent.
Enabling or disabling
IDMT protection
IDMT protection can be disabled or enabled from the local control panel. Moreover,
enabling can be done separately for each parameter subset.
Time-dependent
characteristics
The measuring systems for the evaluation of the three phase currents, the negative-
sequence current and the residual current operate independently and can be set
separately. The user can select from a multitude of characteristics. The tripping
characteristics available for selection are shown in the Figures 3-77 to 3-80.
1000 1000
100 100
k=10
10 10 k=10
t/s k=1
t/s
1 1 k=1
k=0.1
0.1 k=0.05 0.1
k=0.1
k=0.05
0.01 0.01
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
I/Iref I/Iref
S8Z50K1A S8Z50K2A
Characteristic No. 1
Characteristic No. 2
1000 1000
100 100
k=10
10 10
k=1
t/s t/s
k=10
1 1
k=0.1
k=1 k=0.05
0.1 0.1
k=0.1
0.01 k=0.05 0.01
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
I/Iref I/Iref
S8Z50K3A S8Z50K4A
1000 1000
100 100
10 k=10 10
k=10
t/s t/s
1 k=1 1
k=1
I/Iref I/Iref
S8Z50K5C S8Z50K6C
1000
100
10
t/s
k=10
1
k=1
0.1
k=0.1
0.01 k=0.05
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
I/Iref
S8Z50K7C
Characteristic No. 7
1000 1000
100 100
10 10
t/s t/s
k=10
1 1
k=10
k=1
0.1 0.1
k=1
k=0.1 k=0.1
0.01 k=0.05 0.01 k=0.05
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
I/Iref I/Iref
S8Z50K8C S8Z50K9C
1000
100
k=10
10
t/s k=1
1
k=0.1
0.1 k=0.05
0.01
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
I/Iref
S8Z50KAC
Characteristic No. 10
1000 1000
100 100
k=10
k=10
10 10
t/s k=1 t/s
k=1
1 1
k=0.1
k=0.1
k=0.05
0.1 0.1 k=0.05
0.01 0.01
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
I/Iref I/Iref
S8Z50KBA S8Z50KCA
The IDMT protection function can optionally be blocked by the inrush stabilization
function of differential protection.
Negative-sequence current
stage
The P630C calculates the negative-sequence current from the three phase currents
based on the formulas shown below. The rotary field direction setting is taken into
account.
a = e j120°
a 2 = e j240°
The negative-sequence current is monitored by the P630C to detect when they exceed
the set thresholds. One of two different threshold types can be active. The “dynamic”
thresholds are active for the set hold time of the “dynamic parameters” (see “Activation
of Dynamic Parameters”); the “normal” thresholds are active when no hold time is
running. If the current exceeds the set thresholds in one phase, timer stages are started.
Once these stages have elapsed, a trip signal is issued. These timer stages can be
blocked by way of appropriately configured binary signal inputs.
The first stage of the IDMT protection function can optionally be blocked by the inrush
stabilization function of differential protection.
Holding time
The setting for the holding time defines the period for the IDMT starting time to be stored
after the starting has dropped out. If the starting time returns while the hold time elapses,
the new starting time is added to the stored time. If the sum of the starting times reaches
the tripping time determined by the P630C then the appropriate message is issued. If the
starting time does not return while the hold time elapses then the memory storing the
sum of the starting times will – in accordance with the setting - be cleared either without
delay or according to the set characteristic. The phase current stage serves as an
example to illustrate the effect of the holding time in Figure 3-84.
3-84 The effect of the holding time illustrated for the phase current stage as an example
Case A: The determined tripping time is not reached.
Case B: The determined tripping time is reached.
General starting
If 1.05 times the set reference current is exceeded in one phase, a general starting
decision is issued. The user can select whether the starting of the residual current stage
should be taken into account in the general starting decision. The general starting
triggers a timer stage. Once this stage has elapsed, a signal is issued.
Enabling or disabling
thermal overload protection
Thermal overload protection can be disabled or enabled from the local control panel.
Moreover, enabling can be carried out separately for each parameter set.
Tripping characteristics
The maximum phase current IP,max.y of the selected transformer end serves to track a
first-order thermal image according to IEC 255-8. The following parameters will govern
the tripping time:
The object temperature is calculated from the current IP,max.y and can be displayed at
T H R M 1 : O b j e c t t e m p e r a t . , T H 1 . For the coolant temperature a default temperature
value is used. The difference between the settings for the maximum permissible
temperatures of the protected object and the coolant can be displayed at T H R M 1 : O /T
f.Iref persist 1.
I
2
− ∆ϑ0
IB
t trip = τ ⋅ ln 2
I Θ a − Θ a,max
I − ∆ϑtrip ⋅ 1 −
B Θ max − Θ a,max
Figure 3-89 shows the tripping characteristics for ∆ϑ0 = 0 % and with identical settings
for the default of the updated measured coolant temperature and the maximum
permissible coolant temperature.
The setting for the operating mode selects an ‘absolute’ or ‘relative’ replica. If the setting
is for Absolute replica, the P630C will operate with a fixed trip threshold ∆ϑtrip of 100 %.
θtrip / %
10000
200
1000
110
τ/min
50
100
200
110
1000
10 50
t/min 200
1
110
50 30
0.1
0.01 1
0 1 2 3 4 5 6 7 8 9 10
0.001
I/Iref
D5Z50BEA
3-89 Tripping characteristic of thermal overload protection (tripping characteristics apply to ∆ϑ0 = 0 % and identical settings for the default of the
updated measured coolant temperature and the maximum permissible coolant temperature)
Warning
A warning signal is issued when the thermal load reaches the set warning level
T H R M 1 : R e l . O / T w a r n i n g P S x . Moreover, a pre-trip warning time can be
defined. The time difference between the warning time and the trip time is set at
THRM1: Warning pre-trip PSx.
If the current falls below the default threshold of 0.1 Iref, the buffer is discharged with the
set time constant T H R M 1 : T i m . c o n s t . 2 , < I b l P S x . The thermal replica may be
reset either from the local control panel or via an appropriately configured binary signal
input. Resetting is effective even when the thermal overload protection is disabled.
Thermal overload protection can be blocked via an appropriately configured binary signal
input.
In the P630C two measuring-circuit monitoring functions are implemented. For each
MCM function, a read-only parameter is provided for the assignment to one of the
transformer ends monitored by the P630C. Function group MCM_1 will serve as an
example to illustrate the operation of the MCM functions. Function group MCM_2 is
equivalent.
Enabling or disabling
measuring-circuit
monitoring
The measuring-circuit monitoring function can be disabled or enabled from the local
control panel. Moreover, enabling can be done separately for each parameter subset.
Measuring-circuit
monitoring
The ratio of negative- to positive-sequence current is used as the criterion for measuring-
circuit monitoring. The measuring-circuit monitoring function is triggered if the set ratio
Ineg / Ipos is exceeded and either the negative- or the positive-sequence current exceeds
0.02 Inom. After the set operate delay period has elapsed, a warning signal is issued.
In the P630C two limit value monitoring functions are implemented. For each LIMIT
function, a read-only parameter is provided for the assignment to one of the transformer
ends monitored by the P630C. Function group LIM_1 will serve as an example to
illustrate the operation of the MCM functions. Function group LIM_2 is equivalent.
Programmable (or user-configurable) logic enables the user to link binary signals within
a framework of Boolean equations.
Binary signals in the P630C can be linked by logical ‘OR’ or ‘AND’ operations or by
additional ‘NOT’ operations by setting L O G I C : F c t . a s s i g n m . o u t p . n , where
n = 1 to 32. The Boolean equations need to be defined without the use of brackets. The
following rule applies to the operators: ‘NOT’ before ‘AND’ before ‘OR’.
Intervention in the logical operations through the binary signal inputs can occur in
different ways. The binary input signals L O G I C : I n p u t n E X T (n = 1 to 16) have an
updating function, whereas the input signals L O G I C : S e t n E X T (n = 1 to 8) are
stored. The logic can only be controlled from the binary signal inputs that are configured
for L O G I C : S e t n E X T if the corresponding reset input (L O G I C : R e s e t
n E X T ) has also been configured for a binary signal input. If only one or neither of the
two functions is configured, then this is interpreted as ‘Logic externally set’. If the input
signals of the two binary signal inputs are implausible (such as when they both have a
logic value of ‘1’), then the last plausible state remains stored in memory.
3-96 Control of logic operations via setting parameters or stored input signals
3-97 Setting options for programmable logic (shown here for output 1)
The output signal of one equation can be processed as the input signal for another,
higher-order, equation and this makes it possible to have a sequence of interlinked
Boolean equations. The equations are processed in the sequence defined by the order
of each equation so that the end result of a sequence of interlinked Boolean equations is
given by the highest-order equation.
The output signal of each equation is fed to a separate timer stage with two timer
elements and a choice of operating modes. This offers the possibility of assigning a
freely configurable time characteristic to the output signal of each Boolean equation. In
the Minimum time operating mode, the setting of timer stage t2 has no effect. Figures
3-98 to 3-102 show the time characteristics for the various timer stage operating modes.
Note: If the unit is set to “off-line“, the equations are not processed and all outputs are
set to a logic value of '0'.
4 Design
The P630C is mounted in an aluminum case. Connection is via threaded terminal ends.
The case is suitable for either wall-surface mounting or flush panel-mounting. The
mounting brackets adjust for flush mounting.
Figures 4-1 and 4-2 show the case dimensions and mounting dimensions. A cover frame
is supplied for flush mounting (see Installation and Connection).
Regardless of model, the P630C – like all other device types in the MiCOM Px30 system
– is equipped with the standard local control panel. The local control panel is covered
with a tough film so that the specified degree of protection will be maintained. In addition
to the essential control and display elements, a parallel display consisting of a total of
17 LED indicators is also incorporated into the local control panel. The meaning of the
various LED indications is shown in plain text on a label strip.
!
The components located behind the front panel are energized. Therefore always turn off
the supply voltage before opening the device.
The processor module with the local control module is attached to the reverse side of the
removable front plate and connected to the combined I/O module via a ribbon cable. The
I/O module incorporates the power supply, the optional input transformers, the output
relays and optical couplers for binary input signals.
!
The secondary circuit of operating current transformers must not be opened. If the
secondary circuit of an operating current transformer is opened, there is the danger that
resulting voltages may injure personnel or damage the insulation.
The threaded terminal block for current transformer connection is not a shorting block.
Therefore always short-circuit the current transformer before loosening the threaded
terminals.
The front panel houses the -X6 serial interface for parameter setting by way of a PC. The
optional communication interfaces (-X7 and -X8 or -X9 and -X10) and the optional
IRIG-B input (-X11) are located on the underside of the case.
4-1 Dimensional drawing of the wall-mounting case (-X7 and -X8 or -X9 and -X10: optional communication interfaces; -X11: optional IRIG-B input;
-X31 and -X32 or -X33: optional guidance interface)
4-2 Dimensional drawing of the flush-mounting case (-X7 and -X8 or -X9 and -X10: optional communication interfaces; -X11: optional IRIG-B input;
-X31 and -X32 or -X33: optional guidance interface)
All P630C units are packaged separately in their own cartons and shipped inside outer
packaging. Use special care when opening cartons and unpacking units, and do not use
force. In addition, make sure to remove the supporting documents supplied with each
individual unit from the inside carton.
After unpacking each unit, inspect it visually to make sure it is in proper mechanical
condition.
If the P630C needs to be shipped, both inner and outer packaging must be used. If the
original packaging is no longer available, make sure that packaging conforms to
DIN ISO 2248 specifications for a drop height ≤ 0.8 m.
The nominal data and design version of the P630C can be determined by consulting the
type identification label. One type identification label is located next to the upper terminal
blocks. Another copy of the type identification label is affixed to the outside of the P630C
packaging.
The data shown on the type identification label include the nominal auxiliary voltage
VA,nom (‘UH,nom’) and the nominal input voltage Vin,nom (‘UE,nom’).
The P630C design version can be determined from the order number. A breakdown of
the order number is given in Chapter 14 of this manual and in the supporting documents
supplied with the unit.
The P630C has been designed to conform to EN 69255-6. Therefore it is important when
choosing the installation location to make sure that it provides the conditions specified in
the chapter entitled 'Technical Data'. Several important conditions are listed below.
Climatic conditions
Ambient temperature: -5 °C to +55 °C [+23 °F to +131 °F]
Relative humidity: The relative humidity must not result in the formation of
either condensed water or ice in the P630C.
Ambient air: The ambient air must not be significantly polluted by dust,
smoke, gases or vapors, or salt.
Mechanical conditions
Vibration stress: 10 to 60 Hz, 0.035 mm and 60 to 150 Hz, 0.5 g
Electromagnetic conditions
Appropriate measures taken in substations must correspond to the state of the art (see,
for example, the VDEW ring binder entitled "Schutztechnik" [Protective Systems],
Section 8, June 1992 edition, which includes recommended measures for reducing
transient overvoltage in secondary lines in high voltage substations).
5.4 Installation
The dimensions and mounting dimensions for surface-mounted cases are given in
Chapter 4. When the P630C is surface-mounted on a panel, the leads to the P630C are
normally run along the front side of the mounting plane. If the wiring is to be in back, an
opening can be provided above and below the surface-mounted case, as shown in
Figure 5-1 for the lower opening. The same applies analogously to the upper opening.
5-1 Opening for running the connecting leads to the surface-mounted case (dimensions in mm)
Holes for the grounding connection are located in the two mounting brackets of the
P630C. A ground connection assembly kit is supplied with the unit. The clamp bracket
(see Figure 5-4, “Pos. 3”) is marked with a PCT symbol:
The cross-sectional area of this ground conductor must conform to applicable national
standards. A minimum conductor cross section of 2.5 mm2 is required. The grounding
connection must be low-inductance, i.e., as short as possible.
This grounding procedure is also absolutely essential for proper operation of the device
and is thus equivalent to system grounding. Potentials that need to be grounded from an
operational standpoint are already suitably connected to the device ground inside the
unit.
5.6 Connection
The P630C must be connected in accordance with the terminal connection diagram
indicated on the type identification label. The terminal connection diagram is included in
the Supporting Documents supplied with the unit. The terminal connection diagrams that
apply to the P630C are also found in the appendix to this manual.
