Micro-CTL Automation Sdn. BHD.: Analogue Addressable Fire Alarm System

Download as doc, pdf, or txt
Download as doc, pdf, or txt
You are on page 1of 28

Micro-CTL Automation Sdn. Bhd.

MICTRON 9900

ANALOGUE ADDRESSABLE
FIRE ALARM SYSTEM

1
ENGINEERING SPECIFICATION

TABLE OF CONTENTS Page

1.0 Scope of works ............................................................................................................................................... 3

2.0 General requirements ..................................................................................................................................... 4

3.0 System requirements ...................................................................................................................................... 5

4.0 Functional requirements ................................................................................................................................. 6

4.1 Alarm condition ............................................................................................................................................. 6

4.2 Fault warning condition ................................................................................................................................. 6

5.0 System descriptions ....................................................................................................................................... 7

5.1 System configuration ..................................................................................................................................... 7

5.2 Main Fire Alarm Panel (MFAP) .................................................................................................................... 7

2
5.2.1 System Control Display (Central Controller) ................................................................................ 7

5.2.2 Fire Zone Display ............................................................................................................................ 7

5.2.3 Information Display ........................................................................................................................ 7

5.2.4 Mimic Panel ................................................................................................................................... 8

5.2.5 Battery Charger ............................................................................................................................... 8

5.2.6 24 volts DC battery set ................................................................................................................... 8

5.3 Fire detection sensors, monitoring sensors, control outputs and alarm initiating devices .............................. 8

6.0 Fire detection sensor and alarm initiating device requirements ...................................................................... 9

6.1 Addressable Breakglass / call point ................................................................................................................. 9

6.2 Addressable Smoke detector ............................................................................................................................ 9

6.3 Addressable Heat detector ............................................................................................................................... 9

6.4 Addressable Interface Module (I/O) ................................................................................................................ 9

6.5 Short Circuit Isolator ...................................................................................................................................... 9

6.6 Sprinkler flow switch and sprinkler head ....................................................................................................... 10

6.7 Alarm bell ...................................................................................................................................................... 10

7.0 System features .............................................................................................................................................. 11

8.0 Cable requirements ........................................................................................................................................ 12

9.0 Optional requirements .................................................................................................................................... 12

10.0 Technical specifications ................................................................................................................................. 13-22

11.0 Schedule of prices .......................................................................................................................................... 24

12.0 Appendix A - Deviation lists ......................................................................................................................... 25

13.0 Appendix B - System schematic diagram / configuration .............................................................................. 26

3
ANALOGUE ADDRESSABLE FIRE ALARM SYSTEM

1.0 SCOPE OF WORKS Compliance


Yes/No
1.1The scope of works call for the supply, install, test, commission, handing over in approved
working order and 18 months defect liability maintenance of a complete automatic Analogue
Addressable Fire Alarm System and all sensors/ devices in accordance to the specifications and
as shown on drawings.

The Analogue Addressable Fire Alarm System shall comply to the following rules and regulations.
1.1.1) MS 1745-2
1.1.2) EN 54-2
1.1.3) Requirements of Fire and Rescue Department Malaysia (BOMBA Malaysia)
1.1.4) SIRIM QAS
1.1.5) EMC (Electro Magnetic Compatibility) Test

1.2The contractor shall provide all labour, materials, tools and equipment required to complete the
fire alarm system installation. All materials supplied shall be new, free from defects and of best
quality of their respective kind.

1.3On completion of the installation, the contractor shall be responsible for obtaining written
approval from BOMBA Malaysia and other relevant authorities having jurisdiction, stating that the
completed installation is in proper working order.

1.4The cost of all necessary approvals shall be deemed to be included in the contract price. It is also
the responsibility of the contractor to enter and expedite all correspondence in connection with the
approvals.

1.5Any deviation(s) from the specifications descript hereinafter shall be filled in the deviation list as
provided in Appendix A, stating reasons and alternative solution(s), if any. It is understood that
any deviations from the specifications may result in the disqualification of tender contract.

4
2.0 GENERAL REQUIREMENTS Compliance
Yes/No

2.1The Fire Alarm System shall be analogue addressable type complete with a Main Fire Alarm Panel
(MFAP), addressable fire detection sensors and addressable input and output (I/O) modules, alarm
initiating devices and all necessary audio and visual elements.

2.2All locations of all addressable breakglasses, analogue addressable smoke detectors, analogue
addressable heat detectors, I/O modules, alarm bells/sounders, sprinkler flow switches and
sprinkler heads shown in the drawings are approximate. The contractor shall check the site
locations shown on the accompanying drawings and shall adjust accordingly to suit site
conditions. Superintending Officer or Consulting Engineer’s approval shall be obtained prior to
readjustments or installations.

