11kV Power Cable Sizing 15.10.10

Download as pdf or txt
Download as pdf or txt
You are on page 1of 12

NATIONAL CONTRACTING CO. LTD.

,
T&D Division
Kingdom Of Saudi Arabia

PROJECT : KPLC, KENYA DOC. NO: NCC/KPLC/LAN/E-DOC-S-004

TITLE : 11kV POWER CABLE SIZING CALCULATION Date : 15.10.10 Revision : R0

1.0.0 DESIGN INPUTS

1.1.0 LOAD DETAILS

1.1.1 Load Description = 11kV BUS

1.1.2 Fed by From = 23MVA Transformer LV side


To 11kV Switchgear
1.2.0 INPUTS

1.2.1 120% of Maximum Rating of Transfomer (L) = 27600 kVA


(As per KPLC spec. cl. 2.7.3)

122
1.2.2 Voltage rating of Switchgear (v) = 11 kV

1.2.3 Load power factor (Cos Qr) = 0.8 (Assumed)

1.2.4 Full load current (FLC) = 1448.6 A

1.2.5 Route length of HT Switchgear cable (l) = 30 mtrs

1.2.6 Fault level (If) = 25 kA


(As per spec. cl. 3.1.1)

1.2.7 Fault current withstand time (t) = 3 sec

2.0.0 ENVIRONMENTAL DETAILS

2.1.1 Design Ambient Temperature (As per spec. cl. 3.1.1) = 40 deg C

3.0.0 CABLE DATA

3.1.1 Voltage Rating = 11 (6/10) kV

3.1.2 No. of Cores = 1

3.1.3 Cross Section Area (A) = 630 Sq.mm

3.1.4 Conductor Material = Copper

Sheet 1 of 12
NATIONAL CONTRACTING CO. LTD.,
T&D Division
Kingdom Of Saudi Arabia

PROJECT : KPLC, KENYA DOC. NO: NCC/KPLC/LAN/E-DOC-S-004

TITLE : 11kV POWER CABLE SIZING CALCULATION Date : 15.10.10 Revision : R0

3.1.5 Insulation = XLPE, Armoured

3.1.6 Catalogue Reference = PRIMECAB kables

3.1.7 Current Carrying Capacity in air (Ic) = 784 A

3.1.8 Resistance of Cable Selected at 90 deg C (r) = 0.0398 ohms/Km

3.1.9 Reactance of Cable Selected (x) = 0.094 ohms/Km

4.0.0 CHECKING OF THERMAL WITHSTAND CAPABILITY

4.1.0 Laid in Cable trench

4.1.1 Derating factor for variation in air temperature = 1


at 40 deg C

4.1.2 Group derating factor for single core cables


= 0.95
laid in trefoil formation

4.1.3 Overall derating factor considered for the cable (df) = 1 x 0.95
= 0.95

4.1.4 Nominal current carrying capacity of cable in air (Ic) = 784 A

4.1.5 Calculation of De-rated current carrying capacity

4.1.6 Derated current carrying capacity of cable in air (Id = df x lc) = 744.8 A

Therefore, No. of runs required (N=FLC/Id) = 1448.6 / 744.8


= 1.944952 Runs

4.1.7 No. of runs selected (N) = 2 Runs

From the above, it is seen that the thermal current carrying capacity of
2runs of 1C x 630 Sq.mm XLPE Ar. Cu cable is sufficient to carry full load
current of switchgear. Hence the proposed cable is safe.

Sheet 2 of 12
NATIONAL CONTRACTING CO. LTD.,
T&D Division
Kingdom Of Saudi Arabia

PROJECT : KPLC, KENYA DOC. NO: NCC/KPLC/LAN/E-DOC-S-004

TITLE : 11kV POWER CABLE SIZING CALCULATION Date : 15.10.10 Revision : R0

5.0.0 CHECKING OF SHORT CIRCUIT WITHSTAND CAPABILITY

k20x c x ρ 1+α20 (θe - 20oC) 0.5


A x x ln
α20 1+α20 (θb - 20oC)
Isc =
t0.5

(As per IEC 865) Part-1 Pg no 113


Where
Ar is the cross section area required in cm2
k20 = 5.60E+07 is the reciprocal of resistivity at 20oC in 1/ohm-metre
o
c = 390 is the thermal capacity per unit weight in J/(Kg C)
3
ρ = 8900 specific weight of Aluminium in Kg/m
α20 = 0.004 is the thermal coefficient of resistivityy at 20°C in 1/°C
θe = 200 is the conductor temp. at the end of short circuit in °C
θb = 85 is the conductor temp. at the beginning of short circuit in °C

56000000 x 390 x 8900 1 + 0.0039 (200 - 20) 0.5


630 x x ln
0.004 1 + 0.0039 (85 - 20)
Isc =
3 ^0.5

Isc = 44.9 kA

From the above, it is seen that 2runs of 1C x 630 Sq.mm XLPE Ar. Cu cable can
safely withstand fault level of 25kA for 3 seconds. Hence the cable selected
for fault current is safe.