Copper leads having a 2.5-mm2 cross-section are generally suitable as the connecting
leads between the current transformers and the P630C. Under certain conditions the
connecting leads between the main current transformers and the P630C must be short
and have a larger cross-section in order to handle the allowable burden on the main
current transformers. Copper leads having a 1.5 mm2 cross section are adequate for
connecting the binary signal inputs, the signaling and triggering circuits, and the power
supply input.
All connections run into the system must always have a defined potential. Connections
that are pre-wired but not used should preferably be grounded when binary inputs and
output relays are isolated. When binary inputs and output relays are connected to
common potential, the pre-wired but unused connections should be connected to the
common potential of the grouped connections.
Power supply
Before connecting the auxiliary voltage VA for the P630C power supply, make sure that
the nominal value of the auxiliary device voltage agrees with the nominal value of the
auxiliary system voltage.
The P630C has an auxiliary voltage supply that can be switched between ranges and is
factory-set for the voltage range of VA,nom = 110 to 250 V DC or 100 to 230 V AC.
Before changing the auxiliary voltage range, turn off any connected auxiliary voltage.
The components located behind the front panel are energized!
! The ribbon cable plug connecting the local control module to the I / O module
! The ribbon cable plug connecting the local control module to the optional serial
communication interfaces (to optical fibers or to wires)
In the upper portion of the I / O module, between output relay and current input
transformers, are plug-in jumpers, which are plugged in a position depending on the
desired auxiliary voltage range.
5-5 Switching the auxiliary voltage supply. The factory-set jumper position is shown.
Current-measuring inputs
When connecting the system transformers, check to make sure that the secondary
nominal currents of the system and the unit agree.
The secondary circuit of operating current transformers must not be opened. If the
secondary circuit of an operating current transformer is opened, there is the danger that
the resulting voltages may injure personnel or damage the insulation.
The threaded terminal block for current transformer connection is not a shorting block.
Therefore always short-circuit current transformers before loosening the threaded
terminals.
The terminal connection diagrams give a polarity for connection of the binary signal
inputs. However, this is only a recommendation. Connection can be as desired.
B
C
X1 Current-measuring PC interface
inputs X/Y
1 IA T11 X6
2 2
D1[T]
3 IB T12 U16 D2[R]
3
4
5 IC T13 E2[C]
5
6
RS 232
Per order
OR wire link
a X//Y
X9
1
D2[R] 2
3
U19
X1 Power supply 4
D1[T] 5
b 13 (+) UH
14 (-) RS 485
PE U100 Comm. interface
Channel 2
wire link only
X1 Binary inputs X10
X//Y
1
15
UE D2[R] 2
U1
16 3
U20
17 4
UE U2
18 D1[T] 5
RS 485
X3 Output relays
IRIG-B
35 time synchronization X11
36 K1 1
U21
#
32
#
33
34
29
30 K2 Guidance interface
31
optical fiber link X31
27 1
U22 X/Y
28 K3
22 X32
26 K4 1
U23 X/Y
25 K5
24 K6
23 K7 OR wire link
19 X33
X//Y
20 K8 1
21 D2[R] 2
A B C 3
U24
4
D1[T] 5
P630C RS 485
PC interface
The PC interface is provided in order to operate the unit from a personal computer (PC).
!
The PC interface is not designed for permanent connection. Consequently, the female
connector does not have the extra insulation from circuits connected to the system that
is required per VDE 0106 Part 101.
Communication interfaces
Communication interfaces are provided for permanent connection of the unit to a control
system for substations or to a central substation unit. The unit is connected to
communication channel 1 either by a special connector with optical fibers or an RS 485
interface with twisted copper wires, depending on the type of communication interface.
Connection to channel 2 is always by way of an RS 485 interface.
The selection and assembly of a properly cut fiber-optic connecting cable requires
special knowledge and expertise and is therefore not covered in this operating manual.
!
The fiber-optic interface may only be connected or disconnected when the supply
voltage for the unit is shut off.
The RS 485 interface of the P630C is designed electrically to permit full-duplex operation
through a 4-wire connection. However, communication through the RS 485 interface is
always in the half-duplex mode of operation. The following connection instructions must
always be followed:
Always use twisted-pair shielded cables only, the kind used for telecommunications
systems.
At least one symmetrically twisted core pair will be required.
Strip cable cores and cable shield right at the connection point and connect properly
in accordance with specifications.
Ground all shields at both ends (large-area grounding).
Ground free (unshielded) cores at one end only.
As another option, a 2-wire or 4-wire connection is also possible. For the 4-wire
connection, a cable with two symmetrically twisted core pairs is required. Figure 5-7
shows the 2-wire connection and Figure 5-8 the 4-wire connection, as illustrated for
channel 2 of the communication module. If channel 1 of the communication module is
designed as an RS 485 interface, then the same arrangement would apply.
2-wire connection:
Transmitter and receiver must be bridged in all devices that have a full-duplex interface
as part of their electrical system – like the P630C, for example. In the two devices that
form the physical ends of the line, the pair of leads must be terminated by a
200-to-220-Ω resistor. In most Schneider Electric devices, and also in the P630C, a
220-Ω resistor is integrated into the RS 485 interface and can be connected by means of
a wire jumper. An external resistor is therefore not necessary.
4-wire connection:
Transmitter and receiver must be bridged in the device that forms one physical end of
the line. The receivers of the slaves that have a full-duplex interface as part of their
electrial system (like the P630C, for example) are connected to the transmitter of the
communication master, and the transmitters of the slaves are connected to the receiver
of the master. Devices that only have a half-duplex interface are connected to the
transmitter of the communication master. In the last physical participant (master or slave)
of the communication link, the transmitter and receiver must each be terminated by a
200-to-220-Ω resistor. In most Schneider Electric devices, and also in the P630C, a
220-Ω resistor is integrated into the RS 485 interface and can be connected by means of
a wire jumper. An external resistor is therefore not necessary. The second resistor must
be connected to the device externally (see Chapter 13 for the resistor Order No.).
P630C
P630C
P630C
P630C
Control through the PC interface is also possible. This requires a suitable PC and
operating program (S&R-103).
TRIP
ALARM
C
OUT OF SERVICE G
HEALTHY
EDIT MODE
G
G
G
C CLEAR
READ
ENTER
F1
F2
F3
F4
Display levels
All data relevant for operation and all device settings are displayed on two levels. At the
Panel level, data such as measured operating data are displayed in Panels that provide
a quick overview of the current state of the bay. The menu tree level below the Panel
level allows the user to select all data points (settings, signals, measured variables, etc.)
and to change them, if appropriate. The user can access a selected event recording
(event log) from either the Panel level or from any other point in the menu tree, by
pressing the READ key .
Display Panels
The P630C can display 'Measured Value Panels' which are called up by the device
according to system conditions.
Selected measured values are displayed on the Measured Value Panels. The system
condition determines which Panel is called up (examples are the Operation Panel and
the Fault Panel). Only the Measured Value Panels relevant for the design version of the
given unit and its associated range of functions are actually available. The Operation
Panel is always available.
Keys
! ‘Up’ and ‘Down’ Keys /
Panel Level:
Press the ‘Up’ and ‘Down’ keys to switch between the pages of the Measured Value
Panel.
Menu Tree Level:
Press the ‘Up’ and ‘Down’ keys to navigate up and down through the menu tree in a
vertical direction. If the unit is in input mode, the ‘Up’ and ‘Down’ keys have a different
function.
Input mode:
Parameter values can only be changed in the input mode, which is signaled by the
LED indicator labeled EDIT MODE. Press the ‘Up’ and ‘Down’ keys in this mode to
change the parameter value.
(‘Up’ key: the next higher value is selected.
‘Down’ key: the next lower value is selected.)
With list parameters, press the ‘Up’ and ‘Down’ key to change the logic operator of
the value element.
! ENTER Key
Panel Level:
Press the ENTER key at the Panel level to go to the menu tree.
Menu Tree Level:
Press the ENTER key to enter the input mode. Press the ENTER key a second time
to accept the changes as entered and exit the input mode. The LED indicator labeled
EDIT MODE signals that the input mode is active.
! CLEAR Key C
Press the CLEAR key to reset the LED indicators and clear all measured event data.
The records in the recording memories are not affected by this action.
Input mode:
Press the CLEAR key to reject the changes entered and exit the input mode.
! READ Key
Press the READ key to access the set of user-selected functions (see "Configurable
Function Keys" in Chapter 3) from either the Panel level or from any other point in the
menu tree. Repeated pressing of the READ key will then sequentially trigger the
selected functions (such as event recordings or setting parameters) if several
functions have been selected.
! Function Keys F1 to Fx
A single function or a menu jump list can be assigned to each function key (see
"Configurable Function Keys" in Chapter 3). Once a menu jump list has been
assigned to a function key, then repeated pressing of the function key will
sequentially trigger the selected functions.
The following tables, which show the individual control steps, specify the displays that
can be changed by pressing specific keys. A small black square to the right of the
ENTER key indicates that the LED indicator labeled EDIT MODE is on. The examples
shown here do not necessarily apply to the device type described in this manual; they
merely serve to illustrate the control principles involved.
If none of the control keys is pressed, the display illumination will switch off once the set
return time has elapsed (‘return time illumination’ setting in the menu tree at
‘Par/Conf/LOC’). The display illumination is turned on again by pressing one of the
control keys. In this case, the control action that is normally triggered by the key will not
be executed. This response is also exhibited by the function keys. Reactivation of
display illumination is also possible by way of a binary input.
If continuous illumination is desired, the user can set the ‘return time illumination’
function to ‘blocked’.
In the following example, the password for the function keys is the factory-set password.
If the password has been changed by the user (see the section entitled 'Changing the
Password'), the following description will apply analogously.
‘Right’
‘Up’
‘Down’
The display will change as shown in the
column on the right. *
2b Until the enter key is pressed, the control C Voltage C-A prim.
20.8 kV
action can be aborted at any time by pressing Current A prim.
the CLEAR key. 415 A
1 First press the ‘Up’ key and hold it down + C Voltage C-A prim.
20.8 kV
while pressing the CLEAR key. Current A prim.
415 A
Note:
It is important to press the ‘Up’ key first and
release it last to avoid unintentional resetting of
stored data.
Going from the Panel level to
the menu tree level 0 Example of a Measured Value Panel. Voltage C-A prim.
20.8 kV
Current A prim.
415 A
After the set return time has elapsed (setting in menu tree: 'Par/Conf/LOC'), the display
will automatically switch to the Panel level if a Measured Value Panel has been
configured.
The measured values to be displayed on the Measured Value Panels can first be
selected at ‘Par/Conf/LOC’ in the menu tree. The user can select different sets of
measured values for the Operation Panel, the Overload Panel, the Ground Fault Panel,
and the Fault Panel. Only the Measured Value Panels relevant for the design version of
the given unit and its associated range of functions are actually available. The selected
set of values for the Operation Panel is always available. Please see the section entitled
‘Setting a List Parameter’ for instructions regarding selection. If the user has selected
M A I N : W i t h o u t f u n c t i o n for a Panel, then that Panel will be inactive.
The Measured Value Panels are called up in accordance with system conditions. If, for
example, the unit detects an overload or a ground fault, then the corresponding
Measured Value Panel will be displayed as long as the overload or ground fault situation
exists. If the unit detects a fault, then the Fault Panel is displayed and remains active
until the measured fault values are reset – by pressing the CLEAR key C , for example.
At the root of the menu tree is the unit type; the tree branches into the three main folders
‘Parameters’, ‘Operation’ and ‘Events’, which form the first folder level. Up to two further
folder levels follow so that the entire folder structure consists of three main branches and
a maximum of three folder levels.
At the end of each branch of folders are the various function groups in which the
individual data points are combined.
PX yyy
Unit
type
Oper/
Folder Cyclic measurements
level 2
Oper/Cycl/
Folder Meas. operating data
level 3
Oper/Cycl/Data/
Function MAIN
groups
Oper/Cycl/Data/MAIN
Data Date
points 01.01.99 dd.mm.yy
The display on the local control panel can be switched between address mode and plain
text mode. In the address mode the display shows setting parameters, signals, and
measured values in numerically coded form, that is, as addresses. In plain text mode the
setting parameters, signals, and measured values are displayed in the form of plain text
descriptions. In either case, control is guided by the menu tree. The active branch of the
menu tree is displayed in plain text in both modes. In the following examples, the display
is shown in plain text mode only.
Although it is possible to select any data point in the menu tree and read the associated
value by pressing the keys, it is not possible to switch directly to the input mode. This
safeguard prevents unintended changes in the settings.
‘Right’ Oper/CtrlTest/LOC
Param. change enabl.
No
*
‘Up’ Oper/CtrlTest/LOC
Param. change enabl.
No
*
‘Down’ Oper/CtrlTest/LOC
Param. change enabl.
The display will change as shown in the No
column on the right. *
The same procedure applies to any parameter change unless the global change-
enabling function has been activated. This method is recommended for a single
parameter change only. If several settings are to be changed, then the global change-
enabling function is preferable. In the following examples, the global change-enabling
function has been activated.
Automatic return
The automatic return function prevents the change-enabling function from remaining
activated after a change of settings has been completed. Once the set return time (menu
tree ‘Par/Conf/LOC’) has elapsed, the change-enabling function is automatically
deactivated, and the display switches to a Measured Value Panel corresponding to the
current system condition. The return time is restarted when any of the control keys is
pressed.
Forced return
The return described above can be forced from the local control panel by first pressing
the ‘Up’ key and then holding it down while pressing the CLEAR key.
Note: It is important to press the ‘Up’ key first and release it last in order to avoid
unintentional deletion of stored data.
Even when the change-enabling function is activated, not all parameters can be
changed. For some settings it is also necessary to disable the protective function (menu
tree: Par/Func/Glob/MAIN, 'Protection enabled'). Such settings include the configuration
parameters, by means of which the device interfaces can be adapted to the system. The
following entries in the ”Change” column of the address list (see appendix) indicate
whether values can be changed or not:
! "on": The value can be changed even when the protective function is enabled.
! "off": The value can only be changed when the protective function is disabled.
! "-": The value can be read out but cannot be changed.
The device is factory-set so that the protective function is disabled.
If all the conditions for a value change are satisfied (see above), the desired setting can
be entered.