2.3The contractor shall submit complete detail layout and wiring diagrams, fire alarm system
schematic diagram, main fire alarm panel drawings and fire alarm system console/cabinet layout
to Superintending Officer or Consulting Engineer for approval at least two (2) weeks prior to
commencement of works.

2.4CMS communicator shall be provided for direct linkage, through dedicated telephone line, to
nearest fire brigade station’s (Bomba station) CMS for alarm reporting. It shall be able to accept at
least volt-free contacts provided by the MFAP.

2.5The system shall be designed to be self supervising to detect and to monitor any wire breakage,
unauthorized removal of sensors, to annunciate and to display visual signal at MFAP. It shall be
able to initiate fire fighting operations such as annunciation of fire alarm (bell or siren), signal to
start pressurization fans, shut down or trip the AHU (air handling unit), trip the lifts, etc.

2.6Self-contained storage batteries complete with charger shall be provided to enable the system to be
operational during main power supply and essential power supply failure. During such condition,
battery capacity provided shall be able to maintain system operational for at least 72 hours and 1
hours alarm load condition.

2.7A battery calculation data sheet (refer to Appendix B) shall be submitted for approval.

2.8The battery charger shall be capable of charging a fully discharged battery within 24 hours by
normal charge method to a fully charged condition.

2.9The system shall operate on incoming 240 Volt AC, 50 Hz main power supply and connected to
essential power supply. The incoming main shall then be stepped down to 24 Volt DC for
complete usage and operational by the MFAP.

2.10Location of the MFAP shall be in the fire/security control centre as shown in the drawing and the
exact position shall be determined at site.

2.11Console/cabinet housing for the MFAP shall allow space to house the mimic panel and standby
battery set.

2.12Construction of console/cabinet housing shall have a classification of at least IP 2X.

2.13The MFAP shall consist of System Control Display with 128x64 graphic LCD, Fire Zone Display
with 7 units of 16x2 LCD, and Information Display with built-in printer.

2.14System operation shall be by means of alphanumeric keyboard and system operation manual shall
be submitted for reference.

5
3.0 SYSTEM REQUIREMENTS. The Fire Alarm System shall consist of the followings :- Compliance
Yes/No

3.1A MFAP and it shall be analogue addressable and come complete with console/cabinet housing to
be located at the fire/security control centre.

3.2The MFAP shall consist of System Control Display with 128x64 graphic LCD, Fire Zone Display
with 7 units of 16x2 LCD and Information Display with built-in 40 column printer.

3.3A mimic panel and it shall be located at the console/cabinet housing of the MFAP.

3.4Uninterrupted power supply system (batteries) dedicated for providing power to the system during
mains power supply failure.

3.5Battery charger mounted within the console/cabinet housing of MFAP.

3.6All necessary audio devices and visual indicators at or within the MFAP.

3.7All necessary fire detection and monitoring sensors.


a) Addressable breakglasses/call points
b) Addressable smoke detectors
c) Addressable heat detectors
d) flow switches
e) Interface modules (I/O) for indication points.
f) Short circuit isolators

3.8All necessary control outputs and alarm initiating devices


a) I/O for control output points for lift trip, AHU trip, fan run, etc.
b) I/O for alarm bells/sounders.

3.9Volt-free contacts for CMS (Central Monitoring System) interfacing.

3.10Interfacing facilities for Colour Graphic Computer and Building Automation System (BAS).

3.11All the necessary cabling in conduits or trunking for interconnecting the whole system.

6
4.0 FUNCTIONAL REQUIREMENTS. Compliance
Yes/No

4.1Alarm condition - This is the transition of the decision element (addressable breakglass/call point,
addressable smoke detectors, addressable heat detector, or sprinkler flow switch) from a non-fire
state to the fire state and it shall result in the followings:-

4.1.1 Energization of control outputs such as trip the air handling units (AHU), trip the lift, turn
on pressurization fan and ventilation fan, etc. as required.

4.1.2 Energization of alarm initiating devices such as alarm bells or sounders and the sequence
of energization shall be two-stage.

a) Alarm bells or sounders of the affected floor/level shall be energized permanently. i.e.
continuous ringing/sounding.

b) Alarm bells or sounders of the adjacent floor/level shall be energized intermittently. i.e.
intermittent ringing/sounding (1 second ‘ON’ and 1 second ‘OFF’).

4.1.3 Energization of an alarm bell or sounder adjacent to or within the MFAP.


(usually refer to as MASTER BELL).

