Zelio Electromechanical Relays - RHK412BA76
Zelio Electromechanical Relays - RHK412BA76
Zelio Electromechanical Relays - RHK412BA76
Main
Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Range of product Zelio Relay
Product or component type Plug-in relay
Device short name RHK
Contacts type and composition 4 C/O
Contact operation Latching
Standard
[Uc] control circuit voltage 24 V DC
[Ithe] conventional enclosed thermal 5 A at <= 40 °C
current
Status LED Without
Control type Manual control
Coil interference suppression With
Complementary
[Ui] rated insulation voltage 250 V
Operating position Any position
Minimum switching capacity 150 mVA / 1 V
150 mVA at 10 mA
Contact bounce time <= 10 ms
Voltage drop <= 100 V for 3 A at 24 V
Average resistance 30 mOhm at 20 °C
Average coil consumption 1.6 W at 20 °C on coil 1
2.9 W at 20 °C on coil 2
Control circuit voltage limits 0.8...1.1 Uc conforming to IEC 60255
Drop-out voltage threshold 0.1...0.3 Uc
Time constant 12 ms for open contact(s)
15 ms for closed contact(s)
Mechanical durability 10000000 cycles
Operating rate <= 2 cyc/mn
Operating time 1...4 ms for energisation/de-energisation
1.2...4 ms for de-energisation/energisation
10...14 ms between energisation of trip coil and closing of NC contact at 20 °C
12...22 ms between energisation of coil and closing of NO contact at 20 °C
Minimum pulse duration >= 50 ms
Jul 2, 2018
1
CAD overall width 33 mm
CAD overall height 43 mm
CAD overall depth 90 mm
Terminals description ISO n°1 (31-32-34)OC
(41-42-44)OC
(11-12-14)OC
(21-22-24)OC
(B1-B2)CO
(A1-A2)CO
Product weight 0.09 kg
Environment
Standards VDE 0435
NF C 45-250
BS 4794
IEC 255
Product certifications ASE
EDF
CSA
BV
USSR
UR
Protective treatment TC
Dielectric strength 2500 V
Ambient air temperature for operation -5...40 °C conforming to IEC 60255
Ambient air temperature for storage -40...70 °C
Vibration resistance 6 gn (f = 10...55 Hz) conforming to IEC 60068-2-6
6 gn (f = 10...55 Hz) conforming to NF C 20-616
Shock resistance 30 gn for 11 ms conforming to NF C 20-608
Contractual warranty
Warranty period 18 months