Using list parameters, the user is able to select several elements from a list in order to
perform tasks such as defining a trip command or defining the measured values that will
be displayed on Measured Value Panels. The maximum possible number ’m’ that can be
selected out of the total number ’n’ of the set is given in the address list in the ’Remarks’
column. As a rule, the selected elements are linked by an ‘OR’ operator. Other operators
(NOT, OR, AND, NOT OR and NOT AND) are available in the LOGIC function group for
linking the selected list items. In this way binary signals and binary input signals can be
processed in a Boolean equation tailored to meet user requirements. For the DNP 3.0
communication protocol, the user defines the class of a parameter instead of assigning
operators. The definition of a trip command shall be used here as an example to
illustrate the setting of a list parameter.
7 Press the ‘Up’ key to exit the list at any point Par/Func/Glob/MAIN
Fct.assign.trip cmd.
in the list.
After a memory is entered, the memory can be read out at the entry point. It is not
necessary to activate the change-enabling function or even to disable the protective
functions. Inadvertent clearing of a memory at the entry point is not possible.
Not all of these event memories are present in each unit. A given unit may contain only
some of them or even none at all, depending on the device type.
1 Press the ‘Down’ key to enter the monitoring Mon. signal record.
01.01.97 13:33 SFMON
signal memory. The oldest entry is displayed. Checksum error param
3 Press the ‘Left’ key to display the previous Mon. signal record.
01.01.97 13:33 SFMON
entry. Checksum error param
6.6.7 Resetting
All information memories – including the event memories and the monitoring signal
memory – as well as the LED indicators can be reset manually. In addition, the LED
indicators are automatically cleared and initialized at the onset of a new fault – provided
that the appropriate operating mode has been selected – so that they always indicate the
latest fault.
The LED indicators can also be reset manually by pressing the CLEAR key, which is
always possible in the standard control mode. This action also triggers an LED indicator
test and an LCD display test. The event memories are not affected by this action, so that
inadvertent deletion of the records associated with the reset signal pattern is reliably
prevented.
Because of the ring structure of the event memories, the data for eight consecutive
events are updated automatically so that manual resetting should not be necessary, in
principle. If the event memories need to be cleared completely, however, as would be
the case after functional testing, this can be done after selecting the appropriate
parameter. The resetting procedure will now be illustrated using the fault memory as an
example. In this example the global change-enabling function has already been
activated.
Certain actions from the local control panel (such as a manual trip command for testing
purposes) can only be carried out by entering a password. This setup is designed to
prevent accidental output and applies even when the global change-enabling function
has been activated.
‘Right’ Oper/CtrlTest/MAIN
Man. trip cmd. USER
Don't execute
*
‘Up’ Oper/CtrlTest/MAIN
Man. trip cmd. USER
Don't execute
*
‘Down’ Oper/CtrlTest/MAIN
Man. trip cmd USER
The display will change as shown in the Don't execute
column on the right. *
The password consists of a combination of keys that must be entered sequentially within
a specific time interval. The ‘Left’, ’Right’, ‘Up’ and ‘Down’ keys may be used to define
the password and represent the numbers 1, 2, 3 and 4, respectively:
1 2
The password can be changed by the user at any time. The procedure for this change is
described below. The starting point is the factory-set password.
Par/Conf/LOC
Password
********
*
Par/Conf/LOC
Password
********
*
Par/Conf/LOC
Password
**
Par/Conf/LOC
Password
**
**
Operation from the local control panel without password protection is also possible. To
select this option, immediately press the ENTER key a second time in steps 4 and 6
without entering anything else. This will configure the local control panel without
password protection, and no control actions involving changes will be possible until the
global change-enabling function has been activated (see the section entitled ‘Change-
Enabling Function’).
If the configured password has been forgotten, it can be called up on the LCD display as
described below. The procedure involves turning the device off and then on again.
7 Settings
The P630C must be adjusted to the system and to the protected equipment by means of
appropriate settings. This section gives instructions for determining the settings, which
are located in the folder entitled ‘Parameters’ in the menu tree. The sequence in which
the settings are listed and described in this chapter corresponds to their sequence in the
menu tree. The 'Address List' in the Appendix lists all parameters, along with setting
ranges and incrementation or selection tables.
The units are supplied with a factory-set configuration of settings that in most cases
correspond to the default settings given in the Address List. If the factory settings differ
from the default settings, then this is indicated below at the appropriate points.
The default settings given in the Address List are activated after a cold restart. The
P630C is blocked in that case. All settings must be re-entered after a cold restart.
The device identification settings are used to record the ordering information and the
design version of the P630C. They have no effect on the device functions. These
settings should only be changed if the design version of the P630C is modified.
Identification of the change level of the texts of the data model. This display
cannot be altered.
DVICE: Text vers.data model 002 121
Using the ‘text replacement tool’ provided by the operating program, the
user can change the parameter descriptors (plain text designations) and
load them into the device. These customized data models contain an
identifier defined by the user while preparing the data model. This identifier
is displayed at this point in the menu tree. Standard data models have the
identifier ‘0’ (factory-set default).
DVICE: F number 002 124
The F number is the serial number of the device. This display cannot be
altered.
DVICE: Order No. 000 001
Order number of the device. This number cannot be altered by the user.
Item number of the module inserted in the respective slot. The display
always shows the actual component configuration at any given time.
DVICE: Module vers. slot 1 086 193
Index letter specifying the version of the module inserted in the respective
slot.
DVICE: Variant of module A 086 047
Set your numerically coded user data here for your records.
DVICE: Device ID 000 035
The password to be used for changing settings from the local control panel
can be defined here. Further information on changing the password is
given in Chapter 6.
LOC: Fct. read key 080 110
Compilation of functions for the two menu jump lists. One of these menu
jump lists can be assigned to a function key by selecting the en tr y L OC :
Trig. menu jmp x EXT (x: 1 or 2) at F_KEY: Fc t. ass ignm. Fx
(Fx: F1, F2, F3 or F4). Up to 16 functions can be selected as described for
L OC : Fc t. re ad ke y. Repeated pressing (in this case of the assigned
function key rather than the read key) will then sequentially trigger the
selected functions.
LOC: Fct. Operation Panel 053 007 Fig. 3-2
Setting for the time period for which a panel is displayed before the unit
switches to the next panel. This setting is only relevant if more values are
selected for display than can be shown on the LCD display.
LOC: Autom. return time 003 014 Fig. 3-2
If the user does not press a key on the local control panel during this set
time period, the change-enabling function is deactivated.
LOC: Return time illumin. 003 023
If the user does not press a key on the local control panel during this set
time period, then the backlighting of the LCD display is switched off.
Set the same parity that is set at the interface of the PC connected to the
P630C.
PC: Spontan. sig. enable 003 187 Fig. 3-5
Enable for the cyclic transmission of measured values via the PC interface.
PC: Cycl. data ILS tel. 003 185 Fig. 3-5
All measured data are transmitted again through the PC interface after this
time period has elapsed – provided that transmission has not been triggered
by the other delta conditions.
PC: Time-out 003 188 Fig. 3-5
Setting for the time to elapse after the last telegram exchange via the PC
interface before activating the second communication channel of
communication module A.
Enabling additional settings that are relevant for the protocol based on
IEC 870-5-101.
COMM1: Addit. ILS enable 003 217 Fig. 3-6
Enabling additional settings that are relevant for the ILS protocol.
COMM1: MODBUS enable 003 220 Fig. 3-6
Select the communication protocol that shall be used for the communication
interface.
COMM1: MODBUS prot. variant 003 214 Fig. 3-10
In the DNP 3.0 protocol, a 16 bit address is used to identify devices. The
address that can be set here is the higher-order octet, whereas the address
set at C O M M 1 : O c t e t c o m m . a d d r e s s is the lower-order octet of
the DNP address.
Note: This setting is hidden unless the DNP 3.0 protocol is enabled.
COMM1: Test monitor on 003 166 Fig. 3-7,
3-8, 3-9,
3-10, 3-11,
3-12
Setting specifying whether data shall be recorded for service activities.
COMM1: Name of manufacturer 003 161 Fig. 3-7,
3-8, 3-9
Setting for the name of the manufacturer (to ensure compatibility).
Note: This setting is hidden unless an IEC 870-5 protocol is enabled.
Setting for the length of the common address for identification of telegram
structures.
Note:
This setting is hidden unless the IEC 870-5-101 protocol is set.
"ASDU": Application Service Data Unit
COMM1: Octet 2 addr. ASDU 003 194 Fig. 3-8
Setting for the length of the common higher-order address for identification
of telegram structures.
Note:
This setting is hidden unless the IEC 870-5-101 protocol is set.
"ASDU": Application Service Data Unit
Setting for the length of the higher-order address for information objects.
Note: This setting is hidden unless the IEC 870-5-101 protocol is set.
COMM1: Inf.No.<->funct.type 003 195 Fig. 3-8
Setting for the transmission direction. Normally this value will be set at '1' at
the control center and at '0' at the substation.
Note: This setting is hidden unless the IEC 870-5-101 protocol is set.
COMM1: Time-out interval 003 228 Fig. 3-8
Setting for the maximum time that will elapse until the status signal for the
acknowledgment command is issued.
Note: This setting is hidden unless the IEC 870-5-101 protocol is set.
COMM1: Reg.asg. selec. cmds 003 210 Fig. 3-10
Number of bits that must pass between the receipt of the 'request' and the
start of sending the 'response'.
Note: This setting is hidden unless the DNP 3.0 protocol is enabled.
COMM1: Phys. Char. Timeout 003 242 Fig. 3-11
Number of bits that may be missing from the telegram before receipt is
terminated.
Note: This setting is hidden unless the DNP 3.0 protocol is enabled.
COMM1: Link Confirm. Mode 003 243 Fig. 3-11
Setting for the time period within which the master must acknowledge at the
link layer.
Note: This setting is hidden unless the DNP 3.0 protocol is enabled.
COMM1: Link Max. Retries 003 245 Fig. 3-11
Number of repetitions that are carried out on the link layer if errors have
occurred during transmission (such as failure to acknowledge).
Note: This setting is hidden unless the DNP 3.0 protocol is enabled.
COMM1: Appl.Confirm.Timeout 003 246 Fig. 3-11
Setting for the time period within which the master must acknowledge at the
application layer.
Note: This setting is hidden unless the DNP 3.0 protocol is enabled.
COMM1: Appl. Need Time Del. 003 247 Fig. 3-11
Time interval within which the slave requests time synchronization cyclically
from the master.
Note: This setting is hidden unless the DNP 3.0 protocol is enabled.
Selection of data points and data classes for object 1 – binary inputs.
Assignment of indices is made in the order of selection, beginning with 0.
Note: This setting is hidden unless the DNP 3.0 protocol is enabled.
COMM1: Ind./cl. bin.outputs 003 233 Fig. 3-11
Selection of data points and data classes for object 10 – binary outputs.
Assignment of indices is made in the order of selection, beginning with 0.
Note: This setting is hidden unless the DNP 3.0 protocol is enabled.
COMM1: Ind./cl. analog inp. 003 235 Fig. 3-11
Selection of data points and data classes for object 30 – analog inputs.
Assignment of indices is made in the order of selection, beginning with 0.
Note: This setting is hidden unless the DNP 3.0 protocol is enabled.
COMM1: Ind./cl. analog outp 003 236 Fig. 3-11
Selection of data points and data classes for object 40 – analog outputs.
Assignment of indices is made in the order of selection, beginning with 0.
Note: This setting is hidden unless the DNP 3.0 protocol is enabled.
COMM1: Delta meas.v. (DNP3) 003 250 Fig. 3-11
Set the same parity that is set at the interface of the control system
connected to the P630C.
COMM2: Dead time monitoring 103 176 Fig. 3-14
The time between two polling calls from the communication master must be
less than the time set here.
COMM2: Octet comm. address 103 072 Fig. 3-14
The communication address and the ASDU address are used to identify the
device in communication via the interface. An identical setting must be
selected for both addresses.
"ASDU": Application Service Data Unit
COMM2: Name of manufacturer 103 161 Fig. 3-14
The communication address and the ASDU address are used to identify the
device in communication via the interface. An identical setting must be
selected for both addresses.
"ASDU": Application Service Data Unit
COMM2: Spontan. sig. enable 103 177 Fig. 3-14
Adjustment of the baud rate for telegram transmission via the guidance
interface (InterMiCOM interface) so as to meet the requirements of the
transmission carrier.
COMM3: Source address 120 031
This timer triggers the alarm signals CO MM 3 : Com mu nic a ti ons fau l t
and SFM ON : Co mm un ic .fa ul t CO MM 3 and sets the received signals
to their user-defined default values. Time-out occurs when the set time has
elapsed since the most recent 100% valid telegram was received.
COMM3: Time-out link fail. 120 035
Once the password has been entered, the function keys remain active for
no longer than this time. Thereafter, the function keys are disabled until the
password is entered again.
Binary inputs
The P630C has optical coupler inputs for processing binary signals from the substation.
The number and connection schemes for the available binary inputs are shown in the
terminal connection diagrams. The Address List in the Appendix gives information about
the configuration options for all binary inputs.
When configuring binary inputs, one should keep in mind that the same function can be
assigned to several signal inputs. Thus one function can be activated from several
control points having different signal voltages.
In order to ensure that the device will recognize the input signals, the triggering signals
must persist for at least 30 ms.
The operating mode for each binary signal input can be defined. The user can specify
whether the presence (active ‘high’ mode) or absence (active ‘low’ mode) of a voltage
shall be interpreted as the logic ‘1’ signal.
Binary outputs
The P630C has output relays for the output of binary signals. The number and
connection schemes for the available output relays are shown in the terminal connection
diagrams. The Address List in the Appendix gives information about the configuration
options for all binary outputs.
The contact data for the all-or-nothing relays permits them to be used either as
command relays or as signal relays. One signal can also be assigned to several output
relays simultaneously for the purpose of contact multiplication.
An operating mode can be defined for each output relay. Depending on the selected
operating mode, the output relay will operate in either an energize-on-signal (ES) mode
or a normally-energized (NE) mode and in either a latching or non-latching mode. For
output relays operating in latching mode, the operating mode setting also determines
when latching will be canceled.
Note: For relays with make contacts, the energize-on-signal (ES) mode
corresponds to normally-open operation. The normally-energized (NE) mode
means that the polarity of the driving signal is inverted, such that a logic "0"
maintains the relay normally-closed. For relays with changeover contacts,
these more common descriptions are not applicable.
LED indicators
The P630C has a total of 17 LED indicators for parallel display of binary signals. The
Address List in the Appendix gives information about the configuration options for all
LED indicators. The following table provides an overview.