4.1.4 Energization of an internal sounder within the MFAP. (usually refer to as BUZZER).

4.1.5 A visible indication of the alarm at the MFAP.

4.1.6 A visible indication of the alarm at the mimic panel.

4.1.7 In the event of multi-zone operation, a separate and continuous visible indication shall be
provided for each alarm zone for items 4.1.5 and 4.1.6.

4.1.8 Automatic energization of printer for hard copy print-out showing the date, time, type of
alarm and location of alarm.

4.2Fault Warning condition - Fault warning shall result in the following :-

4.2.1 An audible warning from a sounder (usually a buzzer) situated at the MFAP and
preferably within it. Such warning sounder shall be distinctive and of a different character
from any fire alarm sounder.

4.2.2 The occurrence of a fault in a different zone, or a different fault in the same zone, while
the sounder is silenced, shall cause the sounder to sound again.

4.2.3 A visible indication on the MFAP.

4.2.4 In the event of multi-zone operation, a separate visible indication shall be provided for
each fault warning zone for item 4.2.2.

4.2.5 The fire alarm condition responses shall not be inhibited by any fault warning unless the
fault itself prevents the giving of such responses.

4.2.6 Fault indications may be suppressed during an alarm condition, but in this case any faults
remaining after the alarm condition has been reset shall cause the fault indication to be
restored.

4.2.7 Automatic energization of printer for hard copy print-out showing the date, time, type of
fault and location of fault.

7
5.0 SYSTEM DESCRIPTIONS. Compliance
Yes/No

5.1System Configuration - A typical system schematic diagram of an Analogue Addressable Fire


Alarm System shall be as shown in Appendix C. It shall consist of two (2) basic portions as
detailed in items 5.1.1, and 5.1.2.

5.1.1 A Main Fire Alarm Panel (MFAP).

5.1.2 All fire detection sensors, monitoring sensors, control outputs, and alarm initiating
devices.

5.2Main Fire Alarm Panel (MFAP) - This shall be the central controller. All information processing,
monitoring of input points, and controlling of output points shall be done here. The processed data
shall then be converted to understandable audio and visual information. It shall consist of the
following essential components :-

1) System Control Display - Central controller


2) Fire Zone Display - LCD and LED for alarm, fault and disable indications
3) Information Display with built-in 40 column printer
4) Mimic panel,
5) Battery charger, and
6) 24 V DC battery set

5.2.1 System Control Display (Central controller) - This shall form the ‘brain’ of the complete
system. All information shall be processed and displayed into meaningful messages at
LED and LCD panels, mimic panel, and appropriate print-out at printer. It shall consist of
the following elements.

a) LED indicators for


- Power ON
- System FAULT
- AC Power FAULT
- Battery FAULT
- Earth FAULT
- FIRE, FAULT and DISABLE
- AUTO and MANUAL Evacuate
- Sounder Disable
- General Test
- Miscellaneous Status
- Delay to Output Override
b) TEST LAMP/LCD, TEST BUZZER, and SILENCE BUZZER keys
c) LCD - 128x64 graphic display
d) "0 - 9" alphanumeric and scroll keys
e) CONTROL ACCESS keyswitch

5.2.2 Fire Zone Display. It shall consist of the following elements.

a) 7 units of 16x2 LCD


b) LEDs for FIRE, FAULT, DISABLE and QUEUE

5.2.3 Information Display - It shall contain


a) System operation instructions both in English and Bahasa
b) Built-in 40 column printer - This shall be the event logger for permanent recording
of any event happening. Every event print-out shall show the date and time, zone and/or
location of the event, type of event, and status of event.

8
Compliance
Yes/No
5.2.4 Mimic panel - This shall consist of all floor plans and section of the building, printing on
a perspex plastic sheet. It shall be multi-colour. There shall be LEDs on the mimic floor
plans to indicate location of each alarm zone. As a general rule, colour of the areas shall
be as follows :-

a) All escape staircases - yellow


b) All M & E rooms relating to fires (eg. Fire pump room, Fan room, etc) - red
c) All M & E rooms not relating to fires (eg. AHU room, Computer room, etc) - orange
d) All lifts and lift lobbies - brown
e) All other enclosed areas surrounded by walls - blue
f) All lines, wordings and symbols - black
g) Background - white

5.2.5 Battery charger and power supply unit - This shall form the source of power supply for
the complete fireman intercom system. The battery charger shall be able to provide boost
charge. Input voltage to the charger shall be 240 volts AC, 50 Hz. Output voltage from
the charger shall be regulated to 27.5-28.5 volts DC depending on type of battery used.
The power supply unit shall convert the incoming 27.5-28.5 volts DC to other voltages
required by other components and modules within the system.
The charger shall be capable of charging a fully discharged battery within 24 hours by
normal charge method to a fully charged condition. It shall be protected against short
circuit with automatic over-current shutdown. The charger shall be of linear, constant
voltage charging type to prevent unnecessary damages or shortening the lifespan of
battery. When the battery is fully charged, the charger shall automatically switch to float
charging.