Sheet 3 of 12
NATIONAL CONTRACTING CO. LTD.,
T&D Division
Kingdom Of Saudi Arabia

PROJECT : KPLC, KENYA DOC. NO: NCC/KPLC/LAN/E-DOC-S-004

TITLE : 11kV POWER CABLE SIZING CALCULATION Date : 15.10.10 Revision : R0

6.0.0 CHECKING OF STEADY STATE VOLTAGE DROP AT SWITCHGEAR TERMINAL


UNDER FULL LOAD CONDITION

6.1.0 Voltage drop from 11kV Termination end to 11kV Switchgear terminal

Voltage drop (Vd) = FLC x ((Rc.CosQr)+(Xc.SinQr)) / N

= 1448.6 x ((0.001194*0.8) + (0.00282*0.6)) / 2

= 1.92 volts

= 0.010 %

611
6.1.1 Allowed voltage drop from 66/11kV Power = 3 %
Transformer to 11kV Switchgear as per good engineering practice.

From the above, it is seen that, the steady state voltage drop is within the limit.
Hence the proposed cable of 2runs of 1C x 630 Sq.mm XLPE Ar. Cu, is safe.

7.0.0 SUMMARY

a) Cable Selected = 11 (6/10) kV, 1 Core x 630


Sq.mm XLPE, Armoured

b) No. of runs = 2 run

c) Max. Steady State Voltage Drop (%) = 0.010 %

Sheet 4 of 12
NATIONAL CONTRACTING CO. LTD.,
T&D Division
Kingdom Of Saudi Arabia

PROJECT : KPLC, KENYA DOC. NO: NCC/KPLC/LAN/E-DOC-S-004

TITLE : 11kV POWER CABLE SIZING CALCULATION Date : 15.10.10 Revision : R0

1.0.0 DESIGN INPUTS

1.1.0 LOAD DETAILS

1.1.1 Load Description = 11kV BUS

1.1.2 Fed by From = 11kV Switchgear


To 100kVA Station transformer
1.2.0 INPUTS

1.2.1 120% of Maximum Rating of Transfomer (L) = 120 kVA


(As per KPLC spec. cl. 2.7.3)

122
1.2.2 Voltage rating of Switchgear (v) = 11 kV

1.2.3 Load power factor (Cos Qr) = 0.8 (Assumed)

1.2.4 Full load current (FLC) = 6.3 A

1.2.5 Route length of HT Switchgear cable (l) = 30 mtrs

1.2.6 Fault level (If) = 25 kA


(As per spec. cl. 3.1.1)

1.2.7 Fault current withstand time (t) = 0.1 sec

2.0.0 ENVIRONMENTAL DETAILS

2.1.1 Design Ambient Temperature (As per spec. cl. 3.1.1) = 40 deg C

3.0.0 CABLE DATA

3.1.1 Voltage Rating = 11 (6/10) kV

3.1.2 No. of Cores = 1

3.1.3 Cross Section Area (A) = 70 Sq.mm

3.1.4 Conductor Material = Copper

Sheet 5 of 12
NATIONAL CONTRACTING CO. LTD.,
T&D Division
Kingdom Of Saudi Arabia

PROJECT : KPLC, KENYA DOC. NO: NCC/KPLC/LAN/E-DOC-S-004

TITLE : 11kV POWER CABLE SIZING CALCULATION Date : 15.10.10 Revision : R0

3.1.5 Insulation = XLPE, Armoured

3.1.6 Catalogue Reference = PRIMECAB kables

3.1.7 Current Carrying Capacity in air (Ic) = 196 A

3.1.8 Resistance of Cable Selected at 90 deg C (r) = 0.342 ohms/Km

3.1.9 Reactance of Cable Selected (x) = 0.105 ohms/Km

4.0.0 CHECKING OF THERMAL WITHSTAND CAPABILITY

4.1.0 Laid in Cable trench

4.1.1 Derating factor for variation in air temperature = 1


at 40 deg C

4.1.2 Group derating factor for single core cables


= 0.9
laid in trefoil formation

4.1.3 Overall derating factor considered for the cable (df) = 1 x 0.9
= 0.9

4.1.4 Nominal current carrying capacity of cable in air (Ic) = 196 A

4.1.5 Calculation of De-rated current carrying capacity

4.1.6 Derated current carrying capacity of cable in air (Id = df x lc) = 176.4 A

Therefore, No. of runs required (N=FLC/Id) = 6.3 / 176.4


= 0.035714 Runs

4.1.7 No. of runs selected (N) = 1 Runs

From the above, it is seen that the thermal current carrying capacity of
1runs of 1C x 70 Sq.mm XLPE Ar. Cu cable is sufficient to carry full load
current of switchgear. Hence the proposed cable is safe.