H2 ‘OUT OF SERVICE’ Permanently assigned to the function M AIN : Blocke d /fau l ty.
H3 ‘ALARM’ Permanently assigned to the function SF MON : Wa rn ing ( L ED) .
H 5 to H 16 ---- The user has the option of assigning functions to these LED indicators.
The arrangement of the LED indicators on the local control panel is illustrated in the
dimensional drawings of Chapter 4.
An operating mode can be defined for each LED indicator. Depending on the selected
operating mode, the output relay will operate in either energize-on-signal (ES) mode or
normally-energized (NE) mode and in either latching or non-latching mode. For LED
indicators operating in latching mode, the operating mode setting also determines when
latching will be canceled.
Note: For relays with make contacts, the energize-on-signal (ES) mode
corresponds to normally-open operation. The normally-energized (NE) mode
means that the polarity of the driving signal is inverted, such that a logic "0"
maintains the relay normally-closed. For relays with changeover contacts,
these more common descriptions are not applicable.
The user specifies the channel on which each physical variable is recorded.
Canceling protection
functions
By means of a configuration procedure, the user can adapt the device functions flexibly
to the scope of protection functions required in each particular h.v. system.
The following conditions must be met before a protection function can be canceled:
7.3.1 Global
"Logical" communication COMM1: Command block. USER 003 172 Fig. 3-6
interface 1 When command blocking is activated, commands are rejected at
communication interface 1.
COMM1: Sig./meas.block.USER 003 076 Fig. 3-7,
3-8, 3-9
When signal and measured value blocking is activated, no signals or
measured data are transmitted through communication interface 1.
"Logical" communication COMM2: Command block. USER 103 172 Fig. 3-14
interface 2 When command blocking is activated, commands are rejected at
communication interface 2.
COMM2: Sig./meas.block.USER 103 076 Fig. 3-14
When the test mode is activated, signals or measured data for PC and
communication interfaces are labeled ‘test mode’.
MAIN: Nominal frequ. fnom 010 030
Setting for the primary nominal current of the main current transformer
(phase currents) of end a or b.
Setting for the nominal current of the device for the measurement of the
phase currents of ends a or b.
MAIN: Conn.meas.circ. IP,a 010 140
Setting for the minimum current that must be exceeded in order for the
measured operating values of the phase currents to be displayed.
MAIN: Meas. value rel. IN 011 031 Fig. 3-27
Setting for the minimum current that must be exceeded in order for the
measured operating value of the residual current to be displayed.
MAIN: Settl. t. IP,max,del 010 113 Fig. 3-25
Setting for the time after which the delayed maximum current display shall
reach 95% of the maximum current IP,max.
MAIN: Fct.assign. block. 1 021 021 Fig. 3-32
Parameter subset selection PSS: Control via USER 003 100 Fig. 3-41
The setting of this timer stage is relevant only if parameter subset selection
is carried out via the binary signal inputs. Any voltage-free pause that may
occur during selection is bridged. If, after this time period has elapsed, no
binary signal input has yet been set, then the parameter subset selected
from the local control panel shall apply.
This setting defines the monitoring signals that will be entered in the
monitoring signal memory. Signals resulting from internal device faults are
not configurable and always result in a warning.
Fault recording FT_RC: Fct. assig. trigger 003 085 Fig. 3-53
This setting defines the signals that will trigger fault recording.
FT_RC: Id> 016 018 Fig. 3-53
This setting defines the threshold value of the differential current that will
trigger fault recording.
FT_RC: IR> 016 019 Fig. 3-53
This setting defines the threshold value of the restraining current that will
trigger fault recording.
FT_RC: Pre-fault time 003 078 Fig. 3-55
Setting for the time during which data will be recorded before the onset of a
fault (pre-fault recording time).
FT_RC: Post-fault time 003 079 Fig. 3-55
Setting for the time during which data will be recorded after the end of a
fault (post-fault recording time).
FT_RC: Max. recording time 003 075 Fig. 3-55
Setting for the maximum recording time per fault. This includes pre-fault
and post-fault recording times.
Main functions MAIN: Vnom prim., end a 019 017 Fig. 3-57
Setting for the hold time of the “dynamic parameters”. During this period, the
„dynamic“ thresholds are active in place of the “normal“ thresholds.
Differential protection DIFF: General enable USER 019 080 Fig. 3-56
Setting for the reference power, usually the nominal transformer power.
DIFF: Ref. curr. Iref,a 019 023 Fig. 3-57
For standard connection of the P630C (see Chapter 5), the vector group ID
needs to be entered. For connection reversal applied to one individual end,
this can be taken into account in setting. The following algorithms apply:
Setting = ID + 6
If the addition results in a value > 12 then:
Setting = (ID + 6) – 12
If the phase currents of the low and high voltage sides are exchanged and if
this is not accounted for by the settings at M AIN : C on n .m eas ,c irc .
IP,z (where z is end a or b) a nd M AIN : Co nn .me as ,ci rc. IY,z
(where z is end a,b or c) then the algorithm is:
Setting = 12 – ID
If an anti-clockwise rotating field is present then this should be entered as a
setting at the P630C. In this case, the P630C will automatically form the
complementary value of the set vector group ID to the number 12 (vector
group ID = 12 – set ID).
For application of the P630C as machine protection, the setting must be 0
or 6 depending on the current transformer connection.
Setting for the minimum differential current that must be exceeded in order
for the P630C to display the differential currents as measured operating
data.
DIFF: Meas. value rel. IR 011 038 Fig. 3-67
Setting for the minimum restraining current that must be exceeded in order
for the P630C to display the restraining currents as measured operating
data.
Definite-time overcurrent DTOC1: General enable USER 031 135 Fig. 3-69
protection DTOC2: General enable USER 031 136
Inverse-time overcurrent IDMT1: General enable USER 031 141 Fig. 3-76
protection IDMT2: General enable USER 031 142
Thermal overload THRM1: General enable USER 031 144 Fig. 3-88
protection Disabling and enabling the thermal overload protection function.
THRM1: Select. meas. input 019 109 Fig. 3-87
Display of the difference between the settings for the maximum permissible
temperatures of the protected object and the coolant.
Limit value monitoring LIM_1: General enable USER 014 014 Fig. 3-95
LIM_2: General enable USER 014 015
These settings define the static input conditions for the logic function.
These settings define the operating modes for the output timer stages.
These settings assign the function of a binary input signal to the output of
the logic equation.
These settings assign the function of a binary input signal to the output of
the logic equation.
Differential protection DIFF: Enable PSx 072 152 073 152 074 152 075 152 Fig. 3-56
This setting defines the second knee of the tripping characteristic. Above
this knee, the gradient is m2.
DIFF: Op.mode harm.bl. PSx 072 148 073 148 074 148 075 148 Fig. 3-63
Setting for the operating mode of the inrush stabilization function (harmonic
blocking or harmonic restraint).
For application of the P630C as machine protection, the harmonic restraint
can be deactivated by way of this setting.
For application of the P630C as transformer protection, the user can select
whether the harmonic restraint should operate in cross-blocking mode or
selectively for one measuring system.
DIFF: RushI(2f0)/I(f0) PSx 072 159 073 159 074 159 075 159 Fig. 3-64
DIFF: Overflux.bl. en. PSx 072 158 073 158 074 158 075 158 Fig. 3-66
Setting for the delay time of the trip command of differential protection.
DIFF: Hyst. effective PSx 072 006 073 006 074 006 075 006
Definite-time overcurrent DTOC1: Enable PSx 076 050 077 050 078 050 079 050 Fig. 3-69
protection DTOC2: Enable PSx 076 070 077 070 078 070 079 070
This setting defines whether blocking of the residual current stages will take
place for single-pole or multi-pole phase current starting.
DTOC1: Gen.starting modePSx 076 066 077 066 078 066 079 066 Fig. 3-73
DTOC2: Gen.starting modePSx 076 086 077 086 078 086 079 086
This setting defines whether starting of the residual current stages will
involved in the formation of the general starting signal of DTOC protection.
DTOC1: tGS PSx 076 065 077 065 078 065 079 065 Fig. 3-73
DTOC2: tGS PSx 076 085 077 085 078 085 079 085
Setting for the operate delay of the general starting signal of DTOC
protection.
DTOC1: Rush restr.enabl PSx 076 063 077 063 078 063 079 063 Fig. 3-70,
3-71
DTOC2: Rush restr.enabl PSx 076 083 077 083 078 083 079 083
DTOC1: I> dynamic PSx 076 151 077 151 078 151 079 151 Fig. 3-70
DTOC2: I> dynamic PSx 076 161 077 161 078 161 079 161
Setting for the operate value I> in dynamic mode. This operate value is only
effective while the hold time for dynamic parameters is elapsing.
DTOC1: I>> dynamic PSx 076 152 077 152 078 152 079 152 Fig. 3-70
DTOC2: I>> dynamic PSx 076 162 077 162 078 162 079 162
Setting for the operate value I>> in dynamic mode. This operate value is
only effective while the hold time for dynamic parameters is elapsing.
DTOC1: I>>> dynamic PSx 076 153 077 153 078 153 079 153 Fig. 3-70
DTOC2: I>>> dynamic PSx 076 173 077 173 078 173 079 173
Setting for the operate value I>>> in dynamic mode. This operate value is
only effective while the hold time for dynamic parameters is elapsing.
DTOC1: tI> PSx 076 057 077 057 078 057 079 057 Fig. 3-70
DTOC2: tI> PSx 076 077 077 077 078 077 079 077
Setting for the operate value of the Ineg> stage in dynamic mode. This
operate value is only effective while the hold time for dynamic parameters is
elapsing.
DTOC1: Ineg>> dynamic PSx 076 201 077 201 078 201 079 201 Fig. 3-71
DTOC2: Ineg>> dynamic PSx 076 211 077 211 078 211 079 211
Setting for the operate value of the Ineg>> stage in dynamic mode. This
operate value is only effective while the hold time for dynamic parameters is
elapsing.
DTOC1: Ineg>>> dynamic PSx 076 202 077 202 078 202 079 202 Fig. 3-71
DTOC2: Ineg>>> dynamic PSx 076 212 077 212 078 212 079 212
Setting for the operate value of the Ineg>>> stage in dynamic mode. This
operate value is only effective while the hold time for dynamic parameters is
elapsing.
DTOC1: tIneg> PSx 076 203 077 203 078 203 079 203 Fig. 3-71
DTOC2: tIneg> PSx 076 213 077 213 078 213 079 213
Setting for the operate value IN> in dynamic mode. This operate value is
only effective while the hold time for dynamic parameters is elapsing.
DTOC1: IN>> dynamic PSx 076 155 077 155 078 155 079 155 Fig. 3-72
DTOC2: IN>> dynamic PSx 076 175 077 175 078 175 079 175
Setting for the operate value IN>> in dynamic mode. This operate value is
only effective while the hold time for dynamic parameters is elapsing.
DTOC1: IN>>> dynamic PSx 076 156 077 156 078 156 079 156 Fig. 3-72
DTOC2: IN>>> dynamic PSx 076 176 077 176 078 176 079 176
Setting for the operate value IN>>> in dynamic mode. This operate value is
only effective while the hold time for dynamic parameters is elapsing.
DTOC1: tIN> PSx 076 060 077 060 078 060 079 060 Fig. 3-72
DTOC2: tIN> PSx 076 170 077 170 078 170 079 170
Inverse-time overcurrent IDMT1: Enable PSx 081 050 082 050 083 050 084 050 Fig. 3-76
protection IDMT2: Enable PSx 081 170 082 170 083 170 084 170
This setting defines whether blocking of the residual current stages will take
place for single-pole or multi-pole phase current starting.
IDMT1: Gen.starting modePSx 081 059 082 059 083 059 084 059 Fig. 3-85
IDMT2: Gen.starting modePSx 081 179 082 179 083 179 084 179
This setting defines whether starting of the residual current stages will result
in the formation of the general starting signal of IDMT protection.
IDMT1: tGS PSx 081 058 082 058 083 058 084 058 Fig. 3-85
IDMT2: tGS PSx 081 178 082 178 083 178 084 178
Setting for the operate delay of the general starting signal of IDMT
protection.
IDMT1: Rush restr.enabl PSx 081 060 082 060 083 060 084 060 Fig. 3-81,
3-83
IDMT2: Rush restr.enabl PSx 081 180 082 180 083 180 084 180
Setting for the reference current (phase current system) in dynamic mode.
This threshold value is only effective while the hold time for dynamic
parameters is elapsing.
IDMT1: Characteristic P PSx 081 053 082 053 083 053 084 053 Fig. 3-81
IDMT2: Characteristic P PSx 081 173 082 173 083 173 084 173
Setting for factor kt,P of the starting characteristic (phase current system).
IDMT1: Min. trip t. P PSx 081 057 082 057 083 057 084 057 Fig. 3-81
IDMT2: Min. trip t. P PSx 081 177 082 177 083 177 084 177
Setting for the hold time for storing the starting time once the starting has
dropped out (phase current system).
IDMT1: Release P PSx 081 056 082 056 083 056 084 056 Fig. 3-81
IDMT2: Release P PSx 081 176 082 176 083 176 084 176
IDMT1: Iref,neg PSx 081 111 082 111 083 111 084 111 Fig. 3-82
IDMT2: Iref,neg PSx 081 121 082 121 083 121 084 121
Setting for the hold time for storing the starting time once the starting has
dropped out characteristic (negative-sequence current system).
IDMT1: Release neg PSx 081 116 082 116 083 116 084 116 Fig. 3-82
IDMT2: Release neg PSx 081 126 082 126 083 126 084 126
Setting for the reference current (residual current system) in dynamic mode.
This operate value is only effective while the hold time for dynamic
parameters is elapsing.
IDMT1: Characteristic N PSx 081 063 082 063 083 063 084 063 Fig. 3-83
IDMT2: Characteristic N PSx 081 183 082 183 083 183 084 183
Setting for factor kt,N of the starting characteristic (residual current system).
IDMT1: Min. trip t. N PSx 081 067 082 067 083 067 084 067 Fig. 3-83
IDMT2: Min. trip t. N PSx 081 187 082 187 083 187 084 187
IDMT1: Hold time N PSx 081 065 082 065 083 065 084 065 Fig. 3-83
IDMT2: Hold time N PSx 081 185 082 185 083 185 084 185
Setting for the hold time for storing the starting time once the starting has
dropped out (residual current system).