5.2.6 24 volts DC battery set - This shall form as backup/standby power supply in case of 240
V main AC failure. It shall be sealed lead acid type of sufficient capacity to maintain the
system operational for at least 72 hours in case of 240 V mains AC failure. In addition, it
shall be capable of supplying full emergency evacuation alarm load of at least 1 hour. The
battery set shall be mounted in the lower compartment of the console/cabinet housing and
the charging equipment shall be installed above it and readily accessible.

5.3Fire Detection Sensors, Monitoring Sensors, Control Outputs and Alarm Initiating Devices - These
shall be the reporting and energizing elements to the MFAP.

5.3.1 Fire detection sensors - These shall form the whole part of alarm zones. Depending on
design requirements, they shall consist of addressable smoke detectors, addressable heat
detectors, flow switches, and addressable breakglasses/call points.

5.3.2 Monitoring sensors - These shall form the whole part of status indications. Depending on
design requirements, they shall consist of fire pump indications, fire tank indications,
CO2/FM 200 indications, gen-set indications, butterfly/subsidiary valve indications,
AHU run indications, fan trip indications, and etc.

5.3.3 Control outputs - These shall form the whole part of the events/equipments energization
sequence. Depending on design requirements, they shall consist of AHU trip, lift trip, fan
run, fire damper open, magnetic door close, and etc.

5.3.4 Alarm initiating devices - These shall form the whole part of alert/evacuation
energization sequence. Depending on design requirements, they shall consist of alarm
bells, sirens, flashing lights, and other forms of sounders and visual elements.

9
6.0 FIRE DETECTION SENSOR AND ALARM INITIATING DEVICE REQUIREMENTS Compliance
Yes/No

6.1Addressable breakglass/call point


- It shall be provided with EN 54-11, MS 1745-11 and BOMBA approvals.
- It shall be bright red in colour, flushed/surface mounting type.
- It shall be constructed from shatterproof and corrosion resistance self extinguishing plastic case
suitable for 20 mm conduit entry and a breakable glass with appropriate label/symbol.
- It shall be suitable for operation on 24 V DC.
- It shall be fixed at a height to be determined on site and generally at 1500mm above floor level.
- For outdoor installation, it shall be of weatherproof type to IP 54.
- Address setting shall be DIP switch type or soft addressing type.

6.2Addressable smoke detector


- It shall be provided with EN 54-7 and BOMBA approvals.
- It shall be photoelectric/optical type.
- Separate mounting base shall be required for the detector.
- Colour of the detector and base shall be off-white and constructed from corrosion resistant self
extinguishing plastic.
- It shall be suitable for operation on 24 V DC.
- It shall be suitable for protecting an area of up to 100 sq. m. at a height of up to 12 m.
- 2 LED indicators shall be provided in each detector which illuminates on triggering.
- Address setting shall be DIP switch type or soft addressing type.
- It shall be able to provide analogue signal.

6.3Addressable heat detector


- It shall be provided with EN 54-5 and BOMBA approvals.
- It shall be of “rate of rise and fix temperature” combined type.
- Separate mounting base shall be required for the detector.
- Colour of the detector and base shall be off-white and constructed from corrosion resistant self
extinguishing plastic.
- It shall be suitable for operation on 24 V DC.
- It shall be suitable for protecting an area of up to 50 sq. m. at a height of up to 13 m.
- 2 LED indicators shall be provided in each detector which illuminates on triggering.
- Address setting shall be DIP switch type or soft addressing type.
- It shall be able to provide analogue signal.

6.4Addressable interface module (I/O)


- It shall be provided with EN 54-18 and BOMBA approvals.
- It shall be suitable for operation on 24 V DC.
- It shall be housed inside a weatherproof IP 54 plastic casing.
- It shall be capable of accepting up to 4 input points, or 1 input & 1 output.
- Address setting shall be DIP switch type or soft addressing type.

6.5Addressable Short circuit isolator base


- It shall be installed between every 20 detectors.
- It shall be suitable for operation on 24 V DC.
- In case of short circuit, only the affected segment shall be disabled.
- It shall also act as base for detectors.