Sheet 6 of 12
NATIONAL CONTRACTING CO. LTD.,
T&D Division
Kingdom Of Saudi Arabia

PROJECT : KPLC, KENYA DOC. NO: NCC/KPLC/LAN/E-DOC-S-004

TITLE : 11kV POWER CABLE SIZING CALCULATION Date : 15.10.10 Revision : R0

5.0.0 CHECKING OF SHORT CIRCUIT WITHSTAND CAPABILITY

k20x c x ρ 1+α20 (θe - 20oC) 0.5


A x x ln
α20 1+α20 (θb - 20oC)
Isc =
t0.5

(As per IEC 865) Part-1 Pg no 113


Where
Ar is the cross section area required in cm2
k20 = 5.60E+07 is the reciprocal of resistivity at 20oC in 1/ohm-metre
o
c = 390 is the thermal capacity per unit weight in J/(Kg C)
3
ρ = 8900 specific weight of Aluminium in Kg/m
α20 = 0.004 is the thermal coefficient of resistivityy at 20°C in 1/°C
θe = 200 is the conductor temp. at the end of short circuit in °C
θb = 85 is the conductor temp. at the beginning of short circuit in °C

56000000 x 390 x 8900 1 + 0.0039 (200 - 20) 0.5


70 x x ln
0.004 1 + 0.0039 (85 - 20)
Isc =
0.1 ^0.5

Isc = 27.3 kA

From the above, it is seen that 1runs of 1C x 70 Sq.mm XLPE Ar. Cu cable can
safely withstand fault level of 25kA for 3 seconds. Hence the cable selected
for fault current is safe.

Sheet 7 of 12
NATIONAL CONTRACTING CO. LTD.,
T&D Division
Kingdom Of Saudi Arabia

PROJECT : KPLC, KENYA DOC. NO: NCC/KPLC/LAN/E-DOC-S-004

TITLE : 11kV POWER CABLE SIZING CALCULATION Date : 15.10.10 Revision : R0

6.0.0 CHECKING OF STEADY STATE VOLTAGE DROP AT SWITCHGEAR TERMINAL


UNDER FULL LOAD CONDITION

6.1.0 Voltage drop from 11kV Termination end to 11kV Switchgear terminal

Voltage drop (Vd) = FLC x ((Rc.CosQr)+(Xc.SinQr)) / N

= 6.3 x ((0.01026*0.8) + (0.00315*0.6)) / 1

= 0.03 volts

= 0.000167 %

611
6.1.1 Allowed voltage drop from 11kV bus = 3 %
to station transformer as per good engineering practice.

From the above, it is seen that, the steady state voltage drop is within the limit.
Hence the proposed cable of 1runs of 1C x 70 Sq.mm XLPE Ar. Cu, is safe.

7.0.0 SUMMARY

a) Cable Selected = 11 (6/10) kV, 1 Core x 70


Sq.mm XLPE, Armoured

b) No. of runs = 1 run

c) Max. Steady State Voltage Drop (%) = 0.000167 %

Sheet 8 of 12
NATIONAL CONTRACTING CO. LTD.,
T&D Division
Kingdom Of Saudi Arabia

PROJECT : KPLC, KENYA DOC. NO: NCC/KPLC/LAN/E-DOC-S-004

TITLE : 11kV POWER CABLE SIZING CALCULATION Date : 15.10.10 Revision : R0

1.0.0 DESIGN INPUTS

1.1.0 LOAD DETAILS

1.1.1 Load Description = 11kV Feeder

1.1.2 Fed by From = 11kV Switchgear


To 11kV O/G feeder
1.2.0 INPUTS

1.2.1 11kV feeder rating (L) = 400 A


(considered the 11kV CT primary rating as Feeder rating)

122
1.2.2 Voltage rating of Switchgear (v) = 11 kV

1.2.3 Load power factor (Cos Qr) = 0.8 (Assumed)

1.2.4 Full load current (FLC) = 400 A

1.2.5 Route length of HT Switchgear cable (l) = 110 mtrs

1.2.6 Fault level (If) = 25 kA


(As per spec. cl. 3.1.1)

1.2.7 Fault current withstand time (t) = 1 sec

2.0.0 ENVIRONMENTAL DETAILS

2.1.1 Design Ambient Temperature (As per spec. cl. 3.1.1) = 40 deg C

3.0.0 CABLE DATA

3.1.1 Voltage Rating = 11 (6/10) kV

3.1.2 No. of Cores = 3

3.1.3 Cross Section Area (A) = 300 Sq.mm

3.1.4 Conductor Material = Copper

Sheet 9 of 12
NATIONAL CONTRACTING CO. LTD.,
T&D Division
Kingdom Of Saudi Arabia