IDMT1: Release N PSx 081 066 082 066 083 066 084 066 Fig. 3-83
IDMT2: Release N PSx 081 186 082 186 083 186 084 186
Thermal overload THRM1: Enable PSx 081 070 082 070 083 070 084 070 Fig. 3-88
protection This setting defines the parameter subset in which thermal overload
protection is enabled.
THRM1: Iref PSx 081 074 082 074 083 074 084 074 Fig. 3-90
Setting for the thermal time constants of the protected object with current
flow (Ibl: base line current).
THRM1: Tim.const.2,<Ibl PSx 081 083 082 083 083 083 084 083 Fig. 3-90
Setting for the thermal time constants of the protected object without current
flow (Ibl: base line current).
Note:
This setting option is only relevant when machines are running. In all other
cases, time constant 2 must be set equal to time constant 1.
THRM1: Max.perm.obj.tmp.PSx 081 077 082 077 083 077 084 077 Fig. 3-90
Setting for the coolant temperature to be used for calculation of the trip time
if coolant temperature is not measured.
THRM1: Rel. O/T warning PSx 081 079 082 079 083 079 084 079 Fig. 3-90
A warning will be given in advance of the trip. The time difference between
the warning time and the trip time is set here.
Measuring-circuit MCM_1: Enable PSx 081 038 082 038 083 038 084 038 Fig. 3-92
monitoring MCM_2: Enable PSx 081 039 082 039 083 039 084 039
The P630C generates a large number of signals, processes binary input signals, and
acquires measured data during fault-free operation of the protected object as well as
fault-related data. A number of counters are maintained for statistical purposes.
This information can be read out from the integrated local control panel. All this
information can be found in the ‘Operation’ and ‘Events’ folders in the menu tree.
interface 3 Display of the updated measured operating value for the proportion of
corrupted messages within the last 1000 received messages.
COMM3: No.t.err.,max,stored 120 041
While the hold time is running, the loop back test results can be checked by
reading out these values.
Date display.
Note: The date can also be set here.
MAIN: Time of day 003 091 Fig. 3-38
Display of the residual current calculated by the P630C from the sum of the
phase currents, end a, as a primary quantity.
MAIN: Current IN,b prim. 005 122 Fig. 3-27
Display of the residual current calculated by the P630C from the sum of the
phase currents, end b, as a primary quantity.
Display of the residual current calculated by the P630C from the sum of the
phase currents, end a, as referred to Inom.
MAIN: Current IN,b p.u. 005 142 Fig. 3-27
Display of the residual current calculated by the P630C from the sum of the
phase currents, end b, as referred to Inom.
Thermal overload THRM1: Status replica, TH1 004 150 Fig. 3-90
protection 1 Display of the buffer content of the thermal overload protection function
THRM1.
THRM1: Object temperat.,TH1 004 151 Fig. 3-90
This display appears regardless of the setting for the binary signal input
mode.
This display appears regardless of the operating mode set for the output
relay.
Local control panel LOC: Trig. menu jmp 1 EXT 030 230
"Logical" communication COMM1: Command block. EXT 003 173 Fig. 3-6
interface 1 COMM1: Sig./meas. block EXT 037 074 Fig. 3-7,
3-8, 3-9
COMM1: Command blocking 003 174 Fig. 3-6
COMM1: Sig./meas.val.block. 037 075 Fig. 3-7,
3-8, 3-9
COMM1: IEC 870-5-103 003 219
Binary and analog outputs OUTP: Block outp.rel. EXT 040 014 Fig. 3-21
OUTP: Reset latch. EXT 040 015 Fig. 3-21
OUTP: Outp. relays blocked 021 015 Fig. 3-21
OUTP: Latching reset 040 088 Fig. 3-21
Main functions MAIN: Enable protect. EXT 003 027 Fig. 3-30
MAIN: Disable protect. EXT 003 026 Fig. 3-30
MAIN: Blocking 1 EXT 040 060 Fig. 3-32
MAIN: Blocking 2 EXT 040 061 Fig. 3-32
MAIN: Blocking 3 EXT 040 116 Fig. 3-32
MAIN: Blocking 4 EXT 040 117 Fig. 3-32
MAIN: Reset latch.trip EXT 040 138 Fig. 3-36
MAIN: Trip cmd. block. EXT 036 045 Fig. 3-36
MAIN: M.c.b. trip V EXT 004 061
Parameter subset selection PSS: Control via user EXT 036 101 Fig. 3-41
PSS: Activate PS 1 EXT 065 002 Fig. 3-41
PSS: Activate PS 2 EXT 065 003 Fig. 3-41
PSS: Activate PS 3 EXT 065 004 Fig. 3-41
PSS: Activate PS 4 EXT 065 005 Fig. 3-41
PSS: Control via user 036 102 Fig. 3-41
PSS: Ext.sel.param.subset 003 061 Fig. 3-41
PSS: PS 1 activated ext. 036 094 Fig. 3-41
PSS: PS 2 activated ext. 036 095 Fig. 3-41
PSS: PS 3 activated ext. 036 096 Fig. 3-41
PSS: PS 4 activated ext. 036 097 Fig. 3-41
PSS: Actual param. subset 003 062 Fig. 3-41
PSS: PS 1 active 036 090 Fig. 3-41
PSS: PS 2 active 036 091 Fig. 3-41
PSS: PS 3 active 036 092 Fig. 3-41
PSS: PS 4 active 036 093 Fig. 3-41
Definite-time overcurrent DTOC1: Block. tI> EXT 035 120 Fig. 3-70
protection 1 DTOC1: Block. tI>> EXT 035 121 Fig. 3-70
DTOC1: Block. tI>>> EXT 035 122 Fig. 3-70
DTOC1: Block. tIneg> EXT 036 141 Fig. 3-71
DTOC1: Block. tIneg>> EXT 036 142 Fig. 3-71
DTOC1: Block. tIneg>>> EXT 036 143 Fig. 3-71
DTOC1: Block. tIN> EXT 035 123 Fig. 3-72
DTOC1: Block. tIN>> EXT 035 124 Fig. 3-72
DTOC1: Block. tIN>>> EXT 035 125 Fig. 3-72
DTOC1: Enabled 035 102 Fig. 3-69
DTOC1: General starting 035 128 Fig. 3-73
DTOC1: tGS elapsed 035 129 Fig. 3-73
DTOC1: Starting A 035 104 Fig. 3-70
DTOC1: Starting B 035 105 Fig. 3-70
DTOC1: Starting C 035 106 Fig. 3-70
DTOC1: Starting N 035 107 Fig. 3-72
DTOC1: Starting I> 035 108 Fig. 3-70
DTOC1: Starting I>> 035 109 Fig. 3-70
DTOC1: Starting I>>> 035 110 Fig. 3-70
DTOC1: Trip signal tI> 035 114 Fig. 3-70
DTOC1: Trip signal tI>> 035 115 Fig. 3-70
DTOC1: Trip signal tI>>> 035 116 Fig. 3-70
DTOC1: Starting Ineg 036 144 Fig. 3-71
DTOC1: Starting Ineg> 036 145 Fig. 3-71
DTOC1: Starting Ineg>> 036 146 Fig. 3-71
DTOC1: Starting Ineg>>> 036 147 Fig. 3-71
DTOC1: tIneg> elapsed 036 148 Fig. 3-71
DTOC1: tIneg>> elapsed 036 149 Fig. 3-71
DTOC1: tIneg>>> elapsed 036 150 Fig. 3-71
DTOC1: Trip signal tIneg> 036 151 Fig. 3-71
DTOC1: Trip signal tIneg>> 036 152 Fig. 3-71
DTOC1: Trip signal tIneg>>> 036 153 Fig. 3-71
DTOC1: Starting IN> 035 111 Fig. 3-72
Inverse-time overcurrent IDMT1: Block. tIref,P> EXT 038 114 Fig. 3-81
protection 1 IDMT1: Block.tIref,neg> EXT 038 178 Fig. 3-82
Thermal overload THRM1: Replica block EXT 039 150 Fig. 3-90
protection 1 THRM1: Reset replica EXT 039 122 Fig. 3-91
THRM1: Enabled 039 129 Fig. 3-88
THRM1: Not ready 039 154
Setting the enable for changing values from the local control panel.
Trigger for the transmission of the selected signal (as signal ‘start‘).
COMM1: Test spont.sig. end 003 186 Fig. 3-13
Trigger for the transmission of the selected signal (as signal ‘end‘).
Trigger for the transmission of the selected signal (as signal ‘start‘).
COMM2: Test spont.sig. end 103 186 Fig. 3-15
Trigger for the transmission of the selected signal (as signal ‘end‘).
Binary and analog outputs OUTP: Reset latch. USER 021 009 Fig. 3-21
The relay selected for testing is triggered for the set time (OU T P: Ho ld -
t i m e f o r tes t).
Setting for the time period for which the selected output relay is triggered for
functional testing.
The counters for counting the close and trip commands are reset.
MAIN: Reset IP,max,stored 003 033 Fig. 3-25
A trip command is issued from the local control panel for 100 ms. This
setting is password-protected (see section entitled 'Password-Protected
Control Operations' in Chapter 6).
Note:
The command is only executed if the manual trip command has been
configured as trip command 1 or 2.
MAIN: Warm restart 003 039
A warm restart is carried out. The device functions as it does when the
power supply is turned on.
MAIN: Cold restart 000 085
Operating data recording OP_RC: Reset recording 100 001 Fig. 3-43
The operating data memory and the counter for operation signals are reset.
Monitoring signal recording MT_RC: Reset recording 003 008 Fig. 3-44
Fault recording is enabled from the local control panel for 500 ms.
FT_RC: Reset recording 003 006 Fig. 3-54
Thermal overload THRM1: Reset replica USER 039 120 Fig. 3-91
protection 1 Reset of the thermal replica of the thermal overload protection 1.
Operating data recording OP_RC: Operat. data record. 003 024 Fig. 3-43
Monitoring signal recording MT_RC: Mon. Signal record. 003 001 Fig. 3-44
interface 3
Main functions MAIN: No. general start. 004 000 Fig. 3-35
Operating data recording OP_RC: No. oper. data sig. 100 002 Fig. 3-43
Monitoring signal recording MT_RC: No. monit. signals 004 019 Fig. 3-44
Number of faults.
FT_RC: No. system disturb. 004 010 Fig. 3-53
Definite-time overcurrent DTOC1: No. general start. 009 150 Fig. 3-74
protection DTOC2: No. general start. 009 160
Inverse-time overcurrent IDMT1: No. general start. 009 151 Fig. 3-86
protection IDMT2: No. general start. 009 161
Overload data acquisition OL_DA: Overload duration 004 102 Fig. 3-45
Display of the load current used by the thermal overload protection function
to calculate the tripping time.
OL_DA: Object temp. THRM1 004 156 Fig. 3-46
Fault data acquisition FT_DA: Fault duration 008 010 Fig. 3-49
This display indicates the difference in time between the start of the fault
and the fault data acquisition time.
FT_DA: Fault curr.IP,a p.u. 025 086 Fig. 3-51
Display of the maximum phase current at the data acquisition time, end a,
referred to Inom.
FT_DA: Fault curr.IP,b p.u. 025 087 Fig. 3-51
Display of the maximum phase current at the data acquisition time, end b,
referred to Inom.
9 Commissioning
The device must be reliably grounded before auxiliary voltage is turned on.
The case is grounded using the appropriate bolt and nut as the ground connection.
The cross-sectional area of this ground conductor must also conform to applicable
national standards. A minimum conductor cross section of 2.5 mm2 is required.
Before working on the device itself or in the space where the device is connected,
always disconnect the device from the supply.
The secondary circuit of operating current transformers must not be opened. If the
secondary circuit of an operating current transformer is opened, there is the danger that
the resulting voltages will endanger people and damage the insulation.
The threaded terminal block for current transformer connection is not a shorting block.
Therefore always short-circuit the current transformers before loosening the threaded
terminals.
!
The fiber-optic interface may only be connected or disconnected when the supply
voltage for the unit is shut off.
!
The PC interface is not designed for permanent connection. Consequently the socket
does not have the extra insulation from circuits connected to the system that is required
per VDE 0106 Part 101.
!
Application of analog signals to the measuring inputs must be in compliance with the
maximum permissible rating of the measuring inputs (see chapter entitled 'Technical
Data').
Preparation
After the P630C has been installed and connected as described in Chapter 5, the
commissioning procedure can begin.
Before turning on the power supply voltage, the following items must be checked again:
After the wiring work is completed, check the system to make sure it is properly isolated.
The conditions given in VDE 0100 must be satisfied.
Once all checks have been made, the power supply voltage may be turned on. After
voltage has been applied, the device starts up. During startup, various startup tests are
carried out (see section entitled ‘Self-Monitoring’ in Chapter 3). The LED indicator
labeled ‘HEALTHY’ (H1) and the LED indicator labeled ‘OUT OF SERVICE’ (H2) will
light up. (The LED indicator H2 is coupled to the signal M A I N : B l o c k e d / f a u l t y . )
After approximately 15 s, the P630C is ready for operation. This is indicated by the
display 'P630C' in the first line of the LCD.
Once the change-enabling command has been issued (see the Section Change-
Enabling Function in Chapter 6), all settings can be entered. The procedure for entering
settings from the integrated local control panel is described in Chapter 6.
If either the PC interface or the communication interface will be used for setting the
P630C and reading out event records, then the following settings must first be made
from the integrated local control panel.
! ‘Par/DvID/’ folder:
" DVICE: Device password 1
" DVICE: Device password 2
! ‘Par/Conf/’ folder:
" PC: Name of manufacturer
" PC: Bay address
" PC: Device address
" PC: Baud rate
" PC: Parity bit
" COMM1: Function group COMM1
" COMM1: General enable USER
" COMM1: Name of manufacturer
" COMM1: Line idle state
" COMM1: Baud rate
" COMM1: Parity bit
" COMM1: Communicat. protocol
" COMM1: Octet comm. address
" COMM1: Octet address ASDU
" COMM2: Function group COMM2
" COMM2: General enable USER
" COMM2: Name of manufacturer
" COMM2: Line idle state
" COMM2: Baud rate
" COMM2: Parity bit
" COMM2: Octet comm. address
" COMM2: Octet comm. ASDU
! ‘Par/Func/Glob/’ folder:
Note: The settings given above apply to the IEC 60870-5-103 communication
protocol. If another protocol is being used for the communication interface,
additional settings may be necessary. See Chapter 7 for further details.