10
Compliance
Yes/No
6.6Sprinkler flow switch and sprinkler head
- It shall be provided with UL and BOMBA approvals.
- The sprinkler flow switch shall be paddle type, fitted with a 5 second solid state delay relay to
prevent false alarm caused by water surge in the system.
- The flow switch shall be installed at location such that it is at least 5 times diameter of pipe away
from the butterfly isolation valve.
- The sprinkler head shall be glass bulb type and in general, the temperature rating shall be 68
degree C (155 degree F).
- Unless otherwise approved, the deflector shall be of universal type to enable the sprinkler to be
suitable for operation in either upright or pendant position.
- The sprinkler head shall produce a spherical discharge with a proportion of water being thrown
upwards. It shall be chrome/bronze plated finishing and complete with colour matched
escutcheon.

6.7Alarm bell
- It shall be provided with EN 54-3, MS 1745-3 and BOMBA approvals.
- It shall be motorized type with low current consumption.
- Colour of the bell shall be red, 150 mm in diameter and surface mounted type.
- It shall be constructed from pressed steel with stove enamelled finishing.
- The decibel rating of the bell shall be at least 90db with respect to the surrounding sound level.
- It shall be installed 2.5 m above floor level.
- It shall be suitable for operation on 24 V DC.
- For outdoor installation, it shall be of weatherproof type to IP 54.

11
7.0 SYSTEM FEATURES Compliance
Yes/No

7.1The MFAP shall be analogue addressable type.

7.2A standard MFAP shall have a capacity to handle up to 16 loops and 600 fire zones.

7.3A 128x64 LCD graphic arranged in "ATM" format shall be provided.

7.4System operation shall be through alphanumeric keyboard.

7.5Real time event memory of up to 1000 alarm log and 600 general fault/disable log shall be
provided.

7.6System modules shall be interchangeable from one to another.

7.7The MFAP shall be able to interface to 40 column printer for event printing.

7.8The MFAP shall be able to interface to BAS (Building Automation System) through RS 232 serial
communication or volt-free contacts.

7.9The MFAP shall be able to interface to CMS (Central Monitoring System) for direct linkage to
Bomba (fire authority) through volt-free contacts.

7.10The MFAP shall be able to interface to colour graphic computer for dynamic graphic display of
alarm occurrence. A genuine graphic software (WINFSS) with certificate shall be provided.

7.11A real time clock shall be incorporated.

7.12Password/access level shall be incorporated for security purpose.

7.13Fire Zone Display shall consists of 7 units of 16x2 LCD and separate LEDs for displaying Fire ,
Fault and Disable conditions.

7.14System/operation instruction on the 128x64 LCD graphic display shall be able to display text in
Bahasa Malaysia.

7.15Capability for system interlinking using fibre optic cable shall be provided. All necessary fibre
optic converter, modem, patch panel, etc shall be provided for complete system functioning.

12
8.0 CABLE REQUIREMENTS Compliance
Yes/No

8.1A typical system wiring diagram shall be as shown in Appendix B.

8.2Looping cables from MFAP to detectors/devices and back to the MFAP (Ring circuit)shall be as
follows :-

8.2.1 For Indoor Installation,

- 2 x 1.5 mm-sq PVC cables and non-twisted for up to 1.2km. OR


- 2 x 1.5 mm-sq PVC cable and twisted for up to 2km.

8.2.2 For Outdoor Installation,

- 2 x 1.5 mm-sq armoured cables and non-twisted for up to 1.2km. OR


- 2 x 1.5 mm-sq armoured cable and twisted for up to 2km.

8.3Looping cable size chosen for bells and controls power supply shall be such that during alarm
bells ringing and control outputs energisation, the voltage reaching the furthest bell and control
point shall not be less than 22 volts DC.

9.0 OPTIONAL REQUIREMENTS

9.1Colour Graphic Computer - The software provided shall be able to operate, identify and display
alarm and fault conditions on the dynamic floor plans. It shall consist of a CPU, RAM., DVD
Drive, Hard Disk, Serial and Parallel Cards, Keyboard, Power Supply, Colour Monitor, UPS for
20 minutes and other necessary components to form a complete system.

9.2Lightning Surge Arrestor - Appropriate lightning surge arrestor shall be provided for 240 VAC
line, 24 VDC power line and looping signal data line.

13
10.0 TECHNICAL SPECIFICATIONS

10.1 Main Fire Alarm Panel

10.1.1 Manufacturer / Country --------- Micro-CTL Automation Sdn Bhd / Malaysia

10.1.2 Brand ------------------------------ ---- Mictron

10.1.3 Model -------------------------------- ---- 9900

10.1.4 Part Number ----------------------------- AXP-M9900

10.1.5 Operating Voltage ---------------- Input 220-240VAC/50Hz, Output 24VDC

10.1.6 Operating Temperature --------- ---- 0 – 45 Degree C

10.1.7 Operating Humidity -------------- 95% RH (non – condensation)

10.1.8 Panel Construction ---------------- ---- Mild Steel

10.1.9 Finishing ----------------------- ---- Epoxy powder coated paint, oven baked

10.1.10 Colour ------------------------- ---- red

10.1.11 Dimension ----------------------- --- 720mm (W)x430mm(H)x150mm(D)

10.1.12 Weight --------------------------- 18.6kg (exclude battery)

10.1.13 Approved Standard ------ ----- EN 54-2, MS 1745-2

10.2 Power Supply and Charger

11.3.1Manufacturer / Country --------- ---- Micro-CTL Automation Sdn Bhd / Malaysia