PROJECT : KPLC, KENYA DOC. NO: NCC/KPLC/LAN/E-DOC-S-004

TITLE : 11kV POWER CABLE SIZING CALCULATION Date : 15.10.10 Revision : R0

3.1.5 Insulation = XLPE, Armoured

3.1.6 Catalogue Reference = PRIMECAB kables

3.1.7 Current Carrying Capacity in air (Ic) = 469 A

3.1.8 Resistance of Cable Selected at 90 deg C (r) = 0.0778 ohms/Km

3.1.9 Reactance of Cable Selected (x) = 0.085 ohms/Km

4.0.0 CHECKING OF THERMAL WITHSTAND CAPABILITY

4.1.0 Laid in Cable trench

4.1.1 Derating factor for variation in air temperature = 1


at 40 deg C

4.1.2 Group derating factor for multicore cables


= 0.88
laid in horizontol formation

4.1.3 Overall derating factor considered for the cable (df) = 1 x 0.88
= 0.88

4.1.4 Nominal current carrying capacity of cable in air (Ic) = 469 A

4.1.5 Calculation of De-rated current carrying capacity

4.1.6 Derated current carrying capacity of cable in air (Id = df x lc) = 412.72 A

Therefore, No. of runs required (N=FLC/Id) = 400 / 412.72


= 0.96918 Runs

4.1.7 No. of runs selected (N) = 1 Runs

From the above, it is seen that the thermal current carrying capacity of
1runs of 3C x 300 Sq.mm XLPE Ar. Cu cable is sufficient to carry full load
current of switchgear. Hence the proposed cable is safe.

Sheet 10 of 12
NATIONAL CONTRACTING CO. LTD.,
T&D Division
Kingdom Of Saudi Arabia

PROJECT : KPLC, KENYA DOC. NO: NCC/KPLC/LAN/E-DOC-S-004

TITLE : 11kV POWER CABLE SIZING CALCULATION Date : 15.10.10 Revision : R0

5.0.0 CHECKING OF SHORT CIRCUIT WITHSTAND CAPABILITY

k20x c x ρ 1+α20 (θe - 20oC) 0.5


A x x ln
α20 1+α20 (θb - 20oC)
Isc =
t0.5

(As per IEC 865) Part-1 Pg no 113


Where
Ar is the cross section area required in cm2
k20 = 5.60E+07 is the reciprocal of resistivity at 20oC in 1/ohm-metre
o
c = 390 is the thermal capacity per unit weight in J/(Kg C)
3
ρ = 8900 specific weight of Aluminium in Kg/m
α20 = 0.004 is the thermal coefficient of resistivityy at 20°C in 1/°C
θe = 200 is the conductor temp. at the end of short circuit in °C
θb = 85 is the conductor temp. at the beginning of short circuit in °C

56000000 x 390 x 8900 1 + 0.0039 (200 - 20) 0.5


300 x x ln
0.004 1 + 0.0039 (85 - 20)
Isc =
1 ^0.5

Isc = 37.0 kA

From the above, it is seen that 1runs of 3C x 300 Sq.mm XLPE Ar. Cu cable can
safely withstand fault level of 25kA for 3 seconds. Hence the cable selected
for fault current is safe.

Sheet 11 of 12
NATIONAL CONTRACTING CO. LTD.,
T&D Division
Kingdom Of Saudi Arabia

PROJECT : KPLC, KENYA DOC. NO: NCC/KPLC/LAN/E-DOC-S-004

TITLE : 11kV POWER CABLE SIZING CALCULATION Date : 15.10.10 Revision : R0

6.0.0 CHECKING OF STEADY STATE VOLTAGE DROP AT SWITCHGEAR TERMINAL


UNDER FULL LOAD CONDITION

6.1.0 Voltage drop from 11kV Termination end to 11kV Switchgear terminal

Voltage drop (Vd) = FLC x ((Rc.CosQr)+(Xc.SinQr)) / N

= 400 x ((0.008558*0.8) + (0.00935*0.6)) / 1

= 2.49 volts

= 0.013076 %

611
6.1.1 Allowed voltage drop from 11kV bus = 3 %
to station transformer as per good engineering practice.

From the above, it is seen that, the steady state voltage drop is within the limit.
Hence the proposed cable of 1runs of 3C x 300 Sq.mm XLPE Ar. Cu, is safe.

7.0.0 SUMMARY

a) Cable Selected = 11 (6/10) kV, 3 Core x 300


Sq.mm XLPE, Armoured

b) No. of runs = 1 run

c) Max. Steady State Voltage Drop (%) = 0.013076 %

Sheet 12 of 12