After the settings have been made, the following checks should be carried out again
before blocking is canceled:
! Does the function assignment of the binary signal inputs agree with the terminal
connection diagram?
! Has the correct operating mode been selected for the binary signal inputs?
! Does the function assignment of the output relays agree with the terminal connection
diagram?
! Has the correct operating mode been selected for the output relays?
! Have all settings been made correctly?
! M A I N : D e v i c e o n - l i n e "Yes (on)"
Tests
By using the signals and displays generated by the P630C, it is possible to determine
whether the P630C is correctly set and properly interconnected with the station. Signals
are signaled by output relays and LED indicators and entered into the event memory. In
addition, the signals can be checked by selecting the appropriate signal in the menu
tree.
If the user does not wish to operate the circuit breaker during the protection functions
test, the trip commands can be blocked through M A I N : T r i p c m d . b l o c k . U S E R
('Par/Func/Glob/' folder) or an appropriately configured binary signal input. If circuit
breaker testing is desired, it is possible to issue a trip command for 100 ms through
M A I N : M a n . t r i p c m d . U S E R ('Oper/CtrlTest' folder) or an appropriately
configured binary signal input. Selection of the trip command from the integrated local
control panel is password-protected (see Section Password-Protected Control Actions in
Chapter 6).
Note: The manual trip command is only executed if it has been configured for trip
command 1 or 2.
If the P630C is connected to substation control level, it is advisable to activate the test
mode via MAIN: T e s t m o d e U S E R ('Par/Func/Glob/' folder) or an appropriately
configured binary signal input. The telegrams are then identified accordingly (cause of
transmission: test mode).
This display appears regardless of the binary signal input mode selected.
!
Before starting the test, open any triggering circuits for external devices so that no
inadvertent switching operations will take place.
!
Application of analog signals to the measuring inputs must be in compliance with the
maximum permissible rating of the measuring inputs (see the Chapter on Technical
Data).
A protection function can only be checked if it is included in the configuration and then
enabled as a function group and furthermore enabled as part of the active parameter
subset.
When testing the protection device with a testing device, the measuring-circuit
monitoring functions should be deactivated (M C M _ 1 : G e n e r a l e n a b l e U S E R
a n d M C M _ 2 : G e n e r a l e n a b l e U S E R , folder ‘Par/Func/Gen/’) since it would
otherwise always operate and thus, depending on the setting, issue fault signals.
Checking differential
protection
For single-side feed, the fault current characteristic crosses the first knee of the tripping
characteristic of the P630C so that the basic threshold value is always checked for.
The current I to which the P630C responds for single-side feed is calculated as follows:
Idiff >
Ix,z = ⋅ Inom,z
k am,z
The differential and restraining currents formed by the P630C are displayed as
measured operating data. They aid in assessing whether the connection of the P630C
to the system current transformers and the setting of the vector group ID are correct.
The display of differential and restraining currents is prevented, however, if they fall
below minimum thresholds that can be set by the user:
k am,z ⋅ Ix,z
Id,y =
Inom,z
1 k am,z ⋅ Ix,z
IR,y = ⋅
2 Inom,z
For single-side one-phase feed, another matching factor in accordance with the set
vector group ID and the set zero-sequence current filtering needs to be taken into
account in addition to the amplitude-matching factor. The threshold current Ix,z is
calculated as follows:
Idiff >
Ix,z = ⋅ Inom,z
k am,z ⋅ k s,z
The differential and restraining currents to be displayed as measured operating data are
calculated as follows:
where:
x: Phase A, B or C
y: Measuring system 1, 2 or 3
z: Transformer end a or b
Ix,z: Test current phase x transformer end z
Inom,z: Nominal current transformer end z
kam,z: Amplitude-matching factor transformer end z
ks,z: Matching factor in accordance with the set vector group ID and
the set zero-sequence current filtering (see tables) transformer end z
Idiff>: Operate value of the differential protection function
Id,y: Differential current measuring system y as displayed
IR,y: Restraining current measuring system y as displayed
Matching factor ks,z for the individual measuring systems y as a function of the supplied
phase x for the high-voltage side:
Matching factor ks,z for the individual measuring systems y as a function of the supplied
phase x and as a function of the set vector group for the low-voltage side in question:
In evaluating the test results, one should be aware that the P630C will trip as follows, if a
value of Idiff>> or Idiff>>> is exceeded.
The connection of the phase currents can be checked using the phase angles provided
as measured operating data by the P630C.
With an ideally symmetrical load through the transformer, the phase angles between the
phase currents of a given end must be displayed as follows, depending on the rotary
field direction in the system:
The setting of the function parameter for direction of rotating field has no effect in this
case.
The phase angles of a given phase between the phase currents of two ends must be
displayed as follows, depending on the transformer vector group:
Vector Group
0 = 12 ϕ x,a − z = ±180°
1 ϕ x,a − z = −150°
2 ϕ x,a − z = −120°
3 ϕ x,a − z = −90°
4 ϕ x,a − z = −60°
5 ϕ x,a − z = −30°
6 ϕ x,a − z = ±0°
7 ϕ x,a − z = 30°
8 ϕ x,a − z = 60°
9 ϕ x,a − z = 90°
10 ϕ x,a − z = 120°
11 ϕ x,a − z = 150°
The rotary field direction in the system has no effect in this case. On the other hand, a
change in the setting of the function parameter for the connection direction of a given
main current transformer set affects the corresponding measured operating value by
±180°.
!
Application of analog signals to the measuring inputs must be in compliance with the
maximum permissible rating of the measuring inputs (see the Chapter on Technical
Data).
!
Application of analog signals to the measuring inputs must be in compliance with the
maximum permissible rating of the measuring inputs (see the Chapter on Technical
Data).
!
Application of analog signals to the measuring inputs must be in compliance with the
maximum permissible rating of the measuring inputs (see the Chapter on Technical
Data).
In order to test the thermal overload protection function, first clear the thermal replica.
Clearing the thermal replica is achieved by briefly disabling the protection function
(M A I N : D e v i c e o n - l i n e set to No, folder ‘Par/Func/Glob/’). The updated status of the
thermal replica can be interrogated via the operating data display T H ER M : T h e r m .
r e p l i c a ve r s . ( folder ‘Oper/Cycl/Data/’) The trip time can be checked.
With cleared thermal replica, the test current is changed abruptly from 0 to a value
of ≥ 0.1 Iref. The following parameters and data will govern the tripping time:
2
I
− ∆ϑ0
t = τ ⋅ ln Iref
2
I Θ a − Θ a,max
− ∆ϑ trip ⋅ 1 −
Iref Θmax − Θ a,max
Completion of
commissioning
Before the P630C is released for operation, the user should make sure that the following
steps have been taken:
10 Troubleshooting
This chapter describes problems that might be encountered, their causes, and possible
methods for eliminating them. It is intended as a general orientation only, and in cases
of doubt it is better to return the P630C to the manufacturer. Please follow the
packaging instructions in the section entitled ‘Unpacking and Packing’ in Chapter 5 when
returning equipment to the manufacturer.
Problem:
Before checking further, disconnect the P630C from the power supply.
!
The local control panel is connected to the I/O module by a plug-in connecting cable.
Make sure the connector position is correct. Do not bend the connecting cable.
" Check to see whether the magnitude of the auxiliary voltage is correct. The
P630C has an auxiliary voltage supply that can be switched between ranges and
is factory-set for the voltage range of VA,nom = 110 to 250 V DC or 100 to 230 V
AC. See Chapter 5 for information on switching to the voltage range of VA,nom = 24
to 60 V DC . The P630C is protected against damage from polarity reversal.
! The P630C issues a ‘Warning’ signal on LED H3. (H3 is labeled ‘ALARM’,
it is coupled to the signal SF MON : Wa rn ing ( L ED) .)
Identify the specific problem by reading out the monitoring signal memory (see the
section entitled ‘Monitoring Signal Memory Readout’ in Chapter 6). The table below
lists possible monitoring or warning indications (provided that a configuration setting
has been entered at S F M O N : F c t . a s s i g n . w a r n i n g ) , the faulty area, the
P630C response, and the mode of the output relay configured for 'Warning' and
'Blocked/faulty'.
Key
-: No reaction and/or no output relay triggered.
Updating: The output relay configured for 'Warning' starts only if the monitoring
signal is still present.
1)
: The 'Blocked/faulty' output relay only operates if the signal has been
configured at M A I N : F c t . a s s i g n m . f a u l t .
2)
: The 'Warning' output relay only operates if the signal has been
configured at S F M O N : F c t . a s s i g n m . w a r n i n g .
A cold restart has been carried out on account of a checksum error in the
memory (NOVRAM).
1st device reaction / 2nd device reaction: Warm restart / Device blocking
'Warning' output relay: Yes / Yes
'Blocked/faulty' output relay: Yes / Yes
SFMON: Cold rest./SW update 093 025
1st device reaction / 2nd device reaction: Warm restart / Device blocking
'Warning' output relay: Yes / Yes
'Blocked/faulty' output relay: Yes / Yes
SFMON: Blocking HW failure 090 019
1st device reaction / 2nd device reaction: Warm restart / Device blocking
'Warning' output relay: Yes / Yes
'Blocked/faulty' output relay: Yes / Yes
SFMON: +15V supply faulty 093 081
The +15 V internal supply voltage has dropped below a minimum value.
1st device reaction / 2nd device reaction: Warm restart / Device blocking
'Warning' output relay: Yes / Yes
'Blocked/faulty' output relay: Yes / Yes
SFMON: +24V supply faulty 093 082
The +24 V internal supply voltage has dropped below a minimum value.
1st device reaction / 2nd device reaction: Warm restart / Device blocking
'Warning' output relay: Yes / Yes
'Blocked/faulty' output relay: Yes / Yes
SFMON: -15V supply faulty 093 080
The -15 V internal supply voltage has dropped below a minimum value.
1st device reaction / 2nd device reaction: Warm restart / Device blocking
'Warning' output relay: Yes / Yes
'Blocked/faulty' output relay: Yes / Yes
SFMON: Power supply faulty 093 083
The +24 V or +15 V or -15 V internal supply voltage has dropped below a
minimum value.
1st device reaction / 2nd device reaction: Warm restart / Device blocking
'Warning' output relay: Yes / Yes
'Blocked/faulty' output relay: Yes / Yes
1st device reaction / 2nd device reaction: Warm restart / Device blocking
'Warning' output relay: Yes / Yes
'Blocked/faulty' output relay: Yes / Yes
SFMON: Defect.module slot 1 097 000
1st device reaction / 2nd device reaction: Warm restart / Device blocking
'Warning' output relay: Yes / Yes
'Blocked/faulty' output relay: Yes / Yes
SFMON: Invalid arithm. op. 093 011
1st device reaction / 2nd device reaction: Warm restart / Device blocking
'Warning' output relay: Yes / Yes
'Blocked/faulty' output relay: Yes / Yes
SFMON: Undefined interrupt 093 012
1st device reaction / 2nd device reaction: Warm restart / Device blocking
'Warning' output relay: Yes / Yes
'Blocked/faulty' output relay: Yes / Yes
SFMON: Exception oper.syst. 093 013
1st device reaction / 2nd device reaction: Warm restart / Device blocking
'Warning' output relay: Yes / Yes
'Blocked/faulty' output relay: Yes / Yes
SFMON: Data acquis. failure 090 021
1st device reaction / 2nd device reaction: Warm restart / Device blocking
'Warning' output relay: Yes / Yes
'Blocked/faulty' output relay: Yes / Yes
SFMON: Checksum error param 090 003
1st device reaction / 2nd device reaction: Warm restart / Device blocking
'Warning' output relay: Yes / Yes
'Blocked/faulty' output relay: Yes / Yes
SFMON: Clock sync. error 093 041
Faulty test pattern in the RAM. This can occur, for example, if the processor
module or the power supply module is removed from the bus module
(digital). This fault is only detected during device startup. After the fault is
detected, the software initializes the RAM. This means that all records are
deleted.
1st device reaction / 2nd device reaction: Warm restart / Device blocking
'Warning' output relay: Yes / Yes
'Blocked/faulty' output relay: Yes / Yes
SFMON: Overflow MT_RC 090 012
Software overloaded.
Incorrect or invalid software for the local control component has been
downloaded.
The set time CO MM 3 : T im e-o u t com m .fa ul t has elapsed since the
most recent 100% valid telegram was received. The receive signals are set
to their user-defined default values.
11 Maintenance
The P630C is a low-maintenance device. The components used in the units are selected
to meet exacting requirements. Recalibration is not necessary.
The P630C incorporates in its system a very extensive self-monitoring function for
hardware and software. The internal structure guarantees, for example, that
communication within the processor system will be checked on a continuing basis.
Nonetheless, there are a number of subfunctions that cannot be checked by the self-
monitoring feature without running a test from the device terminals. The respective
device-specific properties and setting parameters must be observed in such cases.
In particular, none of the control and signaling circuits that are run to the device from the
outside are checked by the self-monitoring function.
The best way to carry out a static test of the analog input circuits is to check the primary
measured operating data using the operating data measurement function or to use a
suitable testing instrument. A “small” measured value (such as the nominal current in the
current path) and a “large” measured value (such as the nominal voltage in the voltage
path) should be used to check the measuring range of the A/D converter. This makes it
possible to check the entire control range.
In addition, a dynamic test can be used to check transmission performance and the
phase relation of the current transformers and the anti-aliasing filter. This can best be
done by measuring the trigger point of the first zone when there is a two-phase
ungrounded fault. For this test, the short-circuit current should be dimensioned so that a
loop voltage of approximately 2 V is obtained at the device terminals with the set
impedance. Furthermore, a suitable testing instrument that correctly replicates the two-
phase ungrounded fault should be used for this purpose.
This dynamic test is not absolutely necessary, since it only checks the stability of a few
less passive components. Based on reliability analysis, the statistical expectation is that
only one component in 10 years in 1000 devices will be outside the tolerance range.
Additional analog testing of such factors as the impedance characteristic or the starting
characteristic is not necessary, in our opinion, since information processing is completely
digital and is based on the measured analog current and voltage values. Proper
operation was checked in conjunction with type testing.
Binary inputs
The binary inputs are not checked by the self-monitoring function. However, a testing
function is integrated into the software so that the trigger state of each input can be read
out (‘Oper/Cycl/Phys’ folder). This check should be performed for each input being used
and can be done, if necessary, without disconnecting any device wiring.