11.3.2Brand ------------------------------ ---- Mictron

11.3.3Type -------------------------------- ---- Constant Voltage and Current

11.3.4Input Voltage --------------------- ---- 220 - 240VAC, 50Hz, Single phase

11.3.5Output Voltage ------------------- ---- 27.5VDC, 5A maximum

11.3.6Type of power Switches --------- ---- AC on, CPU on, RPPU/LC on, BELL on

11.3.7Operating Temperature ---------- ---- 0 – 45 degree C

11.3.8Operating Humidity -------------- ---- 95% RH (non-condensation)

14
10.3 Colour Mimic Panel

10.3.1Manufacturer / Country --------- ---- Micro-CTL Automation Sdn Bhd/ Malaysia

10.3.2Brand ------------------------------ ---- Mictron

10.3.3Model ------------------------------ M9900 – mimic

10.3.4Type -------------------------------- ---- Colour printing or silkscreen

10.3.5Material ---------------------------- ---- Perspex sheet

10.3.6Operating Voltage ---------------- 24VDC

10.3.7Operating Temperature ---------- ---- 0 – 45 degree C

10.3.8Operating Humidity -------------- ---- 95% RH (non-condensation)

10.4 Addressable Breakglass /Call


Point

10.4.1Manufacturer / Country --------- Micro-CTL Automation Sdn Bhd / Malaysia

10.4.2Brand ------------------------------- Mictron

10.4.3Model ------------------------------ Series AX

10.4.4Part Number ------------------------ AX-9BG

10.4.5Quiescent Current ------------------ 800 uA

10.4.6Alarm Current ----------------------- 1.6 mA

10.4.7Operating Voltage ------------------ 18 - 28 VDC

10.4.8Type -------------------------------- Non-resettable

10.4.9Temperature Range --------------- -20 to 70 degree C

10.4.10Operating Humidity --------------- 95% RH (non-condensation)

10.4.11Weight ------------------------------- 140 g

10.4.12Material ------------------------------ ABS

10.4.13Dimension (mm) -------------------- 88mm x 88mm x 59mm

10.4.14Colour -------------------------------- red

10.4.15Approved Standard ----------------- EN 54-11, MS 174-11

15
10.5 Addressable Smoke Detector

10.5.1Manufacturer / Country --------- Micro-CTL Automation Sdn Bhd / Malaysia

10.5.2Brand ------------------------------- Mictron

10.5.3Model ------------------------------ Series AX

10.5.4Part Number ------------------------ AX-9SL

10.5.5Quiescent Current ------------------ 500 uA

10.5.6Alarm Current ----------------------- 7 mA

10.5.7Operating Voltage ------------------ 17 - 28 VDC

10.5.8Type -------------------------------- Photoelectric

10.5.9Temperature Range --------------- -10 to 50 degree C

10.5.10Operating Humidity --------------- 95% RH (non-condensation)

10.5.11Weight ------------------------------- 150 g with base

10.5.12Material ------------------------------ ABS

10.5.13Dimension (mm) -------------------- 100mm (diameter) x 46mm (depth) with base

10.5.14Colour -------------------------------- White

10.5.15Approved Standard ----------------- EN 54-7

10.5.16Analogue capability ---------------- Yes

16
10.6 Addressable Heat Detector

10.6.1Manufacturer / Country --------- Micro-CTL Automation Sdn Bhd / Malaysia

10.6.2Brand ------------------------------- Mictron

10.6.3Model ------------------------------ Series AX

10.6.4Part Number ------------------------ AX-9HL

10.6.5Quiescent Current ------------------ 500 uA

10.6.6Alarm Current ----------------------- 7 mA

10.6.7Operating Voltage ------------------ 17 - 28 VDC

10.6.8Type -------------------------------- ROR & Fixed Temperature

10.6.9Temperature Range --------------- -10 to 50 degree C

10.6.10Operating Humidity --------------- 95% RH (non-condensation)

10.6.11Weight ------------------------------- 150 g with base

10.6.12Material ------------------------------ ABS

10.6.13Dimension (mm) -------------------- 100mm (diameter) x 46mm (depth) with base