Binary outputs
With respect to binary outputs, the integrated self-monitoring function includes even two-
phase triggering of the relay coils of all the all-or-nothing relays. There is no monitoring
function for the external contact circuit. In this case, the all-or-nothing relays must be
triggered by way of device functions or integrated test functions. For these testing
purposes, triggering of the output circuits is integrated into the software through a special
control function (‘Oper/CtrlTest/’ folder).
!
Before starting testing, open any triggering circuits for external devices so that no
inadvertent switching operations will take place.
Serial interfaces
The integrated self-monitoring function for the PC or communication interface also
includes the communication module. The complete communication system, including
connecting link and fiber-optic module (if applicable), is always totally monitored as long
as a link is established through the control program or the communication protocol.
12 Storage
Devices must be stored in a dry and clean environment. A temperature range of -25°C to
+70°C (-13°F to +158°F) must be maintained during storage (see chapter entitled
'Technical Data'). The relative humidity must be controlled so that neither condensation
nor ice formation will result.
If the units are stored without being connected to auxiliary voltage, then the electrolytic
capacitors in the power supply area need to be reformed every 4 years. Reform the
capacitors by connecting auxiliary voltage to the P630C for approximately 10 minutes.
The P630C is supplied with standard labeling for the LED indicators. LED indicators that
are not already configured and labeled can be labeled using the label strips supplied with
the P630C. Affix the label strips to the front of the unit at the appropriate location.
The label strips can be filled in using a Stabilo brand pen containing water-resistant ink
(Type OH Pen 196 PS).
14 Order Information
MiCOM P630C
Basic device:
Compact Device 9
with 2 binary inputs and 8 output relays
Current transformer:
Inom = 1 A / 5 A (T11...T13, T21...T23) 2) 9
Language:
English (German) 4) Without order extension no.
Px40 English (English) 4) On request -800
German (English) 4) -801
French (English) 4) On request -802
Spanish (English) 4) On request -803
Polish (English) 4) On request -804
Russian (English) 4) 7) On request -805
Language Versions
For a display of the Russian data model (menu texts), order extension No. -805 must be
specified with the order. The device will then be fitted with the hardware supporting
Cyrillic characters. The English reference texts are fully supported by this hardware
option but additional characters in other West European languages are not. The Russian
/ English language version is therefore not suited to a subsequent loading of West
European data models.
A Glossary
B List of Signals
A Glossary A-1
A1 Function Groups A-1
A2 Symbols A-2
A3 Examples of Signal Names A-9
A4 Symbols Used A-10
A1 Function Groups
A2 Symbols
Graphic symbols for block diagrams
Binary elements according to DIN 40900 Part 12, September 1992,
IEC 617-12: amended 1991
Analog information processing according to DIN 40900 Part 13, January 1981
To document the linking of analog and binary signals, additional symbols have been
used, taken from several DIN documents.
As a rule, direction of the signal flow is from left to right and from top to bottom. Other
flow directions are marked by an arrow. Input signals are listed on the left side of the
signal flow, output signals on the right side.
Symbol Description
Note:
This rule does not necessarily apply to configurations
with two or more signal flow directions, such as for
symbols with a control block and an output block.
Components of a symbol
A symbol consists of a contour or contour combination
and one or more qualifiers.
Symbol Description
Control block
A control block contains an input function common to
several symbols. It is used for the collective setting of
several trigger elements, for example.
Output block
An output block contains an output function common
to several symbols.
Symbol Description
Static input
Only the state of the binary input variable is effective.
Dynamic input
Only the transition from value 0 to value 1 is
effective.
Negation of an output
The value up to the border line is negated at the
output.
Negation of an input
The input value is negated before the border line.
AND element
The output variable will be 1 only if all input variables
are 1.
OR element
The output variable will be 1 only if at least one input
variable is 1.
Threshold element
The output variable will be 1 only if at least two input
variables are 1. The number in the symbol may be
replaced by any other number.
(m out of n) element
The output variable will be 1 only if just one input
variable is 1.
Symbol Description
Delay element
The transition from value 0 to 1 at the output occurs
after a time delay of t1 relative to the corresponding
transition at the input.
The transition from value 1 to 0 at the output occurs
after a time delay of t2 relative to the corresponding
transition at the input.
Monostable flip-flop
The output variable will be 1 only if the input variable
changes to 1. The output variable will remain 1 for
100 ms, independent of the duration of the input
value 1 (non-retriggerable).
Analog-digital converter
An analog input signal is converted to a binary
signal.
Subtractor
The output variable is the difference between the two
input variables.
A summing element is obtained by changing the
minus sign to a plus sign at the symbol input.
Memory, general
Storage of a binary or analog signal.
Symbol Description
Non-stable flip-flop
When the input variable changes to 1, a pulse
sequence is generated at the output.
Amplifier
The output variable is 1 only if the input variable is
also 1.
Counter
At the + input the input variable transitions from 0 to 1
are counted and stored in the function block.
At the R(eset) input a transition of the input variable
from 0 to 1 resets the counter to 0.
Electromechanical drive
in general, here a relay, for example.
Symbol Description
Input transformer
with phase and item identifiers
(according to DIN EN 60445)
Change-over contact
with item identifier
Special symbol
Output relay in normally-energized arrangement
(‘closed-circuit operation’).
Symbol Description
PC interface
with pin connections
Multiplier
The output variable is the result of the multiplication
of the two input variables.
Divider
The output variable is the result of the division of
the two input variables.
Comparator
The output variable becomes 1 only if the input
variable(s) are equal to the function in the function
block.
Formula block
The output variable becomes 1 only if the input
variable(s) satisfy the equation in the function block
! FT_RC: Fault recording n Internal signal names are not coded by a data model
305 100
address. In the block diagrams they are marked with
a diamond. The small figure underneath the signal
name represents a code that is irrelevant to the user.
The internal signal names used and their origins are
listed in Appendix B.
DIST: VNG>> triggered Signal names coded by a data model address are
[ 036 015 ] represented by their address (shown in square
brackets). Their origin is given in Chapters 7 and 8.
MAIN: General reset A specific setting to be used later on is shown with its
[ 003 002 ] signal name, address, and the setting preceded by
!1: Execute the setting arrow.
A4 Symbols Used
Symbol Meaning
t Time duration
V Complex voltage
I Electrical current
I Complex current
Z Complex impedance
f Frequency
Σ Sum, result
α Angle
Θ Absolute temperature in °C
τ Time constant
This section incorporates Section 8 of EN 60870-5-101 (1996), which includes a general definition of the telecontrol
interface for substation control systems.
B 2.1 Interoperability
This application-based standard (companion standard) specifies parameter sets and other options from which subsets
are to be selected in order to implement specific telecontrol systems. Certain parameters such as the number of octets
in the COMMON ADDRESS of the ASDU are mutually exclusive. This means that only one value of the defined
parameter is allowed per system. Other parameters, such as the listed set of different process information in the
command and monitor direction, permit definition of the total number or of subsets that are suitable for the given
application. This section combines the parameters given in the previous sections in order to facilitate an appropriate
selection for a specific application. If a system is made up of several system components supplied by different
manufacturers (“equipment stemming”), then it is necessary for all partners to agree on the selected parameters.
Note: The overall definition of a system may also require individual selection of certain parameters for specific
parts of a system such as individual selection of scaling factors for individually addressable measured
values.
1
The transmission rates for control direction and monitor direction must be identical.
P630C-301-401-601 / P630C/EN M/B11 B-3
Appendix B - List of Signals
(continued)
Frame format FT 1.2, single character 1, and the fixed time-out interval are used exclusively in this companion
standard.
! Two octets 1
1
Balanced only.
B-4 P630C-301-401-601 / P630C/EN M/B11
Appendix B - List of Signals
(continued)
Mode 1 (least significant octet first), as defined in clause 4.10 of IEC 870-5-4, is used exclusively in this companion
standard.
! Three octets
<14> = Measured value, short floating point value with time tag M_ME_TC_1
! <18> = Packed start events of protection equipment with time tag ME_EP_TB_1
! <19> = Packed output circuit information of protection equipment with time tag M_EP_TC_1
1
Incorrectly identified with control direction in IEC 870-5-101.
B-8 P630C-301-401-601 / P630C/EN M/B11
Appendix B - List of Signals
(continued)
1
The command procedure is formally processed, but there is no change in the local time in the station.
P630C-301-401-601 / P630C/EN M/B11 B-9
Appendix B - List of Signals
(continued)
<122> = Call directory, select file, call file, call section F_SC_NA_1
! Remote initialization
! Global
! Group 5 ! Group 11
! Clock synchronization
Direct set point command transmission Select and execute set point command
! No additional definition
Persistent output
! Threshold value
Smoothing factor
This section incorporates Section 8 of IEC 60870-5-103, including definitions applicable to the P630C.
B 3.1 Interoperability
! EIA RS 485
Note: EIA RS 485 defines the loads in such a way that 32 of them can be operated on one line. For detailed
information see EIA RS 485, Section 3.
! Glass fiber
! Plastic fiber
! F-SMA connector
BFOC/2.5 connector
! 9 600 bit/s
! 19 200 bit/s
Mode 1 (least significant octet first) as defined in clause 4.10 of IEC 60870-5-4 is used exclusively in this companion
standard.
INF Description
! <3> Reset CU
<5> Power on
1
Different designations are used, for example, in IEC 60870-5-103 Annex A (phase A rather than L1).
B-16 P630C-301-401-601 / P630C/EN M/B11
Appendix B - List of Signals
(continued)
! <36>1 Trip circuit supervision 041 200 SFMON: Relay Kxx faulty
1
The message content is formed from the OR operation of the individual signals
P630C-301-401-601 / P630C/EN M/B11 B-17
Appendix B - List of Signals
(continued)
1
Different designations are used, for example, in IEC 60870-5-103 Annex A (phase A rather than L1).
B-18 P630C-301-401-601 / P630C/EN M/B11
Appendix B - List of Signals
(continued)
<69> Trip L1
<70> Trip L2
<71> Trip L3
<78> Zone 1
<79> Zone 2
<80> Zone 3
<81> Zone 4
<82> Zone 5
1
Different designations are used, for example, in IEC 60870-5-103 Annex A (phase A rather than L1).
P630C-301-401-601 / P630C/EN M/B11 B-19
Appendix B - List of Signals
(continued)
<128> CB ‘on’ by AR
<130> AR blocked
<144> Measurand I
<145> Measurands I, V
<146> Measurands I, V, P, Q
1
Switches PSS: Select PS USER to "Parameter set 1"
2
Switches PSS: Select PS USER to "Parameter set 2"
3
Switches PSS: Select PS USER to "Parameter set 3"
4
Switches PSS: Select PS USER to "Parameter set 4"
P630C-301-401-601 / P630C/EN M/B11 B-23
Appendix B - List of Signals
(continued)
! Test mode
! Disturbance data
Generic services
! Private data
B 3.1.3.6 Miscellaneous
Measured values are transmitted both with ASDU 3 and ASDU 9. As defined in Sec. 7.2.6.8, the maximum MVAL can
be either 1.2 or 2.4 times the rated value. In ASDU 3 and ASDU 9, different ratings may not be used; in other words,
there is only one choice for each measurand.
1.2 or 2.4
Current L1 Current A
Current L2 Current B
Current L3 Current C
Frequency f Frequency f
1
IEC 60870-5-103 Annex also uses phase A rather than L1.
Schneider Electric
35 rue Joseph Monier
92506 Rueil-Malmaison
FRANCE
Phone: +33 (0) 1 41 29 70 00
Fax: +33 (0) 1 41 29 71 00
www.schneider-electric.com Publishing: Schneider Electric
Publication: P630C/EN M/C11 Version: -601 11/2011
MiCOM P630C
P630C/EN AD/C21
Upgrade Documentation
P630C, Changes in Software Version -601 to -602
Contents
In the new version of the P630C several enhanced features and changes on existing
features have been included. These are described with reference to the technical
manuals listed below.
References
Released Version Documentation
28.06.2004 P630C -301 -401 -601 Technical Manual
P630C/EN M/B11
(AFSV. 12.09380 D)
1 Overview
Version Changes
Software
Software
Version Changes
Software
LOC The previous English text for the menu point at (003 020) has been
changed to L O C : L a n g u a g e .
COMM1 Bug fixing in the MODBUS protocol:
The analog current channels can now be read.
Names of manufacturers AREVA and AREVA_D have been added.
COMM2 With the new parameter (103 203)
C O M M 2 : P o s i t i v e a c k n . F a u l t it is now possible to set whether
or not faults can be acknowledged positively after transmission (and
consequently deleted from the fault overview at the COMM2/PC
interface).
The default setting for parameter
(103 177) C O M M 2 : S p o n t a n . s i g . e n a b l e has been changed to
'None'. This setting must be selected when spontaneous signals are to
be polled non-cyclically at communication interface COMM2.
Names of manufacturers AREVA and AREVA_D have been added.
OUTP Bug fixing:
The test function for output relays may now be used; available output
relays can be selected at the address
(003 042) O U T P : R e l a y a s s i g n . f . t e s t .
LOC Two menu jump lists may now be configured. These menu jump lists
MAIN make it possible to select individual menu points (i.e. set values,
counters, triggering functions, event logs) in a freely definable sequence.
(030 238) L O C : F c t. m e n u j m p l i s t 1
(030 239) L O C : F c t. m e n u j m p l i s t
MAIN Bug fixing:
Measured data for currents in phase C could be given incorrectly when
operating at fnom = 60 Hz.
Version Changes
MAIN The reset functions have been extended:
• There are now two group resetting parameters available which
each allow several memories to be cleared at the same time.
The assignment of the relevant memories to the two group
resetting parameters can be configured. Group resetting is then
also available for manual resetting from the local control panel
and, as an alternative, it can also be mapped to a binary signal
input or a function key.
• Similarly to this, the "CLEAR" key on the local control panel may
be assigned a selection of memories to be cleared. Any
pressing of the "CLEAR" key will not only result in the usual
resetting of the LEDs and clearing of the LCD but the selected
memories will also be cleared immediately.
Synchronization of date and time may now be checked with these new
parameters:
MAIN: Prim.Source TimeSync (103 210)
MAIN: BackupSourceTimeSync (103 211)
MAIN: Time sync. time-out (103 212)
The previous description text used for the menu point [010 049]
M A I N : R o t a r y f i e l d (values: Clockwise rotation or Anti-clockwise
rot.) has been changed for conformity with other devices to
M A I N : P h a s e s e q u e n c e (values: A - B - C, A - C - B).
MAIN The negative- and the positive-sequence current (for ends a and b, and
as primary quantities as well as derived quantities) are now available as
new measured operating data together with the associated enabling
parameters.
MAIN: Meas.value rel. Ineg (011 048)
MAIN: Meas.value rel. Ipos (011 058)
PSS Bug fixing:
Time tags for a signal that was entered into the operating data memory
and a spontaneous signal, transferred via COMMx using the protocol per
IEC 60870-5-103, differed when an other parameter subset was
selected.
SFMON Bug fixing in the data model:
The addresses (097 000) S F M O N : D e f e c t . m o d u l e s l o t 1
(i.e. processor module) and (097 001) S F M O N : D e f e c t . m o d u l e
s l o t 2 (i.e. I/O module) are now no longer signaled with the default
setting 'Yes'.
These unused signals have been deleted:
(098 000) S F M O N : M . c . b . t r i p V ,
(098 036) S F M O N : C T A e r r o r T H R M 1 ,
(093 120) S F M O N : I n v . i n p . f . c l o c k s y n c
Version Changes
SFMON The parameter (093 120) S F M O N : I n v . i n p . f . c l o c k s y n c has
been deleted.
The new parameter (021 018) S F M O N : M o n . s i g . r e t e n t i o n
specifies for what length of time monitoring signals will remain stored in
the monitoring signal memory before they are cleared.
In the course of platform harmonization the configuration table of the
alarm condition has been supplemented by the instantaneous outputs
30..32 and the timed outputs 30...32 (t) of the programmable LOGIC:
098 053 S F M O N : Output 30 ↔ 042 090 L O G I C : Output 30
098 054 S F M O N : Output 30 (t) ↔ 042 091 L O G I C : Output 30 (t)
098 055 S F M O N : Output 31 ↔ 042 092 L O G I C : Output 31
098 056 S F M O N : Output 31 (t) ↔ 042 093 L O G I C : Output 31 (t)
098 057 S F M O N : Output 32 ↔ 042 094 L O G I C : Output 33
098 058 S F M O N : Output 32 (t) ↔ 042 095 L O G I C : Output 32 (t)
2 Operation
With the example for function key F1 the operation is demonstrated in the figure in
section "Configurable Function Keys (Function Group F_KEY). Function key F1 is
enabled only after the associated password, as defined at F _ K E Y : P a s s w o r d
f u n c t . k e y 1 , has been entered. After the password has been entered the function
key will remain active for the time period set at F _ K E Y : R e t u r n t i m e f c t . k e y s .
Thereafter, the function key is disabled until the password is entered again. The same is
valid for function keys F2 to F6.
Further information on the function keys and their application can be found in section
"Configurable Function Keys (Function Group F_KEY)" and section "Resetting
Mechanisms".
Note: There is an LED indicator next to each of the four function keys. As the other LED
indicators, these are freely configurable and they are independent of the configuration of
the function keys.
Configuration of the
READ key
As with L O C : F c t . m e n u j m p l i s t x up to 16 functions may also be selected from
the same menu jump list at L O C : F c t . r e a d k e y . They are triggered in sequence by
repeated pressing of the "READ" key.
Configuration of the
CLEAR key ('C')
Similarly to the setting at M A I N : F c t . a s s i g n . r e s e t x up to 10 reset functions
may be selected from a list at L O C : F c t . r e s e t k e y . These are carried out by
pressing the "CLEAR" C key.
z: End a z: End b
MAIN: Current Ineg z prim. 005 125 005 129
M AIN : C u r r e n t Ip o s z p r i m . 005 127 005 134
MAIN: Current Ineg z p.u. 005 126 005 130
M AIN : C u r r e n t Ip o s z p .u . 005 128 005 135
When the CB's contacts are open, it is also possible to force to zero the setting of small
positive- and negative-sequence current measured values if such measured values are
below additionally created settable thresholds.
Synchronization source
The P630C protection device provides several ways of synchronizing the internal clock:
o Telegram with the time of day via the communication interface COMM1/IEC (full
time)
o Telegram with the time of day via the communication interface COMM2/PC (full time)
o IRIG-B Signal (IRIGB; time of day only)
o Impulse every minute via a binary signal input (MAIN), see Figure 3-38 in the
complete operating manual and associated text on page 3-52.
With older device versions these interfaces were of equal priority, i.e. clock
synchronization was carried out irrespective of the source. No conflicts have to be taken
into account as long as synchronization sources (communication master, IRIG-B and
minute impulse source) operate at the same time of day. Should the synchronization
sources operate with a different time basis unwanted step changes in the internal clock
may occur. On the other hand a redundant time of day synchronization is often used so
as to sustain time synchronization via IRIG-B interface even if and while the SCADA
communication is out of service.
As of the currently available device versions a primary source and a backup source for
time of day synchronization may now be set, where both provide the four options
listedabove.
MAIN: Prim.Source TimeSync
MAIN: BackupSourceTimeSync
With this feature synchronization occurs continuously from the primary source as long as
time synchronization telegrams are received within a time-out period set at
M A I N : T i m e s y n c . t i m e - o u t . The backup source is used when there is no
synchronization generated by the primary source after M AIN : T i m e s yn c . ti m e - o u t
has elapsed.
When selecting the time telegram via IEC as the primary source the device will expect
time synchronization telegrams from server SNTP2 after server SNTP 1 has become
defective, before it will switch over to the backup source.
Time synchronization occurs solely from the primary source when the time-out stage is
blocked.
Stored data such as event logs, measured fault data etc, can be cleared in several ways.
The following mechanisms are available:
Automatic resetting of the event signals provided by LED indicators (given that the
LED operating mode has been set accordingly) and of the display of measured event
data on the front panel LCD whenever a new event occurs. In this case only the
displays on the front panel LCD are cleared but not the internal memories such as the
fault memory.
Resetting of LED indicators and measured event data displayed on the front panel
LCD by pressing the "CLEAR" key C located on the front panel user interface
(HMI). By selecting the required function at L O C : F c t . r e s e t k e y further
memories may be assigned which will then also be cleared when the "CLEAR" key is
pressed.
Selective resetting, e.g. fault memories only, from the local control panel. (For this
example: Navigate to menu point F T _ R C : R e s e t r e c o r d . U S E R and set to
'Execute', see also the exact step-by-step description in Chapter 6 "Local Control",
section 'Reset'.)
Selective resetting of a particular memory type (e.g. only the fault memory) through
appropriately configured binary signal inputs. (For this example: Assign parameter
F T _ R C : R e s e t r e c o r d . E X T to the relevant binary signal input e.g.
I N P : F c t . a s s i g n m . U 1 .)
Group resetting from the local control panel, by navigating to menu point
M A I N : G r o u p r e s e t x U S E R and setting it to 'Execute'. For this the relevant
memories (i.e. those to be reset) must be assigned to parameter
MAIN: Fct.assign. reset x.
Group resetting through appropriately configured binary signal inputs. (That is assign
parameter M A I N : G r o u p r e s e t . x E X T to the relevant binary signal input, e.g.
I N P : F c t . a s s i g n m . U 1 after memories to be reset have been assigned to
parameter M A I N : F c t . a s s i g n . r e s e t x .)
General resetting by setting parameters (menu point
M A I N : G e n e r a l r e s e t U S E R ). All memories, counters, events etc. are reset
without any special configuration options.
Should several resetting actions have been configured to one particular memory then
they all have equal priority.
In the event of a cold restart, namely simultaneous failure of both internal battery and
substation auxiliary supply, all stored signals and values will be lost.
Further resetting possibilities are basically not distinct resetting actions but make access
especially easy to one of the resetting actions described above i.e. by configuring them
to a function key.
MAIN: General
reset USER
[ 003 002 ]
0
1 1: execute
0: don't execute
1: execute
MAIN: Reset
indicat. USER
[ 021 010 ]
0
1
0: don't execute
1: execute
≥1 MAIN: Reset LED
306 020
MAIN: Reset
indicat. EXT
[ 065 001 ]
12Z6115 A_EN
3-1 General reset, LED reset and measured event data reset from the local control panel
m out of n
MAIN: Group
reset 1 USER
[ * ]
0
1 ≥1 &
0: don't execute
1: execute
MAIN: Group
reset 1 EXT
[ * ]
MAIN: Fct.assign.
reset 1
[ * ]
m out of n
12Z61RMB_EN
3-2 "CLEAR" key on the local control panel and, as an example, group resetting of the operating data recording (e.g. as an example for the
reset signal [005 213] OP_RC: Reset record. EXT); further examples for resetting signals generated in this way are:
- [005 210] MAIN: Reset c. cl/tr.c EXT
- [005 211] MAIN: Reset IP,max,st. EXT
- [005 213] OP_RC: Reset record. EXT
- [005 240] MT_RC: Reset record. EXT
- [005 241] OL_RC: Reset record. EXT
- [005 243] FT_RC: Reset record. EXT
- [005 255] MAIN: General reset EXT
- [006 054] COMM3: Reset No.tlg.err.EXT
- [039 122] THRM1: Reset replica EXT
- [040 015] OUTP: Reset latch. EXT
- [040 138] MAIN: Reset latch.trip EXT
- [065 001] MAIN: Reset indicat. EXT
The default for this timer stage is blocked e.g. blocking of the protection device with two
identical faults always occurs independent of the time evolved since the first fault
monitoring signal was issued.
The behavior caused by sporadic faults could lead to an unwanted blocking of the device
if the monitoring signal memory has not been reset in the interim, for example, because
the substation is difficult to reach in wintertime or reading-out and clearing of the
monitoring signal memory via the communication interfaces was not enabled. To defuse
this problem it is suggested to set the function parameter to a specific time duration
period so that the device will be blocked only if the same fault occurs again within this
time period. Otherwise, the device will continue to operate normally after a warm restart.
3 Settings
The following menu points (as compared to software version -601) have been changed
or added.
3.1 Parameters
Selection of such counters and protocols that are to be reset when the
"CLEAR" key is pressed.
Selection of the primary source for date and time synchronization. Available
are COMM1, COMM2/PC, IRIG-B or a binary input for minute signal pulses.
MAIN: BackupSourceTimeSync 103 211
Selection of the backup source for date and time synchronization. Available
are COMM1, COMM2/PC, IRIG-B or a binary input for minute signal pulses.
The backup source is used when there is no synchronization generated by
the primary source after M AIN : T i m e s yn c . ti m e - o u t has elapsed.
MAIN: Time sync. time-out 103 212
3.1.3.1 Global
Setting for the minimum current that must be exceeded in order for the
negative-sequence current to be displayed as a measured operating value.
MAIN: Meas.value rel. Ipos 011 058
Setting for the minimum current that must be exceeded in order for the
positive-sequence current to be displayed as a measured operating value.
MAIN: Fct.assign. reset 1 005 248
The following menu points (as compared to software version -601) have been changed
or added.
4.1 Operation
The counters for counting close and trip commands are reset.
MAIN: Reset IP,max,st.USER 003 033
The operating data memory and the counter for operation signals are reset.
Schneider Electric
35 rue Joseph Monier
92506 Rueil-Malmaison
FRANCE
Phone: +33 (0) 1 41 29 70 00
Fax: +33 (0) 1 41 29 71 00
www.schneider-electric.com Publishing: Schneider Electric
Publication: P630C/EN AD/C21 Version: -602 11/2010
MiCOM P630C
P630C/EN AD/A31
(AFSV.12.11010 D)
Upgrade Documentation
P630C, Changes in software version -602 to -603
In the new versions of the Transformer Differential Protection Device MiCOM P630C,
several enhanced features and changes on existing features have been included.
These are described with reference to the documentation listed below:
References
Released Version Documentation
28.06.2004 P630C -301 -401 -601 Technical Manual
P630C/EN M/B11
(AFSV.12.09380 D)
06.06.2008 P630C -301 -401 -602 Upgrade Documentation
P630C/EN AD/C21
(AFSV.12.10301 D)
1 Overview
Version Changes
P630C-301-401-603 Hardware New Schneider-Electric design for the local control panel (HMI).
Diagram No change
Release: 09.02.2011 Software
PC The following menu point has been removed:
P C : N a m e o f m a n u f a c t u r e r (003 183)
Note:
Compatibility even with older versions of the operating program
continues to be guaranteed.
COMM1 The data point C O M M 1 : M O D B U S p r o t . v a r i a n t (003 214) may
now be used to select between the MODBUS protocol variants Private
and Compatible.
The protocol variant Compatible corresponds to the MODBUS
implementation in the MiCOM Px20 and Px40 protection devices.
The protocol variant Private corresponds to the first implementation of
the MODBUS protocol.
Note:
As before this setting is hidden unless the MODBUS protocol is enabled.
COMM1, The menu points C O M M 1 : N a m e o f m a n u f a c t u r e r (003 161)
COMM2 and C O M M 2 : N a m e o f m a n u f a c t u r e r (103 161) can no longer
be set by using a selection list but, for reasons of compatibility, they may
now be defined as free text. The default is SE but, in individual cases, it
may become necessary to enter texts differing from the default.
Notes:
These parameters can only be set using the operating program and it is
not possible to set them locally using the integrated local control panel
(HMI).
The maximum text length is 8 characters and designations exceeding
this will be truncated.
The parameter C O M M 1 : N a m e o f m a n u f a c t u r e r is hidden
unless an IEC 60870-5 protocol is enabled.
Bug fixing:
An incorrect INF code was used to signal
M A I N : R e s e t i n d i c a t . U S E R with the IEC 60870-5-103 protocol.
Schneider Electric
35 rue Joseph Monier
92506 Rueil-Malmaison
FRANCE
Phone: +33 (0) 1 41 29 70 00
Fax: +33 (0) 1 41 29 71 00
www.schneider-electric.com Publishing: Schneider Electric
Publication: P630C/EN AD/A31 // AFSV.12.11010 D /// P630C-301-401-603 06/2011
Customer Care Centre
http://www.schneider-electric.com/CCC
Schneider Electric
35 rue Joseph Monier
92506 Rueil-Malmaison
FRANCE
Phone: +33 (0) 1 41 29 70 00
Fax: +33 (0) 1 41 29 71 00
www.schneider-electric.com Publishing: Schneider Electric
Publication: P630C/EN M/B31 Version: -601 -602 -603 11/2011