10.6.14Colour -------------------------------- White

10.6.15Approved Standard ----------------- EN 54-5

10.6.16Analogue capability ---------------- Yes

17
10.7 Input Interface Module

10.7.1Manufacturer / Country --------- Micro-CTL Automation Sdn Bhd / Malaysia

10.7.2Brand ------------------------------- Mictron

10.7.3Model ------------------------------ Series AX

10.7.4Part Number ------------------------ AXM-1ZV-B

10.7.5Quiescent Current ------------------ 1.4 mA

10.7.6Alarm Current ----------------------- N/A

10.7.7Operating Voltage ------------------ 20 - 28 VDC

10.7.8Type -------------------------------- 4-inputs

10.7.9Temperature Range --------------- 0 to 50 degree C

10.7.10Operating Humidity --------------- 95% RH (non-condensation)

10.7.11Weight ------------------------------- 180 g with enclosure

10.7.12Material ------------------------------ ABS

10.7.13Dimension (mm) -------------------- 110mm x 110mm x 55mm

10.7.14Colour -------------------------------- Light grey

10.7.15Approved Standard ----------------- EN 54-18

18
10.8 Output Interface Module

10.8.1Manufacturer / Country --------- Micro-CTL Automation Sdn Bhd / Malaysia

10.8.2Brand ------------------------------- Mictron

10.8.3Model ------------------------------ Series AX

10.8.4Part Number ------------------------ AXM-1ZV-A

10.8.5Quiescent Current ------------------ 1.4 mA

10.8.6Alarm Current ----------------------- 3-7 mA (Output on)

10.8.7Operating Voltage ------------------ 20 - 28 VDC

10.8.8Type -------------------------------- 1-output /sounder and 1-input

10.8.9Temperature Range --------------- 0 to 50 degree C

10.8.10Operating Humidity --------------- 95% RH (non-condensation)

10.8.11Weight ------------------------------- 180 g with enclosure

10.8.12Material ------------------------------ ABS

10.8.13Dimension (mm) -------------------- 110mm x 110mm x 55mm

10.8.14Colour -------------------------------- Red

10.8.15Approved Standard ----------------- EN 54-18

19
10.9 Short Circuit Isolator

10.9.1Manufacturer / Country --------- Micro-CTL Automation Sdn Bhd / Malaysia

10.9.2Brand ------------------------------- Mictron

10.9.3Model ------------------------------ Series AX

10.9.4Part Number ------------------------ AX-9SCI

10.9.5Quiescent Current ------------------ 30 uA

10.9.6Alarm Current ----------------------- 2 mA

10.9.7Operating Voltage ------------------ 17 - 28 VDC

10.9.8Type -------------------------------- Resettable

10.9.9Temperature Range --------------- -20 to 70 degree C

10.9.10Operating Humidity --------------- 95% RH (non-condensation)

10.9.11Weight ------------------------------- 25 g with enclosure

10.9.12Material ------------------------------ ABS

10.9.13Dimension (mm) -------------------- 100mm (diameter)x 20mm (depth)

10.9.14Colour -------------------------------- White

10.9.15Approved Standard ----------------- N/A

20
10.10 Sprinkler Flow Switch

10.10.1Manufacturer / Country ---------

10.10.2Brand -------------------------------

10.10.3Model ------------------------------

10.10.4Part Number ------------------------

10.10.5Operating Voltage ------------------

10.10.6Type --------------------------------

10.10.7Temperature Range ---------------

10.10.8Operating Humidity ---------------

10.10.9Weight -------------------------------

10.10.10Material ------------------------------

10.10.11Dimension (mm) --------------------

10.10.12Colour --------------------------------

10.10.13Approved Standard -----------------

10.11 Sprinkler Head

10.11.1Manufacturer / Country ---------

10.11.2Brand -------------------------------

10.11.3Model ------------------------------

10.11.4Part Number ------------------------

10.11.5Operating Voltage ------------------

10.11.6Type --------------------------------

10.11.7Temperature Range ---------------

10.11.8Operating Humidity ---------------

10.11.9Weight -------------------------------

10.11.10Material ------------------------------

10.11.11Dimension (mm) --------------------

10.11.12Colour --------------------------------

10.11.13Approved Standard -----------------

21
10.12 6" Alarm Bell

10.12.1Manufacturer / Country --------- Micro-CTL Automation Sdn Bhd / Malaysia

10.12.2Brand ------------------------------- Mictron

10.12.3Model ------------------------------ Series C

10.12.4Part Number ------------------------ C-9BL

10.12.5Alarm Current ------------------ 30 mA

10.12.6Sound Output ---------------------- 95 dBA

10.12.7Operating Voltage ------------------ 20 - 28 VDC

10.12.8Type -------------------------------- DC Motor

10.12.9Temperature Range --------------- -20 to 60 degree C

10.12.10Operating Humidity --------------- 95% RH (non-condensation)

10.12.11Weight ------------------------------- 764 g

10.12.12Material ------------------------------ High Quality Steel

10.12.13Dimension (mm) -------------------- 150mm (diameter)x 56mm (depth)

10.12.14Colour -------------------------------- Red

10.12.15Approved Standard ----------------- EN 54-3, MS 1745-3

22
10.13 Lightning Surge Arrestor
(240 VAC)

10.13.1Manufacturer / Country --------- Dehn & Sohne / Germany

10.13.2Brand ------------------------------- Dehn

10.13.3Model ------------------------------ DG T 275 & DGP CT 255

10.13.4Part Number ------------------------ 900 650 & 900 133

10.13.5Maximum AC Voltage ----------- 275 V & 255 V

10.13.6Maximum Discharge Current ---- 20 kA (8/20uS) & 40 kA (8/20 uS)

10.13.7Response Time -------------------- <= 25 nS & <= 100 uS

10.13.8Type -------------------------------- Type 2 / Class 2

10.13.9TOV Voltage ----------------------- 335 V / 5 Sec & 1200 V / 200 mS

10.13.10Temperature Range --------------- -40 deg C to +80 deg C

10.13.11Material ------------------------------ Red Thermoplastic

10.13.12Approved Standard ----------------- IEC 61643-1

10.14 Lightning Surge Arrestor


(24 VDC Power Line)

10.14.1Manufacturer / Country --------- Dehn & Sohne / Germany

10.14.2Brand ------------------------------- Dehn

10.14.3Model ------------------------------ DR M 2P 30

10.14.4Part Number ------------------------ 953 201

10.14.5Maximum DC Voltage ----------- 30 V

10.14.6Maximum Discharge Current ---- 2 kA (8/20uS)

10.14.7Response Time -------------------- <= 100 nS

10.14.8Type -------------------------------- Type 3 / Class 3

10.14.9Temperature Range --------------- -40 deg C to +80 deg C

10.14.10Material ------------------------------ Red Thermoplastic

10.14.11Approved Standard ----------------- IEC 61643-1

23
10.15 Lightning Surge Arrestor
(24 VDC Signal/Data Line)

10.15.1Manufacturer / Country --------- Dehn & Sohne / Germany

10.15.2Brand ------------------------------- Dehn

10.15.3Model ------------------------------ DCO RK ME 24

10.15.4Part Number ------------------------ 919 921

10.15.5Maximum DC Voltage ----------- 33 V

10.15.6Maximum Discharge Current ---- 10 kA (8/20uS)

10.15.7Series Impedance per Line ------- 1.8 ohms

10.15.8Type -------------------------------- Type 2

10.15.9Temperature Range --------------- -40 deg C to +80 deg C

10.15.10Material ------------------------------ Polyamide PA 6.6

10.15.11Approved Standard ----------------- IEC 61643-21

10.16 OPTIONAL ITEMS

Colour Graphic Computer

10.16.1Manufacturer ---------------------

10.16.2Brand -------------------------------

10.16.3Model ------------------------------

10.16.4Type of Processor ----------------

10.16.5Colour Monitor size --------------

10.16.6Other features ----------------------

24
11.0 SCHEDULE OF PRICES

11.1 MAIN FIRE ALARM PANEL (MFAP) QTY UNIT PRICE TOTAL
(RM.) (RM.)

11.1.1CPU central controller, loop controller , power


supply and charger, built-in printer, and software.

11.1.2Mimic panel complete with multi-colour plans,


LEDs and mimic LED driver cards.

11.1.3 Sealed lead acid battery AH 24 V DC

11.2 Console housing for items 11.1.1 to 11.1.3


(optional)

11.3 Addressable breakglasses/call points

11.4 Addressable smoke detectors

11.6 Addressable heat detectors

11.7 Addressable interface modules (I/O)

11.8 Short circuit isolators

11.9 Sprinkler flow switches

11.10 Sprinkler heads complete with escutcheons

11.11 Sprinkler heads without escutcheons

11.12 Lightning surge arrestors

11.13 Alarm bells

11.14 Lump sum wiring, conduits and/or trunkings

11.15 Lump sum installation work,inclusive of testing


and commissioning.

11.16 Optional item.

a) Colour graphic computer complete with all


necessary hardware and software.

TOTAL

25
12.0 APPENDIX A - DEVIATION LISTS

Items deviated Reason and alternative solution(s)

26
13.0 APPENDIX B - SYSTEM SCHEMATIC DIAGRAM / CONFIGURATION.

27